Z
SERIES
CONTROL PANEL FOR 230V OPERATORS
INSTALLATION MANUAL
ZM3E - ZM3EC
English
EN
“IMPORTANT INSTALLATION, SAFETY INSTRUCTIONS”
“CAUTION: IMPROPER INSTALLATION MAY CAUSE SERIOUS DAMAGE, FOLLOW ALL INSTALLATION INSTRUCTIONS CAREFULLY”
“THIS MANUAL IS ONLY FOR PROFESSIONAL INSTALLERS OR QUALIFIED PERSONS”
This symbol indicates sections to be read with particular care.
This symbol indicates sections concerning safety.
This symbol indicates notes to communicate to users.
2 Intended use and application
2.1 Intended use
The ZM3 control panel is designed to command the following swing-gate operators ATI, AXO, FAST, FERNI, FROG, KRONO.
The ZM3EC control panel is engineered to command CBX - F4000 industrial doors. It comes with its own safety release and buttons.
The use of this product for purposes other than as described above and installation executed in a manner other than as
instructed in this technical manual are prohibited.
2.2 Application
Make sure you respect the distances and cable diameters as shown in “cable types and minimal thicknesses” table.
The overall power of the motors must not exceed 750 W.
3 Reference Standards
For its quality processes management Came Cancelli Automatici is ISO 9001:2000 certified, and for its environmental management it is
ISO 14001 certified. Came designs and manufactures entirely in Italy.
This product complies with the following standards: see Declaration of Compliance.
4 Description
This product is engineered and manufactured by CAME cancelli automatici s.p.a. and complies with current safety regulations.
Guaranteed 24 months if not tampered with.
The control panel works on 230V a.c. of power, 50/60Hz frequency.
Both command and control devices and accessories are 24V powered. Warning! Accessories must not exceed 35 W overall.
All connections are protected by quick fuses, see table.
The input and output contact functions, the timing settings and users’ management, are set and viewed on the display, which is run by
software.
FUSES
TECHNICAL FEATURES
Power supply 230V - 50/60Hz
max. rated power 750W
Power draw when idling 85mA
Max power of 24V accessories 35W
Insulation rating II
Material ABS
Protection rating IP54
operating temperature -20 / +55°C
protection:
fuse type:
Electrolock
3.15A-F
Electronic board (power supply line)
5A-F
Accessories
1.6A-F
Control devices
630mA-F
Pag. 2 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
1 Legend of symbols
4.1 Dimensions, spans and anchoring holes
!02%
#()5$%
4.2 Main components
3
2
4
4
3
{
1
2
1 - Transformer
2 - M1 gearmotor condenser (black wires)
3 - M2 gearmotor condenser (red wires)
4 - Card fuse
5 - Accessories fuse
6 - Electrolock fuse
7 - Display
8 - Display lighting adjustment trimmer
9 - Memory roll card connector
10 - AF card connector
11 - R700 card connector
12 - Open contact error - warning LED
13 - Programming buttons
14 - Terminal board for connecting
15 - Terminal board for 230V a.c. power grid
16 - Line fuse
17 - 230V-power signalling LED
18 - STOP button
19 - CLOSE button
ZM3EC
20 - OPEN button
21 - Safety block
1
Pag. 3 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ZM3EC
ZM3C
ENGLISH
(mm)
5
6
7
17
8
9
16
15
10
14
13
12
11
#!-%
18
Warning! Before acting on the machinery, cut off the
main power supply and disconnect any emergency
batteries.
21
20
19
5 Installation
Installation must be carried out by expert qualified personnel and in full observance of regulations in force.
5.2 Tools and materials
Make sure you have all the tools and materials you will need for the installation at hand to work in total safety and compliance with the
current standards and regulations. The following figure illustrates the minimum equipment needed by the installer.
Here are some examples.
5.3 Fixing and mounting the box
1) Fix the base of the panel in a protected area; we suggest
using round top Phillips recessed head screws of max.
6mm in diameter.
2) Perforate the pre-punched holes and insert the cable
glands with the corrugated tubing for the electrical
cables to travel through.
N.B.: diameter of the pre-punched holes: 20 mm.
3) Assemble the pressure hinges.
!!
4) Insert the pressure hinges into the box (on the left or right as you
wish) and set them using the provided screws and washers.
They must slide in
order to tum
15 mm~
Pag. 4 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Before installing do the following:
• Check that the panel’s anchoring point is protected from possible blows, and that the anchoring surface is solid. Also check that the
anchoring is done using the appropriate bolts, screws etc.;
• Make sure you have a suitable omnipolar cut-off device with contacts more than 3 mm apart, and independent (sectioned off) power
supply;
•
Make sure that any connections inside the case (that provide continuance to the protective circuit) are fitted with extra insulation
as compared to the other conductive parts inside;
• Make sure you have suitable tubing and conduits for the electrical cables to pass through and be protected against mechanical
damage.
ENGLISH
5.1 Preliminary checks
5) Snap the cover into place onto the hinges. Close it and fix it
using the provided screws.
ENGLISH
Pag. 5 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
6) After the adjustments and settings, fix the cover
using the provided screws.
6 Electrical connections
6.1 Cable and type and section
Connections
Type
of cable
Length of cable
1 < 10 m
Length of cable
10 < 20 m
Length of cable
20 < 30 m
Control panel power supply
3G x 1,5 mm2
3G x 1,5 mm2
3G x 2,5 mm2
Motor power supply
3G x 1,5 mm2
3G x 1,5 mm2
3G x 2,5 mm2
2 x 1,5 mm2
2 x 1,5 mm2
2 x 1,5 mm2
2 x 0,5 mm2
2 x 0.5 mm2
2 x 0,5 mm2
4 x 0,5 mm2
4 x 0,5 mm2
4 x 0,5 mm2
Power supply to accessories
2 x 0,5 mm2
2 x 0,5 mm2
2 x 1 mm2
Control and safety devices
2 x 0,5 mm2
2 x 0,5 mm2
2 x 0,5 mm2
flashing lamp
Transmitter photocells
Receiver photocells
FROR CEI
20-22
CEI EN
50267-2-1
Encoder connection
2402C 22AWG
max. 30 m
Antenna connection
RG58
max. 10 m
N.B.: If the cable length differs from that specified in the table, then you must determine the proper cable diameter based on the actual
power draw from the connected devices and according to the CEI EN 60204-1 standards.
For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual power draw
and distances.
When connecting products that are not specified in this manual, please follow the documentation provided with said products.
6.2 Electrical connections
Power supply to accessories
Terminals for powering the following accessories:
- 24V A.C. Overall power allowed: 20W
Electrolock connection
(12V - 15W max)
+ -
Possible output of the radio
receiver’s second channel
(N.O. socket).
Socket rating: 1A-24V (D.C.).
Power supply
230V (A.C.) 50/60 Hz
,
" "
Signalling and Lighting devices
Open gate indicator-light
(socket rating: 24V - 3W max.).
Turns on when the gate is ajar or open.
It turns off when the gate is closed.
Cycle lamp: (contact rating: 230V – 60W max.)
It lights up the driving area and stays on from the
moment the gate begins to open until it is fully closed
(including the automatic closing time). If automatic
closing is not activated, the lamp stays on only during
movement or for a set time of 5 minutes if used as a
courtesy lamp.
Command devices
N.B.: insert the R700 emcoding card for the
TSP00 sensors and LT001 card readers to be
recognised.
LT001 - Magnetic card reader
TSP00 - Transponder sensor
ACCESS CONTROL
ME
Black
Red
CA
3 '.$
Stop button (N.C. contact) - Button to stop gate while
excluding the automatic closing cycle. For movement to
resume you must press the command button or transmitter
button.
N.B.: if contact is unused, select Disabled on the
“FUNCTIONS” menu.
Key selector and/or opening button (N.O. contact) Gate opening command.
Key selector and/or partial opening button (N.O.
contact) - Partial gate opening for pedestrian
access.
Key selector and/or closing button (N.O. contact) Gate closing command.
Key selector and/or commands button (N.O.
contact) - Commands for opening and closing the
gate – pressing the button or turning the keyswitch, inverts the gate’s movement or stops it
depending on how it is set on the 2-7 command in
the “FUNCTIONS” menu.
CANCELLI AUTOMATICI
R700
Antenna with RG58
cable for the remote
control.
Pag. 6 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
Signal Flasher (socket rating: 230V
- 25W max.) Flashes during opening
and closing phases.
Gearmotor, mechanical stops
M1 - 230V A.C. gearmotor featuring delayed action on opening
M2 - 230V A.C. gearmotor featuring delayed action on closing
FERNI
F7001
KRONO
KRONO
ATI
ATI
Pag. 7 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
FERNI
FROG A
F7001
&! &!
CBX
F4000
F4000
Gearmotor, encoder
ENCODER A
M1 - 230V A.C. gearmotor featuring
delayed action on opening
ENCODER B
M2 - 230V A.C. gearmotor featuring
delayed action on closing
FROG AE
FROG AE
Green
Brown
White
White
Brown
Green
F7001E
F7001E
AXO
AXO
Safety devices
DIR photocells
Configure either (N.C.) contacts CX, CY or CZ, input
for safety devices such as photocells, that comply
with EN 12978 standards. See CX, CY or CZ input
functions in:
- C1 «re-open during closing phase», When the
gate leaf is closing, opening the contact triggers the
inversion of the direction of movement until the gate
leaf is fully open.
- C2 «re-close during opening phase», When gate
is opening, if the contact is opened it triggers an
inversion of the direction until gate is fully closed;
- C3 «partial stop», Halts moving gate leaves and
causes them to automatically close (if this functions
has been selected);
- C4 «stand-by Obstacle», Halts the moving gate
leaves causing them to start moving again once
obstacle is removed.
- Deactivated, if contact is unused.
RX
RX
./ # .#
TX
DOC photocells
TX
ENGLISH
FROG A
DF
(DIR)
#
.#
(DOC)
&53)"),% M!
48 # .#
48
48
At each opening and closing command, the control board assesses the efficiency status of the control devices (photocells). Any
anomaly found is signalled with the flashing of the LED on the control panel. Consequently it cancels any commands coming from the
remote control or the button.
Electrical connection to enable the photocell safety test:
- the transmitter and the receiver, must be connected as per the diagram;
- from the functions menu, select “safety tests” and select either CX - CY - CZ input/s to activate the test.
Pag. 8 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
DF with DFI connections
monitor card
6.3 Electrical connection for the photocells functions test
./
ENGLISH
Configure either (N.C.) contacts CX, CY or CZ,
input for EN 12978 compliant safety devices such
as sensitive edges. See CX input functions in:
- C7 «Open while closing», During gate closing,
opening the contact causes inversion of movement
until gate is fully open;
- C8 «close while opening», During gate opening,
opening the contact causes inversion of movement
until gate is fully close.
- Deactivated, if contact is unused.
7 Programming
Lingua
Italiano
Pag. 9 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Þ
The ESC key is for:
- exiting the menu;
- cancelling modifications.
ß
{
The < > keys are for:
- shifting from one menu item to another;
- increase or decrease values.
{
the <...> symbols on the display are for:
-pointing out the currently, selected item
{
The ENTER key is for:
- entering the menu;
- confirming and memorising set values.
{
7.2 Browsing the menu
To enter the menu, keep the
ENTER key pressed for at least one
second.
To select a menu item,
mode using the greater
than-lesser than keys...
Þ
LANGUAGE
English
Þ
LANGUAGE
ß
English
FUNCTIONS
Þ
Þ
...then press ENTER
ß
English
TIMING ADJ.
Þ
also use the greater
than-lesser than keys
for the “sub-menus”...
ß
A.C.T.
Þ
90s
Cycle Time
ß
...then press ENTER
ß
ß
90s
Cycle Time
Þ
90s
ß
If the <> are on the TIME
function, you may modify the
value.
To increase or reduce values,
use the greater than-lesser
than keys...
...then press ENTER to confirm...
Cycle Time
Þ
100s
ß
N.B.: when the menu is active, the system cannot be used.
...to exit the menu, wait 30
seconds, or press ESC, until start
screen is displayed.
ENGLISH
7.1 Description of display commands
7.3 Menu structure
< LANGUAGE >
ENTER
>
>
< FUNCTIONS >
>
>
>
>
ENTER
See detailed functions on pages 17, 18, 19 and 20 (the “ENCODER” function, appears only if
selected from the “Config.” function in the FUNCTIONS menu.
ENTER
>
< TIMING ADJ >
ENTER
>
<
USERS
<
>
T.C.A.
>
< 0s. >
ENTER
>
ENTER
>
ENTER
< Add User >
< 300s.>
confirm? (no)
>
confirm? (yes)
< 0s. >
ENTER
>
>
>
>
ENTER
< Mod. name >
<
Cycle Time
Sel.Utente
<002:-U002->
>
< 10s. >
ENTER
>
>
>
ENTER
>
Choose User
<001:-U001->
< Op. Delay M1 >
>
>
>
>
Sel.Utente
<002:-U002->
< Cl. Delay M2 >
Choose User
<001:-U001->
>
ENTER
>
< 10s. >
< 1s. >
ENTER
>
< 150s.>
< 1s. >
ENTER
>
< 300s.>
Choose User
<001:-U001->
>
< Mod. Code >
>
>
< 60s >
>
>
>
ENTER
< 1s. >
ENTER
>
Choose User
<001:-U001->
>
>
>
< Lock time
Sel.Utente
<002:-U002->
>
>
ENTER
confirm? (no)
< Ram hit time >
>
>
>
< Backup data >
ENTER
confirm? (yes)
>
< Ped.opening >
confirm? (no)
>
>
>
>
>
< 0s. >
ENTER
>
>
>
>
< INFO >
<
>
>
>
TEST MOT.
ENTER
ESC
<
<=M1
M2=>
>
No. of Runs
16480
fw. 3.0
>
< TEST MOT.
>
< 30s.>
confirm? (yes)
< Version >
ENTER
< 60s.>
confirm? (no)
>
ENTER
>
confirm? (yes)
>
< 10s. >
< 5s. >
ENTER
>
< 5s. >
< 1s. >
ENTER
>
>
< 60s.>
< 1s. >
ENTER
>
< Remove Usr.
Sel.Utente
<002:-U002->
>
>
>
>
>
>
< Standby Msg. >
< System Reset >
>
Pag. 10 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
< ENCODER >
>
ENGLISH
>
< AutoClose >
< Turn on >
ENTER
< Disabled >
>
>
>
< Disabled >
ENTER
< Turn on >
>
>
>
>
< Turn on >
ENTER
< Disabled >
>
>
< Safety d.Test >
< Disabled >
ENTER
>
>
< Preflashing >
ENTER
< CX >
>
< CY+CZ >
>
< Turn on >
< CY >
>
>
>
< CX+CY >
< Disabled >
>
>
>
ENTER
< Turn on >
< Disabled >
>
>
>
<
< CZ >
>
< CX+CZ >
>
Total Stop
>
ENTER
>
< Turn on >
< Disabled >
>
>
<
CX Input
ENTER
>
< Disabled >
>
< C1 >
>
< C7 >
>
< C8 >
< C2 >
>
>
< C3 >
< C4 >
>
>
>
<
CY Input
>
ENTER
< Disabled >
>
>
< CZ Input >
ENTER
>
<
Cl. Thrust
>
< C2 >
>
Lock
>
< Turn on >
ENTER
>
ENTER
< Slow run >
>
endstop
< Disabled >
>
>
ENTER
<
< Fcap-RallCh >
>
N.C.
>
<
>
N.A.
>
>
>
ENTER
>
>
cmd 2-3P >
ENTER
>
< Partial >
>
>
< Courtesy >
>
>
<
>
<
lamp E3
>
ENTER
<
Cycle
>
>
ENTER
>
>
>
<
No. Motors
>
ENTER
ENTER
<
M1 + M2
>
<
-ooo+
>
•
>
<
M2
>
>
>
>
>
<
< encoder >
< Time of Run >
>
>
>
cmd 2-7
>
>
>
<
< C3 >
>
Config.
<
>
>
< Disabled >
>
>
<
< C3 >
< C4 >
>
>
<
>
< C4 >
>
< C7 >
>
< Turn on >
ENTER
< C1 >
>
< C8 >
< C2 >
>
< C7 >
>
< C8 >
< Disabled >
>
< C1 >
>
-ooo+
>
••
>
Pag. 11 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
>
>
ENGLISH
< Obstacle Det. >
7.4 Main menu
LANGUAGE
English
>
<
ENGLISH
Press ENTER
for 1 second
FUNCTIONS
>
<
ENCODER
>
It appears only if selected from the “Config.”
Section in the FUNCTIONS menu.
<
TEST MOT.
>
<
INFO
>
<
< TIMING ADJ. >
USERS
250
>
Max. 250 users
7.5 Language menu
Select language: selects among the languages displayed.
LANGUAGE
< English >
< LANGUAGE >
English
LANGUAGE
< Deutsch >
LANGUAGE
< Francais >
FUNCTIONS
TIMING
IMING ADJ.
ADJ
LANGUAGE
< Italiano >
USERS
LANGUAGE
< Espanol >
INFO
TEST MOT
MOT.
7.6 Functions menu
Automatic Closing: activates or deactivates the automatic closing function.
The automatic closing timer activates at each opening endpoint. The predetermined time may be adjusted, and is in any case
dependent on any safety devices that may activate; and it does not activate after a total safety “stop” or during a power outage.
< LANGUAGE >
English
sh
< AutoClose >
Turn on
FUNCTIONS
<
AutoClose
Turn on
>
TIMING AD
ADJ.
USERS
X2
<
AutoClose
Disabled >
INFO
TEST MOT
MOT.
Maintained action: the gate works by keeping the button pressed (button 2-3 for opening, button 2-4 for closing, or if set to the “On
Closing” function, only with button 2-4.
< LANGUAGE >
English
h
Disabled
FUNCTIONS
TIMING AD
ADJ.
USERS
INFO
TEST MOT
MOT.
X2
Maintained Act
< Disabled >
Maintained Act
<
Turn on
>
Maintained Act
< when close >
Pag. 12 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
<
Obstacle detected: when motor is stopped (gate closed or after a total stop command) it prevents any movement if safety devices,
such as photocells, detect any obstacles.
< LANGUAGE >
English
sh
X2
TIMING AD
ADJ.
Obstacle Det.
< Disabled >
X2
Obstacle Det.
< Turn on >
Pag. 13 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
USERS
INFO
TEST MOT
MOT.
Safety test: allows the card to check the efficiency of any safety devices (i.e. photocells) after every opening or closing command.
X3
< LANGUAGE >
English
sh
Disabled
Safety d.Test
< Disabled >
Safety d.Test
<
CX
>
FUNCTIONS
TIMING AD
ADJ.
USERS
INFO
Safety d.Test
< CX+CY+CZ >
Safety d.Test
<
CY
>
Safety d.Test
<
CX+CZ
>
Safety d.Test
<
CZ
>
TEST MOT
MOT.
X2
Safety d.Test
<
CX+CY
>
Pre-flashing: after an opening or closing command, the flashing light, connected to W-E, starts flashing before the gate begins its run
(to set the time, see “Pre-flashing timing” from the Adjust Timings menu
< LANGUAGE >
English
sh
X4
< Preflashing >
Disabled
FUNCTIONS
TIMING AD
ADJ.
Preflashing
< Disabled >
X2
USERS
INFO
TEST MOT
MOT.
Ram blow: before any opening run, the gate leaves will press onto the mechanical endstop for a few seconds, to help release the electrolock (to set the time, see “Starting ram timing” in the Adjust Timings menu).
< LANGUAGE >
English
X5
Disabled
FUNCTIONS
TIMING ADJ.
T
D
USERS
INFO
X2
Ram hit funct.
< Disabled >
ENGLISH
Disabled
FUNCTIONS
Total Stop: this function stops the gate and consequently excludes any automatic closing cycle; for movement to resume, you need to
use the keypad or transmitter. Insert safety device on [1-2]; Insert the safety device on [1 -2]; if unused, select “Deactivated”
< LANGUAGE >
English
X6
< Total Stop >
Turn on
TIMING
IMING ADJ.
ADJ
<
Total Stop
Turn on
>
X2
Total Stop
< Disabled >
USERS
INFO
TEST MOT.
CX input: the N.C. safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when
opening), C3 (partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for
sensitive edges) or, be deactivated. See safety devices on electrical connections.
X7
< LANGUAGE >
English
< CX Input >
Disabled
CX Input
C1
>
CX Input
< Disabled >
<
<
CX Input
C8
>
<
CX Input
C2
>
<
CX Input
C7
>
<
CX Input
C3
>
FUNCTIONS
TIMING
IMING ADJ.
ADJ
USERS
INFO
TEST MOT.
X2
<
CX Input
C4
>
CY input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges)
or, be deactivated. See safety devices on electrical connections.
X8
< LANGUAGE >
English
< CY Input >
Disabled
CY Input
< Disabled >
<
CY Input
C1
>
FUNCTIONS
TIMING
IMING ADJ.
ADJ
USERS
INFO
<
CY Input
C8
>
<
CY Input
C2
>
<
CY Input
C7
>
<
CY Input
C3
>
TEST MOT.
X2
<
CY Input
C4
>
Pag. 14 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
FUNCTIONS
CZ input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges)
or, be deactivated. See safety devices on electrical connections.
X9
< LANGUAGE >
English
< CZ Input >
Disabled
CZ Input
< Disabled >
<
CZ Input
C1
>
CZ Input
<
C8
>
<
CZ Input
C2
>
CZ Input
C7
>
<
CZ Input
C3
>
Pag. 15 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
TIMING AD
ADJ.
USERS
INFO
TEST MOT
MOT.
X2
<
<
CZ Input
C4
>
Closing thrust: at the endpoint stage during closing, the gearmotors perform a final closing-thrust of the doors for a few seconds.
< LANGUAGE >
English
h
X 10
TIMING ADJ.
T
D
Cl. Thrust.
< Disabled >
< Cl. Thrust. >
Disabled
FUNCTIONS
X2
USERS
<
Cl. Thrust.
Turn on
>
INFO
Lock: to lock the gate leaves. Required for gate leaves longer than 2.50 m.
< LANGUAGE >
English
sh
X 11
<
FUNCTIONS
TIMING ADJ.
T
D
Lock
< Disabled >
Lock
>
Disabled
X2
USERS
<
Lock
Turn on
>
INFO
Deceleration configuration: configuring decelerations when opening or closing:
- slow run: decelerations when opening and closing;
- Fcap-RallCh.: end stop when opening and deceleration when closing;
- ecoder: managing decelerations, obstacle detection and sensitivity;
(FROG-AE)
- Time of Run: timed end stop (default function);
(FROG-A, FERNI 230V, ATI 230V, FAST 230V and KRONO)
- Limit switch (endstop): opening and closing endstop.
(C-BX and F4000)
< LANGUAGE >
English
h
X 12
<
Config.
Slow run
>
<
Config.
Slow run
>
Config.
< Fcap-RallCh >
FUNCTIONS
TIMING AD
ADJ.
USERS
INFO
TEST MOT
MOT.
X2
Config.
<
Config.
Config.
encoder
>
ENGLISH
FUNCTIONS
Endstop: configure the endpoints are normally closed or open contacts.
N.B.: this function appears only if selected from the “Config.” function in the FUNCTIONS menu.
< LANGUAGE >
English
sh
X 13
<
TIMING AD
ADJ.
endstop
N.C
>
<
endstop
N.C
>
X2
USERS
endstop
N.A
<
>
INFO
TEST MOT
MOT.
Command 2-7: setting the 2-7 contact to step-by- step mode (open-close) or sequential (open-stop-close-stop).
< LANGUAGE >
English
sh
X 14
< cmd 2-7 >
Op.-Stop-Cl.
FUNCTIONS
TIMING AD
ADJ.
cmd 2-7
X2
cmd 2-7
USERS
INFO
TEST MOT
MOT.
Command 2-3P: setting the 2-3P contact to pedestrian opening (second gate leaf opens fully) or partial (second gate leaf opens
partially depending on the time set on “Partial opening” from the Adjust Times menu).
< LANGUAGE >
English
sh
X 15
< cmd 2-3P >
Pedestrian
FUNCTIONS
TIMING AD
ADJ.
cmd 2-3P
< Pedestrian >
X2
cmd 2-3P
< Partial >
USERS
INFO
TEST MOT
MOT.
E3 lamp: configuring the lamp connected to E-E3:
- cycle: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area.
It stays on from the moment the gate leaf begins to open, until it is fully closed (including automatic closing time).
In case the automatic closing function is not inserted, it stays on only during gate movement.
- courtesy: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area.
It stays on for a set time of 5 minutes.
< LANGUAGE >
English
sh
X 16
< lamp E3 >
Cycle
FUNCTIONS
TIMING AD
ADJ.
<
lamp E3
Cycle
X2
USERS
<
INFO
TEST MOT
MOT.
>
lamp E3
Courtesy
>
Pag. 16 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
FUNCTIONS
B1-B2 output: setting contact B1-B2 to MONO-STABLE or BI-STABLE (switch) mode.
< LANGUAGE >
English
X 17
TIMING AD
ADJ.
output B1-B2
Monostable
>
output B1-B2
<
X2
USERS
Pag. 17 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Monostable
<
output B1-B2
Bistable
>
INFO
TEST MOT
MOT.
Slow Down: setting the deceleration speed when opening or closing, or, only when closing if said deceleration is configured as (FcapRallCh.).
N.B.: this function only appears if the decelerations are selected.
< LANGUAGE >
English
sh
X 18
-ooo+
•
FUNCTIONS
TIMING AD
ADJ.
<
Slow Down Spd.
•
-ooo+
>
•
X2
USERS
Slow Down Spd.
-ooo+
>
••
<
INFO
TEST MOT
MOT.
Number of motors: setting the number of motors, either one or two, depending on the number of gate leaves installed on the system.
< LANGUAGE >
English
X 19
<
FUNCTIONS
TIMING AD
ADJ.
No. Motors
M1 + M2
>
<
No. Motors
M1 + M2
>
X2
USERS
<
No. Motors
M2
>
INFO
TEST MOT
MOT.
Motor Type: setting up the type of swing gate motor installed in the system.
< LANGUAGE >
English
sh
< Motor Type >
FROG
Motor Type
<
FROG
>
FUNCTIONS
Motor Type
<
AXO
>
TIMING AD
ADJ.
USERS
INFO
TEST MOT
MOT.
X2
Motor Type
<
FAST
>
ENGLISH
<
FUNCTIONS
7.7 Encoder Menu (the ENCODER menu, appears only if selected from the “Config.” function in the FUNCTIONS menu.)
N.B.: before setting the functions in the encoder menu, run the gearmotor checks to verify the proper turning direction.
Sensitivity: the obstacle detection function is activated during gate operation and deceleration.
< LANGUAGE >
FUNCTION
FUNCTIONS
ENCODER
TIMING ADJ.
T
D
Sensibility
< Turn on
>
< Sensibility >
Turn on
X2
Sensibility
Gate operation sensitivity: this adjusts the obstacle detection sensitivity during opening and closing gate operation.
N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
< LANGUAGE >
English
FUNCTION
FUNCTIONS
< Sensib. Run >
-oooooooo+
•
ENCODER
TIMING ADJ.
T
D
<
Sensib. Run
-oooooooo+
>
•
X2
USERS
<
Sensib. Run
-oooooooo+
>
••
Deceleration sensitivity: it adjusts the obstacle detection sensitivity during opening and closing gate deceleration.
N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
< LANGUAGE >
English
X2
FUNCTION
FUNCTIONS
-oooooooo+
•
ENCODER
TIMING ADJ.
T
D
Sensib. Decel.
< -oooooooo+
>
•
X2
Sensib. Decel.
< -oooooooo+
>
••
USERS
Encoder Deceleration: this activates the opening and closing deceleration starting points.
< LANGUAGE >
English
X3
FUNCTION
FUNCTIONS
< Slow run Enc >
ON
ENCODER
TIMING ADJ.
T
D
<
Slow run Enc
ON
>
X2
USERS
<
Slow run Enc
OFF
>
M1 opening deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the opening endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
< LANGUAGE >
English
sh
X4
FUNCTION
FUNCTIONS
<
ENCODER
TIMING ADJ.
T
D
USERS
M1 Slow.AP.%
10
>
<
M1 Slow.AP.%
10
>
X2
<
M1 Slow.AP.%
11
>
Pag. 18 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
English
M1 closing deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the closing endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
< LANGUAGE >
English
<
Pag. 19 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENCODER
TIMING ADJ.
T
D
M1 Slow.CH %
10
M1 Slow.CH %
10
>
>
<
X2
USERS
M1 Slow.CH %
11
>
<
INFO
M2 opening deceleration%: this adjusts the (M2) second motor’s deceleration starting point before the opening endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
< LANGUAGE >
English
X6
FUNCTION
FUNCTIONS
<
ENCODER
TIMING ADJ.
T
D
M2 Slow.AP %
10
>
<
M2 Slow.AP %
10
>
X2
USERS
<
M2 Slow.AP %
11
>
INFO
M2 closing deceleration %: this adjusts the (M2) second motor’s deceleration starting point before the closing endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
< LANGUAGE >
English
sh
X7
FUNCTION
FUNCTIONS
<
ENCODER
TIMING ADJ.
T
D
M2 Slow.CH %
10
>
<
M2 Slow.CH %
10
>
X2
USERS
<
M2 Slow.CH %
11
>
INFO
M1 closing acceleration %: this adjusts the (M1) first motor’s percentage rate of approach to the final closing and opening points
before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See
illustration on page 28.
< LANGUAGE >
English
X8
FUNCTION
FUNCTIONS
<
ENCODER
TIMING ADJ.
T
D
USERS
INFO
M1 Appr.CH %
5
>
<
M1 Appr.CH %
5
>
X2
<
M1 Appr.CH %
6
>
ENGLISH
X5
FUNCTION
FUNCTIONS
M2 closing acceleration %: this adjusts the (M2) second motor’s percentage rate of approach to the final closing and opening points
before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See
illustration on page 28.
< LANGUAGE >
English
X8
<
ENCODER
TIMING AD
ADJ.
M2 Appr.CH %
5
>
<
M2 Appr.CH %
5
>
X2
USERS
<
M2 Appr.CH %
6
>
INFO
TEST MOT
MOT.
X9
< LANGUAGE >
English
< Set Encoder >
Set Encoder
FUNCTION
FUNCTIONS
ENCODER
X2
TIMING AD
ADJ.
Set Encoder
USERS
INFO
See detailed
description on
page 28
TEST MOT
MOT.
7.8 Time setting menu
Automatic closing: to set the waiting time when gate is in the open position.
Once this time is elapsed, the gate closes automatically. The waiting time can be set to between 0” and 300”.
< LANGUAGE >
English
h
FUNCTION
FUNCTIONS
<
TIMING ADJ.
USERS
A.C.T.
10s.
>
<
A.C.T.
10s.
>
X2
INFO
<
A.C.T.
11s.
>
TEST MOT
MOT.
Automatic Pedestrian Closing: waiting time of the (M2) second gate leaf when in the open position. Once this time interval has
elapsed, the gate automatically closes. The waiting time interval can go anywhere from 0” to 300”.
< LANGUAGE >
English
h
FUNCTION
FUNCTIONS
10s.
TIMING ADJ.
USERS
INFO
TEST MOT
MOT.
Pedestrian ACT
<
10s.
>
X2
Pedestrian ACT
<
11s.
>
Pag. 20 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
FUNCTION
FUNCTIONS
Cycle time: the working time of the motor during opening or closing phases is anywhere from 10” to 150”.
< LANGUAGE >
English
< Cycle Time >
90s.
TIMING ADJ.
Pag. 21 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
USERS
<
Cycle Time
90s.
>
X2
INFO
<
Cycle Time
91s.
>
TEST MOT
MOT.
M1 delayed opening: the waiting time of the (M1) first gate lead, unlike the (M2) second one, after each opening command. The
waiting time can be set to between 0” and 10”.
< LANGUAGE >
English
X3
FUNCTION
FUNCTIONS
<
TIMING ADJ.
USERS
Op. Delay M1
2s
>
<
Op. Delay M1
2s
>
X2
INFO
<
Op. Delay M1
3s
>
TEST MOT
MOT.
M2 delayed closing: the waiting time of the (M2) second gate leaf, unlike the (M1) first one, after each closing command. the waiting
time can be set to between 0” and 60”.
< LANGUAGE >
English
X4
FUNCTION
FUNCTIONS
<
TIMING ADJ.
USERS
Cl. Delay M2
2s
>
<
Cl. Delay M2
2s
>
X2
INFO
<
Cl. Delay M2
3s
>
TEST MOT
MOT.
Pre-flashing time: after an opening or closing command is given, the flasher connected to “W-E), flashes for between 1” and 60”,
before the gate begins to move.
< LANGUAGE >
English
X5
FUNCTION
FUNCTIONS
5s.
TIMING ADJ.
USERS
INFO
TEST MOT
MOT.
Preflashing T.
<
5s.
>
X2
Preflashing T.
<
6s.
>
ENGLISH
X2
FUNCTION
FUNCTIONS
Lock time: the time required for releasing the electro-lock after each opening command. The time of operation can be set to between
1” and 5”.
< LANGUAGE >
English
X6
<
ENGLISH
TIMING ADJ.
USERS
Lock time
2s.
>
<
Lock time
2s.
X2
INFO
<
>
Lock time
3s.
>
TEST MOT
MOT.
Ram hit time: the gearmotor’s thrust time when fully closing after each opening command. The thrust time can be set to between 1”
and 10”.
< LANGUAGE >
English
FUNCTION
FUNCTIONS
X7
<
TIMING ADJ.
Ram hit time
2s.
>
<
Ram hit time
2s.
>
USERS
X2
INFO
<
Ram hit time
3s.
>
TEST MOT
MOT.
Partial opening: the opening time of the (M2) second gate leaf. The time can be set to between 5” and 60”.
< LANGUAGE >
English
X8
FUNCTION
FUNCTIONS
< Ped. opening >
5s.
TIMING ADJ.
USERS
<
Ped. opening
5s.
>
X2
INFO
<
Ped. opening
6s.
>
TEST MOT
MOT.
Slow down time: the gate leaf’s deceleration time before every endpoint. The time can be set to between 0” and 30”.
N.B.: this function only appears if the decelerations are selected.
< LANGUAGE
LANGUAG >
English
h
X9
FUNCTION
FUNCTIONS
NS
< Slow down time >
5s.
TIMING ADJ.
USERS
INFO
TEST
EST MOT.
MO
Slow down time
<
5s.
>
X2
Slow down time
<
6s.
>
Pag. 22 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
FUNCTION
FUNCTIONS
7.9 Users Radio Menu
Add User: to create a new user and assigned function (max. 250 users).
< LANGUAGE >
Add User
< Add User >
English
TIMING AD
ADJ.
ENGLISH
Pag. 23 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
FUNCTION
FUNCTIONS
X2
USERS
Add User
INFO
See detailed
description on
page 26
TEST MOT
MOT.
Mod. Name: to change a user number or existing name to another name.
< LANGUAGE >
English
Choose User
001:--001--
< Mod. name >
<
>
FUNCTION
FUNCTIONS
TIMING AD
ADJ.
X2
USERS
Choose User
002:--002--
<
INFO
>
See detailed
description on
page 26
TEST MOT
MOT.
Mod. Code: to change a user’s current code.
< LANGUAGE >
English
X2
<
Mod. Code
>
<
Choose User
001:--001--
>
FUNCTION
FUNCTIONS
TIMING AD
ADJ.
X2
USERS
Choose User
002:--002--
<
>
INFO
See detailed
description on
page 27
TEST MOT
MOT.
Related Function: to change the function assigned to the user.
< LANGUAGE >
English
X3
< Related Func >
<
Choose User
001:--001-- >
FUNCTION
FUNCTIONS
TIMING AD
ADJ.
USERS
INFO
TEST MOT
MOT.
X2
<
Choose User
002:--002--
>
See detailed
description on
page 27
Remove user: to remove an exisiting user. Confirm the use you wish to remove with the ENTER key.
X4
< LANGUAGE >
English
< Remove Usr. >
Choose User
< 001:--001-- >
FUNCTIONS
USERS
Remove Usr.
INFO
TEST MOT.
Remove Usr.
Delete all user: to cancel all registered users. Confirm cancellation of all users with ENTER.
< LANGUAGE >
English
X5
FUNCTIONS
Delete all Usr
X2
TIMING
IMING ADJ.
ADJ
USERS
Delete all Usr
INFO
TEST MOT.
Backup data: to save the users in the memory roll. Confirm saving of users on the memory roll with ENTER.
X6
< LANGUAGE >
English
< Backup data >
Backup data
FUNCTIONS
TIMING
IMING ADJ.
ADJ
X2
Backup data
USERS
INFO
TEST MOT.
Backup data
WRITE:250
Restore backup: to load the data saved on the memory roll onto card.
X7
< LANGUAGE
ANGUAG >
English
h
FUNCTIONS
TIMING
IMING ADJ.
ADJ
X2
Restore backup
Restore backup
USERS
INFO
TEST MOT
MOT.
Restore backup
READ:250
Pag. 24 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
Choose User
< 002:--002-- >
X2
TIMING
IMING ADJ.
ADJ
7.10 nfo Menu
<
Version
fw : 3.0
< No. of Runs >
10
>
FUNCTION
FUNCTIONS
<
< System Reset >
TIMING AD
ADJ.
Standby Msg.
>
USERS
-
INFO
WWW.CAME.IT
ZM3E
TEST MOT
MOT.
7.11 Motor test menu
TEST MOT.: Test to check the proper direction of the gearmotors.
< LANGUAGE >
English
sh
FUNCTION
FUNCTIONS
Gate leaf opening
run of the first (M1)
gearmotor. If the
direction is wrong,
invert the motor’s
phases.
TIMING AD
ADJ.
USERS
INFO
<
TEST MOT.
<=M1
M2=>
Gate leaf opening run
of the second (M2)
gearmotor. If the
direction is wrong,
invert the motor’s
phases.
>
TEST MOT.
7.12 Decoding card
Connect the required (R700, AF43S cards) to insert, change, remove and command the operator via transmitter, card or transponder.
Insert the memory roll to save and load all setting including users registered by another card.
TAM
AF Card
CAM
E
TFM
Þ
Lingua
Italiano
ATOMO
ß
E
CAM
TOP
TWIN
TOUCH
Frequency/MHz
ACCESS CONTROL
Pag. 25 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
< LANGUAGE >
English
sh
ENGLISH
Version: to view software version.
Number of gate runs: to view the number of runs performed by the gate.
Starting Mssg: to view the starting message, confirm with ENTER to change text. Use the ENTER key to move the cursor forward, ESC
to move it backwards and <> to select the letter of number. Confirm the text by pressing the ENTER key for a few seconds.
System reset: it resets the system to its original settings. Press ENTER key to confirm.
CANCELLI AUTOMATICI
LT001
Memory roll
Transmitter
FM 26.995
AF130
TFM
FM 30.900
AF150
TFM
AM 26.995
AF26
TOP
AM 30.900
AF30
TOP
AM 433.92
AF43S
TAM / TOP
ATOMO / TWIN
AM 433.92
AF43TW
TWIN
AM 40.685
AF40
TOUCH
AM 868.35
AF868
TOP
R700
R700 Card
TSP00
Card
1) From the Users
menu, select “Add
User”.
Press ENTER to
confirm.
3) Choose which
function to assign to
the user....
Þ
Add User
ß
Related Func.
Þ
2-7
ß
2) Select “ confirm
(yes)” and press
ENTER key to confirm.
Add User
Þ confirm? (yes) ß
4) .... will ask to input
a code. Send the
code with the radiocommand button or
slide-through card or
transponder.
Waiting Code
>>>>
ACCESS CONTROL
5) ... once the code
is inputted, the user
name will come up
showing the type of
command that was
memorised...
--001--
... or if the code is
already inputted,
“Existing Code” will
appear.
radio
Code exist
001:--001--
7.14 Changing users
1) From the Users
menu, choose
“Mod. name”.
Press ENTER to
confirm.
3) Use the ENTER
key to move the
cursor forward, ESC
to move it backwards
and < > to select the
letter or number.
Þ
Mod. name
Mod. name
--001--
ß
2) Choose the user
number or name you
wish to change the
text of and press
ENTER to confirm.
4) Confirm the text by
pressing the ENTER key
for a few seconds.
Choose User
Þ
001:--U001--
Mod. name
JOHN
ß
Pag. 26 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
7.13 Inputting users
7.15 Changing code
Mod. Code
Choose User
3) .... you will be
asked to input a
code. Send the code
using the transmitter
button or the slide through card or the
transponder.
Waiting Code
4) .. once the code
is inputted, the user
name will come up
showing the type of
command that was
memorised...
>>>>
ENGLISH
2) Choose the user
Þ 001:--U001-- ß
name for which you
Choose User
wish to change the
Þ 002:--U002-- ß
code and press ENTER
to confirm.
--002-radio
ACCESS CONTROL
Pag. 27 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
1) From the Users
menu, choose
“Mod. Code”.
Press ENTER to
confirm.
5) Select “ confirm (yes)”
and press ENTER key to
confirm.
Mod. Code
Þ
confirm? (yes)
7.16 Function assigned to the user
1) From the Users
menu, choose
“Related Fuc.”.
Press ENTER to
confirm.
3) Choose the new
function to assign
to the user. Press
ENTER to confirm.
Þ
Related Func.
2) Choose the user
name fo which you
wish to change the
command function
and press ENTER to
confirm.
ß
Choose User
Þ
001:--U001-Choose User
Þ
ß
002:--U002--
ß
Related Func.
Þ
2-7
Related Func.
Þ
open
ß
ß
4) Choose “confirm
(yes)” and press
ENTER to confirm.
Related Func.
Þ confirm? (yes) ß
ß
7.17 Gate run calibration
1) From the Encoder
menu, select “Set
Encoder”. Press ENTER
to confirm.
Þ
Set Encoder
2) Select “confirm
(yes) and press ENTER
to confirm.
ß
Set Encoder
Þ
confirm? (no)
Set Encoder
ß
< confirm? (yes) >
3) the gate leaf of the
first motor will perform
a closing run until fully
closed.....
Set Encoder
Close 1
0
0
5) …then, the gate leaf
of the second motor, will
perform and opening run
until fully open…
4) …then, the
gate leaf of the
second motor will
perform the same
manoeuvre…
Set Encoder
Close 2
0
0
Set Encoder
Open 2
0
0
7) When the procedure is
finished, the display will show
“Set Encoder ok” for a few
seconds.
6) ...after which,
the gate leaf of
the first motor will
perform the same
manoeuvre…
Set Encoder
Open 1
0
Set Encoder
OK
7.18 Error messages
-“encoder ERROR”: check proper connections or functionality of the device and possibly even the motor’s torque”
-“safety d. test ERROR”: malfunctioning of safety devices, check proper functioning of connections and functionalities;
-“end stop ERROR”: check proper connections on end point connections or functionality of devices;
-“cycle time ERROR”: check the working time settings, the set time may be insufficient to complete the duty cycle.
- Safety STOP, C1, C3, C4”: check proper functioning of connections and functionalities of devices.
0
Pag. 28 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENGLISH
N.B. before calibrating the gate run, check that the manoeuvring area is free of any obstacles and check the proper direction of rotation of the
gearmotors. (para. 7.11)
7.19 Illustration depicting the areas and points of deceleration and final opening and closing approaches per encoder device.
A = Area of movement at normal speed
B* = Run zone at decelerated speed
C = Encoder intervention zone with
movement inversion
D= Encoder intervention zone with
movement stop
E = Opening deceleration beginning point
(M1 Open Deceler %)
F = Closing deceleration beginning point
(M1 Close Deceler %)
G = Opening deceleration beginning point
(M2 Open Deceler %)
H = Closing deceleration beginning point
(M2 Close Deceler %)
I** = Closing and opening final phase
beginning point (M1 Final Close %)
L** = Closing and opening final phase
beginning point (M2 Final Close %)
M= endstops
M
D
D
0
0
B
A
I
L
B
A
F H
C
ENGLISH
Pag. 29 - Manual code: 319U75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Note: the areas and points of deceleration and final opening and closing approaches are tested according to the parameters set forth by
Technical Norms EN12445 and EN12453 regarding compatibility of impact forces generated by moving gate leaves.
C
B
B
D
D
E
G
M
L
I
* Minimum 600 mm from the Final full stop.
**Set the function’s final phase % “M1 Final Close” for the first (M1) mtors and “M2 Final Close” for the second (M2) motor from the
“ENCODER” menu so as to obtain a distance of between 1 and 50 mm maximum from the final full stop.
8 Demolition and disposal
In its premises, CAME CANCELLI AUTOMATICI S.p.A. implements an Environmental Management System certified in
compliance with the UNI EN ISO 14001 standard to ensure environmental protection.
Please continue our efforts to protect the environment—which CAME considers one of the cardinal elements in the development of its
operational and market strategies—simply by observing brief recommendations as regards disposal:
DISPOSAL OF PACKAGING
The packaging components (cardboard, plastic, etc.) are all classifiable as solid urban waste products and may be disposed of easily,
keeping in mind recycling possibilities.
Prior to disposal, it is always advisable to check specific regulations in force in the place of installation.
PLEASE DISPOSE OF PROPERLY!
PRODUCT DISPOSAL
Our products are made up of various types of materials. Most of them (aluminium, plastics, iron, electrical wires, etc.) may be disposed
of in normal garbage collection bins and can be recycled by disposing of in specific recyclable material collection bins and disposal in
authorized centres. Other components (electrical boards, remote control batteries, etc.), however, may contain polluting substances.
They should therefore be removed and given to qualified service companies for proper disposal.
Prior to disposal, it is always advisable to check specific regulations in force in the place of disposal.
PLEASE DISPOSE OF PROPERLY!
9 Manufacturer’s warranty
MANUFACTURER’S DECLARATION OF CONFORMITY
Pursuant to the Low Voltage Directive 2006/95/EC
CAME Cancelli Automatici S.p.A.
via Martiri della Libertà, 15
31030 Dosson di Casier - Treviso - ITALY
tel (+39) 0422 4940 - fax (+39) 0422 4941
internet: www.came.it - e-mail: info@came.it
IMPORTANT WARNING!
Do not use the equipment specified here above, before
completing the full installation
In full compliance with the Machinery Directive 98/37/EC
Declares under its own responsibility that the equipments for automatic garage doors and gates listed below:
ZM3E - ZM3EC
… comply with the National Law related to the following European Directives and to the applicable parts of the
following Standards.
2006/95/EC
2004/108/EC
EN 60335-1
EN 13241-1
LOW VOLTAGE DIRECTIVE
ELECTROMAGNETIC COMPATIBILITY DIRECTIVE
EN 61000-6-2
EN 61000-6-3
Reference code to request a true copy of the original: DDF L EN Z002e
MANGING DIRECTOR
Mr. Andrea Menuzzo
M
English - Manual code: 119EU75 ver. 2.0 01/2009 © CAME cancelli automatici s.p.a.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
CAME France S.a.
7, Rue Des Haras
Z.i. Des Hautes Patures
92737 Nanterre Cedex - FRANCE
(+33) 1 46 13 05 05
(+33) 1 46 13 05 00
CAME Gmbh Seefeld
Akazienstrasse, 9
16356 Seefeld
Bei Berlin - DEUTSCHLAND
(+49) 33 3988390
(+49) 33 39883985
CAME Automatismes S.a.
3, Rue Odette Jasse
13015 Marseille - FRANCE
(+33) 4 95 06 33 70
(+33) 4 91 60 69 05
CAME Gmbh
Kornwestheimer Str. 37
70825 Korntal
Munchingen Bei Stuttgart - DEUTSCHLAND
(+49) 71 5037830
(+49) 71 50378383
CAME Automatismos S.a.
C/juan De Mariana, N. 17-local
28045 Madrid - SPAIN
(+34) 91 52 85 009
(+34) 91 46 85 442
CAME Americas Automation Llc
1560 Sawgrass Corporate Pkwy, 4th Floor
Sunrise, FL 33323 - U.S.A
Sunrise
(+1) 305 433 3307
(+1) 305 396 3331
CAME Automatismos Catalunya S.a.
P.i. Moli Dels Frares N. 23 C/a
08620 Sant Vicenc Del Horts - SPAIN
(+34) 93 65 67 694
(+34) 93 67 24 505
Paf - CAME
Estrada Nacional 249-4 Ao Km 4,35
Cabra Figa - Trajouce
2635-047 Rio De Mouro - PORTUGAL
(+351) 219 257 471
(+35) 219 257 485
CAME United Kingdom Ltd.
Unit 3 Orchard Business Park
Town Street, Sandiacre
Nottingham - Ng10 5du - UNITED KINGDOM
(+44) 115 9210430
(+44) 115 9210431
CAME Belgium Sprl
Zoning Ouest 7
7860 Lessines - BELGIUM
(+32) 68 333014
(+32) 68 338019
CAME Cancelli Automatici S.p.a.
Via Martiri Della Libertà, 15
31030 Dosson Di Casier (Tv)
(+39) 0422 4940
(+39) 0422 4941
Informazioni Commerciali 800 848095
www.came.it
CAME Service Italia S.r.l.
Via Della Pace, 28
31030 Dosson Di Casier (Tv)
(+39) 0422 383532
(+39) 0422 490044
Assistenza Tecnica 800 295830
CAME Middle East Fzco
Po Box 17131 Warehouse N. Be02
South Zone - Jebel Ali Free Zone - Dubai - U.A.E.
(+971) 4 8860046
(+971) 4 8860048
CAME Polska Sp.Zo.o
Ul. Ordona 1
01-237 Warszawa - POLAND
(+48) 22 8365076
(+48) 22 8363296
S.c. CAME Romania S.r.l.
B-dul Mihai Eminescu, Nr. 2, Bloc R2
Scara A, Parter, Ap. 3
Buftea, Judet Ilfov Bucarest - ROMANIA
(+40) 21 3007344
(+40) 21 3007344
CAME Russia
Leningradskij Prospekt, Dom 80
Pod’ezd 3, office 608
125190, Moskva - RUSSIA
(+7) 495 937 33 07
(+7) 495 937 33 08
CAME Nord s.r.l.
Piazza Castello, 16
20093 Cologno Monzese (MI)
(+39) 02 26708293
(+39) 02 25490288
CAME Sud s.r.l.
Via F. Imparato, 198
Cm2 Lotto A/7
80146 Napoli
(+39) 081 7524455
(+39) 081 7529109
Source Exif Data:
File Type : PDF
File Type Extension : pdf
MIME Type : application/pdf
PDF Version : 1.4
Linearized : Yes
XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Format : application/pdf
Title : ZM3E_319U75_V2.0_multi.indd
Creator : mviviani
Create Date : 2009:02:03 11:02:45+01:00
Creator Tool : PScript5.dll Version 5.2
Modify Date : 2009:02:03 11:02:45+01:00
Producer : Acrobat Distiller 8.0.0 (Windows)
Document ID : uuid:01c9a9ea-888a-49c4-945c-61b643a93b1c
Instance ID : uuid:8008bb0b-3ab0-464a-bd0c-d00c5ffbd704
Page Count : 30
Author : mviviani
EXIF Metadata provided by EXIF.tools