Connector Installation Guide
Compression and Mechanical
Connectors

Typical Cross Section of a
Compression Connector Before
Installation
Before compression, a
typical cross section of
cable consists of 75%
metal and 25% air

Typical Cross Section of a
Compression Connector After
Installation
After compression, little air is left.

Compression
Connector Types

1 - 2 hole lug

Single & Dual

Narrow Tongue

Flared-End

C-Taps

Mounting holes

Splices

H-Taps

Grid Grounding

1. Determine Proper Connector For Cable
• Conductor size and CU = Copper conductors only
• Conductor size and “AL9” = Aluminum conductors only
• Conductor size and “AL9CU” = Aluminum or Copper
conductors
• Match size and type of conductor to proper lug
Note: Consult manufacturers instructions on whether fine stranded conductors
or welding cable conductor types may be used.

Marking Information on Connectors:
• Manufacturer
• Wire Size
• Wire material- CU, AL, or AL9CU (indicates
Dual Rating and 90° C)
• Optional Crimp Indicator Bands
• Listing Information

2. Strip and Properly Prepare Cable
• Strip insulation carefully to avoid nicking strands.
• Strip to proper length so conductor can be fully inserted.
• Refer to manufacturer’s instructions for strip length.
• Most connectors are suitable for one conductor. Never
install more than one conductor unless specifically
allowed by the manufacturer’s instructions.
Aluminum Conductor –

• Brush the stripped portion of the conductor to
remove oxide film using a stainless steel wire brush.
• Apply oxide inhibitor compound and wire brush into
the stranding. Do not remove pre-filled inhibitor from
the barrel.

Installation Guide for
Compression

3. Select proper installing die tool
•
•
•
•

Always refer to the connector manufacturer’s instructions for the
proper compression die that is intended for the connector.
Manufacturer’s may use colored bands or dots that correspond
to color markings on dies.
Manufacturer’s may use die code number marked or stamped on
the connector.
Knurls may be used in place of colored bands.

1st Crimps
2nd Crimps

4. Locate tool with correct die in proper position on connector
and activate tool
• Connectors that are banded with colored stripes to indicate
number and location of each crimp.
• Connectors may also be marked with the die code number at
each compression location.
• Follow manufacturers instructions whether to crimp on the
colored bands or between the colored bands.

4. Continued….
When crimped, the die code number or other marking will be
embossed on connector for easy inspection to determine if
correct die and connector combination were used.

Dieless Tools

Select proper installing dieless tool
•

Crimp as directed by the manufacturer’s instructions.

5. Connector Securement

Use a 2-hole connector if there is a
concern for twisting the connection.

Installation Guide
for Mechanical

Mechanical
Connector Types

Double
Conductor
Lug

Double
Conductor
Lug, NEMA
Pad

Single
Conductor
Lug

Copper
Single
Conductor
Lug

Overhead
Transformer

Stud Type Transformer

Marking Information on Connectors:
•
•
•
•
•
•

Manufacturer’s name or Symbol
Wire Size or range
Wire material- CU, AL, or Both
Temperature Rating if applicable
AL9CU Shows Dual Rating (Al & Cu) and 90°C
UL and/or CSA if it is a listed connector

1.

Unlike Compression connectors, mechanical connectors
typically take a range of conductors. It is important to check
that the cable falls within the cable range listed on the
connector.

2.

If the connector is intended to be used on a bus, pad or
equipment, mount the connector and tighten the mounting
hardware per the manufacturer’s specifications.

3.Strip and Properly Prepare Cable
• Strip insulation carefully to avoid nicking strands
• Strip to proper length so conductors can be fully
inserted
• Refer to manufacturers instructions for strip length
• Aluminum Conductor –
• Brush the stripped portion of the conductor to
remove oxide film with a stainless steel wire brush.
Apply oxide inhibitor compound and wire brush into
the stranding

4. Insert the conductor(s) and tighten all set screws per the
manufacturer’s recommendations.
• Do not retighten after properly torqued.
• Most connectors are suitable for one conductor. Never
install more than one conductor unless specifically
allowed by the manufacturers instructions.
• Use the mounting bolt size as recommended by the
manufacturer.

Split Bolts

• Generally used as taps.
• If conductors are different materials, a spacer bar
is included. Aluminum conductor should always be
positioned on top.

•
•
•
•
•
•

Voltage Rating (Insulated Only)
300 volts
600 volts
1000 volts signs/luminaires
Note: NOT MARKED
Non-insulated listed connectors are suitable for
2,000 volts. They may be used over 2,000 volts up
to 35,000 volts where the effects of corona have
been investigated.

• Non-insulated Temperature Rating
• 75°C - Use the connector at 75°C ampacity
• 90°C - Use the connector at 90°C ampacity
• Higher temp rated conductors at higher ambient
temperatures may be used as long as the ampacity
levels are used per the connector rating.
• Use the NEC® to obtain the conductor ampacity ratings.

• Insulated Temperature Rating
– Never exceed the temperature rating of
an insulated connector. See Packaging
or Product for the marking.

Conductor Material
–
–
–
–

AL 9
AL9CU CU9AL
AL7
AL7CU CU7AL

AL9CU

Aluminum
90°C
Aluminum/Copper 90°C
Aluminum
75°C
Aluminum/Copper 75°C

Installation Guide
for Grounding

• Grounding
• DB Direct Burial
• The connector is suitable for
direct burial in the soil or
embedded in concrete.

DB = Direct Burial

Suitable Conductor

Compression Die Information

Rod size Information

Grounding Connections

Look for the product markings for suitability for
attachment to rods, pipe, and concrete encased
reinforcement steel.

Rod size

Conductor size

Direct burial

Conductor size

Rebar size

Suggested Ways to
Load or Balance

Improper Way to
Load or Balance

X

Incorrect application

Typical Failure Modes
in Sealed Connectors

Fully
inserted

Angled Cut
1. Incorrect

Straight Cut
Correct

2. Not fully inserted

3. Straight Cut
on end of wire

Screw
Plugs

Wire
Plugs

4. Missing wire plugs or
screw plugs

5. Correct
insulation
strip length

Safety Standards
Wire Connectors
• UL 486A-486B
• CSA C22.2 No. 65
• ANCE NMX-J-543
• ANSI C119.1, C119.4,
C119.5, C119.6
Splicing Wire Connectors
• UL 486C
• CSA C22.2 No. 188
• ANCE NMX-J-548
Grounding and Bonding Equipment
• UL 467
• CSA C22.2 No. 41
• ANCE NMX-J-567



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 34
Language                        : en-US
Tagged PDF                      : Yes
Title                           : PowerPoint Presentation
Author                          : Beth Kaiser
Create Date                     : 2016:02:03 13:50:39-05:00
Modify Date                     : 2016:02:03 13:50:39-05:00
Producer                        : Microsoft® PowerPoint® 2010
Creator                         : Microsoft® PowerPoint® 2010
EXIF Metadata provided by EXIF.tools

Navigation menu