DRTS 6 _GB DATA SHEET
ISA-DRTS-6-Data-Sheet-Brochure ISA-DRTS-6-Data-Sheet-Brochure
User Manual: DRTS-6-DATA-SHEET
Open the PDF directly: View PDF .
Page Count: 11
DRTS 6
Advanced Relays, Energy Meters and Transducers Test Set
APPLICATION
• Multi-tasking test set designed for testing
protection relays, energy meters, transducers.
• Powerful and lightweight.
• High accuracy: better than 0.1% (standard);
HP model better than 0,05%.
• IEC61850 Protocol interface.
• Up to 9 current and 6 voltage outputs plus
auxiliary DC supply (option).
•
Laptop PC or PDA control.
• USB and RS232 interfaces.
• Advanced testing and data management
software TDMS.
• Complete library of relays from the major
manufacturers.
• Highest quality, safety and reliability.
• Worldwide high quality technical support in
100 countries.
DRTS 6 can test all the following relays
RELAY TYPE IEEE NO
Distance relay 21
Synchronizing device 25
Under/over-voltage relay 27/59
Directional Power relay 32
Field relay 40
Reverse phase current relay 46
Phase sequence voltage relay 47
Incomplete sequence relay 48
Instantaneous over-current relay 50
Inverse time over-current relay 51
Power factor relay 55
Voltage balance relay 60
Ground detector relay 64
Directional over-current relay 67
Phase angle out of step relay 78
Automatic reclosing relay 79
Frequency relay 81
Pilot wire receiver relay 85
Lockout relay 86
Differential protection relay 87
Voltage directional relay 91
Power directional relay 92
Tripping relay 94
DRTS 6
2
. Waveform resolution: 28 bit.
. Capable of stepping or ramping the voltage.
. Rate of change programmable between ± 0.001 V/s and
± 999 V/s.
. Voltage accuracy: ± 0.05% typical, ± 0.1% guaranteed.
. Distortion: 0.1%.
. Automatic protection for overloads, counter-feed and short
circuit.
. The fourth voltage output can be selected to act as:
.. Fourth voltage output V4 (AC/DC);
.. Zero-sequence component
VO = (V1+V2+V3)/3 or VO = (V1+V2 +V3)/1.73.
Battery simulator
Output voltage: 0…260 V DC, program controlled.
Power: 100 W or 2 A; continuous duty.
Accuracy: ± 1%.
Automatic protection for overloads.
Step or ramp control.
Angles
Phase angle range: 0° - 360°.
Angle resolution: 0.01°.
Angle accuracy: ± 0.1°.
Step or ramp control with a rate of change between
± 0.1°/s and 999°/s.
Output frequency
Frequency range: from DC (0 Hz) to 2000 Hz. Transient 5 kHz.
Capable of generating different frequencies on any output.
Maximum frequency error: 25 µHz (0.5 ppm).
Resolution: 0.1 mHz.
Possibility of slewing the frequency, with a slope from 0.001
Hz/s to 999.999 Hz/s. Resolution: 0.001 Hz/s.
Capable of generating waveform with superimposed harmonic
distortion.
Binary inputs
10 binary inputs clean or with voltage from 24 to 425 V AC
and 4.5 to 600 V DC, separated in two groups of 5, with two
common points isolated at 1 kV AC.
Selection of the type of input: Voltage clean; 5 - 24 - 48 - 100
V; software controlled.
Selection of the input debounce duration, from 0 us to
2 ms, in 64 steps of 32 us each, program controlled.
Timer range: 0 - 999,999.9999 s (277 hours) or, in cycles:
CURRENT POWER ZMAX RESOLUTION
A VA Ohm
6 X 0...15 80 0.35 1 mA
6 X 0...1.5 0.35 0.1 mA
6 X 0...0.15 0.35 0.1 mA
3 X 0...15 100 0.44 1 mA
3 X 0...1.5 0.44 0.1 mA
3 X 0...0.15 0.44 0.1 mA
3 X 0...30 160 0.18 2 mA
3 X 0...3 0.18 0.2 mA
3 X 0...0.3 0.18 0.2 mA
3 X 0...15 160 0.71 1 mA
2 X 0...45 240 0.12 3 mA
1 X 0...90 480 0.06 6 mA
1 X 0...30 320 0.35 2 mA
DRTS 6 SPECIFICATIONS
Six phase AC/DC current outputs
AC/DC current outputs
. Six independent current sources with a common neutral.
. Independent adjustment of current outputs.
. Duty cycle: at 20°C ambient temperature: 3*15 A continuous;
6*7.5 A continuous; 6*15 A 3 minutes.
. Waveform resolution: 28 bit.
. Capable of stepping or ramping the current.
. Rate of change programmable between ± 0.001 A/s and ±
999 A/s.
. Output accuracy: ± 0.05% typical, ± 0.1% guaranteed.
. Distortion: 0.1%.
. Automatic protection for overloads and open circuit.
Four phase AC/DC voltage outputs
AC/DC voltage outputs
VOLTAGE POWER ZMAX RESOLUTION
V VA Ohm
4 X 0...300 85 1125 4.6 mV
3 X 0...300 100 900 4.6 mV
3 X 0...125 100 160 1.9 mV
3 X 0...12.5 10 160 190 µV
1 X 0...600 200 1800 9.2 mV
1 X 0...300 200 450 4.6 mV
. Four independent voltage sources, with a common neutral.
. Independent adjustment of voltage outputs.
. Duty cycle: continuous.
3
DRTS 6 RELAYS, ENERGY METERS AND TRANSDUCERS TEST SET
0 - 50,000,000 cycles (50 Hz);
0 - 60,000,000 cycles (60 Hz).
Resolution: 0.1 ms.
Timer accuracy: 0.025% of reading ± 0.1 ms.
Counter inputs
These inputs allow testing energy meters, including high
frequency outputs.
Number of inputs: 2; with no common zero point.
Frequency range: 0 to 50 kHz.
Auxiliary outputs
Four timed relay contacts; both normal open and normal closed
provided.
Characteristics of contacts with a resistive load:
. Maximum voltage: 300 V AC/DC;
. Maximum current: 8 A.
Range of programmable delay: from 0 to 999.99 s.
Low level signal outputs
The purpose of these low voltage outputs is to test protection
relays that use transducers such as Rogowsky coils and voltage
dividers; for this simulation low voltage inputs are necessary.
Number of outputs: 6.
Full range V & I output: 0... 7.26 V rms.
Frequency: DC to 20 kHz.
Output current: 5 mA max.
Resolution: 0.43 mV or 0.043 mV.
Accuracy: 0.1% of the range.
Distortion: 0.1% typical.
Analog Measurements (optional):
DC Current measuring Input, Low
Measuring range: ± 20 mA.
Accuracy: 0.02% of range ± 0.01% of value.
DC Voltage measuring Input, Low
Measuring range ± 10 V.
Accuracy: 0.02% of range ± 0.01% of value.
AC/DC Current measuring Input, High
Measuring range: ± 20 A.
AC accuracy: 0.2% of range ± 0.1% of value.
DC accuracy: 0.1% of range ± 0.1% of value.
AC/DC Voltage measuring Input, High
Measuring range ± 250 V.
AC accuracy: 0.1% of range ± 0.1% of value.
DC accuracy: 0.05% of range ± 0.05% of value.
Interface connection
Type of interface: USB and RS232 at 57.6 kbaud.
Power supply
Mains power supply: 90 to 132 and 180 to 264 V AC, sinusoidal,
single phase.
Frequency: 47 to 63 Hz.
Power consumption:
. standby: less than 150 W;
. maximum load: 1600 W.
Case
Aluminum, with carrying handle.
Weight and dimensions
Weight: 18 kg.
Dimensions: 170 (h) x 470 (w) x 430 (d) mm.
Accessories supplied with the unit
Protective carrying bag.
Set of test leads.
Power supply cable.
Serial interface cable and USB cable.
Ground connection cable.
Instruction and maintenance manuals.
TDMS software.
DRTS 6 HP
High Precision option
This option has enhanced characteristics with respect to
the standard model. This model is conceived for the test of
class 0.2 energy meters. The following table summarizes the
performances of the DRTS 6 HP (High Precision) version with
respect to the standard one.
DRTS 6
4
OUTPUT CURRENT Typical: ± 0.05% ± 0.01% of range
Maximum: ± 0.1% ± 0.02% of range
OUTPUT VOLTAGE Typical: ± 0.05% ± 0.01% of range
Maximum: ± 0.1% ± 0.02% of range
PHASE ANGLE Typical: ± 0.02°
Maximum: ± 0.1°
3 PHASE POWER Typical: ± 0.05%
Maximum: ± 0.2%
STANDARD DRTS 6 ACCURACY
OUTPUT CURRENT Typical: ± 0.02% from 0.1 to 15 A
Maximum: ± 0.05% from 0.1 to 15 A
OUTPUT VOLTAGE Typical: ± 0.02% from 50 to 300 V
Maximum: ± 0.05% from 50 to 300 V
PHASE ANGLE Typical: ± 0.01°
Maximum: ± 0.02°
3 PHASE POWER Typical: ± 0.05%
Maximum: ± 0.1%
DRTS 6 HP ACCURACY
ADDITIONAL EXTERNAL AMPLIFIERS
FOR DRTS 6
AMI 99
Three phase current amplifier
The three phase current amplifier AMI 99 is an additional
device to the DRTS 6. DRTS 6 in connection with AMI 99
allows to have 9 currents or 6 currents at 30 A per phase or
three currents at 60 A per phase.
CURRENT POWER ZMAX RESOLUTION
A VA Ohm
9 X 6 x 0...15 80 0.35 230 µA
3 x 0...30 160 0.18 460 µA
9 X 6 x 0...1.5 23 µA
3 x 0...3 46 µA
9 X 6 x 0...0.15 2.3 µA
3 x 0...0.3 4.6 µA
6 X 0...30 160 0.18 460 µA
6 X 0...3 0.18 46 µA
6 X 0...0.3 0.18 4.6 µA
3 X 0...60 320 0.09 920 µA
3 X 0...6 0.09 92 µA
3 X 0...0.6 0.09 9.2 µA
1 X 0...180 960 0.029 2.8 mA
CURRENT POWER ZMAX RESOLUTION
A VA Ohm
3 X 0...30 160 0.18 460 µA
3 X 0...3 0.18 46 µA
3 X 0...0.3 0.18 4.6 µA
1 X 0...30 320 0.35 460 µA
1 X 0...90 480 0.06 1.38mA
AMI 99 with DRTS 6
AMI 99 stand alone
AMI 99 stand alone
. Three independent current sources, with a common neutral.
. Automatic range switch and independent range selection.
. Waveform resolution: 28 bit.
. Output accuracy: ± 0.1% of the output, ± 0.02% of the range.
. Distortion: 0.1% total maximum, with any load.
. Automatic protection for overloads.
. Angle accuracy: ± 0.05°.
Power supply
Mains power supply: 90 to 264 V AC, single phase.
Frequency: 47 to 63 Hz.
Power consumption:
. stanby: less than 100 W;
. maximum load: 1000 W.
Weight and dimensions
Weight: 16 kg.
Dimensions: 170 (h) x 470 (w) x 430 (d) mm.
5
DRTS 6 RELAYS, ENERGY METERS AND TRANSDUCERS TEST SET
Case
Case: aluminium, with carrying handle.
Accessories supplied with the unit
. Protective plastic bag.
. Mains supply cable to DRTS 6.
. Interconnecting cable to DRTS 6.
AMIV 66
Three phase current and two phase voltage
amplifier
The three phase current and two phase voltage amplifier
AMIV 66 is an accessory for the DRTS 6 for tests that require
nine independent currents at the same time (two secondary
differential transformers), or six voltages at the same time
(synchronising devices), or six currents and six voltages.
The three current outputs of AMIV 66 can be generated together
with DRTS 6: this also allows paralleling current outputs, thus
increasing output current and power.
Three phase current generator
AMIV 66 with DRTS 6
CURRENT POWER ZMAX RESOLUTION
A VA Ohm
9 X 0...15 80 0.35 230 µA
9 X 0...1.5 23 µA
9 X 0...0.15 2.3 µA
3 X 0...45 240 0.12 690 µA
3 X 0...4.5 69 µA
3 X 0...0.45 6.9 µA
1 X 0...135 720 0.04 2 mA
3 X 0...15 80 0.35 230 µA
3 X 0...1.5 0.35 23 µA
3 X 0...0.15 0.35 2.3 µA
1 X 0...15 160 0.71 230 µA
1 X 0...45 240 0.12 0.69 mA
AMIV 66 stand alone
AMIV 66 stand alone
. Three independent current sources, with a common neutral.
. Automatic range switch and independent range selection.
. Waveform resolution: 28 bit.
. Output accuracy: ± 0.1% of the output, ± 0.02% of the range.
. Distortion: 0.1% total maximum, with any load.
. Automatic protection for overloads.
. Angle accuracy: ± 0.05°.
Two phase voltage generator
AMIV 66 with DRTS 6
VOLTAGE POWER ZMAX RESOLUTION
V VA Ohm
6 X 0...300 85 1060 4.6 mV
6 X 0...125 85 185 1.9 mV
6 X 0...12.5 8 185 190 µV
1 X 0...600 400 200 9.2 mV
1 X 0...300 400 50 4.6 mV
CURRENT POWER ZMAX RESOLUTION
A VA Ohm
AMIV 66 stand alone
VOLTAGE POWER ZMAX RESOLUTION
V VA Ohm
2 X 0...300 100 900 4.6 mV
2 X 0...125 100 160 1.9 mV
2 X 0...12.5 10 160 190 µV
1 X 0...600 200 1800 9.2 mV
1 X 0...300 200 450 4.6 mV
DRTS 6
6
Two phase voltage generator
AMV 66 with DRTS 6
VOLTAGE POWER ZMAX RESOLUTION
V VA Ohm
6 X 0...300 80 1125 4.6 mV
6 X 0...125 80 195 1.9 mV
6 X 0...12.5 195 190 µV
1 X 0...600 320 195 9.2 mV
1 X 0...300 320 50 4.6 mV
AMV 66 stand alone
VOLTAGE POWER ZMAX RESOLUTION
V VA Ohm
2 X 0...300 80 1125 4.6 mV
2 X 0...125 80 195 1.9 mV
2 X 0...12.5 195 190 µV
1 X 0...600 160 390 9.2 mV
1 X 0...300 160 97 4.6 mV
AMV 66 stand alone
. Two independent voltage sources, with a common neutral.
. Output frequency: from 0 Hz to 2000 Hz; transient 5 kHz.
. Waveform resolution: 28 bit.
. Output accuracy: ± 0.1% of the output, ± 0.02% of the range.
. Distortion: 0.1% total maximum, with any load.
. Automatic protection for overloads and counter-feed.
. Angle accuracy: ± 0.05°.
Power supply
Power supply voltage: 90 to 264 V AC single phase.
Frequency: 47 to 63 Hz.
Power consumption, maximum load: 500 W.
Case
Aluminium, with carrying handle.
Accessories supplied with the unit
. Power supply cable.
. Interconnecting cable to DRTS 6.
. Plastic carrying bag.
AMIV 66 stand alone
. Two independent voltage sources, with a common neutral.
. Output frequency: from 0 Hz to 2000 Hz; transient 5 kHz.
. Waveform resolution: 28 bit.
. Output accuracy: ± 0.1% of the value, ± 0.02% of the range.
. Distortion: 0.1% total maximum, with any load.
. Automatic protection for overloads and counter-feed.
. Angle accuracy: ± 0.05°.
Power supply
Power supply voltage: 90 to 264 V AC single phase.
Frequency: 47 to 63 Hz.
Power consumption:
. stanby: less than 100 W;
. maximum load: 500 W.
Case
Aluminium, with carrying handle.
Accessories supplied with the unit
. Power supply cable.
. Relay connection cables kit.
. Interconnecting cable to DRTS.6.
. Plastic carrying bag.
Weight and dimensions
Weight: 18 kg.
Dimensions: 170 (h) x 470 (w) x 360 (d) mm.
AMV 66
Two phase voltage amplifier
The two phase voltage amplifier AMV 66 is an accessory for
the DRTS 6, for tests that require six voltages at the same
time (synchronising devices).
7
DRTS 6 RELAYS, ENERGY METERS AND TRANSDUCERS TEST SET
Primaries: 12.5 A and 15 A;
Secondaries: 0.5 A; 1 A; 2.5 A; 5 A;
Nominal power: 100 VA;
Current ratio error: 0.2.
Case: plastic.
For the single phase test of the CDG relay it is possible to
have three times the above power, connecting current
outputs in series.
I100A CURRENT BOOSTER
The option I100A is a set of six current transformers, that
allows to perform the following tests:
- With DRTS 6, 3x50 A;
- With DRTS 6 and AMI 99, 6X50 A (differential relays) or
3x100 A (over-current relays).
Characteristics:
Primary: 3x(2x15) +3x30 A;
Secondary: 6x50 A, that can be put in parallel, to form 3x100 A;
Nominal power: 6x120 VA @ 50 A, or 3x240 VA, steady;
Current ratio error: 0.5;
Frequency range: 40 Hz to 2 kHz.
Case: plastic.
Dimensions: 400 x 300 x 175 mm.
Weight: 12 kg.
Inputs from DRTS 6 are put in parallel inside the option:
all transformers have 30 A on the primary and 50 A on the
secondary.
The option includes twelve connecting cables to DRTS 6 and
AMI 99 current outputs.
GPS SYNCHRONIZER
The GPS synchronizer is an external module that allows to
synchronize the test start of two DRTS 6.
Weight and dimensions
Weight: 7 kg.
Dimensions: 170 (h) x 230 (w) x 360 (d) mm.
OPTIONAL ACCESSORIES
IEC61850 INTERFACE
The standard IEC61850 describes the communication of
devices in substations. IEC61850 messages coming from the
devices connected to the substation network (such as a relay)
are also called GOOSE. GOOSE messages describe binary
status signals over the substation network and are also used
for relays tripping . For relay testing applications within IEC
61850 substations it is necessary to access to these data.
This new feature is performed by ISA Automatic Relay Test Set
DRTS 6 and with the TDMS software.
By means of a dedicated hardware and the TDMS software, ISA
DRTS 6 can expand his testing capabilities by handling those
IEC61850 messages.
The IEC61850 Interface option for DRTS 6 is required for
relay testing with Ethernet-based substation communication
protocol. The IEC61850 Interface is mounted directly on the
front panel of the DRTS 6.
IN2-CDG CURRENT BOOSTER FOR 1 A RATED
HIGH BURDEN RELAYS
With DRTS 6 the full power of 100 VA is available only at the
current of 15 A. The option IN2-CDG by means of a set of three
current transformers, has the following characteristics:
DRTS 6
8
The option includes:
. A support to keep the scanning head in front of the energy
meter;
. The cable, 2 m long, from the scanning head to the DRTS 6;
. The power supply transformer, for the power of 220 V AC, to
supply the scanning head.
. Two safety banana plugs for the connection to DRTS 6.
TRANSIT CASE
Three options are available:
. Heavy duty transit case (Discovery type) in black plastics,
with handle and wheels.
. Heavy duty transit case in aluminium, with handle and
wheels.
. Soft carrying bag.
TESTING CABLES
This option includes additional cables, with different colours.
SEI OPTION FOR THE SERIES CONNECTION OF
CURRENTS
This option is made of a set of three burdens that equalize
the load for current outputs of DRTS 6. Each burden includes
two resistors rated 22 Ohm 1 W; at maximum load it causes
an error of – 1.6 %. The burden is easily connected to cur-
rent outputs by means of three safety banana sockets plus
plugs, that ease connections.
PAV OPTION FOR THE PARALLEL CONNECTION
OF VOLTAGES
The option includes small resistors to be connected in
series to voltage outputs of DRTS 6 and of AMV 66 or AMIV
66 options. Burden is 1 Ohm for tests up to 125 V and 5.7
Ohm for tests at 300 V; at maximum load it causes an error
of – 0.5%.
- Case: plastic.
- Dimensions: 22 x 45 x 85 mm.
- Connections to the instrument: two wires 0.2 m long, with
safety banana plugs.
- Connection to the load: by a safety banana plug.
- 125 V or 300 V selection: by switch.
Features:
. 1 digital output O-24 V DC, for synchronization.
. 1 selector to program the following pulse intervals: 5 s; 10 s;
20 s; 30 s; 40 s; 60 s.
. Maximum timing error with respect to nominal: 2 µs.
. Lights to confirm: power-on; Locked; Pulse available.
. 1 START and STOP push-button.
. Power supply: 110/22O V AC.
The option includes:
. the antenna;
. an extension cable for the antenna, 20 m long;
. two cables, red and black, 2 m long, with banana
terminations, for the connection to the test set trip input;
. the power supply cable.
Weight: 1.7 kg.
Dimensions: 150 (w) x 100 (h) x 240 (d) mm.
Case: aluminium.
Two test sets synchronized with GPS produce the maximum
error of 50 µs.
SH 2003 ENERGY METERS UNIVERSAL SCAN-
NING HEAD
SH 2003 is a scanning head that eases the test of energy
meters. lt is an universal scanning head because it can be used
both with LED impulse electronic meters and Ferraris rotating
disk meters. With rotating disk the sensor uses a green light
beam that optimizes the recognition of any type of mark.
With LED recognition the following specification applies:
. lmpulse duration: more than 60 µs.;
. lmpulse frequency: less than 500 Hz;
. Light wavelength: 500 to 960 nm (red).
9
DRTS 6 RELAYS, ENERGY METERS AND TRANSDUCERS TEST SET
PAI OPTION FOR THE USE AT 30 A, THREE
PHASE
The option PAI is made of four jumpers, that ease the paral-
leling of output sockets: I1 and I4; I2 and I5; I3 and I6, and
of the two IN sockets: this eases the connection to the relay
under test.
MAINS SYNCHRONISER
The option is made of a plug that fits into the mains, and
that has two banana sockets for the connection to the
test set counting input. The purpose is to synchronize the
outputs of two test sets to the mains: as the synchronisa-
tion is repeated every 2 minutes, the test set stays locked
to the mains for the infinity. The option includes a circuit
that squares the sinusoidal mains waveform; the isolated
output is a square-wave with an amplitude of 18 V nominal,
running at the mains frequency.
There are two instances where the option can be necessary:
. Generating a current or voltage into a device that is also
taking a signal from the mains;
. Synchronising two test sets to the mains, and then using
them to test line differential relays.
STAND UP SUPPORT
The stand-up support allows using the test set in a stand-up
position. This is very useful in case of too small room or no
support for the test set. There is enough room for the power
supply cord, and for the cooling air to flow in.
APPLICABLE STANDARD
The test set conforms to the EEC directives regarding
Electromagnetic Compatibility and Low Voltage instruments.
A) Electromagnetic Compatibility:
Directive 2004/108/EC (CE conform). Applicable standard:
EN 61326:2006.
B) Low Voltage Directive:
Directive 2006/95/EC (CE conform).
. Applicable standards, for a class I instrument, pollution
degree 2, Installation category II: CEI EN 61010-1.
In particular:
. Inputs/outputs protection: IP 2X - CEI EN 60529.
. Operating temperature: 0°C to 55°C;
storage: -25°C to 70°C.
. Relative humidity: 5 - 95% without condensing.
ORDERING INFORMATION
CODE MODULE
30156 DRTS 6
6 x I 0...15 A - 4 x V 0...300 V
1 x VDC output 0...260 V at 100 W
Standard set of test cables
Soft carry bag
TDMS - Test & Data Management Software
CODE MODULE
19153 Analog AC/DC Measurement Module
23156 High Precision (HP) outputs; 0.05% accuracy
outputs with SIT laboratory certificate (EU
accreditated)
81156 IEC61850 Interface, hardware and software
98156 IN 2 CDG - Option for High Burden Relays
47156 I 100 - 100 A Current Booster
10161 GPS syncronizer
20162 SH 2003 energy meter universal scanning
head
15156 Additional set of test cables
77156 Heavy duty transport case (Discovery type)
18156 Aluminium transport case
48156 Soft carrying bag
35150 SEI option to put in serie the current outputs
36156 PA-I option to put in parallel the current
output (3 x 30A)
34156 PA-V
24156 Mains synchronizer
19170 Stand up support
59156 Thytronic thysensor cables set
58156 ABB zero power cables set
OPTIONAL ACCESSORIES
EXTERNAL AMPLIFIERS
27156 AMI-99 (3 x I - 0 … 30 A at 160 VA)
28156 AMV-66 (2 x V - 0 … 300 V at 80 VA)
13156 AMIV-66 (3 x I - 0 … 15 A at 80 VA)
(2 x V - 0 … 300 V at 80 VA)
CODE MODULE
OPTIONAL ACCESSORIES FOR EXTERNAL
AMPLIFIERS
15156 Set of testing cables
18156 Aluminium Transport Case
CODE MODULE
DRTS 6
10
Soft bag
Heavy duty transport case
Heavy duty transport case in aluminium
AMI 99 - External amplifi er
AMIV 66 - External amplifi er
AMV 66 - External amplifi er
ISA Srl
Via Prati Bassi, 22
21020 Taino VA - Italy
Tel +39 0331 956081
Fax +39 0331 957091
Web site: www.isatest.com
E-Mail: isa@isatest.com
EN - DRTS 6 - 06/2014
The document is subject to change without notice.
Always refer to our technical specification for more detailed
information and as formal contract document.
DRTS 6
11
Optional set of testing cables
Standard set of testing cables
IN 2 CDG - Option for High Burden Relays Stand up support