DV Power Battery Charger BAC25A User Manual Brochure

User Manual: DV-Power-Battery-Charger-BAC25A-User-Manual-Brochure

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadDV-Power-Battery-Charger-BAC25A-User-Manual-Brochure Brochure
Open PDF In BrowserView PDF
Battery Charger BAC25A


Lightweight – only 10 kg / 22 Ibs



Instrument max power – up to 2,7 kW



Voltage range: 10-300 V DC



Current range up to 25 A DC



Measurement resolution – current 0,1 A,
voltage 0,1 V



Two charging modes available:
IU - constant current + constant voltage,
UU - constant voltage + constant voltage,
with current limit



Adjustable alarm and shutdown parameters for preventing excessive charge

Powerful and Portable Battery Charger
Description
Following a power outage, various power
engineering objects such as power plants should
be kept operating on batteries. It is necessary
batteries to be charged in order to compensate
its energy loss and keep their voltage within the
predefined limits. Battery charger BAC25A is a
portable battery charger used for charging
primarily Lead-Acid and Ni-Cd batteries.
BAC25A is intended to support the main charger
in order to charge battery much faster or to
quickly recharge a battery following a discharge

Mains Voltage
(V AC)

B-B025CN-307-EN 2017-02-27

230/115

test. Using two charging modes it provides the
possibility of maintaining and recharging the
batteries either with a constant current or a
constant voltage. The output voltages are
selectable in the range of 10 V to 300 V DC.
This device generates current up to 25 A. In
addition, it is equipped with thermal, overcurrent,
and over-voltage or under voltage protection.
Provided display enables users to read all
relevant information during a charging process
and to adjust the charging current, charging
time, etc.
Boost voltage (V DC)

Float voltage (V DC)

Voltage
(V DC)

Current
(A DC)

Lead-Acid

Ni-Cd

Lead-Acid

Ni-Cd

12

Up to 25

14

15

13

14

24

Up to 25

29

30

27

28

48

Up to 25

57

60

54

56

60

Up to 25

72

75

68

70

133/145

140/150

125/135

130/140

263/290

275/300

148/270

250/280

110/120
220/240

Up to 20 (230 V)
Up to 10 (115 V)
Up to 10 (230 V)
Up to 5 (115 V)

1

Benefits and Features
1.

Display - Values of output voltage, current and
other working status information are displayed on
the LCD screen.

2.

Keyboard - used for controlling and operating the
instrument.

3.

Status indicating LED diodes

4.

PT100
probe
connector
temperature measurement.

5.

USB PC Interface.

6.

Overvoltage alarm terminal - used for triggering
external alarm.

7.

Undervoltage alarm terminal
triggering external alarm.

8.

Current and voltage sense terminals connecting the current and voltage sense cables.

for

-

ambient

used

for

Application example
Typical application is charging batteries that serve as a backup power supply in:







Power plants
Generator excitation systems
Substations
Protection and control systems
UPS battery strings

B-B025CN-307-EN 2017-02-27

The BAC25A instrument is connected to a test
battery using the current cables. The voltage
sense cables may be used optionally. Next step
is to set the current and the voltage alarm levels.
After starting the charging process BAC25A
keeps the current or voltage level constant
depending on the selected charging mode.
When applying the IU charging mode the battery
is charged with a constant current. The voltage
increases to a level close to the final voltage
(boost voltage), the device switches to a
constant voltage (float voltage) mode and the
current begins to decrease. Cut off occurs when
a predetermined minimum current value, which
indicates a full charge, has been reached. When
opting for the UU charging mode the battery will
be charged under a constant voltage. If the
battery current becomes larger than the defined

current limit, the charger will switch into a
constant current mode and continue charging
with constant current that is equal to specified
current limit.

Otherwise, the charger keeps charging under
the selected constant voltage, the current will
decrease over time until it reaches a
predetermined minimum value. At this point of
time the charger will switch to a float charge
stage and decrease to a selected float voltage.
2

Technical Data
Mains Power Supply

Dimensions and Weight








Connection according to IEC/EN60320-1;

Dimensions:

C320

(D x W x H) without handle:

Voltage 90 V – 264 V AC, 50 / 60 Hz,

407 mm x 198 mm x 275 mm

single-phase

16 in x 7.8 in x 10.8 in

Power consumption: up to 3 300 VA



Weight:
10 kg / 22 lbs.

Output data



Output current: up to 25 A DC

Warranty



Voltage: 10-300 V DC





Typical voltage accuracy:
± (0,25 % rdg + 0,25 % FS)

Three year warranty applies to the
instrument ordered with its transport case



15 months warranty applies to the
instrument ordered without the transport
case

Environment conditions



Temperature -10 °C to +45 °C / 14 °F to
+113 °F



Safety Standards


Maximum relative humidity 95 % for

- Low Voltage Directive:
Directive 2014/35/EU (CE conform)
Applicable standards, for a class I
instrument, pollution degree 2,
Installation category II: IEC EN 61010-1

temperatures up to 31 °C, decreasing
linearly to 40 % relative humidity at 45 °C



Pollution degree 2

Electromagnetic Compatibility (EMC)



Safety



CAN/CSA-C22.2 No. 61010-1

Directive 2014/30/EU (CE conform)
Applicable standard: EN 61326-1

All specifications herein are valid at ambient temperature of + 25 °C/77° F and recommended accessories.
Specifications are subject to change without notice.

B-B025CN-307-EN 2017-02-27

Voltage sense cables

Current cables

Transport case

3

Order Info
Device with included accessories
Battery charger BAC25A

BAC25A-NN-00

Mains power cable

MPCxxA-xx-00

Ground (PE) cable

CABLE-GND-00

Recommended
Current cables 2 x 5 m 6 mm2 (16.4 ft., 9 AWG) with alligator clamps
(A2) isolated
Transport case

Optional
Current cables 2 x 10 m 6 mm2 (32.8 ft., 9 AWG) with alligator
clamps (A2) isolated

Article No

Article No
C2-05-06LMA2
HARD-CASE-ME

Article No
C2-10-06LMA2

Current cables 2 x 15 m 6 mm2 (49.2 ft., 9 AWG) with alligator
clamps (A2) isolated

C2-15-06LMA2

Current cables 2 x 20 m 6 mm2 (65.6 ft., 9 AWG) with alligator
clamps (A2) isolated

C2-20-06LMA2

Sense cables 2 x 5 m 2,5 mm2 (16.4 ft., 13 AWG) with banana
plugs + dolphin clip

S2-05-15BPDC

Sense cables 2 x 10 m 2,5 mm2 (32.8 ft., 13 AWG) with banana
plugs + dolphin clip

S2-10-15BPDC

Sense cables 2 x 15 m 2,5 mm2 (49.2 ft., 13 AWG) with banana
plugs + dolphin clip

S2-15-15BPDC

Sense cables 2 x 20 m 2,5 mm2 (65.6 ft., 13 AWG) with banana
plugs + dolphin clip

S2-20-15BPDC

Cable for external alarm 2 x 5 m (16.4 ft.)

CA-EXABAC-05

Extension cable for external alarm 2 x 5 m (16.4 ft.,)

E1-EXABAC-05

PT100 temperature indicator

TI-000-PT100

Device bag

DEVIC-BAG-00

Cable bag

CABLE-BAG-00

B-B025CN-307-EN 2017-02-27

IBEKO Power AB
Stockholmsvägen 18
181 50 Lidingö, Sweden

Contact
Phone: +46 70 0925 000
E-mail: sales@dv-power.com

4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 4
Language                        : en-GB
Tagged PDF                      : Yes
Author                          : Goran
Creator                         : Microsoft® Word 2013
Create Date                     : 2017:02:27 11:11:00+05:30
Modify Date                     : 2017:02:27 11:11:00+05:30
Producer                        : Microsoft® Word 2013
EXIF Metadata provided by EXIF.tools

Navigation menu