HARDWARE LIST – Pyropanel Fire Doors
INTRODUCTION
Hardware items listed are approved for Pyropanel VP and SP Series doorsets. This approval does not
apply to other door types. The list is updated regularly but includes obsolete items which are listed for
reference purposes. Refer to website www.pacificdoors.co.nz for the most up-to-date list. All items
indicated in the list as [PDS] must be factory installed or prepared for by Pacific Door Systems Ltd.
Hardware for F0.5 doorsets is listed separately.

1. MECHANICAL LATCHES
Note: For fire doors to comply with AS/NZS 1905.1 the following conditions apply to latches:
•
No non-self-latching functions are permitted, including deadlock bolts
•
Materials for essential latching components must have a melting point of:
- For integrity up to and including 120 min not less than 890oC
- For integrity in excess of 120 min not less than 1030oC
1.1 CYLINDRICAL OR TUBULAR LOCKS AND LATCHES
Make

Code

AH

2000-100 series

1

VP120

Boyd

LE series

1

VP240

Carbine

EA 3000 series

1

VP240

Corbin

400, 1400

1

VP240

Corbin

6600

VP120

Corkey

800 KT

VP240

Dorma

CL600

VP240

Efco

1000

1

VP240

Efco

5300

1

VP240

EZSET

EA3000

1

VP240

EZSET

100EA, 104EA

VP240

EZSET

RA series

VP240

Falcon

S 452 DL

1

VP240

Gainsborough

840 SS, GOV, CV

1

VP240

Gainsborough

4000 series

VP240

Gainsborough

4300

VP240

Gainsborough

4500 series

VP240

Gainsborough

4600 series

VP240

Gainsborough

4700 series

VP240

Goal

UH series

Hafele

1200

VP240

Ilco Unican

Model EA3000

VP240

Ilco Unican

6000 series

VP240

Ilco Unican

Model 3700

VP120

Kaba

KL series

VP240

Kwikset

411 B, C, G, WL

VP120

© 2008 Pacific Door Systems Ltd

Note

1

Max.Rating

VP240

1

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
1.1 CYLINDRICAL OR TUBULAR LOCKS AND LATCHES CONTINUED.
Make

Code

Note

Max.Rating

Laidlaw Thomson

AD series

1

VP240

Lane

3000, 3100 series

1

VP240

Legge

G2 series

Lemaar

Montoro, Denia

Lockwood

500

Lockwood

530

Lockwood

930-950-970-990

VP240

Lockwood

1300 series KNK

VP120

Lockwood

5200

VP120

Lockwood

5300

1

VP240

Lockwood

7000, 7020, 7040, 7070

1

VP240

Lockwood

110 combination lock

1

VP240

Lockwood

NX5 and NX6

1

VP240

Lockwood

Nexion NF22, NF12

MCM

500

1

VP120

Nara

HL 4000 Series

1

VP240

Nara

HL 8300 Series

1

VP240

Posse

B300

1

VP240

Posse

C100 SS series

VP240

Posse

C300 SS series

VP240

Premiapri

N14PB

VP240

Schlage

A and AL Series

1

VP240

Schlage

D Series

1

VP240

Schlage

F series

VP120

Schlage

S Series

VP240

Schlage

TH885

VP240

Schlage

Z series

VP120

Showa

SS G25

VP120

Stanley Byron

32

VP60

Stronglok

LHS1082 with Vinco C-70 FDL

VP180

Vinco

CL7000

Weiser

A530

VP240

Wilka

3000

VP120

Yale

5300

VP240
1

VP240
VP120

1

VP240

VP240

1

1,2

VP240

VP240

1.2 MORTICE LOCKS AND LATCHES
Make

Code

Note

Abloy

2595

1

Abloy

3000 series

© 2008 Pacific Door Systems Ltd

Max.Rating
VP240
VP240

2

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
1.2 MORTICE LOCKS AND LATCHES CONTINUED.
Make

Code

Abloy

EL580 series

VP240

Abloy

4291

VP240

ABS

1100 series

Accord

CH-382

VP120

Accord

CH-382 SS

VP240

Astra

430-439

Boyd

ML

Chubb

3R35X

CISA

52300

VP120

CISA

52760

VP240

Corbin

Series 9200, 9500, models –01, -51, -54, 55

VP120

Corbin

Series 9400, 9700, 9700T
Models –10, -51, -54, -55, -57

VP240

Corbin

Series 9800 models –51, -54, -55, -57

VP240

Dorma

ST9600 series (excluding 9603 deadlock)

VP240

Efco

3000

1

VP240

Efco

8000 series

1

VP240

Erebus

E900, E901, E951, E954, E957

VP120

Falcon

M and LM2000 series
Models 2100,2380,2410,2520,2560,2580

VP120

Gainsborough

1000 series 1100, 1400, 1500, 1900

Gainsborough

3000 series 3400, 3500, 3900

VP120

Glutz

4728, 4828, 4738, 4838

VP240

Goal

AS-1

7

VP120

Goal

UC-1

7

VP240

Goal

UCC; GC Cup Handle

VP240

Hafele

2500

VP240

Hafele

2595 with Dialock furniture

VP120

Hafele

911.23.270

VP240

Hafele

911.03.181 with Dialock DTSH terminal

VP240

Kaba

MS mortice lock

VP240

Lanetronics

E335

Lane

Astra 430-439

VP240

Legge

990 series

VP240

Legge

Ingersoll Rand PRO5596-990 keypad / lever
furniture with 990 mortice lock

VP60

Legge

E800 – Models E800, E801, E802, E803,
E851, E852, E853, E857

VP120

© 2008 Pacific Door Systems Ltd

Note

1

1

Max.Rating

VP120

VP240
VP240

1

10

1

VP240

VP240

VP240

3

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
1.2 MORTICE LOCKS AND LATCHES CONTINUED.
Make

Code

Note

Max.Rating

Legge

E900 – Models E900, E901, E951, E954

VP120

Lockwood

Electric Access Deadlatch

VP240

Lockwood

570, 572, 574

VP240

Lockwood

3570 and 3570E series incl. digital furniture

VP240

Lockwood

3670 series Securilock

VP240

Lockwood

M8600

VP240

Lockwood

8000 series

VP240

Lockwood

Digital Access Locks DGT530, DGT572DL,
DKO572DL, DKOLKO572DL

VP240

MIWA

UXAL3H

VP240

MIWA

AL5HA Card Lock (with auto deadbolt)

VP180

AL5H series with deadbolt removed
Modric

HD99 – Models 9960, 9962, 9970, 9990

VP120

Novas

6000 series

VP120

Padde

XS

VP180

Pennine E900

Models E900, E901, E951, E954, E957

VP120

Pennine 800

Models 800, 801, 802, 803, 806, 851,
852, 853

VP120

Russwin

5000 series with Saflok Mark 5 or Saflok
Micro Card card key furniture

VP120

Saflok

Mark 5 Card Key Lock

1, 8

VP240

Saflok

Micro Card Key Lock

1, 8

VP240

Saflok

ME, MS, MT series

VP180

Schlage

M series (except Deadbolts or devices fitted
with hold back function)

VP240

Schlage

L – Models 9010, 9040, 9050, 9060, 9070,
9080, 9082

VP240

Showa

535-15

VP120

Showa

LL

VP120

Tesa

2035

VP120

Tesa / Onity

HT24 card operated

VP120

Union

2642, 2657, 2677, 26773, 2370

Vingcard

Models 1040, 1050, 1060, 1080, 1090,
2100, 3000, 3500 Euro or ANSI lockcase

VP240

Vingcard

DV80 series Presidio

VP240

Weider

5750

VP240

Winkhaus

2501 series

VP240

Wilka

207

VP240

Yaletronic

1100

VP180

© 2008 Pacific Door Systems Ltd

9

VP120

4

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
1.3 RIM AND SURFACE MOUNTED LOCKS AND LATCHES
Make

Code

Note

Efco

506, 507

VP120

Lockwood

001 double cylinder automatic deadlatch

VP240

Lockwood

001/002 combination set

VP120

Padde

GK Escape latch

Rivers

Model D, 2 and 4 point locks using sexbolts

VP240

Surelock McGill

Multiple Bolting system with auto latching

VP240

3

Max.Rating

VP240

[PDS]
[PDS]

1.4 ROLLER LATCHES
Make

Code

Note

Max.Rating

Clifton

Roller latch

4

VP30 DA

[PDS]

Kevdon

Roller latch

4

VP30 DA

[PDS]

Legge (Erebus)

1511

4

VP30 DA

[PDS]

Sopers

SP15201

4

VP30 DA

[PDS]

UDM

FR Roller latch

5,6

VP240

[PDS]

Notes:

1. The latch sets indicated might have either steel or brass strike bolts, strikers, or bolt
retaining plates. Steel is rated VP240 while brass is rated VP120.
2. Plastic striker box not permitted on Yale 5300
3. With steel through-bolt fixings
4. The Clifton, Kevdon, Legge and Soper Roller latches may only be used with VP30
Double Action (DA) doorsets in timber frames (including VP30-DA Heritage).
5. The UDM Roller latch may be used with Double or Single Action frames
6. The UDM Roller latch may be the sole means of latching (Head latching or Stile
latching) in VP series hinged doorsets.
7. Timber knobs or plastic levers not permitted.
8. In conjunction with any approved mortise lock.
9. Only used in pair doorsets if no taller than 2200mm
10. The locksets must be installed with three holes through the face, one 12.7mm in
diameter and two 6.5mm diameter holes 21mm either side

2. POWER BOLTS
Make
Loktronic

Code
Locking Bolt (Fail Secure)

Trimec

ES8000 V-lock

Notes:

Max. Rating
VP240
VP120
VP240

Note
1
2
3

[PDS]
[PDS]

1. Device is rated VP240 as a supplementary locking device only
2. Device is rated VP120 as a sole latching device, but must be fitted with a brass
change of direction block. Only approved with fail-secure or power-to-open function.
Device must be fitted with a bevelled bolt or electrically wired to hold the bolt
retracted until the door leaf has closed
3. Power-To-Lock (PTL) with supplementary latching. Power-To-Open (PTO) can be sole
latching device.

© 2008 Pacific Door Systems Ltd

5

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
3. ELECTRIC LATCHES Type: C = Cylindrical; M = Mortise
Make
Accord
Corkey
Lane
Lockwood

Code
Digital Latch Bolt Series
800KT
Lanetronics E335240
3570 Series Electric with conventional or digital
furniture
990MFE
Electron UXAL 3H
5000 with Saflock Mk5 Card Key
M Series electric
Intellis TH885
D Series electric
Unican 1000 Series, L1000 Series, EE1000 Series

Legge
Miwa
Russwin
Schlage
Schlage
Schlage
ILCO
Notes:

Type
C
C
M
M
M
M
M
M
C
C
C

Max. Rating
VP30
VP240
VP240
VP240
VP240
VP240
VP120
VP240
VP240
VP240
VP120

[PDS]

[PDS]

1. Steel latch bolts rated VP240, Brass rated VP120.
2. For installation of wire-ways in door leaf [PDS] is required.
3. Latches in fail-safe mode require auxiliary latching. UDM Roller Head latching is
recommended.

4. ELECTRIC STRIKES
Make
Adams Rite
EFF-EFF
Gainsborough
Harcor
Honeywell
Honeywell
Lockwood
Loktronic
Padde

Padde
Rofu
Trimec

Von Duprin
Von Duprin
Notes:

Code
7800 Series
43 KI
ES1000 series
50/12/C
RS 2-75959
Alpha RS 2-75959
EK 35
500 Series DKS Strike
ES100 series
ES110 series
ES200 and ES2000 series
ES700 and ES7000 series
MT110
1400 or 3400 Series
TS100
TS110
TS200 and TS2000
TS700 and TS7000
ES 3100
3041 or 3042
6211

Max. Rating
VP90
VP240
VP240
VP240
VP120
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP120
VP240
VP240
VP240
VP240
VP240
VP120
VP120

1. “Fail Safe” electric strikes are only approved if the door closer is fitted to the opening
or hinge face of the leaf.
2. All strikes are approved only in steel jambs.

© 2008 Pacific Door Systems Ltd

6

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
5. MAGCLAMPS
Make
Efco

Efco
Guardsman
HFH
Lockwood
Loktronic
Loktronic
Locknetics
Padde
Rixon Firemark
Rixon Firemark
Rofu
Securiton
Trimec
Von Duprin
Notes:

Code
GI 300 & GI 300D (VP60 without seal to
head of leaf; VP120 with seal; VP240
with seal and fusible screw fixing)
GI 200 (VP60 without seal to head of
leaf; VP240 with seal to head of leaf)
MES series
10000 Series – 10000, 10002, 10010ECO, 10030, 10050, 10060-ECO-D
GI 200, GI 300, GI 300D as for Efco GI
1710 Slimline
ZB1710 Slimline, ZB1710
Models 268, 280, 290, 350, 390
Models CCW30, EML2H, EML2HD, EML6,
EML10, EML11, EML12
1700, FM1710
ZBFM1710
8011-LC or 8022(pair)
62 Magnalock
Z series
1200 series, DS4010, DS4020, DD4010

Max. Rating
Up to
VP240

Note
1-3

Up to
VP240
VP60
VP240

1-3
1-3
1-4

VP240
VP60
VP240
VP60

1-4
1-3
1-4
1-3

VP240
VP60
VP240
VP240
VP240
VP240

1-4
1-3
1-4
1-4
1-3
1-4

1. Approved for both timber and steel jambs. For installation in timber jambs [PDS] is
required. In timber jambs the magclamps body may be housed into oversize stops or
located between lengths of stop.
2. Electromagnet must be connected to jamb not door leaf. “Z” bracket installation is
only rated VP60. All-steel connectors must be used.
3. Auxiliary approved mechanical latch is required with all magclamps
4. For installation on VP90-240 doors [PDS] is required.

6. SHEARLOCKS
Make
Locknetics
Von Duprin
Notes:

Code
GF3000 series
700 Series (Obsolete model)

Max. Rating
VP30
VP30

[PDS]
[PDS]

1. Device must be used in conjunction with an auxiliary mechanical latch set
2. Shearlock may only be fitted to 48mm leaf in a steel-framed doorset, and to a special
modified head in a timber framed doorset, both for 30 minutes fire resistance.

7. HOLD OPEN DEVICES
Make
Dorma

Dorma
LCN

Code
A50, A70, AW50, AT50, AT70 armatures
associated with EM-50 and EM-70 series
electromagnetic hold open devices.
MAG, MAW, MAT armatures for Dorma EM series
SEM7830

© 2008 Pacific Door Systems Ltd

Max. Rating
VP240

VP60-DA
VP240

7

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
8. HINGES
Type
Butt

Broad Butt
Rising Butt
Butterfly
Lift-off
Strap
Continuous

Restrictions

Make
Model
Material
Ajax
100 x 100mm
Classic
100 x 100 Ball Bearing
Stainless Steel
Dalco 321
100 x 100mm
Stainless Steel
Efco
EF10025SSFPBB
Efco
SS Ball bearing
Stainless Steel
Glutz
SS Ball bearing
Stainless Steel
Hafele
926.84, 926.89
HK
SS90044B30
Stainless Steel
Kingsway
100 x 100
2.5mm Stainless Steel
Laidlaw Thompson 100 x 100
3mm Stainless Steel
Lane
100 x 100
2.5mm Steel
Lockwood
HS 100x100
Lockwood
SUS304 100x100
McKinney
TB 100 x 100
Steel or S/S
Nara
D10 100x100
3mm S/S
Nara
All metal spring hinge
100x100
Nikon
100 x 100
Stainless Steel
Pyropanel
Surface mount 100x70
2.4mm Stainless Steel
Schlage
413, 100 x 100
2.5mm Stainless Steel
Schlage
417, 100 x 100
3mm Stainless Steel
SCL
SUS-304, 102x102mm
Stainless Steel
Stanley
PB780, SW781, BB783
Stainless Steel
Trio
100 x 100
Mild or Stainless Steel
Yank
100 x 100
3mm Brass
100h x 125w
S/S 3mm thick
Schlage
411, 100 x 75
(Note 3)
Surelock
S2 / HA2 / 130 x 75
Nara
D10 / 100 x100
Stainless Steel
UDM
127 x 100
Stainless Steel
Tuff TUI
Ball bearing steel/ 250mm
Steel or Stainless steel continuous hinge at least 1.6mm thick,
leaf width not less than a 100 x100 butt hinge, fixed with screws
in a staggered pattern at not less than 200mm centres.

Max. Rating
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP120
VP240
VP240
VP240
VP240
VP240
(Note 4)
VP60
VP240
VP240
VP240
VP240
VP240
VP120

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

1. Brass hinges or screws are generally not approved. Brass plated steel is approved
2. May only be used as a centre hinge or as an additional hinge of 3 or 4 and must
be used in conjunction with Nara D10 hinges to accommodate lift.
3. Brass hinge is limited to FRR60 minutes in steel frames for leaf sizes up to 1.95m2
and FRR 30 minutes in timber frames.

© 2008 Pacific Door Systems Ltd

8

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
9. OTHER ELECTRONIC ACCESSORIES
Device
Microswitch Keep
Reed Switch

Power Transfer

Notes:

Make
Abloy
Chubb
GRI-Telemark
Sentrol 1076, 1077, 1078,
1076C, 1077C, 1078C
Tane Alarm SD-70, SD-80
Abloy 8810 and 8811 Lead Cover
Abloy EA280 & EA281 Lead Cover
Lane Flexitran
Lockwood PWRLEAD
Lockwood power transfer hinge
Loktronic
McKinney TA or TB Series
Schlage PT1
Von Duprin EPT 218 & EPT 1024

Notes
3
3
3
3
2
2
1

1
3

Max. Rating
VP30
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

1. Only rated VP30 in timber frame
2. Where timber frames are used a layer of Intumex L is to be glued to the
inside base of the lead cover channel
3. May only be used in a steel frame

10. SELF LATCHING PAIR HARDWARE FOR INACTIVE LEAF
Make
Dalco
Lockwood
Glutz
Glynn Johnson
Schlage
UDM
UDM
UDM
Weider
Winkhaus
Yank
Restrictions:

Type
DC1851 chain bolt
530 or 930 or 950 Deadlatch
GDS-0148-A-SS
FB41T or FB41B Autolatch
D Model 14-043
FR Roller Latch
Autobolt
Chain latch
Model 180
Flushbolt
Flushbolt

Note
2
3

Max. Rating
VP240
VP120
VP240
VP30/VP60
VP120
VP240
VP240
VP240
VP240
VP240
VP120

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

1. All are approved for timber and steel jambs.
2. These deadlatches are installed in the door head with an appropriate snib (The
Lockwood 8530-57SC is recommended). Backset length should be 70mm
minimum. The deadlatches are rated VP60 for door leaves taller than 2400mm.
3. VP60 in steel jambs only.

© 2008 Pacific Door Systems Ltd

9

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
11. SEQUENCE SELECTOR FOR PAIRS
Make
Briton
DCI
Dorma
Dorma
Dorma
Efco
Gainsborough
Glynn Johnson
Hafele
Lane
Lockwood / Efco
Newstar
Ryobi
Tiki
Weider

Code
Closerite
600
SR390
SR391, SR392, SR393
TS93 GSR system
3000 & 4000
3350SS
COR
931.71.900
5230, 5180, 5305, 2359, 2369
3000 & 4000
SF-250F
RB-34
S1991
DS-2800, DS-3600

Max. Rating
VP240
VP240
VP240
VP60
VP120
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240

Note: Sequence Selectors are required on pair doorsets with non-self-latching functions such as
rebated meeting stiles or central locking.

12. SECURITY ACCESSORIES
Make

Type

Code

Chubb

Hinge Bolt

WS12

Chubb

Hinge Bolt

WS7

Duo

Hinge Bolt

HBC, HBW

Securicraft

Securichain

MC41

Notes:

Notes

Max.Rating
VP60

2

VP240

3

VP120

[PDS]

VP240
[PDS]

1. Up to 2 hinge bolts may be used, set into the leaf near the top and/or bottom hinges
2. Steel jambs only
3. Rated VP60 in Drywall and VP120 in concrete/masonry installation

13. SURFACE MOUNTED CLOSERS
Note:
• Fixture of surface-mounted closers to Pyropanel mineral fibre board cored fire doors requires selftapping screws, which must penetrate at least 32mm into the leaf.
• Cushioned backcheck function is required on all closers for compliance with AS/NZS 1905.1. All
listed closers comply with this requirement.
• Hold open devices are required on certain fire doors for compliance with NZ Building Code C/AS1
3.17.9. Requirements for fire detection to release hold-open devices are given in C/AS1 3.17.10.
• For fire doors on escape routes, NZBC C/AS1 requires closers to be adjustable to satisfy the
requirements for maximum forces required to open the door, set out in C/AS1 Appendix C 8.1.2.
Make
Abloy
Abloy
Accord

Code
Modul 230 series
DC240
90

© 2008 Pacific Door Systems Ltd

Maximum Rating
VP240
VP240
VP240

10

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
13. SURFACE MOUNTED CLOSERS CONTINUED
Make
Code
Arrow
7x7 Series Surface mounted
Boyd/Axim
Boyd/Axim
Boyd/Axim
Boyd Sentronic

1500BC
1024 Series
7000/1000BC
4010/4110

Briton
Briton
Briton
Briton
Briton
Briton
Briton
Corbin
Delta
Doric
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma
Dorma

81 series
121.5 series
220
1000 series
2000 series
2508S
5000
500 series
70BC Series
DK53
TS68
TS73F Series
TS71
TS72 without hold open
TS73 EMF
TS73 EMR
TS73 V-F
TS77 Series
TS83 Series
TS90
TS92 without hold open

Dorma
Dor-o-matic
Efco
Efco
Gainsborough
Gainsborough
Gainsborough
Gainsborough
Geze (Hafele)
Geze (Hafele)
Geze (Hafele)
Global
Glutz
Hafele

TS93 series incl. EMF or EMR
TS97
SC60, SC80
4080 Series
1300 Series
3000 series
3200 series
3050/3060
3100
TS2000V BC series
TS4000, TS4000DA series
TS5000, TS5000L, TS5500 series
70BC series
PDC-500, PDC-730, PDC-770, PDC-830
DCL51, DCL55, DCL110

© 2008 Pacific Door Systems Ltd

Maximum Rating
VP90 plastic cover,
VP240 metal cover
VP120
VP90
VP120
VP90 plastic cover,
VP120 metal cover
VP120
VP120
VP240
VP120
VP120
VP120
VP120
VP120
VP120
VP120
VP240
VP240
VP240
VP240
VP120
VP120
VP240
VP240
VP120
VP240
VP120
VP120
VP120
VP240
VP120
VP240
VP240
VP120
VP120
VP240
VP240
VP120
VP120
VP120
VP240
VP90

11

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
13. SURFACE MOUNTED CLOSERS CONTINUED
Make
Code
HFH
60 BC series
Justor
CH series
Kaba
702 SIL
King
D70 BC, D70 P BC series
King
600 BC, 600 P BC series
King
900 BC series
Lane
70 BC series
Lane
SL 65 BC
LCN
524, 523T
LCN
4310 ME series
LCN
1070 series
1460 series
4010, 4110, 4040 series
Sentronic 4010/411 SE
Leado
980 series
C999 EM hold open to any Lockwood
Lockwood
closer
Lockwood
3024 series
Lockwood
414 / 426 series
Lockwood
409 series
Lockwood
713 series
Lockwood
714 / 726 series
Lockwood
724 series
Lockwood
1300 series
Lockwood
LW 1730 series
Lockwood
LW 1830 series
Lockwood
LW 2000 series
Lockwood
LW 2500 series
Lockwood
7714 / 7724 series
Lockwood
7726 series
Lockwood
Miwa M200
Lockwood
Miwa M800
Lockwood
8002 Door Operator
MAB
400 series
MBC
525 BC series
MBC
527 BC series
Newman Tonks
NT 121 BC
Newstar
80
Nikon
90
NHN
1080 series
Novas
1000 BC
Novas (Guardsman)
1300 BC
Novas (Guardsman)
1500 BC

© 2008 Pacific Door Systems Ltd

Maximum Rating
VP120
VP240
VP120
VP240
VP120
VP120
VP120
VP120
VP 240
VP90
All VP90 with
plastic cover,
VP120 with metal
cover
VP240
VP240
VP240
VP120
VP120
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP120
VP240
VP60
VP120
VP240
VP120
VP240
VP120
VP240
VP120
VP240
VP240
VP120

12

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
13. SURFACE MOUNTED CLOSERS CONTINUED
Make
Code
Novas (Guardsman)
3000 BC
Pyropanel
TS77 Series
Ryobi
7000 Series
Ryobi
70 Series
Ryobi
90 Series
Ryobi
1500 BC Series
Ryobi
1550 BC Series
Ryobi
D-2550 DA series
Ryobi
D-3550 series
Sabre
BC730 series: models 732, 733, 734
Sabre
Models 735, 736
Sabre
836 AS
Sabre
2100 B series
Spartan
1002-BC
Tiki
80 series, 90
Vinco
DC67
Vinco
DC934
Weider
1000 series
Weider
1500 BC series
Yale
2000 series
Yale
Yank

Maximum Rating
VP240
VP240
VP120
VP120
VP120
VP120
VP90 plastic cover
VP240
VP240
VP240
VP120
VP240
VP240
VP240
VP120
VP120
VP240
VP240
VP120
VP90 plastic cover
VP240 metal cover
VP120
VP240

3501 series
BC1002AS

14. CONCEALED CLOSERS
Make
Arrow
Briton
Corbin
Dorma
Dorma
LCN
LCN
Lockwood
Newstar
Tiki
Notes:

Type
7x7 Series
531
500
ITS-86
ITS-96 without hold open
3030 Series
330
409/091
CL60
60
1.
2.
3.
4.
5.
6.

Notes

1
1
3
1

Max. Rating
VP120
VP60
VP120
VP180
VP180
VP240
VP240
VP240
VP240
VP240

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

Installation approved in steel jambs only (where noted)
Only surface mounted arm brackets may be used with timber jambs (except see Note
3). Either surface mounted or mortised arm brackets may be used with steel jambs.
Mortised arm may be installed in timber jamb in Heritage VP30 Series doors.
Leaf glazing directly below concealed closers is not permitted except in VP30 Series
Heritage fire doors
Concealed closers are not recommended in exterior doors.
Rating VP120 applies where door height exceeds 2400mm.

© 2008 Pacific Door Systems Ltd

13

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
15. PANIC EXIT DEVICES
Type
Rod/Latch

Rod/Latch

Rim Latch

Mortice Latch

Restrictions:

Make
Adams Rite
Briton
Dorma
Glutz
JPM
Lionheart
Lockwood
Lockwood
Lockwood
Massoud (MBC)
Trident
Weider
Von Duprin
Adams Rite
Boyd
JPM
Lockwood
Lockwood
Massoud (MBC)
Von Duprin
Adams Rite
Lockwood
Von Duprin
Weider

Code
3100
373, 374, 377, 378, 379
PHA 2102/2203 (3 point
latching only)
8600
9300, 9400
E9801, E9802
520V
5510 and 5530 series
9000
571 series
1089
3730, 3731 Series
2227F, 8827F, 9827F,
9927F
3700
ED22F
9000, 9100
520
9000
570 Series
22F, 88F, 98F, 99F
3300
9000
8875F, 9875F, 9975F
8909

Note
4

4
5

4
4
3

3

3

Max. Rating
VP240
VP240
VP120

[PDS]
[PDS]
[PDS]

VP240
VP240
VP240
VP240
VP240
VP240
VP60
VP240
VP240
VP240/VP60

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

VP240
VP60
VP240
VP240
VP240
VP60
VP240/VP60
VP240
VP240
VP240/VP60
VP240

[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]
[PDS]

1. VP Series fire doors – All devices are surface-fixed and must be mounted using
at least nominal 5mm steel hex bolts passing through the leaf.
2. All devices in VP Series fire doors may be fitted to doorsets with timber or steel
jambs (except see Note 5)
3. Models without the F suffix have brass components and are therefore only rated
60 minutes.
4. Device may only be used in conjunction with a fire rated mortice or tubular latch
or lockset. Fire resistance is then dependent on the fire resistance of the latch or
lockset.
5. Steel frame only. Length adjustment mechanism for the vertical actuating rods
must be fitted with a nylon screw.

© 2008 Pacific Door Systems Ltd

14

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
16. DOUBLE-ACTION HARDWARE
Device

Make

Roller latch

Kevdon
Clifton
Soper SP15201
Legge (Erebus) 1511

FR Roller latch

UDM

Locking

Abloy EL414 Electric Lock

8

Abloy EL415 Electric Lock

Head Spring

[PDS]
[PDS]
[PDS]
[PDS]

VP120

[PDS]

VP60

[PDS]

7

VP60

[PDS]

Loktronic Power Bolt

1

VP120

[PDS]

Trimec ES8000 V-lock

9

VP120

[PDS]

Dorma RTS85

VP120

[PDS]

Lockwood Efco OTC series

VP120

[PDS]

Lockwood 9800 series

VP120

[PDS]

VP120

[PDS]

VP120

[PDS]

Notes:

5

Dorma BTS80F
Dorma BTS75

Panic Exit Lock

3
3
3
3

Max.Rating
VP30
VP30
VP30
VP30

Ryobi 30 series
Floor Spring

Notes

VP30

[PDS]

Dorma EMB

3

VP120

[PDS]

Lockwood Efco EF840 (FS 840)

VP120

[PDS]

Lockwood 7310/7410

VP120

[PDS]

Lockwood 7750 series

VP120

[PDS]

MAB 7312, 7412

4

VP120

[PDS]

Surelock McGill Multiple Bolt B1

6

VP120

[PDS]

1. The Loktronic Power Bolt should be integrated with a fire detection system so that
the bolt disengages on an alarm or power failure (fail safe or power-to-lock mode). In
this mode the lock requires an auxiliary UDM roller latch.
2. A roller latch is required with double action doorsets. The UDM roller latch is standard
3. These items are approved only for VP30-DA in timber jambs with special requirements
4. VP120 with steel arms, VP60 with brass arms
5. Ryobi 30 series is limited to models without hold-open and with cushioned backcheck
function.
6. Fitted with solid lower latch bar and hollow upper latch bar. Requires fitting of roller
restraint auto-bolting mechanism and associated head ramp.
7. Abloy EL415 (fail unlocked) installed in the frame head, requires a modified strike
plate to the head of the door leaf and an auxiliary UDM roller latch.
8. Abloy EL414 (fail locked) installed in the frame head, requires a modified strike plate
to the head of the door leaf but does not require auxiliary latching and may not meet
egress requirements.
9. Power-To-Lock (PTL) with supplementary latching. Power-To-Open (PTO) can be sole
latching device

© 2008 Pacific Door Systems Ltd

15

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
17. DOOR OPERATORS
Make
Abloy
Ditec
Ditec
Dorma
Dorma
Dorma
LCN
LCN
LCN
Lockwood
Notes:

Type
DA361 swing door operator
Transit UE
Wel E
CD80 Door Operator
ED200 Door Operator
ED800 Door Operator
4611, 4622 autoequaliser
4630 / 4640 autoequaliser
4820 auto equaliser door operator
8002 series, transom mounted

Notes
1
2
2
3
4
4
5
6
7

Max. Rating
VP120
VP60
VP60
VP240
VP240
VP240
VP120
VP240
VP120
VP240

1.

Modifications to installation are required – contact distributor www.levco.co.nz.
Local fire or smoke detection is required either side of doors.

2.

In timber-framed door only. Modifications are required to the standard installation - a
fire door package is available from the distributor www.doormaticsnz.co.nz.
Local fire or smoke detection is required either side of doors.

3.

Transom mounted; fitted to a steel plate, or with long screws into lintel

4.

Special conditions apply for fixing this closer. Closer may only use standard arm and
may only be mounted on the push side of the leaf. Operator must revert to closer in
the event of fire exposure

5.

Modifications to installation required. Autoequaliser must revert to self-closure on
local detection of smoke or heat from fire.

6.

Modification of operator to include steel mounting plate is required

7.

Latching of door leaf must prevent inadvertent operation of opener during fire
exposure.

18. VIEWING LENSES
Make
ABUS
Chubb
Chubb
Doorscope
ERA
Hafele
HH
Hotel Gong system
Lane
Lockwood
Nikon
Pyropanel
Schlage
Yank
Note:

Type
2200
8V001, WS8, WS13
WS9
DS-1000
959.06.002 and .008
Model B-03
Model 006
160 Security Door Viewer
2200, 2180, 2170, 2160
Panaramic
DV004
Models 2160, 2170, 2180, 2200

Notes

1

Max.Rating
VP240
VP120
VP60
VP60
VP240
VP240
VP240
VP240
VP240
VP240
VP240
VP120
VP240
VP240

[PDS]

1. Special factory fitting methods are required for the Doorscope DS-1000.

© 2008 Pacific Door Systems Ltd

16

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
19. DOOR EDGE SEALS
Make

Code

Max. Rating

Firepro

FP1212

VP240

Firepro

FP1515

VP240

Lorient

FDBU20 Intumescent sill seals

VP240

Lorient

HP4002 intumescent perimeter seal

VP240

Lorient

IS7010si

VP240

Lorient

IS7020si

VP240

Lorient

IS7025si

VP240

Lorient

IS7080si

VP240

Lorient

IS7085si

VP240

Lorient

IS8010si

VP240

Lorient

IS8011si

VP240

Lorient

IS8020si

VP240

Lorient

IS8085si

VP240

Lorient

IS8090si

VP240

Lorient

IS8091si

VP240

Lorient

LE1212

VP240

Lorient

LE1515

VP240

Pacific Door Systems

Acoustic Compression Seal (bottom edge)

VP60

[PDS]

Pyropanel

Euroseal

VP120

[PDS]

Pacific Door Systems

PFS-3

VP240

[PDS]

Pacific Door Systems

TP390

VP60

[PDS]

Raven

RP4T

VP240

Raven

RP8

VP240

Raven

RP10 & RP10Si

VP240

Raven

RP23

VP240

Raven

RP24

VP240

Raven

RP25

VP240

Raven

RP38 & RP38Si (rebated or surface-fixed)

VP240

Raven

RP39

VP240

Raven

RP60

VP240

Raven

RP78 and RP78Si

VP240

Raven

RP93Si

VP240

Raven

RP99Si

VP240

Raven

RP114 Sill gap seal

VP240

Raven

RP120

VP240

Raven

RP150

VP240

© 2008 Pacific Door Systems Ltd

[PDS]

[PDS]

[PDS]

17

Datasheet: E02
Date: 3-03-08

HARDWARE LIST – Pyropanel Fire Doors
20. FIRE RESISTANT GLAZING
Insulation
Rating

Make

Maximum Specification with Integrity Rating

DTI Film Overlay

FW60/VP240

-

[PDS]

NEG Firelite

VP30 / FW30-1 / FW30-2 / VP60 / FW60

-

[PDS]

Georgian Wired

VP120 / FW60 / FW30-1 / FW30-2

-

[PDS]

Georgian Wired Clear
Laminated Float

VP30 / FW30-2

-

[PDS]

Schott Robax

VP240 / FW30-1 / FW30-2

-

[PDS]

Schott Pyran

VP120 / FW30-1 / FW30-2

-

[PDS]

Schott Vycor

VP240

-

[PDS]

Pyroceram

VP240 / FW60 / FW120

-

[PDS]

Pyrobel 16

FW30-1 / VP30 / VP60

30

[PDS]

Restrictions:

Datasheets for FW30-1 and FW30-2 should be consulted for further information on
approved glazing

© 2008 Pacific Door Systems Ltd

18



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Extract, Print high-res
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Creator Tool                    : Acrobat PDFMaker 8.1 for Word
Modify Date                     : 2008:03:03 09:08:34+13:00
Create Date                     : 2008:03:03 09:08:30+13:00
Metadata Date                   : 2008:03:03 09:08:34+13:00
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Format                          : application/pdf
Creator                         : Pacific Door Systems Ltd
Title                           : Hardware List VP & SP Doors
Document ID                     : uuid:28bd6578-b3a1-40fd-b89e-a0da8472c6ff
Instance ID                     : uuid:d2f5bbf4-0e85-4d67-85be-dbefc04496e5
Company                         : Pacific Door Systems Ltd
Part                            : 1
Conformance                     : B
Page Count                      : 18
Page Layout                     : OneColumn
Author                          : Pacific Door Systems Ltd
EXIF Metadata provided by EXIF.tools

Navigation menu