Tyco Fire & Building Products is a leading

manufacturer and distributor of water-based fire
suppression systems and components, offering one of
the broadest lines of fire protection system equipment
worldwide.
Continually expanding its capabilities through aggressive
research and product development, it provides its
customers effective fire protection and construction
solutions for residential, commercial, industrial, and
institutional buildings. Tyco Fire & Building Products
serves a diverse group of specifiers, including architects,
engineers, contractors, and associated industries with a
nationwide network of distribution and manufacturing
facilities. Tyco takes pride in the introduction of new and
innovative products, technologies and product application
extensions.
With over 150 years in the industry, Tyco Fire & Building
Products is uniquely qualified to provide and develop
cost effective solutions customized to any building
configuration and fire protection application. Our patented
solutions provide significant performance advantages with
lower installation and maintenance costs.
Tyco Fire & Building Products also offers the
industry’s most complete fire protection design
software package through its SprinkCAD® programs.

Table of Contents
AUTOMATIC Sprinklers
Standard Spray Sprinklers . . . . . . . . . . . . . . . . . 7 – 10
Extended Coverage Sprinklers  . . . . . . . . . . . . 11 – 16
Storage Sprinklers . . . . . . . . . . . . . . . . . . . . . . 17 – 22
Rapid Response™ Sprinklers . . . . . . . . . . . . . . 23 – 26
Dry Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . 27 – 30
Special Purpose Sprinklers  . . . . . . . . . . . . . . . 31 – 36
Sprinkler Accessories . . . . . . . . . . . . . . . . . . . . 37 – 38
Nozzles & Nozzle Accessories . . . . . . . . . . . . . 39 – 42

System Valves & Devices
Wet System Valves & Devices . . . . . . . . . . . . . 43 – 46
Dry System Valves & Devices . . . . . . . . . . . . . 47 – 50
Deluge & Preaction Systems . . . . . . . . . . . . . . 51 – 56
General Purpose Valves . . . . . . . . . . . . . . . . . . 57 – 60
Specialty Items  . . . . . . . . . . . . . . . . . . . . . . . . 61 – 64

PIPING & Electrical Products
Grooved Piping Products  . . . . . . . . . . . . . . . . 65 – 68
CPVC Pipe & Fittings  . . . . . . . . . . . . . . . . . . . 69 – 70
Electrical Devices  . . . . . . . . . . . . . . . . . . . . . . 71 – 76

Specialty Systems
Foam Systems . . . . . . . . . . . . . . . . . . . . . . . . . 77 – 82
Aquamist® Systems . . . . . . . . . . . . . . . . . . . . . 83 – 85

T Yco Fire & Building Products
Leading the Way for More than 150 years
In 1881, industry pioneer Frederick
Grinnell patented the first “sensitive”
automatic fire sprinkler incorporating a
number of features still found in modern
day units. Since that time, many of the
major advancements in fire
sprinkler technology can
be attributed to Grinnell
and other leading names
in the industry that are
now part of Tyco Fire &
Building Products.
The history of our company
is one of tremendous growth
through organic development
and acquisition with over 150 years in the industry,
to create a single powerful global resource for owners,
and those to whom they turn for engineering advice and
support. Today our company is proud to
be associated with our corporate and
legacy brands that continue to operate
on the cutting edge of fire protection
innovation, mechanical applications and
product performance.

We stand behind every product we manufacture
by offering the industry’s only 10-year limited
warranty*, that’s up to ten times longer than our
competitors’ warranties.
(Full warranty details can be found on all of our
current product technical data sheets, or at our
website at www.tyco-fire.com.)
All metric measurements throughout this catalog are based on
U.S. standard-to-metric conversions. Metric specifications may
vary from country to country.

We Cover All The Action



Fire Protection General Products Catalog

Tyco Fire & Building Products

The industry leader
Best-in-class solutions start with best-in-class technology,
and only Tyco Fire & Building Products offers more of
both. That’s how we are able to simplify installation
and improve the performance of fire protection and
mechanical systems, providing the owner with the
lowest installed cost. Here are just some of the
industry-leading technologies we have developed:

• Extended Coverage Ordinary and Light Hazard
Fire Sprinkler Technology
• The First Residential Sprinklers for Life Safety
Purposes
• Electronic Quick Opening Accelerator for Dry
Sprinkler Systems
• Back-to-Back CPVC Fittings for Residential Fire
Protection
• Sprinkler System Design Software (SprinkCAD)
and Fluid Delivery Time Calculation Software

In addition, Tyco Fire & Building Products provides
turnkey Engineered Systems’ a choice of fully integrated
solutions focused on specialty applications in Europe, the
Middle East, the Americas, and Asia/Pacific, including:
• Pump/Valve Skid Packages
• Water Mist Systems for Fire Protection
• Valve Packages for Seawater and Harsh
Environments
Tyco Fire & Building Products has made a commitment
to the world-class performance of its products and,
as a result, has received independent approvals and
certifications from industry agencies globally.
Our state-of-the-art international manufacturing facilities
have all been granted ISO 9000 approvals, and are
routinely audited by independent testing agencies for
quality and conformance. We also participate in more
than 70 National Fire Protection Association committees
and a number of international standards and
code-making bodies.

FM
Underwriters
Laboratories Inc.

Underwriters
Laboratories Inc.
for use in Canada

T yco Fire & Building Products

Scientific
Services
Laboratory

Verband der
Schadenversicherer

Factory Mutual
Research
Corporation

Loss Prevention
Certification Board
in association with
AB & Lloyds

Fire Protec tion General Products Catalog

T yco F i r e & B u i l d i n g P r o d u c t s

• Storage Fire Protection Solutions such as K-14,
K-25 and K-17 ESFR Technology. It was the first
of the ESFR technology, and we pioneered it.



Standard Spray Sprinklers

a p p l icatio n s :
responses: standard and quick. Together they offer a wide
range of sprinklers from which to choose when designing
a standard coverage fire sprinkler system.

Standard Response Sprinklers are intended for use
in fire sprinkler systems designed in accordance with the
installation rules recognized by the applicable Listing or
Approval agency. There are two types or response elements:
bulb and solder.
Series TY-B bulb type sprinklers are available in a variety of
attractive finishes that blend well with their surroundings.
When in service, a small bubble in the fluid contained in
the bulb compensates for normal temperature changes.
When heated, the fluid in the bulb expands and shatters
the bulb, allowing water to be discharged.
Series TY-L solder type sprinklers employ a link whose
two sections are joined by solder with a predetermined
temperature rating. Heat absorbed by the link is conducted
directly to the soldered joint. When the solder melts, the
link springs apart, releasing water that strikes the sprinkler
deflector.

T yco Fire & Building Products

• Office
Buildings
• Banks
• Factories
• Libraries

• Theaters
• Light &
Ordinary
Hazard
Occupancies
• Schools

Quick Response Sprinklers are designed with a
3mm bulb or small nickel link to react more quickly at
the specified temperature. They are available in pendent,
upright, recessed, concealed, vertical sidewall, and
horizontal sidewall styles.
The narrow profile bulbs and attractive finishes of the
Series TY-FRB provide specifiers with a wide variety of
sprinklers for use in quick response applications. The
versatile Quick Response TY-FRL Series provides the
specifier with a solder type sprinkler for most commercial
and industrial applications.

Fire Protec tion General Products Catalog

Standard Spray Sprinklers

Standard Spray Sprinklers are comprised of two



Au to mat i c S p r i n k l e r s

Standard Spray Sprinklers
T Y-B
Upright, Pendent & Recessed Pendent
• All hazard
• 5 mm bulb
•	Discharges a hemispherical water spray
pattern in the area beneath the sprinkler
• Small frame, narrow profile bulb

K Factor	K=5.6 (80,6),

K=8.0 (115,2)
1
3
Thread Size	 ⁄2" NPT • ⁄4" NPT
Escutcheon	Style 10 • Style 40
Escutcheon finish	White Coated, Chrome
Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome
Plated, White Polyester,
Lead Coated, Wax Coated,
Wax over Lead Coated
SIN
TY3151, TY3251, TY4151,
TY4251, TY4851, TY4951
Tech Data	TFP151

Horizontal, Recessed Horizontal & Vertical Sidewall
• Light hazard/Ordinary hazard

K Factor

• 5 mm bulb

Thread Size	 ⁄2" NPT

• Small frame

Escutcheon	Style 10

• Unique deflector design of the horizontal
sidewall sprinkler results in smaller profile

Escutcheon finish	White Coated, Chrome

• Designed for installation along a wall or on
the side of a beam just beneath a smooth
ceiling

Sprinkler Finish	Natural Brass, Chrome

Sta n da r d Sp r ay Sp r i n k l e r s

• Water discharge is directed primarily outward
and downward in a quarter spherical pattern
• Special deflector on the vertical sidewall
sprinkler allows it to be installed in either a
pendent or upright position

K=5.6 (80,6)
1

Plated, Brass Plated

Plated, White Polyester,
Lead Coated, Wax Coated,
Wax over Lead Coated
SIN	TY3351, TY3451
Tech Data	TFP161
• Sidewall sprinklers are often used in lieu
of standard pendent or upright sprinklers
due to building construction, economic
considerations, or aesthetics

T Y-FRB
Upright, Pendent & Recessed Pendent
• Light hazard/Ordinary hazard
light hazard K=2.8 (40,3)

K Factor	K=2.8 (40,3) • K=4.2 (60,5)

• 3 mm bulb

Thread Size	1⁄2" NPT • 3⁄4" NPT

• Hemispherical water spray pattern in the
area beneath the sprinkler

Escutcheon	Style 10 • Style 20

• Small frame and narrow profile bulb enhance
appearance

Escutcheon finish	White Coated, Chrome

K=5.6 (80,6) • K=8.0 (115,2)

Style 30 • Style 40
Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester,
Lead Coated
SIN	TY1131, TY1231, TY2131,
TY2231, TY3131, TY3231,
TY4131, TY4231, TY4831,
TY4931
Tech Data	TFP171
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.



Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

Standard Spray Sprinklers

T Y-FRB
Horizontal, Recessed Horizontal Sidewall & Vertical Sidewall
•	Light hazard/Ordinary hazard

K Factor	K=5.6 (80,6)

• 3 mm bulb

Thread Size	 ⁄2" NPT

•	Designed for use in applications where
aesthetics must be considered or where
building construction makes the installation
of standard pendent or upright sprinklers
impractical

Escutcheon	Style 10 • Style 20

• Vertical sidewall sprinkler can be installed in
either the pendent or upright position along
a wall or the side of a beam and just below a
smooth ceiling

1

Escutcheon finish	White Coated, Chrome

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester,
Lead Coated
SIN	TY3331, TY3431
Tech Data	TFP176

RFII “Royal Flush II”
Pendent Concealed
• Light hazard/Ordinary hazard

K Factor	K=5.6 (80,6)

• 5 mm bulb (standard)
3 mm bulb (quick)

Thread Size	 ⁄2"

• Concealed in an enclosed escutcheon plate
with flat cover for use in those applications
where aesthetics is a primary consideration

Plated, Natural Brass
Plated, White Polyester
Painted, Custom
SIN	TY3551, TY3531
Tech Data	TFP181

Sprinkler Finish	Cover Plate: Chrome

• Internally threaded closure with
1
⁄2" (12,7 mm) of adjustment
• Available with optional dust
and air seal

T Y-L
Upright, Pendent & Recessed Pendent
• All hazards
• Solder type
• Discharges a hemispherical water spray
pattern in the area beneath the sprinkler

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1

Thread Size	 ⁄2" NPT •

3

⁄4" NPT
Escutcheon	Style 20 • Style 30
Escutcheon finish	White Coated, Chrome
Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome
Plated, Lead Coated, Wax
Coated, Wax over Lead
Coated
SIN	TY3111, TY3211, TY4111
TY4211, TY4811, TY4911
Tech Data	TFP110

Sta n da r d Sp r ay Sp r i n k l e r s

• Separable, two-piece design of the mounting
cup and cover plate allows installation of the
sprinklers and pressure testing of the fire
protection system prior to installation of a
suspended ceiling or application of the finish
coating to a fixed ceiling

1

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog



Au to mat i c S p r i n k l e r s

Standard Spray Sprinklers
T Y-L
Horizontal Sidewall
• Light hazard / Ordinary hazard

K Factor	K=5.6 (80,6)

• Solder type

Thread Size	 ⁄2" NPT

• Suited for hotels, nursing homes and
hospitals

Sprinkler Finish	Natural Brass, Chrome

• Design allows piping to be confined to
corridors, closets or service areas

1

Plated, Lead Coated, Wax
Coated, Wax over Lead
Coated
SIN	TY3311
Tech Data	TFP120

T Y-FRL
Upright, Pendent & Recessed Pendent
• Light hazard/Ordinary hazard
light hazard K=2.8 (40,3)
• Solder type
• Typically used in hotels, motels, office
buildings and other commercial and
industrial applications

K Factor	K=2.8 (40,3) • K=5.6 (80,6)

K=8.0 (115,2)
1
3
Thread Size	 ⁄2" NPT • ⁄4" NPT
Escutcheon	Style 20
Escutcheon finish	White Coated, Chrome
Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome
Plated
SIN	TY1121, TY1221, TY3121
TY3221, TY4121, TY4221
Tech Data	TFP130

Sta n da r d Sp r ay Sp r i n k l e r s

Horizontal Sidewall
• Solder type

K Factor	K=5.6 (80,6)

• Light hazard/Ordinary hazard

Thread Size	 ⁄2" NPT

• Designed for compact installation along a
wall or on the side of a beam just beneath a
smooth ceiling

Sprinkler Finish	Natural Brass, Chrome

• Generally used in lieu of pendent or upright
sprinklers because of aesthetics, building
construction or economic considerations

Tech Data	TFP140

1

Plated

SIN	TY3321

T Y-QRF
Flush Pendent
• Solder type

K Factor	K=5.6 (80,6)

• Light hazard/Ordinary hazard

Thread Size	 ⁄2" NPT

• Features separable escutcheon with
3
⁄8" vertical adjustment

Escutcheon finish	Chrome Plated, White

1

Polyester, Black
Sprinkler Finish	Chrome Plated, White
Polyester, Black
SIN	TY3261
Tech Data	TFP190

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

10

Fire Protection General Products Catalog

Tyco Fire & Building Products

a p p l icatio n s :
Extended Coverage Sprinklers are intended for the
protection of areas larger than those specified in standard
installation rules and for specific light, ordinary, or extra
hazard occupancies. Extended coverage sprinklers are
available in both standard response (EC) and quick
response (QR-EC). They are available in upright, pendent,
horizontal sidewall and recessed horizontal sidewall. These
sprinklers are typically used in hotels, restaurants, office
buildings, warehouses, and other areas where it is desirable
to reduce the overall number of required sprinklers.

T yco Fire & Building Products

• Office
Buildings

• High-Piled
Storage

• Hotels

• “Big-Box”
Retailing

• Hospitals
• Libraries

Fire Protec tion General Products Catalog

Ex tENded Coverage Sp r i n k l e r s

Extended Coverage Sprinklers

11

Au to mat i c S p r i n k l e r s

extended coverage Sprinklers
EC-25
Upright
•	All hazard

K Factor	K=25.2 (362,9)

•	Solder type

Thread Size	1" NPT or ISO 7-R1

•	Extended coverage area/density

Sprinkler Finish	Natural Brass

•	Deflector design allows maximum coverage
area of 14' X 14' (4,3m X 4,3m)

SIN	TY9128
Tech Data	TFP213

• For use in high density applications such
as “big box” retailing, extra hazard, and
high-piled storage occupancies
• Minimum operating pressure of
7 psi (0,48 bar)

ec - 1 7
Pendent & Recessed Pendent
• Solder type

K Factor	K=16.8 (241,9)

• Extended coverage for higher density
applications

Thread Size	 ⁄4" NPT

• Recessed configuration is ideal for retail
applications

Polyester, Chrome Plated
SIN	TY7228
Tech Data	TFP215

• Maximum 196 sq. ft./sprinkler spacing
(14 ft. x 14 ft. spacing)

3

Sprinkler Finish	Natural Brass, White

e x t e n d e d co v e r ag e Sp r i n k l e r s

• Can reduce the number of installed
sprinklers by nearly 50%
• Hydraulic calculations based on actual
spacing (sxl rule)
• Intended for area/density applications
of 0.25 gpm/sq. ft. and higher

EC-11 & EC-14
Upright, Pendent & Recessed Pendent
• Light hazard/Ordinary hazard

K Factor	K=11.2 (161,3), K=14.0

(201,6)

• 3 mm bulb

3

• Nominal K=11.2 designed for coverage
applications of 14' x 14' (4,3 m x 4,3 m)
up to 20' x 20' (6,1 m x 6,1 m)

Thread Size	 ⁄4" NPT

• Nominal K=14.0 designed for coverage
applications of 16' x 16' (4,9 m x 4,9 m)
up to 20' x 20' (6,1 m x 6,1 m)

Escutcheon finish	White Coated, Chrome

• Low profile glass bulb spray sprinklers

Escutcheon

Style 30 • Style 40 • Style

60

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester,
Lead Coated
SIN	TY5137, TY5237, TY6137,
TY6237
Tech Data	TFP220

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

12

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

extended coverage Sprinklers

EC-8
Pendent & Recessed Pendent
• Light hazard

K Factor	K=8.0 (115,2)

• 3 mm bulb

Thread Size	 ⁄4" NPT

• Covers areas as large as
20' x 20' (6,1 m x 6,1 m)

Escutcheon	Style 30 • Style 40

3

Escutcheon finish	White Coated, Chrome

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

SIN	TY4232
Tech Data	TFP223

ec - 5
Pendent & Recessed Pendent
• Light hazard

K Factor	K=5.6 (80,6)

• 3 mm bulb

Thread Size	 ⁄2" NPT

• Coverage up to
20' x 20' (6,1 m x 6,1 m)

Escutcheon

1

Style 50

Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome
Plated, White Polyester
SIN	TY3232
Tech Data	TFP228

Horizontal Sidewall & Recessed Horizontal Sidewall
• Light hazard

K Factor	K=5.6 (80,6)

• 3 mm bulb

Thread Size	 ⁄2" NPT

• Coverage up to
16' x 24' (4,9 m x 7,3 m)

Escutcheon

1

Style 50

Escutcheon finish	White Coated, Chrome

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

SIN	TY3302
Tech Data	TFP298

e x t e n d e d co v e r ag e Sp r i n k l e r s

Escutcheon finish	White Coated, Chrome

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

13

Au to mat i c S p r i n k l e r s

extended coverage Sprinklers
T Y-FRB
Horizontal & Recessed Horizontal Sidewall
• Light hazard
• 3 mm bulb
• Two-piece escutcheon converts sidewall
sprinklers into low profile sprinkler
assemblies with coverage areas up to
16' x 22' (4,9 m x 6,7 m) for K=5.6 and
16' x 24' (4,9 m x 7,3 m) for K=8.0
• Provides 3⁄4" NPT (19,1 mm) of horizontal
adjustment from the flush sidewall position

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1

Thread Size	 ⁄2" NPT •

3

⁄4" NPT
Escutcheon	Style 10 • Style 20
Style 30 • Style 40
Escutcheon finish	White Coated, Chrome
Plated, Brass Plated
Sprinkler Finish	Natural Brass, White
Polyester, Chrome Plated
SIN	TY3332, TY4332
Tech Data	TFP296

E LO S W - 2 0 / S W - 2 4
Horizontal Sidewall
• Ordinary hazard

K Factor	K=11.2 (161,3)

• 3 mm bulb

Thread Size	 ⁄4" NPT

• Utilizes an Extra Large Orifice (ELO) that
allows low water pressure requirements,
while providing the flow required for
extended coverage

Sprinkler Finish	Natural Brass, Chrome

e x t e n d e d co v e r ag e Sp r i n k l e r s

• SW-20 Listed to a 16'-0" (4,9 m) wide and a
20'-0" (6,1 m) throw maximum coverage area

3

Plated, White Polyester
SIN	TY5332, TY5337
Tech Data	TFP230

• SW-24 Listed to a 16'-0" (4,9 m) wide and a
24'-0" (7,3 m) throw maximum coverage area

T Y-FRL
Horizontal Sidewall
• Light hazard

K Factor	K=5.6 (80,6) •K=8.0 (115,2)

• Solder type

Thread Size	 ⁄2" NPT •

• K=5.6 for QR-EC coverage areas up to
16' x 20' (4,9 m x 6,1 m) and
18' x 16' (5,5 m x 4,9 m)

Sprinkler Finish	Natural Brass, Chrome

• K=8.0 for EC and QR-EC coverage areas up
to 16' x 24' (4,9 m x 7,3 m)

Tech Data	TFP280

1

3

⁄4" NPT

Plated

SIN	TY3322, TY4322

• QR-EC coverage areas up to 20' x 16'
(6,1 m x 4,9 m)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

14

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

extended coverage Sprinklers

CHEC
Concealed Horizontal Extended Coverage Sidewall
• Light hazard

K Factor	K=8.0 (115,2)

• 3 mm bulb

Thread Size	 ⁄4" NPT

• Attractive concealed contour

Sprinkler Finish	Bright White, Chrome

3

• Coverage up to 16' x 22' (4,9 m x 6,7 m)
• Lowest flows & pressures allowed by
NFPA 13

Plated, Custom
SIN	TY4332
Tech Data	TFP265

• 1⁄2" adjustment
• Push on / thread off option
• 12" maximum deflector distance from ceiling
• No “Slots” in cover plate

E LO C
Concealed Pendent
• Light hazard

K Factor	K=11.2 (161,3)

• Covers 400 sq. ft. (37,2 m ) using less
pressure than a standard 1⁄2" (12,7 mm)
sprinkler at 225 sq. ft. (20,3 mm)
• Available with optional dust and air seal
• Concealed in an enclosed escutcheon plate
with flat cover for use in those applications
where aesthetics is a primary consideration

3

Thread Size	 ⁄4" NPT
Sprinkler Finish	Cover Plate:

Chrome Plated, Brushed
Chrome Plated, Brass
Plated, Bright Brass, White
Painted, Bright White, Off
White, Custom
SIN	TY5522
Tech Data	TFP250

RFII (Royal Flush II)
Concealed Pendent
• Light hazard

K Factor	K=5.6 (80.6)

• 3 mm bulb

Thread Size	 ⁄2" NPT

• Maximum 18' x 18' (5,5 m x 5,5 m) QR Listing

Sprinkler Finish	Cover Plate:

• Concealed in an enclosed escutcheon plate
with flat cover for use in those applications
where aesthetics is a primary consideration
• Separable, two-piece design of the mounting
cup and cover allows installation of the
sprinklers and pressure testing of the fire
protection system prior to installation of a
suspended ceiling or application of the finish
coating to a fixed ceiling

1

Chrome Plated, Brass
Plated, White Painted,
Custom
SIN	TY3532
Tech Data	TFP260
• Internally threaded closure with 1⁄2"
(12,7 mm) of adjustment

e x t e n d e d co v e r ag e Sp r i n k l e r s

2

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

15

Storage Sprinklers

Storage Sprinklers are intended for use in specific
applications, including the protection of high-piled and
rack storage of a variety of finished goods. These sprinklers
can provide more water at lower pressures or more water
over a greater area of coverage. In many instances, use of
the storage sprinklers can eliminate the need for additional
in-rack sprinklers.
Intermediate level (in-rack) sprinklers are designed for use
in rack storage sprinkler systems, where their thermally
sensitive elements must be shielded from the water spray of
higher elevation sprinklers that could operate during a fire.
Intermediate Level Sprinklers are also used in applications

T yco Fire & Building Products

• High-Piled
Storage

• Warehouse

• In-Rack Storage

• High Challenge
Occupancies

such as beneath open gridded catwalks. These sprinklers
are intended for use in fire sprinkler systems designed in
accordance with the standard installation rules recognized
by the applicable Listing or Approval agency (e.g., FM
approval and UL Listing is based on NFPA requirements).

Fire Protec tion General Products Catalog

STORAGE Sprinklers

a p p l icatio n s :

17

Au to mat i c S p r i n k l e r s

storage Sprinklers
ESFR-25™
Pendent
• Early Suppression, Fast Response (ESFR)

K Factor	K=25.2 (362,9)

• Solder type

Thread Size	1" NPT or ISO 7-R1

• Designed for the protection of rack storage

Sprinkler Finish	Natural Brass

• Eliminates many of the requirements for
in-rack sprinklers

SIN	TY9226

• Materials may be stored up to 40' (12,2 m)
high, in buildings up to 45' (13,7 m)
• Direct attack on burning fuel by improved
heavy sprinkler discharge
• Patented frame design substantially reduces
the frame shadow effects that often produce
non-uniformity in spray pattern

Tech Data	TFP312

• Novel orifice seal and unique fast response
link design are the very latest in sprinkler
technology

ESFR-17
Pendent
•	Early Suppression, Fast Response (ESFR)

K Factor	K=16.8 (241,9)

•	Solder type

Thread Size	 ⁄4" NPT

• Primarily designed for use in ceiling only
sprinkler systems

Sprinkler Finish	Natural Brass

• Use of this sprinkler is especially
advantageous as a means of eliminating the
use of in-rack sprinklers when protecting
rack storage arrangements

3

SIN	TY7226
Tech Data	TFP315

• Operates at lower pressure than ESFR-1

Sto r ag e Sp r i n k l e r s

Upright
•	Early Suppression, Fast Response (ESFR)

K Factor	K=16.8 (241,9)

•	Solder type

Thread Size	 ⁄4" NPT

• Primarily designed for use in ceiling only
sprinkler systems

Sprinkler Finish	Natural Brass

• Use of this sprinkler is especially
advantageous as a means of eliminating
the use of in-rack sprinklers when protecting
rack storage arrangements

3

SIN	TY7126
Tech Data	TFP316

• Unique, upright design and large
K Factor overcome many pendent
obstruction problems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

18

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

storage Sprinklers

ESFR-1
Pendent
• Early Suppression, Fast Response (ESFR)

K Factor	K=14.0 (201,6)

•	Solder type

Thread Size	 ⁄4" NPT

• Designed for the protection of rack storage

Sprinkler Finish	Natural Brass

• Eliminates many of the requirements for
in-rack sprinklers

SIN	TY6226

• Direct attack on burning fuel by improved
heavy sprinkler discharge

3

Tech Data	TFP318

• Patented frame design substantially reduces
the frame shadow effects that often produce
non-uniformity in spray pattern

u ltr a k - 1 7
Upright, Specific Application Control Mode
• 5 mm bulb

K Factor	K=16.8 (241,9)

•	Control mode sprinkler

Thread Size	 ⁄4" NPT

• 155°F/68°C & 200°F/93°C

Sprinkler Finish	Natural Brass

• Full-scale fire testing has shown that the
Ultra K17 can control fires with commodities
up to Group A plastics, and eliminate the
need for in-rack sprinklers

SIN	TY7153

• Reduced end head pressures often eliminate
the need for a fire pump

3

Tech Data	TFP330

• Approved for storage heights of
25' (7,6 m) and building heights to
30' (9,1 m)

Upright, Specific Application Control Mode, 286° F
• 5 mm bulb

K Factor	K=16.8 (241,9)

•	Control mode sprinkler

Thread Size	 ⁄4" NPT

• 286°F/141°C

Sprinkler Finish	Natural Brass

3

Sto r ag e Sp r i n k l e r s

Tech Data	Contact TFBP for details

K17-231
Pendent & Upright
• 5 mm bulb

K Factor	K=16.8 (241,9)

• Very large orifice sprinkler for use in
high challenge storage occupancies

Thread Size	 ⁄4" NPT

• Low-pressure requirement can save cost by
reducing branch line size, taking advantage
of maximized spacing, and upgrading
existing densities

3

Sprinkler Finish	Natural Brass
SIN	TY7151, TY7251
Tech Data	TFP332

• Can operate at pressures as low as
7 psi (0,48 bar)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

19

Au to mat i c S p r i n k l e r s

storage Sprinklers
E LO - 2 3 1 B
Pendent & Upright
• 5 mm bulb

K Factor	K=11.2 (161,3)

• Extra large orifice sprinklers proven for
storage occupancies through full-scale
fire testing

Thread Size	 ⁄2" NPT •

• Designed to control high challenge fires
with relatively low required pressures

1

3

⁄4" NPT

Sprinkler Finish	Natural Brass, Chrome

Plated, Lead Coated, Wax
Coated, Wax over Lead
Coated
SIN	TY5151, TY5251, TY5851
Tech Data	TFP342

E LO - 2 3 1 F R B
Pendent & Upright
• 3 mm bulb

K Factor	K=11.2 (161,3)

• Extra large orifice sprinklers proven for
storage occupancies through full-scale
fire testing

Thread Size	 ⁄4" NPT

• Designed to control high challenge fires
with relatively low required pressures

SIN	TY5131, TY5231

3

Sprinkler Finish	Natural Brass, Chrome

Plated

Tech Data	TFP344

E LO - 2 3 1
Pendent & Upright
• Solder type

K Factor	K=11.2 (161,3)

• Extra large orifice sprinklers proven for
storage occupancies through full-scale fire
testing

Thread Size	 ⁄2" NPT •

Sto r ag e Sp r i n k l e r s

• Designed to control high challenge fires
with relatively low required pressures

1

3

⁄4" NPT

Sprinkler Finish	Natural Brass, Chrome

Plated, Lead Coated, Wax
Coated, Wax over Lead
Coated
SIN	TY5111, TY5211, TY5811
Tech Data	TFP340

ld "Large Drop"
Upright
• 5 mm bulb

K Factor	K=11.2 (161,3)

• Control mode sprinkler

Thread Size	 ⁄4" NPT

• Designed for the protection of high-piled
storage

Sprinkler Finish	Natural Brass

• Can provide a higher level of protection
than standard spray sprinklers

3

SIN	TY5153
Tech Data	TFP335

• Can provide an advantage by eliminating
in-rack sprinklers
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

20

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

storage Sprinklers

T Y-b
Pendent & Upright, Intermediate Level
• 5 mm bulb
• Intermediate level (in-rack) with shield
• Factory assembled unit having an integral
water shield
• Used where sprinkler guards are not required

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1
3
Thread Size	 ⁄2" NPT • ⁄4" NPT
Sprinkler Finish	Natural Brass, Lead Coated,
Wax Coated, Wax over
Lead Coated
SIN	TY3153, TY3251, TY4153,
TY4251
Tech Data	TFP351

ty - frb
Pendent & Upright, Intermediate Level
• 3 mm bulb
• Intermediate level with shield
• Factory assembled unit having an integral
water shield
• Used where sprinkler guards are not required

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1
3
Thread Size	 ⁄2" NPT • ⁄4" NPT
Sprinkler Finish	Natural Brass, Lead Coated
SIN	TY3133, TY3231, TY4133,
TY4231
Tech Data	TFP356

ty - l
Pendent & Upright, Intermediate Level
• Intermediate level with shield
• Factory assembled unit having an integral
water shield
• Used where sprinkler guards are not required

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1
3
Thread Size	 ⁄2" NPT • ⁄4" NPT
Sprinkler Finish	Natural Brass
SIN	TY3113, TY3211, TY4113,
TY4211
Tech Data	TFP350

ty - fr l
Pendent & Upright, Intermediate Level
• Solder type
• Intermediate level with shield
• Factory assembled unit having an integral
water shield.
• Used where sprinkler guards are not required

K Factor	K=5.6 (80,6) • K=8.0

(115,2)
1

Thread Size	 ⁄2" NPT •

3

⁄4" NPT
Sprinkler Finish	Natural Brass, Chrome
Plated
SIN	TY3123, TY3221, TY4123,
TY4221
Tech Data	TFP355

Sto r ag e Sp r i n k l e r s

• Solder type

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

21

Au to mat i c S p r i n k l e r s

storage Sprinklers
s p ri n k l er g u a r d s

Model G1 & G4 Sprinkler Guards
Model G1/S1 & G4/S3 Guards with Shields
• Designed for use with specific types of Series
TY-B, TYFRB, TY-L, and TY-FRL Sprinklers
that may be located in areas that make
them susceptible to mechanical or physical
damage

Finishes	Red Painted,

Chrome

Tech Data	TFP780

• Rugged guard design to minimize possible
damage to sprinklers
• Shields are for use in storage racks or
beneath grated mezzanine, or other areas
requiring the sprinklers to be shielded from
possible discharge from sprinklers above
• Can be used with either 1⁄2" or 3⁄4" NPT
sprinklers

G4/S3 with Shield
G4

G1
S1

Sto r ag e Sp r i n k l e r s

Model G2 Sprinkler Guard, Model WS-2 Shield, and
Model WSG-2 Sprinkler Guard with Shield
• Designed for use with Series ELO-231,
ELO-231B, or ELO-231FRB Sprinklers that
may be located in areas that make them
susceptible to mechanical or physical
damage

Finishes	Red Painted,

Chrome

Tech Data	TFP782

• Rugged guard design to minimize possible
damage to sprinklers

G2

• Shields are for use in storage racks or
beneath grated mezzanine, or other areas
requiring the sprinklers to be shielded from
possible discharge from sprinklers above
• Can be used with either 1⁄2" or 3⁄4" NPT
sprinklers
WSG-2 with Shield
WS-2 Shield

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

22

Fire Protection General Products Catalog

Tyco Fire & Building Products

Rapid Response™ Sprinklers

a p p l icatio n s :

• Apartments
Rapid Response™ Home Fire Sprinkler Systems
• Developed specifically for residential occupancies
• The most complete system on the market today
from a single manufacturer
• Features BlazeMaster® CPVC pipe and fittings,
making installation quick, easy, flexible, and
affordable

• Student
Housing

• Hotels
• Beamed
Ceilings
• Sloped Ceilings

in the industry. Other advantages are listings for beam
ceilings and for sloped ceilings to an 8:12 pitch. These
unique features avoid obstruction to the sprinkler's
discharge pattern without adding additional sprinklers.

• Tyco’s exclusive ten-year limited warranty lets you
install with confidence
• Product line meets all NFPA standards
• Components are all UL listed for residential
installations
Residential Sprinklers offer the optimum design and
flow characteristics for all residential applications. With
k-factors as low as 4.2, the flow requirements are the lowest

T yco Fire & Building Products

We can match any Sherwin Williams color
for sprinklers with this icon.

Fire Protec tion General Products Catalog

R apid Response™ Sprinklers

• Single Family
Homes

23

Au to mat i c S p r i n k l e r s

rapid response™ Sprinklers
LFII
Pendent & Recessed Pendent
• 3 mm bulb type

K Factor	K=4.9 (70,6)

• Approved for special applications with
beamed ceilings

Thread Size	 ⁄2" NPT

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

1

Escutcheon	Style 20
Sprinkler Finish	White Polyester, Chrome

Plated, Natural Brass

SIN	TY2234
Tech Data	TFP400

Pendent & Recessed Pendent
• 3 mm bulb type

K Factor	K=3.0 (43,2)

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, in wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

Thread Size	 ⁄2" NPT

1

Escutcheon	Style 20
Sprinkler Finish	White Polyester, Chrome

Plated, Natural Brass
SIN	TY1234
Tech Data	TFP402

r a p i d r e s p o n s e™ Sp r i n k l e r s

Horizontal & Recessed Horizontal Sidewall
• 3 mm bulb type

K Factor	K=4.4 (63,4)

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

Thread Size	 ⁄2" NPT

1

Escutcheon	Style 20
Sprinkler Finish	White Polyester, Chrome

Plated, Natural Brass
SIN	TY2334
Tech Data	TFP412

Horizontal & Recessed Horizontal Sidewall
• 3 mm bulb type

K Factor	K=4.2 (60,5)

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

Thread Size	 ⁄2" NPT

1

Escutcheon	Style 20
Sprinkler Finish	White Polyester, Chrome

Plated, Natural Brass
SIN	TY1334
Tech Data	TFP410

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

24

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

rapid response™ Sprinklers

LFII
Flat Plate Concealed Pendent
• Solder type

K Factor	K=4.9 (70,6)

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, in wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R, and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

Thread Size	 ⁄2" NPT

1

Sprinkler Finish	Cover Plate:

Flat White, Bright White,
Chrome, Custom
SIN	TY3596
Tech Data	TFP442

• Cover plate conceals sprinkler components
above the ceiling

Flat Plate Concealed Pendent
• Solder type

K Factor

K=4.2 (60,5)

• Can be used for horizontal and
sloped ceilings

Thread Size	 ⁄2" NPT

• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D and in wet pipe
residential sprinkler systems for residential
occupancies up to and including four stories
in height per NFPA 13R

Flat White, Bright White,
Chrome, Custom
SIN	TY2596
Tech Data	TFP440

1

Sprinkler Finish	Cover Plate:

• Cover plate conceals sprinkler components
above the ceiling

Domed Plate Concealed Pendent
• Can be used for horizontal and sloped
ceilings
• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, in wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

K=4.9 (70,6)
1
Thread Size	 ⁄2" NPT
Escutcheon	Style 20
Sprinkler Finish	Cover Plate:
Flat White, Bright White,
Chrome, Custom
SIN	TY2234
Tech Data	TFP450
K Factor

• Cover plate conceals sprinkler components
above the ceiling

Flush Pendent and Horizontal Sidewall
• Solder type
• Pendent model is approved for special
applications with beamed ceilings
• Used in wet pipe residential sprinkler
systems for one/two-family dwellings and
mobile homes per NFPA 13D, in wet pipe
residential occupancies up to and including
four stories in height per NFPA 13R, and in
wet pipe sprinkler systems for the residential
portions of any occupancy per NFPA 13

K=4.2 (60,5)
1
Thread Size	 ⁄2" NPT
escutcheon Finish	White, Chrome, Black,
Antique Brass
Sprinkler Finish	White, Chrome, Black,
Antique Brass
SIN
TY2284, TY2384
Tech Data
TFP420, TFP425
K Factor

r a p i d r e s p o n s e™ Sp r i n k l e r s

• 3 mm bulb type

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

25

Au to mat i c S p r i n k l e r s

rapid response™ Sprinklers
l fii

•

N F PA 1 3 O p ti m i z e d S p ri n k l er s

The large orifice 6.9 K, 5.8 K and 5.6 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density
NFPA 13 design requirement, and are generally used for installations in excess of four stories. They are optimized for residential
applications where this higher water-flow demand is required, and can meet those requirements with less pressure and smaller
pipe sizes.

Pendent, Recessed Pendent & Domed Concealed
• 3 mm bulb type

K Factor	K=6.9 (99,4)

• Used in wet pipe sprinkler systems for
the residential portions of any occupancy
per NFPA 13

Thread Size	 ⁄4" NPT

3

Escutcheon	Style 30
Escutcheon finish	White, Chrome, Brass
Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester
cover plate Finish	Flat White, Bright White,
Chrome, Custom
SIN	TY4234
Tech Data	TFP408

Horizontal & Recessed Horizontal Sidewall Sprinklers
• 3 mm bulb type

K Factor	K=5.8 (83,5)

• Can be used for horizontal and
sloped ceilings

Thread Size	 ⁄2" NPT

1

Escutcheon	Style 20

r a p i d r e s p o n s e™ Sp r i n k l e r s

Sprinkler Finish	White Polyester, Chrome

Plated, Natural Brass
SIN	TY4334
Tech Data	TFP417

Horizontal & Recessed Horizontal Sidewall
• 3 mm bulb type

K Factor	K=5.6 (80,6)

• Can be used for horizontal and sloped
ceilings

Thread Size	 ⁄2" NPT

1

Escutcheon	Style 20
Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester
SIN	TY3334
Tech Data	TFP415

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

26

Fire Protection General Products Catalog

Tyco Fire & Building Products

Dry Sprinklers

Dry Sprinklers

have been specifically designed for areas in
which the sprinkler may be subjected to freezing conditions.
These sprinklers have been developed for use in all standard
applications, as well as multiple unique scenarios. TFBP Dry
Sprinklers are available in both quick and standard response,
and come in a variety of finishes. These features, and the
advanced engineering in the development of these sprinklers,
offer the industry the most complete line of dry sprinklers
available. Most models are listed in lengths up to 4'-0". The
extended escutcheon option has up to 3" of adjustment.

T yco Fire & Building Products

• Unheated Warehouses
• Freezing Conditions
• Loading Docks
• Covered Exterior Platforms

Fire Protec tion General Products Catalog

Dry Sprinklers

a p p l icatio n s :

27

Au to mat i c S p r i n k l e r s

dry Sprinklers
ds-1

Pendent, Upright & Horizontal Sidewall
• Standard coverage

K Factor	K=5.6 (80,6)

•	All hazards (light hazards, horizontal
sidewall)

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

• 5 mm bulb

escutcheon finish	White Coated, Chrome

• Lengths to 48" (1220 mm)
• Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained
• Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

SIN	TY3255, TY3155, TY3355
Tech Data	TFP500

• Designed for use in applications requiring dry
sprinklers, or where building construction or
aesthetic considerations make the installation
of dry horizontal sidewall sprinklers more
desirable than the dry pendent type

Pendent Shown

Pendent, Upright & Horizontal Sidewall
• Standard coverage

K Factor	K=5.6 (80,6)

•	Light hazard/Ordinary hazard
• 3 mm bulb

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Lengths to 48" (1220 mm)

escutcheon finish	White Coated, Chrome

•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained
•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates
•	Designed for use in applications requiring
dry sprinklers, or where building

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

HSW Shown

SIN	TY3235, TY3135, TY3335
Tech Data	TFP510

construction or aesthetic considerations
make the installation of dry horizontal
sidewall sprinklers more desirable than the
dry pendent type

ds-1

d ry Sp r i n k l e r s

Extended Coverage Horizontal Sidewall
•	EC light hazard

K Factor	K=5.6 (80,6)

• 3 mm bulb

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Lengths up to 48" (1220 mm)
• Designed for use in light hazard occupancy
applications requiring a dry sprinkler to
cover areas up to
16’ x 20’ (4,9 m x 6,1 m) or
18’ x 16’ (5,5 m x 4,9 m)
• Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

escutcheon finish	White Coated, Chrome

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

SIN	TY3338, TY3358
Tech Data	TFP520

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

28

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

dry Sprinklers

ds-C
Concealed Pendent
•	Standard coverage

K Factor	K=5.6 (80,6)

•	All hazard (standard response)

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Light hazard/ordinary hazard
(quick response)
• 3 mm and 5 mm bulb
•	Lengths to 48" (1220 mm)
•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained

Sprinkler Finish	Cover Plate:

Chrome Plated, Brass
Plated, White Painted,
Custom
SIN	TY3535, TY3555
Tech Data	TFP515
•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

ds-ECC
Extended Coverage Concealed Pendent
•	EC light hazard/EC ordinary hazard

K Factor	K=5.6 (80,6)

• 3 mm bulb

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Lengths to 48" (1220 mm)
•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained
•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

Sprinkler Finish	Cover Plate:

Chrome Plated, Brass
Plated, White Painted,
Custom
SIN	TY3539
Tech Data	TFP518

ds-2
•	Standard coverage

K Factor	K=11.2 (161,3)

•	All hazard (standard response)

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Light hazard/Ordinary hazard
(quick response)
• 3 mm and 5 mm bulb
•	Extra large orifice
•	Lengths to 48" (1220 mm)
•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained

escutcheon Finish	White Coated, Chrome

Plated, Brass Plated

Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester
SIN	TY5255, TY5235
Tech Data	TFP530
•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

d ry Sp r i n k l e r s

Pendent

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

29

Au to mat i c S p r i n k l e r s

dry Sprinklers
ds-2

Extended Coverage Pendent
•	EC light hazard/EC ordinary hazard

K Factor	K=11.2 (161,3)

• 3 mm bulb
•	Extra large orifice

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Lengths to 48" (1220 mm)

escutcheon finish	White Coated, Chrome

•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained
•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

SIN	TY5238
Tech Data	TFP540

ds-3
Extended Coverage Horizontal Sidewall
•	EC ordinary hazard

K Factor	K=11.2 (161,3)

• 3 mm bulb

inlet THREAD	1" NPT (Standard Order)
connection	ISO 7-R1

•	Lengths to 48" (1220 mm)
•	Designed for use in applications where
sprinklers and/or connecting piping may
be exposed to freezing conditions, or the
sprinkler system is seasonally drained

escutcheon finish	White Coated, Chrome

•	Ideal for Exterior Loading Docks and Covered
Areas and can eliminate the need for dry or
anti-freeze systems

SIN	TY5339

Plated, Brass Plated
Sprinkler Finish	Natural Brass, Chrome

Plated, White Polyester

Tech Data	TFP550

•	Special assembly provides a seal at the
main pipe to prevent water from entering
the sprinkler assembly until the sprinkler
operates

DS B - 2

d ry Sp r i n k l e r s

Dry Sprinkler Boot (For Use With TFP Dry Type Sprinklers)
• Helps to close the air gap created by the
clearance hole through a wall or ceiling
through which the dry type sprinkler has
penetrated

Includes	1 Boot, 2 Strap Ties, and

•	Intended for use with clearance holes
through freezer ceiling structures

Tech Data	TFP591

1

/3 oz. of Adhesive

(quantity of adhesive is
sufficient for installing 1 Boot)

• Helps to stop the air exchange between the
inside and outside of the freezer (or any other
type of similar construction) to help prevent
transfer of moist air into the freezer space
• Provides the added feature of eliminating the
occurrence of cracking of some commonly
used sealants, where the cracking of these
sealants subsequently allows the passage of
moist air
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

30

Fire Protection General Products Catalog

Tyco Fire & Building Products

The Tyco® ILLUSION™ 11.2 K-factor sprinkler is designed
specifically for Las Vegas' standards. A fast response, extra
large orifice concealed pendant sprinkler, the ILLUSION™
is perfect for casino atriums, exhibit halls and retail areas
with over 25' ceilings heights; blending in so well they give
the illusion they aren't even there.

We Cover All The Action

a p p l icatio n s :
Special Purpose Sprinklers are intended for use
in specific applications, including the protection of
combustible concealed spaces and areas subject to corrosion.
Also, these installations may need consideration for more
water at lower pressures, or more water over a greater area.

• Attic Spaces
• Retail Windows
• High Security
Institutions
• Minimal Water
Damage
Conditions

T yco Fire & Building Products

• High
Temperature
Conditions
• Corrosive
Conditions

Fire Protec tion General Products Catalog

Special Purpose Sprinklers

SPecial Purpose Sprinklers

31

Au to mat i c S p r i n k l e r s

special purpose Sprinklers
Attic

BB (Back-to-Back), SD (Single Directional), HIP, & AP (Attic Plus)
• “Specific Application Sprinklers for Protecting
Attics”
• 3 mm bulb or solder type
• Provides a tested method of protecting an attic

Back-To-Back Application

• Provides a specific cost advantage by reducing
the amount of piping required
•	Cover attics to 60’-0" wide with a single line of
piping, eliminating the need for as many as five
branch lines
• Saves up to 80% of the piping that would
be required with standard sprinklers while
providing a higher level of protection

Back-To-Back
Hip Application

K Factor	K=4.2 (60,5), K=5.6 (80,60),

K=8.0 (115,2)
1

Thread Size	 ⁄2" NPT
3

⁄4" NPT

Sprinkler Finish	Natural Brass
SIN	TY4180, TY4181, TY4182 TY3180,

TY3181, TY3182 TY2180, TY2181,
TY2182 TY3183, TY3184, TY3185
TY3187, TY3190, TY2190
Tech Data	TFP610

Hip

Single Directional
Application

s p e c i a l p u r p o s e Sp r i n k l e r s

BB

Spray Patterns

HIP

Single
Directional
AREA 2
WITH AP
SPRINKLERS

AREA 1
WITH BB
SPRINKLERS

AREA 3
WITH AP
SPRINKLERS

STAGGERED
SPACING WHEN
MORE THAN
ONE ROW

SD
AP

MINIMUM
SEPARATION
15'-0" (4,6 m)

Attic
Attic
Plus
Plus
(AP)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

32

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

special purpose Sprinklers

cc 1
Combustible Concealed Space Sprinklers™,, Upright
• 3 mm bulb

K Factor	K=2.8 (40,3)

• Specific application sprinklers

Thread Size	 ⁄2" NPT

• Provides protection of light hazard
combustible, as well as
non-combustible, concealed spaces
requiring sprinkler protection

Sprinkler Finish	Natural Brass

1

SIN	TY1189
Tech Data	TFP630

• Meets NFPA® Requirements for Specialty
Listed Sprinklers in Combustible Concealed
Spaces
• Allows the use of BlazeMaster® CPVC pipe
in combustible concealed areas with the
benefit of superior sprinkler protection for
Wood truss spaces

CC2
Combustible Concealed Space Sprinklers™,, Upright
• 3 mm bulb

K Factor	K=4.2 (60,5) • K=5.6 (80,6)

• Specific application sprinklers

Thread Size	 ⁄2" NPT

• Provides protection of specific light
hazard combustible, as well as
non-combustible, concealed spaces
requiring sprinkler protection

Sprinkler Finish	Natural Brass

• Allows the use of BlazeMaster® CPVC pipe
in combustible concealed areas with the
benefit of superior sprinkler protection for
Wood truss spaces

Combustible Concealed
Sprinkler Discharge Pattern

SIN	TY2189, TY3189
Tech Data	TFP632

• Can be used on steel dry pipe sprinkler
systems
• Increased spacing from 10 ft. (3,1 m) to
12 ft. (3,7 m)
• Increased coverage area from 100 ft2
(9,3 m2) to 144 ft2 (13,4 m2)

Standard Spray
Sprinkler Discharge Pattern

s p e c i a l p u r p o s e Sp r i n k l e r s

• Meets NFPA® Requirements for Specialty
Listed Sprinklers in Combustible Concealed
Spaces

1

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

33

Au to mat i c S p r i n k l e r s

special purpose Sprinklers
WS™

Window Sprinklers, Horizontal & Pendent Vertical Sidewall
• 3 mm bulb

K Factor	K=5.6 (80,6)

•	Specific application sprinklers

Thread Size	 ⁄2" NPT

•	Only UL tested sprinklers that can protect
glazing in a wall or window and allow it to
maintain its mechanical equivalent rating
up to two hours

Sprinkler Finish	White Polyester Coated,

• First sprinklers to be UL/C-UL Listed, ICC-ES,
and ULC Listed & Approved for maintaining a
rated assembly
• Pendent allows installation farther away from
the glass than the sidewall

1

Chrome Plated, Natural
Brass
SIN	TY3388, TY3488
Tech Data	TFP620

• Provides the only UL tested option when
seeking wall fire ratings when using
tempered or heat strengthened glass

•	Sidewall permits the window mullion to
act as a baffle, allowing the sprinklers to be
spaced closely together, if necessary

tf p m a x
Institutional Pendent
•	Light hazard/Ordinary hazard

K Factor	K=5.6 (80,6)

• 2.5 mm bulb

inlet THREAD	 ⁄2" NPT
connection

• Designed to provide maximum solutions
to the unique fire protection needs of
institutional facilities

s p e c i a l p u r p o s e Sp r i n k l e r s

• For use in correctional, detention, and
mental health care facilities
• Vandalizing, moving, or disassembling the
sprinkler results in activation and a water
flow alarm
• Low breakaway weight

1

escutcheon finish	Chrome Plated
Sprinkler Finish	Chrome Plated
SIN	TY3291
Tech Data	TFP652

• Flush mount escutcheons
• 175 psi (12,1 bar)

Institutional Horizontal Sidewall
•	Light hazard/Ordinary hazard

K Factor	K=5.6 (80,6)

• 2.5 mm bulb

inlet THREAD	 ⁄2" NPT
connection

• Designed to provide maximum solutions
to the unique fire protection needs of
institutional facilities
• For use in correctional, detention, and
mental health care facilities
• Vandalizing, moving, or disassembling the
sprinkler results in activation and a water
flow alarm

1

escutcheon finish	Chrome Plated
Sprinkler Finish	Chrome Plated
SIN	TY3391
Tech Data	TFP656

• Low breakaway weight
• Flush mount escutcheons
• 175 psi (12,1 bar)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

34

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

special purpose Sprinklers

tf p P h 2
Institutional Pendent
• All hazard

K Factor	K=5.6 (80,6)

• Solder type
• Low breakaway weight

inlet THREAD	 ⁄2" NPT
connection

• Flush mount escutcheons

escutcheon finish	Chrome Plated

• 175 psi (12,1 bar)

Sprinkler Finish	Chrome Plated

1

SIN	TY3290
Tech Data	TFP650

tf p P h 5
Institutional Horizontal Sidewall
• Light hazard/Ordinary hazard

K Factor	K=5.6 (80,6)

• Solder type
• Low breakaway weight

inlet THREAD	 ⁄2" NPT
connection

• Flush mount escutcheons

escutcheon finish	Chrome Plated

• 175 psi (12,1 bar)

Sprinkler Finish	Chrome Plated

1

SIN	TY3390
Tech Data	TFP654

I s s u e D Q u a rt z o i d ®
High Temperature, Upright & Pendent
• Standard coverage

K Factor	K=5.6 (80,6) • K=8.0 (115,2)

• All hazard

Thread Size	 ⁄2" NPT •

• 11 mm bulb

Sprinkler Finish	Natural Brass, Chrome

• Extra-high and ultra-high temperature
ratings and corrosion resistant coatings

SIN	TY3191, TY3296, TY4191 ,

3

⁄4" NPT

Plated, Lead Coated
TY4292

Tech Data	TFP690

FTR-1
Fixed Temperature Release
• 3 mm bulb

K Factor	K=5.6 (80,6)

• Fixed-temperature, heat detector intended
for wet or dry pilot release service

Thread Size	 ⁄2" NPT

• Can be used for pilot line service, instead of
standard sprinklers, to activate deluge and
preaction systems equipped with either wet
or dry pilot line detection

Polyester Coated, Gray
Teflon® Coated
SIN	TY3030
Tech Data	TFP1388

• Corrosion resistant assembly option for
outdoor applications (Teflon® coated)

1

Sprinkler Finish	Natural Brass, White

• Maximum 40 ft. x 40 ft. spacing

s p e c i a l p u r p o s e Sp r i n k l e r s

• Temperature Ratings to 650°F (343°C)
available

1

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

35

Au to mat i c S p r i n k l e r s

special purpose Sprinklers

T Y - B & T Y - F R B (Alternate Materials Of Construction)
Upright & Pendent Sprinklers
• TY-B: 5 mm diameter heat sensitive glass
bulb, standard response

K Factor	K=5.6 (80,6) • K=8.0

• TY-FRB: 3 mm diameter heat sensitive glass
bulb, quick response

Thread Size	 ⁄2" NPT •

• Corrosion resistant, standard coverage spray
sprinklers designed for use in commercial
occupancies where corrosive atmospheres
may exist
• Alternate materials of construction (Stainless
Steel, SMO, or Titanium) are utilized to
extend the life of a sprinkler beyond that
which might be expected of copper alloy
sprinklers exposed to corrosive atmospheres

(115,2)
1

3

⁄4" NPT
escutcheon style	Style 10 • Style 40
Sprinkler Finish	Stainless Steel, SMO,
Titanium
SIN	TY8191, TY8291, TY9191
TY9291, TY8181, TY8281
TY9181, TY9281, TY8192
TY8292, TY8182, TY8282
TY8193, TY8293, TY8183
TY8283
Tech Data	TFP680

3mm bulb shown

Vertical, Horizontal & Recessed Horizontal Sidewall Sprinklers
• TY-B: 5 mm diameter heat sensitive glass
bulb, standard response

K Factor	K=5.6 (80,6)

• TY-FRB: 3 mm diameter heat sensitive glass
bulb, quick response

escutcheon style	Style 10

s p e c i a l p u r p o s e Sp r i n k l e r s

• Corrosion resistant, standard coverage spray
sprinklers designed for use in commercial
occupancies where corrosive atmospheres
may exist
• Alternate materials of construction (Stainless
Steel, SMO, or Titanium) are utilized to
extend the life of a sprinkler beyond that
which might be expected of copper alloy
sprinklers exposed to corrosive atmospheres

1

Thread Size	 ⁄2" NPT
Sprinkler Finish	Stainless Steel, SMO,

Titanium

SIN	TY8391, TY8491, TY8381,

TY8481, TY8382, TY8482,
TY8393, TY8493, TY8383,
TY8483
Tech Data	TFP680

3mm bulb shown

I LLUS I ON ™
Concealed Standard Coverage Pendent Sprinklers
• Extra large orifice/Special hazard

K Factor	K=11.2 (161,3)

• Coverage per NFPA 13

Thread Size

• Available with optional dust and air seal
• The ILLUSION is concealed in an enclosed
escutcheon plate with flat cover for use in
those applications where architecturally
sensitive areas such as casinos, hotel lobbies,
office buildings, churches and restaurants

3

⁄4" NPT
escutcheon style	Style 10 • Style 40
Sprinkler Finish	Cover Plate:
Chrome, Brass,
Signal White, Grey White,
Pure White, Custom
SIN
TY5521
Tech Data
TFP184

We Cover All The Action

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

36

Fire Protection General Products Catalog

Tyco Fire & Building Products

a p p l icatio n s :
Sprinkler Accessories are for use with the sprinklers
and nozzles described in this catalog. Escutcheons are
referenced by a style number and are available in brass,
chrome or white finish. Please refer to the technical data
sheet for additional information and a listing of what
finishes are available.

T yco Fire & Building Products

• Improve
Appearance

• Onsite Emergency
Storage Supply

• Conceal
Clearance Holes

• Protection from
Mechanical or
Physical Damage

Fire Protec tion General Products Catalog

Sprinkler Accessories

Sprinkler Accessories

37

Au to mat i c S p r i n k l e r s

sprinkler accessories
E s c u tc h e o n P l ate s

Pendent & Sidewall Recessed Escutcheons
• Styles 10, 20, 30, 40 & 50

finishes	Carbon steel chrome

plated, white coated,
or brass plated. Series
300 stainless steel
white coated or plain
unpolished.

• Consists of a mounting plate and closure for
finished appearance in ceilings or soffits
• Maximum 1⁄2" to 3⁄4" NPT adjustment
• Intended for use in areas with finished
ceilings or walls, and the adjustment
provided by these escutcheons reduces
the accuracy to which fixed piping to the
sprinklers must be cut, while providing a
decorative recessed sprinkler installation
• Primarily designed for use with standard
spray, quick response sprinklers and the

(Other colors available on
request.)
Tech Data	TFP770

Designer residential sidewall sprinklers
• Available for use with 1⁄2" or 3⁄4" NPT sprinkler
heads

Style 65, One-Piece Flat Escutcheon
Style 401, Two-Piece Adjustable Escutcheon
• Used to improve the overall appearance of
the sprinkler installation by concealing the
clearance holes required for wall or ceiling
installation

finishes	Chrome, White, Brass
Tech Data	TFP777

• Deep, two-piece, adjustable

Style 65

• Available for 1⁄2" and 3⁄4" NPT

Style 401

Style 60, Two-Piece Flush Escutcheon

s p r i n k l e r acc e s s o r i e s

• Used to improve the overall appearance of
the sprinkler installation by concealing the
clearance holes required for wall or ceiling
installation

finishes	Chrome, White, Brass
Tech Data	TFP778

• Deep, two-piece, adjustable
Style 60

• Available for 3⁄4" NPT

S p ri n k l er He a d C a bi n et
3, 6 or 12 Capacity
• Provides storage for spare sprinklers
and sprinkler wrench

Tech Data	TFP785

• Spare sprinklers facilitate the prompt
replacement of operated or damaged
sprinklers and return of fire protection
system to service as soon as possible

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

38

Fire Protection General Products Catalog

Tyco Fire & Building Products

Nozzles & Accessories

a p p l icatio n s :

• Equipment or
Processes that
Require Special
Designs
• Cable Trays
• Clean Rooms
• Computer
Rooms

• Gas Turbines
• Historic Sites &
Museums
• Industrial
Process
Equipment
• Machining
Centers
• Ferries

Nozzles & Nozzle Accessories are designed for use in

• Conveyors

a variety of special hazard applications. Their uses include,
but are not limited to, exposure protection, fire control,
fire extinguishment, and explosion prevention. Many types
of nozzles may be required to provide a properly designed
special hazard fire protection system.

• Cut-Off Rooms
• Engine Test Cells
• Flammable
Liquid Storage
• Food Processing

T yco Fire & Building Products

• Fuel Storage

• Offshore
Platforms
• Telecom
• Transformers
• Vapor
Suppression

Fire Protec tion General Products Catalog

Nozzles & Accessories

• Flammable
Liquid Tanks
& Operations

39

Au to mat i c S p r i n k l e r s

nozzles and accessories
D3
Protectospray® Nozzle
• Designed for use in water spray fixed systems
for fire protection applications
• Open orifice design type for use in deluge
systems
• Nozzles are external deflector types that
discharge a filled cone of water droplets at
relatively low velocity
• Spray angles available: 65°, 80°, 95°, 110°,
125°, 140°, 160°, and 180°

K Factor 	 K
 =1.2 (17,3) • K=1.8 (25,9)

K=2.3 (33,1) • K=3.0 (43,2)
K=4.1 (59,0) • K=5.6 (80,6)
K=7.2 (108,7)
1
Thread Size 	 ⁄2" NPT
Sprinkler Finish 	Bronze: Natural Finish,
Teflon Coated, Lead
Coated, Chrome Plated,
or Natural Finish
Stainless Steel
Tech Data	TFP802

EA-1
Automatic Protectospray® Nozzle
• Bulb type frangible element for use in closed
head systems

K Factor 	K=1.4 (20,2), K=2.8 (40,3)

• Discharges a filled cone of water droplets at
relatively low velocity

Thread Size 	 ⁄2" NPT

• Spray angles available: 65°, 80°, 95°, 110°,
125°, 140°, 160°, and 180°

Lead Coated, Chrome
Plated, Corrosion proof
Wax Coated
Tech Data	TFP800

K=5.6 (80,6)
1

Sprinkler Finish 	Bronze: Natural Finish,

B-1

N o z z l e s a n d acc e s s o r i e s

Foam-Water Sprinkler
• Air aspirating foam-water nozzles

K Factor 	K=3.0 (43,2)

• Pendent & upright styles

Thread Size 	 ⁄2"

• Open nozzle for use in NFPA 16 foam
sprinkler system

Sprinkler Finish 	Natural Bronze

1

Tech Data	TFP840

HV ”High Velocit y”
Spray Nozzle
• Open, directional spray nozzles

K Factor 	 K
 =1.6 (23,0) • K=1.8 (26,0)

• Designed for use in fixed water spray fire
protection systems where a high velocity
water application is needed, such as the
protection of flammable liquids, electrical
transformers, circuit breakers, oil-fired
boilers and lube oil systems

K=2.8 (40,3) • K=4.6 (66,2)
K=5.5 (79,2) • K=6.0 (86,4)
Thread Size 	1"
11⁄4" (only K=6.4)
Sprinkler Finish 	Natural Brass or
Stainless Steel
Tech Data	TFP815

• Available in six different orifice sizes
• Produces a solid conical spray pattern
• Available in six angle spray patterns

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

40

Fire Protection General Products Catalog

Tyco Fire & Building Products

Au to mat i c S p r i n k l e r s

nozzles and accessories

AM 4 A Q UAM I S T ®
Open Type
• Open, directional mist nozzles

K Factor 	K=0.24 (3,5)

• Listed and Approved for the protection of
flammable liquid hazards (UL/FM)

Thread Size 	 ⁄2" NPT

• Approved for protection of gas turbines (FM)
• Maximum ceiling height, 26' 3" (8 m)

1

Sprinkler Finish 	Stainless Steel
Tech Data	TD1173

• Compartment volume –
- UL - 56,500 ft3 (1,600 m3)
– FM - 45,203 ft3 (1,280 m3)
• Maximum utilization of water for flammable
liquid fire protection
• Nozzle coverage: maximum 172 ft2 (16 m2)
• Nozzle pressure: 185 to 250 psi
(12,8 to 17,2 bar)

AM 1 0 A Q UAM I S T ®
Open Type
• Open mist nozzles

K Factor 	K=0.24 (3,5)

• Designed for use in water mist protection
systems protecting flammable liquids and
turbine bearings

Thread Size 	 ⁄2" NPT

• Minimal water demand, approximately
3.1 GPM/nozzle at 170psi (11,73 LPM at
11,6 bar)

1

Sprinkler Finish 	Stainless Steel
Tech Data	TD1174

• Mist represents latest in fire protection
technology
• For use in “low pressure” mist applications

n o z z l e s a n d acc e s s o r i e s

• Minimum operating pressure is 170 psi
(11,6 bar)

AM 2 4 A Q UAM I S T ®
Open Type
•	Listed and Approved for Marine Type
Approved by Lloyds, USCG, DNV, American
Bureau of Shipping, MCA, Germanischer
Lloyd, Bureau Veritas
•	Intended Applications – IMO Mandated
Local Application System for Protection of
Class A Machinery Spaces

K Factor 	4.7 lpm/bar 1/2,

0.33 gpm/psi 0.5
1
Thread Size 	 ⁄2" NPT
Sprinkler Finish 	Brass, Chrome Plated,
White Polyester
Tech Data	TD1172

• Maximum Distance between nozzles (to
plane of protection) - Vertical Clearance
Nozzle Spacing
–1 m to 3.5 m nozzles - 4.0 meter spacing
–3.5 m to 5.0 m nozzles - 3.5 meter spacing
–5.0 m to 10.0 m nozzles - 3.0 meter spacing
•	Nozzle pressure: 175-250 psi (12,1 to
17,2 bar)
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Products

Fire Protec tion General Products Catalog

41

Au to mat i c S p r i n k l e r s

nozzles and accessories
F 8 2 2 t h r u F 8 3 4 M u l s ifyre ®

Directional Spray Nozzles, Open, High Velocity
• Two configurations: basic Mulsifyre Nozzle
and Mulsifyre Nozzle with Model F880
Dust Cap
•	Available in six different models provide
a wide range of orifice sizes and water
distribution characteristics
• Air aspirating foam-water nozzles, for use
with all types of foam (required for
Non-AFFF type foams)

K Factor 	K=2.0(28,8) • K=2.3(33,1)

K=2.7(38,9) • K=2.6(37,4)
K=4.6(66,2) • K=5.1(73,4)
3
Thread Size 	 ⁄4"
Sprinkler Finish 	Brass
Tech Data	TFP810

• Designed for use in water spray fixed systems
for fire protection applications where a high
velocity water application may be required
• Pendent & upright designs
• Open nozzle for use on deluge systems

c o o l i n g T o wer n o z z l e
Type 1 and 2
• Intended for use in fire protection systems
for cross flow cooling towers with
combustible fill sections
• Open nozzle design for use in water spray
deluge system

K Factor 	K=2.9 (41,76)
3

Thread Size 	 ⁄4" NPT
Sprinkler Finish 	Stainless Steel
Tech Data	TFP830

• Installed under the distribution basin, they
discharge water in a relatively narrow,
elongated spray pattern

N o z z l e s a n d acc e s s o r i e s

• Type 1 has a waterway designed for use in
towers with diffusion decks, Type 2 for those
without diffusion decks

B l o w - Off P l u g s
Plugs for Protectospray® Nozzles or Open Sprinklers
• Intended for use in applications where
protection is required against infestation
or accumulation of debris within the orifice
of an open Protectospray Nozzle or open
sprinkler

K Factor 	K=5.6 (80) • K=8.0 (115)
Tech Data

TFP890

• Blow-Off Plugs are designed for both indoor
or outdoor use

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

42

Fire Protection General Products Catalog

Tyco Fire & Building Products

a pp l i c a t i o n s :
Wet Pipe Sprinkler Systems are designed for use in
applications where the temperature is maintained above
freezing. In such systems, the entire piping network is fully
pressurized so that water is discharged from a sprinkler head
immediately after actuation.
Alarm check valves or water flow detectors are used to
actuate local and remote alarms. Applications include
heated warehouses, factories, hospitals, stores, shopping
centers and residential settings such as apartment or
condominium complexes, and single family residences.

T yco Fire & Building Produc ts

• Heated
Warehouses
• Factories

• Apartment or
Condominium
Complexes
• Single Family
Residences

• Hospitals
• Stores
• Shopping Centers

Fire Protec tion General Products Catalog

w e t s ys t e m va lv e s & d e v i c e s

WEt System VaLVes & Devices

43

s y s t e m va lv e s & D e v i c e s

wet system valves & devices

AV-1 Alarm Valve

w e t s ys t e m va lv e s & d e v i c e s

Butterfly Valve to
Control Water Supply
to System

Water Supply

AV-1
Alarm Valve
• 21⁄2" (DN65) Alarm Valves may be installed
vertically
• 4", 6", and 8" (DN100, DN150, and DN200)
Alarm Valves may be installed vertically or
horizontally
• Groove x Groove, Flange x Flange,
Flange x Groove Alarm Valves are divided
seat ring, rubber-faced clapper, check type,
water flow alarm valves
• For use in wet pipe (automatic sprinkler) fire
protection systems
• Automatically actuates electrically and/or
hydraulically operated alarms when there

Tech Data	TFP910

is a steady flow equivalent to the discharge
rate for one or more sprinklers
• Optional Retard Chamber used in
installations subject to variable pressure
(generally associated with public water
supplies) to help prevent false alarms
• Available pre-assembled with modular trim
to provide a quick and convenient method
for trimming valve risers. Contact TFBP for
details
• Maximum rated working pressure is
300 psi (20,7 bar)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

44

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

wet system valves & devices

C V-1FR
Riser Check Valve
• Sizes 2" (DN50) through 8" (DN200)
• Intended for use in a wet type automatic
sprinkler system riser
• Furnished with grooved ends that are
compatible with grooved pipe and
couplings
• Can be installed with ANSI class 150 or 300
Flanges utilizing flange adapters

Tech Data	TFP950

• Designed with a removable cover for ease
of field maintenance
• Standard seal is grade “E" EPDM
• Maximum rated working pressure is
300 psi (20,7 bar)

RSV-1
Residential Domestic Shutoff Valve

• During the design of a residential sprinkler
system, domestic water use should be taken
into consideration unless the domestic
supply can be stopped when a sprinkler
operates
• When a sprinkler operates, water supply is
automatically diverted from the domestic
system to the sprinkler system

Tech Data	TFP980

• Valve automatically resets after the fire
protection system is returned to normal
service
• Maximum rated working pressure is
175 psi (12,1 bar)

• Eliminates the need for pumps, pressurized
storage tanks, or electrically operated
domestic shutoff valves

Riser Manifolds
513D (13D), 513D/R (13D/R) and 513 (13)
• 513D (13D) and 513D/R (13D/R):
–	Available sizes: 1", 1-1/2", and 2"
(DN25, DN40, and DN50)
– Provides the necessary water flow
alarm, pressure gauge, and drain
equipment in a single assembly for use
in NFPA 13D or 13R residential sprinkler
systems
• 513 (13):
–	Available sizes: 1-1/2" thru 6"
(DN40 thru DN150)

Tech Data	TFP960 & TFP962

• Available in different configurations and
variety of sizes allowing a cost effective
and easy transition to check valves, control
valves, and system piping
• May be installed either horizontally (flow
switch on top) or vertically (flow going up)
• Maximum rated working pressure is
175 psi (12,1 bar)

– Provides the necessary water flow
alarm, pressure gauge, alarm test
orifice, drain, and sight glass equipment
in a single assembly for use in NFPA 13
sprinkler systems

w e t s ys t e m va lv e s & d e v i c e s

• 1" (DN25) size is designed for single family
demand (NFPA 13D)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

45

s y s t e m va lv e s & D e v i c e s

wet system valves & devices
Resi-Riser
Residential
• Sizes 1"- 2" (25-50 mm)

Tech Data	Contact TFBP for details

• Compact, pre-assembled, ready to install
sprinkler riser
• Brass construction for use in potable water
supply

• Molded mounting points allow for fast
and easy left or right hand installation

• Integral test and drain assembly, flow
switch with retard mechanism, 300 psi
gauge, and check valve

• Available with or without pressure relief
valve or flow switch retard mechanism
features

• Compact size allows for easy installation
between 2" x 4" (50-100 mm) studs

• Maximum rated working pressure is
175 psi (12,1 bar)

WMA-1
Water Motor Alarm
• Hydraulically operated outdoor alarm for
use with appropriate fire protection system
valves (alarm, dry, deluge)

Tech Data	TFP921

• Supplied by dedicated outlet in valve trim
line or retard chamber

• Can accommodate range of wall
thicknesses from 2" to 18" (50 to 450 mm)

• Uses energy-efficient lightweight impeller
design capable of producing very high
sound level

• Furnished with approved 3⁄4" (20 mm)
Y-strainer for use in alarm line

• Corrosion-resistant aluminum alloy gong,
gong-mount, and water motor housing

• Maximum rated working pressure is
300 psi (20,7 bar)

w e t s ys t e m va lv e s & d e v i c e s

• Delrin bearings - do not require lubrication
- for long life
• May be mounted on any type of wall

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

46

Fire Protection General Products Catalog

Tyco Fire & Building Products

a pp l i c a t i o n s :
Dry Pipe Sprinkler Systems are designed for
applications where piping and sprinklers are subjected to
freezing temperatures, such as unheated warehouses,
parking garages, store windows, attic spaces, or loading
docks. Valves for the system, however, must be installed
in areas not subject to freezing, as this portion of the
system does contain water. Pipe lines to the sprinklers
are usually pressurized with air, but nitrogen can be used.
When pressure in the system is lost by actuation of a
sprinkler head, the dry pipe valve trips, activates alarms,
and releases water into the system. The system may be
equipped with automatic or manual air supply controls and
air supervisory devices with appropriate trouble alarms.

T yco Fire & Building Produc ts

• Unheated
Warehouses
• Parking
Garages
• Store Windows

• Attic Spaces
• Loading Docks,
& Other Areas
Exposed To
Freezing
Temperatures

Accessory items, such as dry pipe valve accelerators that
increase the speed of system operation, and pressure
switches used to activate electric alarms, may be used to
enhance the system.

Fire Protec tion General Products Catalog

Dry System Valves & dEvices

Dry System VaLVes & Devices

47

s y s t e m va lv e s & D e v i c e s

dry system valves & devices

Air

DPV-1 Dry Pipe Valve

d ry s ys t e m va lv e s & d e v i c e s

Butterfly Valve to
Control Water Supply
to System

Water Supply

DPV-1
Dry Pipe Valve – 21⁄2" thru 6"
• Available sizes: 21⁄2" (DN65), 3" (DN80),
4" (DN100) and 6" (DN150)

Tech Data	TFP1020

• External reset differential dry pipe valves

• Rated for use at a maximum service
pressure of 250 psi (17.2 bar)

• Available as Flange x Flange, Flange x
Groove, or Groove x Groove

• Listings and Approvals: UL, C-UL, and FM

• Unique, offset clapper design minimizes
valve size and weight
• Used to supply sprinkler installations in
which sprinklers are subjected to freezing
conditions (40˚F / 4˚C or less)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

48

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

dry system valves & devices

ACC-1
Dry Pipe Valve Accelerator
• Designed for use with Model DPV-1 dry
pipe valves

Tech Data	TFP1112

• Speeds operation of the dry pipe valve
upon loss of air pressure

• Rated for use at a maximum water supply
pressure of 250 psi (17,2 bar) and a
maximum system air (or nitrogen) pressure
of 70 psi (4,8 bar)

• Automatically adjusts to small or slow
changes in system pressure but trips upon
a rapid and steady drop in pressure
• Designed to trip when system air pressure
drops at a rate exceeding approximately
1 psi/minute (0.07 bar/min)

• Listings and Approvals:
UL, ULC, FM, LPC, SSL, and VdS

• Upon tripping, it transmits system air
pressure to the intermediate chamber of
the dry pipe valve, which neutralizes the
differential pressure holding the valve
closed and opens the waterway clapper

QRS
• Maximum working air pressure
70 psi (4,8 bar)

Tech Data	TFP1100

• Quick opening device intended to reduce
the time for dry pipe valve operation
following the operation of one or more
automatic sprinklers

• Operation of the dry pipe valve within
four seconds -independent of various
combinations of system initial air pressures,
system volumes, or sprinkler K Factors

• Automatically adjusts to both small and
slow changes in system pressure, but trips
with a steady drop in pressure (as in the
case of sprinkler operation)

• Proven electronic release technology as
used for electrically operated deluge and
preaction systems

• Can be used to retro-fit existing
mechanical accelerators
• Fully assembled package includes switch,
solenoid, control panel, and accelerator
trim pipe and fittings
• Built-in low and high pressure alarm
supervision

• Battery back-up in the event of primary
power failure
• Eliminates re-setting problems often
incurred with traditional mechanical
accelerators
• Listings and Approvals: UL, FM

d ry s ys t e m va lv e s & d e v i c e s

Electronic Accelerator

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

49

s y s t e m va lv e s & D e v i c e s

dry system valves & devices
AMD-1

Air Maintenance Device, Pressure Reducing Type
• Field adjustable

Tech Data	TFP1221

• Used in systems where compressed air
source is available
• Used in systems in which the air supply is
at a higher pressure than is desired for a
sprinkler system or dry pilot line system
• Listings and Approvals:
UL, ULC, and FM

AMD-2
Air Maintenance Device, Compressor (small w/o tank) Control Type
• Field adjustable

Tech Data	TFP1231

• Used in conjunction with a small,
non-tank-mounted air compressor
• Monitors sprinkler system or dry pilot line
detection for deluge system air pressure
and automatically cycles the compressor
to maintain system pressure within preset
limits

d ry s ys t e m va lv e s & d e v i c e s

• Listings and Approvals:
UL, ULC, and FM

AMD-3
Nitrogen Maintenance Device, High Pressure (Cylinder) Reducing Type
• Field adjustable

Tech Data	TFP1241

• Used in conjunction with a cylinder of
high pressure nitrogen to control the
nitrogen pressure in a sprinkler system
or a dry pilot line detection for deluge
systems
• Listings and Approvals:
UL, ULC, and FM

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

50

Fire Protection General Products Catalog

Tyco Fire & Building Products

a pp l i c a t i o n s :
Deluge Systems are normally used in special hazard
installations where water must be applied to an entire area
for protection. They use open sprinklers or spray nozzles
attached to a piping system connected to a water supply
through the deluge valve. The deluge valve is used to control
water flow into deluge, preaction, and special types of fire
protection systems in response to a fire. This valve is opened
by a fire detection system installed in the same areas.

Preaction Systems are used to protect areas where water
damage from damaged sprinklers or piping must be avoided.
A prealarm of a possible fire allows time for alternate fire
extinguishment prior to a sprinkler discharge. They are
designed for applications such as refrigerated areas that
require maximum protection against inadvertent operation
of the sprinkler system.

T yco Fire & Building Produc ts

• Flammable
Liquid
Handling

Using Water as
Extinguishing
Agent

• Storage Areas
for Valuable
Artifacts

• Computer
Rooms

• Aircraft Hangars

• Archives

• High-Hazard
Installations

• Libraries
• Refrigerated
Areas

Fire Protec tion General Products Catalog

Deluge & Preac tion Systems

Deluge & Preaction Systems

51

s y s t e m va lv e s & D e v i c e s

deluge & preaction systems
D e l u g e S y s t e ms
Electric Actuation

d e lug e & p r e ac t i o n s ys t e m s

Deluge fire protection systems are normally
used in special hazard installations where
an entire area application of water or foam
is required for protection. Applications may
include flammable liquid handling and
storage areas, aircraft hangars, and other
high-hazard installations where water is
the most effective extinguishing agent.
Deluge systems employ open sprinklers or
spray nozzles attached to a piping system.
The system is connected to a water supply
through the deluge valve. This valve is
opened by the operation of a fire detection
system installed in the same areas as the
open sprinklers or nozzles. Deluge systems
may be activated by wet or dry pilot
sprinklers, or electric detectors. When the
deluge valve opens, water flows into the
piping system and discharges from all open
sprinklers and nozzles.

Legend:
1 Deluge Valve (DV-5)
2 Isolation Valve
3 Diaphragm Supply Valve
4 Manual Control Station
5 Automatic Shut-off Valve
6 Automatic Drain Valve

7
8
9
10
11
12

Pressure Switch
Water Motor Gong
Releasing Panel
Spray Nozzle
Smoke/Heat Detector
Solenoid Valve

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

52

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

deluge & preaction systems

S i n g l e I n t e r l o c k P r e ac t i o n S y s t e ms
Electric/Electric Actuation

Single interlock preaction systems
employ automatic sprinklers attached to
a piping system containing 10 psi (0,7 bar)
supervisory pressure, with a supplemental
electric fire detection system installed in
the same area as the sprinklers. Preaction
systems with 10 psi (0,7 bar) supervisory
pressure may also be activated by either
wet or dry pilot sprinklers instead of electric
detectors. Actuation of the fire detection
system from a fire opens the deluge valve,
allowing water to flow into the sprinkler
piping system and to be discharged only
from those sprinklers that have been
operated by heat over the fire. Loss of
supervisory pressure from the system
piping as a result of damaged sprinklers or
broken piping will activate a trouble alarm
to indicate impairment of the system. The
deluge valve will not open due to loss of
supervisory pressure.

Legend:
1 Deluge Valve (DV-5)
2 Isolation Valve
3 Diaphragm Supply Valve
4 Manual Control Station
5 Automatic Shut-off Valve
6 Automatic Drain Valve
7 Pressure Switch Water
8 Water Motor Gong

9
10
11
12
13
14
15

Releasing Panel
Sprinkler
Smoke/Heat Detector
Solenoid Valve
Air Supply Inlet
Pressure Switch  (Air)
Check Valve

d e lug e & p r e ac t i o n s ys t e m s

Single interlock preaction systems are used
to protect areas where there is danger of
serious water damage that might result from
damaged automatic sprinklers or piping.
Typically, such areas include computer
rooms, storage areas for valuable artifacts,
libraries and archives. Also, preaction
systems are effectively used to protect
properties where a prealarm of a possible
fire condition may allow time for fire
extinguishment by alternate suppression
means, prior to a sprinkler discharge. In
the event the fire cannot otherwise be
extinguished, the preaction sprinkler
system will then perform as the primary fire
protection system.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

53

s y s t e m va lv e s & D e v i c e s

deluge & preaction systems

D o u b l e I n t e r l o c k P r e ac t i o n S y s t e ms
Pneumatic/Electric Actuation
Double interlock preaction systems
are designed for applications such
as refrigerated areas that require the
maximum degree of protection against
an inadvertent operation that could result
in unnecessary flooding of the sprinkler
system piping.

d e lug e & p r e ac t i o n s ys t e m s

The double interlock system consists of a
deluge valve and swing check valve with
releasing trim featuring both a solenoid
valve and a dry pilot actuator in a series
configuration. The swing check valve
isolates the body of the deluge valve
from the system air or nitrogen pressure
that holds the dry pilot actuator closed.
The solenoid valve remains closed until
it is electrically energized by a deluge
releasing panel that responds to the
operation of a fire detection device.
In order to actuate the double interlock
preaction system, two independent
events, caused by a fire condition, must
occur. The sprinkler system piping must
lose air or nitrogen pressure due to the
operation of one or more sprinklers, and
the deluge releasing panel must energize
and open the solenoid valve upon the
operation of a fire detection device.
The double interlock system will operate
only when both the dry pilot actuator
and the solenoid valve are open at the
same time. Opening of the dry pilot
actuator only (for example: a forklift truck
accidentally dislodges a sprinkler) or of
the solenoid valve only (for example:
accidental operation of an electric manual
pull station) will cause an alarm, and will
not trip the system or flood the sprinkler
system piping.

Legend:
1 Deluge Valve (DV-5)
2 Isolation Valve
3 Diaphragm Supply Valve
4 Manual Control Station
5 FSV (Fail-Safe Valve)
6 Automatic Drain Valve
7 Pressure Switch Water
8 Water Motor Gong

9
10
11
12
13
14
15
16

Releasing Panel
Sprinkler
Smoke/Heat Detector
Pneumatic Actuator
Air Supply Inlet
Pressure Switch  (Air)
Check Valve
Solenoid Valve

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

54

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

deluge & preaction systems

DV-5
Deluge Valve, External Resetting Diaphragm Style – 11/2" thru 8"
Model DV-5 Deluge Valves are diaphragm type valves designed for
vertical or horizontal installation for fire protection system service.
They are used as “automatic water control valves" in deluge, preaction,
and special types of fire protection systems such as foam-water
systems. When properly trimmed, the DV-5 Valves provide actuation of
fire alarms upon system operation.
The unique diaphragm style design of the DV-5 Valve allows external
resetting. Deluge or preaction systems can be reset without having
to open a valve handhole cover and manually reposition a clapper
or latch mechanism. Simply repressurizing the diaphragm chamber
resets the valve.
The one-piece, diaphragm style design of the DV-5 allows standard
internal and external coating of the valve to provide corrosion
resistance. The internal corrosion resistance offered by the Rilsan
coating makes the DV-5 suitable for most seawater and brackish
water supplies when utilized in deluge systems. The external
corrosion resistance of the Rilsan coating permits the use of the DV-5
in corrosive atmospheres associated with many types of industrial
processing plants and outdoor installations.

d e lug e & p r e ac t i o n s ys t e m s

• Available sizes:
11⁄2" (DN40), 2" (DN50), 3" (DN80), 4" (DN100), 6" (DN150), and 8" (DN200)
• Vertical or horizontal installation
• One internal working part
• No linkage or clapper assembly
• Light weight ductile iron body
• Available with deluge and single & double interlock preaction trim
• Internally & externally coated
• Features external resetting
• Diaphragm operation
• For most seawater & brackish water supplies
• For deluge, preaction & foam systems
• Available as Flange x Flange, Flange x Groove, or
Groove x Groove body styles
• Rated for 250 psi service
• Listings and Approvals: UL, C-UL, FM, VdS
Tech Data	TFP1305

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

55

s y s t e m va lv e s & D e v i c e s

deluge & preaction systems
R ED - E - C a b i n e t ®
Integrated Fire Protection Packages

The Red-E-Cabinet is a pre-assembled fire protection valve package
enclosed within a free-standing cabinet designed to occupy minimal
floor space and to provide an aesthetically pleasing enclosure for
a fire protection valve riser. The entire package is pre-wired and
the water inlet and outlets to the valve riser are grooved to ease
installation. The valve package includes the system (manual) shut-off
control valve, automatic water control valve, as well as water flow
and supervisory switches where system air pressure is required for
either supervision or automatic water control valve actuation. An air
compressor and associated controls are also provided.
Integral to the Red-E-Cabinet door is a control panel and back-up
batteries for providing electrical alarm, supervisory, and trouble
functions. All switches within the cabinet are pre-wired to the
control panel, making the electrical connections for power, detection
circuits, and alarms the only remaining electrical connections to
complete the system.

d e lug e & p r e ac t i o n s ys t e m s

In addition to the integral control panel, windows have been provided
in the Red-E-Cabinet door for viewing the releasing panel functions
and essential system pressure gauges. A lock for the control panel
access door is standard, and a lock for the cabinet door is optional.

• The Red-E-Cabinet has been designed to
readily incorporate 11⁄2" (DN40), 2" (DN50),
3" (DN80), 4" (DN100) & 6" (DN200) valve risers
for the following types of systems:
- Deluge System – Electric Actuation
- Single Interlock Preaction System
- Double Interlock Preaction System
• Aesthetically pleasing appearance
• Professionally assembled
• Minimal installation time
• Internally pre-wired
• UL/ULC/FM components
• Custom manufactured
• Model DV-5 deluge valve (standard)
• All gauges and panel display are visible
externally
• UL, C-UL Listed, FM Approved
• The Red-E-Cabinet is constructed of 14 gauge
steel, and is free-standing. The standard paint
finish is bright red
Tech Data	TFP1300

All Four Side Panels
Easily Removed For
Ease of Maintenance

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

56

Fire Protection General Products Catalog

Tyco Fire & Building Products

a pp l i c a t i o n s :
General Purpose Valves are for use in fire protection
service applications where it is necessary to prevent reverse
flow, or where system shut-off or sectional control is desired
for closing a fire protection system after operation, or to
facilitate testing.

T yco Fire & Building Produc ts

• Prevention of
Reverse Flow
• System
Shut-Off or
Sectional
Control

• Closure of Fire
Protection
After Operation
• Facilitation of
Testing

Fire Protec tion General Products Catalog

General Purpose Valves

General Purpose VaLVes

57

s y s t e m va lv e s & D e v i c e s

general purpose valves
PRV-1

Pressure Regulating Valve – 2" thru 8" (DN50 thru DN200)
• Can be installed either vertically or
horizontally

Tech Data	TFP1580

• Available with threaded, flanged, and cut
groove inlet and outlet connections
• Grooved connections are suitable for
use with grooved pipe couplings that
are listed or approved for fire protection
service
• One piece, one moving part diaphragm

Model PRV-1 Pressure Regulating Valve

• In-line service (for maintenance)

Supply Water under Lower pressure
Air - Open to Atmosphere

• Rated for use at a maximum pressure of
125 psi (8,6 bar)
• Factory outlet “set pressure” of
250 psi (17,2 bar)
• Field outlet “set pressure” range of
80 to 150 psi (5,5 to 10,3 bar)

To
Automatic
Sprinklers

Supply Water under High pressure

• Pilot valve provides for any outlet “set
pressure”, i.e., 80 to 150 psi (5,5 to 10,3 bar)

Needle Valve

Pilot
Valve

Tamper
Cap

Regulating
Spring
Diaphragm
Chamber

(Factory Set, Do Not Adjust)

Inlet
Pressure
Gauge

Outlet
Pressure
Gauge

Waterflow
Pressure Alarm

Exit Flow

Adjusting
Screw
Locknut

To
Automatic
Sprinklers

Waterflow
Pressure Alarm

Retard
Chamber

Supply
Pressure
Gauge

Air - Under Pressure

PRV-1

DRY PIPE
SPRINKLER
RISER

WET PIPE
SPRINKLER
RISER

Automatic
Drain Valve
AD-1
Air Supply
Pressure
Gauge

Main
Drain Valve
(Normally Closed)
Main
Control Valve
(Normally Open)

Drain
Reset
Knob

Supply
Pressure
Gauge

Lower
Drain Valve
(Normally Closed)

Main
Drain Valve
(Normally Closed)
Main
Control Valve
(Normally Open)

Outlet
Pressure
Gauge
Sensing
Line

• Listings and Approvals: UL, & FM
MAIN
HEADER
Water in
200 psi

Inlet
Cavity

Diaphragm

Outlet
Cavity

Water out, reduced pressure 125 psi

HOSE
STATIONS

PRV-1

Water out, reduced pressure 125 psi

0RGHO3593UHVVXUH5HJXODWLQJ9DOYH

g e n e r a l pu r p o s e va lv e s

7KLVV\VWHPLVVKRZQLQVWDOOHGDQGUHDG\IRURSHUDWLRQ7KHUHDUHWZR359µVVKRZQLQOLQH
WRUHGXFHSUHVVXUH7KHWRSODUJHU359LVXVHGWRUHGXFHSUHVVXUHEHIRUHWKHVSULQNOHUULVHUV7KH
VHFRQG359LVXVHGWRUHGXFHZDWHUSUHVVXUHIRU)LUH'HSDUWPHQWFRQQHFWLRQV

C V-1F
Grooved Check Valve – 2" thru 10" (DN50 thru DN250)
• Can be installed either vertically or
horizontally

Tech Data	TFP1550

• Cut groove inlet and outlet connections
• Suitable for use with grooved pipe
couplings that are listed or approved for
fire protection service
• Rated for use at a maximum pressure of
300 psi (20,7 bar)
• Listings and Approvals: UL, ULC, FM

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

58

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

general purpose valves

BFV-N
Grooved Butterfly Valve – 21⁄2" thru 10" (DN65 thru DN250)
• Indicating type valves provide visual
indication of whether the valve is open or
closed
• Cut groove inlet and outlet connections
• Suitable for use with grooved pipe
couplings that are listed or approved for
fire protection service

Tech Data	TFP1510

• Rated for use at a maximum pressure of
300 psi (20,7 bar), or 175 psi (12,0 bar) for
the 10" model
• Listings and Approvals:
UL, ULC, FM, Calif. State Fire Marshall

Wafer Butterfly Valve – 2" thru 12" (DN50 thru DN300)
• Indicating type valves provide visual
indication of whether the valve is open
or closed
• Wafer connections
• Suitable for use installation between
ANSI Class 125 or 150 flanges without
the need for flange gaskets

Tech Data	TFP1515

• Rated for use at a maximum pressure
of 250 psi (17,2 bar)
• Listings and Approvals:
UL, ULC, FM, Calif. State Fire Marshall

Lug Butterfly Valve – 2" thru 12" (DN50 thru DN300))

• Lug connections
• Suitable for use installation between
ANSI Class 125 or 150 flanges without the
need for flange gaskets

Tech Data	TFP1520

• Rated for use at a maximum pressure of 250
psi (17,2 bar), or for dead end service the
maximum pressure is 200 psi (13,8 bar)
• Listings and Approvals:
UL, ULC, FM, Calif. State Fire Marshall

g e n e r a l pu r p o s e va lv e s

• Indicating type valves provide visual
indication of whether the valve is open or
closed

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

59

s y s t e m va lv e s & D e v i c e s

general purpose valves
Tr i m V a lv e s
• Designed for general service such as
shut-off, throttling, or drain valves

Tech Data	Contact TFBP for details

• Provide positive shut-off under normal
operating conditions

B u t t e rf ly V a lv e s “ B u t t e r b a l l"
• Bronze body butterfly valves are designed
specifically for fire protection applications

Tech Data	Contact TFBP for details

• Models are available in 2" and 21⁄2" NPT

• BB-SCS01 has built in tamper resistant SPDT
switch for use where proprietary or central
station supervision of open position of
valve is required

• Feature slow closure that substantially
minimizes water hammer
• May be used as sectional or small system
control valves where a distinct visual
indication of the valve status is required

• Rated for use at a maximum service
pressure of 175 psi (12,1 bar)
• Listings and Approvals: UL, ULC, and FM

DP-1
Dry Pilot Actuator
• Dry Pilot Actuator is an auxiliary releasing
device

g e n e r a l pu r p o s e va lv e s

• Designed for Preaction Valves having
double interlock electric/pneumatic
release

Tech Data	TFP1380

• Listings and Approvals: UL, ULC, FM, and
LPCB

• Rated for use at a maximum water
supply pressure of 250 psi (17,2 bar)
and a maximum system air (or nitrogen)
pressure of 50 psi (12,1 bar)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

60

Fire Protection General Products Catalog

Tyco Fire & Building Products

Specialty Items

Specialty Items complement the components used in
fire protection systems. These special items help create the
ideal configuration for any protection usage.

T yco Fire & Building Produc ts

• Automatic
Quarterly Flow
Switch Tests Per
NFPA 25
• Automatic
Actuation of
Electric &/or
Hydraulic
Alarms

• Reduce
Accidental
Manual
Shut-Off &
Unnecessary
Fire Dept.
Dispatch
• Eliminate
Expelled Water

Fire Protec tion General Products Catalog

Specialt y Items

F e at u r e s :

61

s y s t e m va lv e s & D e v i c e s

specialty items
DD - 1 ( Dr u m Dr i p )

Wiliag™ Condensate Drain
• Ready to install

Tech Data	Contact TFBP for details

• No power machine for repair
• No power machine required for cutting
pipe and making fittings
• Eliminates potential leaks
• Eliminates labor of fabrication

• Net weight only 6.25 lbs.
• Overall length 24" (615 mm)
• Turning radius 2.5" (64 mm)

• Classic look of a professional job

model fl-1
Fusible Links – 50 lb.
• Heat-activated releasing device designed
for installation in mechanically operated
systems requiring a positive acting release
mechanism
• Used extensively as releasing devices in
restaurants and industrial fire protection
systems, as well as in heat-activated
counterbalanced systems such as fire
doors, dampers and kitchen chemical
systems
• Consists of fusible alloy sealed in the
center of a bronze tube by a stainless
steel ball

Tech Data	TFP1610

• When the alloy melts, the fusible assembly
compresses, allowing it to eject from
between the two-piece strut, strut assembly
separates, activating the intended fire
protection system or device
• Releasing mechanism rated for 5-lbs. to
50-lbs. loads
• Listings and Approvals: UL and FM

Model A & B-1

sp e c i a lt y i t e m s

Pipe Line Strainers
• Model A available sizes:
– 3" (DN80), 4" (DN100), 6" (DN150),
8" (DN200) and 10" (DN250)

Tech Data	TFP1640 & TFP1642

• Model B-1 available sizes:
– 3" (DN80), 4" (DN100), 6" (DN150),
and 8" (DN200)

• Compact, lightweight, welded assembly
with flanged inlet, outlet and flushing
connection

• Available sizes:
– 6" x 6" (150 mm x 150 mm)
– 8" x 8" (200 mm x 200 mm)
– 8" with 2 - 6" outlets (200 mm with
2 - 150 mm outlets)
– 10" x 8" with 2 - 8" outlets
(250 mm with 2 - 200 mm outlets)

• Corrosion resistant Type 304 stainless
steel screen especially designed for low
pressure loss

Model B shown

• Rated for use in services up to
175 psi (12,1 bar)
• Listings and Approvals:
UL, C-UL and FM

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

62

Fire Protection General Products Catalog

Tyco Fire & Building Products

s y s t e m va lv e s & D e v i c e s

specialty items

Model C
Pipe Line Strainer
• Available sizes:
– 6" x 6" (DN150 x DN150)
– 8" x 8" (DN200 x DN200)
– 8" (DN200) with 2 - 6" outlets
(2 - 150 mm)
– 10" (DN250) x 8" (DN200) with 2 - 8"
outlets (2 - 200 mm)
• Compact lightweight welded hot dipped
galvanized assembly with flanged inlet,
outlet and flushing connection

Tech Data	TFP1644

• Corrosion resistant Type 304 stainless
steel screen especially designed for
low pressure loss
• Rated for use in services up to
250 psi (17.2 bar)
• Listings and Approvals:
UL, C-UL and FM

Model MC-1
Manual Control Station
• Provides a tamper resistant means for
emergency release

Tech Data	TFP1382

• Interconnection with the valves may be
direct via hydraulic (wet) pilot line or
indirect via pneumatic (dry) pilot line to a
Model DP-1 Dry Pilot Actuator

• Listings and Approvals:
UL, C-UL and FM

• Rated for use in services up to
250 psi (17.2 bar)

Signs
Identification Signs
• Designed to provide information to the
end user about the sprinkler system and
its components

Tech Data	TFP1615

sp e c i a lt y i t e m s

• Available with a variety of wording
combinations to meet the signage
requirements of NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

63

s y s t e m va lv e s & D e v i c e s

specialty items

F i r e D e par t m e n t C o n n e c t i o n s
Straight & 90° Fire Department Connections
• Designed for fire department use to
increase water pressure and volume
to automatic sprinkler system or
standard-pipe system

Tech Data	Contact TFBP for details

• Available in both 90° side outlet pattern
and the straight through siamese pattern

H a n g e rs
Pipe Hangers
• A full-line of pipe hangers for every fire
protection need

Tech Data	Contact TFBP for details

• Manufactured to meet the quality
standards that the industry demands

sp e c i a lt y i t e m s

• Meet the requirements of NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

64

Fire Protection General Products Catalog

Tyco Fire & Building Products

F e at u r e s :
Grooved Piping Products are designed for use in fire
protection systems and eliminate the need for screwed,
welded, or flanged connections. They provide several
economic advantages for connecting pipe and fittings
when compared to welded or flanged systems. Grooved
Piping Products also make field modifications easy, as
couplings and fittings can be rotated, added, changed, or
eliminated as necessary. Available in a wide range of sizes
and configurations. TFBP makes a full line of grooved
domestic and import products for fire protection.

T yco Fire & Building Produc ts

• Easy Field
Modifications

• Retro-fitting &
System Repair

• Quickly
Joining Steel
Pipe without
Welding

• Dampening
Noise &
Vibration
Transmission

• Rigid Connections for Long
Runs & Risers

Fire Protec tion General Products Catalog

Grooved Piping Produc ts

Grooved Piping Products

65
65

piping & elec trical devices

grooved piping products
Figure 772
Rigid Coupling - Patented
• Available sizes: 11⁄4" (DN32) through
12" (DN300)

Tech Data	TFP1850

• Specifically designed to provide rigidity in
grooved piping systems

• Standard Grade A pre-lubricated gasket

• Recommended for dry pipe and freezer
applications

• Also available with tri-seal Grade "E"
gasket for dry pipe fire protection systems,
vacuum systems, and freezer applications

• Capable of pressures up to 500 psig
(3447 kPa) depending on pipe size and
wall thickness

Figure 577
Rigid Coupling - Patented
• Available sizes: 11⁄4" (DN32) through
8" (DN200)

Tech Data	TFP1854

• Specifically designed to provide rigidity in
grooved piping systems
• Capable of pressures up to 300 psig
(2069 kPa) depending on pipe size and
wall thickness
• Standard Grade A pre-lubricated gasket

Figure 705
Flexible Coupling

g r o o v e d p i p i n g p r o du c t s

• Available sizes: 11⁄4" (DN32) through
12" (DN300)
• Provides the needed flexibility to
accommodate differential movement
• Capable of pressures up to 300 psig
(2068 kPa) depending on pipe size and
wall thickness

Tech Data	TFP1820

• Also available with tri-seal Grade E gasket
for dry pipe fire protection systems, vacuum
systems, and freezer applications

• Standard Grade A pre-lubed gasket

Figure 716
Flexible Reducing Coupling
• Available sizes: 2" x 11⁄2" (DN50 x DN40)
through 8" x 6" (DN200 x DN150)

Tech Data	TFP1830

• Allows easy transition between two
different pipe sizes and replaces two
couplings and a reducing fitting
• Faster and easier than threading,
welding or using flanges
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

66

Fire Protection General Products Catalog

Tyco Fire & Building Products

piping & elec trical devices

grooved piping products

Figure 71
Flange Adapter
• Available sizes: 2" (DN50) through 12"
(DN300)

Tech Data	TFP1880

• Allows a direct transition from flanged
components to a grooved piping system
• Bolt patterns conform to ANSI Class 125
and 150 standards

Figure 730
Mechanical Tees & Crosses
• Threaded or grooved outlet

Tech Data	TFP1860

• May be used for any tee connection where
a threaded or grooved outlet is needed
• Can be configured as a cross when
necessary

g r o o v e d p i p i n g p r o du c t s

Gr o o v e d F i t t i n g s
Elbows, Tees, Caps & Crosses
• Provide an economical and efficient
method of changing direction, adding
an outlet, reducing or capping grooved
piping systems
• Cast grooved fittings provide full flow
characteristics
• Full back stop behind the groove to ensure
proper coupling engagement and rigidity
• Wide range of grooved fabricated fittings
also available

Tech Data	TFP1810

• Full flow standard end-to-end
dimensions
• Fully listed and approved for fire
protection use
• 300 psi pressure rated
• 90° elbows and tees are also available
in the “short pattern" style

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

67

piping & elec trical devices

grooved piping products
ADAC AP®
• Used to install the last sprinkler on
grooved branch line piping or as a
drain fitting

• Available in 1⁄2", 3⁄4" and 1" outlets

• End-of-the-line sprinkler fittings eliminate
the need for an end cap and female outlet
• Can be turned down for end of line drain

Ga lva n i z e d P r o d u c t s
• Galvanized grooved piping products are
also available

g r o o v e d p i p i n g p r o du c t s

Tech Data	Contact TFBP for details

R o l l Gr o o v e rs
• Large assortment of roll groovers available
• Automatic and portable roll groovers for
1" through 24" pipe
Tech Data	Contact TFBP for details

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

68

Fire Protection General Products Catalog

Tyco Fire & Building Products

CPVC Pipe & Fittings

TFBP CPVC Pipe & Fittings manufactured with
Lubrizol's BlazeMaster® compound are listed by
Underwriters Laboratories, Inc. for use in:
• Light hazard occupancies as defined in the
Standard for Installation of Fire Sprinkler Systems,
NFPA 13
• Residential occupancies as defined in the Standard
for Installation of Fire Sprinkler Systems in
Residential Occupancies to Four Stories in Height,
NFPA 13R
• Residential occupancies as defined in the Standard
for Fire Sprinkler Systems In One and Two Family
Dwellings and Manufactured Homes, NFPA 13D
• Blazemaster Pipe and Fittings are listed and
approved for use in the widest range of
applications for any CPVC fire sprinkler systems
T yco Fire & Building Produc ts

• Light Hazard
& Residential
Occupancies

• Connections to
Copper & Steel
Piping

• Unfinished
Basements

• Resistance
of Sweating,
Condensation
& MIC

• Underground
Water Pressure
Service

• CPVC pipe and fittings
• Pipe available in sizes 3⁄4" through 3" in 10' and
15' lengths (Tech Data: IH-1900)
• Fittings available in a wide range of designs,
in sizes 3⁄4" through 3"
• Elbows, tees, crosses, couplings, sprinkler head
adapters (SHA’s), reducing tees, reducing bushings,
CPVC to grooved couplings
Fire Protec tion General Products Catalog

CPVC Pipe & Fit tings

a pp l i c a t i o n s :

69

piping & elec trical devices

cpvc pipe & threaded fittings
CPVC Pipe & Fittings
• Pipe available in sizes 3⁄4" through 3" in 10’
and 15’ lengths
• Manufactured with Lubrizol's
BLAZEMASTER® compound
• Fittings available in a wide range of
designs and sizes 3⁄4" through 3"
Tech Data	IH-1900

Bac k - t o - Bac k F i t t i n g s
• Included in the TFBP line of
BLAZEMASTER® CPVC products
• Allows two sidewall sprinklers to be
piped from one fitting
• Ideal when the CPVC piping is located
in a 31⁄2" (2" x 4") vertical wall, eliminating
the need for extra nipples, fittings and
sprinkler head adapters typically
associated with supplying two rooms
with the same pipe

Tech Data	IH-1900

• Specially designed and dimensioned to
enable the sidewall sprinklers to be
recessed with 1⁄2" or 5⁄8" sheet-rock
wall covering

C P V C t o C o pp e r F i t t i n g

c pv c p i p e & t h r e a d e d f i t t i n gs

• Available sizes: 3⁄4" through 2"

Tech Data	IH-1900

• Transition to BLAZEMASTER pipe from
traditional copper tube for plumbing
services
• Transition to steel or BLAZEMASTER
CPVC Fire Sprinkler System piping from
traditional copper tube for plumbing
services is fast, easy, and readily available
in the most complete fire sprinkler
package in the industry

C P V C H a n g e rs & S u pp l i e s
• “No Block Hanger" is a two hole strap that
eliminates blocking to the beam when
hanging CPVC pipe
• Positions the face of the pipe 11⁄2" off the
face of the joist
• Headset hanger is designed to hang CPVC
pipe and for the proper placement of the
sprinkler before the ceiling is installed

Tech Data	IH-1900

• One-Step CPVC Cement specifically
formulated for use with BlazeMaster pipe
and fittings

• Provides vertical restraint, eliminating
need for additional hangers
• BLAZEMASTER Caulk and Walk® Firestop

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

70

Fire Protection General Products Catalog

Tyco Fire & Building Products

Electrical Devices

• Easier to
Install, Set &
Maintain than
Mechanical
Accelerators
Electrical Devices (alarm and supervisory) allow
sprinkler and other fire protection systems to be interfaced
with hydraulic or electronic alarm systems so that upon
activation of the system, an electrical or mechanical signal
activates an audible or visible alarm or computerized
notification device.

T yco Fire & Building Produc ts

• Operation of
the Dry Pipe
Valve within
Four Seconds

• Built-in
High & Low
Pressure Alarm
Supervision
• Battery Backup in the Event
of Primary
Power Failure

• Proven Electric
Release
Technology

Fire Protec tion General Products Catalog

Elec
trical
De vices
Grooved
Piping
Produc ts

F e at u r e s :

71

piping & elec trical devices

electrical devices

V S R W at e rf l o w A l arm S w i t ch
Flow & Pressure Switch
• Available sizes:
2" (DN50) through 8" (DN200)

Tech Data	Contact TFBP for details

• Vane type waterflow switch for use on
wet sprinkler systems

• Retard delay is an adjustable feature that
can be set from 0 to 90 seconds

• Actuated with a minimum flow of
10 gallons per minute

• Flow condition must exist for the period of
time necessary to overcome the selected
delay period

V S R W at e rf l o w A l arm S w i t ch f o r sma l l p i p e
Flow & Pressure Switch
• Available pipe sizes:
1" (DN25), 11⁄4" (DN32), 11⁄2" (DN40) or
2" (DN50)

Tech Data	Contact TFBP for details

• Vane type waterflow switch for use on
wet sprinkler systems
• May also be used as a sectional water flow
detector on large systems
• Installs directly into a threaded tee

M o d e l P S 1 0/ P S 4 0 P r e ss u r e a l arm S w i t ch
Flow & Pressure Switch
• Designed to detect a pressure increase or
decrease in fire sprinkler systems

Tech Data	Contact TFBP for details

• PS40 switches are primarily used to
monitor low air pressure conditions in
dry systems

electrical devices

• PS10 switch is appropriate for water flow
detection

Ba l l V a lv e w i t h S u p e rv i s o r y S w i t ch
Ball Valve with Tamper & Alarm Switch
• Utilizes a 1⁄2" ball valve in combination
with a switch assembly

Tech Data	Contact TFBP for details

• Switch assembly enclosed in a tamper
resistant NEMA 4 (water resistant)
enclosure

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

72

Fire Protection General Products Catalog

Tyco Fire & Building Products

piping & elec trical devices

electrical devicecs

P C V S C o n t r o l V a lv e S u p e rv i s o r y S w i t ch
Tamper & Alarm Switch
• Weather proof and tamper resistant switch
for monitoring the open position of post
indicator, butterfly and other types of fire
sprinkler/control valves

Tech Data	Contact TFBP for details

S o l e n o i d V a lv e
For Releasing Service – 1⁄2" (DN15)
• Used in conjunction with an electric
releasing panel that is listed or approved
(as appropriate) for fire protection
releasing service, and where the releasing
panel is operated by listed or approved
(as appropriate) electric fire detectors

Tech Data	TFP2180

• Available in a variety of voltages for both
normal and hazardous locations

OSY-SU
Tamper & Alarm Switch
• Used to monitor the open position of an
OS&Y (outside screw and yoke) type
gate valve

Tech Data	Contact TFBP for details

• Mounts conveniently to most OS&Y
valves ranging in size from 2" (DN50)
to 12" (DN300)
• Can be used on some valves as small as 1⁄2"

4410-RC
Releasing Panel
• Provides the interface between detection
system, deluge or single or double
interlocked preaction valve, and signaling
circuit and devices in electrically actuated
fire protection systems

Tech Data	Contact TFBP for details

• Separate supervisory zone provided for
electronic supervision of valve position,
low pressure, and other critical fire
protection functions

• Has programming capability

• Can be used in single zone, cross zone,
sequential or cross/sequential electric
deduction systems
• Listings and Approvals: UL and FM

electrical devices

• Circulates single sprinkler flow and allows
testing of flow switch without external
discharge of water - replaces traditional
Inspector's test procedure

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

73

piping & elec trical devices

electrical devices

Ta n k M o u n t e d A i r C o mpr e ss o r
For Dry Pipe Sprinkler Systems
• Designed for the same high-performance
as base mounted units

Tech Data	Contact TFBP for details

• Compressor is mounted on an air tank
to offer further ease of installation and
availability

• Multiple dry systems may be supplied from
a single compressor tank that is a constant
source of air

• Automatic and safety features are built
into the unit, reducing installation costs

• This is the recommended air supply
method for all dry pipe sprinkler systems

Bas e M o u n t e d A i r C o mpr e ss o r
For Dry Pipe Sprinkler Systems
• Designed for high volume (cubic feet of
air per minute) at the moderate pressures
required for the system

Tech Data	Contact TFBP for details

• Sized properly, these will fill the system to
40 PSIG of air pressure in approximately
30 minutes as required in NFPA 13

R i s e r M o u n t e d A i r C o mpr e ss o r
Fully Automatic
• Fully automatic and are designed for easy
installation

Tech Data	Contact TFBP for details

• Special mounting kits with U-bolts are
available to facilitate riser mounting

electrical devices

• Sized properly, these compressors will fill
a system to 40 PSIG within 30 minutes as
required in NFPA 13

Model G16AC812
Automatic Supervisory Air Supply
• Supplies and maintains air in single
interlock preaction fire protection systems
having a nominal supervisory air pressure
of 10 psi (0.7 bar)

Tech Data	TFP1620

• Can be mounted on the floor, on a wall, or
to the system riser using optional brackets
• Listings and Approvals: UL

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

74

Fire Protection General Products Catalog

Tyco Fire & Building Products

piping & elec trical devices

electrical devicecs

DAP Series
Dry Air Pac™
General’s DAP Series Dry Air Pac™ is an FM Approved, twin tower regenerative
dryer / compressor package. This turnkey system is designed to provide the
sprinkler system with moisture free air to a -40°F Dew Point. The air compressor is
designed to fill the sprinkler system in accordance with NFPA 13 standards, as well
as provide the higher pressure needed to allow the twin tower regenerative dryer
to function properly.
Prior to entering the regenerative air dryer, an air cooled aftercooler cools the
compressor’s hot discharge air to a maximum 100°F. A coalescing prefilter with
differential pressure gauge removes oil vapor and other contaminants that can
destroy the desiccant in the dryer towers. A combination particulate filter and
regulator prevents downstream migration of desiccant dust while regulating air
pressure to the sprinkler system.
The Dry Air Pac™ is controlled by one integrated control
panel complete with flow diagram display, 120 volt control
circuit with indicating lights for tower drying, drain valve
activation and compressor operation, along with panel
mounted hour meter, separate drain valve duration and
interval controls, drain valve on/off switch and panel control
on/off switch. Four panel-mounted pressure gauges are
provided for receiver, outlet and drying tower pressures.
Purge set pressure gauge is separately mounted and
conveniently located at the purge valve for ease of setting
the purge flow.
All components are pre-piped, pre-tested, and pre-wired
for ease of mechanical and electrical installation on site. Each
unit includes a UL Listed, FM Approved Air Maintenance
Device. -100°F dew point is achievable - consult factory for
details.

• Combination after filter and regulator
• A separate port is provided for attachment of a
dewpoint-monitoring device

• A coalescing filter, with integral differential pressure gauge,
removes oil and water droplets prior to entry to into the
desiccant dryer

• Fully integrated control panel

• The single stage compressor allows for maximum efficiency.
Standard equipment includes intercooler, oil fill/breather, oil
sight glass and easily removable drain plug

• Compact air cooled after cooler

• UL, C-UL Listed, FM Approved

• Oversized mufflers

• Prefilter with differential pressure
• Vibration pads
• The Dry Air Pac™ comes fully charged with desiccant so that
no on-site desiccant installation is required at startup

Tech Data	Contact TFBP for details

• Separate desiccant fill and drain ports are provided to allow
re-charging of the dryer tanks without disassembly of the
dryer component piping

electrical devices

Applications for the Dry Air Pac™ include, but are not limited
to Freezer Rooms, Cold Storage Warehouses, Attic Spaces
and Parking Garages.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

75

piping & elec trical devices

electrical devices
LHD
Linear Heat Detection Cable

The Linear Heat Detection (LHD) cable is a combination of
advanced polymer and digital technologies which can be used on
any panel, and can detect heat anywhere along its entire length.
At the core of the LHD cable is a twisted pair of extremely low
resistance, tri-metallic conductors, sheathed in new advanced
thermal polymers. These polymers are chemically engineered to
break down at specific fixed temperatures allowing the twisted
conductors to make contact and initiate an alarm. The polymer
used for the protective outer coating of LHD cable is chemical
resistant and UV protected. This allows the LHD cable be used in a
wide variety of installations and special hazard applications.
Spot
Detection

Junction Box
Alarm/Release

Cable Strain Relief Connectors

Thermo Cable®
Tri-Metallic Core:
Steel provides tensile strength
Copper Increase conductivity
Tin for corrosion resistance

Loop Cable Ties
or other approved fastener

Leader Wires
Min. 18 AWG 18,000 ft.

Releasing

LHD Cable Secured to the Sprinkler Pipe
by Cable Ties Every 3 - 5 ft.

Advanced Polymer Thermal
Reactant Sheathing

Maximum 10,000 Feet of LHD Cable Per Zone

No Protective Tape Required

Sollenoid
Valve
J-Box or
ELR-Box
Potter® Electronic
Series PFC-4410-RC
Releasing Panel

DV-5
Deluge/Preaction Valve

Chemical and UV Resistant
Polymer Outer Covering

Cable Strain Relief Connectors

Wire O.D. 1⁄8”

Linear Heat Detection Cable allows a Quell designed fire sprinkler
system to be more efficient by quickly recognizing the fire, and
conveying the information back to the fire alarm panel.
• Ideal for double interlock preaction detection
• Install up to 10,000 linear feet per zone

electrical devices

• Compatible with any conventional releasing panel listed
for fire
• Can detect heat anywhere along the entire length of cable
• Multiple alarm temperatures can be incorporated in the
same zone

Ultra K17
Upright Sprinkler
Spaced 10 ft. Apart

10 ft.

10 ft.

• Easy to add a module
• Lower material & installation cost
• UL, C-UL Listed, FM Approved
TEMPERATURE
RANGE

155° F (68°C) (typical temperature)
172° F (78°C), 190° F (88°C)
220° F (105°C)

Available

Polyproplene, PVC, Nylon
Resistance
.05 ohms/ft resistance per twisted pair
RF Tested
Up to 10,000 linear ft.
Tech Data	Contact TFBP for details
Jacket MAterial

3-5 ft.

LHD Cable Secured
to the Sprinkler Pipe with
Guide Wire Every 3-5 ft.

3-5 ft.

3-5 ft.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

76

Fire Protection General Products Catalog

Tyco Fire & Building Products

Foam Systems

a pp l i c a t i o n s :

the balanced pressure proportioning method for
flammable liquid fire protection applications. They
are designed to accurately control the flow of a
foam liquid concentrate into a water stream over a
wide range of flow rates and pressures. Two basic
types, bladder tanks and pump systems, require the
foam concentrate pressure to be balanced with the
water pressure at the proportioner which meters
the proper amount of foam concentrate into the
water stream. The resulting foam solution is piped
to discharge devices protecting the hazard area.

T yco Fire & Building Produc ts

• Refineries
• Marine Vessels
• Warehouses

• Class B Polar
Solvent Fuel fires
such as Methyl
Alcohol, Acetone
& Ethyl Alcohol
• Loading Racks

• Special Class A
Foam
Concentrates
for Use with
Municipal
and Forest
Firefighting
Hardware &
Apparatus

• Aircraft
Hangars
Fire Protec tion General Products Catalog

Foam Systems

Foam-Water Systems most commonly use

• Class B
Hydrocarbon
Fuel Fires Such
as Crude Oils,
Gasoline, Diesel
Fuels & Aviation
Fuels

77

s p e c i a lt y s y s t e m s

foam systems

Legend:
1 Deluge Valve (DV-5)
2 Isolation Valve
3 Diaphragm Supply Valve
4 Manual Control Station
5 Automatic Shut-off Valve
6 Automatic Drain Valve
7 Pressure Switch
8 Water Motor Gong

9 Releasing Panel
10 Spray Nozzle
11 Smoke/Heat Detector
12 Solenoid Valve
13 Foam Proportioner
14 Foam Bladder Tank
15 Foam Concentrate
16 Hydraulic Ball Valve

b l a d d e r ta n Ks
Foam Bladder Tanks
• Elastomeric bladder stores foam liquid
concentrate discharged by incoming
water applying pressure to the bladder

• Foam concentrate capacities from
50 to 1500 gal (190 to 5678 L)

• Both vertical and horizontal models are
available

• Red standard system paint or coated with
an epoxy “CR” red finish for use in marine
or corrosive environments

• Internal tank perforated center tube
provides improved agent discharge

• Standard or pre-piped tanks with
proportioner for ease of installation
300 gal (1136 L) Horizontal
Tank Shown

pr o p o r t i o n e r
2" and 21⁄2" In-Line Proportioner

f oa m s ys t e m s

• Each proportioner consists of a body, inlet
nozzle, and metering orifice, all of which
are corrosion-resistant brass
• The proportioner body is designed with a
female NPT threaded inlet and a male NPT
threaded outlet in sizes of 2" or 21⁄2"

• The metering orifice is sized according to
the type and percentage of concentrate
used and is also secured with a stainless
steel retaining ring)
FOAM CONCENTRATE
INLET

• Clearly marked on the proportioner body
are the flow direction arrow, as well as the
type and percentage of concentrate for
which the proportioner was designed

JET
RETAINING RING
FOAM
SOLUTION
DISCHARGE

• The inlet nozzle is secured by a stainless
steel retaining ring
THROAT

BODY
WATER
INLET

001185

METERING ORIFICE

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

78

Fire Protection General Products Catalog

Tyco Fire & Building Products

s p e c i a lt y s y s t e m s

foam systems

I n - L i n e pr o p o r t i o n e r
In-Line Proportioner Pump System
• Maintains an equal pressure in the foam
concentrate and water inlets to the
proportioner. This allows the proportioner
to be used over a wide range of flows
and pressures. It responds quickly and
accurately to changes in the water inlet
pressures and flow rates
• Spool valve design ensures accurate
pressure regulation and rapid response to
changes in flow demand

• Six standard sizes
• Brass foam concentrate piping with
stainless steel trim accessories
• Standard for use in marine applications and
other corrosive environments
• Nameplates for valve identification
• Choice of unpainted brass or standard red
paint finish
• Used with an atmospheric foam
concentrate tank and a positive
displacement foam concentrate pump

F o am A g e n t s
ANSULITE® 1% AFFF Concentrate
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 1% solution in fresh, salt or hard water. 1% premix in fresh or potable
water. UL Listed.

ANSULITE® 1% Freeze-Protected AFFF Concentrate
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 1% solution in fresh, salt or hard water. 1% premix in fresh or potable
water. Concentrate is freeze protected to –20 °F (–29 °C). UL Listed.

ANSULITE® 3% AFFF Concentrate (AFC-3-A)
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels, and aviation fuels.
Aspirated or nonaspirated discharge devices. 3% solution in fresh, salt or hard water. 3% premix in fresh or
potable water. UL Listed.

• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 3% solution in fresh, salt or hard water. 3% premix in fresh or potable
water. UL Listed. On QPL under U.S. Military Specification MILF- 24385F.

ANSULITE® 3% Freeze-Protected AFFF Concentrate
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 3% solution in fresh, salt or hard water. 3% premix in fresh or potable
water. Concentrate is freeze protected to –20 °F (–29 °C). UL Listed.

f oa m s ys t e m s

ANSULITE® PREMIUM 3% AFFF Concentrate MIL SPEC (AFC-5-A)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

79

s p e c i a lt y s y s t e m s

foam systems

F o am A g e n t s ( c o n t. )
ANSULITE® 6% AFFF Concentrate (AFC-3)
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 6% solution in fresh, salt or hard water. 6% premix in fresh or potable
water. UL Listed.

ANSULITE® PREMIUM 6% AFFF Concentrate MIL SPEC (AFC-5)
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Aspirated
or nonaspirated discharge devices. 6% solution in fresh, salt or hard water. 6% premix in fresh or potable
water. UL Listed. On QPL under U.S. Military Specification MILF- 24385F.

ANSULITE® 3X3 Low Viscosity Alcohol-Resistant AFFF Concentrate
• Superior firefighting performance on Class B fuel fires. Used as 3% concentrate on BOTH hydrocarbon fuels
such as gasoline, fuel oil, etc., and polar solvent (water miscible) fuels such as methyl alcohol, acetone, MTBE,
etc. Low viscosity formula enhances performance with in-line eductors, balanced pressure systems and
built-in systems on firefighting vehicles. Aspirated or nonaspirated discharge devices. 3% solution in fresh,
salt or hard water. 3% premix in fresh water. UL Listed, FM and USCG Approved.

ANSULITE® ARC Alcohol-Resistant 3%/6% AFFF Concentrate
• For use on Class B fuel fires: 3% concentrate on hydrocarbon fuels such as gasoline, fuel oil, etc. and 6% on
polar solvent (water miscible) fuels such as methyl alcohol, acetone, MTBE, etc. Aspirated or nonaspirated
discharge devices. 3%/6% solution in fresh, salt or hard water. 3%/6% premix in fresh or potable water.
UL Listed and FM Approved.

ANSULITE® ARC 3 or 6 Freeze Protected

f oa m s ys t e m s

• Freeze Protected ANSULITE® ARC is intended for use as a 3% or 6% proportioned solution, depending on the
type of fuel hazad. Fresh or salt water can be used to create the foam water solution. The foam concentrate
may be stored at temperatures down to 0 °F (–18 °C) without freezing. If stored below the minimum use
temperature, freezing may occur. If freezing does occur, thaw and remix the concentrate prior to use.

3% Regular Protein Foam Concentrate
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Must be
used with air aspirating type discharge devices. 3% solution in fresh, salt or hard water. UL Listed.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

80

Fire Protection General Products Catalog

Tyco Fire & Building Products

s p e c i a lt y s y s t e m s

foam systems

F o am A g e n t s ( c o n t. )
3% Fluoroprotein Foam Concentrate
• For use on Class B hydrocarbon fuel fires such as crude oils, gasoline, diesel fuels and aviation fuels. Must be
used with air aspirating type discharge devices. 3% solution in fresh, salt or hard water. UL Listed.

SILV-EX® “Class A" Fire Control Concentrate
• Makes water at least five times more effective on many Class A deep-seated applications including wild
fires and fires found in structures, paper, tires, and coal. Proportioned from 0.1% to 1% in fresh brackish
or sea water; as a premix in fresh or potable water for long-term storage. Delivered using aspirating and
nonaspirating discharge devices, compressed air foam systems or dropped from fixed or rotary wing aircraft.
Approved by U.S. Forest Service.

ANSUL-A™ Municipal “Class A" Fire Control Concentrate
• ANSUL-A foam concentrate is formulated using fluorine-free surfactants to perform on Class A combustible
materials. ANSUL-A is compatible for use in compressed air foam systems (CAFS) over the use range of 0.1%
to 1.0%. The minimum storage temperature for this concentrate is 20 °F (–6.7 °C).

TARGET-7™ Vapor Mitigation & Neutralizing Agent
• For use on highly toxic chemicals like chlorine dioxide and titanium tetrachloride. Mitigates dangerous vapor
releases and simultaneously neutralizes (with the addition of an acidic or caustic agent, depending on the
application) the spilled material without causing additional vapor release.

H i g h - E x pa n s i o n f o am P r o d u c t s
JET-X® High-Expansion Foam Generators
• No electrical power is required
• The generators come in various sizes and
are used for both portable and fixed-system
applications

JET-X® 2 3⁄4% High-Expansion Foam Concentrate
• For use on Class A, B and LNG fires. Capable of total flooding large rooms and enclosures when used with
JET-X high expansion generators at 200:1 to 1000:1 expansion ratios (2 3⁄4% concentration). Also used with
medium-expansion equipment at 50:1 to 200:1 expansion ratios (2% concentration). Used only with air
aspirating foam discharge devices. UL Listed and FM Approved.

f oa m s ys t e m s

• Water-powered. Designed to deliver
JET-X® high expansion foam with a
maximum output capacity of 24,000 cfm
(680 cu. m/min.) The generators are of
steel construction with a water powered
motor and stainless steel foam screen

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

81

s p e c i a lt y s y s t e m s

foam systems

A ppr o v e d D i schar g e D e v i c e s f o r u s e w i t h F o am C o n c e n t rat e s
Foam liquid concentrates are suitable for use on fires involving
ordinary hydrocarbon petroleum products, and some foam
liquid concentrates may also be suitable for use on fires
involving polar solvent fuels. The fire protection system
designer first identifies the fuel load and selects the foam liquid
concentrate according to its ability to be used for a given fuel
load. Upon selecting the foam liquid concentrate, the designer
then selects equipment, including discharge devices, based
on listing/approval compatibility of the equipment with the
concentrate.

Discharge devices fall into one of four categories:
• Foam-water sprinklers
• Foam-water spray nozzles
• Non-aspirating spray nozzles
• Standard sprinklers

D3

B-1

Protectospray™ Nozzle

1⁄

Tech Data	TFP802

Tech Data	TFP840

additional info

Page 40

2"

Foam-Water Sprinkler

additional info

Page 40

EA-1

TY - B

Automatic Protectospray™
Nozzle

Upright & Pendent

Tech Data	TFP800

additional info

additional info

Tech Data	TFP151

Page 8

Page 40

TY - F R B

ELO - 231 B

Upright & Pendent

Pendent & Upright

Tech Data	TFP171

Tech Data	TFP342

additional info

Page 8

additional info

Page 20

ELO - 2 3 1 F R B

ELO - 231

Pendent & Upright

Pendent & Upright

Tech Data	TFP344

Tech Data	TFP340

additional info

f oa m s ys t e m s

Tech Data	TFP2005

Page 20

additional info

Page 20

TY - F R L
Upright & Pendent
Tech Data	TFP130
additional info

Page 10

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

82

Fire Protection General Products Catalog

Tyco Fire & Building Products

AQuaMist® Systems

a pp l i c a t i o n s :
• Cable Trays

• Historic Sites &
Museums

• Clean Rooms
• Conveyors

• Machining Centers

• Cut-Off Rooms

• Ferries

• Engine Test Cells
AQUAMIST® Systems utilize the newest and
most unique nozzles developed and approved for
fire protection. They offer an alternative to gaseous,
foam, and heavy density sprinkler systems. By
utilizing a higher pressure than a normal sprinkler
system, but a 50-80% lower water flow, the
AquaMist Systems use less water more effectively,
reduce pipe sizes and labor costs, and minimize
cleanup and water damage.

T yco Fire & Building Produc ts

• Flammable Liquid
Storage
• Food Processing
• Fuel Storage

• Offshore Platforms
• Telecommunications
• Transformers
• Vapor Suppression

• Gas Turbines

Fire Protec tion General Products Catalog

AQuaMist® Systems

• Industrial Process
Equipment

• Computer Rooms

83

s p e c i a lt y s y s t e m s

aquamist® systems

“ M C C " M i s t C o n t r o l C e n t e r w i t h R ED - E C a b i n e t ®
Pre-Assembled Fire Pump, Controller, Deluge Valve Cabinet & Releasing Panel
	The “MCC" Pump Skid Package is the self-contained control
center of the AquaMist® System. The compact skid unit
has been professionally designed and assembled to ease
system installation and to meet the most stringent project
requirements.

• Power must be provided for the control cabinet and
pump controller
• Detection circuits must be installed and wired to the
control cabinet
• An adequate water supply must be piped to the pump
supply piping inlet

Fire Pump Controller
To System

PFC4410  
Single zone,
cross zone,
or sequential
cross zone
releasing panel

Required Outlet Strainer
The pipe, fittings, hangers
and AquaMist nozzles are
to be connected to the
strainer outlet.

DV-5 Deluge
Valve
Variable Pressure
AquaMist Fire Pump

How the AquaMist System Works

aqua m i s t® s ys t e m s

1

•	Evaporation (heat extraction) is a
function of surface area of droplets
HEAT

2

•	Reducing droplet size increases
surface area

OXYGEN

VAPOR

•	Increase in surface area allows for
larger cooling effect for a given flow

3
LARGER DROPS
PENETRATE TO
BURNING SURFACE

• Fire extinguishment is improved with
direct contact of water droplets
•	This type of extinguishment is
normally associated with standard
sprinklers
•	Important part of operation if
ventilation is a factor and Class A
combustibles are present

• Water converts to vapor expanding by
a factor of 1650 times
•	Oxygen is displaced and diluted,
thereby blocking it from the fuel
source
• Higher heat level causes a faster
vaporization

4
BLOCKS RADIANT
HEAT AND
COOLS GASSES

• Small water droplets tend to remain
suspended
•	The expanding mist will expand and
cool the gases and other fuels in the
area
• Blocks the transfer of radiant heat
to the adjacent combustibles and
pre-wets them

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

84

Fire Protection General Products Catalog

Tyco Fire & Building Products

s p e c i a lt y s y s t e m s

aquamist® systems

AM10 AQUAMIST®
Open Type Mist Nozzle
• Open spray nozzles

K Factor 	K=0.24 (3,5)

• Designed for use in water mist protection
systems protecting flammable liquids and
turbine bearings

Thread Size

• Minimal water demand, approximately
3.1 GPM/nozzle at 170 psi (11,73 lpm at
11,6 bar)
• Mist represents latest in fire protection
technology

1⁄

2"

NPT
Finish 	Stainless Steel
tech data 	TD1174
• Pendent & upright designs
• Open nozzle for use on deluge systems

• For use in “low pressure" mist applications
• Minimum operating pressure is 170 psi
(11,6 bar)

AM4 AQUAMIST®
Open Type Mist Nozzle
• Open spray nozzles

K Factor 	K=0.24 (3,5)

• Listed and Approved for the protection of
flammable liquid hazards (UL/FM)

Thread Size

• Approved for protection of gas turbines (FM)
• Maximum ceiling height, 26' 3" (8 m)

1⁄

2"

NPT

Finish 	Stainless Steel
tech data 	TD1173

• Compartment volume:
– UL - 56,500 ft3 (1,600 m3)
– FM - 45,203 ft3 (1,280 m3)
• Maximum utilization of water for flammable liquid fire protection
• Nozzle coverage: maximum 172 ft2 (16 m2)
• Nozzle pressure: 185 to 250 psi
(12,8 to 17,2 bar)

AM24 AQUAMIST®
Automatic Type Mist Nozzle

• Intended applications – IMO mandated
local application system for protection of
class a machinery spaces
• Maximum distance between nozzles
(to plane of protection) - vertical clearance
nozzle spacing
– 1m to 3.5m nozzles - 13.1' (4,0 m)
spacing
– 3.5m to 5.0m nozzles - 11.5' (3,5 m)
spacing
– 5.0 m to 10.0 m nozzles - 9.8' (3,0 m)
spacing

K Factor 	0.33 Gpm/psi 0.5,

aqua m i s t® s ys t e m s

• Listed and Approved for marine type
approved by Lloyds, USCG, DNV, American
Bureau of Shipping, MCA, Germanischer
Lloyd, Bureau Veritas

(4,71 Lpm/bar 1/2)
1⁄ " NPT
Thread Size
2
Finish 	Stainless Steel
tech data 	TD1172
• Nozzle pressure: 175-250 psi
(12,07 - 17,24 bar)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

T yco Fire & Building Produc ts

Fire Protec tion General Products Catalog

85

Index
4410-RC . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

DS-ECC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Model C. . . . . . . . . . . . . . . . . . . . . . . . . . . .63

ACC-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

DV-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Model FL-1. . . . . . . . . . . . . . . . . . . . . . . . . 62

ADACAP®. . . . . . . . . . . . . . . . . . . . . . . . . . 68

EA-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40, 82

Model G16AC812. . . . . . . . . . . . . . . . . . . 74

AM10 AQUAMIST. . . . . . . . . . . . . . . . 41, 85

EC-11 & EC-14. . . . . . . . . . . . . . . . . . . . . . 12

Model MC-1. . . . . . . . . . . . . . . . . . . . . . . . 63

AM24 AQUAMIST. . . . . . . . . . . . . . . . 41, 85

EC-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

AM4 AQUAMIST. . . . . . . . . . . . . . . . . 41, 85

EC-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Model PS10/PS40 Pressure
alarm Switch. . . . . . . . . . . . . . . . . . . . . 72

AMD-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

EC-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Nozzles & Accessories. . . . . . . . . . . . 39-42

AMD-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

EC-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

OSY-SU . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

AMD-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Electrical Devices. . . . . . . . . . . . . . . . 71-76

AP “Attic Plus”. . . . . . . . . . . . . . . . . . . . . . 32

ELO SW-20/SW-24. . . . . . . . . . . . . . . . . . 14

PCVS Control Valve Supervisory
Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Approved Discharge Devices for use
with Foam Concentrates. . . . . . . . . . 82

ELO-231 . . . . . . . . . . . . . . . . . . . . . . . . 20, 82

Aquamist® Systems. . . . . . . . . . . . . . 83-85

ELO-231B. . . . . . . . . . . . . . . . . . . . . . . 20, 82

Attic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

ELOC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

AV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Escutcheon Plates. . . . . . . . . . . . . . . . . . 38

B-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40, 82

ESFR-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Back-to-Back Fittings . . . . . . . . . . . . . . . 70

ESFR-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Ball Valve with Supervisory Switch. . . 72

ESFR-25™ . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Base Mounted Air Compressor. . . . . . 74

Extended Coverage Sprinklers . . . 11-15

BB “Back-to-Back”. . . . . . . . . . . . . . . . . . . 32

F822 thru F834 Mulsifyre®. . . . . . . . . . . 42

BFV-N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Figure 577 . . . . . . . . . . . . . . . . . . . . . . . . . 66

Bladder Tanks. . . . . . . . . . . . . . . . . . . . . . 78

Figure 705 . . . . . . . . . . . . . . . . . . . . . . . . . 66

Blow-Off Plugs. . . . . . . . . . . . . . . . . . . . . 42

Figure 71. . . . . . . . . . . . . . . . . . . . . . . . . . .67

Butterfly Valves “Butterball”. . . . . . . . . 60

Figure 716 . . . . . . . . . . . . . . . . . . . . . . . . . 66

CC1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Figure 730 . . . . . . . . . . . . . . . . . . . . . . . . . 67

CC2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Figure 772 . . . . . . . . . . . . . . . . . . . . . . . . . 66

CHEC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Fire Department Connections. . . . . . . 64

Cooling Tower Nozzle. . . . . . . . . . . . . . . 42

Foam Agents. . . . . . . . . . . . . . . . . . . . 79-81

CPVC Hangers & Supplies. . . . . . . . . . . 70

Foam Systems. . . . . . . . . . . . . . . . . . . 77-82

CPVC Pipe & Fittings. . . . . . . . . . . . . 69-70

FTR-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

CPVC Pipe & Fittings. . . . . . . . . . . . . . . . 70

Galvanized Products. . . . . . . . . . . . . . . . 68

CPVC to Copper Fitting . . . . . . . . . . . . . 70

General Purpose Valves. . . . . . . . . . 57-60

CV-1F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Grooved Fittings . . . . . . . . . . . . . . . . . . . 67

CV-1FR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Grooved Piping Products . . . . . . . . 65-68

D3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40, 82

Hangers . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

DAP Series “Dry Air Pac™”. . . . . . . . . . . 75

High-Expansion Foam Products. . . . . 81

DD-1 (Drum Drip) . . . . . . . . . . . . . . . . . . 62

HIP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Deluge & Preaction Systems . . . . . 51-56

HV “High Velocity”. . . . . . . . . . . . . . . . . . 40

Deluge Systems. . . . . . . . . . . . . . . . . . . . 52

ILLUSION™. . . . . . . . . . . . . . . . . . . . . . . . . 36

Double Interlock Preaction Systems. 54

In-Line Proportioner. . . . . . . . . . . . . . . . 79

DP-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Issue D Quartzoid . . . . . . . . . . . . . . . . . . 35

DPV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

K17-231. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Dry Sprinklers. . . . . . . . . . . . . . . . . . . . . . 27

LD “Large Drop”. . . . . . . . . . . . . . . . . . . . 20

Dry Systems Valves & Devices. . . . 47-50

LFII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25

DS-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

LFII NFPA 13 Optimized Sprinklers. . . 26

DS-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29, 30

LHD Linear Heat Detection Cable. . . . 76

DS-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
DSB-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

MCC Mist Control Center with RED-ECabinet. . . . . . . . . . . . . . . . . . . . . . . . . . 84

DS-C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Model A & B-1. . . . . . . . . . . . . . . . . . . . . . 62

ELO-231 FRB . . . . . . . . . . . . . . . . . . . . 20, 82

Proportioner. . . . . . . . . . . . . . . . . . . . . . . 78
PRV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
QRS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Rapid Response™ Sprinklers. . . . . . 23-26
Red-E-Cabinet®. . . . . . . . . . . . . . . . . . . . . 56
Resi-Riser. . . . . . . . . . . . . . . . . . . . . . . . . . 46
RFII (Royal Flush II). . . . . . . . . . . . . . . 9, 15
Riser Manifolds. . . . . . . . . . . . . . . . . . . . . 45
Riser Mounted Air Compressor. . . . . . 74
Roll Groovers. . . . . . . . . . . . . . . . . . . . . . . 68
RSV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
SD “Single Directional”. . . . . . . . . . . . . . 32
Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Single Interlock Preaction Systems . . 53
Solenoid Valve . . . . . . . . . . . . . . . . . . . . . 73
Special Purpose Sprinklers. . . . . . . 31-36
Specialty Items. . . . . . . . . . . . . . . . . . 61-64
SprinkCAD®. . . . . . . . . . . . . . . . . . . . . . . . 87
Sprinkler Accessories. . . . . . . . . . . . 37-38
Sprinkler Guards . . . . . . . . . . . . . . . . 22, 38
Sprinkler Head Cabinet. . . . . . . . . . . . . 38
Standard Spray Sprinklers. . . . . . . . . 7-10
Tank Mounted Air Compressor. . . . . . 74
TFP MAX. . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TFP PH2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TFP PH5. . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Trim Valves. . . . . . . . . . . . . . . . . . . . . . . . . 60
TY-B. . . . . . . . . . . . . . . . . . . . . . 8, 21, 36, 82
TY-B & TY-FRB (Alternate Materials
of Construction). . . . . . . . . . . . . . . . . .36
TY-FRB. . . . . . . . . . . . . . . 8, 9, 14, 21, 36, 82
TY-FRL. . . . . . . . . . . . . . . . . . . 10, 14, 21, 82
TY-L . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 10, 21
TY-QRF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ultra K-17. . . . . . . . . . . . . . . . . . . . . . . . . . 19
VSR Waterflow Alarm Switch. . . . . . . . 72
Wet Systems Valves & Devices. . . . 43-46
WMA-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
WS™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

SprinkCAD ®

The Next Generation of SprinkCAD Design Software
Complete Fire Sprinkler System Design Programs Built
Upon the Industry-Leading CAD Graphics Program

SprinkCALC ™

Advanced Hydraulic Calculations
Welcome to the newest and most advanced hydraulic
calculation program available today... SprinkCALC

SprinkFDT ™
The first program to be listed by Underwriters Laboratories
and Factory Mutual specification tested for the calculation
of dry type systems per NFPA® requirements

SprinkSLIC ™

Complete Fire Sprinkler Stock Listing
The name of the game is "PIPE ON THE JOB" and
Stocklisting is the bridge between design and installation

SprinkCODE ™

Interactive NFPA 13® Code Selector
Whether it's an estimate or the final design, this Code
Expert is an essential member of your staff

www.sprinkcad.com

NORTH AMERICAN &
WORLDWIDE HEADQUARTERS
Tyco Fire & Building Products
451 N. Cannon Avenue
Lansdale, PA 19446
Tel: 215-362-0700, 800-523-6512
Fax: 215-362-5385

LATIN AMERICA
Regional Headquarters
South America, Central America &
Caribbean
1802 S.W. 2nd Street
Pompano Beach, FL 33069
Tel: 954-781-0866
Fax: 954-781-9330

EUROPE & MIDDLE EAST

AUSTRALIA

Regional Headquarters
Kopersteden 1, NL-7547 TJ
Enschede
P.O. Box 198, 7500 AD
Enschede, The Netherlands
Tel: 31-53-428-4444
Fax: 31-53-428-3377

Regional Headquarters
567 Somerville Road
Sunshine, VIC 3020
Tel: 13-00-725-688
Fax: (61) 3-9933-6204

ASIA
Regional Headquarters
No. 45 Tuas Avenue 9
Singapore 639189
Tel: 65-6861-1655
Fax: 65-6861-1312

www.tyco-fire.com
www.tyco-rapidresponse.com
www.grinnell.com
Europe & Middle East: www.tycobuilding.com
Asia: www.tyco-fire.com.cn
Australia: www.tycobuilding.com.au

TF-2008003 • Copyright ©Tyco Fire & Building Products • Printed in USA • VIS • 25M • 4/08



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Create Date                     : 2008:06:16 14:03:41-04:00
Creator                         : Adobe InDesign CS2 (4.0.5)
Modify Date                     : 2011:08:08 16:11:35-04:00
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:56:37
Instance ID                     : uuid:1ccf8229-bf40-4e5d-9df2-11bee13be754
Document ID                     : adobe:docid:indd:b959d247-e842-11dc-b205-df0137de0025
Rendition Class                 : proof:pdf
Derived From Instance ID        : b959d246-e842-11dc-b205-df0137de0025
Derived From Document ID        : adobe:docid:indd:fc202c6d-e227-11dc-a4a1-bcfedee86a1a
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 762.00, 300.00, 300.00, 72.00, 300.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 334.33, 300.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00
Manifest Placed Y Resolution    : 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 762.00, 300.00, 300.00, 72.00, 300.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 762.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 334.33, 300.00, 300.00, 300.00, 72.00, 72.00, 300.00, 300.00, 72.00, 72.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 72.00, 300.00, 300.00, 300.00, 300.00, 300.00, 762.00, 762.00, 762.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00, 300.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:4CA76D7AE7EE11DCA3E3AD6B426D3E4B, uuid:F3E320E51CF411DDBCABDF64F987667A, uuid:F3E320E51CF411DDBCABDF64F987667A, uuid:060FDD6F69B711DCB907ECDEFCCA1C10, uuid:9E3F50AB69CB11DCB405CEA3FD0362D3, uuid:C5C6BF241D0911DDBCABDF64F987667A, uuid:F3E320E91CF411DDBCABDF64F987667A, uuid:2BEFD898F4DB11DB991BFA1B093C4DED, uuid:2BEFD894F4DB11DB991BFA1B093C4DED, uuid:60AA3E12F4DB11DB991BFA1B093C4DED, uuid:5E6058BB113E11DDB5A38329F750A3A5, uuid:3D87AA9C53BD11DC9897BEE468B83813, uuid:40CB8FB6687611DCA168D72DAA5433AB, uuid:09916AE7A34911DCA7FBFBA6D2A05E54, uuid:A74B23B8136F11DDBE65D7DE8B8806A2, uuid:EB6E67BA176511DDB486823F9D8FBD0B, uuid:978E733C227B11DD8089AE7095C79C6E, uuid:978E733E227B11DD8089AE7095C79C6E, uuid:978E7344227B11DD8089AE7095C79C6E, uuid:B490EAD81CF711DDBCABDF64F987667A, uuid:060FDD6F69B711DCB907ECDEFCCA1C10, uuid:EC2D6DBB1D1211DD9D888B33B886DE79, uuid:B490EAD41CF711DDBCABDF64F987667A, uuid:087E59A71CF811DDBCABDF64F987667A, uuid:B490EADC1CF711DDBCABDF64F987667A, uuid:838C95701D0A11DDBCABDF64F987667A, uuid:3591C8521D1211DDBCABDF64F987667A, uuid:FCEF1488693411DCB7F0C0EECE461212, uuid:83AB02A6693511DCB7F0C0EECE461212, uuid:CB1917F3693511DCB7F0C0EECE461212, uuid:83AB02AB693511DCB7F0C0EECE461212, uuid:5B0C27831CF811DDBCABDF64F987667A, uuid:5B0C27881CF811DDBCABDF64F987667A, uuid:CB1917F8693511DCB7F0C0EECE461212, uuid:838C95681D0A11DDBCABDF64F987667A, uuid:0F40EC5069B911DCB405CEA3FD0362D3, uuid:0F40EC4B69B911DCB405CEA3FD0362D3, uuid:3591C8581D1211DDBCABDF64F987667A, uuid:7398B1071D0A11DDBCABDF64F987667A, uuid:838C956C1D0A11DDBCABDF64F987667A, uuid:A047B7E069B811DCB405CEA3FD0362D3, uuid:A047B7DB69B811DCB405CEA3FD0362D3, uuid:2E33FCC21D0F11DDBCABDF64F987667A, uuid:18F7F50C1D0D11DDBCABDF64F987667A, uuid:D26B2A3F1CF811DDBCABDF64F987667A, uuid:D26B2A3A1CF811DDBCABDF64F987667A, uuid:1D0742071CF911DDBCABDF64F987667A, uuid:D26B2A431CF811DDBCABDF64F987667A, uuid:EE26F8F369BA11DCB405CEA3FD0362D3, uuid:0922C76669BB11DCB405CEA3FD0362D3, uuid:0922C76E69BB11DCB405CEA3FD0362D3, uuid:9291278EFB1011DC9F3BEEC65A0F6863, uuid:9515B35F1D1211DDBCABDF64F987667A, uuid:407CC4A4E7CB11DCA3E3AD6B426D3E4B, uuid:FE788EECE7CB11DCA3E3AD6B426D3E4B, uuid:1D07420B1CF911DDBCABDF64F987667A, uuid:31FBF83CFB2D11DC9F3BEEC65A0F6863, uuid:8AA7232E69BB11DCB405CEA3FD0362D3, uuid:8AA7232E69BB11DCB405CEA3FD0362D3, uuid:D342FFDD69BB11DCB405CEA3FD0362D3, uuid:D342FFE169BB11DCB405CEA3FD0362D3, uuid:C67DECB0FB1111DC9F3BEEC65A0F6863, uuid:dd58e478-11fe-11dd-9cf7-000d93c96644, uuid:458CBB881D0211DDBCABDF64F987667A, uuid:F41C6794E61011DC88A0BDB13F7C92BF, uuid:C5C6BF2C1D0911DDBCABDF64F987667A, uuid:C5C6BF281D0911DDBCABDF64F987667A, uuid:79DDD15169BC11DCB405CEA3FD0362D3, uuid:79DDD15669BC11DCB405CEA3FD0362D3, uuid:02A5E0031D0311DDBCABDF64F987667A, uuid:458CBB911D0211DDBCABDF64F987667A, uuid:C5C6BF2C1D0911DDBCABDF64F987667A, uuid:11618DE669BD11DCB405CEA3FD0362D3, uuid:D0D309F469BC11DCB405CEA3FD0362D3, uuid:66AB192B1D0311DDBCABDF64F987667A, uuid:18F7F50F1D0D11DDBCABDF64F987667A, uuid:02A5E0071D0311DDBCABDF64F987667A, uuid:66AB19271D0311DDBCABDF64F987667A, uuid:C638FBC61D1011DDBCABDF64F987667A, uuid:11618DEF69BD11DCB405CEA3FD0362D3, uuid:332FA34C69BD11DCB405CEA3FD0362D3, uuid:332FA35069BD11DCB405CEA3FD0362D3, uuid:7F009C0C69BD11DCB405CEA3FD0362D3, uuid:9515B3621D1211DDBCABDF64F987667A, uuid:7FA6D82C1D1211DDBCABDF64F987667A, uuid:2E33FCBF1D0F11DDBCABDF64F987667A, uuid:F419B1B51D1011DDBCABDF64F987667A, uuid:E070CFE81D1011DDBCABDF64F987667A, uuid:F419B1AC1D1011DDBCABDF64F987667A, uuid:7FA6D82F1D1211DDBCABDF64F987667A, uuid:AE13FA32E93611DC963BA67F35F9FF9E, uuid:66AB19301D0311DDBCABDF64F987667A, uuid:CAB6C07B1D0311DDBCABDF64F987667A, uuid:5E6058BB113E11DDB5A38329F750A3A5, uuid:A74B23B2136F11DDBE65D7DE8B8806A2, uuid:C638FBC01D1011DDBCABDF64F987667A, uuid:CAB6C07F1D0311DDBCABDF64F987667A, uuid:E3250BB569BD11DCB405CEA3FD0362D3, uuid:55FD91CEFB2B11DC9F3BEEC65A0F6863, uuid:A74B23B2136F11DDBE65D7DE8B8806A2, uuid:81E44A661D0511DDBCABDF64F987667A, uuid:CAB6C07B1D0311DDBCABDF64F987667A, uuid:CAB6C07B1D0311DDBCABDF64F987667A, uuid:FB32630C69BD11DCB405CEA3FD0362D3, uuid:CAB6C07B1D0311DDBCABDF64F987667A, uuid:FB32630C69BD11DCB405CEA3FD0362D3, uuid:81E44A6A1D0511DDBCABDF64F987667A, uuid:34B4B17D1D0611DDBCABDF64F987667A, uuid:A74B23B2136F11DDBE65D7DE8B8806A2, uuid:EBD35830E61211DC88A0BDB13F7C92BF, uuid:16D9CB42DC8911DC97AC8FFCF1F91B5B, uuid:81E44A661D0511DDBCABDF64F987667A, uuid:CAB6C07B1D0311DDBCABDF64F987667A, uuid:9ED7B432FB2A11DC9F3BEEC65A0F6863, uuid:3591C8551D1211DDBCABDF64F987667A, uuid:34B4B1811D0611DDBCABDF64F987667A, uuid:D549163BE61311DC88A0BDB13F7C92BF, uuid:A3C5D8D869BE11DCB405CEA3FD0362D3, uuid:7F4995C5E7D011DCA3E3AD6B426D3E4B, uuid:DBCB17E6E79E11DCA3E3AD6B426D3E4B, uuid:34B4B1851D0611DDBCABDF64F987667A, uuid:34B4B1851D0611DDBCABDF64F987667A, uuid:DDAE31A61D0611DDBCABDF64F987667A, uuid:200791C169BF11DCB405CEA3FD0362D3, uuid:423B029E69BF11DCB405CEA3FD0362D3, uuid:E5B8AC5DE79F11DCA3E3AD6B426D3E4B, uuid:F3E320E11CF411DDBCABDF64F987667A, uuid:0cc21720-179c-11dd-b805-000d93c96644, uuid:A74B23B8136F11DDBE65D7DE8B8806A2, uuid:3D87AA9C53BD11DC9897BEE468B83813, uuid:DDAE31AA1D0611DDBCABDF64F987667A, uuid:423B02A669BF11DCB405CEA3FD0362D3, uuid:7214D80169BF11DCB405CEA3FD0362D3, uuid:7214D80569BF11DCB405CEA3FD0362D3, uuid:BD5E2162E61411DC88A0BDB13F7C92BF, uuid:3FC9F6F66DD311DCABF5D614BA6C5570, uuid:BDEE4520DCD811DC97AC8FFCF1F91B5B, uuid:D42FC0BCDCD911DC97AC8FFCF1F91B5B, uuid:D42FC0BFDCD911DC97AC8FFCF1F91B5B, uuid:BDEE451DDCD811DC97AC8FFCF1F91B5B, uuid:624A57801D0711DDBCABDF64F987667A, uuid:624A57881D0711DDBCABDF64F987667A, uuid:85E79A5F1D0711DDBCABDF64F987667A, uuid:4E610F0E1D0C11DDBCABDF64F987667A, uuid:85E79A681D0711DDBCABDF64F987667A, uuid:85E79A631D0711DDBCABDF64F987667A, uuid:3591C84F1D1211DDBCABDF64F987667A, uuid:E070CFEE1D1011DDBCABDF64F987667A, uuid:23C284B969C011DCB405CEA3FD0362D3, uuid:3B19279369C011DCB405CEA3FD0362D3, uuid:7721B14569C011DCB405CEA3FD0362D3, uuid:2E33FCC61D0F11DDBCABDF64F987667A, uuid:AC1BD4D31D1211DDBCABDF64F987667A, uuid:A86025291D0811DDBCABDF64F987667A, uuid:A86025311D0811DDBCABDF64F987667A, uuid:CA22D0D61D0811DDBCABDF64F987667A, uuid:A74B23B8136F11DDBE65D7DE8B8806A2, uuid:CA22D0DE1D0811DDBCABDF64F987667A, uuid:CA22D0DA1D0811DDBCABDF64F987667A, uuid:AC1BD4D31D1211DDBCABDF64F987667A, uuid:0A6013CF69C111DCB405CEA3FD0362D3, uuid:CDF3200BE79D11DCA3E3AD6B426D3E4B, uuid:B1DCDE0FE78811DCA3E3AD6B426D3E4B, uuid:248BB5F4E79A11DCA3E3AD6B426D3E4B, uuid:879A03381D0F11DDBCABDF64F987667A, uuid:879A033B1D0F11DDBCABDF64F987667A, uuid:F5B6A22D1D0811DDBCABDF64F987667A, uuid:F5B6A2311D0811DDBCABDF64F987667A, uuid:3DA1C5DA69C111DCB405CEA3FD0362D3, uuid:4C0F2DB2686211DCB0CFC2E11F908993, uuid:240EF5E2686511DCB0CFC2E11F908993, uuid:240EF5E7686511DCB0CFC2E11F908993, uuid:5D235AEFE61611DC88A0BDB13F7C92BF, uuid:8CC5876C1D0911DDBCABDF64F987667A, uuid:8CC587701D0911DDBCABDF64F987667A, uuid:9EE69C8E226211DDA0939F645741ED4F, uuid:AC81D478024311DD9A72867D861050E9
Manifest Reference Document ID  : uuid:4CA76D79E7EE11DCA3E3AD6B426D3E4B, uuid:585FBDB0DEEA11DC9498BA1D7E5386F9, uuid:585FBDB0DEEA11DC9498BA1D7E5386F9, uuid:060FDD6E69B711DCB907ECDEFCCA1C10, uuid:46839D5BF4C911DB991BFA1B093C4DED, uuid:F36D75F1F4C811DB991BFA1B093C4DED, uuid:363F96B4F4C711DB991BFA1B093C4DED, uuid:2BEFD897F4DB11DB991BFA1B093C4DED, uuid:2BEFD893F4DB11DB991BFA1B093C4DED, uuid:60AA3E11F4DB11DB991BFA1B093C4DED, uuid:4FBE0319A34B11DCB69A969863D4FD55, uuid:FBE9699C53B011DC9897BEE468B83813, uuid:F986088F687411DCA168D72DAA5433AB, uuid:09916AE6A34911DCA7FBFBA6D2A05E54, uuid:A74B23B6136F11DDBE65D7DE8B8806A2, uuid:EB6E67B8176511DDB486823F9D8FBD0B, uuid:978E733B227B11DD8089AE7095C79C6E, uuid:978E733D227B11DD8089AE7095C79C6E, uuid:978E7343227B11DD8089AE7095C79C6E, uuid:1929A46CDEE111DC9498BA1D7E5386F9, uuid:060FDD6E69B711DCB907ECDEFCCA1C10, uuid:8D3F0D9AF65311DB8126C54713534A8F, uuid:19F869D2A33711DCA7FBFBA6D2A05E54, uuid:FFA7E17FE86C11DC8782A48D3393993E, uuid:EEF44A4EE60311DC88A0BDB13F7C92BF, adobe:docid:photoshop:c7070594-3061-11d7-a4ad-e5231b1ffc5c, uuid:41307DF8D05611DAAE8CCC8BE6271632, adobe:docid:photoshop:d86411df-3061-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:e6b843f2-3061-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:bd9dcc80-3060-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:645cbc5d-64f0-11d7-b15a-a152063338e9, adobe:docid:photoshop:d17dd49d-305f-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:dafcc8a6-305f-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:8a3b7c35-3061-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:6d77207c-87ca-11d7-a001-bfb59e05bac9, adobe:docid:photoshop:22f574c3-3060-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:84f936e3-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:92bcf1d2-3062-11d7-a4ad-e5231b1ffc5c, uuid:C5057BC3680F11DC865DD4C620617CC7, adobe:docid:photoshop:b6f100fb-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:c5485fba-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:7ac87833-3060-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:7ac87837-3060-11d7-a4ad-e5231b1ffc5c, uuid:A8C68E84FB0B11DC9F3BEEC65A0F6863, uuid:5F7DA5F2682111DC865DD4C620617CC7, uuid:5F7DA5F6682111DC865DD4C620617CC7, adobe:docid:photoshop:6a778e59-3062-11d7-a4ad-e5231b1ffc5c, uuid:FDBEAD16FB0B11DC9F3BEEC65A0F6863, adobe:docid:photoshop:062f39aa-9c03-11d7-9e81-aec98a73a22f, uuid:5F7DA5FC682111DC865DD4C620617CC7, uuid:697DD407682211DC865DD4C620617CC7, uuid:7C61FE02682311DC865DD4C620617CC7, uuid:92912789FB1011DC9F3BEEC65A0F6863, uuid:D0F7EDE1682711DC865DD4C620617CC7, uuid:407CC4A3E7CB11DCA3E3AD6B426D3E4B, uuid:FE788EEBE7CB11DCA3E3AD6B426D3E4B, uuid:926B3981FB3A11DC9F3BEEC65A0F6863, uuid:31FBF83BFB2D11DC9F3BEEC65A0F6863, uuid:440DA15D682511DC865DD4C620617CC7, uuid:440DA15D682511DC865DD4C620617CC7, uuid:7901BEB9682811DC865DD4C620617CC7, uuid:E2FCDCAC682811DC865DD4C620617CC7, uuid:7901BEB2682811DC865DD4C620617CC7, uuid:7DF9678F726611DC8E7EE63BA6560C67, uuid:EA7769A5FB6211DC9F3BEEC65A0F6863, adobe:docid:photoshop:58885582-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:472101d9-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:472101d1-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:6de9b4a4-305f-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:6de9b49c-305f-11d7-a4ad-e5231b1ffc5c, uuid:817EF08868FE11DCB7F0C0EECE461212, adobe:docid:photoshop:a03552e9-7e46-11d7-8da7-fe227350e563, adobe:docid:photoshop:472101d9-3062-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:5310b494-305d-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:10e010f5-3063-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:dd1e22b7-305e-11d7-a4ad-e5231b1ffc5c, uuid:4CAA41EDD05511DAAE8CCC8BE6271632, adobe:docid:photoshop:daeb8a05-6903-11dc-a5d7-b6ca52622597, uuid:4CAA41EDD05511DAAE8CCC8BE6271632, uuid:CDF3200FE79D11DCA3E3AD6B426D3E4B, uuid:C037D6BA683C11DCB0CFC2E11F908993, uuid:C037D6BF683C11DCB0CFC2E11F908993, adobe:docid:photoshop:3dc10559-3060-11d7-a4ad-e5231b1ffc5c, uuid:9C6953B5683D11DCB0CFC2E11F908993, uuid:7071CDD7E7CD11DCA3E3AD6B426D3E4B, uuid:14B228E6E7CE11DCA3E3AD6B426D3E4B, uuid:AA45D91AE7CE11DCA3E3AD6B426D3E4B, uuid:14B228E1E7CE11DCA3E3AD6B426D3E4B, uuid:6B872466E7CF11DCA3E3AD6B426D3E4B, uuid:7071CDD2E7CD11DCA3E3AD6B426D3E4B, uuid:AA45D91FE7CE11DCA3E3AD6B426D3E4B, uuid:AA45D924E7CE11DCA3E3AD6B426D3E4B, uuid:3B5E5739684D11DCA168D72DAA5433AB, uuid:1B7705AB691B11DCB7F0C0EECE461212, uuid:4FBE0319A34B11DCB69A969863D4FD55, uuid:DDB01339E49011DCA2C7B54E5F3FF90F, uuid:0CDA29D9DC8311DC97AC8FFCF1F91B5B, uuid:4F5506E025A911DB9108F562C016C5C1, uuid:0B32EEA0693211DCB7F0C0EECE461212, uuid:9ED7B43AFB2A11DC9F3BEEC65A0F6863, uuid:DDB01339E49011DCA2C7B54E5F3FF90F, uuid:BB237937692E11DCB7F0C0EECE461212, uuid:1B7705AB691B11DCB7F0C0EECE461212, uuid:1B7705AB691B11DCB7F0C0EECE461212, uuid:27CD923F693111DCB7F0C0EECE461212, uuid:1B7705AB691B11DCB7F0C0EECE461212, uuid:27CD923F693111DCB7F0C0EECE461212, uuid:94C3108EE93711DC963BA67F35F9FF9E, uuid:D007AAF1E93711DC963BA67F35F9FF9E, uuid:DDB01339E49011DCA2C7B54E5F3FF90F, uuid:985D7FAD684811DCB0CFC2E11F908993, uuid:0CDA29DEDC8311DC97AC8FFCF1F91B5B, uuid:BB237937692E11DCB7F0C0EECE461212, uuid:1B7705AB691B11DCB7F0C0EECE461212, uuid:B095B409FB2711DC9F3BEEC65A0F6863, uuid:13C3F687DD6711DCAFDCEE2AE297F702, uuid:2BF0D74EFB6311DC9F3BEEC65A0F6863, uuid:E8731790684A11DCB0CFC2E11F908993, uuid:0C6C37B5684A11DCB0CFC2E11F908993, uuid:7F4995C4E7D011DCA3E3AD6B426D3E4B, uuid:DBCB17DFE79E11DCA3E3AD6B426D3E4B, uuid:9DB0347DFB3E11DC9F3BEEC65A0F6863, uuid:9DB0347DFB3E11DC9F3BEEC65A0F6863, uuid:2709DFCBE93811DC963BA67F35F9FF9E, uuid:4C0F2DB7686211DCB0CFC2E11F908993, uuid:796EC486691511DCB7F0C0EECE461212, uuid:E5B8AC59E79F11DCA3E3AD6B426D3E4B, uuid:136D97F44206DD1190A0B0C0941830BB, uuid:5657A424190811DDB795F3FFFCB9EFBA, uuid:A74B23B6136F11DDBE65D7DE8B8806A2, uuid:FBE9699C53B011DC9897BEE468B83813, adobe:docid:photoshop:3206f59d-71ad-11d7-b82a-f8ec1d29e726, uuid:53731259690411DCB7F0C0EECE461212, uuid:70DD6A91685111DCB0CFC2E11F908993, uuid:C9677D66685111DCB0CFC2E11F908993, uuid:10C1EA42685511DCB0CFC2E11F908993, uuid:3FC9F6F56DD311DCABF5D614BA6C5570, uuid:91DAB7FFDCD811DC97AC8FFCF1F91B5B, uuid:91DAB803DCD811DC97AC8FFCF1F91B5B, uuid:BDEE4516DCD811DC97AC8FFCF1F91B5B, uuid:47B8C874DCB711DC97AC8FFCF1F91B5B, uuid:6D1EF124685911DCB0CFC2E11F908993, uuid:47B8C86CDCB711DC97AC8FFCF1F91B5B, uuid:7CC8E29FDCA911DC97AC8FFCF1F91B5B, uuid:70DD6A95685111DCB0CFC2E11F908993, adobe:docid:photoshop:acef9def-305d-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:a24b5268-305d-11d7-a4ad-e5231b1ffc5c, uuid:5DF1F892DCE311DC97AC8FFCF1F91B5B, uuid:DE7B12CCDCE311DC97AC8FFCF1F91B5B, adobe:docid:photoshop:05f2a956-305f-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:05f2a952-305f-11d7-a4ad-e5231b1ffc5c, adobe:docid:photoshop:c570eca6-305f-11d7-a4ad-e5231b1ffc5c, uuid:05EEECB2685D11DCB0CFC2E11F908993, uuid:B3C65FD1CC1311DC93D9D994E0A2CEFF, uuid:05EEECB7685D11DCB0CFC2E11F908993, uuid:06561F58FB3C11DC9F3BEEC65A0F6863, uuid:C520B606137711DD91D7B304716E8DDD, uuid:A74B23B6136F11DDBE65D7DE8B8806A2, uuid:4A2EADED138011DD91D7B304716E8DDD, uuid:612B07AE138111DD91D7B304716E8DDD, uuid:B3C65FD1CC1311DC93D9D994E0A2CEFF, uuid:D6EE2BF1685D11DCB0CFC2E11F908993, uuid:CDF3200AE79D11DCA3E3AD6B426D3E4B, uuid:B1DCDE0EE78811DCA3E3AD6B426D3E4B, uuid:248BB5F3E79A11DCA3E3AD6B426D3E4B, uuid:248BB5F8E79A11DCA3E3AD6B426D3E4B, uuid:6F1648E2DBDC11DC8014FDC41C3D3B4D, uuid:86B54DBF685F11DCB0CFC2E11F908993, uuid:6F82096F686111DCB0CFC2E11F908993, uuid:6F820976686111DCB0CFC2E11F908993, uuid:4C0F2DB1686211DCB0CFC2E11F908993, uuid:240EF5E1686511DCB0CFC2E11F908993, uuid:240EF5E6686511DCB0CFC2E11F908993, uuid:84F84359690111DC815BD4FBD2A29AD9, uuid:38E289C67CBF11DCA6F0FED484422BD0, uuid:48B9EE84DED411DC9EC5C226BBA073A4, uuid:5A35D981024311DD9A72867D861050E9, uuid:AC81D477024311DD9A72867D861050E9
Metadata Date                   : 2011:08:08 16:11:35-04:00
Creator Tool                    : Adobe InDesign CS2 (4.0.5)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 15996 bytes, use -b option to extract)
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 88
EXIF Metadata provided by EXIF.tools

Navigation menu