IFD9506_eng_cover_20081229 Network Device IFD9506 O EN 20081208
User Manual: Network Device IFD9506
Open the PDF directly: View PDF .
Page Count: 62
Download | |
Open PDF In Browser | View PDF |
IFD9506 Ethernet Communication Module Applicaton Manual Ethernet Communication Module IFD9506 Warning 3 Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages on the device or injuries to staff. 3 Switch off the power before wiring. 3 IFD9506 is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur. 3 IFD9506 is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified professional staff familiar with the structure and operation of IFD9506 can install, operate, wire and maintain it. 3 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched on. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference. Table of Contents 1 2 INTRODUCTION...................................................................................................................................3 1.1 Features ......................................................................................................................................3 1.2 Specifications ..............................................................................................................................3 PRODUCT PROFILE & OUTLINE .......................................................................................................4 2.1 Dimension ...................................................................................................................................4 2.2 Product Profiles ...........................................................................................................................5 2.3 LED Indicators.............................................................................................................................5 2.4 RJ-11 PIN Definition ....................................................................................................................5 2.5 RJ-11 PIN Definition ....................................................................................................................5 2.6 RJ-45 PIN Definition....................................................................................................................6 2.7 RS-232 PIN Definition .................................................................................................................6 2.8 Address Switch ...........................................................................................................................6 2.9 Data Format ................................................................................................................................6 2.10 Baud Rate for Modbus Communication ......................................................................................6 2.11 Feed-through Terminal PIN Definition .........................................................................................7 3 4 INSTALLATION & WIRING ..................................................................................................................7 3.1 How to Install...............................................................................................................................7 3.2 How to Connect IFD9506 to Network..........................................................................................7 REGISTERS IN IFD9506 ......................................................................................................................8 4.1 Basic Registers (BR) ...................................................................................................................8 4.2 Explanations on BR.....................................................................................................................9 4.3 Alarm Registers (AL) .................................................................................................................12 DVP-PLC Application Manual 1 Ethernet Communication Module IFD9506 5 MONITORING FUNCTIONS .............................................................................................................. 13 5.1 Monitor Bit Registers (MB) ....................................................................................................... 13 5.2 Monitor Word Registerss (MW) ................................................................................................ 14 6 SETTING UP DEVICE ADDRESS & RELAY ADDRESS IN SLAVE MODE ..................................... 15 7 MODBUS COMMUNICATION ........................................................................................................... 15 8 7.1 Function Codes Supported....................................................................................................... 15 7.2 Exception Codes Supported..................................................................................................... 16 7.3 Device Type & Device Address................................................................................................. 16 SETTING UP SOFTWARE................................................................................................................. 16 8.1 Setting up Communication & Searching for Modules in DCISoft.............................................. 16 8.2 Basic Settings........................................................................................................................... 19 8.3 Network Settings ...................................................................................................................... 20 8.4 Setting up E-Mails .................................................................................................................... 21 8.5 Monitoring Settings................................................................................................................... 23 8.6 IP Filter ..................................................................................................................................... 24 8.7 User Defined Format ................................................................................................................ 24 8.8 Virtual COM .............................................................................................................................. 26 8.9 Security Settings....................................................................................................................... 29 8.10 Returning to Default Settings.................................................................................................... 30 9 10 WEBPAGE SETTINGS ...................................................................................................................... 30 9.1 Webpage Connection ............................................................................................................... 30 9.2 Basic Settings........................................................................................................................... 31 9.3 Setting up E-Mails .................................................................................................................... 32 9.4 IP Filter ..................................................................................................................................... 32 9.5 Security Settings....................................................................................................................... 33 9.6 Returning to Default Settings.................................................................................................... 34 9.7 Monitor Table ............................................................................................................................ 34 9.8 User Define............................................................................................................................... 36 APPLICATION EXAMPLES – DCISOFT........................................................................................... 38 10.1 Setting up & Unlocking Password ............................................................................................ 38 10.2 Password Loss (Returning to Default Settings by RS-232) ...................................................... 39 10.3 IP Filter Protection .................................................................................................................... 40 10.4 Application of E-Mail ................................................................................................................. 41 10.5 Monitoring Mode....................................................................................................................... 43 10.6 Application of Modbus Slave .................................................................................................... 44 10.7 Application of Virtual COM Port ................................................................................................ 47 11 APPLICATION EXAMPLE – WPLSOFT ........................................................................................... 52 11.1 Setting up IP Through WPLSoft................................................................................................ 52 11.2 Connecting to IFD9506 Through LAN in PC............................................................................. 56 2 DVP-PLC Application Manual Ethernet Communication Module IFD9506 1 Introduction To ensure correct installation and operation of IFD9506, please read this chapter carefully before using your IFD9506. IFD9506 is an Ethernet communication module for remote setting through Delta’s DCISoft or remote setting and communication through WPLSoft. IFD9506 has 3 digital input contacts on it. They will send out messages to designated E-Mail addresses once being triggered. IFD9506 supports Modbus TCP protocol and can be used for remote monitoring with graphic control software or human machine interface. IFD9506 can be Modbus TCP master, sending out Modbus TCP commands and controlling the peripheral equipment. IFD9506 can be a slave as well, receiving Modbus commands sent out from another master and sending the command to another Modbus communication network through Ethernet. In addition, in MDI/MDI-X auto-detect, jump wire is not needed when you choose the network cable. 1.1 1.2 Features z Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detect. z The monitor table temporarily stores the monitored data for you to fast save or acquire the data. z Supports Modbus TCP protocol (both master and slave modes) z Able to send out E-Mails when triggered. z The station address, RS-485 communication format and baud rate can be set up externally. Specifications Ethernet interface Interface RJ-45 with Auto MDI/MDIX Number of ports 1 port Transmission method IEEE802.3, IEEE802.3u Transmission cable Category 5e Transmission speed 10/100 Mbps Auto-Defect Communication protocol ICMP, IP, TCP, UDP, DHCP, SMTP, Modbus TCP COM1 Interface Mini Dim Number of ports 1 port Transmission method RS-232 Transmission cable DVPACAB215 / DVPACAB230 / DVPACAB2A30 Transmission speed 110/150/300/600/1200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 Communication protocol Modbus, Delta Configuration, User Define COM2 Interface RJ-11 Number of ports 1 port Transmission method RS-485 DVP-PLC Application Manual 3 Ethernet Communication Module IFD9506 Transmission speed 110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 Communication protocol Modbus, User Define Terminal block Interface Feed-through terminal 10PIN Transmission method RS-485 Transmission distance 1,200m Transmissioi speed 110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 Communication protocol Modbus, User Define Max. number of stations 32 Environment ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV, Communication I/O: ±2KV Noise immunity RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150kHz ~ 80MHz, 3V/m Surge Test (Biwave IEC61132-2, IEC61000-4-5): Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM Operation 0°C ~ 55 °C (temperature), 50% ~ 95% (humidity), pollution degree 2 Storage -25°C ~ 70°C (temperature), 5% ~ 95% (humidity) Vibration/shock immunity Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) Certificates IEC 61131-2, UL508 Electrical specification 2 2.1 Power supply voltage 24VDC (-15% ~ 20%) supplied by feed-through terminal Power consumption 3W Insulation voltage 500V Weight 140g Product Profile & Outline Dimension Unit: mm 4 DVP-PLC Application Manual Ethernet Communication Module IFD9506 2.2 Product Profiles 9 c Communication ports: RS-485, Ethernet, RS-232 h RS-485 LED, Reset button, Ethernet LED d POWER LED i Module name e Address switch j RS-485 connector, digital input points, power f Data format/baud rate switch k DIN rail connector supply points, earth point g Digital display 2.3 2.4 LED Indicators Name Color Function POWER Green Power supply indication RS-485 Green Displaying the status of communication port LINK/ACT Green Displaying the status of network RJ-11 PIN Definition RJ-11 sketch 2.5 PIN. Signal Definition 1 -- N/C 2 -- N/C 3 D+ Positive pole for data 4 D- Negative pole for data 5 GND Ground 6 -- N/C PIN. Signal Definition 1 -- N/C 2 -- N/C 3 D+ Positive pole for data 4 D- Negative pole for data 5 GND Ground 6 -- N/C RJ-11 PIN Definition RJ-11 sketch DVP-PLC Application Manual 5 Ethernet Communication Module IFD9506 2.6 RJ-45 PIN Definition RJ-45 sketch 2.7 2.8 2.9 PIN Signal Definition 1 Tx+ Positive pole for data transmission 2 Tx- Negative pole for data transmission 3 Rx+ Positive pole for data receiving 4 -- N/C 5 -- N/C 6 Rx- Negative pole for data receiving 7 -- N/C 8 -- N/C RS-232 PIN Definition PIN Signal Definition 1 -- N/C 2 -- N/C 3 -- N/C 4 Rx Reception data 5 Tx Transmission 6 -- N/C 7 -- N/C 8 GND Ground Address Switch Switch setting Content 01…F7 Valid node address setting Data Format Switch setting Format Switch setting Format 0 7-N-1 8 7-N-2 1 8-N-1 9 8-N-2 2 7-O-1 A 7-O-2 3 8-O-1 B 8-O-2 6 7-E-1 E 7-E-2 7 8-E-1 F 8-E-2 2.10 Baud Rate for Modbus Communication 6 Switch setting Baud rate Switch setting Baud rate 1 110 7 4,000 2 150 8 9,600 3 300 9 19,200 4 600 A 38,400 DVP-PLC Application Manual Ethernet Communication Module IFD9506 5 1,200 B 57,600 6 2,400 C 115,200 2.11 Feed-through Terminal PIN Definition PIN Signal Definition 1 SG Reference ground of signal 2 D- Data- 3 D+ Data- 4 X2 Digital input 2 5 X1 Digital input 1 6 X0 Digital input 0 7 S/S Reference ground of digital input 8 24V +24V input 9 0V 0V input 10 3 Earth ground Installation & Wiring In this section, we will introduce how to connect IFD9506 to other devices and the network. 3.1 How to Install 3.2 How to Connect IFD9506 to Network Connect IFD9506 to the Ethernet hub by CAT-5e twisted pair. Since IFD9506 has Auto MDI/MDIX function, CAT-5e twisted pair does not need to jump wire. See below for the connection between the PC and IFD9506 modules: DVP-PLC Application Manual 7 Ethernet Communication Module IFD9506 PC Master Ethernet RS-485 (Master Mode) AC motor driver 4 4.1 Temperature controller RS-485 (Slave Mode) Human machine interface Registers in IFD9506 Basic Registers (BR) BR# Attribute 0 R Model name Set up by the system; read only. The model code of IFD9506 = H’0200 Yes 1 R Firmware version Displaying the current firmwawre version in hex, e.g. V1.2 is indicated as high byte = 0x01 and low byte = 0x20. Yes Release data of the version Displaying the data in decimal form. 10,000s digit and 1,000s digit are for “month”; 100s digit and 10s digit are for “day”. For 1s digit: 0 = morning; 1 = afternoon. Example: 12191 indicates the version released in the afternoon of December 19. Yes 2 R 3 Content Explanation Default Latched Reserved 4 R/W Communication format Please refer to the table of communication format setting. No 5 R/W Baud rate Please refer to the table of baud rate setting. No 6 R/W Address For setting up the station address No 7 R Number of DI/DO points DI: high bytes; DO: low bytes 8 9 0x300 Yes Displaying the errors. Please refer to the table of error codes. 0 No Reserved R 10 8 RS-485 (Master Mode) Error code Reserved 11 R/W Communication time-out For setting up the communication time-out (ms) in Modbus TCP mode. 5,000 Yes 12 R/W Communication delay time For setting up the minimum interval time between every communication datum.。 0 Yes 13 R/W TCP connection idle time For setting up idle time for TCP communication Unit: second 30 Yes DVP-PLC Application Manual Ethernet Communication Module IFD9506 BR# Attribute 14 ~ 32 33 Content Explanation Default Latched 0 No Reserved R/W Returning to default setting Symbol “R” refers to read only; “R/W” refers to read and write. 4.2 Explanations on BR BR#0: Model N a me Explanations: 1. Model code of IFD9506 = H’0200. 2. You can read the model code in the program to see if the extension module exists. BR# 1: F irmw are Ve rs ion Explanations: The firmware version of IFD9506 is displayed in hex, e.g. H’0100 indicates version V1.00. BR# 2: Re le ase D ate o f th e Vers ion Explanations: Displaying the data in decimal form. 10,000s digit and 1,000s digit are for “month”; 100s digit and 10s digit are for “day”. For 1s digit: 0 = morning; 1 = afternoon. Example: 12191 indicates the version released in the afternoon of December 19. B R # 4: C om m u n icat io n F or m at Explanations: BR#4 low byte b7 ~ b4 Explanation Content Content b2 ~ b1 Stop bit 0: 1 stop bit 1: 2 stop bits Reserved b0 Parity bit 00: None parity bit 01: Odd parity bit 11: Even parity bit Data bit 0: 7 data bits 1: 8 data bits 0000 (0) 7-N-1 0011 (3) 8-O-1 1000 (8) 7-N-2 1011 (B) 8-O-2 0001 (1) 8-N-1 0110 (6) 7-E-1 1001 (9) 8-N-2 1110 (E) 7-E-2 0010 (2) 7-O-1 0111 (7) 8-E-1 1010 (A) 7-O-2 1111 (F) 8-E-2 RS-485 User Define 0: Disable 1: Enable Reserved 00000000 (0) Disable BR4 High byte B3 B2 COM2 RS-485 setting RS-232 User Define 0: Serial Master 0: Disable Ethernet Server 1: Enable 1: Serial Slave Ethernet Client Disable Serial Master 00000001 (1) Disable Disable B7 Explanation b3 DVP-PLC Application Manual B6~B4 Serial Master B1 B0 COM1 RS-232 setting 0: Delta Configuration 1: Modbus Mode 0: ASCII 1: RTU Delta configuration Delta configuration ASCII RTU 9 Ethernet Communication Module IFD9506 B7 00000010 (2) 00000011 (3) 00000100 (4) B6~B4 Disable Disable Disable BR4 High byte B3 B2 Disable Serial Master Disable Serial Master Disable Serial Slave 00000101 (5) Disable Disable Serial Slave 00000110 (6) 00000111 (7) 00001000 (8) Disable Disable Disable Disable Disable Enable Serial Slave Serial Slave Serial Master : 10000111 (135) 10001000 (136) : Enable Enable : Disable Enable : Serial Slave Serial Master 10001001 (137) Enable Enable Serial Master 10001010 (138) 10001011 (139) 10001100 (140) Enable Enable Enable Enable Enable Enable Serial Master Serial Master Serial Slave 10001101 (141) Enable Enable Serial Slave 10001110 (142) 10001111 (143) Enable Enable Enable Enable Serial Slave Serial Slave B1 Modbus Modbus Delta configuration Delta configuration Modbus Modbus Delta configuration : Modbus Delta configuration Delta configuration Modbus Modbus Delta configuration Delta configuration Modbus Modbus B0 ASCII RTU ASCII RTU ASCII RTU ASCII : RTU ASCII RTU ASCII RTU ASCII RTU ASCII RTU BR#5: Baud R ate Explanations: BR#5 low byte for baud rate of COM1 Communication interface Content RS-232 Explanation Data Baud rate (bps) Data Baud rate (bps) Data Baud rate (bps) 0x01 110 0x06 2,400 0x0B 57,600 0x02 150 0x07 4,800 0x0C 115,200 0x03 300 0x08 9,600 0x04 600 0x09 19,200 0x05 1,200 0x0A 38,400 BR#5 high byte for baud rate of COM2 Content RS-485 same as low byte BR#6: Address Explanations: For filling in or reading the Modbus address. The address will be displayed in the message display after being set up. 10 DVP-PLC Application Manual Ethernet Communication Module IFD9506 BR#7: Number of D I/DO Points Explanations: Read the number of DI/DO points from BR#7. BR#9: Error Code Explanations: Error code = 0 refers to no error occurring. Code Indication How to correct Node address of the scan module (when operating normally) -- F0 Returning to default setting -- F1 IFD9506 being powered -- F2 Power supply in low voltage Check if the power supply of the module works normally. F3 Internal memory detection error 1. Re-power IFD9506. If the errir still exists, try step 2. 2. Reset IFD9506. If the error still exists, send the module back to the manufacturer for repair. F4 Internal error. Manufacturing error 1. Re-power IFD9506. If the error still exists, try step 2. 2. Reset IFD9506. If the error still exists, send the module back to the manufacturer for repair. F5 Network connection error Check if IFD9506 is connected normally to the network. F6 Full number of devices connected in the network. Check if the number is too much. F7 UART setting error. Check if the RS-485, RS-232 communication format is correct. E1 Alarm 1 triggered Check alarm point 1. E2 Alarm 2 triggered Check alarm point 2. E3 Alarm 3 triggered Check alarm point 3. 01 Incorrect Modbus function Check if the Modbus instruction is correct. 02 Incorrect address Check if the Modbus instruction is correct. 03 Incorrect data Check if the Modbus instruction is correct. 04 CRC error 1. Check if IFD9506 is normally connected to RS-485. 2. Make sure the transmission speed of IFD9506 is consistent with that of other nodes on the network. 0B No response from the station 1. Check if IFD9506 is normally connected to RS-485. 2. Make sure the transmission speed of IFD9506 is consistent with that of other nodes on the network. 01 ~ F7 B R # 11: C om m u n icat io n Tim e- ou t ( ms) Explanations: For setting up the communication time-out. Default = 5,000ms. For example, if you wish to set up the communication time-out to 7 seconds manually, write 7000 into BR#11. BR# 12: C ommu n icat io n De la y Time ( ms) Explanations: DVP-PLC Application Manual 11 Ethernet Communication Module IFD9506 For setting up the minimum interval time between every Modbus communication datum. Default = 0ms. For example, if you wish to set up the communication delay time to 100ms manually, write 100 into BR#12. BR# 13: TCP Co nn ectio n Id le Time ( s) Explanations: For setting up the TCP Connection Idle time. Default = 30s. For example, if you wish to set up the idle time to 7 seconds manually, write 7 into BR#13. BR#33: R et urning to Default Sett ing Explanations: IFD9506 will return to default setting when "1" is written into BR#33. BR#33 will be cleared to “0" automatically after the returning. 4.3 Alarm Registers (AL) AL# Attribute 0 R/W 1 2 Content Explanation Default Latched Alarm point 1 0 Yes R/W Alarm point 2 0 Yes R/W Alarm point 3 0 Yes Symbol “R” refer to read only; “R/W” refers to read and write. AL #0: A la rm Po int 1 Explanations: You can designate 1 RX extension point as the alarm point by setting up the AL register in IFD9506. When the alarm point is triggered, IFD9506 will execute its corresponding function. When b15 of AL#0 is set to “1”, the gateway will execute the event immediately. When RX point is triggered, the gateway will only execute the triggered event once. Device Function b15 Enabling the function Setting b15 = 1: Enabling b15 = 0: Disabling b4 ~ b14 Reserved AL#0 b2 ~ b3 Type of event enabled when RX alarm point is triggered b3 b2 Reserved 0 0 Trigger E-Mail 0 1 Reserved 1 0 Reserved 1 1 Attribute Default Latched R/W 0 Yes R/W 0 No R/W 0 Yes R/W 0 Yes The setting will be invalid when thealarm function is being executed. 12 b1 Reserved Reserved b0 Condition for triggering RX b0 = 0: Triggered when RX input point is low b0 = 1: Triggered when RX input point is high DVP-PLC Application Manual Ethernet Communication Module IFD9506 A L #1: A la rm O ut p ut 2 Explanations: The settings for AL#1 are the same as those in AL#0. A L #2: A la rm O ut p ut 3 Explanations: The settings for AL#2 are the same as those in AL#0. 5 5.1 Monitoring Functions Monitor Bit Registers (MB) MB# Attribute 0 R/W 1 2 Content Explanation Default Latched Number of devicees Cache mode normally enabled (b15=1), monitored monitoring data in max. 16 slaves. 0 Yes R/W No. of station monitored No. of the station to be monitored 0 Yes R/W Address of the device monitored Recording the address of the device monitored. 0 Yes 3 ~ 32 R/W No. of station monitored, address of the device monitored No. of the station to be monitored; recording the address of the device monitored. 0 Yes 33 ~ 200 R/W Reserved 201 R Monitored value Every MB records the value in the 16-bit device. 0 No 202 ~ 213 R Reserved 214 R Monitored status Every MB records the status in the 16-bit device. 1 = normal; 0 = abnormal 0 No Symbol “R” refer to read only; “R/W” refers to read and write. M B #0: N um b er of D e vic e s M on i t o red Explanations: For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored. b15 is read only (Default =1: normally enabled cache mode) M B # ( O dd N u m be r) : N o . of Stati o n M on it or ed Explanations: MB#1, MB#3, MB#5…MB#33 are for setting up the station No. (0 ~ 255) to be monitored. M B # ( E ve n N u m be r) : A d dr es s of D e vic e Mo n it ore d Explanations: MB#2, MB#4, MB#6…MB#34 are for setting up the address of the device to be monitored. MB#2 01: Mo n it ore d Va lue Explanations: DVP-PLC Application Manual 13 Ethernet Communication Module IFD9506 Every MB records the values in the 16-bit device. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 MB#2 14: Mo n it ore d Stat us Explanations: Every MB records the status in the 16-bit device. 1 = normal; 0 = abnormal. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 5.2 Monitor Word Registerss (MW) MW# Attribute Content Explanation Default Latched 0 R/W Number of devices monitored Cache mode normally enabled (b15=1), monitoring data in max. 16 slaves. 0 Yes 1 R/W No. of station monitored No. of the station to be monitored 0 Yes 2 R/W Address of the device monitored Recording the address of the device monitored 0 Yes 3 ~ 32 R/W No. of station monitored, address No. of the station to be monitore; recording of the device the address of the device monitored. monitored 0 Yes 33 ~ 200 R/W Reserved 201 ~ 216 R Monitored value Every MW records the monitored value in 1 register 0 No 216 ~ 300 R Reserved 301 R Monitored status Every MW records the status in a 16-bit register. 1 = normal; 0 = abnormal 0 No Symbol “R” refers to read only; “R/W” refers to read and write. MW #0: N um b er of D e vic e s M on i t o red Explanations: For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored. b15 is read only (Default =1: normally enabled cache mode) MW # ( O dd N u m be r) : N o . of Stati o n M on it or ed Explanations: MW#1, MW#3, MW#5…MW#33 are for setting up the station No. (0 ~ 255) to be monitored. MW # ( E ven N u mb er) : A d dr ess o f D e vic e M on i t o red Explanations: MW32, MW34, MW#36…MW#34 are for setting up the address of the device to be monitored. 14 DVP-PLC Application Manual Ethernet Communication Module IFD9506 MW #2 01~#2 16: Mo n ito re d Va lu e Explanations: Every MW records the values in 1 register. MW#201 MW#202 MW#203 MW#204 MW#205 MW#206 MW#207 MW#208 MW#209 MW#210 Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10 MW#211 MW#212 MW#213 MW#214 MW#215 MW#216 Device 11 Device 12 Device 13 Device 14 Device 15 Device 16 MW #3 01: Mon ito red Statu s Explanations: Every MW records the status in a 16-bit register. 1 = normal; 0 = abnormal. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device Device 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 6 Setting up Device Address & Relay Address in Slave Mode MIP# Attribute Content 0 ~ 50 R/W Corresponding address 50 ~ 249 R/W Relay IP address Explanation Default Latched Max. 100 addresses are allowed. High byte for 1 address and low byte for 1 address. 0 YES Total 100 IPs. Every address (1 byte) corresponds to 1 IP address (4 bytes). 0 YES Symbol “R” refers to read only; “R/W” refers to read and write. M I P #0: C or re sp on d in g A d dr ess Explanations: The low byte of MIP#0 are for the first address, and the high byte are for the second address, and so on. MIP#51 ~ # 52: C or res po nd ing IP fo r t he 1s t De vic e Ad dr es s Explanations: Example 1: If you wish to convert “192.168.0.1” into “COA80001” (hex), write A8C0 into MIP#50 and H0100 into MIP#51. Example 2: Data in address 1 have to correspond to 192.168.0.8. Data in address 2 have to correspond to 192.168.0.6. To complete such settings, write H0201 into MIP#0, A8C0 into MIP#50, H0800 into MIP#51, A8C0 into MIP#52 and H0600 into MIP#53. 7 7.1 Modbus Communication Function Codes Supported Function code Explanation Devices supported 0x02 Read discrete input RX 0x03 Read holding register BR, AL, MB, MW, MIP 0x06 Write single holding register BR, AL, MB, MW, MIP DVP-PLC Application Manual 15 Ethernet Communication Module IFD9506 Function code 7.2 Explanation 0x10 Write multiple holding registers BR, AL, MB, MW, MIP 0x17 Read/write multiple holding registers BR, AL, MB, MW, MIP Exception Codes Supported Exception code 7.3 Devices supported Explanation 0x01 Illegal function 0x02 Illegal data addresss 0x03 Illegal data value 0x04 Slave device failure 0x0A Gateway path unavailable 0x0B Gateway target device failed to respond Device Type & Device Address Discrete input Device type Modbus address (Hex) 5-digit Modbus address (Dec) 6-digit Modbus address (Dec) Number RX 0x0400 ~ 0x0402 11025 ~ 11027 101025 ~ 101027 3 Holding register 8 Device type Modbus address (Hex) 5-digit Modbus address (Dec) 6-digit Modbus address (Dec) Number BR 0x0000 ~ 0x00FF 40001 ~ 40256 400001 ~ 400256 64 AL 0x0200 ~ 0x0202 40513 ~ 40515 400513 ~ 400515 3 MB 0x2000 ~ 0x20FF 48193 ~ 48448 408193 ~ 408448 256 MW 0x2200 ~ 0x23FF 48705 ~ 49216 408705 ~ 409216 512 MIP 0x2400 ~ 0x24FF 49217 ~ 49471 409217 ~ 409471 256 Setting up Software This section gives instructions on how to set up IFD9506 by DCISoft and explanations on each setup page. IFD9506 is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall. See the explanations below on the software. 8.1 Setting up Communication & Searching for Modules in DCISoft Broadcast search 1. Open DCISoft on the PC and click on the “IP Search” icon. 16 DVP-PLC Application Manual Ethernet Communication Module IFD9506 2. You will see the network modules found. DVP-PLC Application Manual 17 Ethernet Communication Module IFD9506 3. Double-click on the module to be set up to enter the setup page. The first page overviews the basic status of the module. 4. The next page is for basic network setup. Consult your ISP for relevant network settings. For other setting, see BR#4 ~ BR#6 and BR#11 ~ BR#13. 18 DVP-PLC Application Manual Ethernet Communication Module IFD9506 8.2 Basic Settings The basic settings include parameters such as module name, network settings and serial communication. The basics 1. Module name: There can be many IFD9506 modules on the network. Thus, you can set up a module name for each module to identify the module when you need to use them. 2. Master configuration: Open “Serial Master” mode or “Serial Slave” mode. 3. Network settings: Enable DHCP or static IP. Consult your ISP for other relevant settings. A. IP configuration: There are 2 types of IP, static IP and DHCP. Static IP: Preset or manually modified by the user. DHCP: Automatically updated by the server. There has to be a server in the LAN. IP Explanation Static The user enters the IP address, subnet mask and gateway. DHCP DHCP server offers the IP address, subnet mask and gateway. B. IP address: IP address os the location of the equipment on the network. Every equipment connected to the network has to have an IP address. Incorrect IP address will result in connection failure. Consult your ISP for how to set up IP address. The default IP for IFD9506 is 192.168.1.5. C. Subnet mask: Subnet mask is an important parameter for setting up the subnet, used for seeing if the destination IP and the locak equipment are in the same subnet. If not, the equipment will send the packet to the DVP-PLC Application Manual 19 Ethernet Communication Module IFD9506 gateway, and the gateway will send the packet to another subnet. Incorrect setting may cause the destination equipment unable to communicate to IFD9506. To see if your setting is correct, conduct bitwise AND operations between your IP and subnet mask and destination IP and subnet mask. If the two values obtained are the same, the two IPs are in the same subnet. The default subnet mask of IFD9506 is 255.255.255.0. D. Gateway: Gateway is the window for two different subnets, allowing the two ends in different subnets to communicate. For example, if the LAN has to be connected to WAN, it will need a gateway to bridge the communication. The IP of the gateway has to be in the same subnet as IFD9506. The default gateway of IFD9506 is 192.168.1.254. 4. Communication parameter setting: Please refer to explanations on BR#4, BR#5, and BR#6. 5. Timer setting: For setting up TCP connection idle time, Modbus time-out and minimum communication delay time for every communication data. Please refer to explanations on BR#11, BR#12, and BR#13. 8.3 Network Settings The first step for all the equipment to connect to the network is to have its own IP (Internet Protocol) address. The IP address is like a number for every equipment to be identified on the network. Setting up static IP of the PC 1. Enter Control Panel → Network Connection → click on “Local Area Connection”. 2. You will see the “Local Area Connection Status” window. Click on “Properties”. 20 DVP-PLC Application Manual Ethernet Communication Module IFD9506 3. Click on “Internet Protocol (TCP/IP)". 4. Enter “192.168.0.1” into IP address. Click on “OK” to complete the IP address setting of the PC. 8.4 Setting up E-Mails E-Mail is the abbreviation of electronic mail which transmits mails through the network. IFD9506 has E-Mail functions for the user to pre-save a segment of text message, which can be a descriptive message or error message, into the subject of the E-Mail. When the E-Mail is triggered, IFD9506 will send the messages to the DVP-PLC Application Manual 21 Ethernet Communication Module IFD9506 user by E-Mail. Mail settings 1. Mail alarm setup: There are 3 mail alarms to be set up. Check the boxes to enable the alarms. The alarm can be triggered by “low" and “high”. 2. SMTP server: When Alarm 1 is triggered, the E-Mail will first be sent to SMTP server, and SMTP server will send it to the designated address. For example, assume there is an E-Mail to be sent to Test@delta.com.tw, and SMTP server is 192.168.0.1, the E-Mail will be sent to SMTP server first, and the server will further send it to the recipient Test1@delta.com.tw. 3. E-Mail of sender: Maximum 63 Engligh characters are allowed. 4. Subject of E-Mail: You can enter the text message in the column, and the message will be placed in the subject of the E-Mail and sent to the recipient. IFD9506 is able to contain 1~3 E-Mail subjects. Max. 63 English characters are allowed for each subject. 5. E-Mail of recipient: One mail can be sent to 10 addresses according to the alarm setting. Every address allows Max. 63 English characters. For example, (see the figure above) when Alarm 1 is triggered, the E-Mail will be sent to Test1@delta.com.tw. When Alarm 2 is triggered, the E-Mail will be sent to Test2@delta.com.tw. Note: To correctly send out E-Mails, there has to be a SMTP server in the network. When we send out an E-Mail, the mail will be sent to SMTP server first, and the server will further send the mail to the designated address. 22 DVP-PLC Application Manual Ethernet Communication Module IFD9506 8.5 Monitoring Settings You can read data in designated addresses in different equipment in the network by setting up IFD9506. The data can be temporarily stored in IFD9506 for fast storing and acquisition. Setting up monitoring functions 1. Monitor bit: Device addresses for setting up the bit status of serial slave; able to read the content in the corresponding address of the designated slave. 2. Monitor word: Device addresses for setting up the word status of serial slave; able to read the content in the corresponding address of the designated slave. Note: Cache mode normally enabled, and Max. data in 16 slaves can be monitored. When the cache mode is enabled, the data you would like to read will be sent back directly from the register in IFD9506. 3. Serial slave mode: The instruction sent from the master is received and transferred to the network. Please designate the station address and relay IP address. Device address: Address of the slave PLC Relay IP address: IP of the serial master DVP-PLC Application Manual 23 Ethernet Communication Module IFD9506 8.6 IP Filter The IP filter is used for restricting the connection of the network in case some uncertain UP will cause errors. Only the IP set within a certain range can establish a connection. Other IPs will be rejected. Setting up IP filter 1. Enable IP filter function: Check the box to enable IP filter. 2. IP address: IP addresses that are allowed to establish connections. Max. 8 IPs are allowed. 3. Netmask: Subnet mask of the UP that is allowed to establish a connection. To see whether the subnet mask is allowed, conduct bitwise AND operation between the allowed IP and subnet mask and destination IP and subnet mask. If the two values obtained are the same, the subnet mask is allowed by the network. For example, assume the IP is 192.168.0.1 and subnet mask 255.255.255.0, the IPs allowed to establish connections will become 192.168.0.0 ~ 192.168.0.255. 8.7 User Defined Format You can define your own format for the data to be transmitted. The items to be defined include the fixed length, start item and stop item. Select RS-232 or RS-485 to connect the device 24 DVP-PLC Application Manual Ethernet Communication Module IFD9506 Switch to “User Define” page to set up the “Fix Length”, “Start Item” and “Stop Item". 1. Listen Port/Destination Port: Range: 1024 ~ 65535. 2. Fix Length: When this is set, IFD9506 will transmit data following the fixed length. 3. Start Item: The start item of data. Range: 1 ~ 3 DVP-PLC Application Manual 25 Ethernet Communication Module IFD9506 4. Stop Item: The stop item of data. Range: 1 ~ 3 When the start item and stop item are set, IFD9506 will transmit data following the start item and stop item. If the transmission time exceeds the Modbus time-out, IFD9506 will dispose of incomplete data. Note: When using two IFD9506 modules as Mater and Slave and its user define functions, the settings of the fixed length, start item and stop item have to be consistent. If not, the data will be filtered automatically. 8.8 Virtual COM Virtual COM converts the data transmitted to RS-232 to Ethernet. Select “User Define COM”. Switch to “User Define” page and “Listen Port”. 26 DVP-PLC Application Manual Ethernet Communication Module IFD9506 Open Virtual COM setup page DVP-PLC Application Manual 27 Ethernet Communication Module IFD9506 Press “OK”, and you will see all the devices connected on the network. Select the module you need and press “OK”. Relevant information of the device will be imported automatically. Press “OK” to complete the setup. Once the setup is successful, you can see the virtual COM you set in the Device Manager. 28 DVP-PLC Application Manual Ethernet Communication Module IFD9506 8.9 Security Settings To prevent the set values in IFD9506 from being modified, you can set up passwords to lock the settings in IFD9506. Setting up password 1. Password setup: Check the "Modify” box to set up the password. 2. Password: Max. 4 characters. 3. Confirm password: Enter the new password again. 4. See “10.1 Application Examples” for more details. DVP-PLC Application Manual 29 Ethernet Communication Module IFD9506 Note: Once the password is locked, all the pages cannot be set up unless you unlock the password. However, if you set up IFD9506 by RS-232, you can return the setting to default one whether the password is locked or not. For example, if you have locked IFD9506 but forget the password, you have to return IFD9506 to default setting by RS-232, and all the settings will return to default ones. 8.10 Returning to Default Settings If you need to clear all the settings after many modifications on the settings and return the settings to default ones, check the “Factory Setting” box. Returning to default settings Check “Factory Setting” box and click on “Yes”. Note: If you set up IFD9506 by RS-232, you can return to settings to default ones whether the password is locked or not. It will take approximately 10 seconds to return to default settings, so DO NOT switch off the power within the 10 seconds. Besides, you can also press “Reset” button for 2 seconds to return to default settings. 9 Webpage Settings This section introduces how to set up IFD9506 through webpages and explains how to set up columns in each page. IFD9506 is set up by UDP port 20006. Please be aware of the relevant settings for the firewall. 9.1 Webpage Connection Enable webpage function 1. Open the webpage browser and enter the IP address of IFD9506 in the address column. 2. See below for the items to be set up. The block on the left hand side shows the basis status of IFD9506. 30 DVP-PLC Application Manual Ethernet Communication Module IFD9506 9.2 Basic Settings The basic settings include parameters as module name, network functions and serial communication. For network settings, please consult your Internet service provider. For other settings, please refer to BR#4 ~ BR#6 and BR#11 ~ BR#13. The basics For how to set, see 8.2. DVP-PLC Application Manual 31 Ethernet Communication Module IFD9506 9.3 Setting up E-Mails E-Mail is the abbreviation of electronic mail which transmits mails through the network. IFD9506 has E-Mail functions for the user to pre-save a segment of text messages, which can be a descriptive message or error message, into the subject of the E-Mail. When the E-Mail is triggered, IFD9506 will send the messages to the user by E-Mail. E-Mail settings 1. Mail Alarm: There are 3 mail alarms available. Check the alarm to enable that alarm. Every alarm can be triggered by falling edge or rising edge. 2. 9.4 For how to set up SMTP server, E-mail subject and recipients, see 8.4. IP Filter The IP filter is used for restricting the connection of the network in case some uncertain IP will cause errors. Only the IP set within a certain range can establish a connection. Other IPs will be rejected. 32 Setting up IP filter DVP-PLC Application Manual Ethernet Communication Module IFD9506 For how to set, see 8.6. 9.5 Security Settings To prevent the set values in IFD9506 from being improperly modified in a well designed network environment, you can set up passwords to lock the settings in IFD9506. How to set up passwords 1. Setting up password: You can enter maximum 4 characters in the password column to set up the password. Leave the column blank to unlock the password protection. 2. Confirming password: Enter the new password again. Note: Once IFD9506 is locked by the password, all the pages can only be set up after the password is unlocked. However, if IFD9506 is set up through RS-232 COM port, you can return all settings to default settings no matter IFD9506 is locked by the password or not. For example, supposed your IFD9506 is locked but you forget the password, you can return all the settings to default settings through RS-232 COM port. DVP-PLC Application Manual 33 Ethernet Communication Module IFD9506 9.6 Returning to Default Settings You can easily return all the settings to default ones on the page after you have modified those settings several times. How to return to default settings Check “Factory Setting” and press (Y), all the settings in IFD9506 will return to default settings. Note: Returning all the settings in IFD9506 to default ones through RS-232 COM port can be done no matter IFD9506 is locked by the password or not. The entire process will take approximately 10 seconds, and please DO NOT switch off the power during this 10 seconds. To return to default settings, you can also press the “Reset” button for 2 seconds. 9.7 Monitor Table By setting up IFD9506, you will be able to read data in specific addresses on the network and store the data temporarily in IFD9506. This realizes fast data storage and retrieval. 34 How to monitor master DVP-PLC Application Manual Ethernet Communication Module IFD9506 1. Monitor Bit: For setting up the address of the bit-type serial slave, and for you to read the content in the designated slave. 2. Monitored content: Displaying the value monitored in the address. 3. Monitored value status: The value monitored can be disaplayed in hex or decimal forms. 4. Monitor Word: For setting up the address of the word-type serial slave, and for you to read the content in the designated slave. Note: Cache mode normally enabled, and Max. data in 16 slaves can be monitored. When the cache mode is enabled, the data you would like to read will be sent back directly from the register in IFD9506. How to monitor slave DVP-PLC Application Manual 35 Ethernet Communication Module IFD9506 1. Serial slave mode (Used when the communication protocol is Modbus TCP): The instruction sent from the master is received and transferred to the network. Please designate the station address and relay IP address. Device address: Slave PLC address (The Gateway address and PLC address cannot be the same) Relay IP address: Serial mater IP 9.8 User Define You can define your own format for data to be transmitted. The items to be defined include the fixed length, start item and stop item. 36 Select RS-232 or RS-485 to connect the device DVP-PLC Application Manual Ethernet Communication Module IFD9506 Switch to “User Define” page to set up the “Fix Length”, “Start Item” and “Stop Item”. 1 ~ 256 1. Listen Port/Destination Port: Range: 1024 ~ 65535. 5. Fix Length: When this is sest, IFD9506 will transmit data following the fixed length. DVP-PLC Application Manual 37 Ethernet Communication Module IFD9506 6. Start Item: The start item of data. Range: 1 ~ 3 7. Stop Item: The stop item of data. Range: 1 ~ 3 When the start item and stop item are set, IFD9506 will transmit data following the start item and stop item. If the transmission time exceeds the Modbus time-out, IFD9506 will dispose of incomplete data. Note: When using two IFD9506 modules as Mater and Slave and its user define functions, the settings of the fixed length, start item and stop item have to be consistent. If not, the data will be filtered automatically. 10 Application Examples – DCISoft 10.1 Setting up & Unlocking Password Application Setting up password by IFD9506 configuration Steps (1) Set up password in IFD9506. (2) Unlock IFD9506. 1. See 8.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “Security" page. 3. Check “Modify” and enter “aabb” in “Password” and “Confirm Password” columns. Click on “OK” to save the password. 38 DVP-PLC Application Manual Ethernet Communication Module IFD9506 4. Open the setup page again, and IFD9506 is now locked by the password. You cannot open any of the settings now. To unlock the password, check “Unlock” and enter your original password. 10.2 Password Loss (Returning to Default Settings by RS-232) Application Returning to default settings by RS-232. Steps (1) Set up password in IFD9506. (2) Supposed the password is forgotten, return to default settings through RS-232. DVP-PLC Application Manual 39 Ethernet Communication Module IFD9506 1. Use DVPACAB2A30 cable to connect the PC and IFD9506. Open the setup page. 2. Check “Factory Setting” box and the warning dialog box will appear. Click on “Yes” to return to default settings (in approx. 5 ~ 10 seconds), and the password will be cleared as well. 10.3 IP Filter Protection Application Setting up IP filter protection. Only connections to 192.168.0.7 and 172.16.0.1 ~ 172.16.0.255 are allowed. Steps (1) Check "Enable IP Filter” box. (2) Set up IP address to “192.168.0.7” and netmask to “255.255.255.255”. (3) Set up IP addres to “172.16.0.1” and netmask to “255.255.255.0”. 1. See 8.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “IP Filter” page. 3. Check “Enable IP Filter” box. Enter “192.168.0.7” into No. 1 IP and “255.255.255.255” in all “Netmask” columns. 40 DVP-PLC Application Manual Ethernet Communication Module IFD9506 4. Enter “172.16.0.1” in No. 2 IP and “255.255.255.0” in No. 2 Netmask column. Click on “OK” to complete the setting. Only the equipment within the UP range can be connected. 10.4 Application of E-Mail Application Sending E-Mail to notify the administrator when Alarm 1 is triggered. Steps (1) (2) (3) (4) Check “Alarm 1” to enable it. Set the IP of SMTP server to ”192.168.1.99” and "Mail From” to “Message@Delta” Set the E-mail Subject of Event to “MAIL ALARM”. Set the E-mail addres of administrator to test@sample.com. DVP-PLC Application Manual 41 Ethernet Communication Module IFD9506 1. See 8.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “Mail” page. 3. Setting up “Mail” page and check “Mail Alarm Setup”. Enter SMTP server address, “Mail From” column, “Subject of Event”and “Recipient E-mail Address”. For example, when Alarm 1 is triggered, the mail will be sent to test@Delta.com. Trigger Alarm 1 by “low”. Enter 192.168.1.99 into “SMTP Server” column and Mail From Message@Delta. Enter “MAIL EVENT” as the subject and recipient e-mail address as test@delta.com.tw. Check “Alarm 1” and press “OK” to complete the settings. 42 DVP-PLC Application Manual Ethernet Communication Module IFD9506 10.5 Monitoring Mode Application Writing the address of the device to be monitored into the monitor table. Steps (1) Use monitor bit and monitor word functions. (2) Monitor bit data in station address 1, H100 and H300, and word data in station address 1 H150. (3) Monitor bit data in station address 2, H200. (4) Monitor word data in station address 3, H200. (5) Monitor wird data in station address 4, H100. (6) Monitor bit quantity: 3; monitor word quantity: 3 1. See 8.1 for how to set up communication. 2. Open IFD9506 Configuration page and switch to “Monitor” page. 3. The settings: DVP-PLC Application Manual 43 Ethernet Communication Module IFD9506 Note: When the cache mode is enabled, all the read data will be read from IFD9506. In this way, the read speed can be enhanced. 10.6 Application of Modbus Slave Application Giving Modbus command from HMI to remote device. Steps (1) HMI sends out the instruction. (2) Set the IP of slave IFD9506 to “192.168.1.6”, station address to “7” and communication format to “38400, 8, E, 1, RTU”. (3) In the IFD9506 serial slave mode table, set the device address to “1” and “3”, the two relay IPs to “192.168.1.5”. (4) Set the IP of master of IFD9506 to “192.168.1.5", station address to “8” and communication format to “38400, 8, E, 1, RTU”. (5) HMI master and IFD9506 slave transmit data through RS-485. (6) IFD9506 slave and IFD9506 master transmit data through Ethernet. (7) The RS-485 terminal on IFD9506 master is connected to two devices, which are PLC at station address 0x0001 and PLC at station address 0x0003. Assume the communication format is “38400, 8, E, 1, RTU”. 1. The wiring: 44 DVP-PLC Application Manual Ethernet Communication Module IFD9506 2. Setting up HMI editing software, Screen Editor: Step 1: Open Screen Editor, “File" Æ “New”. In the “Base Port Controller” column, select “Delta Controller RTU”. Step 2: “Option” Æ “Configuration”. Set up the communication format in “Communication” page. As below, set it to RS-485 communication mode. DVP-PLC Application Manual 45 Ethernet Communication Module IFD9506 Step 3: If you want to control the On/Off of Y0 (Y0 address: 0500) of PLC at station address 0x0001 and On/Off of Y0 (Y0 address: 0500) of PLC at station address 0x0003, select “Maintained” button and create the button on the screen. Step 4: Create two “Maintained” buttons. (a) Click on the button on the left hand side first. You will see the information of the button in the “Property” window on the right hand side of the screen. Click on “Write Address” to set up the address of Y0 (0500) and the address of the PLC (1). Select “Base Port” in “Link” column and “RWB-“ in “Device Type” column. (b) Next, set up the button on the right hand side. Follow (a) step and modify the address of the PLC as “3”. 46 DVP-PLC Application Manual Ethernet Communication Module IFD9506 Press it to complete the setup. Step 5: “Compile” first and “Download Screen and Recipe” to complete the setups in the HMI. Compile Download Screen and Recipe 10.7 Application of Virtual COM Port Application Steps Through the virtual COM port, IFD9506 is able to transmit the data sent to RS-232 to the Ethernet by connencting to the software supporing serial ports, e.g. Delta’s WPLSoft, VFDSoft and ASDA-Soft. See the example below for how to connect IFD9506 to VFD-E AC motor drive through the virtual COM port by VFDSoft. (1) Select “User Define” protocol and set the parameters in the serial master and serial slave to the ones consistent with those in VFD-E. (2) Open Delta VFDSoft, set up the communication format (COM Setup) and establish the connection. 1. Setting up Virtual COM Port For the COM setting, select “User Define” and set the communication parameters to the ones consistent with those in VFD-E. DVP-PLC Application Manual 47 Ethernet Communication Module IFD9506 48 Switch to “User Define” page and select “Listen Port”. Open Virtual COM setup page DVP-PLC Application Manual Ethernet Communication Module IFD9506 Press “OK”, and you will see all the devices connected on the network. Select the module you need and press “OK”. Relevant information of the device will be imported automatically. Press “OK” to complete the setup. DVP-PLC Application Manual 49 Ethernet Communication Module IFD9506 Once the setup is successful, you can see the virtual COM you set in the Device Manger. 2. Using Virtual COM in Delta VFDSoft 50 Open Delta VFDSoft. DVP-PLC Application Manual Ethernet Communication Module IFD9506 Set up communication format (COM Setup) Enter the virtual COM (COM2) set in the previous steps to “Com Port” column. Next, enter the communication format of VFD-E (38400, 7, E, 1) and press “Test" button. Once the “Success” light is ON, the communication test is regarded successful. Press “OK”, and IFD9506 will be able to communicate with VFD-E by VFDSoft. DVP-PLC Application Manual 51 Ethernet Communication Module IFD9506 11 Application Example – WPLSoft You can set up IFD9506 by WPLSoft software. See the examples below for how to set up the communication connection. Columns in every setup page in WPLSoft are the same as those in DCISoft. Please refer to section 10 for relevant settings. 11.1 Setting up IP through WPLSoft Application Setting up network parameters of IFD9506 directly from the PC. Steps (1) The IP of the PLC executing WPLSoft is “192.168.1.2”. (2) Subnet mask: 255.255.255.0; Gateway: 192.168.1.254 (3) Modify the network parameter of IFD9506. (4) Connecting the PC and IFD9506 by RJ-45 network cable. Note: Both PC and IFD9506 cannot adopt DHCP but static IP. 1. The connections: 2. Open “Communication Setting” in WPLSoft. 52 DVP-PLC Application Manual Ethernet Communication Module IFD9506 3. Select “Ethernet” and press “OK”. 4. Press “broadcast” icon to search for all IFD9506 modules on the network. DVP-PLC Application Manual 53 Ethernet Communication Module IFD9506 5. Designate an IFD9506 module and double click on it to open the setup page. 6. You will first see the “Basic” page. 54 DVP-PLC Application Manual Ethernet Communication Module IFD9506 7. Switch to “Network” page. 8. Enter “IP Address: 192.168.0.4”, “Netmask: 255.255.255.0”and “Gateway:“192.168.0.1”. Press “OK” to save the settings into IFD9506, and WPLSoft will search for IFD9506 automatically again. DVP-PLC Application Manual 55 Ethernet Communication Module IFD9506 9. You will see the IP address of IFD9506 has been modified to 192.168.0.4. 10. Click on DELTA IFD9506, and it will be able to communicate to MPU through WPLSoft. 11.2 Connecting to IFD9506 through LAN in PC Application Setting up network parameters of IFD9506 through LAN in WPLSoft. Steps (1) Connect IFD9506 to PC through KAN by using DHCP server. Note: You can use RJ-45 network cable with/without jump wire. 1. The connection: 56 DVP-PLC Application Manual Ethernet Communication Module IFD9506 PC1 Master PC2 Master Ethernet Ethernet 7x 8x 9x 1x 2x 3x 10x 11x 12x 7x 8x 9x 4x 5x 6x 1x 2x 3x 10x 11x 12x 4x 5x 6x C 7 8 9 101112 A 12 34 56 A B Ethernet Ethernet 2. Open “Communication Setting” in WPLSoft. 3. Select “Ethernet” and press “OK”. DVP-PLC Application Manual 57 Ethernet Communication Module IFD9506 4. Press “broadcast” icon to search for all IFD9506 modules on the network. The IFD9506 module will be detected in “View → Workspace → Communication” window or “View → Workspace → Project” window. (The default module name is DELTA IFD9506, IP:192.168.1.5) 5. Designate IFD9506 module and double click on it to open the setup page. 58 DVP-PLC Application Manual Ethernet Communication Module IFD9506 6. In “Basic” page, you can modify the module name for easier identification. 7. Next, set up the new IP address of IFD9506. In “Network” page, select DHCP in “IP Configuration” if there is DHCP server in LAN. If not, select static IP, but please be noted that the subnet mask and gateway settings have to be the same as the settings in the same LAN. DVP-PLC Application Manual 59 Ethernet Communication Module IFD9506 Press “OK” to save the settings into IFD9506. 8. WPLSoft will search for IFD9506 automatically again. You will see the IP address of IFD9506 has been modified to 172.16.155.19. 9. Click on DELTA IFD9506, and it will be able to communicate to MPU (e.g. upload/download of program, monitoring device). 60 DVP-PLC Application Manual
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:12:29 14:25:43+08:00 Create Date : 2008:12:29 14:25:43+08:00 Format : application/pdf Title : Microsoft Word - IFD9506_eng_cover_20081229.doc Creator : PATTY.LIN Document ID : uuid:d5bd4a3a-0cd9-45a2-a9cc-5baba48b5c58 Instance ID : uuid:b09b5fa7-38be-443d-b48c-b207e15387f5 Page Count : 62 Author : PATTY.LINEXIF Metadata provided by EXIF.tools