Installation_ing_Troublesho Side By MSD2356AEA Installation Ing Troubleshooting Starters Overload Relays

User Manual: Side by Side MSD2356AEA

Open the PDF directly: View PDF PDF.
Page Count: 34

DownloadInstallation_ing_Troublesho Side By MSD2356AEA Installation Ing Troubleshooting Starters Overload Relays
Open PDF In BrowserView PDF
L&T SWITCHGEAR
SAFE & SURE

OVERLOAD RELAYS, STARTERS
TESTING, INSTALLATION &
TROUBLE SHOOTING.

E S P
SERVICE
MANUAL

TESTING OF THERMAL OVERLOAD RELAY
1.

Fill up the following data of relay under test.
a) Relay Type _____________________

b) Relay Range ____________________

c) Max. Back up fuse rating __________
2.

Check continuity of auxiliary contacts and main poles.
a) Normally open __________________

b) Normally closed _________________

c) R Pole ________________________

d) Y Pole _________________________

NOTE : If the answer is O.K. to all above points then only take the relay for
overload testing.
3.

Select the proper size of cable for connection. In case of smaller size of cable or
improper termination, relay may trip early.

4.

Connect all three poles of relay in series as shown in the following diagram.
Use proper size of cables. Length of cable should be one metre.

5.

Connect normally closed (NC) contact of relay in series with test panel's auxiliary
contact. (This will give relay trip to test panel.)

OVERLOAD TEST
FROM CURRENT SOURCE

1m
1m
DUT

1m

'NC' CONTACT
OF RELAY

1m

Connections of Thermal Overload Relay for O/L Testing

L&T SWITCHGEAR
SAFE & SURE

30

E S P
SERVICE
MANUAL

6. Set the relay and calculate the test current as follows:
Relay Setting

X

Multiples of Set Current
(% of overload)

=

Test Current
Amps
20 Amps

Eg.: 10 Amps.

X

2(200%)

=

1.

X

2(200%)

=

2.

X

3(300%)

=

7. Find out the minimum and maximum trip time with respect to multiples of set
current you have selected and note down the values in the following table.
Sr. No.

Relay
Setting

Test Current (Amp)

Trip Time in Seconds
i-t characteristics.
Actual

As per Curve
Min.

Remark
OK /
Not OK

Max.

1.
2.

8. Switch on the supply and adjust the test current. Immediately switch off the current. Keep
variac at adjusted position. Reset the time counter. Cool the relay for about 10 minutes.
9. Switch on the test current and check trip time of the relay.
Caution
After each test, cool the relay for minimum 10 minutes. Otherwise, relay will trip
early and you will not get correct results.

Cable size with respect to test current.
Test Current Amp

0 to 15

15 to 30

30 to 46

For Copper Cables
sq. mm

1

1.5

4

46 to 66 66 to 110
6

10

100 to 150

150 to 220

25

35

L&T SWITCHGEAR
SAFE & SURE

31

E S P
SERVICE
MANUAL

SINGLE PHASING TEST
FROM CURRENT SOURCE

1m
DUT

1m

'NC' CONTACT
OF RELAY

1m
CONNECTIONS OF THERMAL OVERLOAD RELAY
FOR SINGLE PHASE TESTING

Sr. No. Relay Setting

Test Current (Amp)

Trip Time in
Sec. from
i-t characteristics.
Min.

Actual

Remark
OK /
Not OK

Max.

1.
2.

L&T SWITCHGEAR
SAFE & SURE

32

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR MK1 / ML1 RELAYS
FOR RANGES UPTO 6-10 AMPS.

4000

2000

1000
600

TRIPPING TIME IN SECONDS

400

200

100
60
50
40
30
20

10
6
4

2

0.8

1

1.2

1.5

2

3

4

5

6 7 8

MULTIPLES OF SET CURRENT

NOTE :
1. THE TRIPPING TIME FOR ANY CURRENT SHALL LIE BETWEEN THE VALUES
CORRESPONDING TO 90% AND 110% OF THAT CURRENT.
2. CURVE REPRESENTS COLD STATE CHARACTERISTICS.

L&T SWITCHGEAR
SAFE & SURE

33

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR MK1 / ML1 RELAYS
FOR RANGES UPTO 9-14 & 10-16 AMPS.
7200
6000
4000

2000

1000
600

TRIPPING TIME IN SECONDS

400

200

100
60
50
40
30
20

10
6
4

2

0.8

1

1.2

1.5

2

3

4

5

6

7 8

MULTIPLES OF SET CURRENT
NOTE :
1. THE TRIPPING TIME FOR ANY CURRENT SHALL LIE BETWEEN THE VALUES
CORRESPONDING TO 90% AND 110% OF THAT CURRENT.
2. CURVE REPRESENTS COLD STATE CHARACTERISTICS.

L&T SWITCHGEAR
SAFE & SURE

34

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR ML2 / ML3 RELAYS
7200
6000
4000

2000

1000
600

TRIPPING TIME IN SECONDS

400

200
MAXI. TRIP
TIME CURVE
100
60
50
40
30

MINI. TRIP
TIME CURVE

20

10
6
4

2

0.8

1

1.2

1.5

2

3

4

5

6

7 8

MULTIPLES OF SET CURRENT

NOTE : CURVE REPRESENTS COLD STATE CHARACTERISTICS.

L&T SWITCHGEAR
SAFE & SURE

35

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR MN RELAYS
ON 3 POLE LOADING (BALANCED) CONDITION
10000

4000

2000

TRIPPING TIME IN SECONDS

1000

400
MAX. TRIP
TIME CURVE

200

115 SEC.

100

48 SEC.

40

20
MINI. TRIP
TIME CURVE

10

2

0.8

1

1.5

2

3

4

5

6

7

8 9 10

MULTIPLES OF SET CURRENT

NOTE : CURVE REPRESENTS COLD STATE CHARACTERISTICS.

L&T SWITCHGEAR
SAFE & SURE

36

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR MN REL AYS
ON 2 POLE LOADING (SINGLE PHASING) CONDITION
10000

4000

2000

1000

TRIPPING TIME IN SECONDS

400

200
100
60 SEC.
40

20
11 SEC.

10
6
4

2

0.8

1

1.5

2

3

4

5

6

7

8 9 10

MULTIPLES OF SET CURRENT

NOTE : CURVE REPRESENTS COLD STATE CHARACTERISTICS.

L&T SWITCHGEAR
SAFE & SURE

37

E S P
SERVICE
MANUAL

TRIPPING CURVE FOR MN12 L RELAYS
ON 3 POLE BALANCED LOADING CONDITION
104

TRIPPING TIME IN SECONDS

10

3

MAX. SETTING

102

MIN. SETTING

101

0.6

1.2 1.5

2

3

4

6

8

10

MULTIPLES OF SET CURRENT

L&T SWITCHGEAR
SAFE & SURE

38

E S P
SERVICE
MANUAL

WIRING DETAILS

MN25, MN32 DOL

MN16 DOL

MN45, MN65 DOL

L&T SWITCHGEAR
SAFE & SURE

39

E S P
SERVICE
MANUAL

WIRING DETAILS

MN16 FASD

MN16 SASD

MN25, MN32 FASD

MN25, MN32 SASD

L&T SWITCHGEAR
SAFE & SURE

40

E S P
SERVICE
MANUAL

WIRING DETAILS

MN45, MN65 FASD

MN80, MN110, MN140 FASD

L&T SWITCHGEAR
SAFE & SURE

41

E S P
SERVICE
MANUAL

WIRING DETAILS

ML1 DOL

ML1.5 DOL

ML1.5 FASD

ML1.5 SASD

L&T SWITCHGEAR
SAFE & SURE

42

E S P
SERVICE
MANUAL

WIRING DETAILS

ML2 FASD

ML2 SASD

ML3 FASD

ML3 SASD

L&T SWITCHGEAR
SAFE & SURE

43

E S P
SERVICE
MANUAL

WIRING DETAILS

ML4, ML6 FASD

ML10, ML12 FASD

L&T SWITCHGEAR
SAFE & SURE

44

E S P
SERVICE
MANUAL

WIRING DETAILS

MF1 DOL (3 PHASE) STARTERS

MF1 DOL (3 PHASE) STARTERS
FOR SINGLE PHASE LOADS

MF1 DOL (SINGLE PHASE) STARTERS

L&T SWITCHGEAR
SAFE & SURE

45

E S P
SERVICE
MANUAL

WIRING DETAILS

MK1 DOL

MK1 FASD

MK1 SASD

L&T SWITCHGEAR
SAFE & SURE

46

E S P
SERVICE
MANUAL

S TA R D E LTA S TA R T E R S ( M L S E R I E S )

Details of Contactors and timers used in
ML series star delta starters
Starters

Timers

Contactors

STAR

DELTA

HOLD ON

ML 1.5

SASD

ML 1

ML 1.5

ML 1.5

—

ML 1.5

FASD

ML 1

ML 1.5

ML 1.5

GT-200

ML 2

SASD

ML 2

ML 2

ML 2

—

ML 2

FASD

ML 2

ML 2

ML 2

GT-200

ML 3

SASD

ML 2

ML 3

ML 3

—

ML 3

FASD

ML 2

ML 3

ML 3

ET-100

ML 4

FASD

ML 3

ML 4

ML 4

ET-100

ML 6

FASD

ML 4

ML 6

ML 6

ET-100

ML 10

FASD

ML 10

ML 10

ML 10

ET-100

ML 12

FASD

ML 12

ML 12

ML 12

ET-200

L&T SWITCHGEAR
SAFE & SURE

47

E S P
SERVICE
MANUAL

CHART FOR DOL MOTOR STARTERS
WITH ML RELAYS
Motor Rating
240V-1 Phase

Sr.
No
hp

kW

In

(A)

1

0.125

0.09

0.45

0.4-0.65

2

0.15

0.11

0.45

3

0.2

0.15

4

0.25

5

Contactor

Back up
fuse

SDF

Rating

Type

MLO

2

HF

FN32

0.4-0.65

MLO

2

HF

FN32

0.57

0.4-0.65

MLO

2

HF

FN32

0.19

0.7

0.6-1.0

MLO

4

HF

FN32

0.33

0.25

0.88

0.6-1.0

MLO

4

HF

FN32

0.5

0.37

1.2

1.0-1.6

MLO

6

HF

FN32

0.75

0.55

1.6

1.5-2.5

MLO

6

HF

FN32

1.0

0.75

1.8

1.5-2.5

MLO

6

HF

FN32

1.25

0.92

2.1

1.5-2.5

MLO

8

HF

FN32

1.5

1.1

2.6

2.5-4.0

MLO

10

HF

FN32

11

1.75

1.3

3.0

2.5-4.0

MLO

10

HF

FN32

12

2.0

1.5

3.5

2.5-4.0

MLO

10

HF

FN32

2.5

1.8

4.8

4-6.5

MLO

16

HF

FN32

14

3.0

2.2

5.0

4-6.5

MLO

16

HF

FN32

15

4.0

3.0

6.2

4-6.5

MLO

16

HF

FN32

0.125

In

Relay
Range

hp

6

kW

Motor Rating
215V-3 Phase

0.11

7

8

0.25

0.18

2.0

9

10

13

0.5

0.75

0.4

0.55

3.6

L&T SWITCHGEAR
SAFE & SURE

48

E S P
SERVICE
MANUAL

CHART FOR DOL MOTOR STARTERS
WITH ML RELAYS
Motor Rating
240V-1 Phase

Sr.
No
hp

Motor Rating
215V-3 Phase

kW

In

hp

kW

Relay
Range
In

(A)

Contactor

Back up
fuse
Rating

Type

SDF

16

1.0

0.75

7.5

5.0

3.7

7.5

6-10

MLO

20

HF

FN32

17

1.25

0.9

8.0

6.0

4.5

9.0

6-10

MLO

25

HF

FN32

18

2.0

1.5

9.5

7.5

5.5

11.0

10-16

MLO

25

HF

FN32

19

3.0

2.25

14.0

10.0

7.5

14.0

10-16

ML1

32

HF

FN32

20

12.5

9.3

18.0

13-21

ML1.5

50

HF

FN63

21

15.0

11.0

21.0

20-32

ML1.5

63

HF

FN63

22

17.5

13.0

24.0

20-32

ML2

63

HF

FN63

23

20.0

15.0

28.0

20-32

ML2

63

HN/00

FN100

24

25.0

18.6

35.0

28-42

ML3

80

HN/00

FN100

25

30.0

22.5

40.0

28-42

ML3

80

HN/00

Fn100

NOTES:
(1)

The full load currents given apply in the case of single phase motors, to capacitor-start type motors and in the
case of 3 phase motors, to squirrel cage type induction motors at full load having average power factor and
efficiency. The motors should have speeds not less than the following:
Upto 10 hp - 750 R.P.M., 10 to 30 HP - 600 R.P.M., 30 - 125 HP - 500 R.P.M., 125 - 300 HP - 375 R.P.M.

(2)

Contactors/Switches indicated are the minimum ratings suitable for the application. Higher sizes/Ratings can
be used.

(3)

Normal motor starting times are assumed in all cases.

L&T SWITCHGEAR
SAFE & SURE

49

E S P
SERVICE
MANUAL

C H A R T F O R S TA R - D E LTA M O T O R S TA R T E R S
WITH ML RELAYS
Motor Rating

Sr.
No

Current
at 415 V (A)

Relay
Range

Nominal Back
up fuse link

Contactor

SDF

hp

kW

LINE

PHASE

(A)

STAR

LINE

DELTA

Rating
A

Type/
Size

1

1

0.75

1.8

1.04

1-1.6

MLO

MLO

MLO

4

HF

FN32

2

1.5

1.1

2.6

1.5

1-1.6

MLO

MLO

MLO

6

HF

FN32

3

2

1.5

3.5

2.02

1.5-2.5

MLO

MLO

MLO

6

HF

FN32

4

3

2.25

5

2.88

2.5-4.0

MLO

MLO

MLO

8

HF

FN32

5

4

3

6.2

3.58

2.5-4

MLO

MLO

MLO

10

HF

FN32

6

5

3.75

7.5

4.32

4-6.5

MLO

MLO

MLO

16

HF

FN32

7

6

4.5

9

5.2

4-6.5

MLO

MLO

MLO

16

HF

FN32

8

7.5

5.5

11

6.34

6-10

MLO

MLO

MLO

20

HF

FN32

9

10

7.5

14

8.08

6-10

MLO

MLO

MLO

20

HF

FN32

10

12.5

9.3

18

10.04

10-16

MLO

MLO

MLO

32

HF

FN32

11

15

11

21

12.1

10-16

MLO

Ml1

Ml1

32

HF

FN32

12

20

15

28

16.2

13-21

ML1

ML1.5

ML1.5

40

HF

FN63

13

25

18.5

35

20.2

13-21

ML1

ML1.5

ML1.5

50

HF

FN63

14

30

22.5

40

23

20-32

ML2

ML2

ML2

63

HF

FN63

15

35

26

47

27

20-32

ML2

ML2

Ml2

63

HN/00

FN100

16

40

30

55

31.8

28-42

ML2

ML3

ML3

63

HN/00

FN100

17

45

33.5

60

34.6

28-42

ML2

ML3

ML3

80

HN/00

FN100

18

50

37.5

66

38.2

28-42

ML2

ML3

ML3

80

HN/00

FN100

NOTES:
(1)

Contactors/Switches indicated are the minimum ratings suitable for the application. Higher sizes/Ratings can
be used.

(2)

For applications above 35 hp suitable scheme to be employed to ensure change over delay of 40-75ms
between star and delta contactors.

(3)

Normal motor starting times are assumed in all cases.

L&T SWITCHGEAR
SAFE & SURE

50

E S P
SERVICE
MANUAL

CHART FOR MF1 THREE PHASE / SINGLE PHASE

Motor rating in hp

Relay
scale

Maximum safe rating of
back-up fuses*

415V
3 phase

Amps
(A)

Cartridge
fuses

Rewritable
fuses SWG

0.125

0.4-0.65

4A

35

0.25

0.6-1.0

6A

32

0.5

1.0-1.6

6A

32

0.75

1.5-2.5

16A

25

1.0

1.5-2.5

16A

25

1.25

1.5-2.5

16A

25

1.5

2.5-4.0

25A

23

1.75

2.5-4.0

25A

23

2.0

2.5-4.0

25A

23

2.5

4.0-6.5

25A

23

3.0

4.0-6.5

25A

23

4.0

4.0-6.5

25A

23

0.75

4.5-7

25A

23

1.00/1.25

6.5-11

32A

21

5.0

6.0-10

32A

21

6.0

6.0-10

32A

21

10.5-17.5A

32A

21

9.0-15

32A

21

11-18

32A

21

12-20A

32A

21

240V
Single phase

0.125

0.25

0.5

2.00

7.5

3.00

* Cartridge type fuses are recommended

L&T SWITCHGEAR
SAFE & SURE

51

E S P
SERVICE
MANUAL

CHART FOR Mk1 DOL STARTER

Motor rating H.P.
Cat No.

220
1-Phase

400V
3-phase

440V
4-phase

0.005

0.05

0.15-0.25

1A

0.1

0.1

0.25-0.4

2A

0.125

0.125

0.25-0.4

2A

0.15

0.15

0.4-0.65

4A

35

0.2

0.2

0.4-0.65

4A

35

0.25

0.4-0.65

4A

35

0.6-1.0

6A

0.5

1.0-1.6

0.75
0.25

0.75

SS96210

0.5

32

6A

32

6A

32

6A

32

1.0-1.6

6A

32

6A

32

1.0

1.5-2.5

15A

25

6A

32

1.0

1.25

1.5-2.5

15A

25

6A

32

1.25

1.5

2.5-4.0

25A

23

10A

28

1.5

1.75

2.5-4.0

25A

23

10A

28

1.75

2.0

2.5-4.0

25A

23

10A

28

2.5-4.0

25A

23

10A

28

0.5

Diazed

Minimum
SWG

2.0
0.75

Maximum

Diazed

0.25
0.125

Back-up Fuse Rating

Relay
Amps.
Range

SWG

2.5

2.5

4.0-6.5

25A

23

10A

28

3.0

3.0

4.0-6.5

25A

23

10A

28

4.0

4.0-6.5

25A

23

10A

28

6-10

35A

21

15A

25

1.0

4.0

1.25

5.0

5.0

6-10

35A

21

15A

25

1.5

6.0

6.0

6-10

35A

21

15A

25

9-14

35A

21

15A

25

1.75
2.0

7.5

7.5

11-18

35A

21

15A

25

SS96211

2.0

7.5

7.5

11-18

35A

21

15A

25

SS96228

2.0

7.5

7.5

13-22

40A

21

15A

25

Note :
Amp. Rating of back-up fuse refers to the recommended diazed type HRC catridge fuse. Where rewirable
semi-enclosed, tinned copper wire fuses are used, SWG number in table is approximate guide to size of wire
required.

L&T SWITCHGEAR
SAFE & SURE

52

E S P
SERVICE
MANUAL

C H A R T F O R M K 1 S TA R - D E LTA S TA R T E R

Cat No.

Motor
Full load
Rating
line
400/440v current
3-phase in Amps.
hp
ln

In
V3

Relay
Amps.
Range

Back-up Fuse Rating
Maximum

Minimum

Diazed

SWG

Diazed

SWG

1

1.7

1

1-1.6A

6

32

4

35

1.5

2.4

1.4

1-1.6A

15

25

6

32

2

3.1

1.8

1.5-2.5A

15

25

6

32

SS96254

3

4.4

2.5

2.5-4A

25

23

6

32

&

4

5.7

3.3

2.5-4A

25

23

10

28

SS96255

5

7.1

4.1

4-6.5A

25

23

10

28

6

8.4

4.9

4-6.5A

25

23

10

28

7.5

10.4

6

6-10A

35

21

15

25

10

13.6

7.9

6-10A

35

21

15

25

12.5

17

9.7

9-14A

35

21

20

24

15

19.9

11.5

9-14A

35

21

25

23

15

19.9

11.5

11-18A

35

21

25

23

SS96257
&
SS96258

Note: Amp. Rating of back-up fuse refers to the recommended diazed type HRC catridge fuse. Where
rewirable semi-enclosed, tinned copper wire fuses and used, SWG number in table is approximate guide to
size of wire required.
Cat. No SS 96254 & SS 96257 - FASD Starters
Cat. No SS 96255 & SS 96258 - SASD Starters

L&T SWITCHGEAR
SAFE & SURE

53

E S P
SERVICE
MANUAL

SELECTION CHART FOR MU/MBDOL STARTERS

Type

MB1
DOL

MB2
DOL

MU1
DOL
MU2
DOL

Maximum
Motor rating at
145V.3 ph 50 HZ
HP

KW

7.5

5.5

Approx.
Full load
Current in

11

Relay
Range
(A)

Relay

Contactor

9-15

10

7.5

14

14-23

12.5

9.3

18

14-23

15

11

21

14-23

15

11

21

20-33

7.5

5.5

11

9-14

10

7.5

14

13-21

12.5

9.3

18

13-21

15

11

21

13.21

15

11

21

20-32

MN2

MN2

MU2

MU2

MU1

MU2

MU1

MU2

Back-up
HRC Fuse

Switch
Disconector
Fuse Unit

Type

Rating
(A)

HF

32

FN 32

HF

50

FN 63

HF

50

FN 63

HF

63

FN 63

HF

63

FN 63

HF

32

FN 32

HF

50

FN 63

HF

50

FN 63

HF

63

FN 63

HF

63

FN 63

S E L E C T I O N C H A R T F O R M U / M B S TA R D E LTA S TA R T E R S
Type

MB1
SASD

MB2
SASD

MU1
SASD
MU2
SASD

Maximum
Motor rating at
145V.3 ph 50 HZ
HP

KW

15

11

Approx. Phase Relay
Full load Current Range
Current in
(A)

21

12.1

Relay Contactor

9-15

15

11

21

12.1

14-23

20

15

28

16.2

14-23

25

18.5

35

20.2

14-23

30

22.5

40

23

20-33

15

11

21

12.1

9-14

15

11

21

12.1

13-21

20

15

28

16.2

9-14

25

18.5

35

20.2

13-21

30

22.5

40

23

20-32

MN2

MN2

MU2

MU2

MU1

MU1

MU1

MU2

Back-up
HRC Fuse

Switch
Disconector
Fuse Unit

Type

Rating
(A)

HF

32

FN 32

HF

40

FN 63

HF

40

FN 63

HF

50

FN 63

HF

63

FN 63

HF

32

FN 32

HF

40

FN 63

HF

40

FN 63

HF

50

FN 63

HF

63

FN 63

L&T SWITCHGEAR
SAFE & SURE

54

E S P
SERVICE
MANUAL

SELECTION CHART FOR MUG-10 DOL
SUBMERSIBLE PUMP STARTERS
Type

Maximum
submersible
pump rating
at 415 V,
3ph., 50hz

HP

Relay
Range
(A)

KW

Relay

Contactor

Type

Type

Type

Rating
(A)

Back-up HRC Fuse

Switch
Disconnector
Fuse Unit

3

2.2

4-6.5

MU 1

MU 1

HF

16

FN 32

5

3.7

6-10

MU 1

MU 1

HF

16

FN 32

7.5

5.5

9-14

MU 2

MU 1

HF

32

FN 32

10

7.5

13-21

MU 2

MU 1

HF

40

FN 63

5

3.7

6-10

MN 2

MU 1

HF

16

FN 32

7.5

5.5

9-15

MN 2

MU 1

HF

32

FN 32

10

7.5

20-32

MU 2

MU 2

HF

63

FN 63

10

7.5

28-42

MU 2

MU 2

HN/00

63

FN 100

MUG-10 DOL

MUG-10N DOL

MUG-10H DOL*

* - Controllers for low voltage application

Note : MU 1/2 contactors are available in 415 V coil operating voltage also.
Note : MUG-10 DOL are available with dry run facility as a optional feature.

L&T SWITCHGEAR
SAFE & SURE

55

E S P
SERVICE
MANUAL

S E L E C T I O N C H A R T F O R M U G - 2 0 S TA R - D E LTA
SUBMERSIBLE PUMP STARTERS
Type

Maximum
submersible
pump rating
at 415 V,
3ph., 50hz

Relay
Range
(A)

Relay

Contactor

Type

Type

Type

Rating
(A)

Back-up HRC Fuse

Switch
Disconnector
Fuse Unit

HP

KW

MUG-20

15

11

9-14

MU 2

MU 1

HF

32

FN 32

Star-Delta

20

15

13-21

MU 2

MU 1

HF

40

FN 63

MUG-20H*

20

15

20-32

MU 2

MU 2

HF

63

FN 63

Star-Delta

20

15

28-42

MU 2

MU 2

HN/00

63

FN 100

* - Controllers for low voltage application

Note : MU 1/2 contactors are available in 415 V coil operating voltage also.
Note : MUG-10 DOL are available with dry run facility as a optional feature.

L&T SWITCHGEAR
SAFE & SURE

56

E S P
SERVICE
MANUAL
INFORMATION FOR INSTALLATION AND
PREVENTIVE MAINTENANCE
Cable connections to the terminals
When aluminium wires are used, the following method should be adopted:
If the wire is small up to 1 mm

2

– Single strand
1. Clean the wire surface by rubbing with a small hard wire brush.
2. Tin the wire immediately (within 2 or 3 minutes).
3. Put wire under terminal clamp and tighten screws. Do not tighten to such an
extent that the wire becomes flat.
Every two or three months, it may be necessary to ensure that the screws are tight
and the wire has not become loose. This may happen because aluminium is soft and
is likely to “flow”. Always apply inhibiting grease around the terminal and wire to
prevent moisture from reaching the area of contact. Apply inhibiting grease, only on
the terminals and wire and not on the contacts.
If the wire is large – larger than 10 mm2
– Multi-strand
Wires should be connected with the help of cable lugs or thimbles. The cable lugs
may be of "soldering" or "crimping" type.
For "soldering" type cable lugs:
• Check that cable lug socket is clean and dry inside.
• Clean every strand of aluminium wire with a small hard wire brush by opening out
the cable strands.
• Immediately dip all the strands in tin solder.
• Insert the stranded cable in the proper size cable lug and pour solder through the
cable lug. Ensure that solder fills the entire space inside the cable lug socket.
• Wipe off excess solder on cable insulation.
• Connect the cable lug to the terminal and tighten terminal screws using spring
washers on the cable lug.
• There should not be excess load on the cable lug, or else the solder will become
loose. Care must, therefore, be taken to cut the cable core and strip the insulation
to the correct length. The cable lug should sit flat on the terminal and the cable
should not have sharp bends.
Every two or three months it is necessary to check whether the connection is firm
and to tighten the screws, if necessary. Also check and ensure that the cable is
not loose in the cable lug.

L&T SWITCHGEAR
SAFE & SURE

57

E S P
SERVICE
MANUAL

For "crimping" type cable-lugs :
• Check that cable lug socket is clean and dry inside.
• Clean every strand of aluminium wire with a small hard wire brush after opening
strands.
• Close the strand again immediately, insert to the proper length inside the cable lug
socket and crimp, using the correct crimping tool.
• Connect the cable lugs to the terminal and tighten terminal screws using spring
washers on the cable lug.
Contact maintenance
Contact tips are made of silver compositions like silver nickel and silver cadmium
oxide. In normal use, these tips may show slight brown or black tarnish. If the
atmosphere around the starter contains high moisture and sulphur, the contact
tips will show excessive tarnishing. To clean the contact tips, use this maintenance
procedure:

1. Rub the contact tips lightly with fine emery paper.
DO NOT FILE THE CONTACT.
2. Remove small particles by rubbing with wet cotton wool or with a
wet, clean cloth.
3. Remove the water on the contact tip surface with a dry, clean cloth. If possible,
apply acetone or carbon terachloride. Do not use petrol.
The maintenance procedure is necessary only if contact tips are covered' with thick,
black tarnish film. If the contact tip is uneven, but not heavily tarnished, do not disturb
the contact.
Contact replacement
Contact replacement becomes necessary if less than one- third of the original
contact tip remains on the contact. This can be ascertained by comparing the contact
with a new one of the same starter. When replacing contacts, change contact springs
and leaf springs, if any.
Note :
Proper soldering of aluminium cables requires special grade of solders and fluxes
meant for that purpose. Normal solders and fluxes will produce a joint deceptively
acceptable but It will in practice lead to over-heating and eventually to burnouts.

L&T SWITCHGEAR
SAFE & SURE

58

E S P
SERVICE
MANUAL

S E C T I O N VIII
Trouble shooting chart for starters
Given below are some of the common complaints in starters. The probable cause
and suggested remedy are also given. But before attending to any complaint,
ensure that the wiring is as per the wiring diagram given in this booklet. Most of the
complaints can be traced to the wiring carried out at the site.

FOR DOL STARTERS :
Complaint

Reasons / Solutions

1. Motor does not start even
though 'Start' button is pressed.
However on lifting the moving
magnet manually, motor starts.

1) a) Coil does not get energised
(see control wiring diagram)
b) Check nylon strip on relay,
Check nylon button below
start button.

2. Relay/coil has been
charged. However motor
does not start when green
button is pressed.

2. Check if red wire on the relay
and black wire on the coil are
properly connected.

3. Motor starts when green
button is pressed. It
however stops immediately
when it is released.

3. a) Blue wire is not connected
properly or completely absent,
b) Hold-on contact moving strip is
missing or improperly placed.

4. Humming and/or chattering
noise.

4. a) Low supply voltage
b) Magnet faces unclean.
Moving system functioning is
obstructed by dirt.

5. Use of starters on 230V 10
supply. Incoming / outgoing
lines wired. However motor
does not start.

5. Coil obtains supply from across R
& B supply. However if in/out
wires are connected on R & Y
phases coil will not energise. You
may connect all three phases in
series.

6. Remote start/stop button not
working properly; motor starts
on remote start; however does
not stop on remote stop.

6. Red wire not wired as per wiring
diagram.

L&T SWITCHGEAR
SAFE & SURE

59

E S P
SERVICE
MANUAL

7. Thermostat/float
switch/pressure switch are
wired to the starter. Motor
cannot be stopped properly.
Motor stops on pressing stop
button. However it restarts on
releasing the same.

7) No mistake in wiring here
However it is necessary that the
stop button is of the stay-put type
or locked in.Off position
Alternatively, you could shut the
main switch.

8. Motor does not restart
immediately after tripping on
O/L even though resetting has
been resorted to.

8) It takes a little time for the
thermal bimetals to coil and
reset. Hence wait for 2-4 minutes
before restarting.

FOR STAR-DELTA STARTERS :
1. Motor works in Star. However it
does not work properly In Delta
and refuses to take load.

1. Check if only three wires are
being terminated in terminal box
of motor. Six wires should be
connected to starter. If shorting
links are present they should be
removed.

2. a) Motor starts with difficulty in
Star or trips when additional
load is present,
b) Motor works in Star.
However stops when Delta
connection comes on.

2. Reduce time delay from Star to
Delta in case it is kept very long.
a) Or if a semi-automatic starter
is being used, switch over
from Star to Delta earlier than
done previously.
b) Possibly due to low system
voltage.

3. a) Even though all six wires
have been connected, motor
stops when in Delta,
b) Motor stops when in Delta,
starter trips and fuse blows.

3. a) Delta connection from motor is
improper.
b) Low system voltage. Star/Delta
connection in starter wrongly
connected.

4. Relay has been changed in
semi-automatic starter, however
when the main switch is on, the
motor starts immediately
without the necessity of
pressing the start button. Motor
stops in Star itself.

4. This is a usual complaint. You
may have changed the original
relay yourself. All factory made
relays have loop-wires 2-3 wired,
in semi-automatic starters.
2-4 terminals on relays must be
connected. Check relay before
connecting it on starter.

L&T SWITCHGEAR
SAFE & SURE

60

E S P
SERVICE
MANUAL
INSTALLATION & COMMISSIONING OF THE MOTOR
CONTROLLER MU-G10 AND MU-G20
This controller is provided with several protection features and indicating instruments
for the convenience of operation and safety. The motor can be set to start
(automatically) within 30-60 secs. after supply is restored. For this, the rocker switch
on SPPR has to be set to "AUTO", otherwise set to "BY-PASS" mode. This feature is
by-passed as supplied from the factory.
The motor controller is armed with the following protection features:
1. Overload protection
2. Phase failure*
3. Phase unbalance *
4. Phase reversal *
5. Dry run protection (Not Standard)*
* - Protection features enabled only in AUTO mode and not in BY-PASS mode.
Visual indication is provided :
1. Supply Voltage (Line)
2. Current drawn by motor (Phase)
3. Lamp-indicating supply ON
4. Lamp - indicating motor ON
For normal operation (manual mode) motor can be switched ON-OFF with GREEN &
RED push buttons. Toggle switch should be in ON position.
However, please note that the standard RED push button will not function in "AUTO"
mode & toggle switch has to be used for switching OFF.

By taking these few precautions and care the starter will be able to perform
satisfactorily year after year.
installation & Commissioning of the motor controller MU-G10 and MlU-G20
A) Installation instruction:
• Ensure that the enclosure is mounted in the vertical position.
• Set the rocker switch on the SPPR to "BY-PASS" mode, the switch can be set to
"Auto" mode only after ensuring the proper operation of the motor for a few
minutes.
• Use right size of the cables with cable lugs. Use cable glands for fixing cables to
the enclosure to avoid excess stress on terminals.
• Connect the supply (Line) cables on the terminal block provided, Marked "Supply
terminals" in star-delta controller and in DOL controller on the MU contactor.
• Connect the motor terminals on the terminal block provided, marked "Motor
terminals".

L&T SWITCHGEAR
SAFE & SURE

61

E S P
SERVICE
MANUAL

• Ensure that the termination joints are properly tightened.
• Set the relay pointer corresponding to the actual current drawn by the motor, as
indicated by the ammeter. In star-delta controller, the relay setting (phase current)
should be reduced to 1 /1.732 times of the ammeter reading (line current)
B) Commissioning
• Keep the toggle switch in OFF position & SPPR in "By-Pass" mode:
• Switch ON the power supply. The RED lamp will be switched ON indicating the
presence of the power supply, the actual voltage can be read in the voltmeter
(select the phase using the selectorswitch provided.)
• Now put the Toggle switch in ON position.
• Press the START button. The Green LED lamp should glow and the motor should
start.
• Ammeter will show the line current drawn by the motor.
• For starting the motor automatically after the supply is restored set the switch on
the SPPR in "AUTO" mode. The motor will start after a delay of 30-60 secs. In this
mode the motor can be switched OFF by the toggle switch - Not by the red button.

Star Delta Motor Controller Troubleshooting

PROBLEM

CAUSE

SOLUTION

1.

Motor runs in reverse
direction

Phase sequence not
correct

Interchange the supply
sequence

2.

Motor runs in correct
direction but stops
immediately

Motor overloaded
Relay tripping

Check the current &
increase the relay
setting appropriately

3.

Motor not starting

SPPR trips sensing
wrong sequence
(lamp dosn't glow)
Low supply voltage

Interchange Y&B on
the SPPR

Single phasing SPPR
trips Phase is
unbalanced SPPR trips

Wait till proper supply
is restored Wait till
proper supply is
restored Wait till proper
supply is restored

L&T SWITCHGEAR
SAFE & SURE

62



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2006:05:18 08:42:54+05:30
Modify Date                     : 2006:05:18 08:42:54+05:30
Page Count                      : 34
Creation Date                   : 2006:05:18 03:12:54Z
Mod Date                        : 2006:05:18 03:12:54Z
Producer                        : Acrobat Distiller 5.0 (Windows)
Author                          : smita
Metadata Date                   : 2006:05:18 03:12:54Z
Creator                         : smita
Title                           : Installation_Testing_Troublesho.PDF
EXIF Metadata provided by EXIF.tools

Navigation menu