PU 411_012_00 XxA Instruction Manual

User Manual:

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadPU-411_012_00-xxA Instruction Manual
Open PDF In BrowserView PDF
EN

PIC-01
Power Supply
Instruction Manual

PIC120.241C
PIC120.242C
PIC240.241C
PIC480.241C

AC 200-240V / DC 24-28V 5A
AC 200-240V / DC 24-28V 5A
AC 200-240V / DC 24-28V 10A
AC 200-240V / DC 24-28V 20A

Before operating the power supply, read this manual thoroughly and retain it for future reference! This device may only be
installed and put into operation by qualified personnel. If damage or malfunction should occur during operation,
immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The
tripping of an internal fuse is caused by an internal defect.
This power supply is designed for installation in an enclosure and is intended for general use such as in industrial control,
office, communication, and instrumentation equipment. Do not use this device in equipment, where malfunction may
cause severe personal injury or threaten human life.

Risk of electrical shock, fire, personal injury or death:
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)

Do not use the power supply without proper grounding (Protective Earth).
Turn power off before working on the device. Protect against inadvertent re-powering.
Make sure that the wiring is correct by following all local and national codes.
Do not modify or repair the unit. The unit does not contain serviceable parts.
Do not open the unit as high voltages are present inside.
Use caution to prevent any foreign objects from entering the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.

Installation Notes
- Install the device on a DIN-rail according to EN 60715 with the input terminals on the bottom of the unit.
- Do not obstruct air flow as the unit is convection cooled.
Ventilation grid must be kept free of any obstructions (min. 40mm on top, 20mm on the bottom, 5mm left and right side).
- Do not place heat sources adjacent to the power supply.
- Do not use the device in pollution degree 3 environments.
- Do not use the device in parallel connection.
- The unit is tested and approved for branch circuits up to 30A (UL), 32A (IEC) without additional protection device.
If an external fuse is utilized, do not use breakers smaller than 16A B- or 10A C-Characteristic (for PIC240) and not
smaller than 10A B- or 6A C-Characteristic (for PIC120, PIC480) to avoid nuisance tripping.
- Maximum surrounding air temperature: 70°C / 158°F.
- For use in CSA C22.2 No 107 areas: Provide an output disconnecting means and use only in controlled environments.

CE Declaration
The CE mark is in conformance with the EMC directive and the low-voltage directive (LVD).
Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany
Germany
China
France
Austria

+49 89 9278 0
+86 512 62881820
+33 478 668 941
+43 27 64 32 13

www.pulspower.de
www.pulspower.cn
www.pulspower.fr
www.pulspower.at

Singapore
Switzerland
U.K.
U.S.A

www.pulspower.com
+65 6684 2310
+41 56 450 18 10
+44 1525 841001
+1 630 587 9780

www.pulspower.sg
www.pulspower.ch
www.pulspower.co.uk
www.pulspower.us

Technical Data 1)

PIC120.241C
PIC120.242C

Output Voltage
Output Current

nom.
nom.

Output Power
Output Ripple & Noise Voltage 2)
Input Voltage
Input Frequency
Input Current
Power Factor
Input Inrush Current 3)
Efficiency / Power Losses
Operational Temperature Range 4)
Output Derating
Storage Temperature Range
Terminals 5) Stranded / solid wire
AWG
Wire stripping length
Tightening torque
DC-OK Contact

nom.
max.
nom.
nom.
typ.
typ.
typ.
typ.
nom.
nom.
nom.
nom.
nom.
nom.
nom.

EMC Immunity Generic Standard
EMC Emission Generic Standard
Radiated Emission
Conducted Emission
Harmonic Input Current
Dimensions (WxHxD, without DIN-rail) nom.
Weight
max.

PIC240.241C

PIC480.241C

DC 24-28V
DC 24-28V
DC 24-28V
5A at 24V,
10A at 24V,
20A at 24V,
4.3A at 28V
8.6A at 28V
17.1A at 28V
120W
240W
480W
100mVpp
100mVpp
100mVpp
±10%
±10%
AC 200-240V
AC 200-240V ±10%
AC 200-240V
50-60Hz ±6%
50-60Hz ±6%
50-60Hz ±6%
1.1A
2.2A
2.2A
0.54
0.52
0.99
28A peak
48A peak
26A peak
90.5% / 12.6W
91.4% / 22.6W
95.7% / 21.6W
-10°C - +70°C
-10°C - +70°C
-10°C - +70°C
3W/°C (+55°C - +70°C) 6W/°C (+55°C - +70°C)
8W/°C (+55 - +70°C)
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
max. 4mm2/ 6mm2
max. 4mm2/ 6mm2
max. 4mm2/ 6mm2
20-10AWG
20-10AWG
20-10AWG
7mm, 0.28inch
7mm, 0.28inch
7mm, 0.28inch
1Nm, 9lb.in
1Nm, 9lb.in
1Nm, 9lb.in
PIC120.241C: Yes 6)
Yes 6)
Yes 6)
PIC120.242C: No
IEC 61000-6-1/ -6-2
IEC 61000-6-1/ -6-2
IEC 61000-6-1/ -6-2
IEC 61000-6-3 /-6-4
IEC 61000-6-4
IEC 61000-6-3 /-6-4
EN 55011/22 Class B EN 55011/22 Class B EN 55011/22 Class B
EN 55011/22 Class B EN 55011/22 Class B EN 55011/22 Class B
IEC 61000-3-2 Class A
- IEC 61000-3-2 Class A
39x124x124mm
49x124x124mm
49x124x124mm
350g, 0.77lb
550g, 1.2lb
620g, 1.37lb

1)
2)
3)
4)
5)

All parameters are specified at 230Vac, nominal output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
50-Ohm measurement, bandwidth 20MHz
At 230Vac, 40°C ambient and cold start. The input inrush current is limited by a NTC and is temperature dependent.
The operational temperature range equals the surrounding air temperature measured 2cm below the unit.
Use appropriate copper cables, that are designed for a minimum operating temperature of 75°C for ambient temperatures up to 55°C and
90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal.
6) Contact ratings: 60Vdc 0.3A; 30Vdc 1A; 30Vac, 0.5A; resistive load, min. current 1mA.
PU-411.012.00-xxA

The information presented in this document is believed to be accurate and may change without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Format                          : application/pdf
Creator                         : zy
Title                           : Microsoft Word - PU-411_012_00-xxA.doc
Create Date                     : 2016:12:12 11:06:52+01:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2016:12:12 11:06:52+01:00
Producer                        : Acrobat Distiller 9.0.0 (Windows)
Document ID                     : uuid:d1265984-b4a4-449f-99fb-ea1bfa928fa6
Instance ID                     : uuid:808b4dfb-a0ce-490a-95b9-93169108b4f2
Page Count                      : 2
Author                          : zy
EXIF Metadata provided by EXIF.tools

Navigation menu