21 Series Lennox CB29M CB30M IOM

User Manual: 21 Series

Open the PDF directly: View PDF PDF.
Page Count: 20

Download21 Series Lennox CB29M CB30M IOM
Open PDF In BrowserView PDF
INSTALLATION
INSTRUCTIONS

E2005 Lennox Industries Inc.
Dallas, Texas, USA

CB29M & CB30M
Elite® Series Units
MULTI−POSITION BLOWER COILS
504,719M
09/05
Supersedes 04/05

Litho U.S.A.

RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE

Table of Contents

IMPORTANT
For downflow application, kit number 83M57
(LB−109844A) is required. Kit is not provided with
coil blower; order separately.

IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of
California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
09/05

*2P0905*

CB29M & CB30M Series Units . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List . . . . . . . . . . . . . . . . . . . . . . . .
CB29M Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . .
CB30M Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . .
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Piping Connections . . . . . . . . . . . . . . . . . . . . . . .
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sealing the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Speed Adjustments . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . .

1
1
1
2
4
5
5
8
9
9
9
10
16
17

CB29M & CB30M Series Units
The Lennox CB29M and CB30M Elite® series blower coil
units are designed for installation with a matched remote
outdoor unit and optional field−installed electric heat. The
blower coil units are for indoor installation only.
The CB29M and CB30M units, designed for multi−positional installations, are completely assembled at the factory
and shipped ready for upflow or horizontal right−hand discharge installation.

General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installing the unit
Check equipment for shipping damage; if found, immediately contact the last carrier.

Shipping and Packing List
Each CB29M and CB30M unit package contains:
1 − Assembled blower coil unit
Page 1

504,719M

*P504719M*

CB29M Upflow and Downflow Unit Dimensions − inches (mm)
3/4
(19)

PIPING PLATE DETAIL
(For upflow and downflow positions)

SUPPLY
AIR OPENING

D

1-1/8 (29)

3/4
(19)

4-3/8 (111)

2
(51)

LINE VOLTAGE
INLETS (TOP &
LEFT SIDE)

LOW VOLTAGE
INLETS (TOP &
RIGHT SIDE)

Top View

5/8
(16)

CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)

2-3/4
(70)

E

3-1/2 (89)

RETURN
AIR
OPENING

1 (25)

1-3/4 (44)

5/8
(16)

B

5/8
(16)

F

LIQUID LINE

11-1/16
(281)
5-3/8
(137)

5/8 (16)

SUCTION LINE
CONDENSATE
DRAINS (2)
(HORIZONTAL)

Top View
C

C

FILTER
ACCESS

B

FILTER
SUCTION
LINE
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)

AIR
FLOW

LIQUID
LINE
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)

A
SUCTION
LINE

RETURN AIR

FILTER
ACCESS

COIL

Front View

LIQUID
LINE
FILTER

BLOWER

RETURN AIR

SUPPLY
AIR

E
5/8
(16)

A
AIR FLOW

LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)

F
5/8
(16)

COIL

BLOWER

1
(25)

Side View

SUPPLY AIR

11-1/16 (281)
5/8
(16)

Side View

Upflow Position

5/8
(16)

D
5/8
(16)

Front View

5/8 (16)

Downflow Position
(Kit number 83M57 (LB−909844A) required to convert
unit to downflow applications.)

Model No.
Dimension
A
B
C
D
E
F

CB29M-21/26 & CB29M-31
inch
mm
45-1/4
1149
16-1/4
413
20-5/8
524
14-3/4
375
19
483
15
351

CB29M-41 & CB29M-46
inch
mm
49-1/4
1251
21-1/4
540
20-5/8
524
19-3/4
502
19
483
20
508

Page 2
504719M 09/05

CB29M-51 & CB29M-65
inch
mm
52-1/2
1334
21-1/4
540
22-5/8
575
19-3/4
502
21
533
20
508

CB29M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm)
FILTER

2
(51)

5-3/8
(137)

LIQUID
LINE
SUCTION
LINE

CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)

COIL

BLOWER

C

For dimensions A"
through F", see
chart on Page 2.

1-1/8
(29)

CONDENSATE
DRAINS (2)
(HORIZONTAL)

4-3/8
(111)

PIPING
PLATE
DETAIL

5-3/4
(46)

1-3/4
(44)

LIQUID
LINE

SUCTION
LINE

Top View

1-1/2
(38)

5/8
(16)

5/8
(16)

11-1/16 3/4
(281) (19)

A

E

5/8
(16)

OPTIONAL ELECTRIC
HEAT (FIELD−INSTALLED)

F

RETURN
AIR
OPENING

1
(25)

LINE VOLTAGE
INLETS (TOP &
RIGHT SIDE)

AIR
FLOW

3/4
(19)
SUPPLY
AIR
OPENING

B
LOW VOLTAGE
INLETS (BOTTOM
& RIGHT SIDE)

5/8
(16)

End View

Front View

FILTER ACCESS

D

3/4
(19)

End View

Horizontal Position (Right-Hand Air Discharge)
4-3/8
(111)
BLOWER

C

COIL

PIPING
PLATE
DETAIL
FILTER

OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
3/4
LOW VOLTAGE
(19) 11-1/16 INLETS (TOP &
LEFT SIDE)
(281)

Top View

SUPPLY
AIR
OPENING

LINE VOLTAGE INLETS
(BOTTOM & LEFT SIDE)

End View

LIQUID
LINE

2
(51)

FILTER
ACCESS

AIR
FLOW

CONDENSATE DRAINS (2)
(HORIZONTAL)

Front View

5-3/8
(137)
5/8
(16)

A

B

3/4
(19)

SUCTION
LINE

LIQUID
LINE

5/8
(16)

3/4
(19)

D

SUCTION
LINE

1-1/8
(29)

1-1/2
(38)

1-3/4
(44)

5-3/4
(146)

E
1
(25)

5/8
(16)

F
RETURN
AIR OPENING
5/8
(16)

End View

Horizontal Position (Left-Hand Air Discharge)

Page 3
CB29M/CB30M SERIES

CB30M Upflow and Downflow Unit Dimensions − inches (mm)
3/4
(19)

PIPING PLATE DETAIL
(For upflow and downflow positions)

SUPPLY
AIR OPENING

D

1-1/8 (29)

3/4
(19)

4-3/8 (111)

2
(51)

LINE VOLTAGE
INLETS (TOP &
LEFT SIDE)

LOW VOLTAGE
INLETS (TOP &
RIGHT SIDE)

Top View

5/8
(16)

F

CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)

2-3/4
(70)

E

3-1/2 (89)

RETURN
AIR
OPENING

1 (25)

1-3/4 (44)

5/8
(16)

B

5/8
(16)

LIQUID LINE

11-1/16
(281)
5-3/8
(137)

5/8 (16)

SUCTION LINE
CONDENSATE
DRAINS (2)
(HORIZONTAL)

Top View
C

C

FILTER
ACCESS

B

FILTER

G
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)

AIR
FLOW

H

FILTER
ACCESS

SUCTION
LINE

LIQUID
LINE
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)

COIL

LIQUID
LINE
FILTER

Front View

BLOWER

G

RETURN AIR

SUPPLY
AIR

E
5/8
(16)

A
AIR FLOW

LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)

F
5/8
(16)

COIL

BLOWER

A

RETURN AIR

H

SUCTION
LINE

1
(25)

Side View

SUPPLY AIR

11-1/16 (281)
5/8
(16)

Side View

Upflow Position

5/8
(16)

D
5/8
(16)

5/8 (16)

Front View

Downflow Position
(Kit number 83M57 (LB−909844A) required to convert
unit to downflow applications.)

Model No.
Dimension
A
B
C
D
E
F
G
H

CB30M-21/26
inch
mm
45-1/4
1149
16-1/4
413
20-5/8
524
14-3/4
375
19
483
15
351
24-5/8
625
20-5/8
524

CB30M-31
inch
mm
49-1/4
1251
21-1/4
540
20-5/8
524
19-3/4
502
19
483
20
508
24-5/8
625
24-5/8
625

CB30M-41
inch
mm
51
1295
21-1/4
540
22-5/8
575
19-3/4
502
21
533
20
508
26-3/8
670
24-5/8
625

Page 4
504719M 09/05

CB30M-46
inch
mm
52-1/2
1334
21-1/4
540
22-5/8
575
19-3/4
502
21
533
20
508
27-7/8
708
24-5/8
625

CB30M-51 & CB30M-65
inch
mm
58-1/2
1486
21-1/4
540
24-5/8
625
19-3/4
502
23
584
20
508
27-7/8
708
30-5/8
778

CB30M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm)
FILTER

2
(51)

5-3/8
(137)

LIQUID
LINE
SUCTION
LINE

CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)

COIL

BLOWER

C

For dimensions A"
through H", see
chart on Page 4.

1-1/8
(29)

CONDENSATE
DRAINS (2)
(HORIZONTAL)

4-3/8
(111)

PIPING
PLATE
DETAIL

5-3/4
(46)

1-3/4
(44)

LIQUID
LINE

OPTIONAL ELECTRIC
HEAT (FIELD−INSTALLED)

Top View

1-1/2
(38)

H

E
F

RETURN
AIR
OPENING

5/8
(16)

A

5/8
(16)

5/8
(16)

SUCTION
LINE

G

1
(25)

11-1/16 3/4
(281) (19)
LINE VOLTAGE
INLETS (TOP &
RIGHT SIDE)

AIR
FLOW

3/4
(19)
SUPPLY
AIR
OPENING

B
LOW VOLTAGE
INLETS (BOTTOM
& RIGHT SIDE)

5/8
(16)

End View

Front View

FILTER ACCESS

D

3/4
(19)

End View

Horizontal Position (Right-Hand Air Discharge)
4-3/8
(111)

C

BLOWER

COIL

PIPING
PLATE
DETAIL
FILTER

OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
3/4
LOW VOLTAGE
(19) 11-1/16 INLETS (TOP &
LEFT SIDE)
(281)

Top View

SUCTION LIQUID
LINE LINE

SUCTION
LINE
LIQUID
LINE

A

5/8 (16)

G

1-1/8
(29)

2
(51)
5/8
(16)

H

3/4
(19)

D

SUPPLY
AIR
OPENING

B

3/4
(19)
LINE VOLTAGE INLETS
(BOTTOM & LEFT SIDE)

FILTER
ACCESS

AIR
FLOW

1-1/2
(38)

1-3/4
(44)

CONDENSATE DRAINS (2)
(HORIZONTAL)

Front View

End View

5-3/8
(137)

E
1
(25)

5/8
(16)

F
RETURN
AIR OPENING
5/8
(16)

5-3/4
(146)

End View

Horizontal Position (Left-Hand Air Discharge)

Requirements

Installation

Installation of Lennox blower coil units with or without optional electric heat must conform with standards in the National Fire Protection Association (NFPA) Standard for
Installation of Air Conditioning and Ventilation Systems
NFPA No. 90A," and Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA No. 90B," manufacturer’s installation instructions and local municipal building codes.
This unit is certified for installation clearances to combustible material as listed on the unit rating plate. Accessibility
and service clearances must take precedence over combustible material clearances.

WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Installation and service must be performed by a qualified installer or
service agency.
The CB29M and CB30M units are factory−configured for
upflow or horizontal right−hand discharge installation. For
downflow or horizontal left−hand discharge, some field
modification is required.

Page 5
CB29M/CB30M SERIES

2. No further adjustment is necessary. Set unit so that it is
sloped 1/4 inch toward the drain pan end of the unit.

IMPORTANT
Kit number 83M57 (LB−109844A) must be installed
for downflow application.

NOTE − For horizontal applications, an auxiliary drain
pan is recommended. Refer to local codes.

Disassembling CB30M Blower Coil Unit
These units are shipped from the factory fully assembled.
The CB30M blower coil unit’s sections may be separated
to facilitate movement at some installation sites. If required, disassemble the unit as follows:
1. Remove access panels from both blower and coil assemblies. This will lighten the cabinet for lifting.
2. Remove one screw from the left and right posts inside
the unit. Remove one screw from each side on the
back of the unit. Unit sections will now separate.
3. To reassemble, align cabinet sections and reinstall
screws. Replace access panels.

NOTE − For horizontal applications in high humidity
areas, seal around the exiting drain pipe, liquid line,
and suction line to prevent infiltration of humid air.

Right−Hand Discharge Configuration
Upflow/
Downflow
Drain Pan

Horizontal Drip Shield

Horizontal
Drain Pan
No Adjustment
is Necessary

Figure 2

Upflow Application
1. Remove access panels. Remove corrugated padding
from the space between the blower and coil assemblies.
2. To ensure proper operation, remove the horizontal
drain pan from units in upflow configurations (see figure 1).
3. Place unit in desired location. Make sure that unit is
level. Connect return and supply air plenums as required using sheet metal screws.
4. Install units that have no return air plenum on a mounting stand at least 14" from the floor for proper air return. Lennox offers an optional upflow unit stand.
(45K31 for CB29M−21, −26, and −31; 45K32 for
CB29M−41 through −65.)

3. If the unit is to be suspended, it must be supported
along the entire length of the cabinet (see figure 3). If
using a chain or strap, attach a piece of angle iron or
sheet metal to the unit (either above or below the unit),
so that the full length of the cabinet is supported. Use
securing screws which are no longer than 1/2 inch to
avoid damaging the coil or filter. Use sheet metal
screws to connect the return and supply air plenums.

Suspending Horizontal Unit
Angle Iron or
Sheet Metal

Electrical Inlet Clearance
4 in. (102 mm)
1/2 IN.
SCREWS
MAX.

Upflow Configuration

FRONT VIEW

END VIEW

Figure 3
Upflow/
Downflow
Drain Pan

Horizontal Drain Pan
(Remove for Optimum Performance)

CAUTION

Figure 1
Horizontal Right−Hand Discharge Application
1. Remove access panels. Remove corrugated padding
from the space between the blower and coil assembly.

Page 6
504719M 09/05

When removing the coil, there is possible danger of
equipment damage and personal injury. Be careful
when removing the coil assembly from a unit
installed in right− or left−hand applications. The coil
may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.

4. (See Detail B and C in figure 4.) Remove screws from
top cap. Remove horizontal drip shield screw located
in the center of the back coil end seal.
5. Rotate horizontal drip shield 180° front to back.
6. Remove plastic plug from left hole on coil front end
seal and re−install plug in back hole. Re−install horizontal drip shield screw in front coil end seal. Drip shield
should drain downward into horizontal drain pan inside
coil.
7. Rotate top cap 180° front to back and align with unused screw holes. Holes must align with front and back
coil end plates. Note that top cap has a 45° bend on
one side and 90° bend on the other. The 90° bend
must be on the same side as the horizontal drain
pan. See figure 4.

Horizontal Left−Hand Discharge Application
NOTE − For horizontal applications, an auxiliary drain pan
is recommended. Refer to local codes.
Remove the access panels and the corrugated padding
from the space between the blower and coil assembly before operation. Make the following modifications:
1. (See Detail A in figure 4.) Pull coil assembly from unit.
Pull off the horizontal drain pan.
2. Remove drain plugs from back drain holes on horizontal drain pan and re−install them on front holes.
3. Rotate drain pan 180° front to back and install it on the
opposite side of coil.

Left-Hand Discharge Modifications
Coil shown in upflow position for easy conversion

NOTE − Use extreme care when re−installing screws
into coil end plate engaging holes. Misaligned screws
may damage coil.
8. (See figure 5.) From the upflow position, flip cabinet
90° to the left and set into place. Replace coil assembly. Secure coil in place by bending down tab on cabinet support rail.

Detail A
(DRAIN
PAN)
PLUGGED
END

COIL
ASSEMBLY

OPEN END FOR
CONDENSATION
DRAIN

ORIGINAL
PLUG
LOCATION

Left−Hand Discharge Configuration
Securing Tab on
Cabinet Support Rail

Horizontal
Drip Shield

NEW PLUG
LOCATION
TOP CAP ROTATED TO
CORRECT POSITION

TOP CAP
SCREWS

Detail B
(TOP CAP)

Horizontal
Drain Pan

CABINET
SUPPORT

Figure 5

90_
BEND

9.

Detail C
ALIGN HOLES
WITH HOLES
IN COIL END
PLATE.

TOP
CAP

90_
BEND

10.
11.

12.

BACK COIL
END SEAL

DRAIN PAN

Figure 4

NOTE − For horizontal applications in high humidity
areas, seal around the exiting drain pipe, liquid line
and suction line to prevent infiltration of humid air.
Knock out drain seal plate from access door. Secure
plate to cabinet front flange with screw provided.
Flip access door and replace it on the unit.
Set unit so that it is sloped 1/4 inch toward the drain
pan end of the unit. Connect return and supply air plenums as required using sheet metal screws.
If the unit is to be suspended, it must be supported
along the entire length of the cabinet (see figure 3). If
using a chain or strap, attach a piece of angle iron or
sheet metal to the unit (either above or below the unit),
so that the full length of the cabinet is supported. Use
securing screws which are no longer than 1/2 inch to
avoid damaging the coil or filter. Use sheet metal
screws to connect the return and supply air plenums.

Page 7
CB29M/CB30M SERIES

Downflow Application
NOTE − If downflow application is required, separately order kit number 83M57 and install per kit’s instructions.
Also, use metal or class I supply and return air plenums.

If the homeowner reports water dripping from supply air diffusers, check the shields and tape. Make sure the tape is
completely attached to the edges of the drip shield, and
that the drip shield is wedged firmly in place.

Field Piping Connections

WARNING

All CB29M/CB30M coils are equipped with a factory−
installed, internally mounted expansion valve. Use Lennox
L15 (sweat) series line sets as shown in Table 1 or use
field−fabricated refrigerant lines. L10 (flare) line sets may
be used by cutting off flare nut. Refer to the piping section
of the Lennox Unit Information Service Manual for proper
size, type and application of field−fabricated lines.

If electric heat section with circuit breakers (ECB29)
are applied to downflow CB29M or CB30M unit, circuit breakers must be rotated 180_ to the UP position. See ECB29 installation instructions for more
details.

Combustible Flooring Additive Base

Table 1
Refrigerant Line Sets

BLOWER
COIL UNIT

CB29M
CB29M
Unit

Combustible
Floor Additive
Base
Properly−Sized
Floor Opening

Figure 6
On combustible flooring, use an additive base (figure 6).
Cut an appropriately sized opening for combustible base
(see dimensions in figure 7). Set the additive base into
opening. Connect supply air plenum to the additive base.
Set the unit on the additive base so flanges of the unit drop
into the base opening and seal against the insulation strips.
The unit is now locked in place. Install return air plenum
and secure with sheet metal screws.

inches
(mm)

20 (508)
CB29M−41 to −65
CB30M−31 to 65

18−1/4 (464)
CB29M−21/26 & 31
CB30M−21/26
23−1/4 (591)
CB29M−41 to −65
CB30M−31 to 65

3/8 in
(8 mm)

5/8 in
(16 mm)

L10−26
20 ft. − 50 ft.
(6 m − 15 m)

L15−26
20 ft. − 50 ft.
(6 m − 15 m)

−31 −41

3/8 in
(10 mm)

3/4 in.
(19 mm

L10−41
20 ft. − 50 ft.
(6 m − 15 m)

L15−41
20 ft. − 50 ft.
(6 m − 15 m)

−46 −51

3/8 in
(10 mm)

7/8 in.
(22 mm)

L10−65
30 ft. − 50 ft.
(9 m − 15 m)

L15−65
30 ft. − 50 ft.
(9 m − 15 m)

−65

3/8 in
(10 mm)

1−1/8 in.
(29 mm)

FIELD
FABRICATED

FIELD
FABRICATED

4. With heat shield in place, sweat in suction line elbow,
provided, and line set. After procedure is completed,
remove heat shield.

TOP VIEW
22-1/8 (562)
13-3/8 (340)

5. Place heat shield against piping plate and around the
liquid line connection. Sweat in the liquid line elbow
(provided) and the line set.

OPENING
2 (51)

SIDE VIEW

6. Refer to instructions provided with outdoor unit for leak
testing, evacuating and charging procedures.

Figure 7

Page 8
504719M 09/05

−21/26

3. Place heat shield (damp rag) against piping plate and
around the suction line connection. Heat shield must
be in place to guard against damage to the paint.

1-5/8 (41)

5/8 (16)

L15
Line Sets

2. Be aware of filter access panel when connecting lines.
Filter must be accessible.

1-5/8 (41)

SUPPLY
AIR
OPENING

L10
Line Sets

1. Use a wet rag to protect TXV bulb (or remove it) when
brazing suction line.

11-3/8
(289)

15 (381)
CB29M−21/26 & 31
CB30M−21/26

Vapor/
Suction Line

NOTE − CB29M/CB30M series evaporators use nitrogen or dry air as a holding charge. If there is no pressure
when the rubber plugs are removed, check the coil or line
set for leaks before installing. After installation, pull a
vacuum on the line set and coil before releasing the unit
charge into the system.

Downflow Combustible Base Dimensions
1-5/8 (41)

Liquid
Line No.

Condensate Drain

Filters

Connect main condensate drain and route downward to an
open drain or sump. Do not connect drain to a closed waste
system. Refer to figure 8 for typical condensate trap configuration.

IMPORTANT
Filter access panel must be in place during unit operation. Excessive warm air entering the unit may result in water blow−off problems.

Typical Condensate Drain Connection
Minimum 1 inch (25 mm) pitch
per 10 feet (3048mm) of line

Trap must be deep enough to
offset maximum static difference
(generally, 2" [51mm] minimum).

Pipe diameter difference

Each unit includes a factory−installed filter. Note that filter
access door fits over access panel. Air leakage will occur if
access panel is placed over filter door.

Coil
drain
pan

Figure 8
It is recommended that the auxiliary drain be connected to
a drain line for all units. If auxiliary drain is not connected, it
must be plugged with provided cap. For downflow units,
the auxiliary drain MUST be connected and routed to a
drain. See figure 9 for auxiliary and main drain locations.
Left−Hand
Discharge

Upflow or
Downflow

Right−Hand
Discharge

Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper furnace operation.
Reusable filters supplied with some units can be washed
with water and mild detergent. Some units are equipped
with standard throw−away type filters which should be replaced when dirty.
To remove filter, loosen the thumbscrews holding the filter
panel in place. Slide filter out of the guides on either side of
cabinet, insert new filter and replace panel. See Table 2 for
replacement filter sizes.

Table 2
Filter Dimensions
Main drain on right

Auxiliary drain on left

Figure 9
The following practices are recommended to ensure condensate removal (see figures 8 and 9):
1. Drain piping should not be smaller than the drain connections at drain pan.
2. A trap must be installed in the main drain line.
3. The trap must be deep enough to offset the difference
in static pressure between drain pan and atmosphere.
Generally, two inches is satisfactory for medium static
applications.
4. Horizontal runs must be sloped 1 inch per 10 feet of
drain line to offset friction.
5. An open vent in drain line will sometimes be required due
to line length, friction and static pressure.
6. Drain construction and routing should facilitate future
cleaning and must not interfere with filter access.
7. Auxiliary drain should run to an area where homeowner will notice any drainage. Refer to local codes.

Unit Model No.

Filter Size
Inches (mm)

CB29M/CB30M−21/26, CB29M−31
CB29M−41, −46, CB30M−31
CB29M−51, −65, CB30M−41, −46
CB30M−51, −65

15 x 20 (381 x 508)
20 x 20 (508 x 508)
20 x 22 (508 x 559)
20 x 24 (508 x 610)

Sealing the Unit
It is very important to seal the unit so that warm air is not
allowed into the cabinet. Warm air introduces moisture,
which results in water blow−off problems. This is especially
important when the unit is installed in an unconditioned
area.
Make sure the liquid line and suction line entry points are
sealed with either the provided Armaflex material or with
Permagum. Permagum may also be used to seal around
the main and auxiliary drains and around open areas of
electrical inlets.

Page 9
CB29M/CB30M SERIES

Blower Speed Adjustments

Blower Speed Tap Selection
harness
connector

Minimum Blower Speeds (With Electric Heaters)
For the minimum allowable speed for the CB29M/CB30M
series units with electric heat, refer to the ECB29 installation instructions.

Air Volume Adjustment
Blower speed selection is accomplished by changing the
taps at the harness connector at the blower motor. See figure 10. Refer to unit wiring diagram in figure 11. Refer to
Tables 3 through 20 for blower performance data.

Press the tab to release wire connector.
select connector location for new speed.
Insert wire until it clicks.

Figure 10

Table 3
CB29M-21/26 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
External Static
Low
Medium
High
Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
700
330
245
895
420
310
1030
485
.05
10
690
325
240
875
415
305
1010
475
.10
25
680
320
235
865
410
300
990
470
.15
35
665
315
230
850
400
290
970
460
.20
50
655
310
225
830
390
285
955
450
.25
60
640
300
220
810
385
280
925
440
.30
75
625
295
220
795
375
270
900
425
.40
100
595
280
210
750
355
255
850
400
.50
125
555
260
195
700
330
240
800
380
.60
150
510
240
185
640
300
225
725
340
.70
175
395
185
165
---------620
295
.75
185
------------------570
270
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
375
370
365
355
350
345
335
320
305
290
265
255

Table 4
CB29M-31 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1015
480
385
1135
535
410
1230
580
.05
10
995
470
375
1120
530
400
1205
570
.10
25
980
465
365
1095
515
390
1190
560
.15
35
960
455
355
1075
505
380
1165
550
.20
50
945
445
345
1050
495
375
1140
540
.25
60
925
435
335
1025
485
365
1105
520
.30
75
900
425
325
1005
475
355
1080
510
.40
100
860
405
305
950
450
335
1025
485
.50
125
800
380
285
890
420
315
960
450
.60
150
740
350
265
810
385
290
875
415
.70
175
670
315
240
735
345
270
790
375
.75
185
610
290
225
675
320
255
725
340
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 10
504719M 09/05

Watts
450
445
440
430
425
415
405
390
370
350
330
315

Table 5
CB29M-41 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
935
440
420
1145
540
510
1505
710
.05
10
930
440
415
1140
535
500
1485
700
.10
25
925
435
410
1130
535
490
1475
695
.15
35
915
435
395
1125
530
480
1455
685
.20
50
910
430
390
1115
525
475
1435
680
.25
60
905
425
380
1110
525
465
1420
670
.30
75
900
425
370
1100
520
455
1395
660
.40
100
885
415
355
1080
510
430
1350
640
.50
125
865
410
335
1060
500
415
1300
615
.60
150
845
400
315
1030
485
390
1235
585
.70
175
820
390
300
---------1160
550
.75
185
------------------1015
480
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
655
640
630
615
600
585
570
540
510
480
455
425

Table 6
CB29M-41 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
955
450
425
1130
535
530
1460
690
.05
10
950
450
415
1120
530
520
1445
680
.10
25
945
445
410
1115
525
510
1435
675
.15
35
940
445
400
1110
525
500
1415
670
.20
50
935
440
390
1105
520
490
1400
660
.25
60
930
440
385
1100
520
485
1380
650
.30
75
920
435
375
1090
515
475
1360
645
.40
100
910
430
360
1075
510
455
1325
625
.50
125
895
420
345
1060
500
435
1280
605
.60
150
880
415
330
1035
490
410
1225
580
.70
175
855
405
315
---------1145
540
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
665
650
640
630
615
600
585
555
520
480
430

Table 7
CB29M-46 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1295
610
520
1520
720
595
1775
840
.05
10
1275
605
510
1505
710
585
1750
825
.10
25
1255
590
495
1480
700
570
1720
810
.15
35
1230
580
480
1455
685
555
1690
795
.20
50
1215
575
470
1430
675
540
1650
780
.25
60
1195
565
455
1405
665
525
1620
765
.30
75
1170
555
440
1380
650
515
1595
750
.40
100
1125
530
415
1320
625
485
1515
715
.50
125
1065
500
385
1260
595
460
1420
670
.60
150
1005
475
360
1175
555
425
1325
625
.70
175
910
430
330
1075
505
395
1210
570
.80
200
------------------900
425
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
730
720
710
700
685
675
660
635
605
575
545
480

Page 11
CB29M/CB30M SERIES

Table 8
CB29M−51 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1590
750
665
1790
845
805
2055
970
.05
10
1570
740
660
1770
835
790
2035
960
.10
25
1555
735
655
1750
825
785
2005
945
.15
35
1530
720
645
1730
815
775
1980
935
.20
50
1510
710
640
1710
805
765
1945
920
.25
60
1485
700
635
1685
795
755
1915
905
.30
75
1460
690
625
1660
785
745
1885
890
.40
100
1415
670
615
1610
760
725
1820
860
.50
125
1370
645
600
1550
730
705
1750
825
.60
150
1310
620
580
1490
705
685
1670
790
.70
175
1240
585
560
1405
665
660
1575
745
.75
185
1210
570
550
1360
640
645
1520
720
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
1005
995
980
970
955
940
930
900
875
845
820
800

Table 9
CB29M−51 Blower Performance (460V − 1 ph)
External Static Pressure
in. w.g.
Pa

cfm

Low
L/s

Air Volume and Motor Watts at Specific Blower Taps
Medium
High
Watts
cfm
L/s
Watts
cfm
L/s

.00
0
1695
800
680
1900
895
805
2140
1010
.05
10
1675
790
670
1880
885
795
2110
995
.10
25
1655
780
665
1855
875
780
2080
980
.15
35
1640
775
655
1830
865
770
2050
970
.20
50
1620
765
650
1805
850
755
2025
955
.25
60
1595
750
640
1775
840
740
1995
940
.30
75
1570
740
630
1750
825
730
1965
925
.40
100
1525
720
610
1700
805
710
1905
900
.50
125
1475
695
595
1640
775
685
1845
870
.60
150
1420
670
575
1585
750
665
1770
835
.70
175
1355
640
555
1515
715
640
1700
800
.80
200
1290
610
535
1450
685
620
1625
765
.85
210
1255
590
525
1405
665
610
1595
750
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
965
950
935
920
910
895
885
860
835
805
780
755
745

Table 10
CB29M-65 Blower Performance (208/230v)
Air Volume and Motor Watts at Specific Blower Taps
External Static
Low
Medium−Low
Medium
Medium−High
Pressure
in.w.g.
Pa
cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm
L/s
Watts cfm
.00
0
1570 740
575
1800 850
700
2005 945
825
2135 1005
930
2245
.05
10
1550 730
570
1780 840
690
1980 935
815
2110
995
925
2220
.10
25
1530 725
560
1760 830
680
1950 920
805
2080 985
915
2190
.15
35
1520 715
560
1735 820
670
1930 910
795
2055 970
905
2165
.20
50
1495 705
550
1710 805
660
1910 900
790
2025 955
895
2135
.25
60
1475 695
545
1690 795
655
1880 890
780
1995 940
885
2105
.30
75
1460 690
540
1670 785
650
1855 875
770
1965 930
875
2075
.40
100
1415 670
530
1615 760
630
1795 850
750
1910 900
855
2005
.50
125
1370 645
520
1560 735
615
1735 820
730
1850 875
835
1935
.60
150
1310 620
505
1495 705
595
1670 790
710
1780 840
810
1855
.70
175
1250 590
490
1425 675
575
1600 755
690
1705 805
785
1780
.80
200
1175 555
470
1360 640
560
1520 715
665
1620 765
755
1685
.90
225
1025 485
440
1280 605
545
1420 670
645
1520 715
725
1595
.95
235
- - - - - - - - - - - 1240 585
535
1365 645
630
1460 690
705
1545
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 12
504719M 09/05

High
L/s
Watts
1060 1080
1050 1070
1035 1060
1020 1050
1010 1040
995
1030
980
1020
945
995
910
975
875
950
840
925
795
900
750
875
730
860

Table 11
CB29M−65 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1785
845
750
2050
970
925
2230
1055
.05
10
1775
835
745
2025
955
915
2200
1040
.10
25
1745
825
735
2005
945
905
2170
1025
.15
35
1725
815
725
1980
935
900
2135
1010
.20
50
1700
800
715
1955
920
885
2105
995
.25
60
1680
795
705
1925
910
875
2075
980
.30
75
1655
780
695
1900
895
865
2045
965
.40
100
1600
755
675
1840
870
845
1980
935
.50
125
1545
730
655
1785
845
825
1910
900
.60
150
1490
705
640
1715
810
800
1835
865
.70
175
1425
670
620
1645
775
775
1765
830
.80
200
1360
640
600
1565
735
745
1690
795
.90
225
1290
610
585
1465
690
710
1600
755
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
1145
1135
1120
1105
1095
1085
1075
1050
1025
1000
975
955
925

Table 12
CB30M-21/26 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
External Static
Low
Medium
High
Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
700
330
245
895
425
300
1030
485
.05
10
695
330
245
890
420
295
1015
480
.10
25
690
325
240
875
415
290
1000
470
.15
35
680
320
235
860
405
285
980
465
.20
50
665
315
230
845
400
280
960
455
.25
60
650
310
220
825
390
275
935
440
.30
75
635
300
215
800
380
265
910
430
.40
100
590
280
205
745
355
250
850
400
.50
125
535
255
190
685
320
235
780
370
.60
150
470
220
175
605
285
220
705
330
.70
175
395
185
165
520
245
200
615
290
.75
185
350
165
155
475
225
195
565
265
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
365
360
355
345
340
335
325
310
295
280
265
255

Table 13
CB30M-31 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1045
490
315
1175
555
335
1290
610
.05
10
1075
505
310
1190
560
330
1295
610
.10
25
1085
515
300
1190
560
325
1290
610
.15
35
1085
510
295
1175
555
320
1265
600
.20
50
1065
505
285
1145
540
310
1230
580
.25
60
1030
485
270
1105
520
295
1180
555
.30
75
980
460
255
1045
495
280
1115
525
.40
100
830
390
220
890
420
250
945
445
.50
125
615
290
190
675
320
215
720
340
.60
150
335
155
160
405
190
185
440
205
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
385
380
375
370
360
350
335
305
275
240

Page 13
CB29M/CB30M SERIES

Table 14
CB30M-41 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
915
430
335
1120
530
390
1525
720
.05
10
965
455
330
1150
540
385
1520
720
.10
25
1005
475
315
1170
550
380
1510
715
.15
35
1035
490
235
1180
560
285
1495
705
.20
50
1055
495
230
1190
560
280
1475
695
.25
60
1060
500
220
1185
560
275
1450
685
.30
75
1050
495
215
1175
555
375
1415
670
.40
100
1005
475
290
1135
535
325
1335
630
.50
125
915
430
255
1060
500
300
1230
580
.60
150
775
365
230
960
455
280
1100
520
.70
175
590
280
205
830
390
255
950
450
.75
185
485
230
195
750
355
245
870
410
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
505
495
480
470
455
440
430
400
375
345
320
305

Table 15
CB30M-41 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
Low
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
.00
0
1120
530
390
1525
720
.05
10
1150
540
385
1520
720
.10
25
1170
550
380
1510
715
.15
35
1180
560
285
1495
705
.20
50
1190
560
280
1475
695
.25
60
1185
560
275
1450
685
.30
75
1175
555
375
1415
670
.40
100
1135
535
325
1335
630
.50
125
1060
500
300
1230
580
.60
150
960
455
280
1100
520
.70
175
830
390
255
950
450
.75
185
750
355
245
870
410
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
505
495
480
470
455
440
430
400
375
345
320
305

Table 16
CB30M-46 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1325
625
370
1600
755
455
1825
860
.05
10
1335
630
370
1585
750
455
1790
845
.10
25
1335
630
370
1565
740
450
1750
825
.15
35
1330
630
365
1540
725
440
1710
805
.20
50
1320
620
360
1505
710
435
1660
785
.25
60
1300
615
355
1470
695
425
1610
760
.30
75
1270
600
350
1425
675
415
1555
735
.40
100
1195
565
330
1320
625
390
1430
675
.50
125
1090
515
310
1195
565
365
1290
610
.60
150
955
450
285
1050
495
335
1135
535
.70
175
795
375
260
875
415
310
965
455
.75
185
700
330
250
780
370
295
875
415
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 14
504719M 09/05

Watts
565
555
540
530
520
505
495
465
440
415
385
370

Table 17
CB30M-51 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1475
695
430
1785
845
520
1910
900
.05
10
1480
700
430
1770
835
515
1895
895
.10
25
1475
695
425
1750
825
510
1870
880
.15
35
1465
690
420
1720
810
500
1840
865
.20
50
1445
680
410
1685
795
490
1800
850
.25
60
1415
670
405
1645
775
480
1755
830
.30
75
1380
650
395
1600
755
465
1700
805
.40
100
1290
610
370
1485
700
440
1580
745
.50
125
1170
550
345
1350
635
410
1425
675
.60
150
1020
480
320
1190
560
380
1250
590
.70
175
840
395
295
1000
470
350
1045
495
.75
185
740
350
280
900
425
335
930
440
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
590
585
580
570
565
550
540
515
485
450
415
400

Table 18
CB30M-51 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
Low
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
.00
0
1775
835
530
1870
885
.05
10
1775
835
530
1875
885
.10
25
1765
835
515
1870
880
.15
35
1750
825
510
1850
875
.20
50
1720
815
500
1825
860
.25
60
1685
795
490
1790
845
.30
75
1645
775
480
1745
825
.40
100
1530
720
450
1625
765
.50
125
1380
650
420
1465
690
.60
150
1195
565
385
1270
600
.70
175
975
460
350
1030
485
.80
200
720
340
320
755
355
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Watts
610
610
590
585
575
560
545
505
470
425
385
340

Table 19
CB30M-65 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
Medium
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
.00
0
1775
835
585
2025
955
670
2115
995
.05
10
1775
835
590
2010
950
665
2100
990
.10
25
1770
835
580
1995
940
655
2085
985
.15
35
1760
830
570
1975
930
645
2060
970
.20
50
1745
825
560
1950
920
635
2030
960
.25
60
1725
815
550
1915
905
625
2000
945
.30
75
1695
800
535
1880
885
610
1960
925
.40
100
1630
770
505
1795
845
580
1870
880
.50
125
1540
725
475
1690
795
545
1755
830
.60
150
1425
675
440
1560
735
515
1620
765
.70
175
1295
610
410
1415
670
480
1465
690
.80
200
1140
535
375
1250
590
445
1290
610
.85
210
1050
495
360
1160
550
425
1195
565
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
External Static Pressure

Watts
780
770
765
750
740
730
715
685
655
625
590
560
545

Page 15
CB29M/CB30M SERIES

Table 20
CB30M-65 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
Low
High
External Static Pressure
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
.00
0
1965
930
710
2140
1010
.05
10
1950
920
700
2110
995
.10
25
1930
910
685
2080
980
.15
35
1910
900
675
2045
965
.20
50
1880
890
660
2005
945
.25
60
1850
875
645
1965
925
.30
75
1815
855
630
1920
905
.40
100
1735
820
600
1820
860
.50
125
1635
770
570
1710
805
.60
150
1520
720
540
1585
750
.70
175
1390
655
505
1450
685
.80
200
1245
590
475
1305
615
.85
210
1165
550
460
1225
580
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Electrical

WARNING
USE COPPER CONDUCTORS ONLY.
Run 24V Class II wiring only through specified low
voltage opening. Run line voltage wiring only
through specified high voltage opening. Do not
combine voltage in one opening.
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to follow-

ing wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
Select the proper supply circuit conductors in accordance with Tables 310−16 and 310−17 in the National
Electric Code, ANSI/NFPA No. 70 or Tables 1 through 4
in the Canadian Electric Code, Part I, CSA Standard
C22.1.
This unit is provided with knockouts for conduit. Reducer
washers are provided, in bag assembly to allow use of
smaller conduit. Use provided caps to seal holes not
used. Refer to figure 11 for unit schematic wiring diagram. Refer to figures 13 and 14 for typical field wiring.
Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustration for
specific location.

Page 16
504719M 09/05

Watts
795
780
765
755
740
725
710
680
650
615
585
550
535

System Wiring Diagrams
CB29 & CB30 Typical Wiring Diagram − Single Phase

Figure 11

Page 17
CB29M/CB30M SERIES

CB29 & CB30 Typical Wiring Diagram − Three Phase

Figure 12

Page 18
504719M 09/05

Typical Field Wiring − Cooling Only Application
4

6
1

(Black)

3

9

7

(Orange)

NOTE − USE COPPER CONDUCTORS ONLY.
REFER TO UNIT RATING PLATE FOR MINIMUM
CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE − ALL REMAINING WIRES ARE FACTORY
INSTALLED

CIRCUIT 1
TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM.
FIELD−SUPPLIED
WIRE NUTS

FACTORY INSTALLED JUMPERS
FUSE

Typical Field Wiring − Cooling Application With Electric Heat

4

6
1

3

CIRCUIT 1
9

7
CIRCUIT BREAKERS
OR TERMINAL BLOCK

FUSE

NOTE − USE COPPER CONDUCTORS ONLY.
REFER TO UNIT RATING PLATE FOR MINIMUM
CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE − ALL REMAINING WIRES ARE FACTORY
INSTALLED
TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM.
THERMOSTAT HEAT ANTICIPATION SETTING 0.4
AMP ELECTRIC HEAT
WHEN TWO−STAGE THERMOSTAT IS USED,
CONNECT SECOND STAGE HEAT BULB TO TERMINAL W2" AND REMOVE JUMPER BETWEEN
TERMINALS R" AND W2."
FACTORY INSTALLED JUMPERS
L3 CONNECTION USED ON (Y−VOLTAGE)
3−PHASE ELECTRIC HEATERS ONLY.

Figure 13

Page 19
CB29M/CB30M SERIES

Typical Field Wiring − Heat Pump Only Application
LINE VOLTAGE FIELD INSTALLED

4

CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC
NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED

6
1

TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM

3

FACTORY INSTALLED JUMPERS
Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED (HP21).

CIRCUIT 1

7

9

USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1
IN HEAT PUMP UNIT.

CIRCUIT BREAKERS
OR TERMINAL BLOCK

COMMON USED ONLY ON SOME THERMOSTATS.
AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY
ON SOME THERMOSTATS.

1

FUSE
E

C W1 G

O Y1

R

L

T

Y2

2
5

HEAT PUMP CLASS 2
VOLTAGE TERMINALS

T

L

Y2

THERMISTOR

SERVICE LIGHT

R
POWER

COMPRESSOR

ELECTRIC HEAT

Y1

REVERSING VALVE

COMMON

C

O

4

2ND STAGE COMPRESSOR

3
W1

6

Typical Field Wiring − Heat Pump Application With Electric Heat

7

3

E

6

C

W1

G

O Y1

R

L

O

R

L

T
THERMISTOR

CIRCUIT 1

K22

6
1

SERVICE LIGHT

4

T Y2

9

CIRCUIT
BREAKERS OR
TERMINAL
BLOCK
FUSE

S23

LINE VOLTAGE FIELD
INSTALLED
CLASS 2 VOLTAGE FIELD
INSTALLED NEC/CEC
NOTE − ALL REMAINING WIRES
ARE FACTORY INSTALLED
THERMOSTAT HEAT ANTICIPATION
SETTING 0.4 AMP ELECTRIC HEAT

Figure 14

Page 20
504719M 09/05

POWER

AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON
SOME THERMOSTATS.

HEAT PUMP CLASS 2
VOLTAGE TERMINALS

Y2
2ND STAGE COMPRESSOR

Y2 USED ONLY WHEN TWO-SPEED COMPRESSOR IS USED (HP21)

Y1
COMPRESSOR

COMMON USED ONLY ON SOME THERMOSTATS.

W1
ELECTRIC HEAT

EMERGENCY HEAT RELAY (USED
ONLY IF OUTDOOR T’STAT IS
USED) FIELD PROVIDED AND
INSTALLED NEW INDOOR UNIT.
24VAC 5VA MAX NEC/CEC CLASS 2

USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1 IN
HEAT PUMP UNIT.

COMMON

WHEN OUTDOOR THERMOSTAT IS
USED, CONNECT LEADS TO
TERMINALS R" AND W2" AND
REMOVE JUMPER BETWEEN
TERMINALS R’ AND W2."

C

REVERSING VALVE

7

FACTORY INSTALLED JUMPERS

8



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 20
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:5e333dbb-92e5-42fc-8461-7837083838d2
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : BroadVision, Inc.
Modify Date                     : 2005:09:30 13:54:03-05:00
Create Date                     : 2005:09:30 13:54:03-05:00
Document ID                     : uuid:078a986b-d68a-4209-8041-6ad7cfdc1aaf
Format                          : application/pdf
Title                           : Document:
Creator                         : jao3
Author                          : jao3
EXIF Metadata provided by EXIF.tools

Navigation menu