21 Series Lennox CB29M CB30M IOM
User Manual: 21 Series
Open the PDF directly: View PDF
.
Page Count: 20
| Download | |
| Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS E2005 Lennox Industries Inc. Dallas, Texas, USA CB29M & CB30M Elite® Series Units MULTI−POSITION BLOWER COILS 504,719M 09/05 Supersedes 04/05 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Table of Contents IMPORTANT For downflow application, kit number 83M57 (LB−109844A) is required. Kit is not provided with coil blower; order separately. IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. WARNING Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor. Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900 09/05 *2P0905* CB29M & CB30M Series Units . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shipping & Packing List . . . . . . . . . . . . . . . . . . . . . . . . CB29M Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . CB30M Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Piping Connections . . . . . . . . . . . . . . . . . . . . . . . Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sealing the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Blower Speed Adjustments . . . . . . . . . . . . . . . . . . . . . Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . 1 1 1 2 4 5 5 8 9 9 9 10 16 17 CB29M & CB30M Series Units The Lennox CB29M and CB30M Elite® series blower coil units are designed for installation with a matched remote outdoor unit and optional field−installed electric heat. The blower coil units are for indoor installation only. The CB29M and CB30M units, designed for multi−positional installations, are completely assembled at the factory and shipped ready for upflow or horizontal right−hand discharge installation. General These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installing the unit Check equipment for shipping damage; if found, immediately contact the last carrier. Shipping and Packing List Each CB29M and CB30M unit package contains: 1 − Assembled blower coil unit Page 1 504,719M *P504719M* CB29M Upflow and Downflow Unit Dimensions − inches (mm) 3/4 (19) PIPING PLATE DETAIL (For upflow and downflow positions) SUPPLY AIR OPENING D 1-1/8 (29) 3/4 (19) 4-3/8 (111) 2 (51) LINE VOLTAGE INLETS (TOP & LEFT SIDE) LOW VOLTAGE INLETS (TOP & RIGHT SIDE) Top View 5/8 (16) CONDENSATE DRAINS (2) (UPFLOW AND DOWNFLOW) 2-3/4 (70) E 3-1/2 (89) RETURN AIR OPENING 1 (25) 1-3/4 (44) 5/8 (16) B 5/8 (16) F LIQUID LINE 11-1/16 (281) 5-3/8 (137) 5/8 (16) SUCTION LINE CONDENSATE DRAINS (2) (HORIZONTAL) Top View C C FILTER ACCESS B FILTER SUCTION LINE OPTIONAL ELECTRIC HEAT (FIELD− INSTALLED) AIR FLOW LIQUID LINE OPTIONAL ELECTRIC HEAT (FIELD− INSTALLED) A SUCTION LINE RETURN AIR FILTER ACCESS COIL Front View LIQUID LINE FILTER BLOWER RETURN AIR SUPPLY AIR E 5/8 (16) A AIR FLOW LOW VOLTAGE (RIGHT SIDE) LINE VOLTAGE (LEFT SIDE) F 5/8 (16) COIL BLOWER 1 (25) Side View SUPPLY AIR 11-1/16 (281) 5/8 (16) Side View Upflow Position 5/8 (16) D 5/8 (16) Front View 5/8 (16) Downflow Position (Kit number 83M57 (LB−909844A) required to convert unit to downflow applications.) Model No. Dimension A B C D E F CB29M-21/26 & CB29M-31 inch mm 45-1/4 1149 16-1/4 413 20-5/8 524 14-3/4 375 19 483 15 351 CB29M-41 & CB29M-46 inch mm 49-1/4 1251 21-1/4 540 20-5/8 524 19-3/4 502 19 483 20 508 Page 2 504719M 09/05 CB29M-51 & CB29M-65 inch mm 52-1/2 1334 21-1/4 540 22-5/8 575 19-3/4 502 21 533 20 508 CB29M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm) FILTER 2 (51) 5-3/8 (137) LIQUID LINE SUCTION LINE CONDENSATE DRAINS (2) (UPFLOW AND DOWNFLOW) COIL BLOWER C For dimensions A" through F", see chart on Page 2. 1-1/8 (29) CONDENSATE DRAINS (2) (HORIZONTAL) 4-3/8 (111) PIPING PLATE DETAIL 5-3/4 (46) 1-3/4 (44) LIQUID LINE SUCTION LINE Top View 1-1/2 (38) 5/8 (16) 5/8 (16) 11-1/16 3/4 (281) (19) A E 5/8 (16) OPTIONAL ELECTRIC HEAT (FIELD−INSTALLED) F RETURN AIR OPENING 1 (25) LINE VOLTAGE INLETS (TOP & RIGHT SIDE) AIR FLOW 3/4 (19) SUPPLY AIR OPENING B LOW VOLTAGE INLETS (BOTTOM & RIGHT SIDE) 5/8 (16) End View Front View FILTER ACCESS D 3/4 (19) End View Horizontal Position (Right-Hand Air Discharge) 4-3/8 (111) BLOWER C COIL PIPING PLATE DETAIL FILTER OPTIONAL ELECTRIC HEAT (FIELD INSTALLED) 3/4 LOW VOLTAGE (19) 11-1/16 INLETS (TOP & LEFT SIDE) (281) Top View SUPPLY AIR OPENING LINE VOLTAGE INLETS (BOTTOM & LEFT SIDE) End View LIQUID LINE 2 (51) FILTER ACCESS AIR FLOW CONDENSATE DRAINS (2) (HORIZONTAL) Front View 5-3/8 (137) 5/8 (16) A B 3/4 (19) SUCTION LINE LIQUID LINE 5/8 (16) 3/4 (19) D SUCTION LINE 1-1/8 (29) 1-1/2 (38) 1-3/4 (44) 5-3/4 (146) E 1 (25) 5/8 (16) F RETURN AIR OPENING 5/8 (16) End View Horizontal Position (Left-Hand Air Discharge) Page 3 CB29M/CB30M SERIES CB30M Upflow and Downflow Unit Dimensions − inches (mm) 3/4 (19) PIPING PLATE DETAIL (For upflow and downflow positions) SUPPLY AIR OPENING D 1-1/8 (29) 3/4 (19) 4-3/8 (111) 2 (51) LINE VOLTAGE INLETS (TOP & LEFT SIDE) LOW VOLTAGE INLETS (TOP & RIGHT SIDE) Top View 5/8 (16) F CONDENSATE DRAINS (2) (UPFLOW AND DOWNFLOW) 2-3/4 (70) E 3-1/2 (89) RETURN AIR OPENING 1 (25) 1-3/4 (44) 5/8 (16) B 5/8 (16) LIQUID LINE 11-1/16 (281) 5-3/8 (137) 5/8 (16) SUCTION LINE CONDENSATE DRAINS (2) (HORIZONTAL) Top View C C FILTER ACCESS B FILTER G OPTIONAL ELECTRIC HEAT (FIELD− INSTALLED) AIR FLOW H FILTER ACCESS SUCTION LINE LIQUID LINE OPTIONAL ELECTRIC HEAT (FIELD− INSTALLED) COIL LIQUID LINE FILTER Front View BLOWER G RETURN AIR SUPPLY AIR E 5/8 (16) A AIR FLOW LOW VOLTAGE (RIGHT SIDE) LINE VOLTAGE (LEFT SIDE) F 5/8 (16) COIL BLOWER A RETURN AIR H SUCTION LINE 1 (25) Side View SUPPLY AIR 11-1/16 (281) 5/8 (16) Side View Upflow Position 5/8 (16) D 5/8 (16) 5/8 (16) Front View Downflow Position (Kit number 83M57 (LB−909844A) required to convert unit to downflow applications.) Model No. Dimension A B C D E F G H CB30M-21/26 inch mm 45-1/4 1149 16-1/4 413 20-5/8 524 14-3/4 375 19 483 15 351 24-5/8 625 20-5/8 524 CB30M-31 inch mm 49-1/4 1251 21-1/4 540 20-5/8 524 19-3/4 502 19 483 20 508 24-5/8 625 24-5/8 625 CB30M-41 inch mm 51 1295 21-1/4 540 22-5/8 575 19-3/4 502 21 533 20 508 26-3/8 670 24-5/8 625 Page 4 504719M 09/05 CB30M-46 inch mm 52-1/2 1334 21-1/4 540 22-5/8 575 19-3/4 502 21 533 20 508 27-7/8 708 24-5/8 625 CB30M-51 & CB30M-65 inch mm 58-1/2 1486 21-1/4 540 24-5/8 625 19-3/4 502 23 584 20 508 27-7/8 708 30-5/8 778 CB30M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm) FILTER 2 (51) 5-3/8 (137) LIQUID LINE SUCTION LINE CONDENSATE DRAINS (2) (UPFLOW AND DOWNFLOW) COIL BLOWER C For dimensions A" through H", see chart on Page 4. 1-1/8 (29) CONDENSATE DRAINS (2) (HORIZONTAL) 4-3/8 (111) PIPING PLATE DETAIL 5-3/4 (46) 1-3/4 (44) LIQUID LINE OPTIONAL ELECTRIC HEAT (FIELD−INSTALLED) Top View 1-1/2 (38) H E F RETURN AIR OPENING 5/8 (16) A 5/8 (16) 5/8 (16) SUCTION LINE G 1 (25) 11-1/16 3/4 (281) (19) LINE VOLTAGE INLETS (TOP & RIGHT SIDE) AIR FLOW 3/4 (19) SUPPLY AIR OPENING B LOW VOLTAGE INLETS (BOTTOM & RIGHT SIDE) 5/8 (16) End View Front View FILTER ACCESS D 3/4 (19) End View Horizontal Position (Right-Hand Air Discharge) 4-3/8 (111) C BLOWER COIL PIPING PLATE DETAIL FILTER OPTIONAL ELECTRIC HEAT (FIELD INSTALLED) 3/4 LOW VOLTAGE (19) 11-1/16 INLETS (TOP & LEFT SIDE) (281) Top View SUCTION LIQUID LINE LINE SUCTION LINE LIQUID LINE A 5/8 (16) G 1-1/8 (29) 2 (51) 5/8 (16) H 3/4 (19) D SUPPLY AIR OPENING B 3/4 (19) LINE VOLTAGE INLETS (BOTTOM & LEFT SIDE) FILTER ACCESS AIR FLOW 1-1/2 (38) 1-3/4 (44) CONDENSATE DRAINS (2) (HORIZONTAL) Front View End View 5-3/8 (137) E 1 (25) 5/8 (16) F RETURN AIR OPENING 5/8 (16) 5-3/4 (146) End View Horizontal Position (Left-Hand Air Discharge) Requirements Installation Installation of Lennox blower coil units with or without optional electric heat must conform with standards in the National Fire Protection Association (NFPA) Standard for Installation of Air Conditioning and Ventilation Systems NFPA No. 90A," and Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA No. 90B," manufacturer’s installation instructions and local municipal building codes. This unit is certified for installation clearances to combustible material as listed on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances. WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency. The CB29M and CB30M units are factory−configured for upflow or horizontal right−hand discharge installation. For downflow or horizontal left−hand discharge, some field modification is required. Page 5 CB29M/CB30M SERIES 2. No further adjustment is necessary. Set unit so that it is sloped 1/4 inch toward the drain pan end of the unit. IMPORTANT Kit number 83M57 (LB−109844A) must be installed for downflow application. NOTE − For horizontal applications, an auxiliary drain pan is recommended. Refer to local codes. Disassembling CB30M Blower Coil Unit These units are shipped from the factory fully assembled. The CB30M blower coil unit’s sections may be separated to facilitate movement at some installation sites. If required, disassemble the unit as follows: 1. Remove access panels from both blower and coil assemblies. This will lighten the cabinet for lifting. 2. Remove one screw from the left and right posts inside the unit. Remove one screw from each side on the back of the unit. Unit sections will now separate. 3. To reassemble, align cabinet sections and reinstall screws. Replace access panels. NOTE − For horizontal applications in high humidity areas, seal around the exiting drain pipe, liquid line, and suction line to prevent infiltration of humid air. Right−Hand Discharge Configuration Upflow/ Downflow Drain Pan Horizontal Drip Shield Horizontal Drain Pan No Adjustment is Necessary Figure 2 Upflow Application 1. Remove access panels. Remove corrugated padding from the space between the blower and coil assemblies. 2. To ensure proper operation, remove the horizontal drain pan from units in upflow configurations (see figure 1). 3. Place unit in desired location. Make sure that unit is level. Connect return and supply air plenums as required using sheet metal screws. 4. Install units that have no return air plenum on a mounting stand at least 14" from the floor for proper air return. Lennox offers an optional upflow unit stand. (45K31 for CB29M−21, −26, and −31; 45K32 for CB29M−41 through −65.) 3. If the unit is to be suspended, it must be supported along the entire length of the cabinet (see figure 3). If using a chain or strap, attach a piece of angle iron or sheet metal to the unit (either above or below the unit), so that the full length of the cabinet is supported. Use securing screws which are no longer than 1/2 inch to avoid damaging the coil or filter. Use sheet metal screws to connect the return and supply air plenums. Suspending Horizontal Unit Angle Iron or Sheet Metal Electrical Inlet Clearance 4 in. (102 mm) 1/2 IN. SCREWS MAX. Upflow Configuration FRONT VIEW END VIEW Figure 3 Upflow/ Downflow Drain Pan Horizontal Drain Pan (Remove for Optimum Performance) CAUTION Figure 1 Horizontal Right−Hand Discharge Application 1. Remove access panels. Remove corrugated padding from the space between the blower and coil assembly. Page 6 504719M 09/05 When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right− or left−hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it. 4. (See Detail B and C in figure 4.) Remove screws from top cap. Remove horizontal drip shield screw located in the center of the back coil end seal. 5. Rotate horizontal drip shield 180° front to back. 6. Remove plastic plug from left hole on coil front end seal and re−install plug in back hole. Re−install horizontal drip shield screw in front coil end seal. Drip shield should drain downward into horizontal drain pan inside coil. 7. Rotate top cap 180° front to back and align with unused screw holes. Holes must align with front and back coil end plates. Note that top cap has a 45° bend on one side and 90° bend on the other. The 90° bend must be on the same side as the horizontal drain pan. See figure 4. Horizontal Left−Hand Discharge Application NOTE − For horizontal applications, an auxiliary drain pan is recommended. Refer to local codes. Remove the access panels and the corrugated padding from the space between the blower and coil assembly before operation. Make the following modifications: 1. (See Detail A in figure 4.) Pull coil assembly from unit. Pull off the horizontal drain pan. 2. Remove drain plugs from back drain holes on horizontal drain pan and re−install them on front holes. 3. Rotate drain pan 180° front to back and install it on the opposite side of coil. Left-Hand Discharge Modifications Coil shown in upflow position for easy conversion NOTE − Use extreme care when re−installing screws into coil end plate engaging holes. Misaligned screws may damage coil. 8. (See figure 5.) From the upflow position, flip cabinet 90° to the left and set into place. Replace coil assembly. Secure coil in place by bending down tab on cabinet support rail. Detail A (DRAIN PAN) PLUGGED END COIL ASSEMBLY OPEN END FOR CONDENSATION DRAIN ORIGINAL PLUG LOCATION Left−Hand Discharge Configuration Securing Tab on Cabinet Support Rail Horizontal Drip Shield NEW PLUG LOCATION TOP CAP ROTATED TO CORRECT POSITION TOP CAP SCREWS Detail B (TOP CAP) Horizontal Drain Pan CABINET SUPPORT Figure 5 90_ BEND 9. Detail C ALIGN HOLES WITH HOLES IN COIL END PLATE. TOP CAP 90_ BEND 10. 11. 12. BACK COIL END SEAL DRAIN PAN Figure 4 NOTE − For horizontal applications in high humidity areas, seal around the exiting drain pipe, liquid line and suction line to prevent infiltration of humid air. Knock out drain seal plate from access door. Secure plate to cabinet front flange with screw provided. Flip access door and replace it on the unit. Set unit so that it is sloped 1/4 inch toward the drain pan end of the unit. Connect return and supply air plenums as required using sheet metal screws. If the unit is to be suspended, it must be supported along the entire length of the cabinet (see figure 3). If using a chain or strap, attach a piece of angle iron or sheet metal to the unit (either above or below the unit), so that the full length of the cabinet is supported. Use securing screws which are no longer than 1/2 inch to avoid damaging the coil or filter. Use sheet metal screws to connect the return and supply air plenums. Page 7 CB29M/CB30M SERIES Downflow Application NOTE − If downflow application is required, separately order kit number 83M57 and install per kit’s instructions. Also, use metal or class I supply and return air plenums. If the homeowner reports water dripping from supply air diffusers, check the shields and tape. Make sure the tape is completely attached to the edges of the drip shield, and that the drip shield is wedged firmly in place. Field Piping Connections WARNING All CB29M/CB30M coils are equipped with a factory− installed, internally mounted expansion valve. Use Lennox L15 (sweat) series line sets as shown in Table 1 or use field−fabricated refrigerant lines. L10 (flare) line sets may be used by cutting off flare nut. Refer to the piping section of the Lennox Unit Information Service Manual for proper size, type and application of field−fabricated lines. If electric heat section with circuit breakers (ECB29) are applied to downflow CB29M or CB30M unit, circuit breakers must be rotated 180_ to the UP position. See ECB29 installation instructions for more details. Combustible Flooring Additive Base Table 1 Refrigerant Line Sets BLOWER COIL UNIT CB29M CB29M Unit Combustible Floor Additive Base Properly−Sized Floor Opening Figure 6 On combustible flooring, use an additive base (figure 6). Cut an appropriately sized opening for combustible base (see dimensions in figure 7). Set the additive base into opening. Connect supply air plenum to the additive base. Set the unit on the additive base so flanges of the unit drop into the base opening and seal against the insulation strips. The unit is now locked in place. Install return air plenum and secure with sheet metal screws. inches (mm) 20 (508) CB29M−41 to −65 CB30M−31 to 65 18−1/4 (464) CB29M−21/26 & 31 CB30M−21/26 23−1/4 (591) CB29M−41 to −65 CB30M−31 to 65 3/8 in (8 mm) 5/8 in (16 mm) L10−26 20 ft. − 50 ft. (6 m − 15 m) L15−26 20 ft. − 50 ft. (6 m − 15 m) −31 −41 3/8 in (10 mm) 3/4 in. (19 mm L10−41 20 ft. − 50 ft. (6 m − 15 m) L15−41 20 ft. − 50 ft. (6 m − 15 m) −46 −51 3/8 in (10 mm) 7/8 in. (22 mm) L10−65 30 ft. − 50 ft. (9 m − 15 m) L15−65 30 ft. − 50 ft. (9 m − 15 m) −65 3/8 in (10 mm) 1−1/8 in. (29 mm) FIELD FABRICATED FIELD FABRICATED 4. With heat shield in place, sweat in suction line elbow, provided, and line set. After procedure is completed, remove heat shield. TOP VIEW 22-1/8 (562) 13-3/8 (340) 5. Place heat shield against piping plate and around the liquid line connection. Sweat in the liquid line elbow (provided) and the line set. OPENING 2 (51) SIDE VIEW 6. Refer to instructions provided with outdoor unit for leak testing, evacuating and charging procedures. Figure 7 Page 8 504719M 09/05 −21/26 3. Place heat shield (damp rag) against piping plate and around the suction line connection. Heat shield must be in place to guard against damage to the paint. 1-5/8 (41) 5/8 (16) L15 Line Sets 2. Be aware of filter access panel when connecting lines. Filter must be accessible. 1-5/8 (41) SUPPLY AIR OPENING L10 Line Sets 1. Use a wet rag to protect TXV bulb (or remove it) when brazing suction line. 11-3/8 (289) 15 (381) CB29M−21/26 & 31 CB30M−21/26 Vapor/ Suction Line NOTE − CB29M/CB30M series evaporators use nitrogen or dry air as a holding charge. If there is no pressure when the rubber plugs are removed, check the coil or line set for leaks before installing. After installation, pull a vacuum on the line set and coil before releasing the unit charge into the system. Downflow Combustible Base Dimensions 1-5/8 (41) Liquid Line No. Condensate Drain Filters Connect main condensate drain and route downward to an open drain or sump. Do not connect drain to a closed waste system. Refer to figure 8 for typical condensate trap configuration. IMPORTANT Filter access panel must be in place during unit operation. Excessive warm air entering the unit may result in water blow−off problems. Typical Condensate Drain Connection Minimum 1 inch (25 mm) pitch per 10 feet (3048mm) of line Trap must be deep enough to offset maximum static difference (generally, 2" [51mm] minimum). Pipe diameter difference Each unit includes a factory−installed filter. Note that filter access door fits over access panel. Air leakage will occur if access panel is placed over filter door. Coil drain pan Figure 8 It is recommended that the auxiliary drain be connected to a drain line for all units. If auxiliary drain is not connected, it must be plugged with provided cap. For downflow units, the auxiliary drain MUST be connected and routed to a drain. See figure 9 for auxiliary and main drain locations. Left−Hand Discharge Upflow or Downflow Right−Hand Discharge Filters should be inspected monthly and must be cleaned or replaced when dirty to assure proper furnace operation. Reusable filters supplied with some units can be washed with water and mild detergent. Some units are equipped with standard throw−away type filters which should be replaced when dirty. To remove filter, loosen the thumbscrews holding the filter panel in place. Slide filter out of the guides on either side of cabinet, insert new filter and replace panel. See Table 2 for replacement filter sizes. Table 2 Filter Dimensions Main drain on right Auxiliary drain on left Figure 9 The following practices are recommended to ensure condensate removal (see figures 8 and 9): 1. Drain piping should not be smaller than the drain connections at drain pan. 2. A trap must be installed in the main drain line. 3. The trap must be deep enough to offset the difference in static pressure between drain pan and atmosphere. Generally, two inches is satisfactory for medium static applications. 4. Horizontal runs must be sloped 1 inch per 10 feet of drain line to offset friction. 5. An open vent in drain line will sometimes be required due to line length, friction and static pressure. 6. Drain construction and routing should facilitate future cleaning and must not interfere with filter access. 7. Auxiliary drain should run to an area where homeowner will notice any drainage. Refer to local codes. Unit Model No. Filter Size Inches (mm) CB29M/CB30M−21/26, CB29M−31 CB29M−41, −46, CB30M−31 CB29M−51, −65, CB30M−41, −46 CB30M−51, −65 15 x 20 (381 x 508) 20 x 20 (508 x 508) 20 x 22 (508 x 559) 20 x 24 (508 x 610) Sealing the Unit It is very important to seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow−off problems. This is especially important when the unit is installed in an unconditioned area. Make sure the liquid line and suction line entry points are sealed with either the provided Armaflex material or with Permagum. Permagum may also be used to seal around the main and auxiliary drains and around open areas of electrical inlets. Page 9 CB29M/CB30M SERIES Blower Speed Adjustments Blower Speed Tap Selection harness connector Minimum Blower Speeds (With Electric Heaters) For the minimum allowable speed for the CB29M/CB30M series units with electric heat, refer to the ECB29 installation instructions. Air Volume Adjustment Blower speed selection is accomplished by changing the taps at the harness connector at the blower motor. See figure 10. Refer to unit wiring diagram in figure 11. Refer to Tables 3 through 20 for blower performance data. Press the tab to release wire connector. select connector location for new speed. Insert wire until it clicks. Figure 10 Table 3 CB29M-21/26 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps External Static Low Medium High Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 700 330 245 895 420 310 1030 485 .05 10 690 325 240 875 415 305 1010 475 .10 25 680 320 235 865 410 300 990 470 .15 35 665 315 230 850 400 290 970 460 .20 50 655 310 225 830 390 285 955 450 .25 60 640 300 220 810 385 280 925 440 .30 75 625 295 220 795 375 270 900 425 .40 100 595 280 210 750 355 255 850 400 .50 125 555 260 195 700 330 240 800 380 .60 150 510 240 185 640 300 225 725 340 .70 175 395 185 165 ---------620 295 .75 185 ------------------570 270 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 375 370 365 355 350 345 335 320 305 290 265 255 Table 4 CB29M-31 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1015 480 385 1135 535 410 1230 580 .05 10 995 470 375 1120 530 400 1205 570 .10 25 980 465 365 1095 515 390 1190 560 .15 35 960 455 355 1075 505 380 1165 550 .20 50 945 445 345 1050 495 375 1140 540 .25 60 925 435 335 1025 485 365 1105 520 .30 75 900 425 325 1005 475 355 1080 510 .40 100 860 405 305 950 450 335 1025 485 .50 125 800 380 285 890 420 315 960 450 .60 150 740 350 265 810 385 290 875 415 .70 175 670 315 240 735 345 270 790 375 .75 185 610 290 225 675 320 255 725 340 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Page 10 504719M 09/05 Watts 450 445 440 430 425 415 405 390 370 350 330 315 Table 5 CB29M-41 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 935 440 420 1145 540 510 1505 710 .05 10 930 440 415 1140 535 500 1485 700 .10 25 925 435 410 1130 535 490 1475 695 .15 35 915 435 395 1125 530 480 1455 685 .20 50 910 430 390 1115 525 475 1435 680 .25 60 905 425 380 1110 525 465 1420 670 .30 75 900 425 370 1100 520 455 1395 660 .40 100 885 415 355 1080 510 430 1350 640 .50 125 865 410 335 1060 500 415 1300 615 .60 150 845 400 315 1030 485 390 1235 585 .70 175 820 390 300 ---------1160 550 .75 185 ------------------1015 480 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 655 640 630 615 600 585 570 540 510 480 455 425 Table 6 CB29M-41 Blower Performance (460V − 1 ph) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 955 450 425 1130 535 530 1460 690 .05 10 950 450 415 1120 530 520 1445 680 .10 25 945 445 410 1115 525 510 1435 675 .15 35 940 445 400 1110 525 500 1415 670 .20 50 935 440 390 1105 520 490 1400 660 .25 60 930 440 385 1100 520 485 1380 650 .30 75 920 435 375 1090 515 475 1360 645 .40 100 910 430 360 1075 510 455 1325 625 .50 125 895 420 345 1060 500 435 1280 605 .60 150 880 415 330 1035 490 410 1225 580 .70 175 855 405 315 ---------1145 540 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 665 650 640 630 615 600 585 555 520 480 430 Table 7 CB29M-46 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1295 610 520 1520 720 595 1775 840 .05 10 1275 605 510 1505 710 585 1750 825 .10 25 1255 590 495 1480 700 570 1720 810 .15 35 1230 580 480 1455 685 555 1690 795 .20 50 1215 575 470 1430 675 540 1650 780 .25 60 1195 565 455 1405 665 525 1620 765 .30 75 1170 555 440 1380 650 515 1595 750 .40 100 1125 530 415 1320 625 485 1515 715 .50 125 1065 500 385 1260 595 460 1420 670 .60 150 1005 475 360 1175 555 425 1325 625 .70 175 910 430 330 1075 505 395 1210 570 .80 200 ------------------900 425 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 730 720 710 700 685 675 660 635 605 575 545 480 Page 11 CB29M/CB30M SERIES Table 8 CB29M−51 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1590 750 665 1790 845 805 2055 970 .05 10 1570 740 660 1770 835 790 2035 960 .10 25 1555 735 655 1750 825 785 2005 945 .15 35 1530 720 645 1730 815 775 1980 935 .20 50 1510 710 640 1710 805 765 1945 920 .25 60 1485 700 635 1685 795 755 1915 905 .30 75 1460 690 625 1660 785 745 1885 890 .40 100 1415 670 615 1610 760 725 1820 860 .50 125 1370 645 600 1550 730 705 1750 825 .60 150 1310 620 580 1490 705 685 1670 790 .70 175 1240 585 560 1405 665 660 1575 745 .75 185 1210 570 550 1360 640 645 1520 720 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 1005 995 980 970 955 940 930 900 875 845 820 800 Table 9 CB29M−51 Blower Performance (460V − 1 ph) External Static Pressure in. w.g. Pa cfm Low L/s Air Volume and Motor Watts at Specific Blower Taps Medium High Watts cfm L/s Watts cfm L/s .00 0 1695 800 680 1900 895 805 2140 1010 .05 10 1675 790 670 1880 885 795 2110 995 .10 25 1655 780 665 1855 875 780 2080 980 .15 35 1640 775 655 1830 865 770 2050 970 .20 50 1620 765 650 1805 850 755 2025 955 .25 60 1595 750 640 1775 840 740 1995 940 .30 75 1570 740 630 1750 825 730 1965 925 .40 100 1525 720 610 1700 805 710 1905 900 .50 125 1475 695 595 1640 775 685 1845 870 .60 150 1420 670 575 1585 750 665 1770 835 .70 175 1355 640 555 1515 715 640 1700 800 .80 200 1290 610 535 1450 685 620 1625 765 .85 210 1255 590 525 1405 665 610 1595 750 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 965 950 935 920 910 895 885 860 835 805 780 755 745 Table 10 CB29M-65 Blower Performance (208/230v) Air Volume and Motor Watts at Specific Blower Taps External Static Low Medium−Low Medium Medium−High Pressure in.w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm .00 0 1570 740 575 1800 850 700 2005 945 825 2135 1005 930 2245 .05 10 1550 730 570 1780 840 690 1980 935 815 2110 995 925 2220 .10 25 1530 725 560 1760 830 680 1950 920 805 2080 985 915 2190 .15 35 1520 715 560 1735 820 670 1930 910 795 2055 970 905 2165 .20 50 1495 705 550 1710 805 660 1910 900 790 2025 955 895 2135 .25 60 1475 695 545 1690 795 655 1880 890 780 1995 940 885 2105 .30 75 1460 690 540 1670 785 650 1855 875 770 1965 930 875 2075 .40 100 1415 670 530 1615 760 630 1795 850 750 1910 900 855 2005 .50 125 1370 645 520 1560 735 615 1735 820 730 1850 875 835 1935 .60 150 1310 620 505 1495 705 595 1670 790 710 1780 840 810 1855 .70 175 1250 590 490 1425 675 575 1600 755 690 1705 805 785 1780 .80 200 1175 555 470 1360 640 560 1520 715 665 1620 765 755 1685 .90 225 1025 485 440 1280 605 545 1420 670 645 1520 715 725 1595 .95 235 - - - - - - - - - - - 1240 585 535 1365 645 630 1460 690 705 1545 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Page 12 504719M 09/05 High L/s Watts 1060 1080 1050 1070 1035 1060 1020 1050 1010 1040 995 1030 980 1020 945 995 910 975 875 950 840 925 795 900 750 875 730 860 Table 11 CB29M−65 Blower Performance (460V − 1 ph) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1785 845 750 2050 970 925 2230 1055 .05 10 1775 835 745 2025 955 915 2200 1040 .10 25 1745 825 735 2005 945 905 2170 1025 .15 35 1725 815 725 1980 935 900 2135 1010 .20 50 1700 800 715 1955 920 885 2105 995 .25 60 1680 795 705 1925 910 875 2075 980 .30 75 1655 780 695 1900 895 865 2045 965 .40 100 1600 755 675 1840 870 845 1980 935 .50 125 1545 730 655 1785 845 825 1910 900 .60 150 1490 705 640 1715 810 800 1835 865 .70 175 1425 670 620 1645 775 775 1765 830 .80 200 1360 640 600 1565 735 745 1690 795 .90 225 1290 610 585 1465 690 710 1600 755 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 1145 1135 1120 1105 1095 1085 1075 1050 1025 1000 975 955 925 Table 12 CB30M-21/26 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps External Static Low Medium High Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 700 330 245 895 425 300 1030 485 .05 10 695 330 245 890 420 295 1015 480 .10 25 690 325 240 875 415 290 1000 470 .15 35 680 320 235 860 405 285 980 465 .20 50 665 315 230 845 400 280 960 455 .25 60 650 310 220 825 390 275 935 440 .30 75 635 300 215 800 380 265 910 430 .40 100 590 280 205 745 355 250 850 400 .50 125 535 255 190 685 320 235 780 370 .60 150 470 220 175 605 285 220 705 330 .70 175 395 185 165 520 245 200 615 290 .75 185 350 165 155 475 225 195 565 265 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 365 360 355 345 340 335 325 310 295 280 265 255 Table 13 CB30M-31 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1045 490 315 1175 555 335 1290 610 .05 10 1075 505 310 1190 560 330 1295 610 .10 25 1085 515 300 1190 560 325 1290 610 .15 35 1085 510 295 1175 555 320 1265 600 .20 50 1065 505 285 1145 540 310 1230 580 .25 60 1030 485 270 1105 520 295 1180 555 .30 75 980 460 255 1045 495 280 1115 525 .40 100 830 390 220 890 420 250 945 445 .50 125 615 290 190 675 320 215 720 340 .60 150 335 155 160 405 190 185 440 205 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 385 380 375 370 360 350 335 305 275 240 Page 13 CB29M/CB30M SERIES Table 14 CB30M-41 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 915 430 335 1120 530 390 1525 720 .05 10 965 455 330 1150 540 385 1520 720 .10 25 1005 475 315 1170 550 380 1510 715 .15 35 1035 490 235 1180 560 285 1495 705 .20 50 1055 495 230 1190 560 280 1475 695 .25 60 1060 500 220 1185 560 275 1450 685 .30 75 1050 495 215 1175 555 375 1415 670 .40 100 1005 475 290 1135 535 325 1335 630 .50 125 915 430 255 1060 500 300 1230 580 .60 150 775 365 230 960 455 280 1100 520 .70 175 590 280 205 830 390 255 950 450 .75 185 485 230 195 750 355 245 870 410 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 505 495 480 470 455 440 430 400 375 345 320 305 Table 15 CB30M-41 Blower Performance (460V − 1 ph) Air Volume and Motor Watts at Specific Blower Taps Low High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s .00 0 1120 530 390 1525 720 .05 10 1150 540 385 1520 720 .10 25 1170 550 380 1510 715 .15 35 1180 560 285 1495 705 .20 50 1190 560 280 1475 695 .25 60 1185 560 275 1450 685 .30 75 1175 555 375 1415 670 .40 100 1135 535 325 1335 630 .50 125 1060 500 300 1230 580 .60 150 960 455 280 1100 520 .70 175 830 390 255 950 450 .75 185 750 355 245 870 410 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 505 495 480 470 455 440 430 400 375 345 320 305 Table 16 CB30M-46 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1325 625 370 1600 755 455 1825 860 .05 10 1335 630 370 1585 750 455 1790 845 .10 25 1335 630 370 1565 740 450 1750 825 .15 35 1330 630 365 1540 725 440 1710 805 .20 50 1320 620 360 1505 710 435 1660 785 .25 60 1300 615 355 1470 695 425 1610 760 .30 75 1270 600 350 1425 675 415 1555 735 .40 100 1195 565 330 1320 625 390 1430 675 .50 125 1090 515 310 1195 565 365 1290 610 .60 150 955 450 285 1050 495 335 1135 535 .70 175 795 375 260 875 415 310 965 455 .75 185 700 330 250 780 370 295 875 415 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Page 14 504719M 09/05 Watts 565 555 540 530 520 505 495 465 440 415 385 370 Table 17 CB30M-51 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1475 695 430 1785 845 520 1910 900 .05 10 1480 700 430 1770 835 515 1895 895 .10 25 1475 695 425 1750 825 510 1870 880 .15 35 1465 690 420 1720 810 500 1840 865 .20 50 1445 680 410 1685 795 490 1800 850 .25 60 1415 670 405 1645 775 480 1755 830 .30 75 1380 650 395 1600 755 465 1700 805 .40 100 1290 610 370 1485 700 440 1580 745 .50 125 1170 550 345 1350 635 410 1425 675 .60 150 1020 480 320 1190 560 380 1250 590 .70 175 840 395 295 1000 470 350 1045 495 .75 185 740 350 280 900 425 335 930 440 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 590 585 580 570 565 550 540 515 485 450 415 400 Table 18 CB30M-51 Blower Performance (460V − 1 ph) Air Volume and Motor Watts at Specific Blower Taps Low High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s .00 0 1775 835 530 1870 885 .05 10 1775 835 530 1875 885 .10 25 1765 835 515 1870 880 .15 35 1750 825 510 1850 875 .20 50 1720 815 500 1825 860 .25 60 1685 795 490 1790 845 .30 75 1645 775 480 1745 825 .40 100 1530 720 450 1625 765 .50 125 1380 650 420 1465 690 .60 150 1195 565 385 1270 600 .70 175 975 460 350 1030 485 .80 200 720 340 320 755 355 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Watts 610 610 590 585 575 560 545 505 470 425 385 340 Table 19 CB30M-65 Blower Performance (208/230V) Air Volume and Motor Watts at Specific Blower Taps Low Medium High in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s .00 0 1775 835 585 2025 955 670 2115 995 .05 10 1775 835 590 2010 950 665 2100 990 .10 25 1770 835 580 1995 940 655 2085 985 .15 35 1760 830 570 1975 930 645 2060 970 .20 50 1745 825 560 1950 920 635 2030 960 .25 60 1725 815 550 1915 905 625 2000 945 .30 75 1695 800 535 1880 885 610 1960 925 .40 100 1630 770 505 1795 845 580 1870 880 .50 125 1540 725 475 1690 795 545 1755 830 .60 150 1425 675 440 1560 735 515 1620 765 .70 175 1295 610 410 1415 670 480 1465 690 .80 200 1140 535 375 1250 590 445 1290 610 .85 210 1050 495 360 1160 550 425 1195 565 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. External Static Pressure Watts 780 770 765 750 740 730 715 685 655 625 590 560 545 Page 15 CB29M/CB30M SERIES Table 20 CB30M-65 Blower Performance (460V − 1 ph) Air Volume and Motor Watts at Specific Blower Taps Low High External Static Pressure in. w.g. Pa cfm L/s Watts cfm L/s .00 0 1965 930 710 2140 1010 .05 10 1950 920 700 2110 995 .10 25 1930 910 685 2080 980 .15 35 1910 900 675 2045 965 .20 50 1880 890 660 2005 945 .25 60 1850 875 645 1965 925 .30 75 1815 855 630 1920 905 .40 100 1735 820 600 1820 860 .50 125 1635 770 570 1710 805 .60 150 1520 720 540 1585 750 .70 175 1390 655 505 1450 685 .80 200 1245 590 475 1305 615 .85 210 1165 550 460 1225 580 NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance. Electrical WARNING USE COPPER CONDUCTORS ONLY. Run 24V Class II wiring only through specified low voltage opening. Run line voltage wiring only through specified high voltage opening. Do not combine voltage in one opening. Wiring must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to follow- ing wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. Select the proper supply circuit conductors in accordance with Tables 310−16 and 310−17 in the National Electric Code, ANSI/NFPA No. 70 or Tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1. This unit is provided with knockouts for conduit. Reducer washers are provided, in bag assembly to allow use of smaller conduit. Use provided caps to seal holes not used. Refer to figure 11 for unit schematic wiring diagram. Refer to figures 13 and 14 for typical field wiring. Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustration for specific location. Page 16 504719M 09/05 Watts 795 780 765 755 740 725 710 680 650 615 585 550 535 System Wiring Diagrams CB29 & CB30 Typical Wiring Diagram − Single Phase Figure 11 Page 17 CB29M/CB30M SERIES CB29 & CB30 Typical Wiring Diagram − Three Phase Figure 12 Page 18 504719M 09/05 Typical Field Wiring − Cooling Only Application 4 6 1 (Black) 3 9 7 (Orange) NOTE − USE COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE. LINE VOLTAGE FIELD INSTALLED CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED CIRCUIT 1 TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM. FIELD−SUPPLIED WIRE NUTS FACTORY INSTALLED JUMPERS FUSE Typical Field Wiring − Cooling Application With Electric Heat 4 6 1 3 CIRCUIT 1 9 7 CIRCUIT BREAKERS OR TERMINAL BLOCK FUSE NOTE − USE COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE. LINE VOLTAGE FIELD INSTALLED CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM. THERMOSTAT HEAT ANTICIPATION SETTING 0.4 AMP ELECTRIC HEAT WHEN TWO−STAGE THERMOSTAT IS USED, CONNECT SECOND STAGE HEAT BULB TO TERMINAL W2" AND REMOVE JUMPER BETWEEN TERMINALS R" AND W2." FACTORY INSTALLED JUMPERS L3 CONNECTION USED ON (Y−VOLTAGE) 3−PHASE ELECTRIC HEATERS ONLY. Figure 13 Page 19 CB29M/CB30M SERIES Typical Field Wiring − Heat Pump Only Application LINE VOLTAGE FIELD INSTALLED 4 CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED 6 1 TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM 3 FACTORY INSTALLED JUMPERS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED (HP21). CIRCUIT 1 7 9 USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1 IN HEAT PUMP UNIT. CIRCUIT BREAKERS OR TERMINAL BLOCK COMMON USED ONLY ON SOME THERMOSTATS. AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON SOME THERMOSTATS. 1 FUSE E C W1 G O Y1 R L T Y2 2 5 HEAT PUMP CLASS 2 VOLTAGE TERMINALS T L Y2 THERMISTOR SERVICE LIGHT R POWER COMPRESSOR ELECTRIC HEAT Y1 REVERSING VALVE COMMON C O 4 2ND STAGE COMPRESSOR 3 W1 6 Typical Field Wiring − Heat Pump Application With Electric Heat 7 3 E 6 C W1 G O Y1 R L O R L T THERMISTOR CIRCUIT 1 K22 6 1 SERVICE LIGHT 4 T Y2 9 CIRCUIT BREAKERS OR TERMINAL BLOCK FUSE S23 LINE VOLTAGE FIELD INSTALLED CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED THERMOSTAT HEAT ANTICIPATION SETTING 0.4 AMP ELECTRIC HEAT Figure 14 Page 20 504719M 09/05 POWER AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON SOME THERMOSTATS. HEAT PUMP CLASS 2 VOLTAGE TERMINALS Y2 2ND STAGE COMPRESSOR Y2 USED ONLY WHEN TWO-SPEED COMPRESSOR IS USED (HP21) Y1 COMPRESSOR COMMON USED ONLY ON SOME THERMOSTATS. W1 ELECTRIC HEAT EMERGENCY HEAT RELAY (USED ONLY IF OUTDOOR T’STAT IS USED) FIELD PROVIDED AND INSTALLED NEW INDOOR UNIT. 24VAC 5VA MAX NEC/CEC CLASS 2 USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1 IN HEAT PUMP UNIT. COMMON WHEN OUTDOOR THERMOSTAT IS USED, CONNECT LEADS TO TERMINALS R" AND W2" AND REMOVE JUMPER BETWEEN TERMINALS R’ AND W2." C REVERSING VALVE 7 FACTORY INSTALLED JUMPERS 8
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Page Count : 20 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:5e333dbb-92e5-42fc-8461-7837083838d2 Producer : Acrobat Distiller 6.0.1 (Windows) Creator Tool : BroadVision, Inc. Modify Date : 2005:09:30 13:54:03-05:00 Create Date : 2005:09:30 13:54:03-05:00 Document ID : uuid:078a986b-d68a-4209-8041-6ad7cfdc1aaf Format : application/pdf Title : Document: Creator : jao3 Author : jao3EXIF Metadata provided by EXIF.tools