Technical Specifications
APC Modular Power Distribution Unit
APC 144kVA Modular Power Distribution Unit,
Isolation Transformer, 480:208V, 72 Poles, 2 Subfeed
APC 144kVA Modular Power Distribution Unit,
Isolation Transformer, 600:208V, 72 Poles, 2 Subfeed
APC 175kVA Modular Power Distribution Unit,
Isolation Transformer, 480:415V, 72 Poles, 2 Subfeed

Table of Contents
Technical Data............................................................................................ 1
Modular PDU Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Power Distribution Modules Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Communication and Management ........................................................... 2
Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

List Of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Network Management Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Input and Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Facility Planning ........................................................................................ 5
Input Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mains Input Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mains Input Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Maximum Short-Circuit Withstand Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Recommended Conductor Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
40° Ambient / 3CCC, 150 & 175 kW Modular PDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
30° Ambient / 3CCC, 150 & 175 kW Modular PDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
JLF361150C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Transformer Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Drawings................................................................................................... 12
Options ..................................................................................................... 16
Hardware Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power Distribution Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APC Power Distribution Modules for 208V Modular PDUs . . . . . . . . . . . . . . . . . . . .
Power Distribution Modules continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APC Power Distribution Modules for 415V Modular PDUs . . . . . . . . . . . . . . . . . . . .
Seismic Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bottom Feed Side Cars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16
16
17
17
18
18

Shunt Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Configuration Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

990-4806

150/175 kVA Modular PDU Technical Specification

i

Warranty ................................................................................................... 19
Three Phase Power Products or Cooling Solutions One-Year Factory
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Non-transferable Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assignment of Warranties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drawings, descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warranty Claims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ii

150/175 kVA Modular PDU Technical Specification

19
19
19
19
19
20
20

990-4806

Technical Data
Model Nomenclature
Modular PDU Values

PD

PM
Distribution
Type
PM: Modular
Power
Distribution

Product Type
PD: Power
Distribution

PDPM150G6H
150
G

6

H

Power (kVA)

Input Voltage

Line Frequency

Output Voltage

150: 144kVA
175: 175kVA

G: 480V
L: 600V

5=50Hz
6=60Hz

F=208V
H=415V

Power Distribution Modules Values

PDM
Product Type

3
Breaker
Poles

Power
Distribution
Mode

Example
PDM3520L2120-1040

990-4806

PDM3520L2120-1040
5
20
Number of
Breaker
Wires
Rating (A)

1
2
3

L2120

1040

Connector Type

Cable Length (cm)

L5-20
L21-20
L21-30
CS50
IEC 309 60A
L6-30R
IEC 309 20A
IEC 309

(for a complete list, see
Power Distribution
Module section of
Accessories)

20A
30A
40A
50A
60A

3
5

Breaker Poles

Number of
Wires

Breaker
Rating (A)

Connector
Type

Cable Length
(cm)

3

5

20A

L2120

1040 cm

150/175 kVA Modular PDU Technical Specification

1

Communication and Management
Display Interface



  













Normal LED

Green = no alarms are present.



Check Log LED

Green = a new event has been added to the log.



Warning LED

Yellow = there are one or more active warning alarms in the system.



Critical LED

Red = there are one or more active critical alarms in the system.



LCD Screen

Displays alarms, status data, instructional help, and configuration items.



UP and DOWN keys

Used to scroll through menu items.



ENTER

Press to display new screens, open menu items, and finalize selections.



? - HELP

Press to open content-sensitive help.



ESC

Press to return to the previous screen.

Menu tree

2

150/175 kVA Modular PDU Technical Specification

990-4806

List Of Alarms
• Low Output Voltage
• High Module Current

• Min Output Voltage
• Maximum Module Current

• High Subfeed Current

• Modular Distribution Communication
• Maximum Subfeed Current

• High Total Output Current

• Module Breaker Open
• Max Total Output Current

• High Output Voltage

• Output Frequency
• Max Output Voltage

• Low Module Current

• Subfeed Breaker Open
• Minimum Module Current

• Low Subfeed Current

• Transformer Overheating
• Minimum Subfeed Current

• Low Total Output Current

• Cooling Fan Failure
• Min Total Output Current

Network Management Card

The system is equipped with one embedded network management card for remote monitoring and
control of an individual Modular Power Distribution Unit (PDU) by connecting it directly to the
network.

990-4806

150/175 kVA Modular PDU Technical Specification

3

pdx0420a

Input and Output Contacts

Note: Input Contacts are “Normally Open”
Available Output Contacts: SPST, 1A@30V
AST0, AST1, AST2, AST EN, EPO 24V AC/DC + ˗, and EPO CONTACT pair are reserved and not
available.
Wiring: 12 AWG to 30 AWG is recommended.

User Interface Relay Outputs
Surge withstand voltage up to 2500VAC,
Surge ratings meets FCC Part 68 and Telecordia

Compliance
• UL - UL 60950-1, 2nd Edition, 2007- 03 -27
• (Information Technology Equipment - Safety - Part 1: General Requirements)
• cUL - CSA C22.2 No. 60950-1-07, 2nd Edition, 2007 - 03
• (Information Technology Equipment - Safety - Part 1: General Requirements)
• The Conditional Short-Circuit Current Rating was not evaluated by Underwriters Laboratories.

4

150/175 kVA Modular PDU Technical Specification

990-4806

Facility Planning
Input Specifications
PDPM150G6F

PDPM150L6F

Grid system

3W + G+GEC

Input mains

3 Phase

Connection
Information:

Hardwire:
Max Input Conductor Size:
350MCM for Cu Cable
500MCM for Al Cable

Disconnect

PDPM175G6H

Hardwire:
Hardwire:
Max Input Conductor Size: Max Input Conductor Size:
300MCM (Cu Cable Only)
350MCM for Cu Cable
500MCM for Al Cable

Molded Case Circuit Breaker (MCCB)

Mains Input Voltage
Nominal

480V

600V

480V

Nominal Current

178A

141A

214A

Maximum Continuous
Current with 100%
Rated Circuit Breaker

180A

150A

214A

200 A

300 A

1500 A

2100 A

Mains Input Current

Recommended current rating of input circuit breakers
225 A
Mains Input1
Inrush Currents
Inrush Current2
2000 A

1 Standard circuit breakers are rated to carry 80% of their current rating continuously.
2 The supply overcurrent protective device must be able to handle the listed transformer

inrush currents.

Maximum Short-Circuit Withstand Rating
PDPM150G6F

PDPM150L6F

PDPM175G6H

Max Short-Circuit
65 kA
50 kA
30 kA
Withstand Rating*
* The Maximum Short-Circuit Withstand Rating was not evaluated by Underwriters Laboratories.

Frequency
Nominal

990-4806

60Hz

150/175 kVA Modular PDU Technical Specification

5

Output Specifications
Grid System
Number of Poles
Number of PDMs
Overload Protection
Full Load Rating
Max Continuous
Current
Nominal Voltage
Number of Subfeeds

PDPM150G6F
208/120V, 3-pole modules
72
24
yes

PDPM150L6F
208/120V, 3-pole modules
72
24
yes

PDPM175G6H
415/240V, 3-pole modules
72
24
yes

144KW @ 208V

144KW @ 208V

175KW @ 415V

400A

400A

243A

208Y/120 V

208Y/120 V
2

415Y/240 V

PDPM150G6F
External to PDU, supplied
by others

PDPM150L6F
External to PDU, supplied
by others

PDPM175G6H
External to PDU, supplied
by others

225A

200A

300A

Breakers

Location
OCP Rating
Max Input Conductor
Size

Terminal: Lug Size

Terminal: Cable Sizing

See the Following Tables:
40° Ambient / 3CCC, 150 & 175 kW Modular PDU
30° Ambient / 3CCC, 150 & 175 kW Modular PDU
Terminal Kit
(included with PDU):
dual lug

Terminal Kit
(included with PDU):
single lug

Terminal Kit
(included with PDU):
dual lug

Dual Terminal:

Single terminal:

Dual Terminal:

from 2/0 AWG to 350
kcmil max for Copper,

from 1/0 AWG to 300
kcmil max, Copper only.

from 2/0 AWG to 350
kcmil max for Copper,

from 2/0 AWG to 500
kcmil max for Aluminum.

from 2/0 AWG to 500
kcmil max for Aluminum.

Recommended Conductor Sizes
Note: All wiring must comply with all applicable national and or local electrical codes.
Conductor sizing in this manual is based on Table 310-16 of the 2011 National Electrical Code (NEC) with
the following assertions:
• 90°C conductors (THHN) for 75°C termination
• 3 Current Carrying Conductors for Unit Input Circuit Breaker and 4 Current Carrying Conductors for
Subfeed Circuit Breaker
• An ambient temperature of 30°C
• Two conduits for each Subfeed
• One Equipment Grounding Conductor for each conduit
If the ambient room temperature is greater than 30°C, larger conductors are to be selected in accordance with
the correction factors of the NEC.
Equipment Grounding Conductors (EGC) are sized in accordance with NEC Article 250-122 and Table 250122.
Grounding Electrode Conductors (GEC) are sized in accordance with NEC Article 250-66 and Table 250-66.
6

150/175 kVA Modular PDU Technical Specification

990-4806

The conductor sizes are recommendations for maximum configurations. Even if the load is less than the
maximum rating, it is wise to plan for future load increases. If the system is operated at a lower load than its
rating and it is desired to supply the system with a lower rated breaker and smaller conductors, conductor
ampacities are to be selected in accordance with the NEC. The transformer inrush must betaken into account
when sizing the circuit breaker.

40° Ambient / 3CCC, 150 & 175 kW Modular PDU
PDPM150G6F
480:208
Cu only: 250kcmil

PDPM150L6F
600:208
Cu only: 3/0 AWG

75°C conductor minimum
Cu: 4 AWG

90°C conductor minimum
Cu: 6 AWG

Grounding Electrode
Conductor (GEC)

Cu: 2 AWG

Cu: 2 AWG

Output

Supplied with Power Distribution Modules

Mains Input Φ
Equipment Grounding
Conductor (EGC)

Cu: (2) 300kcmil Φ and N,
3 AWG EGC,
GEC not required.

Cu: (2) 300kcmil Φ and N,
3 AWG EGC,
GEC not required.

4CCC Subfeed Output

PDPM175G6H
480:415
Cu: 350kcmil
AL: 500kcmil
75°C conductor minimum
Cu: 4 AWG
Al: 2 AWG
Cu: 2 AWG
Al: 1/0 AWG
Cu: (2) 2/0 AWG Φ and N,
4 AWG EGC,
GEC not required.
Al: (2) 4/0 AWG Φ and N,
2 AWG EGC,
GEC not required.

90°C conductor minimum

90°C conductor minimum

75°C conductor minimum

30° Ambient / 3CCC, 150 & 175 kW Modular PDU
PDPM150G6F
480:208
Cu: 4/0 AWG
Mains Input Φ
A1: 300kcmil
75°C conductor minimum
Equipment Grounding Cu: 4 AWG
Conductor (EGC)
A1: 2 AWG
Cu: 2 AWG
Grounding Electrode
Conductor (GEC)
A1: 1/0 AWG
Output

4CCC Subfeed Output

PDPM150L6F
600:208
Cu: 3/0 AWG
90°C conductor minimum
Cu: 6 AWG
Cu: 2 AWG

PDPM175G6H
480:415
Cu: 300kcmil
Al: 400kcmil
75°C conductor minimum
Cu: 4 AWG
Al: 2 AWG
Cu: 2 AWG
Al: 1/0 AWG

Supplied with Power Distribution Modules
Cu: (2) 250kcmil Φ and N, Cu: (2) 250kcmil Φ and N,
3 AWG EGC,
3 AWG EGC,
GEC not required.
GEC not required.

Cu: (2) 2/0 AWG Φ and N,
4 AWG EGC,
GEC not required.

Al: (2) 350 kcmil Φ and N,
1 AWG EGC,
GEC not required.

Al: (2) 350 kcmil Φ and N,
1 AWG EGC,
GEC not required.

Al: (2) 3/0 AWG Φ and N,
2 AWG EGC,
GEC not required.

90°C conductor minimum

90°C conductor minimum

75°C conductor minimum

Φ = phase, N = neutral
(2) = two conductors per phase and neutral (when neutral is required)
Subfeed is required to have two conductors per phase & N for full output due to limited wire bend space
Cu= Copper conductors, Al= Aluminum conductors
CCC = Current Carrying Conductor

990-4806

150/175 kVA Modular PDU Technical Specification

7

CB1

Tripping Curve
Type

PDPM150G6F
480:208
See ‘STR23SP’

PDPM150L6F
600:208
See ‘JLF361150C’

PDPM175G6H
480:415
See ‘STR23SP’

Merlin Gerin

Square D

Merlin Gerin

STR23SP
Merlin Gerin - Trip Units for Compact® NSJ400-NSJ600 Circuit Breakers

10 000
5 000
2 000

Ir = 0.4–1 x In

1 000
500
200
100
50
20
10
5

t(s)

2

Im = 2–9 x Ir

1
.5
.2
.1
.05

Reflex Tripping:
t < 10 ms

.01
.005

I = 11 x In

.002
.001
.5

.7

1

2

3 4 5

7

10

20

30

50 70 100

STR23SP 06153218

.02

200 300

I / Ir

8

150/175 kVA Modular PDU Technical Specification

990-4806

JLF361150C

J-Frame 150–250 A (JD, JG, JJ, and JL)
Thermal-Magnetic Trip

10000
9000
8000

7000

7000

6000

6000

5000

5000

4000

4000

3000

3000

2000

2000

1500

1500

1000
900
800

1000
900
800

700

700

600

600

500

500

Circuit Breaker
Prefix

Continuous
Ampere Rating

400

400

JD, JG, JJ, JL

150–250

2, 3

8000
9000
10000

7000

6000

5000

4000

3000

2000

800
900
1000

700

600

100
90
80

100
90
80

70

70

60

60

50

50

40

40

30

30

20

20

15

15

10
9
8

10
9
8

7

7

6

6

5

5

4

4

3

3

2

2
1.5

1.5

1
.9
.8

LIMITS LOW
SETTING

TIME IN SECONDS

TIME IN SECONDS

Number
of Poles

600

All time/current characteristic curve data is based on 40°C ambient cold start.
Terminations are made with conductors of appropriate length and ratings.
500

150

Maximum
AC Voltage

This curve is to be used for application and coordination purposes only. The
EZ-AMP overlay feature at the bottom of the page should be used during
coordination studies.

400

200

150

CIRCUIT BREAKER INFORMATION

150

200

JD, JG, JJ, JL MOLDED CASE CIRCUIT BREAKERS
CHARACTERISTIC TRIP CURVE NO. 50-5

300

300

Curve No. 0050TC0405
June 2004
Drawing No. 48095-050-05

200

MAXIMUM SINGLE-POLE TRIP TIMES
AT 25 °C BASED ON NEMA AB-4 2003

300

2011 Schneider Electric
All Rights Reserved

1500

80
90
100

70

60

50

40

30

20

15

8
9
10

7

6

5

4

3

2

1.5

.8
.9
1

.7

.6

.5

MULTIPLES OF RATED CURRENT
10000
9000
8000

1
.9
.8

LIMITS HIGH
SETTING

.7

.7

.6

.6

.5

.5

.4

.4

.3

.3

.2

.2
.15

.15

MAGNETIC TRIP
ADJUSTMENT RANGE

.1
.09
.08

.1
.09
.08

.07

.07

.06

.06
.05

.05
.04

.04

MAXIMUM CLEARING TIME
(AT 50 Hz)
(AT 60 Hz)

.03

.03

1 CYCLE
(50 Hz)

.02

1 CYCLE
(60 Hz)

.015

.02
.015

1/2

.01
.009
.008

CYCLE
(50 Hz)

1/2

CYCLE
(60 Hz)

.007

.01
.009
.008
.007

6000

7000

5000

4000

3000

1500

8000
9000
10000
TM

250
225
200
175
150

MULTIPLES OF RATED CURRENT

2000

800
900
1000

700

600

500

400

300

200

150

80
90
100

70

60

50

40

30

20

15

8
9
10

7

6

5

4

3

2

1.5

.8
.9
1

.7

.005
.6

.006

.005
.5

.006

990-4806

150/175 kVA Modular PDU Technical Specification

9

Environmental
PDPM150G6F

PDPM150L6F

Operating Temp

-5 to +40°C
(23 to 104°F)

Storage Temp

-25 to +65°C
(-13 to 149°F)

Operating Humidity

0 to 95%, non-condensing

Storage Humidity

0 to 95%, non-condensing
3,000 m
(9,842.5 ft)
15 000 m
(50,000 ft)

Max Operating Elevation
Max Storage Elevation
Operating Environment

PDPM175G6H

Protected from water and conductive contaminants.

Storage Environment
Full Load Heat Loss @ Nominal Mains
Airflow/Cooling Requirement

Protected from water and conductive contaminants.
3.128 kW/hr
3.272 kW/hr
3.441 kW/hr
(10672.7 BTU/hr) (11164.1 BTU/hr) (11740.7 BTU/hr)
Front to rear airflow

Transformer Specifications
PDPM150G6F

PDPM150L6F

PDPM175G6H

150kVA
Isolated
Transformer
Delta/Wye

150kVA
Isolated
Transformer
Delta/Wye

175kVA
Isolated
Transformer
Delta/Wye

Input Voltage

480V

600V

480V

Input Current

180A

150A

214A

Size
Type
Configuration

Inrush Current

Not to exceed 10X Nominal Input Current Per Phase

Output Voltage

208Y/120V

208Y/120V

415Y/240V

Output Current

400A

400A

243A

Thermal Sensing

180°C
900 lb
(409 kg)
3 - 6%

180°C
900 lb
(409 kg)
3 - 6%

180°C
1232 lb
(560 kg)
3 - 6%

60 Hz

60 Hz

60 Hz

57-63Hz

57-63Hz

57-63Hz

<55db @ Im

<55db @ Im

<55db @ Im

Weight
Impedance in %IZ
Frequency
Frequency Range
Noise

Copper - Each coil to be made from a continuous
conductor (wire or foil).

Windings

10

Insulation rating

180°C

180°C

180°C

Efficiency

>98.2%

>98.2%

>98.5%

150/175 kVA Modular PDU Technical Specification

990-4806

Dimensions
PDPM150G6F

PDPM150L6F

PDPM175G6H

Unpackaged Dimensions
(H × W × D)

79.0 x 23.6 x 42.1 in.
(2007 x 600 x 1069 mm)

79.0 x 23.6 x 42.1 in.
(2007 x 600 x 1069 mm)

79.0 x 23.6 x 42.1 in.
(2007 x 600 x 1069 mm)

Shipping Dimensions
(H x W x D)

84.8 x 40 x 48.0 in.
84.8 x 40 x 48.0 in.
84.8 x 40 x 48.0 in.
(2153 x 1016 x 1219 mm) (2153 x 1016 x 1219 mm) (2153 x 1016 x 1219 mm)

Weight
(Unpopulated PDU)

1843.1 lb
(836 kg)

1942.3 lb
(881 kg)

2074.6 lb
(941 kg)

Shipping weight
(Unpopulated PDU)

1944.5 lb
(882 kg)

2043.7
(927 kg)

2176.0 lb
(987 kg)

Free space around PDU:
Minimum Recommended
Front Service Clearance*

42.0 in.
(1066.8 mm)

Minimum Recommended
Rear Service Clearance*

36 in.
(914.4 mm)
Right: 24 in. (609.6 mm)
Left: None Required

Side Clearance*
Minimum Top Ventilation
Clearance*

8.25 in.
(210 mm)

* In establishing and verifying proper clearance, ensure full compliance with all applicable national, state, and
local electrical codes.
Color

Black

Input Power Entry Cable
Route
(Top, Bottom, Both)

Top

Top

Top

Output Power Exit Cable
Route (Top, Bottom, Both)

Top

Top

Top

Conduit Size
Size of Roof Hole or Bottom
Plate for Conduit

990-4806

Defined by input wiring
Hole is punched by customer according to conduit size.

150/175 kVA Modular PDU Technical Specification

11

Drawings
Note: These drawings are for reference ONLY - subject to change without notice.
Note: A comprehensive set of drawings is available on the APC Web site: www.apc.com

12

150/175 kVA Modular PDU Technical Specification

990-4806

DEVISE

RATING
(100% Rated)

4 POLE BREAKER

3 POLE BREAKER

TYPE

MAKE

MODEL

NJHF36400E20
(100% Rated)

400A, 600V
MERLIN GERIN

S EE NOTE 7

400A, 600V

3 POLE BREAKER
SCHNEIDER
ELECTRIC

UIB

400A, 600V

POWER DISTRIBUTION MODULE

MOB
SUBFEED
BREAKER
400V

NJHF36400E20
MERLIN GERIN
(100% Rated)
NJHS46400E20
MERLIN GERIN
(100% Rated)

MODULE-X

65kA
SYMMETRICAL

RATED SHORT
CIRCUIT CURRENT
65kA
SYMMETRICAL
65kA
SYMMETRICAL

10kA
SYMMETRICAL

13

150/175 kVA Modular PDU Technical Specification

990-4806

DEVISE

400A, 600V

150A, 600V

RATING
(100% Rated)

4 POLE BREAKER

3 POLE BREAKER

TYPE

POWER DISTRIBUTION MODULE

3 POLE BREAKER

UIB

400V

400A, 600V

MOB
SUBFEED
BREAKER
MODULE-X

MAKE

MODEL

SEE NOTE 7

JLF36150CYE
SQUARE D
(100% Rated)
NJHS46400E20
MERLIN GERIN
(100% Rated)
NJHF36400E20
MERLIN GERIN
(100% Rated)
SCHNEIDER
ELECTRIC

RATED SHORT
CIRCUIT CURRENT
50kA
SYMMETRICAL
65kA
SYMMETRICAL
65kA
SYMMETRICAL
10kA
SYMMETRICAL

990-4806

150/175 kVA Modular PDU Technical Specification

14

MOB

UIB

DEVISE

400A, 600V

400A, 600V

400A, 600V

RATING
(100% Rated)

POWER DISTRIBUTION MODULE

3 POLE BREAKER

4 POLE BREAKER

3 POLE BREAKER

TYPE

SCHNEIDER
ELECTRIC

MERLIN GERIN

MAKE

SUBFEED
BREAKER
240V

MODEL

SEE NOTE 7

NJHF36400E20
MERLIN GERIN
(100% Rated)
NJHS46400E20
MERLIN GERIN
(100% Rated)
NJHF36400E20
(100% Rated)

MODULE-X

RATED SHORT
CIRCUIT CURRENT
65kA
SYMMETRICAL
65kA
SYMMETRICAL
65kA
SYMMETRICAL
10kA
SYMMETRICAL

15

150/175 kVA Modular PDU Technical Specification

990-4806

Options
Hardware Options
Power Distribution Modules
The following APC Power Distribution Modules (PDMs) are intended for, and can be installed in the following
208V Modular PDUs:
APC Modular Power
Distribution Units
PDPM150G6F
PDPM150L6F

APC Power Distribution Modules for 208V Modular PDUs
208V Power Distribution Modules have black buss plates which match the black 208V PDU backplane. These
PDMs require one (1) Modular PDU slot position.
# cords

Voltage

Amperage

(Qty)
Circuit
Breakers

PDM1320L5-3P-x

3

120V

20A

(3) 1P

PDM3520L2120-xxx

1

120V

20A

(3) 1P

PDM3530L2130-xxx

1

120V

30A

(3) 1P

PDM3450CS50-xxx

1

208V

50A

(1) 3P

PDM3460IEC309-xxx

1

208V

60A

(1) 3P

PDM2330L6-xx-yyy

1

208V

30A

(1) 2P

Module

(Qty)
Connector
(3) 3-wire
NEMA
L5-20R
(1) 5-wire
NEMA
L21-20
(1) 5 wire
NEMA
L21-30
(1) 4 wire
CS50
(1) 4 wire
(3P+PE) IEC
309 60A
(1) 3 wire
NEMA
L6-30R

Notes:
Input frequency: 50/60Hz
Certifications: UL Listed
Cable rating of Power Distribution Modules: TC-ER, DP-1. Approved for under floor usage per NFPA
645.5(E) and 645.5(E)(3) when used in a designated IT Site as defined in NFPA Article 645, Information
Technology Equipment.
The PDM3460IEC309-xxx PDMs use a 4-wire IEC 309 connector with a 9 o'clock ground position.
Unless otherwise noted, 1-cord Power Distribution Modules are available with these cord lengths:
200, 260, 320, 380, 440, 500, 560, 620, 680, 740, 800, 860, 920, 980, 1040, 1680
Unless otherwise noted, all 3-cord Power Distribution Modules are available with these cord lengths:
Option 1: PDM with 260, 380, and 500 cm cables
Option 2: PDM with 680, 860, and 1040 cm cables
Option 3: PDM with three 1680 cm cables

16

150/175 kVA Modular PDU Technical Specification

990-4806

Power Distribution Modules continued
The following APC Power Distribution Modules (PDMs) are intended for and can be installed in the following
415V Modular PDUs:
APC Modular Power
Distribution Units
PDPM175G6H

APC Power Distribution Modules for 415V Modular PDUs
415V Power Distribution Modules have gray buss plates which match the gray 415V PDU backplane. These
PDMs require one (1) Modular PDU slot position.

# cords

Voltage

Amperage

(Qty) Circuit
Breakers

PDM1320IEC-3P-x

3

240V

20A

(3) 1P

PDM3520IEC309-xxx*

1

240V

20A

(3) 1P

PDM3540IEC309-xxx

1

240V

40A

(3) 1P

Module

(Qty)
Connector
(3) 3-wire IEC
309 20A
(1) 5-wire
IEC 309
(1) 5-wire
IEC 309

Notes:
Input frequency: 50/60Hz
Certifications: UL Listed
Cable rating of Power Distribution Modules: TC-ER, DP-1. Approved for under floor usage per NFPA
645.5(E) and 645.5(E)(3) when used in a designated IT Site as defined in NFPA Article 645, Information
Technology Equipment.
The PDM3520IEC309-xxx and PDM3540IEC309-xxx PDMs use a 5-wire IEC 309 connector with a 6
o'clock ground position.
Unless otherwise noted, 1-cord Power Distribution Modules are available with these cord lengths:
200, 260, 320, 380, 440, 500, 560, 620, 680, 740, 800, 860, 920, 980, 1040, 1680
Unless otherwise noted, all 3-cord Power Distribution Modules are available with these cord lengths:
Option 1: PDM with 260, 380, and 500 cm cables
Option 2: PDM with 680, 860, and 1040 cm cables
Option 3: PDM with three 1680 cm cables
*PDM3520IEC309-xxx is also available with 80 and 140 cm cord lengths

990-4806

150/175 kVA Modular PDU Technical Specification

17

Seismic Kit
Seismic Kit for 300mm Symmetra PX 100, Symmetra PX 250/500,
and Modular PDU Frames

SYOPT600

Bottom Feed Side Cars
Compatible PDUs

SKU

Description

PDPM100SC

APC Symmetra PX 100kW Bottom Feed Side Car,
300mm

PDPM175G6H

PDPM150SC

APC 150KVA Modular PDU Bottom Feed Side
Car, 300mm

PDPM150G6F
PDPM150L6F

Shunt Trip
Square D shunt trip unit models for field installation:
S29384 for 24VAC
S29382 for 12VAC
S29390 for 24VDC
S29391 for 30VDC

Configuration Options
• StruxureWare Data Center Expert
• Network Manageable
• Seismic bracket kits available
• Optional Bottom Feed Side Car for bottom feed input/output

18

150/175 kVA Modular PDU Technical Specification

990-4806

Warranty
SCHNEIDER ELECTRIC IT CORPORATION
LIMITED FACTORY WARRANTY
Three Phase Power Products or Cooling Solutions One-Year Factory Warranty1
The limited warranty provided by Schneider Electric IT Corporation (SE IT) in this Statement of Limited
Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary
course of your business.

Terms of Warranty
SE IT warrants that the product shall be free from defects in materials and workmanship for a period of one
year from the date of product start-up when start-up is performed by SE IT authorized service personnel and
occurs within six months of The SE IT shipment date. This warranty covers repairing or replacing any
defective parts including on-site labor and travel. In the event that the product fails to meet the foregoing
warranty criteria, the warranty covers repairing or replacing defective parts at the sole discretion of SE IT for a
period of one year from the shipment date. For SE IT cooling solutions, this warranty does not cover circuit
breaker resetting, loss of refrigerant, consumables, or preventive maintenance items. Repair or replacement of
a defective product or part thereof does not extend the original warranty period. Any parts furnished under this
warranty may be new or factory-remanufactured.

Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation (herein referred to by “You” or
“Your”) for whom the SE IT product specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of SE IT.

Assignment of Warranties
SE IT will assign you any warranties which are made by manufacturers and suppliers of components of the SE
IT product and which are assignable. Any such warranties are assigned “AS IS” and SE IT makes no
representation as to the effectiveness or extent of such warranties, assumes no responsibility for any matters
which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to
such components.

Drawings, descriptions
SE IT warrants for the warranty period and on the terms of the warranty set forth herein that the SE IT product
will substantially conform to the descriptions contained in the SE IT Official Published Specifications or any
of the drawings certified and agreed to by contract with SE IT if applicable thereto (“Specifications”). It is
understood that the Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.

1 To

determine which factory warranty applies to the SE IT product you purchased, please consult the
factory warranties located on the SE IT web site: www.apc.com/products

990-4806

150/175 kVA Modular PDU Technical Specification

19

Exclusions
SE IT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the
product does not exist or was caused by end user or any third person misuse, negligence, improper installation
or testing. Further SE IT shall not be liable under the warranty for unauthorized attempts to repair or modify
wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive
atmosphere, repair, installation, start-up by non-SE IT designated personnel, a change in location or operating
use, exposure to the elements, Acts of God, fire, theft, or installation contrary to SE IT recommendations or
specifications or in any event if the SEIT serial number has been altered, defaced, or removed, or any other
cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE,
OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN
CONNECTION HEREWITH. SE IT DISCLAIMS ALL IMPLIED WARRANTIES OF
MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SE IT
EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, SE IT RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES
AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES.
THE WARRANTIES SET FORTH ABOVE CONSTITUTE SE IT SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SE IT WARRANTIES RUN
ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SE IT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE
FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING
OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES
ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY
OR WHETHER SE IT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SE IT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR
REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF
DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE. NO SALESMAN,
EMPLOYEE OR AGENT OF SE IT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS
WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY
AN SE IT OFFICER AND LEGAL DEPARTMENT.

Warranty Claims
Customers with warranty claims issues may access the SE IT worldwide customer support network through the
SE IT web site: support.apc.com. Select your country from the country selection pull-down menu. Open the
Support tab at the top of the web page to obtain contact information for customer support in your region.

20

150/175 kVA Modular PDU Technical Specification

990-4806

Worldwide Customer Support
Customer support is available at no charge via e-mail or telephone. Contact information is available at
www.apc.com/support/contact.

© 2013 Schneider Electric, APC and the APC logo are owned by Schneider Electric Industries S.A.S., or its affiliated
companies. All other trademarks are property of their respective owners.

990-4806

8/2013



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Creator Tool                    : FrameMaker 11.0.2
Modify Date                     : 2013:08:27 13:42:24-05:00
Create Date                     : 2013:08:27 13:34:20Z
Metadata Date                   : 2013:08:27 13:42:24-05:00
Format                          : application/pdf
Title                           : untitled
Producer                        : Acrobat Distiller 10.1.7 (Windows)
Document ID                     : uuid:78e0024e-25cc-45f3-a9bc-a5c49d304ced
Instance ID                     : uuid:e0fad004-77b2-4513-aa9c-b483273e2962
Page Mode                       : UseOutlines
Page Count                      : 26
Creator                         : FrameMaker 11.0.2
EXIF Metadata provided by EXIF.tools

Navigation menu