Onan UR Generator Manual Pub 900 0150
900-0150 Onan UR (25 to 180KW) Generator & Controls Service Manual (10-1978) 900-0150 Onan UR (25 to 180KW) Generator & Controls Service Manual (10-1978)
User Manual: Onan-UR-Generator-Manual-pub-900-0150 Onan
Open the PDF directly: View PDF .
Page Count: 81
Download | |
Open PDF In Browser | View PDF |
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x 17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print. Service Manual 2 5 t o I 8 0 kW Generators And Controls Troubleshooting and Test Procedures For Generators Regulator Controls 900-0150 10-78 Printed in U.SA Redistribution or publication of this document, by any means, is strictly prohibited. Safety Precautions The following symbols in this manual highlight conditions potentially dangerous to service personnel, or equipment. Read this manual carefully. Know when these conditions can exist. Then take necessary steps to protect personnel as well as equipment. This symbol is used throughout the I W A R N I N G 1 manual to warn of possible serious personal injury. This symbol refers t o possible equipment damage. PROTECT AGAINST MOVING PARTS Avoid moving parts of the unit. Avoid use of loose jackets, shirts or sleeves due to danger of becoming caught in moving parts. Make sure all nuts and bolts are secure. Keep power shields and guards in position. If you must make adjustments while the unit is running, use extreme caution around hot manifolds, moving parts, etc. Do not work on this equipment when mentally or physically fatigued. GUARD AGAINST ELECTRIC SHOCK Disconnect electric power before removing protective shields or touching electrical equipment. Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surfaces to be damp when handling electrical equipment. Disconnect batteries to prevent accidental engine start. Jewelry is a good conductor of electricity and should be removed before working on electrical equipment. Use extreme caution when working on electrical components. High voltages cause injury or death. Follow all state and local codes. To avoid possible personal injury or equipment damage, a qualified electrician or an authorized service representative must perform installation and all service. EXHAUST GAS IS DEADLY! Exhaust gases contain carbon monoxide, a poisonous gas that might cause unconsciousnessand death. It is an odorless and colorless gas formed during combustion of hydrocarbon fuels. Symptoms of carbon monoxide poisoning are: Dizziness Headache Weakness and Sleepiness Vomiting Muscular Twitching Throbbing in Temples If you experience any of these symptoms, get out into fresh air immediately, shut down the unit and do not use until it has been inspected.. Thebest protection agalnst carbon monoxide inhalation Is proper installallon and regular, frequent visual and audible inspections of the complete exhaust system. If you notice a change in the sound or appearanceof exhaust system, shut the unit down immediately and have it inspected and repaired at once by a competent mechanlc. Redistribution or publication of this document, by any means, is strictly prohibited. Y . GENERATORS AND CONTROLS 25 kW 180 kW . - TABLE OF CONTENTS ' PAGE ' Introduction .......................................... :................ 2 Generator - Section I ................................................. 5 Question and Answer Troubleshooting Guides. .......................... 8 Adjustments and Procedures ............................................ 16 Generator - Section II ............................................... 26 Question and Answer Troubleshooting Guides. ......................... 27 35 Adjustments and Procedures ........................................... Index of Generator Adjustments and Procedures. ....................... 38 Control Section 111 ................................................. 39 Question and Answer Troubleshooting Guides. ......................... 40 Adjustments and Procedures .......................................... 51 Wiring Diagrams ..................................................... 53 . - ONAN RECOMMENDS THAT ALL SERVICE, INCLUDING INSTALLATION OF REPLACEMENT PARTS, BE PERFORMED BY QUALIFIED PERSONNEL. . I I I Redistribution or publication of this document, by any means, is strictly prohibited. INTRODUCTION FOREWORD ' , tion on later UR generator. Section 11 contains troubleshooting information for the later model UR generator where the exciter diode rectifier assembly has been relocated into the contrd panel. Refer to Table 1 for a description of t / : f . appropriate section for your generator. This manual provicds troubleshooting and repair information for ONAN series UR generators. It is intended to provide the maintenance technician, serviceman or Onan distributor with a logical procedure to enable him to systematically locate and 'repair malfunctions in the generator and control systems. This information is not applicable to the prime mover; refer to the engine manufacturer's manual. 2 . CONTROLS - S e c t i o n 111 c o n t a i ! $ s troubleshooting guides and procedures lor testing and repairing the system controls, P description of the components and an analysiz' ti+ the module circuitry is included. Repair information is not extensive because the plugin solid-state printed circuit modules lend themselves more to replacement than repair. ONAN does not recommend repair of the printed circuit module, except at the factory and has initiated a returdexchange service, obtainable through distributors, whereby faulty modules can be returned and exchanged for good units. For more information, contact your distributororthe ONAN service department. TEST EQUIPMENT Most of the tests outlined in this manual can be performed with an AC-DC multimeter such as a Simpson 260 VOM. Application of meters or high heat soldering Other suggested test instruments are - irons to modules by other than qualified personnel can result in unnecessary and expensive damage. ONAN multitester Part No. 420-0303 Wheatstone or Kelvin bridge This rnanual is arranged as follows: - Section I contains general specifications on the U R generator, troubleshooting guides and procedures for testing and repairing of the early UR generator with VR22 exciter regulator and general informa- i . GENERATOR Exercise care when purchasing a foreign made VOM. Some units deliver +9VDC, others, +22VDC to the circuit under test on R x 1 scale. Maximum recommended voltage is +l.SVDC. Damage to solid state devices can result from excessive voltage application. I GENERATING SET MALFUNCTION I GENERATOR FAILS SEE GENERATOR SECTION I OR II ENGINE FAILS SEE ENGINE SERVICE MANUAL CONTROL FAILS CONTROL SECTION Ill 2 Redistribution or publication of this document, by any means, is strictly prohibited. I ' TABLE 1. GENERATOR SPECIFICATION BREAKDOWN Section 1 Spec A kW Model 25.0 EK 30.0 EK Penn EK 25.0 DDA 30.0 DDB 30.0 DEH 25.0 MDEH 30.0 MDEH Penn DEH 37.5 EM 45.0 EM Penn EM 37.5 DEF 45.0 DEF Penn DEF 37.5 DYJ 45.0 DYJ 40.0 DDB 50.0 DDB 40.0 DEG 50.0 DEG Penn DEG 40.0 MDEG 50.0 MDEG 45.0 KB 55.0 KB Penn KB 50.0 DYA 60.0 DYA Penn DYA 55.0 EN 70.0 EN Frequency 50 Hz 60 Hz 50 Hz 60 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 60 50 60 Hz Hz Hz Hz 50 Hz 60 Hz 60 Hz 60 Hz E D E - D D C E E D E H F G - G E F F E R P Q E C D - Section 2 Begin Spec kW Model 55.0 KB 55.0 KB "enn KB 50.0 DYC 75.0 DYC 30.0 DYC 100.0 DYC 'enn DYC 70.0 KR 35.0 KR Penn KR 75.0 DYC 30.0 DYC 30.0 DYD 100.0 DYD Penn DYD 35.0 WA 115.0 WA 100.0 DYD 125.0 DYD Penn DYD 115.0 WE 140.0 WE 125.0 WE 150.0 WE 125.0 DYG 150.0 DYG Penn DYG 130.0 DFE 155.0 DFE Penn DFE 140.0 WB 170.0 WB 145.0 DYG 175.0 DYG Penn DYG 150.0 DFE 180.0 DFE Penn DFE F F F A A G G G G F F F J J J A A A A H H H H H S S S F F F A A Frequency 1 Section 1 Spec A ThN R P 50 Hz 60 Hz Q 50 Hz 60 Hz 50Hz 60 Hz D B - ' j 50 Hz 60 Hz c R P Q 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz60'HZ 50 Hz 60 Hz D B C A B H G C A B B B B B C A B - - 50 Hz 60 Hz 50 Hz 60 Hz K J C A B 50 Hz 60 Hz - - ' Section 2 Begin Spec S S S E E G G 'E S S S E E . D D D J J D D D - D D D H H H L L D D D H H H 3 Redistribution or publication of this document, by any means, is strictly prohibited. UR G’ENERATOR VOLTAGE/CURRENT OPTIONS RATING HE - I_ :ode :ode 1-PHASE STANDARD a 2K g - g @@ 15 515 - 4 1-PHASE SPE - 50 60 - 0 L-- 0 - - - c c 0 0 - -g -g - 3-PHASE - 0 0 @ - kVA 25.0 31.25 30.0 37.50 37.5 46.80 X 213 204 142 135 130 123 123 118 71 40.0 50.0 X 227 217 152 144 139 131 131 126 76 45.0 56.25 X X 256 245 234 171 162 156 148 148 141 135 135 50.0 62.5 X X 284 272 260 190 180 173 164 164 157 150 150 55.0 68.75 X X 313 299 286 209 198 191 180 180 173 165 165 60.0 75.0 180 180 62.5 78.13 65.0 81.25 195 195 70.0 87.5 X X 398 380 365 266 253 243 230 230 220 210 210 133 75.0 93.75 X X 426 408 391 285 271 260 246 246 235 226 226 455 435 304 289 262 262 251 80.0 100.0 85.0 106.25 142 X 136 156 X 95 234 355 X 340 X 237 X 443 X 469 112,5 95.0 118.75 X 100.0 125.0 X X 115.0 143.75 X X 540 516 568 543 . 82 226 217 78 205 205 279 295 312 150.0 125.0 156.25 X 130.0 162.50 X 140.0 175.0 X 256 256 27 1 271 343 330 312 312 298 521 380 361 347 328 328 314 301 599 437 415 399 377 377 361 346 X X E E 43 41 49 68 65 62 72 69 66 85 81 78 95 90 87 104 99 k y 600 45 36 74 68 54 82 75 60 95 90 83 66 104 98 90 72 108 103 113 107 98 78 126 121 115 105 84 142 135 130 123 113 90 152 ’ 144 139 131 147 139 128 102 135 108 113 156 148 180 171 165 156 301 190 180 173 164 150. 120 346 218 207 200 189 173 138 376 237 226 217 205 188 150 247 235 226 213 266 253 243 230 210 168 275 262 252 238 285 271 - . 625 120.0 E . 52 119 361 45 90 196 213 295 47 90 197 226 278 82 98 208 339 X E7 104 313 X 90.0 90 156 - c g - g - g - g - - - - g - - kW - - - - - 475 451 434 410 410 392 494 469 451 426 426 408 532 505 486 459 459 439 551 523 503 476 476 455 570 541 520 492 492 471 376 42 1 421 145.0 181.25 X 150.0 187.5 X 451 451 260 246 226 180 155.0 193.75 X 538 508 466 466 269 254 233 186 170.0 212.5 X 590 558 51 1 51 1 295 279 256 204 175.0 218.75 X 607 574 526 526 304 287 263 210 180.0. 225.25 X 625 591 542 542 313 296 271 - 0- o:, X - @ - 50- and 60 Hz HZ only. @ - 60 Hz only. @- . . . . . - Not Reconnectible. . . .. .. - . 217 GENERATOR v - SECTION I GENERAL COMPONENT LOCATION There are two generator designs used on the UR series. They are basically the same except for the method of field excitation. To gain access to generator, remove grille section below control box. , 1 . Exciter-regulator chassis assembly VR22 mounts on the rear portion of the generator; SCR’s (silicon controlled rectifiers) and diodes are easily accessible for testing. See Figures 1-3. 2. On static-excited generators, brush”es attach to the brush rig inside of end bell housing; inspect through large access holes in the end bell. See Figure 1. 3. On brushless models, rotating exciter assembly mounts directly behind exciter-regulator chassis assembly with all diodes accessible for servicing. See Figure 2. 4. Voltage-regulator PC Board VR21 (Printed Circuit Board) mounts inside the control box on the rear panel (left side); turn 114 turn fasteners o,n front of control box to gain access. See Figure 4. The Static Exciter (brush type) design uses a brush rig and collector rings for field excitation. This design was used on some of the earlier models within the range of 25 KW - 90 KW. The Brushlessdesign uses a rotating rectifier exciter assembly in place of the brush rig for field excitation. The brushless design is standard on all models from 25 KW - 175 KW. Unless otherwise specified, the tests in this section apply to both designs. V R -22 EXCITER REGULATOR CHASSIS ASSEMBLY END B ELL AC - L STATOR OUTPUT ‘\-- 208-240 VOLTS AC RESIDUAL MAGNETISM IN R O T O R S T A R T S PROCESS , & ~ SOLID STATE 4 N D VOLTAGE REGULATOR . .TOR R E V O L V I N G FIELD OVERSPEED S W I T C H QENERATOR E N D VIEW (QRILLE REMOVED) EXCITATION S C H E M A T I C FIGURE 1. STATIC EXCITER DESIGN 5 Redistribution or publication of this document, by any means, is strictly prohibited. A LT E R N A T 0 R EXClT E R- REGULATO R CHASSIS ASSEMBLY iTATOR FENDBELL . 208-240 VOLTS AC EXCITER CIRCUIT I BREAKER FIELD w EXCITER ARMATURE VOLTAGE R E(3U L A T O R I QENERATOR E N D VIEW (QRILLE REMOVED) ~~~ EXCITATION S C H E M A T I C , ! t CHECK T H E S E S I N G L E L E A D RECTIFIERS ACCORDING T O P R O C E D U R E "E" FIGURE 3. TOP VIEW OF EXCITER-REGULATOR CHASSIS ASSEMBLY ! V R21 VOLTAGE REGULATOR P R I N T E D C I R C U I T BOARD i 'FIGURE 4. VOLTAGE REGULATOR PRINTED CIRCUIT BOARD LOCATION 6 , Redistribution or publication of this document, by any means, is strictly prohibited. VISUAL INSPECTION I I Before proceeding with the troubleshooting on the following pages, a few simple checks can be made which could directly indicate the cause'of trouble. 1. Always be sure that connection of generator leads is correct. Whenever leads are reconnected for a different voltage, check the output with an independent voltmeter. Do not use the control panel meter since it could indicate that the voltage is correct even i f connection is wrong. 2. Visually inspect the voltage regulator printed circuit board assembly (VR21) in the control box for burned components, broken wires, loose connections, dust, dirt or moisture. If dirty, clean with a suitable solvent and compressed air. 3. Visually inspect the exciter-regulator chassis assembly (VR22) for burned components, broken wires, loose connections, carbon tracks caused by arcing between parts or between parts and ground. Also check for shorted paths between terminals caused by dust, dirt and moisture. 4. Large banks of SCR (Silicon Controlled Rectifier) regulated loads can cause the generator voltage to increase as load is applied. If such loads exist, and the voltage increased more than 5 or lo%, consult the factory; an additional filter is available for the regulator circuit to correct the situation. THE QUESTION AND ANSWER TROUBLESHOOTING GUIDES BEGINNING ON PAGE 8 GIVE A STEP-BY-STEP PROCEDURE FOR CHECKING THE GENERATOR. THE FLOW-CHART TROUBLESHOOTING GUIDES ARE GIVEN AS A GENERAL GUIDE TO RESOLVE VARIOUS GENERATOR PROBLEMS. ALL CHARTS REFER TO PROCEDURESSHOWN AT THE END OF THIS SECTION. . PRIOR TO ANY TROUBLESHOOTING, CHECK ALL MODIFICATIONS, REPAIRS, REPLACEMENTS, ETC.. PERFORMED SINCE LAST SATISFACTORY OPERATION OF SET. 7 Redistribution or publication of this document, by any means, is strictly prohibited. QUESTION AND ANSWER TROUBLESHOOTING GUIDE To correct a particular problem, answer the question either “yes” or “no,” then proceed to the next step in . given whichever column question was answered. Procedures A thru P follow the troubleshooting guide. ‘LiM I ~~ TABLE A. NO OUTPUT VOLTAGE - ENGINE RUNNING YES 1. Is circuit breaker on the meter panel in the “on” position? 2. Switch circuit breaker to the “on” position. Does AC voltage build up? NOTE: If voltage builds up, but is high, low or unstable, or causes the circuit breaker on the meter panel to trip, refer to Table “B,” “C’ or “D” of the troubleshooting guide. NO PROCEDURt ‘ 1 I 3 I I 3. Is AC voltage at terminals 1 and 2, on VR21 voltage regulator printed circuit board and at terminals 9 and 10 on VR22 exciterregulator chassis assembly 5 to 10 volts? ~~ 4. 5. 6. 7. 9. 10. 11. C Check continuity of wires and connections between terminal 1 on VR21 printed circuit board and terminal 9 on VR22 chassis assembly; and between terminal 2 on VR21 printed circuit board . and terminal 10 on VR22 chassis assembly. Is there continuity between these connections? 10 Check for broken wires and loose connections on VR22 exciterregulator chassis assembly. Replace or repair any that are defective and clean all dust, dirt and other foreign material from the assembly. Does AC voltage now build up? 6 Is DC voltage at terminals 4 and 5 on VR22 exciterregulator chassis assembly 5 to 10 volts? I l3 , Are diodes CR1, CR2 and CR3 on VR22 exciter-regulator chassis assembly OK? 8. 5 ~~ Are SCR’s Q4 and Q5 on VR22 exciter-regulator chassis assembly OK? 8 F 9 The trouble is probably caused by a defective component on the voltage regulator printed circuit board. REPLACE VR21 PRINTED CIRCUIT BOARD (see Figure 4). With the circuit breaker on the meter panel in the “off” position, is AC voltage at terminals 62 and 63 (on terminal board TB21 on the left side of control box) 5 to 10 volts? With the circuit breaker on the meter panel in the “off” position, flash the exciter field. Is AC voltage at terminals 62 and 63 now 5 to 10 volts? 11 12 13 B 8 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE A. NO OUTPUT VOLTAGE - ENGINE RUNNING (continued) YES NO PROCEDURE Turn circuit breaker on the meter panel t o the “on” position. Does AC output voltage build up? NOTE: If voltage builds up, but is high, low or unstable, or causes circuit breakerto trip. refer to table “B.” “C” or “D” of this troubleshooting guide. 17 Is brushless exciter stator winding OK? With a jumper wire connected across the terminals of the circuit breaker on the meter panel, does voltage build up? NOTE: If voltage does build up, the circuit breaker CB21 is defective and MUST BE REPLACED. ~ ~- Is 11 commutating reactor mounted on the back side of VR22 exciter-regulator chassis assembly OK? D Check continuity of wires and connections between 1821 terminal 62 on left side of control box and terminal 1 on VR21 printed circuit board. Also check between TB21 terminal 63 on the left side of control box and terminal 2 on VR21 printed circuit board. Are rotating diodes CR1,CR2, CR3,CR4,CR5 and CR6 on brushless exciter rotor OK? 18 E Is generator field winding OK? 19 G Is brushless exciter rotor winding OK? 20 J H Are generator stator windings OK? 9 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE A. SYNOPSIS BRUSHES OR LOOSE BRUSH CB2l CIRCUIT BREAKER ON METER PANEL I N "OFF" POSITION (RESET) ++ LOSS OF RESIDUAL VOLTAGE (FLASH NO AC POWER TO EXCITER FIELD) FAULT I N GENERATOR FIELD WINDING DEFECTIVE COMPONENT ON REGULATOR PC BOARD (VR21) COMPONENT VOLTAGE REGULATOR CHASSIS ASSEMBLY nI -I- DEFECTIVE CIRCUIT BREAKER ON METER PANEL A -I BUILD-UP RELAY, K1 Q4 OR Q5 1 CR8 OR CR9 OPEN DEFECTIVE DIODE CR1 R l , R2 OR R3 /E\ OPEN OPEN LEAD PC BOARD NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. * TERM"ALS 1 OR 2 - Check SCR's, Q4 and Q5 on VR22 voltage regulator chassis assembly and replace (if defective) before repairing or replacing VR21 voltage regulator printed circuit board. ** - Static excited generators only. __ ... . -.. FAULTY ROTATlNG DIODE ON BRUSHLESS EXCITER P I TERMINAL 1, 2,4,5 FAULT IN BRUSHLESS EXCITER ROTOR OR STATOR WINDING i L t TABLE B. OUTPUT VOLTAGE BUILDS UP BUT IS UNSTABLE ENGINE RUNNING OK ITEM NO. I I I 2. Does adjustment of R26* (damping control pot) on VR21 printed circuit board result in stable generator voltage? 1 8 I I : Are there any loose or broken wires or connections at VR21 printed circuit board terminals? I 3. I The trouble is probably caused by a defective component on VR21 voltage regulator printed circuit board. REPLACE VR21 PRINTED CIRCUIT BOARD (see Figure 4). YES NO PROCEDURE 7: i I - R26 is used on brushless generators only. TABLE B. SYNOPSIS ! UNSTABLE OUTPUT VOLTAGE DEFECTIVE COMPONENT ON (VR21) VOLTAGE REGULATOR PRINTED CIRCUIT BOARD BROKEN WIRES OR LOOSE CONNECTIONS AT (VR21) VOLTAGE REGULATOR PRINTED CIRCUIT BOARD TERMINALS INCORRECT SETTING OF R26 POT ON (VR21) PRINTED CIRCUIT BOARD (BRUSHLESS ONLY) I C6. C7, R14 OR R1S OPEN C11, C12, R27 OR R28 OPEN NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. Redistribution or publication of this document, by any means, is strictly prohibited. F - TABLE C. OUTPUT BUILDS UP BUT IS HIGH OR LOW ENGINE RUNNING OK - YES NO PROCEDURE Does adjustment of R21 "Voltage Adjust" knob on the meter panel result in correct voltage? - 2 Does adjustment of R l b potentiometer on VR21 printed circuit board result in correct voltage? - 3 P Is correct voltage reference transformer tap on TB21 being used? 4 - L Are generator output leads properly connected? 5 - L I - 5. TABLE C. SYNOPSIS TOO HIGH O R I I INCORRECT REFERENCE TRANSFORMER TAP ON T21 INCORRECT SETTING OF VOLTAGE ADJUST POT (R21) ON METER PANEL I INCORRECT SETTING OF VOLTAGE ADJUST POT (R18) ON VR21 PC BOARD I I I DEFECTIVE COMPONENT ON DEFECTIVE COMPONENT ON REGULATOR CHASSIS ASSEMBLY (VR22) REGULATOR PC BOARD (VR21) . CONNECTION AT TERMINALS 3 , 4 , . I I ! .I -. . . .. I NOTE Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. 12 Redistribution or publication of this document, by any means, is strictly prohibited. I NO: ITEM TABLE D. GENERATOR VOLTAGE BUILDS UP BUT CAUSES THE CIRCUIT BREAKER ON CONTROL PANEL TO TRIP. ENGINE RUNNING OK. Does AC output voltage build up to 150% or more of rated voltage before CB21 circuit breaker trips? 1, . Are 2. there any loose or broken terminals or connections at VR21 voltage regulator printed circuit board terminals? 3. Is diode CR3 on center heat sink of VR22 exciter-regulator chassis assembly OK? 4. Are voltage regulator transformer (T21) windings and connections OK? ~ ~ 5. Are stator leads connected properly? 6. The trouble is probably caused by a defective component on VR21 voltage regulator printed circuit board. REPLACE VR21 PRINTED CIRCUIT BOARD (see Figure 4). I Does AC output voltage build up to rated voltage or less before tripping CB21 circuit breaker on meter panel? Are rotating diodes CR1, CR2, CR3, CR4, CR5 and CR6 on brushless exciter rotor OK? 8. 9. . Is brushless exciter stator winding OK? 10.. Is generator field winding OK? 11. Is brushless exciter rotor winding OK? DEFECTIVE ROTATING DIODE CR1, CR2, CR3, CR4, CR5 OR CR6 ON EXCITER ROTOR l-l FAULT IN EXCITER ROTOR OR STATOR WINDING FAULT IN GENERATOR MAIN FIELD WINDING A NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. 13 Redistribution or publication of this document, by any means, is strictly prohibited. ITEM TABLE E. UNBALANCED GENERATOR TERMINAL VOLTAGE -. NO. - YES _________ ~~ ~ 2. Are generator leads properly connected and/or grounded? 3 - 3. Is continuity of generator stator windings OK? - - 4. * I' , Check for ground faults in load. ji H I 51--1 1-14 Is grounding procedure of generator and load correct? ~~~ 5. PROCEDURE I*141 Remove load from 'generator terminals. Are genefator'terminal voltages still unbalanced? 1.. NO I NOTE: Unbalanced voltages of up to 5 percent will occur if unbalanced loads are applied to the generator terminals. \ TABLE E. SYNOPSIS UNBALANCED TERMINAL VOLTAGES * INCORRECT RECONNECTION OR GROUNDING OF GENERATOR LEADS INCORRECT GROUNDING OF LOAD OR GROUND FAULT IN LOAD I ' FAULTY GENERATOR STATOR WINDING , t NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. 14 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE E. SYNOPSIS I VOLTAGE 150% [ ; I I MORE THAN RATED I rI 1 DEFECTIVE COMPONENT ON VOLTAGE REGULATOR CHASSIS ASSEMBLY (VR22) DEFECTIVE COMPONENT ON VOLTAGE REGULATOfi PRINTED CIRCUIT BOARD (VR21) I OPEN TRANSFORMER (T21) WINDING OPEN WIRE OR CONNECTION AT VOLTAGE REGULATOR CHASSIS ASSEMBLY (VR22) TERMINALS 4,5 OR 6 OPEN WIRE OR CONNECTION AT PRINTED CIRCUIT BOARD (VR21) TERMINALS 5,6, 9,10, 11 OR 12 CYCLING BUILD-UP * 1 OPEN LEAD AT (VR21) PRINTED CIRCUIT BOARD TERMINALS 1, 2, 5, 7 OR 8 OPEN IN R21 VOLTAGE ADJUST POT ON METER PANEL I DEFECTIVE COMPONENT ON VR21 PRINTED CIRCUIT BOARD L < OPEN IN R18 VOLTAGE ADJUST POT ON VR21 PRINTED CIRCUIT BOARD NOTE Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. * - Generator voltage builds up. then collapses. builds up. etc. Redistribution or publication of this document, by any means, is strictly prohibited. I ADJUSTMENTS AND PROCEDURES BRUSHES ment. Do not use a substitute brush that may look identical but may have entirely different electrical characteristics. Be sure to install the brush SO that the short side of its taper is toward the spring and its bracket. See Figures 5 and 6. When brushes wear to approximately 5/8 inch or when wear extends into the stamped Onan part number, replace brushes. Do not attempt to remove the brush without first removing its spring and brackets. Never bend a spring back over its bracket doing so will put a kink in it and require its replace- i I N S T A L L B R U S H E S W I T H BEVELED TOP S L A N T I N G D O W N TOWARD S P R I N G HOLDER-, REPLACE BEFORE BRUSH WEARS TO THIS POINT TO REMOVE BRUSH SPRING,PRESS SPRl NG HOLDER DOWN A N D OUT A S SHOWN IN BROKEN LINES. FIGURE 5. FIGURE 6. BRUSH REPLACEMENT FLASHING THE FIELD (No Voltage) 1 . . If output voltage will not build up, it may be necessary '. to flash the field to restore residual masnetism. 1. Remove end grille to obtain access to'exciterregulator chassis assembly:. 2. Use a six volt dry cell (lantern) battery with a 12 amp 300 volt diode as shown in' Figure 7. This prevents current flow from exciter circuit to battery when voltage builds up. If a lantern battery is not available, a 12 volt automotive (generator set) battery can be used by installing a 20-ohm 2 . tJ BRUSH REMOVAL .watt resistor in series with diode; or a 24 volt automotive (generatorset) battery can be used by increasing the resistor value to 40-ohms. 3. After starting the set, touch the positive (+) lead to TB5 and the negative (-) lead to TB4; hold on terminals just long enough forvoltage to build up. ' ' Do not keep excitation circuitry connected longer than 5-seconds or damage may occur to the exciter regulator. Be cautiouswhen working on agenerator that is running. High voltages aye present. CHASSIS ASS T O BUILD UP. FIGURE 7. FLASHING THE FIELD 16 Redistribution or publication of this document, by any means, is strictly prohibited. I Resistance between coils (e.g., 1-4) or from any terminai to reactor frame should be infinity. CCI NO AC POWER TO EXCITER If any of the above conditions are not met, install a new reactor. Residual should be checked before the circuit breaker; the best place to check it is at the five leads 61 through 65 coming directly out of the stator. The combinationof leadsshouldbechosen by the wiring configuration of the stator, Le., 120/240 Delta, 120/208 ParallelWye. 277/430Series Wye. After checking residual,proceed to VR21 PC board arid then check the circuit breaker CB21. TESTING DIODES If residual voltage is present, check AC voltage at terminals 1 and 2 on VR21 voltage regulator printed circuit board. Voltage should be 5-10 volts. The AC voltage at terminals 9 and 10 on VR22 exciterregulator chassis assembly should be the same (5 to 10 volts). If not, check continuity between these points. If voltage is low, check L1 reactor. On both brushless and brush type generators. three diodes mount on the center heat sink of the exciterregulator chassis assembly. They are labeled CR1, CR2 and CR3 as shown in Figure 3. On brushless generators, six diodes mount on the rotating exciter assembly as shown in Figure 2. These six diodes are labeled CR1. CR2, CR3, CR4, CR5 and CR6. Test diodes as follows: 1. Disconnect one diode at a time. Test that diode and reconnect lead before proceeding to the next one. 2. Use an accurate ohmmeter to check the resistance of the diode. Connect one lead to the top of the diode and the other lead to the heat sink. Observe reading. 3. Now reverse leads and again observe reading. A good diode should have a higher reading in one direction than the other. I f both readingsare high, or if both readings are low, diode is defective and must be replaced with a new, identical part. TESTING L1 REACTOR The L1 reactor mounts on the rear of VR22 exciterregulator chassis assembly. Terminals are marked 1, 2, 3 and 4. 3 h 4 Coils 1-2 and 3-4 are wound on the same iron core. Resistance between 1-2 and 3-4 should be .0544 and .0614-ohms f 1O0/o respectively (brush type generators) . m Excessive dust or dirt on diodes and other componentswill causeoverheatingand eventual failure. Keep these assemblies clean! CAUTION LEAD LEAD GOOD DIODE WILL HAVE HIGH RESISTANCE READING I N ONE DIRECTION AND LOW READING WHEN OHMMETER LEADS ARE REVERSED. FIGURE 8. TESTING DIODES 17 Redistribution or publication of this document, by any means, is strictly prohibited. 0 H MMETER SHORT BETWEEN SATE AND ANODE CATHODE ANODE FIGURE 9. TESTING SCR’s - FIGURE 10. TESTING SCR’s [FI FIGURE 11. TESTING SCR’s REPLACING Diodes) TESTING SCR’s RECTIFIERS (SCR’s and 1. Unsolder leadwires from terminals. 2. Use proper size wrenches to hold the body while removing the nut. 3. Push the rectifier free of its mounting hole in the heat sink. 4. Insert new rectifier into its mounting hole in the heat sink. Using nut and washer provided, secure rectifier to heat ,sink. 5. .Torque the two large diodes on the center heat sink of exciter-regulator chassis assembly to 2025 in. Ib. 6. Torque the small diode on center heat sink of exciter-regulator chassis assemb.ly to 12-15 in. Ib. 7. Torque SCR’s o n outer heat sinks-to 20-25 in. Ib. 8. On brushless generators, torque diodes on rotating exciter assembly to 15 in: Ib. 9. Solder leadwires to new rectifiers. SCR’s mount on the outer heat sinks of the exciterregulator chassis assembly. They are labeled Q4 and Q5 as shown in Figure 3. 1. Remove the leads from both SCR’s. 2. Determine polarity of ohmmeter leads. Connect the ohmmeter leads to the anode and cathode as shpwn in Figure 9. Use the high scale on the ohmmeter. The resistance should be 1 megohm or greater. The cathode is the longer lead, the gate is the shorter lead. The anode is the threaded stud. 3. Reverse the leads as shown in Figure 10. The resistance again should be 1 megohm or greater. 4. With the leads connected as in Step 3, and using the low scale on the ohmmeter, short the gate to the anode as shown in Figure 11. The resistance should drop to a low value. 5. Remove the short between the anode and the gate. The resistance should remain at the same low value. Use a 40 watt soldering iron. Hold a needlenose pliers between rectifier and soldering point to prevent destructive heating. Excessive heat on these components will destroy them. 18 Redistribution or publication of this document, by any means, is strictly prohibited. TESTING GENERATOR ROTOR Testing for Grounds: Use an ohmmeter (R x 100 scale'); measure as follows: Brush Type - from each slip ring to the rotor shaft. Brushless Type - disconnect F1 and F2 rotor leads from the rotating diodes; measure between either lead and the rotor shaft. A reading of less than infinity indicates a ground. See Figure 12. C O N T A C T ONE P R O D TO ONE SLIP RING AND T H E OTHER P R O D T O T H E SECOND SLIP RING. 0 HM M ETER BRUSH DESIGN C O N T A C T ONE P R O D TO EACH O F THE SLIP RINGS AND T H E OTHER PROD T O THE R O T O R SHAFT. IF ROTOR IS G O O D THERE S H O U L D BE NO READING O N OHMMETER. C O N T A C T O N E P R O D TO ONE FIELD LEAD AND T H E SECOND P R O D T O THE OTHER FIELD LEAD OHMMETER FIGURE 13. TESTING ROTOR FOR AN OPEN CIRCUIT TABLE 3. RESISTANCE VALUES FOR ROTORS KW RATING I I 1 50HERTZ 25.0 C O N T A C T ONE P R O D TO EACH O F THE FIELD L E A D S AND T H E OTHER PROD T O THE ROTOR SHAFT. IF ROTOR IS G O O D ' T H E R E S H O U L D BE N O READING ON OHMMETER FIGURE 12. 37.0 40.0 45.0 50.0 55.0 60.0 70.0 75.0 80.0 95.0 1 10.0 1 1 5.0 125.0 140.0 145.0 TESTING ROTOR FOR GROUNDS Testing for an Open Circuit: On brush type generators, check for an open circuit by measuring resistance in the windings. Check between the two slip rings as shown in Figure 13. On brushless generators, disconnect and test between F1 and F2 leads as shown in Figure 13. Resistance values given in Table 3 apply to both brushless and brush type generator rotors. 60HERTZ 30.0 40.0 45.0 50.0 55.0 55.0 60.0 65.0 75.0 85.0 90.0 100.0 115.0 125.0 140.0 150.0 170.0 175.0 RESISTANCE IN OHMS FROM 3.32 2.49 2.49 2.49 2.76 2.76 3.02 3.02 3.16 2.76 2.76 3.19 3.26 3.96 3.96 3.09 3.42 3.42 TO , 4.06 3.05 3.05 3.05 3.38 3.38 3.70 3.70 3.86 3.38 3.38 3.90 3.99 4.40 4.40 3.78 4.18 4.18 All resistances should be within the values specified at 20°C (68"F). This includes readings between slip rings on static excited rotors and between field leads (with rectifiers disconnected) on brushless rotors. Use Wheatstone Bridge for testing. Replace the rotor if it is grounded or has an open or short. 19 Redistribution or publication of this document, by any means, is strictly prohibited. TESTING GENERATOR STATOR FROM KELVIN BRIDGE Testing for Grounds: Connect all stator output leads (Tl-T12) together. Use an ohmmeter set on the R x 100 scale and measure the insulation resistance between these windings and the stator frame. A reading of less than infinity indicates a ground. Field circuit breaker can be either “ON” or “OFF”. ! Testing for Shorts: To check for shorts between individual windings first refer to Figure 18 to determine individual coil lead wires (Tl-T4, T7-Tl0, etc.) Connect one lead of an ohmmeter (RX100 scale) to one of the stator windings and the other ohmmeter lead to all other stator leads connected together. A reading of less than infinity indicates a short. Repeat until all stator coils have been tested in this manner. i Coil Resistances: Measure resistance of windings using a Wheatstone or Kelvin bridge meter. SeeTable 4 and Figure 14. If any windings are shorted, open or grounded, replace the stator assembly. Before replacing the assembly, check the leads for broken wires or damaged insulation. FIGURE 14. TESTING STATOR WINDINGS Stator output leads T4, T7, T8, T9 and T10 are interconnected (within the stator) to five stranded (#lo aircraft) control wires. These wires are labeled 4,7,8,9 and 10 respectively and terminate at TB2.1 (terminals 61-65). TABLE 4. .RESISTANCE VALUES FOR STATORS* VOLTAGE CODE (Resistance in Ohms) KW R TlNG I I 50 HERTZ 6O.HERTZ 25.0 30.0 40.0 45.0 50.0 55.0 ’ 37.0 40.0 ’ ,450 50.0 55.0 60.0 70.0 75.0 80.0 95.0 110.0 115.0 125.0 140.0 145.0 55.0 60.0 65.0 75.0 85;O 90.0 100.0 115.0 125.0 140.0 150.0 170.0 175.0 I 15 0.116 0.047 0.047 0.047 0.028 0.038 0.028 0.028 0.022 0.019 0.019 0.015 0.012 0.009 0.009 0.0075 0.0059 0.0059 - I 9x 3 0.425 - 0.520 0.141 0.058 0.058 0.058 0.035 0.047 0.035 0.035 0.027 0.024 0.024 0.018 0.015 0.011 0:Oll 0.0092 0.0072 0.0072 . 0.193 0.193 - 0.236 0.236. . 0.052 0.047 0.047 - 0.063 0.058 0.058 0.156 - 0.191 0.113 - 0.138 0.113 - 0.138 -6.089 - 0.108 0.072 - 0.089 0.072 - 0.089 0.054 - 0.067 0.045 - 0.055 0.039 - 0.048 0.039 - 0.048’ 0.027 - 0.033 0.018 - 0.023 0.018 - 0.023 AI: r’(?sislancesshould be within the values shown at 20°C (68’ F). Use an accurate instrument such as a Kelvin Bridge for this test. Test between the following coil leads: T1-T4 17-T 10 T3-T6 T9-Tl2 T2-T5 T8-Tl1 20 Redistribution or publication of this document, by any means, is strictly prohibited. . Testing Winding Resistance: Measure coil resistance between leads F1 and F2 with an ohmmeter (scale Rx 1). Resistance should be17.82 to 21.78ohmsat 20°C (68°F). See Figure 16A. IJI TESTING EXCITER ROTOR (Armature) ! Testing for Grounds: Remove diodes CR1, CR2, CR3, CR4, CR5, and CR6 from diode heat sink assemblies. Using an ohmmeter (R x 100 scale) measure insulation resistance between any of the leads and the laminations (exclude the diodes from the test circuit). A reading of less than infinity indicates a ground. Testing Winding Resistance: Using a Wheatstone or Kelvin bridge meter, measure resistance between leads pairs T1-T2, T2-T3 and Ti-13. Resistance should be 0.464 to 0.567 ohms at 20°C (68°F). See Figure 15. FIGURE 16A. TESTING EXCITER FIELD RECONNECTION Figure 18 shows reconnection possibilities forthe UR series generators. When reconnecting for a different voltage, be sure to also reconnect lead from terminal 63 (inside control box) to either H3, H4, H50rH6.See Figures 17 and 18. FIGURE 15. TESTING EXCITER ARMATURE TESTING EXCITER STATOR Testing for Grounds: Using an ohmmeter (R x 100 scale), measure the insulation resistance between either lead F1 or F2 and the laminations. A reading of less than infinity indicates a ground. See Figure 16. (W12 WIRE) CONNECT LOOSE W I R E F R O M TERMINAL #63 T O E I T H E R H3.H4.H5 O R H6 D E P E N D I N G ' O N V O L T A G E SELECTED. FIGURE 17. CONNECTING LEAD FROM TERMINAL 63 FIGURE 16. TESTING EXCITER FIELD 21 Redistribution or publication of this document, by any means, is strictly prohibited. E, NAMEPLATE VOLTAGE CODE 9 X N A M E P L A T E VOLTAGE CODE 3 T1 + CONNECT L E A D FROM TERMINAL 63 TO H5 CONNECT LEAD FROM TERMINAL 63 10 H5 THIS D I A G R A M APPLIES TO 12 LEAD GENERATORS ONLY GENERATOR CONNECTION W I R I N G D I A G R A M 8'l SCHEMATIC DIAGRAM (WITH CURRENT TRANSFORMERS WHEN USED) / 11 LO 12 i LO IS 120/240 1 60 H5 115/230 1 50 H6 116220 1 5 0 H6 115 TI0 77 75 L2 LO 15 120/140 3 60 115/230 3 50 19 T 1 12 16 111 18112 14 L1 1s 17 T 3 110 L3 12 H5 H6 i1S T10 11 16 17 12 L1 LO 111 14 T 8 '73 L2 T12 T5 19 13 I I W 5 '7: 13 1 , . 4 16 I5 111 110 112" LO l7 12 T 8 13 19 L1 12 13 T I T 7 T4 12 T 8 15 T3T9 1 111 710 711 LO 79 L3 1101lt T12 98C2193 FIGURE 18. RECONNECTION DIAGRAM 22 Redistribution or publication of this document, by any means, is strictly prohibited. t i. 1 I il :! . . SENSITIVITY REFERENCE CIRCUIT UR series voltage regulators (VR21) can be set to either frequency sensitive or non-frequency sensitive reference. With a frequency sensitive reference, the output voltage of the generator will decrease in proportion to the frequency (Le., prime moverspeed). This decrease in output voltage will reduce the load on the prime mover, permitting it to return to rated voltage and frequency when overload is removed. A temporary overload with a non-frequency sensitive reference could cause a prime mover to reduce speed, then would require a further 50% to 60% load reduction to allow it to return to rated speed. This reference change is accomplished by soldering wire W1 to terminal E l for frequency sensitivity or to terminal E2 for non-frequency sensitive reference. See Figure 19. Unless requested otherwise by purchaser, Onan sets are connected at the factory to a frequency sensitive reference. TOP SIDE OF. VOLTAGE REGULATOR WHENMOUNTED UNSOLDER THIS WIRE FROM E I AND CONNECT TO E2 FOR A NONFREQUENCY SENSITIVE VOLTAGE REFERENCE CIRCUIT. - FIGURE 19. VR21 PRINTED CIRCUIT BOARD 23 Redistribution or publication of this document, by any means, is strictly prohibited. GENERATOR DISASSEMBLY , If generator testing determines that generator needs repair, remove and disassemble according to Figure '20 and the following instructions: 7. Using an overhead hoist and sling, slide the stator assembly off the rotor assembly. Disconnect and remove load wires. Disconnect leadwires from the control box. Check wire markings for legibility to ease assembly. Arrange leads so they can be withdrawn easily from the control box. Remove front grille (14) and sheet metal work. Remove the four capscrews securing voltage regulator chassis (23) to end bell (9) and remove chassis assembly. Remove the centrifugal switch (8) from end bell and rotor shaft. On static excited models, slip the brushes (7) and brush springs (6) from brush rig (5) - it is not necessary to disconnect the brush leads unless brush replacement is required. Block the rear of the engine in place by supporting the flywheel housing. Remove the narrow generator band (10). Remove the large capscrews securing generator mounting pad (11) to the skid base. Remove the capscrews securing the stator assembly (4) to the engine flywheel housing. 8. Remove end bell from stator assembly; disconnect and remove brush rig from end bell on static excited generators. On brushless models, remove exciter field (24) from end bell assembly if required. 9. Attach the hoist and sling to the rotor assembly (1) and apply a slight lift to support the rotor. Remove the capscrews securing the flexibledrive coupling (13) to the engine flywheel and remove rotor from the engine. 10. Remove bearing capscrew (18) and washer (17) and remove bearing from shaft. If required, remove blower (2) from the rotor. 11. Disconnect rotor field leads from heat sinks F1 and F2 on the exciter armature. Remove exciter armature (25). E z 3 Use care not to damage the brush rig (or exciter on brushless models) while removing the stator. Do not allow the stator to rest on rotor during removal. CAUT,ON ' 9 23 L A / BRUSHLESS G E N E R A T O R FIGURE 20. GENERATOR DISASSEMBLY 24 Redistribution or publication of this document, by any means, is strictly prohibited. GENERATORASSEMBLY Generator assembly is the reverse of disassembly procedure: 1. Always replace bearing with a new one; apply a layer of grease on end bell bearing hole before inserting bearing. 2. Torque bearing capscrew to 60-70 Ib. ft. 3. Torque drive disc-to-rotor capscrews to 200-240 Ib. ft. 4. Torque drive disc-to-flywheel capscrews to 45-50 Ib. ft. 5. Torque generator through-stud nuts to 30-40 Ib. ft. 6. Refer to Purrs Curu/o,y for replaceable parts and assemblies. Refer to Wiring Diuputii for reassembly. [PI VOLTAGE ADJUSTMENT After replacement, voltage regulator (VR21) adjustment is performed as follows (see Figure 21): 1. Center the voltage adjust knob so pointer is in a vertical position. 2. Open meter panel doors. Start unit. 3. Using a screwdriver, turn R18 potentiometer on printed circuit board VR21 counterclockwise to increase the voltage or clockwise to decrease the voltage. Observe voltmeter on meter panel while making adjustment. Set voltage with no load connected to generator. (Example: For a 120/240 volt connection, set at no-load voltage or approximately 246 volts.) If voltage is unstable or tends to hunt, turn R26 potentiometer on VR21 in the direction shown on printed circuit board to increase voltage sensitivity. I ADJUST R26 HERE \ ADJUST R 18 HERE FIGURE 21. ADJUSTING VOLTAGE ON VR21 25 Redistribution or publication of this document, by any means, is strictly prohibited. - SECTION II GENERATOR GENERAL , , Generators discussed in this section are brushless type only. The difference between these and the generators in Section I is in the VR22 diode assembly and the commutating reactor. These have been removed from the generator end bell and relocated in the control panel. The diodes are now encapsulated within a hermetically sealed block, therefore if any diode or silicon controlled rectifier fails, the entire unit has to be replaced. See Figure27fordetailsof the rectifier assembly (CR21) and Figure 25 for the reactor (L21). Principles of operation and method of excitation remain unchanged from the units described in Section I. Refer to Table 1 for generators to which this section . applies. ROTATING EXCITER WITH RECTIFIERS ov‘ERSPEED SWITCH QENERATOR END VIEW (QRILLE REMOVED) FIGURE 22. ROTATING RECTIFIER ASSEMBLY VR2‘ VOLTAGE RE GU LATO R 121 REACTOR FIGURE 23. / \ CR2 I SCR BRIDGE SCR BRIDGE AND REACTOR LOCATION :TROUBLESHOOTING ing the generator. To use the guides, answer the questions either “yes” or “no” then proceed to the next step given in whichever column is indicated. Use the following troubleshooting charts and procedures to locate malfunctions in the generating system. Section 11 also references procedures A thru P of Section 1. When using block diagrams, a letter with a triangle indicates a procedure in Generator - Section 1. A letter within a diamond indicates a procedure in GeneratorSection II. The question and answer troubleshooting guides which follow give a step-by-step procedure for check- 26 Redistribution or publication of this document, by any means, is strictly prohibited. QUESTION AND ANSWER TROUBLESHOOTING GUIDE$ To correct a particular problem, answer the question either “yes” or “no,” then proceed to the next step given in whichever column question was answered. Procedures R thru P follow the troubleshooting guide. ITEM NO. F. N O AC OUTPUT VOLTAGE - ENGINE RUNNING AT RATED RPM YES NO Is Exciter Circuit Breaker (CB21) on the meter panel in the “ON” position? 3 2 Switch CB21 to “ON” position. Does AC voltage build up? - 3 Is A C voltage measured at terminals 1 and 2 on voltage regulator (VR21) printed circuit board 5 to 10 volts? 6 4 Is AC voltage measured at terminals 11 and 12 on VR21 5 to 10 volts? 5 7 5. Replace reactor assembly (L21). - - 6. Is DC voltage measured at terminals + and - on Rectifier Bridge (CR21) 5 to 10 volts? 15 11 Shut down generator set. Check continuity through L21 coils between terminal 2 on VR21 and T8 on generator, between terminal 1 on VR21 and T7 on generator. Is there continuity between these connections? VR21-2 to T8 VR21-1 to T7 14 14 10 8 If there is no continuity between VR21-1 and T7 ((2621-ON) apply a shorting jumper across CB21. Is continuity obtained? 9 10 Replace CB21. - - Check for loose or broken wires on VR21, CR21, L21, reference voltage transformer (T21), generator bus-bars and terminal board (TB21) in control box. Secure or repair where necessary. If repairs have been made, restart engine. Does AC voltage now build up? - 14 Are diodes CR1, CR2 and CR3 on CR21 assembly good? (See method T in procedure section for checking diodes.) If faulty diode located, replace CR21. 12 - T Are SCRs 1 and 2 in CR21 good? (See method T in procedure section for checking diodes.) If faulty SCR’s located, replace CR21. 13 - T 1. 2. TABLE PROCEDURE NOTE If voltage builds up but is high, low or unstable, or causes CB21 to trip, refer to table G. H or I of troubleshooting guide. 3. 4. 7. 8. 9. 10. 12. Redistribution or publication of this document, by any means, is strictly prohibited. ! ; ITEM NO. TABLE F. NO AC OUTPUT VOLTAGE- YES ENGINE RUNNING AT RATED RPM (continued) 13. Fault probably lies with a defective component on VR21. Replace VR21. 14. Start engine. Place CB21 in “OFF” position. Using method prescribed under “R” in procedure section flash the exciter field to restore residual magnetism. Place CB21 ON. Does the AC output voltage build up? 15. Shut off engine. is exciter field winding (F1: F2) OK? 16 16. Are rotating diodes CRI, through CR6 on exciter rotor OK? 17 ~~ 17. I No lPROCEDURE ~ Is generator stator winding OK? 18 - . . 18. Is exciter rotor winding OK? 19 19. Are generator rotor windings OK? 13 I . . . . . . I . i 28 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE F. SYNOPSIS 1 NO VOLTAGE BUILD-UP N eo SCRl OR SCRP OPEN , - DEFECTIVE DlODECR1 CR2 OR CR3 OPEN LEAD - REGULATOR PC BOARD TERMINALS 1 OR 2 . OPEN LEAD AT TERMINAL NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of the, appropriate section. . . .... ._ _. .- - .... TABLE G. UNSTABLE OUTPUT TION I - ENGINE RUNNING AT 1800 RPM - NO FLUCTUA- I 1 YES NO IPROCEDURE I I I I I I Are there any loose or broken wires or connections at VR21 terminals? - 2 Does adjustment of R26 (damping control potentiometer) on VR21 stabilize generator voltage? - 3 Replace VR21. - - I P TABLE G. SYNOPSIS UNSTABLE OUTPUT VOLTAGE i DEFECTIVE COMPONENT ON (VR21) VOLTAGE REGULATOR PRINTED CIRCUIT BOARD BROKEN WIRES OR LOOSE CONNECTIONS AT (VR21) VOLTAGE REGULATOR PRINTED CIRCUIT BOARD TERMINALS INCORRECT SETTING OF R26 POT ON (VR21) PRINTED CIRCUIT BOARD . , , , , ._ .. . . .. .- ". 1 . .. . I I NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of the appropriate section. 30 Redistribution or publication of this document, by any means, is strictly prohibited. .- TABLE H. OUTPUT VOLTAGE TO HIGH OR LOW &M YES NO PROCEDURE -- 1. 2. 3. Does adjustment of R21 “voltage adjust knob” on meter panel correct voltage level? - 2 Does adjustment of R18 potentiometer on VR21 correct voltage level? - 3 Are rotating diode heat sink mounting screw insulators OK? - - __ P If generator output voltage has been optionally reconnected, consider the following - 4- I Is reference transformer (T21) tap correctly connected on TB21? 1 5 5. Are the reconnections correct and secure? 6 6. Replace VR21. TABLE H. SYNOPSIS TOO HIGH OR TOO LOW i I INCORRECT REFERENCE TRANSFORMER TAP ON T21 - I INCORRECT SETTING OF VOLTAGE ADJUST POT (R21) ON METER PANEL 1 I DEFECTIVE COMPONENT ON RECTIFIER ASSEMBLY CR21 % /L\ I I r INCORRECT SETTING OF VOLTAGE ADJUST POT (R18) ON VR21 PC BOARD OPEN LEAD OR CONNECTION AT TERMINALS G1 OR G2 DEFECTIVE COMPONENT ON VOLTAGE REGULATOR PC BOARD (VR21) H DEFECTIVE ROTATING DIODE OR BAD INSULATOR ON HEAT SINK MOUNTING SCREW 1 OPEN IN CR1, CR2 OR CR3 1 I VOLTAGE BREAKDOWN OF SCRl ORSCR2 I NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of the appropriate section. 31 Redistribution or publication of this document, by any means, is strictly prohibited. IiLM TABLE 1. EXCITER CIRCUIT BREAKER TRIPS YES 1. Does AC output build up to 150% or more of rated voltage before CB21 trips? 2. Are there loose or broken terminals or connections at VRZl? NO PROCEDURE Is diode CR3 (connected between + and - in CR21 rectifier assembly) OK? Are reference voltage transformer (T21) windings and connections O K ? 5. Replace VR21. 6. Does AC output build up to rated value before tripping CB21? 7. Are rotating diodes CR1 through CR6 on exciter rotor OK? 8. Is exciter stator winding OK? 9. Is generator field winding OK? 10. Is exciter rotor winding OK? DEFECTIVE ROTATING DIODE CR1, CR2, CR3, ON, EXCITER FAULT IN EXCITER ROTOR OR STATOR WINDING ROTOR N O T E Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of the appropriate section. 32 Redistribution or publication of this document, by any means, is strictly prohibited. YES TABLE J. UNBALANCED GENERATOR OUTPUT VOLTAGE - Remove load from generator terminals. Is output still unbalanced? 2 Are generator leads properly connected or grounded? 3 Is generator stator winding continuous? 4 Is grounding procedure of generator and load correct? 5 [ NO lPROCEDUREl I - Check for ground faults on load. TABLE J. SYNOPSIS TERMINAL VOLTAGES ! I INCORRECT RECONNECTION AND/OR GROUNDING OF GENERATOR LEADS 1 INCORRECT GROUNDING OF LOAD OR GROUND FAULT IN LOAD I I FAULTY GENERATOR STATOR WINDING I 1 NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter is given at the end of the appropriate section. 33 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE J. SY NOPSlS (Continued) I VOLTAGE 150% MORE THAN RATED I OPEN TRANSFORMER (T21) WINDING OPEN WIRE OR CONNECTION AT VR21 MODULE TERMINALS 5, 6, 9,10, 11 OR 12 DEFECTIVE COMPONENl ON RECTIFIER ASSEMBLY CR21 1. * DlODECR3 OPEN DEFECTIVE COMPONENl ON VOLTAGE REGULATOR (VR21) MODULE I- BREAKDOWN OF S C R l OR SCRP NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of the appropriate section. Malfunction occurs after warmup or voitage adjustment. 34 Redistribution or publication of this document, by any means, is strictly prohibited. ADJUSTMENTS AND PROCEDURES (Applies to Section II Only) I FLASHING THE FIELD If output voltage does not build up it may be necessary to restore the residual magnetism of the poles by flashing the field. Assembleasixvolt battery, and diode as shown in Figure 24. If a six volt lantern battery is not available a 12-volt (generator set battery) or a 24-volt battery can be used, however a 20-ohm or a 40-ohm 2 watt resistor must be used in conjunction with the 12 amp 300 V diode. Start the generator set, touch positive lead to + on rectifier bridge, and negative lead to the - terminal. Hold leads on terminals just long enough for voltage to build up. TESTING L21 REACTOR The L21 commutating reactor mounts inside the control box, below the VR21 Voltage Regulator. I The coils 1-2 and 3-4 are wound on the same core. Resistance between 1-2 and 3-4 should be .034 ohm f .0034 and .042 ohms .0042 respectively (brushless units). Resistance between coils (e.g., 1/4) or from any terminal to frame of the reactor should be icfinity (Figure 25). * Do not keep excitation circuitry connected longer than 5-seconds, or damage may occur to the exciter regulator. I I2 AMP. 300 v. I RECTIFIER BRIDGE FIGURE 24. FIELD FLASHING CIRCUIT FIGURE 25. 35 L21 REACTOR Redistribution or publication of this document, by any means, is strictly prohibited. 1 TESTING RECTIFIER BRIDGE ASSEMBLY (CR21) The rectifier bridge located within the control cabinet, below the voltage regulator, contains 3 diode? CRl. CR2. and CR3, and two silicon C O I I I I ~ I ~ rI 'IcIx~t t~l i ~ t t t~ SCR1 and SCR2. These diodes and SCR's arc cncali:;dated within a hermetically sealed block, therefore lailurc! of any diode or SCR means the entire unit has to bc replaced. See Figure 26. I A C TERMINALS ARE GIVEN NUMERIC DESIGNATIONS FOR T E X T REFERENCE ONLY. DOES NOT APPEAR ON UNIT. CR I 7i- -1 I h CR3 - ' I - CR2 FIGURE 26. RECTIFIER ASSEMBLY Disconnect wires from rectifier unit prior to testing. Test unit in order shown in Table 5. Refer to Figure 27 for SCR1 and SCR2test circuit. When test is complete and satisfactory, reconnect unit observing correct wiring hook-up. r--- ' 6 VOLT DRY CELL BATTERY FIGURE 27. TESTING SCR 36 Redistribution or publication of this document, by any means, is strictly prohibited. I NG REMARKS METER SCALE CR3 Infinity RXlOK CR3 6- to 50-Ohms R X l Infinity RXlOK lnfinitv RXlOK SCR SCRl CR1 RX1 2CR2 Infinity RXlOK Infinity R X l OK 6- to 50-Ohms RX1 DC Voltmeter lead DC Voltmeter Reading CR2 CR2 I + 1 3CR2.I AC2 I + + 1 I I 3 Volts 3 Volts - Apply temporary jumper from AC1 to G1 to test SCR1. Remove jumper, read voltmeter. See Figure 27. **.Apply temporary jumper from AC2 to G2 to test SCR2. Remove jumper, read voltmeter. See Figure 27. 37 Redistribution or publication of this document, by any means, is strictly prohibited. ! INDEX OF GENERATOR ADJUSTMENTS AND PROCEDURES SECTION I PROCEDURE A B C D E F G H J K . L M N P PAGE TITLE Brushes .............................. Flashing Field ........................ No AC Power t o Exciter Testing L1 Reactor Testing Diodes Testing SCR’s Testing Generator Rotor Testing Generator Stator Testing Exciter Rotor Testing Exciter Stator ................. Reconnection Sensitivity Reference Circuit .......... Generator Disassembly Voltage Adjustment .............. : ............... ................... ....................... ........................ .............. .............. ................. ........................ ............... .... 16 16 17 17 17 18 19 20 21 21 21 23 24 25 SECTION II PROCEDURE R S T TITLE PAGE Flashing Field ........................ Testing L21 Reactor .................. Testing Bridge Rectifier (CR21) ....... 35 35 36 38 Redistribution or publication of this document, by any means, is strictly prohibited. CONTROLS - SECTION 111 GENERAL gauges. An optional door has holes for electric tachometer and/or oil temperature gauge. The bracket supports the terminal blocks, cycle cranker and relays in the DC engine control circuit. The shock mounted control box has two doors that open from the center. The left hand door holds the field circuit breaker, voltmeter and voltage adjusting rheostat. The optional meter package adds running time meter, frequency meter, ammeter or ammeters plus volts-amps selector switch to the left hand door. Plug mounted relays in both the AC section and DC section plus printed circuit modules in the DCsection facilitate troubleshooting and servicing. Snap-in lamps with Faston connectors make lamp replacement very easy. See Figure 28. The right hand door, attached to a removable bracket, holds the instrument lamp, fault lights, switches and I A12 C R A N K I N G LIMITER (MAY A L S O U S E A N O P T I O N A L CYCLE CRANKER) K11 S T A R T D I S C O N N E C RELAY -FAULT K12 IGNITION RELA LAMPS TIME D E L A Y K13 S T A R T S O L E N O I -ENGINE MONITOR PC B O A R D \KI l FIGURE 28. LOCATION OF RELAY K 2 RELAY DC CONTROL COMPONENTS THE QUESTION AND ANSWER TROUBLESHOOTING GUIDES BEGINNING ON PAGE 39 GIVE A STEP-BY-STEP PROCEDURE FOR CHECKING CONTROL SYSTEM PROBLEMS. THEFLOW-CHART TROUBLESHOOTING GUIDES ARE GIVEN AS A GENERAL GUIDE TO RESOLVE VARIOUS CONTROL SYSTEM PROBLEMS. ALL CHARTS REFER TO PROCEDURES AND NOTES WHICH ARE GIVEN AT THE END OF THIS SECTION. 39 Redistribution or publication of this document, by any means, is strictly prohibited. QUESTION AND ANSWER TROUBLESHOOTING GUIDE FOR UNITS WITH ONE FAULT LAMP To correct a particular problem, answer the question either “yes“ or “no” then proceed to the next step given in whichever column question was answered. TABLE A. ENGINE FAILS TO CRANK WHEN SWITCH TO “RUN” Does fault lamp light? 1. 2. ~ 1 Is battery connected correctly and is voltage normal? ~~~ ~ l 3 I I relay K13’ (start solenoid) pick up? 3. 4. YES Does ignition relay K12 pick up? I l7 lo Is voltage from ground terminal to center terminal of run-stop-remote switch equal to battery voltage? 7 6. Switch is defective or in “stop” position. - 7. Is voltage from ground terminal to ignition relay K12 terminal “B” equal to battery voltage? 5. 0. 9. 10. I lo Jumper battery positive from center terminal of run-stop-remote switch to terminal “6”of ignition relay K12. Does engine now crank? 9 Replace engine monitor printed circuit board. - Is voltage from ground to terminal 26 on battery voltage? , TBll equal to 14 11. Does ignition relay K12 (4-7)contact close? 12. a. Check socket connection. b. Coil may be open. c. Replace ignition relay K12. 13. Clean relay contacts and check wiring. 13 I I 14. 15. Is voltage from ground to start disconnect relay equal to battery voltage? K11 terminal 1 Clean relay contact K11 (7-1)and check wiring. I l6 I - NOTE: On EK. EM, and EN series, start solenoid relay is mounted on the engine, rather than in the control, and is designated K6. 40 Redistribution or publication of this document, by any means, is strictly prohibited. t ITEM NO. A. ENGINE FAILS TO CRANK WHEN SWITCHED TO “RUN” (Continued) YES NO Is voltage from ground to coil terminal of K13’ start solenoid I equal to battery voltage? 17 18 17. Does voltage from ground to TBll-22equal battery voltage? 21 20 18. Jumper from K13’ coil terminal to Does relay K13’ pick up? 19 - 16. K11 terminal 1. 19. Replace cycle cranker printed circuit board A12. - - 20. Replace start solenoid K13’. - - 21. Is voltage from ground to starter coil terminal equal to battery voltage? 22 23 22. Replace starter. - - 23. Check thermal breaker CB1 and wiring to starter. - - PROCEDURE ‘NOTE: On EK. EM, and EN series. start solenoid is mounted on engine, rather than in the control, and is designated K6. TABLE A. SYNOPSIS ENGINE FAILS TO CRANK A12 CYCLE CRANKER FAILS LOOSE OR REVERSED BATTERY CONNECTlO N IGNITION RELAY K12 FAILS I K12 COIL (4-7) FAILS TO CLOSE 41 START SOLENOID FAILS MONIT0R PRINTED CIRCUIT BOARD ~ SOLENOID COIL OPEN SOLENOID CONTACT FAILS TO CLOSE CONTACT FAILS TO CLOSE CIRCUIT PATH Redistribution or publication of this document, by any means, is strictly prohibited. ITEM NO. TABLE B. ENGINE SHUTS DOWN IMMEDIATELY AFTER START YES 1 Is overspeed switch S3 closed? 1. 1 NO PROCEDURE NO IPROCEDUREI 2 Open overspeed switch, then reset fault lamp by switching to “stop”, then back to “run”. Does engine crank and run OK? I Remove wire from TB11-29. Reset fault lamp by switching to “stop”, then back to “run”. Does engine crank? 4 Place wire back onto TB11-29 while engine is running. Does fault lamp light and engine stop? 5 5. Check overspeed switch and wiring for grounds. - 6. Jumper from ignition relay K12 terminal “B” to center terminal of run-stop-remote switch. See Method M in Procedure section. Does engine crank? 7 Replace engine monitor printed circuit board and remove jumper. - ~ 7. I ITEMTABLE C. ENGINE SHUTS DOWN AFTER RUNNING A SHORT TIME NO. YES I I 1. Does fault lamp light and does plant stop after running about 12 seconds? 2. Does fault lamp light and does plant stop after running about 1 minute? 3. Remove wire from terminal TB11-30. Does engine run restarting? 4. Engine is either not pumping oil properly or oil pressure sensor is defective. ~ . 5. 6. 7. OK after Replace wire on TB11-30 and remove wire from TB11-31. Does engine run OK after restarting? 6 Engine is either operating over temperature, temperature sensor is defective or wire between sensor and terminal block is grounded. - Jumper K11 terminals 6-9. Does engine run OK? a ~~ ~ 8r-1 Replace r e l a y G 1 or clean contacts 6-9. 9. I Replace engine monitor. 42 Redistribution or publication of this document, by any means, is strictly prohibited. ITEMTABLE NO. D. ENGINE HESITATES WHEN ATTEMPTING TO CRANK YES 1. Does engine crank as soon as run-stop switch is put into “run” position? 2. Check contacts K12 (3-9)for failure to close or to make proper contact. NO PROCEDURE TABLE D. SYNOPSIS ENGINE SOMETIMES HESITATES BEFORE CRANKING 5 I 43 DIRTY CONTACTS, BAD CONNECTION I Redistribution or publication of this document, by any means, is strictly prohibited. . ITEM NO. TABLE E. STARTER FAILS TO DISENGAGE OR TRIES TO RE-ENGAGE WHILE RUNNING I YES 1. Does starter continue to run after engine starts? 2 2. Does charge ammeter show a charging current while running? 4 3. Is charging alternator belt on and driving alternator properly? 4. Does start disconnect relay K11 and starter protection relay K14 pick up when engine starts? 5. Does voltage from ground to K13’ coil terminal drop to zero when K11 relay picks up? 6. Does voltage at starter terminal drop to zero when K13* drops out? 7 7. Check for faulty starter. - 8. Start solenoid contacts may be welded - replace K13’ solenoid. . ~ 9. 10. . I ~ Check K11 and K14 contacts (1-7) to make sure they open when relay picks up. l 4 l6 I - l- Does voltage across K11 terminals (A-B) build up’to battery voltage? 11. Replace start disconnect relay K11 or starter protection relay K14. Coil may be open. 12. Does relay K12 (5-8) close to bring battery voltage to alternator regulator? 11 l- I l3 13. Check for faulty alternator, regulator or shorted alternator output. - 14. Check K12 ignition relay for dirty contact or broken wire. - , NOTE On EK. EM and EN series, start solenoid is mounted on the engine, rather than the control, and is designated K6. 44 Redistribution or publication of this document, by any means, is strictly prohibited. TABLE E. SYNOPSIS J STARTER FAILS TO DISENGAGE START SOLENOID COWTACT FAILS TO OQEN - ENERGIZE START DISCONNECT RELAY K11 AND K14 D.RlVE BELT OFF OR SLIPPING 7 I K14 STARTER PROTECTION RELAY FAILS - START DISCONNECT RELAY K11 FAILS AND-c IGNITION RELAY K12 (5-8) FAILS TO CLOSE w 7 1 I K14 COIL, . ' K11 START DISCONNECT COIL OPEN I I I , CONTACTS 1-7 ON K11 FAIL TO OPEN CONTACTS 1-7 ON K14 FAIL TO OPEN ALTERNATOR OUTPUT SHORT CIRCUITED DEFECTIVE REGULATOR /G\ NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section. - K14 starter protection relay was added to units beginning with the Specs shown below. This relay prevents starter engagement when unit is running. SERIES SPEC SERIES SPEC SERIES SPEC SERIES SPEC EK-EM EN KB-KR DDA-MDDA DDB . D A P A A DEH DEF DEG DFE DYA D F D H C DYC DYD DYG (150-175 kW) DYJ B A WA WE WB F B H 45 A A Redistribution or publication of this document, by any means, is strictly prohibited. QUESTION AND ANSWER TROUBLESHOOTING GUIDE FOR UNITS WITH 5 FAULT LAMPS - I L‘ kM I - TABLE F. ENGINE FAILS TO CRANK When switch is put into “run” position, does. engine csank? . : ’ . . ’ Is battery connected correctly and is voltage normal? - YES NO - 2 3 - PROCEDURE I . Does one of the following fault lamps light? (Choose one of the following:) I I ’ 30 25 27 29 .. Overspeed? High Engine Temperature? Low Oil Pressure? Overcrank? - . . I Does ‘relay K13* (sfarfsolenoid) pick up? 22 5 Does ignition relay K12 pick up? 11 6 Is voltage from ground terminal to center terminal of run-stopremote switch equal to battery voltage? 8 7 Switch is in “stop” position or defective. - - Is voltage from ground terminal to ignition relay K12 terminal “B” equal to battery voltage? 1131g1 I Jumper battery positive from center terminal of run-stop-remote switch to terminal “B” of relay K12. Does engine crank? ~~ I I 1 0 1-1 1 . M ~~ Remove jumper and replace engine monitor printed circuit board. - - Is voltage from ground to terminal 26 on TB11 equal to battery voltage? 15 12 Does contact ignition relay K12 (4-7) close? 14 13 Clean socket connection. Coil may be open. Replace ignition relay K12. - - Clean relay contacts or replace relay and check wiring. - - NOTE: On EK. EM and EN series, start solenoid relay is mounted on the engine, rather than in the control, and is designated K5. 46 Redistribution or publication of this document, by any means, is strictly prohibited. 15. Is voltage from ground to K11 iterminal 1 equal to battery voltage? 16. Clean relay contact K11 (1-7) and check wiring. Replace relay K11 if necessary. 17. Does voltage from ground to coil terminal of K13’ start solenoid equal battery voltage? 18. Does voltage from ground to TB11-22 equal battery voltage? 19. Jumper from K13* coil terminal to K11 terminal 1. Does relay K13* start solenoid pick up? I 17 I I 18 I I l6 l9 22 20 I 20. Replace cycle cranker and check printed circuit connection. 21. Replace K13* start solenoid. 22. Does voltage from ground to starter coil terminal equal battery voltage? 23 24 23. Replace starter. - - 24. Check wiring between TB11 terminal 22 and starter. Some units have an automatic resetting circuit breaker in this circuit. 25. Remove lead from TB11-31. Reset by switching to “stop”, then back to “run”. Does engine crank OK? 26 29 26. Inspect for bare wires and shorts to ground. Replace engine temperature sensor. - - 27. Are relay contacts K11 (8-5) open? 29 28 28. Replace relay and reset by switching to “stop”, then back to “run”. Does engine crank OK? - 29 29. Replace engine monitor printed circuit board. - - 30. Remove lead from TB11-29. Reset by switching to “stop”, then. back to “run”. Does engine crank when switched to run? 31. Replace the lead to TB11-29 when engine is running. Does overspeed lamp light and engine stop? 1 - 1 - 1 1-1-1 I I I I I I 29 31 ’ I 32 I 33 I I-1-1 32. Check for defective overspeed switch or bare wires grounding terminal TB11-29. 33. Stop and start engine several times. Works OK? - 34 34. Replace engine monitor printed circuit board. - - I I NOTE: On EK, EM and EN series, start solenoid is mounted o n the’engine, rather than the control, and is designated K6. Redistribution or publication of this document, by any means, is strictly prohibited. ITEM NO. 1. 2. 3. ’ YES TABLE G. ENGINE SHUTS DOWN AFTER RUNNING A SHORT TIME ~ ~ ~~~ Does low oil pressure lamp light and plant stop after running about 12 seconds? 3 Does overcrank lamp light and plant stop after running about 1 minute? 5 Remove wire from terminal TB11-30. Reset alarm by switching to “stop”, then back to “run”. Does engine run OK? (Replace wire after test.) l- Engine is either not pumping oil properly o r oil pressure sensor is defective. 5. Does relay K11 pick up after engine starts? 6 6. Jumper relay K11 contacts (6-9) after engine starts. Does engine continue to run OK? (Remove jumper after test.) 7 7. Replace relay K l l . - 8. Replace engine monitor printed circuit board. - 9. Does charge ammeter show a charging current while running? 10 Does battery voltage appear across K11 co,iI terminal (A-B) when engine runs? 7 11. Check for an open circuit in wiring or a loose connection from alternator “AUX” terminal to K11 coil circuit. 12. Check .alternator and regulator output; replace if necessary. PROCEDURE , 4 4. 10. NO ~ l- - TABLE G. SYNOPSIS SHUTS DOWN I I I TEMPERATURE START DISCONNECT RELAY K11 (6-9) 1 AEE:YF:E SENSOR CLOSED PRESSURE 1 SENSOR CLOSED F ’ % w I NO ALTERNATOR OUTPUT I I I SWITCH . ovER:EED,CLOSED I A-11 ENGINE MONITOR PRINTED CIRCUIT DEFECTIVE REGULATOR 48 Redistribution or publication of this document, by any means, is strictly prohibited. I SINGLE LAMP ENGINE MONITOR FAULT FAULT ENGINE FAILS TO CRANK LOW OIL PRESSURE OR HIGH ENG. TEMP. CIRCUIT FAILS AFTER APPROX. 12 SECONDS *'* PATH 9-7 ON A-11 PRINTED CIRCUIT BOARD K1 RELAY CONTACT FAILS TO CLOSE LIGHTS AS SOON AS RUN SWITCH CLOSED LIGHTS AND ENGINE SHUTS DOWN DIODE CR3 OPEN TRANSISTOR 0 7 FAILED, SHORT EMITTER TO COLLECTOR ** . CAPACITOR c2 SHORTED NOTE: Whenever a letter appears near the box, a separate procedure, corresponding to that letter, is given at the end of this section ** I.. - With swiich in run position, check for voltage across R9 (27-ohms). A voltage of 0.5 to 1.0 will turn on SCR CR6. If voltage is present, remove TB11 terminal 29. If voltage is still present, check transistors 0 7 for short-emitter to collector. Remove TB11 terminal 30 and 31. If engine still shuts down, remove transistor Q8. If this prevents shutdown - replace Q8. SCR CR6 SHORTED r EXTERNAL ALARM FAILS ON ALARM SHUTDOWN CONTACT FAILS TO CLOSE ON SHUTDOWN CIRCUIT PATH 9-8 OPEN ENGINE MONITOR ** I ENGINE FAILS TO CRANK LIGHTS AS SOON AS RUN I CIRCUIT PATH 18-19 OPEN HIGH ENGINE TEMPERATURE LAMP LIGHTS I I LOW OIL PRESSURE LAMP LIGHTS ENGINE SHUTS DOWN I I OVERSPEED LAMP LIGHTS - OVERCRA'NK LAMP LIGHTS _ I LAMP LIGHTS AFTER APPROX. 12 SECONDS - TRANSISTOR Q6 FAILS TO TURN OFF K1 RELAY CONTACT ON A-11 FAILS TO CAPACITOR C6 OPEN TRANSISTOR Q10 SHORTED T I CAPACITOR F l CAPACITOR POTENTIOMETER R-15 ON A-11 PRINTED ClRCUl BOARD FOR CORRECT TIME CAPACITOR CAPACITOR OPEN OPEN I I TRANSISTOR Q13 SHORTED POTENTIOMETER R2 ON A-11 PRINTED CIRCUIT BOARD FOR CORRECT TIME T I CAPACITOR . NOTE: Whenever a letter appears near the box, a separate procedure, correspondjng to that letter, is given at the end of this section. ' ** - Capacitor C1 must be discharged when engine starts to prevent an overcrank shuidown. Check relay contact that connects to terminal 16 of engine monitor. See typical wiring diagram. ' .. .- I- . OVERCRANK RELAY FAILS TO DISCHARGE CAPACITOR C1 ADJUSTMENTS AND P.ROCEDURES If starter fails to disengage, the engine may drive starter to unsafe speeds that could cause starter rotor windings to separate. Inspect contacts for dirt particles, obstructions or insulating film. Clean, using low pressure compressed air and bond paper. Check relay socket. Contacts are normally closed when engine is not running. Contacts must open when engine is running normal. R E M O V E K11 OR K 1 2 F R O M C O N T R O L B O X (PULL S T R A I G H T up). cT)NNECT A N O H M M E T E R TO TERMINALS M A R K E D "A" A N D "6" O N B A S E O F R E L A Y . IH1 O F 12 V O L T RE.LAY IS 120 O H M S . R E S I S T A N C E O F 2 4 V O L T R E L A Y IS 4 7 0 O H M S . Contacts are normally open; contacts close for alarm condition only. (Overspeed switch may have to be reset manually.) IJI Contacts may have welded closed or plunger may be stuck. Remove solenoid from circuit to test for proper operation. FIGURE 29. TESTING K11 AND K12 RELAYS [KI Inspect printed circuit board paths that supply voltage to relay K12. (Between terminals 18-19of 3000681; between terminals 7-9 of 300-0679.) When connecting battery cables, terminal will spark i f connection is reversed. Unit will not crank with reversed cables or loose connections. DC alternator will overheat and will probably burn up. [LI A reverse battery connection will show a maximum positive charge on the DC ammeter. Remove cycle cranker printed circuit board and jumper terminal 2-3 to by-pass cycle cranker circuit. On dry charged batteries, no woltage is present until electrolyte is added. See ooerator's manual for alternator belt tension edjustment. In an extreme emergency, engine may be operated without any safeties by removing engine monitor printed circuit board and jumping terminals 7-9. (It may be easier to jump from center contact of RunStop switch to terminal "B" on Kl-2 relay; see Figure 30.) Check for voltage from starter terminals to ground. Voltage should be present at both terminals when solenoid is energized for cranking. 51 Redistribution or publication of this document, by any means, is strictly prohibited. ' Units With Five Fault Lamps: Potentiometer H2 on All printed circuit board is factory adjusted for 75 seconds ( ' 5 seconds). To lengthen delay, use a screwdriver and turn R2 clockwise; to shorten delay, turn counterclockwise. See Figure 32. R15 OIL PRESSURE D E L A Y - FACTORY SET A T 12% SECONDS SWITCH \ . . '. FIGURE 30. EMERGENCY STARTING R 2 OVERCRANK DELAY' -FACTORY SET A T 75 SECONDS ADJUSTING LOW OIL PRESSURE TIME DELAY ON ENGINE MONITOR PRINTED CIRCUIT BOARD FIGURE 32. ADJUSTING TIME DELAYS ON'FIVE LAMP ENGINE MONITOR Units With Single Fault Lamp: Potentiometer R l O on A-11 printed circuit board is factory adjusted for 12112 seconds ( ? 2-1/2 seconds). To lengthen delay, use a screwdriver and turn potentiometer clockwise. To shorten delay, turn ' potentiometer counterclockwise. Refer to Figure 31. ADJUSTING OPTIONAL CYCLE CRANKER The optional cycle cranker is factory set:for 15 seconds crank time and, 10 seconds rest time. To lengthen crank time, .turn potentiometer R4 clockwise; to shorten crank time, turn counterclockwise. To lengthen rest time, turn potentiometer R1 clockwise; to' shorten, turn counterclockwise. See Figure 33. Units With Five Fault Lamps: Potentiometer R15 on All printed circuit board is factory adjusted for 12-1/2 seconds ( 2 2-1/2 seconds). To lengthen delay, use a screwdriver and turn clockwise; to shorten delay, turn counterclockwise. See Figure 32. 1 4 A12 C Y C L E CRANKEF ADJUSTING OVERCRANK TIME DELAY ON ENGINE MONITOR PRINTED CIRCUIT BOARD 3OOC714-12V. 3OOC715-24V. ' ' Units With SingleFault Lamp: Potentiometer R4on All printed circuit board is factory adjusted for 75 seconds ( r 5 seconds). To increase delay, use a screwdriver and turn R4 clockwise; to shorten delay, turn counterclockwise. See Figure 31. R 4 OVERCRANK D E L A Y (FACTORY SET A T R 4 C R A N K TIME FACTORY SET A T 15 SECONDS., T O INCREASE T U R N CLOCKWISE OIL PRESSURE DELAY (FACTORY SET A T 12% SECONDS) \ R1 R E S T TIMEFACTORY SET A T 10 SECONDS. TO INCREASE TURN CLOCKWISE FIGURE 31. ADJUSTING TIME DELAYS ON SINGLE LAYP ENGINE MONITOR 0 FIGURE 33. OPTIONAL CYCLE CRANKER ADWSTMENTS 52 Redistribution or publication of this document, by any means, is strictly prohibited. WIRING DIAGRAMS 612-4173 612-3919 625-1007 625-0987 612-4350 612-4353 300-0679 300-0680 300-0681 300-0682 300-0714 625-1036 612-5300 612-5301 612-5302 612-5303 612-5304 612-5305 612-5310 612-5311 612-5312 612-5313 PAGE 100-175 kW Brushless Exciter ...................................... -54 30-90 kW Static Exciter ............................................ -55 VR21 Brushless Exciter ............................................. 56 VR21 Static Exciter ................................................. 57 30-50 kW Controls .Single Light .................................... 58 30-90 kW Controls .Five Light ...................................... 59 Engine Control Monitor .12 V ....................................... 60 Engine Control Monitor .24 V ....................................... 61 Engine Control Monitor 12 V Five Light ............................ 62 Engine Control Monitor .24 V . Five Light ............................ 63 Cycle Cranker .12 V ............................................... 64 Tap Switch ......................................................... 65 25-90 kW Brushless 15R; 515R ..................................... 166 25-180 kW Brushless, Full Meter Panel ............................... 67 25-45 kW-3R Brushless 120/240 V . 1 Phase .......................... 68 25-45 kW .3R Brushless 120/240 V . 1 Phase, Full Meter Panel . . . . . . . .69 25-90 kW 9XR Brushless 347/600V ................................... 70 25-180 kW .9XR Brushless 347/600V. Full Meter Panel ...............71 Generator Set Engine Control, 12V Ignition; EK, EM, EN .............. 72 Generator Set Engine Control, 12 V Ignition; EK, EM, EN ............. 73 Generator Set Engine Control, 12V ignition; KR, WA .................74 Generator Set Engine Control, 12 V Ignition; KR, WA .................75 . . 53 Redistribution or publication of this document, by any means, is strictly prohibited. 1 I 612C4173 I WIRING MAGRAM CONTROL BOX (INSIDE) 111. TI T 2 FIELO 1 W 12- NOTE SEE VOLTAGE CHART I M23 M?4 v HOUSING-CONTROL BOX T2 n. v ... .. IC ,a<, .--._ I SCHEMATIC DIAGRAM __ - REAR VIEW_-P/\NEL s I I cfs C821 7 rT6 CT21-23 .TI2 $7 1 3208431 ow I 320P307 I LOCKXKTBRKR HANDLE [PENNSTATE 3028743 ,3028744 '3088745 3028746 3028747 3028748 I TRANSFORMER ASSY-CUR t 2 5 - 4 0 K W TRWSFORMER ASSY-CUR(41-45KWl FIANSFORMER AS=- CUR ( 4 6 6 o ( w I TRANSFORMER ASST- CUR (61-lWl(W TRANSFORMER *SSY~CUR(IOI~IUI:Wl TRANSFORMER A3SY-CURU26-175KWI PA111 M rnY.!"O* CIRCUIT BREAKER. 2hMP I I I I I a d - T3 7 ELlt3219 3150322 I VR21 33201268 1 VR22 305D49NREa WII 3380525 1 W12 336A1913 I I--- - NOTE: CONNECT LEAO W12 FROM TERMINAL TB21-63 TO 7821-IH-I PER VOLTAGE CHART BELOW -- I ROARDASSY-PC V0LTA:E RGLTR CHASSIS ASSY-VOLTAGE RGLTR WIRING HARNESS LEAO ASSY , VOLTAGE CONNECTIONS .. . 115/23OV, 50Hz,(H61 120/240V, 60H2, (H51 1 I I I , -. -. I15/2WV, 50 Hz. (H41 IZOl2JEV. 60Hz,(H31 127/220V, 60 Hz,(H41 I39/240V. . 60 HZ.(H51 . -.. -. ,-234/40OV, 50 Hz. (H41 240/416V, 60 Hz,(H3) 254/440V, 60 Hz.( H4) 277/480V. . 60 Hz..(H51 I'PHASE 115/23OV, 5 0 H z . (H61 120/240V, 60Hz. (H5) NOTE. UNLESS OTHERWISE NOTED, 3PH. 50/60Hz 12 W RECONNECTABLE - . ........- -.--,.-- , 612C4173 . SCHEMATIC DIAGRAM m111 ,'SI , CONTROL BOX (INSIDE) nr.KS. m. 32082 320818 yOPm7 CBZI I' 6 : -- T.- -TI1 *TI2 I I - G2A131 ' - $ WI2-NOTE SEEVOLTAGE CHART % TI T2 T3 74 TS T6 77 \ i I T 2 % - . . K L . x)781061 - 30lK.224 I I -- _ -HOUSING-CONTROL BOX TO T9 * \ I \ \ \ 0 I I \ 3 \ Si! -I -I NOTE. CONNECT LEAD W12 FROM TERMINAL TB21-63 TO'TEZI.IH,) PER CHART VOLTAGE CONNECTIONS 3 PHASE 1I - GENEfiIATOR 110/190V. 115/2WV, 120/208V, 127/220V, 139/240V, 115/23OV. 50H1, (H6) 120/240V, 60Hr, (H51 220/3EOV, SO HI. (til) 234/400V, 50 HI, (H4) 2 4 0 / 4 1 6 V 60 Hr:(H4) HZ (H3) 254/440$60 5CJHr, (H3) 50 Ht. (H4) 60 HZ.lH3) 60 Hr,(H41 60 Hr.(H51 277/480V, 60 HZ. (ti51 T7 F2 I LI FIELD LO (MOUNTED IN E N ) 6 7 8 910 O O Q Q ? 5 4 1 TI I I - L3 NOTE. UNLESS OTHERWISENOTED, ALL COMPONENTS ARE SHOWN IN THE 0E.ENERGIZED POSITION DS22 ' LO . KxmnM aiv CIRCIJI_T BREAKER.IIAW IZS-WKN I CIRCUIT BREAKER. 2 0 W P ( 4 - 9 0 K W l I J O B C K T ERKR HANDLE (PEW STATE I I I I ' ' I --a LIGHT-UPPER SCALE LIGHT-LOWER 7GENEFA! I TRELAY-VOLTAGE 11 ---q SELECTOR .BRACKET- RELAY MTG _. - 625D1007] ; I ! VRZl WARD A5SI- PC 332DIL68 i I Lr - . ,\..,. r 1 .. . . . . . . I ... . pi i ----T8 . I. .. CII I 4 l - .. c121.47 T R27 100 K *-- i I N N 5 B I- .; 57 Redistribution or publication of this document, by any means, is strictly prohibited. - I I ? 1.: 12 I I D ---i _- 7 I . .. I . I N * i i 58 Redistribution or publication of this document, by any means, is strictly prohibited. . 612C4353 1 -WIRING - DIAGRAM (FRONT VIEW1 I Z V 8OMA c ;EMOTE hNNUNCIATOR IUEBCRANK .ow oh PRES! I1 EN6 TEMP I -7 -- SCHEMATIC DIAGRAM (REAR V I F Y I I6 ,1 1) i 9 10 .C CNG TEMP I id iENERATlNG I s2 53 I NOTES: I. W12 USED ON STD CONTROL ONLY 2.USED ON PRE-ALARM CONTROL ONLY 3.REMOTE ALARM CIRCUIT RATED 5AMP MAX 4.SHUTDOWN 8 A L A R M S 4.1 STD CONTROL 4.1.1 SAFETY SHUTDOWN 8 ALARMS Oh OVERCRANK,OVERSPEED,HI ENG TEMP 8 L O OIL PRESS 4.1.2 SAFETY A L A R M ONLY ON LO ENG TEMP 4.2 PENN STATE CONTROL " " I 6 3 ON TBZl 4.2.1 SAFETY SHUTDOWN a ALARMS 30-24OVAC ON OVERCRANK 8 OVERSPEED vi 4.2.2 SAFETY A L A R M S ON HI ENG T E M ~ L OOIL PRESS a LO ENG TEMP 4.3 PRE-ALARM CONTROL 4.3.1 SAFETY'PRE-ALARMS ON HI EN( TEMP 8 LO OIL PRESS 4.3.2 SAFETY SHUTDOWN a ALARMS ON OVERCRANK,OVERSPEED,HI ENG TEMP e LO OIL PRESS KI I 4.3.3 SAFETY ALARM ONLY ON La EN( 13 TEMP B U A WHEN U S E D 5.S3 OVERSPEEO SWITCH MOUNTED IN GENERATOR END B E L L ISTP &UNLESS OTHERWISE NOTED,ALL CRANKER CR*NKI COMPONENTS ARE SHOWN I N T H E ST^ C ~ N T R O L -01 -03 -01 ,-04 DE-ENERGIZED POSITION .ICRE+iLARMBPENH $TATELSWE&QF) ...... ".. , n ICYCLE F?'ps 4 1931108 1931109 193A104 SI . IHlADDCD DDA.DDB,DYJ El P E N N STATE (SPEC:C,D,E.ECI -0s -06 s5 S6 57 1 I I I SWIICH-LOW Dl1 PRESSURE 1 I 1 SIlTCH-HIGH WATER TEMP I I StNOER -011 PRESSURE SEWOER-WATER TEMP < O V A . O K ) SINOER-WATER TEMP. (OEF. OEH. FUEL PUMP I I I C I R C U I I B R E I K t R . I 7 5 AIP(0VC OHLVJ , I I I I _. - I ' I I I TO TERM 62 I 8 63 ON TB21 I 190-24OVAC 1201%3- 12 II IVERSPEED CBI - I 1 f SIITCH-OYIRSPfEO I I - 4; I I OEC) I S?ITCH-LOI l I T f R TEMP SWITCH-LOU 011 PRESS (PRE.lJARI) ' SIITCH-HIGH WATER TEMP (PM-ALARM) 300C679 I I . HOW: 1. SOLDER fER SOLDERIH6 PROCESS MIL-S-1872 ITEM 23. U S I N S SOLDER. 2 . SOLDER J O l H l S AN0 OR C W O N E N T LEAOS SHALL NO1 PWOJECT MORE THAN 3 4 6 BLYOND SURFACE OF BOARD. @ Q) 0 FUELSOL >R IGN RLLl 7 17- 9 I t X5 --1 3. F A C l O R l AOJUST POTEHTIOYETER R13 FOR 12.5 f 2 . 5 SECONDS LOP 01111. FACTORY AOJUST POTENTIDPETER R4 FBR 7 5 2 IO SECONDS O V E R C R d K 01111. A9 19 RE I8 I7 .RtO A6 A2 P I I1 16 15 14 I3 350-517 550-505 I RESISTOR I RESISTOR 350-572 3031169 350-552 350-526 I 2 1 350-536 2 RESISTOR POTENTIOIETER RESISTOR RESlSlOR RESIPIOP. I 27n 2.711 I iim 3.5 YEm 22m 15On loom 7 8 9 IO I I I2 I3 1 1 1 1 I4 1 1 1 ' 1 1 1 1 NOTES' I . SOLOEk ?ER SOLOLklNf PROCESS MIL-S-6172 USINC SOLOER. ITEN 23 2 SOLOER JOINIS ANU'OR'COYPONEkT LEAOS SWLLL HOT PHOJECI MORE IHAN 3 16 3tlWO SURfACL OF EOARO. D 3. SET R4 4. FUEL SQL OR IGN RELAY 7 8 I-~-n n FOR AN OVERCRANK TIME OELAV Of 1525 SEMNOS ton OIL PRESS TIME OELAY SHOULD BE i z . 5 i z . 5 SECOHDS 71 I P 62 Redistribution or publication of this document, by any means, is strictly prohibited. i I I " c 63 Redistribution or publication of this document, by any means, is strictly prohibited. ... d BY AVl3U N9I CB M I N I I : I '.\ . -_ I @ - - - . e - - - EQUIVALENT CIRCUIT -1 h I A \- I I I L3 120/208V, 3 @ L3 120/240 V, I # I I NOlcS: I. REMOX JiiMFER W12 B i X E E N TB21-i3 & Ta21-H3. MOUNT VOLTllGC SELECTOR RELAY X!!j I N UOKTROL BOX AND l l R E A; SHOWN. RELAY WILL ENEOGIZ: Oi4 120 '29BV 30 CIRCUIT COMPLETING CONNECTION BETWEEN TB21-63 I TB21-H3. RELAY WILL RElAAlN DE-ENERGIZED ON 1 2 0 / 2 4 0 , 1 1 CIRCUIT COMPLETING CONNECTION BETWEEN TB21-63 & TB21-H5. WRING DIAGRAM -- /0 /? CEkTROL BOX (INSIDE) SCHEMATIC DIAGRAM . 11115 L'51 ' G21 7 I I ;if. T5 DES CB21 1 1 , m r NO 3208431 law I I MXfiIIItON I IClRCUlT BREAKER.2AMP GENERATgR RELAY-VOLTAGE --- I_ __ _ -HOUSING-CONTROL BOX t ~ 2 1 ADJ 3 5 ~ 3 5 ~ 303P32 I I IKNOB-RHEOSTAT 1350-5561REfll I I RESISTOR.47,ODO. IIPWATT I R22 I I I I I 1 I I ' . ._ 5 0 H.I 1H41 60 Hzi(H31 60 HI, IH41 60Hz. 1H51 230/400V. -240/416V; 2 5 4 /440V, 27?/480V. L3 L3 - NnTF. UNLESS OTHERWISE NOTED, ALL COMPONENTS ARE SHOWN IN THE DE.ENERGIZED , POSITION VOLTAGE RGLTR , - 50 Hz. 1H51 50 Hz.1H41 50Hz.IH31 5 0 HI. IH41 60HZ.IH31 60 H z . ~ H 4 ~ 60 HZ.IH51 LO T5 1 BOARDASSY-PC VOLTAGE CONNECTIONS PHASE __ - 3. 127/220V, 120R08V. 110/190V. 115/2OOV. 1201208V. 127/220V, 139/240V. 110/220V SOHz IH6l =115/230< 50Hz:IH6l 1% 120/240V, 6 0 H z . !H5l SELEZR- i 3 ~ 3 ~ 1 s zii - I i RHEOSTAT-VOLTAGE 33201956 NOTE CONNECT LEAD W12 FROM TERMINAL T821.63 TO TL12I.IH-I PER VOLTAGE CHART BELOW I ' 60 Hz -01 I PfNN 6& Ik ps 545A22 1. I%R% L%T -AC CONT HOW. 1110/220V 51% I I5123OV: 5 0 H z (H61 50 H:I IH61 15R120/240V. 60H1. 1H51 -- CONTROL BOX (INSIDE) I C I t 1 I'li TOVRZl ' I HOUSING-CONTROL BOX EXCITER WI2-NOTE. SEE VOLTAGE CHART z GENERATOR I 545A23 I I, I I I !WRTS I LIST-AC CONT HDW SCHEMATIC DIAGRAM C O N T R O L BOX IINS-IEE 0 \ ‘2 T pk/3D1II1LIM.$GiE7K-.S.O-.OOYI 302-0466 P VR21 WIZ I I 1 I I I 1 I I I I I I ! I I I i I I -- L2 : TIME 1332-19SS( D I I BOARD 4SSY-PC VOLTAGE RGLTR I I 1 I 1330-076S D I WIRING HARNESS (336-1913 A I I I L E A 0 ASSY I -- USING-CONTROL BOX METER-RUNNING { ZOEG-Z19 LL O GENERATOR I CR4 CRS CR6 F:: VOLTAGE CONNECTION 1201240 V ALTERNATOR. FIELD T2 T2 L2 . NOTE: UNLESS OTHERWISE NOTED, ALL COMPONENTSARE SHOWN IN THE DE-ENERGIZED POSITION. (WIRING DIAGRAM) l20/24CV. IPH. .- 612-5302 12-5303 I REAR WIRING DIAGRAM VILE --- PANEL SCHEMATIC DIAGRAM , C O N T R O L BOX I I N S I D E I A C CONTROL PARTS 1151 EXCITER ARMATURE 1wF/ FI 2 ~ = FOR VR SYSTEM SCHEMATIC SE -24S(Dl / I 621 L21 I T2 I I I I I lGENERATOR I I REACTOR A S S 1 COMY 1 I I I I EOES-119 : CT22 1 TO GENERATOR I VOLTAGE CONNECTION 1201240 V l I B1 \ CT22 l 1 I 1 1315-0384 -2J7g TI i I CfYRlPllON CIRCUIT BREAKER,ZA LOCK-CKT BRKR HANDLE(PENN STATE1 RECTIFIER BRIDGE TRANSFORUER A S S I - C U R I I I I I M z3 ] I USING.CONIROLBOX u 0 P C B 1 I ALTERNATOR FIELD I :,' an. Ii WI2 I - PART NO. CB21 320.0431 320-0307 CR21 105-0524 CT21.22 3 0 2 - 0 7 3 9 KEf. C f S . D .U C T 2L2 2 I I I I I I 512-5304 I WIRING DIAGRAM REAR VIEW-YNEL SCHEMATIC DIAGRAM CONTROL BOX IINSIDEI EXCITER ,, FOR VR SEE625-1245101 SYSTEM SCHEMATIC 621 O f CR21 303-00761 - ' SWITCH-VOLTMETER I I SELECTOR KNOB I I I 1 I I I M22 v I I HOUSING-CONTROL BOX I I I I I I I I I I . : I I I I I I I I I I GENERATOR VOLTAGE CONNECTION 3 PHASE, 3 4 7 / 6 0 0 V I ALTERNATOR FIELD T3 67.1 9 TO 65 'I I NOTE: UNLESS OTHERWISE NOTED, A L L COMPONENTS A R E SHOWN IN THE DE-ENERGIZED POSITION. I I I I I - ItOES 2 19 I I 612-5305 I REAR_VI_EW PANEL SCHEMATIC DIAGRAM CONTROL BOX l!NSIDE) fI 8 r- WIRING DIAGRAM I 'G21 I K T21 b A I L21 M23 TO VR21 I lG M --USING-CONTROL EXClIER F+ GENERATOR I REACTOR ASSYCOMM I I BOX M22 - 3020779 P I . ~~LTMETER+C.O-75OV I300V MOVEMENT) M23 302-0221 B M24 3024466 P I I METER-FkEOUENCVf240) METER-RUNHINO TIME ( 2 4 0 V l F --- I L3 ^- I I w12 n EXCITER ......-.. I 1115-03841 81 I I 1 nrr I II I i I I I I I I I I I t I I VOLTAGE CONNECTION 3PHASE.S47/600V, 60Hr ALTERNATOR FIELO 65 l C T 2 3 5 KW 2535 36-55 56-70 71-110 60H -01 PLNNW L3 . . NOTE: -02 -03 -04 -07 -08 -09 -10 Ill -145 -05 -11 POSITION. 146-180 -06 -12 ALL COMPONENTS ARE SHOWN B ~ U S ~ L ~ S S I N THE DE-ENERGIZE0 347/ECOV, 4W.,60 HZ 3 P H , (WIRING DIAGRAM) OWL 612-5305 1 I I ! j I 0 2 2 72 . N Redistribution or publication of this document, by any means, is strictly prohibited. S S 3 M d 110 0 1 9 d W 3 1 OR3 l H ' O 3 3 d S Y 3 A O ' n N V Y 3 Y 3 A O NO S W Y V l V B AMOOlllHS ,413315 Z'E'b I 03511 N ~ I M . S S 3 Y d 110 01 9 d W 3 1 N 3 I H N O S W Y V l V - 3 Y d A 1 3 3 V S I'E'b l O Y l N 0 3 W Y V l V - 3 Y d E'b d W 3 2 O N 3 0 1 6 S S 3 Y d 110 O l W 3 1 O N 3 I H N O S W M V l V ,413315 2.Z.b 0 3 3 d S Y 3 A 0 6 X N V t ( 3 Y 3 A 0 NO 5 W Y l l V 9 N M O a l n H S A 1 3 3 V S 1'2'b l O Y l N 0 3 3 1 V l S N N 3 d Z'b dW31 9 N 3 01 NO A l N O W Y V l V A l 3 j V S Z7.b SS3Yd 110 0 1 9 dW31 O N 3 I H ' a 3 3 d S Y 3 A O 1 Y N 1 Y 3 Y 3 A O 0 S W Y V l V 9 N M O O l n H S ,41331s 1'1% 1 0 Y l N 0 3 01s I'b S W Y V l V 6 NM001nHS'b XVW dWVS 0 3 1 V Y lln3Y13 W Y V l V 310W3Y'E A l N O l O Y l N 0 3 W Y V l V - 3 Y d NO a 3 S l l ' Z A i N o ~ O Y I N O ~ ais NO a 3 s n Z I M ' I S310h - -_ I - a ONllVYPNB d N 3 1 9N3 0' d A 3 1 I N 3 I1 S53Md 110 MO XNVM3M3A( -7NOW.03 WYVlV ON9 E 310N 8 WlV k- IIW . NOI+ISOd 03ZIDM3N3-30 3 H l NI NMOHS 3MV SlN3NOdW63 111 ' 0 3 1 0 N 3SIMU3HlO S S 3 l N f l 'C 1 1 3 0 dN3 U01VM3N3B N1 03LNflOW HJllMS 033dSM3AO €S 'E S S 3 t l d l l O 01 B dW32 3 ~ IH3 NO wnviv AIPJVS z z z 033dSM3AO 9)INVt13L13hO NO W W l V B NMOOlflHS A 1 3 d V S 1'2'2 l O M l N 0 3 31VlS NN3d 2'1 SS3Ud 110 0 1 B d W 3 1 BN3 IH'a33dSM~AO1HNVM3n3AO 0 WLlVlV 9 NMOOLnHS A 1 3 N S 1.1'7. 1 0 ~ ~ ais 0 31.1 S H M V l V B NMOOlflHS '1 xvw dKJS 031V8 Llfl3M13 W W l V 310W3M 'I :S310N 3VA OCZ-061 1201 NO E9 W 29 wn3i 01 4-I -- I I .... . . .. . - .~ .. . -L w > I . t 75 Redistribution or publication of this document, by any means, is strictly prohibited. Redistribution or publication of this document, by any means, is strictly prohibited. c Redistribution or publication of this document, by any means, is strictly prohibited. i Onan Corporation 1400 73rd Avenue N. E. Minneapolis, MN 55432 612-574-5000 Telex: 275477 Fax: 612-574-8087 Onan is a registered trademark Of Onan Corporation Redistribution or publication of this document, by any means, is strictly prohibited.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Modify Date : 2005:01:05 10:12:16-06:00 Create Date : 2005:01:04 14:36:46-06:00 Creator : Acrobat Capture 3.0 Style : Searchable Image (Compact) Page Count : 81 Page Mode : UseOutlines Mod Date : 2005:01:05 10:12:16-06:00 Creation Date : 2005:01:04 14:36:46-06:00 Producer : Adobe PDF Library 4.0 Metadata Date : 2005:01:05 10:12:16-06:00 Has XFA : NoEXIF Metadata provided by EXIF.tools