Onan UR Generator Manual Pub 900 0150
900-0150 Onan UR (25 to 180KW) Generator & Controls Service Manual (10-1978) 900-0150 Onan UR (25 to 180KW) Generator & Controls Service Manual (10-1978)
User Manual: Onan-UR-Generator-Manual-pub-900-0150 Onan
Open the PDF directly: View PDF .
Page Count: 81
- Cover
- Safety Precautions
- Table of Contents
- Introduction
- Generator Section I
- Question and Answer Troubleshooting Guide
- Adjustments and Procedures
- Generator Section II
- Question and Answer Troubleshooting Guides
- Adjustments and Procedures Section II Only
- Index of Generator Adjustments and Procedures
- Controls Section III
- Question and Answer Troubleshooting Guide
- Adjustments and Procedures
- Wiring Diagrams
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings
according to the size of each page you wish to print.
Redistribution or publication of this document,
by any means, is strictly prohibited.
Service
Manual
25to
I80
kW
Generators
And
Controls
Troubleshooting and
Test Procedures For
Generators
Regulator
Controls
900-0150
10-78
Printed
in
U.SA
Redistribution or publication of this document,
by any means, is strictly prohibited.
Safety Precautions
The following symbols
in
this manual highlight con-
ditions potentially dangerous
to
service personnel, or
equipment. Read this manual carefully. Know when
these conditions can exist. Then take necessary
steps to protect
I
WARNING1
personal injury.
personnel as well as equipment.
equipment damage.
This symbol is used throughout the
manual
to
warn
of
possible serious
This symbol refers to possible
PROTECT AGAINST MOVING PARTS
Avoid moving parts of the unit. Avoid use of loose
jackets, shirts or sleeves due to danger of becoming
caught
in
moving parts.
Make sure all nuts and bolts are secure. Keep power
shields and guards
in
position.
If
you
must make adjustments while the unit is
running, use extreme caution around hot manifolds,
moving parts, etc.
Do not work on this equipment when mentally or
physically fatigued.
Y
GUARD AGAINST
ELECTRIC
SHOCK
Disconnect electric power before removing protec-
tive shields or touching electrical equipment.
Use
rubber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around
electrical equipment.
Do
not wear damp clothing
(particularly wet shoes) or allow skin surfaces to be
damp when handling electrical equipment.
..
Disconnect batteries to prevent accidental engine
start. Jewelry is a good conductor of electricity and
should be removed before working on electrical
equipment.
Use extreme caution when working on electrical
components. High voltages cause injury or death.
Follow
all state and local codes. To avoid possible
personal injury or equipment damage, a qualified
electrician or an authorized service representative
must perform installation and all service.
EXHAUST GAS
IS
DEADLY!
Exhaust gases contain carbon monoxide,
a
poisonous gas that might cause
unconsciousness and death. It is an odorless and colorless gas formed during
combustion of hydrocarbon fuels. Symptoms of carbon monoxide poisoning
are:
Dizziness Vomiting
Headache Muscular Twitching
Weakness and Sleepiness Throbbing in Temples
If you experience any of these symptoms, get out into fresh air immediately,
shut down the unit and do not use until it has been inspected..
The best protection agalnst carbon monoxide inhalation Is proper installallon
and regular, frequent visual and audible inspections of the complete exhaust
system. If
you
notice
a
change in the sound
or
appearance
of
exhaust system,
shut the unit down immediately and have it inspected and repaired at once by a
competent mechanlc.
Redistribution or publication of this document,
by any means, is strictly prohibited.
.
GENERATORS
AND
CONTROLS
25
kW
-
180
kW
TABLE
OF
CONTENTS
'
PAGE
'
Introduction
..........................................
:
................
2
.
Generator
-
Section
I
.................................................
5
Question and Answer Troubleshooting Guides.
..........................
8
Adjustments and Procedures
............................................
16
Generator
-
Section
II
...............................................
26
Question and Answer Troubleshooting Guides.
.........................
27
Adjustments and Procedures
...........................................
35
Index
of
Generator Adjustments and Procedures.
.......................
38
Control
-
Section
111
.................................................
39
Question and Answer Troubleshooting Guides.
.........................
40
Adjustments and Procedures
..........................................
51
Wiring Diagrams
.....................................................
53
.
I
I
ONAN RECOMMENDS THAT ALL SERVICE, INCLUDING
INSTALLATION
OF
REPLACEMENT PARTS, BE PERFORMED
BY
QUALIFIED PERSONNEL.
I
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
NTRO
DU
CTIO
N
FOREWORD
This manual provicds troubleshooting and repair
information for ONAN series
UR
generators. It is
intended to provide the maintenance technician,
serviceman or Onan distributor with a logical
procedure to enable him
to
systematically locate and
'
'repair malfunctions
in
the generator and control
systems. This information is not applicable to the
prime mover; refer to the engine manufacturer's
manual.
Repair information is not extensive because the plug-
in solid-state printed circuit modules lend themselves
more to replacement than repair. ONAN does not
recommend repair
of
the printed circuit module,
except at the factory and has initiated a returdex-
change service, obtainable through distributors,
whereby faulty modules can be returned and ex-
changed for good units.
For
more information, con-
tact your distributororthe ONAN service department.
,
Application
of
meters or high heat soldering
irons
to
modules
by
other than qualified
personnel can result in unnecessary and expensive damage.
This
rnanual is arranged
as
follows:
i.
GENERATOR
-
Section
I
contains general
specifications
on
the
UR
generator,
troubleshooting guides and procedures for
testing and repairing of the early
UR
generator
with
VR22
exciter regulator and general informa-
tion on later
UR
generator.
Section
11
contains
troubleshooting information for the later model
UR
generator where the exciter diode rectifier
assembly has been relocated into the contrd
panel.
Refer
to
Table
1
for
a
description of
t/:f.
appropriate section for your generator.
2.
CONTROLS
-
Section
111
contai!$s
troubleshooting guides and procedures
lor
testing and repairing the system controls,
P
description of the components and an analysiz'
ti+
the module circuitry is included.
TEST EQUIPMENT
Most
of
the tests outlined
in
this manual can be
performed with an AC-DC multimeter such as a
Simpson
260
VOM.
Other suggested test instruments are
-
ONAN multitester Part No.
420-0303
Wheatstone or Kelvin bridge
Exercise care when purchasing
a
foreign
made
VOM.
Some units deliver
+9VDC,
others,
+22VDC
to the circuit under test
on
R
x
1
scale. Maximum
recommended voltage is
+l.SVDC.
Damage
to
solid state devices
can result from excessive voltage application.
GENERATING SET
MALFUNCTION
GENERATOR
FAILS
SEE GENERATOR
SECTION
I
OR
II
ENGINE FAILS
SEE
ENGINE
I
SERVICE MANUAL
I
I'
CONTROL FAILS
CONTROL SECTION
Ill
2
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
1.
GENERATOR SPECIFICATION BREAKDOWN
kW
Model
25.0
EK
30.0 EK
Penn EK
25.0 DDA
30.0
DDB
30.0 DEH
25.0
MDEH
30.0 MDEH
Penn DEH
37.5
EM
45.0 EM
Penn EM
37.5 DEF
45.0
DEF
Penn DEF
37.5 DYJ
45.0
DYJ
40.0
DDB
50.0
DDB
40.0
DEG
50.0 DEG
Penn DEG
40.0
MDEG
50.0 MDEG
45.0 KB
55.0 KB
Penn KB
50.0
DYA
60.0 DYA
Penn DYA
55.0
EN
70.0 EN
50
Hz
60 Hz
50
Hz
60
Hz
60
Hz
50
Hz
60 Hz
50
Hz
60 Hz
50
Hz
60
Hz
50
Hz
60
Hz
50
Hz
60
Hz
50
Hz
60
Hz
50
Hz
60 Hz
50
Hz
60 Hz
50
Hz
60 Hz
60 Hz
60 Hz
E
D
E
-
-
D
D
C
E
E
D
E
H
F
G
-
-
-
-
G
E
F
F
E
R
P
Q
E
C
D
-
-
Section
1
Spec
A
Frequency
Section
2
Begin
Spec
F
F
F
A
A
G
G
G
G
F
F
F
J
J
J
A
A
A
A
H
H
H
H
H
S
S
S
F
F
F
A
A
kW
Model
55.0
KB
55.0
KB
"enn KB
50.0
DYC
75.0
DYC
30.0
DYC
100.0
DYC
'enn DYC
70.0
KR
35.0
KR
Penn KR
75.0
DYC
30.0
DYC
30.0
DYD
100.0
DYD
Penn DYD
35.0
WA
11
5.0
WA
100.0 DYD
125.0 DYD
Penn DYD
115.0 WE
140.0 WE
125.0 WE
150.0 WE
125.0 DYG
150.0 DYG
Penn DYG
130.0 DFE
155.0 DFE
Penn DFE
140.0 WB
170.0 WB
145.0 DYG
175.0 DYG
Penn DYG
150.0 DFE
180.0 DFE
Penn DFE
Section
1
Spec
A
Frequency
1
ThN
'
50
Hz
60
Hz
50
Hz
60
Hz
50Hz
'
60
Hz
50
Hz
60 Hz
50
Hz
60
Hz
50
Hz
60 Hz
50
Hz
60 Hz
50
Hz
60
Hz
50
Hz
60
Hz
50
Hz
60
Hz
50
Hz-
60'HZ
50 Hz
60 Hz
50
Hz
60 Hz
50
Hz
60 Hz
50
Hz
60 Hz
R
P
Q
D
B
-
-
jc
R
P
Q
D
B
C
A
B
H
G
C
A
B
B
B
B
B
C
A
B
-
-
-
K
J
C
A
B
-
-
-
Section
2
Begin
Spec
S
S
S
E
E
G
G
'E
S
S
S
E
E
.D
D
D
J
J
D
D
D
-
-
-
-
D
D
D
H
H
H
L
L
D
D
D
H
H
H
3
Redistribution or publication of this document,
by any means, is strictly prohibited.
UR G’ENERATOR VOLTAGE/CURRENT OPTIONS
1-PHASE 3-PHASE
1-PHASE
STANDARD
@@
2K
156
234
I_
:ode
15
60
-
-
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
HE
:ode
50
-
515
-
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
SPE
-
0
g
-
142
21 3
227
256
284
31 3
355
398
426
455
540
568
L
0
-
156
234
260
286
313
339
365
391
443
469
521
599
625
RATING
-
c
g
-
90
135
144
162
180
198
226
253
271
289
343
361
415
451
469
505
523
541
-
0
g
-
82
123
131
148
164
180
205
230
246
262
31 2
328
377
41
0
426
459
476
492
-
0
g
-
78
118
126
141
157
173
196
220
235
251
298
314
361
392
408
439
455
471
-
@
g
-
90
135
150
165
180
195
210
226
256
271
301
346
376
421
451
466
51
1
526
542
-
g
-
47
71
76
85
95
104
119
133
142
152
’
180
190
218
237
247
266
275
285
-
c
-
95
142
152
171
190
209
237
266
285
304
361
380
437
475
494
532
551
570
-
0
-
82
98
123
131
148
164
180
197
205
213
230
246
262
279
295
312
328
377
410
426
459
476
492
508
558
574
591
-
c
-
45
68
72
81
90
99
113
126
135
144
171
180
207
226
235
253
262
271
-
E
-
43
.
52
65
69
78
87
95
104
108
113
121
130
139
147
156
165
173
200
217
226
243
252
260
269
295
304
313
-
E
g
-
45
68
75
83
90
98
105
113
128
135
150.
173
188
210
226
233
256
263
271
-
E
-
41
49
62
66
74
82
90
98
103
107
115
123
131
139
148
156
164
189
205
213
230
238
246
254
279
287
296
a
g
-
136
204
21 7
245
272
299
340
380
408
435
516
543
0
-
E7
.
104
130
139
156
173
191
208
217
226
243
260
278
295
312
330
347
399
434
451
486
503
520
538
590
607
625
g
-
90
135
150
165
180
195
210
226
256
27
1
301
346
-.
376
42 1
451
466
51 1
526
542
ky
600
- -
36
54
60
66
72
78
84
90
102
108
120
138
150
168
180
186
204
210
217
-
kW
25.0
30.0
37.5
40.0
45.0
50.0
55.0
60.0
62.5
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
115.0
120.0
125.0
130.0
140.0
145.0
150.0
155.0
170.0
175.0
180.0.
kVA
31.25
37.50
46.80
50.0
56.25
62.5
68.75
75.0
78.13
81.25
87.5
93.75
100.0
106.25
112,5
11 8.75
125.0
143.75
150.0
156.25
162.50
175.0
181.25
187.5
193.75
212.5
218.75
225.25
4
0
-
,:o
HZ
only.
@
-
60
Hz
only.
@
-
50-
and
60
Hz
@
-
Not
Reconnectible.
.
.
.
.
.
-
.
.
..
..
-.
Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERATOR
v
GENERAL
There are two generator designs used
on
the
UR
series. They are basically the same except for the
method of field excitation.
,
The
Static Exciter
(brush type) design uses a brush
rig and collector rings for field excitation. This design
was
used on some of the earlier models within the
range of 25
KW
-
90
KW.
The Brushlessdesign uses a rotating rectifier exciter
assembly
in
place of the brush rig for field excitation.
The brushless design is standard on all models from
25
KW
-
175
KW.
.
Unless otherwise specified, the tests in this section apply to both
designs.
V R
-22
EXCITER REGULATOR
CHASSIS ASSEMBLY END
B
ELL
.TOR
-
SECTION
I
COMPONENT LOCATION
To
gain access to generator, remove grille section
below control box.
1.
2.
3.
4.
Exciter-regulator chassis assembly VR22 mounts
on the rear portion of the generator; SCR’s
(silicon controlled rectifiers) and diodes are easi-
ly accessible for testing. See Figures
1-3.
On static-excited generators, brush”es attach to
the brush rig inside of end bell housing; inspect
through large access holes in the end bell. See
Figure
1.
On brushless models, rotating exciter assembly
mounts directly behind exciter-regulator chassis
assembly with all diodes accessible for servicing.
See Figure
2.
Voltage-regulator PC Board VR21 (Printed Cir-
cuit Board) mounts inside the control box on the
rear panel (left side); turn
114
turn fasteners o,n
front of control box to gain access. See Figure
4.
AC
STATOR
L
OUTPUT
-
208-240
VOLTS
‘\--
RESIDUAL MAGNETISM AC
IN ROTOR STARTS
PROCESS
,
&
~
SOLID STATE
4ND VOLTAGE
REGULATOR
REVOLVING FIELD OVERSPEED SWITCH
QENERATOR END
VIEW
(QRILLE REMOVED) EXCITATION SCHEMATIC
FIGURE
1.
STATIC EXCITER
DESIGN
5
Redistribution or publication of this document,
by any means, is strictly prohibited.
EXCl TE
R-
REGU LATO
R
CHASSIS ASSEMBLY FENDBELL
QENERATOR END VIEW (QRILLE REMOVED)
I
A
LT
ERN AT0 R
iTATOR
w
FIELD
I
.
208-240
VOLTS
AC
EXCITER
CIRCUIT
BREAKER
EXCITER
ARMATURE
VOLTAGE
R E(3U LATOR
~~~
EXCITATION SCHEMATIC
t
CHECK THESE SINGLE LEAD RECTIFIERS
ACCORDING TO PROCEDURE "E"
FIGURE
3.
TOP VIEW OF EXCITER-REGULATOR CHASSIS ASSEMBLY
V R21
VOLTAGE REGULATOR
PRINTED CIRCUIT
BOARD
,
!
!
i
'FIGURE
4.
VOLTAGE REGULATOR PRINTED CIRCUIT BOARD LOCATION
6,
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
I
VISUAL
INSPECTION
Before proceeding with the troubleshooting on the
following pages, a few simple checks can be made
which could directly indicate the cause'of trouble.
1.
Always be sure that connection of generator
leads is correct. Whenever leads are reconnected
for a different voltage, check the output with an
independent voltmeter.
Do
not use the control
panel meter since it could indicate that the
voltage is correct even
if
connection is wrong.
2.
Visually inspect the voltage regulator printed
circuit board assembly (VR21)
in
the control box
for
burned components, broken wires, loose
connections, dust, dirt
or
moisture.
If
dirty, clean
with a suitable solvent and compressed air.
3.
Visually inspect the exciter-regulator chassis
assembly
(VR22)
for burned components, broken
wires, loose connections, carbon tracks caused
by arcing between parts
or
between parts and
ground.
Also
check for shorted paths between
terminals caused by dust, dirt and moisture.
4.
Large banks of SCR (Silicon Controlled Rectifier)
regulated loads can cause the generator voltage
to increase as load is applied.
If
such loads exist,
and the voltage increased more than
5
or
lo%,
consult the factory; an additional filter is available
for the regulator circuit to correct the situation.
THE QUESTION AND ANSWER TROUBLESHOOTING GUIDES BEGINNING
ON PAGE
8
GIVE A STEP-BY-STEP PROCEDURE FOR CHECKING THE
GENERATOR. THE FLOW-CHART TROUBLESHOOTING GUIDES ARE
GIVEN AS
A
GENERAL GUIDE TO RESOLVE VARIOUS GENERATOR
PROBLEMS. ALL CHARTS REFER TO PROCEDURESSHOWN AT THE END
OF
THIS SECTION.
.
PRIOR TO ANY TROUBLESHOOTING, CHECK ALL MODIFICATIONS,
REPAIRS, REPLACEMENTS, ETC.. PERFORMED
SINCE
LAST SATISFAC-
TORY OPERATION OF SET.
7
Redistribution or publication of this document,
by any means, is strictly prohibited.
QUESTION AND ANSWER TROUBLESHOOTING GUIDE
To
correct a particular problem, answer the question either “yes”
or
“no,” then proceed to the next step given in
‘LiM
I
TABLE
A.
NO OUTPUT VOLTAGE
-
ENGINE RUNNING
.-
whichever column question was answered. Procedures A thru P follow the troubleshooting guide.
~~
YES NO PROCEDURt
Are diodes CR1, CR2 and CR3 on VR22 exciter-regulator chassis
assembly
OK?
Are SCR’s
Q4
and
Q5
on VR22 exciter-regulator chassis
-
assembly
OK?
1.
2.
3.
4.
5.
8
9
6.
7.
8.
9.
10.
11.
13
Is circuit breaker on the meter panel in the
“on”
position?
‘
I
Switch circuit breaker to the “on” position.
Does AC voltage build up?
NOTE:
If voltage builds up, but is high, low
or
unstable,
or
causes
the circuit breaker on the meter panel to
trip,
refer to
Table
“B,”
“C’
or
“D” of the troubleshooting guide.
I
I
Is AC voltage at terminals
1
and 2, on VR21 voltage regulator
printed circuit board and at terminals
9
and
10
on VR22 exciter-
regulator chassis assembly
5
to 10 volts?
5
~~ ~~
Check continuity of wires and connections between terminal
1
on
VR21 printed circuit board and terminal
9
on VR22 chassis
assembly; and between terminal 2 on VR21 printed circuit board
.
and terminal 10 on VR22 chassis assembly.
Is
there continuity
between these connections?
Check for broken wires and loose connections on VR22 exciter-
regulator chassis assembly. Replace
or
repair any that are
defective and clean all dust, dirt and other foreign material
from the assembly. Does AC voltage now
build
up?
Is DC voltage at terminals
4
and
5
on VR22 exciter-
regulator chassis assembly
5
to
10
volts?
I
l3
The trouble is probably caused by a defective component on
the voltage regulator printed circuit board.
REPLACE VR21 PRINTED CIRCUIT BOARD (see Figure
4).
With the circuit breaker on the meter panel
in
the “off” position,
is
AC voltage at terminals 62 and 63 (on
,
terminal board
TB21
on
the left side of control box)
5
to 10 volts?
With the circuit breaker on the meter panel
in
the “off” position,
flash the exciter field.
Is
AC voltage at terminals 62 and 63
now
5
to 10 volts? 12
10
6
11
13
C
F
B
8
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
A.
NO
OUTPUT
VOLTAGE
-
ENGINE
RUNNING
(continued)
YES
NO
PROCEDURE
Turn circuit breaker on the meter panel to the “on” position.
Does
AC
output voltage build up?
NOTE:
If
voltage builds up, but
is
high, low
or
unstable,
or
causes circuit breakerto trip. refer
to
table
“B.”
“C”
or
“D”
of
this troubleshooting guide.
Is
brushless exciter stator winding
OK?
With a jumper wire connected across the terminals
of
the circuit
breaker on the meter panel, does voltage build up?
NOTE:
If
voltage does build up, the circuit breaker
CB21
is defective and
MUST
BE
REPLACED.
~
~-
Is
11
commutating reactor mounted on the back side
of
VR22
exciter-regulator chassis assembly
OK?
Check continuity of wires and connections between
1821
terminal
62
on left side of control box and terminal
1
on
VR21
printed
circuit board.
Also
check between
TB21
terminal
63
on the left
side of control box and terminal
2
on
VR21
printed
circuit board.
Are rotating diodes
CR1,
CR2,
CR3,
CR4,
CR5
and
CR6
on
brushless exciter rotor
OK?
Is
generator field winding
OK?
Is
brushless exciter rotor winding
OK?
Are generator stator windings
OK?
17
18
19
20
D
E
G
J
H
9
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
A.
SYNOPSIS
NO AC
POWER
TO
EXCITER
LOSS OF
RESIDUAL
VOLTAGE
(FLASH
FIELD)
BRUSHES
OR
LOOSE
BRUSH
-I-
CB2l
CIRCUIT
BREAKER
ON METER
PANEL IN
"OFF"
POSITION
(RESET)
++
DEFECTIVE
CIRCUIT
BREAKER
ON METER
PANEL
1
NOTE: Whenever a letter appears near the box, a separate procedure,
corresponding to that letter, is given at the end
of
this section.
*
-
Check
SCR's,
Q4
and
Q5
on
VR22
voltage regulator chassis assembly
and replace
(if
defective) before repairing or replacing
VR21
voltage
regulator printed circuit board.
**
-
Static excited generators
only.
FAULT IN
GENERATOR
FIELD
WINDING
n
DEFECTIVE
COMPONENT
ON
REGULATOR
PC
BOARD
(VR21)
I
COMPONENT
VOLTAGE
REGULATOR
CHASSIS
ASSEMBLY
BUILD-UP
RELAY, K1
CR8
OR
CR9
OPEN
Rl,
R2
OR R3
OPEN
PC BOARD
P
TERM"ALS
1
OR
2
I
Q4
OR
Q5
-I
FAULTY
ROTATl NG
DIODE
ON
BRUSHLESS
EXCITER
A
DEFECTIVE
DIODE CR1
/E\
OPEN LEAD
TERMINAL
1,
2,4,5
FAULT IN
BRUSHLESS
EXCITER
ROTOR
OR
STATOR
WINDING
.
-..
__
...
Redistribution or publication of this document,
by any means, is strictly prohibited.
L
t
18
:
i
ITEM TABLE
B.
OUTPUT VOLTAGE BUILDS UP BUT IS UNSTABLE
-
YES NO PROCEDURE
NO. ENGINE RUNNING
OK
I
Are there any loose
or
broken wires
or
connections at
VR21
printed circuit board terminals?
I
I
2.
Does adjustment of
R26*
(damping control pot) on
VR21
printed
circuit board result in stable generator voltage?
I
I
I
3.
The trouble is probably caused by a defective component on
VR21
voltage regulator printed circuit board.
REPLACE
VR21
PRINTED CIRCUIT
BOARD
(see Figure 4).
I
I
-
R26
is
used on brushless generators
only.
TABLE
B.
SYNOPSIS
UNSTABLE OUTPUT
VOLTAGE
7:
i
!
DEFECTIVE COMPONENT
ON (VR21) VOLTAGE
REGULATOR PRINTED
CIRCUIT BOARD
I
C6. C7, R14
OR
R1S
OPEN
C11, C12, R27
OR
R28
OPEN
BROKEN WIRES
OR
LOOSE CONNECTIONS
AT (VR21) VOLTAGE
REGULATOR PRINTED
CIRCUIT BOARD
TERMINALS
INCORRECT SETTING
OF R26 POT ON (VR21)
PRINTED CIRCUIT
BOARD (BRUSHLESS ONLY)
NOTE: Whenever a letter appears near the
box,
a separate procedure, corresponding
to that letter,
is
given at the end
of
this section.
Redistribution or publication of this document,
by any means, is strictly prohibited.
F
5.
-
TABLE C. OUTPUT BUILDS UP BUT
IS
HIGH
OR
LOW
-
ENGINE RUNNING
OK
YES
I
Does adjustment of R21 "Voltage Adjust" knob on the meter
panel result in correct voltage?
Does adjustment
of
Rlb
potentiometer on VR21 printed circuit
-
board result in correct voltage?
-
-
Is
correct voltage reference transformer tap on TB21
being used?
4
Are generator output leads properly connected?
5
NO PROCEDURE
2
3
P
L
L
-
-
TABLE
C.
SYNOPSIS
TOO
HIGH
OR
I
I
I
I
I
I
INCORRECT
REFERENCE
TRANSFORMER TAP
ON
T21
INCORRECT
SETTING OF
VOLTAGE ADJUST
POT (R21) ON
METER PANEL
INCORRECT
SETTING
OF
VOLTAGE ADJUST
POT
(R18)
ON
VR21 PC BOARD
I
DEFECTIVE DEFECTIVE
COMPONENT ON COMPONENT ON
REGULATOR CHASSIS REGULATOR PC
ASSEMBLY (VR22) BOARD (VR21)
CONNECTION AT
TERMINALS
3,4,.
.
I
.I
--
.
..
I
..
!
NOTE
Whenever a letter appears near the
box,
a separate procedure, corresponding
to that letter,
is
given at the end
of
this section.
12
Redistribution or publication of this document,
by any means, is strictly prohibited.
NO:
TABLE D. GENERATOR VOLTAGE BUILDS
UP
BUT CAUSES THE CIRCUIT BREAKER
ON
CONTROL PANEL
TO
TRIP.
ENGINE RUNNING
OK.
ITEM
I
3.
4.
Does AC output voltage build up to 150% or more of rated
voltage before CB21 circuit breaker trips?
Is
diode CR3 on center heat sink of VR22 exciter-regulator
chassis assembly
OK?
Are voltage regulator transformer (T21) windings and
connections
OK?
2.
.
Are
there any loose or broken terminals or connections at VR21
1,
voltage regulator printed circuit board terminals?
~
5.
~
Are stator leads connected properly?
6.
The
trouble is probably caused by a defective component
on
VR21 voltage regulator printed circuit board. REPLACE VR21
PRINTED CIRCUIT BOARD (see Figure 4).
I
8.
Does
AC
output voltage build up to rated voltage or less
before tripping CB21 circuit breaker
on
meter panel?
Are rotating diodes CR1, CR2, CR3, CR4, CR5 and CR6 on
brushless exciter rotor
OK?
9.
.
10..
Is
brushless exciter stator winding
OK?
Is
generator field winding
OK?
11.
DEFECTIVE
ROTATING DIODE
CR1, CR2, CR3,
CR4, CR5
OR
CR6
ON
EXCITER
ROTOR
Is
brushless exciter rotor winding
OK?
l-l
FAULT IN
EXCITER ROTOR
OR
STATOR
WINDING
FAULT IN
GENERATOR
MAIN FIELD
WINDING
A
NOTE:
Whenever a letter appears near the box, a separate procedure, corresponding
to that letter, is given at the end
of
this section.
13
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO.
1..
-.
-
TABLE
E.
UNBALANCED GENERATOR TERMINAL VOLTAGE
YES
2.
3.
NO PROCEDURE
4.
5.
_________
~~ ~
Are generator leads properly connected and/or grounded?
Is
continuity of generator stator windings
OK?
-
3
H
- -
Remove load from 'generator terminals. Are genefator'terminal
voltages still unbalanced?
UNBALANCED
TERMINAL VOLTAGES
*
I
*141
INCORRECT GROUNDING
OF LOAD
OR
GROUND
FAULT IN LOAD
'
FAULTY GENERATOR
STATOR WINDING
t
I
51--1
I
Is grounding procedure of generator and load correct?
~~~
Check
for ground faults in load.
1-14
I'
,
ji
*
NOTE:
Unbalanced voltages of up to
5
percent will occur if unbalanced loads
are applied to the generator terminals.
TABLE
E.
SYNOPSIS
INCORRECT RECONNECTION
OR
GROUNDING OF
GENERATOR LEADS
I
\
,
NOTE:
Whenever
a
letter appears near the
box,
a separate procedure,
corresponding to that letter, is given at the end of this section.
14
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
E.
SYNOPSIS
1
I
OPEN
IN
R21 DEFECTIVE COMPONENT
OPEN LEAD AT
(VR21)
PRINTED CIRCUIT
BOARD TERMINALS
1,
2,
5,
7
OR
8
ON VR21 PRINTED
VOLTAGE ADJUST POT
ON METER PANEL CIRCUIT BOARD
<
L
OPEN TRANSFORMER
(T21) WINDING
I
VOLTAGE
150%
I
[;I
MORE
THAN
RATED
I I
1
I
OPEN WIRE
OR
CONNECTION AT
VOLTAGE REGULATOR
CHASSIS ASSEMBLY
(VR22)
TERMINALS
4,5
OR
6
DEFECTIVE COMPONENT
ON VOLTAGE
REGULATOR CHASSIS
r-
ASSEMBLY (VR22)
I
DEFECTIVE COMPONENT
ON VOLTAGE
REGULATOfi PRINTED
CIRCUIT
BOARD
(VR21)
OPEN
WIRE
OR
CONNECTION AT
PRINTED CIRCUIT
BOARD (VR21)
TERMINALS
5,6,
9,10,
11
OR
12
CYCLING
BUILD-UP
*
OPEN IN R18
VOLTAGE ADJUST POT
ON VR21 PRINTED
CIRCUIT BOARD
NOTE Whenever a letter appears near the box, a separate procedure,
corresponding to that letter,
is
given at the end
of
this section.
*
-
Generator voltage builds up. then collapses. builds up. etc.
Redistribution or publication of this document,
by any means, is strictly prohibited.
ADJUSTMENTS
AND
PROCEDURES
BRUSHES
ment.
Do
not use a substitute brush that may look
1
I
When brushes wear to approximately
5/8
inch or
when wear extends into the stamped Onan part
number, replace brushes.
Do
not attempt to remove
the brush without first removing its spring and
brackets. Never bend a spring back over its bracket
-
doing
so
will put a kink in it and require its replace-
identical but may have entirely different electrical
characteristics. Be sure to install the brush
SO
that the
short side of its taper is toward the spring and its
bracket. See Figures
5
and
6.
i
REPLACE
BEFORE
BRUSH
WEARS
TO
THIS
POINT
INSTALL BRUSHES
WITH
BEVELED
TOP
SLANTING
DOWN
TOWARD
SPRING HOLDER-,
TO
REMOVE
BRUSH
SPRING,PRESS
SPRl
NG
HOLDER
DOWN
AND OUT AS
SHOWN
IN
BROKEN
tJ
LINES.
FIGURE
6.
BRUSH REMOVAL
..
.watt resistor in series with diode; or a 24 volt
.
'
'
automotive (generatorset) battery can be used by
increasing the resistor value
to
40-ohms.
FIGURE 5. BRUSH REPLACEMENT
FLASHING THE FIELD (No
Voltage)
If
output voltage will not build up, it may be necessary
'.
to flash the field to restore residual masnetism.
1.
2.
-
Remove end grille to obtain access to'exciter-
regulator chassis assembly:.
Use a six volt
dry
cell (lantern) battery with a 12
amp
300
volt diode as shown
in'
Figure
7.
This
prevents current flow from exciter circuit to
battery when voltage builds up. If a lantern battery
is not available, a 12 volt automotive (generator
set) battery can be used by installing a 20-ohm 2
3.
After starting the set, touch the positive
(+)
lead to
TB5 and the negative
(-)
lead to TB4; hold on
terminals just long enough forvoltage to build up.
Do not keep excitation circuitry connected
longer than 5-seconds or damage
may
occur
to the exciter regulator.
Be cautious when working on agenerator that
is running. High voltages aye present.
CHASSIS
ASS
TO
BUILD
UP.
FIGURE
7.
FLASHING THE FIELD
16
Redistribution or publication of this document,
by any means, is strictly prohibited.
CCI
NO
AC
POWER
TO
EXCITER
Residual should be checked before the circuit breaker; the best
place
to
check
it
is
at the five leads
61
through
65
coming directly
out
of the stator. The combination of leadsshould bechosen by the
wiring configuration of the stator, Le.,
120/240
Delta,
120/208
Parallel Wye.
277/430
Series Wye. After checking residual, proceed
to
VR21
PC
board arid then check the circuit breaker
CB21.
If
residual voltage is present, check AC voltage at
terminals
1
and 2 on VR21 voltage regulator printed
circuit board. Voltage should be
5-10
volts. The AC
voltage at terminals
9
and
10
on VR22 exciter-
regulator chassis assembly should be the same
(5
to
10 volts). If not, check continuity between these
points.
If
voltage is low, check L1 reactor.
TESTING
L1
REACTOR
The
L1
reactor mounts
on
the rear
of
VR22 exciter-
regulator chassis assembly. Terminals are marked
1,
2, 3
and 4.
3h4
Coils 1-2 and 3-4 are wound on the same iron core.
Resistance between 1-2 and
3-4
should be .0544 and
.0614-ohms
f
1O0/o respectively (brush type
generators)
.
LEAD
Resistance between coils (e.g., 1-4)
or
from any
terminai
to
reactor frame should be infinity.
If
any of the above conditions are not met, install a
new reactor.
TESTING
DIODES
On both brushless and brush type generators. three
diodes mount on the center heat sink of the exciter-
regulator chassis assembly. They are labeled CR1,
CR2 and CR3 as shown
in
Figure
3.
On brushless
generators, six diodes mount on the rotating exciter
assembly as shown in Figure 2. These six diodes are
labeled CR1. CR2, CR3, CR4, CR5 and CR6. Test
diodes as follows:
1.
Disconnect one diode at a time. Test that diode
and reconnect lead before proceeding to the next
one.
2. Use an accurate ohmmeter to check the
resistance
of
the diode. Connect one lead to the
top of the diode and the other lead to the heat
sink. Observe reading.
3. Now reverse leads and again observe reading.
A
good diode should have a higher reading
in
one
direction than the other.
If
both readingsare high,
or if both readings are low, diode is defective and
must be replaced with a new, identical part.
Excessive dust or dirt on diodes and other
m
components
will
causeoverheating and even-
tual failure. Keep these assemblies clean!
CAUTION
LEAD
GOOD DIODE WILL HAVE HIGH RESISTANCE READING IN ONE DIRECTION
AND LOW READING WHEN OHMMETER LEADS ARE REVERSED.
FIGURE
8.
TESTING
DIODES
17
Redistribution or publication of this document,
by any means, is strictly prohibited.
0
H
MM ETER
FIGURE
9.
TESTING
SCR’s
[FI
1.
2.
3.
4.
5.
-
ANODE
SHORT BETWEEN
SATE AND ANODE
CATHODE
FIGURE
10.
TESTING
SCR’s
FIGURE
11.
TESTING
SCR’s
TESTING
SCR’s
SCR’s mount on the outer heat sinks of the exciter-
regulator chassis assembly. They are labeled
Q4
and
Q5
as shown in Figure
3.
Remove the leads from both
SCR’s.
Determine polarity of ohmmeter leads. Connect
the ohmmeter leads to the anode and cathode as
shpwn in Figure
9.
Use the high scale on the
ohmmeter. The resistance should be
1
megohm
or greater.
The cathode
is
the longer lead, the gate
is
the shorter lead. The
anode
is
the threaded stud.
Reverse the leads as shown in Figure
10.
The
resistance again should be
1
megohm or greater.
With the leads connected as
in
Step
3,
and using
the low scale on the ohmmeter, short the gate to
the anode as shown in Figure
11.
The resistance
should drop to a
low
value.
Remove the short between the anode and the
gate. The resistance should remain at the same
low
value.
REPLACING RECTIFIERS (SCR’s
and
Diodes)
1.
Unsolder leadwires from terminals.
2.
Use proper size wrenches to hold the body while
removing the nut.
3.
Push the rectifier free of its mounting hole
in
the
heat sink.
4.
Insert new rectifier into its mounting hole in the
heat sink. Using nut and washer provided, secure
rectifier to heat ,sink.
5.
.Torque the two large diodes on the center heat
sink of exciter-regulator chassis assembly to
20-
25
in. Ib.
6.
Torque the small diode on center heat sink
of
exciter-regulator chassis
assemb.ly to
12-15
in.
Ib.
7.
Torque SCR’s on outer heat sinks- to
20-25
in. Ib.
8.
On brushless generators, torque diodes
on
9.
Solder leadwires to new rectifiers.
rotating exciter assembly to
15
in: Ib.
Use a
40
watt soldering iron. Hold
a
needlenose pliers between rectifier and
soldering point to prevent destructive heating. Excessive heat on
these components
will
destroy them.
18
Redistribution or publication of this document,
by any means, is strictly prohibited.
TESTING GENERATOR
ROTOR
Testing
for
Grounds:
Use an ohmmeter
(R
x
100
scale'); measure as follows:
Brush Type
-
from each slip ring to the rotor shaft.
Brushless Type
-
disconnect F1 and F2 rotor leads
from the rotating diodes; measure between either
lead and the rotor shaft.
A
reading of less than infinity
indicates a ground. See Figure 12.
0
H
M M ETER
BRUSH
DESIGN
CONTACT ONE PROD TO EACH OF THE SLIP
RINGS AND THE OTHER PROD TO THE ROTOR
SHAFT.
IF ROTOR
IS
GOOD THERE SHOULD BE NO
READING ON OHMMETER.
OHMMETER
CONTACT ONE PROD TO EACH OF THE FIELD
LEADS AND THE OTHER PROD TO THE ROTOR
SHAFT.
IF
ROTOR
IS
GOOD'THERE SHOULD BE NO
READING ON OHMMETER
FIGURE
12.
TESTING
ROTOR
FOR GROUNDS
Testing
for
an Open Circuit:
On brush type
generators, check for an open circuit by measuring
resistance in the windings. Check between the two
slip rings as shown in Figure 13.
On brushless generators, disconnect and test
between F1 and F2 leads as shown in Figure 13.
Resistance values given in Table
3
apply to both brushless and
brush type generator rotors.
Replace the rotor if
it
is grounded or has an open or
short.
CONTACT ONE PROD TO ONE
SLIP
RING AND
THE OTHER PROD TO THE SECOND SLIP RING.
CONTACT ONE PROD TO ONE FIELD LEAD AND
THE SECOND PROD TO THE OTHER FIELD LEAD
FIGURE
13.
TESTING ROTOR FOR AN OPEN CIRCUIT
TABLE
3.
RESISTANCE VALUES
FOR
ROTORS
KW
RATING
I
RESISTANCE
IN
OHMS
50HERTZ
I
60HERTZ
1
FROM TO
25.0
37.0
40.0
45.0
50.0
55.0
60.0
70.0
75.0
80.0
95.0
1
10.0
11
5.0
125.0
140.0
145.0
30.0
40.0
45.0
50.0
55.0
55.0
60.0
65.0
75.0
85.0
90.0
100.0
115.0
125.0
140.0
150.0
170.0
175.0
3.32 4.06
2.49 3.05
2.49 3.05
2.49 3.05
2.76 3.38
2.76 3.38
3.02 3.70
3.02 3.70
3.16 3.86
2.76 3.38
2.76 3.38
3.19 3.90
3.26 3.99
3.96 4.40
3.96 4.40
3.09 3.78
3.42
,
4.18
3.42 4.18
All
resistances should be within the values specified at
20°C
(68"
F).
This includes readings between slip rings on static excited
rotors and between field leads (with rectifiers disconnected) on
brushless rotors. Use Wheatstone Bridge for testing.
19
Redistribution or publication of this document,
by any means, is strictly prohibited.
TESTING GENERATOR STATOR
Testing
for
Grounds:
Connect all stator output leads
(Tl-T12) together. Use an ohmmeter set on the
R
x
100
scale and measure the insulation resistance
between these windings and the stator frame.
A
reading of less than infinity indicates a ground. Field
circuit breaker can be either
“ON”
or
“OFF”.
Testing
for
Shorts:
To check for shorts between
individual windings first refer to Figure 18 to deter-
mine individual coil lead wires (Tl-T4, T7-Tl0, etc.)
Connect one lead of an ohmmeter (RX100 scale) to
one of the stator windings and the other ohmmeter
lead
to
all other stator leads connected together.
A
reading of less than infinity indicates a short. Repeat
until all stator coils have been tested in this manner.
Coil Resistances:
Measure resistance of windings
using a Wheatstone or Kelvin bridge meter. SeeTable
4 and Figure 14. If any windings are shorted, open
or
grounded, replace the stator assembly. Before
replacing the assembly, check the leads for broken
wires
or
damaged insulation.
FROM
KELVIN
BRIDGE
FIGURE 14. TESTING STATOR WINDINGS
Stator output leads T4, T7, T8, T9 and T10 are interconnected
(within the stator) to five stranded (#lo aircraft) control wires.
These wires are labeled 4,7,8,9 and 10 respectively and terminate
at
TB2.1
(terminals 61-65).
TABLE
4.
.RESISTANCE VALUES
FOR
STATORS*
KW
R
50
HERTZ
25.0
37.0
’
40.0
,450
55.0
60.0
70.0
75.0
80.0
95.0
110.0
11 5.0
125.0
140.0
145.0
’
50.0
TlNG
6O.HERTZ
30.0
40.0
45.0
50.0
55.0
55.0
60.0
65.0
75.0
85;O
90.0
100.0
115.0
125.0
140.0
150.0
170.0
175.0
VOLTAGE CODE (Resistance in
Ohms)
I
I
15
I
9x
I
3
0.116
-
0.141
0.047
-
0.058
0.047
-
.
0.058
0.047
-
0.058
0.028
-
0.035
0.038
-
0.047
0.028
-
0.035
0.028
-
0.035
0.022
-
0.027
0.019
-
0.024
0.019
-
0.024
0.015
-
0.018
0.012
-
0.015
0.009
-
0.011
0.009
-
0:Oll
0.0075
-
0.0092
0.0059
-
0.0072
0.0059
-
0.0072
0.425
-
0.520
0.193
-
0.236
0.193
-
0.236.
0.156
-
0.191
0.113
-
0.138
0.113
-
0.138
-6.089
-
0.108
0.072
-
0.089
0.072
-
0.089
0.054
-
0.067
0.045
-
0.055
0.039
-
0.048
0.039
-
0.048’
0.027
-
0.033
0.018
-
0.023
0.018
-
0.023
0.052
-
0.063
0.047
-
0.058
.
0.047
-
0.058
!
i.
AI:
r’(?sislances should be within the values shown at
20°C (68’
F).
Use an accurate instrument such
as
a Kelvin Bridge for this test.
Test
between the following coil leads:
T1 -T4 17-T 10 T3-T6
T9-Tl2 T2-T5 T8-Tl1
20
Redistribution or publication of this document,
by any means, is strictly prohibited.
!
Testing Winding Resistance:
Measure coil resistance
between leads F1 and F2 with an ohmmeter (scale Rx
1).
Resistance should be17.82 to 21.78ohmsat 20°C
(68°F). See Figure 16A.
IJI
TESTING EXCITER ROTOR (Armature)
Testing for Grounds:
Remove diodes
CR1,
CR2, CR3,
CR4,
CR5,
and CR6 from diode heat sink assemblies.
Using an ohmmeter
(R
x 100 scale) measure insula-
tion resistance between any of the leads and the
laminations (exclude the diodes from the test circuit).
A reading of less than infinity indicates a ground.
Testing Winding Resistance:
Using a Wheatstone or
Kelvin bridge meter, measure resistance between
leads pairs T1-T2, T2-T3 and Ti-13. Resistance
should be 0.464 to 0.567 ohms at 20°C (68°F). See
Figure
15.
FIGURE 16A. TESTING EXCITER FIELD
FIGURE 15. TESTING EXCITER ARMATURE
TESTING EXCITER STATOR
Testing for Grounds:
Using an ohmmeter
(R
x
100
scale), measure the insulation resistance between
either lead F1 or
F2
and the laminations.
A
reading of
less than infinity indicates a ground. See Figure 16.
RECONNECTION
Figure 18 shows reconnection possibilities forthe
UR
series generators. When reconnecting for
a
different
voltage, be sure to also reconnect lead from terminal
63 (inside control box) to either H3, H4, H50rH6.See
Figures
17
and 18.
(W12
WIRE)
CONNECT LOOSE WIRE
FROM TERMINAL
#63
TO EITHER
H3.H4.H5
OR
H6
DEPENDING'ON
VOLTAGE SELECTED.
FIGURE 16. TESTING EXCITER FIELD
21
FIGURE 17. CONNECTING LEAD
FROM
TERMINAL
63
Redistribution or publication of this document,
by any means, is strictly prohibited.
NAMEPLATE VOLTAGE CODE
9X
NAMEPLATE VOLTAGE CODE
3
T1
CONNECT LEAD
FROM
TERMINAL
63
10
H5
E,
+
CONNECT LEAD FROM
TERMINAL
63
TO
H5
IS
120/240
1
60
H5
115/230
1
50
H6
115
116220
1
50
H6
15
120/140
3
60
H5
115/230
3
50
H6
i1S
THIS
DIAGRAM APPLIES
TO
12 LEAD GENERATORS
ONLY
GENERATOR CONNECTION WIRING DIAGRAM
SCHEMATIC
(WITH
CURRENT
TRANSFORMERS
WHEN
USED)
DIAGRAM
THIS
DIAGRAM APPLIES
TO
12 LEAD GENERATORS
ONLY
GENERATOR CONNECTION WIRING DIAGRAM
SCHEMATIC
(WITH
CURRENT
TRANSFORMERS
WHEN
USED)
DIAGRAM
8'l
LO
TI0
77
75
L2
13
I
W
5
'7:
111
LO
71
0
711
79
L3
/
LO
11
12
T1
12
16
111
18112
14
19
1s
17
T3
110
LO L1
12
L3
11
T10
16
17
12
111
14
T8
'73
T12 T5
19
LO
L1 L2
13
4
16
111
12
T8
13
19
I5
110
112"
l7
LO
L1
12
13
T3T9
1
1101lt
T12 TI T7 T4
12
T8
15
98C2193
i
I
1
,.
t
i.
FIGURE
18.
RECONNECTION
DIAGRAM
22
Redistribution or publication of this document,
by any means, is strictly prohibited.
1
I
il
:!
..
SENSITIVITY REFERENCE CIRCUIT
UR
series voltage regulators
(VR21)
can be set to
either frequency sensitive or non-frequency sensitive
reference. With a frequency sensitive reference, the
output voltage of the generator will decrease in
proportion to the frequency (Le., prime moverspeed).
This decrease
in
output voltage will reduce the load
on the prime mover, permitting
it
to return to rated
voltage and frequency when overload is removed.
A
temporary overload with a non-frequency sensitive
reference could cause a prime mover to reduce
speed, then would require a further
50%
to
60%
load
reduction
to
allow it to return to rated speed.
This reference change is accomplished by soldering
wire
W1
to terminal
El
for frequency sensitivity or to
terminal
E2
for non-frequency sensitive reference.
See Figure
19.
Unless requested otherwise by purchaser, Onan sets are con-
nected at the factory to a frequency sensitive reference.
TOP SIDE
OF.
VOLTAGE
REGULATOR
WHENMOUNTED
UNSOLDER THIS WIRE
FROM E
I
AND CONNECT
TO E2
FOR
A NON-
FREQUENCY SENSITIVE
VOLTAGE REFERENCE
CIRCUIT.
-
FIGURE
19.
VR21
PRINTED CIRCUIT BOARD
23
Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERATOR
DISASSEMBLY
,
If generator testing determines that generator needs
repair, remove and disassemble according to Figure
'20
and the following instructions:
7.
Using an overhead hoist and sling, slide the stator
Use care not to damage the brush rig (or
Ez3
exciter on brushless models) while
removing the stator. Do not allow the stator to rest on rotor
assembly off the rotor assembly.
CAUT,ON
Disconnect and remove load wires.
Disconnect leadwires from the control box.
Check wire markings for legibility to ease
assembly. Arrange leads
so
they can be
withdrawn easily from the control box.
Remove front grille (14) and sheet metal work.
Remove the four capscrews securing voltage
regulator chassis
(23)
to end bell
(9)
and remove
chassis assembly.
Remove the centrifugal switch
(8)
from end bell
and rotor shaft. On static excited models, slip the
brushes (7) and brush springs
(6)
from brush rig
(5)
-
it is not necessary to disconnect the brush
leads unless brush replacement is required.
Block the rear of the engine
in
place by suppor-
ting the flywheel housing. Remove the narrow
generator band
(10).
Remove the large capscrews
securing generator mounting pad
(11)
to the skid
base. Remove the capscrews securing the stator
assembly
(4)
to the engine flywheel housing.
during removal.
8.
Remove end bell from stator assembly; dis-
connect and remove brush rig from end bell on
static excited generators. On brushless models,
remove exciter field (24) from end bell assembly
if
required.
9.
Attach the hoist and sling to the rotor assembly
(1) and apply a slight lift to support the rotor.
Remove the capscrews securing the flexibledrive
coupling (13) to the engine flywheel and remove
'
rotor from the engine.
10.
Remove bearing capscrew (18) and washer (17)
and remove bearing from shaft.
If
required,
remove blower
(2)
from the rotor.
11. Disconnect rotor field leads from heat sinks
F1
and
F2
on the exciter armature. Remove exciter
armature
(25).
9
23
LA
/
BRUSHLESS
GENERATOR
FIGURE
20.
GENERATOR DISASSEMBLY
24
Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERATOR
ASSEMBLY
Generator assembly is the reverse of disassembly
procedure:
1.
Always replace bearing with a new one; apply a
layer of grease on end bell bearing hole before
inserting bearing.
2.
Torque bearing capscrew to
60-70
Ib. ft.
3.
Torque drive disc-to-rotor capscrews to 200-240
Ib. ft.
4. Torque drive disc-to-flywheel capscrews to 45-50
Ib. ft.
5.
Torque generator through-stud nuts to
30-40
Ib.
ft.
6. Refer to
Purrs
Curu/o,y
for replaceable parts and
assemblies. Refer to
Wiring
Diuputii
for
reassembly.
[PI
VOLTAGE ADJUSTMENT
After replacement, voltage regulator (VR21) adjust-
ment is performed as follows (see Figure 21):
1. Center the voltage adjust knob
so
pointer is in a
2. Open meter panel doors. Start unit.
3.
Using a screwdriver, turn R18 potentiometer on
printed circuit board VR21 counterclockwise to
increase the voltage
or
clockwise to decrease the
voltage. Observe voltmeter on meter panel while
making adjustment. Set voltage with no load
connected to generator. (Example: For a 120/240
volt connection, set at no-load voltage
or
ap-
proximately 246 volts.)
vertical position.
If
voltage is unstable
or
tends to hunt, turn R26
potentiometer on VR21
in
the direction shown on
printed circuit board to increase voltage sensitivity.
I
\
ADJUST R26 ADJUST R
18
HERE HERE
FIGURE
21.
ADJUSTING VOLTAGE
ON
VR21
25
Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERATOR
-
SECTION
II
GENERAL
Generators discussed in this section are brushless
type only. The difference between these and the
generators in Section
I
is
in
the VR22 diode assembly
and the commutating reactor. These have been
,
removed from the generator end bell and relocated in
the control panel. The diodes are now encapsulated
within a hermetically sealed block, therefore if any
diode or silicon controlled rectifier fails, the entire
unit has to be replaced. See Figure27fordetailsof the
,
rectifier assembly (CR21) and Figure 25 for the
reactor
(L21).
Principles of operation and method of excitation
remain unchanged from the units described in Sec-
tion
I.
Refer to Table
1
for generators to which this section
.
applies.
VR2‘ VOLTAGE
RE
GU
LATO R
121 REACTOR
/
ov
ROTATING EXCITER
‘ERSPEED SWITCH WITH RECTIFIERS
QENERATOR END VIEW (QRILLE REMOVED)
FIGURE 22. ROTATING RECTIFIER ASSEMBLY
\
CR2
I
SCR BRIDGE
FIGURE
23.
SCR BRIDGE AND REACTOR LOCATION
:TROUBLESHOOTING
ing the generator. To use the guides, answer the
Use the following troubleshooting charts and questions either “yes” or
“no”
then proceed to the
procedures to locate malfunctions
in
the generating next step given in whichever column
is
indicated.
system.
Section
11
also references procedures
A
thru
P
of
Section
1.
When using block diagrams, a letter with a triangle
indicates a procedure
in
Generator
-
Section
1.
A
letter
The question and answer troubleshooting guides
within a diamond indicates a procedure in
Generator-
which follow give a step-by-step procedure for check-
Section
II.
26
Redistribution or publication of this document,
by any means, is strictly prohibited.
!
;
QUESTION
AND
ANSWER
TROUBLESHOOTING
GUIDE$
To
correct a particular problem, answer the question either “yes” or “no,” then proceed
to
the next step given in
whichever column question was answered. Procedures
R
thru
P
follow the troubleshooting guide.
ITEM
NO.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
12.
TABLE
F.
NO
AC OUTPUT VOLTAGE
-
ENGINE RUNNING
AT
RATED
RPM YES NO PROCEDURE
Is
Exciter Circuit Breaker (CB21) on the meter panel
in
the
“ON”
position?
3
2
Switch CB21 to
“ON”
position. Does AC voltage build up?
3
-
NOTE
If
voltage builds up but is high,
low
or
unstable,
or causes CB21 to trip, refer to table
G.
H
or
I
of
troubleshooting guide.
Is
AC
voltage measured at terminals
1
and 2 on voltage
regulator (VR21) printed circuit board 5 to 10 volts? 6
4
Is
AC voltage measured at terminals 11 and 12 on
VR21
5
to 10 volts?
5
7
Replace reactor assembly (L21).
-
-
Rectifier Bridge (CR21)
5
to 10 volts? 15 11
Is
DC voltage measured at terminals
+
and
-
on
Shut down generator set. Check continuity through L21
coils between terminal 2 on VR21 and T8 on generator,
between terminal 1 on VR21 and
T7
on generator.
Is
there continuity between these connections?
VR21-2 to T8 14
10
VR21-1 to T7 14
8
If
there is no continuity between VR21-1 and T7
((2621
-ON)
apply
a
shorting jumper across CB21.
Is
continuity obtained?
9
10
Replace CB21.
-
-
Check for loose or broken wires on VR21, CR21, L21,
reference voltage transformer (T21), generator
bus-bars and terminal board (TB21) in control
box. Secure or repair where necessary.
If
repairs have been made, restart engine. 14
Does AC voltage now build up?
Are diodes CR1, CR2 and CR3 on CR21 assembly good?
-
T
-
12
(See method T in procedure section for checking
diodes.) If faulty diode located, replace CR21.
Are
SCRs
1 and 2 in CR21 good?
(See method T in procedure section for checking
diodes.)
If
faulty SCR’s located, replace CR21.
T
-
13
Redistribution or publication of this document,
by any means, is strictly prohibited.
.
.
ITEM
NO.
13.
14.
15.
16.
17.
18.
19.
Fault probably lies with a defective component on VR21.
Replace VR21.
TABLE
F.
NO AC OUTPUT VOLTAGE- ENGINE RUNNING AT RATED RPM
(continued)
~~ ~
Start engine. Place CB21
in
“OFF” position. Using method
prescribed under
“R”
in
procedure section flash the exciter
field
to
restore residual magnetism. Place CB21
ON.
Does the AC output voltage build up?
I
No
lPROCEDURE
YES
Shut off engine.
is
exciter field winding (F1: F2)
OK?
16
Are rotating diodes CRI, through CR6 on exciter
rotor
OK?
17
Is
generator stator winding
OK?
Is
exciter rotor winding
OK?
18
19
-
Are generator rotor windings
OK?
13
I
...
I.
...
i
28
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
F.
SYNOPSIS
1
NO
VOLTAGE
BUILD-UP
N
eo
-
SCRl
OR
SCRP
OPEN
,
DEFECTIVE
-
DlODECR1
CR2
OR
CR3
.
OPEN LEAD
AT
-
TERMINAL
OPEN LEAD
REGULATOR
PC BOARD
TERMINALS
1
OR
2
NOTE: Whenever
a
letter appears near the
box,
a separate procedure, corresponding
to that letter,
is
given at the end
of
the, appropriate section.
....
._
.-
_.
-
.
.
....
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE G. UNSTABLE OUTPUT
-
ENGINE RUNNING AT
1800
RPM
-
NO FLUCTUA-
I
YES
1
NO IPROCEDURE
TION
I
I
I
I
I
I
I
Are there any loose or broken wires or connections at
VR21
terminals?
Does adjustment
of
R26
(damping control potentiometer)
I
on
VR21
stabilize generator voltage?
Replace
VR21.
2
-
-
3
P
-
-
TABLE
G.
SYNOPSIS
UNSTABLE OUTPUT
VOLTAGE
i
.
, ,
..
.
.-
-
BROKEN
WIRES
OR
AT (VR21) VOLTAGE
CIRCUIT BOARD
TERMINALS
DEFECTIVE COMPONENT LOOSE CONNECTIONS
REGULATOR PRINTED REGULATOR PRINTED
ON (VR21) VOLTAGE
CIRCUIT BOARD
NOTE:
Whenever a letter appears near the
box,
a
separate procedure, corresponding
to
that letter,
is
given at the end
of
the appropriate section.
INCORRECT SETTING
OF R26 POT ON (VR21)
PRINTED CIRCUIT
BOARD
,
,
._ .
..
".
1
. ..
.I
I
30
Redistribution or publication of this document,
by any means, is strictly prohibited.
i
&M
1.
2.
3.
.-
TABLE
H.
OUTPUT VOLTAGE TO
HIGH
OR
LOW YES NO PROCEDURE
__
--
Does adjustment of
R21
“voltage adjust knob” on meter
2
panel correct voltage level?
-
voltage level?
-
Are rotating diode heat sink mounting screw insulators
OK?
Does adjustment of
R18
potentiometer on
VR21
correct
3
P
-
-
If
generator output voltage has been optionally reconnected,
consider the following
-
5.
6.
Is
reference transformer
(T21)
tap correctly connected
on
TB21?
4-
I
Are the reconnections correct and secure?
6
Replace
VR21.
-
15
%
DEFECTIVE DEFECTIVE
COMPONENT ON
VOLTAGE
REGULATOR PC
BOARD (VR21)
COMPONENT ON
CR21
RECTIFIER ASSEMBLY
TABLE
H.
SYNOPSIS
TOO
HIGH
OR
TOO
LOW
r
INCORRECT
SETTING OF
VOLTAGE ADJUST
POT (R18) ON
VR21 PC BOARD
I
-
I
I
1
H
OPEN LEAD
OR
CONNECTION AT
TERMINALS
G1
OR
G2
INCORRECT
SETTING OF
VOLTAGE ADJUST
POT (R21) ON
METER PANEL
INCORRECT
REFERENCE
TRANSFORMER TAP
ON T21
DEFECTIVE ROTATING
DIODE
OR
BAD INSULATOR
ON HEAT SINK MOUNTING
SCREW
1
OPEN
IN
CR1,
CR2
OR
CR3
/L\
1
VOLTAGE
BREAKDOWN OF
I
I
I
I
SCRl ORSCR2
NOTE: Whenever a letter appears near the
box,
a
separate procedure, corresponding
to that letter,
is
given at the end
of
the appropriate section.
31
Redistribution or publication of this document,
by any means, is strictly prohibited.
IiLM
1.
2.
Is
diode
CR3
(connected between
+
and
-
in
CR21
rectifier assembly)
OK?
TABLE
1.
EXCITER CIRCUIT BREAKER TRIPS
Does
AC
output build up to
150%
or more
of
rated voltage
before
CB21
trips?
Are there loose or broken terminals or connections at
VRZl?
Are reference voltage transformer
(T21)
windings and
connections
OK?
5.
6.
Replace
VR21.
Does
AC output build up
to
rated value before tripping
CB21?
7.
Are rotating diodes
CR1
through CR6 on exciter
rotor
OK?
8.
9.
YES
NO PROCEDURE
Is
exciter stator winding
OK?
Is
generator field winding
OK?
DEFECTIVE
ROTATING DIODE
CR1,
CR2, CR3,
ON, EXCITER
ROTOR
10.
FAULT
IN
EXCITER ROTOR
OR
STATOR
WINDING
Is
exciter rotor winding
OK?
NOTE
Whenever a letter appears near the
box,
a separate procedure, corresponding
to
that letter, is given at the end
of
the appropriate section.
32
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
J.
UNBALANCED GENERATOR OUTPUT VOLTAGE
-
YES
[
NO lPROCEDUREl
Remove load from generator terminals.
Is
output
still unbalanced?
Are generator leads properly connected or grounded?
I-
Check for ground faults
on
load.
2
3
TABLE
J.
SYNOPSIS
TERMINAL
VOLTAGES
Is
generator stator winding continuous?
Is grounding procedure of generator and load correct?
4
5
INCORRECT RECONNECTION
AND/OR GROUNDING OF
GENERATOR LEADS
I
!
1
INCORRECT GROUNDING
OF LOAD
OR
GROUND
FAULT IN LOAD
I
FAULTY GENERATOR
STATOR WINDING
I
I
1
NOTE:
Whenever a letter appears near the
box,
a
separate procedure, corresponding
to that letter is given at the end
of
the appropriate section.
33
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
J.
SY
NOPSlS
(Continued)
VOLTAGE
150%
MORE
THAN
RATED
I
I
OPEN WIRE
OR
DEFECTIVE COMPONENl
ON RECTIFIER
ASSEMBLY CR21
CONNECTION AT
VR21 MODULE
TERMINALS 5,
6,
9,10,
OPEN TRANSFORMER
(T21) WINDING
11
OR
12
*
DlODECR3
-
1.
OPEN
I
BREAKDOWN
OF
SCRl
OR
SCRP
NOTE:
Whenever a letter appears near the
box,
a separate procedure, corresponding
to that letter,
is
given at the end of the appropriate section.
Malfunction occurs after warmup or voitage adjustment.
DEFECTIVE COMPONENl
ON VOLTAGE
REGULATOR (VR21)
MODULE
34
Redistribution or publication of this document,
by any means, is strictly prohibited.
ADJUSTMENTS
AND
PROCEDURES
(Applies
to
Section
II
Only)
FLASHING
THE
FIELD
If output voltage does not build up
it
may be
necessary to restore the residual magnetism of the
poles by flashing the field. Assembleasixvolt battery,
and diode
as
shown
in
Figure 24. If a
six
volt lantern
battery is not available a 12-volt (generator set
battery) or a 24-volt battery can be used, however a
20-ohm or a 40-ohm 2 watt resistor must be used in
conjunction with the 12 amp 300
V
diode. Start the
generator set, touch positive lead to
+
on
rectifier
bridge, and negative lead to the
-
terminal. Hold leads
on terminals just long enough for voltage to build up.
Do
not keep excitation circuitry connected
longer than 5-seconds, or damage may occur
to the exciter regulator.
I
I2
AMP.
I
300
v.
RECTIFIER
BRIDGE
FIGURE
24.
FIELD
FLASHING
CIRCUIT
I
TESTING
L21
REACTOR
The L21 commutating reactor mounts inside the
control box, below the
VR21
Voltage Regulator.
The coils 1-2 and 3-4 are wound on the same core.
Resistance between 1-2 and 3-4 should be .034 ohm
f
.0034 and .042 ohms
*
.0042 respectively (brushless
units). Resistance between coils (e.g.,
1/4)
or from
any terminal to frame
of
the reactor should
be
icfinity
(Figure
25).
I
1
FIGURE
25.
L21
REACTOR
35
Redistribution or publication of this document,
by any means, is strictly prohibited.
TESTING RECTIFIER BRIDGE ASSEMBLY
(CR21)
The rectifier bridge located within the control cabinet,
below the voltage regulator, contains
3
diode?
CRl.
CR2.
and CR3, and two silicon
COIIII~I~III~~~~
r'cxttlittt
SCR1
and
SCR2.
These diodes and
SCR's
arc cncali-
:;dated
within a hermetically sealed block, therefore
lailurc!
of
any diode
or
SCR means the entire unit has
to
bc
replaced. See Figure 26.
I
7i-
-1
h
I
CR2
'
CR
I
CR3
-
I
-
AC TERMINALS ARE
GIVEN NUMERIC
DESIGNATIONS
FOR
TEXT REFERENCE
ONLY.
DOES
NOT
APPEAR
ON
UNIT.
FIGURE
26.
RECTIFIER ASSEMBLY
Disconnect wires from rectifier unit prior to testing.
Test unit in order shown in Table
5.
Refer to Figure 27
for SCR1 and SCR2test circuit. When test is complete
and satisfactory, reconnect unit observing correct
wiring hoo k-up.
r---
6
VOLT
DRY CELL
BATTERY
'I
FIGURE
27.
TESTING
SCR
36
Redistribution or publication of this document,
by any means, is strictly prohibited.
NG
SCR
REMARKS
METER
SCALE
CR3
CR3
CR1
CR2
CR2
Infinity
RXlOK
6-
to
50-Ohms
RXl
Infinity
RXlOK
SCRl
lnfinitv
RXlOK
RX1
2CR2
Infinity
RXlOK
I
nf
ini ty
RXl OK
6-
to
50-Ohms
RX1
DC
Voltmeter
DC
Voltmeter
lead Reading
I+
3
Volts
I
1+1
3CR2.I
AC2
I
+
I
3
Volts
-
Apply
temporary jumper from AC1 to
G1
to test
SCR1.
Remove jumper,
**.Apply temporary jumper from AC2 to G2 to test
SCR2.
Remove jumper,
read voltmeter. See Figure 27.
read voltmeter. See Figure 27.
37
Redistribution or publication of this document,
by any means, is strictly prohibited.
INDEX
OF
GENERATOR
!
ADJUSTMENTS
AND
PROCEDURES
PROCEDURE
A
B
C
D
E
F
G
H
J
K
L
M
N
.
P
SECTION
I
TITLE
Brushes
..............................
No
AC Power to Exciter
...............
Flashing Field
........................
Testing L1 Reactor
...................
Testing Diodes
.......................
Testing
SCR’s
........................
Testing Generator Rotor
..............
Testing Generator Stator
..............
Testing Exciter Rotor
.................
Testing Exciter Stator
.................
Reconnection
........................
Sensitivity Reference Circuit
..........
Generator Disassembly
...............
Voltage Adjustment
..............
:
....
PAGE
16
16
17
17
17
18
19
20
21
21
21
23
24
25
SECTION
II
R
Flashing Field
........................
35
S
Testing L21 Reactor
..................
35
PROCEDURE
TITLE
PAGE
T Testing Bridge Rectifier (CR21)
.......
36
38
Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROLS
-
SECTION
111
GENERAL
The shock mounted control box has two doors that
open from the center. The left hand door holds the
field circuit breaker, voltmeter and voltage adjusting
rheostat. The optional meter package adds running
time meter, frequency meter, ammeter or ammeters
plus volts-amps selector switch to the left hand door.
The right hand door, attached to a removable bracket,
holds the instrument lamp, fault lights, switches and
gauges.
An
optional door has holes for electric
tachometer and/or oil temperature gauge. The
bracket supports the terminal blocks, cycle cranker
and relays
in
the
DC
engine control circuit.
Plug mounted relays in both the AC section and DC
section plus printed circuit modules
in
the DCsection
facilitate troubleshooting and servicing. Snap-in
lamps with Faston connectors make lamp replace-
ment very easy. See Figure
28.
A12 CRANKING LIMITER
(MAY ALSO USE AN
OPTIONAL CYCLE
CRANKER)
I
K11 START DISCONNEC
RELAY
K12 IGNITION RELA
K13 START SOLENOI
FIGURE
28.
LOCATION OF
DC
CONTROL COMPONENTS
-FAULT LAMPS
TIME DELAY
-ENGINE MONITOR
PC BOARD
\KI RELAY
lK2 RELAY
THE QUESTION AND ANSWER TROUBLESHOOTING GUIDES BEGINNING
ON
PAGE
39
GIVE A STEP-BY-STEP PROCEDURE FOR CHECKING
GUIDES ARE GIVEN AS A GENERAL GUIDE TO RESOLVE VARIOUS
CONTROL SYSTEM PROBLEMS. ALL CHARTS REFER TO PROCEDURES
AND NOTES WHICH ARE GIVEN AT THE END OF THIS SECTION.
CONTROL SYSTEM PROBLEMS. THEFLOW-CHART TROUBLESHOOTING
39
Redistribution or publication of this document,
by any means, is strictly prohibited.
QUESTION
AND
ANSWER TROUBLESHOOTING GUIDE
l3
~
Is
battery connected correctly and is voltage normal?
FOR
UNITS
WITH
ONE FAULT LAMP
I
I
lo
~
Does ignition relay
K12
pick up?
To
correct
a
particular problem, answer the question either “yes“ or “no” then proceed to the next step given in
whichever column question was answered.
TABLE A. ENGINE FAILS
TO
CRANK WHEN SWITCH
TO
“RUN”
Does fault lamp light?
YES
1
Is
voltage from ground terminal to center terminal of
run-stop-remote switch equal to battery voltage?
Switch is defective or in “stop” position.
7
-
Replace engine monitor printed circuit board.
Is
voltage from ground to terminal
26
on
TBll
equal to
battery voltage?
Does ignition relay
K12 (4-7)
contact close?
-
14
13
1.
2.
~~~
relay
K13’
(start solenoid) pick up?
I
l7
3.
4.
5.
6.
,
7.
Is
voltage from ground terminal to ignition relay
K12
terminal
“B”
equal to battery voltage?
I
lo
0.
Jumper battery positive from center terminal of run-stop-remote
switch to terminal
“6”
of
ignition relay
K12.
Does engine
now crank? 9
9.
10.
11.
12.
a. Check socket connection.
b. Coil may be open.
c. Replace ignition relay
K12.
I-
Clean relay contacts and check wiring.
13.
14.
I
Is
voltage from ground to start disconnect relay
K11
terminal
1
equal to battery voltage?
I
l6
15.
I-
Clean relay contact
K11
(7-1)
and check wiring.
t
NOTE:
On
EK.
EM,
and
EN
series, start solenoid relay is mounted
on
the engine,
rather than in the control, and
is
designated
K6.
40
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO.
A. ENGINE FAILS TO CRANK WHEN SWITCHED
TO
“RUN”
YES NO PROCEDURE
(Continued)
Is
voltage from ground to coil terminal of
K13’
start solenoid
I
equal to battery voltage?
17
18
21 20
Does voltage from ground to
TBll-22
equal battery voltage?
Does relay
K13’
pick up?
Replace cycle cranker printed circuit board
A12.
-
-
Replace start solenoid
K13’.
-
-
Is
voltage from ground to starter coil terminal equal to
battery voltage?
22 23
Jumper from
K13’
coil terminal to
K11
terminal
1.
-
19
Replace starter.
-
-
Check thermal breaker
CB1
and wiring
to
starter.
- -
16.
17.
18.
19.
20.
21.
22.
23.
‘NOTE:
On
EK.
EM,
and
EN
series.
start
solenoid
is
mounted on engine,
rather than in
the
control, and
is
designated
K6.
TABLE
A.
SYNOPSIS
ENGINE
FAILS
TO
CRANK
A12 CYCLE
CRANKER
FAILS
IGNITION
RELAY K12
FAILS
LOOSE
OR
REVERSED
BATTERY
CON N ECTlO
N
I
~
K12 COIL
(4-7)
FAILS
TO CLOSE
START
SOLENOID
FAILS
SOLENOID
COIL OPEN
SOLENOID
CONTACT FAILS
TO CLOSE
MO N
IT0
R
PRINTED
CIRCUIT BOARD
CONTACT FAILS
TO
CLOSE
CIRCUIT PATH
41
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO. TABLE B. ENGINE SHUTS DOWN IMMEDIATELY AFTER START
1.
1
Is
overspeed switch S3 closed? 12
YES NO PROCEDURE
Open overspeed switch, then reset fault lamp by switching
to “stop”, then back to “run”. Does engine crank and run OK?
5.
6.
I
Check overspeed switch and wiring for grounds.
Jumper from ignition relay K12 terminal “B” to center terminal
of run-stop-remote switch. See Method M in Procedure section.
Does engine crank?
Remove wire from TB11-29. Reset fault lamp by switching
to “stop”, then back to “run”. Does engine crank?
~
7.
4
Replace engine monitor printed circuit board and remove jumper.
-
Place wire back onto TB11-29 while engine is running.
Does fault lamp light and engine stop?
1.
2.
Does fault lamp light and does plant stop after running about
12 seconds?
Does fault lamp light and does plant stop after running about
1
minute?
5
-
~
3.
4.
. 5.
7
Remove wire from terminal TB11-30. Does engine run
OK
after
restarting?
Engine is either not pumping oil properly or oil pressure
sensor is defective.
Replace wire on TB11-30 and remove wire from TB11-31.
Does engine run OK after restarting?
6.
7.
ITEM
I
TABLE C. ENGINE SHUTS DOWN AFTER RUNNING
A
SHORT
TIME
NO.
I
Engine is either operating over temperature, temperature
sensor is defective or wire between sensor and terminal block
is grounded.
Jumper K11 terminals
6-9.
Does engine run OK?
~~ ~
8r-1
Replace relayG1 or clean contacts
6-9.
9.
I
Replace engine monitor.
YES
I
NO IPROCEDUREI
6
-
a
42
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO.
1.
2.
TABLE
D.
SYNOPSIS
TABLE
D.
ENGINE HESITATES WHEN ATTEMPTING TO CRANK
Does engine crank as soon as run-stop switch is put into
“run” position?
Check contacts K12
(3-9)
for
failure to close
or
to make
proper contact.
ENGINE
SOMETIMES
HESITATES
BEFORE
CRANKING
5
YES NO PROCEDURE
.
I
DIRTY CONTACTS,
BAD CONNECTION
I
43
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Does starter continue to run after engine starts?
Does charge ammeter show
a
charging current while running?
TABLE E. STARTER FAILS
TO
DISENGAGE
OR
TRIES
TO
RE-ENGAGE WHILE
YES
RUNNING
I
2
4
Does voltage at starter terminal drop to zero when K13* drops out?
Check for faulty starter.
l4
Is
charging alternator belt on and driving alternator properly?
7
-
Does start disconnect relay K11 and starter protection relay
K14 pick up when engine starts?
Does voltage across K11 terminals
(A-B)
build up’to battery
voltage?
Does voltage from ground to K13’ coil terminal drop to zero
when K11 relay picks up?
11
l6
Check for faulty alternator, regulator or shorted
alternator output.
Check K12 ignition relay for dirty contact or broken wire.
-
-
I-
Start solenoid contacts may be welded
-
..I
replace K13’ solenoid.
~ ~
Check K11 and K14 contacts (1-7) to make sure they open when
relay picks up.
l-
Replace start disconnect relay K11 or starter protection
relay K14. Coil may be open.
l-
Does relay K12
(5-8)
close to bring battery voltage to
alternator regulator?
I
l3
,
NOTE
On
EK.
EM
and
EN
series,
start solenoid
is
mounted on the engine,
rather than the control, and
is
designated
K6.
44
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE
E.
SYNOPSIS
ENERGIZE
NECT RELAY
K11 AND K14
D.RlVE BELT
OFF
OR
START DISCON-
7
SLIPPING
J
K14 STARTER
PROTECTION
RELAY FAILS
STARTER
FAILS
TO
DISENGAGE
START
SOLENOID
COWTACT
FAILS
TO
OQEN
START
DISCONNECT
RELAY K11
FAILS
-
AND-c
I
-
K14 COIL,
7
.',
1
CONTACTS
FAIL TO OPEN
1-7 ON K14
I
K11 START
I
DISCONNECT
COIL OPEN
w
CONTACTS 1-7
ON K11 FAIL
TO OPEN
/G\
NOTE: Whenever a letter appears near the box, a separate procedure, corresponding
to
that letter, is given at the end
of
this section.
-
K14
starter protection relay was added to units beginning with the Specs shown below.
This relay prevents starter engagement when unit is running.
IGNITION RELAY
TO CLOSE
K12
(5-8)
FAILS
I
ALTERNATOR
OUTPUT SHORT
CIRCUITED
I
DEFECTIVE
REGULATOR
SERIES SPEC SERIES SPEC SERIES SPEC SERIES SPEC
EK-EM D DEH D DYC
B
WA F
EN
A
DEF F DYD
A
WE B
KB-KR
P
DEG D DYG WB H
DDA-MDDA
A
DFE H
(1
50-1
75
kW) A
DDB
.
A DYA C DYJ A
45
Redistribution or publication of this document,
by any means, is strictly prohibited.
QUESTION
AND
ANSWER TROUBLESHOOTING GUIDE
-
I
‘LkM
I
TABLE
F.
ENGINE
FAILS
TO
CRANK
When switch is put into “run” position, does. engine csank?
.
:
’
Is
battery connected correctly and is voltage normal?
..
’
FOR
UNITS
WITH
5
FAULT
LAMPS
--
YES
NO PROCEDURE
2
-
-
3
Does ‘relay K13* (sfarfsolenoid) pick up?
Does ignition relay K12 pick up?
Is
voltage from ground terminal to center terminal of run-stop-
remote switch equal to battery voltage?
Switch is in “stop” position
or
defective.
I
I’
I
22
5
11
6
8
7
-
-
Does
one of the following fault lamps light?
(Choose one
of
the following:)
.
Overspeed?
..
High Engine Temperature?
Low Oil Pressure?
Overcrank?
..
~~ ~~
Remove jumper and replace engine monitor printed circuit board.
Is
voltage from ground to terminal 26 on TB11 equal to battery
voltage?
Does contact ignition relay K12 (4-7) close?
Clean socket connection. Coil may be open. Replace ignition
relay K12.
Clean relay contacts
or
replace relay and check wiring.
-
30
25
27
29
-
-
15 12
14 13
-
-
-
-
I
Is
voltage from ground terminal to ignition relay K12
terminal
“B”
equal to battery voltage?
1131g1
I
I
1
Jumper battery positive from center terminal of run-stop-remote
switch to terminal “B” of relay K12. Does engine crank? I10
1-1
.M
NOTE:
On
EK.
EM
and
EN
series, start solenoid relay is mounted on the engine,
rather than in the control, and is designated
K5.
46
Redistribution or publication of this document,
by any means, is strictly prohibited.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
Does voltage from ground to starter coil terminal equal battery voltage?
Replace starter.
28.
29.
30.
31.
32.
33.
34.
23 24
-
-
Is
voltage from ground to K11 iterminal 1 equal to
battery voltage?
Remove lead from TB11-31. Reset by switching to “stop”,
then back to “run”. Does engine crank OK?
Inspect for bare wires and shorts to ground. Replace engine
temperature sensor.
Are relay contacts K11 (8-5) open?
I
l6
I
17
26 29
-
-
29 28
Clean relay contact K11 (1-7) and check wiring. Replace
relay K11 if necessary.
Replace relay and reset by switching to “stop”, then back to
“run”. Does engine crank OK?
Replace engine monitor printed circuit board.
Does voltage from ground to coil terminal
of
K13’ start
solenoid equal battery voltage?
29
-
-
-
I
l9
I
18
Stop and start engine several times. Works
OK?
Does voltage from ground to TB11-22 equal battery voltage?
I
34
-
Jumper from K13* coil terminal to K11 terminal
1.
Does relay K13* start solenoid pick up?
Replace engine monitor printed circuit board.
22
20
- -
I
Replace cycle cranker and check printed circuit connection.
Replace K13* start solenoid.
1-1-1
Check wiring between TB11 terminal 22 and starter. Some units
have an automatic resetting circuit breaker
in
this circuit.
1-1-1
Remove lead from TB11-29. Reset by switching to “stop”, then.
back to “run”. Does engine crank when switched to run?
I
31
I
29
I
Replace the lead to TB11-29 when engine is running. Does
overspeed lamp light and engine stop?
’
I
32
I
33
I
I I I
I
I
Check for defective overspeed switch
or
bare wires grounding
terminal TB11-29.
I-1-1
NOTE:
On
EK,
EM
and
EN
series,
start solenoid
is
mounted on the’engine,
rather than the control, and
is
designated
K6.
Redistribution or publication of this document,
by any means, is strictly prohibited.
ITEM
NO.
1.
2.
3.
’
4.
5.
6.
7.
8.
9.
10.
11.
12.
Does relay K11 pick up after engine starts?
Jumper relay K11 contacts
(6-9)
after engine starts.
(Remove jumper after test.)
Does engine continue to
run
OK?
Replace relay Kll.
TABLE G. ENGINE SHUTS DOWN AFTER RUNNING A SHORT TIME
6
7
-
~ ~ ~~~ ~
Does low oil pressure lamp light and plant stop after running
about
12
seconds?
Does overcrank lamp light and plant stop after running about
1
minute?
Remove wire from terminal TB11-30. Reset alarm by switching
to “stop”, then back to “run”. Does engine run OK?
(Replace wire after test.)
Replace engine monitor printed circuit board.
Does charge ammeter show a charging current while running?
when engine runs?
Does battery voltage appear across K11 co,iI terminal
(A-B)
-
10
7
YES
3
5
Check .alternator and regulator output; replace if necessary.
4
-
Engine is either not pumping oil properly or oil pressure
sensor
is
defective.
l-
Check for an open circuit
in
wiring or a loose connection
from alternator
“AUX”
terminal to K11 coil circuit.
l-
TABLE
G.
SYNOPSIS
SHUTS
DOWN
NO PROCEDURE
,
I
I
I
I
TEMPERATURE PRESSURE
START DISCON-
NECT RELAY
K11
(6-9)
1
AEE:YF:E
1
F’%w
I I
SWITCH
.
ovER:EED,
CLOSED
I
SENSOR CLOSED SENSOR CLOSED
I
NO ALTERNATOR DEFECTIVE
OUTPUT REGULATOR
A-11 ENGINE
MONITOR
PRINTED CIRCUIT
48
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
SINGLE LAMP
ENGINE MONITOR
ENGINE
FAILS TO
CRANK
TRANSISTOR
07
FAILED,
SHORT
EMITTER TO
COLLECTOR
**
.
PATH
9-7
ON A-11
PRINTED
CIRCUIT
BOARD
K1 RELAY
CONTACT
FAILS TO
CLOSE
DIODE
CR3
OPEN
FAULT
LIGHTS AND
ENGINE
SHUTS DOWN
LOW OIL
PRESSURE
OR
HIGH
ENG. TEMP.
CIRCUIT
FAILS AFTER
APPROX. 12
SECONDS
*'*
NOTE: Whenever a letter appears near the
box,
a separate procedure, corresponding to that
letter, is given at the end
of
this section
FAULT
LIGHTS AS
SOON AS
RUN SWITCH
CLOSED
CAPACITOR
c2
SHORTED
SCR
CR6
SHORTED
EXTERNAL
ALARM
FAILS ON
ALARM
SHUTDOWN
r
CONTACT
FAILS TO
CLOSE
ON
SHUTDOWN
CIRCUIT
PATH
9-8
OPEN
**
-
With swiich in run position, check for voltage across
R9
(27-ohms).
A
voltage
of
0.5
to
1.0
will turn on
SCR
CR6.
If
voltage
is
present, remove
TB11
terminal
29.
If
voltage
is
still
present, check transistors
07
for short-emitter to collector.
Remove
TB11
terminal
30
and
31.
If
engine still shuts down, remove transistor
Q8.
If
this
prevents shutdown
-
replace
Q8.
I..
-
Redistribution or publication of this document,
by any means, is strictly prohibited.
ENGINE
MONITOR
**
ENGINE
FAILS TO
CRANK
LIGHTS AS
SOON AS RUN
I
I
I
I
CIRCUIT PATH HIGH ENGINE LOW OIL OVERSPEED OVERCRA'NK
18-19 TEMPERATURE PRESSURE LAMP LAMP
OPEN LAMP LIGHTS LAMP LIGHTS LIGHTS LIGHTS
_I-
-
K1 RELAY CAPACITOR
CONTACT ON C6
A-11 FAILS TO OPEN
TRANSISTOR
Q10
SHORTED
CAPACITOR
Fl
POTENTIOMETER
PRINTED ClRCUl
BOARD FOR
CORRECT TIME
R-15 ON A-11
CAPACITOR CAPACITOR
OPEN OPEN
I
TRANSISTOR
Q13
SHORTED
..
.-
I
POTENTIOMETER
R2
ON A-11
PRINTED CIRCUIT
BOARD FOR
CORRECT TIME
CAPACITOR
TI
CAPACITOR
TI
NOTE: Whenever a letter appears near the
box,
a separate procedure, correspondjng to that
.
letter,
is
given at the end
of
this section.
'
Capacitor C1 must be discharged when engine starts to prevent an overcrank shuidown.
'
Check relay contact that connects to terminal
16
of
engine monitor.
**
-
See typical wiring diagram.
I
ENGINE
SHUTS DOWN
I
OVERCRANK
LAMP LIGHTS
AFTER APPROX.
12 SECONDS
TRANSISTOR RELAY FAILS
Q6 FAILS TO TO DISCHARGE
TURN OFF CAPACITOR C1
I-
.
Redistribution or publication of this document,
by any means, is strictly prohibited.
ADJUSTMENTS
AND
P.ROCEDURES
If
starter fails to disengage, the engine may
drive starter to unsafe speeds that could
cause starter rotor windings to separate.
REMOVE K11
OR
K12 FROM
CONTROL
BOX
(PULL
STRAIGHT
TO
TERMINALS MARKED "A"
AND
"6"
ON BASE
OF
RELAY.
up).
cT)NNECT AN OHMMETER
OF
12
VOLT RE.LAY
IS
120
OHMS. RESISTANCE
OF
24
VOLT RELAY
IS
470
OHMS.
FIGURE
29.
TESTING
K11
AND
K12
RELAYS
When connecting battery cables, terminal will spark
if
connection
is
reversed.
Unit will not crank with reversed cables
or
loose
connections.
DC
alternator will overheat and will probably burn up.
A
reverse battery connection will show a maximum
positive charge on the DC ammeter.
On
dry charged batteries, no woltage
is
present until electrolyte
is
added.
See ooerator's manual for alternator belt tension
edjustment.
Check for voltage from starter terminals to ground.
Voltage should be present at both terminals when
solenoid is energized for cranking.
Inspect contacts for dirt particles, obstructions
or
insulating film. Clean, using low pressure com-
pressed air and bond paper. Check relay socket.
Contacts are normally closed when engine is not
running. Contacts must open when engine is running
normal.
IH1
Contacts are normally open; contacts close
for
alarm
condition only. (Overspeed switch may have to be
reset manually.)
'
IJI
Contacts may have welded closed
or
plunger may be
stuck. Remove solenoid from circuit to test for proper
operation.
[KI
Inspect printed circuit board paths that supply
voltage to relay
K12.
(Between terminals 18-19of
300-
0681;
between terminals 7-9 of
300-0679.)
[LI
Remove cycle cranker printed circuit board and
jumper terminal
2-3
to by-pass cycle cranker circuit.
In an extreme emergency, engine may be operated
without any safeties by removing engine monitor
printed circuit board and jumping terminals 7-9. (It
may be easier to jump from center contact
of
Run-
Stop switch to terminal
"B"
on
Kl-2
relay;
see
Figure
30.)
51
Redistribution or publication of this document,
by any means, is strictly prohibited.
SWITCH
..
'.
FIGURE
30.
EMERGENCY
STARTING
ADJUSTING LOW OIL PRESSURE TIME
DELAY ON ENGINE MONITOR PRINTED
CIRCUIT BOARD
Units With Single Fault Lamp:
Potentiometer
RlO
on
A-11 printed circuit board is factory adjusted for 12-
112 seconds
(
?
2-1/2 seconds). To lengthen delay,
use a screwdriver and turn potentiometer clockwise.
To
shorten delay, turn
'
potentiometer coun-
terclockwise. Refer to Figure 31.
Units With Five Fault Lamps:
Potentiometer R15 on
A-
ll
printed circuit board is factory adjusted for 12-1/2
seconds
(2
2-1/2 seconds).
To
lengthen delay, use a
screwdriver and turn clockwise; to shorten delay, turn
counterclockwise. See Figure 32.
ADJUSTING OVERCRANK TIME DELAY
ON ENGINE MONITOR PRINTED CIRCUIT
BOARD
Units With SingleFault Lamp:
Potentiometer R4on
A-
ll
printed circuit board is factory adjusted for
75
seconds
(
r5
seconds).
To
increase delay, use a
screwdriver and turn R4 clockwise; to shorten delay,
turn counterclockwise. See Figure
31.
R4 OVERCRANK DELAY
(FACTORY SET
AT
OIL PRESSURE DELAY
(FACTORY SET AT
\
12%
SECONDS)
Units With Five Fault Lamps:
Potentiometer
H2
on A-
ll
printed circuit board is factory adjusted for
75
seconds
(
'5
seconds).
To
lengthen delay, use a
screwdriver and turn R2 clockwise; to shorten delay,
turn counterclockwise. See Figure 32.
R15
OIL
PRESSURE
AT
12%
SECONDS
DELAY- FACTORY SET
\
R2 OVERCRANK DELAY'
-FACTORY SET AT
75
SECONDS
FIGURE
31.
ADJUSTING TIME DELAYS ON SINGLE
LAYP
ENGINE
MONITOR
FIGURE
32.
ADJUSTING TIME DELAYS ON'FIVE
LAMP ENGINE MONITOR
ADJUSTING OPTIONAL CYCLE CRANKER
The optional cycle cranker
is
factory set:for 15
seconds crank time and, 10 seconds rest time. To
lengthen crank time, .turn potentiometer R4
clockwise; to shorten crank time, turn coun-
terclockwise.
To
lengthen rest time, turn poten-
tiometer R1 clockwise; to' shorten, turn coun-
terclockwise. See Figure 33.
A12 CYCLE CRANKEF
3OOC714-12V.
'
3OOC715-24V.
'
R4 CRANK TIME
FACTORY
SET
AT
15
SECONDS.,
TO INCREASE
TURN CLOCKWISE
R1 REST TIME-
FACTORY SET AT
10
SECONDS.
TO
INCREASE
TURN
CLOCKWISE
1
4
0
FIGURE
33.
OPTIONAL CYCLE CRANKER
ADWSTMENTS
52
Redistribution or publication of this document,
by any means, is strictly prohibited.
WIRING
DIAGRAMS
61
2-41 73
612-3919
625-1007
625-0987
612-4350
612-4353
300-0679
300-0680
300-0681
300-0682
300-071
4
625-1036
61 2-5300
61 2-5301
612-5302
61 2-5303
612-5304
61 2-5305
61 2-5310
61 2-531
1
612-5312
612-5313
PAGE
100-175
kW
Brushless Exciter
......................................
-54
30-90
kW Static Exciter
............................................
-55
VR21 Brushless Exciter
.............................................
56
VR21 Static Exciter
.................................................
57
30-50
kW Controls
.
Single Light
....................................
58
30-90 kW Controls
.
Five Light
......................................
59
Engine Control Monitor
.
12
V
.......................................
60
Engine Control Monitor
.
24
V
.......................................
61
Engine Control Monitor
.
12
V
.
Five Light
............................
62
Engine Control Monitor
.
24
V
.
Five Light
............................
63
Cycle Cranker
.
12
V
...............................................
64
Tap Switch
.........................................................
65
25-90 kW Brushless 15R;
515R
.....................................
166
25-180 kW Brushless, Full Meter Panel
...............................
67
25-45 kW-3R Brushless 120/240
V
.
1
Phase
..........................
68
25-45 kW
.
3R Brushless 120/240
V
.
1
Phase, Full Meter Panel
........
69
25-90
kW 9XR Brushless 347/600V
...................................
70
25-180 kW
.
9XR Brushless 347/600V
.
Full Meter Panel
...............
71
Generator Set Engine Control, 12V Ignition; EK,
EM,
EN
..............
72
Generator Set Engine Control, 12
V
Ignition;
EK,
EM, EN
.............
73
Generator Set Engine Control, 12V ignition;
KR, WA
.................
74
Generator Set Engine Control, 12
V
Ignition;
KR,
WA
.................
75
53
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
...
IC
,a<,
SCHEMATIC DIAGRAM
WIRING MAGRAM
I
1
1
612C4173
I
REAR
VIEW_-P/\NEL
__
-
.--._
..
rnY.!"O*
111.
cfs
PA111
M
ow
C821 3208431
I
CIRCUIT BREAKER. 2hMP
320P307
I
LOCKXKTBRKR HANDLE [PENNSTATE
7
rT6
CONTROL
BOX
(INSIDE) TI T2
FIELO CT21-23 3028743
I
TRANSFORMER ASSY-CUR t25-40KW
.TI2 ,3028744
I
TRWSFORMER ASSY-CUR(41-45KWl
'3088745
I
FIANSFORMER AS=- CUR (466o(wI-
$7
3028746
I
TRANSFORMER ASST-
CUR
(61-lWl(W
3028747
I
TRANSFORMER *SSY~CUR(IOI~IUI:Wl
3028748
I
TRANSFORMER A3SY-CURU26-175KWI
s
1
W
12-
NOTE
SEE VOLTAGE
CHART
a
d
I
M23
I
v
M?4
I
v
HOUSING-CONTROL
BOX
T2
-
n.
T3
7
ELlt3219
3150322
I1
VR21 33201268
1
I
ROARDASSY-PC V0LTA:E RGLTR
VR22 305D49NREa
I
CHASSIS ASSY-VOLTAGE RGLTR
.
WII
3380525
1
I
WIRING HARNESS
W12 336A1913
I
I
LEAO ASSY
NOTE:
CONNECT LEAO W12
FROM
TERMINAL
TB21-63
TO 7821-IH-I
,
PER
VOLTAGE CHART BELOW VOLTAGE CONNECTIONS
-
I---
-
-
,
-
.
..
.
-
.
,--
-..
-.
I15/2WV,
50
Hz. (H41
I39/240V.
60
HZ.(H51
234/40OV,
50
Hz.
(H41
115/23OV, 50Hz,(H61
IZOl2JEV.
60Hz,(H31 240/416V,
60
Hz,(H3)
120/240V, 60H2, (H51 127/220V,
60
Hz,(H41 254/440V,
60
Hz.( H4)
277/480V.
60
Hz. (H51
I'PHASE
115/23OV, 50Hz.
(H61
120/240V, 60Hz.
(H5)
..
..
NOTE.
UNLESS OTHERWISE NOTED,
. .
.
.
.
. .
.
.
-
-
.--,
.--
,
3PH.
50/60Hz
612C4173
-
12
W RECONNECTABLE
Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROL
BOX
(INSIDE)
,
I-
I
WI2-NOTE
SEEVOLTAGE
I
CHART
_-
-
--
HOUSING-CONTROL
BOX
TI
\
T2
T3
\
74
*
\
TS
\
T6
\
77
\
TO
\
T9
I
--
Si!
3
I--
--
F2
FIELD
6
7
8
910
OOQQ?
5
41
GENEfi IATOR
TI
I
(MOUNTED
IN EN)
SCHEMATIC DIAGRAM
m111
,'SI
KxmnM
nr.
KS.
m.
aiv
CBZI 32082
I
CIRCIJI_T BREAKER.IIAW
IZS-WKN
320818
I
CIRCUIT BREAKER. 20WP
(4-90KWl
yOPm7
I
JOBCKT ERKR HANDLE
(PEW
STATE
I'
-T6
:
I
0
I
I
I I
-
-
.-
I
II
--a
-TI1
*TI2
NOTE.
CONNECT LEAD W12 FROM
TERMINAL TB21-63 TO'TEZI.IH,)
PER
CHART
VOLTAGE CONNECTIONS
3
PHASE
-1
110/190V.
5CJHr,
(H3)
115/2WV,
50
Ht.
(H4)
127/220V,
60
Hr,(H41
139/240V,
60
Hr.(H51
220/3EOV,
SO
HI.
(til)
234/400V,
50
HI,
(H4)
240/416V
60
HZ
(H3)
115/23OV. 50H1,
(H6)
120/208V,
60
HZ.lH3)
254/440$60
Hr:(H4)
120/240V,
60Hr,
(H51 277/480V,
60
HZ.
(ti51
I-
I
LI
.
T7
I-
L3
NOTE.
UNLESS OTHERWISENOTED,
ALL COMPONENTS ARE SHOWN
IN THE 0E.ENERGIZED
POSITION
LO
G2A131
'
'
LIGHT-UPPER SCALE
---q
DS22 '.-%2Ti%-$-'
I
LIGHT-LOWER
7
GENEFA-
KL.
x)781061
!
I
TRELAY-VOLTAGE SELECTOR
-
.
30lK.224
11
.BRACKET- RELAY
MTG
_.
LO
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
-
.
.
..
I
1.
.......
.
,\..,.
r
-
625D1007]
.. .
.
;I
!
pi
i
i
I
----
T8
L
VRZl
WARD A5SI-
PC
332DIL68
r
CII
R27
I
100
K
4l-
..
c121-
*--
.47
T
Redistribution or publication of this document,
by any means, is strictly prohibited.
-
I
1.:
I?
12
7
I I .I
I
ID
.
..
---i
_-
N
*ii
58
Redistribution or publication of this document,
by any means, is strictly prohibited.
.
WIRING DIAGRAM
--
-7
612C4353
1
--
(FRONT VIEW1
I
(REAR
VIFYI
ZV
8OMA
hNNUNCIATOR
c
;EMOTE
IUEBCRANK
.ow
oh
PRES!
I1
EN6 TEMP
.C
CNG
TEMP
IVERSPEED
iENERATlNG
I
I6
,1
1)
i
I
9
10
id
II
I
'I
I
I
TO TERM
62
I
8
63
ON
TB21
I
190-24OVAC
NOTES:
I.
W12 USED ON STD CONTROL ONLY
2.USED ON PRE-ALARM CONTROL ONLY
3.REMOTE ALARM CIRCUIT RATED 5AMP
4.SHUTDOWN
8
ALARMS
MAX
4.1
STD CONTROL
4.1.1
SAFETY SHUTDOWN
8
ALARMS
Oh
OVERCRANK,OVERSPEED,HI ENG TEMP
8
LO OIL PRESS
4.1.2 SAFETY ALARM ONLY ON LO ENG
TEMP
4.2
PENN STATE CONTROL
ON OVERCRANK
8
OVERSPEED
4.2.2
SAFETY ALARMS ON
HI
ENG
4.3
PRE-ALARM CONTROL
4.3.1
SAFETY'PRE-ALARMS ON
HI
EN(
TEMP
8
LO OIL PRESS
ON OVERCRANK,OVERSPEED,HI ENG
4.2.1
SAFETY
SHUTDOWN
a
ALARMS
TEM~LO
OIL
PRESS
a
LO
ENG
TEMP
4.3.2
SAFETY
SHUTDOWN
a
ALARMS
TEMP
e
LO
OIL
PRESS
4.3.3
SAFETY
ALARM
ONLY
ON
La
EN(
TEMP
SCHEMATIC DIAGRAM
"
......
"
"..
I63
ON
TBZl
30-24OVAC
,
vi
KI
I
13
n
BUA
WHEN USED
5.S3 OVERSPEEO SWITCH MOUNTED IN
GENERATOR END BELL
ISTP
ICYCLE
&UNLESS OTHERWISE NOTED,ALL CRANKER CR*NKI
-01
-03
COMPONENTS ARE SHOWN IN THE
DE-ENERGIZED POSITION .ICRE+iLARMBPENH $TATELSWE&QF)
-01
,-04
ST^
C~NTROL
IHlADDCD
DDA.DDB,DYJ
F?'p
s4
PENN STATE (SPEC:C,D,E.ECI
-0s
-06
I
CBI
1201%3-
I
CIRCUII
BREIKtR.
I7
5
AIP(0VC
OHLVJ
,
El
1931108
I
StNOER
-011
PRESSURE
12
1931109
I
SEWOER-WATER
TEMP
<OVA. OK)
193A104
I
SINOER-WATER
TEMP. (OEF.
OEH.
OEC)
I
FUEL
PUMP
_.
-
I
I1
SI
I
I
I
I
SWIICH-LOW
Dl1
PRESSURE
s2
I
1
I
1
SIlTCH-HIGH
WATER
TEMP
53
I
I
1
f
SIITCH-OYIRSPfEO
I
I
S6
SWITCH-LOU
011
PRESS
(PRE.lJARI)
'
-
4;
57
I
SIITCH-HIGH
WATER
TEMP
(PM-ALARM)
-
.
s5
I
I
S?ITCH-LOI
lITfR
TEMP
Redistribution or publication of this document,
by any means, is strictly prohibited.
Q)
0
I
.
300C679
I
FUELSOL
>R
IGN
RLLl
7
17-
9
t
X5
I
HOW:
1.
SOLDER fER SOLDERIH6 PROCESS MIL-S-1872 USINS SOLDER.
ITEM
23.
2.
SOLDER
JOlHlS
AN0
OR CWONENT
LEAOS
SHALL
NO1
PWOJECT
MORE
THAN
346
BLYOND SURFACE
OF
BOARD.
3.
FAClORl AOJUST
POTEHTIOYETER
R13
FOR
12.5
f
2.5
SECONDS
LOP
01111.
FACTORY
AOJUST
POTENTIDPETER
R4
FBR
75
2
IO
SECONDS OVERCRdK
01111.
@
A9
19
350-517
I
RESISTOR
27n
RE
I8
550-505
I
RESISTOR
2.711
I7
350-572
I
RESISTOR
I
iim
.RtO
16
3031169 2
POTENTIOIETER
3.5
YEm
A6
15
350-552
1
RESISTOR
22m
A2
14
350-526
I
RESlSlOR
15On
PI
I1
I3
350-536
2
RESIPIOP.
loom
--1
Redistribution or publication of this document,
by any means, is strictly prohibited.
7
8
9
IO
II
I2
I3
I4
1111111'1111
FUEL
SQL
OR
IGN
RELAY
7
8
I-~-n
n
D
NOTES'
I.
SOLOEk
?ER
SOLOLklNf
PROCESS
MIL-S-6172
USINC
SOLOER.
ITEN
23
SOLOER
JOINIS
ANU'OR'COYPONEkT
LEAOS
SWLLL
HOT
PHOJECI
MORE
IHAN
3
16
3tlWO
SURfACL
OF
EOARO.
2
3.
SET
R4
FOR
AN OVERCRANK
TIME
OELAV
Of
1525
SEMNOS
4.
ton
OIL
PRESS
TIME
OELAY
SHOULD
BE
iz.5iz.5
SECOHDS
Redistribution or publication of this document,
by any means, is strictly prohibited.
I
71
P
62
Redistribution or publication of this document,
by any means, is strictly prohibited.
d
CB
MI
NII
...
BY
AVl3U
N9I
-_
:
I
'.\
.
I
Redistribution or publication of this document,
by any means, is strictly prohibited.
@
NOlcS:
I.
REMOX JiiMFER
W12
BiXEEN
TB21-i3
&
Ta21-H3.
MOUNT VOLTllGC SELECTOR RELAY
X!!j
IN UOKTROL
BOX AND llRE
A;
SHOWN. RELAY
WILL
ENEOGIZ:
Oi4
120
'29BV
30
CIRCUIT COMPLETING CONNECTION
DE-ENERGIZED ON 120/240,11 CIRCUIT COMPLETING
BETWEEN TB21-63
I
TB21-H3. RELAY
WILL
RElAAlN
I
CONNECTION BETWEEN TB21-63
&
TB21-H5.
-1
---
e
----
.
EQUIVALENT
CIRCUIT
h
A
\-
I
L3
120/208V,
3@
L3
120/240
V,
I
#
I
I
I
I
Redistribution or publication of this document,
by any means, is strictly prohibited.
11115
L'51
WRING SCHEMATIC DIAGRAM
'
DIAGRAM
.
MXfiIIItON
;if.
DES
1
mr
NO
law
I
CEkTROL
BOX
(INSIDE)
--
CB21
1
3208431
I
I
IClRCUlT BREAKER.2AMP
T5
,
I
/0
/?
I
I
t
---
I__
__
- -
HOUSING-CONTROL
BOX
NOTE
CONNECT LEAD W12 FROM
TERMINAL T821.63 TO TL12I.IH-I
PER VOLTAGE CHART BELOW
110/220V
SOHz
IH6l
=115/230< 50Hz:IH6l
1%
120/240V,
60Hz.
!H5l
G21
7
VOLTAGE CONNECTIONS
3
PHASE
-
-
.
__
127/220V,
50
Hz.
1H51
120R08V.
50
Hz.1H41
110/190V. 50Hz.IH31
115/2OOV.
50
HI.
IH41
1201208V. 60HZ.IH31
127/220V,
60
Hz.~H4~
139/240V.
60
HZ.IH51
LO
L3
'
L3
T5
NnTF.
-
UNLESS OTHERWISE NOTED,
ALL COMPONENTS ARE SHOWN
IN THE DE.ENERGIZED
,
POSITION
230/400V.
50
HI. 1H41
-240/416V;
60
Hzi(H31
254 /440V,
60
HI,
I
H41
27?/480V. 60Hz.
1H51
GENERATgR
RELAY-VOLTAGE
SELEZR-
~21
i
3~3~1szi-
i
I
i
RHEOSTAT-VOLTAGE
ADJ
35~35~
I
303P32
I
I
IKNOB-RHEOSTAT
I II
R22
1350-5561REfll
I
I
RESISTOR.47,ODO. IIPWATT
I1
33201956
I
I
1
BOARDASSY-PC VOLTAGE RGLTR
I,
.
._
545A22
1.
I%R%
L%T -AC CONT HOW.
110/220V 50Hz (H61
-
51%
I
I5123OV:
50
HI: IH61
15R120/240V. 60H1. 1H51
1-
--I
'
60
Hz
I
PfNN
6&
Ik
-01
ps
Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROL
BOX
(INSIDE)
I
C
I
WI2-NOTE.
SEE
VOLTAGE
CHART
t
TOVRZl
'
1
I'li
I
HOUSING-CONTROL
BOX
z
EXCITER
GENERATOR
I
545A23
I
II
,!
I
I
I
WRTS LIST-AC CONT HDW
Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROL BOX IINS-IEE
-
-
-
--
- -
USING-CONTROL
BOX
L:
LO
GENERATOR
I
CR4 CRS CR6
ALTERNATOR.
FIELD
T2
VOLTAGE CONNECTION
1201240
V
F::
L2
T2
SCHEMATIC DIAGRAM
0
\
‘2
T
L2
pk/3D1II1LIM.$GiE7K-.S.O-.OOYI
302-0466
P
METER-RUNNING TIME
VR21
1332-19SS(
D
I
I
I
BOARD 4SSY-PC VOLTAGE RGLTR
I
I1
I
1330-076S
I
D
1
I
I
WIRING
HARNESS
I
I1
I
WIZ
(336-1913
I
AI
I
ILEA0 ASSY
I II I
I
!I I
{
ZOEG-Z19
I
iI
I
NOTE:
UNLESS OTHERWISE NOTED,
ALL COMPONENTSARE SHOWN
POSITION.
(WIRING DIAGRAM)
.
IN THE DE-ENERGIZED
612-5302
l20/24CV.
IPH.
.-
Redistribution or publication of this document,
by any means, is strictly prohibited.
WIRING DIAGRAM SCHEMATIC DIAGRAM
AC CONTROL
PARTS
1151
D
KEf.
CfS.
PART
NO.
',:
an.
CfYRlPllON
EXCITER CB21 320.0431
0
I
CIRCUIT BREAKER,ZA
12-5303
I
REAR
VILE
PANEL
320-0307 P
I
LOCK-CKT BRKR HANDLE(PENN STATE1
ARMATURE
1
wF/
FI
2
=
FOR
VR
SYSTEM SCHEMATIC
~
CR21
105-0524
C
I
RECTIFIER BRIDGE
CT21.22 302-0739 B
I
TRANSFORUER ASSI-CUR
SE -24S(Dl
/
CONTROL BOX IINSIDEI
,
---
I
I1
I
621
I
I
1
I
lGENERATOR
L21 1315-0384
I
B
1
I
I
REACTOR ASS1 COMY
1
Ii
WI2
I1
I
I
I
I
I
II
I
Mz
3
USING.CONIROL
BOX
--]I
-2J7g
CT22
1
TI
T2
\
CT22
TO
I
EOES-119
:
I
I II I
I
GENERATOR
I
I-
VOLTAGE CONNECTION
1201240 V
u
ALTERNATOR
FIELD
.
UL2
CT22
i
ll
Redistribution or publication of this document,
by any means, is strictly prohibited.
WIRING DIAGRAM
512-5304
I
REAR
VIEW-YNEL
SCHEMATIC DIAGRAM
621
CONTROL BOX IINSIDEI EXCITER
O
,,,
FOR
VR SEE625-1245101 SYSTEM SCHEMATIC
f
CR21
I
SWITCH-VOLTMETER
SELECTOR
I
I
303-00761
-'
I
KNOB
M22
v
I
I
I
I
1
I
HOUSING-CONTROL
BOX
I
I
I
I
I
I
I
I
I
I
I
I.
:
I
ItOES
-
2
19
I
I
I
I
I
I
I
I
I
GENERATOR
VOLTAGE CONNECTION
3
PHASE, 347/600V
I
II
I
II
I
I
ALTERNATOR
FIELD
T3
67.1
9
65
TO
'I
I
NOTE:
UNLESS OTHERWISE NOTED,
ALL COMPONENTS ARE SHOWN
IN THE DE-ENERGIZED
POSITION.
Redistribution or publication of this document,
by any means, is strictly prohibited.
5
KW
60H
PLNNW
2535
-01
-07
36-55
-02
-08
56-70
-03
-09
71-110
-04
-10
Ill
-145
-05
-11
146-180
-06
-12
L3
..
NOTE:
ALL
COMPONENTS ARE SHOWN
IN THE DE-ENERGIZE0
POSITION.
OWL
(WIRING DIAGRAM)
B~US~L~SS
4W.,60
HZ
347/ECOV, 3PH,
612-5305
WIRING DIAGRAM
612-5305
I
REAR_VI_EW
PANEL
SCHEMATIC DIAGRAM 'G21
CONTROL
BOX
l!NSIDE)
I
b
K
T21
8
f
T21
w12
r-
A
I I
I
II
I
I
I1
I
L21
1115-03841
81
I
I
REACTOR ASSYCOMM
M23
n
TO VR21
M22
3020779
P
I
.
~~LTMETER+C.O-75OV I300V
M23
302-0221
B
I
METER-FkEOUENCVf240)
M24
3024466
P
I
METER-RUNHINO TIME (240Vl
-
MOVEMENT)
IM
lG
F
---
---
USING-CONTROL
BOX
I
nrr
L3
II
EXCITER EXClIER F+ GENERATOR
......-..
^-
I
II
I
II
I
I
I
i
I
It
I
I
VOLTAGE CONNECTION
3PHASE.S47/600V,
60Hr
ALTERNATOR
FIELO
65
lCT23
Redistribution or publication of this document,
by any means, is strictly prohibited.
03511
N~IM
.
I
-7NOW.03 WYVlV
8
k-
ON9
E
310N WlV
SS3Md
110
01
9
dW31
OR3
lH'O33dSY3AO'nNVY3Y3AO
NO
SWYVlV
B
AMOOlllHS
,413315
Z'E'b
SS3Yd
110
01
9
dW31
N3 IH NO SWYVlV-3Yd
A133VS
I'E'b
lOYlN03 WYVlV-3Yd E'b
dW32 ON3
01
6
SS3Yd
110
OlW31
ON3 IH NO SWMVlV
,413315
2.Z.b
033dSY3A0
6
XNVt(3Y3A0
NO
5WYllV
9
NMOalnHS
A133VS
1'2'b
lOYlN03
31VlS
NN3d
Z'b
dW31
9N3
01
NO AlNO WYVlV
Al3jVS
Z7.b
SS3Yd
110 01
9
dW31
ON3 IH'a33dSY3AO1YN1Y3Y3AO
0
SWYVlV
9
NMOOlnHS
,41331s
1'1%
10YlN03
01s
I'b
SWYVlV
6
NM001nHS'b
dWVS
031VY
lln3Y13
WYVlV
310W3Y'E
AlNO
lOYlN03
WYVlV-3Yd
NO
a3Sll'Z
S310h
XVW
AiNo
~OYINO~
ais
NO
a3sn
ZIM'I
-
-_
I-
IIW
ONllVYPNB
dN31
9N3
0'
dA31
IN3
I1
S53Md
110
MO
XNVM3M3A(
a
Redistribution or publication of this document,
by any means, is strictly prohibited.
.
NOI+ISOd
03ZIDM3N3-30
3Hl NI NMOHS
3MV
SlN3NOdW63
111
'0310N 3SIMU3HlO SS3lNfl
'C
1130 dN3 U01VM3N3B
N1
03LNflOW
HJllMS
033dSM3AO
€S
'E
SS3tldllO
01
B
dW32
033dSM3AO
9)INVt13L13hO
NO
WWlV
B
NMOOlflHS
A13dVS
1'2'2
lOMlN03
31VlS
NN3d
2'1
SS3Ud
110
01
B
dW31 BN3 IH'a33dSM~AO1HNVM3n3AO
0
WLlVlV
9
NMOOLnHS
A13
NS
1.1'7.
3~3
IH
NO
wnviv
AIPJVS
zzz
10~~03
ais
1.1
SHMVlV
B
NMOOlflHS
'1
xvw
dKJS
031V8 Llfl3M13
WWlV
310W3M
'I
:S310N
I
3VA
OCZ-061
1201
NO
E9
W
29
wn3i
01
4
-I --
I
....
.
.
.
.
.- .~
..
.
Redistribution or publication of this document,
by any means, is strictly prohibited.
.
t
-
L
w
>
I
75
Redistribution or publication of this document,
by any means, is strictly prohibited.
Redistribution or publication of this document,
by any means, is strictly prohibited.
c
Redistribution or publication of this document,
by any means, is strictly prohibited.
i
Onan Corporation
1400 73rd Avenue N.
E.
Minneapolis, MN 55432
Telex: 275477
Fax: 612-574-8087
Onan
is
a
registered trademark
Of
Onan
Corporation
61 2-574-5000
Redistribution or publication of this document,
by any means, is strictly prohibited.