VEEDER ROOT PETRO Gauge TLS350 Serial Interface Manual

User Manual: manual pdf -FilePursuit

Open the PDF directly: View PDF PDF.
Page Count: 704

DownloadVEEDER - ROOT PETRO Gauge TLS350 Serial Interface Manual
Open PDF In BrowserView PDF
VEEDER - ROOT
SERIAL INTERFACE MANUAL
for
TLS-300 and TLS-350
UST Monitoring Systems
and
TLS-350R
Environmental & Inventory
Management System
through Software Versions 020/133/333/433/520
Manual Number 576013-635
Revision AA

NOTICE
Veeder-Root makes no warranty of any kind with regard to this publication, including but not
limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this publication.
The information contained in this publication may be subject to change without notice.
This publication contains proprietary information which is protected by copyright. All rights
reserved. No part of this publication may be photocopied, reproduced, or translated to another
language without the prior written consent of Veeder-Root.

©Veeder-Root 2014. All rights reserved.

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
NOTICE ............................................................................................................................................................................... ii
1.0
INTRODUCTION ................................................................................................................................................... 1
2.0
HARDWARE CONNECTIONS .............................................................................................................................. 1
2.1
RS-232 ............................................................................................................................................................... 1
2.2
EIA RS-232 INTERFACE ................................................................................................................................... 1
2.3
INTERNAL MODEM........................................................................................................................................... 2
3.0
CHARACTER FORMAT AND BAUD RATE .......................................................................................................... 2
4.0
SWITCH SETTINGS .............................................................................................................................................. 2
4.1
DIP SWITCH ...................................................................................................................................................... 2
5.0
COMMAND MESSAGE FORMAT ......................................................................................................................... 3
6.0
RESPONSE MESSAGE FORMAT ........................................................................................................................ 4
6.1
COMPUTER FORMAT ...................................................................................................................................... 4
6.2
DISPLAY FORMAT ............................................................................................................................................ 4
6.3
ASCII FLOATING POINT FORMAT .................................................................................................................. 5
6.3.1
NOTES ....................................................................................................................................................... 5
6.3.2
EXAMPLES ................................................................................................................................................ 6
7.0
FUNCTION CODES AND RESPONSE MESSAGES ............................................................................................ 7
7.1 CONTROL FUNCTIONS ........................................................................................................................................ 9
7.2 OPERATIONAL REPORTS .................................................................................................................................. 37
7.2.1 SYSTEM REPORTS ..................................................................................................................................... 37
7.2.2 IN-TANK REPORTS...................................................................................................................................... 58
7.2.3 SENSOR REPORTS ................................................................................................................................... 101
7.2.4 LINE LEAK REPORTS ................................................................................................................................ 123
7.2.5 MISCELLANEOUS REPORTS ................................................................................................................... 142
7.2.6 I/O DEVICE REPORTS ............................................................................................................................... 145
7.3 SETUP FUNCTIONS & REPORTS .................................................................................................................... 152
7.3.1 SYSTEM SETUP ......................................................................................................................................... 152
7.3.2 COMMUNICATIONS SETUP ...................................................................................................................... 181
7.3.3 WARNING, ALARM, & AUTO-PRINT SETUP ............................................................................................ 202
7.3.4 IN-TANK SETUP ......................................................................................................................................... 244
7.3.5 SENSOR SETUP ........................................................................................................................................ 314
7.3.6 VOLUMETRIC LINE LEAK SETUP ............................................................................................................. 347
7.3.7 PUMP SENSOR SETUP ............................................................................................................................. 366
7.3.8 PRESSURE LINE LEAK SETUP................................................................................................................. 372
7.3.9 RECONCILIATION SETUP ......................................................................................................................... 403
7.3.10 WIRELESS PLLD SETUP ......................................................................................................................... 419
7.3.11 METER MAP & DELIVERY TICKET SETUP ............................................................................................ 435
7.3.12 PUMP MONITOR RELAY SETUP ............................................................................................................ 442
7.3.13 I/O DEVICE SETUP .................................................................................................................................. 448
7.3.14 EEPROM SETUP ...................................................................................................................................... 462
7.3.15 MISCELLANEOUS SETUP ....................................................................................................................... 465
7.4 DIAGNOSTIC REPORTS ................................................................................................................................... 483
7.4.1 SYSTEM DIAGNOSTIC REPORTS ............................................................................................................ 483
7.4.2 IN-TANK DIAGNOSTIC REPORTS ............................................................................................................ 489
7.4.3 SENSOR DIAGNOSTIC REPORTS ........................................................................................................... 519
7.4.4 LINE LEAK DIAGNOSTIC REPORTS ........................................................................................................ 537
7.4.5 RECONCILIATION DIAGNOSTIC REPORTS ............................................................................................ 564
7.5 RECONCILIATION REPORTS ........................................................................................................................... 570
7.6 VARIANCE ANALYSIS REPORTS..................................................................................................................... 585
7.7 IN-STATION DIAGNOSTICS (ISD) .................................................................................................................... 598
7.7.1 ISD REPORTS ............................................................................................................................................ 598
7.7.2 ISD SETUP.................................................................................................................................................. 635
7.7.3 ISD DIAGNOSTIC REPORTS..................................................................................................................... 653
8.0 IFSF DATABASE SUPPORT .................................................................................................................................. 675
8.1 TANK LEVEL GAUGE DATABASE .................................................................................................................... 675

Part No. 576013-635, Revision AA

iii

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
8.2 TANK LEVEL GAUGE ERROR CODE DATABASE .......................................................................................... 676
8.3 TANK PROBE DATABASE ................................................................................................................................ 676
8.4 TANK CONTENTS TABLE DATABASE ............................................................................................................. 678
8.5 TANK TEMPERATURE TABLE DATABASE ..................................................................................................... 678
8.6 TANK PROBE ERROR CODE DATABASE ....................................................................................................... 678
8.7 DATA DOWNLOAD DATABASE........................................................................................................................ 679
8.8 COMMUNICATION SERVICE DATABASE........................................................................................................ 679
9.0 FUNCTION CODE SUMMARY ............................................................................................................................... 680
CONTROL FUNCTIONS (7.1) ................................................................................................................................... 680
OPERATIONAL REPORTS (7.2) .............................................................................................................................. 681
SYSTEM REPORTS (7.2.1) .................................................................................................................................. 681
IN-TANK REPORTS (7.2.2) .................................................................................................................................. 681
SENSOR REPORTS (7.2.3) ................................................................................................................................. 682
LINE LEAK REPORTS (7.2.4) .............................................................................................................................. 683
MISCELLANEOUS REPORTS (7.2.5) .................................................................................................................. 683
I/O DEVICE REPORTS (7.2.6) ............................................................................................................................. 684
SETUP FUNCTIONS & REPORTS (7.3) .................................................................................................................. 684
SYSTEM SETUP (7.3.1) ....................................................................................................................................... 684
COMMUNICATIONS SETUP (7.3.2) .................................................................................................................... 685
WARNING, ALARM, & AUTO-PRINT SETUP (7.3.3) .......................................................................................... 685
IN-TANK SETUP (7.3.4)........................................................................................................................................ 687
SENSOR SETUP (7.3.5) ....................................................................................................................................... 689
VOLUMETRIC LINE LEAK SETUP (7.3.6) ........................................................................................................... 690
PUMP SENSOR SETUP (7.3.7) ........................................................................................................................... 690
PRESSURE LINE LEAK SETUP (7.3.8) ............................................................................................................... 691
RECONCILIATION SETUP (7.3.9) ....................................................................................................................... 691
WIRELESS PLLD SETUP (7.3.10) ....................................................................................................................... 692
METER MAP & DELIVERY TICKET SETUP (7.3.11)........................................................................................... 692
LINE/PLLD/WPLLD SETUP .................................................................................................................................. 693
PUMP MONITOR RELAY SETUP (7.3.12) ........................................................................................................... 693
PRESSURE LINE LEAK SETUP (refer to 7.3.8) ................................................................................................... 693
PUMP SENSOR SETUP (refer to 7.3.7) ............................................................................................................... 693
I/O DEVICE SETUP (7.3.13) ................................................................................................................................. 693
EEPROM SETUP (7.3.14) .................................................................................................................................... 694
MISCELLANEOUS SETUP (7.3.15) ..................................................................................................................... 694
DIAGNOSTIC REPORTS (7.4) ................................................................................................................................. 695
SYSTEM DIAGNOSTIC REPORTS (7.4.1) .......................................................................................................... 695
IN-TANK DIAGNOSTIC REPORTS (7.4.2) ........................................................................................................... 695
SENSOR DIAGNOSTIC REPORTS (7.4.3) .......................................................................................................... 696
LINE LEAK DIAGNOSTIC REPORTS (7.4.4) ....................................................................................................... 696
RECONCILIATION DIAGNOSTIC REPORTS (7.4.5) .......................................................................................... 697
VARIANCE ANALYSIS REPORTS (7.6) ................................................................................................................... 698
IN-STATION DIAGNOSTICS (ISD) (7.7)................................................................................................................... 698
ISD REPORTS (7.7.1) ........................................................................................................................................... 698
ISD SETUP (7.7.2) ................................................................................................................................................ 698
ISD DIAGNOSTIC REPORTS (7.7.3) ................................................................................................................... 699

Part No. 576013-635, Revision AA

iv

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

1.0

INTRODUCTION

The serial RS-232 interface is used to connect the system to a controlling computer, a display terminal
(CRT) or a printing terminal. A modem can be connected directly to the system to provide telephone
line access.
NOTE: The software versions for these systems vary depending on when they were purchased and if
software upgrades have been installed. The version in which each function code first appeared is
indicated in a box next to its description in Section 7. Commands appearing in software versions greater
than 100 are only active in systems equipped with an ECPU.

2.0

HARDWARE CONNECTIONS

The RS-232 interface is a module accessed via a 25-pin D-connector located on the bottom-left of the
console.

2.1

RS-232

The RS-232 D-connector is a panel mount, 25-pin female type, wired in a Data Terminal Equipment
(DTE) configuration. A modem (DCE) may be connected directly to the interface using a straightthrough cable. A CRT or printing terminal (DTE) may be connected to the interface by using a null
cable which reverses the sense of the transmit/receive signals. The system does not require or activate
any handshake signals.
RS-232 signals are wired to the female D-connector as follows:
PIN
2
3
7

2.2

Transmitted Data
Received Data
Signal Ground (common return) and Chassis

EIA RS-232 INTERFACE

The EIA RS-232 interface is designed to connect to modems for transmission of data over telephone
lines. It can be used for direct local attachment of terminals if the cable run is no more than 50 feet. In
practice, cable runs longer than 50 feet have performed satisfactorily; however, since the RS-232
specification is designed for operation up to 50 feet, direct connect cable runs greater than 50 feet are not
warranted for proper operation.

Part No. 576013-635, Revision AA

1

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
2.3

INTERNAL MODEM

The optional internal modem operates at up to 2400 Baud. The modem module contains two RJ11 jacks
for phone line connections, and is accessible at the bottom left of the console.

3.0

CHARACTER FORMAT AND BAUD RATE

The system receives and sends characters via the RS-232 interface in an ASCII format that is configured
via the system front panel keypads. Selections consist of: 1 start bit; 7 or 8 data bits; odd, even or no
parity; and 1 or 2 stop bits. Communications rate is selectable: 300, 1200, 2400, 4800 or 9600 baud.
The system operates in a full duplex mode. Characters are not echoed when received, and transmitted
characters must not be echoed back to the system. Transmit and receive can occur simultaneously, and
commands can be stacked in the system buffer (up to 128 characters).

4.0

SWITCH SETTINGS

4.1

DIP SWITCH

A four-position DIP switch is located on the CPU board, which is mounted in the right-back of the
console printer compartment. The DIP switch is next to the battery switch. The DIP switch positions
are assigned as follows:
Switch
1

Front Panel Setup Security Enable

2

RS-232 Security Enable

3

Unused

4

Fiscal Height Security

Part No. 576013-635, Revision AA

2

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

5.0

COMMAND MESSAGE FORMAT

All command and response messages are configured in a format which includes a surrounding envelope
of control characters and a function code and data field message. The control characters are described in
this section while the function codes and data field messages are described in subsequent sections.
The system responds to a command message that has the following configuration:
SOH

Security Code

Function Code

Data Field

SOH is a control-A character (ASCII 01).
The RS-232 security code is an optional six-digit code used to limit external serial access to the system
for security purposes. It can be set to any unique set of characters using either the front panel switches
or the external communication interface setup commands. The system will not respond to a command
without the proper security code, if the DIP switch is set to enable RS-232 security.
The function code is a six character command code which the system interprets to determine the type of
action to take and response to return. System function codes and response messages are defined in
subsequent sections.
The data field is optional and contains information necessary to perform the selected function (such as
setup information).
If the system receives a command message string containing a function code that it does not recognize, it
will respond with a 9999FF1B. The "9999" indicates that the system has not understood
the command, while the "FF1B" is the appropriate checksum for the preceding 9999 string.
There is one command which does not follow the above format. The escape command is performed by
sending an ESC (escape character, ASCII 27), to the system. It is a means to halt a response message at
any time before its completion.

Part No. 576013-635, Revision AA

3

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

6.0

RESPONSE MESSAGE FORMAT

There are two types of response message formats: computer (or packed data format) and display format.
Each format uses a different surrounding envelope of control characters.

6.1

COMPUTER FORMAT

The computer format is a stream of numbers without any formatting characters; i.e., carriage return, line
feed, spaces, labels, etc. The message format is as follows:
SOH

Function Code

Data Field

&&

Checksum

ETX

The function code is identical to the received command message function code.
The data field contains the response message which is described in subsequent sections.
The "&&" is a fixed tag character which indicates that the checksum immediately follows.
The Checksum is a series of four ASCII-hexadecimal characters which provide a check on the integrity
of all the characters preceding it, including the control characters. The four characters represent a 16-bit
binary count which is the 2's complemented sum of the 8-bit binary representation of the message
characters after the parity bit (if enabled) has been cleared. Overflows are ignored. The data integrity
check can be done by converting the four checksum characters to the 16-bit binary number and adding
the 8-bit binary representation of the message characters to it. The binary result should be zero.
ETX is programmable if enabled via the S53100f command. If it is disabled, the ETX is a fixed
Control-C character (ASCII 03). Caution should be taken before changing the ETX character, because it
affects the transmitted messages on ALL communications ports of the system, and additional host
devices may be connected to other ports which expect the ETX to be a Control-C.

6.2

DISPLAY FORMAT

The display format is intended for display on a CRT or printer. It includes all the necessary formatting
characters such as carriage returns, line feeds, nulls, spaces, labels, etc. The message format is as
follows:
SOH

Function Code

Data Field

ETX

See subsequent sections for a description of the data field response messages.

Part No. 576013-635, Revision AA

4

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
6.3

ASCII FLOATING POINT FORMAT

6.3.1 NOTES
6.3.1.1

HHHHHHHH (H = 0-9 or A-F) indicates the 8 "nibble" ASCII-Hexadecimal representation of
a 4-Byte Floating Point number. Many data parameters are transmitted in this format.

6.3.1.2

The 32-bits are arranged as follows:

Byte

Nibble

1

2

3

4

S EEE

EEEE

E MMM

MMMM

MMMM

MMMM

MMMM

MMMM

1

2

3

4

5

6

7

8

S is the sign bit (0 if positive, 1 if negative).
EEE EEEE E represents the 2's exponent. It is a 2's complement value biased by 127 (7F
Hex). The exponent can be determined by subtracting 127 from the value of the E field and
raising 2 to the resulting power.
MMM MMMM MMMM MMMM MMMM MMMM represents the 23-bit mantissa. Since
the mantissa describes a value which is greater than or equal to 1.0 and less than 2.0, the 24th
bit is always assumed to be equal to 1 and is not transmitted or stored. The value23of the
mantissa can be determined by dividing the value of the M field by 8,388,608 (2 ) and adding
1.0.
6.3.1.3

The complete value of the floating point number can then be determined by multiplying the
exponent by the mantissa and attaching the appropriate positive or negative sign.

6.3.1.4

By convention,
00 00 00 00 represents the value 0.0 even though it actually converts to 5.8775
x 10-39.

6.3.1.5

The eight "nibbles" are transmitted in sequence from 1 through 8 as shown in section 6.3.1.2.

Part No. 576013-635, Revision AA

5

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
6.3.2 EXAMPLES
6.3.2.1

3F800000 hex = 0011 1111 1000 0000 0000 0000 0000 0000 bin
S = 0 = + (positive)
E = 011 1111 1 bin = 7F hex = 127 dec
M = 000 0000 0000 0000 0000 0000 bin = 0 hex = 0 dec
Exponent = 2(127-127) = 1.0
Mantissa = 1.0 + (0/8,388,608) = 1.0
Decimal Value = +1.0 x 1.0 = 1.0

6.3.2.2

B8D1B717 hex = 1011 1000 1101 0001 1011 0111 0001 0111 bin
S = 1 = - (negative)
E = 011 1000 1 bin = 71 hex = 113 dec
M = 101 0001 1011 0111 0001 0111 bin = 51 B7 17 hex = 5,355,287 dec
Exponent = 2(113-127) = 0.0000610352
Mantissa = 1.0 + (5,355,287/8,388,608) = 1.63840
Decimal Value = -0.0000610352 x 1.63840 = -0.0001

6.3.2.3

C2C7FAE1 hex = 1100 0010 1100 0111 1111 1010 1110 0001 bin
S = 1 = - (negative)
E = 100 0010 1 bin = 85 hex = 133 dec
M = 100 0111 1111 1010 1110 0001 bin = 47 FA E1 hex = 4,717,281 dec
Exponent = 2(133-127) = 64
Mantissa = 1.0 + (4,717,281/8,388,608) = 1.56234
Decimal Value = -64 x 1.56234 = -99.99

6.3.2.4

461C4000 hex = 0100 0110 0001 1100 0100 0000 0000 0000 bin
S = 0 = + (positive)
E = 100 0110 0 bin = 8C hex = 140 dec
M = 001 1100 0100 0000 0000 0000 bin = 1C 40 00 hex = 1,851,392 dec
Exponent = 2(140-127) = 8,192
Mantissa = 1.0 + (1,851,392/8,388,608) = 1.22070
Decimal Value = +8,192 x 1.22070 = 10,000

Part No. 576013-635, Revision AA

6

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

7.0

FUNCTION CODES AND RESPONSE MESSAGES

All response messages are sent in a format described in previous sections. The function codes and data
fields of these message formats are described in this section. The data field response messages are
divided into the following major groupings:
Function Codes ................................................................................................................. Response Types
001 to 09B .........................................................................................................................Control Functions
101 to 132 ...................................................................................................... Operational Reports (System)
201 to 2E2 ...................................................................................................... Operational Reports (In-tank)
301 to 34C ....................................................................................................... Operational Reports (Sensor)
351 to 389 ................................................................................................. Operational Reports (Line Leak)
391 to 392 ...........................................................................................Operational Reports (Miscellaneous)
401 to 412 ................................................................................................ Operational Reports (I/O Device)
501 to 51E ........................................................................................... Setup Functions & Reports (System)
520 to 531 ........................................................................... Setup Functions & Reports (Communications)
532 to 5E2 ..................................................... Setup Functions & Reports (Warning, Alarm, & Auto-print)
601 to 683 ........................................................................................... Setup Functions & Reports (In-tank)
701 to 74E ............................................................................................Setup Functions & Reports (Sensor)
751 to 7BC .................................................................. Setup Functions & Reports (Volumetric Line Leak)
771 to 7DC ................................................................................ Setup Functions & Reports (Pump Sensor)
774 to 7D9........................................................................ Setup Functions & Reports (Pressure Line Leak)
790 to 79F ............................................................................... Setup Functions & Reports (Reconciliation)
7A0 to 7BE ............................................................................ Setup Functions & Reports (Wireless PLLD)
7B1 to 7B6 ......................................................Setup Functions & Reports (Meter Map & Delivery Ticket)
7C4 to 7C9 .................................................................... Setup Functions & Reports (Pump Monitor Relay)
801 to 813 ..................................................................................... Setup Functions & Reports (I/O Device)
851 to 853 ...................................................................................... Setup Functions & Reports (EEPROM)
881 to 8C4 ............................................................................... Setup Functions & Reports (Miscellaneous)
901 to 908 ....................................................................................................... Diagnostic Reports (System)
A01 to A91....................................................................................................... Diagnostic Reports (In-tank)
B01 to B4B ...................................................................................................... Diagnostic Reports (Sensor)
B50 to B8E .................................................................................................. Diagnostic Reports (Line Leak)
B91 to BB1 .......................................................................................... Diagnostic Reports (Reconciliation)
C01 to C09 ................................................................................................................ Reconciliation Reports
C10 to C25 .......................................................................................................... Variance Analysis Reports
V00 to V12................................................................................................. In-Station Diagnostics (Reports)
V40 to V52.................................................................................................... In-Station Diagnostics (Setup)
V80 to XE0 ......................................................................................... In-Station Diagnostics (Diagnostics)

Part No. 576013-635, Revision AA

7

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Most response messages can be requested for either a single device (tank, sensor, line, etc.) or all
devices. A "TT" in the function code signifies single device number 01 through 16. When "TT" is 00, it
signifies all devices.
Typically, response messages include information on the active devices only. That is, those devices that
are connected and working. However, the system can be forced to send data on inactive devices by
using an inactive device number. In this case, if no valid data is available on a device, the message is
filled out with question marks (?) in the place of numbers.
Computer format response messages do not include any formatting characters such as carriage returns,
line feeds, spaces, nulls, labels, etc. Only those characters shown are actually included in the response
message. For convenience, the messages are shown in segments and do not actually include any line
feeds, carriage returns, etc. Also, the notes to the right and between the message lines are not included
in the messages. All number values contained in the response messages retain leading zeroes.
Display format response messages include the formatting characters shown. All message lines end with
a carriage return, line feed and six nulls. All response messages start and end with at least one blank
line.
The system function codes and response messages are described in detail in the following sections under
the major headings given above. A summary list of all function codes is given at the end of this
document.

Part No. 576013-635, Revision AA

8

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.1 CONTROL FUNCTIONS
Function Code: 001
Function Type: System Reset

Version 1

Command Format:
Display: S00100
Computer: s00100
Typical Response Message, Display Format:

S00100
MAR 27, 1996


4:47 PM

Typical Response Message, Computer Format:
s00100YYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

9

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 002
Function Type: Clear Power Reset Flag

Version 1

Command Format:
Display: S00200
Computer: s00200
Typical Response Message, Display Format:

S00200
MAR 27, 1996


8:06 PM

Typical Response Message, Computer Format:
s00200YYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

10

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 003
Function Type: Remote Alarm Reset

Version 1

Command Format:
Display: S00300
Computer: s00300
Typical Response Message, Display Format:

S00300
MAR 27, 1996


8:04 PM

Typical Response Message, Computer Format:
s00300YYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

11

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 010
Function Type: Cancel Autodial Computer Mode Session

Version 14

Command Format:
Display: S01000
Computer: s01000
Typical Response Message, Display Format:

S01000
MAR 27, 1996


8:04 PM

Typical Response Message, Computer Format:
s00300YYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

12

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 031
Function Type: Confirm Clear Function

Version 10

Command Format:
Display: S03100832382
Computer: s03100832382
Typical Response Message, Display Format:

S03100
MAR 29, 1996

6:27 PM

CONFIRM CLEAR COMPLETE

Typical Response Message, Computer Format:
s03100YYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

13

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 051
Function Type: Clear In-Tank Delivery Reports

Version 1

Command Format:
Display: S051TT
Computer: s051TT
Typical Response Message, Display Format:

S051TT
MAR 29, 1996

6:27 PM

DELIVERY REPORTS ERASED

Typical Response Message, Computer Format:
s051TTYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

14

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 052
Function Type: Start In-Tank Leak Detect Test

Version 1

Command Format:
Display: S052TT
Computer: s052TT
Typical Response Message, Display Format:

S052TT
MAR 27, 1996
TANK
1

6:28 PM

PRODUCT LABEL
UNLEADED REGULAR

LEAK TEST START
TEST BY EXTERN INTERFACE


Typical Response Message, Computer Format:
s052TTYYMMDDHHmmTTk&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
k - Status Flag
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

15

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 053
Function Type: Stop In-Tank Leak Detect Test

Version 1

Command Format:
Display: S053TT
Computer: s053TT
Typical Response Message, Display Format:

S053TT
MAR 29, 1996
TANK
1


6:27 PM

PRODUCT LABEL
REGULAR UNLEADED

LEAK TEST STOP

Typical Response Message, Computer Format:
s053TTYYMMDDHHmmTTk&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
k - Status Flag
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

16

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 054
Function Type: Delete CSLD Rate Table

Version 5

Command Format:
Display: S054TT149
Computer: s054TT149
Notes:
1.
2.

TT - Tank Number (command valid for single tank only)
149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S054TT
MAR 29, 1996

6:27 PM

T 1:REGULAR UNLEADED


CSLD RECORDS DELETED

Typical Response Message, Computer Format:
s054TTYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
&&
CCCC

-

Current Date and Time
Tank Number
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

17

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 081
Version 7
Function Type: Start Pressure Line Leak Test (3.00 GPH only in V18)
Command Format:
Display: S081QQ149
Computer: s081QQ149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S081QQ
MAR 29, 1996

6:27 PM

Q 1:REGULAR UNLEADED
STATUS: TEST COMPLETE

Typical Response Message, Computer Format:
s081QQYYMMDDHHmmQQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.10 gal/hr
04=test aborted
05=running pump (manual test starting)
06=line lockout
07=disable alarm
08=test pending
09=testing delay
0A=pressure check
0B=testing at 0.20 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

18

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 082
Function Type: Stop Pressure Line Leak Test

Version 7

Command Format:
Display: S082QQ149
Computer: s082QQ149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S082QQ
MAR 29, 1996

6:27 PM

Q 1:REGULAR UNLEADED
STATUS: TEST COMPLETE

Typical Response Message, Computer Format:
s082QQYYMMDDHHmmQQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.10 gal/hr
04=test aborted
05=running pump (manual test starting)
06=line lockout
07=disable alarm
08=test pending
09=testing delay
10=pressure check
11=testing at 0.20 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

19

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 083
Version 10
Function Type: Start WPLLD Line Leak Test (3.00 GPH only in V18)
Command Format:
Display: S083WW149
Computer: s083WW149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S083WW
MAR 27, 1996

3:47 PM

W 1:UNLEADED REGULAR
STATUS: TEST PENDING

Typical Response Message, Computer Format:
s083WWYYMMDDHHmmWWtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
05=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

20

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 084
Function Type: Stop WPLLD Line Leak Test

Version 10

Command Format:
Display: S084WW149
Computer: s084WW149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S084WW
MAR 27, 1996

3:48 PM

W 1:UNLEADED REGULAR
STATUS: TEST ABORTED

Typical Response Message, Computer Format:
s084WWYYMMDDHHmmWWtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
05=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

21

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 087
Function Type: Start Pressure Line Leak Test by Type

Version 18

Command Format:
Display: S087QQ149rr
Computer: s087QQ149rr
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S087QQ
MAR 29, 1999

6:27 PM

Q 1:REGULAR UNLEADED
0.2 GPH SCHEDULED
STATUS: TEST COMPLETE

Typical Response Message, Computer Format:
s087QQYYMMDDHHmmQQrrtt&&CCCC
Notes:
1.
2.
3.

4.

5.
6.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
rr - Test Type
01=0.10 GPH
02=0.20 GPH
03=3.00 GPH
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.10 gal/hr
04=test aborted
05=running pump (manual test starting)
06=line lockout
07=disable alarm
08=test pending
09=testing delay
0A=pressure check
0B=testing at 0.20 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

22

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 088
Function Type: Start WPLLD Line Leak Test by Type

Version 18

Command Format:
Display: S088WW149rr
Computer: s088WW149rr
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S088WW
MAR 29, 1999

6:27 PM

W 1:REGULAR UNLEADED
0.2 GPH SCHEDULED
STATUS: TEST COMPLETE

Typical Response Message, Computer Format:
s088WWYYMMDDHHmmWWrrtt&&CCCC
Notes:
1.
2.
3.

4.

5.
6.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
rr - Test Type
01=0.10 GPH
02=0.20 GPH
03=3.00 GPH
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
05=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

23

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 089
Function Type: Pressure Line Leak Pressure Offset Reset

Version 19

Command Format:
Display: S089QQ149
Computer: s089QQ149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S089QQ
JAN 1, 2000

6:27 PM

Q 1:REGULAR UNLEADED
PRESSURE OFFSET RESET

Typical Response Message, Computer Format:
s089QQYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
QQ
&&
CCCC

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

24

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 090
Function Type: WPLLD Line Leak Pressure Offset Reset

Version 19

Command Format:
Display: S090WW149
Computer: s090WW149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S090WW
JAN 1, 2000

6:27 PM

W 1:REGULAR UNLEADED
PRESSURE OFFSET RESET

Typical Response Message, Computer Format:
s090WWYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
WW
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

25

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 091
Function Type: Close Current Shift

Version 15

Command Format:
Display: S09100
Computer: s09100
Typical Response Message, Display Format:

S09100
MAR 27, 1996

8:04 PM

CLOSE CURRENT SHIFT: YES

Typical Response Message, Computer Format:
s09100YYMMDDHHmmff&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
ff - Close Current Shift Flag
01=If close accepted
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

26

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 092
Function Type: Start Pressure Line Leak Profile Line Test

Version 23

Command Format:
Display: S092QQ149
Computer: s092QQ149
Notes:
1.

149 - This verification code must be sent to confirm the comand

Typical Response Message, Display Format:

I092QQ
NOV 14, 2001

10:15 PM

START PRESSURE LINE LEAK PROFILE LINE TEST
Q 1:UNLEADED REGULAR
STATUS: RUNNING PUMP

Typical Response Message, Computer Format:
s092QQYYMMDDHHmmQQtt
QQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
tt - Test Status
00 = TEST COMPLETE
(DONE: BULK MOD
10000)
01 = TURN PUMP ON
(RUNNING PUMP)
02 = PUMP ON WAIT
(RUNNING PUMP)
03 = PRESSURE 1 WAIT (PUMP OFF)
04 = PRESSURE 2 WAIT (MEASURING Pxx 19.123 PSI)
05 = CALC WAIT TIME (MEASURING Pxx 19.123 PSI)
06 = PRESSURE N WAIT (MEASURING Pxx 19.123 PSI)
07 = EVALUATE PERIOD (MEASURING Pxx 19.123 PSI)
08 = TEST ABORT
(ABORTED)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

27

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 093
Function Type: Stop Pressure Line Leak Profile Line Test

Version 23

Command Format:
Display: S093QQ149
Computer: s093QQ149
Notes:
1.

149 - This verification code must be sent to confirm the comand

Typical Response Message, Display Format:

I093QQ
NOV 14, 2001

10:15 PM

STOP PRESSURE LINE LEAK PROFILE LINE TEST
Q 1:UNLEADED REGULAR
STATUS: ABORTED

Typical Response Message, Computer Format:
s093QQYYMMDDHHmmQQtt
QQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
tt - Test Status
00 = TEST COMPLETE
(DONE: BULK MOD
10000)
01 = TURN PUMP ON
(RUNNING PUMP)
02 = PUMP ON WAIT
(RUNNING PUMP)
03 = PRESSURE 1 WAIT (PUMP OFF)
04 = PRESSURE 2 WAIT (MEASURING Pxx 19.123 PSI)
05 = CALC WAIT TIME (MEASURING Pxx 19.123 PSI)
06 = PRESSURE N WAIT (MEASURING Pxx 19.123 PSI)
07 = EVALUATE PERIOD (MEASURING Pxx 19.123 PSI)
08 = TEST ABORT
(ABORTED)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

28

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 094
Version 23
Function Type: Recalculate Pressure Line Leak Profile Bulk Modulus
Command Format:
Display: S094QQ149
Computer: s094QQ149
Notes:
1.

149 - This verification code must be sent to confirm the comand

Typical Response Message, Display Format:

I094QQ
NOV 14, 2001

10:15 PM

RECALCULATE PRESSURE LINE LEAK PROFILE LINE TEST BULK MODULUS
Q 1:UNLEADED REGULAR
STATUS: DONE: BULK MOD


10000

Typical Response Message, Computer Format:
s094QQYYMMDDHHmmQQtt
QQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
tt - Test Status
00 = TEST COMPLETE
(DONE: BULK MOD
10000)
01 = TURN PUMP ON
(RUNNING PUMP)
02 = PUMP ON WAIT
(RUNNING PUMP)
03 = PRESSURE 1 WAIT (PUMP OFF)
04 = PRESSURE 2 WAIT (MEASURING Pxx 19.123 PSI)
05 = CALC WAIT TIME (MEASURING Pxx 19.123 PSI)
06 = PRESSURE N WAIT (MEASURING Pxx 19.123 PSI)
07 = EVALUATE PERIOD (MEASURING Pxx 19.123 PSI)
08 = TEST ABORT
(ABORTED)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

29

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 095
Function Type: Start Vacuum Sensor Manual Test

Version 24

Command Format:
Display: S095SS149
Computer: s095SS149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S095SS
FEB 14, 2004

10:15 AM

START VACUUM SENSOR MANUAL TEST
s 1:VACUUM SENSOR #1
MANUAL TEST STARTED

Typical Response Message, Computer Format:
s095SSYYMMDDHHmmSStt...
SStt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
tt - Manual Test Status
00=ABORTED
01=STARTED
02=PENDING
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

30

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 096
Function Type: Stop Vacuum Sensor Manual Evacuation Test

Version 24

Command Format:
Display: S096SS149
Computer: s096SS149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S096SS
FEB 14, 2004

10:15 AM

STOP VACUUM SENSOR MANUAL EVACUATION TEST
s 1:VACUUM SENSOR #1
MANUAL TEST ABORTED

Typical Response Message, Computer Format:
s096SSYYMMDDHHmmSStt...
SStt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
tt - Manual Test Status
00=ABORTED
01=STARTED
02=PENDING
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

31

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 097
Function Type: Start Vacuum Sensor Evacuation Hold

Version 24

Command Format:
Display: S097SS149
Computer: s097SS149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S097SS
FEB 14, 2004

10:15 AM

START VACUUM SENSOR EVACUATION HOLD
s 1:VACUUM SENSOR #1
EVAC HOLD STARTED
EVACUATION STATE: EVAC_HOLD

Typical Response Message, Computer Format:
s097SSYYMMDDHHmmSSEE...
SSEE&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
EE - Evacuation State (Hex)
00=Vacuum Ok
01=Evacuation Pending
02=Evacuation Active
03=Evacuation Pending Manual
04=Evacuation Active Manual
05=No Vacuum
06=Evacuation Hold
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

32

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 098
Function Type: Stop Vacuum Sensor Evacuation Hold

Version 24

Command Format:
Display: S098SS149
Computer: s098SS149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S098SS
FEB 14, 2004

10:15 AM

STOP VACUUM SENSOR EVACUATION HOLD
s 1:VACUUM SENSOR #1
EVAC HOLD ABORTED
EVACUATION STATE: VACUUM OK

Typical Response Message, Computer Format:
s098SSYYMMDDHHmmSSEE...
SSEE&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
EE - Evacuation State (Hex)
00=Vacuum Ok
01=Evacuation Pending
02=Evacuation Active
03=Evacuation Pending Manual
04=Evacuation Active Manual
05=No Vacuum
06=Evacuation Hold
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

33

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 099
Function Type: Start Mag Sump Leak Test

Version 26

Command Format:
Display: S099ss149
Computer: s099ss149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S099ss
FEB 14, 2004

10:15 AM

START MAG SUMP LEAK TEST
s 1:SUMP 1
LEAK TEST STARTED

Typical Response Message, Computer Format:
s099ssYYMMDDHHmmsstt...
sstt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
ss - Smart Sensor Number (Decimal, 00=all)
tt - Mag Sump Leak Test Status
00=NO TEST DATA AVAILABLE
01=LEAK TEST ABORTED
02=FILL SUMP
03=MEASURING HEIGHT
04=LEAK TEST PASSED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

34

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 09A
Function Type: Start Mag Sump Leak Test Measuring Height Phase

Version 26

Command Format:
Display: S09Ass149
Computer: s09Ass149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S09Ass
FEB 14, 2004

10:15 AM

START MAG SUMP LEAK TEST MEASURING HEIGHT PHASE
s 1:SUMP 1
STABLILITY PHASE STARTED

Typical Response Message, Computer Format:
s09AssYYMMDDHHmmsstt...
sstt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
ss - Smart Sensor Number (Decimal, 00=all)
tt - Mag Sump Leak Test Status
00=NO TEST DATA AVAILABLE
01=LEAK TEST ABORTED
02=FILL SUMP
03=MEASURING HEIGHT
04=LEAK TEST PASSED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

35

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 09B
Function Type: Stop Mag Sump Leak Test

Version 26

Command Format:
Display: S09Bss149
Computer: s09Bss149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S09Bss
FEB 14, 2004

10:15 AM

STOP MAG SUMP LEAK TEST
s 1:SUMP 1
LEAK TEST ABORTED

Typical Response Message, Computer Format:
s09BssYYMMDDHHmmsstt...
sstt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
ss - Smart Sensor Number (Decimal, 00=all)
tt - Mag Sump Leak Test Status
00=NO TEST DATA AVAILABLE
01=LEAK TEST ABORTED
02=FILL SUMP
03=MEASURING HEIGHT
04=LEAK TEST PASSED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

36

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2 OPERATIONAL REPORTS
7.2.1 SYSTEM REPORTS
Function Code: 101
Function Type: System Status Report

Version 1

Command Format:
Display: I10100
Computer: i10100
Notes:
1.

This command will report all active OR unacknowledged alarms
and warnings up to the limit of 25 alarms in display format,
and 150 alarms in computer format

Typical Response Message, Display Format:

I10100
JUL 29, 1997
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

9:02 AM
1....
2....
3....
4....

SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL


Part No. 576013-635, Revision AA

37

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
Typical Response Message, Computer Format:
i10100YYMMDDHHmmAANNTT...
AANNTT&&CCCC
Notes:
1.
2.

YYMMDDHHmm - Current Date and Time
AA - Alarm/Warning Category:
00=All Functions Normal
01=System Alarm
02=Tank Alarm
03=Liquid Sensor Alarm
04=Vapor Sensor Alarm
05=Input Alarm
06=Volumetric Line Leak Alarm
07=Groundwater Sensor Alarm
08=Type A Sensor Alarm
12=Type B Sensor Alarm
13=Universal Sensor Alarm
14=Auto-Dial Fax Alarm
18=Mechanical Dispenser Interface Alarm
19=Electronic Dispenser Interface Alarm
20=Product Alarm
21=Pressure Line Leak Alarm
26=Wireless PLLD Alarm
28=Smart Sensor Alarm
29=Modbus Alarm
30=ISD Site Alarm
31=ISD Hose Alarm
32=ISD Vapor Flow Meter Alarm
33=PMC Alarm
34=Pump Relay Monitor Alarm
35=VMCI Dispenser Interface Alarm
36=VMC Alarm
37=APM Alarm

(Version 28)
(Version 28)
(Version 31)

99=Externally Detected Alarm (not reported by Console)

Part No. 576013-635, Revision AA

38

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
3.

NN - Alarm Type Number:
- If AA is 01 and NN is:
01=Printer out of Paper
02=Printer Error
03=EEPROM Configuration Error
04=Battery Off
05=Too Many Tanks
06=System Security Warning
07=ROM Revision Warning
08=Remote Display Communications Error
09=Autodial Error
10=Software Module Warning
11=Tank Test Shutdown Warning
12=Protective Cover Alarm
13=BIR Shift Close Pending
14=BIR Daily Close Pending
15=PC(H8) Revision Warning
16=System Self Test Error
17=System Clock Incorrect Warning
18=System Device Poll Timeout
19=Maintenance Tracker NVMem Removed
20=Maintenance Tracker Communication Module Removed

Part No. 576013-635, Revision AA

39

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
- If AA is 02 and NN is:
01=Tank Setup Data Warning
02=Tank Leak Alarm
03=Tank High Water Alarm
04=Tank Overfill Alarm
05=Tank Low Product Alarm
06=Tank Sudden Loss Alarm
07=Tank High Product Alarm
08=Tank Invalid Fuel Level Alarm
09=Tank Probe Out Alarm
10=Tank High Water Warning
11=Tank Delivery Needed Warning
12=Tank Maximum Product Alarm
13=Tank Gross Leak Test Fail Alarm
14=Tank Periodic Leak Test Fail Alarm
15=Tank Annual Leak Test Fail Alarm
16=Tank Periodic Test Needed Warning
17=Tank Annual Test Needed Warning
18=Tank Periodic Test Needed Alarm
19=Tank Annual Test Needed Alarm
20=Tank Leak Test Active
21=Tank No CSLD Idle Time Warning
22=Tank Siphon Break Active Warning
23=Tank CSLD Rate Increase Warning
24=Tank AccuChart Calibration Warning
25=Tank HRM Reconciliation Warning
26=Tank HRM Reconciliation Alarm
27=Tank Cold Temperature Warning
28=Tank Missing Delivery Ticket Warning
29=Tank/Line Gross Leak Alarm
30=Delivery Density Warning
31=Density Warning
32=Fuel Quality Alarm

Part No. 576013-635, Revision AA

40

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
- If AA is 03,
02=Sensor
03=Sensor
04=Sensor
05=Sensor
06=Sensor
07=Sensor
08=Sensor
09=Sensor
10=Sensor
- If AA is 05
01=Input
02=Input
03=Input

04, 07, 08, 12, or 13 and NN is:
Setup Data Warning
Fuel Alarm
Out Alarm
Short Alarm
Water Alarm
Water Out Alarm
High Liquid Alarm
Low Liquid Alarm
Liquid Warning

and NN is:
Setup Data Warning
Normal
Alarm

- If AA is 06 and NN is:
01=VLLD Setup Data Warning
02=VLLD Self Test Alarm
03=VLLD Shutdown Alarm
04=VLLD Leak Test Fail Alarm
05=VLLD Selftest Invalid Warning
06=VLLD Continuous Handle On Warning
07=VLLD Gross Line Test Fail Alarm
08=VLLD Gross Line Selftest Fail Alarm
09=VLLD Gross Pump Test Fail Alarm
10=VLLD Gross Pump Selftest Fail Alarm
11=VLLD Periodic Test Needed Warning
12=VLLD Annual Test Needed Warning
13=VLLD Periodic Test Needed Alarm
14=VLLD Annual Test Needed Alarm
15=VLLD Periodic Line Test Fail Alarm
16=VLLD Periodic Line Selftest Fail Alarm
17=VLLD Periodic Pump Test Fail Alarm
18=VLLD Periodic Pump Selftest Fail Alarm
19=VLLD Annual Line Test Fail Alarm
20=VLLD Annual Line Selftest Fail Alarm
21=VLLD Annual Pump Test Fail Alarm
22=VLLD Annual Pump Selftest Fail Alarm
23=VLLD Pressure Warning
24=VLLD Pressure Alarm
25=VLLD Gross Test Fault Alarm
26=VLLD Periodic Test Fault Alarm
27=VLLD Annual Test Fault Alarm
28=VLLD Fuel Out Alarm
- If AA is 14 and NN is:
01=Autodial Setup Data Warning
02=Autodial Failed Alarm
03=Autodial Service Report Warning
04=Autodial Alarm Clear Warning
05=Autodial Delivery Report Warning

(Added in V19)
(Added in V19)
(Added in V19)

- If AA is 18, 19 and NN is:
02=DIM Disabled Alarm
03=DIM Communication Failure Alarm
04=DIM Transaction Alarm

Part No. 576013-635, Revision AA

41

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
- If AA is 20 and NN is:
01=BIR Setup Data Warning
02=BIR Threshold Alarm
03=BIR Close Shift Warning
04=BIR Close Daily Warning
- If AA is 21 and NN is:
01=PLLD Setup Data Warning
02=PLLD Gross Test Fail Alarm
03=PLLD Annual Test Fail Alarm
04=PLLD Periodic Test Needed Warning
05=PLLD Periodic Test Needed Alarm
06=PLLD Sensor Open Alarm
07=PLLD High Pressure Alarm
08=PLLD Shutdown Alarm
09=PLLD High Pressure Warning
10=PLLD Continuous Handle On Warning
11=PLLD Periodic Test Fail Alarm
12=PLLD Annual Test Needed Warning
13=PLLD Annual Test Needed Alarm
14=PLLD Low Pressure Alarm
15=PLLD Sensor Short Alarm
16=PLLD Continuous Handle On Alarm
17=PLLD Fuel Out Alarm
18=PLLD Line Equipment Alarm
- If AA is 26
01=WPLLD
02=WPLLD
03=WPLLD
04=WPLLD
05=WPLLD
06=WPLLD
07=WPLLD
08=WPLLD
09=WPLLD
10=WPLLD
11=WPLLD
12=WPLLD
13=WPLLD
14=WPLLD
15=WPLLD
16=WPLLD
17=WPLLD
18=WPLLD

Part No. 576013-635, Revision AA

and NN is:
Setup Data Warning
Gross Test Fail Alarm
Periodic Test Fail Alarm
Periodic Test Needed Warning
Periodic Test Needed Alarm
Sensor Open Alarm
Communications Alarm
Shutdown Alarm
Continuous Handle On Warning
Annual Test Fail Alarm
Annual Test Needed Warning
Annual Test Needed Alarm
High Pressure Warning
High Pressure Alarm
Sensor Short Alarm
Continuous Handle On Alarm
Fuel Out Alarm
Line Equipment Alarm

(Obsolete V19)
(Obsolete V19)
(Obsolete V19)

(Obsolete V19)

(Obsolete V19)

(Obsolete V19)
(Obsolete V19)
(Obsolete V19)

42

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
- If AA is 28
01=Smart
02=Smart
03=Smart
04=Smart
05=Smart
06=Smart
07=Smart
08=Smart
09=Smart
10=Smart
11=Smart
12=Smart
13=Smart
14=Smart
15=Smart
16=Smart
17=Smart

and NN
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor

is:
Setup Data Warning
Communication Alarm
Fault Alarm
Fuel Warning
Fuel Alarm
Water Warning
Water Alarm
High Liquid Warning
High Liquid Alarm
Low Liquid Warning
Low Liquid Alarm
Temperature Warning
Relay Active
Install Alarm
Sensor Fault Warning
Vacuum Warning
No Vacuum Warning

- If AA is 29 and NN is:
01=Improper Setup alarm
02=Communication Loss alarm
- If AA is 30 and NN is:
01=Stage 1 Transfer Monitoring Failure warning
(ISD only)
02=Containment Monitoring Gross Failure warning
(ISD)
03=Containment Monitoring Gross Failure alarm
(ISD)
04=Containment Monitoring Degradation Failure warning
(ISD only)
05=Containment Monitoring Degradation Failure alarm
(ISD only)
06=Containment Monitoring CVLD Failure warning
(ISD)
07=Containment Monitoring CVLD Failure alarm
(ISD)
08=Vapor Processor Over Pressure Failure warning
(ISD only)
09=Vapor Processor Over Pressure Failure alarm
(ISD only)
10=Vapor Processor Status Test warning
(ISD only)
11=Vapor Processor Status Test alarm
(ISD only)
12=Missing Relay Setup alarm
(ISD only)
13=Missing Hose Setup alarm
(ISD only)
14=Missing Tank Setup alarm
(ISD)
15=Missing Vapor Flow Meter alarm
(ISD only)
16=Missing Vapor Pressure Sensor alarm
(ISD)
17=Missing Vapor Pressure Input alarm
(ISD)
18=Setup Fail warning
(ISD)
19=Setup Fail alarm
(ISD)
20=Sensor Out warning
(ISD)
21=Sensor Out alarm
(ISD)
22=PC-ISD Offline
(ISD)

Part No. 576013-635, Revision AA

43

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 101 Notes: (Continued)
- If AA is 31 and NN is:
01=Collection Monitoring Gross Failure warning
02=Collection Monitoring Gross Failure alarm
03=Collection Monitoring Degradation Failure warning
04=Collection Monitoring Degradation Failure alarm
05=Flow Performance Hose Blockage Failure warning
06=Flow Performance Hose Blockage Failure alarm
07=Vapor Flow Meter Setup alarm
- If AA is 32 and NN is:
01=Locked rotor alarm
- If AA is 33 and NN is:
01=Vapor Processor Run Time Fault warning
02=Processor Monitoring Effluent Emissions Failure
warning
03=Processor Monitoring Effluent Emissions Failure alarm
04=Processor Monitoring Over Pressure Failure warning
05=Processor Monitoring Over Pressure Failure alarm
06=Processor Monitoring Duty Cycle Failure warning
07=Processor Monitoring Duty Cycle Failure alarm
08=PMC (stand alone mode only) Setup warning
- If AA is 34 and NN is:
01=Setup Data Warning
02=Pump Relay Alarm
- If AA is 35 and NN is:
01=Setup Data Warning
02=Disabled VMCI Alarm
03=VMC Comm Timeout Alarm
- If AA is 36 and NN is:
01=VMC Comm timeout
02=Meter Not Connected
03=FP Shutdown Warning
04=FP Shutdown Alarm

(Added in V31)
(Obsolete V31)

- If AA is 37 and NN is:
01=Gross Over-Pressure Test Warning
02=APM Gross Over-Pressure Test Failure warning
03=APM Gross Over-Pressure Test Failure alarm
04=APM Degradation Over-Pressure Test Failure warning
05=APM Degradation Over-Pressure Test Failure alarm
06=APM Sensor Test Failure warning
07=APM Sensor Test Failure alarm
08=APM Setup Failure warning
09=APM Sensor Out Failure warning
10=APM Sensor Out Failure alarm
- If AA is 99 and NN is:
01=Externally Dectected Communication Alarm
02=Communications - Data Reception Timeout
03=Communications - Failed Checksum
04=Communications - Parity Error
05=Modem - Line Busy
06=Modem - No Answer
07=Modem - No Carrier
08=Modem - No Dial Tone
09=Modem - Modem Error
10=Modem - Modem Not Responding
11=Modem - Port Not Available
12=Polling - Could Not Update Queue
13=Polling - Invalid Data Type Requested
4.
5.
6.

TT - Tank/Sensor Number
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

44

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 102
Function Type: System Configuration Report

Version 1

Command Format:
Display: I10200
Computer: i10200
Typical Response Message, Display Format:

I10200
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:05 PM
1....
2....
3....
4....

SYSTEM CONFIGURATION
SLOT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

BOARD TYPE
4 PROBE / G.T.
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
4 INPUT BOARD
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
UNUSED
COMM 1 FAXMODEM BOARD
COMM 2 RS232 SERIAL BD
COMM 3 ELEC DISP INT.
COMM 4 UNUSED
COMM 5 UNUSED
COMM 6 UNUSED

POWER ON RESET
164040
10191362
10122894
10107912
10115504
10105807
10097749
10102487
40158
15000000
15000000
15000000
15000000
15000000
15000000
15000000
47008
14764
100725
15000000
15000000
15000000

CURRENT
166912
10329900
10209602
10186864
10165331
10165451
10164467
10152837
40158
15000000
15000000
15000000
15000000
15000000
15000000
15000000
47006
14753
100748
15000000
15000000
15000000



Part No. 576013-635, Revision AA

45

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 102 Notes: (Continued)
Typical Response Message, Computer Format:
i10200YYMMDDHHmmNNSSTTFFFFFFFFCCCCCCCC...
SSTTFFFFFFFFCCCCCCCC&&CCCC
Notes:
1.
2.
3.
4.

5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
NN - Number of Modules to Follow (Hex)
SS - Slot Number (Hex)
TT - Type of Module (Hex):
00=Not used
01=Four Probe Module
02=Vapor Sensor Module
03=Liquid Sensor Module
04=Four Relay Module
05=I/O Combo Module
06=Printer Module
07=RS-232 Module
08=Modem Module
09=Volumetric Line Leak Module
0A=Four Probe w/ Ground Temp Module
0B=Groundwater Sensor Module
0C=Type A Sensor Module
0D=Remote Display Module
10=Type B Sensor Module
11=Universal Sensor Module
12=Fax/Modem (1785) Module
13=Remote/Local Printer Module
14=Pump Sensor Module
15=European RS-232 Module
17=Eight Probe Module
18=Mechanical Dispenser Interface Module
19=Electronic Dispenser Interface Module
1A=Pressure Line Leak Sensor Module
1B=Pressure Line Leak Controller Module
1D=Remote Printer Module
1E=External Fax/Modem Module
1F=RS-485 Module
20=Wireless PLLD AC Interface Module
21=Wireless PLLD Communications Module
22=Wireless PLLD Controller Module
23=Hughes Satellite J-Box Module
24=Fax/Modem (1786) Module
25=Serial Satellite Module
26=Four Probe / Four Liquid Sensor Module
27=Four PLLD Sensor Module
28=SmartSensor(8) Module
29=RS-485 Modbus Module
2B=SmartSensor(7) Module
2C=Four Input Module
2D=MT Comm Module
2E=Pump Relay Monitor Module
2F=VMCI Dispenser Interface Module
FFFFFFFF
CCCCCCCC
&&
CCCC

-

(Version
(Version
(Version
(Version

26)
27)
27)
28)

Power On Reset (ASCII Hex IEEE float)
Current I/O Reading (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

46

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 111
Function Type: Priority Alarm History Report

Version 2

Command Format:
Display: I11100
Computer: i11100
Typical Response Message, Display Format:

I11100
JUL 29, 1997
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

9:02 AM
1....
2....
3....
4....

PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION
W 3 OTHER
SPECIAL
W 3 OTHER
SPECIAL
SYSTEM
SYSTEM


ALARM TYPE
WPLLD SHUTDOWN ALM
WPLLD SHUTDOWN ALM
BATTERY IS OFF
BATTERY IS OFF

STATE
CLEAR
ALARM
CLEAR
ALARM

DATE
1-01-96
1-01-96
1-01-96
1-01-96

TIME
8:07AM
8:06AM
8:00AM
8:00AM

Typical Response Message, Computer Format:
i11100YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.

YYMMDDHHmm - Current Date and Time
AA - Alarm/Warning Category:
See explanation for "AA" in Function i10100
cc - Sensor Category
00=Other
01=Annular
02=Dispenser Pan
03=Monitoring Well
04=STP Sump
05=Piping Sump
NN - Alarm Type Number:
See explanation for "NN" in Function i10100
TT - Tank/Sensor Number
SS - Alarm State
01=Alarm cleared
02=Alarm occurred
YYMMDDHHmm - Date/Time Alarm state occurred
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

47

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 112
Function Type: Non-Priority Alarm History Report

Version 2

Command Format:
Display: I11200
Computer: i11200
Typical Response Message, Display Format:

I11200
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:05 PM
1....
2....
3....
4....

NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION
SYSTEM
SYSTEM
T 2 TANK
SPECIAL
T 2 TANK
SPECIAL


ALARM TYPE
PAPER OUT
PAPER OUT
INVALID FUEL LEVEL
INVALID FUEL LEVEL

STATE
CLEAR
ALARM
CLEAR
ALARM

DATE
12-20-95
12-20-95
12-20-95
12-20-95

TIME
12:01PM
12:00PM
11:59AM
11:59AM

Typical Response Message, Computer Format:
i11200YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.

YYMMDDHHmm - Current Date and Time
AA - Alarm/Warning Category:
See explanation for "AA" in Function i10100
cc - Sensor Category
00=Other
01=Annular
02=Dispenser Pan
03=Monitoring Well
04=STP Sump
05=Piping Sump
NN - Alarm Type Number:
See explanation for "NN" in Function i10100
TT - Tank/Sensor Number
SS - Alarm State
01=Alarm cleared
02=Alarm occurred
YYMMDDHHmm - Date/Time Alarm state occurred
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

48

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 113
Function Type: Active Alarm Report

Version 14

Command Format:
Display: I11300
Computer: i11300
Notes:
1.

This command will report ALL active alarms and warnings
regardless of their acknowledgement state. If there are
more than can be contained in the non-priority and priority
history storage areas, they will be reported here without
time and date stamps

Typical Response Message, Display Format:

I11300
JAN 28, 1996 10:09 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ACTIVE ALARMS REPORT
ID

CATEGORY
SYSTEM
T 2 TANK


DESCRIPTION
SPECIAL

ALARM TYPE
PAPER OUT
INVALID FUEL LEVEL

DATE
TIME
12-20-95 12:00PM
12-20-95 11:59AM

Typical Response Message, Computer Format:
i11300YYMMDDHHmma..ab..bc..cd..dAAccNNTTYYMMDDHHmm...
AAccNNTTYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
a..a
b..b
c..c
d..d
AA

-

7.

cc -

8.

NN -

9.
10.
11.
12.

TT
YYMMDDHHmm
&&
CCCC

-

Current Date and Time
Station Header 1: 20 ASCII characters
Station Header 2: 20 ASCII characters
Station Header 3: 20 ASCII characters
Station Header 4: 20 ASCII characters
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Sensor Category
00=Other
01=Annular
02=Dispenser Pan
03=Monitoring Well
04=STP Sump
05=Piping Sump
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number
Alarm Date and Time
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

49

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 114
Function Type: Cleared Alarm Report

Version 19

Command Format:
Display: I11400
Computer: i11400
Typical Response Message, Display Format:

I11400
JAN 28, 1996 10:09 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CLEARED ALARMS REPORT
ID CATEGORY
T 4 TANK
T 1 TANK
SYSTEM


DESCRIPTION
PRODUCT 4
PRODUCT 1

ALARM TYPE
PROBE OUT
INVALID FUEL LEVEL
PAPER OUT

STATE
CLEAR
CLEAR
CLEAR

DATE
TIME
1-02-96 4:10AM
1-02-96 1:12AM
1-02-96 1:09AM

Typical Response Message, Computer Format:
i11400YYMMDDHHmma..ab..bc..cd..dAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
a..a
b..b
c..c
d..d
AA

-

7.

cc -

8.

NN -

9.
10.

TT SS -

11.
12.
13.

YYMMDDHHmm && CCCC -

Current Date and Time
Station Header 1: 20 ASCII characters
Station Header 2: 20 ASCII characters
Station Header 3: 20 ASCII characters
Station Header 4: 20 ASCII characters
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Sensor Category
00=Other
01=Annular
02=Dispenser Pan
03=Monitoring Well
04=STP Sump
05=Piping Sump
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number
Alarm State
01=Alarm cleared
02=Alarm occurred
Clear Alarm Date and Time
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

50

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 115
Function Type: Maintenance Tracker Unacknowledged Alarm Report

Version 27

Command Format:
Display: I11500
Computer: i11500
Typical Response Message, Display Format:

I11500
JUL 29, 2006
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:05 PM
1....
2....
3....
4....

MAINTENANCE TRACKER UNACKNOWLEDGED ALARM REPORT
ID CATEGORY
L12 OTHER
L 1 OTHER


DESCRIPTION
LIQUID SENS 12
LIQUID SENS 1

ALARM TYPE
SENSOR OUT
SENSOR OUT

DATE
7-08-06
7-08-06

TIME
11:12AM
10:10AM

Typical Response Message, Computer Format:
i11500YYMMDDHHmma..ab..bc..cd..dAAccNNTTYYMMDDHHmm...
AaccNNTTYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
a..a
b..b
c..c
d..d
AA

-

7.

cc -

8.

NN -

9.
10.
11.
12.

TT
YYMMDDHHmm
&&
CCCC

-

Current Date and Time
Station Header 1: 20 ASCII characters
Station Header 2: 20 ASCII characters
Station Header 3: 20 ASCII characters
Station Header 4: 20 ASCII characters
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Sensor Category
00=Other
01=Annular
02=Dispenser Pan
03=Monitoring Well
04=STP Sump
05=Piping Sump
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number
Maintenance Tracker Alarm Active Date and Time
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

51

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 116
Function Type: Service Report History

Version 19 (Obsolete V27)

Command Format:
Display: I11600
Computer: i11600
Typical Response Message, Display Format:

I11600
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1:47 PM
1....
2....
3....
4....

SERVICE REPORT
DATE/TIME
MAR 29, 1996
MAR 28, 1996
FEB 26, 1996
JAN 25, 1996
JAN 23, 1996


8:50
8:50
8:15
2:20
1:48

AM
AM
AM
PM
PM

ID
1234567890
3482221100
3482221100
3482221100
3482221100

CODE
12345
EABC2
12345
Z1234
12345

Typical Response Message, Computer Format:
i11600YYMMDDHHmma..ab..bc..cd..dNNYYMMDDHHmmiiiiiiiiiiccccc...
YYMMDDHHmmiiiiiiiiiiccccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

YYMMDDHHmm
a..a
b..b
c..c
d..d
NN
YYMMDDHHmm
iiiiiiiiii
ccccc
&&
CCCC

-

Current Date and Time
Station Header 1: 20 ASCII characters
Station Header 2: 20 ASCII characters
Station Header 3: 20 ASCII characters
Station Header 4: 20 ASCII characters
Number of Records to follow (Decimal)
Date and Time of entry
Service ID entered by Service Contractor (10 alpha/numeric)
Service Code entered by Service Contractor (5 alpha/numeric)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

52

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 119
Function Type: Maintenance History Report

Version 27

Command Format:
Display: I11900YYMMDDYYMMDD OR I11900
Computer: i11900YYMMDDYYMMDD OR i11900
Notes:
1.
2.
3.

YYMMDD - Requested Start Date (year, month, day).
YYMMDD - Requested End Date (year, month, day).
- If the dates are not specified, the most recent 20 records
are returned.

Typical Response Message, Display Format:

I11900
MAR 26, 2006
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1:47 PM
1....
2....
3....
4....

MAINTENANCE HISTORY
TYPE
LOGOUT
SERVICE CODE
SERVICE CODE
ALARM ACKNOWLEDGED
ALARM ACKNOWLEDGED
LOGIN
ALARM CLEAR
ALARM CLEAR
ALARM ACTIVE
ALARM ACTIVE
MTC ERR
ALARM CLEAR
ALARM ACTIVE
HISTORY DISABLED
VLLD TEST
WPLLD TEST
PLLD TEST
TANK TEST
HISTORY ENABLED


DATE/TIME
JAN 09, 2006 11:50 AM
JAN 09, 2006 10:27 AM
JAN 09, 2006 9:55 AM
JAN 09, 2006 8:52 AM
JAN 09, 2006 8:52 AM
JAN 09, 2006 8:50 AM
JAN 08, 2006 7:31 AM
JAN 08, 2006 7:30 AM
JAN 08, 2006 6:52 AM
JAN 08, 2006 6:50 AM
JAN 05, 2006 8:30 PM
JAN 03, 2006 8:30 AM
JAN 03, 2006 6:25 AM
JAN 02, 2006 7:25 PM
JAN 02, 2006 6:25 PM
JAN 02, 2006 3:45 PM
JAN 02, 2006 1:45 PM
JAN 02, 2006 10:28 AM
JAN 01, 2006 6:25 AM

Part No. 576013-635, Revision AA

DESCRIPTION
J SMITH
A12345
COLD BOOT SYSTEM
1203
INSTALLED PAPER
1211
L12:SENSOR OUT ALARM
L 1:SENSOR OUT ALARM
J SMITH
A12345
L12:SENSOR OUT ALARM
L 1:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SENSOR OUT ALARM
L 1:SENSOR OUT ALARM
L 1:SENSOR OUT ALARM
P
W
Q
T

1
1
1
1

0.2 GPH TEST PASS
0.2 GPH TEST PASS
0.2 GPH TEST PASS
PERIODIC TEST PASS

53

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 119 Notes: (Continued)
Typical Response Message, Computer Format:
i11900YYMMDDHHmmNNNNNYYMMDDHHmmttXXXXXXYYMMDDHHmmttXXXXXX...
YYMMDDHHmmttXXXXXX&&CCCC
Notes:
1.
2.
3.
4.

5.

6.
7.

YYMMDDHHmm
NNNNN
YYMMDDHHmm
tt

-

Current Date and Time
Number of records to Follow (Decimal)
Date/time of record
Record type (Hex)
01=Maintenance History Enabled
02=Maintenance History Disabled
03=Maintenance Tracker Login
04=Maintenance Tracker Logout
05=Maintenance Tracker Remote Login
06=Maintenance Tracker Remote Logout
07=Maintenance Alarm Active
08=Maintenance Alarm Inactive
09=Maintenance Alarm Acknowledge
0A=Maintenance Alarm Remote Acknowledge
0B=Service Code
0C=Tank Test, 0.20 Gal/Hr Fullest Monthly
0D=PLLD Test, 0.20 Gal/Hr Latest Monthly
0E=WPLLD Test, 0.20 Gal/Hr Latest Monthly
0F=MT Comm Card Removed
10=VLLD Test, 0.20 Gal/Hr Latest Monthly
XXXXXX - Six digit data field:
000000= place filler (unused) for types 01, 02
iiiiii= login ID code for types 03, 04, 05, 06 (ASCII,
padded with leading zeros)
ddttnn= Alarm device #, type, and alarm number for types
07, 08, 09, 0A (Decimal)
00cccc= Four digit service code for type 0B (Decimal,
padded with leading zeros)
0000tt= Device # for types 0C, 0D, 0E (Decimal, padded
with leading zeros)
000000= Place filler (unused) for type 0F
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

54

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 11A
Function Type: Service Report History

Version 27

Command Format:
Display: I11A00
Computer: i11A00
Typical Response Message, Display Format:

I11A00
MAR 26, 2006
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1:47 PM
1....
2....
3....
4....

SERVICE REPORT
DATE/TIME
MAR 29, 2006
MAR 28, 2006
FEB 26, 2006
JAN 25, 2006
JAN 23, 2006


8:50
8:50
8:15
2:20
1:48

AM
AM
AM
PM
PM

LABEL
J DOE
D SMITH
D SMITH
D SMITH
D SMITH

ID
A12345
A34822
A34822
A34822
A34822

LABEL
INSTALLED PAPER
CLEARED PAPER JAM
RECONNECT PHONE LN
REPLACED PROBE
FIX STUCK FLOAT

CODE
1211
0204
0503
0304
0305

Typical Response Message, Computer Format:
i11A00YYMMDDHHmmNNYYMMDDHHmmiiiiiicccc...
YYMMDDHHmmiiiiiicccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
NN
YYMMDDHHmm
iiiiii
cccc
&&
CCCC

-

Current Date and Time
Number of Records to follow (Decimal)
Date and Time of entry
Service ID entered by Service Contractor (6 alpha/numeric)
Service Code entered by Service Contractor (4 numeric)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

55

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 11B
Function Type: Service Notice Session Report

Version 28

Command Format:
Display: I11B00
Computer: i11B00
Typical Response Message, Display Format:

I11B00
APR 10, 2007
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:05 PM
1....
2....
3....
4....

SERVICE NOTICE SESSION REPORT
START TIME
APR 10, 2007
APR 9, 2007
APR 8, 2007


8:00 AM
8:10 AM
8:05 AM

END TIME
IN PROGRESS
APR 9, 2007
APR 8, 2007

9:10 AM
8:45 AM

Typical Response Message, Computer Format:
i11B00YYMMDDHHmmfYYMMDDHHmmNNYYMMDDHHmmYYMMDDHHmm...
YYMMDDHHmmYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
f - Service Notice Session Enable
0 = Disabled
1 = Enabled
YYMMDDHHmm - Start Date and Time
- if Service Notice Session Enable = 0 (Disabled) then
Start Date/Time is invalid
- if Service Notice Session Enable = 1 (Enabled) then Start
Date/Time is valid
NN - Number of Service Notice Session Start/End records to follow
(Hex)
YYMMDDHHmm - Start Date and Time
YYMMDDHHmm - End Date and Time
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

56

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 132
Function Type: Fiscal Height Security Report

Version 32

Command Format:
Display: I13200
Computer: i13200
Typical Response Message, Display Format:

I13200
APR 1, 2011

8:03 AM

FISCALLY SEALED

: NO

FISCAL HEIGHT SECURITY
: DISABLED
FISCAL HEIGHT SECURITY SWITCH : OFF

Typical Response Message, Computer Format:
i13200YYMMDDHHmmsfp&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
s - Is Fiscally Sealed
0=No
1=Yes
f - Fiscal Height Security Enable/Disable Flag
0=Disabled
1=Enabled
p - Fiscal Height Security Switch Position
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

57

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2.2 IN-TANK REPORTS
Function Code: 201
Function Type: In-Tank Inventory Report

Version 1

Command Format:
Display: I201TT
Computer: i201TT
Typical Response Message, Display Format:

I201TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

TANK PRODUCT
1 REGULAR UNLEADED


VOLUME TC VOLUME
5329
5413

ULLAGE
4699

HEIGHT
48.97

WATER
0.00

TEMP
37.39

Typical Response Message, Computer Format:
i201TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
ssss

-

5.
6.

NN FFFFFFFF -

7.
8.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress
Bit 2 - Leak Test in Progress
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

58

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 202
Function Type: In-Tank Delivery Report

Version 1

Command Format:
Display: I202TT
Computer: i202TT
Typical Response Message, Display Format:

I202TT
JUL 29, 1997
STATION
STATION
STATION
STATION

9:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

DELIVERY REPORT
T 1:REGULAR UNLEADED
INCREASE
DATE / TIME

GALLONS TC GALLONS WATER

TEMP DEG F

HEIGHT

END: JUL 28, 1997
START: JUL 28, 1997
AMOUNT:

3:14 PM
3:05 PM

3231
1244
1987

3194
1231
1963

0.00
0.00

76.14
73.89

48.27
24.40

END: JUL 25, 1997
START: JUL 25, 1997
AMOUNT:


2:48 PM
2:37 PM

4460
1157
3303

4414
1146
3268

0.00
0.00

74.56
72.85

63.06
23.22

Typical Response Message, Computer Format:
i202TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
dd

-

5.
6.
7.
8.

YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Starting Volume
2. Starting TC Volume
3. Starting Water
4. Starting Temp
5. Ending Volume
6. Ending TC Volume
7. Ending Water
8. Ending Temp
9. Starting Height
10. Ending Height
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

59

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 203
Function Type: In-Tank Leak Detect Report

Version 1

Command Format:
Display: I203TT
Computer: i203TT
Typical Response Message, Display Format:

I203TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

TANK 1
REGULAR UNLEADED
TEST STATUS: OFF
0.2 GAL/HR TEST PASS
TEST START TIME: OCT 22, 1991 10:30 PM
DURATION:
START TEMP: 58.7 DEG F
START VOLUME:
2123 GALLONS
ENDING TEMP: 58.1 DEG F
LEAK RATE: -0.01 GALLONS/HR
CUMULATIVE PERIODIC VOLUME CHANGE (GALLONS):
-0.01
-0.02
-0.01
-0.03
-0.05
-0.04


7 HOURS

Typical Response Message, Computer Format:
i203TTYYMMDDHHmmTTpYYMMDDHHmmHHNNFFFFFFFF...
TTpYYMMDDHHmmHHNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm
TT
p
YYMMDDHHmm
HH
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Starting Date/Time
Test Duration (hours)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Starting Temp
2. Ending Temp
3. Starting Volume
4. Ending Rate
5. Hourly changes up to the number of fields
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

60

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 204
Function Type: In-Tank Shift Inventory Report

Version 1

Command Format:
Display: I204TT
Computer: i204TT
Typical Response Message, Display Format:

I204TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

TANK PRODUCT
1 REGULAR UNLEADED
SHIFT 1 STARTING VALUES
ENDING VALUES
DELIVERY VALUE
TOTALS
SHIFT 2 STARTING VALUES
ENDING VALUES
DELIVERY VALUE
TOTALS


VOLUME TC VOLUME
8518
8492
8518
8492
0
0
8518
8492
8518
8492
0
0

ULLAGE
1482
1482

HEIGHT
76.26
76.26

WATER
0.00
0.00

TEMP
64.57
64.57

1482
1482

76.26
76.26

0.00
0.00

64.57
64.57

Typical Response Message, Computer Format:
i204TTYYMMDDHHmmTTpssNNFFFFFFFF...
TTpssNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

7.
8.

YYMMDDHHmm
TT
p
ss
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Shift Number 01, 02, 03
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Start Volume
2. Start Ullage
3. Start TC Volume
4. Start Height
5. Start Water
6. Start Temperature
7. End Volume
8. End Ullage
9. End TC Volume
A. End Height
B. End Water
C. End Temperature
D. Total Value
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

61

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 205
Function Type: In-Tank Status Report

Version 1

Command Format:
Display: I205TT
Computer: i205TT
Typical Response Message, Display Format:

I205TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:07 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

TANK

PRODUCT

STATUS

1


REGULAR UNLEADED

NORMAL

Typical Response Message, Computer Format:
i205TTYYMMDDHHmmTTnnNN...
TTnnNN&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
nn
NN

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of alarms active for tank (Hex, 00=none)
Alarm Type Number:
See explanation for "NN" when "AA" is 02 in Function i10100
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

62

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 206
Function Type: In-Tank Alarm History Report

Version 1

Command Format:
Display: I206TT
Computer: i206TT
Typical Response Message, Display Format:

I206TT
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:07 PM
1....
2....
3....
4....

TANK ALARM HISTORY
TANK 1

REGULAR UNLEADED

LOW PRODUCT ALARM

DEC 22, 1995 3:31 PM
DEC 19, 1995 10:05 AM

INVALID FUEL LEVEL

DEC 20, 1995 11:59 AM
DEC 20, 1995 11:58 AM
DEC 20, 1995 11:57 AM


Typical Response Message, Computer Format:
i206TTYYMMDDHHmmTTnnYYMMDDHHmmaaaa...
TTnnYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
nn
YYMMDDHHmm

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of alarms in history for tank (Decimal, 00=none)
Date and time alarm occurred

Part No. 576013-635, Revision AA

63

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 206 Notes: (Continued)
5.

6.
7.

aaaa - Type of alarm:
0001=Tank Setup Data Warning
0002=Tank Leak Alarm
0003=Tank High Water Alarm
0004=Tank Overfill Alarm
0005=Tank Low Product Alarm
0006=Tank Sudden Loss Alarm
0007=Tank High Product Alarm
0008=Tank Invalid Fuel Level Alarm
0009=Tank Probe Out Alarm
000A=Tank High Water Warning
000B=Tank Delivery Needed Warning
000C=Tank Maximum Product Alarm
000D=Tank Gross Leak Test Fail Alarm
000E=Tank Periodic Leak Test Fail Alarm
000F=Tank Annual Leak Test Fail Alarm
0010=Tank Periodic Test Needed Warning
0011=Tank Annual Test Needed Warning
0012=Tank Periodic Test Needed Alarm
0013=Tank Annual Test Needed Alarm
0014=Tank Leak Test Active
0015=Tank No CSLD Idle Time Warning
0016=Tank Siphon Break Active Warning
0017=Tank CSLD Rate Increase Warning
0018=Tank AccuChart Calibration Warning
0019=Tank HRM Reconciliation Warning
001A=Tank HRM Reconciliation Alarm
001B=Tank Cold Temperature Warning
001C=Tank Missing Delivery Ticket Warning
001D=Tank/Line Gross Leak Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

64

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 207
Function Type: In-Tank Leak Test History Report

Version 2

Command Format:
Display: I207TT
Computer: i207TT
Typical Response Message, Display Format:

I207TT
JUL 29, 1997 9:02 AM
TANK LEAK TEST HISTORY
T 1:REGULAR UNLEADED
LAST GROSS TEST PASSED:
TEST START TIME
JUL 29, 1997 6:02 AM

HOURS

VOLUME
2821

% VOLUME
48.9

TEST TYPE
STANDARD

HOURS
27

VOLUME
2680

% VOLUME
46.4

TEST TYPE
CSLD

HOURS
25

VOLUME
2916

% VOLUME
50.5

TEST TYPE
CSLD

LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
TEST START TIME
JUL 29, 1997 4:15 AM
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME
JUL 20, 1997 1:52 AM


Part No. 576013-635, Revision AA

65

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 207 Notes: (Continued)
Typical Response Message, Computer Format:
i207TTYYMMDDHHmmTTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp...
TTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

7.
8.
9.
10.
11.
12.

YYMMDDHHmm
TT
NN
RR

-

nn tt -

YYMMDDHHmm
hhhhhhhh
VVVVVVVV
pppppppp
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of Leak History Reports to Follow (Hex)
Leak Report Type:
00=Last Test Passed
01=Fullest Test Passed
02=Fullest Periodic Monthly Test Passed
Leak History Number (1-12) for first Monthly Tests Passed
In-Tank Leak Test Type:
00=0.20 gal/hr test
01=0.10 gal/hr test
02=Gross (3 gal/hr)test
In-Tank Leak Test Start Time
Leak Test Duration in Hours (ASCII Hex IEEE float)
Leak Test Volume (ASCII Hex IEEE float)
Leak Test Percentage of Full Volume (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

66

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 208
Function Type: In-Tank Leak Test Results Report

Version 2

Command Format:
Display: I208TT
Computer: i208TT
Typical Response Message, Display Format:

I208TT
JAN 22, 1996

3:07 PM

PREVIOUS IN TANK LEAK TEST RESULTS
TANK 1
REGULAR UNLEADED
TEST TYPE START TIME
ANNUAL
NOV 21, 1995
8:34 AM
PERIODIC NOV 21, 1995
8:34 AM
GROSS
NOV 24, 1995
8:04 AM


RESULT
PASSED
PASSED
PASSED

RATE
0.00
0.00
0.00

HOURS
12
12

VOLUME
9088
9088
9088

Typical Response Message, Computer Format:
i208TTYYMMDDHHmmTTNNttmmYYMMDDHHmmRRrrrrrrrrhhhhhhhhVVVVVVVV...
TTNNttmmYYMMDDHHmmRRrrrrrrrrhhhhhhhhVVVVVVVV&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
NN
tt

-

5.

mm -

6.
7.

YYMMDDHHmm RR -

8.
9.
10.
11.
12.

rrrrrrrr
hhhhhhhh
VVVVVVVV
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of Results to Follow (Hex)
In-Tank Leak Test Result Type:
00=0.20 gal/hr Test
01=0.10 gal/hr Test
02=Gross (3 gal/hr) Test
In-Tank Leak Manifold Status:
00=Tank Not Manifolded During Leak Test
01=Tank Manifolded During Leak Test
Previous In-Tank Leak Test Start Time
Previous In-Tank Leak Test Result:
00=Test Invalid
01=Test Passed
02=Test Failed
Test Rate (ASCII Hex IEEE float)
Leak Test Duration in Hours (ASCII Hex IEEE float)
Leak Test Volume (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

67

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 20A
Function Type: HRM Adjusted Delivery Report

Version 110

Command Format:
Display: I20ATT
Computer: i20ATT
Typical Response Message, Display Format:

I20ATT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:08 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ADJUSTED DELIVERY REPORT
T 1:REGULAR UNLEADED
INCREASE DATE/TIME
JAN 13, 1996 2:06
JAN 15, 1996 1:07
JAN 17, 1996 3:13
JAN 19, 1996 3:22
JAN 21, 1996 2:52


AM
PM
AM
AM
AM

INCREASE
VOLUME
3795
5383
6012
4413
6005

INCREASE
TC VOLUME
3859
5458
6114
4480
6112

ADJUSTMENT
8
30
-1
-3
6

DELIVERY DELIVERY
VOLUME TC VOLUME
3803
3868
5413
5487
6010
6113
4409
4473
6011
6119

Typical Response Message, Computer Format:
i20A00YYMMDDHHmmTTpPPrrYYMMDDHHmmNNFFFFFFFF...
TTpPPrrYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

9.
10.

YYMMDDHHmm
TT
p
PP
rr
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type
Number of Records to follow (Decimal)
Date/Time of Delivery Start
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Increase Volume
2. Increase Temp Comp Volume
3. Adjustment factor
4. Adjusted Increase Value
5. Adjusted Temp Comp Volume
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

68

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 20B
Function Type: BIR Adjusted Delivery Report

Version 110

Command Format:
Display: I20BTT
Computer: i20BTT
Typical Response Message, Display Format:

I20BTT
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:08 PM
1....
2....
3....
4....

BIR ADJUSTED DELIVERY REPORT
T 1:REGULAR UNLEADED
DELIVERY START
DATE
JAN 21, 1996 2:52 AM
JAN 19, 1996 3:22 AM
JAN 17, 1996 3:13 AM


DELIVERY END
DATE
JAN 21, 1996 3:12 AM
JAN 19, 1996 3:40 AM
JAN 17, 1996 3:40 AM

Part No. 576013-635, Revision AA

START
VOLUME
3193
4193
2739

END
VOLUME
9197
8602
8749

ADJ
DELIV
6011
4409
6010

ADJ TC
DELIV
6119
4473
6113

69

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 20B Notes: (Continued)
Typical Response Message, Computer Format:
i20BTTYYMMDDHHmmTTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm
TT
dd
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=All)
Number of Deliveries to follow
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Starting Volume
2. Ending Volume
3. Adjusted Delivery Volume
4. Adjusted Temperature Compensated Delivery Volume
5. Starting Fuel Height
6. Starting Fuel Temperature 1
7. Starting Fuel Temperature 2
8. Starting Fuel Temperature 3
9. Starting Fuel Temperature 4
10. Starting Fuel Temperature 5
11. Starting Fuel Temperature 6
12. Ending Fuel Height
13. Ending Fuel Temperature 1
14. Ending Fuel Temperature 2
15. Ending Fuel Temperature 3
16. Ending Fuel Temperature 4
17. Ending Fuel Temperature 5
18. Ending Fuel Temperature 6
19. Total Dispensed During Delivery
20. Starting Fuel Temperature Average
21. Ending Fuel Temperature Average
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

70

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 20C
Function Type: In-Tank Most Recent Delivery Report

Version 15

Command Format:
Display: I20CTT
Computer: i20CTT
Typical Response Message, Display Format:

I20CTT
JUL 29, 1997
STATION
STATION
STATION
STATION

9:03 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

LAST DELIVERY REPORT
T 1:REGULAR UNLEADED
INCREASE
DATE / TIME
END: JUL 28, 1997
START: JUL 28, 1997
AMOUNT:


GALLONS TC GALLONS WATER
3:14 PM
3:05 PM

3231
1244
1987

3194
1231
1963

0.00
0.00

TEMP DEG F

HEIGHT

76.14
73.89

48.27
24.40

Typical Response Message, Computer Format:
i20CTTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
dd

-

5.
6.
7.
8.

YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Starting Volume
2. Starting TC Volume
3. Starting Water
4. Starting Temp
5. Ending Volume
6. Ending TC Volume
7. Ending Water
8. Ending Temp
9. Starting Height
10. Ending Height
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

71

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 20D
Function Type: In-Tank Stick Height Report

Version 15

Command Format:
Display: I20DTT
Computer: i20DTT
Notes:
1.

This command will respond only if stick height is enabled.
Tank stick height is fuel height (without tilt) + stick
offset. If the stick height is less then zero, it will be
set to zero. If the stick height is greater than tank
diameter, it will be set to tank diameter.

Typical Response Message, Display Format:

I20DTT
OCT 15, 1996

4:29 PM

TANK STICK HEIGHT
TANK
1
2
3


PRODUCT LABEL
REGULAR
MIDGRADE
SUPER

INCHES
25.0
67.5
66.1

Typical Response Message, Computer Format:
i20DTTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Stick Height (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

72

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 211
Function Type: Tank Chart Report

Version 14

Command Format:
Display: I211TThhhhhh
Computer: i211TTFFFFFFFF
Notes:
1.
2.
3.

TT - Tank number, 00=All tanks
hhhhh - height step size (inches or millimeters). Up to 6 decimal
digits. If less then 6 digits are entered, use carriage
return to terminate the command.
FFFFFFFF - height step size (ASCII Hex IEEE float)

Minimum Step Size:0.010 inches or 0.397 millimeter
Minimum Resolution: 3 decimal places
Typical Response Message, Display Format:

I21101
OCT 15, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

4:29 PM
1....
2....
3....
4....

TANK CALIBRATION CHART

TANK 1
REGULAR UNLEADED
10028 GALLONS
96.00 INCHES

DEPTH
CAPACITY
DEPTH
CAPACITY
DEPTH
CAPACITY
DEPTH
CAPACITY
INCHES
GALLONS
INCHES
GALLONS
INCHES
GALLONS
INCHES
GALLONS
----------------------------------------------------------------------------0.000
0
26.000
2413
52.000
5827
78.100
9021
0.500
69
26.500
2474
52.500
5894
78.500
9073
1.000
90
27.000
2535
53.000
5961
79.000
9123
1.500
114
27.500
2596
53.500
6028
79.500
9173
:
:

Typical Response Message, Computer Format:
i211TTYYMMDDHHmmTTnnnnaaaaaaaaAAAAAAAAbbbbbbbbBBBBBBBB...
TTnnnnaaaaaaaaAAAAAAAAbbbbbbbbBBBBBBBB&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm
TT
nnnn
aaaaaaaa
AAAAAAAA
bbbbbbbb
BBBBBBBB
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
Height 1 (ASCII Hex IEEE float)
Volume 1 (ASCII Hex IEEE float)
Height 2 (ASCII Hex IEEE float)
Volume 2 (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

73

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 212
Function Type: In-Tank Leak Test History Report 2

Version 24

Command Format:
Display: I212TT
Computer: i212TT
Typical Response Message, Display Format:

I212TT
JUL 29, 1997 9:02 AM
TANK LEAK TEST HISTORY
T 1:REGULAR UNLEADED
LAST GROSS TEST PASSED:
TEST START TIME
JUL 29, 1997 6:02 AM

HOURS

VOLUME
2821

% VOLUME
48.9

TEST TYPE
STANDARD

HOURS
27

VOLUME
2680

% VOLUME
46.4

TEST TYPE
CSLD

HOURS
25

VOLUME
2916

% VOLUME
50.5

TEST TYPE
CSLD

LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
TEST START TIME
JUL 29, 1997 4:15 AM
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME
JUL 20, 1997 1:52 AM


Part No. 576013-635, Revision AA

74

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 212 Notes: (Continued)
Typical Response Message, Computer Format:
i212TTYYMMDDHHmmTTNNRRnnttYYMMDDHHmm
hhhhhhhhVVVVVVVVppppppppzzmmmmmmmm...
TTNNRRnnttYYMMDDHHmm
hhhhhhhhVVVVVVVVppppppppzzmmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

7.
8.
9.
10.
11.
12.
13.
14.

YYMMDDHHmm
TT
NN
RR

-

nn tt -

YYMMDDHHmm
hhhhhhhh
VVVVVVVV
pppppppp
zz
mmmmmmmm

-

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Number of Leak History Reports to Follow (Hex)
Leak Report Type:
00=Last Test Passed
01=Fullest Test Passed
02=Fullest Periodic Monthly Test Passed
Leak History Number (1-12) for first Monthly Tests Passed
In-Tank Leak Test Type:
00=0.20 gal/hr test
01=0.10 gal/hr test
02=Gross (3 gal/hr) test
In-Tank Leak Test Start Time
Leak Test Duration in Hours (ASCII Hex IEEE float)
Leak Test Volume (ASCII Hex IEEE float)
Leak Test Percentage of Full Volume (ASCII Hex IEEE float)
Number of 8 Byte Fields to Follow (Hex)
In-Tank Leak Test Method (Hex)
00000000=Standard
00000001=CSLD
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

75

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 213
Function Type: In-Tank Extended Standard Delivery Report

Version 26

Command Format:
Display: I213TTnn
Computer: i213TTnn
Notes:
1.
2.

TT - Tank Number (Decimal, 00=all)
nn - Number of most recent deliveries (Decimal)

Typical Response Message, Display Format:

I213TTnn
JUL 29, 1997
STATION
STATION
STATION
STATION

9:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

DELIVERY REPORT
T 1:REGULAR UNLEADED
INCREASE
DATE / TIME

GALLONS TC GALLONS WATER

TEMP DEG F

HEIGHT

END: JUL 28, 1997
START: JUL 28, 1997
AMOUNT:

3:14 PM
3:05 PM

3231
1244
1987

3194
1231
1963

0.00
0.00

76.14
73.89

48.27
24.40

END: JUL 25, 1997
START: JUL 25, 1997
AMOUNT:


2:48 PM
2:37 PM

4460
1157
3303

4414
1146
3268

0.00
0.00

74.56
72.85

63.06
23.22

Part No. 576013-635, Revision AA

76

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 213 Notes: (Continued)
Typical Response Message, Computer Format:
i213TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
dd

-

5.
6.
7.
8.

YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (single ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Starting Volume
2. Starting TC Volume
3. Starting Water
4. Starting Temp
5. Ending Volume
6. Ending TC Volume
7. Ending Water
8. Ending Temp
9. Starting Height
10. Ending Height
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

77

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 214
Function Type: In-Tank Mass/Density Inventory Report

Version 26

Command Format:
Display: I214TT
Computer: i214TT
Typical Response Message, Display Format:

I214TT
JUL 22, 1996
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

IN-TANK MASS/DENSITY INVENTORY
TANK PRODUCT
1 REGULAR UNLEADED


VOLUME
5329

MASS
20357

DENSITY
5.9987

HEIGHT
48.97

WATER
0.00

TEMP
37.39

Typical Response Message, Computer Format:
i214TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
ssss

-

5.
6.

NN FFFFFFFF -

7.
8.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (single ASCII character [20h-7Eh])
Tank Status Bits:
Bit 1=(LSB) Delivery in Progress
Bit 2=Leak Test in Progress
Bit 3=Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Volume
2. Mass
3. Density
4. Height
5. Water
6. Temperature
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

78

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 215
Function Type: In-Tank Mass/Density Delivery Report

Version 26

Command Format:
Display: I215TT
Computer: i215TT
Typical Response Message, Display Format:

I215TT
JUL 29, 1997
STATION
STATION
STATION
STATION

9:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

MASS/DENSITY DELIVERY REPORT
T 1:REGULAR UNLEADED
INCREASE
DATE / TIME
GALLONS
END: JUL 28, 1997 3:14 PM
3231
START: JUL 28, 1997 3:05 PM
1244
AMOUNT:
1987
END: JUL 25, 1997
START: JUL 25, 1997
AMOUNT:

Note:

2:48 PM
2:37 PM

4460
1157
3303

MASS
19380
7461
11918
26754
6940
19813*

DENSITY WATER
5.9983
0.00
5.9983
0.00
5.9987
5.9987

0.00
0.00

TEMP HEIGHT
76.14
48.27
73.89
24.40
74.56
72.85

63.06
23.22

asterisk (*) indicates default density.

Typical Response Message, Computer Format:
i215TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

9.
10.
11.

YYMMDDHHmm
TT
p
dd
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (single ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00=no data)
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Starting Volume
2. Starting Mass
3. Starting Density
4. Starting Water
5. Starting Temp
6. Ending Volume
7. Ending Mass
8. Ending Density
9. Ending Water
10. Ending Temp
11. Starting Height
12. Ending Height
f - Default Density Flag (0=new value, 1=default)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

79

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 216
Function Type: Tank 50 Point Heights, Volumes and Slope Report

Version 26

Command Format:
Display: I216TT
Computer: i216TT
Typical Response Message, Display Format:

I216TT
SEP 16, 2004

3:15 PM

TANK 50 POINT HEIGHTS, VOLUMES AND SLOPES
T 1: REGULAR UNLEADED

PAIR
1
2
3
4
5

DIAMETER
96.00

FULL VOLUME
10000

SLOPE
104.17

HEIGHT
94.08
92.16
90.24
88.32
86.44

VOLUME
9800
9600
9400
9200
9000

SLOPE
104.17
104.17
104.17
104.17
104.17

1000
800
600
400
200

104.17
104.17
104.17
104.17
104.17

:
:
45
46
47
48
49


9.60
7.68
5.76
3.84
1.92

Typical Response Message, Computer Format:
i216TTYYMMDDHHmmTTddddddddffffffffssssssssnn
HHHHHHHHVVVVVVVVSSSSSSSS...
HHHHHHHHVVVVVVVVSSSSSSSS...
TTddddddddffffffffssssssssnn
HHHHHHHHVVVVVVVVSSSSSSSS...
HHHHHHHHVVVVVVVVSSSSSSSS&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

YYMMDDHHmm
TT
dddddddd
ffffffff
ssssssss
nn
HHHHHHHH
VVVVVVVV
SSSSSSSS
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Tank Diameter, Inches (ASCII Hex IEEE float)
Full Volume, Gallons (ASCII Hex IEEE float)
Slope, Gallons per Inch (ASCII Hex IEEE float)
Number of Height/Volume Pairs to Follow (Hex).
Height, Inches (ASCII Hex IEEE float)
Volume, Gallons (ASCII Hex IEEE float)
Slope, Gallons per Inch (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

80

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 217
Function Type: Tank Profile

Version 26

Command Format:
Display: I217TT
Computer: i217TT
Typical Response Message, Display Format:

I217TT
SEP 16, 2004

3:15 PM

TANK PROFILE
T 1: REGULAR UNLEADED
TANK
PRODUCT LABEL
1
REGULAR UNLEADED


PROFILE
1 PT

Typical Response Message, Computer Format:
i217TTYYMMDDHHmmTTpp...TTpp&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
pp - Tank Profile Selected (Hex)
00= 1 Pt
01= 4 Pts
02=20 Pts
03=Linear
04=50 Pts
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

81

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 218
Function Type: Tank Chart Audit Trail

Version 26

Command Format:
Display: I218TT
Computer: i218TT
Notes:
1.

Returns the times of the last 10 tank chart modifications, most recent first

Typical Response Message, Display Format:

I218TT
JUL 29, 1997

9:02 AM

TANK CHART AUDIT TRAIL
T 1: REGULAR UNLEADED
TANK CAPACITY
: 1000
CONSOLE SERIAL NUMBER:
xxxxxxxxxxxxxxxxxxxx
PROBE S/N
: yyyyyy
WEIGHTS AND MEASURES:
zzzzzzzzzzzzzzzzzzzz
DATE/TIME
SEP 10, 2004 4:33 PM
SEP 09, 2004 3:25 PM
SEP 08, 2004 11:10 AM
SEP 02, 2004 5:30 PM
SEP 01, 2004 3:28 PM

Typical Response Message, Computer Format:
i218TTYYMMDDHHmmTTccccccccxxxxxxxxxxxxxxxxxxxxyyyyyyzzzzzzzzzzzzzzzzzzzz
nnyymmddhhmm...yymmddhhmm...
TTccccccccxxxxxxxxxxxxxxxxxxxxyyyyyyzzzzzzzzzzzzzzzzzzzz
nnyymmddhhmm...yymmddhhmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm
TT
cccccccc
x..x
yyyyyy
z..z
nn
yymmddhhmm
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Tank Capacity, Gallons (ASCII Hex IEEE float)
Console Serial Number (20 ASCII characters [20h-7Eh])
Probe Serial Number (Decimal)
Weights and Measures Office (20 ASCII characters [20h-7Eh])
Number of Date/Time fields to follow (Decimal)
Date and Time of Tank Chart Modification
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

82

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 219
Function Type: Tank Chart Security Status

Version 26

Command Format:
Display: I219TT
Computer: i219TT
Typical Response Message, Display Format:

I21900
JUN 22, 2001

3:15 PM

TANK CHART SECURITY
ENABLED

Typical Response Message, Computer Format:
i21900YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Tank Chart Security Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

83

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 21A (like 201)
Function Type: In-Tank Inventory Report With 90/95% Ullage

Version 27

Command Format:
Display: I21ATT
Computer: i21ATT
Typical Response Message, Display Format:

I21ATT
JAN 22, 2006
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

TANK PRODUCT
1 REGULAR UNLEADED


VOLUME TC VOLUME
8904
8904

95% ULLAGE
596

HEIGHT
80.00

WATER
0.00

TEMP
60.00

Typical Response Message, Computer Format:
i21ATTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
ssss

-

5.
6.

NN FFFFFFFF -

7.
8.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress
Bit 2 - Leak Test in Progress
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4 - 16 - Unused
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Volume
2. TC Volume
3. 90/95% Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

84

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 21B
Function Type: BIR Extended Adjusted Delivery Report

Version 26

Command Format:
Display: I21BTTnn
Computer: i21BTTnn
Notes:
1.
2.

TT - Tank Number (Decimal, 00=All)
nn - Number of most recent deliveries (Decimal)

Typical Response Message, Display Format:

I21BTTnn
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:08 PM
1....
2....
3....
4....

BIR ADJUSTED DELIVERY REPORT
T 1:REGULAR UNLEADED
DELIVERY START
DATE
JAN 21, 1996 2:52 AM
JAN 19, 1996 3:22 AM
JAN 17, 1996 3:13 AM


DELIVERY END
DATE
JAN 21, 1996 3:12 AM
JAN 19, 1996 3:40 AM
JAN 17, 1996 3:40 AM

Part No. 576013-635, Revision AA

START
VOLUME
3193
4193
2739

END
VOLUME
9197
8602
8749

ADJ
DELIV
6011
4409
6010

ADJ TC
DELIV
6119
4473
6113

85

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 21B Notes: (Continued)
Typical Response Message, Computer Format:
i21BTTYYMMDDHHmmTTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm
TT
dd
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=All)
Number of Deliveries to follow
Starting Date/Time
Ending Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Starting Volume
2. Ending Volume
3. Adjusted Delivery Volume
4. Adjusted Temperature Compensated Delivery Volume
5. Starting Fuel Height
6. Starting Fuel Temperature 1
7. Starting Fuel Temperature 2
8. Starting Fuel Temperature 3
9. Starting Fuel Temperature 4
10. Starting Fuel Temperature 5
11. Starting Fuel Temperature 6
12. Ending Fuel Height
13. Ending Fuel Temperature 1
14. Ending Fuel Temperature 2
15. Ending Fuel Temperature 3
16. Ending Fuel Temperature 4
17. Ending Fuel Temperature 5
18. Ending Fuel Temperature 6
19. Total Dispensed During Delivery
20. Starting Fuel Temperature Average
21. Ending Fuel Temperature Average
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

86

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 221
Function Type: Ticketed Delivery Report

Version 116

Command Format:
Display: I221TTtt
Computer: i221TTtt
Notes:
1.
2.

TT - Tank Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

I221TT
MAR 20, 1998
STATION
STATION
STATION
STATION

3:25 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CURRENT PERIOD TICKETED DELIVERY REPORT
VOLUMES ARE STANDARD
T 1:REGULAR UNLEADED
DELIVERY END DATE
MAR 7, 1998 8:26 AM
MAR 9, 1998 11:37 AM
MAR 10, 1998 11:34 PM


TICKET
VOLUME
5901.0
5901.0
4099.0

GAUGE
VOLUME
5905.0
5905.0
4094.0

DLVY
VAR
-4.0
-4.0
5.0

BEFORE
TMP
44.8
44.6
44.6

AFTER EST DLVY
TMP
TMP
42.4
41.0
43.2
42.4
42.6
40.5

Typical Response Message, Computer Format:
i221TTYYMMDDHHmmTTpPPdddYYMMDDHHmmNNFFFFFFFF...
TTpPPdddYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
p
PP
ddd

-

6.
7.
8.

YYMMDDHHmm NN FFFFFFFF -

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe type (Decimal)
Number of deliveries to follow (decimal) if 0, no more data
for this tank will follow
Ending date/ time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. ticket volume
2. gauged volume
3. delivery variance
4. start fuel temperature
5. end fuel temperature
6. estimated delivery temperature
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

87

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 222
Function Type: Bill of Lading Report

Version 23

Command Format:
Display: S222TTtt
Computer: s222TTtt
Notes:
1.
2.

Inquire:
I222TT
i222TT

TT - Tank Number (Decimal, 00=all)
tt - Report Type (if tt is not entered current is default)
01=current
02=previous

Typical Response Message, Display Format:

2220101
JAN 1, 1996
STATION
STATION
STATION
STATION

8:00 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CURRENT PERIOD TICKETED AND BOL DELIVERY REPORT
PROD

1:

UNLEADED GASOLINE

DELIVERY END DATE
DEC 2, 1993 2:00 AM
DEC 6, 1993 2:00 AM
DEC 10, 1993 2:00 AM

BOL
NUMBER
123456
123983
123902

TICKET
VOLUME
0.0
7375.0
2799.0

GAUGE
VOLUME
502.0
7369.0
2790.0

TC GAUGE
VOLUME
0.0
7375.0
2799.0

Typical Response Message, Computer Format:
222TTYYMMDDHHmmTTpPPdddYYMMDDHHmmAAaa..aaNNFFFFFFFF....FFFFFFFF...
TTpPPdddYYMMDDHHmmAAaa..aaNNFFFFFFFF....FFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
p
PP
ddd

-

6.
7.
8.
9.
10.

YYMMDDHHmm
AA
aa..aa
NN
FFFFFFFF

-

11.
12.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 0=all)
Product Code (Decimal)
Probe type (Decimal)
Number of deliveries to follow (Decimal) if 0, no more data
for this tank will follow
Ending date/ time
Number of ASCII characters to follow (Hex)
Bill of Lading Number (ASCII characters [20h-7Eh])
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Ticketed volume
2. Gauged volume
3. Gauged TC volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

88

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 225
Function Type: Periodic Delivery Variance Report

Version 116

Command Format:
Display: I225TTtt
Computer: i225TTtt
Notes:
1.
2.

TT - Tank Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

I225TT
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:25 PM
1....
2....
3....
4....

CURRENT PERIOD DELIVERY VARIANCE REPORT
VOLUMES ARE STANDARD
T 1:REGULAR UNLEADED

MAR
MAR
MAR
MAR
MAR
MAR
MAR

7,
9,
10,
12,
14,
16,
18,

1998 8:26 AM
1998 11:37 AM
1998 11:34 PM
1998 8:27 PM
1998 8:28 AM
1998 11:39 AM
1998 2:02 PM

TOTALS

TICKET
VOLUME
5901.0
5901.0
4099.0
3800.0
5900.0
5902.0
5901.0

GAUGE
VOLUME
5905.0
5905.0
4094.0
3797.0
5899.0
5916.0
5900.0

37404.0

37417.0

PERCENT VARIANCE OF SALES


Part No. 576013-635, Revision AA

VARIANCE
-4.0
-4.0
5.0
3.0
1.0
-14.0
1.0
-13.0

-13.0=-0.0%

89

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 225 Notes: (Continued)
Typical Response Message, Computer Format:
i225TTYYMMDDHHmmTTpPPdddYYMMDDHHmmNNFFFFFFFF...
TTpPPdddYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Numbers (Decimal, 00=all tanks)
3.
p - Product Number (Decimal)
4.
PP - Probe type (Decimal)
5.
ddd - Number of deliveries to follow (decimal) if 000, no more
data for this tank will follow
6.
YYMMDDHHmm - Delivery Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE floats:
1. Ticketed volume
2. Gauged volume
3. Delivery variance
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

90

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 226
Function Type: Weekly Delivery Variance Report

Version 116

Command Format:
Display: I226TTtt
Computer: i226TTtt
Notes:
1.
2.

TT - Tank Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

I226TT
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:25 PM
1....
2....
3....
4....

CURRENT WEEK DELIVERY VARIANCE REPORT
VOLUMES ARE STANDARD
T 1:REGULAR UNLEADED

MAR 16, 1998 11:39 AM
MAR 18, 1998 2:02 PM

TICKET
VOLUME
5902.0
5901.0

GAUGE
VOLUME
5916.0
5900.0

TOTALS

11803.0

11816.0

PERCENT VARIANCE OF SALES


VARIANCE
-14.0
1.0
-13.0

-13.0=-0.1%

Typical Response Message, Computer Format:
i226TTYYMMDDHHmmTTpPPdddYYMMDDHHmmNNFFFFFFFF...
TTpPPdddYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Numbers (Decimal, 00=all tanks)
3.
p - Product Number (Decimal)
4.
PP - Probe type (Decimal)
5.
ddd - Number of deliveries to follow (decimal) if 0, no more data
for this tank will follow
6.
YYMMDDHHmm - Delivery Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE float:
1. Ticketed volume
2. Gauged volume
3. Delivery variance
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

91

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 227
Function Type: Daily Delivery Variance Report

Version 116

Command Format:
Display: I227TTMMDD
Computer: i227TTMMDD
Notes:
1.
2.

TT - Tank number
MMDD - Month and day for Daily Report, if left blank will report
current date

Typical Response Message, Display Format:

I227TT
MAR 20, 1998
STATION
STATION
STATION
STATION

3:26 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

DAILY DELIVERY VARIANCE REPORT
VOLUMES ARE STANDARD
T 1:REGULAR UNLEADED

MAR 16, 1998 11:39 AM


TICKET
VOLUME
5902.0

GAUGE
VOLUME
5916.0

VARIANCE
-14.0

Typical Response Message, Computer Format:
i227TTYYMMDDHHmmTTpPPdddYYMMDDHHmmNNFFFFFFFF...
TTpPPdddYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
p
PP
ddd

-

6.
7.
8.

YYMMDDHHmm NN FFFFFFFF -

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type (Decimal)
Number of deliveries to follow (decimal) if 000, no more
data for this tank will follow
Delivery Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Ticketed volume
2. Gauged volume
3. Delivery variance
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

92

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 237
Function Type: In-Tank Product Inventory Report

Version 33

Command Format:
Display: I237TT
Computer: i237TT
Typical Response Message, Display Format:

I237TT
JAN 22, 2012
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

PRODUCT INVENTORY REPORT
TANK
1
2
3
4
5

PRODUCT
REGULAR
REGULAR
REGULAR
REGULAR

LABEL
1
2
3
4
TOTAL:

VOLUME
5265
5265
5265
5265
21060

TC VOLUME
5224
5220
5217
5231
20892

TOTAL:

3287
3287

3276
3276

DIESEL


Typical Response Message, Computer Format:
i237TTYYMMDDHHmmNNTTpnnaaaaaaaaAAAAAAAA...
TTpnnaaaaaaaaAAAAAAAAbbccccccccCCCCCCCC&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
NN
TT
p
nn
aaaaaaaa
AAAAAAAA
bb
cccccccc
CCCCCCCC
&&
CCCC

-

Current Date and Time
Number of tanks to follow (Hex)
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Number of eight byte ASCII Hex floats to follow
Tank Volume
Tank TC Volume
Number of eight byte ASCII Hex floats to follow
Product Volume
Product TC Volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

93

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 238
Function Type: In-Tank Siphon Manifolded Inventory Report

Version 33

Command Format:
Display: I238TT
Computer: i238TT
Typical Response Message, Display Format:

I238TT
JAN 22, 2012
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:06 PM
1....
2....
3....
4....

SIPHON MANIFOLDED INVENTORY REPORT
TANK PRODUCT LABEL
1 REGULAR 1
2 REGULAR 2
3
4
5

TOTAL:

VOLUME
5265
5265
10530

TC VOLUME
5224
5220
10448

TOTAL:

5265
5265
10530

5217
5231
10448

TOTAL:

3287
3287

3276
3276

PREMIUM 1
PREMIUM 2
DIESEL


Typical Response Message, Computer Format:
i238TTYYMMDDHHmmNNTTpnnaaaaaaaaAAAAAAAA...
TTpnnaaaaaaaaAAAAAAAAbbccccccccCCCCCCCC&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
NN
TT
p
nn
aaaaaaaa
AAAAAAAA
bb
cccccccc
CCCCCCCC
&&
CCCC

-

Current Date and Time
Number of tanks to follow (Hex)
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Number of eight byte ASCII Hex floats to follow
Tank Volume
Tank TC Volume
Number of eight byte ASCII Hex floats to follow
Product Volume
Product TC Volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

94

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 239
Function Type: In-Tank Manifolded Delivery Report
With Sales Adjustment if BIR available

Version 33

Command Format:
Display: I239TT
Computer: i239TT
Typical Response Message, Display Format:

I239TT
JUL 29, 2012
STATION
STATION
STATION
STATION

9:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

MANIFOLDED DELIVERY REPORT
TANK
PRODUCT LABEL
1
REGULAR A
2
REGULAR B
3
REGULAR C
DATE / TIME
OCT 10, 2012 1:01 AM
OCT 9, 2012 1:01 AM
OCT 8, 2012 1:01 AM
OCT 7, 2012 1:01 AM
OCT 6, 2012 1:01 AM
OCT 5, 2012 1:01 AM


GALLONS TC GALLONS
25857
25857
25854
25854
25851
25851
25848
25848
25845
25845
25842
25842

Typical Response Message, Computer Format:
i239TTYYMMDDHHmmnnTTp...TTpddYYMMDDHHmmNNFFFFFFFF...
nnTTp...TTpddYYMMDDHHmmNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
nn
TT
p
dd

-

6.
7.
8.

YYMMDDHHmm NN FFFFFFFF -

9.
10.

&& CCCC -

Current Date and Time
Number of Tanks to follow (???)
Tank Number (Decimal, 00=all)
Product Code (single ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00 if no data
available)
Starting Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Unadjusted Delivery Volume, IEEE float
2. Unadjusted TC Delivery Volume, IEEE float
3. Estimated Sales, IEEE float
4. Manifolded tanks bit mask, unsigned long
5. Probe Out bit mask, unsigned long
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

95

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 23A
Function Type: In-Tank Manifolded Delivery Report
With Sales Adjustment if BIR available

Version 33

Command Format:
Display: I23ATT
Computer: i23ATT
Typical Response Message, Display Format:

I23ATT
JUL 29, 2012
STATION
STATION
STATION
STATION

9:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

MANIFOLDED DELIVERY REPORT
TANK
PRODUCT LABEL
1
REGULAR A
2
REGULAR B
3
REGULAR C
START DATE / TIME
OCT 10, 2012 1:01 AM
OCT 9, 2012 1:01 AM
OCT 8, 2012 1:01 AM
OCT 7, 2012 1:01 AM
OCT 6, 2012 1:01 AM
OCT 5, 2012 1:01 AM


END DATE / TIME
OCT 10, 2012 1:21
OCT 9, 2012 1:21
OCT 8, 2012 1:21
OCT 7, 2012 1:21
OCT 6, 2012 1:21
OCT 5, 2012 1:21

AM
AM
AM
AM
AM
AM

GALLONS TC GALLONS
25857
25857
25854
25854
25851
25851
25848
25848
25845
25845
25842
25842

Typical Response Message, Computer Format:
i239TTYYMMDDHHmmnnTTp...TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
nnTTp...TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
nn
TT
p
dd

-

6.
7.
8.
9.

YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

10.
11.

&& CCCC -

Current Date and Time
Number of Tanks to follow
Tank Number (Decimal, 00=all)
Product Code (single ASCII character [20h-7Eh])
Number of Deliveries to follow (Decimal, 00 if no data
available)
Start Date/Time
End Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Unadjusted Delivery Volume, IEEE float
2. Unadjusted TC Delivery Volume, IEEE float
3. Estimated Sales, IEEE float
4. Manifolded tanks bit mask, unsigned long
5. Probe Out bit mask, unsigned long
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

96

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 251
Function Type: CSLD Results Report

Version 3

Command Format:
Display: I251TT
Computer: i251TT
Typical Response Message, Display Format:

I251TT
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:09 PM
1....
2....
3....
4....

CSLD TEST RESULTS
TANK PRODUCT
1 REGULAR UNLEADED


RESULT
PER: JAN 22, 1996 PASS

Typical Response Message, Computer Format:
i251TTYYMMDDHHmmTTrr...
TTrr&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
rr - Tank CSLD Results:
01=PASS
02=FAIL
03=NO RESULTS AVAILABLE
04=INVALID (software versions 3 and 4 only)
08=INCR (software versions 5 and above)
09=WARN (software versions 5 and above)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

97

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 281
Function Type: Fuel Management Report

Version 3

Command Format:
Display: I281TT
Computer: i281TT
Typical Response Message, Display Format:

I281TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:09 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

FUEL MANAGEMENT REPORT
REGULAR UNLEADED
( TANK 1 )
DAYS FUEL REMAINING: 1.8
INVENTORY :
5308 GAL
95% ULLAGE:
4218 GAL


SUN
2696

AVERAGE SALES (GALLONS)
MON
TUE
WED
THR
FRI
2075 2602 2046 2471 2805

SAT
2824

Typical Response Message, Computer Format:
i281TTYYMMDDHHmmPPTTpttp...NNFFFFFFFF...
PPTTpttp...NNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
PP
TTp,ttp
NN
FFFFFFFF

-

Current Date and Time
Number of tank product code pairs to follow (Hex)
Tank Number (decimal) and Product Code (ASCII character)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Days Supply of Fuel Remaining
2. Present Inventory
3. Present 95% Ullage
4. Average Sales on Sundays
5. Average Sales on Mondays
6. Average Sales on Tuesdays
7. Average Sales on Wednesdays
8. Average Sales on Thursdays
9. Average Sales on Fridays
10. Average Sales on Saturdays
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

98

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 282
Function Type: FLS Diagnostic: Volume History Table

Version 19

Command Format:
Display: I282TT
Computer: i282TT
Typical Response Message, Display Format:

I282TT
JAN 3, 1996 10:07 PM
FLS DIAGNOSTICS: VOLUME TABLE
T 1:UNLEADED GASOLINE
CURRENT INVENTORY VOLUME: 5345
CURRENT INVENTORY TIME:
JAN 3, 1996 10:07:22 PM
MOST RECENT STORED:
JAN 3, 1996 10:00:22 PM
1141
2248
3476
4281


1297
2265
3625
4307

1476
2281
3742
4339

1625
2307
3932
4405

1742
2339
4085
4456

1932
2405
4156
4573

2085
2456
0
4701

2156
2573
0
4854

2218
2701
4242
5022

2242
2854
4242
5160

2242
3022
4242
5276

2242
3141
4248
5345

2242
3297
4265
5450

Typical Response Message, Computer Format:
iXXXTTYYMMDDHHmmTTFFFFFFFFYYMMDDHHmmNNFFFFFFFF...
TTFFFFFFFFYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
FFFFFFFF
YYMMDDHHmm

-

5.
6.

NN FFFFFFFF -

7.
8.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=All Tanks)
Current Inventory Volume (ASCII Hex IEEE float)
Date and Time of the most recent stored hourly history
volume
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Latest recorded hourly volume
2. Intermediate hourly recorded volumes
3. Oldest recorded hourly volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

99

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 2E2
Function Type: In-Tank Stored Inventory Report

Version 14

Command Format:
Display: I2E2TTII
Computer: i2E2TTII
Typical Response Message, Display Format:

I2E2TT
JAN 22, 1996
STATION
STATION
STATION
STATION

3:06 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

JAN 22, 1996 8:00 AM
TANK PRODUCT
1 REGULAR UNLEADED


VOLUME TC VOLUME
5329
5413

ULLAGE
4699

HEIGHT
48.97

WATER
0.00

TEMP
37.39

Typical Response Message, Computer Format:
i2E2TTYYMMDDHHmmIIYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
II
YYMMDDHHmm
TT
p
ssss

-

7.
8.

NN FFFFFFFF -

9.
10.

&& CCCC -

Current Date and Time
Inventory Record Number (Decimal 01, 02, 03, 04)
Date and Time of Recorded Inventory
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress
Bit 2 - Leak Test in Progress
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

100

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2.3 SENSOR REPORTS
Function Code: 301
Function Type: Liquid Sensor Status Report

Version 1

Command Format:
Display: I301SS
Computer: i301SS
Typical Response Message, Display Format:

I301SS
JAN 28, 1995 10:10 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

LIQUID STATUS REPORT
SENSOR
1


LOCATION
LIQUID # 1

STATUS
SENSOR NORMAL

Typical Response Message, Computer Format:
i301SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

101

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 302
Function Type: Liquid Sensor Alarm History Report

Version 1

Command Format:
Display: I302SS
Computer: i302SS
Typical Response Message, Display Format:

I302SS
JAN 28, 1995 10:10 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

LIQUID ALARM HISTORY REPORT
SENSOR
1

LOCATION
LIQUID # 1
JAN 6, 1995

8:02 AM

FUEL ALARM


Typical Response Message, Computer Format:
i302SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

102

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 306
Function Type: Vapor Sensor Status Report

Version 1

Command Format:
Display: I306SS
Computer: i306SS
Typical Response Message, Display Format:

I306SS
JAN 28, 1995 10:11 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

VAPOR STATUS REPORT
SENSOR
1


LOCATION
VAPOR # 1

STATUS
SENSOR NORMAL

Typical Response Message, Computer Format:
i306SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

103

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 307
Function Type: Vapor Sensor Alarm History Report

Version 1

Command Format:
Display: I307SS
Computer: i307SS
Typical Response Message, Display Format:

I307SS
JAN 28, 1995 10:11 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

VAPOR ALARM HISTORY REPORT
SENSOR
1

LOCATION
VAPOR # 1
JAN 6, 1995

8:02 AM

WATER ALARM


Typical Response Message, Computer Format:
i307SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

104

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 311
Function Type: Groundwater Sensor Status Report

Version 1

Command Format:
Display: I311SS
Computer: i311SS
Typical Response Message, Display Format:

I311SS
JAN 28, 1995 10:11 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

GROUNDWATER STATUS REPORT
SENSOR
1


LOCATION
GROUND WATER # 1

STATUS
SENSOR NORMAL

Typical Response Message, Computer Format:
i311SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

105

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 312
Function Type: Groundwater Sensor Alarm History Report

Version 1

Command Format:
Display: I312SS
Computer: i312SS
Typical Response Message, Display Format:

I312SS
JAN 28, 1995 10:11 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

GROUNDWATER ALARM HISTORY REPORT
SENSOR
1

LOCATION
GROUND WATER # 1
JAN 6, 1995 8:02 AM

OPEN ALARM


Typical Response Message, Computer Format:
i312SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

106

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 315
Function Type: Smart Sensor Status Report

Version 24

Command Format:
Display: I315SS
Computer: i315SS
Typical Response Message, Display Format:

I315SS
JAN 22, 2003
STATION
STATION
STATION
STATION

3:07 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

SMART SENSOR STATUS REPORT
SENSOR
1

LOCATION

STATUS

SUMP 1

SENSOR NORMAL


Typical Response Message, Computer Format:
i315SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
ssss - Sensor status value:
0000=Smart Sensor Normal
0001=Smart Sensor Setup Data Warning
0002=Smart Sensor Communication Alarm
0003=Smart Sensor Fault Alarm
0004=Smart Sensor Fuel Warning
0005=Smart Sensor Fuel Alarm
0006=Smart Sensor Water Warning
0007=Smart Sensor Water Alarm
0008=Smart Sensor High Liquid Warning
0009=Smart Sensor High Liquid Alarm
0010=Smart Sensor Low Liquid Warning
0011=Smart Sensor Low Liquid Alarm
0012=Smart Sensor Temperature Warning
0013=Smart Sensor Relay Active
0014=Smart Sensor Install Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

107

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 316
Function Type: Smart Sensor Alarm History Report

Version 24

Command Format:
Display: I316SS
Computer: i316SS
Typical Response Message, Display Format:

I316SS
JAN 22, 2003
STATION
STATION
STATION
STATION

3:07 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

SMART SENSOR ALARM HISTORY REPORT
SENSOR
1

LOCATION
T1 SUMP
JUN 23, 2003
JUN 23, 2003
JUN 23, 2003

2:12 PM
2:12 PM
2:12 PM

WATER WARNING
WATER ALARM
FUEL ALARM


Typical Response Message, Computer Format:
i316SSYYMMDDHHmmSSnnYYMMDDHHmmaaaa...
SSnnYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
nn
YYMMDDHHmm
aaaa

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Number of alarms incidents to follow (Decimal, 00=none)
Date and time alarm occurred
Alarm type number:
0001=Smart Sensor Setup Data Warning
0002=Smart Sensor Communication Alarm
0003=Smart Sensor Fault Alarm
0004=Smart Sensor Fuel Warning
0005=Smart Sensor Fuel Alarm
0006=Smart Sensor Water Warning
0007=Smart Sensor Water Alarm
0008=Smart Sensor High Liquid Warning
0009=Smart Sensor High Liquid Alarm
0010=Smart Sensor Low Liquid Warning
0011=Smart Sensor Low Liquid Alarm
0012=Smart Sensor Temperature Warning
0013=Smart Sensor Relay Active
0014=Smart Sensor Install Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

108

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 317
Function Type: Mag Sump Leak Test In Progress/Last Test Report

Version 26

Command Format:
Display: I317ss
Computer: i317ss
Typical Response Message, Display Format:

I317ss
FEB 19, 2005

9:55 AM

MAG SUMP LEAK TEST
IN PROGRESS
s 1:SUMP NUMBER 1
STATUS:MEASURING HEIGHT
START TIME:
FEB 19, 2005 9:43 AM
START HT:
20.971 IN.
START TEMP:
76.1 F
CURRENT HT:
20.971 IN.
CURRENT TEMP:
76.1 F
DURATION:
12 MINS
TEMP RATE:
6.0 F/HR
LEAK RATE: 0.0000 IN./HR


Part No. 576013-635, Revision AA

109

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 317 Notes: (Continued)
Typical Response Message, Computer Format:
i317ssYYMMDDHHmmssttccYYMMDDHHmmNNHHHHHHHHTTTTTTTThhhhhhhhttttttttdddddddd
RRrrrrrrrrmmmmmmmmLLllllllll...
ssttccYYMMDDHHmmNNHHHHHHHHTTTTTTTThhhhhhhhttttttttdddddddd
RRrrrrrrrrmmmmmmmmLLllllllll&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
ss - Smart Sensor Number (Decimal, 00=all)
3.
tt - Mag Sump Leak Test Status
00=NO TEST DATA AVAILABLE
01=LEAK TEST ABORTED
02=FILL SUMP
03=MEASURING HEIGHT
04=LEAK TEST PASSED
4.
cc - Abort Reason Code
00=NOT ABORTED
01=MAG SENS ALM/WARN
02=WATER TOO LOW
03=WATER TOO HIGH
04=TEMP TOO LOW
05=TEMP TOO HIGH
06=WATER INCREASED
07=WATER DECREASED
08=INSUFFICIENT DATA
09=LEAK RATE TOO HIGH
10=TEST PHASE TIMEOUT
11=TEMP STABLE TIMEOUT
5.
YYMMDDHHmm - Start Date/Time
6.
NN - Number of 8 bytes data fields to follow (Decimal)
7.
HHHHHHHH - Starting Height, Inches (ASCII Hex IEEE float)
8.
TTTTTTTT - Starting Temperature, Degrees F (ASCII Hex IEEE float)
9.
hhhhhhhh - Ending Height (ASCII Hex IEEE float)
10.
tttttttt - Ending Temperature (ASCII Hex IEEE float)
11.
dddddddd - Duration in minutes (ASCII Hex IEEE float)
12.
RR - Temperature Change Rate Status Flag
00=UNKNOWN
01=VALID
02=COMPUTING
03=STABLE
13.
rrrrrrrr - Temperature Rate Change, Degrees F/Hr (ASCII Hex IEEE float)
14.
mmmmmmmm - Temperature Stable Time in minutes (ASCII Hex IEEE float)
15.
LL - Leak Rate Status Flag
00=UNKNOWN
01=VALID
02=COMPUTING
16.
llllllll - Leak Rate, Inches/Hr (ASCII Hex IEEE float)
17.
&& - Data Termination Flag
18.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

110

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 318
Function Type: Mag Sump Leak Test Last Passed Test Report

Version 26

Command Format:
Display: I318ss
Computer: i318ss
Typical Response Message, Display Format:

I318ss
FEB 21, 2005 10:50 AM
MAG SUMP LEAK TEST
LAST PASSED TEST
s 1:SUMP NUMBER 1
RESULT: TEST PASSED
START TIME:
FEB 19, 2005 9:43 AM
START HT:
20.971 IN.
START TEMP:
76.1 F
END HT:
20.971 IN.
END TEMP:
76.1 F
DURATION:
120 MINS

Typical Response Message, Computer Format:
i318ssYYMMDDHHmmssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
ssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm - Current Date and Time
ss - Smart Sensor Number (Decimal, 00=all)
tt - Mag Sump Leak Test Status
00=NO TEST DATA AVAILABLE
01=LEAK TEST ABORTED
02=FILL SUMP
03=MEASURING HEIGHT
04=LEAK TEST PASSED
YYMMDDHHmm - Start Date/Time
NN - Number of 8 bytes data fields to follow (Decimal)
HHHHHHHH - Starting Height, Inches (ASCII Hex IEEE float)
TTTTTTTT - Starting Temperature, Degrees F (ASCII Hex IEEE float)
hhhhhhhh - Ending Height (ASCII Hex IEEE float)
tttttttt - Ending Temperature (ASCII Hex IEEE float)
dddddddd - Duration in minutes (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

111

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 319
Function Type: Mag Sump Leak Test Last 10 Test Passed Report

Version 26

Command Format:
Display: I319ss
Computer: i319ss
Typical Response Message, Display Format:

I319ss
NOV 15, 2004

8:26 AM

MAG SUMP LEAK TEST
LAST 10 TEST PASSED
s 1:SUMP NUMBER 1
START DATE/TIME
JAN 19, 2005 9:43
DEC 12, 2004 10:24
MAY 3, 2004 1:18
FEB 23, 2004 3:12


AM
AM
PM
PM

START
HEIGHT
22.971
22.344
21.972
21.065

START
TEMP
76.1
75.4
72.0
76.2

END
HEIGHT
22.971
22.338
21.970
21.061

END
TEMP
76.1
75.3
72.2
76.2

DURATION
MINUTES
120
120
120
120

Typical Response Message, Computer Format:
i319ssYYMMDDHHmmssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
YYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
ssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
YYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
ss
tt
YYMMDDHHmm
NN
HHHHHHHH
TTTTTTTT
hhhhhhhh
tttttttt
dddddddd
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=All)
Number of Tests to follow (Max=10)
Date/Time Test
Number of 8 bytes data fields to follow
Starting Height, Inches (ASCII Hex IEEE float)
Starting Temperature, Degrees F (ASCII Hex IEEE float)
Ending Height (ASCII Hex IEEE float)
Ending Temperature (ASCII Hex IEEE float)
Duration in minutes (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

112

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 31A
Function Type: Mag Sump Leak Test Last Passed Each Year Report

Version 26

Command Format:
Display: I31Ass
Computer: i31Ass
Typical Response Message, Display Format:

I31Ass
NOV 15, 2004

8:26 AM

MAG SUMP LEAK TEST
LAST PASSED EACH YEAR
s 1:SUMP NUMBER 1
START DATE/TIME
JAN 19, 2005 9:43
FEB 12, 2004 10:24
MAR 3, 2003 1:18
JAN 23, 2002 3:12


AM
AM
PM
PM

START
HEIGHT
22.971
22.344
21.972
21.065

START
TEMP
76.1
75.4
72.0
76.2

END
HEIGHT
22.971
22.338
21.970
21.061

END
TEMP
76.1
75.3
72.2
76.2

DURATION
MINUTES
120
120
120
120

Typical Response Message, Computer Format:
i31AssYYMMDDHHmmssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
YYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
ssttYYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd...
YYMMDDHHmmNNHHHHHHHHTTTTTTTT
hhhhhhhhttttttttdddddddd&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
ss
tt
YYMMDDHHmm
NN
HHHHHHHH
TTTTTTTT
hhhhhhhh
tttttttt
dddddddd
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=All)
Total Tests to follow (Max=3)
Date/Time Test
Number of 8 bytes data fields to follow
Starting Height, Inches (ASCII Hex IEEE float)
Starting Temperature, Degrees F (ASCII Hex IEEE float)
Ending Height (ASCII Hex IEEE float)
Ending Temperature (ASCII Hex IEEE float)
Duration in minutes (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

113

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 322
Function Type: Pump Relay Monitor Status Report

Version 27

Command Format:
Display: I322rr
Computer: i322rr
Typical Response Message, Display Format:

I322rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR STATUS REPORT
DEVICE
1


LABEL
PUMP RELAY UNLEADED

PUMP
(OUT)
OFF

PUMP RELAY
(IN)
Q 1: OFF

STATUS
NORMAL

Typical Response Message, Computer Format:
i322rrYYMMDDHHmmrrabssss...
rrabssss&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm - Current Date and Time
rr - Pump Relay Monitor Number (Decimal, 00=all)
a - Pump Status (ASCII Hex)
0=Off
1=On
b - Relay Status (ASCII Hex)
0=Off (or N/A B no Pump Relay assigned)
1=On
ssss - Number of 8-character data fields to follow (ASCII Hex)
0000=Normal
0001=Setup Data Warning
0002=Pump Relay Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

114

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 323
Function Type: Pump Relay Monitor Alarm History Report

Version 27

Command Format:
Display: I323rr
Computer: i323rr
Typical Response Message, Display Format:

I323rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR ALARM HISTORY REPORT
DEVICE LABEL
PUMP RELAY UNLEADED
JUN 1, 2006


8:02 AM

PUMP RELAY ALARM

Typical Response Message, Computer Format:
i323rrYYMMDDHHmmrrNNYYMMDDHHmmaaaa...
rrNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
rr
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Pump Relay Monitor Number (Decimal, 00=all)
Number of Alarm Incidents to follow (ASCII Hex)
Date and Time of Alarm
Alarm Type number (ASCII Hex):
0001=Setup Data Warning
0002=Pump Relay Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

115

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 333
Function Type: Smart Sensor Install Log

Version 24

Command Format:
Display: I333SS
Computer: i333SS
Typical Response Message, Display Format:

I333SS
JAN 22, 2003

3:25 PM

SMART SENSOR INSTALL LOG
DATE
01-01-03
01-01-03


6:00:00
6:00:00

SENSOR
1
2

SERIAL NUMBER
123456
123457

TYPE
MAG SENSOR
FLOWMETER

Typical Response Message, Computer Format:
i333SSYYMMDDHHmmnnnYYMMDDHHmmSSNNNNNNNNffff...
YYMMDDHHmmSSNNNNNNNNffff&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
nnn
YYMMDDHHmm
SS
NNNNNNNN
ffff
&&
CCCC

-

Current Date and Time
Number of Events to Follow (Decimal)
Date and Time of Install Event
Smart Sensor Number (Decimal)
Sensor Serial Number (ASCII Hex IEEE float)
Smart Sensor Model Number (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

116

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 341
Function Type: Type A (2 Wire CL) Sensor Status Report

Version 2

Command Format:
Display: I341SS
Computer: i341SS
Typical Response Message, Display Format:

I341SS
FEB 18, 1990
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

10:53 AM
1....
2....
3....
4....

2 WIRE CL STATUS REPORT
SENSOR
1


LOCATION
2 WIRE CL SENSOR #1

STATUS
FUEL ALARM

Typical Response Message, Computer Format:
i341SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

117

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 342
Function Type: Type A (2 Wire CL) Sensor Alarm History Report

Version 2

Command Format:
Display: I342SS
Computer: i342SS
Typical Response Message, Display Format:

I342SS
FEB 18, 1990
STATION
STATION
STATION
STATION

10:53 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

2 WIRE CL ALARM HISTORY REPORT
SENSOR
1

LOCATION
2 WIRE CL SENSOR #1
FEB 12, 1990 11:32 AM
FEB 10, 1990 10:09 AM

FUEL ALARM
OPEN ALARM


Typical Response Message, Computer Format:
i342SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

118

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 346
Function Type: Type B (3 Wire CL) Sensor Status Report

Version 2

Command Format:
Display: I346SS
Computer: i346SS
Typical Response Message, Display Format:

I346SS
FEB 18, 1990
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

10:53 AM
1....
2....
3....
4....

3 WIRE CL STATUS REPORT
SENSOR
1


LOCATION
3 WIRE CL SENSOR #1

STATUS
FUEL ALARM

Typical Response Message, Computer Format:
i346SSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

119

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 347
Function Type: Type B (3 Wire CL) Sensor Alarm History Report

Version 2

Command Format:
Display: I347SS
Computer: i347SS
Typical Response Message, Display Format:

I347SS
FEB 18, 1990
STATION
STATION
STATION
STATION

10:53 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

3 WIRE CL ALARM HISTORY REPORT
SENSOR
1

LOCATION
3 WIRE CL SENSOR #1
FEB 12, 1990 11:32 AM
FEB 10, 1990 10:09 AM

FUEL ALARM
OPEN ALARM


Typical Response Message, Computer Format:
i347SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

120

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 34B
Function Type: Universal Sensor Status Report

Version 4

Command Format:
Display: I34BSS
Computer: i34BSS
Typical Response Message, Display Format:

I34BSS
FEB 18, 1990
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

10:53 AM
1....
2....
3....
4....

UNIVERSAL STATUS REPORT
SENSOR
1


LOCATION
UNIVERSAL SENSOR #1

STATUS
FUEL ALARM

Typical Response Message, Computer Format:
i34BSSYYMMDDHHmmSSssss...
SSssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal, 00=all)
ssss - Sensor Status Value:
0000=Sensor Normal
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

121

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 34C
Function Type: Universal Sensor Alarm History Report

Version 4

Command Format:
Display: I34CSS
Computer: i34CSS
Typical Response Message, Display Format:

I34CSS
FEB 18, 1990
STATION
STATION
STATION
STATION

10:53 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

UNIVERSAL ALARM HISTORY REPORT
SENSOR
1

LOCATION
UNIVERSAL SENSOR 1
FEB 12 1990 11:32 AM
FEB 10 1990 10:09 PM

FUEL ALARM
OPEN ALARM


Typical Response Message, Computer Format:
i34CSSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
SS
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Alarm Incidents to follow
Date and Time of Alarm
Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

122

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2.4 LINE LEAK REPORTS
Function Code: 351
Function Type: Volumetric Line Leak Result Report

Version 1

Command Format:
Display: I351PP
Computer: i351PP
Typical Response Message, Display Format:

I351PP
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1:55 PM
1....
2....
3....
4....

P 1:REGULAR UNLEADED
3.0 GAL/HR TEST
LINE
PREV 24 HOURS
104
SINCE MIDNIGHT
53
0.2 GAL/HR TEST
MAR 25, 1996 8:14 PM
MAR 25, 1996 2:02 AM
MAR 24, 1996 2:20 AM
0.1 GAL/HR TEST
MAR 26, 1996 1:48 AM
MAR 25, 1996 4:11 AM
MAR 24, 1996 3:25 AM


SELF
104
53

PUMP
111
56
PASSED
PASSED
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
i351PPYYMMDDHHmmPPLLSSBBllssbbNNYYMMDDHHmmRR...nnYYMMDDHHmmRR...
PPLLSSBBllssbbNNYYMMDDHHmmRR...nnYYMMDDHHmmRR&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.

YYMMDDHHmm
PP
LL
SS
BB
ll
ss
bb
NN
YYMMDDHHmm
RR
nn
YYMMDDHHmm
RR
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
3.00 GPH Line tests passed in previous 24 hours (Hex)
3.00 GPH Self tests passed in previous 24 hours (Hex)
3.00 GPH Pumpside tests passed in previous 24 hours (Hex)
3.00 GPH Line tests passed since midnight (Hex)
3.00 GPH Self tests passed since midnight (Hex)
3.00 GPH Pumpside tests passed since midnight (Hex)
Number of 0.20 GPH test date entries to follow (Decimal)
Date and Time of test
Test result (00=fail, 01=pass)
Number of 0.10 GPH test date entries to follow (Decimal)
Date and Time of test
Test result (00=fail, 01=pass)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

123

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 352
Function Type: Volumetric Line Leak Alarm History Report

Version 1

Command Format:
Display: I352PP
Computer: i352PP
Typical Response Message, Display Format:

I352PP
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1:55 PM
1....
2....
3....
4....

P 1:REGULAR UNLEADED
DEC 24, 1991 9:51 PM
DEC 23, 1991 9:46 PM
DEC 22, 1991 9:31 PM


LINE LEAK SHUTDOWN
LLD SELF TEST FAIL
LINE LEAK TEST FAIL

Typical Response Message, Computer Format:
i352PPYYMMDDHHmmPPNNYYMMDDHHmmaaaa...
PPNNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
PP
NN
YYMMDDHHmm

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Number of Alarm entries to follow (Decimal)
Date and Time of Alarm

Part No. 576013-635, Revision AA

124

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 352 Notes: (Continued)
5.

6.
7.

aaaa - Alarm type code:
0001=VLLD Setup Data Warning
0002=VLLD Self Test Alarm
0003=VLLD Shutdown Alarm
0004=VLLD Leak Test Fail Alarm
0005=VLLD Selftest Invalid Warning
0006=VLLD Continuous Handle On Warning
0007=VLLD Gross Line Test Fail Alarm
0008=VLLD Gross Line Selftest Fail Alarm
0009=VLLD Gross Pump Test Fail Alarm
000A=VLLD Gross Pump Selftest Fail Alarm
000B=VLLD Periodic Test Needed Warning
000C=VLLD Annual Test Needed Warning
000D=VLLD Periodic Test Needed Alarm
000E=VLLD Annual Test Needed Alarm
000F=VLLD Periodic Line Test Fail Alarm
0010=VLLD Periodic Line Selftest Fail Alarm
0011=VLLD Periodic Pump Test Fail Alarm
0012=VLLD Periodic Pump Selftest Fail Alarm
0013=VLLD Annual Line Test Fail Alarm
0014=VLLD Annual Line Selftest Fail Alarm
0015=VLLD Annual Pump Test Fail Alarm
0016=VLLD Annual Pump Selftest Fail Alarm
0017=VLLD Pressure Warning
0018=VLLD Pressure Alarm
0019=VLLD Gross Test Fault Alarm
001A=VLLD Periodic Test Fault Alarm
001B=VLLD Annual Test Fault Alarm
001C=VLLD Fuel Out Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

125

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 353
Function Type: Volumetric Line Leak Pump Status

Version 2

Command Format:
Display: I353PP
Computer: i353PP
Typical Response Message, Display Format:

I353PP
MAR 26, 1996

1:55 PM

STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

LINE
1


LOCATION
REGULAR UNLEADED

STATUS
ENABLED

Typical Response Message, Computer Format:
i353PPYYMMDDHHmmPPaaaa...
PPaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
aaaa - Line Status:
0001=Enabled
0002=Disabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

126

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 373
Version 14
Function Type: Pressure Line Leak Test Results (with 0.20 test data)
Command Format:
Display: I373QQ
Computer: i373QQ
Typical Response Message, Display Format:

I373QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:52 PM
1....
2....
3....
4....

PRESSURE LINE LEAK TEST RESULTS
Q 1:REGULAR UNLEADED
3.0 GAL/HR RESULTS:
LAST TEST:
JAN 24, 1996

2:49 PM PASS

NUMBER OF TESTS PASSED
PREV 24 HOURS :
149
SINCE MIDNIGHT :
76
0.20 GAL/HR RESULTS:
JAN 22, 1996

1:32 AM PASS

0.10 GAL/HR RESULTS:
JAN 23, 1996 11:59 PM PASS
NO-VENT TEST ABORTS:
3 OUT OF 10 TESTS


Part No. 576013-635, Revision AA

(Added in V19)
(Added in V19)

127

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 373: (Continued)
Typical Response Message, Computer Format:
i373QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt...
QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
QQ
yymmddhhmm
rr
TT
PPPP

-

7.
8.

MMMM NN -

9.
10.

YYMMDDHHmm RR -

11.
12.

tt nn -

13.
14.

YYMMDDHHmm RR -

15.
16.
17.

tt && CCCC -

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Last 3.00 gal/hr test time
3.00 gal/hr test result (Hex)
3.00 gal/hr test type (unused, always 00)
Number of 3.00 gal/hr tests passed in previous 24 hours
(Hex)
Number of 3.00 gal/hr tests passed since midnight (Hex)
Number of 0.10 gal/hr test results (14 character groups) to
follow (Hex)
Date and time of 0.10 gal/hr test
Test result
01=PASS
02=FAIL
0.10 gal/hr test type (unused, always 00)
Number of 0.20 gal/hr test results (14 character groups) to
follow (Hex)
Date and time of 0.20 gal/hr test
Test result
01=PASS
02=FAIL
0.20 gal/hr test type (unused, always 00)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

128

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 374
Version 14
Function Type: Pressure Line Leak Test History (with 0.20 test data)
Command Format:
Display: I374QQ
Computer: i374QQ
Typical Response Message, Display Format:

I374QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

2:52 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

PRESSURE LINE LEAK TEST HISTORY
Q 1:REGULAR UNLEADED
LAST

3.0 PASS:

JAN 24, 1996

2:49 PM

FIRST 0.10 PASS EACH MONTH:

JAN 16, 1996 12:38 AM

FIRST 0.20 PASS EACH MONTH:


JAN 14, 1996 10:21 PM

Typical Response Message, Computer Format:
i374QQYYMMDDHHmmQQyymmddhhmmTTNNYYMMDDHHmmttnnYYMMDDHHmmtt...
QQyymmddhhmmTTNNYYMMDDHHmmttnnYYMMDDHHmmtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
yymmddhhmm - Last 3.00 gal/hr test pass time ("0000000000" if no test
yet)
TT - 3.00 gal/hr test type (unused, always 00)
NN - Number of 0.10 gal/hr test results (12 character groups) to
follow (Hex)
YYMMDDHHmm - Date and time of 0.10 gal/hr test
tt - 0.10 gal/hr test type (unused, always 00)
nn - Number of 0.20 gal/hr test results (12 character groups) to
follow (Hex)
YYMMDDHHmm - Date and time of 0.20 gal/hr test
tt - 0.20 gal/hr test type (unused, always 00)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

129

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 381
Function Type: Pressure Line Leak Status

Version 7

Command Format:
Display: I381QQ
Computer: i381QQ
Typical Response Message, Display Format:

I381QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:52 PM
1....
2....
3....
4....

PRESSURE LINE LEAK STATUS
LINE
Q 1:REGULAR UNLEADED

DISPENSING
ENABLED

TEST STATUS
TESTING 0.10 GAL/HR

PUMP
OFF

HANDLE
OFF

ACTIVE ALARMS:

Typical Response Message, Computer Format:
i381QQYYMMDDHHmmQQSSSSttNNaaaa...
QQSSSSttNNaaaa&&CCCC
Notes:
1.
2.
3.

4.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
SSSS - Status Bits:
Bit 1 - (LSB) Dispensing enabled flag
(0=Disabled, 1=Enabled)
Bit 2 - Pump power
(0=Pump Off, 1=Pump On)
Bit 3 - Dispenser Handle
(0=Handle Off, 1=Handle On)
Bit 4-16 - Unused
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.10 gal/hr
04=test aborted
05=running pump (manual test starting)
06=line lockout
07=disable alarm
08=test pending
09=test delay
0A=pressure check
0B=testing at 0.20 gal/hr

Part No. 576013-635, Revision AA

130

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 381 Notes: (Continued)
5.
6.

7.
8.

NN - number of active alarms to follow (Hex)
aaaa - type of alarm:
0001=PLLD Setup Data Warning
0002=PLLD Gross Test Fail Alarm
0003=PLLD Annual Test Fail Alarm
0004=PLLD Periodic Test Needed Warning
0005=PLLD Periodic Test Needed Alarm
0006=PLLD Sensor Open Alarm
0007=PLLD High Pressure Alarm
0008=PLLD Shutdown Alarm
0009=PLLD High Pressure Warning
000A=PLLD Continuous Handle On Warning
000B=PLLD Periodic Test Fail Alarm
000C=PLLD Annual Test Needed Warning
000D=PLLD Annual Test Needed Alarm
000E=PLLD Low Pressure Alarm
000F=PLLD Sensor Short Alarm
0010=PLLD Continuous Handle On Alarm
0011=PLLD Fuel Out Alarm
0012=PLLD Line Equipment Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

(Obsolete V19)
(Obsolete V19)
(Obsolete V19)

(Obsolete V19)

131

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 382
Function Type: Pressure Line Leak Alarm History Report

Version 7

Command Format:
Display: I382QQ
Computer: i382QQ
Typical Response Message, Display Format:

I382QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

2:52 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:REGULAR UNLEADED
GROSS LINE FAIL


JAN

9, 1995

6:12 AM

Typical Response Message, Computer Format:
i382QQYYMMDDHHmmQQNNyymmddhhmmaaaa...
QQNNyymmddhhmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
QQ
NN
yymmddhhmm
aaaa

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
number of alarms to follow (Hex)
Date and time that the alarm occurred
type of alarm:
0001=PLLD Setup Data Warning
0002=PLLD Gross Test Fail Alarm
0003=PLLD Annual Test Fail Alarm
0004=PLLD Periodic Test Needed Warning
0005=PLLD Periodic Test Needed Alarm
0006=PLLD Sensor Open Alarm
0007=PLLD High Pressure Alarm
(Obsolete
0008=PLLD Shutdown Alarm
0009=PLLD High Pressure Warning
(Obsolete
000A=PLLD Continuous Handle On Warning
(Obsolete
000B=PLLD Periodic Test Fail Alarm
000C=PLLD Annual Test Needed Warning
000D=PLLD Annual Test Needed Alarm
000E=PLLD Low Pressure Alarm
000F=PLLD Sensor Short Alarm
(Obsolete
0010=PLLD Continuous Handle On Alarm
0011=PLLD Fuel Out Alarm
0012=PLLD Line Equipment Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

V19)
V19)
V19)

V19)

132

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 383
Version 7
Function Type: Pressure Line Leak Test Results (0.10 test data only)
Command Format:
Display: I383QQ
Computer: i383QQ
Notes:
1.

In Version 12, this command's response is inadvertently
identical to I373QQ. In Versions 7-11, 14, and higher, the
response is accurately defined here.

Typical Response Message, Display Format:

I383QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:52 PM
1....
2....
3....
4....

PRESSURE LINE LEAK TEST RESULTS
Q 1:REGULAR UNLEADED
3.0 GAL/HR RESULTS:
LAST TEST:
JAN 24, 1996

2:49 PM PASS

NUMBER OF TESTS PASSED
PREV 24 HOURS :
149
SINCE MIDNIGHT :
76
0.10 GAL/HR RESULTS:
JAN 23, 1996 11:59 PM PASS


Part No. 576013-635, Revision AA

133

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 383 Notes: (Continued)
Typical Response Message, Computer Format:
i383QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
QQ
yymmddhhmm
rr
TT
PPPP

-

7.
8.

MMMM NN -

9.
10.

YYMMDDHHmm RR -

11.
12.
13.

tt && CCCC -

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Last 3.00 gal/hr test time
3.00 gal/hr test result (Hex)
3.00 gal/hr test type (unused, always 00)
Number of 3.00 gal/hr tests passed in previous 24 hours
(Hex)
Number of 3.00 gal/hr tests passed since midnight (Hex)
Number of 0.10 gal/hr test results (14 character groups) to
follow (Hex)
Date and time of 0.10 gal/hr test
Test result
01=PASS
02=FAIL
0.10 gal/hr test type (unused, always 00)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

134

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 384
Version 7
Function Type: Pressure Line Leak Test History (0.10 test data only)
Command Format:
Display: I384QQ
Computer: i384QQ
Notes:
1.

In Version 12, this command's response is inadvertently
identical to I374QQ. In Versions 7-11, 14, and higher, the
response is accurately defined here.

Typical Response Message, Display Format:

I384QQ
JAN 24, 1996
STATION
STATION
STATION
STATION

2:52 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

PRESSURE LINE LEAK TEST HISTORY
Q 1:REGULAR UNLEADED
LAST

3.0 PASS:

FIRST 0.10 PASS EACH MONTH:


JAN 24, 1996

2:49 PM

JAN 16, 1996 12:38 AM

Typical Response Message, Computer Format:
i384QQYYMMDDHHmmQQyymmddhhmmTTNNYYMMDDHHmmtt...
QQyymmddhhmmTTNNYYMMDDHHmmtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
yymmddhhmm - Last 3.00 gal/hr test pass time ("0000000000" if no test
yet)
TT - 3.00 gal/hr test type (unused, always 00)
NN - Number of 0.10 gal/hr test results (12 character groups) to
follow (Hex)
YYMMDDHHmm - Date and time of 0.10 gal/hr test
tt - 0.10 gal/hr test type (unused, always 00)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

135

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 386
Function Type: WPLLD Line Leak Status

Version 10

Command Format:
Display: I386WW
Computer: i386WW
Typical Response Message, Display Format:

I386WW
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:52 PM
1....
2....
3....
4....

WPLLD LINE LEAK STATUS
LINE
W 1:REGULAR UNLEADED

DISPENSING
ENABLED

TEST STATUS
TESTING 0.20 GAL/HR

PUMP
OFF

HANDLE
OFF

ACTIVE ALARMS:
PLLD PERIODIC WARN

Typical Response Message, Computer Format:
i386WWYYMMDDHHmmWWSSSSttNNaaaa...
WWSSSSttNNaaaa&&CCCC
Notes:
1.
2.
3.

4.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
SSSS - Status Bits:
Bit 1 - (LSB) Dispensing enabled flag
(0=Disabled, 1=Enabled)
Bit 2 - Pump power
(0=Pump Off, 1=Pump On)
Bit 3 - Dispenser Handle
(0=Handle Off, 1=Handle On)
Bit 4-16 - Unused
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
05=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr

Part No. 576013-635, Revision AA

136

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 386 Notes: (Continued)
5.
6.

7.
8.

NN - number of active alarms to follow (Hex)
aaaa - type of alarm:
0001=WPLLD Setup Data Warning
0002=WPLLD Gross Test Fail Alarm
0003=WPLLD Periodic Test Fail Alarm
0004=WPLLD Periodic Test Needed Warning
0005=WPLLD Periodic Test Needed Alarm
0006=WPLLD Sensor Open Alarm
0007=WPLLD Communications Alarm
0008=WPLLD Shutdown Alarm
0009=WPLLD Continuous Handle On Warning
000A=WPLLD Annual Test Fail Alarm
000B=WPLLD Annual Test Needed Warning
000C=WPLLD Annual Test Needed Alarm
000D=WPLLD High Pressure Warning
000E=WPLLD High Pressure Alarm
000F=WPLLD Sensor Short Alarm
0010=WPLLD Continuous Handle On Alarm
0011=WPLLD Fuel Out Alarm
0012=WPLLD Line Equipment Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

(Obsolete V19)

(Obsolete V19)
(Obsolete V19)
(Obsolete V19)

137

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 387
Function Type: WPLLD Line Leak Alarm History Report

Version 10

Command Format:
Display: I387WW
Computer: i387WW
Typical Response Message, Display Format:

I387WW
JAN 24, 1996
STATION
STATION
STATION
STATION

2:52 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

WPLLD LINE LEAK ALARM HISTORY REPORT
W 1:REGULAR UNLEADED
GROSS LINE FAIL


JAN

9, 1995

6:12 AM

Typical Response Message, Computer Format:
i387WWYYMMDDHHmmWWNNyymmddhhmmaaaa...
WWNNyymmddhhmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
WW
NN
yymmddhhmm
aaaa

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
number of alarms to follow (Hex)
Date and time that the alarm occurred
type of alarm:
0001=WPLLD Setup Data Warning
0002=WPLLD Gross Test Fail Alarm
0003=WPLLD Periodic Test Fail Alarm
0004=WPLLD Periodic Test Needed Warning
0005=WPLLD Periodic Test Needed Alarm
0006=WPLLD Sensor Open Alarm
0007=WPLLD Communications Alarm
0008=WPLLD Shutdown Alarm
0009=WPLLD Continuous Handle On Warning
(Obsolete
000A=WPLLD Annual Test Fail Alarm
000B=WPLLD Annual Test Needed Warning
000C=WPLLD Annual Test Needed Alarm
000D=WPLLD High Pressure Warning
(Obsolete
000E=WPLLD High Pressure Alarm
(Obsolete
000F=WPLLD Sensor Short Alarm
(Obsolete
0010=WPLLD Continuous Handle On Alarm
0011=WPLLD Fuel Out Alarm
0012=WPLLD Line Equipment Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

V19)

V19)
V19)
V19)

138

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 388
Function Type: WPLLD Line Leak Test Results

Version 10

Command Format:
Display: I388WW
Computer: i388WW
Typical Response Message, Display Format:

I388WW
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:52 PM
1....
2....
3....
4....

WPLLD LINE LEAK TEST RESULTS
W 1:REGULAR UNLEADED
3.0 GAL/HR RESULTS:
LAST TEST:
JAN 24, 1996

2:12 PM PASS

NUMBER OF TESTS PASSED
PREV 24 HOURS :
75
SINCE MIDNIGHT :
39
0.20 GAL/HR RESULTS:
JAN 23, 1996 10:59 PM PASS
0.10 GAL/HR RESULTS:
JAN 21, 1996

3:27 AM PASS

NO-VENT TEST ABORTS:
3 OUT OF 10 TESTS


Part No. 576013-635, Revision AA

(Added in V19)
(Added in V19)

139

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 388 (Continued)
Typical Response Message, Computer Format:
i388WWYYMMDDHHmmWWyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt...
WWyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
WW
yymmddhhmm
rr
TT
PPPP

-

7.
8.

MMMM NN -

9.
10.

YYMMDDHHmm RR -

11.
12.

tt nn -

13.
14.

YYMMDDHHmm RR -

15.
16.
17.

tt && CCCC -

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Last 3.00 gal/hr test time
3.00 gal/hr test result (Hex)
3.00 gal/hr test type (unused, always 00)
Number of 3.00 gal/hr tests passed in previous 24 hours
(Hex)
Number of 3.00 gal/hr tests passed since midnight (Hex)
Number of 0.20 gal/hr test results (14 character groups) to
follow (Hex)
Date and time of test
Test result
01=PASS
02=FAIL
Test type (unused, always 00)
Number of 0.10 gal/hr test results (14 character groups) to
follow (Hex)
Date and time of test
Test result
01=PASS
02=FAIL
Test type (unused, always 00)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

140

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 389
Function Type: WPLLD Line Leak Test History
Notes:
1.

Version 12

While this command was implemented in Versions 10 & 11,
the format shown below was not correct until Version 12.
The format used in Versions 10 & 11 is shown in Command
I384, except that the WPLLD tests were 0.20 GPH instead
of 0.10 GPH.
Command Format:
Display: I389WW
Computer: i389WW

Typical Response Message, Display Format:

I389WW
JAN 24, 1996
STATION
STATION
STATION
STATION

2:52 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

WPLLD LINE LEAK TEST HISTORY
W 1:REGULAR UNLEADED
LAST

3.0 PASS:

JAN 24, 1996

2:12 PM

FIRST 0.20 PASS EACH MONTH:

JAN 15, 1996 11:38 PM

FIRST 0.10 PASS EACH MONTH:


JAN 12, 1996

1:21 AM

Typical Response Message, Computer Format:
i389WWYYMMDDHHmmWWyymmddhhmmTTNNYYMMDDHHmmtt...nnYYMMDDHHmmtt...
WWyymmddhhmmTTNNYYMMDDHHmmtt...nnYYMMDDHHmmtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
yymmddhhmm - Last 3.00 gal/hr test pass time ("0000000000" if no test
yet)
TT - 3.00 gal/hr test type (unused, always 00)
NN - Number of 0.20 gal/hr test results (12 character groups) to
follow (Hex)
YYMMDDHHmm - Date and time of 0.20 gal/hr test
tt - 0.20 gal/hr test type (unused, always 00)
nn - Number of 0.10 gal/hr test results (12 character groups) to
follow (Hex)
YYMMDDHHmm - Date and time of 0.10 gal/hr test
tt - 0.10 gal/hr test type (unused, always 00)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

141

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2.5 MISCELLANEOUS REPORTS
Function Code: 391
Function Type: Tanker Load Report

Version 10

Command Format:
Display: I391TT
Computer: i391TT
Typical Response Message, Display Format:

I391TT
JAN 9, 1995
STATION
STATION
STATION
STATION
TANK

10:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

1 REGULAR UNLEADED

NO START DATE/TIME
4 YY/MM/DD HH:mm
3 YY/MM/DD HH:mm
2 YY/MM/DD HH:mm
1 YY/MM/DD HH:mm


VOLUME
GGGGGG
GGGGGG
GGGGGG
GGGGGG

TEMP
TT.T
TT.T
TT.T
TT.T

END DATE/TIME
YY/MM/DD HH:mm
YY/MM/DD HH:mm
YY/MM/DD HH:mm
YY/MM/DD HH:mm

VOLUME
GGGGGG
GGGGGG
GGGGGG
GGGGGG

TEMP
TT.T
TT.T
TT.T
TT.T

TOTAL
GGGGGG
GGGGGG
GGGGGG
GGGGGG

Typical Response Message, Computer Format:
i391TTYYMMDDHHmmTTLLSSNNYYMMDDHHmmaaaaaaaabbbbbbbb
YYMMDDHHmmccccccccddddddddeeeeeeee...
TTLLSSNNYYMMDDHHmmaaaaaaaabbbbbbbb
YYMMDDHHmmccccccccddddddddeeeeeeee&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

YYMMDDHHmm
TT
LL
SS
NN
YYMMDDHHmm
aaaaaaaa
bbbbbbbb
YYMMDDHHmm
cccccccc
dddddddd
eeeeeeee
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Total Loads for tank (Decimal, no data to follow if 00)
Load Sequence Number (Decimal)
Number of data items to follow (Hex)
Starting Date/Time
Starting Volume (ASCII Hex IEEE float)
Starting Temperature (ASCII Hex IEEE float)
Ending Date/Time
Ending Volume (ASCII Hex IEEE float)
Ending Temperature (ASCII Hex IEEE float)
Total (start volume - end volume) (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

142

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 392
Function Type: Tanker Load Report II

Version 26

Command Format:
Display: I392TT
Computer: i392TT
Typical Response Message, Display Format:

I392TT
JAN 9, 1995
STATION
STATION
STATION
STATION
TANK
NO
4

10:02 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

1 REGULAR UNLEADED

START:
END:
TOTAL:
3 START:
END:
TOTAL:
2 START:
END:
TOTAL:
1 START:
END:
TOTAL:


DATE/TIME
VOLUME
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG
YY/MM/DD HH:mm GGGGGG

Part No. 576013-635, Revision AA

TEMP
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T
TT.T

TC VOLUME
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG
GGGGGG

143

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 392 Notes: (Continued)
Typical Response Message, Computer Format:
i392TTYYMMDDHHmmTTLLSSNNYYMMDDHHmmYYMMDDHHmmnnaaaaaaaabbbbbbbbcccccccc
ddddddddeeeeeeeeffffffffgggggggghhhhhhhh...
TTLLSSNNYYMMDDHHmmYYMMDDHHmmnnaaaaaaaabbbbbbbbcccccccc
ddddddddeeeeeeeeffffffffgggggggghhhhhhhh&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
LL - Total Loads for tank (Decimal, no data to follow if 00)
4.
SS - Load Sequence Number (Decimal)
5.
NN - Number of 10 byte Date/Times to follow (Hex)
6.
YYMMDDHHmm - Starting Date/Time
7.
YYMMDDHHmm - Ending Date/Time
8.
nn - Number of 8 byte data items to follow (Hex)
9.
aaaaaaaa - Starting Volume (ASCII Hex IEEE float)
10.
bbbbbbbb - Starting Temperature (ASCII Hex IEEE float)
11.
cccccccc - Ending Volume (ASCII Hex IEEE float)
12.
dddddddd - Ending Temperature (ASCII Hex IEEE float)
13.
eeeeeeee - Total Volume (start volume - end volume) (ASCII Hex IEEE
float)
14.
ffffffff - Starting TC Volume (ASCII Hex IEEE float)
15.
gggggggg - Ending TC Volume (ASCII Hex IEEE float)
16.
hhhhhhhh - Total TC Volume (start TC volume - end TC volume) (ASCII Hex
IEEE float)
17.
&& - Data Termination Flag
18.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

144

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.2.6 I/O DEVICE REPORTS
Function Code: 401
Function Type: Input Status Report

Version 1

Command Format:
Display: I401II
Computer: i401II
Typical Response Message, Display Format:

I401II
MAR 27, 1996

5:44 PM

STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

INPUT
1


LOCATION
* EXTERNAL INPUT 1 *

STATUS
OFF

Typical Response Message, Computer Format:
i401IIYYMMDDHHmmIIssss...
IIssss&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
II - Input Number (Decimal, 00=all)
ssss - Input Status:
0001=Input Setup Data Warning
0002=Input Normal
0003=Input Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

145

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 402
Function Type: Input Alarm History Report

Version 1

Command Format:
Display: I402II
Computer: i402II
Typical Response Message, Display Format:

I402II
MAR 27, 1996

5:45 PM

STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

INPUT
1

LOCATION
* EXTERNAL INPUT 1 *
JAN 15, 1996 8:04 AM

SETUP DATA WARNING


Typical Response Message, Computer Format:
i402IIYYMMDDHHmmIINNYYMMDDHHmmaaaa...
IINNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
II
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Input Number (Decimal, 00=all)
Number of Alarm Incidents to follow (Hex)
Date and Time of alarm
Alarm type number:
0001=Input Setup Data Warning
0002=Input Normal
0003=Input Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

146

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 403
Version 5
Function Type: Input/Generator Alarm History Report
(Setup parameters determine whether an input is from a
generator.)
Command Format:
Display: I403II
Computer: i403II
Typical Response Message, Display Format:

I403II
MAR 27, 1996
STATION
STATION
STATION
STATION

5:47 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

INPUT / GENERATOR ALARM HISTORY REPORT
INPUT
1

LOCATION
* EXTERNAL INPUT 1 *
AUG 19, 1995
2:03 PM
AUG 20, 1995
6:15 AM

EXTERN INPUT ALARM
EXTERN INPUT ALARM


Typical Response Message, Computer Format:
i403IIYYMMDDHHmmIINNYYMMDDHHmmaaaa...
IINNYYMMDDHHmmaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
II
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
Input Number (Decimal, 00=all)
Number of Alarm Incidents to follow (Hex)
Date and Time of alarm
Alarm type number:
0001=Input Setup Data Warning
0002=Input Normal
0003=Input Alarm
0004=Generator Off
0005=Generator On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

147

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 404
Version 31
Function Type: Input Generator Report
(Setup parameters determine whether an input is from a
generator.)
Command Format:
Display: I404TT
Computer: i404TT
Typical Response Message, Display Format:

I40400
MAR 27, 2010
STATION
STATION
STATION
STATION

5:47 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

INPUT GENERATOR REPORT
START
DATE / TIME
12-20-10 12:59
12-21-10 12:59


END
DATE / TIME
12-20-10 19:06
12-21-10 19:06

START
LITERS
350000
350000

END
LITERS
349745
349745

DURATION
HHHH:MM
0006:06
0006:06

CONSUMPTION
LITERS
L/HR
200
33.33
200
33.33

Typical Response Message, Computer Format:
i40400YYMMDDHHmmTTNNYYMMDDHHmmYYMMDDHHmmnnFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm
TT
NN
YYMMDDHHmm
YYMMDDHHmm
nn
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of Records to follow (Hex)
Start Time
End Time
Number of 8 character data fields to follow (Hex)
Alarm type number:
1=Start Height
2=Start Volume
3=Start TC Volume
4=Start Water
5=Start Temperature
6=End Height
7=End Volume
8=End TC Volume
9=End Water
10=End Temperature
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

148

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 406
Function Type: Relay Status Report

Version 1

Command Format:
Display: I406RR
Computer: i406RR
Typical Response Message, Display Format:

I406RR
MAR 27, 1996

5:47 PM

STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

RELAY
1


LOCATION
* RELAY 1

*

STATUS
OPEN

Typical Response Message, Computer Format:
i406RRYYMMDDHHmmRRssss...
RRssss&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
RR - Relay Number (Decimal, 00=all)
3.
ssss - Relay Status:
0001=Relay Open
0002=Relay Closed
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

149

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 411
Function Type: VMCI Alarm History Report

Version 28

Command Format:
Display: I411xx
Computer: i411xx
Typical Response Message, Display Format:

I41100
JAN 22, 2007

3:11 PM

VMCI ALARM HISTORY REPORT
DEVICE
1

ALARMS
JAN 1, 2007
JAN 20, 2007

8:02 AM
12:00 PM

SETUP DATA WARNING
DISABLED ALARM


Typical Response Message, Computer Format:
i411xxYYMMDDHHmmxxNNYYMMDDHHmmaaaa...
xxNNYYMMDDHHmmaaaa...&&&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
xx
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
VMCI Board Number (Decimal, 01-06, 00=all)
Number of alarm Incidents to follow (ASCII Hex)
Date and Time of Alarm
Alarm Type number (ASCII hex):
0001 = Setup Data Warning:
More than 1 board installed
0002 = Disabled VMCI Board
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

150

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 412
Function Type: VMC Alarm History Report

Version 28

Command Format:
Display: I412xx
Computer: i412xx
Typical Response Message, Display Format:

I41200
JAN 22, 2007

3:11 PM

VMC ALARM HISTORY REPORT
VMC
1

S/N
111111

2
222222


ALARMS
JAN 1,
JAN 10,
JAN 20,
JAN 1,

2007
2007
2007
2007

8:02
12:00
12:00
8:02

AM
PM
PM
AM

METER NOT CONNECTED
FP SHUTDOWN WARNING
FP SHUTDOWN ALARM
VMC COMM TIMEOUT

Typical Response Message, Computer Format:
i412xxYYMMDDHHmmxxNNYYMMDDHHmmaaaa...
xxNNYYMMDDHHmmaaaa...&&&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
xx
NN
YYMMDDHHmm
aaaa

-

Current Date and Time
VMC Controller Number (Decimal, 01-18, 00=all)
Number of alarm Incidents to follow (ASCII Hex)
Date and Time of Alarm
Alarm Type number (ASCII hex):
0001 = VMC Communication Timeout Alarm
0002 = Roots meter not connected Alarm
0003 = Fueling Point Shutdown Warning
0004 = Fueling Point Shutdown Alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

151

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3 SETUP FUNCTIONS & REPORTS
7.3.1 SYSTEM SETUP
Function Code: 501
Function Type: Set Time of day
Command Format:
Display: S50100YYMMDDHHmm
Computer: s50100YYMMDDHHmm

Version 1
Inquire:
I50100
i50100

Typical Response Message, Display Format:

I50100
JAN 22, 1996

3:11 PM

SYSTEM DATE AND TIME

Typical Response Message, Computer Format:
i50100YYMMDDHHmmYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
YYMMDDHHmm
&&
CCCC

-

Current Date and Time
Year, Month, Day, Hour and Minute
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

152

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 502
Function Type: Set Shift Start Time 1, 2, 3, 4
Command Format:
Display: S502SSHHmm
Computer: s502SSHHmm
Notes:
1.

Version 1
Inquire:
I502SS
i502SS

SS - Shift Start time (01, 02, 03, 04)

Typical Response Message, Display Format:

I50201
JAN 22, 1996

3:12 PM

SHIFT TIME 1 : DISABLED

Typical Response Message, Computer Format:
i502SSYYMMDDHHmmHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
HHmm
&&
CCCC

-

Current Date and Time
Hour and Minute (EE00=Disabled)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

153

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 503
Function Type: Set Print Header Line 1, 2, 3, 4
Command Format:
Display: S503LLaaaaaaaaaaaaaaaaaaaa
Computer: s503LLaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I503LL
i503LL

Typical Response Message, Display Format:

I503LL
JAN 22, 1996

3:12 PM

# 1:STATION HEADER 1....

Typical Response Message, Computer Format:
i503LLYYMMDDHHmmaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
LL
a
&&
CCCC

-

Current Date and Time
Header line number 1, 2, 3, 4
Header Line (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

154

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 504
Function Type: Set System RS-232 Security Code
Command Format:
Display: S50400aaaaaa
Computer: s50400aaaaaa

Version 1
Inquire:
I50400
i50400

Typical Response Message, Display Format:

I50400
JAN 22, 1996

3:12 PM

SYSTEM SECURITY CODE
CODE : 000000

Typical Response Message, Computer Format:
i50400YYMMDDHHmmaaaaaa&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
aaaaaa
&&
CCCC

-

Current Date and Time
Security Code (6 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

155

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 505
Function Type: Set System Type & Language Flags
Command Format:
Display: S50500UL
Computer: s50500UL

Version 1
Inquire:
I50500
i50500

Typical Response Message, Display Format:

I50500
JAN 22, 1996

3:12 PM

SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM

Typical Response Message, Computer Format:
i50500YYMMDDHHmmUL&&CCCC
Notes:
1.
2.
3.

4.

5.
6.

For all languages beyond Finnish (L=9), use command S51700.
YYMMDDHHmm - Current Date and Time
U - System Units:
1=U.S
2=Metric
3=Imperial Gallons
L - System Language:
1=English
2=French
3=Spanish
4=German
5=Portuguese
6=Polish
7=Swedish
8=Japanese
9=Finnish
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

156

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 506
Function Type: Set Periodic Test Needed Warning
Command Format:
Display: S50600f
Computer: s50600f

Version 2
Inquire:
I50600
i50600

Typical Response Message, Display Format:

I50600
JAN 22, 1996

3:12 PM

PERIODIC TEST WARNINGS: DISABLED

Typical Response Message, Computer Format:
i50600YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Periodic Test Needed Warnings Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

157

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 507
Function Type: Set Days Before Periodic Test Needed Warning
Command Format:
Display: S50700dd
Computer: s50700dd

Version 4
Inquire:
I50700
i50700

Typical Response Message, Display Format:

I50700
JAN 22, 1996

3:12 PM

PERIODIC TEST WARNING: DAYS= 25

Typical Response Message, Computer Format:
i50700YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Periodic Test Needed Warning
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

158

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 508
Function Type: Set Days Before Periodic Test Needed Alarm
Command Format:
Display: S50800dd
Computer: s50800dd

Version 4
Inquire:
I50800
i50800

Typical Response Message, Display Format:

I50800
JAN 22, 1996

3:12 PM

PERIODIC TEST ALARM: DAYS= 30

Typical Response Message, Computer Format:
i50800YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Periodic Test Needed Alarm
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

159

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 509
Function Type: Set Annual Test Needed Warning
Command Format:
Display: S50900f
Computer: s50900f

Version 4
Inquire:
I50900
i50900

Typical Response Message, Display Format:

I50900
JAN 22, 1996

3:12 PM

ANNUAL TEST WARNINGS: DISABLED

Typical Response Message, Computer Format:
i50900YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Annual Test Needed Warnings Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

160

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50A
Function Type: Set Days Before Annual Test Needed Warning
Command Format:
Display: S50A00ddd
Computer: s50A00ddd

Version 4
Inquire:
I50A00
i50A00

Typical Response Message, Display Format:

I50A00
JAN 22, 1996

3:12 PM

ANNUAL TEST WARNING: DAYS=355

Typical Response Message, Computer Format:
i50A00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before Annual Test Needed Warning
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

161

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50B
Function Type: Set Days Before Annual Test Needed Alarm
Command Format:
Display: S50B00ddd
Computer: s50B00ddd

Version 4
Inquire:
I50B00
i50B00

Typical Response Message, Display Format:

I50B00
JAN 22, 1996

3:12 PM

ANNUAL TEST ALARM: DAYS=365

Typical Response Message, Computer Format:
i50B00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before Annual Test Needed Alarm
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

162

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50C
Function Type: Set Remote Printer Page Eject Flag
Command Format:
Display: S50C00f
Computer: s50C00f

Version 5
Inquire:
I50C00
i50C00

Typical Response Message, Display Format:

I50C00
JAN 22, 1996

3:13 PM

REMOTE PRINTER
DISABLED

Typical Response Message, Computer Format:
i50C00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Page Eject Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

163

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50D
Function Type: Set Print Temperature Compensation Flag
Command Format:
Display: S50D00f
Computer: s50D00f

Version 8
Inquire:
I50D00
i50D00

Typical Response Message, Display Format:

I50D00
JAN 22, 1996

3:13 PM

PRINT TC VOLUMES
ENABLED

Typical Response Message, Computer Format:
i50D00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Print Temperature Compensation Flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

164

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50E
Function Type: Set Temperature Compensation Value
Command Format:
Display: S50E00DDD.hh
Computer: s50E00FFFFFFFF
Notes:
1.
2.

Version 8
Inquire:
I50E00
i50E00

DDD.hh - Compensation Temperature, Degrees and hundredths (Decimal)
FFFFFFFF - Compensation Temperature, Degrees (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I50E00
JAN 22, 1996

3:13 PM

TEMP COMPENSATION
VALUE (DEG F ):
60.0

Typical Response Message, Computer Format:
i50E00YYMMDDHHmmFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
FFFFFFFF
&&
CCCC

-

Current Date and Time
Compensation Temperature, Degrees (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

165

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 50F
Function Type: Set System Date/Time Display Format

Version 10

Command Format:
Display: S50F00xx
Computer: s50F00xx

Inquire:
I50F00
i50F00

Typical Response Message, Display Format:

I50F00
JAN 22, 1996

3:13 PM

MON DD YYYY HH:MM:SS xM

Typical Response Message, Computer Format:
i50F00YYMMDDHHMMxx&&CCCC
Notes:
1.
2.

3.
4.

YYMMDDHHmm - Current Date and Time
xx - Display format for DATE/TIME code
01 - MON DD, YYYY HH:MM:SS xM (12
02 - MON DD YYYY HH:MM:SS
(24
03 - MM-DD-YY HH:MM:SS xM
(12
04 - MM-DD-YY HH:MM:SS
(24
05 - DD-MM-YY HH:MM:SS
(24
06 - YY-MM-DD HH:MM:SS
(24
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

Hour
Hour
Hour
Hour
Hour
Hour

Clock)
Clock)
Clock)
Clock)
Clock)
Clock)

166

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 511
Function Type: Set BIR Shift Printouts Flag
Command Format:
Display: S51100f
Computer: s51100f

Version 110
Inquire:
I51100
i51100

Typical Response Message, Display Format:

I51100
JAN 22, 1996

3:13 PM

SHIFT BIR PRINTOUTS
ENABLED

Typical Response Message, Computer Format:
i51100YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Shift Printouts flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

167

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 512
Function Type: Set BIR Daily Printouts Flag
Command Format:
Display: S51200f
Computer: s51200f

Version 110
Inquire:
I51200
i51200

Typical Response Message, Display Format:

I51200
JAN 22, 1996

3:13 PM

DAILY BIR PRINTOUTS
ENABLED

Typical Response Message, Computer Format:
i51200YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Daily Printouts flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

168

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 513
Function Type: Set Tanker Load Report Flag
Command Format:
Display: S51300f
Computer: s51300f

Version 10
Inquire:
I51300
i51300

Typical Response Message, Display Format:

I51300
JAN 22, 1996

3:14 PM

TANKER LOAD REPORT
ENABLED

Typical Response Message, Computer Format:
i51300YYMMDDHHmmf&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Tanker Load Report Flag:
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

169

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 514
Function Type: Set H-Protocol Height/Volume format
Command Format:
Display: S51400f
Computer: s51400f

Version 10
Inquire:
I51400
i51400

Typical Response Message, Display Format:

I51400
JAN 24, 1996

2:53 PM

H-PROTOCOL DATA FORMAT
HEIGHT

Typical Response Message, Computer Format:
i51400YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Data Format
0=Height
1=Volume
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

170

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 515
Function Type: Set HRM - QPLD Monthly Printout
Command Format:
Display: S51500x
Computer: s51500x

Version 110
Inquire:
I51500
i51500

Typical Response Message, Display Format:

I51500
JAN 24, 1996

2:53 PM

QPLD MONTHLY PRINTOUT
ENABLED

Typical Response Message, Computer Format:
i51500YYMMDDHHmmx&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
x - QPLD Monthly Report:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

171

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 516
Function Type: Set Re-direct Local Printout Flag
Command Format:
Display: S51600x
Computer: s51600x

Version 14
Inquire:
I51600
i51600

Typical Response Message, Display Format:

I51600
OCT 15, 1996

4:29 PM

RE-DIRECT LOCAL PRINTOUT
ENABLED

Typical Response Message, Computer Format:
i51600YYMMDDHHmmx&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
x - Re-direct Local Printout:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

172

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 517
Function Type: Set System Type & Language Flags
Command Format:
Display: S51700ULL
Computer: s51700ULL

Version 15
Inquire:
I51700
i51700

Typical Response Message, Display Format:

I51700
JUL 29, 1997

9:03 AM

SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM

Typical Response Message, Computer Format:
i51700YYMMDDHHmmULL&&CCCC
Notes:
1.
2.

3.

4.
5.

YYMMDDHHmm - Current Date and Time
U - System Units:
1=U.S.
2=Metric
3=Imperial Gallons
LL - System Language:
01=English
02=French
03=Spanish
04=German
05=Portuguese
06=Polish
07=Swedish
08=Japanese
09=Finnish
10=Greek
11=Russian
12=Turkish
13=Dutch
14=Italian
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

173

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 518
Function Type: Set Secondary Language Code Page Output
Command Format:
Display: S51800PP
Computer: s51800PP

Version 15
Inquire:
I51800
i51800

Typical Response Message, Display Format:

I51800
JUL 29, 1997 9:04 AM
ALTERNATE LANGUAGE CODE PAGE
CODE PAGE SELECTED:
WINDOWS

Typical Response Message, Computer Format:
i51800YYMMDDHHmmPP&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
PP - Code Page selected
00=Windows
01=DOS
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

174

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 519
Version 15
Function Type: Set PLLD & WPLLD Duration Before Precision Retest
Command Format:
Display: S51900DDD
Computer: s51900DDD

Inquire:
I51900
i51900

Typical Response Message, Display Format:

I51900
JUL 29, 1997

9:04 AM

PRECISION TEST DURATION
HOURS: 12

Typical Response Message, Computer Format:
i51900YYMMDDHHmmDDD&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
DDD
&&
CCCC

-

Current Date and Time
Retest Duration in hours (Decimal, 012-744)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

175

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 51A
Function Type: Set Enable/Disable Auto Daylight Saving Time
Command Format:
Display: S51A00f
Computer: s51A00f

Version 15
Inquire:
I51A00
i51A00

Typical Response Message, Display Format:

I51A00
JUL 29, 1997

9:04 AM

DAYLIGHT SAVING TIME
ENABLED ON

Typical Response Message, Computer Format:
i51A00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Daylight Saving Time Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

176

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 51B
Function Type: Set Start/End Daylight Saving Date and Time
Command Format:
Display: S51BttMMWDHHmm
Computer: s51BttMMWDHHmm
Notes:
1.
2.
3.

Version 15
Inquire:
I51Btt
i51Btt

YYMMDDHHmm - Current Date and Time
tt - Start or End Time Indicator
01=Start Date & Time
02=End Date & Time
MMWDHHmm - Date & Time
MM=Month (01-12)
W=Week of Month (1-6)
D=Day of Week (1=Monday, 2=Tuesday, .. 7=Sunday)
HH=Hour (00-23)
mm=Minute (00-59)

Typical Response Message, Display Format:

I51B00
JUL 29, 1997 9:04 AM
DAYLIGHT SAVING TIME
START DATE
END DATE


APR
OCT

WEEK 1
WEEK 4

SUN
SUN

2:00 AM
2:00 AM

Typical Response Message, Computer Format:
i51BttYYMMDDHHmmMMWDHHmm&&CCCC
Notes:
1.
2.

3.

4.
5.

YYMMDDHHmm - Current Date and Time
tt - Start or End Time Indicator
00=in computer format returns only Start Date & Time
01=Start Date & Time
02=End Date & Time
MMWDHHmm - Date & Time
MM=Month (01-12)
W=Week of Month (1-6)
D=Day of Week (1=Monday, 2=Tuesday, .. 7=Sunday)
HH=Hour (00-23)
mm=Minute (00-59)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

177

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 51C
Function Type: Set Ticketed Delivery Flag Enable
Command Format:
Display: S51C00f
Computer: s51C00f

Version 116
Inquire:
I51C00
i51C00

Typical Response Message, Display Format:

I51C00
MAR 20, 1998

3:27 PM

TICKETED DELIVERY
ENABLED

Typical Response Message, Computer Format:
i51C00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Ticketed Delivery flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

178

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 51D
Version 116
Function Type: Set Ticketed Delivery Temperature Compensation Flag
Command Format:
Display: S51D00f
Computer: s51D00f

Inquire:
I51D00
i51D00

Typical Response Message, Display Format:

I51D00
MAR 20, 1998

3:27 PM

TICKETED DELIVERY TEMP COMPENSATION
STANDARD

Typical Response Message, Computer Format:
i51D00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Ticketed Delivery Temperature Compensation flag
0=Standard
1=Temperature compensated
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

179

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 51E
Function Type: Set Ticketed Delivery Close Day of Week
Command Format:
Display: S51E00D
Computer: s51E00D

Version 116
Inquire:
I51E00
i51E00

Typical Response Message, Display Format:

I51E00
MAR 20, 1998

3:28 PM

CLOSE DAY OF WEEK
SUN

Typical Response Message, Computer Format:
i51E00YYMMDDHHmmD&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
D
&&
CCCC

-

Current Date and Time
Day of Week (1=Monday, 2=Tuesday, .. 7=Sunday)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

180

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.2 COMMUNICATIONS SETUP
Function Code: 520
Function Type: Set Receiver Auto Dial Type and Start Time II
Command Format:
Display: S520RRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
f
Computer: s520RRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
f

(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6) Reserved
M=7) Reserved
M=8)

(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6) Reserved
M=7) Reserved
M=8)

Version 20
Inquire:
I520RR

i520RR

Typical Response Message, Display Format:

I520RR
JUN 1, 2000

8:02 AM

RECEIVER AUTO DIAL TYPE & START TIME
RCVR
1
2
3
4
5
6
7
8


LOCATION LABEL
TLS LAB R1
TLS LAB R2
FINANCE R3
FINANCE R4
TCH SUP R5
TCH SUP R6
ENG/MKT R7
ENG/MKT R8

Part No. 576013-635, Revision AA

DIAL TYPE
DAILY
DAILY
DAILY
DAILY
DAILY
DAILY
DAILY
DAILY

START
4:00
4:30
5:00
5:30
6:00
6:30
7:00
7:30

TIME
PM
PM
PM
PM
PM
PM
PM
PM

181

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 520: (Continued)
Typical Response Message, Computer Format:
i520RRYYMMDDHHmmRRNNMYYMMDDHHmm...
MMWDHHmm...
WDHHmm...
DHHmm...
HHmm...
f...
RRNNMYYMMDDHHmm&&CCCC
MMWDHHmm&&CCCC
WDHHmm&&CCCC
DHHmm&&CCCC
HHmm&&CCCC
f&&CCCC
Notes:
1.
2.
3.
4.

5.

YYMMDDHHmm
RR
NN
M

-

(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6) Reserved
M=7) Reserved
M=8)

(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6) Reserved
M=7) Reserved
M=8)

Current Date and Time
Receiver Number (Decimal, 00=all)
Number of Data Fields to follow (Hex)
Auto Dial Method (frequency):
1=On Date
2=Annually
3=Monthly
4=Weekly
5=Daily
8=BIR End (V20 - BIR only)

- If M=1 ON DATE, NNMYYMMDDHHmm:
NN =0B - Number of characters to follow (Hex)
M
=1 - ON DATE
YY =Year
MM =Month (01-12)
DD =Day
HHmm=Hour, Minute (EE00=Disabled)
- If M=2 ANNUALLY, NNMMMWDHHmm:
NN =09 - Number of characters to follow (Hex)
M
=2 - ANNUALLY
MM =Month (01-12)
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)

Part No. 576013-635, Revision AA

182

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 520 Notes: (Continued)
- If M=3 MONTHLY, NNMWDHHmm:
NN =07 - Number of characters to follow (Hex)
M
=3 - MONTHLY
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=4 WEEKLY, NNMDHHmm:
NN =06 - Number of characters to follow (Hex)
M
=4 - WEEKLY
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=5 DAILY, NNMHHmm:
NN =05 - Number of characters to follow (Hex)
M
=5 - DAILY
HHmm=Hour, Minute (EE00=Disabled)
- If M=8
NN
M
f

6.
7.

BIR END, NNMf:
=02 - Number of characters to follow (Hex)
=8 - BIR END
=BIR Period End Enable Flag
0=Disabled
1=Auto Daily Closing

&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

183

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 521
Function Type: Set Receiver Configuration Flag
Command Format:
Display: S521RRf
Computer: s521RRf

Version 2
Inquire:
I521RR
i521RR

Typical Response Message, Display Format:

S521RR
MAR 29, 1996

6:27 PM

RECEIVER CONFIGURATION
DEVICE
1


LABEL
HOME OFFICE

CONFIGURED
ON

Typical Response Message, Computer Format:
i521RRYYMMDDHHmmRRf...
RRf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
RR - Receiver Number (Decimal)
f - Receiver Configuration Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

184

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 522
Function Type: Set Receiver Location Label
Command Format:
Display: S522RRaaaaaaaaaaaaaaaaaaaa
Computer: s522RRaaaaaaaaaaaaaaaaaaaa

Version 2
Inquire:
I522RR
i522RR

Typical Response Message, Display Format:

I522RR
JAN 22, 1996

3:14 PM

RECEIVER LABEL
DEVICE
1


LABEL
aaaaaaaaaaaaaaaaaaaa

Typical Response Message, Computer Format:
i522RRYYMMDDHHmmRRaaaaaaaaaaaaaaaaaaaa...
RRaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
a
&&
CCCC

-

Current Date and Time
Receiver Number (Decimal)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

185

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 523
Function Type: Set Receiver Telephone Number
Command Format:
Display: S523RRaaaaaaaaaaaaaaaaaaaa
Computer: s523RRaaaaaaaaaaaaaaaaaaaa

Version 2
Inquire:
I523RR
i523RR

Typical Response Message, Display Format:

I523RR
JAN 22, 1996

3:14 PM

RECEIVER TELEPHONE NUMBER
RCVR
1


LOCATION LABEL
HOME OFFICE

PHONE NUMBER
aaaaaaaaaaaaaaaaaaaa

Typical Response Message, Computer Format:
i523RRYYMMDDHHmmRRaaaaaaaaaaaaaaaaaaaa...
RRaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
a
&&
CCCC

-

Current Date and Time
Receiver Number (Decimal)
Phone Number (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

186

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 524
Function Type: Set Receiver Dialing Destination Type
Command Format:
Display: S524RRTT
Computer: s524RRTT

Version 2
Inquire:
I524RR
i524RR

Typical Response Message, Display Format:

I524RR
JAN 22, 1996

3:15 PM

RECEIVER DIALING DESTINATION TYPE
RCVR
1


LOCATION LABEL
HOME OFFICE

FAX TYPE
FACSIMILE

Typical Response Message, Computer Format:
i524RRYYMMDDHHmmRRTT...
RRTT&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
RR - Receiver Number (Decimal)
TT - Dialing Destination Type:
01=Teletype
02=Facsimile
03=Computer
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

187

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 525
Function Type: Set Receiver Port Number to Dial
Command Format:
Display: S525RRn
Computer: s525RRn

Version 2
Inquire:
I525RR
i525RR

Typical Response Message, Display Format:

I525RR
JUL 29, 1997

9:05 AM

RECEIVER MODEM NUMBER TO DIAL
RCVR
1


LOCATION LABEL
HOME OFFICE

PORT NUMBER
1

Typical Response Message, Computer Format:
i525RRYYMMDDHHmmRRn...
RRn&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
n
&&
CCCC

-

Current Date and Time
Receiver Number (Decimal)
Port Number (max 3, or 6 in Version 1xx)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

188

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 526
Function Type: Set Receiver Retry Number
Command Format:
Display: S526RRnn
Computer: s526RRnn

Version 2
Inquire:
I526RR
i526RR

Typical Response Message, Display Format:

I526RR
JUL 29, 1997

9:05 AM

RECEIVER RETRY NUMBER
RCVR
1


LOCATION LABEL
HOME OFFICE

RETRY NUMBER
3

Typical Response Message, Computer Format:
i526RRYYMMDDHHmmRRnn...
RRnn&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
nn
&&
CCCC

-

Current Date and Time
Receiver Number (Decimal)
Retry Number (03 through 99)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

189

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 527
Function Type: Set Receiver Retry Delay Time
Command Format:
Display: S527RRnn
Computer: s527RRnn

Version 2
Inquire:
I527RR
i527RR

Typical Response Message, Display Format:

I527RR
JUL 29, 1997

9:06 AM

RECEIVER RETRY DELAY TIME
RCVR
1


LOCATION LABEL
HOME OFFICE

RETRY DELAY
3

Typical Response Message, Computer Format:
i527RRYYMMDDHHmmRRnn...
RRnn&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
nn
&&
CCCC

-

Current Date and Time
Receiver Number (Decimal)
Retry Delay Time (00 to 60 minutes)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

190

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 528
Function Type: Set Receiver Confirmation Report Flag
Command Format:
Display: S528RRf
Computer: s528RRf

Version 2
Inquire:
I528RR
i528RR

Typical Response Message, Display Format:

I528RR
JAN 22, 1996

3:15 PM

RECEIVER CONFIRMATION REPORT FLAG
RCVR
1


LOCATION LABEL
HOME OFFICE

CONFIRMATION REPORT
OFF

Typical Response Message, Computer Format:
i528RRYYMMDDHHmmRRf...
RRf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
RR - Receiver Number (Decimal)
f - Confirmation Report Flag:
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

191

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 529
Function Type: Set Fax Auto Dial Method
Command Format:
Display: S52900f
Computer: s52900f

Version 19
Inquire:
I52900
i52900

Typical Response Message, Display Format:

I52900
MAY 05, 1999 1:54 PM
ALL PHONES

Typical Response Message, Computer Format:
i52900YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Fax Auto Dial Method
0=ALL PHONES
1=SINGLE PHONE
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

192

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52A
Function Type: Set Receiver Report List
Command Format:
Display: S52ARRNNRRss
Computer: s52ARRNNRRss

Version 3
Inquire:
I52ARR
i52ARR

Typical Response Message, Display Format:

I52ARR
JUL 29, 1997

9:06 AM

RECEIVER REPORT LIST
RCVR
1

LOCATION LABEL
HOME OFFICE

REPORT LIST
SYSTEM STATUS
IN-TANK STATUS
INVENTORY
PERIODIC DLVY VAR
PERIODIC BOOK VAR
DAILY VAR ANALY


Typical Response Message, Computer Format:
i52ARRYYMMDDHHmmRRNNrrss...
RRNNrrss&&CCCC
Notes:
1.
2.
3.
4.

5.
6.
7.

YYMMDDHHmm
RR
NN
rr

-

Current Date and Time
Receiver Number (Decimal)
Total Number of Reports to Follow (Decimal)
Report Number:
01=System Status
02=Priority Alarm History
03=Non-Priority Alarm History
05=In-Tank Status
06=In-Tank Inventory
07=In-Tank Delivery
08=In-Tank Leak Test
09=Shift Report
10=PLLD Results
11=WPLLD Results
12=Volumetric Line Leak Status
13=Periodic Row Report
14=Fuel Management Report
15=CSLD Results
16=Most Recent Delivery Report
17=Current Periodic Delivery Variance Report(Added in V19)
18=Current Periodic Book Variance Report
(Added in V19)
19=Daily Variance Analysis Report
(Added in V19)
ss - Report Status
01=ON
00=OFF
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

193

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52B
Function Type: Set Receiver Auto Dial Type and Start Time
Command Format:
Display: S52BRRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
Computer: s52BRRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm

(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=1)
M=2)
M=3)
M=4)
M=5)

Version 3
Inquire:
I52BRR

i52BRR

Typical Response Message, Display Format:

I52BRR
JAN 22, 1996

3:15 PM

RECEIVER AUTO DIAL TYPE & START TIME
RCVR
1


LOCATION LABEL
HOME OFFICE

DIAL TYPE
DAILY

START TIME
4:15 AM

Typical Response Message, Computer Format:
i52BRRYYMMDDHHmmRRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
RRMYYMMDDHHmm&&CCCC
MMWDHHmm&&CCCC
WDHHmm&&CCCC
DHHmm&&CCCC
HHmm&&CCCC
Notes:
1.
2.

(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=1)
M=2)
M=3)
M=4)
M=5)

YYMMDDHHmm - Current Date and Time
RR - Receiver Number (Decimal, 00=all)

Part No. 576013-635, Revision AA

194

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 52B Notes: (Continued)
3.

M - Auto Dial Method:
1=On Date
2=Annually
3=Monthly
4=Weekly
5=Daily
- If M=1 ON DATE, YYMMDDHHmm:
YY =Year
MM =Month (01-12)
DD =Day
HHmm=Hour, Minute (EE00=Disabled)
- If M=2 ANNUALLY, MMWDHHmm:
MM =Month (01-12)
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=3 MONTHLY, WDHHmm:
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=4 WEEKLY, DHHmm:
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=5 DAILY, HHmm:
HHmm=Hour, Minute (EE00=Disabled)

4.
5.

&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

195

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52C
Function Type: Set Receiver Auto Dial On Alarms
Command Format:
Display: S52CRRAANNTTSS
Computer: s52CRRAANNTTSS

Version 3
Inquire:
I52CRR
i52CRR

Typical Response Message, Display Format:

I52CRR
JAN 22, 1996

3:15 PM

RECEIVER SETUP REPORT
D 1: HOME OFFICE
- NO ALARM ASSIGNMENTS 
Typical Response Message, Computer Format:
i52CRRYYMMDDHHmmRRnnAANNTTSS...
RRnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
RR
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Receiver Number (Decimal)
Number of Alarms to Follow (Hex)
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status (Hex):
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

196

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52D
Function Type: Autodial Alarm Status
Command Format:
Display: S52DRRf
Computer: s52DRRf
Notes:
1.
2.

Version 17
Inquire:
I52DRR
i52DRR

RR - Receiver number (00=all)
f - Alarm clear flag
1=clear; all others ignored

Typical Response Message Display Format:

I52DRR
JAN 1, 1996

8:06 AM

RECEIVER AUTODIAL ALARM STATUS
RCVR
STATUS
1
CLEAR
Typical Response Message, Computer Format:
i52D00YYMMDDHHmmNNf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
NN - Number of receiver alarm flags to follow
f - Alarm flags
0=clear
1=alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

197

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52E
Function Type: Set Delay for Autodial on Alarm Clear
Command Format:
Display: S52ERRhh
Computer: s52ERRhh

Version 19
Inquire:
I52ERR
i52ERR

Typical Response Message, Display Format:

I52ERR
JAN 28, 1996 10:09 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

RECEIVER CLEARED ALARMS REPORT DELAY PERIOD
RCVR
1
2
3
4


LOCATION LABEL
Main Office D- 1
Finance D- 2
Home Office D- 3
Service D- 4

DELAY PERIOD
1
3
8
3

Typical Response Message, Computer Format:
i52ERRYYMMDDHHmmRRhh...
RRhh&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
RR - Receiver Number (Decimal, 00=All)
hh - Number of hours to delay autodial on clear alarm (Decimal,
01-99)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

198

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 52F
Function Type: Set Receiver Alarm Status
Command Format:
Display: S52FRRAAf
Computer: s52FRRAAf
Notes:
1.
2.

RR - Receiver number (00=all)
AA - Alarm Type number
00=all
03=Service Report Warning
04=Alarm Clear Warning
05=Delivery Report Warning
06=No Dial Tone Alarm
f - Alarm clear flag
0=clear; all others invalid

3.

Version 19
Inquire:
I52FRR
i52FRR

(Version 20)

Typical Response Message, Display Format:

I52FRR
JAN 1, 2000

8:06 AM

RECEIVER ALARM STATUS
D 1: HOME OFFICE
SERVICE REPORT WARN:
ALARM CLEAR WARN
:
DELIVERY REPORT WRN:
NO DIAL TONE ALARM :


CLEAR
CLEAR
CLEAR
CLEAR

Typical Response Message, Computer Format:
i52FRRYYMMDDHHmmNNRRf...
RRf&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
NN - Number of receiver alarm flags per receiver
Order of alarms: Service Report Warn, Alarm Clear Warn,
Delivery Report Warn, and No Dial Tone Alarm
RR - Receiver number
f - Alarm flags
0=clear
1=alarm
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

199

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 530
Function Type: Beeper Enable/Disable
Command Format:
Display: S53000x149
Computer: s53000x149
Notes:
1.

Version 26
Inquire:
I53000
i53000

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I53000
JAN 22, 1996

3:12 PM

BEEPER: ENABLED

Typical Response Message, Computer Format:
i53000YYMMDDHHmmx&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
x - Beeper Enable/Disable Flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

200

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 531
Function Type: Set RS-232 End of Message
Command Format:
Display: S53100f
Computer: s53100f

Version 8
Inquire:
I53100
i53100

Typical Response Message, Display Format:

I53100
JAN 22, 1996

3:16 PM

RS-232 END OF MESSAGE
DISABLED

Typical Response Message, Computer Format:
i53100YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - End of Message flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

201

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.3 WARNING, ALARM, & AUTO-PRINT SETUP
Function Code: 532
Function Type: Set Ticketed Variance Analysis Printout Flags
Command Format:
Display: S53200PWD
Computer: s53200PWD

Version 116
Inquire:
I53200
i53200

Typical Response Message, Display Format:

I53200
MAR 20, 1998

3:28 PM

PERIODIC, WEEKLY AND DAILY PRINTOUTS
VARIANCE ANALYSIS
PERIODIC
DISABLED
WEEKLY
DISABLED
DAILY
ENABLED

Typical Response Message, Computer Format:
i53200YYMMDDHHmmPWD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
P - Periodic Printout flag
0=Disable
1=Enable
W - Weekly Printout flag
0=Disable
1=Enable
D - Daily Printout flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

202

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 533
Version 116
Function Type: Set Ticketed Delivery Book Variance Printout Flags
Command Format:
Display: S53300PWD
Computer: s53300PWD

Inquire:
I53300
i53300

Typical Response Message, Display Format:

I53300
MAR 20, 1998

3:28 PM

PERIODIC, WEEKLY AND DAILY PRINTOUTS
BOOK VARIANCE
PERIODIC
DISABLED
WEEKLY
DISABLED
DAILY
ENABLED

Typical Response Message, Computer Format:
i53300YYMMDDHHmmPWD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
P - Periodic Printout flag
0=Disable
1=Enable
W - Weekly Printout flag
0=Disable
1=Enable
D - Daily Printout flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

203

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 534
Function Type: Set Ticketed Delivery Variance Printout Flags
Command Format:
Display: S53400PWD
Computer: s53400PWD

Version 116
Inquire:
I53400
i53400

Typical Response Message, Display Format:

I53400
MAR 20, 1998

3:28 PM

PERIODIC, WEEKLY AND DAILY PRINTOUTS
DELIVERY VARIANCE
PERIODIC
DISABLED
WEEKLY
DISABLED
DAILY
ENABLED

Typical Response Message, Computer Format:
i53400YYMMDDHHmmPWD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
P - Periodic Printout flag
0=Disable
1=Enable
W - Weekly Printout flag
0=Disable
1=Enable
D - Daily Printout flag
0=Disable
1=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

204

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 536
Function Type: Set RS-232 Security Code per Port
Command Format:
Display: S536PPsaaaaaa
Computer: s536PPsaaaaaa
Notes:
1.
2.
3.

Version 20
Inquire:
I536PP
i536PP

PP - Port number (Decimal, 01..03 [..06]; 99=this port)
s - Enable or Disable Status (if disabled no password is
required)
aaaaaa - Security code (6 ASCII characters from 20 Hex-7E Hex)

Typical Response Message, Display Format:

I536PP
JUN 1, 2000

8:05 AM

232 SECURITY CODE
PORT
1


SECURITY CODE
123456

STATUS
ENABLED

Typical Response Message, Computer Format:
i536PPYYMMDDHHmmsaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
s
aaaaaa
&&
CCCC

-

Current Date and Time
disabled or enabled status
Security code (6 ASCII characters from 20 Hex-7E Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

205

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 537
Function Type: Set Display Format RS-232 ETX per Port
Command Format:
Display: S537PPAB
Computer: s537PPAB
Notes:
1.
2.
3.

Version 20
Inquire:
I537PP
i537PP

PP - Port number (Decimal, 01..06]; 99=this port)
A - ETX CHAR 1 (value 0-255)
B - ETX CHAR 2 (value 0-255)

4.

The default end of message character transmitted by the TLS
is an  (Decimal 003 or ^C). If desired, the TLS can be
programmed to transmit up to two other characters at the end
of each computer format response message.

5.

The TLS accepts any ASCII character (000-255) in either of
the two positions. However, if the first "A" character is a
 (000), the TLS reverts to its default condition.
If
the first character "A", is not a NULL but the second
character "B" is, only the first character is transmitted
as the response message. If neither character is a ,
both characters are transmitted, in sequence, at the end of
each computer format response message.

6.

This command only sets the ETX characters. To enable the
use of the custom ETX, the 531 command must be used to
enable the user's custom ETX.

Typical Response Message, Display Format:

I537PP
JUN 1, 2000

8:05 AM

DISPLAY MODE RS-232 ETX CHARATERS
PORT
1


ETX
A

ETX
B

Typical Response Message, Computer Format:
i537PPYYMMDDHHmmAB&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
A
B
&&
CCCC

-

Current Date and Time
1st Character (value 0-255)
2nd Character (value 0-255)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

206

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 538
Function Type: Set Computer Format RS-232 ETX per Port
Command Format:
Display: S538PPAB
Computer: s538PPAB
Notes:
1.
2.
3.

Version 20
Inquire:
I538PP
i538PP

PP - Port number (Decimal, 01..06]; 99=this port)
A - ETX CHAR 1 (value 0-255)
B - ETX CHAR 2 (value 0-255)

4.

The default end of message character transmitted by the TLS
is an  (Decimal 003 or ^C). If desired, the TLS can be
programmed to transmit up to two other characters at the end
of each computer format response message.

5.

The TLS accepts any ASCII character (000-255) in either of
the two positions. However, if the first "A" character is a
 (000), the TLS reverts to its default condition.
If
the first character "A", is not a NULL but the second
character "B" is, only the first character is transmitted
as the response message. If neither character is a ,
both characters are transmitted, in sequence, at the end of
each computer format response message.

6.

This command only sets the ETX characters. To enable the
use of the custom ETX, the 531 command must be used to
enable the user's custom ETX.

Typical Response Message, Display Format:

I538PP
JUN 1, 2000

8:06 AM

COMPUTER MODE RS-232 ETX CHARATERS
PORT
1


ETX
C

ETX
D

Typical Response Message, Computer Format:
i538PPYYMMDDHHmmAB&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
A
B
&&
CCCC

-

Current Date and Time
1st Character (value 0-255)
2nd Character (value 0-255)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

207

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 546
Function Type: Set Tank Periodic Test Needed Warning
Command Format:
Display: S54600f
Computer: s54600f

Version 15
Inquire:
I54600
i54600

Typical Response Message, Display Format:

I54600
JAN 22, 1996

3:12 PM

TANK PER TEST NEEDED WRN: DISABLED

Typical Response Message, Computer Format:
i54600YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Tank Periodic Test Needed Warning Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

208

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 547
Version 15
Function Type: Set Days Before Tank Periodic Test Needed Warning
Command Format:
Display: S54700dd
Computer: s54700dd

Inquire:
I54700
i54700

Typical Response Message, Display Format:

I54700
JAN 22, 1996

3:12 PM

TANK PER TEST NEEDED WRN: DAYS= 25

Typical Response Message, Computer Format:
i54700YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Tank Periodic Test Needed Warn (Decimal, 00-30)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

209

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 548
Function Type: Set Days Before Tank Periodic Test Needed Alarm
Command Format:
Display: S54800dd
Computer: s54800dd

Version 15
Inquire:
I54800
i54800

Typical Response Message, Display Format:

I54800
JAN 22, 1996

3:12 PM

TANK PER TEST NEEDED ALM: DAYS= 30

Typical Response Message, Computer Format:
i54800YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Tank Periodic Test Needed Alarm (Decimal, 00-30)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

210

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 549
Function Type: Set Tank Annual Test Needed Warning
Command Format:
Display: S54900f
Computer: s54900f

Version 15
Inquire:
I54900
i54900

Typical Response Message, Display Format:

I54900
JAN 22, 1996

3:12 PM

TANK ANN TEST NEEDED WRN: DISABLED

Typical Response Message, Computer Format:
i54900YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Annual Test Needed Warning Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

211

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 54A
Function Type: Set Days Before Tank Annual Test Needed Warning
Command Format:
Display: S54A00ddd
Computer: s54A00ddd

Version 15
Inquire:
I54A00
i54A00

Typical Response Message, Display Format:

I54A00
JAN 22, 1996

3:12 PM

TANK ANN TST NEEDED WRN: DAYS=355

Typical Response Message, Computer Format:
i54A00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before Annual Test Needed Warning (Decimal, 000-365)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

212

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 54B
Function Type: Set Days Before Tank Annual Test Needed Alarm
Command Format:
Display: S54B00ddd
Computer: s54B00ddd

Version 15
Inquire:
I54B00
i54B00

Typical Response Message, Display Format:

I54B00
JAN 22, 1996

3:12 PM

TANK ANN TEST NEEDED ALM: DAYS=365

Typical Response Message, Computer Format:
i54B00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before annual Test Needed Alarm (Decimal, 000-365)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

213

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 54C
Function Type: Set CSLD Evaporation Reid Vapor Pressure Chart
Command Format:
Display: S54C00GG.G...
Computer: s54C00FFFFFFFF...
Notes:
1.
2.
3.

Version 19
Inquire:
I54C00
i54C00

GG.G - 12 Reid Vapor Pressures (Decimal)
FFFFFFFF - 12 Reid Vapor Pressures (ASCII Hex IEEE floats)
The command will be rejected if any value is outside the
range 0.0 to 15.0, or all table values are zero.

Typical Response Message, Display Format:

I54COO
JAN 22, 1996

3:27 PM

CSLD EVAP CONSTANTS
REID VAPOR PRESSURE:
JAN
14.0
FEB
14.0
MAR
12.0
APR
12.0
MAY
11.0
JUN
10.0
JUL
08.0
AUG
04.0
SEP
05.0
OCT
06.0
NOV
09.0
DEC
12.0

Typical Response Message, Computer Format:
i54C00YYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
NN - Number of eight character Data Fields to follow (Hex)
FFFFFFFF - 12 Reid Vapor Pressures (ASCII Hex IEEE floats)
1. Jan RVP
2. Feb RVP
3. Mar RVP
4. Apr RVP
5. May RVP
6. Jun RVP
7. Jul RVP
8. Aug RVP
9. Sep RVP
10. Oct RVP
11. Nov RVP
12. Dec RVP
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

214

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 54D
Function Type: Set IS03166 3 Character Country Code
Command Format:
Display: S54D00aaa
Computer: s54D00aaa

Version 29
Inquire:
I54D00
i54D00

Typical Response Message, Display Format:

I54D00
APR 10, 2007

10:15 AM

ISO3166 COUNTRY CODE: ESP

Typical Response Message, Computer Format:
i54D00YYMMDDHHmmaaa&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
aaa
&&
CCCC

-

Current Date and Time
ISO3166 Country Code (3 ASCII characters [20h-7EH])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

215

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 54E
Function Type: Set Vapor Monitoring Type
Command Format:
Display: S54E00t
Computer: s54E00t

Version 31
Inquire:
I54E00
i54E00

Notes:
1. An ISD/APM SEM is required for this command
Typical Response Message, Display Format:

I54E00
APR 10, 2007

10:15 AM

VAPOR MONITORING TYPE: CARB ISD

Typical Response Message, Computer Format:
i54E00YYMMDDHHmmt&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
t - Vapor Monitoring Type
0=CARB ISD
1=APM
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

216

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 550
Function Type: Set Inventory Alarms Units Configuration
Command Format:
Display: S55000C
Computer: s55000C

Version 33
Inquire:
I55000
i55000

Typical Response Message, Display Format:

I55000
APR 10, 2012

10:15 AM

INVENTORY ALARMS UNITS
CONFIG: STANDARD
MAX OR LABEL: VOLUME
HIGH PRODUCT: % MAX
OVERFILL
: % MAX
DELIV NEEDED: % MAX
LOW PRODUCT : VOLUME

Typical Response Message, Computer Format:
i55000YYMMDDHHmmCMHODL&&CCCC
Notes:
1.
2.

3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm - Current Date and Time
C - Inventory Alarms Units Configuration
1=Standard
2=% Full
3=All Volume
4=All Height
5=Custom
M - Max or Label Units
H - High Product Units
O - Overfill Product Units
D - Delivery Needed Product Units
L - Low Product Units
1=% Max
2=% Full
3=Volume
4=Height
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

217

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 551
Function Type: Set Inventory Alarms Custom Units
Command Format:
Display: S55100AU
Computer: s55100AU

Version 33
Inquire:
I55100
i55100

Notes:
1.

A - Alarm Type (Decimal)
1=Max Product
2=High Product
3=Overfill
4=Delivery Needed
5=Low Product
2.
U - Units Type (Decimal)
1=% Max
2=% Full
3=Volume
4=Height
3.Alarm Type Max Product cannot be set to unit type % Max

Typical Response Message, Display Format:

I55100
APR 10, 2012

10:15 AM

INVENTORY ALARMS UNITS
CONFIG: CUSTOM
MAX OR LABEL: VOLUME
HIGH PRODUCT: % MAX
OVERFILL
: % MAX
DELIV NEEDED: % MAX
LOW PRODUCT : VOLUME

Typical Response Message, Computer Format:
i55100YYMMDDHHmmCMHODL&&CCCC
Notes:
1.
2.

3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm - Current Date and Time
C - Inventory Alarms Units Configuration
1=Standard
2=All % Full
3=All Volume
4=All Height
5=Custom
M - Max Product Units
H - High Product Units
O - Overfill Product Units
D - Delivery Needed Product Units
L - Low Product Units
1=% Max
2=% Full
3=Volume
4=Height
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

218

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 553
Function Type: Set Line Re-Enable Method
Command Format:
Display: S55300f
Computer: s55300f

Version 19
Inquire:
I55300
i55300

Typical Response Message, Display Format:

I55300
JAN 24, 2000

2:54 PM

LINE RE-ENABLE METHOD
PASS LINE TEST

Typical Response Message, Computer Format:
i55300YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Line Re-Enable Method Flag
0=Pass Line Test
1=Alarm Acknowledge
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

219

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 554
Function Type: Set Periodic Line Leak Test Auto-Confirm
Command Format:
Display: S55400f
Computer: s55400f

Version 18
Inquire:
I55400
i55400

Typical Response Message, Display Format:

I55400
JUL 29, 1997

9:07 AM

0.20 GPH LINE TEST AUTO-CONFIRM: ENABLED

Typical Response Message, Computer Format:
i55400YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Periodic Line Leak Test Auto-Confirm:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

220

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 555
Function Type: Set Annual Line Leak Test Auto-Confirm
Command Format:
Display: S55500f
Computer: s55500f

Version 18
Inquire:
I55500
i55500

Typical Response Message, Display Format:

I55500
JUL 29, 1997

9:07 AM

0.10 GPH LINE TEST AUTO-CONFIRM: ENABLED

Typical Response Message, Computer Format:
i55500YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Annual Line Leak Test Auto-Confirm:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

221

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 556
Function Type: Set Line Periodic Test Needed Warning
Command Format:
Display: S55600f
Computer: s55600f

Version 15
Inquire:
I55600
i55600

Typical Response Message, Display Format:

I55600
JAN 22, 1996

3:12 PM

LINE PER TST NEEDED WRN: DISABLED

Typical Response Message, Computer Format:
i55600YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Periodic Test Needed Warning Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

222

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 557
Version 15
Function Type: Set Days Before Line Periodic Test Needed Warning
Command Format:
Display: S55700dd
Computer: s55700dd

Inquire:
I55700
i55700

Typical Response Message, Display Format:

I55700
JAN 22, 1996

3:12 PM

LINE PER TST NEEDED WRN: DAYS= 25

Typical Response Message, Computer Format:
i55700YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Periodic Test Needed Warning (Decimal, 00-30)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

223

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 558
Function Type: Set Days Before Line Periodic Test Needed Alarm
Command Format:
Display: S55800dd
Computer: s55800dd

Version 15
Inquire:
I55800
i55800

Typical Response Message, Display Format:

I55800
JAN 22, 1996

3:12 PM

LINE PER TST NEEDED ALM: DAYS= 30

Typical Response Message, Computer Format:
i55800YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Days Before Periodic Test Needed Alarm (Decimal, 00-30)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

224

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 559
Function Type: Set Line Annual Test Needed Warning
Command Format:
Display: S55900f
Computer: s55900f

Version 15
Inquire:
I55900
i55900

Typical Response Message, Display Format:

I55900
JAN 22, 1996

3:12 PM

LINE ANN TST NEEDED WRN: DISABLED

Typical Response Message, Computer Format:
i55900YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Annual Test Needed Warning Flag:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

225

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 55A
Function Type: Set Days Before Line Annual Test Needed Warning
Command Format:
Display: S55A00ddd
Computer: s55A00ddd

Version 15
Inquire:
I55A00
i55A00

Typical Response Message, Display Format:

I55A00
JAN 22, 1996

3:12 PM

LINE ANN TST NEEDED WRN: DAYS=355

Typical Response Message, Computer Format:
i55A00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before Annual Test Needed Warning (Decimal, 000-365)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

226

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 55B
Function Type: Set Days Before Line Annual Test Needed Alarm
Command Format:
Display: S55B00ddd
Computer: s55B00ddd

Version 15
Inquire:
I55B00
i55B00

Typical Response Message, Display Format:

I55B00
JAN 22, 1996

3:12 PM

LINE ANN TST NEEDED ALM: DAYS=365

Typical Response Message, Computer Format:
i55B00YYMMDDHHmmddd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ddd
&&
CCCC

-

Current Date and Time
Days Before Annual Test Needed Alarm (Decimal, 000-365)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

227

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 55E
Function Type: Set Fiscal Height Security Enable/Disable
Command Format:
Display: S55E00f
Computer: s55E00f

Version 32
Inquire:
I55E00
i55E00

Notes:
1.When the set portion of this command is sent to a TLS-350 that is fiscally
sealed, Display Format returns the format shown below but
Computer Format returns a question mark(?).
Typical Response Message, Display Format:

I55E00
APR 1, 2011

8:03 AM

FISCAL HEIGHT SECURITY: DISABLED

Typical Response Message, Computer Format:
i55E00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Fiscal Height Security Enable/Disable Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

228

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 560
Function Type: Set Mass/Density Enable/Disable
Command Format:
Display: S56000f
Computer: s56000f

Version 26
Inquire:
I56000
i56000

Typical Response Message, Display Format:

I56000
JUN 22, 2001

3:15 PM

MASS/DENSITY
ENABLED

Typical Response Message, Computer Format:
i56000YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Mass/Density Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

229

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 564
Function Type: Set Ullage
Command Format:
Display: S56400f
Computer: s56400f

Version 27
Inquire:
I56400
i56400

Typical Response Message, Display Format:

I56400
JUN 22, 2006

3:15 PM

ULLAGE: 90%

Typical Response Message, Computer Format:
i56400YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Ullage
0=90%
1=95%
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

230

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 565
Function Type: Set Maintenance History
Command Format:
Display: S56500f
Computer: s56500f

Version 27
Inquire:
I56500
i56500

Typical Response Message, Display Format:

I56500
JUN 22, 2006

3:15 PM

MAINTENANCE HISTORY
ENABLED

Typical Response Message, Computer Format:
i56500YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Maintenance History Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

231

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 566
Function Type: Set Service Notice Enable
Command Format:
Display: S56600149f
Computer: s56600149f
Notes:
1.

Version 28
Inquire:
I56600
i56600

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I56600
APR 10, 2007

10:15 AM

SERVICE NOTICE: DISABLED

Typical Response Message, Computer Format:
i56600YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Service Notice Enable
0 = DISABLED
1 = ENABLED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

232

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 567
Function Type: Set Service Notice Delivery Override Enable
Command Format:
Display: S56700149f
Computer: s56700149f
Notes:
1.

Version 28
Inquire:
I56700
i56700

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I56700
APR 10, 2007

10:15 AM

SERVICE NOTICE DELIVERY OVERRIDE: DISABLED

Typical Response Message, Computer Format:
i56700YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Service Notice Delivery Override Enable
0 = DISABLED
1 = ENABLED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

233

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 568
Function Type: Set Service Notice Session Enable
Command Format:
Display: S56800149f
Computer: s56800149f
Notes:
1.

Version 28
Inquire:
I56800
i56800

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I56800
APR 10, 2007

10:15 AM

SERVICE NOTICE SESSION: DISABLED

Typical Response Message, Computer Format:
i56800YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Service Notice Session Enable
0 = DISABLED
1 = ENABLED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

234

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 569
Function Type: Set Service Notice Session Duration
Command Format:
Display: S56900hh
Computer: s56900hh

Version 28
Inquire:
I56900
i56900

Typical Response Message, Display Format:

I56900
APR 10, 2007

10:15 AM

SERVICE NOTICE SESSION DURATION: 2 HOURS

Typical Response Message, Computer Format:
i56900YYMMDDHHmmhh&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
hh
&&
CCCC

-

Current Date and Time
Service Notice Session Duration in Hours (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

235

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 56A
Function Type: System Tank Chart Security Code Audit Trail

Version 29

Command Format:
Display: I56A00
Computer: i56A00
Notes:
1.

Returns the date/time of the last Tank Chart Security Code modification

Typical Response Message, Display Format:

I56A00
APR 10, 2009

10:15 AM

TANK CHART SECURITY
DATE/TIME
MAR 30, 2008 08:00 AM

Typical Response Message, Computer Format:
i56A00YYMMDDHHmmyymmddhhmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
yymmddhhmm
&&
CCCC

-

Current Date and Time
Date and Time of Tank Chart Security Code Modification
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

236

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 581
Function Type: Set Alarm Filter
Command Format:
Display: S58100f
Computer: s58100f

Version 33
Inquire:
I58100
i58100

Typical Response Message, Display Format:

I58100
JUN 24, 2012

3:15 PM

ALARM FILTERING FLAG: ENABLED

Typical Response Message, Computer Format:
i58100YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Alarm Filter Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

237

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 5BC
Function Type: Set Receiver Auto Dial on Alarm II
Command Format:
Display: S5BCRRAANNTTSS
Computer: s5BCRRAANNTTSS

Version 19
Inquire:
I5BCRR
i5BCRR

Typical Response Message, Display Format:

I5BCRR
JAN 15, 1996 4:29 PM
RECEIVER SETUP REPORT
D 1: HOME OFFICE
IN-TANK ALARMS
T 1:LEAK ALARM
T 2:LEAK ALARM

Typical Response Message, Computer Format:
i5BCRRYYMMDDHHmmRRnnAANNTTSS...
RRnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
RR
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Receiver Number (Decimal)
Number of Alarms to Follow (Hex)
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status
00=Clear
01=Set
Data Termination Flag
Message Checksum.

Part No. 576013-635, Revision AA

238

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 5BD
Function Type: Set Enable/Disable Custom Alarms
Command Format:
Display: S5BD00f
Computer: s5BD00f

Version 23
Inquire:
I5BD00
i5BD00

Typical Response Message, Display Format:

I5BD00
JUN 22, 2001

3:15 PM

CUSTOM ALARM LABELS
ENABLED

Typical Response Message, Computer Format:
i5BD00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Custom Alarm Labels Flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

239

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 5BE
Function Type: Set Custom Alarm Labels

Version 23

Command Format:
Display: S5BE00AANNfaaaaaaaaaaaaaaaaaaa
Computer: s5BE00AANNfaaaaaaaaaaaaaaaaaaa

Inquire:
I5BE00
i5BE00

Typical Response Message, Display Format:

I5BE00
JUN 22, 2001

3:15 PM

CUSTOM ALARM LABELS
IN-TANK ALARMS
OVERFILL ALARM
(custom alarm label)
LOW PRODUCT ALARM
T 1:(custom alarm label)

Typical Response Message, Computer Format:
i5BE00YYMMDDHHmmnnAANNfaaaaaaaaaaaaaaaaaaa...
AANNfaaaaaaaaaaaaaaaaaaa...&&CCCC
Notes:
1.
2.
2.
4.
5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
nn - Number of Custom Alarm Labels to follow
AA - Alarm/Warning Category:
See explanation for "AA" in Function
NN - Alarm Type Number:
See explanation for "NN" in Function
f - Custom Alarm Label Flag
0=Disabled
1=Enabled
a - Custom Alarm Label (19 ASCII characters
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

(Hex)
i10100
i10100

[20h-7Eh])

240

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 5BF
Version 26
Function Type: Set Custom Alarm Label, device number, and indications
Command Format:
Display: S5BF00AANNTTflpbdaaaaaaaaaaaaaaaaaaa
Computer: s5BF00AANNTTflpbdaaaaaaaaaaaaaaaaaaa
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

Inquire:
I5BF00
i5BF00

AA - Alarm/Warning Category:
See explanation for "AA" in Function i10100
NN - Alarm Type Number:
See explanation for "NN" in Function i10100
TT - Device (or Tank) Number (Decimal, 00=all)
f - Custom Alarm Flag
0=Disabled
1=Enabled
l - LCD Indication Flag
0=Disabled
1=Enabled
p - PRINTOUT Indication Flag
0=Disabled
1=Enabled
b - BEEP Indication Flag
0=Disabled
1=Enabled
d - LED Indication Flag
0=Disabled
1=Enabled
a - Custom Alarm Label (19 ASCII characters [20h-7Eh])

Typical Response Message, Display Format:

I5BF00
JUN 22, 2001

3:15 PM

CUSTOM ALARM LABELS
IN-TANK ALARMS
OVERFILL ALARM
T 1:(custom alarm label)
LCD:
ENABLED
PRINT: ENABLED
BEEP: DISABLED
LED:
ENABLED
T 2:(custom alarm label)
LCD:
ENABLED
PRINT: ENABLED
BEEP: DISABLED
LED:
ENABLED


Part No. 576013-635, Revision AA

241

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 5BF Notes: (Continued)
Typical Response Message, Computer Format:
i5BF00YYMMDDHHmmnnAANNTTlpbdaaaaaaaaaaaaaaaaaaa...
AANNTTlpbdaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm - Current Date and Time
nn - Number of Custom Alarms to follow (Hex)
AA - Alarm/Warning Category:
See explanation for "AA" in Function i10100
NN - Alarm Type Number:
See explanation for "NN" in Function i10100
TT - Device (or Tank) Number (Decimal, 00=all)
l - LCD Indication Flag
0=Disabled
1=Enabled
p - PRINTOUT Indication Flag
0=Disabled
1=Enabled
b - BEEP Indication Flag
0=Disabled
1=Enabled
d - LED Indication Flag
0=Disabled
1=Enabled
a - Custom Alarm Label (19 ASCII characters [20h-7Eh])
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

242

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 5E2
Function Type: Set Inventory Record Time 1, 2, 3, 4
Command Format:
Display: S5E2SSHHmm
Computer: s5E2SSHHmm

Version 14
Inquire:
I5E2SS
i5E2SS

Typical Response Message, Display Format:

I5E201
JAN 22, 1996
RECORD 1 :


3:12 PM
2:22 PM

Typical Response Message, Computer Format:
i5E2SSYYMMDDHHmmSSHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
HHmm
&&
CCCC

-

Current Date and Time
Inventory Record Time (01, 02, 03, 04)
Hour and Minute (EE00=Disabled)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

243

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.4 IN-TANK SETUP
Function Code: 601
Function Type: Set Tank Configuration
Command Format:
Display: S601TTf
Computer: s601TTf

Version 1
Inquire:
I601TT
i601TT

Typical Response Message, Display Format:

I601TT
JAN 22, 1996

3:16 PM

TANK CONFIGURATION
DEVICE
1


LABEL
REGULAR UNLEADED

CONFIGURED
ON

Typical Response Message, Computer Format:
i601TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Tank Configuration Flag:
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

244

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 602
Function Type: Set Tank Product Label
Command Format:
Display: S602TTaaaaaaaaaaaaaaaaaaaa
Computer: s602TTaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I602TT
i602TT

Typical Response Message, Display Format:

I602TT
JAN 22, 1996

3:16 PM

TANK PRODUCT LABEL
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

Typical Response Message, Computer Format:
i602TTYYMMDDHHmmTTaaaaaaaaaaaaaaaaaaaa...
TTaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
a
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

245

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 603
Function Type: Set Tank Product Code
Command Format:
Display: S603TTa
Computer: s603TTa

Version 1
Inquire:
I603TT
i603TT

Typical Response Message, Display Format:

I603TT
JAN 22, 1996

3:16 PM

TANK PRODUCT CODE
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

1

Typical Response Message, Computer Format:
i603TTYYMMDDHHmmTTa...
TTa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
a
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

246

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 604
Function Type: Set Tank 1 Point Full Height Volume
Command Format:
Display: S604TTGGGGGG
Computer: s604TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I604TT
i604TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Full Height Volume, Gallons (Decimal)
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I604TT
JAN 22, 1996

3:16 PM

TANK FULL VOLUME
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
9728

Typical Response Message, Computer Format:
i604TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Full Height Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

247

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 605
Function Type: Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes
Command Format:
Display: S605TTGGGGGGggggggGGGGGGgggggg
or: S605TTGGGG,gggg,GGGG,ggg
Computer: s605TTFFFFFFFFffffffffFFFFFFFFffffffff
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

TT
GGGGGG
gggggg
GGGGGG
gggggg
FFFFFFFF
ffffffff
FFFFFFFF
ffffffff

- Tank Number (Decimal, 00=all)
- Full Height Volume, Gallons (Decimal)
- 3/4 Height Volume, Gallons (Decimal)
- 1/2 Height Volume, Gallons (Decimal)
- 1/4 Height Volume, Gallons (Decimal)
- Full Height Volume, Gallons (ASCII Hex
- 3/4 Height Volume, Gallons (ASCII Hex
- 1/2 Height Volume, Gallons (ASCII Hex
- 1/4 Height Volume, Gallons (ASCII Hex

IEEE
IEEE
IEEE
IEEE

Version 1
Inquire:
I605TT
i605TT

float)
float)
float)
float)

Typical Response Message, Display Format:

I605TT
JAN 22, 1996

3:16 PM

TANK 4 POINT VOLUMES
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

9728

GALLONS
7296
4864

2432

Typical Response Message, Computer Format:
i605TTYYMMDDHHmmTTFFFFFFFFffffffffFFFFFFFFffffffff...
TTFFFFFFFFffffffffFFFFFFFFffffffff&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
TT
FFFFFFFF
ffffffff
FFFFFFFF
ffffffff
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Full Height Volume, Gallons (ASCII
3/4 Height Volume, Gallons (ASCII
1/2 Height Volume, Gallons (ASCII
1/4 Height Volume, Gallons (ASCII
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

Hex
Hex
Hex
Hex

IEEE
IEEE
IEEE
IEEE

float)
float)
float)
float)

248

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 606
Function Type: Set Tank 20 Point Full, 95%, 90%,...Volumes
Command Format:
Display: S606TTGGGGGGgggggg...
or: S606TTGGGG,gggg,GGGG,...
Computer: s606TTFFFFFFFF...
Notes:
1.
2.
3.

Version 1
Inquire:
I606TT
i606TT

TT - Tank Number (Decimal, 00=all)
GGGGGGgggggg - Series of 20 Volumes, Gallons (Decimal)
FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I606TT
JAN 22, 1996

3:16 PM

TANK 20 POINT VOLUMES
TANK
1

PRODUCT LABEL
REGULAR UNLEADED

9720
7776
5832
3888
1944

GALLONS
9234
7290
5346
3402
1458

8748
6804
4860
2916
972

8262
6318
4372
2430
486


Typical Response Message, Computer Format:
i606TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

249

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 607
Function Type: Set Tank Diameter
Command Format:
Display: S607TTIII.hh
Computer: s607TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I607TT
i607TT

TT - Tank Number (Decimal, 00=all)
III.hh - Tank Diameter, Inches and hundredths (Decimal)
FFFFFFFF - Tank Diameter, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I607TT
JAN 22, 1996

3:16 PM

TANK DIAMETER
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
96.00

Typical Response Message, Computer Format:
i607TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Tank Diameter, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

250

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 608
Function Type: Set Tank Tilt
Command Format:
Display: S608TTIII.hh
Computer: s608TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I608TT
i608TT

TT - Tank Number (Decimal, 00=all)
III.hh - Tank Tilt, Inches and hundredths (Decimal)
FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I608TT
JAN 22, 1996

3:16 PM

TANK TILT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
2.40

Typical Response Message, Computer Format:
i608TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Tank Tilt, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

251

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 609
Function Type: Set Tank Thermal Expansion Coefficient
Command Format:
Display: S609TTc.cccccc
Computer: s609TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I609TT
i609TT

TT - Tank Number (Decimal, 00=all)
c.cccccc - Thermal Expansion Coefficient (decimal)
FFFFFFFF - Thermal Expansion Coefficient (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I609TT
JAN 22, 1996

3:17 PM

TANK THERMAL COEFFICIENT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

0.000700

Typical Response Message, Computer Format:
i609TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Thermal Expansion Coefficient (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

252

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 60A
Function Type: Set Tank Linear Calculated Full Volume
Command Format:
Display: S60ATTGGGGGG
Computer: s60ATTFFFFFFFF
Notes:
1.
2.
3.

Version 9
Inquire:
I60ATT
i60ATT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Full Height Volume, Gallons (Decimal)
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I60ATT
JAN 22, 1996

3:17 PM

TANK FULL VOLUME
TANK

PRODUCT LABEL

1


REGULAR UNLEADED

TANK PROFILE

GALLONS

1 PT

10000

Typical Response Message, Computer Format:
i60ATTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Full height volume (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

253

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 60B
Function Type: Set Tank Stick Height Function Enable
Command Format:
Display: S60B00f
Computer: s60B00f

Version 15
Inquire:
I60B00
i60B00

Typical Response Message, Display Format:

I60B00
JUL 29, 1997

9:07 AM

STICK HEIGHT OFFSET ENABLE STATUS
DISABLED

Typical Response Message, Computer Format:
i60B00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Stick Height Function:
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

254

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 60C
Function Type: Set Tank Stick Height Offset
Command Format:
Display: S60CTTIII.hh
Computer: s60CTTFFFFFFFF
Notes:
1.
2.
3.

Version 15
Inquire:
I60CTT
i60CTT

TT - Tank Number (Decimal, 00=all)
III.hh - Stick Height Offset, Inches and hundredths (Decimal)
FFFFFFFF - Stick Height Offset, Inches (ASCII Hex IEEE float). Value
must be within the range of +144 to -144 inches. It is used
to calculate stick height=height (without tilt) + stick
offset

Typical Response Message, Display Format:

I60CTT
JUL 29, 1997

9:07 AM

TANK STICK HEIGHT OFFSET
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
0.00

Typical Response Message, Computer Format:
i60CTTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Stick Height Offset, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

255

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 60E
Function Type: Set Tank Programmable Float Parameters
Command Format:
Display: S60ETTIIII.tttIIII.tttIIII.tttIIII.ttt
or: S60ETTIII.ttt,III.ttt,III.ttt,III.ttt
Computer: s60ETTFFFFFFFF...FFFFFFFF
Notes:
1.
2.
3.
4.

Version 22
Inquire:
I60ETT
i60ETT

CUSTOM float size must be chosen (Function Code 62F) for
these parameters to be set and used.
TT - Tank Number (Decimal, 00=all)
IIII.ttt - Float Parameters, Inches and thousandths (Decimal)
FFFFFFFF - Float Parameters, Inches (ASCII Hex IEEE floats)

Typical Response Message, Display Format:

I60ETT
JAN 22, 2001 10:02 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CUSTOM FLOAT PARAMETERS
TANK
1


WATER OFFSET
-3.160

FUEL OFFSET
0.270

INVALID FUEL
8.000

WATER MINIMUM
0.750

Typical Response Message, Computer Format:
i60ETTYYMMDDHHmmTTNNFFFFFFFF...
TTNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
TT
NN
FFFFFFFF

-

Current Date
Tank Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
Float Parameters, Inches (ASCII Hex IEEE floats):
1. Water Offset
2. Fuel Offset
3. Invalid Fuel Level
4. Minimum Water Level
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

256

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 60F
Function Type: Set Tank Probe Offset
Command Format:
Display: S60FTTIII.hh
Computer: s60FTTFFFFFFFF
Notes:
1.
2.
3.

Version 22
Inquire:
I60FTT
i60FTT

TT - Tank Number (Decimal, 00=all)
III.hh - Probe offset, Inches and hundredths (Decimal)
FFFFFFFF - Probe offset, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I60FTT
JAN 22, 1996

3:16 PM

PROBE OFFSET
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
2.40

Typical Response Message, Computer Format:
i60FTTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Probe offset, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

257

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 610
Function Type: Set Tank Delivery Delay
Command Format:
Display: S610TTdd
Computer: s610TTdd

Version 1
Inquire:
I610TT
i610TT

Typical Response Message, Display Format:

I610TT
JAN 22, 1996

3:17 PM

TANK DELIVERY DELAY
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

5

Typical Response Message, Computer Format:
i610TTYYMMDDHHmmTTdd...
TTdd&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
dd
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Indicates the length of time in minutes (01-99)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

258

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 611
Function Type: Set Tank Leak Test Type & Start Time
Command Format:
Display: S611TTDDRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm


Computer: s611TTDDRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm



(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6)
M=7)
M=1)
M=2)
M=3)
M=4)
M=5)
M=6)
M=7)

Version 1
Inquire:
I611TT

i611TT

Typical Response Message, Display Format:

I611TT
JUN 1, 2000

8:06 AM

LEAK TEST METHOD
- - - - - - - - - - - TEST ON DATE : TANK 1
JUN 1, 2000
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION
: 2 HOURS
TST EARLY STOP:DISABLED

Typical Response Message, Computer Format:
i611TTYYMMDDHHmmTTDDRMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
(none)
(none)
TTDDRMYYMMDDHHmm&&CCCC
MMWDHHmm&&CCCC
WDHHmm&&CCCC
DHHmm&&CCCC
HHmm&&CCCC
&&CCCC
&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
DD
R

-

(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=6)
M=7)
M=1)
M=2)
M=3)
M=4)
M=5)
M=6)
M=7)

Current Date and Time
Tank Number (Decimal, 00=all)
Leak test Duration in hours (2 <= DD <= 24)
Leak test Rate (0=0.2, 1=0.1)

Part No. 576013-635, Revision AA

259

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 611 Notes: (Continued)
5.

M - Leak test Method:
1=On Date
2=Annually
3=Monthly
4=Weekly
5=Daily
6=Automatic
7=CSLD
- If M=1 ON DATE, YYMMDDHHmm:
YY =Year
MM =Month (01-12)
DD =Day
HHmm=Hour, Minute (EE00=Disabled)
- If M=2 ANNUALLY, MMWDHHmm:
MM =Month (01-12)
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=3 MONTHLY, WDHHmm:
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=4 WEEKLY, DHHmm:
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=5 DAILY, HHmm:
HHmm=Hour, Minute (EE00=Disabled)

6.
7.

&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

260

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 612
Function Type: Set Tank SIPHON Manifolded Partners
Command Format:
Display: S612TTttTTtt...
Computer: s612TTttTTtt...

Version 1
Inquire:
I612TT
i612TT

Typical Response Message, Display Format:

I612TT
JAN 22, 2002

3:17 PM

TANK MANIFOLDED PARTNERS
TANK
2


PRODUCT LABEL
REGULAR UNLEADED

SIPHON MANIFOLDED TANKS
1

LINE MANIFOLDED TANKS
3

Typical Response Message, Computer Format:
i612TTYYMMDDHHmmTTNNtt...
TTNNtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
NN
tt

-

Current Date and Time
Number of the first tank to be SIPHON manifolded
Number of tanks that are SIPHON manifolded together
Tank numbers of other tanks to be SIPHON manifolded to first
tank
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

261

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 613
Function Type: Set CSLD Probability of Detection
Command Format:
Display: S613TTf
Computer: s613TTf

Version 3
Inquire:
I613TT
i613TT

Typical Response Message, Display Format:

I613TT
JAN 22, 1996 3:17 PM
CSLD PROBABLITY OF DETECTION
T 1:REGULAR UNLEADED


: Pd=95%

Typical Response Message, Computer Format:
i613TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number
f - Probability of Detection
1=95%
2=99%
3=CUSTOM (Inquiry Command Only)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

262

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 614
Function Type: Set CSLD Climate Factor
Command Format:
Display: S614TTf
Computer: s614TTf

Version 5
Inquire:
I614TT
i614TT

Typical Response Message, Display Format:

I614TT
JAN 22, 1996 3:17 PM
CSLD CLIMATE FACTOR
T 1:REGULAR UNLEADED


: MODERATE

Typical Response Message, Computer Format:
i614TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number
f - Climate Factor
1=Moderate
2=Extreme
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

263

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 615
Function Type: Set BIR Meter Data Present
Command Format:
Display: S615TTf
Computer: s615TTf

Version 108
Inquire:
I615TT
i615TT

Typical Response Message, Display Format:

I615TT
JAN 22, 1996
TANK
1


3:18 PM

PRODUCT LABEL
REGULAR UNLEADED

METER DATA
YES

Typical Response Message, Computer Format:
i615TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal, 00=All)
3.
f - Meter data availability:
0=No Meter Data Available
1=Meter Data Present
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

264

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 616
Function Type: Set AccuChart Update Scheduling
Command Format:
Display: S616TTf
Computer: s616TTf

Version 110
Inquire:
I616TT
i616TT

Typical Response Message, Display Format:

I616TT
JAN 22, 1996
TANK
1


3:18 PM

PRODUCT LABEL
REGULAR UNLEADED

CAL UPDATE
IMMEDIATE

Typical Response Message, Computer Format:
s616TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal, 00=All)
3.
f - AccuChart Update Scheduling:
1=Immediate
2=Periodic
3=Complete
4=Never
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

265

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 618
Function Type: Set Tank CSLD Evaporation Compensation
Command Format:
Display: S618TTf
Computer: s618TTf
Notes:
1.

Version 19
Inquire:
I618TT
i618TT

Only accepted if CSLD has been selected as the leak test
method (S611TT) for the addressed tank and its Climate
Factor (S614TT) has been set to Extreme. Also, for this
feature to take effect, there must be valid entries in the
RVP table (S54C00).

Typical Response Message, Display Format:

I618TT
JAN 22, 1996

3:16 PM

CSLD EVAPORATION COMPENSATION
DEVICE LABEL
T 1:UNLEADED GASOLINE
T 2:SUPER UNLEADED
T 3:PREMIUM UNLEADED
T 4:REGULAR GASOLINE


ENABLED
YES
YES
NO
YES

Typical Response Message, Computer Format:
i618TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - CSLD Evaporation Compensation flag:
0=NO
1=YES
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

266

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 619
Function Type: Set Tank Stage II Vapor Recovery
Command Format:
Display: S619TTf
Computer: s619TTf
Notes:
1.

Version 19
Inquire:
I619TT
i619TT

Only allowed if CSLD Evaporation Compensation is enabled

Typical Response Message, Display Format:

I619TT
JAN 22, 1996

3:16 PM

STAGE II VAPOR RECOVERY
DEVICE LABEL
T 1:UNLEADED GASOLINE
T 2:SUPER UNLEADED
T 3:PREMIUM UNLEADED
T 4:REGULAR GASOLINE


ENABLED
YES
YES
YES
YES

Typical Response Message, Computer Format:
i619TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Stage II Vapor Recovery flag:
0=NO
1=YES
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

267

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61A
Function Type: Set In-Tank Leak Test Early Stop
Command Format:
Display: S61ATTf
Computer: s61ATTf

Version 20
Inquire:
I61ATT
i61ATT

Typical Response Message, Display Format:

I61ATT
JUN 1, 2000

8:06 AM

IN-TANK LEAK TEST EARLY STOP
TANK
1
2
3
4


PRODUCT LABEL
* PRODUCT 1 *
* PRODUCT 2 *
* PRODUCT 3 *
* PRODUCT 4 *

TST EARLY STOP:
DISABLED
DISABLED
DISABLED
DISABLED

Typical Response Message, Computer Format:
i6A000YYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
3.
4.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - In-Tank Leak Test Early Stop Flag:
0=DISABLED
1=ENABLED
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

268

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61B
Function Type: Set In-Tank Static Gross Test Auto-Confirm
Command Format:
Display: S61BTTf
Computer: s61BTTf

Version 121
Inquire:
I61BTT
i61BTT

Typical Response Message, Display Format:

I61BTT
OCT 10, 2000

3:11 PM

IN-TANK STATIC GROSS TEST AUTO-CONFIRM:
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

AUTO-CONFIRM
DISABLED

Typical Response Message, Computer Format:
i61BTTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - In-Tank Static Gross Test Auto-Confirm flag
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

269

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61C
Function Type: Set CSLD Report Only Mode
Command Format:
Display: S61CTTf
Computer: s61CTTf

Version 121
Inquire:
I61CTT
i61CTT

Typical Response Message, Display Format:

I61CTT
OCT 10, 2000 10:00 AM
CSLD REPORT ONLY
TANK
1


PRODUCT LABEL
UNLEADED GASOLINE

CSLD REPORT ONLY
DISABLED

Typical Response Message, Computer Format:
i61CTTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - CSLD Report Only flag
0=Disabled
1=End of Month
2=Day 15 and End of Month
3=Day 25 and End of Month
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

270

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61D
Function Type: Set Tank LINE Manifolded Partners
Command Format:
Display: S61DTTttTTtt...
Computer: s61DTTttTTtt...

Version 23
Inquire:
I61DTT
i61DTT

Typical Response Message, Display Format:

I61DTT
JAN 22, 2002

3:17 PM

TANK MANIFOLDED PARTNERS
TANK
2


PRODUCT LABEL
REGULAR UNLEADED

SIPHON MANIFOLDED TANKS
1

LINE MANIFOLDED TANKS
3

Typical Response Message, Computer Format:
i61DTTYYMMDDHHmmTTNNtt...
TTNNtt&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
NN
tt

-

Current Date and Time
Number of the first tank to be LINE manifolded
Number of tanks that are LINE manifolded together
Tank numbers of other tanks to be LINE manifolded to first
tank
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

271

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61E
Function Type: Set Tank Density
Command Format:
Display: S61ETTdd.ddddd
Computer: s61ETTFFFFFFFF
Notes:
1.
2.
3.

Version 26
Inquire:
I61ETT
i61ETT

TT - Tank Number (Decimal, 00=all)
dd.dddd - Entered Density, relative, actual or API (Decimal)
FFFFFFFF - Entered Density, relative, actual or API (ASCII Hex IEEE
float)

Typical Response Message, Display Format:

I61ETT
JUN 22, 2001

3:15 PM

TANK DENSITY
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

DENSITY
5.9987

Typical Response Message, Computer Format:
i61ETTYYMMDDHHmmTTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Entered Density (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

272

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 61F
Function Type: Set Delivery Density

Version 26

Command Format:
Display: S61FTTtdd.ddddd
Computer: s61FTTtFFFFFFFF

Inquire:
I61FTTt
i61FTTt

Notes:
1.
2.
3.
4.

TT
t
dd.dddd
FFFFFFFF

-

Tank Number (Decimal, 00=all)
Delivery Type (0=next, 1=last)
Entered Density, relative, actual or API (Decimal)
Entered Density, relative, actual or API (ASCII Hex IEEE
float)

Typical Response Message, Display Format:

I61FTT0
JUN 22, 2001

3:15 PM

NEXT DELIVERY DENSITY
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

DENSITY
5.9987

Typical Response Message, Computer Format:
i61FTTYYMMDDHHmmTTtFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
t
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Delivery Type (0=next, 1=last)
Entered Density (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

273

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 621
Function Type: Set Tank Low Level Limit
Command Format:
Display: S621TTGGGGGG
Computer: s621TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I621TT
i621TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Low Level Limit, Gallons (Decimal)
FFFFFFFF - Low Level Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I621TT
JAN 22, 1996

3:18 PM

TANK LOW PRODUCT LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
1000

Typical Response Message, Computer Format:
i621TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Low Level Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

274

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 622
Function Type: Set Tank High Level Limit
Command Format:
Display: S622TTGGGGGG
Computer: s622TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I622TT
i622TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - High Level Limit, Gallons (Decimal)
FFFFFFFF - High Level Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I622TT
JAN 22, 1996

3:18 PM

TANK HIGH PRODUCT LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
9500

Typical Response Message, Computer Format:
i622TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
High Level Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

275

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 623
Function Type: Set Tank Overfill Level Limit
Command Format:
Display: S623TTGGGGGG
Computer: s623TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I623TT
i623TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Overfill Level Limit, Gallons (Decimal)
FFFFFFFF - Overfill Level Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I623TT
JAN 22, 1996

3:18 PM

TANK OVERFILL LEVEL LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
9300

Typical Response Message, Computer Format:
i623TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Overfill Level Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

276

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 624
Function Type: Set Tank High Water Level Limit
Command Format:
Display: S624TTII.t
Computer: s624TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I624TT
i624TT

TT - Tank Number (Decimal, 00=all)
II.t - High Water Level Limit, Inches and tenths (Decimal,
Max=05.0)
FFFFFFFF - High Water Level Limit, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I624TT
JAN 22, 1996

3:18 PM

TANK HIGH WATER LEVEL LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
4.5

Typical Response Message, Computer Format:
i624TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
High Water Level Limit, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

277

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 625
Function Type: Set Tank Sudden Loss Limit
Command Format:
Display: S625TTGGGGGG
Computer: s625TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I625TT
i625TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Sudden Loss Limit, Gallons (Decimal)
FFFFFFFF - Sudden Loss Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I625TT
JAN 22, 1996

3:18 PM

TANK SUDDEN LOSS LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
100

Typical Response Message, Computer Format:
i625TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Sudden Loss Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

278

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 626
Function Type: Set Tank Leak Alarm Limit
Command Format:
Display: S626TTGGGGGG
Computer: s626TTFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I626TT
i626TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Leak Alarm Limit, Gallons (Decimal)
FFFFFFFF - Leak Alarm Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I626TT
JAN 22, 1996

3:18 PM

TANK LEAK ALARM LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
50

Typical Response Message, Computer Format:
i626TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Leak Alarm Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

279

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 627
Function Type: Set Tank High Water Warning Limit
Command Format:
Display: S627TTII.t
Computer: s627TTFFFFFFFF
Notes:
1.
2.
3.

Version 2
Inquire:
I627TT
i627TT

TT - Tank Number (Decimal, 00=all)
II.t - High Water Warning Limit, Inches and tenths (Decimal,
Max=05.0)
FFFFFFFF - High Water Warning Limit, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I627TT
JAN 22, 1996

3:18 PM

TANK HIGH WATER WARNING LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

INCHES
3.5

Typical Response Message, Computer Format:
i627TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
High Water Warning Limit, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

280

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 628
Function Type: Set Tank Maximum Volume Limit
Command Format:
Display: S628TTGGGGGG
Computer: s628TTFFFFFFFF
Notes:
1.
2.
3.

Version 2
Inquire:
I628TT
i628TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Maximum Volume Limit, Gallons (Decimal)
FFFFFFFF - Maximum Volume Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I628TT
JAN 22, 1996

3:19 PM

TANK MAXIMUM VOLUME LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
9600

Typical Response Message, Computer Format:
i628TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Maximum Volume Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

281

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 629
Function Type: Set Tank Delivery Required Limit
Command Format:
Display: S629TTGGGGGG
Computer: s629TTFFFFFFFF
Notes:
1.
2.
3.

Version 2
Inquire:
I629TT
i629TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Delivery Required Limit, Gallons (Decimal)
FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I629TT
JAN 22, 1996

3:19 PM

TANK DELIVERY REQUIRED LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
1500

Typical Response Message, Computer Format:
i629TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Delivery Required Limit, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

282

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62A
Function Type: Set Tank Annual Leak Test Minimum Volume
Command Format:
Display: S62ATTGGGGGG
Computer: s62ATTFFFFFFFF
Notes:
1.
2.
3.

Version 2
Inquire:
I62ATT
i62ATT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Annual Test Minimum Volume, Gallons (Decimal)
FFFFFFFF - Annual Test Minimum Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I62ATT
JAN 22, 1996

3:19 PM

ANNUAL LEAK TEST MIN VOLUME
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
6000

Typical Response Message, Computer Format:
i62ATTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Annual Test Minimum Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

283

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62B
Function Type: Set Tank Last Annual Test
Command Format:
Display: S62BTTYYMMDD
Computer: s62BTTYYMMDD

Version 2
Inquire:
I62BTT
i62BTT

Typical Response Message, Display Format:

I62BTT
JAN 22, 1996

3:19 PM

TANK LAST ANNUAL TEST
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

DATE
940225

Typical Response Message, Computer Format:
i62BTTYYMMDDHHmmTTYYMMDD...
TTYYMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
YYMMDD
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Year, Month, Day
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

284

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62C
Function Type: Set Tank Periodic Test Type
Command Format:
Display: S62CTTp
Computer: s62CTTp

Version 2
Inquire:
I62CTT
i62CTT

Typical Response Message, Display Format:

I62CTT
JAN 22, 1996

3:19 PM

TANK PERIODIC TEST TYPE
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

PERIODIC TEST TYPE
QUICK

Typical Response Message, Computer Format:
i62CTTYYMMDDHHmmTTp...
TTp&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
p - Periodic Test Type:
0=Standard Test
1=Quick Test (only Mag Probes may be set to QUICK)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

285

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62D
Function Type: Set Enable/Disable Tank Leak Test Fail Alarms
Command Format:
Display: S62DTTgpa
Computer: s62DTTgpa

Version 2
Inquire:
I62DTT
i62DTT

Typical Response Message, Display Format:

I62DTT
JAN 22, 1996

3:19 PM

TANK LEAK TEST FAIL ALARMS
TANK
1

PRODUCT LABEL
REGULAR UNLEADED

GROSS TEST FAIL
PERIODIC TEST FAIL
ANNUAL TEST FAIL

ALARM DISABLED
ALARM DISABLED
ALARM DISABLED


Typical Response Message, Computer Format:
i62DTTYYMMDDHHmmTTgpa...
TTgpa&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
g - Gross Test Fail Alarm
0=Disabled
1=Enabled
p - Periodic Test Fail Alarm
0=Disabled
1=Enabled
a - Annual Test Fail Alarm
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

286

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62E
Function Type: Set CAP0 Probe Conductive Boot Flag
Command Format:
Display: S62ETTc
Computer: s62ETTc

Version 3
Inquire:
I62ETT
i62ETT

Typical Response Message, Display Format:

I62ETT
JAN 22, 1996

3:19 PM

CAP0 PROBE CONDUCTIVE BOOT FLAG
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

CAP0 CONDUCTIVE BOOT:
YES

Typical Response Message, Computer Format:
i62ETTYYMMDDHHmmTTc...
TTc&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
c - CAP0 Conductive Boot Flag
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

287

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 62F
Function Type: Set Mag Probe Float Size
Command Format:
Display: S62FTTf
Computer: s62FTTf

Version 3
Inquire:
I62FTT
i62FTT

Typical Response Message, Display Format:

I62FTT
JAN 22, 1996

3:19 PM

MAG PROBE FLOAT SIZE
TANK
1
2


PRODUCT LABEL
REGULAR UNLEADED
PREMIUM

FLOAT SIZE:
4.0 IN
4.0 IN PS

Typical Response Message, Computer Format:
i62FTTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Mag Probe Float Size
0=4.0"
1=2.0"
2=3.0"
3=1.0"
4=4.0" Phase Separation
9=CUSTOM
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

(Added in V22)
(Added in V30)
(Added in V22)

288

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 630
Function Type: Set Tank Leak Test Notify
Command Format:
Display: S630TTf
Computer: s630TTf

Version 3
Inquire:
I630TT
i630TT

Typical Response Message, Display Format:

I630TT
JAN 22, 1996

3:20 PM

IN-TANK LEAK TEST NOTIFY
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

TANK TEST NOTIFY:
OFF

Typical Response Message, Computer Format:
i630TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Tank Leak Test Notify
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

289

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 631
Function Type: Set Tank Leak Test Averaging
Command Format:
Display: S631TTap
Computer: s631TTap

Version 5
Inquire:
I631TT
i631TT

Typical Response Message, Display Format:

I631TT
JAN 22, 1996

3:20 PM

TANK LEAK TEST AVERAGING
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

ANNUAL
OFF

PERIODIC
OFF

Typical Response Message, Computer Format:
i631TTYYMMDDHHmmTTap...
TTap&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
a - Annual Leak Test Averaging
0=OFF
1=ON
p - Periodic Leak Test Averaging
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

290

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 632
Function Type: Set Tank Test Siphon Break
Command Format:
Display: S632TTf
Computer: s632TTf

Version 5
Inquire:
I632TT
i632TT

Typical Response Message, Display Format:

I632TT
JAN 22, 1996

3:20 PM

TANK TEST SIPHON BREAK
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

SIPHON BREAK
OFF

Typical Response Message, Computer Format:
i632TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Tank Test Siphon Break
0=OFF
1=ON
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

291

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 633
Function Type: Set Leak Test Report Type
Command Format:
Display: S63300f
Computer: s63300f

Version 9
Inquire:
I63300
i63300

Typical Response Message, Display Format:

I63300
JAN 22, 1996

3:20 PM

LEAK TEST REPORT FORMAT: NORMAL

Typical Response Message, Computer Format:
i63300YYMMDDHHmmf&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Leak test Report Type:
0=Normal
1=Enhanced
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

292

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 634
Function Type: Set Tank HRM Reconciliation Warning Limit
Command Format:
Display: S634TTGGGGGG
Computer: s634TTFFFFFFFF
Notes:
1.
2.
3.

Version 110
Inquire:
I634TT
i634TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - HRM Reconciliation Warning Limit, Gallons (Decimal)
FFFFFFFF - HRM Reconciliation Warning Limit, Gallons (ASCII Hex IEEE
float)

Typical Response Message, Display Format:

I634TT
JAN 22, 1996

3:20 PM

RECONCILIATION WARNING LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
50

Typical Response Message, Computer Format:
i634TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
FFFFFFFF - HRM Reconciliation Warning Limit, Gallons (ASCII Hex IEEE
float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

293

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 635
Function Type: Set Tank HRM Reconciliation Alarm Limit
Command Format:
Display: S635TTGGGGGG
Computer: s635TTFFFFFFFF
Notes:
1.
2.
3.

Version 110
Inquire:
I635TT
i635TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - HRM Reconciliation Alarm Limit, Gallons (Decimal)
FFFFFFFF - HRM Reconciliation Alarm Limit, Gallons (ASCII Hex IEEE
float)

Typical Response Message, Display Format:

I635TT
JAN 22, 1996

3:20 PM

RECONCILIATION ALARM LIMIT
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
90

Typical Response Message, Computer Format:
i635TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
FFFFFFFF - HRM Reconciliation Alarm Limit, Gallons (ASCII Hex IEEE
float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

294

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 636
Function Type: Set Tank Periodic Leak Test Minimum Volume
Command Format:
Display: S636TTGGGGGG
Computer: s636TTFFFFFFFF
Notes:
1.
2.
3.

Version 14
Inquire:
I636TT
i636TT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Periodic Test Minimum Volume, Gallons (Decimal)
FFFFFFFF - Periodic Test Minimum Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I636TT
JAN 22, 1996

3:19 PM

PERIODIC LEAK TEST MIN VOLUME
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

GALLONS
3000

Typical Response Message, Computer Format:
i636TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Periodic Test Minimum Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

295

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 639
Function Type: Set Tank AccuChart End Shape Type and Factor
Command Format:
Display: S639TTSU.t
Computer: s639TTSFFFFFFFF
Notes:
1.
2.

3.
4.

Version 115
Inquire:
I639TT
i639TT

TT - Tank Number (Decimal, 00=all)
S - End Shape Type
0=None
1=Flat
2=Hemispheric
3=Other (requires factor)
U.t - End Shape Factor, Units and tenths (Decimal, 0.0-1.0)
FFFFFFFF - End Shape Factor (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I639TT
JUL 29, 1997 9:08 AM
1
REGULAR UNLEADED
END FACTOR: OTHER
END VALUE: 0.1

Typical Response Message, Computer Format:
i639TTYYMMDDHHmmTTSFFFFFFFF...
TTSFFFFFFFF&&CCCC
Notes:
1.
2.
3.

4.
5.
6.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
S - End Shape Type
0=None
1=Flat
2=Hemispheric
3=Other (requires factor)
FFFFFFFF - End Shape Factor (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

296

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 63A
Version 22
Function Type: Set Tank Low Level Threshold for Sequential Line Manifold
Command Format:
Display: S63ATTPP.hh
Computer: s63ATTFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I63ATT
i63ATT

TT - Tank Number (Decimal, set for primary tank)
PP.hh - Low Level Pump Threshold, Percent and hundredths (Decimal)
FFFFFFFF - Low Level Pump Threshold, Percent (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I63A00
JUN 1, 2001

8:07 AM

LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

PUMP THRESHOLD
10.00%

Typical Response Message, Computer Format:
i79800YYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCC

-

Current Date and Time
Tank Number (Decimal, set for primary tank)
Low Level Pump Threshold, Percent (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

297

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 63B
Function Type: Set Tank 50 Point Heights and Volumes
Command Format:
Display: S63BTTnnffIII.hhGGGGGG...ffIII.hhGGGGGG
or: S63BTTnnffII.h, GGGG, ...ffII.h, GGGG
Computer: s63BTTnnffHHHHHHHHVVVVVVVV...ffHHH...
Notes:
1.
2.
3.
4.
5.
6.
7.

Version 26
Inquire:
I63BTT
i63BTT

Set command is only valid if Tank Chart Security is disabled
nn - Number of Height/Volume Pairs to Follow (Decimal). A maximum
of 14 pairs can be set per command to avoid overflowing the
buffer
ff - Added/Remove Pair Flag (Hex):
01=Added Height/Volume Pair
02=Remove Height/Volume Pair
III.hh - Height Inches and Hundreds (Decimal)
GGGGGG - Volume, Gallons (Decimal)
HHHHHH - Height, Inches (ASCII Hex IEEE float)
VVVVVVVV - Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I63BTT
SEP 16, 2004

3:15 PM

TANK 50 POINT HEIGHTS AND VOLUMES
T 1: REGULAR UNLEADED
TANK CAPACITY
: 10000
CONSOLE SERIAL NUMBER:
xxxxxxxxxxxxxxxxxxxx
PROBE S/N
: yyyyyy
WEIGHTS AND MEASURES:
zzzzzzzzzzzzzzzzzzzz
DIAMETER
96.00
PAIR
1
2
3
4
5
45
46
47
48
49


HEIGHT
94.08
92.16
90.24
88.32
86.44
:
:
9.60
7.68
5.76
3.84
1.92

FULL VOLUME
10000
VOLUME
9800
9600
9400
9200
9000
1000
800
600
400
200

Part No. 576013-635, Revision AA

298

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 63B Notes: (Continued)
Typical Response Message, Computer Format:
i63BTTYYMMDDHHmmTTfccccccccxxxxxxxxxxxxxxxxxxxxyyyyyyzzzzzzzzzzzzzzzzzzzz...
ddddddddffffffffnnHHHHHHHHVVVVVVVV...
HHHHHHHHVVVVVVVV...
TTfccccccccxxxxxxxxxxxxxxxxxxxxyyyyyyzzzzzzzzzzzzzzzzzzzz...
ddddddddffffffffnnHHHHHHHHVVVVVVVV...
HHHHHHHHVVVVVVVV&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Tank Chart Security Flag
1=enabled
0=disabled

The following 4 fields marked with an asterisk are only present if Tank Chart
Security is enabled.
4.
5.
6.
7.

cccccccc
x..x
yyyyyy
z..z

-

* Tank Capacity, Gallons (ASCII Hex IEEE float)
* Console Serial Number (20 ASCII characters [20h-7Eh])
* Probe Serial Number (Decimal)
* Weights and Measures Office (20 ASCII characters [20h7Eh])

8.
9.
10.
11.
12.
13.
14.

dddddddd
ffffffff
nn
HHHHHHHH
VVVVVVVV
&&
CCCC

-

Tank Diameter, Inches (ASCII Hex IEEE float)
Full Volume, Gallons (ASCII Hex IEEE float)
Number of Height/Volume Pairs to Follow (Hex)
Height, Inches (ASCII Hex IEEE float)
Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

299

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 63C
Function Type: Set Tank 50 Point Full Volume
Command Format:
Display: S63CTTGGGGGG
Computer: s63CTTVVVVVVVV
Notes:
1.
2.
3.

Version 26
Inquire:
I63CTT
i63CTT

TT - Tank Number (Decimal, 00=all)
GGGGGG - Volume, Gallons (Decimal)
VVVVVVVV - Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I63CTT
SEP 16, 2004

3:15 PM

TANK 50 POINT FULL VOLUME
TANK
1


PRODUCT LABEL
REGULAR UNLEADED

VOLUME
100000

Typical Response Message, Computer Format:
i63CTTYYMMDDHHmmnnTTVVVVVVVV...
TTVVVVVVVV&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
VVVVVVVV
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

300

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 63D
Function Type: Set Tank Vapor Loss Factor
Command Format:
Display: S63DTTo.oo
Computer: s63DTToooooooo
Notes:
1.
2.
3.

Version 29
Inquire:
I63DTT
i63DTT

TT - Tank Number (Decimal, 00=all)
o.oo - Vapor Loss Factor, Percent(Decimal, 0.00 B 0.20)
oooooooo - Vapor Loss Factor, Percent(ASCII Hex IEEE Float 0.00B0.20)

Typical Response Message, Display Format:

I63D00
APR 10, 2007

10:15 AM

TANK VAPOR LOSS FACTOR
TANK
1
2
3


PRODUCT LABEL
REGULAR
PREMIUM
DIESEL

FACTOR
0.14%
0.15%
0.00%

Typical Response Message, Computer Format:
i63DTTYYMMDDHHmmNNTToooooooo...
TToooooooo&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
NN
TT
oooooooo
&&
CCCC

-

Current Date and Time
Number of tank entries to follow(Decimal)
Tank Number (Decimal, 00=all)
Vapor Loss Factor, Percent(ASCII Hex IEEE Float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

301

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 642
Function Type: Set Tank Water Alarm Filter Level
Command Format:
Display: S642TTf
Computer: s642TTf
Notes:
1.
2.

Version 31
Inquire:
I642TT
i642TT

TT - Tank Number (Decimal, 00=all)
f - Water alarm filter level

Typical Response Message, Display Format:

I64200
JAN 22, 2010

3:12 PM

WATER ALARM FILTER LEVEL
TANK
1
2
3


PRODUCT LABEL
REGULAR
MID GRADE
PREMIUM

LOW
MEDIUM
HIGH

Typical Response Message, Computer Format:
i642TTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal, 00=all)
f - Tank Water Alarm Filter Level
1 = Low
2 = Medium
3 = High
4 = Off
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

302

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 648
Function Type: Set Probe Water Minimum
Command Format:
Display: S648TTI.hhh
Computer: s648TTFFFFFFFF
Notes:
1.
2.
3.

Version 33
Inquire:
I648TT
i648TT

TT - Tank Number (Decimal, 00=all)
I.hhh - Water Minimum, Inches and thousandths (Decimal)
FFFFFFFF - Tank Number (Decimal, 00=all)

Typical Response Message, Display Format:

I64800
JAN 22, 2012

3:12 PM

WATER MINIMUM
TANK
1


PRODUCT LABEL
REGULAR

INCHES
0.633

Typical Response Message, Computer Format:
i648TTYYMMDDHHmmTTFFFFFFFF...TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Probe Offset, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

303

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 64B
Function Type: Set Tank Water Alarm Filter Delay
Command Format:
Display: S64BTTf
Computer: s64BTTf
Notes:
1.
2.
3.

Version 33
Inquire:
I64BTT
i64BTT

TT - Tank Number (Decimal, 00=all)
f - Water alarm delay level
The set command is only operational for the water alarm filter level OFF.
For filter levels Low, Medium and High the delay time is fixed at 180
seconds.

Typical Response Message, Display Format:

I64B00
JAN 22, 2010

3:12 PM

WATER ALARM DELAY LEVEL
TANK
1
2
3


PRODUCT LABEL
REGULAR
MID GRADE
PREMIUM

30 S
120 S
180 S

Typical Response Message, Computer Format:
i64BTTYYMMDDHHmmTTf...
TTf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
TT - Tank Number (Decimal)
f - Tank Water Alarm Filter Delay
1 = 30 seconds
2 = 60 seconds
3 = 90 seconds
4 = 120 seconds
5 = 150 seconds
6 = 180 seconds
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

304

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 651
Function Type: Set Tank Max or Label Alarm Threshold
Command Format:
Display: S651TTffffff
Computer: s651TTFFFFFFFF

Version 33
Inquire:
I651TT
i651TT

Typical Response Message, Display Format:

I65100
JAN 22, 2012

3:12 PM

TANK MAX OR LABEL ALARM THRESHOLD
TANK
1


PRODUCT LABEL
REGULAR

GALLONS
9000

Typical Response Message, Computer Format:
i651TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Max or Label Threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

305

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 652
Function Type: Set Tank High Product Alarm Threshold
Command Format:
Display: S652TTffffff
Computer: s652TTFFFFFFFF

Version 33
Inquire:
I652TT
i652TT

Typical Response Message, Display Format:

I65200
JAN 22, 2012

3:12 PM

TANK HIGH PRODUCT ALARM THRESHOLD
TANK
1


PRODUCT LABEL
REGULAR

% MAX VOLUME
97

Typical Response Message, Computer Format:
i652TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
High Product Threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

306

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 653
Function Type: Set Tank Overfill Alarm Threshold
Command Format:
Display: S653TTffffff
Computer: s653TTFFFFFFFF

Version 33
Inquire:
I653TT
i653TT

Typical Response Message, Display Format:

I65300
JAN 22, 2012

3:12 PM

TANK OVERFILL ALARM THRESHOLD
TANK
1


PRODUCT LABEL
REGULAR

% MAX VOLUME
95

Typical Response Message, Computer Format:
i653TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Overfill Threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

307

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 654
Function Type: Set Tank Delivery Needed Alarm Threshold
Command Format:
Display: S654TTffffff
Computer: s654TTFFFFFFFF

Version 33
Inquire:
I654TT
i654TT

Typical Response Message, Display Format:

I65400
JAN 22, 2012

3:12 PM

TANK DELIVERY NEEDED ALARM THRESHOLD
TANK
1


PRODUCT LABEL
REGULAR

% MAX VOLUME
15

Typical Response Message, Computer Format:
i654TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Delivery Needed Threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

308

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 655
Function Type: Set Tank Low Product Alarm Threshold
Command Format:
Display: S655TTffffff
Computer: s655TTFFFFFFFF

Version 33
Inquire:
I655TT
i655TT

Typical Response Message, Display Format:

I65500
JAN 22, 2012

3:12 PM

TANK LOW PRODUCT ALARM THRESHOLD
TANK
1


PRODUCT LABEL
REGULAR

INCHES
12.5

Typical Response Message, Computer Format:
i655TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Low Product Threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

309

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 680
Function Type: Fuel Management General Setup Inquiry

Version 6

Command Format:
Display: I680TT
Computer: Computer format is not supported for this command
Typical Response Message, Display Format:

I680TT
JAN 22, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:20 PM
1....
2....
3....
4....

FUEL MANAGEMENT SETUP
DELIVERY WARN DAYS: 3.5
AUTO PRINT:
10:00 AM
FUEL MANAGEMENT AVERAGE SALES (GALLONS)
REGULAR UNLEADED
SUN
MON
TUE
2696 2075 2602


( TANK 1 )
WED
THR
FRI
2046 2471 2805

Part No. 576013-635, Revision AA

SAT
2824

310

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 681
Function Type: Set Fuel Management Delivery Needed Warning
Command Format:
Display: S68100DD.hh
Computer: s68100FFFFFFFF
Notes:
1.
2.

Version 6
Inquire:
I68100
i68100

DD.hh - Delivery Needed Warning, Days and hundredths (Decimal)
FFFFFFFF - Delivery Needed Warning, Days (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I68100
JAN 22, 1996

3:20 PM

FUEL MANAGEMENT DELIVERY NEEDED WARNING DAYS
DELIVERY WARN DAYS:


2.50

Typical Response Message, Computer Format:
i68100YYMMDDHHmmFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
FFFFFFFF
&&
CCCC

-

Current Date and Time
Delivery Needed Warning, Days (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

311

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 682
Function Type: Set Fuel Management Automatic Report Print Time
Command Format:
Display: S68200hhmm
Computer: s68200hhmm

Version 6
Inquire:
I68200
i68200

Typical Response Message, Display Format:

I68200
JAN 22, 1996

3:21 PM

FUEL MANAGEMENT AUTOMATIC REPORT PRINT TIME
AUTO PRINT: 10:00 AM

Typical Response Message, Computer Format:
i68200YYMMDDHHmmhhmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
hhmm
&&
CCCC

-

Current Date and Time
Report Printout Time (hours, minutes; EE00=disabled)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

312

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 683
Function Type: Set Fuel Management Average Daily Sales
Command Format:
Display: S683TTDVVVVVV
Computer: s683TTDvvvvvvvv
Notes:
1.
2.
3.
4.

Version 6
Inquire:
I683TT
i683TT

TT - Tank Number for any Tank Containing the Product
D - Day for which to Program the Average Sales Volume (0=All
Days, 1=Sunday, 2=Monday,...7=Saturday)
VVVVVV - Average Sales for the Day, Gallons (Decimal, Only one day is
programmed per serial command)
vvvvvvvv - Average Sales for the Day, Gallons (ASCII Hex IEEE float,
Only one day is programmed per serial command)

Typical Response Message, Display Format:

I683TT
JAN 22, 1996

3:21 PM

FUEL MANAGEMENT AVERAGE SALES (GALLONS)
REGULAR UNLEADED
SUN
MON
TUE
2696 2075 2602


( TANK 1 )
WED
THR
FRI
2046 2471 2805

SAT
2824

Typical Response Message, Computer Format:
i683TTYYMMDDHHmmNNTTpSSSSSSSSMMMMMMMMTTTTTTTTWWWWWWWW
RRRRRRRRFFFFFFFFssssssss...
NNTTpSSSSSSSSMMMMMMMMTTTTTTTTWWWWWWWW
RRRRRRRRFFFFFFFFssssssss&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
NN
TTp
SSSSSSSS
MMMMMMMM
TTTTTTTT
WWWWWWWW
RRRRRRRR
FFFFFFFF
ssssssss
&&
CCCC

-

Current Date and Time
Number of Tank/Product Sets (TTp) to Follow (Hex)
Tank Number (decimal) and Product Code (ASCII character)
Avg Sales on Sundays (ASCII Hex IEEE float)
Avg Sales on Mondays (ASCII Hex IEEE float)
Avg Sales on Tuesdays (ASCII Hex IEEE float)
Avg Sales on Wednesdays (ASCII Hex IEEE float)
Avg Sales on Thursdays (ASCII Hex IEEE float)
Avg Sales on Fridays (ASCII Hex IEEE float)
Avg Sales on Saturdays (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

313

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.5 SENSOR SETUP
Function Code: 701
Function Type: Set Liquid Sensor Configuration
Command Format:
Display: S701SSf
Computer: s701SSf

Version 1
Inquire:
I701SS
i701SS

Typical Response Message, Display Format:

I701SS
JAN 28, 1995 10:39 AM
LIQUID CONFIGURATION
DEVICE
1


LABEL
LIQUID SENSOR #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i701SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Liquid Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

314

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 702
Function Type: Set Liquid Sensor Location Label
Command Format:
Display: S702SSaaaaaaaaaaaaaaaaaaaa
Computer: s702SSaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I702SS
i702SS

Typical Response Message, Display Format:

I702SS
JAN 28, 1995 10:39 AM
LIQUID LABEL
DEVICE
1


LABEL
LIQUID SENSOR #1

Typical Response Message, Computer Format:
i702SSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Liquid Sensor Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

315

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 703
Function Type: Set Liquid Sensor Type
Command Format:
Display: S703SSt
Computer: s703SSt

Version 1
Inquire:
I703SS
i703SS

Typical Response Message, Display Format:

I703SS
JAN 28, 1995 10:40 AM
LIQUID TYPE
SENSOR
1


LOCATION
LIQUID SENSOR #1

TYPE
TRI-STATE (SINGLE FLOAT)

Typical Response Message, Computer Format:
i703SSYYMMDDHHmmSSt...
SSt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Liquid Sensor Number (Decimal, 00=all)
t - Liquid Sensor Type:
1=Tri-State
2=Normally Closed
3=Dual Float Hydrostatic
4=Dual Float Discriminating
5=Dual Float High Vapor
6=Interceptor Sensor
7=DW Sump 2-1 Sensor
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

316

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 704
Function Type: Set Liquid Sensor Category
Command Format:
Display: S704SSc
Computer: s704SSc

Version 2
Inquire:
I704SS
i704SS

Typical Response Message, Display Format:

I704SS
JAN 28, 1995 10:40 AM
LIQUID CATEGORY
SENSOR
1


LOCATION
LIQUID SENSOR #1

TYPE
OTHER

Typical Response Message, Computer Format:
i704SSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Liquid Sensor Number (Decimal, 00=all)
c - Liquid Sensor Category:
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

317

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 706
Function Type: Set Vapor Sensor Configuration
Command Format:
Display: S706SSf
Computer: s706SSf

Version 1
Inquire:
I706SS
i706SS

Typical Response Message, Display Format:

I706SS
JAN 28, 1995 10:40 AM
VAPOR CONFIGURATION
DEVICE
1


LABEL
VAPOR SENSOR #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i706SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Vapor Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

318

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 707
Function Type: Set Vapor Sensor Location Label

Version 1

Command Format:
Display: S707SSaaaaaaaaaaaaaaaaaaaa
Computer: s707SSaaaaaaaaaaaaaaaaaaaa

Inquire:
I707SS
i707SS

Typical Response Message, Display Format:

I707SS
JAN 28, 1995 10:40 AM
VAPOR LABEL
DEVICE
1


LABEL
VAPOR SENSOR #1

Typical Response Message, Computer Format:
SOH>i707SSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Vapor Sensor Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

319

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 708
Function Type: Set Vapor Sensor Alarm Threshold
Command Format:
Display: S708SSVVVVVV
Computer: s708SSFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I708SS
i708SS

SS - Vapor Sensor Number (Decimal, 00=all)
VVVVVV - Vapor alarm threshold (Decimal)
FFFFFFFF - Vapor alarm threshold (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I708SS
JAN 28, 1995 10:41 AM
VAPOR ALARM THRESHOLD
SENSOR
1


LOCATION
VAPOR SENSOR #1

THRESHOLD
100000

Typical Response Message, Computer Format:
i708SSYYMMDDHHmmSSFFFFFFFF...
SSFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFFFFFF
&&
CCCC

-

Current Date and Time
Vapor Sensor Number (Decimal, 00=all)
Vapor alarm threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

320

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 709
Function Type: Set Vapor Sensor Category
Command Format:
Display: S709SSt
Computer: s709SSt

Version 2
Inquire:
I709SS
i709SS

Typical Response Message, Display Format:

I709SS
JAN 28, 1995 10:40 AM
VAPOR CATEGORY
SENSOR
1


LOCATION
VAPOR SENSOR #1

CATEGORY
OTHER

Typical Response Message, Computer Format:
i709SSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Vapor Sensor Number (Decimal, 00=all)
c - Vapor Sensor Category:
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

321

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 711
Function Type: Set Groundwater Sensor Configuration
Command Format:
Display: S711SSf
Computer: s711SSf

Version 1
Inquire:
I711SS
i711SS

Typical Response Message, Display Format:

I711SS
JAN 28, 1995 10:41 AM
GROUNDWATER CONFIGURATION
DEVICE
1


LABEL
GROUNDWATER #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i711SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Groundwater Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

322

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 712
Function Type: Set Groundwater Sensor Location Label
Command Format:
Display: S712SSaaaaaaaaaaaaaaaaaaaa
Computer: s712SSaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I712SS
i712SS

Typical Response Message, Display Format:

I712SS
JAN 28, 1995 10:41 AM
GROUNDWATER LABEL
DEVICE
1


LABEL
GROUNDWATER #1

Typical Response Message, Computer Format:
i712SSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Groundwater Sensor Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

323

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 713
Function Type: Set Groundwater Sensor Category
Command Format:
Display: S713SSt
Computer: s713SSt

Version 2
Inquire:
I713SS
i713SS

Typical Response Message, Display Format:

I713SS
JAN 28, 1995 10:41 AM
GROUNDWATER CATEGORY
SENSOR
1


LOCATION
GROUNDWATER #1

CATEGORY
OTHER

Typical Response Message, Computer Format:
SOH>i713SSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Groundwater Sensor Number (Decimal, 00=all)
c - Groundwater Sensor Category:
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

324

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 721
Function Type: Set Smart Sensor Configuration
Command Format:
Display: S721SSc
Computer: s721SSc
Notes:
1.
2.
3.

Version 24
Inquire:
I721SS
i721SS

Smart Sensor card must be installed
SS - Smart Sensor number, 00=all sensors
c - configured
0=off
1=on

Typical Response Message, Display Format:

I721SS
JUN 1, 2002

8:07 AM

SMART SENSOR CONFIGURATION
DEVICE
01
02
03


LABEL
FP 1-2
FP 3-4
FP 5-6

CONFIGURED
ON
ON
OFF

Typical Response Message, Computer Format:
i721nnYYMMDDHHnnYYMMDDHHmmSSc...SSc&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor number
c - Configured
0=off
1=on
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

325

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 722
Function Type: Set Smart Sensor Label
Command Format:
Display: S722SSaaaaaaaaaaaaaaaaaaaa
Computer: s722SSaaaaaaaaaaaaaaaaaaaa
Notes:
1.
2.
3.
4.

Version 24
Inquire:
I722SS
i722SS

Smart Sensor card must be installed
If SS=00, only configured sensors are used
SS - Smart Sensor number, 00=all sensors
a - 20 ASCII characters [20h-7Eh]

Typical Response Message, Display Format:

I72200
JUN 1, 2002

8:07 AM

SMART SENSOR LABEL
DEVICE
01
02
03


LABEL
FP 1-2
FP 3-4
FP 5-6

Typical Response Message, Computer Format:
i722SSYYMMDDHHSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Smart Sensor number
20 ASCII characters [20h-7Eh]
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

326

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 723
Function Type: Set Smart Sensor Category
Command Format:
Display: S723sscc
Computer: s723sscc
Notes:
1.
2.
3.
4.
5.

Version 25
Inquire:
I723ss
i723ss

Smart Sensor card must be installed
If category is known, it cannot be changed to another known type
If ss=00, only configured sensors are used
ss - Smart Sensor number, 00=all sensors
cc - category
00=unknown
01=rotary air flow meter
02=vapor pressure sensor
03=mag sensor
04=vac Sensor
05=atmospheric sensor
08=vapor valve

Typical Response Message, Display Format:

I72300
JUN 1, 2002

8:07 AM

SMARTSENSOR ASSIGNMENT
SENSOR#
01
02
03


LABEL
FP 1-2
FP 3-4
FP 5-6

CATEGORY
VAPOR PRESSURE
AIR FLOW METER
AIR FLOW METER

Typical Response Message, Computer Format:
i723ssYYMMDDHHmmsscc...
sscc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
ss - Smart Sensor number
cc - category
00=unknown
01=rotary air flow meter
02=vapor pressure sensor
03=mag sensor
04=vac Sensor
05=atmospheric sensor
08=vapor valve
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

(Version 29)

327

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 727
Function Type: Set MAG Sensor Alarm Upgrade Delay
Command Format:
Display: S727SSHHHH
Computer: s727SSHHHH
Notes:
1.
2.
3.

Version 24
Inquire:
I727SS
i727SS

Only responds to Smart Sensors that are of type Mag Sensor.
SS - Smart Sensor Number (Decimal, 00=all)
HHHH - MAG Sensor Alarm Upgrade Delay, Hours (ASCII Decimal)

Typical Response Message, Display Format:

I727SS
JAN 22, 2003

3:18 PM

MAG SENSOR ALM UPGRADE DELAY
SENSOR LABEL
1
STP SUMP 1


DELAY
120

Typical Response Message, Computer Format:
i727SSYYMMDDHHmmSSFFFF...
SSFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFF
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Alarm Upgrade Delay (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

328

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 728
Function Type: Set MAG Sensor Alarm Threshold
Command Format:
Display: S728SSAAxxx.xx
Computer: sXXXSSAAFFFFFFFF
Notes:
1.
2.
3.
4.
5.

Only responds
SS
AA
xxx.xx
FFFFFFFF

Version 24
Inquire:
I728SS
i728SS

when the Smart Sensor is a Mag Sensor type.
- Smart Sensor Number (ASCII Decimal, 00=all)
- Alarm Definition Record ID, (ASCII Decimal)
- Alarm Threshold, Inches or Deg. F (ASCII Decimal)
- Alarm Threshold, Inches or Deg. F (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I728SS
JAN 22, 2003

3:18 PM

MAG SENSOR ALARM THRESHOLD
s 1:SS-01
ID VALUE
1 FUEL HT
2 WATER HT
3 WATER HT
4 INSTALL POS
5 FLUID TEMP


THRESHOLD
>
2.0
>
5.0
> 10.0
>
5.0
< -40.0

Part No. 576013-635, Revision AA

ALARM
FUEL ALARM
WATER WARNING
WATER ALARM
INSTALL ALARM
TEMPERATURE WARNING

PROGRAMMABLE
YES
YES
YES
NO
YES

UPGRADE
NO
YES
NO
NO
NO

329

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 728 Notes: (Continued)
Typical Response Message, Computer Format:
i728SSYYMMDDHHmmSSrrPPaaFFppUUnnFFFFFFFFPPaaFFppUUnnFFFFFFFF...
SSrrPPaaFFppUUnnFFFFFFFFPPaaFFppUUnnFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.

6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
SS
rr
PP

-

aa -

FF
pp
UU
nn
FFFFFFFF
&&
CCCC

-

Current Date and Time
Smart Sensor Number (ASCII Decimal)
Number of alarm definition records to follow (ASCII Decimal)
Value for comparison (Hex)
01=Total Height
02=Fuel Height
03=Water Height
04=Install Position
05=Fluid Temperature
06=Board Temperature
Alarm to monitor (Hex)
01=Setup Data Warning
02=Communication Alarm
03=Sensor Fault Alarm
04=Fuel Warning
05=Fuel Alarm
06=Water Warning
07=Water Alarm
08=High Liquid Warning
09=High Liquid Alarm
0A=Low Liquid Warning
0B=Low Liquid Alarm
0C=Temperature Warning
0D=Relay Active
0E=Install Alarm
Compare Direction, 00="<", 01=">"
Programmable Threshold, 00="No", 01="Yes"
Alarm Upgrade, 00="No", 01="Yes"
Number of 8-character ASCII Hex Characters to follow
Alarm Threshold, Inches or Deg F (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

330

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 729
Function Type: Set Vacuum Sensor Pump Number
Command Format:
Display: S729SSAATT
Computer: s729SSAATT

Version 24
Inquire:
I729SS
i729SS

Typical Response Message, Display Format:

I729SS
FEB 14, 2004

10:15 PM

VACUUM SENSOR PUMP NUMBER
DEVICE
1


LABEL
VACUUM #1

PUMP NUMBER
Q 1:UNLEADED REGULAR

Typical Response Message, Computer Format:
i729SSYYMMDDHHmmSSAATT...
SSAATT&&CCCC
Notes:
1.
2.
3.

4.
5.
6.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
AA - Device Type (Decimal)
00=None
11=Output Relay
21=PLLD
26=WPLLD
TT - Device Number (Decimal)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

331

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 72A
Function Type: Set Vacuum Sensor Volume
Command Format:
Display: S72ASSGGGG.t
Computer: s72ASSFFFFFFFF
Notes:
1.
2.

Version 24
Inquire:
I72ASS
i72ASS

GGGG - Volume, Gallons and tenths (Decimal)
FFFFFFFF - Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I72ASS
FEB 14, 2004

10:15 PM

VACUUM SENSOR VOLUME
DEVICE
1


LABEL
VACUUM #1

VOLUME
200.0 GALLONS

Typical Response Message, Computer Format:
i72ASSYYMMDDHHmmSSFFFFFFFF...
SSFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFFFFFF
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Volume, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

332

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 72B
Function Type: Set Vacuum Sensor Relief Valve Present
Command Format:
Display: S72BSSf
Computer: s72BSSf

Version 24
Inquire:
I72BSS
i72BSS

Typical Response Message, Display Format:

I72BSS
FEB 14, 2004

10:15 PM

VACUUM SENSOR RELIEF VALVE PRESENT
DEVICE
1


LABEL
VACUUM #1

RELIEF VALVE
YES

Typical Response Message, Computer Format:
i72BSSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
f - Relief Valve Present
0=No Relief Valve
1=Relief Valve
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

333

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 72C
Function Type: Set Vacuum Sensor Relief Valve Pressure
Command Format:
Display: S72CSSPPPP
Computer: s72CSSFFFFFFFF
Notes:
1.
2.

Version 24
Inquire:
I72CSS
i72CSS

PPPP - Relief Valve Pressure, PSI (Decimal)
FFFFFFFF - Relief Valve Pressure, PSI (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I72CSS
FEB 14, 2004

10:15 PM

VACUUM SENSOR RELIEF VALVE PRESSURE
DEVICE
1


LABEL
VACUUM #1

RELIEF VALVE PRESSURE
-9.0 PSI

Typical Response Message, Computer Format:
i72CSSYYMMDDHHmmSSFFFFFFFF...
SSFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFFFFFF
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Relief Valve Pressure, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

334

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 741
Function Type: Set Type A (2 Wire CL) Sensor Configuration
Command Format:
Display: S741SSf
Computer: s741SSf

Version 2
Inquire:
I741SS
i741SS

Typical Response Message, Display Format:

I741SS
JAN 28, 1995 10:41 AM
2 WIRE CL CONFIGURATION
DEVICE
1


LABEL
2 WIRE CL SENSOR #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i741SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Type A Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

335

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 742
Function Type: Set Type A (2 Wire CL) Sensor Location Label
Command Format:
Display: S742SSaaaaaaaaaaaaaaaaaaaa
Computer: s742SSaaaaaaaaaaaaaaaaaaaa

Version 2
Inquire:
I742SS
i742SS

Typical Response Message, Display Format:

I742SS
JAN 28, 1995 10:41 AM
2 WIRE CL LABEL
DEVICE
1


LABEL
2 WIRE CL SENSOR #1

Typical Response Message, Computer Format:
i742SSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Type A Sensor Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

336

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 743
Function Type: Set Type A (2 Wire CL) Sensor Type
Command Format:
Display: S743SSt
Computer: s743SSt

Version 2
Inquire:
I743SS
i743SS

Typical Response Message, Display Format:

I743SS
JAN 28, 1995 10:41 AM
2 WIRE CL TYPE
SENSOR
1


LOCATION
2 WIRE CL SENSOR #1

TYPE
ULTRA 2

Typical Response Message, Computer Format:
i743SSYYMMDDHHmmSSt...
SSt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Type A Sensor Number (Decimal, 00=all)
t - Type A Sensor Type:
1=ULTRA 2
2=ULTRA 3
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

337

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 744
Function Type: Set Type A (2 Wire CL) Sensor Category
Command Format:
Display: S744SSa
Computer: s744SSa

Version 2
Inquire:
I744SS
i744SS

Typical Response Message, Display Format:

I743SS
JAN 28, 1995 10:41 AM
2 WIRE CL CATEGORY
SENSOR
1


LOCATION
2 WIRE CL SENSOR #1

CATEGORY
ANNULAR

Typical Response Message, Computer Format:
i744SSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Type A Sensor Number (Decimal, 00=all)
c - Type A Sensor Category:
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

338

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 746
Function Type: Set Type B (3 Wire CL) Sensor Configuration
Command Format:
Display: S746SSf
Computer: s746SSf

Version 2
Inquire:
I746SS
i746SS

Typical Response Message, Display Format:

I746SS
JAN 28, 1995 10:41 AM
3 WIRE CL CONFIGURATION
DEVICE
1


LABEL
3 WIRE CL SENSOR #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i746SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Type B Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

339

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 747
Function Type: Set Type B (3 Wire CL) Sensor Location Label
Command Format:
Display: S747SSaaaaaaaaaaaaaaaaaaaa
Computer: s747SSaaaaaaaaaaaaaaaaaaaa

Version 2
Inquire:
I742SS
i742SS

Typical Response Message, Display Format:

I747SS
JAN 28, 1995 10:41 AM
3 WIRE CL LABEL
DEVICE
1


LABEL
3 WIRE CL SENSOR #1

Typical Response Message, Computer Format:
i747SSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Type B Sensor Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

340

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 748
Function Type: Set Type B (3 Wire CL) Sensor Type
Command Format:
Display: S748SSt
Computer: s748SSt

Version 5
Inquire:
I748SS
i748SS

Typical Response Message, Display Format:

I748SS
JAN 28, 1995 10:41 AM
3 WIRE CL TYPE
SENSOR
1


LOCATION
3 WIRE CL SENSOR #1

TYPE
ULTRA/Z-1

Typical Response Message, Computer Format:
i748SSYYMMDDHHmmSSt...
SSt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal)
t - Sensor Type
1=ULTRA/Z-1
2=ULTRA/Z-1 HV
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

341

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 749
Function Type: Set Type B (3 Wire CL) Sensor Category
Command Format:
Display: S749SSa
Computer: s749SSa

Version 2
Inquire:
I749SS
i749SS

Typical Response Message, Display Format:

I749SS
JAN 28, 1995 10:41 AM
3 WIRE CL CATEGORY
SENSOR
1


LOCATION
3 WIRE CL SENSOR #1

CATEGORY
ANNULAR

Typical Response Message, Computer Format:
i749SSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Type B Sensor Number (Decimal, 00=all)
t - Type B Sensor Category:
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

342

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 74B
Function Type: Set Universal Sensor Configuration
Command Format:
Display: S74BSSf
Computer: s74BSSf

Version 4
Inquire:
I74BSS
i74BSS

Typical Response Message, Display Format:

I74BSS
JAN 28, 1995 10:41 AM
UNIVERSAL CONFIGURATION
DEVICE
1


LABEL
UNIVERSAL SENSOR #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i74BSSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

343

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 74C
Function Type: Set Universal Sensor Location Label
Command Format:
Display: S74CSSaaaaaaaaaaaaaaaaaaaa
Computer: s74CSSaaaaaaaaaaaaaaaaaaaa

Version 4
Inquire:
I74CSS
i74CSS

Typical Response Message, Display Format:

I74CSS
JAN 28, 1995 10:41 AM
UNIVERSAL LABEL
DEVICE
1


LABEL
UNIVERSAL SENSOR #1

Typical Response Message, Computer Format:
i74CSSYYMMDDHHmmSSaaaaaaaaaaaaaaaaaaaa...
SSaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
a
&&
CCCC

-

Current Date and Time
Sensor Number (Decimal)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

344

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 74D
Function Type: Set Universal Sensor Type
Command Format:
Display: S74DSSt
Computer: s74DSSt

Version 4
Inquire:
I74DSS
i74DSS

Typical Response Message, Display Format:

I74DSS
JAN 28, 1995 10:41 AM
UNIVERSAL TYPE
SENSOR
1


LOCATION
UNIVERSAL SENSOR #1

TYPE
ULTRA/Z-1

Typical Response Message, Computer Format:
i74DSSYYMMDDHHmmSSt...
SSt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal)
t - Sensor Type
1=TRI-STATE
2=NORMALLY CLOSED
3=DUAL DIFFERENTIATING
4=ULTRA 2
5=ULTRA 3
6=ULTRA/Z-1
7=ULTRA/Z-1 HV
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

345

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 74E
Function Type: Set Universal Sensor Category
Command Format:
Display: S74ESSa
Computer: s74ESSa

Version 4
Inquire:
I74ESS
i74ESS

Typical Response Message, Display Format:

I74ESS
JAN 28, 1995 10:41 AM
UNIVERSAL CATEGORY
SENSOR
1


LOCATION
UNIVERSAL SENSOR #1

CATEGORY
ANNULAR

Typical Response Message, Computer Format:
i74ESSYYMMDDHHmmSSc...
SSc&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor Number (Decimal)
c - Category
1=Other
2=Annular
3=Dispenser Pan
4=Monitoring Well
5=STP Sump
6=Piping Sump
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

346

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.6 VOLUMETRIC LINE LEAK SETUP
Function Code: 751
Function Type: Set Volumetric Line Leak Configuration
Command Format:
Display: S751PPf
Computer: s751PPf

Version 1
Inquire:
I751PP
i751PP

Typical Response Message, Display Format:

I751PP
MAR 26, 1996

1:53 PM

LINE LEAK CONFIGURATION
DEVICE
1


LABEL
REGULAR UNLEADED

CONFIGURED
ON

Typical Response Message, Computer Format:
i751PPYYMMDDHHmmPPf...
PPf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

347

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 752
Function Type: Set Volumetric Line Leak Tank Number
Command Format:
Display: S752PPtt
Computer: s752PPtt

Version 1
Inquire:
I752PP
i752PP

Typical Response Message, Display Format:

I752PP
MAR 26, 1996

1:53 PM

LINE LEAK TANK ASSIGNMENT
LINE LABEL
1 REGULAR UNLEADED


TANK
1

Typical Response Message, Computer Format:
i752PPYYMMDDHHmmPPtt...
PPtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
tt
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Tank number (00=not assigned)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

348

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 753
Function Type: Set Volumetric Line Leak 2 Inch Pipe Length
Command Format:
Display: S753PPLLL
Computer: s753PPFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I753PP
i753PP

PP - Pipeline Number (Decimal, 00=all)
LLL - 2" Pipe Length, Feet (Decimal)
FFFFFFFF - 2" Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I753PP
MAR 26, 1996
LINE LEAK

1:53 PM
2" INCH PIPING LENGTH

P 1:REGULAR UNLEADED
2" PIPING LENGTH: 250

Typical Response Message, Computer Format:
i753PPYYMMDDHHmmPPFFFFFFFF...
PPFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
2" Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

349

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 754
Function Type: Set Volumetric Line Leak 3 Inch Pipe Length
Command Format:
Display: S754PPLLL
Computer: s754PPFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I754PP
i754PP

PP - Pipeline Number (Decimal, 00=all)
LLL - 3" Pipe Length, Feet (Decimal)
FFFFFFFF - 3" Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I754PP
MAR 26, 1996
LINE LEAK

1:53 PM
3" INCH PIPING LENGTH

P 1:REGULAR UNLEADED
3" PIPING LENGTH:
0

Typical Response Message, Computer Format:
i754PPYYMMDDHHmmPPFFFFFFFF...
PPFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
3" Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

350

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 755
Function Type: Set Volumetric Line Leak Pump PSI
Command Format:
Display: S755PPppp
Computer: s755PPFFFFFFFF
Notes:
1.
2.
3.

Version 1
Inquire:
I755PP
i755PP

PP - Pipeline Number (Decimal, 00=all)
ppp - Pump Pressure, PSI (Decimal)
FFFFFFFF - Pump Pressure, PSI (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I755PP
MAR 26, 1996

1:53 PM

LINE LEAK PUMP PSI
P 1:REGULAR UNLEADED
PUMP PSI
: 27

Typical Response Message, Computer Format:
i755PPYYMMDDHHmmPPFFFFFFFF...
PPFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Pump Pressure, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

351

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 756
Function Type: Set Volumetric Line Leak Piping Material
Command Format:
Display: S756PPmm
Computer: s756PPmm

Version 1
Inquire:
I756PP
i756PP

Typical Response Message, Display Format:

I756PP
MAR 26, 1996

1:53 PM

LINE LEAK PIPING MATERIAL
P 1:REGULAR UNLEADED
PIPE TYPE: FIBERGLASS

Typical Response Message, Computer Format:
i756PPYYMMDDHHmmPPmm...
PPmm&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
mm - Piping Material:
01=Steel
02=Fiberglass
03=2-Wall Fiberglass
04=Flexible
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

352

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 757
Function Type: Set Volumetric Line Leak Shutdown Rate
Command Format:
Display: S757PPrr
Computer: s757PPrr

Version 1
Inquire:
I757PP
i757PP

Typical Response Message, Display Format:

I757PP
MAR 26, 1996

1:53 PM

LINE LEAK SHUTDOWN RATE
P 1:REGULAR UNLEADED
SHUTDOWN : 3.0 GAL/HR

Typical Response Message, Computer Format:
i757PPYYMMDDHHmmPPrr...
PPrr&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
rr - Line Leak Shutdown Rate:
01=3.00 Gal/Hr
02=0.20 Gal/Hr
03=0.10 Gal/Hr
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

353

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 758
Function Type: Set Volumetric Line Leak Pump Side Test
Command Format:
Display: S758PPss
Computer: s758PPss

Version 1
Inquire:
I758PP
i758PP

Typical Response Message, Display Format:

I758PP
MAR 26, 1996

1:53 PM

LINE LEAK PUMP SIDE TEST
P 1:REGULAR UNLEADED
PUMPSIDE TEST: ENABLED

Typical Response Message, Computer Format:
i758PPYYMMDDHHmmPPss...
PPss&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
ss - Line Leak Pump Side Test:
00=Disable
01=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

354

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 759
Function Type: Set Volumetric Line Leak Test Type & Start Time
Command Format:
Display: S759PPrrMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
Computer: s759PPrrMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm

(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=1)
M=2)
M=3)
M=4)
M=5)

Version 1
Inquire:
I759PP

i759PP

Typical Response Message, Display Format:

I759PP
MAR 26, 1996

1:53 PM

LINE LEAK TEST SETUP
- - - - - - - - - - - TEST ON DATE : ALL LINES
APR 1, 1996
START TIME : 2:15 PM
TEST RATE :0.20 GAL/HR

Typical Response Message, Computer Format:
i759PPYYMMDDHHmmPPrrMYYMMDDHHmm
MMWDHHmm
WDHHmm
DHHmm
HHmm
PPrrMYYMMDDHHmm&&CCCC
MMWDHHmm&&CCCC
WDHHmm&&CCCC
DHHmm&&CCCC
HHmm&&CCCC
Notes:
1.
2.
3.

(if
(if
(if
(if
(if
(if
(if
(if
(if
(if

M=1)
M=2)
M=3)
M=4)
M=5)
M=1)
M=2)
M=3)
M=4)
M=5)

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
rr - Volumetric Line Leak Test Type:
01=0.20 Gal/Hr
02=0.10 Gal/Hr

Part No. 576013-635, Revision AA

355

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 759 Notes: (Continued)
4.

M - Volumetric Line Leak Test Method:
1=On Date
2=Annually
3=Monthly
4=Weekly
5=Daily
- If M=1 ON DATE, YYMMDDHHmm:
YY =Year
MM =Month (01-12)
DD =Day
HHmm=Hour, Minute (EE00=Disabled)
- If M=2 ANNUALLY, MMWDHHmm:
MM =Month (01-12)
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=3 MONTHLY, WDHHmm:
W
=Week Number (1-4)
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=4 WEEKLY, DHHmm:
D
=Day (1=Monday, 2=Tuesday, . . . 7=Sunday)
HHmm=Hour, Minute (EE00=Disabled)
- If M=5 DAILY, HHmm:
HHmm=Hour, Minute (EE00=Disabled)

5.
6.

&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

356

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75A
Function Type: Set Line Leak Lockout Schedule (All Types)
Command Format:
Display: S75A00SHHmmHHmm
NsHHmmeHHmm
Computer: s75A00SHHmmHHmm
NsHHmmeHHmm

(if
(if
(if
(if

S=0)
S=1)
S=0)
S=1)

Version 1
Inquire:
I75A00
i75A00

Typical Response Message, Display Format:

I75A00
MAR 26, 1996

1:54 PM

LINE LEAK LOCKOUT SETUP
- - - - - - - - - - - LOCKOUT SCHEDULE
DAILY
START TIME: 10:45 PM
STOP TIME : 4:45 AM

Typical Response Message, Computer Format:
i75A00YYMMDDHHmmSHHmmHHmm
NsHHmmeHHmm
SHHmmHHmm&&CCCC
NsHHmmeHHmm&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

(if
(if
(if
(if

S=0)
S=1)
S=0)
S=1)

YYMMDDHHmm - Current Date and Time
S - Lockout Schedule Type:
- If S=0 (Daily):
HHmm=Start Lockout Time (Hours, minutes)
HHmm=End Lockout Time (Hours, minutes)
- If S=1 (Individual):
N
= Lockout Number (0=All Lockouts, 1..7)
s
= Start Lockout Day (1=Mon, 2=Tue, .., 7=Sun)
HHmm= Start Lockout Time (Hours, minutes)
e
= End Lockout Day (1=Mon, 2=Tue, .., 7=Sun)
HHmm= End Lockout Time (Hours, minutes)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

357

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75B
Function Type: Set Line Disable Alarm Assignments
Command Format:
Display: S75BPPAANNTTSS
Computer: s75BPPAANNTTSS

Version 2
Inquire:
I75BPP
i75BPP

Typical Response Message, Display Format:

I75BPP
MAR 26, 1996

1:54 PM

LINE LEAK SETUP REPORT
P 1:REGULAR UNLEADED
- NO ALARM ASSIGNMENTS 
Typical Response Message, Computer Format:
i75BPPYYMMDDHHmmPPnnAANNTTSS...
PPnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
PP
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Pipeline Number (Decimal, 00=all)
Number of Alarms to Follow
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

358

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75C
Function Type: Set Volumetric Line Leak Last Annual Test
Command Format:
Display: S75CPPYYMMDD
Computer: s75CPPYYMMDD

Version 2
Inquire:
I75CPP
i75CPP

Typical Response Message, Display Format:

I75CPP
MAR 26, 1996

1:54 PM

LINE LEAK LAST ANNUAL TEST
P 1:REGULAR UNLEADED
MAR 26, 1996

Typical Response Message, Computer Format:
i75CPPYYMMDDHHmmPPYYMMDD...
PPYYMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
YYMMDD
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Year, Month, Day of Last Annual Test
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

359

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75D
Function Type: Set Volumetric Line Leak Dispense Mode
Command Format:
Display: S75DPPf
Computer: s75DPPf

Version 4
Inquire:
I75DPP
i75DPP

Typical Response Message, Display Format:

I75DPP
MAR 26, 1996

1:54 PM

LINE LEAK DISPENSE MODE
LINE LABEL
1 REGULAR UNLEADED


DISPENSE MODE
STANDARD

Typical Response Message, Computer Format:
i75DPPYYMMDDHHmmPPf...
PPf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
f - Dispensing Mode:
1=Standard
2=Manifolded: Alternate
3=Manifolded: Sequential
4=Manifolded: All Pumps
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

360

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75E
Function Type: Set Volumetric Line Leak Fuel Type
Command Format:
Display: S75EPPss
Computer: s75EPPss

Version 4
Inquire:
I75EPP
i75EPP

Typical Response Message, Display Format:

I75EPP
MAR 26, 1996

1:54 PM

LINE LEAK FUEL TYPE
P 1:REGULAR UNLEADED
FUEL TYPE: GASOLINE

Typical Response Message, Computer Format:
i75PPYYMMDDHHmmPPss...
PPss&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
ss - Fuel Type:
00=Gasoline
01=Diesel
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

361

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 75F
Function Type: Set Volumetric Line Leak Wait Method
Command Format:
Display: S75FPPrr
Computer: s75FPPrr

Version 5
Inquire:
I7F7PP
i7F7PP

Typical Response Message, Display Format:

I75FPP
MAR 26, 1996

1:54 PM

LINE LEAK WAIT MODE
P 1:REGULAR UNLEADED
WAIT MODE: TEMP. MEAS.

Typical Response Message, Computer Format:
i75FPPYYMMDDHHmmPPrr...
PPrr&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
PP - Pipeline Number (Decimal, 00=all)
rr - Line Leak Wait Method:
1=Temperature Measurement
2=Volume Change Measurement
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

362

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 760
Function Type: Set Volumetric Line Leak Location Label
Command Format:
Display: S760PPaaaaaaaaaaaaaaaaaaaa
Computer: s760PPaaaaaaaaaaaaaaaaaaaa

Version 6
Inquire:
I760SS
i760SS

Typical Response Message, Display Format:

I760PP
MAR 26, 1996

1:52 PM

LINE LEAK LABEL
DEVICE
1


LABEL
REGULAR UNLEADED

Typical Response Message, Computer Format:
i760PPYYMMDDHHmmPPaaaaaaaaaaaaaaaaaaaa...
PPaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
a
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

363

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 761
Function Type: Set Volumetric Line Leak Blend Partner
Command Format:
Display: S761PPss
Computer: s761PPss

Version 7
Inquire:
I761PP
i761PP

Typical Response Message, Display Format:

I761PP
MAR 26, 1996 1:52 PM
LINE LABEL
P 1:REGULAR UNLEADED


NBP PARTNER
NONE

Typical Response Message, Computer Format:
i761PPYYMMDDHHmmPPss...
PPss&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
ss
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Pipline Number of Blend Partner (Decimal, 00=all)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

364

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7BC
Function Type: Set Line Disable Alarm Assignments II
Command Format:
Display: S7BCPPAANNTTSS
Computer: s7BCPPAANNTTSS

Version 19
Inquire:
I7BCPP
i7BCPP

Typical Response Message, Display Format:

I7BCPP
JAN 15, 1996 4:29 PM
LINE LEAK SETUP REPORT
P 1: LLD NUMBER 1
LINE LEAK
P 1:ANNUAL LINE FAIL

Typical Response Message, Computer Format:
i7BCPPYYMMDDHHmmPPnnAANNTTSS...
PPnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
PP
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Pipeline Number (Decimal, 00=all)
Number of Alarms to Follow (Hex)
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

365

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.7 PUMP SENSOR SETUP
Function Code: 771
Function Type: Set Pump Sensor Configuration
Command Format:
Display: S771SSf
Computer: s771SSf

Version 2
Inquire:
I771SS
i771SS

Typical Response Message, Display Format:

I771SS
MAR 27, 1996

5:49 PM

PUMP SENSE CONFIGURATION
DEVICE
1


LABEL
UNLEADED REGULAR

CONFIGURED
ON

Typical Response Message, Computer Format:
i771SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Pump Sensor Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

366

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 772
Function Type: Set Pump Sensor Tank Number
Command Format:
Display: S772SStt
Computer: s772SStt

Version 2
Inquire:
I772SS
i772SS

Typical Response Message, Display Format:

I772SS
MAR 27, 1996

5:49 PM

PUMP SENSOR TANK ASSIGNMENT
PUMP SENSOR
1


TANK
1

Typical Response Message, Computer Format:
i772SSYYMMDDHHmmSStt...
SStt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
tt
&&
CCCC

-

Current Date and Time
Pump Sensor Number (Decimal, 00=all)
Tank Number (Decimal, 00=not assigned)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

367

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 773
Function Type: Set Pump Sensor Dispense Mode
Command Format:
Display: S773SSf
Computer: s773SSf

Version 4
Inquire:
I773SS
i773SS

Typical Response Message, Display Format:

I773SS
MAR 27, 1996

5:50 PM

PUMP SENSOR DISPENSE MODE
PUMP SENSOR
1


MODE
MANIFOLDED: SEQUENTIAL

Typical Response Message, Computer Format:
i773SSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
SS - Pump Sensor Number (Decimal)
f - Dispense Mode:
1=Standard
2=Manifolded: Alternate
3=Manifolded: Sequential
4=Manifolded: All Pumps
5=Manifolded: Alternate-Height
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

368

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7DA
Function Type: Set Pump Sensor Alternate Modes
Auto Active Pump Switchover Enable
Command Format:
Display: S7DASSf
Computer: s7DASSf
Notes:
1.

Version 33

Inquire:
I7DASS
i7DASS

f - 0=disabled; 1=enabled

Typical Response Message, Display Format:

I7DASS
MAR 27, 2014

5:50 PM

PUMP SENSOR ALTERNATE MODE SWITCHOVER ENABLE
DEVICE LABEL
S 1:UNLEADED GASOLINE
S 2:UNLEADED GASOLINE


ENABLED
YES
NO

Typical Response Message, Computer Format:
i7DASSYYMMDDHHmmSSf...
SSf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Pump Sensor Number (Decimal, 00=all)
f - Auto Switchover Enabled:
0=No
1=Yes
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

369

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7DB
Function Type: Set Pump Sensor Alternate Mode
Auto Active Pump Switchover Volume Threshold
Command Format:
Display: S7DBSSGGGG
Computer: s7DBSSFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I7DBSS
i7DBSS

SS - Pump Sensor Number (Decimal, 00=all)
GGGG - Full Height Volume, Gallons (Decimal)
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7DBSS
MAR 27, 2014

5:50 PM

PUMP SENSOR ALTERNATE MODE SWITCHOVER THRESHOLD
DEVICE LABEL
1
REGULAR UNLEADED


GALLONS
200

Typical Response Message, Computer Format:
i7DBSSYYMMDDHHmmSSFFFFFFFF...
SSFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pump Sensor Number (Decimal, 00=all)
Switchover threshold, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

370

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7DC
Function Type: Set Pump Sensor Alternate-Height Mode
Auto Active Pump Switchover Height Threshold
Command Format:
Display: S7DCSShhhh.h
Computer: s7DCSSFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I7DCSS
i7DCSS

SS - Pump Sensor Number (Decimal, 00=all)
hhhh.h - Switchover Threshold, Inches and tenths (Decimal)
FFFFFFFF - Switchover Threshold, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7DCSS
MAR 27, 1996

5:50 PM

PUMP SENSOR ALTERNATE-HEIGHT MODE SWITCHOVER THRESHOLD
DEVICE LABEL
S 1:UNLEADED


INCHES
2.0

Typical Response Message, Computer Format:
i7DCSSYYMMDDHHmmSSFFFFFFFF...
SSFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pump Sensor Number (Decimal, 00=all)
Switchover threshold, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

371

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.8 PRESSURE LINE LEAK SETUP
Version 27
Function Code: 774
Function Type: Set Pressure Line Leak Continuous Handle Alarm Timeout
Command Format:
Display: S774QQtt
Computer: s774QQtt
Notes:
1.
2.

Inquire:
I774QQ
i774QQ

QQ - Pressure Line Leak sensor number (Decimal, 00=All)
tt - Continuous Handle Alarm Timeout (Decimal, in hours, 1-16)

Typical Response Message, Display Format:

I774QQ
SEP 16, 2006

3:15 PM

PLLD CONTINUOUS HANDLE ALARM TIMEOUT
LINE
Q 1:REGULAR UNLEADED


TIMEOUT
16 HOURS

Typical Response Message, Computer Format:
i774QQYYMMDDHHmmQQttQQtt...
QQtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
tt
&&
CCCC

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Continuous Handle Alarm Timeout (Decimal, in hours, 1-16)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

372

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 775
Version 23
Function Type: Set Pressure Line Leak Profile Line Test Leak Rate
Command Format:
Display: S775QQrr.rr
Computer: s775QQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I775QQ
i775QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
rr.rr - Profile Line Test Leak Rate, GPH (Decimal)
FFFFFFFF - Profile Line Test Leak Rate, GPH (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I775QQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK PROFILE LINE TEST LEAK RATE
LINE
Q 1:UNLEADED REGULAR


TEST LEAK RATE
3.00 GPH

Typical Response Message, Computer Format:
s775QQYYMMDDHHmmQQFFFFFFFF
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00 = all)
Profile Line Test Leak Rate, GPH (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

373

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 776
Version 23
Function Type: Set Pressure Line Leak Profile Line Test Reference Pressure
Command Format:
Display: S776QQppp.pp
Computer: s776QQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I776QQ
i776QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
ppp.pp - Profile Line Test Reference Pressure, PSI (Decimal)
FFFFFFFF - Profile Line Test Reference Pressure, PSI (ASCII Hex IEEE
float)

Typical Response Message, Display Format:

I776QQ
JAN 14, 1995

10:15 PM

PROFILE LINE TEST REFERENCE PRESSURE
LINE
Q 1:UNLEADED REGULAR


TEST REF PRESSURE
10.00 PSI

Typical Response Message, Computer Format:
s776QQYYMMDDHHmmQQFFFFFFFF
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
FFFFFFFF - Profile Line Test Reference Pressure, PSI (ASCII Hex IEEE
float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

374

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 777
Function Type: Set Pressure Line Leak Primary Pipe Diameter
Command Format:
Display: S777QQI.hh
Computer: s777QQFFFFFFFF
Notes:
1.
2.
3.

Version 23
Inquire:
I777QQ
i777QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
I.hh - Pipe Diameter, Inches and hundredths (Decimal)
FFFFFFFF - Pipe Diameter, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I777QQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK PRIMARY PIPE DIAMETER
LINE
Q 1:UNLEADED REGULAR


1ST LINE DIAMETER
1.75 INCHES

Typical Response Message, Computer Format:
s777QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Diameter, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

375

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 778
Function Type: Set Pressure Line Leak Secondary Pipe Diameter
Command Format:
Display: S778QQI.hh
Computer: s778QQFFFFFFFF
Notes:
1.
2.
3.

Version 23
Inquire:
I778QQ
i778QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
I.hh - Pipe Diameter, Inches and hundredths (Decimal)
FFFFFFFF - Pipe Diameter, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I778QQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK SECONDARY PIPE DIAMETER
LINE
Q 1:UNLEADED REGULAR


2ND LINE DIAMETER
1.75 INCHES

Typical Response Message, Computer Format:
s778QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Diameter, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

376

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 779
Function Type: Set Pressure Line Leak Primary Pipe Bulk Modulus
Command Format:
Display: S779QQBBBBB
Computer: s779QQFFFFFFFF
Notes:
1.
2.
3.

Version 23
Inquire:
I779QQ
i779QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
BBBBB - Pipe Bulk Modulus, PSI (Decimal)
FFFFFFFF - Pipe Bulk Modulus, PSI (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I779QQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK PRIMARY PIPE BULK MODULUS
LINE
Q 1:UNLEADED REGULAR


1ST BULK MODULUS
12000 PSI

Typical Response Message, Computer Format:
s779QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Bulk Modulus, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

377

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77A
Version 23
Function Type: Set Pressure Line Leak Secondary Pipe Bulk Modulus
Command Format:
Display: S77AQQBBBBB
Computer: s77AQQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I77AQQ
i77AQQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
BBBBB - Pipe Bulk Modulus, PSI (Decimal)
FFFFFFFF - Pipe Bulk Modulus, PSI (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I77AQQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK SECONDARY PIPE BULK MODULUS
LINE
Q 1:UNLEADED REGULAR


2ND BULK MODULUS
12000 PSI

Typical Response Message, Computer Format:
s77AQQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Bulk Modulus, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

378

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77B
Version 23
Function Type: Set Pressure Line Leak Thermal Expansion Coefficient
Command Format:
Display: S77BQQc.cccccc
Computer: s77BQQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I77BQQ
i77BQQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
c.cccccc - Thermal Expansion Coefficient (Decimal)
FFFFFFFF - Thermal Expansion Coefficient (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I77BQQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK THERMAL COEFFICIENT
LINE
Q 1:UNLEADED REGULAR


THERMAL COEFFICIENT
0.000700

Typical Response Message, Computer Format:
s77BQQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Thermal Expansion Coefficient (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

379

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77C
Function Type: Set Pressure Line Leak Low Pressure Shutoff
Command Format:
Display: S77CQQf
Computer: s77CQQf

Version 19
Inquire:
I77CQQ
i77CQQ

Typical Response Message, Display Format:

I77CQQ
JAN 24, 2000

2:54 PM

PRESSURE LINE LEAK LOW PRESSURE SHUTOFF
LINE
Q 1:REGULAR UNLEADED


LOW PRESSURE SHUTOFF
YES

Typical Response Message, Computer Format:
i77CQQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - Enabled/disabled flag
0=disabled (no)
1=enabled (yes)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

380

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77D
Function Type: Set Pressure Line Leak Altitude Pressure Offset
Command Format:
Display: S77DQQII.p
Computer: s77DQQFFFFFFFF
Notes:
1.
2.
3.
4.

Version 19
Inquire:
I77DQQ
i77DQQ

QQ - Pressure Line Leak sensor number (Decimal, 00=All)
II.p - Altitude Pressure Offset, PSI or KPA (Decimal)
FFFFFFFF - Altitude Pressure Offset, PSI or KPA (ASCII Hex IEEE float)
Value must be within the range of +5.0 to -5.0 PSI or 34.4
to -34.4 KPA

Typical Response Message, Display Format:

I77DQQ
JAN 1, 2000

1:44 AM

ALTITUDE PRESSURE OFFSET ADJUSTMENT
LINE
Q 1:REGULAR UNLEADED


PRESSURE OFFSET
0.0 PSI

Typical Response Message, Computer Format:
i77DQQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Altitude Pressure offset, PSI or KPA (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

381

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77E
Version 24
Function Type: Set Pressure Line Leak Passive 0.10 GPH Test Enable Flag
Command Format:
Display: S77EQQf
Computer: s77EQQf

Inquire:
I77EQQ
i77EQQ

Typical Response Message, Display Format:

I77EQQ
JUL 14, 2004

10:15 PM

PRESSURE LINE LEAK PASSIVE 0.10 GPH
LINE
Q 1:UNLEADED REGULAR


PASSIVE 0.10 GPH
YES

Typical Response Message, Computer Format:
i777QQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
f - Passive 0.10 GPH Test Enable Flag (Decimal)
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

382

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 77F
Function Type: Set Pressure Line Leak Secondary Pipe Length

Version 17

Only used for the larger diameter line in dual diameter
piping configurations
Command Format:
Display: S77FQQLLL
Computer: s77FQQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I77FQQ
i77FQQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
LLL - Pipe Length, Feet (Decimal)
FFFFFFFF - Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I77FQQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK PIPE LENGTH
LINE
Q 1:UNLEADED REGULAR


1.5 IN DIAM LEN
50 FEET

2.5 IN DIAM LEN
250 FEET

Typical Response Message, Computer Format:
s77FQQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

383

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 780
Function Type: Pressure Line Leak General Setup Inquiry

Version 7

Command Format:
Display: I780QQ
Computer: Computer format is not supported for this command
Typical Response Message, Display Format:

I780QQ
JAN 14, 1995 10:15 PM
PRESSURE LINE LEAK SETUP
Q 1:UNLEADED REGULAR
PIPE TYPE:
FIBERGLASS
0.10 GPH TEST: ENABLED
SHUTDOWN RATE: 3.0 GPH
T 3:REGULAR UNLEADED
DISPENSE MODE:
STANDARD


Part No. 576013-635, Revision AA

384

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 781
Function Type: Set Pressure Line Leak Configuration
Command Format:
Display: S781QQf
Computer: s781QQf

Version 7
Inquire:
I781QQ
i781QQ

Typical Response Message, Display Format:

I781QQ
JAN 24, 1996

2:54 PM

PRESSURE LLD CONFIGURATION
DEVICE
1


LABEL
REGULAR UNLEADED

CONFIGURED
ON

Typical Response Message, Computer Format:
i781QQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - Configuration flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

385

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 782
Function Type: Set Pressure Line Leak Label
Command Format:
Display: S782QQaaaaaaaaaaaaaaaaaaaa
Computer: s782QQaaaaaaaaaaaaaaaaaaaa

Version 7
Inquire:
I782QQ
i782QQ

Typical Response Message, Display Format:

I782QQ
JAN 24, 1996

2:54 PM

PRESSURE LLD LABEL
DEVICE
1


LABEL
REGULAR UNLEADED

Typical Response Message, Computer Format:
i782QQYYMMDDHHmmQQaaaaaaaaaaaaaaaaaaaa...
QQaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
a
&&
CCCC

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Indicates any printable ASCII character
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

386

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 783
Function Type: Set Pressure Line Leak 0.10 GPH Test Schedule
Command Format:
Display: S783QQf
Computer: s783QQf

Version 7
Inquire:
I783QQ
i783QQ

Typical Response Message, Display Format:

I783QQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK 0.10 TEST SCHEDULE
LINE
Q 1:REGULAR UNLEADED


0.10 GPH TEST
DISABLED

Typical Response Message, Computer Format:
i783QQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - 0.10 GPH Test Schedule
0=Disabled
1=Repetitive
2=Auto
(Added in V17)
3=Manual
(Added in V18)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

387

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 784
Function Type: Set Pressure Line Leak Shutdown Rate
Command Format:
Display: S784QQrr
Computer: s784QQrr

Version 7
Inquire:
I784QQ
i784QQ

Typical Response Message, Display Format:

I784QQ
JAN 24, 2000

2:54 PM

PRESSURE LINE LEAK SHUTDOWN RATE
LINE
Q 1:REGULAR UNLEADED


SHUTDOWN RATE
3.0 GPH

Typical Response Message, Computer Format:
i784QQYYMMDDHHmmQQrr...
QQrr&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
rr - Shutdown rate
01=0.10 gal/hr
02=3.00 gal/hr
03=0.20 gal/hr
04=None
(Added in V19)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

388

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 785
Function Type: Set Pressure Line Leak Tank Number
Command Format:
Display: S785QQtt
Computer: s785QQtt

Version 7
Inquire:
I785QQ
i785QQ

Typical Response Message, Display Format:

I785QQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK TANK NUMBER
LINE
Q 1:REGULAR UNLEADED


TANK NUMBER
3

Typical Response Message, Computer Format:
i785QQYYMMDDHHmmQQtt...
QQtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
tt
&&
CCCC

-

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Tank number (Decimal) (00=no tank)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

389

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 786
Function Type: Set Pressure Line Leak Dispense Mode
Command Format:
Display: S786QQf
Computer: s786QQf

Version 7
Inquire:
I786QQ
i786QQ

Typical Response Message, Display Format:

I786QQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK DISPENSE MODE
LINE
Q 1:REGULAR UNLEADED


DISPENSE MODE
STANDARD

Typical Response Message, Computer Format:
i786QQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - Dispensing Mode
1=Standard
2=Manifolded: Alternate
3=Manifolded: Sequential
4=Manifolded: All Pumps
5=Manifolded: Alternate-Height
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

390

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 787
Function Type: Set Pressure Line Leak Disable Alarm Assignments
Command Format:
Display: S787QQAANNTTSS
Computer: s787QQAANNTTSS

Version 7
Inquire:
I787QQ
i787QQ

Typical Response Message, Display Format:

I787QQ
JAN 24, 1996

2:54 PM

PRESSURE LLD SETUP REPORT
Q 1:REGULAR UNLEADED
- NO ALARM ASSIGNMENTS 
Typical Response Message, Computer Format:
i787QQYYMMDDHHmmQQnnAANNTTSS...
QQnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
QQ
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Pressure Line Leak sensor number (Decimal, 00=All)
Number of Alarms to Follow
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

391

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 788
Function Type: Set Pressure Line Leak Piping Material
Command Format:
Display: S788QQtt
Computer: s788QQtt

Version 9
Inquire:
I788QQ
i788QQ

Typical Response Message, Display Format:

I788QQ
JUN 14, 2001

10:15 PM

PRESSURE LINE LEAK PIPE TYPE
LINE
Q 1:UNLEADED REGULAR


PIPE TYPE:
USER DEFINED

Typical Response Message, Computer Format:
i788QQYYMMDDHHmmQQtt
QQtt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
tt - Pipe Type:
01=2.0"/3.0" Fiberglass
02=2.0" Steel
03=White Enviroflex PP1501
04=1.5" Environ Geoflex II
(Added in V11)
05=Omniflex CP1501
(Added in V15)
06=Yellow Enviroflex PP1500
07=1.5"/2.5" Enviroflex PP1502/2502
(Added in V17)
08=OPW Pisces SP-15
(Added in V18)
09=OPW Pisces CP-15
(Added in V18)
10=WFG Coflex 2000 Ribbed
(Added in V19)
11=Enviroflex PP1503/2503
(Added in V19)
12=Omniflex CP1503
(Added in V19)
13=1.5"/2.0" Environ Geoflex D
(Added in V19)
14=APT P175SC
(Added in V121)
15=OPW Pisces CP15DW
(Added in V19)
16=OPW Pisces CP20
(Added in V19)
17=OPW PISCES SP20
(Added in V26)
18=User Defined
(Added in V22)
19=PETROTECHNIK UPP EXTRA 63MM
(Added in V26)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

392

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 789
Function Type: Set Pressure Line Leak Primary Pipe Length

Version 9

Also used for the smaller diameter line in dual diameter
piping configurations
Command Format:
Display: S789QQLLL
Computer: s789QQFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I789QQ
i789QQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
LLL - Pipe Length, Feet (Decimal)
FFFFFFFF - Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I789QQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK PIPE LENGTH
LINE
Q 1:UNLEADED REGULAR


LINE LENGTH
250 FEET

Typical Response Message, Computer Format:
s789QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

393

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 78A
Function Type: Set Pressure Line Leak Sensor Type
Command Format:
Display: S78AQQp
Computer: s78AQQp

Version 11
Inquire:
I78AQQ
i78AQQ

Typical Response Message, Display Format:

I78AQQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK
LINE
Q 1:REGULAR UNLEADED


PUMP
NON-VENTED

Typical Response Message, Computer Format:
i78AQQYYMMDDHHmmQQp...
QQp&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
p - Sensor Type
1=Non-vented
2=Vented
3=High Pressure
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

394

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 78B
Version 16 (Obsolete at V17, use 78E)
Function Type: Set Pressure Line Leak 0.10 GPH Test Schedule
Command Format:
Display: S78BPPMMDD
Computer: s78BPPMMDD

Inquire:
I78BPP
i78BPP

Typical Response Message, Display Format:

I78BPP
JAN 24, 1998

2:55 PM

PLLD 0.10 GPH SCHEDULE
LINE
P 1:REGULAR UNLEADED


SCHEDULE
02/11

Typical Response Message, Computer Format:
s78BPPYYMMDDHHmmPPMMDD...
PPMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
PP
MMDD
&&
CCCC

-

Current Date and Time
PLLD Line Leak sensor number (Decimal, 00=all)
Month and Day for 0.10 GPH test to start
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

395

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 78C
Function Type: Set Pressure Line Leak 0.20 GPH Test Schedule
Command Format:
Display: S78CQQf
Computer: s78CQQf

Version 12
Inquire:
I78CQQ
i78CQQ

Typical Response Message, Display Format:

I78CQQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK 0.20 TEST SCHEDULE
LINE
Q 1:REGULAR UNLEADED


0.20 GPH TEST
MONTHLY

Typical Response Message, Computer Format:
i78CQQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - 0.20 GPH Test Schedule
0=Disabled
1=Repetitive
2=Monthly
(Added in V18)
3=Manual
(Added in V18)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

396

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 78E
Function Type: Set Pressure Line Leak 0.10 GPH Auto Test Enable
Command Format:
Display: S78EQQf
Computer: s78EQQf

Version 17
Inquire:
I78EQQ
i78EQQ

Typical Response Message, Display Format:

I78EQQ
JAN 24, 1996

2:54 PM

PRESSURE LINE LEAK 0.10 AUTO ENABLE
LINE
Q 1:REGULAR UNLEADED


0.10 GPH AUTO
ENABLED

Typical Response Message, Computer Format:
i78EQQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
f - 0.10 GPH Test
0=Disabled
1=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

397

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 78F
Function Type: Set Pressure Line Leak Dispense Threshold
Command Format:
Display: S78FQQPP
Computer: s78FQQFFFFFFFF
Notes:
1.
2.
3.

Version 17
Inquire:
I78FQQ
i78FQQ

QQ - Pressure Line Leak Sensor Number (Decimal, 00=all)
PP - Low Pressure, PSI (Decimal)
FFFFFFFF - Low Pressure, PSI (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I78FQQ
JAN 14, 1995

10:15 PM

PRESSURE LINE LEAK DISPENSE THRESHOLD
LINE
Q 1:UNLEADED REGULAR


LOW PRESSURE
15 PSI

Typical Response Message, Computer Format:
s78FQQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Low Pressure, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

398

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7BD
Function Type: Set Pressure Line Disable Alarm Assignments II
Command Format:
Display: S7BDQQAANNTTSS
Computer: s7BDQQAANNTTSS

Version 19
Inquire:
I7BDQQ
i7BDQQ

Typical Response Message, Display Format:

I7BDQQ
JAN 3, 1996 11:15 PM
PRESSURE LLD SETUP REPORT
Q 1:PLLD NUMBER 1
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
PRESSURE LINE LEAK
ALL:PLLD OPEN ALARM
ALL:CONT HANDLE ALM
ALL:LN EQUIP FAULT ALM

Typical Response Message, Computer Format:
i7BDQQYYMMDDHHmmQQnnAANNTTSS...
QQnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
nn
AA

-

NN -

-

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Number of Alarms to Follow (Hex)
Alarm/Warning Category
02=Tank Alarm
21=Pressure Line Leak Alarm
Alarm Type Number
If AA is 02 and NN is:
02=Tank Leak Alarm
03=Tank High Water Alarm
04=Tank Overfill Alarm
If AA is 21 and NN is:
06=PLLD Sensor Open Alarm
16=PLLD Continuous Handle On Alarm
18=PLLD Line Equipment Alarm
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

399

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7D7
Function Type: Set Pressure Line Leak Alternate Modes
Auto Active Pump Switchover Enable
Command Format:
Display: S7D7QQf
Computer: s7D7QQf
Notes:
1.

Version 33

Inquire:
I7D7QQ
i7D7QQ

f - 0=disabled; 1=enabled

Typical Response Message, Display Format:

I7D7QQ
MAR 27, 1996

5:50 PM

PRESSURE LINE LEAK ALTERNATE MODE SWITCHOVER ENABLE
DEVICE LABEL
S 1:UNLEADED GASOLINE
S 2:UNLEADED GASOLINE


ENABLED
YES
NO

Typical Response Message, Computer Format:
i7D7QQYYMMDDHHmmQQf...
QQf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak Number (Decimal, 00=all)
f - Auto Switchover Enable:
0=No
1=Yes
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

400

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7D8
Function Type: Set Pressure Line Leak Alternate Mode
Auto Active Pump Switchover Volume Threshold
Command Format:
Display: S7D8QQGGGG
Computer: s7D8QQFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I7D8QQ
i7D8QQ

QQ - Pressure Line Leak Number (Decimal, 00=all)
GGGG - Full Height Volume, Gallons (Decimal)
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7D8QQ
MAR 27, 2014

5:50 PM

PRESSURE LINE LEAK ALTERNATE MODE SWITCHOVER THRESHOLD
DEVICE LABEL
1
REGULAR UNLEADED


GALLONS
200

Typical Response Message, Computer Format:
i7D8QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Number (Decimal, 00=all)
Switchover threshold, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

401

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7D9
Function Type: Set Pressure Line Leak Alternate-Height Mode
Auto Active Pump Switchover Height Threshold
Command Format:
Display: S7D9QQhhhh.h
Computer: s7D9QQFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I7D9QQ
i7D9QQ

QQ - Pressure Line Leak Number (Decimal, 00=all)
hhhh.h - Switchover Threshold, Inches and tenths (Decimal)
FFFFFFFF - Switchover Threshold, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7D9QQ
MAR 27, 2014

5:50 PM

PRESSURE LINE LEAK ALTERNATE-HEIGHT MODE SWITCHOVER THRESHOLD
DEVICE LABEL
S 1:UNLEADED


INCHES
2.0

Typical Response Message, Computer Format:
i7D9QQYYMMDDHHmmQQFFFFFFFF...
QQFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
QQ
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Number (Decimal, 00=all)
Switchover threshold, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

402

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.9 RECONCILIATION SETUP
Function Code: 790
Function Type: DIM Software Revision

Version 118

Command Format:
Display: I790PP
Computer: i790PP
Notes:
1.

PP - Communication Port Number (Decimal, 00=all)

Typical Response Message, Display Format:

I790PP
JAN 1, 2000

8:00 AM

EDIM:1 VR:330273-002-C


TD:97.11.13.15.52

Typical Response Message, Computer Format:
Notes:
1.

Response is the same as display format.

Part No. 576013-635, Revision AA

403

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 791
Function Type: Set Mechanical Dispenser Interface String
Command Format:
Display: S791NNaaaaaaaaaaaa
Computer: s791NNaaaaaaaaaaaa

Version 106
Inquire:
I791NN
i791NN

Typical Response Message, Display Format:

S791NN
MAR 29, 1996

6:27 PM

DISP. MODULE DATA STRING
MDIM 1: aaaaaaaaaaaa

Typical Response Message, Computer Format:
i791NNYYMMDDHHmmNNaaaaaaaaaaaa...
NNaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
NN
aaaaaaaaaaaa
&&
CCCC

-

Current Date and Time
MDIM Number (Decimal, 00=all)
Data String (12 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

404

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 792
Function Type: Set Electronic Dispenser Interface String
Command Format:
Display: S792NNaaaaaaaaaaaa
Computer: s792NNaaaaaaaaaaaa

Version 106
Inquire:
I792NN
i792NN

Typical Response Message, Display Format:

I792NN
JAN 22, 1996

3:21 PM

DISP. MODULE DATA STRING
EDIM 1: aaaaaaaaaaaa

Typical Response Message, Computer Format:
i792NNYYMMDDHHmmNNaaaaaaaaaaaa...
NNaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
NN
aaaaaaaaaaaa
&&
CCCC

-

Current Date and Time
EDIM Number (Decimal, 00=all)
Data String (12 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

405

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 793
Function Type: Set Reconciliation Auto Daily Closing Time
Command Format:
Display: S79300HHmm
Computer: s79300HHmm

Version 106
Inquire:
I79300
i79300

Typical Response Message, Display Format:

I79300
JAN 22, 1996

3:21 PM

AUTOMATIC DAILY CLOSING
TIME: 2:00 AM

Typical Response Message, Computer Format:
i79300YYMMDDHHmmHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
HHmm
&&
CCCC

-

Current Date and Time
Auto Daily Closing Time (hours & minutes)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

406

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 794
Function Type: Set Auto Shift Closing Time 1, 2, 3, 4
Command Format:
Display: S794SSHHmm
Computer: s794SSHHmm

Version 106
Inquire:
I794SS
i794SS

Typical Response Message, Display Format:

I794SS
MAR 26, 1996

1:49 PM

AUTO SHIFT #1 CLOSING
TIME: 8:00 AM

Typical Response Message, Computer Format:
i794SSYYMMDDHHmmSSHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
SS
HHmm
&&
CCCC

-

Current Date and Time
Shift Close Number (01, 02, 03, 04)
Hour and Minute (EE00=Disabled)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

407

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 795
Function Type: Set Periodic Reconciliation Mode
Command Format:
Display: S79500ss
Computer: s79500ss

Version 106
Inquire:
I79500
i79500

Typical Response Message, Display Format:

I79500
JAN 22, 1996

3:22 PM

PERIODIC RECONCILIATION
MODE: MONTHLY

Typical Response Message, Computer Format:
i79500YYMMDDHHmmss&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
ss - Periodic Reconciliation Mode
1=Monthly
2=Rolling
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

408

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 796
Function Type: Set Periodic Reconciliation Report Length
Command Format:
Display: S79600dd
Computer: s79600dd

Version 106
Inquire:
I79600
i79600

Typical Response Message, Display Format:

I79600
JAN 22, 1996

3:22 PM

PERIODIC RECONCILIATION
LENGTH: 31 DAYS

Typical Response Message, Computer Format:
i79600YYMMDDHHmmdd&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
dd
&&
CCCC

-

Current Date and Time
Number of days for Rolling Report (Decimal, 01-31)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

409

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 797
Function Type: Set Periodic Reconciliation Alarm Flag
Command Format:
Display: S79700ss
Computer: s79700ss

Version 106
Inquire:
I79700
i79700

Typical Response Message, Display Format:

I79700
JAN 22, 1996

3:22 PM

PERIODIC RECONCILIATION
ALARM: DISABLED

Typical Response Message, Computer Format:
i79700YYMMDDHHmmss&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
ss - Reconciliation Alarm Flag
01=Disable
02=Enable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

410

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 798
Function Type: Set Periodic Reconciliation Alarm Threshold
Command Format:
Display: S79800PP.hh
Computer: s79800FFFFFFFF
Notes:
1.
2.

Version 106
Inquire:
I79800
i79800

PP.hh - Alarm Threshold, Percent and hundredths (Decimal)
FFFFFFFF - Alarm Threshold, Percent (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I79800
JUN 1, 2000

8:07 AM

PERIODIC RECONCILIATION
ALARM THRESHOLD: 1.00%

Typical Response Message, Computer Format:
i79800YYMMDDHHmmFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
FFFFFFFF
&&
CCCC

-

Current Date and Time
Alarm Threshold, Percent (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

411

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 799
Function Type: Set Periodic Reconciliation Alarm Offset
Command Format:
Display: S79900GGGGGG
Computer: s79900FFFFFFFF
Notes:
1.
2.

Version 106
Inquire:
I79900
i79900

GGGGGG - Alarm Offset, Gallons (Decimal)
FFFFFFFF - Alarm Offset, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I79900
JAN 22, 1996

3:22 PM

PERIODIC RECONCILIATION
ALARM OFFSET:
130

Typical Response Message, Computer Format:
i79900YYMMDDHHmmFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
FFFFFFFF
&&
CCCC

-

Current Date and Time
Alarm Offset, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

412

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79A
Function Type: Set Remote Printer Reconciliation Report Format
Command Format:
Display: S79A00tt
Computer: s79A00tt

Version 106
Inquire:
I79A00
i79A00

Typical Response Message, Display Format:

I79A00
JAN 22, 1996

3:22 PM

REMOTE REPORT FORMAT
SELECT: ROW

Typical Response Message, Computer Format:
i79A00YYMMDDHHmmtt&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
tt - Remote Printer Report Type
01=Row
02=Column
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

413

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79B
Function Type: Set Shift Manual Adjustment Value
Command Format:
Display: S79BTTssGGGGGG
Computer: s79BTTssFFFFFFFF
Notes:
1.
2.
3.
4.

Version 106
Inquire:
I79BTT
i79BTT

TT - Tank number
ss - Shift mode
01=Current
02=Previous
GGGGGG - Adjustment Value, Gallons (Decimal)
FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I79BTT
MAR 26, 1996

1:50 PM

T 1:REGULAR UNLEADED
CURRENT SHFT ADJ:
300

Typical Response Message, Computer Format:
i79BTTYYMMDDHHmmTTssFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
TT - Tank number
ss - Shift mode
01=Current
02=Previous
FFFFFFFF - Adjustment Value, Gallons (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

414

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79C
Function Type: Set Daily Manual Adjustment Value
Command Format:
Display: S79CTTMMDDGGGGGG
Computer: s79CTTMMDDFFFFFFFF
Notes:
1.
2.
3.
4.

TT
MMDD
GGGGGG
FFFFFFFF

-

Version 106
Inquire:
I79CTT
i79CTT

Tank number
Month and day
Adjustment Value, Gallons (Decimal)
Adjustment value, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I79CTT
MAR 26, 1996

1:50 PM

T 1:REGULAR UNLEADED
MAR 26
ADJ VOL:
300

Typical Response Message, Computer Format:
i79CTTYYMMDDHHmmTTMMDDFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
MMDD
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank number
Month and day
Adjustment value, Gallons (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

415

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79D
Function Type: Close Current Reconciliation Shift
Command Format:
Display: S79D00ff
Computer: s79D00ff

Version 106
Inquire:
I79D00
i79D00

Typical Response Message, Display Format:

I79D00
JAN 22, 1996

3:23 PM

MANUAL SHIFT CLOSE
STATION IS BUSY
*** CLOSE SHIFT PENDING ***

Typical Response Message, Computer Format:
i79D00YYMMDDHHmmff&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
ff - Close current shift flag
01=Close shift pending
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

416

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79E
Function Type: Clear Tank Map Table

Version 106

Command Format:
Display: S79E00149
Computer: s79E00149
Notes:
1.

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S79E00
JAN 22, 1996

3:23 PM

RECONCILIATION CLEAR MAPS
MAPS TABLE CLEARED

Typical Response Message, Computer Format:
i79E00YYMMDDHHmmss&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
ss - Clear status
00=not clear
01=cleared
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

417

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 79F
Function Type: Set BIR Temperature Compensation Flag
Command Format:
Display: S79F00f
Computer: s79F00f

Version 108
Inquire:
I79F00
i79F00

Typical Response Message, Display Format:

I79F00
JAN 22, 1996

3:24 PM

TEMP COMPENSATION
STANDARD

Typical Response Message, Computer Format:
i79F00YYMMDDHHmmf&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
f - Status
0=Standard
1=TC Volume
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

418

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.10 WIRELESS PLLD SETUP
Function Code: 7A0
Function Type: WPLLD Line Leak General Setup

Version 10

Command Format:
Display: I7A0WW
Computer: Computer format is not supported for this command
Typical Response Message, Display Format:

I7A0WW
JAN 24, 1996

2:54 PM

WPLLD LINE LEAK SETUP
W 1:REGULAR UNLEADED
PIPE TYPE:
FIBERGLASS
LINE LENGTH: 200 FEET
0.20 GPH TEST: ENABLED
SHUTDOWN RATE: 3.0 GPH
T 1:REGULAR UNLEADED
DISPENSE MODE:
STANDARD


Part No. 576013-635, Revision AA

419

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A1
Function Type: Set WPLLD Line Leak Configuration
Command Format:
Display: S7A1WWf
Computer: s7A1WWf

Version 10
Inquire:
I7A1WW
i7A1WW

Typical Response Message, Display Format:

I7A1WW
JAN 24, 1996
WPLLD LLD
DEVICE
1


2:54 PM
CONFIGURATION

LABEL
REGULAR UNLEADED

CONFIGURED
ON

Typical Response Message, Computer Format:
i7A1WWYYMMDDHHmmWWf...
WWf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
f - Configuration flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

420

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A2
Function Type: Set WPLLD Line Leak Label
Command Format:
Display: S7A2WWaaaaaaaaaaaaaaaaaaaa
Computer: s7A2WWaaaaaaaaaaaaaaaaaaaa

Version 10
Inquire:
I7A2WW
i7A2WW

Typical Response Message, Display Format:

I7A2WW
JAN 24, 1996
WPLLD LLD
DEVICE
1


2:54 PM
LABEL

LABEL
REGULAR UNLEADED

Typical Response Message, Computer Format:
i7A2WWYYMMDDHHmmWWaaaaaaaaaaaaaaaaaaaa...
WWaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
a
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Indicates any printable ASCII character
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

421

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A3
Function Type: Set WPLLD Line Leak 0.20 GPH Test Schedule
Command Format:
Display: S7A3WWf
Computer: s7A3WWf

Version 10
Inquire:
I7A3WW
i7A3WW

Typical Response Message, Display Format:

I7A3WW
JAN 24, 1996

2:54 PM

WPLLD LINE LEAK 0.20 TEST SCHEDULE
LINE
W 1:REGULAR UNLEADED


0.20 GPH TEST
MONTHLY

Typical Response Message, Computer Format:
i7A3WWYYMMDDHHmmWWf...
WWf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
f - 0.20 GPH Test Schedule
0=Disabled
1=Repetitive
2=Monthly
(Added in V18)
3=Manual
(Added in V18)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

422

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A4
Function Type: Set WPLLD Line Leak Shutdown Rate
Command Format:
Display: S7A4WWrr
Computer: s7A4WWrr

Version 10
Inquire:
I7A4WW
i7A4WW

Typical Response Message, Display Format:

I7A4WW
JAN 24, 2000

2:55 PM

WPLLD LINE LEAK SHUTDOWN RATE
LINE
W 1:REGULAR UNLEADED


SHUTDOWN RATE
3.0 GPH

Typical Response Message, Computer Format:
i7A4WWYYMMDDHHmmWWrr...
WWrr&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
rr - Shutdown rate
01=0.20 gal/hr
02=3.00 gal/hr
03=0.10 gal/hr
04=None
(Added in V19)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

423

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A5
Function Type: Set WPLLD Line Leak Tank Number
Command Format:
Display: S7A5WWtt
Computer: s7A5WWtt

Version 10
Inquire:
I7A5WW
i7A5WW

Typical Response Message, Display Format:

I7A5WW
JAN 24, 1996

2:55 PM

WPLLD LINE LEAK TANK NUMBER
LINE
W 1:REGULAR UNLEADED


TANK NUMBER
1

Typical Response Message, Computer Format:
i7A5WWYYMMDDHHmmWWtt...
WWtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
tt
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Tank number (Decimal) (00=no tank)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

424

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A6
Function Type: Set WPLLD Line Leak Dispense Mode
Command Format:
Display: S7A6WWf
Computer: s7A6WWf

Version 10
Inquire:
I7A6WW
i7A6WW

Typical Response Message, Display Format:

I7A6WW
JAN 24, 1996

2:55 PM

WPLLD LINE LEAK DISPENSE MODE
LINE
W 1:REGULAR UNLEADED


DISPENSE MODE
STANDARD

Typical Response Message, Computer Format:
i7A6WWYYMMDDHHmmWWf...
WWf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
f - Dispensing Mode
1=Standard
2=Manifolded: Alternate
3=Manifolded: Sequential
4=Manifolded: All Pumps
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

425

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A7
Function Type: Set WPLLD Line Disable Alarm Assignments
Command Format:
Display: S7A7WWAANNTTSS
Computer: s7A7WWAANNTTSS

Version 10
Inquire:
I7A7WW
i7A7WW

Typical Response Message, Display Format:

I7A7WW
JAN 24, 1996
WPLLD LLD

2:55 PM
SETUP REPORT

W 1:REGULAR UNLEADED
- NO ALARM ASSIGNMENTS 
Typical Response Message, Computer Format:
i7A7WWYYMMDDHHmmWWnnAANNTTSS...
WWnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
WW
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Number of Alarms to Follow
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

426

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A8
Function Type: Set WPLLD Line Leak Pipe Type
Command Format:
Display: S7A8WWzz
Computer: s7A8WWzz

Version 10
Inquire:
I7A8WW
i7A8WW

Typical Response Message, Display Format:

I7A8WW
JAN 24, 1996

2:55 PM

WPLLD LINE LEAK PIPE TYPE
LINE
W 1:REGULAR UNLEADED


PIPE TYPE:
FIBERGLASS

Typical Response Message, Computer Format:
s7A8WWYYMMDDHHmmWWzz...
WWzz&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=all)
zz - Pipe Type:
01=2" Fiberglass
02=2" Steel
03=Flexible-A (White Enviroflex PP1501)
04=Flexible-B (1.5" Environ Geoflex D)
(Added in V15)
05=Flexible-C (Omniflex CP1501)
(Added in V15)
06=Flexible-D (Yellow Enviroflex PP1500)
(Added in V15)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

427

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7A9
Function Type: Set WPLLD Line Leak Pipe Length
Command Format:
Display: S7A9WWLLL
Computer: s7A9WWFFFFFFFF
Notes:
1.
2.
3.

Version 10
Inquire:
I7A9WW
i7A9WW

WW - WPLLD Line Leak sensor number (Decimal, 00=all)
LLL - Pipe Length, Feet (Decimal)
FFFFFFFF - Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7A9WW
JAN 24, 1996

2:55 PM

WPLLD LINE LEAK LINE LENGTH
LINE
W 1:REGULAR UNLEADED


LINE LENGTH
200 FEET

Typical Response Message, Computer Format:
s7A8WWYYMMDDHHmmWWFFFFFFFF...
WWFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
FFFFFFFF
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number
Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

428

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7AA
Version 11 (Obsolete at V17, use 7AC)
Function Type: Set WPLLD Line Leak 0.10 GPH Test Schedule
Command Format:
Display: S7AAWWMMDD
Computer: s7AAWWMMDD

Inquire:
I7AAWW
i7AAWW

Typical Response Message, Display Format:

I7AAWW
JAN 24, 1996

2:55 PM

WPLLD 0.10 GPH SCHEDULE
LINE
W 1:REGULAR UNLEADED


SCHEDULE
02/11

Typical Response Message, Computer Format:
s7AAWWYYMMDDHHmmWWMMDD...
WWMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
MMDD
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=all)
Month and Day for 0.10 GPH test to start
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

429

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7AC
Version 17
Function Type: Set WPLLD Line Leak 0.10 GPH Test Schedule Enable
Command Format:
Display: S7ACWWf
Computer: s7ACWWf

Inquire:
I7ACWW
i7ACWW

Typical Response Message, Display Format:

I7ACWW
JAN 24, 1996

2:54 PM

WPLLD LINE LEAK 0.10 TEST SCHEDULE
LINE
W 1:REGULAR UNLEADED


0.10 GPH TEST
DISABLED

Typical Response Message, Computer Format:
i7ACWWYYMMDDHHmmWWf...
WWf&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
f - 0.10 GPH Test Schedule
0=Disabled
1=(Reserved)
2=Auto
3=Manual
(Added in V18)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

430

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7AD
Version 20
Function Type: Set WPLLD Line Leak Secondary Pipe Length
(only used for the larger diameter line in dual diameter
piping configurations)
Command Format:
Display: S7ADWWLLL
Computer: s7ADWWFFFFFFFF
Notes:
1.
2.
3.

Inquire:
I7ADWW
i7ADWW

WW - Wireless Pressure Line Leak Sensor Number (Decimal, 00=all)
LLL - Pipe Length, Feet (Decimal)
FFFFFFFF - Pipe Length, Feet (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7ADWW
JUN 1, 2000

8:09 AM

WPLLD LINE LEAK LINE LENGTH
LINE
W 2:WPLLD NUMBER 2


LARGE
LINE LENGTH
150 FEET

Typical Response Message, Computer Format:
s7ADWWYYMMDDHHmmWWFFFFFFFF...
WWFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pressure Line Leak Sensor Number (Decimal, 00=all)
Pipe Length, Feet (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

431

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7AE
Function Type: WPLLD Continuous Handle Alarm Timeout
Command Format:
Display: S7AEWWtt
Computer: s7AEWWtt
Notes:
1.
2.

Version 27
Inquire:
I7AEWW
i7AEWW

WW - WPLLD Line Leak sensor number (Decimal, 00=All)
tt - Continuous Handle Alarm Timeout (Decimal, in hours, 1-16)

Typical Response Message, Display Format:

I7AEQQ
SEP 16, 2006

3:15 PM

WPLLD CONTINUOUS HANDLE ALARM TIMEOUT
LINE
W 1:REGULAR UNLEADED


TIMEOUT
16 HOURS

Typical Response Message, Computer Format:
i7AEWWYYMMDDHHmmWWttWWtt...
WWtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
tt
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Continuous Handle Alarm Timeout (Decimal, in hours, 1-16)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

432

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7AF
Function Type: Set WPLLD Line Leak Altitude Pressure Offset
Command Format:
Display: S7AFWWII.p
Computer: s7AFWWFFFFFFFF
Notes:
1.
2.
3.
4.

Version 19
Inquire:
I7AFWW
i7AFWW

WW - WPLLD Line Leak sensor number (Decimal, 00=All)
II.p - Altitude Pressure Offset, PSI or KPA (Decimal)
FFFFFFFF - Altitude Pressure Offset, PSI or KPA (ASCII Hex IEEE float)
Value must be within the range of +5.0 to -5.0 PSI or 34.4
to -34.4 KPA

Typical Response Message, Display Format:

I7AFWW
JAN 1, 2000

1:44 AM

ALTITUDE PRESSURE OFFSET ADJUSTMENT
LINE
W 1:REGULAR UNLEADED


PRESSURE OFFSET
0.0 PSI

Typical Response Message, Computer Format:
i7AFWWYYMMDDHHmmWWFFFFFFFF...
WWFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
FFFFFFFF
&&
CCCC

-

Current Date and Time
WPLLD Line Leak sensor number (Decimal, 00=All)
Altitude pressure offset, PSI or KPA (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

433

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7BE
Function Type: Set WPLLD Line Disable Alarm Assignments II
Command Format:
Display: S7BEWWAANNTTSS
Computer: s7BEWWAANNTTSS

Version 19
Inquire:
I7BEWW
i7BEWW

Typical Response Message, Display Format:

I7BEWW
JAN 3, 1996 11:15 PM
WPLLD LLD SETUP REPORT
W 1:WPLLD NUMBER 1
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
WPLLD LINE LEAK
ALL:WPLLD OPEN ALARM
ALL:CONT HANDLE ALM
ALL:LN EQUIP FAULT ALM

Typical Response Message, Computer Format:
i7BEWWYYMMDDHHmmWWnnAANNTTSS...
WWnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
WW
nn
AA

-

NN -

-

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
WPLLD Line Leak Sensor Number (Decimal, 00=all)
Number of Alarms to Follow (Hex)
Alarm/Warning Category
02=Tank Alarm
26=Wireless PLLD Alarm
Alarm Type Number
If AA is 02 and NN is:
02=Tank Leak Alarm
03=Tank High Water Alarm
04=Tank Overfill Alarm
If AA is 26 and NN is:
06=WPLLD Sensor Open Alarm
16=WPLLD Continuous Handle On Alarm
18=WPLLD Line Equipment Alarm
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

434

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.11 METER MAP & DELIVERY TICKET SETUP
Function Code: 7B1
Function Type: Set BIR Meter/Tank Mapping

Version 110

Command Format:
Inquire:
Display: S7B100 B SS FP MM TT
I7B100
Computer: Computer format is not supported for this command
Notes:
1.

B - Bus

2.

SS -

3.
4.

FP MM -

5.

TT -

6.

2=Power Bus (MDIM)
3=Comm Bus
Slot
Bus 2: 09-16
Bus 3: 01-06
Fueling Position (00-99)
Meter (00-99) ** Double-digit meter mapping implemented in
Version 23
Tank Number (-1, 00, or any legitimate tank number)
-1=Probeless tank
00=Unmap present tank
It is not necessary that the meter be in the map prior to
mapping the meter to a tank

Typical Response Message, Display Format:

I7B100
JUN 22, 2001

3:24 PM

FUELING POSITION - METER - TANK MAP
BUS SLOT FUEL_P METER TANK
------------------------------3
3
0
10
1
3
3
0
11
3
3
3
0
12
2
3
3
1
10
1
3
3
1
11
3
3
3
1
12
2
3
3
2
10
2
3
3
2
11
3
3
3
2
12
1
3
3
3
10
2
3
3
3
11
3
3
3
3
12
1
3
3
4
10
1
3
3
4
11
3
3
3
4
12
2
3
3
5
10
1
3
3
5
11
3
3
3
5
12
2
3
3
6
10
2
3
3
6
11
3


Part No. 576013-635, Revision AA

435

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7B2
Function Type: Set Meter Calibration Offset
Command Format:
Display: S7B200pp.ppp
Computer: s7B200FFFFFFFF
Notes:
1.
2.

Version 20
Inquire:
I7B200
i7B200

pp.ppp - Meter Calibration Offset, Percent (Decimal)
FFFFFFFF - Meter Calibration Offset, Percent (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7B200
JUN 1, 2000

8:10 AM

METER CALIBRATION
OFFSET: 0.000%

Typical Response Message, Computer Format:
i7B200YYMMDDHHmmFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
FFFFFFFF
&&
CCCC

-

Current Date and Time
Meter Calibration Offset, Percent (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

436

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7B4
Function Type: Set Individual Meter Offset
Command Format:
Display: S7B400 FF MM TT +o.oo
Computer: Computer format is not supported
Notes:
1.
2.
3.
4.

FF
MM
TT
o.oo

-

Version 29
Inquire:
I7B400

Fueling Position (Decimal)
Meter Number (Decimal)
Tank Number (Decimal)
Meter Offset, percent (Decimal +/-9.99)

Typical Response Message, Display Format:

I7B400
DEC 22, 2006

3:12 PM

INDIVIDUAL METER OFFSET
FP
1

METER
1
2
6
2
1
2
6
3
1
2
6


1
2
3
1
2
3
1
2
3

TANK
REGULAR
PREMIUM
DIESEL
REGULAR
PREMIUM
DIESEL
REGULAR
PREMIUM
DIESEL

GASOLINE
GASOLINE
GASOLINE
GASOLINE
GASOLINE
GASOLINE

OFFSET
+0.10%
-0.10%
0.00%
+0.10%
-0.10%
0.00%
+0.10%
-0.10%
0.00%

Typical Response Message, Computer Format:
i7B400YYMMDDHHmmNNNNFFMMTToooooooo...
FFMMTToooooooo&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
NNNN
FF
MM
TT

-

Current Date and Time
Number of entries to follow (ASCII Hex)
Fuel Position (Decimal)
Meter Number (Decimal)
Tank Number (Decimal)
00=Tank not mapped
oooooooo - Meter Offset, percent (Decimal +/-9.99)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

437

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7B5
Function Type: Set Ticketed Delivery

Version 116

Command Format:
Display: S7B5TTeeYYMMDDHHmmGGGGGG
Computer: s7B5TTeeYYMMDDHHmmFFFFFFFF
Notes:
1.
2.
3.
4.
5.

TT - Tank Number (Decimal, 00=all)
ee - edit function
01=Edit Ticket (enter, modify)
02=Insert Ticket Delivery
YYMMDDHHmm - Delivery Date/Time (End Time)
GGGGGG - Ticket Volume, Gallons (Decimal)
FFFFFFFF - Ticket Volume, Gallons (ASCII Hex IEEE float)
Entering 0 volume will cancel ticketed delivery warning.
VOL TC/STANDARD must match setup for ticketed delivery.

Typical Response Message, Display Format:

S7B5TT
JAN 9, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:08 AM
1....
2....
3....
4....

SET TICKETED DELIVERY
VOLUMES ARE STANDARD
T 1:UNLEADED REGULAR

JAN 8, 1993


2:10 AM

TICKET
VOLUME
500.0

Part No. 576013-635, Revision AA

GAUGE
VOLUME
503.0

VARIANCE
3.0

438

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 7B5: (Continued)
Typical Response Message, Computer Format:
i7B5TTYYMMDDHHmmTTpPPRRYYMMDDHHmmNNFFFFFFFF...
TTpPPRRYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
p
PP
RR

-

6.
7.
8.

YYMMDDHHmm NN FFFFFFFF -

9.
10.

&& CCCC -

Current Date and Time
Tank Number (Decimal)
Product Code (one ASCII character [20h-7Eh])
Probe type (Decimal)
Result code - if an error occurs, just error code will be
returned (Decimal)
00=OK and data will follow
01=BIR not enabled
02=Tank number is invalid
03=missing time/date
04=Time Date not numeric
05=invalid date
06=time is invalid
07=Date out of range of period (curr & prev via BIR)
08=If there is no matching time/date for edit
09=Invalid volume
10=Try to insert when gauged exists
30=Reserved
31=Reserved
Delivery Date/Time (End Time)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Ticketed volume
2. Gauged volume
3. Delivery variance
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

439

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7B6
Function Type: Set BOL number

Version 23

Command Format:
Display: S7B6TTeeYYMMDDHHmmaa..aa
Computer: s7B6TTeeYYMMDDHHmmaa..aa
Notes:
1.
2.

TT - Tank Number (Decimal)
ee - edit function
01=Edit Ticket (enter, modify)
02=Insert Ticketed Delivery
YYMMDDHHmm - Delivery Date/Time (End Time)
aa..aa - Bill of Lading Number

3.
4.

Typical Response Message, Display Format:

I7B60101
FEB 01, 1997
STATION
STATION
STATION
STATION
SET

HEADER
HEADER
HEADER
HEADER

4:29 PM
1....
2....
3....
4....

TICKETED DELIVERY BOL NUMBER

DELIVERY END DATE
DEC 2, 1993 2:00 AM

BOL
NUMBER
123456

Part No. 576013-635, Revision AA

TICKET
VOLUME
0.0

GAUGE
VOLUME
502.0

TC GAUGE
VOLUME
0.0

440

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 7B6 Notes: (Continued)
Typical Response Message, Computer Format:
s7B6TTYYMMDDHHmmTTpPPRRYYMMDDHHmmAAaa..aaNNFFFFFFFF...FFFFFFFF...
TTpPPRRYYMMDDHHmmAAaa..aaNNFFFFFFFF...FFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
TT
p
PP
RR

-

6.
7.
8.
9.
10.

YYMMDDHHmm
AA
aa..aa
NN
FFFFFFFF

-

11.
12.

&& CCCC -

Current Date and Time
Tank Number (Decimal)
Product Code (Decimal)
Probe type (Decimal)
Result code (Decimal) - if error occurs, only error code is
returned
00=OK and data will follow
01=BIR not enabled
02=Tank number is invalid
03=missing time/date
04=Time Date not numeric
05=invalid date
06=time is invalid
07=Date out of range of period (curr & prev via BIR)
08=If there is no matching time/date for edit
30=Reserved
31=Reserved
Delivery Date/Time (End Time)
Number of ASCII characters to follow
Bill of Lading Number (ASCII characters [20h-7Eh])
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats - VOL TC/STANDARD must match setup for
ticketed delivery
1. Ticketed volume
2. Gauged volume
3. Gauged TC volume
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

441

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.12 PUMP MONITOR RELAY SETUP
Function Code: 7C4
Function Type: Set Pump Relay Monitor Configuration
Command Format:
Display: S7C4rrf
Computer: s7C4rrf

Version 27
Inquire:
I7C4rr
i7C4rr

Typical Response Message, Display Format:

I7C4rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR CONFIGURATION
DEVICE
1


LABEL
PUMP RELAY UNLEADED

CONFIGURED
ON

Typical Response Message, Computer Format:
i7C4rrYYMMDDHHmmrrf...
rrf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
rr - Pump Relay Monitor Number (Decimal, 00=all)
f - Configuration Flag (ASCII Hex)
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

442

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7C5
Function Type: Set Pump Relay Monitor Label
Command Format:
Display: S7C5rraaaaaaaaaaaaaaaaaaaa
Computer: s7C5rraaaaaaaaaaaaaaaaaaaa

Version 27
Inquire:
I7C5rr
i7C5rr

Typical Response Message, Display Format:

I7C5rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR LABEL
DEVICE
1


LABEL
PUMP RELAY UNLEADED

Typical Response Message, Computer Format:
i7C5rrYYMMDDHHmmrraaaaaaaaaaaaaaaaaaaa...
rraaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
rr
a
&&
CCCC

-

Current Date and Time
Pump Relay Monitor Number (Decimal, 00=all)
Label (20 ASCII characters from 20 Hex B 7E Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

443

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7C6
Function Type: Set Pump Relay Monitor Pump Relay
Command Format:
Display: S7C6rrAATT
Computer: s7C6rrAATT

Version 27
Inquire:
I7C6rr
i7C6rr

Typical Response Message, Display Format:

I7C6rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR PUMP RELAY
DEVICE
1


LABEL
PUMP RELAY UNLEADED

PUMP RELAY
Q !: UNLEADED

Typical Response Message, Computer Format:
i7C6rrYYMMDDHHmmrrAATT...
rrAATT&&CCCC
Notes:
1.
2.
3.

4.
5.
6.

YYMMDDHHmm - Current Date and Time
rr - Pump Relay Monitor Number (Decimal, 00=all)
AA - Device Type (Decimal)
00=None
11=Output Relay
15=Pump Sensor
16=VLLD
21=PLLD
26=WPLLD
TT - Device Number (Decimal, 00=None)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

444

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7C7
Function Type: Set Pump Relay Monitor Stuck Relay
Command Format:
Display: S7C7rrSSS
Computer: s7C7rrFFFFFFFF
Notes:
1.
2.

Version 27
Inquire:
I7C7rr
i7C7rr

SSS - Stuck Relay, Seconds (Decimal, 5 B 600 seconds)
FFFFFFFF - Stuck Relay, Seconds (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7C7rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR STUCK RELAY
DEVICE
1


LABEL
PUMP RELAY UNLEADED

STUCK RELAY
60 SEC

Typical Response Message, Computer Format:
i7C7rrYYMMDDHHmmrrFFFFFFFF...
rrFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
rr
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pump Relay Monitor Number (Decimal, 00=all)
Stuck Relay, Seconds (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

445

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7C8
Function Type: Set Pump Relay Monitor Max Run Time
Command Format:
Display: S7C8rrhh
Computer: s7C8rrFFFFFFFF
Notes:
1.
2.

Version 27
Inquire:
I7C8rr
i7C8rr

hh - Max Run Time, Hours (Decimal, 1 B 8 hours)
FFFFFFFF - Max Run Time, Hours (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I7C8rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR MAX RUN TIME
DEVICE
1


LABEL
PUMP RELAY UNLEADED

MAX RUN TIME
8 HR

Typical Response Message, Computer Format:
i7C8rrYYMMDDHHmmrrFFFFFFFF...
rrFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
rr
FFFFFFFF
&&
CCCC

-

Current Date and Time
Pump Relay Monitor Number (Decimal, 00=all)
Max Run Time, Hours (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

446

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 7C9
Function Type: Set Pump Relay Monitor Type
Command Format:
Display: S7C9rrt
Computer: s7C9rrt

Version 28
Inquire:
I7C9rr
i7C9rr

Typical Response Message, Display Format:

I7C9rr
DEC 22, 2006

3:12 PM

PUMP RELAY MONITOR TYPE
DEVICE
1
2


LABEL
PUMP RELAY UNLEADED
PROCESSOR

TYPE
PUMP MONITOR RELAY
VAPOR PROCESSOR

Typical Response Message, Computer Format:
i7C9rrYYMMDDHHmmrrt...
rrt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
rr - Pump Relay Monitor Number (Decimal, 00 = all)
t - Type
1 = Pump Relay Monitor
2 = Vapor Processor
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

447

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.13 I/O DEVICE SETUP
Function Code: 801
Function Type: Set Input Configuration
Command Format:
Display: S801IIf
Computer: s801IIf

Version 1
Inquire:
I801II
i801II

Typical Response Message, Display Format:

I801II
MAR 26, 1996

1:50 PM

EXTERNAL INPUT CONFIGURATION
DEVICE
1


LABEL
EXTERNAL INPUT #1

CONFIGURED
OFF

Typical Response Message, Computer Format:
i801IIYYMMDDHHmmIIf...
IIf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
II - Input Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

448

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 802
Function Type: Set Input Location Label
Command Format:
Display: S802IIaaaaaaaaaaaaaaaaaaaa
Computer: s802IIaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I802II
i802II

Typical Response Message, Display Format:

I802II
MAR 26, 1996

1:50 PM

EXTERNAL INPUT LABEL
DEVICE
1


LABEL
aaaaaaaaaaaaaaaaaaaa

Typical Response Message, Computer Format:
i802IIYYMMDDHHmmIIaaaaaaaaaaaaaaaaaaaa...
IIaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
II
a
&&
CCCC

-

Current Date and Time
Input Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

449

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 803
Function Type: Set Input Type

Version 1

Command Format:
Display: S803IItnTT
Computer: s803IItnTT

Inquire:
I803II
i803II

Typical Response Message, Display Format:

I803II
MAR 26, 1996

1:51 PM

EXTERNAL INPUT TYPE
INPUT
1
2


NAME
EXTERNAL INPUT #1
DCD INPUT

TYPE
ORIENTATION
GENERATOR
NORMALLY CLOSED
STANDARD ACK NORMALLY OPEN

TANK#
2

Typical Response Message, Computer Format:
i803IIYYMMDDHHmmIItnNNTT...
IItnNNTT&&CCCC
Notes:
1.
2.
3.

4.

5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
II - Input Number (Decimal, 00=all)
t - Input type:
1=Standard
2=Generator
3=Pump Sense
4=Acknowledge Alarm
5=Vapor Processor (ISD SEM required)
n - Input Orientation
(Generator & Pump Sense only, not returned for others)
1=Normally Open
2=Normally Closed
NN - Number of Tanks to follow (Hex)
(Generator & Pump Sense only, not returned for others)
TT - Tank Number (Decimal, 00=none)
(Generator & Pump Sense only, not returned for others)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

450

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 804
Function Type: Set Input Dispense Mode
Command Format:
Display: S804IIm
Computer: s804IIm

Version 4
Inquire:
I804II
i804II

Typical Response Message, Display Format:

I804II
MAR 27, 1996

5:51 PM

INPUT DISPENSE MODE
INPUT
1


MODE
MANIFOLDED: ALTERNATE

Typical Response Message, Computer Format:
i804IIYYMMDDHHmmIIm...
IIm&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
II - Input (Pump Sensor) Number (Decimal)
m - Dispense Mode:
1=Standard
2=Manifolded: Alternate
3=Manifolded: Sequential
4=Manifolded: All Pumps
5=Manifolded: Alternate-Height
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

451

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 806
Function Type: Set Relay Configuration
Command Format:
Display: S806RRf
Computer: s806RRf

Version 1
Inquire:
I806RR
i806RR

Typical Response Message, Display Format:

I806RR
MAR 26, 1996

1:51 PM

RELAY CONFIGURATION
DEVICE
1


LABEL
OUTPUT RELAY #1

CONFIGURED
ON

Typical Response Message, Computer Format:
i806RRYYMMDDHHmmRRf...
RRf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
RR - Relay Number (Decimal, 00=all)
f - Configuration Flag
0=Off
1=On
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

452

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 807
Function Type: Set Relay Location Label
Command Format:
Display: S807RRaaaaaaaaaaaaaaaaaaaa
Computer: s807RRaaaaaaaaaaaaaaaaaaaa

Version 1
Inquire:
I807RR
i807RR

Typical Response Message, Display Format:

I807RR
MAR 26, 1996

1:51 PM

RELAY LABEL
DEVICE
1


LABEL
aaaaaaaaaaaaaaaaaaaa

Typical Response Message, Computer Format:
i807RRYYMMDDHHmmRRaaaaaaaaaaaaaaaaaaaa...
RRaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
a
&&
CCCC

-

Current Date and Time
Relay Number (Decimal, 00=all)
Location Label (20 ASCII characters [20h-7Eh])
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

453

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 808
Function Type: Set Relay Alarm Assignments
Command Format:
Display: S808RRAANNTTss
Computer: s808RRAANNTTss
Notes:
1.
2.

Version 1
Inquire:
I808RR
i808RR

RR - Relay number (Decimal, RR>00)
AA - Alarm/Warning Category:
See explanation for "AA" in Function i10100
NN - Alarm Type Number:
See explanation for "NN" in Function i10100
TT - Tank/Sensor Number (Decimal, 00=all)
ss - status
00=clear
01=set

3.
4.
5.

Typical Response Message, Display Format:

I808RR
JUN 1, 2002

8:07 AM

RELAY SETUP REPORT
R 1: STP
TYPE:
STANDARD
NORMALLY CLOSED
ISD BAD DATA ALARM
ISD BAD TEST ALARM

Typical Response Message, Computer Format:
i808RRYYMMDDHHRRnnAANNTTss...
RRnnAANNTTss&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
RR
nn
AA

-

5.

NN -

6.
7.

TT ss -

8.
9.

&& CCCC -

Current Date and Time
receiver number (Decimal, RR>00)
number of alarms to follow (Hex)
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
status
00=clear
01=set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

454

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 809
Function Type: Set Relay Orientation
Command Format:
Display: S809RRs
Computer: s809RRs

Version 2
Inquire:
I809RR
i809RR

Typical Response Message, Display Format:

I809RR
MAR 26, 1996

1:51 PM

RELAY ORIENTATION
RELAY DESIGNATION
1 EXTERNAL RELAY #1


ORIENTATION
NORMALLY OPEN

Typical Response Message, Computer Format:
i809RRYYMMDDHHmmRRs...
RRs&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
RR - Relay Number (Decimal, 00=all)
s - Orientation:
1=Normally Open
2=Normally Closed
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

455

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 80A
Function Type: Set Relay Type
Command Format:
Display: S80ARRt
Computer: s80ARRt
Notes:
1.
2.

Version 4
Inquire:
I80ARR
i80ARR

RR - Relay number (Decimal, 00=all relays)
t - type
1=Standard
2=Pump Control Output
3=Momentary
4=Pump Comm Control
5=Vapor Processor (only one relay can be of this type)

Typical Response Message, Display Format:

I80ARR
JUN 1, 2002

8:07 AM

RELAY TYPE
RELAY
1
2
3


DESIGNATION
EXTERNAL RELAY #1
TANK 1
VAPOR PROCESSOR

TYPE
STANDARD
PUMP CONTROL
VAPOR PROCESSOR

Typical Response Message, Computer Format:
i80ARRYYMMDDHHRRt&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
RR - Relay number (Decimal, 00=all relays)
t - type
1=Standard
2=Pump Control Output
3=Momentary
4=Pump Comm Control
5=Vapor Processor (only one relay can be of this type)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

456

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 80B
Function Type: Set Relay Tank Assignment
Command Format:
Display: S80BRRtt
Computer: s80BRRtt

Version 4
Inquire:
I80BRR
i80BRR

Typical Response Message, Display Format:

I80BRR
MAR 26, 1996

1:51 PM

RELAY TANK ASSIGNMENT
RELAY DESIGNATION
1 EXTERNAL RELAY #1


TANK
1

Typical Response Message, Computer Format:
i80BRRYYMMDDHHmmRRtt...
RRtt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
RR
tt
&&
CCCC

-

Current Date and Time
Relay Number (Decimal, 00=All)
Relay Tank Assignment (00=No Assignment)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

457

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 80C
Function Type: Set External Input Type

Version 25

Command Format:
Display: S80CIItOTT...TT
Computer: s80CIItOTT...TT
Notes:
1.
2.

3.
4.

Inquire:
I80CII
i80CII

II - Input device number (Decimal, 00=all)
t - Input type
1=standard
2=generator
3=pump sense
4=standard acknowledge
5=Vapor Processor
O - Input orientation
1=normally open
2=normally closed
TT...TT - tank numbers (for input type 2 and 3 only) (Decimal)

Typical Response Message, Display Format:

I80CII
JUN 1, 2002

8:07 AM

EXTERNAL INPUT TYPE
INPUT
1
2


NAME
TYPE
ORIENTATION
EXTERNAL INPUT #1
STANDARD
NORMALLY CLOSED
OPW VAPOR PROCESSOR VAPOR PROCESSOR NORMALLY OPEN

TANK#
1

Typical Response Message, Computer Format:
i80CIIYYMMDDHHmmIItOnnTT...TT
IItOnnTT...TT&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
II - Input device number (Decimal)
t - input type
1=standard
2=generator
3=pump sense
4=standard acknowledge
5=Vapor Processor (ISD SEM required)
O - orientation
1=normally open
2=normally closed
nn - number of tanks to follow (Hex)
TT...TT - tank numbers (Decimal, 00=none)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

458

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 811
Function Type: Set External Input Alternate Modes
Auto Active Pump Switchover Enable
Command Format:
Display: S811IIf
Computer: s811IIf
Notes:
1.

Version 33

Inquire:
I811II
i811II

f - 0=disabled; 1=enabled

Typical Response Message, Display Format:

I811II
JUN 1, 2002

8:07 AM

EXTERNAL INPUT ALTERNATE MODE SWITCHOVER ENABLE
DEVICE LABEL
S 1:UNLEADED GASOLINE
S 2:UNLEADED GASOLINE


ENABLD
YES
NO

Typical Response Message, Computer Format:
i811IIYYMMDDHHmmIIf
IIf&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
II - External Input number (Decimal, 00=all)
f - Auto Switchover Enabled:
0=No
1=Yes
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

459

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 812
Function Type: Set External Input Alternate Mode
Auto Active Pump Switchover Volume Threshold
Command Format:
Display: S812IIGGGG
Computer: s812IIFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I812II
i812II

II - External Input Number (Decimal, 00=all)
GGGG - Full Height Volume, Gallons (Decimal)
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I812II
JUN 1, 2002

8:07 AM

EXTERNAL INPUT ALTERNATE MODE SWITCHOVER THRESHOLD
DEVICE LABEL
1
REGULAR UNLEADED


GALLONS
200

Typical Response Message, Computer Format:
i812IIYYMMDDHHmmIIFFFFFFFF
IIFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
II
FFFFFFFF
&&
CCCC

-

Current Date and Time
External Input Number (Decimal, 00=all)
Switchover Threshold, Gallons (ASCII Hex IEEE Float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

460

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 813
Function Type: Set External Input Alternate-Height Mode
Auto Active Pump Switchover Height Threshold
Command Format:
Display: S813IIhhhh.h
Computer: s813IIFFFFFFFF
Notes:
1.
2.
3.

Version 33

Inquire:
I813II
i813II

II - External Input Number (Decimal, 00=all)
hhhh.h - Switchover Threshold, Inches and tenths (Decimal)
FFFFFFFF - Switchover Threshold, Inches (ASCII Hex IEEE float)

Typical Response Message, Display Format:

I813II
JUN 1, 2002

8:07 AM

EXTERNAL INPUT ALTERNATE-HEIGHT MODE SWITCHOVER THRESHOLD
DEVICE LABEL
S 1:UNLEADED


INCHES
2.0

Typical Response Message, Computer Format:
i813IIYYMMDDHHmmIIFFFFFFFF
IIFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
II
FFFFFFFF
&&
CCCC

-

Current Date and Time
External Input Number (Decimal, 00=all)
Switchover threshold, Inches (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

461

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.14 EEPROM SETUP
Function Code: 851
Function Type: Restore All Setup Data from EEPROM
Command Format:
Display: S85100149
Computer: s85100149
Notes:
1.

Version 107
Inquire:
I85100
i85100

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I85100
JAN 24, 1996

2:55 PM

RESTORE SETUP DATA: DISABLED

Typical Response Message, Computer Format:
i85100YYMMDDHHmmSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
SS - Status
00=Disabled
01=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

462

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 852
Function Type: Save All Setup Data to EEPROM
Command Format:
Display: S85200149
Computer: s85200149
Notes:
1.

Version 107
Inquire:
I85200
i85200

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I85200
JAN 24, 1996

2:55 PM

SAVE SETUP DATA: DISABLED

Typical Response Message, Computer Format:
i85200YYMMDDHHmmSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
SS - Status
00=Disabled
01=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

463

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 853
Function Type: Clear All Setup Data from EEPROM
Command Format:
Display: S85300149
Computer: s85300149
Notes:
1.

Version 107
Inquire:
I85300
i85300

149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I85300
JAN 24, 1996

2:55 PM

CLEAR SETUP DATA: DISABLED

Typical Response Message, Computer Format:
i85300YYMMDDHHmmSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
SS - Status
00=Disabled
01=Enabled
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

464

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.3.15 MISCELLANEOUS SETUP
Function Code: 881
Function Type: Set Communication Port Data
Command Format:
Display: S881PPBBBBBPSDTAA
Computer: s881PPBBBBBPSDTAA
Notes:
1.

Version 9
Inquire:
I881PP
i881PP

PP - Communication Port Number (Decimal 01..06)

Typical Response Message, Display Format:

I881PP
JUN 1, 2000 8:10 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY
: ODD
STOP BIT
: 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : 123456

Typical Response Message, Computer Format:
i881PPYYMMDDHHmmBBBBBPSDTAA&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm
BBBBB
P
S
D
T
AA
&&
CCCC

-

Current Date and Time
Baud Rate (Decimal)
Parity (Decimal; 0=None, 1 or 2)
Stop Bit (Decimal; 1 or 2)
Data Bit (Decimal; 7 or 8)
Pulse or Tone (Decimal; 0=Tone, 1=Pulse)
Number of Rings before Answer (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

465

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 882
Function Type: Initialize Communication Port Data
Command Format:
Display: S882PP149
Computer: s882PP149
Notes:
1.
2.

Version 9
Inquire:
I882PP
i882PP

PP - Communication Port Number (Decimal 01..06)
149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

I882PP
JUN 1, 2000 8:10 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY
: ODD
STOP BIT
: 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : 123456

Typical Response Message, Computer Format:
i882PPYYMMDDHHmmBBBBBPSDTAA&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm
BBBBB
P
S
D
T
AA
&&
CCCC

-

Current Date and Time
Baud Rate (Decimal)
Parity (Decimal; 0=None, 1 or 2)
Stop Bit (Decimal; 1 or 2)
Data Bit (Decimal; 7 or 8)
Pulse or Tone (Decimal; 0=Tone, 1=Pulse)
Number of Rings before Answer (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

466

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 885
Function Type: Set SiteLink Modem Type
Command Format:
Display: S885PPMM
Computer: s885PPMM

Version 19
Inquire:
I885PP
i885PP

Typical Response Message, Display Format:

I885PP
NOV 5, 1999 12:00 AM
COM BOARD 1:
MODEM TYPE :


S-LINK
NETCOMM SMART M7F

Typical Response Message, Computer Format:
i885PPYYMMDDHHmmMM&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
MM - Modem Type:
00=NETCOMM SMART M7F
01=US ROBOTICS (UK)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

467

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 886
Function Type: Set Modem Setup String
Command Format:
Display: S886PPaaaaaaaaaaaaaaaaaaaa
Computer: s886PPaaaaaaaaaaaaaaaaaaaa
Notes:
1.

Version 20
Inquire:
I886PP
i886PP

PP - Communication Port Number (Decimal 01..06)

Typical Response Message, Display Format:

I886PP
JUN 1, 2000

8:15 AM

COMM BOARD : 3 (FXMOD)
MODEM SETUP STRING : GJMDAQ

Typical Response Message, Computer Format:
i886PPYYMMDDHHmmaaaaaaaaaaaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
a
&&
CCCC

-

Current Date and Time
Modem Setup String (20 ASCII characters)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

468

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 887
Function Type: Set Dial Tone Validation Interval
Command Format:
Display: S887PPHHHH
Computer: s887PPHHHH
Notes:
1.

Version 20
Inquire:
I887PP
i887PP

PP - Modem or SiteLink Board Number (Port #) (Decimal 01..06)

Typical Response Message, Display Format:

I887PP
JUN 1, 2000

8:15 AM

COMM BOARD : 3 (FXMOD)
DIAL TONE VALIDATION INTERVAL:


32 HOURS

Typical Response Message, Computer Format:
i887PPYYMMDDHHmmHHHH&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
HHHH - Number of Idle Hours Before Receiver board checks for dial
tone (Decimal 0001-9999)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

469

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 888
Function Type: Communication Status Information

Version 19

Command Format:
Display: I888PP
Computer: i888PP
Typical Response Message, Display Format:

I888PP
JAN 1, 1996

9:12 AM

COMM BOARD : 1 (RS-232)
CONNECTION : NONE
COMM BOARD : 2 (FXMOD)
CONNECTION : MODEM DIAL IN
FUNCTION
: NONE
ERROR
: UART SETTINGS ERROR
BAUD RATE : 2400
PARITY
: ODD
STOP BIT
: 1 STOP
DATA LENGTH: 7 DATA
TIME OF LAST COMM DATA: JAN 1, 1996
TIME OF LAST COMM ERROR: JAN 1, 1996


Part No. 576013-635, Revision AA

9:12 AM
8:00 AM

470

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 888: (Continued)
Typical Response Message, Computer Format:
i888PPYYMMDDHHmmNNPPnnCCSSEEBBBBBPSDYYMMDDHHmmYYMMDDHHmm...
PPnnCCSSEEBBBBBPSDYYMMDDHHmmYYMMDDHHmm&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
NN - Total Number of Error Reports To Follow
3.
PP - Communication Port Number (00=all)
4.
nn - Number of Errors to follow for each port
5.
CC - Connect Type
00=NO CONNECTION
01=AUTO DIAL TELETYPE
02=AUTO DIAL FAX
03=AUTO DIAL COMPUTER
04=AUTO TRANSMIT
05=MODEM DIAL IN
06=RS232 REQUEST
6.
SS - State or Function Code (Decimal):
00=NONE
01=OPEN PHONE PORT
02=MODEM CHECK CONNECTION
03=TRANSMITTING DATA
04=CHECKING FOR CARRIER
05=WAITING FOR DATA
06=HANGING UP
07=FAXMODEM INITIALIZING
08=FAX CHECK CONNECTION
09=FAX CHECK PAGE
10=FAX END PAGE
11=FAX BUILD MESSAGE
7.
EE - Error Code (Decimal):
01=UART SETTINGS ERROR
02=MODEM INITIALIZATION FAILED
03=MODEM TIMED OUT
04=LOST CARRIER
05=DATA TIMED OUT
06=HANG UP FAILED
07=FAX INITIALIZATION FAILED
08=FAX CONNECTION FAILED
09=FAX TIMED OUT
10=FAX INTERPAGE ERROR
11=FAX END PAGE ERROR
12=FAX BUILD MESSAGE ERROR
8.
BBBBB - BAUD of UART During Error (Decimal)
9.
P - Parity of UART During Error (Decimal):
0: None
1: Odd
2: Even
3: Mark
4: Space
10.
S - Stop Bits of UART During Error (Decimal)
11.
D - Data Bits of UART During Error (Decimal)
12.
YYMMDDHHmm - Last Communication Date/Time
13.
YYMMDDHHmm - Last Error's Date/Time
14.
&& - Data Termination Flag
15.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

471

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 889
Function Type: DTR Normal State for Serial Satellite Boards
Command Format:
Display: S889PPs
Computer: s889PPs
Notes:
1.

Version 121
Inquire:
I889PP
i889PP

PP - Communication Port Number (01..06)

Typical Response Message, Display Format:

I889PP
AUG 22, 2000

4:49 PM

COMM BOARD : 1 (S-SAT )
DTR NORMAL STATE: HIGH

Typical Response Message, Computer Format:
i889PPYYMMDDHHmms&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
s - DTR Normal State for Serial Satellite Board
0=Normally Low
1=Normally High (Default)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

472

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 88D
Function Type: Communication Diagnostic for SiteLink

Version 23

Command Format:
Display: I88DPP
Computer: i88DPP
Notes:
1.

PP - Communication Port Number (Decimal 01..06)

Typical Response Message, Display Format:

I88DPP
JUN 1, 2000

8:10 AM

COMMUNICATION DIAGNOSTIC
COMM BOARD

: 1 S-LINK

MODEM TYPE : VR TLS GSM MODEM
MODEM AUTO DETECTED: VR TLS GSM MODEM
RSSI: XX
BER: XX

Typical Response Message, Computer Format:
i88DPPYYMMDDHHmmPPMMDDrree&&CCCC
Notes:
1.
2.
3.

4.

5.

6.

7.
8.

YYMMDDHHmm - Current Date and Time
PP - Communication Port Number (Decimal 01..06)
MM - Modem Type:
00=NETCOMM SMART M7F
01=US ROBOTICS (UK)
02=VR TLS ANALOG MOD
03=VR TLS GSM MODEM
DD - Modem Auto Detected:
00=NETCOMM SMART M7F
01=US ROBOTICS (UK)
02=VR TLS ANALOG MOD
03=VR TLS GSM MODEM
rr - RSSI received signal strength indication (Decimal), only
valid if Modem Type is WAVECOM GSM.
00
: -113 dBm or less
01
: -111 dBm
02...30 : -109 to -53 dBm
31
: -51 dBm or greater
99
: not known or not detectable
ee - BER channel bit error (Decimal), only valid if Modem Type is
VR TLS GSM MODEM
00...7 : as RXQUAL values in the table GSM 05.08
99
: not known or not detectable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

473

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 891
Function Type: Set AccuChart Calibration Restart
Command Format:
Display: S891TT149
Computer: s891TT149
Notes:
1.
2.

Version 108
Inquire:
I891TT
i891TT

TT - Tank Number (command valid for single tank only)
149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:

S891TT
MAR 29, 1996

6:27 PM

T 1:REGULAR UNLEADED ACCU_CHART RESTART

Typical Response Message, Computer Format:
i891TTYYMMDDHHmmTTSS&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal)
3.
SS - Status:
01=AccuChart restarted
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

474

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8A2
Function Type: Service Code List

Version 27

Command Format:
Display: I8A200
Computer: i8A200
Typical Response Message, Display Format:

I8A200
JAN 22, 2006
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:11 PM
1....
2....
3....
4....

SERVICE CODE LIST
STANDARD LABEL
REPROGRAMMED TLS
COLD BOOT SYSTEM
REPLACED PC BOARD
NO PROBLEM FOUND
NO SOLUTION FOUND
OTHER SOLUTION

CODE
0101
0102
0103
0104
0105
0106

USER DEFINED LABEL
MAINTENANCE CALL
MANUAL TEST


CODE
9902
9910

Typical Response Message, Computer Format:
i8A200YYMMDDHHmmNNNnnnnnnnnnnnnnnnnnnncccc...
nnnnnnnnnnnnnnnnnnncccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
NNN
nnnYnnn
cccc
&&
CCCC

-

Current Date and Time
Number of Service Codes to follow (Decimal)
Service code label (19 characters, ASCII)
Four digit Service Code (ASCII)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

475

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8A3
Function Type: Maintenance Tracker Active Hardware Key List

Version 27

Command Format:
Display: I8A300
Computer: i8A300
Typical Response Message, Display Format:

I8A300
JAN 22, 2006

3:11 PM

MAINTENANCE TRACKER ACTIVE HARDWARE KEY LIST
LABEL
J SMITH
J DOE


ID
A12345
A54321

Typical Response Message, Computer Format:
i8A300YYMMDDHHmmNNNnnnnnnnnnnnnnnnnncccccc...
nnnnnnnnnnnnnnnnncccccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
NNN
nnnYnnn
cccccc
&&
CCCC

-

Current Date and Time
Number of hardware keys to follow (Decimal)
ID label (17 characters, ASCII)
Six digit ID code (ASCII)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

476

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8A4
Function Type: Maintenance Tracker Block Hardware Key
Command Format:
Display: S8A400149cccccc
Computer: s8A400149cccccc
Notes:
1.
2.

Version 27
Inquire:
I8A400
i8A400

149 - This verification code must be sent to confirm the command
cccccc - Six digit ID code to block (ASCII).

Typical Response Message, Display Format:

I8A400
JAN 22, 2006

3:11 PM

MAINTENANCE TRACKER BLOCK HARDWARE KEY
LABEL
J SMITH
J DOE


ID
A12345
A54321

Typical Response Message, Computer Format:
i8A400YYMMDDHHmmNNNnnnnnnnnnnnnnnnnncccccc...
nnnnnnnnnnnnnnnnncccccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
NNN
nnnYnnn
cccccc
&&
CCCC

-

Current Date and Time
Number of blocked hardware keys to follow (Decimal)
ID label (17 characters, ASCII)
Six digit blocked ID codes (ASCII)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

477

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8BC
Function Type: Set Relay Alarm Assignments II
Command Format:
Display: S8BCRRAANNTTSS
Computer: s8BCRRAANNTTSS

Version 19
Inquire:
I8BCRR
i8BCRR

Typical Response Message, Display Format:

I8BCRR
JAN 15, 1996 4:29 PM
RELAY SETUP REPORT
R 1:
TYPE:
STANDARD
NORMALLY OPEN
PRESSURE LINE LEAK
Q 1:ANNUAL LINE FAIL

Typical Response Message, Computer Format:
i8BCRRYYMMDDHHmmRRnnAANNTTSS...
RRnnAANNTTSS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
RR
nn
AA

-

5.

NN -

6.
7.

TT SS -

8.
9.

&& CCCC -

Current Date and Time
Relay Number (Decimal, 00=all)
Number of Alarms to Follow (Hex)
Alarm/Warning Category:
See explanation for "AA" in Function i10100
Alarm Type Number:
See explanation for "NN" in Function i10100
Tank/Sensor Number (Decimal, 00=all)
Status:
00=Clear
01=Set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

478

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8C1
Function Type: VMC Edit/Add Serial Number
Command Format:
Display: S8C1xxIIIIII
Computer: s8C1xxIIIIII
Notes:
1.
2.

Version 28
Inquire:
I8C1xx
i8C1xx

xx - VMC Number (Decimal, 01-18, 00=all)
IIIIII - Serial Number (Decimal)

Typical Response Message, Display Format:

I8C1xx
JAN 22, 2007

3:11 PM

VMC SETUP
VMC
1
2
3


S/N
111111
222222
333333

Typical Response Message, Computer Format:
i8C1xxYYMMDDHHmmxxIIIIII...
xxIIIIII&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
xx
IIIIII
cccc
&&
CCCC

-

Current Date and Time
VMC Number (Decimal, 01-18, 00=all)
Serial Number (Decimal)
Four digit Service Code (ASCII)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

479

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8C2
Function Type: VMC Remove Serial Number
Command Format:
Display: S8C2xxIIIIII
Computer: s8C2xxIIIIII
Notes:
1.
2.

Version 28
Inquire:
I8C2xx
i8C2xx

xx - VMC Number (Decimal, 01-18, 00=all)
IIIIII - Serial Number (Decimal)

Typical Response Message, Display Format:

S8C2xx
JAN 22, 2007

3:11 PM

REMOVE VMC SERIAL NUMBER
VMC
S/N
1
333333

Typical Response Message, Computer Format:
i8C2xxYYMMDDHHmmxxIIIIII&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
xx
IIIIII
&&
CCCC

-

Current Date and Time
VMC Number (Decimal, 01-18, 00=all)
Serial Number (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

480

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8C3
Function Type: VMC Edit/Add Fueling Position Number
Command Format:
Display: S8C3xxAABB
Computer: s8C3xxAABB
Notes:
1.
2.
3.

Version 31
Inquire:
I8C3xx
i8C3xx

xx - VMC Number (Decimal, 01-18, 00=all)
AA - Side A Fueling Position Number (Decimal 00-99)
BB - Side B Fueling Position Number (Decimal 00-99)

Typical Response Message, Display Format:

S8C3xx
JAN 22, 2010

3:11 PM

VMC FUELING POSITION SETUP
VMC
1
2
3


S/N
SIDE A
333333
1
333333
3
333333
11

SIDE B
2
4
12

Typical Response Message, Computer Format:
i8C3xxYYMMDDHHmmxxAABB…
xxAABB&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
xx
AA
BB
&&
CCCC

-

Current Date and Time
VMC Number (Decimal, 01-18, 00=all)
Side A Fueling Position Number (Decimal 00-99)
Side B Fueling Position Number (Decimal 00-99)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

481

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 8C4
Function Type: VMC Communications Timeout Value
Command Format:
Display: S8C400hh
Computer: s8C400hh

Version 31
Inquire:
I8C400
i8C400

Typical Response Message, Display Format:

S8C4xx
JAN 22, 2010

3:11 PM

VMC COMMUNICATIONS TIMEOUT
TIMEOUT VALUE: 0 HOURS

Typical Response Message, Computer Format:
i8C4xxYYMMDDHHmmhh&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
hh
&&
CCCC

-

Current Date and Time
Timeout value in hours (Decimal, 00-99, 99=Alarm Disabled)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

482

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.4 DIAGNOSTIC REPORTS
7.4.1 SYSTEM DIAGNOSTIC REPORTS
Function Code: 901
Function Type: Self Test Results Report

Version 1

Command Format:
Display: I90100
Computer: i90100
Typical Response Message, Display Format:

I90100
JAN 22, 1996
SYSTEM BOARD


3:24 PM
I/O
PASS

RAM
PASS

PROM
PASS

Typical Response Message, Computer Format:
i90100YYMMDDHHmmIIRRPP&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm - Current Date and Time
II - I/O Test result
00=pass
01=fail
RR - RAM Test result
00=pass
01=fail
PP - PROM Test result
00=pass
01=fail
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

483

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 902
Function Type: System Revision Level Report

Version 1

Command Format:
Display: I90200
Computer: i90200
Typical Response Message, Display Format:

I90200
JAN 22, 1996 3:24 PM
SOFTWARE REVISION LEVEL
VERSION 110.01
SOFTWARE# 346110-101-B
CREATED - 95.11.20.13.28
S-MODULE# 330160-115-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
BIR
FUEL MANAGER
PLLD
0.10 REPETITIV
0.20 REPETITIV

Typical Response Message, Computer Format:
i90200YYMMDDHHmmSOFTWARE# nnnnnn-vvv-rrrCREATED - YY.MM.DD.HH.mm&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
nnnnnn-vvv - Software version number (ASCII text string)
3.
rrr - Software revision level (ASCII text string)
4. YY.MM.DD.HH.mm - Date and time of software creation
5.
&& - Data Termination Flag
6.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

484

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 903
Function Type: PC Diagnostic Report

Version 106

Command Format:
Display: I90300
Computer: i90300
Typical Response Message, Display Format:

I90300
JAN 22, 1996 3:24 PM
PC DIAGNOSTIC DATA
PERIPHERAL CONTROLLER
- - - - - - - - - - - PC SWARE# 330269-002-B
CREATED - 94.12.16.13.26
PC ROM CHECKSUM=PASSED
PC RESET COUNTS=
6
PC COMM ERRORS =
0
MC CKSUM ERRS =
108
MC->PC COMMS= 36261666
MC<-PC COMMS= 36262714

Typical Response Message, Computer Format:
i90300YYMMDDHHmmP..PT..TNNR..RE..ES..St..tr..r&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

YYMMDDHHmm - Current Date and Time
P..P - Software Part Number (14 characters)
Y..T - Software Creation Date and Time (14 characters)
YY.MM.DD.HH.MM
NN - Number of values to follow (Decimal)
R..R - PC Reset Counts (Hex, 8 characters)
E..E - PC Communication Errors (Hex, 8 characters)
S..S - MC Checksum Errors (Hex, 8 characters)
t..t - MC -> PC Command Send Counts (Hex, 8 characters)
r..r - MC <- PC Command Receive Counts (Hex, 8 characters)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

485

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 905
Function Type: System Revision Level Report II

Version 15

Command Format:
Display: I90500
Computer: i90500
Typical Response Message, Display Format:

I90500
JUL 29, 1997 9:08 AM
SOFTWARE REVISION LEVEL
VERSION 115.00 TEST #05
SOFTWARE# 346115-199-AX5
CREATED - 97.07.10.20.21
S-MODULE# 330160-115-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
BIR
FUEL MANAGER
PLLD
0.10 REPETITIV
0.20 REPETITIV

Typical Response Message, Computer Format:
i90500YYMMDDHHmmSOFTWARE# 346abb-Tvv-rrrCREATED - YY.MM.DD.HH.mm
nnAABBCCDDEEFFGGHHIIJJKKLLS-MODULE# nnnnnn-vvv-r&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
346 - Software Base number (fixed)
a - Platform
0=Standard CPU, PLLD only
1=Enhanced CPU
2=(Unused)
3=Enhanced CPU 16 Tank
4=Standard CPU without PLLD & WPLLD
5=Standard CPU, WPLLD only
bb - Version level (eg version "15")
T - Software Type
1="Real"
2="Demo"
3="IFSF"

Part No. 576013-635, Revision AA

486

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code 905 Notes: (Continued)
6.

vv - Language
00=English/Spanish
01=English/French
02=English/German
03=English/Swedish
04=English/Portuguese
05=English/Polish
06=English/Finnish
07=English/Japanese
08=English/Greek
09=English/Russian
10=English/Turkish
11=English/Dutch
12=English/Italian
99=English only

7.
rrr - Revision level (eg revision "AX1")
8. YY.MM.DD.HH.mm - Date and time of software creation
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.

nn
AA
BB
CC
DD
EE
FF
GG
HH
II
JJ
KK
LL

-

number of 2 byte values to follow (Hex)
PERIODIC IN-TANK TESTS (00=DISABLE, 01=ENABLE)
ANNUAL IN-TANK TESTS (00=DISABLE, 01=ENABLE)
CSLD (00=DISABLE, 01=ENABLE)
BIR (00=DISABLE, 01=ENABLE)
FUEL MANAGER (00=DISABLE, 01=ENABLE)
PRECISION PLLD (00=DISABLE, 01=ENABLE)
TANKER LOAD (00=DISABLE, 01=ENABLE)
0.2 GPH PLLD (00=DISABLE, 01=ENABLE)
PRECISION PLLD ON DEMAND (00=DISABLE, 01=ENABLE)
SPECIAL 3-TANK/LINE CONSOLE (00=DISABLE, 01=ENABLE)
ISD (00=DISABLE, 01=ENABLE)
UNUSED WAS PMC (00=DISABLE, 01=ENABLE)
(Version 29)

22.
23.
24.
25.
26.
27.

nnnnnn-vvv-r
nnnnnn
vvv
r
&&
CCCC

-

SEM Info 3 parts, if none "NO SOFTWARE MODULE"
SEM number (ASCII text string)
SEM Software version number (ASCII text string)
SEM Software revision level (ASCII text string)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

487

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: 908
Function Type: Power Up Time Report

Version 33

Command Format:
Display: I90800
Computer: i90800
Typical Response Message, Display Format:

I90800
JUL 29, 2012

9:08 AM

SYSTEM POWER UP TIME = 1234 DAYS, 21 HOURS, 31 MINUTES

Typical Response Message, Computer Format:
i90800YYMMDDHHmmllllllll&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
llllllll
&&
CCCC

-

Current Date and Time
Power Up Time (minutes) ASCII-Hex long
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

488

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.4.2 IN-TANK DIAGNOSTIC REPORTS
Function Code: A01
Function Type: Probe Type and Serial Number

Version 1

Command Format:
Display: IA01TT
Computer: iA01TT
Typical Response Message, Display Format:

IA01TT
JAN 22, 1996
TANK 1
TANK 2
TANK 3


3:25 PM

REGULAR UNLEADED
SUPER UNLEADED
PREMIUM UNLEADED

TYPE
MAG
CAP1
CAP0

CODE
C000
A66C
0001

LENGTH
96.00
96.00
96.00

SERIAL NO.
000418
278147
200100

D/CODE
1401
2410
0000

Typical Response Message, Computer Format:
iA01TTYYMMDDHHmmTTpPPKKKKFFFFFFFFSSSSSScccc...
TTpPPKKKKFFFFFFFFSSSSSScccc&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.
10.

KKKK
FFFFFFFF
SSSSSS
cccc
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Circuit Code (Hex)
Probe Length (ASCII Hex IEEE float)
Probe Serial Number (Decimal)
Probe Date Code (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

489

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A02
Function Type: Probe Factory Dry Calibration Values

Version 1

Command Format:
Display: IA02TT
Computer: iA02TT
Typical Response Message, Display Format:

IA02TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
TANK 2 SUPER UNLEADED
1573.000 1871.000 5020.000
5033.000 4972.000 5045.000
265.000
311.000
836.000
839.000
827.000
837.000
TANK 3 PREMIUM UNLEADED
97.000
180.000
649.000


MAG
GRADIENT= 178.1400
CAP1
FACTORY DRYS
4977.000 4961.000 5006.000
834.000

827.000

CAP0
FACTORY DRYS
657.000
652.000

4967.000

5019.000

827.000

833.000

834.000

655.000

647.000

657.000

Typical Response Message, Computer Format:
iA02TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

490

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A03
Function Type: Probe Factory Wet Calibration Values

Version 1

Command Format:
Display: IA03TT
Computer: iA03TT
Typical Response Message, Display Format:

IA03TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
TANK 2 SUPER UNLEADED
3066.000 3197.000 8321.000
8335.000 8205.000 8332.000
569.000
576.000 1485.000
1479.000 1472.000 1474.000
TANK 3 PREMIUM UNLEADED
130.000
335.000 1214.000


MAG
GRADIENT= 178.1400
CAP1
FACTORY WETS
8213.000 8230.000 8189.000

8251.000

8296.000

1486.000

1477.000

1479.000

1476.000

CAP0
FACTORY WETS
1214.000 1204.000 1217.000

1200.000

1222.000

1471.000

Typical Response Message, Computer Format:
iA03TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

491

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A04
Function Type: Probe Updated Dry Calibration Values

Version 1

Command Format:
Display: IA04TT
Computer: iA04TT
Typical Response Message, Display Format:

IA04TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
TANK 2 SUPER UNLEADED
1573.000 1871.000 5020.000
5033.000 4972.000 5045.000
265.000
311.000
836.000
839.000
827.000
837.000
TANK 3 PREMIUM UNLEADED
97.000
180.000
649.000


MAG
CAP1
UPDATED DRYS
4977.000 4961.000 5006.000
834.000

827.000

CAP0
UPDATED DRYS
657.000
652.000

4967.000

5019.000

827.000

833.000

834.000

655.000

647.000

657.000

Typical Response Message, Computer Format:
iA04TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

492

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A05
Function Type: Probe Updated Wet Calibration Values

Version 1

Command Format:
Display: IA05TT
Computer: iA05TT
Typical Response Message, Display Format:

IA05TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
TANK 2 SUPER UNLEADED
3119.000 3197.000 8321.000
8335.000 8205.000 8332.000
569.000
576.000 1485.000
1479.000 1472.000 1474.000
TANK 3 PREMIUM UNLEADED
130.000
335.000 1214.000


MAG
CAP1
UPDATED WETS
8213.000 8230.000 8189.000

8251.000

8296.000

1486.000

1477.000

1479.000

1476.000

CAP0
UPDATED WETS
1214.000 1204.000 1217.000

1200.000

1222.000

1471.000

Typical Response Message, Computer Format:
iA05TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

493

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A06
Function Type: Probe Segment Sensitivity Ratios

Version 1

Command Format:
Display: IA06TT
Computer: iA06TT
Typical Response Message, Display Format:

IA06TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
TANK 2 SUPER UNLEADED
0.000
0.703
0.356
1.000
1.007
0.987
0.000
0.734
0.353
0.989
1.024
0.977
TANK 3 PREMIUM UNLEADED
0.000
1.023
0.279


MAG
CAP1
SENSITIVITY RATIOS
1.002
1.011
0.970

1.032

0.982

1.005

0.985

0.995

CAP0
SENSITIVITY RATIOS
0.971
1.010
1.003

1.010

0.988

1.006

1.006

Typical Response Message, Computer Format:
iA06TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

494

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A07
Function Type: Probe Reference Distance Diagnostic

Version 23

Command Format:
Display: IA07TT
Computer: iA07TT
Typical Response Message, Display Format:

IA07TT
JAN 22, 1996

3:25 PM

TANK 1 REGULAR UNLEADED
MAG7
ORIG REF DISTANCE
12/01/00 XXXXX.XX
CURR REF DISTANCE
12/01/01 XXXXX.XX

Typical Response Message, Computer Format:
iA07TTYYMMDDHHmmTTpPPYYMMDDFFFFFFFFYYMMDDFFFFFFFF...
TTpPPYYMMDDFFFFFFFFYYMMDDFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.
10.

YYMMDD
FFFFFFFF
YYMMDD
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type: (Probe types 01=CAP0 and 02=CAP1 are not
supported by this command)
03=MAG1
Date of reading
Original Ref distance reading (ASCII Hex IEEE float)
Date of reading
Current Reference distance reading (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

495

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A10
Function Type: Probe Last Sample Buffers

Version 1

Command Format:
Display: IA10TT
Computer: iA10TT
Typical Response Message, Display Format:

IA10TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
MAG
NUMBER OF SAMPLES=44520
694.000 8587.000 8587.000 8587.000 8587.000 8587.000 8589.000 8589.000
8586.000 8587.000 8587.000 38250.000 31771.000 30813.000 30617.000 30251.000
30253.000 30261.000 38262.000
TANK 2 SUPER UNLEADED
CAP1
NUMBER OF SAMPLES= 1081
6852.000 6930.000 12054.000 11946.000 11963.000 11922.000 11984.000 12029.000
9026.000 8705.000 8779.000 8290.000 3733.000 4150.000 4144.000 4137.000
4132.000 4126.000 4120.000 2954.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TANK 3 PREMIUM UNLEADED
CAP0
NUMBER OF SAMPLES= 1082
234.000
439.000 1317.000 1319.000 1307.000 1321.000 1104.000
761.000
104.000 1686.000

Typical Response Message, Computer Format:
iA10TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.

SSSS
NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Sample Number (Hex)
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

496

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A11
Function Type: Probe Fast Average Buffers

Version 1

Command Format:
Display: IA11TT
Computer: iA11TT
Typical Response Message, Display Format:

IA11TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
MAG
NUMBER OF SAMPLES=
695.000 8587.200 8587.400 8587.400 8587.000 8587.000
8587.400 8587.000 8587.000 38257.801 31768.199 30813.801
30252.398 30259.600 38261.801
TANK 2 SUPER UNLEADED
CAP1
NUMBER OF SAMPLES=
6852.000 6930.000 12054.000 11946.000 11963.000 11922.000
9026.000 8705.000 8777.000 8290.000 3733.000 4150.000
4132.000 4126.000 4120.000 2954.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TANK 3 PREMIUM UNLEADED
CAP0
NUMBER OF SAMPLES=
234.000
439.000 1317.000 1319.000 1307.000 1321.000
104.000 1686.000


5
8587.000 8587.000
30616.000 30250.398
5
11984.000 12029.000
4144.000 4137.000
0.000
0.000
0.000
0.000
5
1104.000

761.000

Typical Response Message, Computer Format:
iA11TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.

SSSS
NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of Samples (Hex)
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

497

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A12
Function Type: Probe Standard Average Buffers

Version 1

Command Format:
Display: IA12TT
Computer: iA12TT
Typical Response Message, Display Format:

IA12TT
JAN 22, 1996 3:25 PM
TANK 1 REGULAR UNLEADED
MAG
NUMBER OF SAMPLES=
20
695.100 8587.000 8587.450 8587.300 8587.050 8587.650 8587.050 8587.050
8587.200 8587.000 8587.000 38258.148 31767.449 30814.250 30616.801 30250.500
30252.500 30259.801 38261.750
TANK 2 SUPER UNLEADED
CAP1
NUMBER OF SAMPLES=
40
6852.000 6930.000 12054.000 11946.000 11963.000 11922.000 11984.000 12029.000
9026.000 8705.000 8779.000 8290.000 3733.000 4150.000 4144.000 4137.000
4132.000 4126.000 4120.000 2954.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TANK 3 PREMIUM UNLEADED
CAP0
NUMBER OF SAMPLES=
40
234.000
439.000 1317.000 1317.000 1307.000 1321.000 1104.000
761.000
104.000 1686.000

Typical Response Message, Computer Format:
iA12TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.

SSSS
NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of Samples (Hex)
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

498

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A13
Function Type: Probe Long Term Average Buffers

Version 1

Command Format:
Display: IA13TT
Computer: iA13TT
Typical Response Message, Display Format:

IA13TT
JAN 22, 1996 3:26 PM
TANK 1 REGULAR UNLEADED
MAG
NUMBER OF SAMPLES=44544
695.555 9687.276 9687.250 9687.222 9687.210 9687.204 9960.201 9960.196
9960.193 9960.189 9960.189 38259.258 31891.879 30702.641 30339.914 30188.129
30113.578 30118.578 38260.867
TANK 2 SUPER UNLEADED
CAP1
NUMBER OF SAMPLES= 1115
6852.000 6930.000 12054.000 11946.000 11963.000 11922.000 11984.000 12029.000
9026.000 8705.000 8777.000 8290.000 3733.000 4150.000 4144.000 4137.000
4132.000 4126.000 4120.000 2954.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TANK 3 PREMIUM UNLEADED
CAP0
NUMBER OF SAMPLES= 1117
234.000
439.000 1317.000 1317.000 1307.000 1321.000 1104.000
761.000
104.000 1686.000

Typical Response Message, Computer Format:
iA13TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.
9.

SSSS
NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of Samples (Hex)
Number of eight character Data Fields to follow (Hex)
Probe Data (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

499

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A14
Function Type: Mag Probe Option Table

Version 19

Command Format:
Display: IA14TT
Computer: iA14TT
Typical Response Message, Display Format:

IA14TT
JUN 1, 2000

8:15 AM

MAG PROBE OPTIONS TABLE
TNK
NUM
1
2
3
4


LOW
TEMP
NO
NO
NO
NO

Typical Response Message, Computer Format:
iA14TTYYMMDDHHmmTTNNL...
TTNNL&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
NN
L

-

Current Date and Time
Tank Number (Decimal, 00=all)
Number of option flags to follow
Low temperature capability
0=NO
1=YES
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

500

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A15
Function Type: In-Tank Diagnostic Printout

Version 24

Command Format:
Display: IA1500
Computer: iA1500
Typical Response Message, Display Format:

IA1500
JUN 3, 2002
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

IN-TANK DIAGNOSTIC
-----------------PROBE DIAGNOSTICS
T1:PROBE TYPE MAG 1
SERIAL NUMBER 064924
LENGTH: 2489.2
DATE CODE 2774
ID CHAN=D004
GRADIENT= 350.0000
PROBE INIT:
AUG 1,2004 12:25PM
NUM SAMPLES=
C00
C02
C04
C06
C08
C10
C12
C14
C16
C18

811.0
7196.5
7196.3
7196.8
7196.6
7196.8
18534.4
18496.6
18456.4
18534.4

20
C01
C03
C05
C07
C09
C11
C13
C15
C17

7196.8
7196.7
7196.8
7196.2
7196.1
42511.1
18615.1
18518.9
18505.8

SAMPLES READ=
2
SAMPLES USED=
2
LAST ERROR =
0
LAST SAMPLE ERROR TIME:
AUG 2,2004 11:12PM
TEMP SENSOR DATA
T6:
72.6 F
T5:
72.1 F
T4:
70.9 F
T3:
69.4 F
T2:
68.3 F
T1:
67.6 F
REF DISTANCE
12/01/00 XXXXX.XX
12/01/01 XXXXX.XX


- (Original Reference Time/Distance)
- (Current Reference Time/Distance)

Part No. 576013-635, Revision AA

501

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code A15 Notes: (Continued)
Typical Response Message, Computer Format:
iA15TTYYMMDDHHmmTTppppssssssllllllllddddYYMMDDHHmm
ggggggggzzzzoonnnnNNcccccccc...cccccccc
rrrrrrrruuuuuuuueeeeeeeeYYMMDDHHmm
AAaaaaaaaa...aaaaaaaa
YYMMDDhhhhhhhhYYMMDDkkkkkkkk...
TTppppssssssllllllllddddYYMMDDHHmm
ggggggggzzzzoonnnnNNcccccccc...cccccccc
rrrrrrrruuuuuuuueeeeeeeeYYMMDDHHmm
AAaaaaaaaa...aaaaaaaa
YYMMDDhhhhhhhhYYMMDDkkkkkkkk&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm
TT
pppp
ssssss
llllllll
dddd
YYMMDDHHmm
gggggggg
zzzz
oo

-

11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.

nnnn
NN
cccccccc
rrrrrrrr
uuuuuuuu
eeeeeeee
YYMMDDHHmm
AA
aaaaaaaa
YYMMDD
hhhhhhhh
YYMMDD
kkkkkkkk
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Probe Type (Hex)
Serial Number (Decimal)
Probe Length (ASCII Hex IEEE float)
Date Code (Hex)
Probe Initialized (Date and Time)
Gradient (ASCII Hex IEEE float)
Id Code (Hex)
Probe Options (Hex)
00=Not Low Temperature Probe
01=Low Temperature Probe
Number of Samples (Hex)
# of 8-Byte Channel Count Values to Follow (Hex)
Channel Count Values (ASCII Hex IEEE float)
Samples Read (Hex)
Samples Used (Hex)
Last Error Sample Number (Hex)
Last Sample Error Time (Date and Time)
# of 8-Byte Temperature Sensor Values Follow (Hex)
Temperature Sensor Values (ASCII Hex IEEE float)
Original Reference Distance Date
Original Reference Distance Value (ASCII Hex IEEE float)
Current Reference Distance Date
Current Reference Distance Value (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

502

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A20
Function Type: Probe Leak Test Flags - Present Test

Version 1

Command Format:
Display: IA20TT
Computer: iA20TT
Typical Response Message, Display Format:

IA20TT
JAN 28, 1995 10:15 AM
TANK 1 REGULAR UNLEADED
0.1 GAL/HR FLAGS:
0.2 GAL/HR FLAGS:
TANK 2 SUPER UNLEADED
0.1 GAL/HR FLAGS:
0.2 GAL/HR FLAGS:
TANK 3 PREMIUM UNLEADED
0.2 GAL/HR FLAGS:


MAG

PRESENT LEAK TEST ANALYSIS REPORT

CAP1

PRESENT LEAK TEST ANALYSIS REPORT

CAP0

PRESENT LEAK TEST ANALYSIS REPORT

Typical Response Message, Computer Format:
iA20TTYYMMDDHHmmTTpPPNNFFFF...
TTpPPNNFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of 4-character Flag sequences to follow (Hex)
Flag sequence characters indicating which Flag bits are set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

503

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A21
Function Type: Probe Leak Test Flags - Stored Test

Version 1

Command Format:
Display: IA21TT
Computer: iA21TT
Typical Response Message, Display Format:

IA21TT
JAN 28, 1995 10:15 AM
TANK 1 REGULAR UNLEADED
0.1 GAL/HR FLAGS:
0.2 GAL/HR FLAGS:
TANK 2 SUPER UNLEADED
0.1 GAL/HR FLAGS:
0.2 GAL/HR FLAGS:
TANK 3 PREMIUM UNLEADED
0.2 GAL/HR FLAGS:


MAG

STORED LEAK TEST ANALYSIS REPORT

CAP1

STORED LEAK TEST ANALYSIS REPORT

CAP0

STORED LEAK TEST ANALYSIS REPORT

Typical Response Message, Computer Format:
iA21TTYYMMDDHHmmTTpPPNNFFFF...
TTpPPNNFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of 4-character Flag sequences to follow (Hex)
Flag sequence characters indicating which Flag bits are set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

504

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A22
Function Type: Probe Leak Test Flags - Gross Test

Version 2

Command Format:
Display: IA22TT
Computer: iA22TT
Typical Response Message, Display Format:

IA22TT
APR 14, 1995 9:05 AM
TANK 1 REGULAR UNLEADED
GROSS LEAK TEST FLAGS:
TANK 2 SUPER UNLEADED
GROSS LEAK TEST FLAGS:
TANK 3 PREMIUM UNLEADED
GROSS LEAK TEST FLAGS:


MAG

GROSS LEAK TEST ANALYSIS REPORT

CAP1

GROSS LEAK TEST ANALYSIS REPORT

CAP0

GROSS LEAK TEST ANALYSIS REPORT

Typical Response Message, Computer Format:
iA22TTYYMMDDHHmmTTpPPNNFFFF...
TTpPPNNFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
p
PP

-

5.
6.
7.
8.

NN
FFFF
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type:
01=CAP0
02=CAP1
03=MAG1
Number of 4-character Flag sequences to follow (Hex)
Flag sequence characters indicating which Flag bits are set
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

505

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A23
Function Type: Tank Leak Test Averaging Buffers

Version 5

Command Format:
Display: IA23TT
Computer: iA23TT
Typical Response Message, Display Format:

IA23TT
APR 8, 1995 8:27 AM
TANK 1 SUPER UNLEADED
MAG
0.20 GAL/HR LEAK TEST BUFFER
START TIME
HOURS VOLUME
APR 8, 1995 5:22 AM
3.0
6107
APR 8, 1995 1:01 AM
4.0
6107
APR 7, 1995 9:56 PM
3.0
6108
APR 7, 1995 6:51 PM
3.0
6108
APR 7, 1995 4:49 PM
2.0
6108
AVERAGE
3.0
6108
0.10 GAL/HR LEAK TEST BUFFER
START TIME
HOURS VOLUME
APR 8, 1995 5:22 AM
3.0
6107
APR 8, 1995 1:01 AM
4.0
6107
APR 7, 1995 9:56 PM
3.0
6108
APR 7, 1995 6:51 PM
3.0
6108
AVERAGE
3.3
6107


LEAK TEST AVERAGING BUFFERS
RATE
-0.059
-0.058
-0.060
-0.045
-0.039
-0.052
RATE
-0.059
-0.058
-0.060
-0.045
-0.056

Typical Response Message, Computer Format:
iA23TTYYMMDDHHmmTTpPPNNYYMMDDHHmmddddddddVVVVVVVVRRRRRRR...
nnYYMMDDHHmmddddddddVVVVVVVVRRRRRRR...
TTpPPNNYYMMDDHHmmddddddddVVVVVVVVRRRRRRR...
nnYYMMDDHHmmddddddddVVVVVVVVRRRRRRR&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.

YYMMDDHHmm
TT
p
PP
NN
YYMMDDHHmm
dddddddd
VVVVVVVV
RRRRRRRR
nn
YYMMDDHHmm
dddddddd
VVVVVVVV
RRRRRRRR
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=all)
Product Code (one ASCII character [20h-7Eh])
Probe Type
Number of 34 character 0.20 gal/hr test records to follow
Leak test start time - year, month, day, hour, min
Leak test duration in hours (ASCII Hex IEEE float)
Leak test volume (gallons) (ASCII Hex IEEE float)
Leak test rate (gal/hr) (ASCII Hex IEEE float)
Number of 34 character 0.10 gal/hr test records to follow
Leak test start time - year, month, day, hour, min
Leak test duration in hours (ASCII Hex IEEE float)
Leak test volume (gallons) (ASCII Hex IEEE float)
Leak test rate (gal/hr) (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

506

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A51
Function Type: CSLD Diagnostics: Rate Table

Version 3

Command Format:
Display: IA51TT
Computer: iA51TT
Typical Response Message, Display Format:

IA51TT
JAN 22, 1996

3:26 PM

CSLD DIAGNOSTICS: RATE TABLE
T 1:REGULAR UNLEADED
TIME ST
LRT AVTMP TPTMP BDTMP
9601210514
9601220056
9601220417


2 -0.194
3 -0.028
1 -0.007

35.9
36.9
37.0

35.6
35.7
35.8

33.1
33.3
33.3

TMRT DSPNS
0.06
0.02
0.02

853
1528
1470

VOL INTVL
9324 53.5
6829 134.0
6825 25.0

DEL ULLG EVAP
1.4
21.1
24.5

188
320
320

7.8
7.8
7.8

Typical Response Message, Computer Format:
iA51TTYYMMDDHHmmTTRRssNNttttttttFFFFFFFF...
TTRRssNNttttttttFFFFFFFF&&ACF7
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
RR
ss

-

5.
6.
7.

NN tttttttt FFFFFFFF -

8.
9.

&& CCCC -

Current Date and Time
Tank Number (Decimal, 00=All Tanks)
Number of records to follow
Test acceptability:
00=Acceptable
01=Rejected - less than minimum duration requirement
02=Rejected - within delivery threshold
03=Rejected - excessive dispensing
04=Rejected - excessive temperature change
06=Rejected - outside weighted STD
Number of eight character Data Fields to follow (decimal)
Test starting time (seconds since 1/1/70, unsigned long)
ASCII Hex IEEE floats:
1. Leak rate
2. Accept
3. 0.0 (Obsolete)
4. Rate of change of temperature
5. Dispense factor
6. Volume
7. Test interval (minutes)
8. Hours since last delivery
9. Average temperature
10. Top temperature
11. Board temperature
12. Ullage area
13. Throughput
14. Evaporation rate
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

507

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A52
Function Type: CSLD Diagnostics: Rate Test

Version 3

Command Format:
Display: IA52TT
Computer: iA52TT
Typical Response Message, Display Format:

IA52TT
JAN 22, 1996

3:27 PM

CSLD DIAGNOSTICS: RATE TEST
TK
DATE LRATE INTVL ST
1 9601220417 -0.024 22.6 1


AVLRTE
-0.030

VOL
5436

C1
67

C3 FDBK ACPT THPUT EVAP RJT
22 30.4 36.8
7.8 0.100
0

Typical Response Message, Computer Format:
iA52TTYYMMDDHHmmTTYYMMDDHHmmSSCCccNNFFFFFFFF...
TTYYMMDDHHmmSSCCccNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
TT
YYMMDDHHmm
SS

-

5.
6.
7.
8.

CC
cc
NN
FFFFFFFF

-

9.
10.

&& CCCC -

Current Date
Tank Number (Decimal, 00=All Tanks)
Date of last tank evaluation
Status code:
01=PASS
02=FAIL
05=NO RESULTS - Insufficient number of records
06=NO RESULTS - Insufficient test time interval
07=NO RESULTS - Insufficient test date range
08=INVALID - excessive positive leak rate
09=INVALID - negative leak waiting period
Total count of records
Total count of acceptable records
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Compensated leak rate
2. Total test time (hours)
3. Uncompensated leak rate
4. Average volume during tests
5. Feedback factor (minutes)
6. Acceptance factor (minutes)
7. Last throughput * tank capacity/1000
8. DF multiplier
9. Positive rejects
10. Average evaporation rate
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

508

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A53
Function Type: CSLD Diagnostics: Volume History Table

Version 3

Command Format:
Display: IA53TT
Computer: iA53TT
Typical Response Message, Display Format:

IA53TT
MAR 26, 1996

1:48 PM

CSLD DIAGNOSTICS: VOLUME TABLE
T 1:REGULAR UNLEADED
LAST HOUR=229957
3141.9 3297.9 3476.7 3625.4
4218.2 4242.4 4242.5 4242.4
4307.5 4339.7 4405.7 4456.5


3742.9
4242.0
4573.2

3932.8
4247.0
4701.3

4085.4
4265.9
4854.2

4156.5
4281.5
5022.6

Typical Response Message, Computer Format:
iA53TTYYMMDDHHmmTTNNhhhhhhhhFFFFFFFF...
TTNNhhhhhhhhFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm
TT
NN
hhhhhhhh
FFFFFFFF

-

Current Date
Tank Number (Decimal, 00=All Tanks)
Number of eight character Data Fields to follow (Hex)
Last hour recorded (seconds since 1/1/70, unsigned long)
ASCII Hex IEEE floats:
1. Latest recorded hourly volume
2. Intermediate hourly recorded volumes
3. Oldest recorded hourly volume
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

509

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A54
Function Type: CSLD Diagnostics: Moving Average Table

Version 3

Command Format:
Display: IA54TT
Computer: iA54TT
Typical Response Message, Display Format:

IA54TT
MAR 26, 1996

1:48 PM

CSLD DIAGNOSTICS: MOVING AVERAGE TABLE
T 1:REGULAR UNLEADED
TIME
SMPLS
TCVOL
960326132554
31
3074.65
960326132624
30
3072.62
960326132654
31
3072.46
960326132724
30
3072.54
960326132754
31
3073.13
960326132824
31
3072.97
MOVING AVERAGE:
3056.51
DISPENSE STATE: ACTIVE *


HEIGHT
32.279
32.263
32.262
32.263
32.267
32.266

AVGTEMP
45.86
45.86
45.86
45.86
45.86
45.86

TOPTEMP
45.49
45.49
45.49
45.49
45.49
45.49

BDTEMP
48.19
48.19
48.20
48.20
48.21
48.21

702.324829

Typical Response Message, Computer Format:
A5401YYMMDDHHmmTTSSRRssNNaaaaaaaaFFFFFFFF...
TTSSRRssNNaaaaaaaaFFFFFFFF&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.

9.
10.

YYMMDDHHmm - Current Date
TT - Tank Number (Decimal, 00=All Tanks)
SS - Current Test State:
0=No test
1=Test pre-start
2=Test in-progress
3=Test complete
4=Abort test
5=Pre-delay
6=End delay
RR - Number of records to follow
ss - Number of samples averaged into this record
NN - Number of eight character Data Fields to follow (Hex)
aaaaaaaa - Time recorded (seconds since 1/1/70, unsigned long)
FFFFFFFF - ASCII Hex IEEE floats:
1. Time
2. Temperature compensated volume
3. Height
4. Fuel temperature
5. 0.0
6. Current moving average
7. Top temperature
8. Board temperature
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

510

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A55
Function Type: CSLD Diagnostics: Leak Test Status

Version 3

Command Format:
Display: IA55TT
Computer: iA55TT
Typical Response Message, Display Format:

IA55TT
MAR 26, 1996

1:49 PM

CSLD DIAGNOSTICS: LEAK TEST STATUS
TANK
1


TEST STATUS
NO TEST

DURATION
0.0

Typical Response Message, Computer Format:
iA55TTYYMMDDhhmmTTSSFFFFFFFF...
TTSSFFFFFFFF&&CCCC
Notes:
1.
2.
3.

4.
5.
6.

YYMMDDHHmm - Current Date
TT - Tank Number (Decimal, 00=All Tanks)
SS - Status:
00=NO TEST
01=TEST PRE-START
02=TEST IN PROGRESS
03=TEST COMPLETE
04=TEST ABORT
05=TEST PRE-DELAY
06=TEST END DELAY
FFFFFFFF - Elapsed time in minutes (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

511

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A56
Function Type: CSLD Monthly Report

Version 121

Command Format:
Display: IA56TTt
Computer: iA56TTt
Typical Response Message, Display Format:

IA56TT
OCT 25, 2000 10:00 AM
CSLD MONTHLY REPORT
CURRENT MONTH
0.2 GAL/HR TEST
T 1:UNLEADED GASOLINE
PROBE SERIAL NUM 627020
OCT 25,
OCT 24,
OCT 23,
OCT 20,
OCT 20,
OCT 19,
OCT 18,
OCT 16,


2000 7:15 AM
2000 3:22 PM
2000 6:26 AM
2000 12:44 PM
2000 5:23 AM
2000 8:23 AM
2000 9:53 PM
2000 6:14 AM

RESULT:
RESULT:
RESULT:
RESULT:
RESULT:
RESULT:
STATUS:
STATUS:

NO RESULTS AVAIL
PASS
FAIL
INCR
WARN
INVL
NO IDLE DATA
ACTIVE

Typical Response Message, Computer Format:
iA56TTYYMMDDHHmmtTTNNYYMMDDHHmmrr...
TTNNYYMMDDHHmmrr&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

7.
8.

YYMMDDHHmm - Current Date and Time
t - Report Type
0=Current Month
1=Previous Month
TT - Tank Number (Decimal, 00=all)
NN - Number of CSLD State Changes (12 char) to follow (Hex)
YYMMDDHHmm - Date and Time of CSLD State Change
rr - CSLD State Change:
01=RESULT: PASS
02=RESULT: FAIL
03=RESULT: NO RESULTS AVAILABLE
04=RESULT: INVALID
08=RESULT: INCR
98=STATUS: NO IDLE DATA
99=STATUS: ACTIVE
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

512

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A61
Function Type: HRM Diagnostic Report

Version 110

Command Format:
Display: IA61TT
Computer: iA61TT
Typical Response Message, Display Format:

IA61TT
JUL 29, 1997 9:08 AM
T 1:REGULAR UNLEADED
TIME STAMP
ENDTEMP ENDVOL
9707240757
70.61 2633.02
9707240918
70.79 2547.48
9707240948
70.82 2531.58
9707241114
70.93 2464.84
9707241224
71.09 2420.87
9707241310
71.25 2347.41
9707241412
71.38 2298.75


SALES STAT
118.2
0
204.0
0
220.0
0
275.1
0
331.2
0
404.2
0
453.0
0

HR VAR
-0.037
-0.099
0.056
-11.729
11.767
-0.754
-0.019

Typical Response Message, Computer Format:
iA61TTYYMMDDHHmmTTpRRYYMMDDHHmmFFEEEEEEEESSSSSSSSVVVVVVVV...
TTpRRYYMMDDHHmmFFEEEEEEEESSSSSSSSVVVVVVVV&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
p
RR
YYMMDDHHmm
FF

-

7.
8.
9.
10.
11.

EEEEEEEE
SSSSSSSS
VVVVVVVV
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=All Tanks)
Product Code
Number of records to follow
Record Date and Time stamp
Status Flag (Hex)
00=Data Used
01=Not mapped
02=Time Set Back
03=Gap Too Long
04=Delivery
05=Temp Low
06=Temp High
07=Temp Increase
08=Volume High
09=Volume Low
0A=Volume Change
0B=Not Calibrated
0C=Cal Time Filter
0D=No Sales Data
0E=Temp Decrease
0F=Reset Filter
10=Therm Flag
11=DIM Reset
12=BDIM Transaction
Ending Volume (ASCII Hex IEEE float)
Sales (ASCII Hex IEEE float)
Hourly Variance (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

513

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A62
Function Type: HRM Daily History

Version 112

Command Format:
Display: IA62TT
Computer: iA62TT
Typical Response Message, Display Format:

IA62TT
AUG 26, 1996

1:47 PM

T 1:REGULAR UNLEADED
DAILY HRM HISTORY
TIME/DATE
9510010200
9510020200
9510030200
9510040300


RECORDS
24
21
24
24

MIN
-0.562
-0.385
-0.402
-0.436

MAX
0.000
0.650
0.092
0.150

AVE
-0.230
-0.057
-0.135
-0.147

STATUS
PASS
PASS
PASS
PASS

Typical Response Message, Computer Format:
iA61TTYYMMDDHHmmTTpRRYYMMDDHHmmhhaaaaaaaabbbbbbbbccccccccSS...
TTpRRYYMMDDHHmmhhaaaaaaaabbbbbbbbccccccccSS&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

11.
12.

YYMMDDHHmm
TT
p
RR
YYMMDDHHmm
hh
aaaaaaaa
bbbbbbbb
cccccccc
SS

-

Current Date and Time
Tank Number (Decimal, 00=All Tanks)
Product Code (one ASCII character [20h-7Eh])
Number of history records to follow
Record Date and Time stamp
Number of hours in record (decimal)
Minimum Value (ASCII Hex IEEE float)
Maximum Value (ASCII Hex IEEE float)
Average Value (ASCII Hex IEEE float)
Status
00=No Data Available
01=Pass
02=Warning
03=Fail
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

514

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A63
Function Type: Extended HRM Diagnostic Report

Version 26

Command Format:
Display: IA63TT
Computer: iA63TT
Typical Response Message, Display Format:

IA63TT
JUL 29, 1997

9:08 AM

T 1:REGULAR UNLEADED
TIME STAMP
ENDTEMP ENDVOL
9707240757
70.61 2633.02
9707240918
70.79 2547.48
9707240948
70.82 2531.58
9707241114
70.93 2464.84
9707241224
71.09 2420.87


SALES STAT
118.2
0
204.0
0
220.0
0
275.1
0
331.2
0

HR VAR
-0.037
-0.099
0.056
-11.729
11.767

Typical Response Message, Computer Format:
iA63TTYYMMDDHHmmTTpRRYYMMDDHHmmFFNNEEEEEEEESSSSSSSSVVVVVVVVTTTTTTTT...
TtpRRYYMMDDHHmmFFNNEEEEEEEESSSSSSSSVVVVVVVVTTTTTTTT
&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
TT
p
RR
YYMMDDHHmm
FF

-

7.
8.
9.
10.
11.
12.
13.

NN
EEEEEEEE
SSSSSSSS
VVVVVVVV
TTTTTTTT
&&
CCCC

-

Current Date and Time
Tank Number (Decimal, 00=All Tanks)
Product Code
Number of records to follow
Record Date and Time stamp
Status Flag (Hex)
00=Data Used
01=Not mapped
02=Time Set Back
03=Gap Too Long
04=Delivery
05=Temp Low
06=Temp High
07=Temp Increase
08=Volume High
09=Volume Low
0A=Volume Change
0B=Not Calibrated
0C=Cal Time Filter
0D=No Sales Data
0E=Temp Decrease
0F=Reset Filter
10=Therm Flag
11=DIM Reset
12=BDIM Transaction
Number of eight character data fields to follow (Hex)
Ending Volume (ASCII Hex IEEE float)
Sales (ASCII Hex IEEE float)
Hourly Variance (ASCII Hex IEEE float)
Ending Temperature (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

515

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A81
Function Type: Fuel Management Diagnostic Report

Version 6

Command Format:
Display: IA81TT
Computer: iA81TT
Notes:
1.

TT - Tank number for any tank containing desired product

Typical Response Message, Display Format:

IA81TT
JAN 24, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

2:55 PM
1....
2....
3....
4....

FUEL MANAGEMENT DIAGNOSTIC REPORT
REGULAR UNLEADED
( TANK 1 )
DAYS FUEL REMAINING: 2.7
INVENTORY :
2969 GAL
95% ULLAGE:
2516 GAL
LAST SALES:
PREDICTED SALES:


Part No. 576013-635, Revision AA

SUN
1211
910
1122

AVERAGE SALES (GALLONS)
MON
TUE
WED
THR
FRI
462 1362 1005 1123 1184
783 1083 1176 1080 1108
427 1261
929 1039 1096

SAT
970
946
897

516

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code A81 Notes: (Continued)
Typical Response Message, Computer Format:
iA81TTYYMMDDHHmmnnTTp...NNFFFFFFFF...
nnTTp...NNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

YYMMDDHHmm - Current Date and Time
nn - Number of tanks of this product type - number of tank
product code (TTp) sets to follow
TTp - Tank numbers and product codes of this product type
NN - Number of eight character Data Fields to follow (Hex)
FFFFFFFF - ASCII Hex IEEE floats:
1. Days supply of fuel remaining
2. Inventory
3. 95% Ullage
4. Average sales for Sunday
5. Average sales for Monday
6. Average sales for Tuesday
7. Average sales for Wednesday
8. Average sales for Thursday
9. Average sales for Friday
10. Average sales for Saturday
11. Last sales for Sunday
12. Last sales for Monday
13. Last sales for Tuesday
14. Last sales for Wednesday
15. Last sales for Thursday
16. Last sales for Friday
17. Last sales for Saturday
18. Predicted sales for Sunday
19. Predicted sales for Monday
20. Predicted sales for Tuesday
21. Predicted sales for Wednesday
22. Predicted sales for Thursday
23. Predicted sales for Friday
24. Predicted sales for Saturday
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

517

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: A91
Function Type: Power Outage Diagnostic Report

Version 9

Command Format:
Display: IA91TT
Computer: iA91TT
Typical Response Message, Display Format:

IA91TT
JAN 24, 1996
STATION
STATION
STATION
STATION

2:56 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

POWER OUTAGE REPORT
T 1:REGULAR UNLEADED
INCREASE DATE / TIME
POWER REMOVED: JAN 16, 1996
POWER RESTORED: JAN 16, 1996
GROSS VOLUME CHANGE:


FUEL VOLUME
7:46:23 AM
8:00:15 AM

3367
3367
0

WATER VOLUME
0
0

TEMP DEG F
43.1
43.1

Typical Response Message, Computer Format:
iA91TTYYMMDDHHmmTTnnYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTnnYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

8.
9.

YYMMDDHHmm
TT
nn
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Tank Number (Decimal, 00=all).
Number of History Records to follow (Decimal)
Power Restored Date/Time
Power Removed Date/Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Power Removed Fuel Volume
2. Power Removed Water Volume
3. Power Removed Temperature
4. Power Restored Fuel Volume
5. Power Restored Water Volume
6. Power Restored Temperature
7. Gross Change
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

518

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.4.3 SENSOR DIAGNOSTIC REPORTS
Function Code: B01
Function Type: Liquid Sensor Diagnostic Report

Version 1

Command Format:
Display: IB01SS
Computer: iB01SS
Typical Response Message, Display Format:

IB01SS
JAN 24, 1996

2:56 PM

LIQUID DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
1072

LOW
REF
193

VALUE
145727

Typical Response Message, Computer Format:
iB01SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Sample counter
2. High Reference Channel
3. Low Reference Channel
4. Liquid Channel Last Reading
5. Liquid Channel Average Reading
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

519

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B06
Function Type: Vapor Sensor Diagnostic Report

Version 1

Command Format:
Display: IB06SS
Computer: iB06SS
Typical Response Message, Display Format:

IB06SS
JAN 24, 1996

2:56 PM

VAPOR DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
1080

LOW
REF
208

VALUE1
322

VALUE2
175355

Typical Response Message, Computer Format:
iB06SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Sample counter
2. High Reference Channel
3. Low Reference Channel
4. Vapor Channel Last Reading
5. Vapor Channel Average Reading
6. Water Channel Last Reading
7. Water Channel Average Reading
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

520

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B07
Function Type: Vapor Sensor Concentration (PPM) Report

Version 3

Command Format:
Display: IB07SS
Computer: iB07SS
Typical Response Message, Display Format:

IB07SS
JAN 24, 1996

2:56 PM

VAPOR DIAGNOSTIC REPORT - VAPOR CONCENTRATION
SENSOR
1


PPM
0

Typical Response Message, Computer Format:
iB07SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor number (Decimal, 00=All)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Vapor concentration (ppm)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

521

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B11
Function Type: Groundwater Sensor Diagnostic Report

Version 1

Command Format:
Display: IB11SS
Computer: iB11SS
Typical Response Message, Display Format:

IB11SS
JAN 28, 1995 10:16 AM
GROUNDWATER DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
5440

LOW
REF
930

VALUE1
49875

VALUE2
90972

Typical Response Message, Computer Format:
iB11SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Sample counter
2. High Reference Channel
3. Low Reference Channel
4. Hydrocarbon Channel Last Reading
5. Hydrocarbon Channel Average Reading
6. Water Channel Last Reading
7. Water Channel Average Reading
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

522

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B21
Function Type: Ground Temperature Sensor Diagnostic Report

Version 1

Command Format:
Display: IB21SS
Computer: iB21SS
Typical Response Message, Display Format:

IB21SS
JAN 24, 1996

2:56 PM

GROUNDTEMP DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
50


HIGH
REF
1086

LOW
REF
215

VALUE
28393

Typical Response Message, Computer Format:
iB21SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Sample counter
2. High Reference Channel
3. Low Reference Channel
4. Temperature Channel Last Reading
5. Temperature Channel Average Reading
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

523

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B33
Function Type: MAG Sensor Diagnostic Report

Version 24

Command Format:
Display: IB33SS
Computer: iB33SS
Typical Response Message, Display Format:

IB33SS
JAN 22, 2003

3:06 PM

MAG SENSOR DIAGNOSTIC REPORT
s 1: T1 SUMP
TOTAL HT
FUEL HT
WATER HT
INSTALL POS
FLUID TEMP
BOARD TEMP

Notes:
1.

15.0
5.0
10.0
5.0
67.3
70.3

IN.
IN.
IN.
IN.
F
F

Only parameters that are enabled to be displayed are shown.

Typical Response Message, Computer Format:
iB33SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
MAG SENSOR NUMBER (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Total Height
2. Fuel Height
3. Water Height
4. Install Position
5. Fuel Temperature
6. Board Temperature
(-99.9 indicates a value is not enabled for display)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

524

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B34
Function Type: Smart Sensor Last Sample Diagnostic

Version 24

Command Format:
Display: IB34SS
Computer: iB34SS
Typical Response Message, Display Format:

IB34SS
JAN 22, 2003

3:25 PM

SMART SENSOR CHANNEL DATA: LAST SAMPLE
s 1: SUMP 1
MAG SENSOR
SERIAL NUMBER: 123456
00
10
20
XX


0
1
2
3
4
5
6
7
8
9
XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX
XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX
XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX
XXXX

Notes:
1: Values are in ASCII Hex IEEE float format.
Typical Response Message, Computer Format:
iB34SSYYMMDDHHmmSSTTTTnnVVVVVVVV...VVVVVVVV&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
TTTT - Smart Sensor Type:
0001=Air Flow Meter.
0002=Vapor Pressure.
0003=Vapor Pressure.
0004=Vapor Pressure.
0008=Mag Sensor.
0009=Vac Sensor.
0010=Atmospheric Sensor.
nn - Number of channels to follow (Hex)
VVVVVVVV - Channel Value (Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

525

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B35
Function Type: Smart Sensor Type and Serial Number

Version 24

Command Format:
Display: IB35SS
Computer: IB35SS
Typical Response Message, Display Format:

IB35SS
JAN 22, 2003

3:25 PM

SMART SENSOR SERIAL NUMBER
SENSOR LABEL
1 SUMP UNLEADED PLUS


TYPE
008-MAG SENSOR

SERIAL NUMBER
123456

DATE CODE
26214

Typical Response Message, Computer Format:
IB35SSYYMMDDHHmmSSnnMMMMMMMMNNNNNNNNDDDDDDDDPPPPPPPP...
SSnnMMMMMMMMNNNNNNNNDDDDDDDDPPPPPPPP&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm
SS
nn
MMMMMMMM
NNNNNNNN
DDDDDDDD
PPPPPPPP
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Number of 8-byte values to follow.
Smart Sensor Model (Hex)
Smart Sensor Serial Number (Hex)
Smart Sensor Date Code (Hex)
Smart Sensor Protocol Version (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

526

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B36
Function Type: Smart Sensor Constant Data

Version 24

Command Format:
Display: IB36SS
Computer: IB36SS
Typical Response Message, Display Format:

IB36SS
JUN 1, 2000

8:15 AM

SMART SENSOR CONSTANTS DIAGNOSTIC
s 1: SUMP UNLEADED
MAG SENSOR
SERIAL NUMBER
MODEL
LENGTH
GRADIENT
MIN THRESHOLD
MAX THRESHOLD
NUM FLOATS
TEMPERATURE
INSTALL POS


123456
101
24.0
360.000
0.0
24.0
2
YES
YES

Part No. 576013-635, Revision AA

527

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B36 Notes: (Continued)
Typical Response Message, Computer Format:
IB36YYMMDDHHmmSSNNVVVVVVVVvvvvvvvv...VVVVVVVVvvvvvvvv...
NNVVVVVVVVvvvvvvvv...VVVVVVVVvvvvvvvv&&CCCC
Notes:
1.
2.
3.

YYMMDDHHmm - Current Date and Time
SS - Smart Sensor Number (Decimal, 00=all)
NN - Number of eight character data fields to follow
VVVVVVVV
vvvvvvvv
VVVVVVVV
vvvvvvvv
VVVVVVVV
vvvvvvvv
VVVVVVVV
vvvvvvvv

12.
13.
14.

NN=03 for Vacuum Sensors
VVVVVVVV - Model Number (Hex)
vvvvvvvv - Calibration Data, Slope (ASCII Hex IEEE float)
VVVVVVVV - Calibration Data, Offset (ASCII Hex IEEE float)

15.
16.
17.
18.

VVVVVVVV
vvvvvvvv
VVVVVVVV
VVVVVVVV

19.
20.

-

NN=08 for Mag Sensors
Model Number (Hex)
Sensor Length (ASCII Hex IEEE float)
Gradient (ASCII Hex IEEE float)
Min Threshold (ASCII Hex IEEE float)
Max Threshold (ASCII Hex IEEE float)
Number of Floats (1 or 2) (Hex)
Temperature enabled (0 or 1) (Hex)
Install Position enabled (0 or 1) (Hex)

4.
5.
6.
7.
8.
9.
10.
11.

-

NN=04 for Atmospheric Pressure Sensors
Model Number (Hex)
Software Version (Hex)
Calibration Data, Slope (ASCII Hex IEEE float)
Calibration Data, Offset (ASCII Hex IEEE float)

&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

528

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B37
Function Type: Atmospheric Pressure Sensor Diagnostic Report

Version 24

Command Format:
Display: IB37SS
Computer: iB37SS
Typical Response Message, Display Format:

IB37SS
JAN 22, 2004

3:25 PM

ATM P SENSOR DIAGNOSTIC REPORT
s 8:ATMP SENSOR #1
ATM P SENSOR
SERIAL NUMBER
ATM PRESSURE


7
0.062 PSI

Typical Response Message, Computer Format:
iB37SSYYMMDDHHmmSSNNNNNNNNnnFFFFFFFF...
SSNNNNNNNNnnFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
SS
NNNNNNNN
nn
FFFFFFFF
&&
CCCC

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Serial Number (Hex)
Number of 8-byte values to follow (Hex)
Atmospheric Pressure, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

529

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B38
Function Type: Vacuum Sensor Diagnostic Report

Version 24

Command Format:
Display: IB38SS
Computer: iB38SS
Typical Response Message, Display Format:

IB38SS
JAN 22, 2004

3:25 PM

VAC SENSOR DIAGNOSTIC REPORT
s 1:VACUUM SENSOR #1
VAC SENSOR
SERIAL NUMBER
24
COMPENSATED PRESSURE:
-9.000 PSI
UNCOMPENSATED PRESSURE:
-9.123 PSI
EVACUATION STATE:
VACUUM OK
FLUID STATUS: NORMAL
VCV: CLOSED
4-12-04 11:28AM
LEAK RATE:
0.123 GPH
TIME TO NO VAC:
150:20 HHHH:MM
4-12-04 10:15AM
EVAC RATIO:5.2 @ -4.3PSI
SENSOR FAULTS:
RELIEF VALVE FAULT


Part No. 576013-635, Revision AA

530

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B38 Notes: (Continued)
Typical Response Message, Computer Format:
iB38SSYYMMDDHHmmSSNNNNNNNNeFcVYYMMDDHHmmLLLLLLLLv
YYMMDDHHmmTTTTTTTTf
YYMMDDHHmmEEEEEEEEPPPPPPPPffff
nnFFFFFFFF...FFFFFFFF...
SSNNNNNNNNeFcVYYMMDDHHmmLLLLLLLLv
YYMMDDHHmmTTTTTTTTf
YYMMDDHHmmRRRRRRRRPPPPPPPPffff
nnFFFFFFFF...FFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
SS
NNNNNNNN
e

-

Current Date and Time
Smart Sensor Number (Decimal, 00=all)
Serial Number (Hex)
Evacuation State (Hex)
0=Vacuum Ok
1=Evacuation Pending
2=Evacuation Active
3=Evacuation Pending Manual
4=Evacuation Active Manual
5=No Vacuum
6=Evacuation Hold

5.

F - Fluid Status (Hex)
0=Normal
1=Fault
2=Fluid

6.

c - Vacuum Control Valve State (Hex)
0=Closed
1=Open
2=Fault

7.

V - Valid Leak Rate flag
0=Leak Rate invalid
1=Leak Rate valid

Part No. 576013-635, Revision AA

531

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B38 Notes: (Continued)
8.
9.
10.

YYMMDDHHmm - Date/Time of Leak Rate
LLLLLLLL - Leak Rate, GPH (ASCII Hex IEEE float)
v - Valid Time to No Vacuum flag
0=Time to No Vacuum invalid
1=Time to No Vacuum valid

11.
12.
13.

YYMMDDHHmm - Date/Time of Time to No Vacuum
TTTTTTTT - Time to No Vacuum, minutes (Hex)
f - Valid Evac Ratio flag
0=Evac Ratio invalid
1=Evac Ratio valid

14.
15.
16.
17.

YYMMDDHHmm
RRRRRRRR
PPPPPPPP
ffff

-

Date/Time of Evac Ratio
Evac Ratio, (ASCII Hex IEEE float)
Evac Ratio Pressure, PSI (ASCII Hex IEEE float)
Sensor Fault Bits:
Bit 1=Fluid Sensor Fault
Bit 2=Pressure Sensor Fault
Bit 3=Relief Valve Fault
Bit 4=VCV Fault
Bit 5 - 16=Unused

18.
19.
20.
21.
22.

nn
FFFFFFFF
FFFFFFFF
&&
CCCC

-

Number of 8-byte values to follow.
Compensated Pressure, PSI (ASCII Hex IEEE float)
Uncompensated Pressure, PSI (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

532

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B39
Function Type: Vacuum Sensor Evacuation Diagnostic Report

Version 24

Command Format:
Display: IB39SS
Computer: iB39SS
Typical Response Message, Display Format:

IB3901
MAY 4, 2004

1:58 PM

VAC SENSOR EVACUATION DIAGNOSTIC REPORT
s 1:VACUUM SENSOR #1
DURATION
HH:MM:SS
0:02:24
0:02:24
0:01:44
0:00:47
0:01:46

START DATE/TIME
04-05-04 09:06:58
04-05-04 09:06:58
04-05-04 09:15:33
04-05-04 09:19:26
04-05-04 09:20:11


Typical Response Message, Computer Format:
iB39SSYYMMDDHHmmSSnnYYMMDDHHmmDDDDDDDD...
YYMMDDHHmmDDDDDDDD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
SS
nn
YYMMDDHHmm
DDDDDDDD
&&
CCCC

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of Evacuation Events to follow (Decimal, 00=none)
Start Date and Time of Evacuation Event
Duration of Evacuation in Seconds (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

533

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B41
Function Type: Type A Sensor (2 Wire CL) Diagnostic Report

Version 2

Command Format:
Display: IB41SS
Computer: iB41SS
Typical Response Message, Display Format:

IB41SS
MAR 26, 1996

1:45 PM

2 WIRE CL DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
1815

LOW
REF
7823

VALUE
4193

Typical Response Message, Computer Format:
iB41SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Sample Counter Value
2. High Reference Value
3. Low Reference Value
4. Last Reading
5. Current Average Value
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

534

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B46
Function Type: Type B Sensor (3 Wire CL) Diagnostic Report

Version 2

Command Format:
Display: IB46SS
Computer: iB46SS
Typical Response Message, Display Format:

IB46SS
JAN 28, 1995 10:16 AM
3 WIRE CL DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
8900

LOW
REF
32000

VALUE1
5200

VALUE2
100000

Typical Response Message, Computer Format:
iB46SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Sample Counter Value
2. High Reference Value 1
3. Low Reference Value 1
4. Last Reading 1
5. Current Average Value 1
6. High Reference Value 2
7. Low Reference Value 2
8. Last Reading 2
9. Current Average Value 2
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

535

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B4B
Function Type: Universal Sensor Diagnostic Report

Version 4

Command Format:
Display: IB4BSS
Computer: iB4BSS
Typical Response Message, Display Format:

IB4BSS
FEB 18, 1990 10:53 AM
UNIVERSAL DIAGNOSTIC REPORT
SAMPLE
SENSOR COUNTER
1
5


HIGH
REF
8900

LOW
REF
32000

VALUE1
5200

VALUE2
100000

Typical Response Message, Computer Format:
iB4BSSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.

5.
6.

YYMMDDHHmm
SS
NN
FFFFFFFF

-

Current Date and Time
Sensor Number (Decimal, 00=all)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Sample Counter Value
2. High Reference Value 1
3. Low Reference Value 1
4. Last Reading 1
5. Current Average Value 1
6. High Reference Value 2
7. Low Reference Value 2
8. Last Reading 2
9. Current Average Value 2
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

536

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.4.4 LINE LEAK DIAGNOSTIC REPORTS
Function Code: B50
Function Type: Volumetric Line Leak Status

Version 1

Command Format:
Display: IB50PP
Computer: iB50PP
Typical Response Message, Display Format:

IB50PP
MAR 26, 1996

1:46 PM

P 1:REGULAR UNLEADED
PMP IN=OFF
PMP OUT=OFF
PRS SW= ON
EQU VLV=OFF
FIN SW=OFF
TST VLV=OFF
STR SW= ON
DISABLE= ON

Typical Response Message, Computer Format:
iB50PPYYMMDDHHmmPPIIppFFssOOeeTTdd...
PPIIppFFssOOeeTTdd&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

YYMMDDHHmm
PP
II
pp
FF
ss
OO
ee
TT
dd
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Pump In signal state (00=off, 01=on)
Pressure switch state (00=off, 01=on)
Final switch state (00=off, 01=on)
Start switch state (00=off, 01=on)
Pump Out signal state (00=off, 01=on)
Equalizing valve state (00=off, 01=on)
Test valve state (00=off, 01=on)
Disable output state (00=off, 01=on)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

537

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B51
Version 1
Function Type: Volumetric Line Leak Diagnostic Gross Test History
Command Format:
Display: IB51PP
Computer: iB51PP
Typical Response Message, Display Format:

IB51PP
MAR 26, 1996

1:46 PM

P 1:REGULAR UNLEADED
DATE/TIME
MAR 26, 1996 1:43
MAR 26, 1996 1:43
MAR 26, 1996 1:42
MAR 26, 1996 1:42


PM
PM
PM
PM

TYP
6
5
4
3

GRND
46.9
46.9
46.9
46.9

TANK
45.9
45.9
45.9
45.9

DELY
1
1
0
0

LGTH
300.0
10.0
13.5
13.5

RSET
0.0
0.5
0.0
0.0

TEST
7.8
10.0
5.3
13.5

RSLT
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
iB51PPYYMMDDHHmmPPNNYYMMDDHHmmTTg..gt..tDDDDLLLLRRRRTTTTrr...
PPNNYYMMDDHHmmTTg..gt..tDDDDLLLLRRRRTTTTrr&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

YYMMDDHHmm
PP
NN
YYMMDDHHmm
TT
g..g
t..t
DDDD
LLLL
RRRR
TTTT
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Number of test data entries to follow (Decimal)
Date and Time of test
Test type code (Hex)
Ground Temp dispenser off (8 character ASCII Hex IEEE float)
Tank Temp dispenser off (8 character ASCII Hex IEEE float)
Minutes since dispenser off (Hex)
Allowed tenths of a second for Final Switch to actuate (Hex)
Tenths of a second for Start Switch to close (Hex)
Actual tenths of a second for Final Switch to actuate (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

538

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B52
Version 1
Function Type: Volumetric Line Leak 0.10 & 0.20 GPH Diagnostic History
Command Format:
Display: IB52PP
Computer: iB52PP
Typical Response Message, Display Format:

IB52PP
MAR 26, 1996

1:47 PM

P 1:REGULAR UNLEADED
DATE/TIME
MAR 26, 1996 1:48
MAR 26, 1996 1:45
MAR 26, 1996 1:41
MAR 26, 1996 1:27
MAR 25, 1996 8:14
MAR 25, 1996 8:12
MAR 25, 1996 8:10
MAR 25, 1996 8:05

Notes:
1.

AM
AM
AM
AM
PM
PM
PM
PM

TYP
14
13
12
11
10
9
8
7

GRND
45.3
45.3
45.3
45.3
44.8
44.8
44.8
44.8

TANK
45.4
45.4
45.4
45.4
45.3
45.3
45.3
45.3

DELY
81
78
74
60
29
27
25
20

LGTH
300.0
146.0
794.0
794.0
300.0
60.0
326.0
326.0

RSET
0.0
0.1
0.0
0.0
0.0
4.9
1.1
0.0

TEST
7.5
146.0
251.3
794.1
7.3
60.0
97.7
326.0

RSLT
PASSED
PASSED
PASSED
PASSED
PASSED
PASSED
PASSED
PASSED

Numbers in "TYP" column above and "TT" below refer to 0.20
GPH tests (7-10) or 0.10 GPH tests (11-14)

Typical Response Message, Computer Format:
iB52PPYYMMDDHHmmPPNNYYMMDDHHmmTTg..gt..tDDDDLLLLRRRRTTTTrr...
PPNNYYMMDDHHmmTTg..gt..tDDDDLLLLRRRRTTTTrr&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

YYMMDDHHmm
PP
NN
YYMMDDHHmm
TT
g..g
t..t
DDDD
LLLL
RRRR
TTTT
rr
&&
CCCC

-

Current Date and Time
Pipeline Number (Decimal, 00=all)
Number of test data entries to follow (Decimal)
Date and Time of test
Test type code (Hex)
Ground Temp dispenser off (8 character ASCII Hex IEEE float)
Tank Temp dispenser off (8 character ASCII Hex IEEE float)
Minutes since dispenser off (Hex)
Allowed tenths of a second for Final Switch to actuate (Hex)
Tenths of a second for Start Switch to close (Hex)
Actual tenths of a second for Final Switch to actuate (Hex)
Test result code (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

539

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B61
Function Type: Vapor Valve Diagnostic

Version 29

Command Format:
Display: IB61ss
Computer: iB61ss
Typical Response Message, Display Format:

IB61ss
JAN 22, 2007

3:11 PM

VAPOR VALVE DIAGNOSTIC REPORT
s 1:VAPOR VALVE 1
VAPOR VALVE
SERIAL NUMBER
47466902
VALVE POSITION:
CLOSED
BATTERY:
FULL
OPEN CAP:
CHARGED
CLOSE CAP:
CHARGED
AMBNT TEMP:
70.12 F
OUTLET TMP:
72.34 F
SENSOR FAULTS:
VALVE COMMAND FAULT
CAP NOT CHARGING FAULT
CAP NOT HOLDING FAULT
REF RESISTOR FAULT
VAPOR RESISTANCE FAULT
TEMPERATURE RANGE FAULT
DATA NOISE FAULT
VALVE NOISE FAULT
NONE


Part No. 576013-635, Revision AA

(only if wireless)

(only active reason(s) for alarm/warning are listed)

540

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B61 Notes: (Continued)
Typical Response Message, Computer Format:
iB61ssYYMMDDHHmmssNNNNNNNNPBOCFnnTTTTTTTTtttttttt&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ss
NNNNNNNN
P

-

5.

B -

6.

O -

7.

C -

8.

F -

9.
10.
11.
12.
13.

nn
TTTTTTTT
tttttttt
&&
CCCC

-

Current Date and Time
Smart Sensor Number
Serial Number (Decimal)
Valve Position
0=Closed
1=Open
Battery Status (n/a unless wireless)
0=Unknown
1=Full
2=Medium
3=Low
4=Replace
Open Capacitor Status
0=Discharged
1=Charged
Close Capacitor Status
0=Discharged
1=Charged
Sensor Fault Bits
Bit 1 = Valve Command Fault B could not OPEN/CLOSE to
calibrate
Bit 2 = (unused)
Bit 3 = Cap Not Charging Fault B too long to charge
capacitors
Bit 4 = Cap Not Holding Fault B too frequent re-charges
needed
Bit 5 = Temperature Range Fault B temp reading(s) out of
range
Bit 6 = Reference Resistor Range Fault B reference resistor
reading(s) out of range
Bit 7 = Vapor Sensor Resistance Range Fault B vapor sensor
resistance reading out of range
Bit 8 = Data Noise Fault B Readings within range but too
noisy
Bit 9 = Valve Noise Fault B Coil reading too noisy to
calibrate and control valve
Number of 8 byte values to follow (Hex)
Ambient Temperature, Degrees F (ASCII Hex IEEE float)
Outlet Temperature, Degrees F (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

541

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B62
Function Type: Sub Alarm History Report

Version 29

Command Format:
Display: IB6200
Computer: iB6200
Typical Response Message, Display Format:

IB6200
JAN 22, 2007
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:11 PM
1....
2....
3....
4....

SMART SENSOR SUB ALARM HISTORY
ID TYPE
5
14
5
14
5
14
5
14
5
14
5
14
5
14
5
14
5
14
5
14
5
14
5
14


ALARM TYPE
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT

ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM

Part No. 576013-635, Revision AA

SUB ALARM
VAPOR RESISTANCE FAULT
VAPOR RESISTANCE FAULT
REF RESISTOR FAULT
REF RESISTOR FAULT
TEMPERATURE RANGE FAULT
TEMPERATURE RANGE FAULT
VALVE COMMAND FAULT
VALVE COMMAND FAULT
CAP NOT HOLDING FAULT
CAP NOT HOLDING FAULT
CAP NOT CHARGING FAULT
CAP NOT CHARGING FAULT

STATE
CLEAR
ALARM
CLEAR
ALARM
CLEAR
ALARM
CLEAR
ALARM
CLEAR
ALARM
CLEAR
ALARM

DATE
TIME
1-04-08 10:57AM
1-04-08 10:44AM
1-04-08 9:23AM
1-04-08 9:13AM
1-04-08 8:45AM
1-04-08 8:44AM
1-04-08 7:23AM
1-04-08 7:14AM
1-04-08 6:34AM
1-04-08 6:27AM
1-04-08 5:12AM
1-04-08 5:00AM

542

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B62 Notes: (Continued)
Typical Response Message, Computer Format:
iB6200YYMMDDHHmmnnssTTNNSSAAYYMMDDHHmm...
ssTTNNSSAAYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
nn
ss
TT

-

5.

NN -

6.

SS -

7.

AA -

8.
9.
10.

YYMMDDHHmm && CCCC -

Current Date and Time
Number of Sub Alarm records to follow (Hex)
Smart Sensor Number (Hex, 00=all)
Smart Sensor Type (Hex)
0E = Vapor Valve
Alarm Type Number (Hex):
If TT is 0E and NN is:
03 = Sensor Fault Alarm
Sub Alarm Type Number (Hex):
If TT is 0E and NN is 03 and SS is:
00 = Cap Not Charging Fault
01 = Cap Not Holding Fault
02 = Valve Command Fault
03 = Temperature Range Fault
04 = Ref Resistor Fault
05 = Vapor Resistance Fault
06 = Data Noise Fault
07 = Valve Noise Fault
Alarm State (Hex)
00 = Alarm cleared
01 = Alarm occurred
Date/Time Alarm state occurred
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

543

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B71
Function Type: Pump Sensor Diagnostic

Version 2

Command Format:
Display: IB71SS
Computer: iB71SS
Typical Response Message, Display Format:

IB7102
JAN 17, 1995 8:35 AM
PUMP SENSOR DIAGNOSTIC
S 2: SUPER UNLEADED
CARD 1 INPUT 2
TANK #: 3
PUMP OFF
MINS PUMP OFF=14

Typical Response Message, Computer Format:
iB71SSYYMMDDHHmmSSNNttttssssMMMMMMMM...
SSNNttttssssMMMMMMMM&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
SS
NN
tttt
ssss

-

Current Date and Time
Pump Sensor Number (Decimal, 00=all)
Number of 4 character Data Blocks to Follow (Hex)
Tank Number (Hex)
Pump Status
0001=ON
0000=OFF
MMMMMMMM - Minutes Pump has been Off (Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

544

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B72
Function Type: Pump Relay Monitor Diagnostic

Version 27

Command Format:
Display: IB72rr
Computer: iB72rr
Typical Response Message, Display Format:

IB72rr
JUN 22, 2006

3:12 PM

PUMP RELAY MONITOR DIAGNOSTIC
DEVICE
1


LABEL
PUMP RELAY UNLEADED

PUMP
(OUT)
OFF

PUMP RELAY
(IN)
Q 1: OFF

STUCK
RELAY
0 SEC

RUN
TIME
00:00

Typical Response Message, Computer Format:
iB72rrYYMMDDHHmmrrabNNccccccccdddddddd...
rrabNNccccccccdddddddd&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm - Current Date and Time
rr - Pump Relay Monitor Number (Decimal, 00=all)
a - Pump Status (ASCII Hex)
0=Off
1=On
b - Relay Status (ASCII Hex)
0=Off (or N/A B no Pump Relay assigned)
1=On
NN - Number of 8-character data fields to follow (ASCII Hex)
cccccccc - Stuck Relay, Seconds (ASCII Hex IEEE float)
0 if N/A B no Pump Relay assigned
dddddddd B Run Time, Hours (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

545

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B7B
Function Type: Pressure Line Leak Profile Line Test

Version 23

Command Format:
Display: IB7BQQ
Computer: iB7BQQ
Typical Response Message, Display Format:

IB7BQQ
JUL 15, 2001

1:27 PM

PRESSURE LINE LEAK PROFILE LINE TEST
Q 1:REGULAR UNLEADED
LAST PROFILE LINE TEST: NOV 15, 2001 10:15 AM
BULK MODULUS: 12000 PSI
TEST LEAK RATE: 1.50 GPH
REF PRESSURE: 30.00 PSI
TYP:USER
1ST LINE
2ND LINE
1ST LINE
2ND LINE


DEFINED
LEN :100 FEET
LEN :200 FEET
DIAM: 1.50 IN.
DIAM: 2.50 IN.

Part No. 576013-635, Revision AA

546

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B7B Notes: (Continued)
Typical Response Message, Computer Format:
iB7BQQYYMMDDHHmmQQaYYMMDDHHmmttNNFFFFFFFF...FFFFFFFF...
QQaYYMMDDHHmmttNNFFFFFFFF...FFFFFFFF&CCCC
Notes:
1.
2.
3.
4.
5.

6.
7.

8.
9.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
a - Valid profile line test flag
0=profile line test invalid
1=profile line test valid
YYMMDDHHmm - Date and Time of Last Profile Line Test
tt - Pipe Type:
01=2.0"/3.0" Fiberglass
02=2.0" Steel
03=White Enviroflex PP1501
04=1.5" Environ Geoflex II
(Added in V11)
05=Omniflex CP1501
(Added in V15)
06=Yellow Enviroflex PP1500
07=1.5"/2.5" Enviroflex PP1502/2502
(Added in V17)
08=OPW Pisces SP-15
(Added in V18)
09=OPW Pisces CP-15
(Added in V18)
10=WFG Coflex 2000 Ribbed
(Added in V19)
11=Enviroflex PP1503/2503
(Added in V19)
12=Omniflex CP1503
(Added in V19)
13=1.5"/2.0" Environ Geoflex D
(Added in V19)
14=APT P175SC
(Added in V121)
15=OPW Pisces CP15DW
(Added in V19)
16=OPW Pisces CP20
(Added in V19)
17=OPW PISCES SP20
(Added in V26)
18=User Defined
(Added in V22)
19=PETROTECHNIK UPP EXTRA 63MM
(Added in V26)
NN - Number of eight character Data Fields to follow (Hex)
FFFFFFFF - ASCII Hex IEEE float:
1. Bulk Modulus
2. Test Leak Rate (GPH)
3. Test Reference Pressure (PSI)
4. 1st
Line Length (FEET)
st
5. 1nd Line Diameter (INCHES)
6. 2nd Line Length (FEET)
7. 2 Line Diameter (INCHES)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

547

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B7C
Function Type: Pressure Line Leak Pressure Offset Test

Version 19

Command Format:
Display: IB7CQQ
Computer: iB7CQQ
Typical Response Message, Display Format:

IB7CQQ
JAN 1, 2000

6:27 PM

PRESSURE LINE LEAK PRESSURE OFFSET TEST
Q 1:REGULAR UNLEADED
LAST PRESSURE OFFSET TEST: +2.5 PSI


DEC

1, 1999

5:20 PM

Typical Response Message, Computer Format:
iB7CQQYYMMDDHHmmQQaFFFFFFFFYYMMDDHHmm...
QQaFFFFFFFFYYMMDDHHmm&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
a - Valid pressure flag
0=pressure invalid
1=pressure valid
FFFFFFFF - Last Pressure Offset Test Pressure in PSI (ASCII Hex IEEE
float)
YYMMDDHHmm - Date and Time of last Pressure Offset Test
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

548

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B7D
Function Type: WPPLD Line Leak Pressure Offset Test

Version 19

Command Format:
Display: IB7DWW
Computer: iB7DWW
Typical Response Message, Display Format:

IB7DWW
JAN 1, 2000
WPLLD

6:27 PM

LINE LEAK PRESSURE OFFSET TEST

W 1:REGULAR UNLEADED
LAST PRESSURE OFFSET TEST: +2.5 PSI


DEC

1, 1999

5:20 PM

Typical Response Message, Computer Format:
iB7DWWYYMMDDHHmmWWaFFFFFFFFYYMMDDHHmm...
WWaFFFFFFFFYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
a - Valid pressure flag
0=pressure invalid
1=pressure valid
FFFFFFFF - Last Pressure Offset Test Pressure in PSI (ASCII Hex IEEE
float)
YYMMDDHHmm - Date and Time of last Pressure Offset Test
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

549

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B7E
Version 19
Function Type: Pressure Line Leak Pressure Offset Monitor Report
Command Format:
Display: IB7EQQ
Computer: iB7EQQ
Typical Response Message, Display Format:

IB7EQQ
JAN 1, 2000

2:56 PM

PRESSURE LINE LEAK PRESSURE OFFSET MONITORS REPORT
Q 1:REGULAR UNLEADED
P0: PASS
LAST UPDATE: 21 DAYS
Pd: FAIL
LAST UPDATE: 44 DAYS
Pd=
40.1 PSI
Pd Ref=32.3 PSI
Pv: PASS
Pv =28.1 PSI
Pon=44.1 PSI
Pd =40.1 PSI

Typical Response Message, Computer Format:
IB7EQQYYMMDDHHmmQQAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ...
QQAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
AA - P0 pass/fail status
00=fail
01=pass
BBBB - P0 last update in days
CC - Pd pass/fail status
00=fail
01=pass
DDDD - Pd last update in days
EEEEEEEE - Pd in PSI (ASCII Hex IEEE float)
FFFFFFFF - Pd Ref in PSI (ASCII Hex IEEE float)
GG - Pd pass/fail status
00=fail
01=pass
HHHHHHHH - Pv in PSI (ASCII Hex IEEE float)
IIIIIIII - Pon in PSI (ASCII Hex IEEE float)
JJJJJJJJ - Pd in PSI (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

550

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B7F
Function Type: WPLLD Line Leak Pressure Offset Monitor Report

Version 19

Command Format:
Display: IB7FWW
Computer: iB7FWW
Typical Response Message, Display Format:

IB7FWW
JAN 1, 2000

2:56 PM

WPLLD LINE LEAK

PRESSURE OFFSET MONITORS REPORT

W 1:REGULAR UNLEADED
P0: PASS
LAST UPDATE: 21 DAYS
Pd: FAIL
LAST UPDATE: 44 DAYS
Pd=
40.1 PSI
Pd Ref=32.3 PSI
Pv: PASS
Pv =28.1 PSI
Pon=44.1 PSI
Pd =40.1 PSI

Typical Response Message, Computer Format:
IB7FWWYYMMDDHHmmWWAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ...
WWAABBBBCCDDDDEEEEEEEEFFFFFFFF
GGHHHHHHHHIIIIIIIIJJJJJJJJ&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
AA - P0 pass/fail status
00=fail
01=pass
BBBB - P0 last update in days
CC - Pd pass/fail status
00=fail
01=pass
DDDD - Pd last update in days
EEEEEEEE - Pd in PSI (ASCII Hex IEEE float)
FFFFFFFF - Pd Ref in PSI (ASCII Hex IEEE float)
GG - Pd pass/fail status
00=fail
01=pass
HHHHHHHH - Pv in PSI (ASCII Hex IEEE float)
IIIIIIII - Pon in PSI (ASCII Hex IEEE float)
JJJJJJJJ - Pd in PSI (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

551

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B81
Function Type: Pressure Line Leak Diagnostic Report

Version 7

Command Format:
Display: IB81QQ
Computer: iB81QQ
Typical Response Message, Display Format:

IB81QQ
JAN 24, 1996

2:56 PM

PRESSURE LINE LEAK DIAGNOSTIC REPORT
LINE
Q 1:REGULAR UNLEADED
14.397 PSI
A/D COUNTS
LOW REF=
HIGH REF=
SENSOR=


DISPENSING
ENABLED

TEST STATUS
TESTING 0.10 GAL/HR

PUMP
OFF

HANDLE
OFF

5926 CNTS
551 CNTS
1556 CNTS

Part No. 576013-635, Revision AA

552

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code B81 Notes: (Continued)
Typical Response Message, Computer Format:
iB81QQYYMMDDHHmmQQSSSSttNNFFFFFFFF...
QQSSSSttNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.

4.

5.
6.

7.
8.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
SSSS - Status Bits:
Bit 1 - (LSB) Dispensing enabled flag
(0=Disabled, 1=Enabled)
Bit 2 - Pump power
(0=Pump Off, 1=Pump On)
Bit 3 - Dispenser Handle
(0=Handle Off, 1=Handle On)
Bit 4-16 - Unused
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.10 gal/hr
04=test aborted
05=running pump (manual test starting)
06=line lockout
07=disable alarm
08=test pending
09=test delay
0A=pressure check
0B=testing at 0.20 gal/hr
NN - Number of eight character Data Fields to follow (Hex)
FFFFFFFF - ASCII Hex IEEE floats:
1. Pressure sensor reading
2. A/D low reference counts
3. A/D high reference counts
4. A/D sensor counts
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

553

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B82
Function Type: WPLLD Line Leak Diagnostic Report

Version 10

Command Format:
Display: IB82WW
Computer: iB82WW
Typical Response Message, Display Format:

IB82WW
JAN 24, 1996

2:56 PM

WPLLD LINE LEAK DIAGNOSTIC REPORT
LINE
W 1:REGULAR UNLEADED

DISPENSING
ENABLED

TEST STATUS
DISPENSING

PUMP
ON

HANDLE
ON

34.782 PSI
P 0:-99.000
P 1:-99.000
P 2:-99.000
P 3:-99.000
P 4:-99.000
P 5:-99.000
P 6:-99.000


PSI
PSI
PSI
PSI
PSI
PSI
PSI

P 7:-99.000
P 8:-99.000
P 9:-99.000
P10:-99.000
P11:-99.000
P12:-99.000
P13:-99.000

PSI
PSI
PSI
PSI
PSI
PSI
PSI

Typical Response Message, Computer Format:
iB82WWYYMMDDHHmmWWSSSSttPPPPPPPP...
WWSSSSttPPPPPPPP&&CCCC
Notes:
1.
2.
3.

4.

5.
6.
7.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
SSSS - Status Bits:
Bit 1 - (LSB) Dispensing enabled flag
(0=Disabled, 1=Enabled)
Bit 2 - Pump power
(0=Pump Off, 1=Pump On)
Bit 3 - Dispenser Handle
(0=Handle Off, 1=Handle On)
Bit 4-16 - Unused
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
05=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr
PPPPPPPP - Current Pressure in PSI (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

554

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B83
Function Type: WPLLD Line Leak Communication Diagnostic Report

Version 10

Command Format:
Display: IB83WW
Computer: iB83WW
Typical Response Message, Display Format:

IB83WW
JAN 24, 1996

2:56 PM

WPLLD LINE LEAK COMMUNICATION REPORT
W 1:REGULAR UNLEADED
CRC:0
PARITY:0
#: 349666-666-666
95.11.09.14.46

Typical Response Message, Computer Format:
iB83WWYYMMDDHHmmWWSSSSttAAAAAAAABBBBBBBB...
WWSSSSttAAAAAAAABBBBBBBB&&CCCC
Notes:
1.
2.
3.

4.

5.
6.
7.
8.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (decimal)
SSSS - Status Bits:
Bit 1 - (LSB) Dispensing enabled flag
(0=Disabled, 1=Enabled)
Bit 2 - Pump power
(0=Pump Off, 1=Pump On)
Bit 3 - Dispenser Handle
(0=Handle Off, 1=Handle On)
Bit 4-16 - Unused
tt - Test status
00=test complete
01=dispensing
02=testing at 3.00 gal/hr
03=testing at 0.20 gal/hr
04=test aborted
06=line lockout
06=disable alarm
07=test pending
08=test delay
09=testing at 0.10 gal/hr
AAAAAAAA - Checksum error count (ASCII Hex IEEE float)
BBBBBBBB - Parity error count (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

555

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B87
Function Type: Pressure Line Leak 3.00 GPH Test Diagnostic

Version 19

Command Format:
Display: IB87QQ
Computer: iB87QQ
Typical Response Message, Display Format:

IB87QQ
OCT 15, 1996 4:29 PM
PRESSURE LINE LEAK DIAGNOSTIC REPORT
Q 1:PLLD NUMBER 1
3.0 TEST PASSES
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

3.0 TEST FAILS
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

3.0 HI PRESSURE EVENTS
DATE/TIME
NO TEST DATA AVAILABLE


PUMP ON

FIRST READ

SECOND READ

Typical Response Message, Computer Format:
IB87QQYYMMDDHHmmQQRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
QQRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
RR - Test result type
00=Pass
01=Fail
02=Hi-pressure events
LL - Total Events to follow (Max=5 each)
YYMMDDHHmm - Date/Time Test Passed
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
bbbbbbbb - First pressure read (ASCII Hex IEEE float)
cccccccc - Second pressure read (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

556

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B88
Function Type: Pressure Line Leak Mid-range Test Diagnostic

Version 19

Command Format:
Display: IB88QQ
Computer: iB88QQ
Typical Response Message, Display Format:

IB88QQ
JAN 1, 1996

8:24 AM

PRESSURE LINE LEAK DIAGNOSTIC REPORT
Q 1:PLLD NUMBER 1
MID TEST PASSES
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

MID TEST FAILS
DATE/TIME
JAN 1, 1970 12:00 AM


PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

Typical Response Message, Computer Format:
IB88QQYYMMDDHHmmQQRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
QQRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm - Current Date and Time
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
RR - Test result type
00=Pass
01=Fail
LL - Total Events to follow (Max=5 each)
YYMMDDHHmm - Date/Time Test Passed
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
bbbbbbbb - First pressure read (ASCII Hex IEEE float)
cccccccc - Second pressure read (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

557

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B89
Function Type: Pressure Line Leak 0.20 GPH Test Diagnostic

Version 19

Command Format:
Display: IB89QQ
Computer: iB89QQ
Notes:
1.

For User Defined Pipe Types PUMP ON will be PMID(Version 23)

Typical Response Message, Display Format:

IB89QQ
JAN 1, 1996

8:26 AM

PRESSURE LINE LEAK DIAGNOSTIC REPORT
Q 1:PLLD NUMBER 1
0.20 TEST RESULTS
DATE/TIME
JUL 10, 1995 9:33
JUN 9, 1995 8:52
MAY 9, 1995 8:10
APR 8, 1995 7:28


AM
AM
AM
AM

PUMP ON
0.0 PSI
0.0 PSI
0.0 PSI
0.0 PSI

RATIO
0.00
0.00
0.00
0.00

DURATION
0
0
0
0

RESULTS
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
IB89QQYYMMDDHHmmQQLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc...
QQLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
LL - Total Tests to follow (Max=10)
4.
YYMMDDHHmm - Date/Time Test
5.
RR - Test Result
00=Pass
01=Fail
6.
aaaaaaaa - Pump on pressure read, PSI (ASCII Hex IEEE float)
7.
bbbbbbbb - Fail ratio (ASCII Hex IEEE float)
8.
cccccccc - Duration (in minutes) (ASCII Hex IEEE float)
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

558

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B8A
Function Type: Pressure Line Leak 0.10 GPH Test Diagnostic

Version 19

Command Format:
Display: IB8AQQ
Computer: iB8AQQ
Notes:
1.

For User Defined Pipe Types PUMP ON will be PMID(Version 23)

Typical Response Message, Display Format:

IB8AQQ
JAN 1, 1996

8:30 AM

PRESSURE LINE LEAK DIAGNOSTIC REPORT
Q 1:PLLD NUMBER 1
0.10 TEST RESULTS
DATE/TIME
JUL 10, 1995 10:20
JUN 9, 1995 9:39
MAY 9, 1995 8:57
APR 8, 1995 8:15


AM
AM
AM
AM

PUMP ON
0.0 PSI
0.0 PSI
0.0 PSI
0.0 PSI

RATIO
0.00
0.00
0.00
0.00

DURATION
0
0
0
0

RESULTS
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
IB8AQQYYMMDDHHmmQQLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc...
QQLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
LL - Total Tests to follow (Max=10)
4.
YYMMDDHHmm - Date/Time Test
5.
RR - Test Result
00=Pass
01=Fail
6.
aaaaaaaa - Pump on pressure read, PSI (ASCII Hex IEEE float)
7.
bbbbbbbb - Fail ratio (ASCII Hex IEEE float)
8.
cccccccc - Duration (in min) (ASCII Hex IEEE float)
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

559

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B8B
Function Type: WPLLD Line Leak 3.00 GPH Test Diagnostic

Version 19

Command Format:
Display: IB8BWW
Computer: iB8BWW
Typical Response Message, Display Format:

IB8BWW
OCT 15, 1996 4:29 PM
WPLLD LINE LEAK DIAGNOSTIC REPORT
W 1:WPLLD NUMBER 1
3.0 TEST PASSES
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

3.0 TEST FAILS
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

3.0 HI PRESSURE EVENTS
DATE/TIME
NO TEST DATA AVAILABLE


PUMP ON

FIRST READ

SECOND READ

Typical Response Message, Computer Format:
IB8BWWYYMMDDHHmmWWRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
WWRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
RR - Test result type
00=Pass
01=Fail
02=Hi-pressure events
LL - Total Events to follow (Max=5 each)
YYMMDDHHmm - Date/Time Test Passed
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
bbbbbbbb - First pressure read (ASCII Hex IEEE float)
cccccccc - Second pressure read (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

560

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B8C
Function Type: WPLLD Line Leak Mid-range Test Diagnostic

Version 19

Command Format:
Display: IB8CWW
Computer: iB8CWW
Typical Response Message, Display Format:

IB8CWW
JAN 1, 1996

8:24 AM

WPLLD LINE LEAK DIAGNOSTIC REPORT
W 1:WPLLD NUMBER 1
MID TEST PASSES
DATE/TIME
JAN 1, 1970 12:00 AM

PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

MID TEST FAILS
DATE/TIME
JAN 1, 1970 12:00 AM


PUMP ON
0.0 PSI

FIRST READ
0.0 PSI

SECOND READ
0.0 PSI

Typical Response Message, Computer Format:
IB8CWWYYMMDDHHmmWWRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
WWRRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc...
RRLLYYMMDDHHmmaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm - Current Date and Time
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
RR - Test result type
00=Pass
01=Fail
LL - Total Events to follow (Max=5 each)
YYMMDDHHmm - Date/Time Test Passed
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
bbbbbbbb - First pressure read (ASCII Hex IEEE float)
cccccccc - Second pressure read (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

561

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B8D
Function Type: WPLLD Line Leak 0.20 GPH Test Diagnostic

Version 19

Command Format:
Display: IB8DWW
Computer: iB8DWW
Typical Response Message, Display Format:

IB8DWW
JAN 1, 1996

8:26 AM

WPLLD LINE LEAK DIAGNOSTIC REPORT
W 1:WPLLD NUMBER 1
0.20 TEST RESULTS
DATE/TIME
JUL 10, 1995 9:33
JUN 9, 1995 8:52
MAY 9, 1995 8:10
APR 8, 1995 7:28


AM
AM
AM
AM

PUMP ON
0.0 PSI
0.0 PSI
0.0 PSI
0.0 PSI

RATIO
0.00
0.00
0.00
0.00

DURATION
0
0
0
0

RESULTS
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
IB8DWWYYMMDDHHmmWWLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc...
WWLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
3.
LL - Total Tests to follow (Max=10)
4.
YYMMDDHHmm - Date/Time Test
5.
RR - Test Result
00=Pass
01=Fail
6.
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
7.
bbbbbbbb - Fail ratio (ASCII Hex IEEE float)
8.
cccccccc - Duration (in min) (ASCII Hex IEEE float)
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

562

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B8E
Function Type: WPLLD Line Leak 0.10 GPH Test Diagnostic

Version 19

Command Format:
Display: IB8EWW
Computer: iB8EWW
Typical Response Message, Display Format:

IB8EWW
JAN 1, 1996

8:30 AM

WPLLD LINE LEAK DIAGNOSTIC REPORT
W 1:WPLLD NUMBER 1
0.10 TEST RESULTS
DATE/TIME
JUL 10, 1995 10:20
JUN 9, 1995 9:39
MAY 9, 1995 8:57
APR 8, 1995 8:15


AM
AM
AM
AM

PUMP ON
0.0 PSI
0.0 PSI
0.0 PSI
0.0 PSI

RATIO
0.00
0.00
0.00
0.00

DURATION
0
0
0
0

RESULTS
PASSED
PASSED
PASSED
PASSED

Typical Response Message, Computer Format:
IB8EWWYYMMDDHHmmWWLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc...
WWLLYYMMDDHHmmRRaaaaaaaabbbbbbbbcccccccc&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
WW - WPLLD Line Leak sensor number (Decimal, 00=All)
3.
LL - Total Tests to follow (Max=10)
4.
YYMMDDHHmm - Date/Time Test
5.
RR - Test Result
00=Pass
01=Fail
6.
aaaaaaaa - Pump on pressure read (ASCII Hex IEEE float)
7.
bbbbbbbb - Fail ratio (ASCII Hex IEEE float)
8.
cccccccc - Duration (in min) (ASCII Hex IEEE float)
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

563

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.4.5 RECONCILIATION DIAGNOSTIC REPORTS
Function Code: B91
Function Type: AccuChart Diagnostics Report

Version 108

Command Format:
Display: IB91TT
Computer: iB91TT
Typical Response Message, Display Format:

IB91TT
JAN 24, 1996

2:56 PM

ACCU_CHART DIAGNOSTICS
TK STATUS
1 ENABLED


DIAMETER
91.0

LENGTH
144.4

OFFSET
0.00

TILT
1.00

SHAPE F
1.00

CAPACITY
5774

Typical Response Message, Computer Format:
iB91TTYYMMDDHHmmTTSSNNFFFFFFFF...
TTSSNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal, 00=All)
3.
SS - Status:
00=AccuChart disabled
01=AccuChart enabled
4.
NN - Number of eight character Data Fields to follow (Hex)
5.
FFFFFFFF - ASCII Hex IEEE floats:
1. Tank diameter
2. Tank length
3. Probe offset
4. Tank tilt
5. Tank end shape factor
6. Tank capacity
6.
&& - Data Termination Flag
7.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

564

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B93
Function Type: AccuChart Status Report

Version 108

Command Format:
Display: IB93TT
Computer: iB93TT
Typical Response Message, Display Format:

IB93TT
JAN 24, 1996

2:56 PM

ACCU_CHART STATUS
TK STATUS
1 ENABLED


MODE
CALIBRATE

USER STATUS
DISABLED

DURATION
9.2

ALARM
OFF

FITNESS
0.00

DATA
566

Typical Response Message, Computer Format:
iB9301YYMMDDHHmmTTSSMMUUAANNFFFFFFFF...
TTSSMMUUAANNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal, 00=All)
3.
SS - Status:
00=AccuChart disabled
01=AccuChart enabled
4.
MM - Mode:
00=Calibrate
01=Monitor
5.
UU - User enable:
00=user chart
01=AccuChart
6.
AA - Alarm status:
00=No Alarm
01=Alarm
02=Alarm latched
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE floats:
1. Mode duration in days
2. Calibration fitness factor
3. Data quantity factor
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

565

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: B94
Function Type: AccuChart Calibration History Report

Version 108

Command Format:
Display: IB94TT
Computer: iB93TT
Typical Response Message, Display Format:

IB94TT
JAN 24, 1996

2:57 PM

ACCU_CHART CALIBRATION HISTORY
T 1:REGULAR UNLEADED
DATE/TIME
96/01/01 08:03


DIAM
91.0

LENGTH
144.4

OFFSET
0.00

TILT
1.00

SHAPE F
1.00

CAPACITY
5774

FITNESS
0.00

Typical Response Message, Computer Format:
iB94TTYYMMDDHHmmTTrrYYMMDDHHmmNNFFFFFFFF...
TTrrYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank number (Decimal, 00=All)
3.
rr - Number of calibration records to follow
4.
YYMMDDHHmm - Calibration Date and Time
5.
NN - Number of eight character Data Fields to follow (Hex)
6.
FFFFFFFF - ASCII Hex IEEE floats:
1. Tank diameter
2. Tank length
3. Probe offset
4. Tank tilt
5. Tank end shape factor
6. Tank capacity
7. Calibration fitness
7.
&& - Data Termination Flag
8.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

566

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: BA0
Function Type: MDIM Totalizer Report

Version 110

Command Format:
Display: IBA000
Computer: iBA000
Typical Response Message, Display Format:

IBA000
FEB 4, 1995

6:25 AM

MDIM TOTALIZER
1
0.000
2
0.000
3
0.000
4
0.000

Typical Response Message, Computer Format:
iBA000YYMMDDHHmmddddFFFFFFFF...
ddddFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
dddd
FFFFFFFF
&&
CCCC

-

Current Date and Time
Dim identifier
Totalizer value (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

567

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: BA1
Function Type: DIM Communciation Status and History

Version 32

Command Format:
Display: IBA100
Computer: iBA100
Typical Response Message, Display Format:

IBA100
JUNE 22, 2010

4:52 PM

DIM COMMUNICATION STATUS AND FAULT HISTORY

PORT 1

STATUS: FAULT
FAULT HISTORY:
POST TIME
06/22/10 03:33
06/18/10 04:23


CLEAR TIME
FAULT
06/18/10 14:56

DURATION (HOURS)
1.25
14.55

Typical Response Message, Computer Format:
iBA100YYMMDDHHmmppNNPPPPPPPPCCCCCCCC...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
pp
NN
PPPPPPPP
CCCCCCCC

-

Current Date and Time
Communciation Port number
Communciation Port number
Totalizer value (ASCII Hex IEEE float)
Totalizer value (ASCII Hex IEEE float)
0 indicates the condition is currently active.
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

568

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: BB1
Function Type: VMC Status Report

Version 28

Command Format:
Display: IBB1xx
Computer: iBB1xx
Notes:
1.

xx - VMC Number (Decimal, 01-18, 00=all)

Typical Response Message, Display Format:

IBB101
JAN 22, 2007
STATION
STATION
STATION
STATION

3:11 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

VMC REPORT
VMC
S/N
1
111111
1
111111


SIDE
A
B

STATUS
IDLE
IDLE

RECOVER RATE
85.2
93.8

FUEL CNT
12382
13875

ERR CNT
372
436

REM TIME
0
0

Typical Response Message, Computer Format:
iBB1xxYYMMDDHHmmxxIIIIIIsSSrrrrffffeeeetttt...
xxIIIIIIsSSrrrrffffeeeetttt&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
xx
IIIIII
s
SS

-

6.
7.
8.
9.
10.
11.

rrrr
ffff
eeee
tttt
&&
CCCC

-

Current Date and Time
VMC Number (Decimal, 01-18, 00=all)
Serial Number (Decimal)
Side (1=A, 2=B)(ASCII Hex)
Status (ASCII Hex)
00=Roots meter not connected
01=Idle
02=Running
03=Last transaction failed
04=FP shutdown warning
05=FP shutdown alarm
FE=Status Unknown
FF=VMC Comm Timeout
Recover Rate (ASCII decimal, x10)
Fueling Counter (ASCII Hex)
Error Counter (ASCII Hex)
Remaining Time, minutes (ASCII Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

569

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.5 RECONCILIATION REPORTS
Version 106
Function Code: C01
Function Type: Basic Inventory Reconciliation Daily "Row" Report
Command Format:
Display: IC01PPMMDD
Computer: iC01PPMMDD
Notes:
1.

MMDD - Month and Day for Daily Report

Typical Response Message, Display Format:

IC01PP
MAR 26, 1996
STATION
STATION
STATION
STATION

1:43 PM

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1....
2....
3....
4....
1:43 PM

DAILY RECONCILIATION REPORT
T 1:REGULAR UNLEADED
DATE
MAR 25
MAR 26

TIME
OPENING
METERED
2:00 AM VOLUME DLVRIES
SALES
2:00 AM
6081
0
1888

MANUAL CALC'D PHYSICAL WATER
ADJUST INVNTRY INVNTRY HEIGHT VARIANCE
0
4193
4199
0.00
6

SIGNATURE _________________________

Typical Response Message, Computer Format:
iC01PPYYMMDDHHmmPPnnTTYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTTYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

9.
10.

YYMMDDHHmm
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

570

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C02
Version 106
Function Type: Basic Inventory Reconciliation Daily "Column" Report
Command Format:
Display: IC0200MMDD
Computer: iC0200MMDD
Notes:
1.

MMDD - Month and Day for Daily Report

Typical Response Message, Display Format:

IC0200
MAR 26, 1996
STATION
STATION
STATION
STATION

1:43 PM

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1....
2....
3....
4....

1:43 PM

DAILY RECONCILIATION REPORT
PRODUCT
OPENING DATE
OPENING TIME
OPENING VOLUME
DELIVERIES
METERED SALES
MANUAL ADJUST
CALC'D INVNTRY
PHYSICAL INVNTRY
WATER HEIGHT
VARIANCE
CLOSING DATE
CLOSING TIME

UNLEADED
MAR 25, 1996
2:00 AM
6081
0
1888
0
4193
4199
0.00
6
MAR 26, 1996
2:00 AM

SIGNATURE _________________________


Part No. 576013-635, Revision AA

571

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C02: (Continued)
Typical Response Message, Computer Format:
iC02PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
GG
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Number of product Groupings to follow (Hex)
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

572

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C03
Version 106
Function Type: Basic Inventory Reconciliation Shift "Row" Report
Command Format:
Display: IC03PPtt
Computer: iC03PPtt
Notes:
1.

tt - Shift Type (01=Current, 02=Previous)

Typical Response Message, Display Format:

IC03PP
MAR 26, 1996
STATION
STATION
STATION
STATION

1:44 PM

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1....
2....
3....
4....
1:44 PM

CURRENT SHIFT RECONCILIATION REPORT
T 1:REGULAR UNLEADED
DATE
MAR 26
MAR 26

TIME
OPENING
METERED
6:00 AM VOLUME DLVRIES
SALES
1:42 PM
4114
0
1083

MANUAL CALC'D PHYSICAL WATER
ADJUST INVNTRY INVNTRY HEIGHT VARIANCE
0
3031
3026
0.00
-5

SIGNATURE _________________________

Typical Response Message, Computer Format:
iC03PPYYMMDDHHmmPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

9.
10.

YYMMDDHHmm
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE float:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

573

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C04
Version 106
Function Type: Basic Inventory Reconciliation Shift "Column" Report
Command Format:
Display: IC0400tt
Computer: iC0400tt
Notes:
1.

tt - Shift Type (01=Current, 02=Previous)

Typical Response Message, Display Format:

IC0400
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1:44 PM
1....
2....
3....
4....
1:44 PM

PREVIOUS SHIFT RECONCILIATION REPORT
PRODUCT
OPENING DATE
OPENING TIME
OPENING VOLUME
DELIVERIES
METERED SALES
MANUAL ADJUST
CALC'D INVNTRY
PHYSICAL INVNTRY
WATER HEIGHT
VARIANCE
CLOSING DATE
CLOSING TIME

UNLEADED
MAR 26, 1996
6:00 AM
4114
0
1083
0
3031
3026
0.00
-5
MAR 26, 1996
1:42 PM

SIGNATURE _________________________


Part No. 576013-635, Revision AA

574

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C04: (Continued)
Typical Response Message, Computer Format:
iC04PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
GG
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Number of product Groupings to follow (Hex)
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

575

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C05
Version 106
Function Type: Basic Inventory Reconciliation Periodic "Row" Report
Command Format:
Display: IC05PP
Computer: iC05PP
Typical Response Message, Display Format:

IC05PP
MAR 26, 1996
STATION
STATION
STATION
STATION

1:42 PM

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1....
2....
3....
4....
1:42 PM

CURRENT PERIODIC RECONCILIATION REPORT
T 1:REGULAR UNLEADED
DATE
MAR 1
MAR 2
MAR 3
MAR 4
MAR 5
MAR 6
MAR 7
MAR 8
MAR 9
MAR 10
MAR 11
MAR 12
MAR 13
MAR 13
MAR 14
MAR 16
MAR 17
MAR 18
MAR 19
MAR 20
MAR 21
MAR 22
MAR 23
MAR 24
MAR 25
MAR 26

TIME
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:21
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00

TOTALS

AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM

OPENING
METERED
VOLUME DLVRIES
SALES
5429
0
3341
2092
5409
1876
5625
3336
3065
5874
2009
2207
5672
0
1568
4108
6503
2170
8444
0
1574
6872
0
2295
4581
5405
2881
7099
0
3312
3793
3898
2436
5253
0
1745
3497
4811
1599
6718
0
2111
4612
6213
3896
6896
0
2807
4096
3302
3440
3969
4802
1930
6839
0
2079
4775
5407
2242
7947
0
2552
5398
5410
3309
7510
0
3055
4465
4812
3200
6081
0
1888
5407

61317

62578

THRESHOLD:

MANUAL CALC'D PHYSICAL WATER
ADJUST INVNTRY INVNTRY HEIGHT VARIANCE
0
2088
2092
0.00
4
0
5625
5625
0.00
0
0
5896
5862
0.00
-34
0
5676
5672
0.00
-4
0
4104
4108
0.00
4
0
8441
8443
0.00
2
0
6870
6872
0.00
2
0
4577
4581
0.00
4
0
7105
7099
0.00
-6
0
3787
3793
0.00
6
0
5255
5253
0.00
-2
0
3508
3497
0.00
-11
0
6709
6718
0.00
9
0
4607
4612
0.00
5
0
6929
6931
0.00
2
0
4089
4096
0.00
7
0
3958
3969
0.00
11
0
6841
6839
0.00
-2
0
4760
4775
0.00
15
0
7940
7947
0.00
7
0
5395
5398
0.00
3
0
7499
7510
0.00
11
0
4455
4465
0.00
10
0
6077
6081
0.00
4
0
4193
4199
0.00
6
0

4146

4199

0.00

53
755

SIGNATURE _________________________


Part No. 576013-635, Revision AA

576

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C05: (Continued)
Typical Response Message, Computer Format:
iC05PPYYMMDDHHmmPPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
PP
nn
TT
dd
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Number of reconciliation days to follow (Hex)
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

577

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C06
Version 106
Function Type: Basic Inventory Reconciliation Periodic "Column" Report
Command Format:
Display: IC0600
Computer: iC0600
Typical Response Message, Display Format:

IC0600
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1:42 PM
1....
2....
3....
4....
1:42 PM

CURRENT PERIODIC RECONCILIATION REPORT
PRODUCT
OPENING DATE
OPENING TIME
OPENING VOLUME
DELIVERIES
METERED SALES
MANUAL ADJUST
CALC'D INVNTRY
PHYSICAL INVNTRY
WATER HEIGHT
VARIANCE
THRESHOLD
CLOSING DATE
CLOSING TIME

UNLEADED
MAR

1, 1996
2:00 AM
5407
61317
62578
0
4146
4199
0.00
53
755

MAR 20, 1996
2:00 AM

SIGNATURE _________________________


Part No. 576013-635, Revision AA

578

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C06: (Continued)
Typical Response Message, Computer Format:
iC06PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
GG
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Number of product Groupings to follow (Hex)
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

579

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C07
Version 114
Function Type: Basic Inventory Reconciliation Periodic "Row" Report
(Current/Previous)
Command Format:
Display: IC07PPtt
Computer: iC07PPtt
Notes:
1.
2.

PP - Product Number (00=all products)
tt - Report type
00=Current Period
01=Previous Period

Typical Response Message, Display Format:

IC07PP
MAR 26, 1996
STATION
STATION
STATION
STATION

1:42 PM

HEADER
HEADER
HEADER
HEADER

APR 11, 1996

1....
2....
3....
4....
1:42 PM

PREVIOUS PERIODIC RECONCILIATION REPORT
T 1:REGULAR UNLEADED
DATE
MAR 1
MAR 2
MAR 3
MAR 4
MAR 5
MAR 6
MAR 7
MAR 8
MAR 9
MAR 10
MAR 11
MAR 12
MAR 13
MAR 13
MAR 14
MAR 16
MAR 17
MAR 18
MAR 19
MAR 20

TIME
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:00
2:21
2:00
2:00
2:00
2:00
2:00
2:00

TOTALS

AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM
AM

OPENING
METERED
VOLUME DLVRIES
SALES
5429
0
3341
2092
5409
1876
5625
3336
3065
5874
2009
2207
5672
0
1568
4108
6503
2170
8444
0
1574
6872
0
2295
4581
5405
2881
7099
0
3312
3793
3898
2436
5253
0
1745
3497
4811
1599
6718
0
2111
4612
6213
3896
6896
0
2807
4096
3302
3440
3969
4802
1930
6839
0
2079
5407

45688

46332

THRESHOLD:

MANUAL CALC'D PHYSICAL WATER
ADJUST INVNTRY INVNTRY HEIGHT VARIANCE
0
2088
2092
0.00
4
0
5625
5625
0.00
0
0
5896
5862
0.00
-34
0
5676
5672
0.00
-4
0
4104
4108
0.00
4
0
8441
8443
0.00
2
0
6870
6872
0.00
2
0
4577
4581
0.00
4
0
7105
7099
0.00
-6
0
3787
3793
0.00
6
0
5255
5253
0.00
-2
0
3508
3497
0.00
-11
0
6709
6718
0.00
9
0
4607
4612
0.00
5
0
6929
6931
0.00
2
0
4089
4096
0.00
7
0
3958
3969
0.00
11
0
6841
6839
0.00
-2
0
4760
4775
0.00
15
0

4763

4775

0.00

12
755

SIGNATURE _________________________


Part No. 576013-635, Revision AA

580

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C07: (Continued)
Typical Response Message, Computer Format:
iC07PPYYMMDDHHmmPPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...ddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
PP
nn
TT
dd
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Number of reconciliation days to follow (Hex)
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

581

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C08
Version 114
Function Type: Basic Inventory Reconciliation Periodic "Column" Report
(Current/Previous)
Command Format:
Display: IC0800tt
Computer: iC0800tt
Notes:
1.

tt - Report type
00=Current Period
01=Previous Period

Typical Response Message, Display Format:

IC0800
MAR 26, 1996
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

MAR 26, 1996

1:42 PM
1....
2....
3....
4....
1:42 PM

PREVIOUS PERIODIC RECONCILIATION REPORT
PRODUCT
OPENING DATE
OPENING TIME
OPENING VOLUME
DELIVERIES
METERED SALES
MANUAL ADJUST
CALC'D INVNTRY
PHYSICAL INVNTRY
WATER HEIGHT
VARIANCE
THRESHOLD
CLOSING DATE
CLOSING TIME

UNLEADED
MAR

1, 1996
2:00 AM
5407
61317
62578
0
4146
4199
0.00
53
755

MAR 20, 1996
2:00 AM

SIGNATURE _________________________


Part No. 576013-635, Revision AA

582

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C08: (Continued)
Typical Response Message, Computer Format:
iC08PPYYMMDDHHmmGGPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.

YYMMDDHHmm
GG
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Date and Time
Number of product Groupings to follow (Hex)
Product Number (Decimal, 00=All Products)
Number of tanks that are mapped to the product (Decimal)
Tank numbers mapped to product
Opening Date and Time
Closing Date and Time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

583

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C09
Version 19
Function Type: Individual Basic Reconciliation Daily History Diagnostic
Command Format:
Display: IC09TTD
Computer: iC09TTD
Notes:
1.
2.

TT - Tank Number (Decimal; 00=all)
D - If 1, will use ticketed delivery else if not entered,
default will use gauged delivery

Typical Response Message, Display Format:

IC09TT1
JAN 1, 2000 3:30 PM
INDIVIDUAL BASIC RECONCILIATION HISTORY DIAGNOSTIC
T 1:* MAG PROBE #1 *
STRT TIME END TIME
STRT HT END HT STRT VL END_VL SALES
9912311104 0001010130 45.737 48.000 4700.0 5000.0 0.0
0001010130 0001010931 48.000 47.895 5000.0 4986.1 0.0

DELIV OFFSET
VAR
300.0 0.0
0.0
0.0 0.0
-13.9

Typical Response Message, Computer Format:
iC0900YYMMDDHHmmTTrrYYMMDDHHmmYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTrrYYMMDDHHmmYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

9.
10.

YYMMDDHHmm
TT
rr
YYMMDDHHmm
YYMMDDHHmm
YYMMDDHHmm
NN
FFFFFFFF

-

Current Time of Day.
Tank Number (Decimal, 00=all)
Number of records to follow (Hex)
Requested start time
Actual start time
End time
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Start height
2. End height
3. Start Volume
4. End Volume
5. Metered sales (dispensed volume)
6. Ticket Delivery
7. Gauged Delivery
8. Offset volume
9. Variance (calculated with ticketed volume)
10. Variance (calculated with gauged volume)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

584

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.6 VARIANCE ANALYSIS REPORTS
Function Code: C10
Function Type: Periodic Book Variance

Version 116

Command Format:
Display: IC10PPtt
Computer: iC10PPtt
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

IC10PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:29 PM
1....
2....
3....
4....

CURRENT PERIOD BOOK VARIANCE
T 1:REGULAR UNLEADED
DATE
TIME
OPENING METERED
MAR 5 9:18 PM
VOLUME
SALES
MAR 6 12:00 AM
6279
151
MAR 7 12:00 AM
6128
3069
MAR 8 12:00 AM
3063
2775
MAR 9 12:00 AM
6196
2674
MAR 10 12:00 AM
3526
2427
MAR 11 12:00 AM
7007
2763
MAR 12 12:00 AM
8344
3091
MAR 13 12:00 AM
5256
3085
MAR 14 12:00 AM
5972
2818
MAR 15 12:00 AM
3160
3041
MAR 16 12:00 AM
6023
2986
MAR 17 12:01 AM
3030
2539
MAR 18 12:00 AM
6404
3061
MAR 19 12:00 AM
3346
3069
MAR 20 12:00 AM
6179
2565
TOTALS

6279

TICKET
DLVY
0
0
5901
0
5901
4099
0
3800
0
5900
0
5902
0
5901
0

40114

THRESHOLD:

37404

MAN CLS BOOK GAUGED
ADJ INVNTRY INVNTRY
0
6128
6128
0
3059
3063
0
6189
6196
0
3522
3526
0
7000
7007
0
8343
8344
0
5253
5256
0
5971
5972
0
3154
3160
0
6019
6023
0
3037
3030
0
6393
6404
0
3343
3346
0
6178
6179
0
3614
3617
0

3569

3617

DAILY
VARIANCE
0= 0.00%
-4= 0.13%
-7= 0.25%
-4= 0.15%
-7= 0.29%
-1= 0.04%
-3= 0.10%
-1= 0.03%
-6= 0.21%
-4= 0.13%
7= 0.23%
-11= 0.43%
-3= 0.10%
-1= 0.03%
-3= 0.12%
-48= 0.12%
531

SIGNATURE _________________________


Part No. 576013-635, Revision AA

585

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C10: (Continued)
Typical Response Message, Computer Format:
iC10PPYYMMDDHHmmPPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
PP - Product Number (Decimal, 00=all)
3.
nn - Number of tanks mapped to product (Decimal)
4.
TT - Tank Number(s) (Decimal)
5.
rr - Number of records to follow (decimal) if 0, no more data for
this tank will follow
6.
YYMMDDHHmm - Opening Date and Time
7.
YYMMDDHHmm - Closing Date and Time
8.
NN - Number of eight character Data Fields to follow (Hex)
9.
FFFFFFFF - ASCII Hex IEEE floats:
1. open volume
2. metered sales
3. ticketed delivery
4. manual adjust
5. close book inventory
6. gauged inventory
7. water height
8. daily variance
9. percent
10.
&& - Data Termination Flag
11.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

586

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C11
Function Type: Weekly Book Variance

Version 116

Command Format:
Display: IC11PPtt
Computer: iC11PPtt
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

IC11PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:30 PM
1....
2....
3....
4....

CURRENT WEEK BOOK VARIANCE
T 1:REGULAR UNLEADED
DATE
TIME
OPENING METERED
MAR 16 12:00 AM
VOLUME
SALES
MAR 17 12:01 AM
3030
2539
MAR 18 12:00 AM
6404
3061
MAR 19 12:00 AM
3346
3069
TOTALS

3030

TICKET
DLVY
5902
0
5901

8669

THRESHOLD:

11803

MAN CLS BOOK GAUGED
ADJ INVNTRY INVNTRY
0
6393
6404
0
3343
3346
0
6178
6179
0

6164

6179

DAILY
VARIANCE
-11= 0.43%
-3= 0.10%
-1= 0.03%
-15= 0.17%
216

SIGNATURE _________________________


Part No. 576013-635, Revision AA

587

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C11 Notes: (Continued)
Typical Response Message, Computer Format:
iC11PPYYMMDDHHmmPPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...rrYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
PP - Product Number (Decimal), 00=all)
3.
nn - Number of tanks mapped to product (Decimal)
4.
TT - Tank Number(s) mapped to product (Decimal)
5.
rr - Number of records to follow
6.
YYMMDDHHmm - Open date and time
7.
YYMMDDHHmm - Close date and time
8.
NN - Number of eight character Data Fields to follow (Hex)
9.
FFFFFFFF - ASCII Hex IEEE floats:
1. open volume
2. metered sales
3. ticketed delivery
4. manual adjust
5. close book inventory
6. gauged inventory
7. water height
8. daily variance
9. percent
10.
&& - Data Termination Flag
11.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

588

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C12
Function Type: Daily Book Variance

Version 116

Command Format:
Display: IC12PPMMDD
Computer: iC12PPMMDD
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
MMDD - Month and day for report (if not entered, will default to
current day)

Typical Response Message, Display Format:

IC12PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:30 PM
1....
2....
3....
4....

DAILY BOOK VARIANCE
T 1:REGULAR UNLEADED
DATE
TIME
OPENING METERED
MAR 18 12:00 AM
VOLUME
SALES
MAR 19 12:00 AM
3346
3069

TICKET
DLVY
5901

MAN CLS BOOK GAUGED
ADJ INVNTRY INVNTRY
0
6178
6179

DAILY
VARIANCE
-1= 0.03%

THRESHOLD:

148

SIGNATURE _________________________

Typical Response Message, Computer Format:
iC10PPYYMMDDHHmmPPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTT...YYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
PP - Product Number (Decimal, 00=all)
3.
nn - Number of tanks mapped to product (Decimal)
4.
TT - Tank Number(s) (Decimal)
5.
YYMMDDHHmm - Open date and time
6.
YYMMDDHHmm - Close date and time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE floats:
1. open volume
2. metered sales
3. ticketed delivery
4. manual adjust
5. close book inventory
6. gauged inventory
7. water height
8. daily variance
9. percent
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

589

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C20
Function Type: Periodic Variance Analysis Report

Version 116

Command Format:
Display: IC20PPtt
Computer: iC20PPtt
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

IC20PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:30 PM
1....
2....
3....
4....

CURRENT PERIOD VARIANCE ANALYSIS
T 1:REGULAR UNLEADED
DATE
TIME
BOOK
MAR 19 2:00 AM
VAR
MAR 20 12:00 AM
-48

DLVY
VAR
-13

SALES BK_VAR
VAR
%
-35
0.12

MTR
VAR
-1

TEMP
VAR
-16

VAP
VAR
0

WATER
CHG
0

UNEX
VAR
-18

SIGNATURE _________________________


Part No. 576013-635, Revision AA

590

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C20 Notes: (Continued)
Typical Response Message, Computer Format:
iC20PPYYMMDDHHmmPPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF...
PPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
PP
nn
TT
dd
YYMMDDHHmm
YYMMDDHHmm
LLLLLLLL

-

9.
10.
11.

llllllll NN FFFFFFFF -

12.
13.

&& CCCC -

Current Date and Time
Product Number (Decimal)
Number of tanks that are mapped to the product (Decimal)
Tank Number (Decimal, 00=all)
Number of reconciliation records to follow
Opening Date and Time for period
Closing Date and Time for period
failure to calibrate in 56 days (bit encoded long integer
with tank 1=lsb)
tank chart alarm (bit encoded long integer with tank 1=lsb)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. book variance
2. delivery variance
3. sales variance
4. book variance percent
5. temperature variance
6. water change
7. unexplained variance
8. Meter variance
(V29)
9. Vapor variance
(V29)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

591

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C21
Function Type: Weekly Variance Analysis Report

Version 116

Command Format:
Display: IC21PPtt
Computer: iC21PPtt
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
tt - Report Type (if not entered will default to current)
01=current
02=previous

Typical Response Message, Display Format:

IC21PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:30 PM
1....
2....
3....
4....

CURRENT WEEK VARIANCE ANALYSIS
T 1:REGULAR UNLEADED
DATE
TIME
BOOK
MAR 18 2:00 AM
VAR
MAR 19 12:00 AM
-15

DLVY
VAR
-13

SALES BK_VAR
VAR
%
-2
0.17

MTR
VAR
-2

TEMP
VAR
-2

VAP
VAR
0

WATER
CHG
0

UNEX
VAR
0

SIGNATURE _________________________


Part No. 576013-635, Revision AA

592

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C21 Notes: (Continued)
Typical Response Message, Computer Format:
iC21PPYYMMDDHHmmPPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF...
PPnnTTddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
PP
nn
TT
dd
YYMMDDHHmm
YYMMDDHHmm
LLLLLLLL

-

9.
10.
11.

llllllll NN FFFFFFFF -

12.
13.

&& CCCC -

Current Date and Time
Product Number (Decimal, 00=all products)
Number of tanks that are mapped to the product (Decimal)
Tank Number (Decimal, 00=all)
Number of reconciliation records to follow
Open date and time
Close date and time
failure to calibrate in 56 days (bit encoded long integer
with tank 1=lsb)
tank chart alarm (bit encoded long integer with tank 1=lsb)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. book variance
2. delivery variance
3. sales variance
4. book variance percent
5. temperature variance
6. water change
7. unexplained variance
8. Meter variance
(V29)
9. Vapor variance
(V29)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

593

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C22
Function Type: Daily Variance Analysis Report

Version 116

Command Format:
Display: IC22PPMMDD
Computer: iC22PPMMDD
Notes:
1.
2.

PP - Product Number (Decimal, 00=all)
MMDD - Month and day for report (if not entered, will default to
current day)

Typical Response Message, Display Format:

IC22PP
MAR 20, 1998
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:31 PM
1....
2....
3....
4....

DAILY VARIANCE ANALYSIS
T 1:REGULAR UNLEADED
DATE
TIME
BOOK
MAR 18 2:00 AM
VAR
MAR 19 12:00 AM
-15

DLVY
VAR
-13

SALES BK_VAR
VAR
%
-2
0.17

MTR
VAR
-1

TEMP
VAR
-2

VAP
VAR
0

WATER
CHG
0

UNEX
VAR
0

SIGNATURE _________________________


Part No. 576013-635, Revision AA

594

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C22 Notes: (Continued)
Typical Response Message, Computer Format:
iC22PPYYMMDDHHmmPPnnTTYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF...
PPnnTTYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllll
NNFFFFFFFF&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
PP
nn
TT
YYMMDDHHmm
YYMMDDHHmm
LLLLLLLL

-

8.
9.
10.

llllllll NN FFFFFFFF -

11.
12.

&& CCCC -

Current Date and Time
Product Number (Decimal, 00=all products)
Number of tanks that are mapped to the product (Decimal)
Tank Number (Decimal, 00=all)
Open date and time
Close date and time
failure to calibrate in 56 days (bit encoded long integer
with tank 1=lsb)
tank chart alarm (bit encoded long integer with tank 1=lsb)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. book variance
2. delivery variance
3. sales variance
4. book variance percent
5. temperature variance
6. water change
7. unexplained variance
8. Meter variance
(V29)
9. Vapor variance
(V29)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

595

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: C25
Function Type: Periodic Variance Analysis Daily Report

Version 19

Command Format:
Display: IC25PPtt
Computer: iC25PPtt
Notes:
1.
2.

PP - Product Number
tt - Report Type
01=current
02=previous

(Decimal, 00=all Products)

Typical Response Message, Display Format:

IC25PP
JAN 1, 1996
STATION
STATION
STATION
STATION

8:05 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CURRENT PERIOD VARIANCE ANALYSIS
T 1:UNLEADED
DATE
TIME
DEC 10 2:00
DEC 10 2:00
DEC 11 2:00
DEC 12 2:00
DEC 13 2:00
DEC 14 2:00
DEC 15 2:00
DEC 16 2:00
DEC 17 2:00
DEC 18 2:00
DEC 19 2:00
DEC 20 2:00
DEC 21 2:00
DEC 22 2:00
DEC 23 2:00
DEC 24 2:00
DEC 25 2:00
DEC 26 2:00
DEC 27 2:00
DEC 28 2:00
DEC 29 2:00
DEC 30 2:00
DEC 31 2:00
JAN 1 2:00


GASOLINE
BOOK
AM
VAR
AM
7
AM
-1
AM
0
AM
-2
AM
-3
AM
-15
AM
-2
AM
0
AM
-2
AM
2
AM
1
AM
-1
AM
5
AM
1
AM
-3
AM
7
AM
0
AM
5
AM
0
AM
0
AM
-2
AM
13
AM
-503

Part No. 576013-635, Revision AA

DLVY
VAR
9
0
0
0
0
-10
0
0
-5
0
0
0
0
0
0
10
0
0
0
0
0
10
-503

SALES BK_VAR
VAR
%
-2
0.54
-1
0.07
0
0.00
-2
0.15
-3
0.30
-5
1.04
-2
0.14
0
0.00
3
0.13
2
0.13
1
0.08
-1
0.14
5
0.36
1
0.09
-3
0.24
-3
0.51
0
0.00
5
0.40
0
0.00
0
0.00
-2
0.17
3
0.98
0 33.83

MTR
VAR
-1
0
0
0
-1
0
0
0
0
0
-2
0
0
0
0
0
0
-1
0
0
0
0
-4

TEMP
VAR
6
0
0
0
0
0
0
0
-9
0
0
0
0
0
0
-11
0
0
0
0
0
-20
31

VAP
VAR
-2
0
0
0
-1
0
-2
0
0
0
0
-1
-1
-1
0
0
0
0
0
0
-2
-2
-2

WATER
CHG
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
0
0
0
0
0

UNEX
VAR
-8
-1
0
-2
-3
-5
-2
0
12
2
1
-1
5
1
-3
8
0
5
0
0
-2
23
-31

596

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code C25 Notes: (Continued)
Typical Response Message, Computer Format:
iC25PPYYMMDDHHmm...
PPnnTTYddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllllNNFFFFFFFF...
PpnnTTYddYYMMDDHHmmYYMMDDHHmmLLLLLLLLllllllllNNFFFFFFFF...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
PP
nn
TT
dd
YYMMDDHHmm
YYMMDDHHmm
LLLLLLLL

-

9.
10.
11.

llllllll NN FFFFFFFF -

12.
13.

&& CCCC -

Current Date and Time
Product Code (Decimal)
Number of tanks that are mapped to the product (Decimal)
Tank Number (Decimal, 0=all)
Number of reconciliation records to follow
Opening Date and Time for period
Closing Date and Time for period
failure to calibrate in 56 days (bit encoded long integer
with tank 1=lsb)
tank chart alarm (bit encoded long integer with tank 1=lsb)
Number of eight character Data Fields to follow (Hex)
ASCII Hex IEEE floats:
1. Book variance
2. Delivery variance
3. Sales variance
4. Book variance percent
5. Temperature variance
6. Water change
7. Unexplained variance
8. Meter variance
(Version 29)
9. Vapor variance
(Version 29)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

597

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.7 IN-STATION DIAGNOSTICS (ISD)
7.7.1 ISD REPORTS
Version 25
Function Code: V00
Function Type: ISD CARB Certified Operating Requirements and Monitoring
Thresholds
Command Format:
Display: IV0000
Computer: iV0000
Notes:
1.

ISD feature required

Typical Response Message, Display Format:

IV0000
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

CARB EVR CERTIFIED OPERATING REQUIREMENTS
VAPOR COLLECTION ASSIST SYSTEM A/L RANGE

Min
0.90

Max
1.10

Below
0.60
-------------

Above
---1.30"wcg
0.30"wcg
13.5cfh
2.50"wcg

ISD MONITORING TEST PASS/FAIL THRESHOLDS
VAPOR
VAPOR
VAPOR
VAPOR
STAGE

COLLECTION BALANCE SYS FLOW PERFORMANCE
CONTAINMENT GROSS FAIL, 95TH PERCENTILE
CONTAINMENT DEGRADATION, 75TH PERCENTILE
CONTAINMENT LEAK DETECTION FAIL @2"WCG
I VAPOR TRANSFER FAIL, 75TH PERCENTILE

Period
7dys
7dys
30dys
7dys
20min

CARB STANDARD REPORT FORMAT - CP201 APPENDIX "EVR-ISD MONTHLY STATUS REPORT"

Typical Response Message, Computer Format:
iV0000YYMMDDHHmmooffNNmmmmmmmm...ppggNNtttttttt...&&CCCC
Notes:
1.
2.
3.

4.
5.
6.

YYMMDDHHmm - Current Date and Time
oo - Number of CARB EVR Certified Operating Requirement fields
(Decimal)
ff - Type of CARB EVR Certified Operating Requirement field
01=Vapor Collection Assist System A/L Range (min/max)
[Assist only]
NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
mmmmmmmm - CARB EVR Certified Operating Requirement field data (ASCII
Hex IEEE float)
pp - Number of ISD Monitoring Test Pass/Fail Threshold fields
(Decimal)

Part No. 576013-635, Revision AA

598

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V00 Notes: (Continued)
7.

gg - Type of ISD Monitoring Test Pass/Fail Threshold field
01=Vapor Collection Assist System A/L Gross Fail
(Days/Low/High) [Assist only]
02=Vapor Collection Assist System A/L Degradation Fail
(Days/Low/High) [Assist only]
03=Vapor Collection Balance System Flow Performance
(Days/High) [Balance Only]
04=Vapor Containment Gross Fail, ?? Percentile
(Days/High)
05=Vapor Containment Degradation, ?? Percentile
(Days/High)
06=Vapor Containment Leak Detection Fail @2\"WCG
(Days/High)
07=Stage I Vapor Transfer Fail, ?? Percentile
(Minutes/High)
08=Vapor Processor Pressure Fail, Performed Daily [Vapor
Processor Required]
09=Vapor Processor Self Test Fail (Days) [VP Required, VP
Control Level: No Control]
10=Vapor Processor HC Emission Concentration Fail
(Days/High) [VP Control Level: Full Control]
11=Vapor Processor Duty Cycle Fail, Performed Daily [VP
Control Level: Full Control]

8.
9.
10.
11.

NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
tttttttt - ISD Monitoring Test Pass/Fail Thresholds field data (ASCII
Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

599

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V01
Function Type: ISD Alarm Status Report

Version 25

Command Format:
Display: IV0100
Computer: iV0100
Notes:
1.
2.

ISD feature required
Last 10 of each alarm group

Typical Response Message, Display Format:

IV0100
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.00
VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME
WARNING ALARMS
DATE/TIME
03-07-17 17:45:11
FAILURE ALARMS
DATE/TIME
03-07-17 17:45:03
03-07-17 17:44:58

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

DESCRIPTION
READING
MISSING VAPOR PROCESSOR INPUT ED1
DISABLED DIM ALARM

VALUE

DESCRIPTION
MISSING VAPOR
LLD SELF TEST
MISSING VAPOR
LLD SELF TEST

VALUE

READING
PROCESSOR INPUT
FAIL
PROCESSOR INPUT
FAIL

SHUTDOWN & MISCELLANEOUS EVENTS
DATE/TIME
DESCRIPTION
ACTION/NAME
03-07-17 14:04:07
ISD STARTUP
03-07-17 14:04:05
READINESS ISD:PF
EVR:NNN CHECK ISD SENSORS
03-07-17 14:04:05
READINESS ISD:FN
EVR:NNN CHECK SETUP CONFIGURATION
03-07-17 14:04:05
READINESS ISD:PP
EVR:FFP EVR READINESS PENDING
03-07-17 14:04:05
ISD STARTUP
03-07-17 13:58:53
ISD SHUTDOWN
------------------------------------------------------------------------------CARB STANDARD REPORT FORMAT - CP201 APPENDIX "EVR-ISD ALARM STATUS REPORT"


Part No. 576013-635, Revision AA

600

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V01 Notes: (Continued)
Typical Response Message, Computer Format:
iV0100YYMMDDHHmmqqqSSSSSSSSaabbccddeettff...f...
rrrSSSSSSSSaabbccddeettff...f...
sssSSSSSSSSaabbccddeettff...f...&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

YYMMDDHHmm
qqq
SSSSSSSS
aa
bb
cc
dd
ee
tt

-

10.
11.
12.
13.
14.
15.
16.
17.
18.
19.

ff
ffffffff
rrr
SSSSSSSS
aa
bb
cc
dd
ee
tt

-

20.
21.
22.
23.

ff
ffffffff
sss
SSSSSSSS

-

24.

aa -

Time/Date stamp of report
number of ISD Warning Alarms to follow (Decimal)
Timestamp of the Warning Alarm (Seconds since 1/1/1970, Hex)
primary warn event category
primary warn event type
device ID (Hex)
secondary warn event category (Hex)
secondary warn event type (Hex)
Data type to follow
00=No Data
01=integer
02=floating point number
Data type (optional, depends on tt)
Data type (optional, depends on tt, Hex)
Number of ISD Failure Alarms to follow (Decimal)
Timestamp of the Failure Alarm (Seconds since 1/1/1970, Hex)
primary failure event category (Hex)
primary failure event type (Hex)
device ID (Hex)
secondary failure event category (Hex)
secondary failure event type (Hex)
Data type to follow
00=No Data
01=integer
02=floating point number
Data type (optional, depends on tt)
Data type (optional, depends on tt, Hex)
Number of ISD Shutdown & Misc. Events to follow (Decimal)
Timestamp of the Shutdown/Misc. Event (Seconds since
1/1/1970, Hex)
primary misc event category
01=System Event
02=Pumps Re-enabled
03=Test Manually Cleared
04=Disabled Dispensers
05=Disabled FP
06=EVR/ISD Readiness Check
99=Internal Error

Part No. 576013-635, Revision AA

601

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V01 Notes: (Continued)
25.

26.
27.
28.
29.

30.
31.
32.
33.

bb - primary misc event type
If aa=01:
01=ISD Startup at:
02=ISD Shutdown at:
03=Time Change Detected at:
If aa=03:
01=ISD SelfTest
02=Vapor Processor
03=Containment Gross & Degrd
04=Containment Vapor Leakage
05=Collection Test HHhh grade
06=Sensor Out
If aa=04:
01=Vapor Containment Leakage,
02=Containment Gross,
03=Containment Pressure Degradation,
04=Vapor Processor Problem
If aa=05:
01=A/L Ratio Gross Blockage,
02=A/L Ratio Degradation,
03=Flow Performance Blk
If aa=06:
01=Check Setup Configuration
02=ISD Sensors Readiness Pending
03=Check ISD Sensors
cc - hose number (Hex)
dd - secondary misc event category (Hex) (future uses)
ee - secondary misc event type (Hex) (future uses)
tt - Data type to follow
00=No Data
01=integer
02=floating point number
ff - Data type (optional, depends on tt)
ffffffff - Data type (optional, depends on tt, Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

602

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V02
Function Type: ISD Monthly Status Report

Version 25

Command Format:
Display: IV0200yyyymm
Computer: iV0200yyyymm
Notes:
1.
2.
3.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.

Typical Response Message, Display Format:

IV0200
JUN 1, 2012
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ISD MONTHLY STATUS REPORT
REPORT DATE: JUN 2012
EVR TYPE: BALANCE
ISD TYPE: V1.00
VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

CARB EVR CERTIFIED OPERATING REQUIREMENTS
VAPOR COLLECTION ASSIST SYSTEM A/L RANGE

Min
0.90

Max
1.10

ISD MONITORING TEST PASS/FAIL THRESHOLDS
VAPOR
VAPOR
VAPOR
VAPOR
STAGE

COLLECTION BALANCE SYS FLOW PERFORMANCE
CONTAINMENT GROSS FAIL, 95TH PERCENTILE
CONTAINMENT DEGRADATION, 75TH PERCENTILE
CONTAINMENT PRESSURE INTEGRITY FAIL @2"WCG
I VAPOR TRANSFER FAIL, 75TH PERCENTILE

PERIOD
7DYS
7DYS
30DYS
7DYS
20MIN

BELOW
0.60
-------------

ABOVE
---1.30"WCG
0.30"WCG
13.5CFH
2.50"WCG

ISD WARNING ALARMS
DATE
2012/06/06
2012/06/06

TIME
23:55
23:55

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE

READING
FP1 SUPER
FP4 REG

VALUE
BLKD
BLKD

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE

READING
FP8 SUPER
FP3 REG
FP8 SUPER

VALUE
BLKD
BLKD
BLKD

FAILURE ALARMS
DATE
2012/06/07
2012/06/06
2012/06/06

TIME
23:55
23:55
23:55

SHUTDOWN & MISC. EVENT LOG
DATE
2012/03/07
2012/03/06
2012/03/06
2012/03/05

TIME
23:55
23:55
23:55
23:59

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
READINESS CODE ISD:PP EVR: PPPP EVR/ISD

ACTION OR NAME
DISABLED FP8
DISABLED FP3
DISABLED FP8
SYSTEM READY

CARB STANDARD REPORT FORMAT - CP201 APPENDIX "EVR-ISD MONTHLY STATUS REPORT"


Part No. 576013-635, Revision AA

603

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V02 Notes: (Continued)
Typical Response Message, Computer Format:
iV0200YYMMDDHHmmooffNNmmmmmmmmppgg
NNttttttttqqqSSSSSSSSaabbccddeettf...f...
rrrSSSSSSSSaabbccddeettf...f...
sssSSSSSSSSaabbccddeettf...f...&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.

YYMMDDHHmm - Time/Date stamp of report
oo - Number of CARB EVR Certified Operating Requirement fields
(Decimal)
ff - Type of CARB EVR Certified Operating Requirement field
01=Vapor Collection Assist System A/L Range (min/max)
[Assist only]
NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
mmmmmmmm - CARB EVR Certified Operating Requirement field data (ASCII
Hex IEEE float)
pp - Number of ISD Monitoring Test Pass/Fail Threshold fields
(Decimal)
gg - Type of ISD Monitoring Test Pass/Fail Threshold field
01=Vapor Collection Assist System A/L Gross Fail
(Days/Low/High) [Assist only]
02=Vapor Collection Assist System A/L Degradation Fail
(Days/Low/High) [Assist only]
03=Vapor Collection Balance System Flow Performance
(Days/High) [Balance Only]
04=Vapor Containment Gross Fail, ?? Percentile
(Days/High)
05=Vapor Containment Degradation, ?? Percentile
(Days/High)
06=Vapor Containment Leak Detection Fail @2\"WCG
(Days/High)
07=Stage I Vapor Transfer Fail, ?? Percentile
(Minutes/High)
08=Vapor Processor Pressure Fail, Performed Daily [Vapor
Processor Required]
09=Vapor Processor Self Test Fail (Days) [VP Required, VP
Control Level: No Control]
10=Vapor Processor HC Emission Concentration Fail
(Days/High) [VP Control Level: Full Control]
11=Vapor Processor Duty Cycle Fail, Performed Daily [VP
Control Level: Full Control]

Part No. 576013-635, Revision AA

604

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V02 Notes: (Continued)
8.
9.
10.
11.

NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
tttttttt - ISD Monitoring Test Pass/Fail Thresholds field data (ASCII
Hex IEEE float)
qqq - number of ISD Warning Alarms to follow (Hex)
SSSSSSSS - Timestamp of the Warning Alarm (Seconds since 1/1/1970, Hex)

12.
13.
14.
15.
16.
17.

aa
bb
cc
dd
ee
tt

-

18.
19.
20.
21.
22.
23.
24.
25.
26.
27.

ff
ffffffff
rrr
SSSSSSSS
aa
bb
cc
dd
ee
tt

-

28.
29.
30.
31.

ff
ffffffff
sss
SSSSSSSS

-

primary warn event category
primary warn event type
device ID (Hex)
secondary warn event category (Hex)
secondary warn event type (Hex)
Data type to follow
00=No Data
01=integer
02=floating point number
Data type (optional, depends on tt)
Data type (optional, depends on tt, Hex)
Number of ISD Failure Alarms to follow (Hex)
Timestamp of the Failure Alarm (Seconds since 1/1/1970, Hex)
primary failure event category (Hex)
primary failure event type (Hex)
device ID (Hex)
secondary failure event category (Hex)
secondary failure event type (Hex)
Data type to follow
00=No Data
01=integer
02=floating point number
Data type (optional, depends on tt)
Data type (optional, depends on tt, Hex)
Number of ISD Shutdown & Misc. Events to follow (Hex)
Timestamp of the Shutdown & Misc. Event (Seconds since
1/1/1970, Hex)

Part No. 576013-635, Revision AA

605

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V02 Notes: (Continued)
32.

33.

34.
35.
36.
37.

38.
39.
40.
41.

aa - primary misc event category
01=System Event
02=Pumps Re-enabled
03=Test Manually Cleared
04=Disabled Dispensers
05=Disabled FP
06=EVR/ISD Readiness Check
99=Internal Error
bb - primary misc event type
If aa=01:
01=ISD Startup at:
02=ISD Shutdown at:
03=Time Change Detected at:
If aa=03:
01=ISD SelfTest
02=Vapor Processor
03=Containment Gross & Degrd
04=Containment Vapor Leakage
05=Collection Test HHhh grade
06=Sensor Out
If aa=04:
01=Vapor Containment Leakage,
02=Containment Gross,
03=Containment Pressure Degradation,
04=Vapor Processor Problem
If aa=05:
01=A/L Ratio Gross Blockage,
02=A/L Ratio Degradation,
03=Flow Performance Blk
If aa=06:
01=Check Setup Configuration
02=ISD Sensors Readiness Pending
03=Check ISD Sensors
cc - hose number (Hex)
dd - secondary misc event category (Hex) (future uses)
ee - secondary misc event type (Hex) (future uses)
tt - Data type to follow
00=No Data
01=integer
02=floating point number
ff - Data type (optional, depends on tt)
ffffffff - Data type (optional, depends on tt, Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

606

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V03
Function Type: ISD Daily Status Report

Version 25

Command Format:
Display: IV0300YYYYMMDD
Computer: iV0300YYYYMMDD
Notes:
1.
2.

ISD feature required
YYYYMMDD - Year/Month/Day of records

Typical Response Message, Display Format:

IV0300
JUN 1, 2002
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ISD DAILY STATUS REPORT:

Report Date - MMM DD, YYYY

EVR TYPE: BALANCE
ISD TYPE: V1.00
VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

CARB EVR CERTIFIED OPERATING REQUIREMENTS
VAPOR COLLECTION ASSIST SYSTEM A/L RANGE

Min
0.90

Max
1.10

ISD MONITORING TEST PASS/FAIL THRESHOLDS
VAPOR
VAPOR
VAPOR
VAPOR
STAGE

COLLECTION BALANCE SYS FLOW PERFORMANCE
CONTAINMENT GROSS FAIL, 95TH PERCENTILE
CONTAINMENT DEGRADATION, 75TH PERCENTILE
CONTAINMENT PRESSURE INTEGRITY FAIL @2"WCG
I VAPOR TRANSFER FAIL, 75TH PERCENTILE

PERIOD
7DYS
7DYS
30DYS
7DYS
20MIN

BELOW
0.60
-------------

ABOVE
---1.30"WCG
0.30"WCG
13.5CFH
2.50"WCG

ISD WARNING ALARMS
DATE
2002/06/07
2002/06/06
2002/06/06

TIME
23:55
23:55
23:55

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE

READING
FP7 MID
FP1 SUPER
FP4 REG

VALUE
BLKD
BLKD
BLKD

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE

READING
FP8 SUPER
FP3 REG
FP8 SUPER

VALUE
BLKD
BLKD
BLKD

FAILURE ALARMS
DATE
2002/06/07
2002/06/06
2002/06/06

TIME
23:55
23:55
23:55

SHUTDOWN & MISC. EVENT LOG
DATE
2002/03/06
2002/03/06
2002/03/05

TIME
23:55
23:55
23:59

DESCRIPTION
A/L RATIO GROSS BLOCKAGE
A/L RATIO GROSS BLOCKAGE
READINESS CODE ISD:PP EVR: PPPP EVR/ISD

ACTION OR NAME
DISABLED FP3
DISABLED FP8
SYSTEM READY

CARB STANDARD REPORT FORMAT - CP201 APPENDIX "EVR-ISD DAILY STATUS REPORT"


Part No. 576013-635, Revision AA

607

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V03 Notes: (Continued)
Typical Response Message, Computer Format:
iV0300YYMMDDHHmmooffNNmmmmmmmmppgg
NNttttttttqqqSSSSSSSSaabbccddeettf...f...
rrrSSSSSSSSaabbccddeettf...f...
sssSSSSSSSSaabbccddeettf...f...&&CCCC
Notes:
1.
2.
3.

4.
5.
6.
7.

YYMMDDHHmm - Time/Date stamp of report
oo - Number of CARB EVR Certified Operating Requirement fields
(Decimal)
ff - Type of CARB EVR Certified Operating Requirement field
01=Vapor Collection Assist System A/L Range (min/max)
[Assist only]
NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
mmmmmmmm - CARB EVR Certified Operating Requirement field data (ASCII
Hex IEEE float)
pp - Number of ISD Monitoring Test Pass/Fail Threshold fields
(Decimal)
gg - Type of ISD Monitoring Test Pass/Fail Threshold field
01=Vapor Collection Assist System A/L Gross Fail
(Days/Low/High) [Assist only]
02=Vapor Collection Assist System A/L Degradation Fail
(Days/Low/High) [Assist only]
03=Vapor Collection Balance System Flow Performance
(Days/High) [Balance Only]
04=Vapor Containment Gross Fail, ?? Percentile
(Days/High)
05=Vapor Containment Degradation, ?? Percentile
(Days/High)
06=Vapor Containment Leak Detection Fail @2\"WCG
(Days/High)
07=Stage I Vapor Transfer Fail, ?? Percentile
(Minutes/High)
08=Vapor Processor Pressure Fail, Performed Daily [Vapor
Processor Required]
09=Vapor Processor Self Test Fail (Days) [VP Required, VP
Control Level: No Control]
10=Vapor Processor HC Emission Concentration Fail
(Days/High) [VP Control Level: Full Control]
11=Vapor Processor Duty Cycle Fail, Performed Daily [VP
Control Level: Full Control]

Part No. 576013-635, Revision AA

608

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V03 Notes: (Continued)
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.

18.
19.
20.
21.
22.
23.
24.
25.
26.
27.

28.
29.
30.
31.

NN - number of ASCII Hex IEEE float data fields to follow
(Decimal)
tttttttt - ISD Monitoring Test Pass/Fail Thresholds field data (ASCII
Hex IEEE float)
qqq - number of ISD Warning Alarms to follow (Hex)
SSSSSSSS - Timestamp of the Warning Alarm (Seconds since 1/1/1970, Hex)
aa - primary warn event category
bb - primary warn event type
cc - device ID (Hex)
dd - secondary warn event category (Hex)
ee - secondary warn event type (Hex)
tt - Data type to follow
00=No Data
01=integer
02=floating point number
ff - Data type (optional, depends on tt)
ffffffff - Data type (optional, depends on tt, Hex)
rrr - Number of ISD Failure Alarms to follow (Hex)
SSSSSSSS - Timestamp of the Failure Alarm (Seconds since 1/1/1970, Hex)
aa - primary failure event category (Hex)
bb - primary failure event type (Hex)
cc - device ID (Hex)
dd - secondary failure event category (Hex)
ee - secondary failure event type (Hex)
tt - Data type to follow
00=No Data
01=integer
02=floating point number
ff - Data type (optional, depends on tt)
ffffffff - Data type (optional, depends on tt, Hex)
sss - Number of ISD Shutdown & Misc. Events to follow (Hex)
SSSSSSSS - Timestamp of the Shutdown & Misc. Event (Seconds since
1/1/1970, Hex)

Part No. 576013-635, Revision AA

609

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V03 Notes: (Continued)
32.

33.

34.
35.
36.
37.

38.
39.
40.
41.

aa - primary misc event category
01=System Event
02=Pumps Re-enabled
03=Test Manually Cleared
04=Disabled Dispensers
05=Disabled FP
06=EVR/ISD Readiness Check
99=Internal Error
bb - primary misc event type
If aa=01:
01=ISD Startup at:
02=ISD Shutdown at:
03=Time Change Detected at:
If aa=03:
01=ISD SelfTest
02=Vapor Processor
03=Containment Gross & Degrd
04=Containment Vapor Leakage
05=Collection Test HHhh grade
06=Sensor Out
If aa=04:
01=Vapor Containment Leakage,
02=Containment Gross,
03=Containment Pressure Degradation,
04=Vapor Processor Problem
If aa=05:
01=A/L Ratio Gross Blockage,
02=A/L Ratio Degradation,
03=Flow Performance Blk
If aa=06:
01=Check Setup Configuration
02=ISD Sensors Readiness Pending
03=Check ISD Sensors
cc - hose number (Hex)
dd - secondary misc event category (Hex) (future uses)
ee - secondary misc event type (Hex) (future uses)
tt - Data type to follow
00=No Data
01=integer
02=floating point number
ff - Data type (optional, depends on tt)
ffffffff - Data type (optional, depends on tt, Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

610

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V04
Function Type: ISD Daily Report Details (by month)

Version 25

Command Format:
Display: IV0400yyyymm
Computer: iV0400yyyymm
Notes:
1.
2.
3.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.

Typical Response Message, Display Format:

IV0400
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest- Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor
FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass
Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass
1.05 Blkd 1.01 1.02 0.98 1.06
---------------------------------------------------------------------------------Hose Flow Performance----Collection Tests---------------FP3
FP3
FP3
FP4
FP4
FP4
FP5
FP5
FP5
Date
Reg
Super Mid
Reg
Super Mid
Reg
Super Mid
02/19 Blkd 0.68N 1.00N Blkd 0.87 0.96 Blkd 0.87 0.92
02/20 Blkd 0.75 1.00N Blkd 0.83 0.97 0.86 1.09 0.92
02/21 Blkd 0.80 1.04 Blkd 0.89 1.00 0.88 1.12 1.03
02/22 Blkd 0.77 1.09 Blkd Blkd 0.95 Blkd 1.12 1.04
02/23 Blkd 0.95 1.03 Blkd Blkd 0.93 Blkd 1.15 0.99
02/24
N N 0.96 0.99 Blkd 0.72N 0.98 Blkd 1.02 0.89
02/25
N N 0.90 1.07 0.76 0.67N 0.99 Blkd 1.01 0.91
02/26 0.69N 0.90 1.06 0.71 Blkd 0.93 Blkd 0.99 0.95
02/27 Blkd 0.97 1.06 Blkd Blkd 0.94 Blkd 1.02 0.88
02/28 Blkd 0.82 1.02 Blkd Blkd 0.89 Blkd 0.90 1.14
----------------------------------------------------------CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

611

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V04 Notes: (Continued)
Typical Response Message, Computer Format:
iV0400YYMMDDHHmmiiiiMMDDaddskkkkkkkksttttttttrrrrrrrrvvvvvvvv
sccccccccegnnffhhsmmmmmmmm...
nnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
iiii
MMDD
a
dd
s

-

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

16.

nn -

17.
18.
19.

ff hh s -

20.
21.
22.

mmmmmmmm && CCCC -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
ISD Monitor Up Time % (Hex) (00-64)
status for containment gros
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (-0.01=Blkd) (ASCII Hex IEEE float)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (-0.01=Blkd) (ASCII Hex IEEE
float)
Containment Min value (-0.01=Blkd) (ASCII Hex IEEE float)
Containment Max value (-0.01=Blkd) (ASCII Hex IEEE float)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (-0.01=Blkd) (ASCII Hex IEEE float)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS
number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (Hex)
fuel position number (Decimal)
hose number (Decimal)
status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
A/L Ratio value (-0.01=Blkd) (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

612

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V05
Function Type: ISD Daily Report Details (by day(s))

Version 25

Command Format:
Display: IV0500ddd
Computer: iV0500ddd
Notes:
1.
2.

ISD feature required
ddd - number of days
000=current day
001=yesterday & today
002=including two days ago, etc.

Typical Response Message, Display Format:

IV0500
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest-Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor
FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass
Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass
1.05 Blkd 1.01 1.02 0.98 1.06
----------------------------------------------------------------------------------

Date
02/19
02/20
02/21
02/22
02/23
02/24
02/25
02/26
02/27
02/28

-------------------Collection
FP3
FP3
FP3
FP4
FP4
Reg
Super Mid
Reg
Super
Blkd 0.68N 1.00N Blkd 0.87
Blkd 0.75 1.00N Blkd 0.83
Blkd 0.80 1.04 Blkd 0.89
Blkd 0.77 1.09 Blkd Blkd
Blkd 0.95 1.03 Blkd Blkd
N N 0.96 0.99 Blkd 0.72N
N N 0.90 1.07 0.76 0.67N
0.69N 0.90 1.06 0.71 Blkd
Blkd 0.97 1.06 Blkd Blkd
Blkd 0.82 1.02 Blkd Blkd

Tests-----------------FP4
FP5
FP5
FP5
Mid
Reg
Super Mid
0.96 Blkd 0.87 0.92
0.97 0.86 1.09 0.92
1.00 0.88 1.12 1.03
0.95 Blkd 1.12 1.04
0.93 Blkd 1.15 0.99
0.98 Blkd 1.02 0.89
0.99 Blkd 1.01 0.91
0.93 Blkd 0.99 0.95
0.94 Blkd 1.02 0.88
0.89 Blkd 0.90 1.14

CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

613

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V05 Notes: (Continued)
Typical Response Message, Computer Format:
iV0500YYMMDDHHmmiiiiMMDDaddskkkkkkkksttttttttrrrrrrrrvvvvvvvv...
sccccccccegnnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
iiii
MMDD
a

-

5.
6.

dd s -

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
0=N/A
1=WARN
2=FAIL
3=PASS
4=ISD/W
5=ISD/F
ISD Monitor Up Time % (Hex) (0-100)
status for containment gross
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (ASCII Hex IEEE float) (0.01=Blkd)
Containment Min value (ASCII Hex IEEE float) (-0.01=Blkd)
Containment Max value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (ASCII Hex IEEE float) (-0.01=Blkd)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS

Part No. 576013-635, Revision AA

614

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V05 Notes: (Continued)
16.
17.
18.
19.

20.
21.
22.

nn - number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (-0.01=Blkd) (Decimal)
ff - fuel position number (Decimal)
hh - hose number (Decimal)
s - status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
mmmmmmmm - A/L Ratio value (ASCII Hex IEEE float
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

615

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V06
Function Type: ISD Daily Report Details, 132 columns (by month)

Version 25

Command Format:
Display: IV0600yyyymm
Computer: iV0600yyyymm
Notes:
1.
2.
3.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.

Typical Response Message, Display Format:

IV0600
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest-Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass 1.05 Blkd 1.01 1.02 0.98 1.06
----------------------------------------------------------------------------------------------------Collection Tests-----------------FP3
FP3
FP3
FP4
FP4
FP4
FP5
FP5
FP5
Date
Reg
Super Mid
Reg
Super Mid
Reg
Super Mid
02/19 Blkd 0.68N 1.00N Blkd 0.87 0.96 Blkd 0.87 0.92
02/20 Blkd 0.75 1.00N Blkd 0.83 0.97 0.86 1.09 0.92
02/21 Blkd 0.80 1.04 Blkd 0.89 1.00 0.88 1.12 1.03
02/22 Blkd 0.77 1.09 Blkd Blkd 0.95 Blkd 1.12 1.04
02/23 Blkd 0.95 1.03 Blkd Blkd 0.93 Blkd 1.15 0.99
02/24
N N 0.96 0.99 Blkd 0.72N 0.98 Blkd 1.02 0.89
02/25
N N 0.90 1.07 0.76 0.67N 0.99 Blkd 1.01 0.91
02/26 0.69N 0.90 1.06 0.71 Blkd 0.93 Blkd 0.99 0.95
02/27 Blkd 0.97 1.06 Blkd Blkd 0.94 Blkd 1.02 0.88
02/28 Blkd 0.82 1.02 Blkd Blkd 0.89 Blkd 0.90 1.14
----------------------------------------------------------CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

616

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V06 Notes: (Continued)
Typical Response Message, Computer Format:
iV0600YYMMDDHHmmiiiiMMDDaddskkkkkkkksttttttttrrrrrrrrvvvvvvvv...
sccccccccegnnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
iiii
MMDD
a

-

5.
6.

dd s -

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
0=N/A
1=WARN
2=FAIL
3=PASS
4=ISD/W
5=ISD/F
ISD Monitor Up Time % (Hex) (0-100)
status for containment gross
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (ASCII Hex IEEE float) (0.01=Blkd)
Containment Min value (ASCII Hex IEEE float) (-0.01=Blkd)
Containment Max value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (ASCII Hex IEEE float) (-0.01=Blkd)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS

Part No. 576013-635, Revision AA

617

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V06 Notes: (Continued)
16.
17.
18.
19.

20.
21.
22.

nn - number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (-0.01=Blkd) (Decimal)
ff - fuel position number (Decimal)
hh - hose number (Decimal)
s - status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
mmmmmmmm - A/L Ratio value (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

618

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V07
Function Type: ISD Daily Report Details (by day(s))

Version 25

Command Format:
Display: IV0700ddd
Computer: iV0700ddd
Notes:
1.
2.

ISD feature required
ddd - number of days
000=current day
001=yesterday & today
002=including two days ago, etc.

Typical Response Message, Display Format:

IV0700
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest-Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass 1.05 Blkd 1.01 1.02 0.98 1.06
----------------------------------------------------------------------------------

Date
02/19
02/20
02/21
02/22
02/23
02/24
02/25
02/26
02/27
02/28

-------------------Collection
FP3
FP3
FP3
FP4
FP4
Reg
Super Mid
Reg
Super
Blkd 0.68N 1.00N Blkd 0.87
Blkd 0.75 1.00N Blkd 0.83
Blkd 0.80 1.04 Blkd 0.89
Blkd 0.77 1.09 Blkd Blkd
Blkd 0.95 1.03 Blkd Blkd
N N 0.96 0.99 Blkd 0.72N
N N 0.90 1.07 0.76 0.67N
0.69N 0.90 1.06 0.71 Blkd
Blkd 0.97 1.06 Blkd Blkd
Blkd 0.82 1.02 Blkd Blkd

Tests-----------------FP4
FP5
FP5
FP5
Mid
Reg
Super Mid
0.96 Blkd 0.87 0.92
0.97 0.86 1.09 0.92
1.00 0.88 1.12 1.03
0.95 Blkd 1.12 1.04
0.93 Blkd 1.15 0.99
0.98 Blkd 1.02 0.89
0.99 Blkd 1.01 0.91
0.93 Blkd 0.99 0.95
0.94 Blkd 1.02 0.88
0.89 Blkd 0.90 1.14

CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

619

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V07 Notes: (Continued)
Typical Response Message, Computer Format:
iV0700YYMMDDHHmmiiiiMMDDadddskkkkkkkksttttttttrrrrrrrrvvvvvvvv...
sccccccccegnnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
iiii
MMDD
a

-

5.
6.

dd s -

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
0=N/A
1=WARN
2=FAIL
3=PASS
4=ISD/W
5=ISD/F
ISD Monitor Up Time % (Hex) (0-100)
status for containment gross
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (ASCII Hex IEEE float) (0.01=Blkd)
Containment Min value (ASCII Hex IEEE float) (-0.01=Blkd)
Containment Max value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (ASCII Hex IEEE float) (-0.01=Blkd)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS

Part No. 576013-635, Revision AA

620

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V07 Notes: (Continued)
16.
17.
18.
19.

20.
21.
22.

nn - number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (-0.01=Blkd) (Decimal)
ff - fuel position number (Decimal)
hh - hose number (Decimal)
s - status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
mmmmmmmm - A/L Ratio value (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

621

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V08
Function Type: ISD Daily Report Details (by month)

Version 25

Command Format:
Display: IV0800yyyymmCCC
Computer: iV0800yyyymmCCC
Notes:
1.
2.
3.
4.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.
CCC - Number of columns, Default=255 [055-999] (Decimal)

Typical Response Message, Display Format:

IV0800
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest-Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass
Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass
1.05 Blkd 1.01 1.02 0.98 1.06
----------------------------------------------------------------------------------------------------Collection Tests-----------------FP3
FP3
FP3
FP4
FP4
FP4
FP5
FP5
FP5
Date
Reg
Super Mid
Reg
Super Mid
Reg
Super Mid
02/19 Blkd 0.68N 1.00N Blkd 0.87 0.96 Blkd 0.87 0.92
02/20 Blkd 0.75 1.00N Blkd 0.83 0.97 0.86 1.09 0.92
02/21 Blkd 0.80 1.04 Blkd 0.89 1.00 0.88 1.12 1.03
02/22 Blkd 0.77 1.09 Blkd Blkd 0.95 Blkd 1.12 1.04
02/23 Blkd 0.95 1.03 Blkd Blkd 0.93 Blkd 1.15 0.99
02/24
N N 0.96 0.99 Blkd 0.72N 0.98 Blkd 1.02 0.89
02/25
N N 0.90 1.07 0.76 0.67N 0.99 Blkd 1.01 0.91
02/26 0.69N 0.90 1.06 0.71 Blkd 0.93 Blkd 0.99 0.95
02/27 Blkd 0.97 1.06 Blkd Blkd 0.94 Blkd 1.02 0.88
02/28 Blkd 0.82 1.02 Blkd Blkd 0.89 Blkd 0.90 1.14
----------------------------------------------------------CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

622

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V08 Notes: (Continued)
Typical Response Message, Computer Format:
iV0800YYMMDDHHmmiiiiMMDDadddskkkkkkkksttttttttrrrrrrrrvvvvvvvv...
sccccccccegnnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
iiii
MMDD
a

-

5.
6.

dd s -

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
0=N/A
1=WARN
2=FAIL
3=PASS
4=ISD/W
5=ISD/F
ISD Monitor Up Time % (Hex) (0-100)
status for containment gross
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (ASCII Hex IEEE float) (0.01=Blkd)
Containment Min value (ASCII Hex IEEE float) (-0.01=Blkd)
Containment Max value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (ASCII Hex IEEE float) (-0.01=Blkd)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS

Part No. 576013-635, Revision AA

623

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V08 Notes: (Continued)
16.
17.
18.
19.

20.
21.
22.

nn - number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (-0.01=Blkd) (Decimal)
ff - fuel position number (Decimal)
hh - hose number (Decimal)
s - status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
mmmmmmmm - A/L Ratio value (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

624

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V09
Version 25
Function Type: ISD Daily Report Details, user input columns (by day(s))
Command Format:
Display: IV0900dddCCC
Computer: iV0900dddCCC
Notes:
1.
2.

3.

ISD feature required
ddd - number of days
000=current day
001=yesterday & today
002=including two days ago, etc.
CCC - Number of columns, Default=255 [055-999] (Decimal)

Typical Response Message, Display Format:

IV0900
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD DAILY REPORT DETAILS
EVR Type: BALANCE
ISD Type: V1.00
Vapor Processor Type: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME

:FAIL
:PASS
: 97%
: 5%

EVR VAPOR COLLECTION :NO TEST
STAGE I TRANSFERS:

12 of 12 PASS

Status Codes: (W)Warn (F)Fail (D)Degradation (G)Gross Fail (ISD-W) ISD SelfTest-Warn (ISD-F) ISD
SelfTest-Fail (N)No Test
ISD
ISD ---Containment Tests--Stage
----Collection Tests----Daily Average
EVR
%UP Gross Dgrd Max Min Leak
I Vapor FP1
FP1
FP1
FP2
FP2
FP2
Date Status Time 95%
75%
"wc "wc CFH
Xfr Prcsr
Reg
Super Mid
Reg
Super Mid
02/19
F
100% 2.1N -0.1N
0.0 -0.1 10N Pass Pass
0.79 1.00 1.09 1.06 1.05 1.00
02/20
F
100% 0.3N -0.1N -0.4 0.4 5 N
1.05 0.97 1.08 1.08 1.03 0.90
02/21
F
100% -0.2N -0.2N -0.6 0.6 0 N Pass Pass
1.17 1.03 1.08 1.01 0.98 0.91
02/22
F
100% 0.9 -0.1N -0.2 0.2 0
1.05 0.96 1.05 0.96 0.93 1.06
02/23
F
100% -0.1 -0.2N -0.9 0.9 0
Pass Pass
0.93 1.02 1.06 1.04 0.92 0.97
02/24
F
100% 0.4 -0.2N -0.3 0.3 0
1.03 1.02 1.05 1.04 0.98 0.94
02/25
F
100% -0.3 -0.2N -0.8 0.8 0
Pass Pass
0.86 1.02 1.06 0.99 0.99 1.00
02/26
F
100% 0.6 -0.2N -0.4 0.4 0
Pass Pass
Blkd Blkd 1.05 Blkd 1.11 1.06
02/27
F
100% -0.3 -0.2N -0.7 0.7 0
1.00 Blkd 1.05 1.01 1.10 0.0W
02/28
F
100% -0.1 -0.2N -0.6 0.6 0
Pass Pass
1.05 Blkd 1.01 1.02 0.98 1.06
----------------------------------------------------------------------------------

Date
02/19
02/20
02/21
02/22
02/23
02/24
02/25
02/26
02/27
02/28

-------------------Collection
FP3
FP3
FP3
FP4
FP4
Reg
Super Mid
Reg
Super
Blkd 0.68N 1.00N Blkd 0.87
Blkd 0.75 1.00N Blkd 0.83
Blkd 0.80 1.04 Blkd 0.89
Blkd 0.77 1.09 Blkd Blkd
Blkd 0.95 1.03 Blkd Blkd
N N 0.96 0.99 Blkd 0.72N
N N 0.90 1.07 0.76 0.67N
0.69N 0.90 1.06 0.71 Blkd
Blkd 0.97 1.06 Blkd Blkd
Blkd 0.82 1.02 Blkd Blkd

Tests-----------------FP4
FP5
FP5
FP5
Mid
Reg
Super Mid
0.96 Blkd 0.87 0.92
0.97 0.86 1.09 0.92
1.00 0.88 1.12 1.03
0.95 Blkd 1.12 1.04
0.93 Blkd 1.15 0.99
0.98 Blkd 1.02 0.89
0.99 Blkd 1.01 0.91
0.93 Blkd 0.99 0.95
0.94 Blkd 1.02 0.88
0.89 Blkd 0.90 1.14

CARB Standard Report Format - CP201 Appendix "EVR-ISD Monthly Details Report"


Part No. 576013-635, Revision AA

625

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V09 Notes: (Continued)
Typical Response Message, Computer Format:
iV0900YYMMDDHHmmiiiiMMDDadddskkkkkkkksttttttttrrrrrrrrvvvvvvvv...
sccccccccegnnffhhsmmmmmmmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
iiii
MMDD
a

-

5.
6.

dd s -

7.
8.

kkkkkkkk s -

9.

tttttttt -

10.
11.
12.

rrrrrrrr vvvvvvvv s -

13.
14.

cccccccc e -

15.

g -

Time/Date stamp of report
Number of Record (Hex)
Date stamp of the day detail record
ISD EVR 1 status character
0=N/A
1=WARN
2=FAIL
3=PASS
4=ISD/W
5=ISD/F
ISD Monitor Up Time % (Hex) (0-100)
status for containment gross
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Gross value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment degradation
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Degradation value (ASCII Hex IEEE float) (0.01=Blkd)
Containment Min value (ASCII Hex IEEE float) (-0.01=Blkd)
Containment Max value (ASCII Hex IEEE float) (-0.01=Blkd)
status for containment leak
0=NO TEST
1=WARN
2=FAIL
3=PASS
Containment Leak value (ASCII Hex IEEE float) (-0.01=Blkd)
status for Stage I Transfer
0=NO TEST
1=WARN
2=FAIL
3=PASS
status for Vapor Processor
0=NO TEST
1=WARN
2=FAIL
3=PASS

Part No. 576013-635, Revision AA

626

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V09 Notes: (Continued)
16.
17.
18.
19.

20.
21.
22.

nn - number of records consisting of 1 status character & one
ASCII Hex IEEE Float to follow (-0.01=Blkd) (Decimal)
ff - fuel position number (Decimal)
hh - hose number (Decimal)
s - status for hose
0=NO TEST
1=WARN
2=FAIL
3=PASS
mmmmmmmm - A/L Ratio value (ASCII Hex IEEE float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

627

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V0A
Function Type: ISD Daily Overall Status Report

Version 25

Command Format:
Display: IV0A00yyyymmdd
Computer: iV0A00yyyymmdd
Notes:
1.
2.
3.
4.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.
dd - day 01-31

Typical Response Message, Display Format:

IV0A00
FEB 2, 2005 12:08 AM
ISD DAILY REPORT
REPORT DATE: JAN 29, 2005
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.00
VAPOR PROCESSOR TYPE: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME


Part No. 576013-635, Revision AA

:PASS
:NOTEST
:100%
:100%

EVR VAPOR COLLECTION :PASS
STAGE I TRANSFERS:
VAPOR PROCESSOR :

1 of
PASS

1 PASS

628

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V0A Notes: (Continued)
Typical Response Message, Computer Format:
iV0A00YYMMDDHHmmyyyymmddEVV.VVPACNUUsssSSSpptT&&CCCC
Notes:
1.
2.
3.
4.
5.

6.

7.

8.

9.
10.
11.
12.
13.
14.

15.
16.

YYMMDDHHmm - Time/Date stamp of report
yyyymmdd - Report Date (4 byte Decimal, 2 byte Decimal, 2 byte Decimal)
E - EVR Type
0=Assist
1=Balance
VV.VV - ISD Version number (ASCII)
P - Processor Type
0=None
1=VST
2=OPW
3=ARID
4=User Defined
A - Overall Status
0=Unknown
1=Warning
2=Failure
3=Pass
C - Collection Status
0=Unknown
1=Warning
2=Failure
3=Pass
N - Containment Status
0=Unknown
1=Warning
2=Failure
3=Pass
UU - Percentage Up (Hex 00-64)
sss - Stage 1 Passing Count (Hex)
SSS - Stage 1 Total Count (Hex) Total fail=(SSS-sss)
pp - Percent ISD Pass (Hex 0-64)
t - Processor Installed
0=No
1=Yes
T - Processor Status
0=Unknown
1=Warning
2=Failure
3=Pass
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

629

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V0B
Function Type: ISD Monthly Overall Status Report

Version 25

Command Format:
Display: IV0B00yyyymm
Computer: iV0B00yyyymm
Notes:
1.
2.
3.

ISD feature required
yyyy - year number (e.g. 2002)
mm - month number, 01=January, 02=February, etc.

Typical Response Message, Display Format:

IV0B00
FEB 2, 2005 12:05 AM
ISD MONTHLY REPORT
REPORT DATE: JAN 2005
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.00
VAPOR PROCESSOR TYPE: VST VAPOR PROCESSOR
OVERALL STATUS
EVR VAPOR CONTAINMENT
ISD MONITOR UP-TIME
EVR/ISD PASS TIME


Part No. 576013-635, Revision AA

:PASS
:NOTEST
:100%
:100%

EVR VAPOR COLLECTION :PASS
STAGE I TRANSFERS: 13 of 13 PASS
VAPOR PROCESSOR : PASS

630

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V0B Notes: (Continued)
Typical Response Message, Computer Format:
iV0B00YYMMDDHHmmyyyymmddEVV.VVPACNUUsssSSSpptT&&CCCC
Notes:
1.
2.
3.
4.
5.

6.

7.

8.

9.
10.
11.
12.
13.
14.

15.
16.

YYMMDDHHmm - Time/Date stamp of report
yyyymmdd - Beginning of the report period (for monthly report dd=01) (4
byte Decimal, 2 byte Decimal, 2 byte Decimal)
E - EVR Type
0=Assist
1=Balance
VV.VV - ISD Version number
P - Processor Type
0=None
1=VST
2=OPW
3=ARID
4=User Defined
A - Overall Status
0=Unknown
1=Warning
2=Failure
3=Pass
C - Collection Status
0=Unknown
1=Warning
2=Failure
3=Pass
N - Containment Status
0=Unknown
1=Warning
2=Failure
3=Pass
UU - Percentage Up (Hex 0-64)
sss - Stage 1 Passing Count (Hex)
SSS - Stage 1 Total Count (Hex) Total fail=(SSS-sss)
pp - Percent ISD Pass (Hex 0-64)
t - Processor Installed
0=No
1=Yes
T - Processor Status
0=Unknown
1=Warning
2=Failure
3=Pass
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

631

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V10
Function Type: ISD Version Number

Version 25

Command Format:
Display: IV1000
Computer: iV1000
Typical Response Message, Display Format:

IV1000
JUN 7, 2004

4:07 PM

ISD VERSION: 01.00

Typical Response Message, Computer Format:
iV1000YYMMDDHHmmvv.rr&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
vv
rr
&&
CCCC

-

Current Date and Time
ISD Version
ISD Revision
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

632

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V12
Function Type: Vapor Collection Test Results

Version 30

Command Format:
Display: IV1200nnn
Computer: iV1200nnn
Typical Response Message, Display Format:

IV1200
JUN 10, 2010

4:07 PM

BALANCE FLOW MONITORING TEST RESULTS
REC# TEST TIMESTAMP
ESTPRORVR
0001 10-06-09 23:59:00 25.1%
---DISPENSER-- -----FLOW MONITORING--- ----------ORVR----------FP LABEL
STATUS A/L
DAYS EVNT STATUS EVNT &BLCK %THRS
03 BLEND3
NOTEST 0.84 0.3
14 PASS
14 35.71 54.97
02 BLEND3
NOTEST 0.59 0.1
3 PASS
3 33.33 0.00
05 BLEND3
NOTEST 0.86 0.3
26 PASS
26 23.08 47.02
06 BLEND3
NOTEST 0.82 0.3
7 PASS
7 42.86 0.00


Part No. 576013-635, Revision AA

633

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V12 Notes: (Continued)
Typical Response Message, Computer Format:
iV1200YYMMDDHHmmnnnnssssssssoo
00000000LLLLLLLLttttttttTTTTTTTTS
nnpphhvvcsrrrrrrrrddddddddeeee…
pphhvvcsrrrrrrrrddddddddeeee…
csaabbbbmmmgggggggghhhhhhhh&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.
12.
13.
14.
15.

16.
17.
18.
19.

20.
21.
22.
23.
24.

25.
26.
27.
28.
29.
30.

YYMMDDHHmm - Current Date and Time
nnnn - Number of records to follow (hex)
ssssssss - Date and Time of test as seconds since 1/1/1970 (ascii hex
long)
oo - Number of ORVR header records to follow (hex)
Note: Items OOOOOOOO to S are only included when oo = 1
OOOOOOOO - Est proporation of ORVR % (ascii hex float)
LLLLLLLL - ORVR Penetration Limit % (ascii hex float)
tttttttt - ChiSquare value (scii hex float)
TTTTTTTT - ChiSquare threshold (ascii hex float)
S - Chi^2 Test Status (decimal)
0=N/A
1=WARN
2=FAIL
3=PASS
nn - Number of records to follow (hex)
ff - Fuel Position Number (decimal)
hh - Hose number (decimal)
vv - Flowmeter number (decimal)
c - EVR Type (decimal)
1=Gross Test
2=Gross and Degradation Test
s - Gross Test Status (decimal)
0=N/A
1=WARN
2=FAIL
3=PASS
rrrrrrrr - Gross A/L ratio (ascii hex float)
dddddddd - Gross days of data (ascii hex float)
eeee - Gross number of events used for test (hex)
S - Degradation test status
0=N/A
1=WARN
2=FAIL
3=PASS
RRRRRRRR - Degradation A/L ratio (ascii hex float)
DDDDDDDD - Degradation days of data (ascii hex float)
EEEE - Degradation number of events used for test (hex)
c - Stat test results 0 or 1 (decimal)
s - ORVR test status (decimal)
0=N/A
1=WARN
2=FAIL
3=PASS
bbbb - Number of zero events (hex)
mmmm - Number of A/L events (hex)
gggggggg - % A/L events blocked (ascii hex float)
hhhhhhhh - % Threshold (ascii hex float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

634

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.7.2 ISD SETUP
Function Code: V40
Function Type: Set Vapor Processor Type
Command Format:
Display: SV4000tt
Computer: sV4000tt
Notes:
1.
2.

PMC feature required
tt - type of
00 =
01 =
03 =
05 =
07 =

Vapor Processor
None
VST ECS Processor
HIRT Vapor Processor (ISD SEM required)
Veeder-Root Polisher
VST Green Machine

Version 25
Inquire:
IV4000
iV4000

(V30)

Typical Response Message, Display Format:

IV4000
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

VAPOR PROCESSOR TYPE
VST ECS PROCESSOR

Typical Response Message, Computer Format:
iV4000YYMMDDHHmmtt&&CCCC
Notes:
1.
2.

3.
4.

YYMMDDHHmm - Current Date and Time
tt - type of Vapor Processor
00 = None
01 = VST ECS Processor
02 = OPW Vapor Processor
(Obsolete V28)
03 = HIRT Vapor Processor (ISD SEM required)
(V30)
04 = User Defined
(Obsolete V28)
05 = Veeder-Root Polisher
06 = Husky Polisher (ISD SEM required)
(Obsolete V30)
07 = VST Green Machine
(V30)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

635

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V41
Function Type: Set Vapor Processor Control Level
Command Format:
Display: SV4100ll
Computer: sV4100ll
Notes:
1.
2.

Version 25
Inquire:
IV4100
iV4100

PMC feature required
ll - level
00=Full Control
01=Partial Control
02=No Control

Typical Response Message, Display Format:

IV4100
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

PROCESSOR CONTROL LEVEL: FULL

Typical Response Message, Computer Format:
iV4100YYMMDDHHmmll&&CCCC
Notes:
1.
2.

3.
4.

YYMMDDHHmm - Current Date and Time
ll - level
00=Full Control
01=Partial Control
02=No Control
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

636

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V42
Function Type: Set Clear Sensor/AFM/Hose Maps

Version 25

Command Format:
Inquire:
Display: SV42SS149[AA(F1FL{M1(H1L1)}M2H2L2M3H3L3M4H4L4)
(F2FL{M1(H1L1)}M2H2L2M3H3L3M4H4L4)]
IV42SS
Computer: sV42SS149[AA(F1FL{M1(H1L1)}M2H2L2M3H3L3M4H4L4)
(F2FL{M1(H1L1)}M2H2L2M3H3L3M4H4L4)]
iV42SS
Notes:
1.
2.
3.

4.
5.
6.
7.
8.
9.
10.

11.

ISD feature required
- Brackets [],(),{} are not included, they explain the
relationship of the data
SS - index to Sensor Table [01-99]
00149 Clears all tables. This will do the following:
- Set all AFM sensors to disable. All other types of sensors
such as hydrocarbon and pressure sensors are left untouched
- Clears all AFM table entires
- Clears all Fuel grade table entries
- Removes all Hose devices and associated table entries from
system
AA - Airflow meter ID [01-99, 00=unassigned] Assigned to Grade
Table and Hose Table entries
Fn - Fuel position ID in the Grade Table [01-99, 00=unassigned]
FL - Fuel position Label used when creating the Hose Table
Entries for each Hn [00-99]
Mn - Meter n of the nth fuel grade table entry [01-06, 09-blend,
00=unassigned]
Hn - Hose ID used for hose grade table entry [01-99,
00=unassigned]
Ln - Hose Label Id used when creating the hose entry [01-10,
00=Non EVR meter]
Sensor Table - Uses SS as index into sensor table and set sensor to ENABLED
(used by ISD)
- Only valid if SS is an AFM sensor. If it is not AFM, command
will fail
AFM Table - Use SS as sensor index
- New AFM is defined with AA
- Data between [] used to build AFM table
- If one already exists, command will fail (clear all entries
with SS=0 before setting up tables)
- Fn and Hn are used to make up the hose entries in the AFM
table
- Only one hose entry is made for each unique Hn entry. So if
a hose is used more than once, it will only appear once in
the AFM table
- If Fuel Grade table entry exists with another AFM id already
defined, command will fail

Part No. 576013-635, Revision AA

637

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V42 Notes: (Continued)
12.

Hose Table - Hose table entry is made for each unique Hn
- Hoses may be used more than once. Only one Hose device is
created for each unique hose. If Hose entry already exists,
the command does NOT fail
- Ln used when creating the Hn table entry is the only Ln
assigned. Duplicate HnLn pairs are ignored if Hn is already
found in the Hose table
- FL, fuel position label is used when creating Hn table entry
- FI, fuel position id is assigned only when creating Hn table
entry

13.

Fuel Grade Table - If Fuel Grade Table entry exists for Fn, the command will
fail
- New FGT entry is created for each Fn
- Grade entry n is made for each {MnHn} combination
- If Hn Hose Table entry FI does not match Fuel Grade Table
index, command will fail (hose previously used on another
fp)
- Data between () is used to define Fuel Grade Table
- List the active meters from low to high. M1 should not be
00 while M2-M4 have values. All unused meters appear at the
end of the list for that fuel position

Typical Response Message, Display Format:

IV42SS
JUN 27, 2003 10:49 AM
Sensor /
SS AA F1
01 03 06
04 01 02
07 02 04


Airflow Meter / Hose Table / Grade Table Relationship
FL M1H1L1 M2H2L2 M3H3L3 M4H4L4 F2 L2 M1H1L1 M2H2L2 M3H3L3
05 020502 030502 100502 06UU01 07 06 020602 030602 100602
01 020102 030102 100102 000001 03 02 020202 030202 100202
03 020302 030302 100302 000001 05 04 020402 030402 100402

M4H4L4
06UU01
000001
000001

(Note: UU=unassigned)
Typical Response Message, Computer Format:
iV4200YYMMDDHHmmSSAAF1FLM1H1L1M2H2L2M3H3L3M4H4L4F2FLM1H1L1M2H2L2M3H3L3M4H4L4
...
SSAAF1FLM1H1L1M2H2L2M3H3L3M4H4L4F2FLM1H1L1M2H2L2M3H3L3M4H4L4
&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm
SS
AA
Fn
FL
Mn
Hn
Ln
&&
CCCC

-

Current Date and Time
Smart Sensor
Airflow Meter
Fuel Position Number
Fuel Position Label
Meter Number
Hose Number, UU=Unassigned
Label Id
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

638

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V43
Function Type: Set Sensor Table ISD In Use Flag
Command Format:
Display: SV4300149SSF
Computer: sV4300149SSF
Notes:
1.
2.
3.

Version 25
Inquire:
IV4300SS
iV4300SS

ISD feature required
SS - Sensor index [00=all (inquire only), 01-99]
F - In Use Flag
0=Not Used
1=Used

Typical Response Message, Display Format:

IV4300
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

SENSOR INDEX TABLE
SENSOR
01
02
03
05


TYPE
AIR FLOW METER
PRESSURE SENSOR
HYDROCARBON SENSOR
AIR FLOW METER

S/N
10220AF001
74210PS001
74210HC001
14520AF001

IN USE FLAG
YES
YES
NO
YES

Typical Response Message, Computer Format:
iV4300YYMMDDHHmmSSF..SSF&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
SS - Sensor index (Decimal)
F - In Use Flag
0=Not Used
1=Used
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

639

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V44
Function Type: Set Vapor Processor ON/OFF Pressure Thresholds
Command Format:
Display: SV4400149 -a.bcd -A.BCD
Computer: sV4400149AAAAAAAABBBBBBBB
Notes:
1.
2.
3.
4.
5.
6.
7.

Version 25
Inquire:
IV4400
iV4400

PMC (only) feature required
a.bcd - Low/off threshold, inches (or mm) H2O (ab.cd, abc.d also OK)
A.BCD - High/on threshold, inches (or mm) H2O (AB.CD, ABC.D also OK)
AAAAAAAA - Low/off threshold (ASCII Hex IEEE float)
BBBBBBBB - High/on threshold (ASCII Hex IEEE float)
English units: -8.000 <= low/off threshold < high/on threshold <= 3.000
Metric units: -203.20 <= low/off threshold < high/on threshold <= 76.20

Typical Response Message, Display Format:

IV4400
JUN 1, 2001
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

VAPOR PROCESSOR
LOW (OFF) THRESHOLD
HIGH (ON) THRESHOLD


-0.600 inches (or mm) H20
-0.200 inches (or mm) H20

Typical Response Message, Computer Format:
iV4400YYMMDDHHmmAAAAAAAABBBBBBBB&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
AAAAAAAA
BBBBBBBB
&&
CCCC

-

Current Date and Time
Vapor Pressure low threshold, (ASCII Hex IEEE float)
Vapor Pressure high threshold, (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

640

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V45 (Obsolete at V30)
Function Type: Set Vapor Processor Maximum Runtime
Command Format:
Display: SV4500MMM
Computer: sV4500MMM
Notes:
1.
2.

Version 25
Inquire:
IV4500
iV4500

PMC feature required
MMM - Runtime threshold in minutes [010-180] (Decimal)

Typical Response Message, Display Format:

IV4500
JUL 29, 1997
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

9:04 AM
1....
2....
3....
4....

VAPOR PROCESSOR
MAX RUNTIME MINUTES 113

Typical Response Message, Computer Format:
iV4500YYMMDDHHmmMMM&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
MMM
&&
CCCC

-

Current Date and Time
Runtime threshold in minutes [010-180] (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

641

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V46
Function Type: Set Hydrocarbon Alarm Threshold
Command Format:
Display: SV4600xx.xx
Computer: sV4600AAAAAAAA
Notes:
1.
2.
3.

Version 25
Inquire:
IV4600
iV4600

PMC only feature required to set new value
xx.xxx - ASCII alarm threshold
AAAAAAAA - alarm threshold (ASCII Hex IEEE float)
0.00% <= threshold <= 100.0%, Default=10%

Typical Response Message, Display Format:

IV4600
JUN 1, 2001
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

EFFLUENT EMISSIONS LIMIT 10.00 PERCENT

Typical Response Message, Computer Format:
iV4600YYMMDDHHmmAAAAAAAA&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
AAAAAAAA
&&
CCCC

-

Current Date and Time
Alarm threshold (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

642

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V47
Version 25
Function Type: Set time of day ISD/PMC tests are started and results posted
Command Format:
Display: SV4700HHMMmmm
Computer: sV4700HHMMmmm
Notes:
1.
2.

3.
4.
5.
6.

Inquire:
IV4700
iV4700

ISD or VCM or PMC features required
If the difference between post results time and start tests
time is less than the time needed to perform all tests, then
the results will be posted as soon as they become available
Default Start-of-Tests time=11:59
Default time delay minutes=1
Data being analyzed will be limited to 5 minutes before
Start-of-Tests time
HH - Hour of day tests are started [00-23] (Decimal)
MM - minute of hour tests are started [00-59] (Decimal)
mmm - time delay between time tests are started and time test
results are posted in minutes [000-720] (Decimal)

Typical Response Message, Display Format:

IV4700
JUN 1, 2002
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ASSESSMENT TIME


START TIME

11:59 PM

TIME DELAY MINUTES 1

Typical Response Message, Computer Format:
iV4700YYMMDDHHmmHHMMmmm&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
HH
MM
mmm
&&
CCCC

-

Current Date and Time
start tests hour [00-23] (Decimal)
start tests minute [00-59] (Decimal)
time delay minutes [000-720] (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

643

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V48
Function Type: Read Airflow Meter Table
Command Format:
Display: IV48SS
Computer: iV48SS
Notes:
1.
2.

Version 25
Inquire:

ISD feature required
Inquire only, use Function Code V42 to set

Typical Response Message, Display Format:

IV4800
JUN 22, 2001
STATION
STATION
STATION
STATION

3:24 PM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

AIRFLOW METER TABLE
MTR-ID INDEX F1 H1 H2 H3
01
05 01 xx 01 02
02
09 03 xx 07 08
03
11 05 xx xx xx
04
22 07 13 14 15


H4
03
09
xx
xx

F2
02
04
06
xx

H1
04
10
xx
xx

H2
05
11
xx
xx

H3
06
12
xx
xx

H4
xx
xx
xx
xx

(xx=unassigned)
Typical Response Message, Computer Format:
iV4800YYMMDDHHmmIISSF1H1H2H3H4F2H5H6H7H&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
II
SS
Fn
Hn
&&
CCCC

-

Current Date and Time
Meter ID [01-99] (use 00 for all meters) (Decimal)
index to Sensor Table [00-99] (Decimal)
fuel position ID [01-99] (Decimal)
Hose ID [01-99] (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

644

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V49
Function Type: Set Hose Label Table
Command Format:
Display: SV4900IIaaaaaaaaaa
Computer: sV4900IIaaaaaaaaaa
Notes:
1.
2.
3.

Version 25
Inquire:
IV4900
iV4900

ISD feature required
II - Hose Label ID (02-10, 01=Unassigned)
a - 10 ASCII characters [20h-7Eh]

Typical Response Message, Display Format:

IV4900
JUN 22, 2001

3:24 PM

LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4

Typical Response Message, Computer Format:
iV4900YYMMDDHHmmiiaaaaaaaaaa...
iiaaaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
ii
aaaaaaaaaa
&&
CCCC

-

Current Date and Time
Label ID (00-10) (Decimal)
10 ASCII characters [20h-7Eh]
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

645

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V4A
Function Type: Read Hose Table Data

Version 25

Command Format:
Display: IV4Aii
Computer: iV4Aii
Notes:
1.
2.

ISD feature required
Inquire only, use Function Code V42 to set

Typical Response Message, Display Format:

IV4A00
JUN 27, 2003 10:06 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ISD HOSE TABLE
HOSE
ID
01
02
03
04


FP
ID
00
01
02
03

FP
LABEL
00
01
02
03

AFM
ID
01
02
03
04

REL
ID
01
02
03
04

HOSE
LABEL
UNASSIGNED
BLEND3
REGULAR
MID GRADE

Typical Response Message, Computer Format:
iV4A00YYMMDDHHmmhhffggaall...
hhffggaall&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.

YYMMDDHHmm
hh
ff
gg
aa
ll
&&
CCCC

-

Current Date and Time
Hose ID [01-99] (Hex)
Mapped Fuel position id (Hex)
Visual Fuel Position Number [00-99] (Hex)
Air flow meter id [00-99] (Hex)
Hose Label Id (Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

646

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V4B
Function Type: Read Grade Table

Version 25

Command Format:
Display: IV4B00
Computer: iV4B00
Notes:
1.
2.

ISD feature required
Inquire only, use Function Code V42 to set

Typical Response Message, Display Format:

IV4B00
JUN 22, 2001
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:24 PM
1....
2....
3....
4....

PRODUCT/HOSE MAP TABLE FP AFID
01
01
01/01 xx/xx xx/xx
02
02
02/02 xx/xx xx/xx
03
03
03/03 xx/xx xx/xx
04
04
04/04 xx/xx xx/xx
05
05
05/05 xx/xx xx/xx
06
06
06/06 xx/xx xx/xx
07
07
xx/xx xx/xx xx/xx
08
08
xx/xx xx/xx xx/xx
09
09
xx/xx xx/xx xx/xx


M1/H1
xx/xx
xx/xx
xx/xx
xx/xx
xx/xx
xx/xx
xx/xx
xx/xx
xx/xx

M2/H2

M3/H3

M4/H4

Typical Response Message, Computer Format:
iV4B00YYMMDDHHmmffaam1h1m2h2m3h3m4h4&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.

YYMMDDHHmm
ff
aa
mx
hx
&&
CCCC

-

Current Date and Time
Real fuel position (Decimal)
Air flow meter Id (Decimal)
Meter id (x=1-4)
Hose id (x=1-4)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

647

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V4E
Function Type: Set ISD EVR TYPE
Command Format:
Display: SV4E00EEVV
Computer: sV4E00EEVV
Notes:
1.
2.
3.

Version 25
Inquire:
IV4E00EEVV
iV4E00EEVV

ISD feature required
EE - EVR Type
01=Balance
02=Vacuum Assist
VV - Vacuum Assist Type
01=Vapor Vac
02=Wayne Vac
03=Healy Vac
04=Vapor Vac ORVR

Typical Response Message, Display Format:

IV4E00
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: VAPOR VAC

Typical Response Message, Computer Format:
iV4E00YYMMDDHHmmEEVV&&CCCC
Notes:
1.
2.
3.

4.
5.

YYMMDDHHmm - Current Date and Time
EE - EVR Type
01=Balance
02=Vacuum Assist
VV - Vacuum Assist Type
01=Vapor Vac
02=Wayne Vac
03=Healy Vac
04=Vapor Vac ORVR
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

648

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V4F
Function Type: Set Nozzle Type
Command Format:
Display: SV4F00 a.bcd A.BCD
Computer: sV4F00AAAAAAAABBBBBBBB
Notes:
1.
2.
3.
4.
5.

Version 25
Inquire:
IV4F00
iV4F00

ISD feature required
a.bcd - Low Nozzle A/L Range Value, minimum Value=0.5
A.BCD - High Nozzle A/L Range Value, maximum Value=1.5
AAAAAAAA - Low Nozzle A/L Range Value (ASCII Hex IEEE float)
BBBBBBBB - High Nozzle A/L Range Value (ASCII Hex IEEE float)

Typical Response Message, Display Format:

IV4F00
JUN 1, 2002
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

NOZZLE A/L RANGE
A/L RATIO: 1.00 - 1.20

Typical Response Message, Computer Format:
iV4F00YYMMDDHHmmAAAAAAAABBBBBBBB&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
AAAAAAAA
BBBBBBBB
&&
CCCC

-

Current Date and Time
Low Nozzle A/L Range Value (ASCII Hex IEEE float)
High Nozzle A/L Range Value (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

649

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V50
Function Type: Set CVLD Minimum Pressure Time Window
Command Format:
Display: SV5000HHMMddd
Computer: sV5000HHMMddd
Notes:
1.
2.
3.
4.
5.

Version 25
Inquire:
IV5000
iV5000

ISD and PMC features required
If VST Vapor Processor, then not Balance and not Healy VAC are required
HH - window start hour of day, Default=02, [00-23] (Decimal)
MM - window start minute of hour, Default=00, [00-59] (Decimal)
ddd - window duration in minutes, Default=120, [000-720] (Decimal)

Typical Response Message, Display Format:

IV5000
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

CVLD MINIMUM PRESSURE TIME WINDOW
START TIME: 2:00 AM
DURATION: 120 MINUTES

Typical Response Message, Computer Format:
iV5000YYMMDDHHmmHHMMddd&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
HH
MM
ddd
&&
CCCC

-

Current Date and Time
window start hour of day [00-23] (Decimal)
window start minute of hour [00-59] (Decimal)
window duration in minutes [000-720] (Decimal)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

650

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V51
Function Type: Perform ISD Setup Verification Test

Version 25

Command Format:
Display: IV5100
Computer: iV5100
Notes:
1.
2.

ISD and/or PMC features required
Inquire only

Typical Response Message, Display Format:

IV5100
JAN 1, 1996 11:05 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ISD/PMC TEST STATUS: PASS

Typical Response Message, Computer Format:
iV5100YYMMDDhhmmS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDhhmm - Current Date and Time
S - Status of ISD/PMC Setup Test
0=Pass
1=Fail
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

651

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V52
Function Type: Accept High ORVR Configuration
Command Format:
Display: SV5200F
Computer: sV5200F
Notes:
1.
2.

Version 25
Inquire:
IV5200
iV5200

ISD and/or PMC features required
F - Enable/Disable Flag
0=Enable
1=Disable

Typical Response Message, Display Format:

IV5200
JAN 1, 1996 11:05 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

ACCEPT HIGH ORVR: YES

Typical Response Message, Computer Format:
iV5200YYMMDDhhmmF&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDhhmm - Current Date and Time.
F - Enable/Disable Flag
0=Enable
1=Disable
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

652

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
7.7.3 ISD DIAGNOSTIC REPORTS
Function Code: V80
Function Type: Vapor Processor Report

Version 25

Command Format:
Display: SV8000149
Computer: sV8000149

Inquire:
IV8000
iV8000

Notes:
1.
2.
3.

Set command clear buffer
PMC Feature and Full Vapor Processor Control required
149 - This verification code must be sent to confirm the command

Typical Response Message, Display Format:
When VST Polisher selected:

IV8000
JUL 29, 1997 9:04 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

VAPOR PROCESSOR
DATE-TIME ON
12-26-01 10:51 AM
12-27-01 11:01 PM


ELAPSED
MINUTES
xxx.xx
xxx.xx

PRESSURE INCHES H2O
ON
OFF
-x.xxx
-x.xxx
-x.xxx
-x.xxx

RUNTIME
FAULT
NO
YES

When Veeder-Root Polisher selected:

IV8000
JUL 29, 2006 9:04 AM
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

VAPOR POLISHER
VALVE EVENT
DATE-TIME
10-20-07 11:16AM


PRESSURE
"WC
-0.300

Part No. 576013-635, Revision AA

EVENT CODE
OPEN PURGE

653

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V80 Notes: (Continued)
Typical Response Message, Computer Format:
iV8000YYMMDDHHmmnnnnTTTTTTTTiiaaaaaaaabbbbbbbbcccccccc...
TTTTTTTTiiaaaaaaaabbbbbbbbccccccccS&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
nnnn - number of Vapor Processor cycles (Decimal,0-20)
3.
TTTTTTTT - On time, unsigned long ascii-hex seconds since 1/1/1970
(Valve Event On or Off Time for V-R Polisher)
4.
ii - number of floating point fields per cycle (decimal)
5.
aaaaaaaa - elapsed time (ASCII Hex IEEE float)
(Event Type Code for V-R Polisher)
9D = No Event
F7 = Close Cold Start
F8 = Close Timer
F9 = Close Test
FA = Close No Load
FB = Close Force Purge
FC = Close No Purge
FD = Close HC Limit
FE = Close Full
FF = Close Near Full
00 = Close Empty
01 = Open Purge
02 = Open Excess Purge
03 = Open Fill
04 = Open Test
05 = Open Timer
6.
bbbbbbbb - on pressure in inches(or mm) of H20 (ASCII Hex IEEE float)
(pressure at event time for V-R Polisher)
7.
cccccccc - off pressure in inches(or mm) of H2O (ASCII Hex IEEE float)
(0 for V-R Polisher)
8.
S - 0=no runtime fault, 1=runtime fault (decimal)
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

654

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V81
Function Type: Percent Hydrocarbon Report
Command Format:
Display: SV8100149
Computer: sV8100149
Notes:
1.
2.

Version 25
Inquire:
IV8100
iV8100

PMC Feature and Full Vapor Processor Control Required
Set command clears buffer

Typical Response Message, Display Format:

IV8100
JUL 29, 1997
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

9:04 AM
1....
2....
3....
4....

HYDROCARBON SENSOR DIAGNOSTIC
DATE/TIME
READING %
12-26-01 10:51:15 AM
5.101
12-26-01 10:51:30 AM
5.102
12-26-01 10:51:45 PM
5.103
12-26-01 10:52:00 AM
5.104

Typical Response Message, Computer Format:
iV8100YYMMDDHHmmnnnnTTTTTTTTaaaaaaaa&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
nnnn
TTTTTTTT
aaaaaaaa
&&
CCCC

-

Current Date and Time
number of HC samples [00-20] (Decimal)
sample time (Seconds since 1/1/1970, Hex)
percent (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

655

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V82
Function Type: Vapor Processor Status Report

Version 30

Command Format:
Display: IV8200
Computer: iV8200
Typical Response Message, Display Format:

IV8200
JUL 13, 2009
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

9:04 AM
1....
2....
3....
4....

VAPOR PROCESSOR STATUS REPORT
PMC VERSION: 01.03
VAPOR PROCESSSOR TYPE: VST ECS PROCESSOR
PMC MONITORING TEST PASS/FAIL THRESHOLDS
PERIOD
1DAYS
1DAYS

VAPOR PROCESSOR MASS EMISSION FAIL
VAPOR PROCESSOR DUTY CYCLE FAIL
EFFLUENT EMISSIONS TEST: PASS
VP DUTY CYCLE TEST
: NOTEST
VP INPUT STATUS
: NOTEST
RUN TIME HOURS :
DAILY THROUGHPUT:
AVG HC PERCENT :


BELOW
-------

ABOVE
0.64 LBS/1KG
75.00 %

(0.00 LBS/1KG)

-1.0
-1 GALS
0.00 %

Typical Response Message, Computer Format:
iV8200YYMMDDHHmmSSSSSSSS
nnaabbccddeeNNffffffffgggggggghhhhhhhhiiiiiiii
jjjjjjjjkkkkkkkk&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.

YYMMDDHHmm - Time and Date stamp of report
SSSSSSSS - Timestamp of CVPM test (Hex, seconds since 1/1/1970
00:00:00)
nn - Number of 2-byte ASCII hex values to follow
aa - VP overpress test status (decimal)
bb - Emission test status (decimal)
cc - Maximum runtime test status (decimal)
dd - Autonomous vapor processor test status (decimal)
ee - Vapor processor test status (decimal)
NN - Number of 8-byte ASCII hex
values to follow
ffffffff - Ullage pressure of the 95 th percentile (ASCII hex float)
gggggggg - Emission value LB/lKG (ASCII hex float)
hhhhhhhh - Duty Cycle % (ASCII hex float)
iiiiiiii - Runtime, hours (ASCII hex float)
jjjjjjjj - Daily Throughput (ASCII hex float)
kkkkkkkk - Average HC % (ASCII hex float)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

656

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V83
Function Type: Read Sensor Calibration History

Version 25

Command Format:
Display: IV8300CCNNIII
Computer: iV8300CCNNIII
Notes:
1.

CC - Sensor Category
00=All
01=Smart Sensors
02=MODBus Sensors
03=Serial Sensors
NN - Sensor Number (Decimal, 00=all)
III - Requested number of records per category [001-255] (Decimal)

2.
3.

Typical Response Message, Display Format:

IV8300
JUN 1, 2001
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

SMART SENSOR CALIBRATION HISTORY
DATE
NUMBER TYPE
12-26-01 10:59
01
AIR FLOW
12-15-01 12:59
01
AIR FLOW
12-15-01 12:59
02
PRESSURE

S/N
123
123
1231231230

MODBUS SENSOR CALIBRATION HISTORY
DATE
NUMBER TYPE
S/N
12-15-01 12:59
01
HYDROCARBON 123

LABEL
AFM 2
AFM 2
PRESSURE10

SLOPE
5.023
5.023
1.104

OFFSET
5.000
5.000
0.033

P/F
P
F
P

LABEL
SLOPE
HC SENSOR1 5.023

OFFSET
5.000

P/F
P

SERIAL SENSOR CALIBRATION HISTORY
NONE

Typical Response Message, Computer Format:
iV8300YYMMDDHHmmCCNNIIIYYMMDDHHmmSSSSSSSSOOOOOOOOR&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

YYMMDDHHmm
CC
NN
III
YYMMDDHHmm
SSSSSSSS
OOOOOOOO
R

-

Current Date and Time
Sensor Category
Sensor number
Record number
Calibration Date and Time
Slope Value (ASCII Hex IEEE float)
Offset Value (ASCII Hex IEEE float)
Test result
0=fail
1=pass
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

657

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V85
Function Type: ISD Service Report Test Fail Clear
Command Format:
Display: SV8500149TTFFHH
Computer: sV8500149TTFFHH
Notes:
1.
2.

3.
4.

Version 25
Inquire:
IV8500
iV8500

ISD feature required
TT - Test Type
01=Containment
02=CVLD
03=Vapor Processor
04=Sensor Out
05=Setup
06=Collection
FF - fuel position label (used only for collection test, Decimal)
HH - hose id (used only for collection test, Decimal)
a) FF=00, HH=00:
All FP's and hoses are cleared.
b) FF=FP Label, HH=00:
All hoses for the FP are
cleared.
c) FF=FP Label, HH=Hose Id: The selected hose is cleared.

Typical Response Message, Display Format:

IV8500
JUN 1, 2002
STATION
STATION
STATION
STATION

8:07 AM

HEADER
HEADER
HEADER
HEADER

1....
2....
3....
4....

CONTAINMENT TESTS (GROSS AND DEGRADATION):
CONTINUOUS VAPOR LEAK DETECTION TEST
:
VAPOR PROCESSOR TESTS
:
SENSOR OUT TEST
:
SETUP TEST
:
COLLECTION TESTS
FP
HOSE-DATE
01
REG-02/15/03
02
REG-03/12/03
03
SUPER-04/31/03


Part No. 576013-635, Revision AA

HOSE-DATE
PLUS-02/15/03
REG-02/15/03

02/15/03
02/15/03
02/15/03
02/15/03
02/15/03
HOSE-DATE
SUPER-02/15/03
SUPER-02/15/03

HOSE-DATE
SUPER+-02/15/03

658

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code V85 Notes: (Continued)
Typical Response Message, Computer Format:
iV8500YYMMDDHHmmYYMMDDYYMMDDYYMMDDYYMMDDYYMMDDFFHHYYMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

YYMMDDHHmm
YYMMDD
YYMMDD
YYMMDD
YYMMDD
YYMMDD
FF
HH
YYMMDD

-

Current Date and Time
Containment Tests (Gross & Degradation) Date and Time
CVLD Date and Time
Vapor Processor Date and Time
Sensor Out Date and Time
Setup Date and Time
Fuel Position (Decimal) (Collection)
Hose number (Decimal) (Collection)
Time/Date stamp of the test clear time for the Collection
tests on the fuel position and hose
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

659

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: V88
Function Type: PMC Daily Vapor Polisher Diagnostic

Version 30

Command Format:
Display: IV8500yyyymmddnnnn
Computer: iV8500yyyymmddnnnn
Typical Response Message, Display Format:

IV8800
JUN 7, 2009

3:48 PM

PMC DAILY VAPOR POLISHER DIAGNOSTIC
DATE/TIME
09-07-05 23:59:00
09-07-06 23:59:00


LOAD
HRS
4.9
1.9

PRGE
HRS
18.6
11.9

MIN%
LOAD
2
0

MAX%
LOAD
29
10

SELF
TEST
NOTEST
------

PRESS
TEST
PASS
-----

Typical Response Message, Computer Format:
iV8800YYMMDDHHmmnnnniiiissssssssLLLLLLLLPPPPPPPP
mmmmmmmmMMMMMMMMVSSOO&&CCCC
Notes:
1. YYMMDDHHmm - Current Date and Time
2.
nnnn - Number of records (Decimal)
3.
iiii - Record mumber (Decimal)
4.
ssssssss - Seconds since 1/1/1970 (Decimal)
5.
LLLLLLLL - Load Hours (ASCII Hex IEEE float)
6.
PPPPPPPP - Purge Hours (ASCII Hex IEEE float)
7.
mmmmmmmm - Min Load Percent (ASCII Hex IEEE float)
8.
MMMMMMMM - Max Load Percent (ASCII Hex IEEE float)
9.
V - Valid flag for next 3 fields (ASCII Hex IEEE float)
0 = Not Valid
1 = Valid
10.
SS - Self Test (Decimal)
00 = NO TEST
01 = WARN
02 = FAIL
03 = PASS
11.
OO - Overpressure Test
00 = NO TEST
01 = WARN
02 = FAIL
03 = PASS
12.
&& - Data Termination Flag
13.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

660

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA1
Function Type: VMC A/L Daily Records Report

Version 31

Command Format:
Display: IVA1ffYYYYMMDDHHMMyyyymmddhhmm
Computer: iVA1ffYYYYMMDDHHMMyyyymmddhhmm
Notes:
1.
2.
3.

ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
YYYYMMDDHHMM - Start Time Stamp (Optional)
yyyymmddhhmm - End Time Stamp (Optional)

Typical Response Message, Display Format:

IVA1xx
JUN 7, 2010

3:48 PM

A/L Daily Report @23:59 - VMC:001502 Side:2
Avg
No of
Test
Date
Time
A/L
Trans.
Status
2010.07.05 23:59:00
041.3
0028
WARN
2010.07.06 23:59:00
211.0
0045
IDLE


FP:03

Typical Response Message, Computer Format:
iVA1ffYYMMDDHHmmIIIIIIsffYYMMDDHHmmssFFFFS…
YYMMDDHHmmssFFFFS&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
IIIIII - Serial Number (Decimal)
3.
s - Side (1=A, 2=B) (ASCII Hex)
4.
ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
5. YYYYMMDDHHmmss - Timestamp of data record
6.
FFFF - Average A/L (ASCII decimal, x10)
7.
TTTT - Number of Transactions
8.
S - Status (ASCII Hex)
0=Roots meter not connected
1=Idle
2=Running
3=Last Transaction Failed
4=FP Shutdown Warning
5=FP Shutdown Alarm
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

661

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA2
Function Type: VMC A/L Exception Report

Version 31

Command Format:
Display: IVA2ffYYYYMMDDHHMMyyyymmddhhmm
Computer: iVA2ffYYYYMMDDHHMMyyyymmddhhmm
Notes:
1.
2.
3.

ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
YYYYMMDDHHMM - Start Time Stamp (Optional)
yyyymmddhhmm - End Time Stamp (Optional)

Typical Response Message, Display Format:

IVA2xx
JUN 7, 2010

3:48 PM

A/L Exception Report - VMC: 010472 Side: 1 FP: 01
Error
Fueling Recovery
Date
Time
Counter Counter
Rate
Duration
2010.07.05 23:59:00
00254
09385
147.8
00027


Status
WARN

Vapor
Rate
26.43

Fuel
Rate
17.88

Typical Response Message, Computer Format:
iVA2ffYYMMDDHHmmIIIIIIsffYYMMDDHHmmsseeeeffffrrrrttttSVVVVFFFF…
YYMMDDHHmmsseeeeffffrrrrttttSVVVVFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
IIIIII - Serial Number (Decimal)
3.
s - Side (1=A, 2=B) (ASCII Hex)
4.
ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
5. YYYYMMDDHHmmss - Timestamp of data record
6.
eeee - Error Counter (ASCII Hex)
7.
ffff - Fueling Counter (ASCII Hex)
8.
rrrr - Recover Rate (ASCII decimal, x10)
9.
tttt - Reamaining Time, minutes (ASCII Hex)
10.
S - Status Code
0=No meter
3=Not Pass
4=Warning (VMC Alarm)
5=Fail
(VMC Stop)
11.
VVVV - Vapor Rate (ASCII Decimal, x100)
12.
FFFF - Fuel Rate (ASCII Decimal, x100)
13.
&& - Data Termination Flag
14.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

662

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA3
Function Type: VMC A/L Transaction Report

Version 31

Command Format:
Display: IVA3ffYYYYMMDDHHMMyyyymmddhhmm
Computer: iVA3ffYYYYMMDDHHMMyyyymmddhhmm
Notes:
1.
2.
3.

ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
YYYYMMDDHHMM - Start Time Stamp (Optional)
yyyymmddhhmm - End Time Stamp (Optional)

Typical Response Message, Display Format:

IVA3xx
JUN 7, 2010

3:48 PM

A/L Transaction Report - VMC: 001499 Side: 2 FP: 07
Error
Fueling Recovery
Date
Time
Counter Counter
Rate
Duration
2011.02.10 16:06:18
00001
00015
999.9
00028
2011.02.10 17:00:28
00000
00018
086.9
00074


Status
NOTPASS
IDLE

Vapor
Rate
33.61
29.95

Fuel
Rate
00.00
34.45

Typical Response Message, Computer Format:
iVA3ffYYMMDDHHmmIIIIIIsffYYMMDDHHmmsseeeeffffrrrrttttSVVVVFFFF…
YYMMDDHHmmsseeeeffffrrrrttttSVVVVFFFF&&CCCC
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
IIIIII - Serial Number (Decimal)
3.
s - Side (1=A, 2=B) (ASCII Hex)
4.
ff - Fuel Position Number (Decimal, 01-99, 00=Not Allowed)
5. YYYYMMDDHHmmss - Timestamp of data record
6.
eeee - Error Counter (ASCII Hex)
7.
ffff - Fueling Counter (ASCII Hex)
8.
rrrr - Recover Rate (ASCII decimal, x10)
9.
tttt - Remaining Time, minutes (ASCII Hex)
10.
S - Status Code
0=No meter
3=Not Pass
4=Warning (VMC Alarm)
5=Fail (VMC Stop)
11.
VVVV - Vapor Rate (ASCII decimal, x10)
12.
FFFF - Fuel Rate (ASCII decimal, x10)
13.
&& - Data Termination Flag
14.
CCCC - Message Checksum

Part No. 576013-635, Revision AA

663

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA4
Function Type: Perform APM Setup Verification Test

Version 31

Command Format:
Display: IVA400
Computer: iVA400
Notes:
1.APM feature required
Typical Response Message, Display Format:

IVA400
JUN 7, 2010

3:48 PM

APM SETUP TEST STATUS: PASS

Typical Response Message, Computer Format:
iVA400YYMMDDHHmmS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
S - Status of APM Setup Test
0=Pass
1=Fail
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

664

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA5
Function Type: VMCI Sub Alarm History Report

Version 31

Command Format:
Display: IVA500
Computer: iVA500
Typical Response Message, Display Format:

IVA500
JUN 7, 2010

3:48 PM

VMCI SUB ALARM HISTORY
ID
ALARM
X 1: VMC COMM
X 1: VMC COMM
X 1: VMC COMM
X 1: VMC COMM


TIMEOUT
TIMEOUT
TIMEOUT
TIMEOUT

ID
x 1:
x 2:
x 2:
x 1:

SUB
VMC
VMC
VMC
VMC

ALARM
COMM TIMEOUT
COMM TIMEOUT
COMM TIMEOUT
COMM TIMEOUT

STATE
CLEAR
CLEAR
ALARM
ALARM

DATE
6-11-10
6-11-10
6-11-10
6-11-10

TIME
12:57PM
12:34PM
12:27PM
12:17PM

Typical Response Message, Computer Format:
iVA500YYMMDDHHmmnnXXNNxxSSAAYYMMDDHHmm...
XXNNxxSSAAYYMMDDHHmm&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
nn
XX
NN

-

5.
6.

xx SS -

7.

AA -

8.
9.
10.

YYMMDDHHmm && CCCC -

Current Date and Time
Number of Sub Alarm records to follow (Hex)
VMCI Sensor Number (Hex)
Alarm Type Number
03 = VMC Comm Timeout
VMC Sensor Number (Hex)
Sub Alarm Type Number
If NN is 03 and SS is:
03 = VMC Comm Timeout
Alarm State
00 = Alarm Cleared
01 = Alarm Occurred
Date and Time Alarm state occurred
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

665

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA6
Function Type: APM Diagnostic Report

Version 31

Command Format:
Display: IVA600
Computer: iVA600
Typical Response Message, Display Format:

IVA600
JUN 7, 2010

3:48 PM

APM DIAGNOSTIC
--------------------VAPOR PRESSURE
-10.0 IWC

Typical Response Message, Computer Format:
iVA600YYMMDDHHmmNNFFFFFFFFYYMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm
NN
FFFFFFFF
&&
CCCC

-

Current Date and Time
Number of eight character data fields to follow (Hex)
Vapor Pressure, IWC (ASCII Hex IEEE float)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

666

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA7
Function Type: APM Service Report Test Fail Clear
Command Format:
Display: SVA700149TT
Computer: sVA700149TT

Version 31
Inquire:
IVA700
iVA700

Notes:
1.APM feature required
2.
TT - Test Type
01 = APM Tests
02 = APM Sensor Self Test
03 = APM Setup Self Test
Typical Response Message, Display Format:

IVA700
JUN 7, 2010

3:48 PM

APM TESTS
APM SENSOR SELF TEST
APM SETUP SELF TEST


: 04/30/10
: 04/29/10
: 04/27/10

Typical Response Message, Computer Format:
iVA700YYMMDDHHmmYYMMDDYYMMDDYYMMDD&&CCCC
Notes:
1.
2.
3.
4.
5.
6.

YYMMDDHHmm
YYMMDD
YYMMDD
YYMMDD
&&
CCCC

-

Current Date and Time
APM Test Date and Time
APM Sensor Self Test Date and Time
APM Setup Self Test Date and Time
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

667

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VA8
Function Type: APM Miscellaneous Events Report

Version 31

Command Format:
Display: IVA800YYYYMMDDyyyymmddnnnn
Computer: iVA800YYYYMMDDyyyymmddnnnn
Notes:
1.
2.
3.

YYYYMMDD - Start Date stamp (optional)
yyyymmdd - End Date stamp (optional)
nnnn - Limit number of records (optional)

Typical Response Message, Display Format:

IVA800
APR 16, 2010
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

3:11 PM
1
2
3
4

AUTOMATIC PRESSURE MONITORING MISCELLANEOUS EVENTS REPORT
DATE
10-04-30
10-04-30
10-04-29
10-04-29
10-04-29
10-04-29
10-04-27
10-04-02
10-04-02
10-04-02
10-04-01


TIME
11:36:26
08:00:00
11:59:00
11:59:00
11:36:26
09:13:01
11:37:21
15:12:00
11:36:26
11:36:26
11:36:26

DESCRIPTION
APM TEST
PUMPS MANUALLY ENABLED
APM GROSS OVER-PRESSURE
APM SENSOR
APM DEGRD OVER-PRESSURE
APM SENSOR SELF TEST
APM SETUP SELF TEST
TIME CHANGE DETECTED AT
APM STARTUP
APM SHUTDOWN
APM STARTUP

Part No. 576013-635, Revision AA

ACTION/NAME
TEST MANUALLY CLEARED
DISABLED DISPENSERS
DISABLED DISPENSERS
DISABLED DISPENSERS
TEST MANUALLY CLEARED
TEST MANUALLY CLEARED
10-06-01 15:02:00

668

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code VA8 Notes: (Continued)
Typical Response Message, Computer Format:
iVA800YYMMDDHHmmssssSSSSSSSSaabbccddeettff...f...&&CCCC
Notes:
1.
2.
3.
4.

5.

6.
7.
8.
9.

10.
11.
12.
13.

YYMMDDHHmm - Current Date and Time
ssss - Number of ISD Shutdown & Misc. Events to follow (Decimal)
SSSSSSSS - Timestamp of the Shutdown/Misc. Event (seconds since
1/1/1970, Hex)
aa - Primary Misc. Event Category
01=System Event
02=Pumps Re-enabled
03=Test Manually Cleared
04=Disabled Dispensers
bb - Primary Misc. Event Type
If aa=01:
01=APM Startup at:
02=APM Shutdown at:
03=Time Change Detected at:
If aa=03:
01=APM Setup Self Tests
03=APM Tests
06=APM Sensor Self Tests:
If aa=04:
05=APM Gross Over-Pressure Test
06=APM Degradation Over-Pressure Test
07=APM Sensor Test
cc - Hose Number (Hex) (future use)
dd - Secondary Misc. Event Category (Hex) (future use)
ee - Secondary Misc. Event Type (Hex) (future use)
tt - Data Type to follow
00=No Data
01=Integer
02=Floating Point Number
ff - Data Type (optional, depends on tt)
ffffffff - Data Type (optional, depends on tt, Hex)
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

669

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VC0
Function Type: Automatic/Manual Vapor Processor Control
Command Format:
Display: SVC000149C
Computer: sVC000149C
Notes:
1.
2.
off
3.

Version 25
Inquire:
IVC000
iVC000

PMC Feature and Vapor Processor relay required
Changing from automatic to manual while VP is on turns VP (and HC sensor)
C - Control
0=Set VP to Manual
1=Set VP to Automatic

Typical Response Message, Display Format:

IVC000
JUN 1, 2001
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

VAPOR PROCESSOR AUTOMATIC CONTROL

Typical Response Message, Computer Format:
iVC000YYMMDDHHmmC&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
n - Control
0=VP is set to Manual
1=VP is set to Automatic
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

670

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VC1
Function Type: Manual Override of Vapor Processor
Command Format:
Display: SVC100149C
Computer: sVC100149C
Notes:
1.
2.
3.

Version 25
Inquire:
IVC100
iVC100

PMC Feature and Vapor Processor relay required
VP control MUST be Manual (see VC0 command)
C - Control
0=Turn VP off
1=Turn VP on

Typical Response Message, Display Format:

IVC100
JUN 1, 2001
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

VAPOR PROCESSOR ON

Typical Response Message, Computer Format:
iVC100YYMMDDHHmmC&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
C - Control
0=VP is off
1=VP is on
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

671

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VC5
Function Type: Acknowledge ISD Alarm to Re-Enable Site
Command Format:
Display: SVC500149
Computer: sVC500149
Notes:
1.
2.

Version 25
Inquire:
IVC500
iVC500

ISD feature required
Set command acknowledges alarm

Typical Response Message, Display Format:

IVC500
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

ISD SHUTDOWN ALARMS OVERRIDDEN: YES

Typical Response Message, Computer Format:
iVC500YYMMDDHHmmS&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm - Current Date and Time
S - ISD shutdown alarms overridden
0=Yes
1=No
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

672

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: VC8
Function Type: Set Manual Override of Veeder-Root Polisher
Command Format:
Display: SVC800149R
Computer: sVC800149R
Notes:
1.
2.
3.
4.

VP Control Must
Vapor Processor
149 R -

Version 29
Inquire:
IVC800
iVC800

be Manual (see VC0 Command)
Type must be Veeder-Root Polisher
This verification code must be sent to confirm the command
Request Vapor Valve Position
0 = Closed
1 = Open

Typical Response Message, Display Format:

IVC800
JUN 1, 2002
STATION
STATION
STATION
STATION

HEADER
HEADER
HEADER
HEADER

8:07 AM
1....
2....
3....
4....

VAPOR VALVE POSITION


CURRENT
CLOSED

REQUESTED
OPEN

Typical Response Message, Computer Format:
iVC800YYMMDDHHmmCR&&CCCC
Notes:
1.
2.
3.
4.
5.

YYMMDDHHmm - Current Date and Time
C - Current Vapor Valve Position
0 = Closed
1 = Open
R - requested Vapor Valve Position
0 = Closed
1 = Open
&& - Data Termination Flag
CCCC - Message Checksum

Part No. 576013-635, Revision AA

673

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
Function Code: XE0
Function Type: ISD Setup Data Time Stamp EEPROM
Command Format:
Display: SXE000ssssssss
Computer: sXE000ssssssss

Version 25
Inquire:
IXE000
iXE000

Typical Response Message, Display Format:
Notes:
1. Response is the same as computer format.

To be used with EEPROM only

Typical Response Message, Computer Format:
iXE000YYMMDDHHmmssssssss&&CCCC
Notes:
1.
2.
3.
4.

YYMMDDHHmm
ssssssss
&&
CCCC

-

Current Date and Time
ISD Setup Data Time Stamp (Seconds since 1/1/1970, Hex)
Data Termination Flag
Message Checksum

Part No. 576013-635, Revision AA

674

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

8.0 IFSF DATABASE SUPPORT
When equipped with the appropriate software and interface module, these systems can
respond to commands using the International Forecourt Standards Forum (IFSF) tank
gauge communications protocols as defined in the following tables. Please see the IFSF
documents "PART II, COMMUNICATION SPECIFICATION" and "PART III.3 TANK LEVEL
GAUGE APPLICATION" for further details.

8.1 TANK LEVEL GAUGE DATABASE
TANK LEVEL GAUGE DATABASE
DB_Ad=TLG_DAT (01H)
Data_Id Data Element Name
CONFIGURATION DATA
1
Nb_Tanks
2
Reference_Temp
3
TLG_Measurement_Units
6
Country_Code
7
Maint_Password
50
TLG_Manufacturer_Id
51
TLG_Model
52
TLG_Type
53
TLG_Serial_Nb
54
TLG_Appl_Software_Ver
58
IFSF_Protocol_Ver
59
Current_Date
60
Current_Time
61
SW_Checksum
TLG COMMAND
Enter_Maint_Mode
70
71

Exit_Maint_Mode

Part No. 576013-635, Revision AA

M/O

Supported

M
O
O
M
M
M
M
M
M
M
M
O
O
M

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

M

Yes

M

Yes

675

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
8.2 TANK LEVEL GAUGE ERROR CODE DATABASE
TANK LEVEL GAUGE ERROR CODE DATABASE
DB_Ad=TLG_DAT (01H) + TLG_ER_DAT (41H) + TLG_ER_ID (01H-40H)
Data_Id Data Element Name

M/O

Supported

ERROR DATA
1
TLG_Error_Type
2
TLG_Err_Description
3
TLG_Error_Total
4
TLG_Error_Total_Erase_Date

M
O
M
O

Yes
Yes
Yes
Yes

UNSOLICITED DATA
100
TLG_Error_Type_Mes

M

Yes

M/O

Supported

M
M
M
M
M
O
O
O
O
O
O
O
O
O
O
O

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
No
No

8.3 TANK PROBE DATABASE
TANK PROBE DATABASE
DB_Ad=TP_ID (21H-3FH)
Data_Id Data Element Name
CONFIGURATION
1
TP_Manufacturer_Id
2
TP_Type
3
TP_Serial_Nb
4
TP_Model
5
TP_Appl_Software_Ver
6
Prod_Nb
7
Prod_Description
8
Prod_Group_Code
9
Ref_Density
10
Tank_Diameter
11
Shell_Capacity
12
Max_Safe_Fill_Capacity
13
Low_Capacity
14
Min_Operating_Capacity
15
HiHi_Level_Setpoint
16
Hi_Level_Setpoint
Part No. 576013-635, Revision AA

676

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
TANK PROBE DATABASE
DB_Ad=TP_ID (21H-3FH)
Data_Id Data Element Name

M/O

Supported

17
18

Lo_Level_Setpoint
LoLo_Level_Setpoint

O
O

No
No

19
20
21
22
23

Hi_Water_Setpoint
Water_Detection_Thresh
Tank_Tilt_Offset
Tank_Manifold_Partners
TP_Measurement_Units

O
O
O
O
O

Yes
Yes
Yes
Yes
Yes

CONTROL DATA
32
TP_Status
33
TP_Alarm

M
M

Yes
Yes

TANK READING
64
Product_Level
65
Total_Observed_Volume
66
Gross_Standard_Volume
67
Average_Temp
68
Water_Level
69
Observed_Density
70
Last_Reading_Date
71
Last_Reading_Time

M
O
O
O
M
O
O
O

Yes
Yes
Yes
Yes
Yes
No
Yes
Yes

UNSOLICITED
100 TP_Status_Message

M

Yes

Part No. 576013-635, Revision AA

677

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
8.4 TANK CONTENTS TABLE DATABASE
TANK CONTENTS TABLE DATABASE
DB_Ad=TP_ID (21H-3FH) + CAL_DAT (21H) + ENTRY (01H-FFH)
Data_Id Data Element Name
CONFIGURATION
1
Strap_Level
2
Strap_Vol

M/O

Supported

O
O

No
No

8.5 TANK TEMPERATURE TABLE DATABASE
TANK TEMPERATURE TABLE DATABASE
DB_Ad=TP_ID (21H-3FH) + TEMP_DAT (22H) + TEMP_ADDR (01H-08H)
Data_Id Data Element Name
CONFIGURATION
1
Temp_height
2
Temp_value

M/O

Supported

O
O

Yes
Yes

8.6 TANK PROBE ERROR CODE DATABASE
TANK PROBE ERROR CODE DATABASE
DB_Ad=TP_ID (21H-3FH) + TP_ER_DAT (41H) + TP_ER_ID (01H-40H)
Data_Id Data Element Name

M/O

Supported

ERROR DATA
1
TP_Error_Type
2
TP_Err_Description
3
TP_Error_Total
4
TP_Error_Total_Erase_Date
5
TP_Error_Status

M
O
M
O
M

Yes
Yes
Yes
Yes
Yes

UNSOLICITED DATA
100
TP_Error_Type_Mes

M

Yes

Part No. 576013-635, Revision AA

678

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
8.7 DATA DOWNLOAD DATABASE
DATA DOWNLOAD DATABASE
DB_Ad=SW_DAT (81H)
Data_Id Data Element Name

M/O

Supported

CONFIGURATION DATA
1
Data_Type
2
Software_Block_Id
3
Start_Addr
4
Nb_Bytes
5
Data_Download
6
Data_Checksum

O
O
O
O
O
O

No
No
No
No
No
No

COMMAND
10
Activate_Software
11
Restart

O
O

No
No

8.8 COMMUNICATION SERVICE DATABASE
COMMUNICATION SERVICE DATABASE
DB_Ad=00H
Data_Id Variable Name

Supported

CONFIGURATION
1
Communication_Protocol_Ver (read only)
2
Local_Node_Address
3
Recipient_Addr_Table
4
Heartbeat_Interval
5
Max_Block_Length

Yes
Yes
Yes
Yes
Yes

COMMANDS
10
Heartbeat_Error
11
Add_Recipient_Addr
12
Remove_Recipient_Addr

Yes
Yes
Yes

Part No. 576013-635, Revision AA

679

Serial Interface Manual
TLS-300/350/350R Monitoring Systems

9.0 FUNCTION CODE SUMMARY
CONTROL FUNCTIONS (7.1)
Code Ver
001
1
002
1
003
1

Function
System Reset
Clear Power Reset Flag
Remote Alarm Reset

010

14

Cancel Autodial Computer Mode Session

031

10

Confirm Clear Function

051
052
053

1
1
1

Clear In-Tank Delivery Reports
Start In-Tank Leak Detect Test
Stop In-Tank Leak Detect Test

054

5

Delete CSLD Rate Table

081
082

7
7

Start Pressure Line Leak Test (3.00 GPH only in V18)
Stop Pressure Line Leak Test

083
084

10
10

Start WPLLD Line Leak Test (3.00 GPH only in V18)
Stop WPLLD Line Leak Test

087
088

18
18

Start Pressure Line Leak Test by Type
Start WPLLD Line Leak Test by Type

089
090

19
19

Pressure Line Leak Pressure Offset Reset
WPLLD Line Leak Pressure Offset Reset

091

15

Close Current Shift

092
093
094

23
23
23

Start Pressure Line Leak Profile Line Test
Stop Pressure Line Leak Profile Line Test
Recalculate Pressure Line Leak Profile Bulk Modulus

095
096
097
098

24
24
24
24

Start Vacuum Sensor Manual Test
Stop Vacuum Sensor Manual Evacuation Test
Start Vacuum Sensor Evacuation Hold
Stop Vacuum Sensor Evacuation Hold

099
09A
09B

26
26
26

Start Mag Sump Leak Test
Start Mag Sump Leak Test Measuring Height Phase
Stop Mag Sump Leak Test

Part No. 576013-635, Revision AA

680

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
OPERATIONAL REPORTS (7.2)
SYSTEM REPORTS (7.2.1)
Code Ver
101
1
102
1

Function
System Status Report
System Configuration Report

111
112
113
114
115

2
2
14
19
27

Priority Alarm History Report
Non-Priority Alarm History Report
Active Alarm Report
Cleared Alarm Report
Maintenance Tracker Unacknowledged Alarm Report

116
119
11A
11B

19
27
27
28

Service Report History (Obsolete V27)
Maintenance History Report
Service Report History
Service Notice Session Report

132

32

Fiscal Height Security Report

IN-TANK REPORTS (7.2.2)
Code Ver
201
1
202
1
203
1
204
1
205
1
206
1
207
2
208
2

Function
In-Tank Inventory Report
In-Tank Delivery Report
In-Tank Leak Detect Report
In-Tank Shift Inventory Report
In-Tank Status Report
In-Tank Alarm History Report
In-Tank Leak Test History Report
In-Tank Leak Test Results Report

20A
20B

110
110

HRM Adjusted Delivery Report
BIR Adjusted Delivery Report

20C
20D

15
15

In-Tank Most Recent Delivery Report
In-Tank Stick Height Report

211

14

Tank Chart Report

212
213

24
26

In-Tank Leak Test History Report 2
In-Tank Extended Standard Delivery Report

Part No. 576013-635, Revision AA

681

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
IN-TANK REPORTS (7.2.2) (Continued)
Code Ver
214
26
215
26

Function
In-Tank Mass/Density Inventory Report
In-Tank Mass/Density Delivery Report

216
217
218
219

26
26
26
26

Tank 50 Point Heights, Volumes and Slope Report
Tank Profile
Tank Chart Audit Trail
Tank Chart Security Status

21A
21B

27
26

In-Tank Inventory Report With 90/95% Ullage
BIR Extended Adjusted Delivery Report

221
222

116
23

Ticketed Delivery Report
Bill of Lading Report

225
226
227

116
116
116

Periodic Delivery Variance Report
Weekly Delivery Variance Report
Daily Delivery Variance Report

237
238
239
23A

33
33
33
33

251

3

281
282

3
19

Fuel Management Report
FLS Diagnostic: Volume History Table

2E2

14

In-Tank Stored Inventory Report

In-Tank Product Inventory Report
In-Tank Siphon Manifolded Inventory Report
Manifolded Delivery Report with Sales Adjustment if BIR available
Manifolded Delivery Report with Sales Adjustment if BIR available
CSLD Results Report

SENSOR REPORTS (7.2.3)
Code Ver
301
1
302
1

Function
Liquid Sensor Status Report
Liquid Sensor Alarm History Report

306
307

1
1

Vapor Sensor Status Report
Vapor Sensor Alarm History Report

311
312

1
1

Groundwater Sensor Status Report
Groundwater Sensor Alarm History Report

315
316

24
24

Smart Sensor Status Report
Smart Sensor Alarm History Report

Part No. 576013-635, Revision AA

682

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
SENSOR REPORTS (7.2.3) (Continued)
Code Ver
317
26
318
26
319
26
31A
26

Function
Mag Sump Leak Test In Progress/Last Test Report
Mag Sump Leak Test Last Passed Test Report
Mag Sump Leak Test Last 10 Test Passed Report
Mag Sump Leak Test Last Passed Each Year Report

322
323

27
27

Pump Relay Monitor Status Report
Pump Relay Monitor Alarm History Report

333

24

Smart Sensor Install Log

341
342

2
2

Type A (2 Wire CL) Sensor Status Report
Type A (2 Wire CL) Sensor Alarm History Report

346
347

2
2

Type B (3 Wire CL) Sensor Status Report
Type B (3 Wire CL) Sensor Alarm History Report

34B
34C

4
4

Universal Sensor Status Report
Universal Sensor Alarm History Report

LINE LEAK REPORTS (7.2.4)
Code Ver
351
1
352
1
353
2

Function
Volumetric Line Leak Result Report
Volumetric Line Leak Alarm History Report
Volumetric Line Leak Pump Status

373
374

14
14

Pressure Line Leak Test Results (with 0.20 test data)
Pressure Line Leak Test History (with 0.20 test data)

381
382
383
384

7
7
7
7

Pressure Line Leak Status
Pressure Line Leak Alarm History Report
Pressure Line Leak Test Results (0.10 test data only)
Pressure Line Leak Test History (0.10 test data only)

386
387
388
389

10
10
10
12

WPLLD Line Leak Status
WPLLD Line Leak Alarm History Report
WPLLD Line Leak Test Results
WPLLD Line Leak Test History

MISCELLANEOUS REPORTS (7.2.5)
Code Ver
391
10
392
26

Function
Tanker Load Report
Tanker Load Report II

Part No. 576013-635, Revision AA

683

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
I/O DEVICE REPORTS (7.2.6)
Code Ver
401
1
402
1
403
5
404
31

Function
Input Status Report
Input Alarm History Report
Input/Generator Alarm History Report
Input Generator Report

406

1

Relay Status Report

411
412

28
28

VMCI Alarm History Report
VMC Alarm History Report

SETUP FUNCTIONS & REPORTS (7.3)
SYSTEM SETUP (7.3.1)
Code Ver
501
1
502
1
503
1
504
1
505
1

Function
Set Time of day
Set Shift Start Time 1, 2, 3, 4
Set Print Header Line 1, 2, 3, 4
Set System RS-232 Security Code
Set System Type & Language Flags

506
507
508

2
4
4

Set Periodic Test Needed Warning
Set Days Before Periodic Test Needed Warning
Set Days Before Periodic Test Needed Alarm

509
50A
50B

4
4
4

Set Annual Test Needed Warning
Set Days Before Annual Test Needed Warning
Set Days Before Annual Test Needed Alarm

50C
50D
50E
50F

5
8
8
10

511
512

110
110

Set BIR Shift Printouts Flag
Set BIR Daily Printouts Flag

513

10

Set Tanker Load Report Flag

514
515
516

10
110
14

Set Remote Printer Page Eject Flag
Set Print Temperature Compensation Flag
Set Temperature Compensation Value
Set System Date/Time Display Format

Set H-Protocol Height/Volume format
Set HRM - QPLD Monthly Printout
Set Re-direct Local Printout Flag

Part No. 576013-635, Revision AA

684

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
SYSTEM SETUP (7.3.1) (Continued)
Code Ver
517
15
518
15

Function
Set System Type & Language Flags
Set Secondary Language Code Page Output

519

15

Set PLLD & WPLLD Duration Before Precision Retest

51A
51B

15
15

Set Enable/Disable Auto Daylight Saving Time
Set Start/End Daylight Saving Date and Time

51C
51D
51E

116
116
116

550
551

33
33

Set Ticketed Delivery Flag Enable
Set Ticketed Delivery Temperature Compensation Flag
Set Ticketed Delivery Close Day of Week
Set Inventory Alarms Units Configuration
Set Inventory Alarms Custom Units

COMMUNICATIONS SETUP (7.3.2)
Code Ver
520
20
521
2
522
2
523
2
524
2
525
2
526
2
527
2
528
2
529
19
52A
3
52B
3
52C
3
52D
17
52E
19
52F
19

Function
Set Receiver Auto Dial Type and Start Time II
Set Receiver Configuration Flag
Set Receiver Location Label
Set Receiver Telephone Number
Set Receiver Dialing Destination Type
Set Receiver Port Number to Dial
Set Receiver Retry Number
Set Receiver Retry Delay Time
Set Receiver Confirmation Report Flag
Set Fax Auto Dial Method
Set Receiver Report List
Set Receiver Auto Dial Type and Start Time
Set Receiver Auto Dial On Alarms
Autodial Alarm Status
Set Delay for Autodial on Alarm Clear
Set Receiver Alarm Status

530
531

Beeper Enable/Disable
Set RS-232 End of Message

26
8

WARNING, ALARM, & AUTO-PRINT SETUP (7.3.3)
Code Ver
532
116
533
116

Function
Set Ticketed Variance Analysis Printout Flags
Set Ticketed Delivery Book Variance Printout Flags

Part No. 576013-635, Revision AA

685

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
WARNING, ALARM, & AUTO-PRINT SETUP (7.3.3) (Continued)
Code Ver
534
116

Function
Set Ticketed Delivery Variance Printout Flags

536
537
538

20
20
20

Set RS-232 Security Code per Port
Set Display Format RS-232 ETX per Port
Set Computer Format RS-232 ETX per Port

546
547
548

15
15
15

Set Tank Periodic Test Needed Warning
Set Days Before Tank Periodic Test Needed Warning
Set Days Before Tank Periodic Test Needed Alarm

549
54A
54B

15
15
15

Set Tank Annual Test Needed Warning
Set Days Before Tank Annual Test Needed Warning
Set Days Before Tank Annual Test Needed Alarm

54C
54D
54E

19
29
31

Set CSLD Evaporation Reid Vapor Pressure Chart
Set IS03166 3 Character Country Code
Set Vapor Monitoring Type

553
554
555
556
557
558

19
18
18
15
15
15

Set Line Re-Enable Method
Set Periodic Line Leak Test Auto-Confirm
Set Annual Line Leak Test Auto-Confirm
Set Line Periodic Test Needed Warning
Set Days Before Line Periodic Test Needed Warning
Set Days Before Line Periodic Test Needed Alarm

559
55A
55B

15
15
15

Set Line Annual Test Needed Warning
Set Days Before Line Annual Test Needed Warning
Set Days Before Line Annual Test Needed Alarm

55E

32

Set Fiscal Height Security Enable/Disable

560

26

Set Mass/Density Enable/Disable

564

27

Set Ullage

565
566
567
568
569
56A

27
28
28
28
28
29

Set Maintenance History
Set Service Notice Enable
Set Service Notice Delivery Override Enable
Set Service Notice Session Enable
Set Service Notice Session Duration
System Tank Chart Security Code Audit Trail

581

33

Set Alarm Filter

5BC

19

Set Receiver Auto Dial on Alarm II

Part No. 576013-635, Revision AA

686

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
WARNING, ALARM, & AUTO-PRINT SETUP (7.3.3) (Continued)
Code Ver
5BD
23
5BE
23
5BF
26

Function
Set Enable/Disable Custom Alarms
Set Custom Alarm Labels
Set Custom Alarm Label, device number, and indications

5E2

Set Inventory Record Time 1, 2, 3, 4

14

IN-TANK SETUP (7.3.4)
Code Ver
601
1
602
1
603
1
604
1
605
1
606
1
607
1
608
1
609
1
60A
9

Function
Set Tank Configuration
Set Tank Product Label
Set Tank Product Code
Set Tank 1 Point Full Height Volume
Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes
Set Tank 20 Point Full, 95%, 90%,...Volumes
Set Tank Diameter
Set Tank Tilt
Set Tank Thermal Expansion Coefficient
Set Tank Linear Calculated Full Volume

60B
60C

15
15

Set Tank Stick Height Function Enable
Set Tank Stick Height Offset

60E
60F
610

22
22
1

Set Tank Programmable Float Parameters
Set Tank Probe Offset
Set Tank Delivery Delay

611
612

1
1

Set Tank Leak Test Type & Start Time
Set Tank SIPHON Manifolded Partners

613
614

3
5

Set CSLD Probability of Detection
Set CSLD Climate Factor

615
616

108
110

Set BIR Meter Data Present
Set AccuChart Update Scheduling

618
619

19
19

Set Tank CSLD Evaporation Compensation
Set Tank Stage II Vapor Recovery

61A
61B

20
121

Set In-Tank Leak Test Early Stop
Set In-Tank Static Gross Test Auto-Confirm

Part No. 576013-635, Revision AA

687

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
IN-TANK SETUP (7.3.4) (Continued)
Code Ver
61C 121
61D
23

Function
Set CSLD Report Only Mode
Set Tank LINE Manifolded Partners

61E
61F

26
26

Set Tank Density
Set Delivery Density

621
622
623
624
625
626
627
628
629
62A
62B
62C
62D
62E
62F

1
1
1
1
1
1
2
2
2
2
2
2
2
3
3

Set Tank Low Level Limit
Set Tank High Level Limit
Set Tank Overfill Level Limit
Set Tank High Water Level Limit
Set Tank Sudden Loss Limit
Set Tank Leak Alarm Limit
Set Tank High Water Warning Limit
Set Tank Maximum Volume Limit
Set Tank Delivery Required Limit
Set Tank Annual Leak Test Minimum Volume
Set Tank Last Annual Test
Set Tank Periodic Test Type
Set Enable/Disable Tank Leak Test Fail Alarms
Set CAP0 Probe Conductive Boot Flag
Set Mag Probe Float Size

630
631
632
633

3
5
5
9

Set Tank Leak Test Notify
Set Tank Leak Test Averaging
Set Tank Test Siphon Break
Set Leak Test Report Type

634
635

110
110

Set Tank HRM Reconciliation Warning Limit
Set Tank HRM Reconciliation Alarm Limit

636
639
63A

14
115
22

Set Tank Periodic Leak Test Minimum Volume
Set Tank AccuChart End Shape Type and Factor
Set Tank Low Level Threshold for Sequential Line Manifold

63B
63C
63D

26
26
29

Set Tank 50 Point Heights and Volumes
Set Tank 50 Point Full Volume
Set Tank Vapor Loss Factor

642

31

Set Tank Water Filter Level

648

33

Set Probe Water Minimum

64B

33

Set Tank Water Alarm Filter Delay

651

33

Set Tank Max or Label Alarm Threshold

Part No. 576013-635, Revision AA

688

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
IN-TANK SETUP (7.3.4) ) (Continued)
Code Ver
652
33
653
33
654
33
655
33
680
6
681
6
682
6
683
6

Function
Set Tank High Product Alarm Threshold
Set Tank Overfill Alarm Threshold
Set Tank Delivery Needed Alarm Threshold
Set Tank Low Product Alarm Threshold
Fuel Management General Setup Inquiry
Set Fuel Management Delivery Needed Warning
Set Fuel Management Automatic Report Print Time
Set Fuel Management Average Daily Sales

SENSOR SETUP (7.3.5)
Code Ver
701
1
702
1
703
1
704
2

Function
Set Liquid Sensor Configuration
Set Liquid Sensor Location Label
Set Liquid Sensor Type
Set Liquid Sensor Category

706
707
708
709

1
1
1
2

Set Vapor Sensor Configuration
Set Vapor Sensor Location Label
Set Vapor Sensor Alarm Threshold
Set Vapor Sensor Category

711
712
713

1
1
2

Set Groundwater Sensor Configuration
Set Groundwater Sensor Location Label
Set Groundwater Sensor Category

721
722
723

24
24
25

Set Smart Sensor Configuration
Set Smart Sensor Label
Set Smart Sensor Category

727
728

24
24

Set MAG Sensor Alarm Upgrade Delay
Set MAG Sensor Alarm Threshold

729
72A
72B
72C

24
24
24
24

Set Vacuum Sensor Pump Number
Set Vacuum Sensor Volume
Set Vacuum Sensor Relief Valve Present
Set Vacuum Sensor Relief Valve Pressure

741
742
743
744

2
2
2
2

Set Type A (2 Wire CL) Sensor Configuration
Set Type A (2 Wire CL) Sensor Location Label
Set Type A (2 Wire CL) Sensor Type
Set Type A (2 Wire CL) Sensor Category

746
747

2
2

Set Type B (3 Wire CL) Sensor Configuration
Set Type B (3 Wire CL) Sensor Location Label

Part No. 576013-635, Revision AA

689

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
SENSOR SETUP (7.3.5) (Continued)
Code Ver
748
5
749
2

Function
Set Type B (3 Wire CL) Sensor Type
Set Type B (3 Wire CL) Sensor Category

74B
74C
74D
74E

Set Universal Sensor Configuration
Set Universal Sensor Location Label
Set Universal Sensor Type
Set Universal Sensor Category

4
4
4
4

VOLUMETRIC LINE LEAK SETUP (7.3.6)
Code Ver
751
1
752
1
753
1
754
1
755
1
756
1
757
1
758
1
759
1
75A
1
75B
2

Function
Set Volumetric Line Leak Configuration
Set Volumetric Line Leak Tank Number
Set Volumetric Line Leak 2 Inch Pipe Length
Set Volumetric Line Leak 3 Inch Pipe Length
Set Volumetric Line Leak Pump PSI
Set Volumetric Line Leak Piping Material
Set Volumetric Line Leak Shutdown Rate
Set Volumetric Line Leak Pump Side Test
Set Volumetric Line Leak Test Type & Start Time
Set Line Leak Lockout Schedule (All Types)
Set Line Disable Alarm Assignments

75C
75D
75E
75F
760
761

2
4
4
5
6
7

Set Volumetric Line Leak Last Annual Test
Set Volumetric Line Leak Dispense Mode
Set Volumetric Line Leak Fuel Type
Set Volumetric Line Leak Wait Method
Set Volumetric Line Leak Location Label
Set Volumetric Line Leak Blend Partner

7BC

19

Set Line Disable Alarm Assignments II

PUMP SENSOR SETUP (7.3.7)
Code Ver
771
2
772
2
773
4

Function
Set Pump Sensor Configuration
Set Pump Sensor Tank Number
Set Pump Sensor Dispense Mode

7DA
7DB
7DC

Set Alternate Modes Auto Active Pump Switchover Enable
Set Alternate Modes Auto Active Pump Switchover Volume Threshold
Set Alternate-Height Modes Auto Active Pump Switchover Height Threshold

33
33
33

Part No. 576013-635, Revision AA

690

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
PRESSURE LINE LEAK SETUP (7.3.8)
Code Ver
774
27
775
23
776
23
777
23
778
23
779
23
77A
23
77B
23
77C
19
77D
19
77E
24
77F
17

Function
Set Pressure Line Leak Continuous Handle Alarm Timeout
Set Pressure Line Leak Profile Line Test Leak Rate
Set Pressure Line Leak Profile Line Test Reference Pressure
Set Pressure Line Leak Primary Pipe Diameter
Set Pressure Line Leak Secondary Pipe Diameter
Set Pressure Line Leak Primary Pipe Bulk Modulus
Set Pressure Line Leak Secondary Pipe Bulk Modulus
Set Pressure Line Leak Thermal Expansion Coefficient
Set Pressure Line Leak Low Pressure Shutoff
Set Pressure Line Leak Altitude Pressure Offset
Set Pressure Line Leak Passive 0.10 GPH Test Enable Flag
Set Pressure Line Leak Secondary Pipe Length

780
781
782
783
784
785
786
787
788
789
78A

7
7
7
7
7
7
7
7
9
9
11

Pressure Line Leak General Setup Inquiry
Set Pressure Line Leak Configuration
Set Pressure Line Leak Label
Set Pressure Line Leak 0.10 GPH Test Schedule
Set Pressure Line Leak Shutdown Rate
Set Pressure Line Leak Tank Number
Set Pressure Line Leak Dispense Mode
Set Pressure Line Leak Disable Alarm Assignments
Set Pressure Line Leak Piping Material
Set Pressure Line Leak Primary Pipe Length
Set Pressure Line Leak Sensor Type

78B
78C

16
12

Set Pressure Line Leak 0.10 GPH Test Schedule (Obsolete at V17, use 78E)
Set Pressure Line Leak 0.20 GPH Test Schedule

78E
78F

17
17

Set Pressure Line Leak 0.10 GPH Auto Test Enable
Set Pressure Line Leak Dispense Threshold

7BD

19

Set Pressure Line Disable Alarm Assignments II

7D7
7D8
7D9

33
33
33

Set Alternate Modes Auto Active Pump Switchover Enable
Set Alternate Modes Auto Active Pump Switchover Volume Threshold
Set Alternate-Height Modes Auto Active Pump Switchover Height Threshold

RECONCILIATION SETUP (7.3.9)
Code
790
791
792

Ver
118
106
106

Function
DIM Software Revision
Set Mechanical Dispenser Interface String
Set Electronic Dispenser Interface String

793

106

Set Reconciliation Auto Daily Closing Time

Part No. 576013-635, Revision AA

691

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
RECONCILIATION SETUP (7.3.9) (Continued)
Code
794
795
796
797
798
799

Ver
106
106
106
106
106
106

Function
Set Auto Shift Closing Time 1, 2, 3, 4
Set Periodic Reconciliation Mode
Set Periodic Reconciliation Report Length
Set Periodic Reconciliation Alarm Flag
Set Periodic Reconciliation Alarm Threshold
Set Periodic Reconciliation Alarm Offset

79A
79B
79C

106
106
106

Set Remote Printer Reconciliation Report Format
Set Shift Manual Adjustment Value
Set Daily Manual Adjustment Value

79D

106

Close Current Reconciliation Shift

79E
79F

106
108

Clear Tank Map Table
Set BIR Temperature Compensation Flag

WIRELESS PLLD SETUP (7.3.10)
Code Ver
7A0
10
7A1
10
7A2
10
7A3
10
7A4
10
7A5
10
7A6
10
7A7
10
7A8
10
7A9
10

Function
WPLLD Line Leak General Setup
Set WPLLD Line Leak Configuration
Set WPLLD Line Leak Label
Set WPLLD Line Leak 0.20 GPH Test Schedule
Set WPLLD Line Leak Shutdown Rate
Set WPLLD Line Leak Tank Number
Set WPLLD Line Leak Dispense Mode
Set WPLLD Line Disable Alarm Assignments
Set WPLLD Line Leak Pipe Type
Set WPLLD Line Leak Pipe Length

7AA

11

Set WPLLD Line Leak 0.10 GPH Test Schedule (Obsolete at V17, use 7AC)

7AC
7AD
7AE
7AF

17
20
27
19

Set WPLLD Line Leak 0.10 GPH Test Schedule Enable
Set WPLLD Line Leak Secondary Pipe Length
WPLLD Continuous Handle Alarm Timeout
Set WPLLD Line Leak Altitude Pressure Offset

7BE

19

Set WPLLD Line Disable Alarm Assignments II

METER MAP & DELIVERY TICKET SETUP (7.3.11)
Code Ver
7B1 110
7B2
20

Function
Set BIR Meter/Tank Mapping
Set Meter Calibration Offset

Part No. 576013-635, Revision AA

692

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
METER MAP & DELIVERY TICKET SETUP (7.3.11) (Continued)
Code Ver
7B4
29
7B5 116
7B6
23

Function
Set Individual Meter Offset
Set Ticketed Delivery
Set BOL number

LINE/PLLD/WPLLD SETUP
Code Ver
7BE
19
7BE
19
7BE
19

Function
Set Line Disable Alarm Assignments II (refer to 7.3.5)
Set Pressure Line Disable Alarm Assignments II (refer to 7.3.8)
Set WPLLD Line Disable Alarm Assignments II (refer to 7.3.10)

PUMP MONITOR RELAY SETUP (7.3.12)
Code Ver
7C4
27
7C5
27
7C6
27
7C7
27
7C8
27
7C9
28

Function
Set Pump Relay Monitor Configuration
Set Pump Relay Monitor Label
Set Pump Relay Monitor Pump Relay
Set Pump Relay Monitor Stuck Relay
Set Pump Relay Monitor Max Run Time
Set Pump Relay Monitor Type

PRESSURE LINE LEAK SETUP (refer to 7.3.8)
Code Ver
7D7
33
7D8
33
7D9
33

Function
Pressure Line Leak Setup Refer to 7.3.8
Pressure Line Leak Setup Refer to 7.3.8
Pressure Line Leak Setup Refer to 7.3.8

PUMP SENSOR SETUP (refer to 7.3.7)
Code Ver
7DA
33
7DB
33
7DC
33

Function
Pump Sensor Setup Refer to 7.3.7
Pump Sensor Setup Refer to 7.3.7
Pump Sensor Setup Refer to 7.3.7

I/O DEVICE SETUP (7.3.13)
Code Ver
801
1
802
1
803
1
804
4
806
1
807
1

Function
Set Input Configuration
Set Input Location Label
Set Input Type
Set Input Dispense Mode
Set Relay Configuration
Set Relay Location Label

Part No. 576013-635, Revision AA

693

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
I/O DEVICE SETUP (7.3.13) (Continued)
Code Ver
808
1
809
2
80A
4
80B
4
80C
25

Function
Set Relay Alarm Assignments
Set Relay Orientation
Set Relay Type
Set Relay Tank Assignment
Set External Input Type

811
812
813

Set Alternate Modes Auto Active Pump Switchover Enable
Set Alternate Modes Auto Active Pump Switchover Volume Threshold
Set Alternate-Height Modes Auto Active Pump Switchover Height Threshold

33
33
33

EEPROM SETUP (7.3.14)
Code
851
852
853

Ver
107
107
107

Function
Restore All Setup Data from EEPROM
Save All Setup Data to EEPROM
Clear All Setup Data from EEPROM

MISCELLANEOUS SETUP (7.3.15)
Code Ver
881
9
882
9

Function
Set Communication Port Data
Initialize Communication Port Data

885
886
887
888
889

19
20
20
19
121

Set SiteLink Modem Type
Set Modem Setup String
Set Dial Tone Validation Interval
Communication Status Information
DTR Normal State for Serial Satellite Boards

88D

23

891

108

8A2
8A3
8A4

27
27
27

Service Code List
Maintenance Tracker Active Hardware Key List
Maintenance Tracker Block Hardware Key

8BC

19

Set Relay Alarm Assignments II

8C1
8C2
8C3
8C4

28
28
31
31

VMC Edit/Add Serial Number
VMC Remove Serial Number
VMC Edit/Add Fueling Position Number
VMC Communications Timeout Value

Communication Diagnostic for SiteLink
Set AccuChart Calibration Restart

Part No. 576013-635, Revision AA

694

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
DIAGNOSTIC REPORTS (7.4)
SYSTEM DIAGNOSTIC REPORTS (7.4.1)
Code Ver
901
1
902
1
903
106
905
15
908
33

Function
Self Test Results Report
System Revision Level Report
PC Diagnostic Report
System Revision Level Report II
Power Up Time Report

IN-TANK DIAGNOSTIC REPORTS (7.4.2)
Code Ver
A01
1
A02
1
A03
1
A04
1
A05
1
A06
1

Function
Probe Type and Serial Number
Probe Factory Dry Calibration Values
Probe Factory Wet Calibration Values
Probe Updated Dry Calibration Values
Probe Updated Wet Calibration Values
Probe Segment Sensitivity Ratios

A07

23

Probe Reference Distance Diagnostic

A10
A11
A12
A13
A14
A15

1
1
1
1
19
24

Probe Last Sample Buffers
Probe Fast Average Buffers
Probe Standard Average Buffers
Probe Long Term Average Buffers
Mag Probe Option Table
In-Tank Diagnostic Printout

A20
A21
A22
A23

1
1
2
5

A51
A52
A53
A54
A55
A56

3
3
3
3
3
121

CSLD Diagnostics: Rate Table
CSLD Diagnostics: Rate Test
CSLD Diagnostics: Volume History Table
CSLD Diagnostics: Moving Average Table
CSLD Diagnostics: Leak Test Status
CSLD Monthly Report

A61
A62
A63

110
112
26

HRM Diagnostic Report
HRM Daily History
Extended HRM Diagnostic Report

Probe Leak Test Flags - Present Test
Probe Leak Test Flags - Stored Test
Probe Leak Test Flags - Gross Test
Tank Leak Test Averaging Buffers

Part No. 576013-635, Revision AA

695

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
IN-TANK DIAGNOSTIC REPORTS (7.4.2) (Continued)
Code Ver
A81
6

Function
Fuel Management Diagnostic Report

A91

Power Outage Diagnostic Report

9

SENSOR DIAGNOSTIC REPORTS (7.4.3)
Code Ver
B01
1

Function
Liquid Sensor Diagnostic Report

B06
B07

1
3

Vapor Sensor Diagnostic Report
Vapor Sensor Concentration (PPM) Report

B11
B21

1
1

Groundwater Sensor Diagnostic Report
Ground Temperature Sensor Diagnostic Report

B33

24

MAG Sensor Diagnostic Report

B34
B35
B36

24
24
24

Smart Sensor Last Sample Diagnostic
Smart Sensor Type and Serial Number
Smart Sensor Constant Data

B37

24

Atmospheric Pressure Sensor Diagnostic Report

B38
B39

24
24

Vacuum Sensor Diagnostic Report
Vacuum Sensor Evacuation Diagnostic Report

B41
B46

2
2

Type A Sensor (2 Wire CL) Diagnostic Report
Type B Sensor (3 Wire CL) Diagnostic Report

B4B

4

Universal Sensor Diagnostic Report

LINE LEAK DIAGNOSTIC REPORTS (7.4.4)
Code Ver
B50
1
B51
1
B52
1

Function
Volumetric Line Leak Status
Volumetric Line Leak Diagnostic Gross Test History
Volumetric Line Leak 0.10 & 0.20 GPH Diagnostic History

B61
B62

29
29

Vapor Valve Diagnostic
Sub Alarm History Report

B71
B72

2
27

Pump Sensor Diagnostic
Pump Relay Monitor Diagnostic

Part No. 576013-635, Revision AA

696

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
LINE LEAK DIAGNOSTIC REPORTS (7.4.4) (Continued)
Code Ver
B7B
23
B7C
19
B7D
19
B7E
19
B7F
19

Function
Pressure Line Leak Profile Line Test
Pressure Line Leak Pressure Offset Test
WPPLD Line Leak Pressure Offset Test
Pressure Line Leak Pressure Offset Monitor Report
WPLLD Line Leak Pressure Offset Monitor Report

B81
B82

7
10

Pressure Line Leak Diagnostic Report
WPLLD Line Leak Diagnostic Report

B83

10

WPLLD Line Leak Communication Diagnostic Report

B87
B88
B89
B8A

19
19
19
19

Pressure Line Leak 3.00 GPH Test Diagnostic
Pressure Line Leak Mid-range Test Diagnostic
Pressure Line Leak 0.20 GPH Test Diagnostic
Pressure Line Leak 0.10 GPH Test Diagnostic

B8B
B8C
B8D
B8E

19
19
19
19

WPLLD Line Leak 3.00 GPH Test Diagnostic
WPLLD Line Leak Mid-range Test Diagnostic
WPLLD Line Leak 0.20 GPH Test Diagnostic
WPLLD Line Leak 0.10 GPH Test Diagnostic

RECONCILIATION DIAGNOSTIC REPORTS (7.4.5)
Code
B91
B93
B94

Ver
108
108
108

Function
AccuChart Diagnostics Report
AccuChart Status Report
AccuChart Calibration History Report

BA0
BA1

110
32

MDIM Totalizer Report
DIM Communication Status and History

BB1
C01
C02

28
106
106

VMC Status Report
Basic Inventory Reconciliation Daily "Row" Report
Basic Inventory Reconciliation Daily "Column" Report

C03
C04

106
106

Basic Inventory Reconciliation Shift "Row" Report
Basic Inventory Reconciliation Shift "Column" Report

C05
C06

106
106

Basic Inventory Reconciliation Periodic "Row" Report
Basic Inventory Reconciliation Periodic "Column" Report

C07
C08
C09

114
114
19

Basic Inventory Reconciliation Periodic "Row" Report
Basic Inventory Reconciliation Periodic "Column" Report
Individual Basic Reconciliation Daily History Diagnostic

Part No. 576013-635, Revision AA

697

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
VARIANCE ANALYSIS REPORTS (7.6)
Code
C10
C11
C12

Ver
116
116
116

Function
Periodic Book Variance
Weekly Book Variance
Daily Book Variance

C20
C21
C22

116
116
116

Periodic Variance Analysis Report
Weekly Variance Analysis Report
Daily Variance Analysis Report

C25

19

Periodic Variance Analysis Daily Report

IN-STATION DIAGNOSTICS (ISD) (7.7)
ISD REPORTS (7.7.1)
Code Ver
V00
25
V01
25
V02
25
V03
25
V04
25
V05
25
V06
25
V07
25
V08
25
V09
25
V0A
25
V0B
25
V10
25
V12
30

Function
ISD CARB Certified Operating Requirements and Monitoring
ISD Alarm Status Report
ISD Monthly Status Report
ISD Daily Status Report
ISD Daily Report Details (by month)
ISD Daily Report Details (by day(s))
ISD Daily Report Details, 132 columns (by month)
ISD Daily Report Details (by day(s))
ISD Daily Report Details (by month)
ISD Daily Report Details, user input columns (by day(s))
ISD Daily Overall Status Report
ISD Monthly Overall Status Report
ISD Version Number
Vapor Collection Test Results

ISD SETUP (7.7.2)
Code Ver
V40
25
V41
25
V42
25
V43
25
V44
25
V45
25
V46
25
V47
25

Function
Set Vapor Processor Type
Set Vapor Processor Control Level
Set Clear Sensor/AFM/Hose Maps
Set Sensor Table ISD In Use Flag
Set Vapor Processor ON/OFF Pressure Thresholds
Set Vapor Processor Maximum Runtime (Obsolete at V30A)
Set Hydrocarbon Alarm Threshold
Set time of day ISD/PMC tests are started and results posted

Part No. 576013-635, Revision AA

698

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
ISD SETUP (7.7.2) (Continued)
Code Ver
V48
25
V49
25
V4A
25
V4B
25
V4E
25
V4F
25
V50
25
V51
25
V52
25
V54
29

Function
Read Airflow Meter Table
Set Hose Label Table
Read Hose Table Data
Read Grade Table
Set ISD EVR TYPE
Set Nozzle Type
Set CVLD Minimum Pressure Time Window
Perform ISD Setup Verification Test
Accept High ORVR Configuration
Set VR Polisher (Obsolete)

ISD DIAGNOSTIC REPORTS (7.7.3)
Code Ver
V80
25
V81
25
V82
30

Function
Vapor Processor Report
Percent Hydrocarbon Report
Vapor Processor Status Report

V83

25

Read Sensor Calibration History

V85

25

ISD Service Report Test Fail Clear

V88

30

PMC Daily Vapor Polisher Diagnostic

VA1
VA2
VA3

31
31
31

VMC A/L Daily Records Report
VMC A/L Exception Report
VMC A/L Transaction Report

VA4

31

Perform APM Setup Verification Test

VA5

31

VMCI Sub Alarm History Report

VA6
VA7
VA8
VA9
VAA
VAB
VAC
VAD
VAE
VAF

31
31
31
31
31
31
31
31
31
31

APM Diagnostic Report
APM Service Report Test Fail Clear
APM Miscellaneous Events Report
Acknowledge APM Alarm to Re-enable Site
Set Automatic Pressure Monitoring Type
APM Daily Summary Report
APM Fault History Report
Set APM Assessment Time
Set APM Sensor Test Warn/Fail Enable
Set Sensor Table APM in Use Flag

VC0
VC1

25
25

Automatic/Manual Vapor Processor Control
Manual Override of Vapor Processor

Part No. 576013-635, Revision AA

699

Serial Interface Manual
TLS-300/350/350R Monitoring Systems
ISD DIAGNOSTIC REPORTS (7.7.3) (Continued)
Code Ver
VC5
25

Function
Acknowledge ISD Alarm to Re-Enable Site

VC8
XE0

Set Manual Override of Veeder-Root Polisher
ISD Setup Data Time Stamp EEPROM

29
25

Part No. 576013-635, Revision AA

700



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Print high-res
Author                          : Linda Cristallo
Company                         : Toshiba
Create Date                     : 2014:09:29 05:38:26-04:00
Modify Date                     : 2014:10:03 11:03:46-04:00
Source Modified                 : D:20140929093807
Subject                         : 
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2014:10:03 11:03:46-04:00
Creator Tool                    : Acrobat PDFMaker 10.1 for Word
Document ID                     : uuid:4386c058-abf0-4382-8e34-b3d139282742
Instance ID                     : uuid:49defb30-c6e1-46c4-8eb4-a1f691b240d3
Format                          : application/pdf
Title                           : VEEDER - ROOT
Description                     : 