110 724B Paragon EC7000 04 05 Manual

User Manual: Paragon-EC7000-04-05-manual

Open the PDF directly: View PDF PDF.
Page Count: 10

Download110-724B Paragon-EC7000-04-05-manual
Open PDF In BrowserView PDF
http://waterheatertimer.org/Paragon-timers-and-manuals.html#EC

I N T RO D U C T I O N

Output
UL Ratings

Replacement timer

http://waterheatertimer.org/Intermatic-ET-series-timers-and-manuals.html#ET1700
The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 setpoints available, this time control provides programming versatility.

EC7000, EC7004 and EC7005
Single Channel
Electronic Time Controls
GENERAL INSTRUCTIONS

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, factory bells, remote animal feeders, and air and water purity samplers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.
EC7000 SPDT

EC7004 SPST

•
•
•

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.
24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.
Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.
Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N
L2

L
L1

(24, 120 or 277)
(208 or 240)

N
L2

L
L1

See jumpers below

2

3

4

120V jumpers

1

2

3

208 or 240V jumpers

4
L
L1
L

K E Y PA D D E S C R I P T I O N

Terminals can accommodate 10-16 AWG wire.

EC7000
Normally open contacts:
10 amp resistive at 24-240 Vac
1/2 Hp at 120 Vac
1 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 120 Vac
10 amp resistive at 240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of 4 days. A built-in special capacitor eliminates the inconvenience of battery replacement.

ENVIRONMENTAL
EC7000 & EC7004 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL
EC7000 and EC7004 MonutingNEMA 1 enclosure mounting
Weight - Approx. 2 lbs.(0.9kg)
DimensionsWidth 10.8 cm (4-1/4”)
Height 20.0 cm (7-7/8”)
Depth 7.6 cm (3”)

EC7005 MountingNEMA 3 enclosure mounting
Weight - Approx. 3 lbs.(1.4kg)
DimensionsWidth 16.7 cm (6-9/16”)
Height 23.1 cm (8-1/8”)
Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
DimensionsWidth 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

EC7000, EC7004 and EC7005

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

(120 or 277V)
(208 or 240V)

EC7005 SPST

1

WIRING

CSA Ratings

EC7000
Normally open contacts:
20 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed information and carry out instructions but input power does not power
the load. To make circuits function, you must provide power to
the contacts.

S P E C I F I C C A PA B I L I T I E S
•

C O N TAC T R AT I N G S

N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)

I N T RO D U C T I O N

C O N TAC T R AT I N G S
Output
UL Ratings

The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 setpoints available, this time control provides programming versatility.

EC7000, EC7004 and EC7005
Single Channel
Electronic Time Controls
GENERAL INSTRUCTIONS

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, factory bells, remote animal feeders, and air and water purity samplers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.
EC7000 SPDT

EC7004 SPST

•
•
•
•

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.
24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.
Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.
Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N
L2

L
L1

(24, 120 or 277)
(208 or 240)

N
L2

L
L1

EC7000
Normally open contacts:
10 amp resistive at 24-240 Vac
1/2 Hp at 120 Vac
1 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 120 Vac
10 amp resistive at 240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

See jumpers below

2

3

4

120V jumpers

1

2

3

208 or 240V jumpers

4
L
L1
L

POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of 4 days. A built-in special capacitor eliminates the inconvenience of battery replacement.

ENVIRONMENTAL
EC7000 & EC7004 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL
EC7000 and EC7004 MonutingNEMA 1 enclosure mounting
Weight - Approx. 2 lbs.(0.9kg)
DimensionsWidth 10.8 cm (4-1/4”)
Height 20.0 cm (7-7/8”)
Depth 7.6 cm (3”)

EC7005 MountingNEMA 3 enclosure mounting
Weight - Approx. 3 lbs.(1.4kg)
DimensionsWidth 16.7 cm (6-9/16”)
Height 23.1 cm (8-1/8”)
Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
DimensionsWidth 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

EC7000, EC7004 and EC7005

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

(120 or 277V)
(208 or 240V)

EC7005 SPST

1

K E Y PA D D E S C R I P T I O N

Terminals can accommodate 10-16 AWG wire.

CSA Ratings

EC7000
Normally open contacts:
20 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed information and carry out instructions but input power does not power
the load. To make circuits function, you must provide power to
the contacts.

S P E C I F I C C A PA B I L I T I E S

WIRING

N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)

I N T RO D U C T I O N

C O N TAC T R AT I N G S
Output
UL Ratings

The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 setpoints available, this time control provides programming versatility.

EC7000, EC7004 and EC7005
Single Channel
Electronic Time Controls
GENERAL INSTRUCTIONS

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, factory bells, remote animal feeders, and air and water purity samplers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.
EC7000 SPDT

EC7004 SPST

•
•
•
•

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.
24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.
Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.
Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N
L2

L
L1

(24, 120 or 277)
(208 or 240)

N
L2

L
L1

EC7000
Normally open contacts:
10 amp resistive at 24-240 Vac
1/2 Hp at 120 Vac
1 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 120 Vac
10 amp resistive at 240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

See jumpers below

2

3

4

120V jumpers

1

2

3

208 or 240V jumpers

4
L
L1
L

POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of 4 days. A built-in special capacitor eliminates the inconvenience of battery replacement.

ENVIRONMENTAL
EC7000 & EC7004 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL
EC7000 and EC7004 MonutingNEMA 1 enclosure mounting
Weight - Approx. 2 lbs.(0.9kg)
DimensionsWidth 10.8 cm (4-1/4”)
Height 20.0 cm (7-7/8”)
Depth 7.6 cm (3”)

EC7005 MountingNEMA 3 enclosure mounting
Weight - Approx. 3 lbs.(1.4kg)
DimensionsWidth 16.7 cm (6-9/16”)
Height 23.1 cm (8-1/8”)
Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
DimensionsWidth 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

EC7000, EC7004 and EC7005

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

(120 or 277V)
(208 or 240V)

EC7005 SPST

1

K E Y PA D D E S C R I P T I O N

Terminals can accommodate 10-16 AWG wire.

CSA Ratings

EC7000
Normally open contacts:
20 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed information and carry out instructions but input power does not power
the load. To make circuits function, you must provide power to
the contacts.

S P E C I F I C C A PA B I L I T I E S

WIRING

N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)

I N T RO D U C T I O N

C O N TAC T R AT I N G S
Output
UL Ratings

The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 setpoints available, this time control provides programming versatility.

EC7000, EC7004 and EC7005
Single Channel
Electronic Time Controls
GENERAL INSTRUCTIONS

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, factory bells, remote animal feeders, and air and water purity samplers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.
EC7000 SPDT

EC7004 SPST

•
•
•
•

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.
24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.
Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.
Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N
L2

L
L1

(24, 120 or 277)
(208 or 240)

N
L2

L
L1

EC7000
Normally open contacts:
10 amp resistive at 24-240 Vac
1/2 Hp at 120 Vac
1 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 120 Vac
10 amp resistive at 240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

See jumpers below

2

3

4

120V jumpers

1

2

3

208 or 240V jumpers

4
L
L1
L

POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of 4 days. A built-in special capacitor eliminates the inconvenience of battery replacement.

ENVIRONMENTAL
EC7000 & EC7004 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL
EC7000 and EC7004 MonutingNEMA 1 enclosure mounting
Weight - Approx. 2 lbs.(0.9kg)
DimensionsWidth 10.8 cm (4-1/4”)
Height 20.0 cm (7-7/8”)
Depth 7.6 cm (3”)

EC7005 MountingNEMA 3 enclosure mounting
Weight - Approx. 3 lbs.(1.4kg)
DimensionsWidth 16.7 cm (6-9/16”)
Height 23.1 cm (8-1/8”)
Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
DimensionsWidth 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

EC7000, EC7004 and EC7005

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

(120 or 277V)
(208 or 240V)

EC7005 SPST

1

K E Y PA D D E S C R I P T I O N

Terminals can accommodate 10-16 AWG wire.

CSA Ratings

EC7000
Normally open contacts:
20 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed information and carry out instructions but input power does not power
the load. To make circuits function, you must provide power to
the contacts.

S P E C I F I C C A PA B I L I T I E S

WIRING

N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)

I N T RO D U C T I O N

C O N TAC T R AT I N G S
Output
UL Ratings

The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 setpoints available, this time control provides programming versatility.

EC7000, EC7004 and EC7005
Single Channel
Electronic Time Controls
GENERAL INSTRUCTIONS

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, factory bells, remote animal feeders, and air and water purity samplers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.
EC7000 SPDT

EC7004 SPST

•
•
•
•

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.
24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.
Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.
Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N
L2

L
L1

(24, 120 or 277)
(208 or 240)

N
L2

L
L1

EC7000
Normally open contacts:
10 amp resistive at 24-240 Vac
1/2 Hp at 120 Vac
1 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

Normally closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac
1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac

EC7004
Normally open contacts:
30 amp resistive at 120 Vac
10 amp resistive at 240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

See jumpers below

2

3

4

120V jumpers

1

2

3

208 or 240V jumpers

4
L
L1
L

POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of 4 days. A built-in special capacitor eliminates the inconvenience of battery replacement.

ENVIRONMENTAL
EC7000 & EC7004 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL
EC7000 and EC7004 MonutingNEMA 1 enclosure mounting
Weight - Approx. 2 lbs.(0.9kg)
DimensionsWidth 10.8 cm (4-1/4”)
Height 20.0 cm (7-7/8”)
Depth 7.6 cm (3”)

EC7005 MountingNEMA 3 enclosure mounting
Weight - Approx. 3 lbs.(1.4kg)
DimensionsWidth 16.7 cm (6-9/16”)
Height 23.1 cm (8-1/8”)
Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
DimensionsWidth 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

EC7000, EC7004 and EC7005

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

(120 or 277V)
(208 or 240V)

EC7005 SPST

1

K E Y PA D D E S C R I P T I O N

Terminals can accommodate 10-16 AWG wire.

CSA Ratings

EC7000
Normally open contacts:
20 amp resistive at 24-240 Vac
1 Hp at 120 Vac
2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed information and carry out instructions but input power does not power
the load. To make circuits function, you must provide power to
the contacts.

S P E C I F I C C A PA B I L I T I E S

WIRING

N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)

UNDE RS TA N D I N G
S E TP O I N T S

Before you begin programming, make sure you understand setpoints and durations.
A setpoint defines the type of event - ON, OFF or momentary, as
well as the time of the event and the day(s) on which the event
will occur. For example, to turn the lights on at 8: A.M each day
of the week, a setpoint like this would be required: ON 8:00 A.M.,
Mon-Tue-Wed-Thur-Fri-Sat-Sun. Setpoint programming provides
built-in skip-a-day capability; to skip any day(s), simply do not
add the day(s) to the setpoint.
As a simple example, consider the following schedule for turning
lights on and off.
SUN: No lighting required
MON through FRIDAY: Lights ON at 7:30 AM, OFF at 5:30 PM
SAT:On at 7:30 AM, OFF at 12:30 PM
NOTE: When programming, “no” on the display means no event
is required at that setpoint on the particular day. “YES” means an
event is required (either on or off) at that setpoint on that day.
The sample schedule would be arranged as follows:
1st setpoint: required:
(ON at 7:30 AM Monday through Saturday only)
Set as follows - SUN: no
MON through SAT:(YES) ON at 7:30 AM
2nd setpoint: required:
(OFF at 5:30 PM Monday through Friday only)
Set as follows - SUN: no
MON through FRI:(YES) OFF at 5:30 PM
SAT: no
3rd setpoint: required:
(OFF at 12:30 PM Saturday only)
Set as follows - SUN through FRI: no
SAT:(YES) OFF at 12:30 PM

P RO G R A M M I N G
I N S T RU C T I O N S
These timers initially power up in the Clock Format Select Mode.
This mode is only accessible once. If the clock format needs to
be changed, the timer will have to be reset. To reset the timer,
insert a pointed object into the reset hole to the right of the display.

CLOCK FORMAT SELECT mode
STEP
KEY
DESCRIPTION
1.
Apply power to timer. Control displays 12 Hr, indicating 12 hour clock
format.
2.
"
Toggles between 12 hour (AM/PM)
and 24 hour (17:00 = 5:00 P.M.)
clock formats. Choose the format
desired.
3.
ENTER Advances to RUN mode.

SET TIME mode
STEP
1.

2.
3.
4.
5.
6.

KEY
MODE

"
ENTER
"
ENTER
"

DESCRIPTION
Advances to SET TIME mode.
Control displays time with hours
flashing. TOD is also displayed to
indicate that Time of Day is being
set.
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
Day of week begins flashing.
Advance to current day of week, then
go directly to setpoint programming
mode below.

SETPOINT PROGRAMMING mode

TO REVIEW SETPOINTS

(Refer to Understanding Setpoints and your worksheet.)

STEP
1.

KEY
MODE

2.

MODE

3.

"

4.

RUN

STEP
1.

KEY
MODE

DESCRIPTION
Advances from the SET TIME mode
to the SETPOINT PROGRAMMING
mode. The timer displays “1” at bottom of display and “_ _:_ _”. The “1”
indicates that the first of 16 setpoints
is being programmed. The dashes
indicate that this setpoint is clear.
2.
ENTER Display shows “SU” and “no”. This
indicates that Sunday is not included
in the setpoint.
3.
"
Display toggles between “YES” and
“no”. If the event is desired for the
particular day select “YES”, if not
select “no”. Then go to step 4 on next
page.
4.
ENTER Display shows “MO” and “no”. Repeat
steps 3 and 4 to select which day(s)
to include in the setpoint. After programming Saturday, the display will
show the setpoint with the hours
flashing. Dashes in the hour location
indicate that the setpoint is still clear.
5.
"
Advance to desired hour.
6.
ENTER Minutes begin flashing.
7.
"
Advance to desired minute.
8.
ENTER Event type begins flashing.
9.
"
Display toggles between ON and
OFF event types. Choose the type of
event desired.
10.
ENTER Advances to next setpoint. Repeat
steps 2 through 10 to program additional setpoints. When all setpoints
required, are programmed, advance
to steps 11.
11.
RUN
Returns to the RUN mode when programming is complete.
NOTE: Once programming has been completed through
step 11, the display should sow correct Time-of-Day, Dayof-Week and Setpoint status (ON/OFF). If present load
status should be an ON event, but shows as on OFF
event, press ENTER/OVR to turn load ON and to initiate
programmed schedule.

DESCRIPTION
Advances from RUN mode to SET
TIME mode. (TOD displays.)
Advances from SET TIME mode to
SETPOINT PROGRAMMING mode.
The control will display the first setpoint (1 displays at bottom.) To modify the setpoint, go to step 2 of the
SETPOINT PROGRAMMING mode
instructions.
Advance through the remaining setpoints.
Returns to RUN mode when done
reviewing setpoints.

OVERRIDE:
Manual override reverses the current output state. loads
that are ON turn Immediately OFF; loads that are OFF
turn immediately ON. The timer displays OVR to indicate
that the current load state is the result of an override. the
override remains in effect until overridden again or until
the next setpoint is reached. To initiate override, press
OVR (ENTER) key while in the RUN mode.
NOTE: After an override has been initiated the OVR will
display until the next programmed setpoint is reached,
even if the timer is overridden again. Display will show if
the load is on or off.

T RO U B L E S H O OT I N G T I P S
Problem
Nothing happens when a setpoint occurs to turn the load
ON or OFF.
Solution
Review programmed setpoints making sure the day has
not been skipped.
Problem
You wish to clear the control’s memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. remember, the contacts
on these units only switch what is applied to them. (Dry or
isolated contacts.)
Problem
Blank Display
Solution
Check the input power source, insure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time
or entering a setpoint) the control will not update itself.
Press the ENTER key and override the load until the next
scheduled setpoint.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Paragon Electric Canada, Ltd.
5875 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

110-724B

UNDE RS TA N D I N G
S E TP O I N T S

Before you begin programming, make sure you understand setpoints and durations.
A setpoint defines the type of event - ON, OFF or momentary, as
well as the time of the event and the day(s) on which the event
will occur. For example, to turn the lights on at 8: A.M each day
of the week, a setpoint like this would be required: ON 8:00 A.M.,
Mon-Tue-Wed-Thur-Fri-Sat-Sun. Setpoint programming provides
built-in skip-a-day capability; to skip any day(s), simply do not
add the day(s) to the setpoint.
As a simple example, consider the following schedule for turning
lights on and off.
SUN: No lighting required
MON through FRIDAY: Lights ON at 7:30 AM, OFF at 5:30 PM
SAT:On at 7:30 AM, OFF at 12:30 PM
NOTE: When programming, “no” on the display means no event
is required at that setpoint on the particular day. “YES” means an
event is required (either on or off) at that setpoint on that day.
The sample schedule would be arranged as follows:
1st setpoint: required:
(ON at 7:30 AM Monday through Saturday only)
Set as follows - SUN: no
MON through SAT:(YES) ON at 7:30 AM
2nd setpoint: required:
(OFF at 5:30 PM Monday through Friday only)
Set as follows - SUN: no
MON through FRI:(YES) OFF at 5:30 PM
SAT: no
3rd setpoint: required:
(OFF at 12:30 PM Saturday only)
Set as follows - SUN through FRI: no
SAT:(YES) OFF at 12:30 PM

P RO G R A M M I N G
I N S T RU C T I O N S
These timers initially power up in the Clock Format Select Mode.
This mode is only accessible once. If the clock format needs to
be changed, the timer will have to be reset. To reset the timer,
insert a pointed object into the reset hole to the right of the display.

CLOCK FORMAT SELECT mode
STEP
KEY
DESCRIPTION
1.
Apply power to timer. Control displays 12 Hr, indicating 12 hour clock
format.
2.
"
Toggles between 12 hour (AM/PM)
and 24 hour (17:00 = 5:00 P.M.)
clock formats. Choose the format
desired.
3.
ENTER Advances to RUN mode.

SET TIME mode
STEP
1.

2.
3.
4.
5.
6.

KEY
MODE

"
ENTER
"
ENTER
"

DESCRIPTION
Advances to SET TIME mode.
Control displays time with hours
flashing. TOD is also displayed to
indicate that Time of Day is being
set.
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
Day of week begins flashing.
Advance to current day of week, then
go directly to setpoint programming
mode below.

SETPOINT PROGRAMMING mode

TO REVIEW SETPOINTS

(Refer to Understanding Setpoints and your worksheet.)

STEP
1.

KEY
MODE

2.

MODE

3.

"

4.

RUN

STEP
1.

KEY
MODE

DESCRIPTION
Advances from the SET TIME mode
to the SETPOINT PROGRAMMING
mode. The timer displays “1” at bottom of display and “_ _:_ _”. The “1”
indicates that the first of 16 setpoints
is being programmed. The dashes
indicate that this setpoint is clear.
2.
ENTER Display shows “SU” and “no”. This
indicates that Sunday is not included
in the setpoint.
3.
"
Display toggles between “YES” and
“no”. If the event is desired for the
particular day select “YES”, if not
select “no”. Then go to step 4 on next
page.
4.
ENTER Display shows “MO” and “no”. Repeat
steps 3 and 4 to select which day(s)
to include in the setpoint. After programming Saturday, the display will
show the setpoint with the hours
flashing. Dashes in the hour location
indicate that the setpoint is still clear.
5.
"
Advance to desired hour.
6.
ENTER Minutes begin flashing.
7.
"
Advance to desired minute.
8.
ENTER Event type begins flashing.
9.
"
Display toggles between ON and
OFF event types. Choose the type of
event desired.
10.
ENTER Advances to next setpoint. Repeat
steps 2 through 10 to program additional setpoints. When all setpoints
required, are programmed, advance
to steps 11.
11.
RUN
Returns to the RUN mode when programming is complete.
NOTE: Once programming has been completed through
step 11, the display should sow correct Time-of-Day, Dayof-Week and Setpoint status (ON/OFF). If present load
status should be an ON event, but shows as on OFF
event, press ENTER/OVR to turn load ON and to initiate
programmed schedule.

DESCRIPTION
Advances from RUN mode to SET
TIME mode. (TOD displays.)
Advances from SET TIME mode to
SETPOINT PROGRAMMING mode.
The control will display the first setpoint (1 displays at bottom.) To modify the setpoint, go to step 2 of the
SETPOINT PROGRAMMING mode
instructions.
Advance through the remaining setpoints.
Returns to RUN mode when done
reviewing setpoints.

OVERRIDE:
Manual override reverses the current output state. loads
that are ON turn Immediately OFF; loads that are OFF
turn immediately ON. The timer displays OVR to indicate
that the current load state is the result of an override. the
override remains in effect until overridden again or until
the next setpoint is reached. To initiate override, press
OVR (ENTER) key while in the RUN mode.
NOTE: After an override has been initiated the OVR will
display until the next programmed setpoint is reached,
even if the timer is overridden again. Display will show if
the load is on or off.

T RO U B L E S H O OT I N G T I P S
Problem
Nothing happens when a setpoint occurs to turn the load
ON or OFF.
Solution
Review programmed setpoints making sure the day has
not been skipped.
Problem
You wish to clear the control’s memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. remember, the contacts
on these units only switch what is applied to them. (Dry or
isolated contacts.)
Problem
Blank Display
Solution
Check the input power source, insure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time
or entering a setpoint) the control will not update itself.
Press the ENTER key and override the load until the next
scheduled setpoint.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Paragon Electric Canada, Ltd.
5875 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

110-724B

UNDE RS TA N D I N G
S E TP O I N T S

Before you begin programming, make sure you understand setpoints and durations.
A setpoint defines the type of event - ON, OFF or momentary, as
well as the time of the event and the day(s) on which the event
will occur. For example, to turn the lights on at 8: A.M each day
of the week, a setpoint like this would be required: ON 8:00 A.M.,
Mon-Tue-Wed-Thur-Fri-Sat-Sun. Setpoint programming provides
built-in skip-a-day capability; to skip any day(s), simply do not
add the day(s) to the setpoint.
As a simple example, consider the following schedule for turning
lights on and off.
SUN: No lighting required
MON through FRIDAY: Lights ON at 7:30 AM, OFF at 5:30 PM
SAT:On at 7:30 AM, OFF at 12:30 PM
NOTE: When programming, “no” on the display means no event
is required at that setpoint on the particular day. “YES” means an
event is required (either on or off) at that setpoint on that day.
The sample schedule would be arranged as follows:
1st setpoint: required:
(ON at 7:30 AM Monday through Saturday only)
Set as follows - SUN: no
MON through SAT:(YES) ON at 7:30 AM
2nd setpoint: required:
(OFF at 5:30 PM Monday through Friday only)
Set as follows - SUN: no
MON through FRI:(YES) OFF at 5:30 PM
SAT: no
3rd setpoint: required:
(OFF at 12:30 PM Saturday only)
Set as follows - SUN through FRI: no
SAT:(YES) OFF at 12:30 PM

P RO G R A M M I N G
I N S T RU C T I O N S
These timers initially power up in the Clock Format Select Mode.
This mode is only accessible once. If the clock format needs to
be changed, the timer will have to be reset. To reset the timer,
insert a pointed object into the reset hole to the right of the display.

CLOCK FORMAT SELECT mode
STEP
KEY
DESCRIPTION
1.
Apply power to timer. Control displays 12 Hr, indicating 12 hour clock
format.
2.
"
Toggles between 12 hour (AM/PM)
and 24 hour (17:00 = 5:00 P.M.)
clock formats. Choose the format
desired.
3.
ENTER Advances to RUN mode.

SET TIME mode
STEP
1.

2.
3.
4.
5.
6.

KEY
MODE

"
ENTER
"
ENTER
"

DESCRIPTION
Advances to SET TIME mode.
Control displays time with hours
flashing. TOD is also displayed to
indicate that Time of Day is being
set.
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
Day of week begins flashing.
Advance to current day of week, then
go directly to setpoint programming
mode below.

SETPOINT PROGRAMMING mode

TO REVIEW SETPOINTS

(Refer to Understanding Setpoints and your worksheet.)

STEP
1.

KEY
MODE

2.

MODE

3.

"

4.

RUN

STEP
1.

KEY
MODE

DESCRIPTION
Advances from the SET TIME mode
to the SETPOINT PROGRAMMING
mode. The timer displays “1” at bottom of display and “_ _:_ _”. The “1”
indicates that the first of 16 setpoints
is being programmed. The dashes
indicate that this setpoint is clear.
2.
ENTER Display shows “SU” and “no”. This
indicates that Sunday is not included
in the setpoint.
3.
"
Display toggles between “YES” and
“no”. If the event is desired for the
particular day select “YES”, if not
select “no”. Then go to step 4 on next
page.
4.
ENTER Display shows “MO” and “no”. Repeat
steps 3 and 4 to select which day(s)
to include in the setpoint. After programming Saturday, the display will
show the setpoint with the hours
flashing. Dashes in the hour location
indicate that the setpoint is still clear.
5.
"
Advance to desired hour.
6.
ENTER Minutes begin flashing.
7.
"
Advance to desired minute.
8.
ENTER Event type begins flashing.
9.
"
Display toggles between ON and
OFF event types. Choose the type of
event desired.
10.
ENTER Advances to next setpoint. Repeat
steps 2 through 10 to program additional setpoints. When all setpoints
required, are programmed, advance
to steps 11.
11.
RUN
Returns to the RUN mode when programming is complete.
NOTE: Once programming has been completed through
step 11, the display should sow correct Time-of-Day, Dayof-Week and Setpoint status (ON/OFF). If present load
status should be an ON event, but shows as on OFF
event, press ENTER/OVR to turn load ON and to initiate
programmed schedule.

DESCRIPTION
Advances from RUN mode to SET
TIME mode. (TOD displays.)
Advances from SET TIME mode to
SETPOINT PROGRAMMING mode.
The control will display the first setpoint (1 displays at bottom.) To modify the setpoint, go to step 2 of the
SETPOINT PROGRAMMING mode
instructions.
Advance through the remaining setpoints.
Returns to RUN mode when done
reviewing setpoints.

OVERRIDE:
Manual override reverses the current output state. loads
that are ON turn Immediately OFF; loads that are OFF
turn immediately ON. The timer displays OVR to indicate
that the current load state is the result of an override. the
override remains in effect until overridden again or until
the next setpoint is reached. To initiate override, press
OVR (ENTER) key while in the RUN mode.
NOTE: After an override has been initiated the OVR will
display until the next programmed setpoint is reached,
even if the timer is overridden again. Display will show if
the load is on or off.

T RO U B L E S H O OT I N G T I P S
Problem
Nothing happens when a setpoint occurs to turn the load
ON or OFF.
Solution
Review programmed setpoints making sure the day has
not been skipped.
Problem
You wish to clear the control’s memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. remember, the contacts
on these units only switch what is applied to them. (Dry or
isolated contacts.)
Problem
Blank Display
Solution
Check the input power source, insure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time
or entering a setpoint) the control will not update itself.
Press the ENTER key and override the load until the next
scheduled setpoint.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Paragon Electric Canada, Ltd.
5875 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

110-724B

UNDE RS TA N D I N G
S E TP O I N T S

Before you begin programming, make sure you understand setpoints and durations.
A setpoint defines the type of event - ON, OFF or momentary, as
well as the time of the event and the day(s) on which the event
will occur. For example, to turn the lights on at 8: A.M each day
of the week, a setpoint like this would be required: ON 8:00 A.M.,
Mon-Tue-Wed-Thur-Fri-Sat-Sun. Setpoint programming provides
built-in skip-a-day capability; to skip any day(s), simply do not
add the day(s) to the setpoint.
As a simple example, consider the following schedule for turning
lights on and off.
SUN: No lighting required
MON through FRIDAY: Lights ON at 7:30 AM, OFF at 5:30 PM
SAT:On at 7:30 AM, OFF at 12:30 PM
NOTE: When programming, “no” on the display means no event
is required at that setpoint on the particular day. “YES” means an
event is required (either on or off) at that setpoint on that day.
The sample schedule would be arranged as follows:
1st setpoint: required:
(ON at 7:30 AM Monday through Saturday only)
Set as follows - SUN: no
MON through SAT:(YES) ON at 7:30 AM
2nd setpoint: required:
(OFF at 5:30 PM Monday through Friday only)
Set as follows - SUN: no
MON through FRI:(YES) OFF at 5:30 PM
SAT: no
3rd setpoint: required:
(OFF at 12:30 PM Saturday only)
Set as follows - SUN through FRI: no
SAT:(YES) OFF at 12:30 PM

P RO G R A M M I N G
I N S T RU C T I O N S
These timers initially power up in the Clock Format Select Mode.
This mode is only accessible once. If the clock format needs to
be changed, the timer will have to be reset. To reset the timer,
insert a pointed object into the reset hole to the right of the display.

CLOCK FORMAT SELECT mode
STEP
KEY
DESCRIPTION
1.
Apply power to timer. Control displays 12 Hr, indicating 12 hour clock
format.
2.
"
Toggles between 12 hour (AM/PM)
and 24 hour (17:00 = 5:00 P.M.)
clock formats. Choose the format
desired.
3.
ENTER Advances to RUN mode.

SET TIME mode
STEP
1.

2.
3.
4.
5.
6.

KEY
MODE

"
ENTER
"
ENTER
"

DESCRIPTION
Advances to SET TIME mode.
Control displays time with hours
flashing. TOD is also displayed to
indicate that Time of Day is being
set.
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
Day of week begins flashing.
Advance to current day of week, then
go directly to setpoint programming
mode below.

SETPOINT PROGRAMMING mode

TO REVIEW SETPOINTS

(Refer to Understanding Setpoints and your worksheet.)

STEP
1.

KEY
MODE

2.

MODE

3.

"

4.

RUN

STEP
1.

KEY
MODE

DESCRIPTION
Advances from the SET TIME mode
to the SETPOINT PROGRAMMING
mode. The timer displays “1” at bottom of display and “_ _:_ _”. The “1”
indicates that the first of 16 setpoints
is being programmed. The dashes
indicate that this setpoint is clear.
2.
ENTER Display shows “SU” and “no”. This
indicates that Sunday is not included
in the setpoint.
3.
"
Display toggles between “YES” and
“no”. If the event is desired for the
particular day select “YES”, if not
select “no”. Then go to step 4 on next
page.
4.
ENTER Display shows “MO” and “no”. Repeat
steps 3 and 4 to select which day(s)
to include in the setpoint. After programming Saturday, the display will
show the setpoint with the hours
flashing. Dashes in the hour location
indicate that the setpoint is still clear.
5.
"
Advance to desired hour.
6.
ENTER Minutes begin flashing.
7.
"
Advance to desired minute.
8.
ENTER Event type begins flashing.
9.
"
Display toggles between ON and
OFF event types. Choose the type of
event desired.
10.
ENTER Advances to next setpoint. Repeat
steps 2 through 10 to program additional setpoints. When all setpoints
required, are programmed, advance
to steps 11.
11.
RUN
Returns to the RUN mode when programming is complete.
NOTE: Once programming has been completed through
step 11, the display should sow correct Time-of-Day, Dayof-Week and Setpoint status (ON/OFF). If present load
status should be an ON event, but shows as on OFF
event, press ENTER/OVR to turn load ON and to initiate
programmed schedule.

DESCRIPTION
Advances from RUN mode to SET
TIME mode. (TOD displays.)
Advances from SET TIME mode to
SETPOINT PROGRAMMING mode.
The control will display the first setpoint (1 displays at bottom.) To modify the setpoint, go to step 2 of the
SETPOINT PROGRAMMING mode
instructions.
Advance through the remaining setpoints.
Returns to RUN mode when done
reviewing setpoints.

OVERRIDE:
Manual override reverses the current output state. loads
that are ON turn Immediately OFF; loads that are OFF
turn immediately ON. The timer displays OVR to indicate
that the current load state is the result of an override. the
override remains in effect until overridden again or until
the next setpoint is reached. To initiate override, press
OVR (ENTER) key while in the RUN mode.
NOTE: After an override has been initiated the OVR will
display until the next programmed setpoint is reached,
even if the timer is overridden again. Display will show if
the load is on or off.

T RO U B L E S H O OT I N G T I P S
Problem
Nothing happens when a setpoint occurs to turn the load
ON or OFF.
Solution
Review programmed setpoints making sure the day has
not been skipped.
Problem
You wish to clear the control’s memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. remember, the contacts
on these units only switch what is applied to them. (Dry or
isolated contacts.)
Problem
Blank Display
Solution
Check the input power source, insure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time
or entering a setpoint) the control will not update itself.
Press the ENTER key and override the load until the next
scheduled setpoint.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Paragon Electric Canada, Ltd.
5875 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

110-724B

UNDE RS TA N D I N G
S E TP O I N T S

Before you begin programming, make sure you understand setpoints and durations.
A setpoint defines the type of event - ON, OFF or momentary, as
well as the time of the event and the day(s) on which the event
will occur. For example, to turn the lights on at 8: A.M each day
of the week, a setpoint like this would be required: ON 8:00 A.M.,
Mon-Tue-Wed-Thur-Fri-Sat-Sun. Setpoint programming provides
built-in skip-a-day capability; to skip any day(s), simply do not
add the day(s) to the setpoint.
As a simple example, consider the following schedule for turning
lights on and off.
SUN: No lighting required
MON through FRIDAY: Lights ON at 7:30 AM, OFF at 5:30 PM
SAT:On at 7:30 AM, OFF at 12:30 PM
NOTE: When programming, “no” on the display means no event
is required at that setpoint on the particular day. “YES” means an
event is required (either on or off) at that setpoint on that day.
The sample schedule would be arranged as follows:
1st setpoint: required:
(ON at 7:30 AM Monday through Saturday only)
Set as follows - SUN: no
MON through SAT:(YES) ON at 7:30 AM
2nd setpoint: required:
(OFF at 5:30 PM Monday through Friday only)
Set as follows - SUN: no
MON through FRI:(YES) OFF at 5:30 PM
SAT: no
3rd setpoint: required:
(OFF at 12:30 PM Saturday only)
Set as follows - SUN through FRI: no
SAT:(YES) OFF at 12:30 PM

P RO G R A M M I N G
I N S T RU C T I O N S
These timers initially power up in the Clock Format Select Mode.
This mode is only accessible once. If the clock format needs to
be changed, the timer will have to be reset. To reset the timer,
insert a pointed object into the reset hole to the right of the display.

CLOCK FORMAT SELECT mode
STEP
KEY
DESCRIPTION
1.
Apply power to timer. Control displays 12 Hr, indicating 12 hour clock
format.
2.
"
Toggles between 12 hour (AM/PM)
and 24 hour (17:00 = 5:00 P.M.)
clock formats. Choose the format
desired.
3.
ENTER Advances to RUN mode.

SET TIME mode
STEP
1.

2.
3.
4.
5.
6.

KEY
MODE

"
ENTER
"
ENTER
"

DESCRIPTION
Advances to SET TIME mode.
Control displays time with hours
flashing. TOD is also displayed to
indicate that Time of Day is being
set.
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
Day of week begins flashing.
Advance to current day of week, then
go directly to setpoint programming
mode below.

SETPOINT PROGRAMMING mode

TO REVIEW SETPOINTS

(Refer to Understanding Setpoints and your worksheet.)

STEP
1.

KEY
MODE

2.

MODE

3.

"

4.

RUN

STEP
1.

KEY
MODE

DESCRIPTION
Advances from the SET TIME mode
to the SETPOINT PROGRAMMING
mode. The timer displays “1” at bottom of display and “_ _:_ _”. The “1”
indicates that the first of 16 setpoints
is being programmed. The dashes
indicate that this setpoint is clear.
2.
ENTER Display shows “SU” and “no”. This
indicates that Sunday is not included
in the setpoint.
3.
"
Display toggles between “YES” and
“no”. If the event is desired for the
particular day select “YES”, if not
select “no”. Then go to step 4 on next
page.
4.
ENTER Display shows “MO” and “no”. Repeat
steps 3 and 4 to select which day(s)
to include in the setpoint. After programming Saturday, the display will
show the setpoint with the hours
flashing. Dashes in the hour location
indicate that the setpoint is still clear.
5.
"
Advance to desired hour.
6.
ENTER Minutes begin flashing.
7.
"
Advance to desired minute.
8.
ENTER Event type begins flashing.
9.
"
Display toggles between ON and
OFF event types. Choose the type of
event desired.
10.
ENTER Advances to next setpoint. Repeat
steps 2 through 10 to program additional setpoints. When all setpoints
required, are programmed, advance
to steps 11.
11.
RUN
Returns to the RUN mode when programming is complete.
NOTE: Once programming has been completed through
step 11, the display should sow correct Time-of-Day, Dayof-Week and Setpoint status (ON/OFF). If present load
status should be an ON event, but shows as on OFF
event, press ENTER/OVR to turn load ON and to initiate
programmed schedule.

DESCRIPTION
Advances from RUN mode to SET
TIME mode. (TOD displays.)
Advances from SET TIME mode to
SETPOINT PROGRAMMING mode.
The control will display the first setpoint (1 displays at bottom.) To modify the setpoint, go to step 2 of the
SETPOINT PROGRAMMING mode
instructions.
Advance through the remaining setpoints.
Returns to RUN mode when done
reviewing setpoints.

OVERRIDE:
Manual override reverses the current output state. loads
that are ON turn Immediately OFF; loads that are OFF
turn immediately ON. The timer displays OVR to indicate
that the current load state is the result of an override. the
override remains in effect until overridden again or until
the next setpoint is reached. To initiate override, press
OVR (ENTER) key while in the RUN mode.
NOTE: After an override has been initiated the OVR will
display until the next programmed setpoint is reached,
even if the timer is overridden again. Display will show if
the load is on or off.

T RO U B L E S H O OT I N G T I P S
Problem
Nothing happens when a setpoint occurs to turn the load
ON or OFF.
Solution
Review programmed setpoints making sure the day has
not been skipped.
Problem
You wish to clear the control’s memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. remember, the contacts
on these units only switch what is applied to them. (Dry or
isolated contacts.)
Problem
Blank Display
Solution
Check the input power source, insure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time
or entering a setpoint) the control will not update itself.
Press the ENTER key and override the load until the next
scheduled setpoint.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Paragon Electric Canada, Ltd.
5875 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

110-724B



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2001:03:08 14:45:01Z
Modify Date                     : 2001:03:08 14:51:59-06:00
Page Count                      : 10
Creation Date                   : 2001:03:08 14:45:01Z
Mod Date                        : 2001:03:08 14:51:59-06:00
Producer                        : Acrobat Distiller 5.0.5 for Macintosh
Author                          : 
Metadata Date                   : 2001:03:08 14:51:59-06:00
Creator                         : 
Title                           : 110-724B
Has XFA                         : No
EXIF Metadata provided by EXIF.tools

Navigation menu