S3394 (2015 08) Honeywell Water Pump DC3
User Manual: Honeywell Water Pump DC3
Open the PDF directly: View PDF .
Page Count: 5
Download | |
Open PDF In Browser | View PDF |
DC3000 Series Solid State Lead/Lag Controller with DC Fan Control The DC3002 is a 2-unit HVAC lead/lag controller, and the DC3003 is designed to control 3-units. For DC3003, the #3 HVAC unit is always last to operate, while the #1 and #2 units will switch for lead/lag operation. They will work with units with and without economizers, and are designed with the additional feature to control an auxiliary DC Fan system supplied by others. These controllers have an independent pilot duty control relay for purpose of controlling the load control relay (supplied by others) for the DC Fan package, and the user has a choice of designating the DC Fan to be used for emergency ventilation only, for free cooling only, or both. There is also a purge cycle option available that permits the DC Fan package to function periodically to purge the building. The purge length can be from 1 to 10 minutes long in 1-minute increments, and the interval between purge cycles can by from 1 to 24 hours in 1-hour increments — both user selectable. Both DC3002 and DC3003 have a full-featured alarm board with Form C (SPDT) dry contact alarm relays used, offering both NC and NO switching to meet the user’s specific alarm protocol, providing complete flexibility to meets any user’s requirements. All alarm actuations are individually indicated on the controller front panel, along with active stages of cooling or heating, and which unit is currently “lead”. A digital display indicates building temperature and is also used for all of the programming functions. Refer to DC3002 and DC3003 Installation Instruction #2100-484 (latest revision) for complete operation details. Key Design Features Controller: • Electronic (non-mercury) design • Programmable • Works with or without economizers • Dehumidification control option • Auxiliary DC fan control Alarm Boards: • Alarm circuits can be NO or NC logic Ease of Installation: • Powered by 24V from A/C units • Phasing of 24V from units is not required • Durable metal enclosure adequately sized for ease of conduit and wire installation Certifications: • Tested for FCC and CE requirements • EN50082-2 Standard for Immunity • EN55011 Standard for Emissions Controller Models Available DC3002 DC3003 Complete controller system for 2-units Complete controller system for 3-units Remote Sensors – Optional 8612-023A 35-foot sensor, used for both remote indoor and outdoor sensor. Note: 1 of the 8612-023A sensors is required as outdoor sensor for non economizer units if auxiliary DC Fan is to be used for free cooling. Form No. Supersedes Page S3394-815 S3394-114 1 of 5 Feature Selection Guide DC3002 DC3003 2 3 Yes Yes Cooling stages (See Note 3) 4 5 Heating stages (configured for A/C with electric heat) 2 3 Electronic Electronic Digital Digital Stage “On” LED for Cooling and Heating Yes Yes Lead unit LED Yes Yes Advance (switch) lead unit feature Yes Yes One button comfort (72F for 1-hour) feature Yes Yes Local sensor (standard with controller) Yes Yes Remote indoor sensor option (See Notes 1 and 2) Yes Yes Remote outdoor sensor option (See Note 4) Yes Yes Controller locking feature (prevents unauthorized changes) Yes Yes Smoke/fire lockout circuit (shutdown of controller & A/C) Yes Yes Generator run feature (inhibits lag A/C unit operation) Yes Yes Humidity control feature (requires optional humidity controller input) Yes Yes Selectable continuous fan control, lead-both-none (See Note 5) Yes Yes Both fans On @ 5F delta T between 2 sensors (selectable) Yes Yes Control strategy to limit excessive compressor cycling Yes Yes -24V or -48V backup power connection for emergency alarms Yes Yes Power loss alarm relay and LED for all units Yes Yes HP/LP refrigerant lockout alarm relay and LED for all units Yes Yes Smoke/fire alarm relay and LED Yes Yes Low temperature alarm relay and LED Yes Yes High temperature #1 alarm relay and LED Yes Yes High temperature #2 alarm relay and LED Yes Yes 2nd stage cooling alarm relay Yes Yes Controller failure alarm relay and LED Yes Yes Economizer relay (emergency vent strategy) for all units Yes Yes Auxiliary DC Fan pilot duty control relay (load control relay by others) Yes Yes Option to use Auxiliary DC Fan for emergency ventilation Yes Yes Option to use Auxiliary DC Fan for free cooling Yes Yes Option to use Auxiliary DC Fan for purge cycle Yes Yes Number of HVAC units controlled 2-unit lead/lag control (DC3003, Unit #3 is always last) Temperature control type Display (4 character .375" high LCD) Note Note A. B. Note Note Note 1: Optional remote 35-foot space temperature sensors available, Bard PN 8612-023A. Controller automatically detects any connected sensors. 2: Multiple Sensor Control Strategy: If only the standard local sensor is used, it will govern space temperature control along with low and high temperature alarm monitoring. If 1 remote sensor is installed and connected, the temperature readout display and the building temperature are controlled to an average of connected sensors. If there is more than 10F difference between the two sensors, the actual control will be governed by the hottest sensor for cooling and the coldest sensor for heating. 3: Also for use with A/C units that have either 2-stage compressors or units with 2 compressors. 4: Required for non-economizer application if DC Fan is to be used for free cooling. 5: For DC3003, the HVAC #3 blower operates on demand only. Form No. S3394-815 Supersedes S3394-114 Page 2 of 5 Specifications/Features for Basic Controller DC3000 Basic Controller • Input power: 18 to 32VAC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 (or A/C #3 for DC3003) • Isolation circuitry: no line or low voltage phasing required • Backup power: connection for -24VDC or -48VDC (-20 to -56V) allows DC Fan Control and maintains microprocessor operation, front panel indication, and alarm relay operation during commercial power outages • Digital display: 4-character LCD • Temperature display: F or C • HVAC outputs: Form A (NO) relays (1A @ 24VAC) • Cooling control stages: 2 for each A/C unit (4 total), DC3003 has 5 stages total with Unit 3 located on DC3003 alarm board • Heating control stages: 1 for each A/C unit • Dehumidification circuit: requires optional humidity controller as input signal • Locking feature, allows controller to be “locked” so no unauthorized changes to programming can be made • Operating temperature range: 0 to 120F (-18 to 49C) • Storage temperature range: -20 to 140F (-29 to 60C) • Temperature accuracy: +/- 1F from 60-85F (16-30C) +/- 1% outside 60-85F • Lead/lag changeover time: 0 to 30 days • Timing accuracy: +/- 1% • Inter-stage time delay: 10 seconds between stages • Inter-stage differential: 2F (1C) for all modes • On-Off differential: 2F (1C) is standard, 4F (3C) when “excessive cycling” mode is enabled • Cooling set point range: 65 to 90F (18 to 32C) • Comfort setting-Cooling 72F, Heating 68F, for 1 hour • Dead band (difference between cooling and heating set points): 2F to 20F (1C to 10C) • Fire/smoke interface: standard NC circuit jumper, remove for connection to building system control, shuts down both A/C units • Generator run feature, inhibits lag A/C unit from operating if generator is operating (to limit amperage) • Memory: EEPROM for set point and changeable parameters (maintains settings on power loss) • Indoor space temperature sensors: 1 local is standard, will accept 1 optional 25-foot remote sensors. When two sensors are used temperatures are averaged for basic control • Outdoor space temperature sensors: required only in non-economizer application and desire to use Auxiliary DC Fan for free cooling • LEDs for basic controller: Lead unit, Active Cooling stages, Active Heating stages, Dehumidification operation • Six (6) Push-button controls: On/Off switch-Change lead unit-Increase and Decrease set points-Program/Save-Comfort • Controller Enclosure: 20-gauge pre-painted steel, 9.25"W x 13.50"H x 3.00"D, hinged cover, thirteen (13) .875" diameter electrical knockouts Specifications/Features for Alarm Boards DC3002 Alarm Board (Inputs/Outputs) Alarm relays can be wired for NO (close on alarm) or • Refrigerant alarm from A/C #1, input NC (open on alarm) strategy. • Refrigerant alarm from A/C #2, input • Cooling operation signal from A/C #1, input Alarm relays can be used individually if there are • Cooling operation signal from A/C #2, input enough available building alarm points, or can be • Power loss alarm A/C #1, Form C (SPDT) output arranged into smaller groups or even a single group so • Power loss alarm A/C #2, Form C (SPDT) output that all alarm capabilities can be utilized. • Smoke/fire alarm, Form C (SPDT) output When multiple alarms are grouped together and • Low temperature alarm, Form C (SPDT) output issued as a single alarm, there will be no off-site • 1st stage (H1) high temperature alarm, Form C (SPDT) output indication of which specific problem may have nd • 2 stage (H2) high temperature alarm, Form C (SPDT) output occurred, only that one of the alarms in the group has • Refrigerant system lockout A/C #1, Form C (SPDT) output been triggered. The individual alarm problem will be • Refrigerant system lockout A/C #2, Form C (SPDT) output displayed on the LED display on face of the controller. nd • 2 stage cooling alarm, Form C (SPDT) output • Controller system failure alarm, Form C (SPDT) output • Emergency ventilation economizer outputs, Form A (SPNO) for both A/C #1 and A/C #2 o Emergency ventilation option for either air conditioner with refrigerant alarm @ H1 high temp alarm set point o Emergency ventilation option for both air conditioners @ H2 high temp alarm set point • Auxiliary DC Fan control relay, Form C (SPDT) output Note: All alarm/output relays are dry contacts rated DC3003 Alarm Board (Inputs/Outputs) 1A @ 24VAC, 1A @ 30VDC, 0.5A @ 150VDC • All alarm inputs/outputs same as base version above, plus: • HVAC outputs for HVAC #3, Form A (NO) relays (1A @ 24VAC) • Refrigerant alarm from A/C #3, input • Power loss alarm A/C #3, Form C (SPDT) output • Refrigerant system lockout A/C #3, Form C (SPDT) output • Emergency ventilation economizer output A/C #3 o Same sequence as for DC3002 • Also located on DC3003 alarm board are LED’s for A/C #3, 1st and 2nd stage cooling, power loss and refrigerant lockout Form No. Supersedes Page S3394-815 S3394-114 3 of 5 General Programming Overview DC3000 Controller Buttons and Function On/Off Button 1. 2. Press and release the On/Off button to turn On controller, 4-character display will illuminate and Lead unit LED will light. Press and release the On/Off button to turn Off controller. Controller will go dark and A/C units will stop. Comfort Button 1. 2. 3. 4. Press and release the Comfort button to change the Cooling Set Point to 72F and the Heating Set Point to 68F for a period of 1 hour. Set Points will return to the programmed settings automatically after 1 hour. Pressing the Comfort button during the 1 hour period will deactivate the Set Point change. The temperature display will flash the current temperature while in override mode. Program Button 1. 2. Press the Program button and release it when the message “Prog” appears on the display. Refer to Programming Instructions and follow these commands to change from Default settings. Advance/Change/Save Button 1. 2. 3. 4. 5. 6. Press and release the Advance button to swap lead and lag unit positions. When in Program mode the Down and Up buttons are used to scroll through the programming steps. A flashing display means that the particular function of that programming step is “set”, and the display will alternate between the step function and the setting. To change the setting press the Change button and the display will stop flashing, allowing change to the setting. Use Down or Up arrows to change setting as desired, and press the Save button and proceed as desired. When done with programming changes press the Program button until display stops flashing and room temperature is shown. Up and Down Buttons These buttons are used to change the settings in conjunction with the Advance/Change/Save button when in programming mode. Controller Programmable Features and Default Settings Feature Description Range/Choice Default Cooling Set Point 65F to 90F (18C to 32C) 75F (24C) Dead Band (difference between Cooling and Heating Set Points) 2F to 20F (1C to 10C) 10F (5C) Lead/Lag Changeover Time 0 to 30 Days 7 Humidistat Logic Enable (Requires optional humidity controller) Yes/No No Continuous Blower Operation None/Lead/Both Lead Continuous Blower (Both Units) on 5F Delta T (Requires 1 remote sensor) Yes/No Yes Minimum Compressor Off-Delay (3-minutes Lead, 4-minutes Lag) Yes/No No Minimum Compressor Runtime Option (3-minutes) Yes/No No Change Compressor Turn On/Turn Off w/ Excessive Cycling Rate Yes/No Yes Standard On/Off differential is 2F (1C), When Excessive Cycling is Yes the differential is 4F (3C) Low Temperature Alarm Set Point 28F to 65F (-2C to 18C) 50F (10C) High Temperature Alarm #1 Set Point 70F to 120F (21C to 49C) 85F (29C) High Temperature Alarm #2 Set Point 70F to 120F (21C to 49C) 90F (32C) Also DC Fan Set Point for Emergency Ventilation DC Fan Operation (Emergency Vent only, Free Cool only, both) EdcF, Free, Both Both DC Fan On Set Point for Non-Economizer Units (• Requires Outdoor Sensor) 50-55-60 55 DC Fan Used for Building Purge Cycle (Minutes) No,1,2,3,4,5,6,7,8,9,10 No DC Fan Purge Cycle, Interval between Cycles (Hours) 1,2,3,4,5 Up to 24 1 Form No. S3394-815 Supersedes S3394-114 Page 4 of 5 Mounting Hole Layout 9" 1 12" 11 13 32 " 6" 10" 21 1 32 " MIS-3760 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Due to our continuous product improvement policy, all specifications subject to change without notice. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Form No. S3394 August, 2015 Supersedes: S3394-114 Form No. Supersedes Page S3394-815 S3394-114 5 of 5
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Create Date : 2015:08:19 11:00:26-04:00 Keywords : DC, DC3002, DC3003 Modify Date : 2015:08:19 13:31:47-04:00 XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Metadata Date : 2015:08:19 13:31:47-04:00 Creator Tool : Adobe InDesign CS6 (Windows) Instance ID : uuid:e40ee98b-ccb9-4819-9fe2-5ea060ec1612 Original Document ID : xmp.did:50EFE52E8378E3119A57FC8C2F0DE99B Document ID : xmp.id:526AB6A08246E511A42ADB8BDAD637DE Rendition Class : proof:pdf Derived From Instance ID : xmp.iid:516AB6A08246E511A42ADB8BDAD637DE Derived From Document ID : xmp.did:E26A91972740E511903F8F77A388A281 Derived From Original Document ID: xmp.did:50EFE52E8378E3119A57FC8C2F0DE99B Derived From Rendition Class : default History Action : converted History Parameters : from application/x-indesign to application/pdf History Software Agent : Adobe InDesign CS6 (Windows) History Changed : / History When : 2015:08:19 11:00:26-04:00 Format : application/pdf Title : S3394 (2015 08) Description : S Creator : Subject : DC, DC3002, DC3003 Producer : Adobe PDF Library 10.0.1 Trapped : False Page Layout : OneColumn Page Count : 5EXIF Metadata provided by EXIF.tools