10021_SBCC District Standard Specification Sectionsx VR910 SBCC Sections 2014 05 22

User Manual: VR910

Open the PDF directly: View PDF PDF.
Page Count: 19

SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 1 of 19
SANTA BARBARA CITY COLLEGE
DECLARED DISTRICT STANDARDS
The following lists of items are the Declared District Standards and have been reviewed by the
Board of Trustees and are declared as District Standard Materials. Items declared as District
Standards shall be used without exception and no substitutions shall be allowed.
SECTION 075000 MEMBRANE ROOFING
Manufacturer: Tremco
New Roofs: Warranty: Ten year Quality Assurance Plus “Full System” type
with options to extend 15 or 20 year warranty.
Rating: UL Class “A” for entire system.
Testing: FM 4470 for wind uplift to 74 mph min, fire and hail.
Inspections: Manufacturer inspections and preventative
maintenance as follows:
Year 2 and 5 for 10-year QA Plus Warranty.
Year 2, 5 and 10 for 15-year QA Plus Warranty.
Year 2, 5, 10 and 15 for 20-year QA Plus Warranty.
Restored Roofs: Prior Testing: Infrared and/or electrical capacitance scanning
pinpointing any damaged or wet insulation areas.
Membrane core testing limited to tensile strength,
bitumen softening point, amount of interply and flood
coat of bitumen, and asbestos testing.
Warranty: Ten Year Quality Assurance Plus with same
coverage as new roof systems.
Mfr Requirements: Inspections performed by full-time, trained employees of manufacturer
Field inspections during roofing with daily reports issued to SBCC
Final acceptance inspection report issued to SBCC
Have mfr representative available at all times during roofing operation
Provide technical and architectural assistance during warranty term
Provide names & addresses of manufacturer certified roofing contractors
Contact: Jim Gilday 800-524-2067 jgilday@tremcoinc.com
SECTION 081113 HOLLOW METAL DOORS & FRAMES
Doors, General 1” cell kraft honeycomb core
Full height, epoxy-filled mechanical interlock edges
14 gage inverted top and bottom channels
1-3/4” door thickness
Usage Frequency: Extra Heavy Duty
Interior Doors: Cold rolled steel
Exterior Doors: Hot-dip galvannealed steel (A60) or galvanized steel (G90)
Doors (Flush): Exterior Doors: 16 gauge
Interior Doors: 18 gauge
Doors (Stile & Rail): Minimum 5” wide vertical stiles and top rails with no visible seams
Minimum 10” high bottom rail
Exterior and Interior Doors: 16 gauge
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 2 of 19
SECTION 081113 HOLLOW METAL DOORS & FRAMES - continued
Door Frames: Exterior: 14 gauge (hot-dip galvannealed or galvanized)
Interior: 16 gauge
SECTION 084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
Entrance Doors: Minimum 5-1/2” wide vertical stiles and top rails
Minimum 10” high bottom rail
Aluminum Finishes: High-Performance Organic Finish
3-Coat Fluoropolymer Finish Complying with AAMA 2605
70% PVDF Resin by Weight in Color Coat and Clear Topcoat
SECTION 085000 WINDOWS
Windows: District Standard is for aluminum windows. Other materials (fiberglass,
wood, vinyl or steel) are not allowed.
Aluminum Finishes: High-Performance Organic Finish
3-Coat Fluoropolymer Finish Complying with AAMA 2605
70% PVDF Resin by Weight in Color Coat and Clear Topcoat
SECTION 087100 DOOR HARDWARE
General Notes: Deviations must be approved by Director of Facilities & Campus Development
Electric strikes shall include all assoc elec & conduits for functioning system
Deviations in exterior door pulls must be approved by the Director of Security
Deviations from electrified components must be approved by IT Department.
Keying as directed by Director of Admin Services & Director of Security
Work Includes: Mechanical door hardware for swinging and sliding doors.
Cylinders for door hardware specified elsewhere.
Electrified door hardware.
Related Sections: Section 087113 “Automatic Door Operators”
Section 281300 “Access Control” for access control devices installed at
door openings and provided as part of a security system
Hinges: Interior: Ives 3CB1 4.5x4.5 652 Dull Chrome
Exterior: Ives 3CB1 4.5x4.5 630 Stainless Steel NRP
Continuous: Ives 224HD AL at hollow metal & wood doors
Ives 112HD AL at aluminum doors
Continuous hinge height 1” less than door height
Locksets: Office Lock: Schlage ND50 JD Rhodes 626
Entry Lock: Schlage ND53 JD Rhodes 626
Storeroom Lock: Schlage ND80 JD Rhodes 626
Classroom Lock: Schlage ND70 JD Rhodes 626
Privacy Lock: Schlage ND40S Rhodes 626
Passage Set: Schlage ND10S Rhodes 626
Cylinders: Primus High Security: Schlage 20-740 9G
Keypad Locks: Cylindrical: Schlage Electronics CO100 CY KP RHO 626
(Stand-Alone) Mortise: Schlage Electronics CO100 MS KP RHO 626
Rim Panic: Schlage Electronics CO100 993R KP RHO 626
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 3 of 19
SECTION 087100 DOOR HARDWARE – continued
Remote Button: Schlage Electronics PB660
Electric Strikes: Von Duprin 6211 FSE 24VAC
Panic Devices: Exit Only: Von Duprin 99 EO
With Lever Trim: Von Duprin 99L x 996 06 626
Surface Vertical Rod: Von Duprin 9927 EO
Concealed Vert Rod: Von Duprin 9947 EO
Electrified Panics: Add “EL” suffix to part numbers listed above
Door Cord: Schlage Electronics 788-12
Power Transfer: Von Duprin EPT-10 26D
Locking Devices: Rim Cylinder: Schlage 20-057 626 (for panic device)
Mortise Cylinder: Schlage 30-137 626
Deadbolt w/ Thumb: Schlage B660JD 626
Padlocks: Schlage
Door Pulls: Vandal-Resist Pulls: Ives VR910 NL 330 (pull with cylinder)
Ives VR910 DT 630 (dummy pull)
Standard Pulls: Ives 8303-0 4x16 630
Offset Pulls: Ives 8190-0-N 630
Lock Guard: Ives LG-1 630
Door Plates: Push Plates: Ives 8200 4x16 630
Kickplates: Ives 8400 Series 630, 10” high x 2” less than door
width (1” less than door width at non-mullioned pairs)
Door Closers: Interior Inswing: LCN 4040XP REG 689
Interior Outswing: LCN 4040XP RW/PA 689
Exterior Outswing: LCN 4040XP EDA 689
Hold-Open Option: Add “H” to part numbers listed above
High Security Single Door: Schlage Electronics M490
Magnetic Lock: Pair Doors: Schlage Electronics M492
Hardware Mullions: Steel: Von Duprin 4954 x door height
Aluminum: Von Duprin KR1654 x door height
Storage Kit: Von Duprin MT54
Stabilizer: Von Duprin 154
Weatherstripping: Adjustable Type: Pemko 379 DSK head/jambs at exterior doors
Pemko 379 DS head/jambs
Threshold: Pemko 290 DPK threshold stop
Door Stops: Interior (Wall): Ives WS407CCV-630 (reinforce walls as required)
Exterior (Floor): Ives FS18L-BLK
Overhead Stops: Glynn-Johnson 90 series and 100 series
(Use only when floor or wall stops not advisable)
Floor Closers: New Doors: Not allowed
Retrofit Applications: Replace with continuous hinge and closer
Contact: Marc Schwartz 909-610-2539 x2558 marc.schwartz@allegion.com
Allegion, PLC 626-390-0605 cell
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 4 of 19
SECTION 087113 AUTOMATIC DOOR OPERATORS
General Notes: Deviations must be approved by Director of Facilities & Campus Development
Automatic door operators shall include all associated electrical & conduits
for a functioning system
Related Sections: Section 087100 “Door Hardware”
Section 281300 “Access Control” for access control devices installed at
door openings and provided as part of a security system
Auto Operators: Push Side Mount: LCN 9542 REG
Pull Side Mount: LCN 9531STD
Actuator: Wikk Industries 136-3SW TRAN 300M wireless
Receiver: Wikk Industries 1-Channel Receiver
Keyswitch: Schlage 653-04-L2
Power Supply: Single Door: Schlage Electronics PS902
Single w/ Panic: Schlage PS914
Pair w/ Panic: Schlage PS914-2RS
2-Pair w/ Panic: Schlage PS914-4ARL
Battery Backup: Schlage Electronics 900 BBK
ADA Push Button: Battery or hardwire
Contact: Marc Schwartz 909-610-2539 x2558 marc.schwartz@allegion.com
Allegion, PLC 626-390-0605 cell
SECTION 095113 ACOUSTICAL PANEL CEILINGS
General: Fire Resistance: Class A
Light Reflectance: Not less than 0.82
Warranty (30 year): Resistant to visible sag, mold/mildew & bacterial growth
Standard Panels: Square Edge: USG Radar ClimaPlus Panels #2410
(NRC 0.55) (Standard) Armstrong Fine Fissured Panels #1729
Scored Panels USG Radar ClimaPlus Illusion Two/24 Panels #78780
(Special Areas) Armstrong Fine Fissured Panels #1729
Sound Control: Square Edge: USG Radar ClimaPlus Panels #2410
(NRC 0.70) (Standard) Armstrong Fine Fissured Panels #1729
Scored Panels: USG Millenia ClimaPlus Illusion Two/24 Panels #78780
(Special Areas) Armstrong Cirrus Second Look II Panels #513 (NRC=0.65)
Suspension System: USG Donn DX/DXL24 15/16” Exposed Grid Suspension SysteM
Armstrong Prelude XL 15/16” Exposed Grid Suspension System
SECTION 095123 ACOUSTICAL TILE CEILINGS
General: Fire Resistance: Class A
Light Reflectance: Not less than 0.82
Ceiling Tiles: USG Radar ClimaPlus Tiles #2570 or
(NRC 0.45) Armstrong Fine Fissured Tiles #741
12” x 12” x 1/2” or 5/8” with tongue & groove edges for surface application
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 5 of 19
SECTION 096516 RESILIENT SHEET FLOORING
Linoleum Flooring: Forbo Flooring, Inc. (or approved equal)
Marmoleum® Sheet Flooring.
SECTION 096519 RESILIENT TILE FLOORING
Rubberized material is preferred over linoleum but may not be feasible due to project budget
Rubber Flooring: Nora Rubber Flooring; Freudenberg Building Systems, Inc. (or equal).
Noraplan® 24” x 24” Rubber Tile Flooring
SECTION 096813 TILE CARPETING (CLIMATE NEUTRAL MODULAR CARPET TILE)
Manufacturer: Interface FLOR
Product Style: Cubic 1380102500
Color: TBD
Mfr Requirements: At least 15 years of production experience with similar modular carpet
Registration to the ISO 9001/9002 Quality Management System.
Demonstrate environmental responsibility through programs of source
reduction, recycling, reuse and conservation and registration as a submittal
to the ISO 14001 Environmental Management System
Carpet Tiles: Tufted textured loop
Orthogonally ambiguous non repeating pattern for random installation
Gauge to be 1/12th
Soil and stain protection to be Protekt²®
Yarn system to be Type 6.6 or 6 from Aquafil, Universal, Solutia or Invista
Fiber modification ratio equal to or less than 2.5
100% Solution Dyed with post-consumer recycled fiber
30% minimum post-consumer content
50% minimum total recycled content
24 oz/sq yd maximum tufted yarn weight
6000 pile density
50 cm x 50 cm size
Standard backing to be GlasBac® RE Tile
Mill extruded nylon not acceptable
Tile Performance: Modular carpet tile shall meet the following performance standards:
Pill Test Passes
Radiant Panel Test 0.45 watts/cm2, Class 1
Smoke Density: 450 flaming mode
Dimensional Stability: 0.1% change
Static Generation at 70°F: 2.5 kV at 20% R.H
Lightfastness: 4.0 after 60 hours
Crocking: 4.0 wet, dry
Cold Water Bleed: 4
Gas Fade: 4
Ozone Fade: 4
Antimicrobial >95.0% reduction
Fungicidal: No growth
Soil/Stain Protection: >8.0 on Red 40 Stain Scale
California 01350: Passes
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 6 of 19
SECTION 096813 TILE CARPETING – continued
Installation: Tactile installation method preferred with no adhesive to be applied to
sub-floor for installation
Green Requirements: Green Label Plus Certified #GLP0820 Sustainable Carpet
Assessment Standard: (NSF-140) Sustainable Choice Platinum
All existing carpet and existing carpet waste be reused or recycled in an
“environmentally friendly” manner.
Warranty For: Surface fiber wear shall not be more than 10% by weight (no chair pads)
(15 Years Minimum) Static generation at less than 3.0 kV at 70º F, and 20% R.H
No delamination, edge ravel or dimensional instability (i.e., shrinkage,
curling and doming) which adversely affect the ability of the tile to lay flat
Mold warranty
Dyelot mergeability warranty
No damage to sub-floor can occur when carpet is removed
Contact: Phil Botwinick 310-451-4191 Phil.Botwinick@interfaceflor.com
SECTION 099100 - PAINTING
Manufacturer: Dunn Edwards
Primer: ULTRA-GRIP Premium UGPR00 Interior / Exterior Multi-Purpose Primer
Interiors: EVEREST EVER50 Interior Semi-Gloss Paint (Standard Finish)
Exteriors: EVERSHIELD EVSH10 Exterior Flat (Standard Finish)
Doors/Windows: EVERSHIELD EVSH50 Exterior / Interior Semi-Gloss Paint
Contact: Chuck Martin 805-712-0444 chuck.martin@dunnedwards.com
805-570-4401
SECTION 101400 SIGNAGE
Interior ADA Signage: 1/32” Rowmark single ply modified acrylic face plate with text pre-cut out of
face mounted to 1/8” top-painted acrylic back plate. Text will be drop-fitted
into place. Provide raster Grade II Braille at ADA signs. Surface texture to
be matte finish. Mount signs to wall with double-sided foam type at
perimeter of sign.
Interior Non-ADA: 1/16” non-glare acrylic face plate that is backpainted with sub-surface
Signage: engraved, paint filled text. Face plate to be mounted to 1/8” top-painted
acrylic back plate. Surface texture to be matte finish. Mount signs to wall
with double-sided foam type at perimeter of sign.
Interior Sign Colors: Base Color: Rowmark ADA Alternative, 3X1-302 China Blue (matte)
Text/Graphics: Rowmark ADA Alternative, 3X1-204 Bright White (matte)
Parking Signage: Minimum 1/8” aluminum sheet with semi-gloss baked enamel or two-
component acrylic polyurethane finish, mounted to galvanized steel posts.
Provide beaded porcelain enamel finish at reflectorized signs.
Base Color: 557 Imperial Blue
Text/Graphics: 02 White
Logos & Graphics: Information regarding college logos, colors and other official graphics can
be obtained at http://www.sbcc.edu.marketing/
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 7 of 19
SECTION 101419 DIMENSIONAL LETTER SIGNAGE
Dimensional Letters: Individual dimensional letters, stud mounted to wall. Painted aluminum cut
in Helvetica Medium font type, ¼” thick with ¼” alum offset collars.
Letter Color: Medium Bronze face and return
Offset Color: Natural finish
SECTION 102113 TOILET COMPARTMENTS
Manufacturer: Bradley Mills Partitions (or approved equal).
Toilet Compartments Sentinel Series 400 overhead-braced restroom compartments
Urinal Screens Model No. 3 floor-anchored urinal screens.
Material &Finish: 5WL Textured stainless steel finish.
Hardware: Continuous SS spring-loaded hinges.
Continuous SS U-brackets at walls and pilasters.
SS surface-mounted ADA compliant slide latch & keeper.
Doors 32” to have combination coat hook/door bumper.
Doors >32” to have separate coat hook, door bumper and door pull.
SECTION 102800 TOILET AND BATH ACCESSORIES
Electric Hand Dryer: Dyson Airblade Model AB14
(@ Public RR only) Polycarbonate-ABS casing in gray finish with anti-microbial additive
Input Voltage: 110-120V AC, single phase 60 Hz
Rated Power: 1400W, 12.0A
Standby Power Consumption: 1W
Energy Consumption per Dry: 0.00468kwh
Towel Dispenser: Bobrick B-39167 Recessed Convertible Touch-Free Paper Towel
(@ Individual RR) Dispenser and Waste Receptacle (18 gallon)
Toilet Tissue Kimberly Clark Model JRT 09612
Dispenser: Jumbo Roll Tissue Dispenser
Seat Cover Georgia-Pacific Model 57710
Dispenser: Safe-T-Gard ½ Fold Seatcover Dispenser, White
Sanitary Napkin Rubbermaid Model 6140
Disposal: Sanitary Napkin Receptacle with Rigid Liner, White
Soap Dispenser: Spartan Model 9751 Lite ‘n Foamy Dispenser, White
ADA Toilet Bobrick B-3888 (or approved equal) for fully recessed wall installation.
Tissue Dispenser: Bobrick B-386 (or approved equal) for 2-sided partition installation.
ADA Sanitary Bobrick B-353 (or approved equal) for fully recessed wall installation.
Napkin Disposal: Bobrick B-354 (or approved equal) for 2-sided partition installation.
Framed Mirror: Bobrick B-165 (or approved equal)
Frameless mirrors should not be specified.
Clothes Hook: Bobrick B-233 Clothes Hook (or approved equal).
Locate near lavatories for hanging purses/backpacks.
ADA Lavatory and: IPS Corporation, TrueBro LavShield protective lavatory enclosure.
Sink Guards: IPS Corporation, TrueBro BasinGuard undersink protection.
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 8 of 19
SECTION 115213 PROJECTION SCREENS
Manual Screens: Draper Luma2 Front Projection Screen (or equal)
SECTION 115216 PROJECTOR MOUNTS
Manufacturer: Business Machine Security (www.LocDown.com)
Drop Ceiling Plate ADJ-DCP 824
Adjustable mounting bracket plate installed above suspended acoustic tile
with security cable and hanger wire support system to attach ceiling plate to
structure above
Maximum Load: 60 lbs.
Clg Projector Mount: LCD LOC II Universal Mount
Two interlocking steel trays to provide security and stability for LCD/DLP
projectors. ±15° tilt, pitch, roll adjustments and 360° swivel
Maximum Load: 150 lbs
Color: Projector Grey (standard)
Locking: High-security, pick resistant, five wafer, cylindrical screw type key lock at
Drop Ceiling Plate and Projector Mount, keyed alike
SECTION 129300 SITE FURNISHINGS
Benches: DuMor, Inc.11 Series PL, 6’-0” long bench with “Cedar” recycled plastic
slats withType S-1 mounting (18” deep support posts mounted in concrete)
Bicycle Racks: Peak Racks, Inc. (www.PeakRacks.com)
Campus Racks single or double-sided hot-dipped galvanized bike racks.
SECTION 129323 TRASH AND LITTER RECEPTACLES
Exteriors: Wausau Tile Precast Concrete Waste Container with security cable assembly
Base: Model TF1875 with Weatherstone Sand B-3 finish
Lids: Model TF1476 custom plastic double-sided dome top
Trash: Brown 4 with custom “Landfill” mark-it logo one side
Recycling: Blue 0 with custom “Recycling” mark-it logo one side
Liner: Model 750153 (36 gallon) plastic liner
Corridors & Forms + Surfaces Model SLTRD-24L
Public Spaces: Triad Litter and Recycling Receptacle
Color & Finish: Stainless Steel with Diamond Finish
Lids: Black plastic with trapezoidal lid opening
Graphics: Black background with custom text “Landfill”
Blue background with standard text “Recycling”
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 9 of 19
SECTION 142400 HYDRAULIC ELEVATORS
Manufacturer: Republic Elevator Company or approved equal
Elevator Type: Single direct acting hydraulic cylinder in well holes
Rated Speed = 125 feet per minute
Main Power Supply = 208 Volts, 3 phase, with separate equipment
grounding conductor
Operation: Nonproprietary programmable microprocessor-based controller (Motion
2000 by Motion Control Engineering or approved equal) with automatic
operation by means of car and hall buttons.
SECTION 232500 HVAC WATER TREATMENT (FOR NEW SYSTEMS ONLY)
Manufacturer: Chem-Aqua is preferred water treatment vendor and should be consulted
for all projects that have mechanical water treatment requirements.
System Cleaner: Chem-Aqua 61502 (sufactants, metasilicate, polyphosphate) at 2.5 gal per
(No Aluminum or) 1000 gal of system volume, and Chem-Aqua 11000 at 1 gal per 1000 gal of
Galvanized Mtl) system water. Add FC-101 defoamer as needed. Circulate 12-24 hrs then
drain and flush system.
Iron Dispersant: Chem-Aqua CBD-95 at 1 gal per 1000 gal of system volume; circulate for 2
days then drain and flush system thoroughly
System Passivation: Refill system, add Chem-Aqua 11000 at 1 gal per 1000 gal system volume.
Circulate for 5-7 days. Drain and flush system.
Recharge System: Use corrosion and scale inhibitor Chem-Aqua 999/777 sodium nitrite.
By-Pass Pot Feeder Chem-Aqua-Aqua Pass Pot feeder w/filter 5 gallon capacity. Isolation
valves and drain valve for pot feeder will be needed.
SECTION 224213 COMMERCIAL WATER CLOSETS AND URINALS
Toilet: American Standard - Madera – ADA – Floor mounted – White
Model 3465.001 elongated, top spud with 4 bolts
Toilet Seat: Olsonite model 95SSCT open front – no cover
Toilet Flush Valve: Sloan Optima, 1.28 GPF, sensor operated
Model 111-1.28 ES-S TMO hard wired w/ transformer for new construction
Model 111-1.28 SMO battery powered for remodels
Urinal: American Standard – Washbrook – ADA – White
Model 6590.001, top spud.
Urinal Flush Valve: Sloan Optima, 1.0 GPF, sensor operated
Model 180-1.0 ES-S TMO hard wired w/ transformer for new construction
Model 180-1.0 SMO battery powered for remodels
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 10 of 19
SECTION 224216 COMMERCIAL LAVATORIES AND SINKS
Lavatories: American Standard – ADA – White
Wall-mounted with concealed arms or wall hanger
8” Centers: Lucerne Model 0356.015 wall-mount lavatory (District Standard)
Murro Model 0958.900.020 wall-mount lav w/ shroud/knee contact guard
4” Centers: Lucerne Model 0355.012 wall-mount lavatory (District Standard)
Murro Model 0954.900.020 wall-mount lav w/ shroud/knee contact guard
Single Hole: Lucerne Model 0356.421 wall-mount lavatory (District Standard)
Murro Model 0955.000 wall-mount lavatory less shroud (Optional)
(for installation with Dyson Airblade Tap Combo Hand Dryer/Faucet only)
Faucets: Chicago Faucets
8” Lav Faucet: Model 404-VE2805-665ABCP, 0.5 gpm, metering, dual supply temperature,
8” centers, less than 0.25% total lead content
4” Lav Faucet: Model 3500-4E2805ABCP, 0.5 gpm, metering, single supply temperature,
4” centers, less than 0.25% total lead content
Lab Faucet: Model 930CP dual temperature faucet with GN2BVBJKABCP 6” gooseneck
spout with vacuum breaker, single hole, 204PR handles and E7 serrated
nozzle outlet (Note: Does not meet ADA requirements)
SECTION 224700 DRINKING FOUNTAINS AND WATER COOLERS
Water Cooler with Elkay EZH20 bottle filling station with bi-level filtered LZ cooler
Bottle Fill Station: Model LZSTL8WSLK. Provide #51300C_3PK 3-pack replacement filters
SECTION 230000 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)
Chillers: Trane, York, McQuay
Air Handlers: Catalog: Trane, York, McQuay
Custom: UMP, Temtrol, Haakon
DX Unitary Packaged Rooftop Units: Trane, York, McQuay
Commercial Split and Packaged Rooftop Units: Trane, York, McQuay
VRF (Variable Refrigerant Flow) Systems: Mitsubishi, Trane
Make Up Air Units: Greenheck, UMP, Modine
Variable Air Volume (VAV) Units: Trane, York, McQuay
Unit Ventilators: Trane, York, McQuay
Blower Coil Air Handlers: Trane, York, McQuay, Magic Aire
Make Up Air Gas Heating Systems: Reznor, Modine
Boilers: Lochnivar (standard)
Raypak (if required due to size limitations)
Variable Frequency Drives (VFDs): Johnson for new equipment & replacement drives
Valves and Actuators: Belimo or Johnson
Elodrive waterproof type (for exposed to weather
applications)
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 11 of 19
SECTION 250000 ENERGY MANAGEMENT SYSTEM (EMS)
Backbone System: JCI Metasys Field Devices
JCI Facility Explorer FX 60/90 Building Supervisory Panels
JCI NAE controllers not allowed
Johnson DDC DX-9100 Controller for Lighting System at each building that
controls outdoor lighting via time schedule in FX server and light sensor
connected to controller
Software: Niagara AX Platform using FX workbench software connected to existing
campus-wide Ethernet network to be installed on owner-provided PC
Field Devices –WGX9100, CCT Software
All Software and Devices must be approved by SBCC
Scope of Work: Provide and install all necessary conduit, wire, controllers, testing,
programming, commissioning and interfacing to supervisory controllers.
All new equipment to be interfaced with back bone system
All FX supervisory panels will be programmed using complete
commissioned field DDC controller software
Points for each building’s controller will be mapped to that building’s FX
supervisory panel which will be mapped to campus-wide FX server.
System to automatically activate backup lighting schedule if network to
controller from FX panel fails
Provide separate data screen and separate graphic screen for each piece
of equipment controlled by the DDC, also provide project floor plan
graphics with schematics. All to match existing graphics at campus.
Control Points: Air Moving Devices and Equipment
Air Control Devices and Equipment
Liquid Moving Devices and Equipment
Liquid Control Devices and Equipment
Package Single Zone AC w/ Gas Heat (CAV)
Reheat or HW Heating Coils
Variable Speed Drives w/ Electronic Bypass
Electric Radiant Heaters
EMS not required at Fans < 5 HP, Evaporative Coolers, Air Compressors,
Kitchen Equipment or Domestic Hot Water Heaters
SECTION 260000 ELECTRICAL
Manufacturer: Square D Products
Items: Main High Voltage Switch Gear (4160)
Main Electrical Distribution Systems (I line, NF, NQ (bolt on) panels)
Lighting Contactors (277V and 120V coils)
Transformers (EE type, K-rated where required)
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 12 of 19
SECTION 265100 LIGHTING
Classroom Lighting: Focal Point Equation 2x4 Fixture or
Ledalite PureFX 2x4 Fixture
Lamps: LED lamps with CRI>80 are encouraged where available and within budget
Fixtures using 4' T8 lamps are preferred where LED is not practical
4' T8 Lamps with SP41 Color are stocked on site & preferred for interiors
High efficacy specialty lamps, such as T5HO, may be used in applications
where LED and T8 are not practical (such as coves or large, high ceiling
spaces where LED can't be made to work)
Low efficacy Incandescent/Halogen/MR16/PAR lamps are discouraged
except where needed for specific applications
Fluorescent dimming is discouraged. LED (if no low end is required) or
incandescent (for extremely low light levels) is preferred - minimize the
amount of dimming through stepped switching where possible
Exterior lighting is being converted to LED, and all new exterior lighting
should be LED
Lighting Controls: Watt Stopper, dual technology motion sensors:
1. Ceiling sensors with wall manual control for large areas
2. Wall mounted, dual switched wall plates for small rooms and offices
Exit Signs: Depending on application, three types are allowed. All signs shall have
green lettering (or background for the tritium based signs)
Specification grade, brushed aluminum face, LED lighting with battery
backup and self-diagnostics (equal to Lithonia LES series)
Specification grade, mirrored glass(acrylic), LED lighting with battery
backup and self-diagnostics (equal to Lithonia LRP series)
Tritium based, self-luminous with green faceplate, 20 year life minimum
(equal to Isolite SLX-60 series)
Exterior Pole Lights: Gardco Pole Lights, Hardtop, MP or Side Mount
8’, 10’, 15’, or 25’ Poles with BRA Finish
LED or HPS Lamp, if no LED option, Multi-Tap, Mogal Base
Bega Model 8878P Poles and Fixtures (Single or Twin Fixture)
Bega Model 890C Anchorage
Exterior Decorative: Teka, various styles
Bega, various styles
Exterior Wall Packs: Hubbell, various styles, with LED Lamps (HPS if LED not available)
Step/Walk Lights: Devine
Contacts: Mar Vista Sales
Steve Dominguez 805-642-7714 steve@marvistasales.com
Prudential
Dave Relyea 805-598-3973 drelyea@plpnorth.com
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 13 of 19
SECTION 270000 DATA AND VOICE COMMUNICATIONS, GENERAL
Data Closets: Provide minimum of one data closet per floor
All computers wired to data closet on same floor
Data closets to be on generator circuit for emergency power
Data closets to be air conditioned
A/C to switch to emergency power during outages
Cable TV: Cable and satellite TV to tie into head end at Administration Building
Data at Offices: Provide one duplex data jack at every power outlet in offices
Telephones: All telephone wiring to be Cat6 cabling run over the data network
Provide one 25-pair copper phone line from each building to phone room in
Administration Building.
Emergency announcements made over phone system (no separate PA)
Provide one telephone at each instructor station and office
Contact: SBCC IT Department
Paul Bishop 805-965-0581x2213 pwbishop@sbcc.edu
SECTION 271113 COMMUNICATIONS ENTRANCE PROTECTION
Protector Panels: Commscope/Systimax (489 type)
Circa (189 type) or prior approved equal
SECTION 271116 COMMUNICATIONS CABINETS, RACKS, FRAMES & ENCLOSURES
Rack-Mounted Provide at equipment rack/cabinet locations
Fiber Enclosures: Commscope (RFE-FXC/RFE-FXD products)
Leviton (Lightspace DPS/DPC products)
OFS (LST/LSS products)
Wall-Mounted Provide in basement of Administration Building
Fiber Enclosure Leviton (Lightspace CPC-48)
or equivalent products by Commscope or OFS
Cabinets: Dell PowerEdge 4210 (or approved equal)
Racks: Chatsworth (55053-703)
Cooper B-Line (SB-556-084-XUFB)
Hoffman (E-DR19FM45U)
SECTION 271119 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
Manufacturers: Amp
Hubbell
Panduit
or prior approved equal
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 14 of 19
SECTION 271123 COMMUNICATIONS CABLE MANAGEMENT AND LADDER RACKS
Vertical Cable Chatsworth (30163-703 for 10”, 30162-703 for 6”)
Management: Panduit (PatchRunner™) or prior approved equal
Horizontal Cable Chatsworth (30330-719)
Management: Systimax (HCM2U)
or prior approved equal
Patch Panel Wire 19” rack mountable
Management: Chatsworth (12176-701) or equal from patch panel manufacturer
Ladder Rack: Chatsworth (11275-718)
Cooper B-Line (SB-17-18-FB)
Mono-Systems (MR-17T-18-PB)
SECTION 271126 COMMUNICATIONS RACK MOUNTED POWER PROTECTION AND
POWER STRIPS
Power Strips: Chatsworth (12816-705) or approved equal
SECTION 271313 COMMUNICATIONS COPPER BACKBONE CABLING
Underground Voice Superior Essex (09-097-02)
Backbone Cabling: Or equivalent by Belden or General Cable
Plenum Voice Superior Essex (18-599-33)
Backbone Cabling: or equivalent by Berk-Tek or General Cable
SECTION 271323 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLE
Fiber, General: Provide 50/125µm multi-mode optical fiber backbone cabling to each
building that terminates in NW corner of Administration building basement
Fiber Cabling: Exterior Cabling: Corning Commscope O-012-LA-5K-F12NS (or equal)
(Multi-Mode) Interior Cabling: Corning Commscope P-012-DS-5L-FSU-AQ (or equal)
(Adjust product numbers according to strand counts as required)
Fiber Cabling: Exterior Cabling: Corning Commscope O-012-LA-8W-F12NS (or equal)
(Single-Mode) Interior Cabling: Corning Commscope P-012-DS-8W-FSU-YL (or equal)
(Adjust product numbers according to strand counts as required)
SECTION 271513 COMMUNICATIONS COPPER HORIZONTAL CABLING
Product: Category 6A cable utilized for horizontal voice and data cabling
Manufacturers: ADC (10G-A6TP-WT02)
Hubbell (DBASPW)
or equivalent by AMP or Belden
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 15 of 19
SECTION 275313 CLOCK SYSTEMS
Manufacturer: Visiplex
Clocks: 14” Wireless Synchronized Analog Clock with Custom SBCC Logo Face
Model TS-CLK-1462S
Transmitter: Model TS101-100
Wireless Encoder: Model TS2800
Contact: Simplex Grinnell
Jim Faltemier 805-642-0366 jfaltemier@simplexgrinnell.com
SECTION 281300 ACCESS CONTROL
Section Includes: Access control devices installed at door openings and provided as part of a
security system.
1. A complete access control system as described in the Specifications
and as detailed on the Drawings
2. Complete system is defined as all work required to install the access
control system described herein and on the Drawings including, but
not limited to: all electrical, conduit, conduit stubs, cables, cabling,
connectors, terminations, risers, back boxes, junction boxes, security
junction boxes, security terminal cabinets (STC), card readers,
Integrated Card Reader Locksets, system software licenses, alarm
contacts, controllers, access control panels, power supplies,
transformers, power distribution boards, batteries, enclosures, tamper
switches, latches and locks, mounts, electrified door hardware and
connection to electrified door hardware
Related Sections: Section 087100 “Door Hardware”
Section 087113 “Automatic Door Operators”
Software: Wireless locks programmed for use with Allegion Blackboard Transact
Electronic Locks: Wireless Cylindrical: Schlage AD-400-CY-MT-50-JD RHO
(Networked) Wireless Mortise Schlage AD-400-MS-MT-50-JD RHO
Wireless Rim Panic: Schlage AD-400-993R-MT-50-JD RHO
Wireless SVR Panic: Schlage AD-400-993S-MT-50-JD RHO
For Hard-Wire Locks: Substitute “300” for the “400” series listed above
Com Cover w/ IPB: Schlage Kit #46928875 for AD-400-CY locks, converts
function from 70 “Classroom/Storeroom” to 50 “Office”
Infa-Red Scanner: Schlage Electronic Scan II White/Black.
Door Position Switch: Schlage Electronics 679-05 HM/WD.
Controllers: Master Controller: Blackboard SA 3000.
Door Controller: Blackboard SA 3032, 1 for each hard-wired door.
Provide SA series power supply and enclosure
Card Reader: Blackboard DR4100 Hybrid Door Reader - Sony FeliCa contactless ISO
18092 compliant with 3-track HiCo mag stripe read head
IR Panel Interface Schlage PIM 400-485
Module (PIM):
Electric Latch (EL) Retrofit/Conversion: Von Duprin EL Kit, 3 feet or 4 feet
Retraction Kits: For New Work: Von Duprin Computer Lock, CL993
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 16 of 19
SECTION 281300 ACCESS CONTROL – continued
IR Power Supply: For Panic Devices: Von Duprin PS914-2RS
For Doors Operators: Von Duprin PS914-4RL
Contact: Integrated Door Systems
Bob Simpson (805) 693-9299 (805) 693-9719 fax
SECTION 281600 INTRUSION DETECTION SYSTEM
Control Panel: Digital Monitoring Products (DMP)
Model XR500 Series 574-Zone Command Processor Panel
Keypads: Digital Monitoring Products (DMP)
Series 7000 Thinline LCD Keypad
Door Contacts: Sentrol 1078 Series
GE 1078/1076 Series
Contact: Bay Alarm Company
Rick Prinz 805-662-2714 rick.prinz@bayalarm.com
SECTION 282300 VIDEO SURVEILLANCE SYSTEM
Camera & Housing: Bosch VDN-495 Series
Camera Power: Altronix ALTV2316350
DVR: Bosch DiBos Model DB30C5160R2
Monitor/Keyboard: Orion 17RTC in Rack Mounted Assembly
17” LCD with 1280 x 1024 Resolution with Built-In Speakers
NTSC/PAL Video System
Multiple Video Input/Output (2 BNC, 1 S-Video),
VGA, Component and HDMI Input
Contact: Bay Alarm Company
Rick Prinz 805-662-2714 rick.prinz@bayalarm.com
SECTION 283100 FIRE DETECTION AND ALARM
Manufacturer: Simplex Grinnell
Equipment: 4100-9111 FACP Panel and Cabinet
4010-9101 FACP Panel
4098-9714 Smoke Detector (addressable, requires 4098-9792 base)
4098-9733 Heat Detector (addressable, requires 4098-9292 base)
4098-9751 In-Line Duct Detector (for usage with smoke/fire dampers)
4098-9756 Tube-Style Duct Detector (for usage on HVAC equipment)
4090-9001 Addressable IAM Monitor Module (for sprinkler connections)
4090-9002 Addressable Relay Module (for elevator recall connections)
4096-9101 Multi-Candela Strobe (typical, various types available)
4096-9128 Multi-Candela Horn/Strobe (typical, various types available)
Contact: Jim Faltemier 805-642-0366 jfaltemier@simplexgrinnell.com
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 17 of 19
SECTION 323000 SITE IMPROVEMENTS
Skate Stops: Required on all site walls and curbs accessible to skateboarders
Exact locations to be determined by project team
Manufacturer: Skatestoppers by Intellicept
619-447-6374
www.skatestoppers.com
New Concrete: F2 Series, aluminum
(Cast-In-Place) ½” radius trowel maximum and ½” chamfer maximum
Existing Concrete: FA Series (fixed angle), aluminum
(Surface Mount) FR Series (fixed radius), aluminum
Masonry/Precast: Insert Series
Cast Bronze with brown patina or White Tombasil (white brass)
SECTION 320523 CEMENT AND CONCRETE FOR EXTERIOR IMPROVEMENTS
(COLORED CONCRETE FOR SIDEWALKS, STAIRS & PLANTERS)
Manufacturer: Solomon Colors, Inc. (or approved equal)
866-747-2656
www.solomoncolors.com
Color Pigment: SGS Integral Colors Dry Pigment Ready Mix
Color: 750 Desert Tan
Field Mockup: Provide at least one mockup to verify match to existing colored concrete
SECTION 321413 PRECAST CONCRETE UNIT PAVING
Manufacturer: Belgard / Sierra Building Products
909-355-6422 / 866-749-3038
www.belgardcalifornia.com
Concrete Pavers: Cambridge Collection untumbled interlocking concrete pavers
I-Pattern (75% rectangular, 25% square)
2-3/8” x 5-7/8” x 7-7/8” rectangular
2-3/8” x 5-7/8” x 5-7/8” square
Colors: 60% Bella Blend, 20% Toscana Blend, 20% Sahara Blend
Local Distributor: Stoneyard Building Materials
805-962-9511
www.stoneyardbuilding.com
SECTION 321726 TACTILE WARNING SURFACING
Manufacturer: Wausau Tile (or approved equal)
Warning Tiles: ADA-3 Pavers, nominal 12 by 12 inches square with 1.67-inch spacing
straight dome pattern.
Color: ADA-70
Contact: Jeff Wren 909-628-4296 wrenco@live.com
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 18 of 19
SECTION 328400 PLANTING IRRIGATION
Controllers: Rainmaster RME (or equal)
Valves: Rainbird EFA-CP, brass
Rainbird EFA-CP-PRS, brass
Superior Mod 950, brass
Wire: 14 gauge minimum
Where multiple controllers are used, color code each common wire and use
different color control wires
Pipe: Main lines shall be Class 315 PVC for pipes 2” and larger
Main lines shall be Schedule 40 PVC for pipes 1-1/2” and smaller
Lateral lines shall be Schedule 40 PVC
Sleeves shall be Schedule 40 PVC
All pipe shall be colored appropriately according to supply source
Backflow Device: Shall be on approved list of Water Agency
Master Valves: Hardie 102 Series or 123 Series as required
Quick Couplers: Nelson 1” Model 7642, 7643, 7644 and 7655
Booster Pumps: Constant-Flow by Southern California Pump Sales (or equal)
Great Valves: Nibco T-113 or Equal, brass
Wire Connectors: 24 Volt - Rainbird “Snap-Tite” (or equal)
Backflow Enclosure: Strong Box SS (or equal)
Pressure Regulators: Wilkins 500 Series (or equal)
Irrigation, General: For all areas under 5’ x 5’ pop bubblers or drip are the preferred delivery
method. All future or retro-fitted planting beds should use bubblers.
All sprinkler applications must minimize surface water runoff and provide
head-to-head coverage. MP rotors should be considered first and used
whenever possible.
Heads: Hunter MP Rotator 1000, 2000 and 3000 Series
Hunter 1-40 Rotors
Hunter 1-20 Rotors
Toro 300 Series
Rainbird 1800 Series SAM-PRS
Rainbird 1402 Bubblers
Rainbird 5000 PRS Series
SECTION 329200 TURF AND GRASSES
Turfgrass Sod: Southland Sod Marathon II Sod, Dwarf Tall Fescue
SBCC DECLARED DISTRICT STANDARDS 05/22/2014
Page 19 of 19
SECTION 329300 PLANTS
General Planting: Do not use plants on the Cal-IPC invasive plants list. For reference:
http://www.cal-ipc.org/ip/inventory/pdf/Inventory1999.pdf
Special Trees: The following are a list of trees that can not be planted without special
exemption from the College:
Eucalyptus sp
Corymbia sp
Pinus Pinea
Washingtonia sp
Ceratonia sp
Platanus acerifolia
Ficus sp
END OF DISTRICT STANDARDS