Service Event Codes 4 Digits
User Manual: Home
Open the PDF directly: View PDF .
Page Count: 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
1900
Mains voltage (feed phase) exceeds
measuring range
Disconnect converter immediately from mains and DC generator;
make sure that connection was not established between 2 phases.
x
1910 DC voltage too high
Check layout and stringing (2 strings in series instead of parallel?)
Measure DC voltage before connecting to the converter. Disconnect
from DC generator immediately
x
1920 Polarity of DC connection reversed Correct polarity of the strings. x
1930 Insulation resistance too low
Check insulation of the generator against earth (animal bite on cable,
pinched cable, damaged modules,...).
x
1940 internal short circuit
Converter needs to be exchanged. Send repair request to PLATINUM
service.
x
1950 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11010 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11020 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11060 internal system error
Converter needs to be exchanged. Send repair request to PLATINUM
service.
x
11061 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
11062 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
11063 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
11070 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11080 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Cause
Seite 1 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
1081 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1082 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1083 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1084 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1085 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1086 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1087 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1088 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1089 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
1090 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11100 Relay error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11110 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11120
Frequency measuring not plausible
(poss. bouncing mains voltage)
Check all contact points (tight fit of screws) on the mains side from the
converter to the connection point (also automatic cut-outs)
x
11130 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 2 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
11140 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11200 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11210 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11220 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11250 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11270 internal system error Perform reconfiguration, set correct country code x
11290 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11300
Connection phase (L) and neutral
conductor (N) switched (or bad PE
connection)
Set connection phase L and N correctly, check PE connection from
converter to feeding point.
Measure voltage between L1 and N
x x
11310 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11340 Country code not yet set Set country code, poss. perform reconfiguration (service menu) x
11350 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11380 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11400 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11401 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 3 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
11410 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11420 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11500 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
11510 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22010
Voltage limit for feeding amplitude (L1)
exceeded
Check feeding phase for contact resistance/transition resistance, poss.
contact mains operator if voltage is generally too high
x
22011
Voltage limit for feeding amplitude (L1)
undercut
Check feeding phase for contact resistance/transition resistance, poss.
contact mains operator if voltage is generally too low
x
22012
Voltage limit for amplitude (L2)
exceeded
Check phase for contact resistance/transition resistance, poss. contact
mains operator if voltage is generally too high
x
22013
Voltage limit for amplitude (L2)
undercut
Check fuse phase L2, poss. contact mains operator if voltage is
generally too low
x
22014
Voltage limit for amplitude (L3)
exceeded
Check phase for contact resistance/transition resistance, poss. contact
mains operator if voltage is generally too high
x
22015
Voltage limit for amplitude (L3)
undercut
Check fuse phase L3, poss. contact mains operator if voltage is
generally too low
x
22020 phase to phase voltage L12 exceeded
Check mains connection for contact resistance/transition resistance,
poss. contact mains operator if voltage is generally too high
x
22021 phase to phase voltage L12 undercut
Check fuses on mains connection, poss. contact mains operator if
voltage is generally too low
x
22030 phase to phase voltage L23 exceeded
Check mains connection for contact resistance/transition resistance,
poss. contact mains operator if voltage is generally too high
x
22031 phase to phase voltage L23 undercut
Check fuses on mains connection, poss. contact mains operator if
voltage is generally too low
x
Seite 4 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
22040 phase to phase voltage L31 exceeded
Check mains connection for contact resistance/transition resistance,
poss. contact mains operator if voltage is generally too high
x
22041 phase to phase voltage L31 undercut
Check fuses on mains connection, poss. contact mains operator if
voltage is generally too low
x
22080
Mains voltage errors (e.g. voltage
peak through switching another
consumer)
Remedy error cause, check all contact points (tight fit of screws) on the
mains side from the converter to the connection point (also automatic
cut-outs)
x
2090
Voltage limit for feeding amplitude (L1)
exceeded (mains quality limit)
Check feeding phase for contact resistance/transition resistance, poss.
contact mains operator if voltage is generally too high
x
22100
Frequency limit for feeding phase
exceeded
poss. contact mains operator x
22101
Frequency limit for feeding phase
undercut
poss. contact mains operator x
22110
Frequency limit for feeding phase
undercut
poss. contact mains operator x
22120
Frequency measuring not plausible
(poss. bouncing mains voltage)
Check all contact points (tight fit of screws) on the mains side from the
converter to the connection point (also automatic cut-outs)
x
22130 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22140 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22150 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22160 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22170 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22180 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 5 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
22190 AFI error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22200
Excess temperature on power
semiconductors
Check ventilation (dirt build-up/clogging of cooling ribs, air circulation
blocked). Select cooler suspension site (shadow, ventilation, etc.)
Once the WR is cooled down, it will connect again.
x
22210 Inside temperature too high
Check ventilation (dirt build-up/clogging of cooling ribs, air circulation
blocked). Select cooler suspension site (shadow, ventilation, etc.)
Once the WR is cooled down, it will connect again.
x
22220 Excess temperature on choke coil
Check ventilation (dirt build-up/clogging of cooling ribs, air circulation
blocked). Select cooler suspension site (shadow, ventilation, etc.)
Once the WR is cooled down, it will connect again.
x
22230 Inside temperature too high
Check ventilation (dirt build-up/clogging of cooling ribs, air circulation
blocked). Select cooler suspension site (shadow, ventilation, etc.)
Once the WR is cooled down, it will connect again.
x
22260 Current limit exceeded
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
22261 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
22262 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x x
22263 Mains error (isolated operation) Check fuses and contacts on mains connection. x x
22270 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22280 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22281 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22290 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22300
Temperature sensor on power
semiconductor defect
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 6 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
22310 Temperature sensor choke coil defect
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22320 Inside temperature sensor defect
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22330 Inside temperature sensor defect
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22340 Error relay cut-off
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22341 Error relay cut-off
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22342 Error relay cut-off
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22350 Error relay cut-off
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22360 Error relay connection
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22370 Error relay connection
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22380 Error relay connection
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22390 Error DC measuring AC side offset
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22401 Error DC measuring AC side
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22402 Error DC measuring AC side
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22410 Excess DC current
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 7 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
22411 Internal excess DC current
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22420 Excess DC voltage
Check layout and stringing (2 strings in series instead of parallel?)
Measure DC voltage before connecting to the converter.
x
22421 Excess internal DC voltage If error recurs repeatedly, check DC cables for external errors. x x
22450 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22460 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
22470 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22500 Internal communication error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22511 Internal communication error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22512 Internal communication error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22513 Internal communication error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22530 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22541 Error relay connection
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22550 Internal communication error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
Seite 8 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
22570 Communication error phase balancer
If phase balancer is activated, check cable, ensure that AC supply of all
3 converters is OK.
With individual converters, check phase balancer setting - must be
deactivated.
x x
22580 Communication error phase balancer Check phase balancer settings
22690 Internal memory error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22700 Internal memory error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22710 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22720 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22730 internal system error
Disconnect converter from DC generator and mains. Wait until device
has discharged (approx. 3 min.) and connect again. In case error
occurs again: Contact PLATINUM service, have error code and serial
number ready.
x
22740 Voltage from generator too low Check (measure) DC voltage on generator
Check layout and stringing
x
22900
Accompanying message when
converter shuts off due to an error
See corresponding simultaneous error code in the event list x
22980
Self-test error (only with certain
country codes, e.g. Italy)
Self- test only works during feed operation, meaning when AC and DC
have the corresponding values.
x
33010 Sudden DC voltage drop
Check DC plug connections and DC shut-off, may also occur at
sundown
x
44000
Internal information reset, only entered
in events list
No intervention necessary, for information only, can be recorded e.g.
when activating AC supply
x
44001
Information reset, only entered in
events list
No intervention necessary, for information only, can be recorded e.g.
when activating AC supply
x
44002
Information reset, only entered in
events list
No intervention necessary, for information only, can be recorded e.g.
when activating AC supply
x
Seite 9 von 10
Event list product family TL (four-digit event report; 2011)
Author: Service
Type
Event
code
Error description Remedy
DC generator
Converter
Mains (AC)
Cause
44020
Information "sunrise", is only entered
in events list when reaching the
generator voltage feeding threshold
no intervention necessary, for information only x
44030
Information "sundown", is only entered
in events list when undercutting the
feeding threshold (capacity)
no intervention necessary, for information only x
44090
Information, AC measuring values
outside of admissible limits.
no intervention necessary, for information only x
44120 Parameters were changed. no intervention necessary, for information only x
44130 Parameters were changed. no intervention necessary, for information only x
44170
Capacity limitation through phase
balancer was configured.
no intervention necessary, for information only x
44180
Capacity limitation cancelled by phase
balancer.
no intervention necessary, for information only x
44230
Self-test completed successfully (only
certain country codes, e.g. Italy)
no intervention necessary, for information only x
44500
Information reset (e.g. after mains
failure) only entered in events list
no intervention necessary, for information only x
44600 Software update was performed. no intervention necessary, for information only x
44610 Software update was performed. no intervention necessary, for information only x
Seite 10 von 10