Intralink LC2000 Logic Controller Siemens

User Manual: LC2000

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadIntralink LC2000 Logic Controller Siemens
Open PDF In BrowserView PDF
Water Technologies

Intralink™ LC2000
Logic Controller

The Siemens Control Systems IntraLink™ LC2000
combines on board I/O with a state of the art open
Controller. The LC2000 was developed specifically for
smaller, remote applications in the water and
wastewater industry.
This innovative Controller combines robust I/O, open
architecture
and
powerful
communications
capabilities. This combination produces an economic,
feature rich solution that is ideal for use in remote
control applications. Siemens Water Technologies has
embedded it’s eighty plus years of water and
wastewater knowledge into special purpose function
blocks so the customer will get a consistently
programmed system built on proven optimized
algorithms.
The IntraLink™ LC2000 is the perfect building block for
creating an effective control and telemetry system. The
hardware includes high performance CPU, large
memory, powerful programming tools, 26 on-board
discrete and analog I/O and built-in Ethernet. The
optional, user-friendly operator interface uses both text
and graphics to display the information an operator
needs to effectively run a system. An operator can
easily view operating parameters, change set points,
view and acknowledge alarms, review alarm history,
and view historical trends through a high contrast,
backlit display with an ergonomic 20 key keypad.

The Controller can be programmed locally or
remotely via multiple access options. These options
include telephone dial-up connection using a
standard modem, or an Ethernet network
connection.
The LC2000 can communicate to older
Consolidated Electric (D620), Autocon (Microcat)
and Dynamic Systems (PLTU) controllers, providing
a seamless migration path for customers with
these systems.
The IntraLink™ LC2000 has the flexibility for now
and the future. Cost effective on-board I/O
(expandable up to 256 points), extensive
communications capabilities and powerful control
ability make the LC2000 ideally suited for remote
(RTU) applications.
This innovative Controller combines an industry
standard
control
programming
language
(IEC61131-3)
with
Modbus
and
DF1
communications to deliver a truly open
architecture.
The primary focus of the Controller is to be open,
robust, flexible and useable. This product has been
developed for the water and wastewater industry,
to provide a quality driven solution now and in the
future.

Intralink™ LC2000

CONTROLLER
Processor
Operating system
Dynamic memory (RAM)
Program memory (Flash)
Datalogging memory (RAM)
Configuration software
Maximum local I/O
Maximum distributed I/O
Ethernet port
Serial ports
Input power
Input current
Temperature
Humidity
Hazardous locations
EN50021 Zone 2
(Class 1, Div 2, Groups A,B,C,D)
Mounting
OPERATOR INTERFACE
Display
Distance from Controller
Power Supply
Temperature
Humidity
Physical Dimensions
Environmental rating

Industrial PowerPC (32 bit data bus)
Embedded LINUX
16 Megabytes – 32 bit
16 Megabytes
512K
IsaGRAF IEC 61131-3
26 points (12DI, 8DO, 6AI)
256 points
10/100BaseTx
Two RS232 and one RS485
10 – 30 VDC
100 mA @24 VDC
-40 to 70ºC
5% to 95% RH (non-condensing)
UL 1604, CSA C22.2/213, Cenelec

DIN rail (EN50022) or flat panel
128 x 64 pixel (backlit)
10 feet
Supplied by Controller
0 to 50ºC
15% to 85% RH (non-condensing)
5.7” x 8.0”
IP65/Nema 4

INTRALINK LC2000 FEATURES
• Telephone, wireless, Ethernet and Internet
connectivity.
• Windows based configuration tools.
• MTU to RTU uploads and downloads.
• 26 I/O points on-board (12 DI, 8 DO, 6 AI)
• Scalable solution (up to 256 local I/O)
• Shared resource database.
• Advanced data logging capabilities resident in the
Controller
• Alarm logging resident in the Controller.
• Supports remote access via dial-up or network.
• Advanced communication capabilities.
• Multiple communication ports.
• High speed Ethernet connection.
• Flexible radio communications.
• Supports open and native protocols.
• Industry standard IEC 61131-3 programming
software.
• Embedded specialized water and wastewater
function blocks.

•
•
•
•
•
•
•
•
•
•
•
•
•

Fast controller speed.
Large amount of controller memory.
Small footprint runs on 10-30 Vdc.
Certified hardware.
Ergonomically designed keypad.
Back lighted, high contrast display.
Pre-configured operator interface display formats.
Three levels of operator interface security.
Graphical trend data.
View and acknowledge alarms locally.
Resident 1000 entry event log.
Detailed system diagnostics.
Ability to force outputs and simulate inputs to
locally test operations.
• Intrusion detection to alert unwanted access.

The information provided in this literature contains merely general descriptions or characteristics
of performance which in actual case of use do not always apply as described or which may
change as a result of further development of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the terms of the contract.
Intralink is a trademark of Siemens its subsidiaries or affiliates.
Siemens
Water Technologies
1239 Willow Lake Blvd.
Vadnais Heights, MN 55110
651.766.2700 phone
651.766.2701 fax
www.usfilter.com

Printed in U.S.A.
CS-LC2-DS-0806

©2006 Siemens Water Technologies Corp.
Subject to change without prior notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Create Date                     : 2006:08:14 09:22:24-05:00
Keywords                        : Controller, IntraLink, monitoring, PLC, programmable logic controller, telemetry, water, wastewater, control, instrumentation
Modify Date                     : 2009:02:25 15:22:56-09:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2009:02:25 15:22:56-09:00
Format                          : application/pdf
Title                           : Intralink LC2000 Logic Controller
Creator                         : 
Description                     : LC2000 Controller
Subject                         : Controller, IntraLink, monitoring, PLC, programmable logic controller, telemetry, water, wastewater, control, instrumentation
Document ID                     : uuid:1564935f-0dbb-4272-a410-8b468f4996a3
Instance ID                     : uuid:23523d3f-da6e-47be-bad4-b960fae5b17a
Page Count                      : 2
EXIF Metadata provided by EXIF.tools