Installation Instructions
Document No. 129-371
October 13, 2003

SED2 Variable Frequency Drives
Table 1. SED2 Full Load Amp (FLA) Ratings.

Product Description
Provides a quick and efficient site installation of the
SED2 Variable Frequency Drive (VFD).

Product Numbers

(leave blank)

* Available with Voltage Codes 3 and 4.
Example shown:
SED2-0.75/22X =
SED2 only, 0.75 kW (1hp), 200V to 240V, open type IP20.

1 1.5

2

3

575V 480V 240V

A

5

7.5 10 15 20 25 30 40 50 60 75 100 125

3

4

5.5 7.5 11 15 19 22 30 37 45 55 75 90

C

A

CAUTION:

4

B
B

D
C

E
D

F
E

0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0

WARNING:

SED2 IP20 and NEMA Type 1 frame sizes and
power ranges are as follows:
.7

kW

Output Current Max (amps)
208V to
240V
(3-Phase)
2.3
3.0
3.9
5.5
7.4
10.4
13.6
17.5
22.0
28.0
42.0
54.0
68.0
80.0
104.0
130.0
154.0
—
—
—

380V to
480V
(3-Phase)

500V to
600V
(3-Phase)

1.2
1.6
2.1
3.0
4.0
5.9
7.7
10.2
13.2
18.4
26.0
32.0
38.0
45.0
62.0
75.0
90.0
110.0
145.0
178.0

—
—
1.4
2.1
2.7
3.9
5.4
6.1
9.0
11.0
17.0
22.0
27.0
32.0
41.0
52.0
62.0
77.0
99.0
125.0

Warning/Caution Notations

Frame Sizes and Power Ratings

HP .5

HP
0.5
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
125.0

Your Product Number: S E D 2 /
X
Example Product Number: S E D 2 - 0 . 7 5 / 2 2 X
Model:
SED2kW:
(uses 2 to 4 spaces
0.37, 0.55, 0.75, 1.1, 1.5, 2.2,
plus a divider "/")
3, 4, 5.5, 7.5, 11, 15, 18.5,
22, 30, 37, 45, 55, 75, 90
Voltage:
2 = 200 to 240
3 = 380 to 480
4 = 500 to 600
NEMA:
2 (IP 20)
1 NEMA Type 1
5 NEMA Type 12 (IP 54) *
Other:
X include with all part #'s

kW .37 .5 .75 1.1 1.5 2.2

Output Rating

Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.

Required Tools
F

C

See Mounting and Dimensions to determine correct
tool sizing.

SED2 IP54/NEMA Type 12 frame sizes and power
ranges are as follows:
HP .5

.7

1 1.5

2

3

575V 480V

kW .37 .5 .75 1.1 1.5 2.2

4

5

7.5 10 15 20 25 30 40 50 60 75 100 125

3

4

5.5 7.5 11 15 19 22 30 37 45 55 75 90

B

Expected Installation Time
15 minutes

C
D

E

F

C

Item Number 129-371, Rev. 012

http://www.sbt.siemens.com/hvp/drives

Page 1 of 8

Document No. 129-371
Installation Instructions
October 13, 2003

Gland Plate Installation and Conduit
Connections

Installation
Prerequisites

For Frame Sizes A, B, and C, see Figures 1 and 2
for gland plate installation and for conduit connection
diameters. Circled numbers indicate the order of
assembly.

CAUTION:
On installation of a SED2 after extended
storage, see the Extended Storage:
Conditioning of Capacitors section in the
SED2 VFD Startup, Operation, and
Maintenance Manual (Document Number
125-3201). If capacitors are not properly
recharged, catastrophic damage to the
drive can result.

For Frame Sizes D, E, and F, see Figures 3 and 4
for conduit connection diameters.
CAUTION:

Install the SED2 in a climate-controlled environment
that is free of moisture and conductive
contaminants, such as condensation and dust. The
air entering the unit for ventilation must be clean and
free of corrosive materials. The ambient temperature
must be between 14°F and 104°F (–10°C and 40°C)
and the relative humidity must be 0% to 95%
non-condensing. Do not mount unit in direct sunlight.

•

Bonding between conduit
connections is not automatic and
must be provided as part of the
installation.

•

Each bonding conductor must be
equal or greater in cross-section to
the power supply cable.

3

4

Ground

2

5


Ground

VFD0002R1

Conduit Connections:
.90
(22.8)

Figure 1. Frame Size A Gland Plate Installation and Conduit Connection Diameters in Inches (Millimeters).

Page 2 of 8

http://www.sbt.siemens.com/hvp/drives

Siemens Building Technologies, Inc.

Document No. 129-371
Installation Instructions
October 13, 2003

3

2

4

1

5
Conduit Connections:

nd

ou
Gr

VFD0003R1

Frame Size B

.90
(22.8)

Frame Size C

.74
(18.8)

.90
(22.8)

1.10
(28)

.74
(18.8)

1.10
(28)

Figure 2. Frame Size B & C Gland Plate Installation and Conduit Connection Diameters in Inches (Millimeters).

13.5
(343)

6.8
(173)
.3
(58)

1.8
(46)

ON
1

2

20

21

22

23

24

25

12

13

14

15

16

17

26

27

28

29

30

1

2

3

4

5

6

7

8

9

10

11

4.4
(112)

1.8
(46)

1.4
o(36)

9.0
(229)
o 6.1
(155)

o 0.25
(6)

o 3.5
(89)

.35
(9)

VFD0091R1

PE

VFD0062R1

1.77
(45.0)

1.77
(45.0)
1.10
(28.4)

1.5
(38)

14.0
(356)

1.0
(25)

Figure 4. Frame Size F Conduit Connection Diameters
(Bottom View) in Inches (Millimeters).

1.77
(45.0)
.90
(22.8)

Figure 3. Frame Size D & E Conduit Connection
Diameters in Inches (Millimeters).

Siemens Building Technologies, Inc.

http://www.sbt.siemens.com/hvp/drives

Page 3 of 8

Document No. 129-371
Installation Instructions
October 13, 2003

CAUTION:

Mounting and Dimensions

Overheating/Ventilation:
Install SED2 vertically for optimum
ventilation. Do not obstruct SED2 vents.
Additional ventilation may be required if
SED2 is mounted horizontally.

Mount the SED2 so there is a minimum clearance for
ventilation and equipment access.

IP20 SED2s
Table 2. IP20 SED2 Overall Dimensions in Inches (Millimeters).
Frame
Size

Height x Width x
Depth

Mounting Specification

6.8 x 2.9 x 5.9
(173 x 73 x 149)
8.0 x 5.9 x 6.8
(202 x 149 x 172)
9.6 x 7.3 x 7.7
(245 x 185 x 195)
20.5 x 10.8 x 9.6
(520 x 275 x 245)
25.6 x 10.8 x 9.6
(650 x 275 x 245)
33.5 x 13.8x x 12.6
(850 x 350 x 320)

A
B
C
D
E
F

Frame Size A

2 × M4 Bolts, nuts, washers, or
connecting to DIN rail

115
(13)

4 × M8 Bolts, nuts, washers

221
(25)

Frame
Size

Frame Size C
0.22
(5.5)

5.4
(138)

Vmin Clearance in
Inches (Millimeters)
4
(100)
11-3/4
(300)
13-3/4
(350)

A, B, C

8.0
(204)

6.9
(174)

0.17
(4.5)

2.9
(1.3)
7.5
(3.4)
12.1
(5.5)
35.3
(16)
44.1
(20)
116
(53)

26
(3.0)

4 × M5 Bolts, nuts, washers

0.19
(4.8)

6.3
(160)

Weight
lb (kg)

22
(2.5)

4 × M4 Bolts, nuts, washers

Frame Size B

0.22
(5.5)

Tightening Torque
lb-in (Nm)

D, E
F

6.9
(174)

Frame Size F
Frame Size E
Frame Size D

Vmin.

0.59
(15)

0.68
(17.5)

SIEMENS

0.68
(17.5)

31.9
(810)

24.3
(616)

19.1
(486)

SED2
VFD0143R1

VFD0012R1

9.3
(235)

9.3
(235)

11.8
(300)

Figure 5. IP20 SED2 Mounting Dimensions
in Inches (Millimeters).

Page 4 of 8

SIEMENS

SED2

Vmin.

NOTE: When fitted with a protective
shield, allow 12-inches (305 mm) of space
between each SED2.

http://www.sbt.siemens.com/hvp/drives

Siemens Building Technologies, Inc.

Document No. 129-371
Installation Instructions
October 13, 2003
NEMA Type 1 SED2s
Table 3. NEMA Type 1 SED2 Overall Dimensions in Inches (Millimeters).
Frame
Size
A
B
C
D

Height x Width x
Depth

Mounting Specification

9.1 x 2.9 x 5.9
(231 x 73 x 149)
11.8 x 5.9 x 6.8
(300 x 49 x 172)
13.8 x 7.3 x 7.7
(351 x 185 x 195)
24.6 x 10.8 x 9.6
(625 x 275 x 245)

E

29.7 x 10.8 x 9.6
(754 x 275 x 245)

F

54.5 x 16.0 x 14.0
(1384 x 406 x 356)

Tightening Torque
lb-in (Nm)

2 × M4 Bolts, nuts, washers, or
connecting to DIN rail
4 × M4 Bolts, nuts, washers
4 × M5 Bolts, nuts, washers

0.19
(4.8)

0.22
(5.5)

3.2
(1.5)
8.3
(3.8)
13.6
(6.2)
37,5
(17.1)

22
(2.5)
26
(3.0)
115
(13)

46.4
(21.1)

4 × M8 Bolts, nuts, washers
221
(25)

Frame Size C

Frame
Size

0.22
(5.5)

A, B, C

Frame Size B
Frame Size A

8.0
(204)

6.9
(174)

6.3
(160)

200
(91)

Vmin Clearance in
Inches (Millimeters)
4
(100)
11-3/4
(300)
13-3/4
(350)

D, E
F

0.17
(4.5)

Weight
lb (kg)

5.4
(138)

6.9
(174)

Vmin.

Frame Size F

Frame Size E

0.59
(15)

Vmin.

SIEMENS

SIEMENS

Frame Size D
0.68
(17.5)

12 in.
(305 mm)

0.68
(17.5)

VFD0092R2

SED2

VFD0143R1

19.1
(486)

9.3
(235)

51
(1295)

24.3
(616)

9.3
(235)

Vmin.

SED2

Vmin.

15
(381)

Figure 6. NEMA Type 1 SED2 Mounting Dimensions
in Inches (Millimeters).

Siemens Building Technologies, Inc.

http://www.sbt.siemens.com/hvp/drives

Page 5 of 8

Document No. 129-371
Installation Instructions
October 13, 2003
IP54/NEMA Type 12 SED2s
Table 4. IP54/NEMA Type 12 SED2 Overall Dimensions in Inches (Millimeters).

Frame Size

B
C
D
E
F

Mounting
Clearance
Top x Bottom x
Sides

Overall Dimensions
Height x Width x
Depth
15.2 x 10.6 x 10.6
(385 x 270 x 270)
23.9 x 13.8 x 11.2
(606 x 350 x 284)
27.0 x 142 x 13.9
(685 x 360 x 200)
34.8 x 14.2 x 17.8
(885 x 360 x 453)
45.3 x 17.7 x 18.6
(1150 x 450 x 473)

5.9 x 5.9 x 3.9
(150 x 150 x 100)

7.9 x 7.9 x 5.9
(200 x 200 x 150)

Mounting
Specification

Tightening
Torque
lb-in (Nm)

4 × M6 Bolts, nuts,
washers

44
(5)

177
(20)

0.22
(5.5)

D, E
F

12.3
(313)

9.1
(230)

NOTE:

In all cases, Smin Clearance is
5-7/8 inches (150 millimeters).

Frame Size F
0.59
(15)

Frame Size E
Frame Size D

4
(100)
11-3/4
(300)
13-3/4
(350)

A, B, C

22.2
(564)

13.5
(343)

Vmin Clearance in
Inches (Millimeters)

Frame Size

Frame Size C
0.19
(4.8)

22
(10)
42
(19)
77
(35)
105
(48)
178
(81)

115
(13)

4× M8 Bolts, nuts,
washers

11.8 x 9.8 x 5.9
(300 x 250 x 150)

Frame Size B

Weight
lb (kg)

Vmin.

0.68
(17.5)
SIEMENS

0.68
(17.5)

43.8
(1112)

33.5
(847)

SED2

VFD0144R1

VFD0013R1

12.2
(310)

Smin.

Smin.

Smin.

25.5
(647)

SIEMENS

SED2

Vmin.

15.7
(400)

12.2
(310)

Figure 7. IP54/NEMA Type 12 SED2 Mounting Dimensions in
Inches (Millimeters).

Wiring

Cable Cross-Sections for Power and
Motor Cables

Tightening Torque for Connecton
Terminals

Tables 5 through 7 provide cable cross-sections for
input power cables and for motor cables.

Frame Size

A

B

C

D

E

F

Tightening
Torque
lb-in (Nm)

9.7
(1.1)

13.3
(1.5)

19.9
(2.25)

88.5
(10)
max.

88.5
(10)
max.

442
(50)

Page 6 of 8

http://www.sbt.siemens.com/hvp/drives

Siemens Building Technologies, Inc.

Document No. 129-371
Installation Instructions
October 13, 2003
Table 5. Cable Cross-Sections for Input Voltage
Range 3ø AC 200V through 240V.
Input Power Cable

Table 6. Cable Cross-Sections for Input Voltage
Range 3ø AC 380V through 480V.

Motor Cable

Input Power Cable

Motor Cable

Output
Rating
kW (hp)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

Output
Rating
kW (hp)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

0.37 (.50)
0.55 (.75)
0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3 (4.0)
4 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)

17 (1)
17 (1)
17 (1)
17 (1)
15 (1.5)
13 (2.5)
11 (4)
11 (4)
11 (4)
7 (10)
5 (16)
5 (16)
3 (25)
2 (35)
0 (50)
-2 (70)
-2 (70)

13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)

17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
15 (1.5)
11 (4)
11 (4)
7 (10)
16 (5)
5 (16)
5 (16)
2 (35)
0 (50)
-2 (70)
-3 (95)

13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)

0.37 (.50)
0.55 (.75)
0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3 (4.0)
4 (5.0)
5.5 (7.5)
7.5 (10)
0.37 (.50)
0.55 (.75)
0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3 (4.0)
4 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)

17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
13 (2.5)
11 (4)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
13 (2.5)
11 (4)
9 (6)
7 (10)
7 (10)
5 (16)
3 (25)
3 (25)
2 (35)
-2 (70)
-2 (70)
-2 (70)

13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)
-5 (150)

17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
13 (2.5)
11 (4)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
13 (2.5)
11 (4)
9 (6)
7 (10)
7 (10)
5 (16)
3 (25)
2 (35)
2 (35)
-2 (70)
-3 (95)
-3 (95)

13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
13 (2.5)
9 (6)
9 (6)
9 (6)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)
-5 (150)

Table 7. Cable Cross-Sections for Input Voltage
Range 3ø AC 500V through 600V.
Input Power Cable

Motor Cable

Output
Rating
kW (hp)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

Min.
CrossSection
AWG
(mm2)

Max.
CrossSection
AWG
(mm2)

0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3 (4.0)
4 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)

17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
15 (1.5)
13 (2.5)
11 (4)
9 (6)
9 (6)
7 (10)
5 (16)
3 (25)
3 (25)
0 (50)
-2 (70)
-2 (70)

7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)
-5 (150)

17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
17 (1)
15 (1.5)
13 (2.5)
11 (4)
9 (6)
9 (6)
7 (10)
5 (16)
5 (16)
3 (25)
2 (35)
0 (50)
0 (50)

7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
7 (10)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
-5 (150)
-5 (150)
-5 (150)
-5 (150)

Siemens Building Technologies, Inc.

Input Power Connection
WARNING:
Use only permanently wired input power
connections.
Connect input power to SED2 terminals L1, L2,
and L3.

http://www.sbt.siemens.com/hvp/drives

Page 7 of 8

Document No. 129-371
Installation Instructions
October 13, 2003

Motor Cable Length

Motor Connection

Maximum motor cable length is 164 ft (50 m). Motor
cable length is given to ensure performance of only
the SED2, not the suitability of the motor when
connected to a SED2 at this distance. See Figure 8
for motor cable installation notes.

The motor nameplate indicates the required supply
voltage and method of connection (delta, ∆, or
star/wye, ‘Y’, configuration). Connect motor wiring to
SED2 terminals U, V, and W. See Figure 9.

!

1. Never run control or drive input
wires in the same conduit as
the drive output wires.

2. Keep the distance from the drive
to the motor as short as possible
to maximize motor life.

4. If a disconnect is mounted on the
load side of your drive, it is desirable
to wire an auxiliary contact to the drive
that will disable drive operation when
the disconnect opens. (The wiring for
this contact must not be run in the same
conduit as the drive output wires).

SED2

VFD0014R2

M

3. If needed, use
SBT-specified input line reactors
to ensure a good impedance match
with your drive.

5. Inverter duty motors are recommended.
Install motors within their guidelines. Use
dV/dT filters, output reactors, or other load
conditioners as applicable or as specified
by the motor manufacturer.

Figure 8. Motor Cable Installation Notes.

MOTOR TERMINALS

VFD0029R2

U1

W2

V1

U2

W1

V2

U1

W2

V1

U2

W1

V2

Wye "Y"

Figure 9. SED2 Motor Connections.

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their
respective owners. © 2003 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
U.S.A.

Your feedback is important to us. If you have
comments about this document, please send
them to technical.editor@siemens.com

Document No.129-371
Printed in the U.S.A.

Page 8 of 8



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Page Count                      : 8
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:541a1df6-1985-4570-9c92-30cc1e25c9c6
Producer                        : Acrobat Distiller 5.0 (Windows)
Create Date                     : 2003:10:14 16:52:25Z
Modify Date                     : 2003:10:23 15:40:25-05:00
Metadata Date                   : 2003:10:23 15:40:25-05:00
Creator Tool                    : Acrobat PDFMaker 5.0 for Word
Document ID                     : uuid:9ebc7616-1cb4-402a-a472-c1c20a46098d
Format                          : application/pdf
Creator                         : Technical Communications Services, LRye
Title                           : SED2 Variable Frequency Drives
Description                     : Installation Instructions
Tagged PDF                      : Yes
Author                          : Technical Communications Services, LRye
Keywords                        : HVP, 127-371, October 13, 2003
Subject                         : Installation Instructions
EXIF Metadata provided by EXIF.tools

Navigation menu