SED2 Variable Frequency Drives
Startup, Operation, and
Maintenance Manual

Item Number 125-3201, Rev. 012

SED2 Variable
Frequency Drives
Startup, Operation, and
Maintenance Manual

NOTICE
The information contained within this document is subject to change without
notice and should not be construed as a commitment by Siemens Building
Technologies, Inc. Siemens Building Technologies, Inc. assumes no
responsibility for any errors that may appear in this document.
All software described in this document is furnished under a license and may be
used or copied only in accordance with the terms of such license.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is
mechanical in nature and all mechanical components must be regularly serviced
to optimize their operation. All Siemens Building Technologies, Inc. branch
offices and authorized distributors offer technical support programs that will
ensure your continuous, trouble-free system performance.
For further information, contact your nearest Siemens Building Technologies, Inc.
representative.
CREDITS
Product or company names mentioned herein may be the trademarks of their
respective owners.

Copyright © 2003 by Siemens Building Technologies, Inc.
TO THE READER
Your feedback is important to us. If you have comments about this manual,
please submit them to technical.editor@siemens.com.
Printed in U.S.A.

Table of Contents

Table of Contents
How To Use This Manual ......................................................
Manual Organization ..........................................................
Manual Notations................................................................
Where To Send Comments ................................................
Reference Documents........................................................

1
1
2
2
2

Safety Instructions ................................................................
General ...............................................................................
Environmental Compatibility and Disposal .........................

3
3
4

Mechanical Installation .........................................................
Product Numbers................................................................
Frame Sizes........................................................................
Interpreting Serial Numbers and Date Codes ....................
Output Ratings....................................................................
Accessories ........................................................................
Environmental Conditions...................................................
Dimensions and Mounting for IP20 SED2s ........................
Overall Dimensions and Mounting Specifications .........
Mounting Dimensions....................................................
Mounting Instructions ....................................................
Gland Plate Installation and Conduit Connections........
Dimensions and Mounting for NEMA Type 1 SED2s .........
Overall Dimensions and Mounting Specifications .........
Mounting Dimensions....................................................
Mounting Instructions ....................................................
Dimensions and Mounting for IP54,
NEMA Type 12 SED2s .......................................................
Overall Dimensions and Mounting Specifications .........
Mounting Dimensions....................................................
Mounting Instructions ....................................................

5
5
6
7
8
10
11
12
12
13
13
14
17
17
18
18

Electrical Installation.............................................................
Extended Storage: Conditioning of Capacitors ..................
Input Power and Motor Connections ..................................
Operation in Ungrounded Systems ...............................

22
23
24
25

Siemens Building Technologies, Inc.

19
19
20
21

i

SED2 VFD Startup, Operation, and Maintenance Manual

ii

Ungrounded Systems and Y Capacitor .........................
Access to Connection Terminals...................................
Motor Frequency and Unit of Measurement
DIP Switches .................................................................
Input Power and Motor Terminal Layout .......................
Tightening Torque for Input Power and
Motor Connections ........................................................
Cable Cross-Sections for Input Power and
Motor Cables .................................................................
Input Power Connection ................................................
Motor Cable Length .......................................................
Motor Connection (Wye "Y"/Star or
Delta Configuration) ......................................................
Direction of Motor Rotation............................................
Motor Overload Protection ............................................
Connection of Multiple Motors.......................................
Analog Input DIP Switches............................................
Control Terminal Connections ............................................
Control Terminal Layout ................................................
Analog and Digital I/O Control
Terminal Connections ...................................................

25
28

Parameters .............................................................................
Overview.............................................................................
Parameter Structure ...........................................................
Parameter Indexes .............................................................

49
49
49
49

SED2 Operator Panels...........................................................
Overview.............................................................................
Basic Operator Panel (BOP) ..............................................
Advanced Operator Panel (AOP) .......................................
BOP Display and Pushbuttons ...........................................

51
51
51
52
52

Commissioning ......................................................................
Motor Nameplate Data for Parameter Settings ..................
Prerequisites to Startup Procedure ....................................
SED2 (stand-alone) Startup Procedure..............................
Quick Commissioning Procedure .......................................

55
56
57
59
61

31
32
34
34
37
38
39
40
41
42
43
44
44
47

Siemens Building Technologies, Inc.

Table of Contents

Additional Parameter Settings ............................................
Flying Start ....................................................................
Automatic Restart ..........................................................
Vdc Controller................................................................
Pulse Frequency ...........................................................
Reset to Factory Defaults..............................................
Network Communications .............................................
Changing Individual Parameter Digits ................................

70
70
72
74
74
75
76
77

Maintenance ...........................................................................
Prerequisites.......................................................................
General Inspection and Cleaning .......................................
Muffin Fan Inspection and Cleaning ...................................
Re-energize Unit.................................................................
DC Bus Integrity Test .........................................................
Contactors and Switches....................................................
Motor Bearing Wear ...........................................................

78
78
78
78
79
79
79
79

Troubleshooting.....................................................................
Reading Faults ...................................................................
Resetting Faults..................................................................
Troubleshooting the Operator Panel ..................................
Troubleshooting Using the Operator Panel ........................
Fault Codes ........................................................................
Warning Messages .............................................................

80
80
81
82
83
84
92

Replacement Parts ................................................................ 96
Repair...................................................................................... 97
Technical Specifications....................................................... 98
Appendix A: Parameters, Defaults, and Settings ............... 100
Appendix B: SED2 Point Maps ............................................. 111
Glossary.................................................................................. 117

Siemens Building Technologies, Inc.

iii

How to Use This Manual

How To Use This Manual
This manual is written for users of Siemens Building Technologies, Inc.
SED2 Variable Frequency Drives (VFDs). It contains information to
install, commission, and set parameters for SED2s in order to provide
effective and trouble-free operation.

Manual Organization
This manual contains the following sections:
Section

Description

How to Use this
Manual

Describes the organization of this manual, its notations,
and lists reference documents.

Safety Instructions

Presents general safety regulations, guidelines, and
recommendations.

Mechanical
Installation

Provides information for mounting and installing a
SED2.

Electrical Installation

Provides information for installing and terminating SED2
wiring.

Parameters

Provides an overview about SED2 parameters.

SED2 Operator
Panels

Provides an overview about the SED2 Basic Operator
Panel and its pushbuttons

Commissioning

Describes how to commission and start a SED2 for
operation.

Maintenance

Provides preventive maintenance information.

Troubleshooting

Lists SED2 fault codes, and warning messages.

Replacement Parts

Provides a list of SED2 replacement parts.

Repairs

Provides repair information.

Appendix A:
Parameters, Defaults,
and Settings

Provides a table of SED2 parameters with the number,
title, and user access level.

Appendix B: SED2
Point Maps

Provides a SED2 P1 point map for APOGEE
Automation Systems and a SED2 N2 point map for
Johnson Controls, Inc. systems.

Glossary

Defines terms related to the SED2.

®

Siemens Building Technologies, Inc.

1

SED2 VFD Startup, Operation, and Maintenance Manual

Manual Notations
Notation

Symbol

Meaning

DANGER:

Indicates that personal injury, or loss of life may
occur if you do not perform a procedure as
specified.

WARNING:

Indicates that personal injury, or equipment
damage may occur if you do not perform a
procedure as specified.

CAUTION:

Indicates that equipment damage, or loss of data
may occur if you do not perform a procedure as
specified.

Where To Send Comments
Your feedback is important to us. If you have comments about this
manual, please submit them to technical.editor@siemens.com.

Reference Documents
SED2s control the speed of fan and pump motors. SED2s can also be
programmed to manage many other motor functions and limits set by
parameters, which are programmed using the SED2 keypad. See the
SED2 VFD Parameter Reference Guide (125-3214) for more details and
a complete listing of the SED2 parameters.
The following SED2 documentation is available from your local Siemens
Building Technologies, Inc. representative:
•

SED2 VFD AOP Operating Instructions (125-3206), operating
instructions and procedures for the SED2 Advanced Operator Panel.

•

SED2 VFD Conventional Bypass Operating Instructions (125-3215),
start-up and operation of the SED2 Conventional Bypass Option.

•

SED2 VFD Electronic Bypass Operating Instructions (125-3208),
start-up, application, and operation of the SED2 Electronic Bypass
Option.

•

SED2 VFD LON Interface Option Operating Instructions (125-3212),
®
startup and operation of the SED2 LON Interface Option.

2

Siemens Building Technologies, Inc.

Safety Instructions

Safety Instructions
General
The following general guidelines are provided for your safety, to prevent
damage, and to extend the service life of the SED2 product and any
connected equipment. Read this information carefully. Specific
Warnings, Cautions, and Notes are provided in the relevant sections of
this manual.
WARNING:

NOTE:

•

The SED2 uses hazardous voltages and controls
potentially dangerous rotating mechanical parts. Noncompliance with warnings, or failure to follow the
instructions contained in this manual, can result in loss
of life, severe personal injury, or serious damage to
property/equipment.

•

Only authorized personnel should work on this
equipment, and only after becoming familiar with all local
regulations and ordinances, safety notices, and
procedures in this manual. Successful and safe
operation of this equipment depends upon its proper
handling, installation, operation, and maintenance.

•

Before doing any installation and commissioning
procedures, you must read all safety instructions and
warnings, including all warning labels attached to the
equipment. Ensure that the warning labels are legible
and replace missing or damaged labels.

•

Observe the regulations of safety codes whenever
working with live equipment and high-voltage
installations. Also, use suitable tools and protective
equipment.

•

Prevent any unauthorized person from accessing or
approaching this equipment.

Keep this manual near the equipment and available to all
users.

Siemens Building Technologies, Inc.

3

SED2 VFD Startup, Operation, and Maintenance Manual

Environmental Compatibility and
Disposal
The SED2s are developed and manufactured using materials and
processes that take full account of environmental issues and which
comply with environmental standards. For disposal at the end of the
SED2 service life or in the event of its replacement, note the following:
•

For disposal purposes, this product is defined as waste derived from
electrical and electronic equipment (“electronic waste”) and must not
be disposed of as household waste. This applies particularly to the
PCB assembly.

•

Always use the most environmentally compatible method of disposal,
in line with the latest developments in environmental protection,
recycling, and waste management. Observe all local legislation and
applicable laws.

•

Always aim for maximum re-use of the basic materials, and minimum
environmental stress. Observe any notes about materials and
disposal that may be attached to individual components.

•

Use local depots and waste management companies, or see your
supplier or manufacturer to return used products or to obtain further
information on environmental compatibility and waste disposal.

•

Special handling of components such as electrolytic capacitors and
LCD panels may in some cases be compulsory by law or
environmentally desirable.

•

The SED2 is delivered in re-usable packaging. Please retain this
packaging for later use or in case you need to return the product.

4

Siemens Building Technologies, Inc.

Mechanical Installation

Mechanical Installation
Product Numbers
The following chart shows SED2 product numbers:
Your Product Number: S E D 2 Example Product Number: S E D 2 - 0 . 7 5 / 2 2 X
Model:
SED2kW:
0.37, 0.55, 0.75, 1.1, 1.5, 2.2,
(use 2 to 4 spaces
3, 4, 5.5, 7.5, 11, 15, 18.5,
plus a divider "/")
22, 30, 37, 45, 55, 75, 90
Voltage:
2 = 200 to 240
3 = 380 to 480
4 = 500 to 600
NEMA:
2 = (IP20)
1 = NEMA Type 1
5 = NEMA Type 12 (IP54) *
Other:
X = Other
(leave blank)
* Available with Voltage Codes 3 and 4.

Example shown:
SED2-0.75/22X = SED2 only, 0.75 kW (1 hp), 200V to 240V,
open type IP20.

Siemens Building Technologies, Inc.

5

SED2 VFD Startup, Operation, and Maintenance Manual

Frame Sizes
The following chart shows SED2 IP20 and NEMA Type 1 (drive only)
frame sizes and power ranges.
HP .5

.7

1 1.5

2

3

575V 480V 240V

kW .37 .5 .75 1.1 1.5 2.2

A

4

5

7.5 10 15 20 25 30 40 50 60 75 100 125

3

4

5.5 7.5 11 15 19 22 30 37 45 55 75 90

B

C

A

B

D
C

E
D

F
E

F

C

The following chart shows SED2 IP54, NEMA Type 12 (drive only) frame
sizes and power ranges.
HP .5

.7

1 1.5

2

3

575V 480V

kW .37 .5 .75 1.1 1.5 2.2

6

4

5

7.5 10 15 20 25 30 40 50 60 75 100 125

3

4

5.5 7.5 11 15 19 22 30 37 45 55 75 90

B

C
D

E

F

C

Siemens Building Technologies, Inc.

Mechanical Installation

Interpreting Serial Numbers and Date
Codes
Each SED2 has a manufacturing/serial number. The date of
manufacture, or the date code, is part of the serial number. The following
examples show how to interpret the date code and serial code.
Example 1:
A SED2 manufactured April 21, 2000 with a 000219 serial number.
X

A

M

Indicates
Year:
manufacturing
M = 00
location
N = 01

4
Month:

2

1

-

0

0

0

2

1

9

Day:

A
Six-digit serial number
separator in the range of 1
Jan = 1, 01
to facilitate through 999999.
Feb = 2, through reading of
.
31
the serial
O = 02 .
number.
.
P = 03 Sept = 9,
Q = 04 Oct = O,
Nov = N,
Dec = D

Example 2:
A SED2 manufactured July 24, 2001 with a 00535 serial number.
T

-

N

Indicates
Year:
manufacturing
M = 00
location
N = 01

7
Month:

2

4

Day:

Jan = 1, 01
Feb = 2, through
.
31
O = 02 .
.
P = 03 Sept = 9,
Q = 04 Oct = O,
Nov = N,
Dec = D

Siemens Building Technologies, Inc.

6

2

Product
number

0

0

0

5

3

5

Five-digit serial number
in the range of 1
through 99999.

7

SED2 VFD Startup, Operation, and Maintenance Manual

Output Ratings
Table 1 shows SED2 product numbers and the associated output ratings.

380V to 480V (3-Phase)

208V to 240V (3-Phase)

Voltage
(±10%)

Table 1. SED2 Product Numbers and Output Ratings.
Product Number
IP20
SED2-0.37/22X
SED2-0.55/22X
SED2-0.75/22X
SED2-1.1/22X
SED2-1.5/22X
SED2-2.2/22X
SED2-3/22X
SED2-4/22X
SED2-5.5/22X
SED2-7.5/22X
SED2-11/22X
SED2-15/22X
SED2-18.5/22X
SED2-22/22X
SED2-30/22X
SED2-37/22X
SED2-45/22X
SED2-0.37/32X
SED2-0.55/32X
SED2-0.75/32X
SED2-1.1/32X
SED2-1.5/32X
SED2-2.2/32X
SED2-3/32X
SED2-4/32X
SED2-5.5/32X
SED2-7.5/32X
SED2-11/32X
SED2-15/32X
SED2-18.5/32X
SED2-22/32X
SED2-30/32X
SED2-37/32X
SED2-45/32X
SED2-55/32X
SED2-75/32X
SED2-90-32X

Output Rating

NEMA Type 1

IP54, NEMA
Type 12

SED2-0.37/21X
SED2-0.55/21X
SED2-0.75/21X
SED2-1.1/21X
SED2-1.5/21X
SED2-2/21X
SED2-3/21X
SED2-4/21X
SED2-5.5/21X
SED2-7.5/21X
SED2-11/21X
SED2-15/21X
SED2-18.5/21X
SED2-22/21X
SED2-30/21X
SED2-37/21X
SED2-45/21X
SED2-0.37/31X
SED2-0.55/31X
SED2-0.75/31X
SED2-1.1/31X
SED2-5/31X
SED2.2/31X
SED2-3/31X
SED2-4/31X
SED2-5.5/31X
SED2-7.5/31X
SED2-11/31X
SED2-15/31X
SED2-18.5/31X
SED2-22/31X
SED2-30/31X
SED2-37/31X
SED2-45/31X
SED2-55/31X
SED2-75/31X
SED2-90/31X

—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
SED2-1.1/35X
SED2-1.5/35X
SED2-2/35X
SED2-3/35X
SED2-4/35X
SED2-5.5/35X
SED2-7/5/35X
SED2-11/35X
SED2-15/35X
SED2-18.5/35X
SED2-22/35X
SED2-30/35X
SED2-37/35X
SED2-45/35X
SED2-55/35X
SED2-75/35X
SED2-90/35X

HP

kW

0.5
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
0.5
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
125.0

0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0

Output
Current Frame
Size
Max.
(amps)
2.3
3.0
3.9
5.5
7.4
10.4
13.6
17.5
22.0
28.0
42.0
54.0
68.0
80.0
104.0
130.0
154.0
2.1
2.6
2.1
3.0
4.0
5.9
7.7
10.2
13.2
18.4
26.0
32.0
38.0
45.0
62.0
75.0
90.0
110.0
145.0
178.0

A
A
A
B
B
B
C
C
C
C
D
D
D
E
E
F
F
A
A
A
A*
A*
B
B
B
C
C
C
C
D
D
D
E
E
F
F
F

* IP54, NEMA Type 12 drives start at Frame Size B.

8

Siemens Building Technologies, Inc.

Mechanical Installation

500V to 600V (3-Phase)

Voltage
(±10%)

Table 1. SED2 Product Numbers and Output Ratings. (Continued)
Product Number
IP20
SED2-0.75/42X
SED2-1.1/42X
SED2-1.5/42X
SED2-2.2/42X
SED2-3/42X
SED2-4/42X
SED2-5.5/42X
SED2-7.5/42X
SED2-11/42X
SED2-15/42X
SED2-18.5/42X
SED2-22/42X
SED2-30/42X
SED2-37/42X
SED2-45/42X
SED2-55/42X
SED2-75/42X
SED2-90/42X

Output Rating

NEMA Type 1

IP54, NEMA
Type 12

SED2-0.75/41X
SED2-1.1/41X
SED2-1.5/41X
SED2-2.2/41X
SED2-3/41X
SED2-4/41X
SED2-5.5/41X
SED2-7.5/41X
SED2-11/41X
SED2-15/41X
SED2-18.5/41X
SED2-22/41X
SED2-30/41X
SED2-37/41X
SED2-45/41X
SED2-55/41X
SED2-75/41X
SED2-90/41X

—
SED2-1.1/45X
SED2-1.5/45X
SED2-2.2/45X
SED2-3/45X
SED2-4/45X
SED2-5.5/45X
SED2-7.5/45X
SED2-11/45X
SED2-15/45X
SED2-18.5/45X
SED2-22/45X
SED2-30/45X
SED2-37/45X
SED2-45/45X
SED2-55/45X
SED2-75/45X
SED2-90/45X

Siemens Building Technologies, Inc.

HP

kW

1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
125.0

0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0

Output
Current Frame
Size
Max.
(amps)
1.4
2.1
2.7
3.9
5.4
6.1
9.0
11.0
17.0
22.0
27.0
32.0
41.0
52.0
62.0
77.0
99.0
125.0

C
C
C
C
C
C
C
C
C
C
D
D
D
E
E
F
F
F

9

SED2 VFD Startup, Operation, and Maintenance Manual

Accessories
SED 2 accessories include the following:

Gland Plates
•

SED2-GL-A, Gland Plate, Frame A (included with NEMA Type 1)

•

SED2-GL-B, Gland Plate, Frame B (included with NEMA Type 1)

•

SED2-GL-C, Gland Plate, Frame C (included with NEMA Type 1)

BOP/AOP Door Mounting Kits
•

SED2-Door-Kit1, BOP/AOP Single Inverter Door Mounting Kit

•

SED2-Door-Kit2, AOP Multi-Inverter Door Mounting Kit

Protection Shields (included with NEMA Type 1)
•

SED2-PS-A, Protection Shield, Frame A

•

SED2-PS-B, Protection Shield, Frame B

•

SED2-PS-C, Protection Shield, Frame C

•

SED2-PS-DE, Protection Shield, Frame D, E

Operator Panel
•

SED2-BOP1, Basic Operator Panel (included with all SED2s)

•

SED2-AOP1, Advanced Operator Panel

LON Interface Option
•

SED2-LONI/F

Modbus Interface Cable
•

10

SED2-MODBUS1, Converts SED2 USS bus to Modbus RTU

Siemens Building Technologies, Inc.

Mechanical Installation

Environmental Conditions
Install the SED2 in a heated, indoor-controlled environment that is free of
moisture and conductive contaminants, such as condensation and dust.
The air entering the unit for ventilation or cooling must be clean and free
of corrosive materials. If installed in a confined space, remove the heat
from the area by ventilation or by air conditioning equipment. The
ambient temperature must be between 14°F and 104°F (–10°C and
40°C) and the relative humidity must be 0% to 95% non-condensing. Do
not mount unit in direct sunlight.
Storage Temperature:
Maximum temperature: +158°F (+70°C) *
Minimum temperature: –40°F (–40°C)
Operating Temperature:
Maximum temperature: +104°F (+40°C) *
Minimum temperature: +14°F (–10°C)
* Be aware of the potential increase in temperature inside a control
cabinet (de-rating is required; contact the factory).
Humidity: Maximum 95% rh (non-condensing)
Altitude: The SED2 can be installed at altitudes up to 3280 ft (1000 m)
above sea level with no reduction in output current rating (contact the
factory).

NOTE:

If installing the SED2 at an altitude higher than 3280 ft
(1000 m) above sea level, de-rating is required.

Location: Do not install the SED2 in an area that is exposed to repeated
shock or vibration, water hazards, or atmospheric pollutants such as dust
and corrosive gases.
EMI and RFI: Do not install the SED2 near powerful sources of
electromagnetic interference (EMI) and radio frequency interference
(RFI) without a suitable filter.

Siemens Building Technologies, Inc.

11

SED2 VFD Startup, Operation, and Maintenance Manual

Dimensions and Mounting for IP20
SED2s
Overall Dimensions and Mounting
Specifications
Table 2. Overall Dimensions of IP20 SED2 in Inches (Millimeters).
Tightening
Torque
lb-in (Nm)

Weight
lb (kg)

2 x M4 Bolts, Nuts, and
Washers, or
Connecting to DIN rail

22
(2.5)

2.9
(1.3)

6.8
(172)

4 x M4 Bolts, Nuts, and
Washers

22
(2.5)

7.5
(3.4)

7.3
(185)

7.7
(195)

4 x M5 Bolts, Nuts, and
Washers

26
(3.0)

12.1
(5.5)

20.5
(520)

10.8
(275)

9.6
(245)

4 x M8 Bolts, Nuts, and
Washers

115
(13)

35.3
(16)

E

25.6
(650)

10.8
(275)

9.6
(245)

4 x M8 Bolts, Nuts, and
Washers

115
(13)

44.1
(20)

F

33.5
(850)

13.8
(350)

12.6
(320)

4 x M8 Bolts, Nuts, and
Washers

221
(25)

116
(53)

Frame
Height Width
Size

Depth

Mounting Specification

A

6.8
(173)

2.9
(73)

5.9
(149)

B

8.0
(202)

5.9
(149)

C

9.6
(245)

D

12

Siemens Building Technologies, Inc.

Mechanical Installation

Mounting Dimensions
Frame Size A

Frame Size B

Frame Size C

0.19
(4.8)

0.22
(5.5)

0.22
(5.5)
8.0
(204)

6.9
(174)

6.3
(160)
0.17
(4.5)

5.4
(138)

6.9
(174)

Frame Size F
Frame Size E
Frame Size D

0.59
(15)

0.68
(17.5)

0.68
(17.5)

VFD0012R1

19.1
(486)

9.3
(235)

31.9
(810)

24.3
(616)

9.3
(235)

11.8
(300)

Figure 1. Mounting Dimensions of IP20 SED2 in Inches (Millimeters).

Mounting Instructions
The IP20 SED2 can mount side-by-side without space in between units.
There must be a minimum clearance at the top and bottom for ventilation
and equipment access.
Vmin.
SIEMENS

VFD0143R1

SED2

SIEMENS

Frame
Size

Vmin Minimum Clearance in
Inches (Millimeters)

A, B, C

4 (100)

D, E

11-3/4 (300)

F

13-3/4 (350)

SED2

Vmin.

Mounting Clearance Note:
If fitted with a protective shield, allow 12-inches (305 mm) of space
between each SED2 to allow for sufficient heat dissipation.

Siemens Building Technologies, Inc.

13

SED2 VFD Startup, Operation, and Maintenance Manual

Gland Plate Installation and Conduit
Connections
CAUTION:
Bonding between conduit connections is not automatic and
must be provided as part of the installation.
Each bonding conductor must be equal or greater in crosssection to the power supply cable.
Installation:

Ground

Conduit
Connections:
.90
(22.8)

VFD0002R1

Ground

Figure 2. Gland Plate Installation and Conduit Connection Diameters for
Frame Size A.

14

Siemens Building Technologies, Inc.

Mechanical Installation

Installation:

Conduit Connections:

nd

ou
Gr

VFD0003R1

Frame Size B

.90
(22.8)

.74
(18.8)

Frame Size C

.90
(22.8)

1.10
(28)

.74
(18.8)

1.10
(28)

Figure 3. Gland Plate Installation and Conduit Connection Diameters for
Frame Size B and C.

Siemens Building Technologies, Inc.

15

SED2 VFD Startup, Operation, and Maintenance Manual

ON
1

20

21

22

23

24

25

12

13

14

15

16

17

26

27

28

29

30

1

2

3

4

5

6

7

8

9

10

11

2

PE

VFD0062R1

1.77
(45.0)

1.77
(45.0)

1.77
(45.0)

1.10
(28.4)

.90
(22.8)

Figure 4. Conduit Connection Diameters for Frame Size D and E
in Inches (Millimeters).
13.5
(343)

6.8
(173)
.3
(58)

1.8
(46)

4.4
(112)

1.8
(46)

1.4
o(36)

VFD0091R1

1.5
(38)

9.0
(229)
o 6.1
(155)

o 0.25
(6)

o 3.5
(89)

.35
(9)

14.0
(356)

1.0
(25)

Figure 5. Conduit Connection Diameters (Bottom View)
for Frame Size F in Inches (Millimeters).

16

Siemens Building Technologies, Inc.

Mechanical Installation

Dimensions and Mounting for NEMA
Type 1 SED2s
Overall Dimensions and Mounting
Specifications
Table 3. Overall Dimensions of NEMA Type 1 SED2 Assembled with a
Protective Shield and a Gland Plate. Dimensions in Inches (Millimeters).
Frame
Height Width Depth Mounting Specification
Size

Tightening
Torque
lb-in (Nm)

Weight
lb (kg)

A

9.1
(231)

2.9
(73)

2 x M4 Bolts, Nuts, and
5.9
Washers, or
(149)
Connecting to DIN rail

22
(2.5)

3.2
(1.5)

B

11.8
(300)

5.9
(149)

6.8 4 x M4 Bolts, Nuts, and
(172) Washers

22
(2.5)

8.3
(3.8)

C

13.8
(351)

7.3
(185)

7.7 4 x M5 Bolts, Nuts, and
(195) Washers

26
(3.0)

13.6
(6.2)

D

24.6
(625)

10.8
(275)

9.6 4 x M8 Bolts, Nuts, and
(245) Washers

115
(13)

37.5
(17.1)

E

29.7
(754)

10.8
(275)

9.6 4 x M8 Bolts, Nuts, and
(245) Washers

115
(13)

46.4
(21.1)

F

54.5
(1384)

16.0
(406)

14.0 4 x M8 Bolts, Nuts, and
(356) Washers

221
(25)

200
(91)

Siemens Building Technologies, Inc.

17

SED2 VFD Startup, Operation, and Maintenance Manual

Mounting Dimensions
Frame Size C
Frame Size B
Frame Size A

0.19
(4.8)

0.22
(5.5)

0.22
(5.5)
8.0
(204)

6.9
(174)

6.3
(160)
0.17
(4.5)

5.4
(138)

6.9
(174)

Frame Size F
Frame Size E

0.59
(15)

Frame Size D
0.68
(17.5)
0.68
(17.5)

VFD0092R2

19.1
(486)

9.3
(235)

51
(1295)

24.3
(616)

15
(381)

9.3
(235)

Figure 6. Mounting Dimensions of NEMA Type 1 SED2
in Inches (Millimeters).

Mounting Instructions
The NEMA Type 1 SED2 must have a minimum clearance at the top and
bottom for ventilation and equipment access. In addition, allow 12-inches
(305 mm) of space between each SED2 to allow for sufficient heat
dissipation.
V

V

min.

min.

SIEMENS

VFD0143R1

18

V

V

min Minimum Clearance
in Inches (Millimeters)

A, B, C

4 (100)

D, E

11-3/4 (300)

F

13-3/4 (350)

SIEMENS

12 Inches
(305 mm)

SED2

Frame
Size

SED2

min.

V

min.

Siemens Building Technologies, Inc.

Mechanical Installation

Dimensions and Mounting for IP54,
NEMA Type 12 SED2s
Overall Dimensions and Mounting
Specifications
Table 4. Overall Dimensions and Mounting Clearances for IP54, NEMA
Type 12 SED2. Dimensions in Inches (Millimeters).
Frame
Size

Overall Dimensions

Mounting Clearance

Mounting
Specification

Tightening
Torque
lb-in (Nm)

Weight
lb (kg)

Height Width Depth

Top

Bottom

Sides

B

15.2 10.6 10.6
(385) (270) (268)

5.9
(150)

5.9
(150)

3.9
(100)

4 x M6 Bolts,
Nuts, and
Washers

44
(5)

22
(10)

C

23.9 13.8 11.2
(606) (350) (284)

5.9
(150)

5.9
(150)

3.9
(100)

4 x M6 Bolts,
Nuts, and
Washers

44
(5)

42
(19)

D

27.0 14.2 13.9
(685) (360) (353)

7.9
(200)

7.9
(200)

5.9
(150)

4 x M8 Bolts,
Nuts, and
Washers

115
(13)

77
(35)

E

34.8 14.2 17.8
(885) (360) (453)

7.9
(200)

7.9
(200)

5.9
(150)

4 x M8 Bolts,
Nuts, and
Washers

115
(13)

105
(48)

F

45.3 17.7 18.6
(1150) (450) (473)

11.8
(300)

9.8
(250)

5.9
(150)

4 x M8 Bolts,
Nuts, and
Washers

177
(20)

178
(81)

Siemens Building Technologies, Inc.

19

SED2 VFD Startup, Operation, and Maintenance Manual

Mounting Dimensions
Frame Size C
Frame Size B
0.19
(4.8)

0.22
(5.5)
22.2
(564)

13.5
(343)

9.1
(230)

12.3
(313)

Frame Size F
Frame Size E
Frame Size D

0.59
(15)

0.68
(17.5)

0.68
(17.5)

43.8
(1112)

33.5
(847)

VFD0013R1

25.5
(647)

12.2
(310)

12.2
(310)

15.7
(400)

Figure 7. Mounting Dimensions of IP54, NEMA Type 12 SED2
in Inches (Millimeters).

20

Siemens Building Technologies, Inc.

Mechanical Installation

Mounting Instructions
There must be a clearance of at least 5-7/8 inches (150 mm) in all
directions. A good bonding between the SED2 and the metal backplate is
necessary to ensure good grounding and low RFI (radio frequency
interference). If necessary, remove some backplate paint and/or use
toothed washers to ensure safety and EMC (electro-magnetic
compatibility). Earth braid screened armored cable provides the best
bond.
V
min.
SIEMENS

S
min.

SIEMENS

S
min.

VFD0144R1

SED2

S
min.

SED2

Vmin.

Frame Size

Smin Minimum Clearance
in Inches (Millimeters)

Vmin Minimum Clearance
in Inches (Millimeters)

B, C

5-7/8 (150)

5-7/8 (150)

D, E

5-7/8 (150)

11-3/4 (300)

F

5-7/8 (150)

13-3/4 (350)

NOTE:

Install the SED2 vertically for optimum cooling. Do not
obstruct the vents on the SED2. Additional ventilation may be
required if the SED2 is mounted horizontally.

Siemens Building Technologies, Inc.

21

SED2 VFD Startup, Operation, and Maintenance Manual

Electrical Installation
DANGER:
•

To ensure safe operation of the SED2, authorized persons
must install and commission it in full compliance with the
warnings, cautions, and notes in this manual. Authorized
persons must also follow general and regional installation
and safety regulations regarding working with high voltages
as well as relevant regulations for the correct use of tools
and protective equipment.

•

The SED2 must be grounded (per IEC 536, Class 1, NEC
and other relevant industry standards). Extremely
hazardous conditions may result if the SED2 is not correctly
grounded.

NOTE: IP20 and NEMA Type 1 SED2s can operate in
ungrounded systems if the Y capacitor is
disconnected or removed.
IP54, NEMA Type 12 SED2s cannot operate in
ungrounded systems. See the Operation in
Ungrounded Systems section for more details.

22

•

The SED2 is suitable for use in a circuit capable of
delivering not more than 10,000 symmetrical amperes, for
a maximum voltage of 240/480/575V when protected by a
time delay Type J, H, or K fuse or circuit breaker.

•

Always wait 5 minutes after disconnecting the SED2 from
the power source before performing any work. The DC link
capacitors of all SED2s remain charged with dangerous
voltages for 5 minutes after all power sources have been
disconnected. When working on IP20 units, note that live
parts are exposed. Do not touch these parts.

•

In cases where a fault in the input or output power wiring
could cause significant equipment damage or severe
physical injury (such as potentially dangerous short
circuits), use additional external precautions to ensure safe
operation (such as independent limit switches and
mechanical interlocks).

Siemens Building Technologies, Inc.

Electrical Installation

Extended Storage: Conditioning of
Capacitors
After an extended period of storage, recharge the capacitors in the SED2.
Calculate the storage time from the date of manufacture or the date code,
and not from the date of delivery. (See the Interpretation of Serial
Numbers and Date Codes section for more details.) The recharge
procedure varies according to the storage period as follows:
Period of
Storage

Required Action

Total Preparation
Time

1 year or less Recharging not required.

No preparation

1 to 2 years

Before issuing the “run” command, connect
the SED2 to input power for one hour.

1 hour

2 to 3 years

Use a variable AC power source as follows:

2 hours

•
•
•
•

Apply 25% of the input voltage for
30 minutes.
Increase the voltage to 50% for an
additional 30 minutes.
Increase the voltage to 75% for an
additional 30 minutes.
Increase the voltage to 100% for an
additional 30 minutes.

The SED2 is then ready for operation.
3 or more
years

Use a variable AC power source as follows:
•
•
•

•

8 hours

Apply 25% of the input voltage for
2 hours.
Increase the voltage to 50% for an
additional 2 hours.
Increase the voltage to 75% for an
additional 2 hours.
Increase the voltage to 100% for an
additional 2 hours.

The SED2 is then ready for operation.

CAUTION:
After an extended period of storage, if capacitors are not
properly recharged, catastrophic damage to the drive can
result.

Siemens Building Technologies, Inc.

23

SED2 VFD Startup, Operation, and Maintenance Manual

Input Power and Motor Connections
DANGER:
•

Make certain that the motor rated full load amps (FLA)
does NOT exceed the rated output current of the SED2
controlling it.
When multiple motors are simultaneously operated by the
SED2, the sum of all motor rated FLA values must be
less than or equal to the SED2 controlling them.

•

Never switch on the SED2 with it open.

•

Always isolate the input power cables before connecting
them to the SED2.

•

Always use insulated tools when working on input power
and motor terminals.

•

Ensure that terminal covers are securely replaced after
connecting the input power and motor cables.

WARNING:

24

•

Verify that the SED2 and motor are correctly rated for the
input power voltage.

•

Verify that the input power cables are correctly sized for
the anticipated use.

•

Confirm that appropriate circuit breakers or fuses have
been installed between the input power supply and the
SED2.

•

Never use high-voltage insulation test equipment on any
cables connected to the SED2.

Siemens Building Technologies, Inc.

Electrical Installation

Operation in Ungrounded Systems
IP20 and NEMA Type 1 SED2s can operate in ungrounded systems if the
Y capacitor is disconnected or removed. They remain in operation when
an input ground fault occurs. In the event of an output ground fault, the
SED2 switches off and displays fault code F0001.

NOTE:

IP54, NEMA Type 12 SED2s cannot operate in ungrounded
systems.

Ungrounded Systems and Y Capacitor
In ungrounded systems, remove or disconnect the Y capacitor (and install
an output choke/load reactor) per Figures 8 through 11.

1

VFD060R1

2

Figure 8. Disconnecting Y Capacitor in SED2 Frame Size A.

Siemens Building Technologies, Inc.

25

SED2 VFD Startup, Operation, and Maintenance Manual
1

2

VFD0061R1

3

Figure 9. Disconnecting Y Capacitor in SED2 Frame Size B and C.

ON

1

20

21

22

23

24

25

12

13

14

15

16

17

26

27

28

29

30

1

2

3

4

5

6

7

8

9

10

11

2

PE

Torx driver T20

M4
S crew

5192Z 0 3en

Figure 10. Disconnecting Y Capacitor in SED2 Frame Size D and E.

26

Siemens Building Technologies, Inc.

Electrical Installation

T30
Torx screwdriver

VFD0063R1

M6

Figure 11. Disconnecting Y Capacitor in SED2 Frame Size F.

Siemens Building Technologies, Inc.

27

SED2 VFD Startup, Operation, and Maintenance Manual

Access to Connection Terminals
To access input power and output motor connection terminals, remove
the cover, operator panel, terminal cover, and I/O module per Figures 12
through 17.
The I/O module is located under the operator panel. In frame sizes A
through C/IP20, and NEMA Type 1 SED2s, the operator panel directly
connects to the I/O module. In frame sizes D through F, and all IP54
NEMA Type 12 SED2s, the operator panel connects to the I/O module via
a cable.
In all SED2s, the control module is located under the I/O module.

1

VFD0064R1

VFD0065R1

2

Figure 12. Removing Operator Panel (All Frame Sizes).

1
1
2

Figure 13. Removing Terminal
Cover (All Frame Sizes).

28

VFD0067R1

VFD0066R1

2

Figure 14. Removing I/O Module
(All Frame Sizes).

Siemens Building Technologies, Inc.

Electrical Installation

VFD0068R1

1

Figure 15. Removing Cover on Frame Sizes B and C.

1

2

3

4

VFD0069R1

5
6

Figure 16. Accessing Connection Terminals for Frame Sizes D and E.

Siemens Building Technologies, Inc.

29

SED2 VFD Startup, Operation, and Maintenance Manual

1
2

4
6

3

VFD0070R1

5

Figure 17. Accessing Connection Terminals for Frame Size F.

30

Siemens Building Technologies, Inc.

Electrical Installation

Motor Frequency and Unit of Measurement DIP
Switches
In all versions of the SED2, DIP switches for selecting motor frequency
and unit of measurement are located on the control module under the I/O
module. (See Access to Connection Terminals section for disassembly
instructions.)
DIP Switch

Position

2*

ON

North American operation (60 Hz, hp).

OFF

European operation (50 Hz, kW), factory default.

OFF

Not for customer use.

1

Function

NOTE:
This switch must be OFF for correct operation.

* Set DIP switch 2 ON (60 Hz, hp) for all North American installations.

DIP SWITCHES

ON

VFD0145R1

1 2

Figure 18. Location of Motor Frequency and Unit of Measurement DIP
Switches on Control Module.

Siemens Building Technologies, Inc.

31

SED2 VFD Startup, Operation, and Maintenance Manual

Input Power and Motor Terminal Layout
DANGER:
The following terminals carry hazardous voltages even when
the SED2 is not running:
•
•
•

Input power terminals: L1, L2, L3
Motor terminals: U, V, W
Link terminals: DC-, DC+/B+, DC/R+, B- (not for
customer use)

L3

L2

VFD0071R1

L1

R+
DC

B-

DC+

DC-

U

V

W

PE
(Ground)

(Ground)

Figure 19. Input Power and Motor Terminal Layout for SED2 Frame Size A.

L3

L2

L1

DC- DC+
B+

DC
R+

B-

U

V

W

VFD0072R1

PE

PE
(Ground)

(Ground)

Figure 20. Input Power and Motor Terminal Layout for SED2
Frame Size B and C.

32

Siemens Building Technologies, Inc.

Electrical Installation

VFD0073R1

L1

L2

L3

DC-

DC+
B+

DC
R+

PE
(Ground)

B-

U

V

W

(Ground)

Figure 21. Input Power and Motor Terminal Layout for SED2
Frame Size D and E.

L1

R+

B+

B+

DC-

B-

DC+

DC+

DC+

L2

L3

U

V

W

VFD0074R1

PE

PE
(Ground)

(Ground)

Figure 22. Input Power and Motor Terminal Layout for SED2
Frame Size F.

Siemens Building Technologies, Inc.

33

SED2 VFD Startup, Operation, and Maintenance Manual

Tightening Torque for Input Power and Motor
Connections
Frame size

A

B

C

D

E

F

Tightening
torque
lb-in (Nm)

9.7
(1.1)

13.3
(1.5)

19.9
(2.25)

88.5
(10) max.

88.5
(10) max.

442
(50)

Cable Cross-Sections for Input Power and Motor
Cables
Table 5. Cable Cross-Sections for Input Voltage Range
3Ø AC 200V through 240V.
Input Power Cable
Maximum
Output
rating
kW (hp)

34

Motor Cable

Minimum
CrossSection
AWG (mm2)

Maximum
CrossSection
AWG (mm2)

Minimum
CrossSection
AWG (mm2)

Maximum
CrossSection
AWG (mm2)

0.37 (.50)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

0.55 (.75)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

0.75 (1.0)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

1.1 (1.5)

17 (1)

9 (6)

17 (1)

9 (6)

1.5 (2.0)

15 (1.5)

9 (6)

17 (1)

9 (6)

2.2 (3.0)

13 (2.5)

9 (6)

17 (1)

9 (6)

3 (4.0)

11 (4)

7 (10)

15 (1.5)

7 (10)

4 (5.0)

11 (4)

7 (10)

11 (4)

7 (10)

5.5 (7.5)

11 (4)

7 (10)

11 (4)

7 (10)

7.5 (10)

7 (10)

2 (35)

7 (10)

2 (35)

11 (15)

5 (16)

2 (35)

16 (5)

2 (35)

15 (20)

5 (16)

2 (35)

5 (16)

2 (35)

18.5 (25)

3 (25)

2 (35)

5 (16)

2 (35)

22 (30)

2 (35)

2 (35)

2 (35)

2 (35)

30 (40)

0 (50)

-5 (150)

0 (50)

-5 (150)

37 (50)

-2 (70)

-5 (150)

-2 (70)

-5 (150)

45 (60)

-2 (70)

-5 (150)

-3 (95)

-5 (150)

Siemens Building Technologies, Inc.

Electrical Installation
Table 6. Cable Cross-Sections for Input Voltage Range
3Ø AC 380V through 480V.
Input Power Cable
Maximum
Output
rating
kW (hp)

Motor Cable

Minimum
CrossSection
AWG (mm2)

Maximum
CrossSection
AWG (mm2)

Minimum
CrossSection
AWG (mm2)

Maximum
CrossSection
AWG (mm2)

0.37 (.50)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

0.55 (.75)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

0.75 (1.0)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

1.1 (1.5)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

1.5 (2.0)

17 (1)

13 (2.5)

17 (1)

13 (2.5)

2.2 (3.0)

17 (1)

9 (6)

17 (1)

9 (6)

3 (4.0)

17 (1)

9 (6)

17 (1)

9 (6)

4 (5.0)

17 (1)

9 (6)

17 (1)

9 (6)

5.5 (7.5)

13 (2.5)

7 (10)

13 (2.5)

7 (10)

7.5 (10)

11 (4)

7 (10)

11 (4)

7 (10)

11 (15)

9 (6)

7 (10)

9 (6)

7 (10)

15 (20)

7 (10)

2 (35)

7 (10)

2 (35)

18.5 (25)

7 (10)

2 (35)

7 (10)

2 (35)

22 (30)

5 (16)

2 (35)

5 (16)

2 (35)

30 (40)

3 (25)

2 (35)

3 (25)

2 (35)

37 (50)

3 (25)

2 (35)

2 (35)

2 (35)

45 (60)

2 (35)

-5 (150)

2 (35)

-5 (150)

55 (75)

-2 (70)

-5 (150)

-2 (70)

-5 (150)

75 (100)

-2 (70)

-5 (150)

-3 (95)

-5 (150)

90 (125)

-2 (70)

-5 (150)

-3 (95)

-5 (150)

Siemens Building Technologies, Inc.

35

SED2 VFD Startup, Operation, and Maintenance Manual
Table 7. Cable Cross-Sections for Input Voltage Range
3Ø AC 500V through 600V.
Input Power Cable
Maximum
Output
rating
kW (hp)

Motor Cable

Minimum
CrossSection
AWG (mm2)

Maximum CrossSection
AWG (mm2)

Minimum
CrossSection
AWG (mm2)

Maximum CrossSection
AWG (mm2)

0.75 (1.0)

17 (1)

7 (10)

17 (1)

7 (10)

1.1 (1.5)

17 (1)

7 (10)

17 (1)

7 (10)

1.5 (2.0)

17 (1)

7 (10)

17 (1)

7 (10)

2.2 (3.0)

17 (1)

7 (10)

17 (1)

7 (10)

3 (4.0)

17 (1)

7 (10)

17 (1)

7 (10)

4 (5.0)

17 (1)

7 (10)

17 (1)

7 (10)

5.5 (7.5)

15 (1.5)

7 (10)

15 (1.5)

7 (10)

7.5 (10)

13 (2.5)

7 (10)

13 (2.5)

7 (10)

11 (15)

11 (4)

7 (10)

11 (4)

7 (10)

15 (20)

9 (6)

2 (35)

9 (6)

2 (35)

18.5 (25)

9 (6)

2 (35)

9 (6)

2 (35)

22 (30)

7 (10)

2 (35)

7 (10)

2 (35)

30 (40)

5 (16)

2 (35)

5 (16)

2 (35)

37 (50)

3 (25)

2 (35)

5 (16)

2 (35)

45 (60)

3 (25)

-5 (150)

3 (25)

-5 (150)

55 (75)

0 (50)

-5 (150)

2 (35)

-5 (150)

75 (100)

-2 (70)

-5 (150)

0 (50)

-5 (150)

90 (125)

-2 (70)

-5 (150)

0 (50)

-5 (150)

36

Siemens Building Technologies, Inc.

Electrical Installation

Input Power Connection
DANGER:
•

As supplied, the SED2 must be grounded (per IEC
536, Class 1, NEC and other relevant industry
standards). Extremely hazardous conditions can occur if
the SED2 is not correctly grounded.

•

Use only permanently wired input power connections.
Only hard-wired input power connections are permissible.
Use Class 1 60/75° copper wire only.

•

The cross-section of the ground-bonding conductor must
be at least equal to the input power cables.

•

The following terminals can carry hazardous voltages
even when the SED2 is not running:
−
−
−

Input power terminals: L1, L2, L3
Motor terminals: U, V, W
Link terminals: DC-, DC+/B+, DC/R+, B- (not for
customer use)

Connect input power to SED2 terminals L1, L2, and L3 (Figures 19
through 22).

Siemens Building Technologies, Inc.

37

SED2 VFD Startup, Operation, and Maintenance Manual

Motor Cable Length
Maximum motor cable length is 164 ft (50m). Motor cable length is given
to ensure performance of only the SED2, not the suitability of the motor
when connected to a SED2 at this distance.

!

1. Never run control or drive input
wires in the same conduit as
the drive output wires.

2. Keep the distance from the drive
to the motor as short as possible
to maximize motor life.

4. If a disconnect is mounted on the
load side of your drive, it is desirable
to wire an auxiliary contact to the drive
that will disable drive operation when
the disconnect opens. (The wiring for
this contact must not be run in the same
conduit as the drive output wires).

SED2

VFD0014R2

M

3. If needed, use
SBT-specified input line
reactors to ensure a good
impedance match with
your drive.

5. Inverter duty motors are recommended.
Install motors within their guidelines. Use
dV/dT filters, output reactors, or other load
conditioners as applicable or as specified
by the motor manufacturer.

Figure 23. Motor Cable Installation Notes.

NOTE:

38

If connecting multiple motors to one SED2, the total length of
the individual motor cables must not exceed the maximum
motor cable length.

Siemens Building Technologies, Inc.

Electrical Installation

Motor Connection
(Wye "Y"/Star or Delta Configuration)
DANGER:
Do not use the SED2 with a motor of higher nominal power
rating than the SED2, or a nominal power less than half that
of the SED2. Only operate the SED2 when the nominal
current (P0305) is set to match motor rating continuous
current.

The motor nameplate indicates the required supply voltage and method of
connection. In general, larger 400/690V motors connect in a delta (∆)
configuration and smaller 230/400V motors connect in a Wye “Y” or star
configuration (Figure 24).
Connect motor wiring to SED2 terminals U, V, and W (Figures 19 through
22).

MOTOR TERMINALS

VFD0029R2

U1
W2

V1
U2

W1
V2

U1
W2

V1
U2

W1
V2

Wye "Y"

Figure 24. Delta and Star (Wye, Y) Motor Connections.

Siemens Building Technologies, Inc.

39

SED2 VFD Startup, Operation, and Maintenance Manual

Direction of Motor Rotation
To change the direction of motor rotation, cross-connect two of the output
conductors on the SED2 (Figure 25). This is the desired method for
changing rotation.

NOTE:

The Reverse Output Phase Sequence parameter (P1820) can
also reverse the direction of rotation. However, if the SED2 is
reset to factory defaults, P1820 is reset to OFF.

VFD0030R1

SED2

SED2

U

U

V

V

W

W

U

V

V

U

W

W

M

M

Figure 25. Direction of Motor Rotation.

40

Siemens Building Technologies, Inc.

Electrical Installation

Motor Overload Protection
WARNING:
The SED2 is capable of providing internal motor overload
protection in accordance with UL508C, Section 42. Accurately
configure motor parameters for the motor overload protection
2
to operate correctly. See Motor I t Temperature Reaction
2
parameter (P0610); I t is On by default.
Motor overload protection also can be provided using an
external PTC temperature-thermistor sensor (disabled by
default via Motor Temperature Sensor parameter (P0601)).
During operation below nominal speed, the cooling effect of the fans
mounted to the motor shaft is reduced. Therefore, most motors require
de-rating if operated continuously at low frequencies. To ensure that
motors are protected from overheating under these conditions, mount a
PTC temperature-thermistor sensor to the motor and connect it to the
control terminals of the SED2.

NOTE:

To enable the switch-off function with a PTC temperaturethermistor sensor, set Motor Temperature Sensor parameter
(P0601) to 1 for PTC temperature-thermistor sensor. Use a
shielded cable to connect the PTC temperature-thermistor
sensor.
14

VFD0031R1

SED2
CONTROL
TERMINALS

15

Figure 26. External Motor Overload Protection.

Siemens Building Technologies, Inc.

41

SED2 VFD Startup, Operation, and Maintenance Manual
5192Z10

SED2

Connection of Multiple
Motors
The SED2 can control several motors in
parallel as long as all of the motors have
the same power rating. When multiple
motors connect to the SED2 in parallel,
the motors cannot operate individually.
NOTES:
1. When determining the required
power, take into account the total
current from all the motors (or the
total of all ratings).

M1

2. The sum of all individual motor cable
lengths must not exceed the
maximum motor cable length.

42

M2

M3

M4

Mn

∑ IM1..Mn ≤ ISED2, max.
∑ PM1..Mn ≤ PSED2, max.
Figure 27. SED2 Connection
to Multiple Motors.

Siemens Building Technologies, Inc.

Electrical Installation

Analog Input DIP Switches
WARNING:
When using analog inputs, the DIP switches must be correctly
set and the analog inputs correctly configured before being
enabled. If this is not done, the motor may start inadvertently.
After completing settings for motor frequency and unit of measurement
DIP switches, and wiring for input power and motor connections, reattach
the I/O module.
For all versions of the SED2, the DIP switches used to configure the
analog inputs are located on the I/O module. (See Access to Connection
Terminals section for disassembly instructions.)
DIP
Switch

Position

1

OFF

Analog Input 1, voltage 0 to 10 Vdc, factory default.

OFF

Analog Input 1, Ni 1000 sensor input with parameter setting
P0756[0]=5.

ON

Analog Input 1, current 0 to 20 mA.

OFF

Analog Input 2, voltage 0 to 10 Vdc, factory default.

OFF

Analog Input 2, Ni 1000 sensor input with parameter setting
P0756[1]=5.

ON

Analog Input 2, current 0 to 20 mA.

2

Function

Siemens Building Technologies, Inc.

43

SED2 VFD Startup, Operation, and Maintenance Manual

DIP SWITCHES
ON

VFD0146R1

1 2

20

21

22

23

24

25

12

13

14

15

16

17

26

27

28

29

30

1

2

3

4

5

6

7

8

9

10

11

Figure 28. Location of Analog Input DIP Switches on I/O Module.

Control Terminal Connections
Control Terminal Layout
The control terminals (Figures 29 and 30) are located on the I/O module.
The I/O module is identical for all versions of the SED2. The I/O module is
located under the operator panel. (See the Access to Connection
Terminals section for disassembly instructions.)
Connect control wiring to SED2 control terminals 1 through 30 per sitespecific drawings. See the Analog and Digital I/O Control Terminal
Connections section for examples of connections.

44

Siemens Building Technologies, Inc.

Electrical Installation

NOTE:
1.

Use only shielded cables for control cables.

2.

Route control cables in separate cable trunks at least
7-3/4 inches (20 cm) away from motor and power cables.

After completing analog input DIP switch settings and wiring for control
terminal connections, reattach the SED2 cover and operator panel.

AIN1
On = [A], 0 - 20 mA
Off = [V], 0 - 10 V

ON

RL1
NC

RL1 RL1
NO COM

1

20

21

2

22

RL2
NC

RL2
NO

RL2
COM

23

24

25

P+

N-

29

30

AIN2
On = [A], 0 - 20 mA
Off = [V], 0 - 10 V
AOUT AOUT PTC
1+
1A

VFD0017R1

12

13

PTC
B

DIN
5

DIN AOUT AOUT ISO
6
2+
20V

14

15

16

17

26

27

28

10V

0V

AIN
1+

AIN
1-

DIN
1

DIN
2

DIN
3

DIN
4

ISO
24V

1

2

3

4

5

6

7

8

9

AIN
2+

AIN
2-

10

11

Figure 29. SED2 Control Terminals on I/O Module.

NOTES: 1. Analog inputs 1 and 2 can be optionally configured for direct
connection of a Ni 1000 temperature sensor. The sensor
connects between terminals 4 and 2 or 11 and 2.
2. 0 to 10 Vdc analog inputs connect between terminals 2 and 3.
3. 0 mA to 20 mA and 4 mA to 20 mA analog inputs connect
between terminals 3 and 4.
When using a 4 mA to 20 mA input, DIP switches must be
set to appropriate input.

Siemens Building Technologies, Inc.

45

SED2 VFD Startup, Operation, and Maintenance Manual
Motor Parameters
r0021 - r0035 Motor performance data
P0304 - P0313 Standard data
Calculation of motor parameters
P0340
P0601 - P0640 Motor protection
Motor data identification
P1910
Reference frequency
P2000

Drive Parameters
User acces level
P0003
Commissioning parameter filter
P0010
VFD DC-link voltage
r0026
r0039 - P0040 Energy consumption meter
US / Europe
P0100
r0206 - r0209 Performance data
P1000 - P1028 Frequency setpoint
P1080 - P1110 Frequency adjustment
200 to 240V, 3OAC
380 to 480V, 3OAC
500 to 600V, 3OAC
L1
L2
L3

DC/R+
DC/B+
U
V
W
PE
PE

PE

M
3

L1L2L3 PE
1

Drive Features
P1270
Enable essential mode
P1210 - P1212 Automatic restart

+10Vdc

2

+0Vdc

4
Analog Inputs
1 and 2
P0756 - P0762

Ni 1000

3
V: 0 to 10V
2 to 10V
I: 0 to 20 mA
4 to 20 mA 2

+
12
D/A
AI1

13
+
26

A/D
D/A

11
10
V: 0 to 10V
2 to 10V
AI2
I: 0 to 20 mA
A/D
4 to 20 mA 2
0V
Digital Input
28 Isolated 0V (output)
P0700
Command source
9 Isolated 50 mA at
P0701 - P0706 P0705 counter
18 to 32Vdc (output)
P0722 - P0725 NPN / PNP
5 DI1
P0707 - P0708 Analog Inputs
CPU
1 and 2 configured
6 DI2
as digital inputs
7 DI3

V: 0 to 10V
2 to 10V
I: 0 to 20 mA

27
120V, 2A or 230V, 1A
20
21 Relay
Output 1
22
120V, 2A or 230V, 1A

Digital Output
P0731 - P0732
r0747 - r0748

23
24 Relay
Output 2
25
BOP
r0000
P0005
r0019 - r0039

opto isolated

8 DI4
16 DI5
17 DI6

AO2

Analog Output
r0770 - P0781

- 4 to 20 mA

Ni 1000

PID
P2200
P2201 - P2231
P2240 - r2260
P2253 - P2305
P2264 - r2272

V: 0 to 10V
2 to 10V
I: 0 to 20 mA

- 4 to 20 mA
0V

PTC
P0601

AO1

14
Motor
PTC

BOP (Standard)

15

AOP
See AOP
Operating
Instructions

Enable PID
Fixed setpoint
PID setpoint
Standard setpoint
PID feedback
AOP (Optional)
RS-485

Communications
P2000 - r2091

29 30

Figure 30. SED2 Terminal Connections and Related Parameters.

46

Siemens Building Technologies, Inc.

Electrical Installation

Analog and Digital I/O Control Terminal
Connections
Figures 31 through 35 show typical analog and digital input/output control
terminal connections.
WARNING:
When using analog inputs, the DIP switches must be correctly
set and the analog inputs correctly configured before enabling
them. If this is not done, the motor may start inadvertently.
5

DIN2

7
DIN3

8
DIN4

16
DIN5

DC-ISOLATED

DIN1

6

17
DIN6

9

VFD0048R1

PNP
or

28

NPN

ISOLATED +24 Vdc
(OUTPUT)
ISOLATED 0 Vdc
(OUTPUT)

Figure 31. Digital Inputs 1 through 6.

EXTERNAL 0-10V

VFD0022R1

+

EXTERNAL 0-20 mA
SPEED POTENTIOMETER

2

2
3

3

1

4

2

4.7k OHM
MINIMUM

+10 V

0V

3
AIN1+

A/D

VFD 24V dc Powered 0-20 mA Device
(Power consumption cannot exceed 100 mA)

4
AIN1-

10

mA

VFD0050R1

2
3

AIN2+

11

A/D

AIN2-

VFD0021R1

4
24V ac Power

9
28

Figure 32. Analog Inputs 1 and 2.

Siemens Building Technologies, Inc.

47

VFD0049R1

SED2 VFD Startup, Operation, and Maintenance Manual

1

1

2

2

3

11

DIN7

DIN8
4

12

Figure 33. Connection of Analog Inputs 1 and 2 as
Digital Inputs 7 and 8.

120V, 2A or 230V, 1A
20
21

RELAY
OUTPUT 1

22
120V, 2A or 230V, 1A
23
VFD0150R1

24

RELAY
OUTPUT 2

25

Figure 34. Digital Outputs 1 and 2.

+
12

D/A

AOU T1
-

V : 0 - 10 V
2 - 10 V
I: 0 - 20mA
4 - 20mA

ANALOG OUTPU T
r0770 - P0781

13

VFD0051R1

+
26

D/A

AOU T2
27

V : 0 - 10 V
2 - 10 V
I: 0 - 2 0mA
4 - 20mA

Figure 35. Analog Outputs 1 and 2.

48

Siemens Building Technologies, Inc.

Parameters

Parameters
Overview
The SED2 uses parameters to define the required operating
characteristics, such as motor data, ramp times, and maximum and
minimum frequency. Users enter and modify the SED2 parameters using
the Basic Operator Panel, the Advanced Operator Panel, or a serial
interface.
Each parameter consists of the letter "r" or "P", followed by four
numbers, such as r0000 or P0010. The letter "r" identifies read-only
parameters. The letter "P" identifies programmable parameters.

Parameter Structure
Figure 36 depicts the structure of the SED2 parameters.
•

User Access Level parameter (P0003) selects the access level for
using the parameters (1=standard, 2=extended, or 3=expert). The
access level selected via parameter P0003 determines the number
of parameters that are accessible by the user. For most applications,
the Standard (1) and Extended (2) levels are sufficient. The factory
default setting is P0003=1 (Standard).

•

The filters of Parameter Filter parameter (P0004) categorize the
parameters that are available via the access level according to
functionality. The filters/categories enable a more focused
operational approach. If parameter P0004=0 for no filter/category,
then all parameters for a selected user access level are available.

NOTE:

Some parameters are intended for commissioning only and
can be viewed as a function of this filter. In order to set these
parameters, P0010 must be set to 1 (quick commissioning).

Parameter Indexes
Certain parameters have indexes. The indexes provide subsets of a
particular parameter function and group together closely related
parameter type information. The Parameter Reference Guide (Document
Number 125-3214) lists any indexes associated with a parameter.

Siemens Building Technologies, Inc.

49

SED2 VFD Startup, Operation, and Maintenance Manual
The following indexes are associated with P0700, P1000, and digital
input and output parameters:
•

IN000 (AUTO), 1st command data set (CDS)

•

IN001 (HAND), 2nd command data set (CDS)

The following indexes are associated with analog input and output
parameters:
•

IN000, Analog input 1, AO1

•

IN001, Analog input 2, AO2

NOTE:

Throughout this manual, a parameter number followed by [0]
or [1] denotes index number 000 or 001 respectively.
P0004=22
PI Controller

P0

00

, Acce

ss Leve
l Ex
pe
rt

cess Leve
, Ac
lE
=2
xt
03
s
s
L
e
e
c
ve
l
Ac

P0004=3
Motor Data

andard
St

P0003=
1,

ed

P0004=20
Communication

3= 3

d
en

P0
0

P0004=21
Alarms, Warnings,
and Monitoring

P0004=2
Inverter Unit

P0004=7
Commands and
Digital I/O

P0004=13
Motor Control

P0004=8
Analog I/O

P0004=12
Drive Features

VFD0019R1

P0004=8, P0003=2
Parameters in
Access Levels 1 and 2
associated with
Analog I/O are Available

P0004=10
Setpoint Channel
and Ramp Generator

P0004=8
Analog I/O

P0004=8, P0003=3
Parameters in
Access Levels 1, 2, and 3
associated with
Analog I/O are Available

P0004=8, P0003=1
Parameters in
Access Levels 1
associated with
Analog I/O are Available

Figure 36. SED2 Parameter Access Levels and Filters.

50

Siemens Building Technologies, Inc.

SED2 Operator Panels

SED2 Operator Panels
Overview
The SED2 includes the Basic Operator Panel (BOP) mounted as
standard. An Advanced Operator Panel (AOP) is available as an option.

Figure 37. Basic Operator Panel
(BOP).

Figure 38. Advanced Operator
Panel (AOP).

NOTES:
1. On initial startup, the SED2 display values alternate
between 0.0 Hz (zero) and the speed it would be running if
it were given a start command.
2. The BOP or AOP can connect to or disconnect from the
SED2 without switching off power.

Basic Operator Panel (BOP)
The BOP provides access to the parameters of the SED2 and allows for
application-specific settings of the SED2.
The parameters and measured values are shown in a 5-digit LCD
display. The BOP can mount directly onto the SED2 or, alternatively, it
can mount into a control cabinet door using a special installation kit
(SED2-DOOR-KIT1 or SED2-DOOR-KIT2).
The BOP cannot store parameter data.

Siemens Building Technologies, Inc.

51

SED2 VFD Startup, Operation, and Maintenance Manual

Advanced Operator Panel (AOP)
For information on the AOP, see the AOP Operating Instructions
(Document Number 125-3206). AOP features include a real-time clock,
ability to upload/download parameter sets, and control of a network of up
to 31 drives.

BOP Display and Pushbuttons
Operator
Panel/Button

Function

Status
display

Description
The LCD (five-digit display for BOP; multi-line, clear-text
display for AOP) displays the settings presently used by
the SED2 or used to set parameters in the SED2.
Press this pushbutton to start the SED2.

Start motor

OFF1

Press this pushbutton to stop the SED2 within
the selected ramp-down time.
As part of the factory setting, this pushbutton is
enabled for manual mode.

Stop motor

OFF2

Press this pushbutton twice (or once with
sustained pressure) to cause the motor to
coast freely to a standstill.
This function is enabled in the manual and
automatic operating modes.

Change to
manual
control

Places the SED2 in HAND mode.

Change to
automatic
control

Places the SED2 in AUTO mode.

Increase
value

Decrease
value

52

As part of the factory setting, this pushbutton is enabled for
manual mode.

Press this pushbutton to increase the current display value
during parameter setting.
In manual mode, this pushbutton increases the speed
(internal motor potentiometer).
Press this pushbutton to decrease the current display
value during parameter setting.
In manual mode, this pushbutton decreases the speed
(internal motor potentiometer).

Siemens Building Technologies, Inc.

SED2 Operator Panels

Operator
Panel/Button

Function

Description
Press this pushbutton to do one of the following:

Access to
parameters

•

Access the parameters.

•

Exit a parameter by accepting its value.

Press this pushbutton to display additional information.
Press and hold this pushbutton for three seconds for a
quick view display.
Press this pushbutton repeatedly to display DC-V/A/Hz/V.
Press and hold this pushbutton for three seconds to return
to normal view.
Multiple display mode:
When you press this pushbutton for three seconds with
power applied, the following information displays:

Functions

•

DC link voltage
(indicated by d – units V)

•

Output current (A)

•

Output frequency (Hz)

•

Output voltage
(indicated by o – units V)

Repeatedly press the pushbutton to cycle through these
display items. Press this pushbutton again for a sustained
time to exit the multiple display mode.
The value selected in P0005 (Drive Display for r0000
parameter). If P0005 is configured to display any of these
items (1 to 4), the value does not redisplay.
Jump function:
You can jump from any parameter (rXXXX or PXXXX)
directly to r0000 (Drive Display parameter) by briefly
pressing the Fn pushbutton. This allows you to modify
another parameter if required. After jumping to r0000,
press the Fn pushbutton again to return to the starting
point.

Siemens Building Technologies, Inc.

53

SED2 VFD Startup, Operation, and Maintenance Manual
NOTES:
1.

If you attempt to modify a parameter that cannot be modified under the
current conditions (for example, a parameter that cannot be modified during
operation or that can only be modified in the Quick Commissioning mode),
the display reads:

2.

Busy Signal — While changing parameters, the BOP can display:
for a maximum of 5 seconds. This display means that the SED2 is busy
with higher-priority activities.

3.
Displays when SED2 is processing information and will not respond to input
actions until processing is complete.

54

Siemens Building Technologies, Inc.

Commissioning

Commissioning
WARNING:

•

Only authorized personnel trained in the setup, installation,
commissioning, and operation of the SED2 may work on the
product and mechanical system.

•

SED2s operate at high voltages. In some components,
operation of electrical equipment involves using dangerous
voltages.

•

In cases where faults in the control equipment could cause
significant equipment damage or severe physical injury (such
as potentially dangerous short circuits), use external
precautions to ensure and to enforce safe operation (such as
independent limit switches and mechanical interlocks).

•

Emergency stop facilities must remain functional in all operating
modes of the control equipment. Resetting the emergency stop
facility must not result in an uncontrolled or undefined restart.
Do not use the SED2 as an emergency stop mechanism.

•

The equipment incorporates internal motor overload protection
2
in accordance with UL508C, Section 42. See Motor I t
2
Temperature Reaction parameter (P0610); I t is ON by default.
(Motor overload protection can also be provided with an
external PTC temperature-thermistor sensor disabled by default
via Motor Temperature Sensor parameter (P0601). See the
Motor Overload Protection section in this manual for details.)
For reliable motor overload protection, the motor parameters
must be configured accurately.

•

Certain parameter settings can cause the SED2 to start
automatically or to restart automatically after a fault or an input
power failure (provided the fault is eliminated or acknowledged
or the supply voltage is restored).

Siemens Building Technologies, Inc.

55

SED2 VFD Startup, Operation, and Maintenance Manual

Motor Nameplate Data for Parameter
Settings
You can modify motor data via the parameter settings only if
Commissioning Parameter Filter P0010=1, for the quick commissioning
procedure.
Motor control via the BOP is enabled in Hand mode by default. To
enable motor control via the BOP during the quick commissioning
procedure, set Selection of Command Source parameter P0700[0]=1 (for
BOP) and Selection of Frequency Setpoint P1000[0]=1 (for motor
potentiometer setpoint).
If the BOP is configured for control (P0700[0]=1 for BOP), the motor
stops when the BOP is removed.

P0307
P0304
P0310

VFD0032R1

P0305
P0311
P0309

SIEMENS
PE 21 PLUS TM

PREMIUM EFFICIENCY

LOW VOLTAGE
CONNECTION
4
6
5

Type : RGZZESD
Rating : Cont
HP : 3
Ins Class : F
7
8
9
Volts : 230YY/460Y
Serv Factor : 1,0
1
2
3
o
Amps : 7,8 / 3,9
Amb Temp : 40 C
LINE
RPM : 1740
Temp Rise : Class B
HIGH VOLTAGE
NEMA nom Eff : 87,5 %
NEMA design : B
CONNECTION
4
5
6
Frame : 182 T
KVA Code : K
Sh end brg : 30BC02JP3
Weight : 95 lbs
7
8
9
Opp end brg : 30BC02JP3
Serial No : M00T0194 CE 18 1 2 3
Part No : 1MJP1824YP60 LR 39020
LINE
TEFC
3 PH
60 Hz

Figure 39. Motor Nameplate Data for Commissioning Parameters.

56

Siemens Building Technologies, Inc.

Commissioning

Prerequisites to Startup Procedure
To ensure reliable SED2 operation and to avoid any extra costs related
to loss or reduction of warranty coverage, a factory certified specialist
should complete this startup procedure.
Complete the following checklist and maintain it in a secure location as
service personnel may request this information.
CAUTION:
The SED2 has no isolating switch on the input power and is live as
soon as the input power is connected. The SED2 remains with the
(green start pushbutton) or until it
output disabled until you press
receives a digital On command signal.
Check

Step

(

)

1.

The SED2 is thoroughly tested at the factory. Verify that the
SED2 is free of shipping and installation damage. Shipping
damage is not covered by the Siemens Building
Technologies, Inc. warranty; claims must be filed directly
with the shipping company as soon as possible.

(

)

2.

Verify that the model numbers and the voltage ratings are as
specified in the purchase order by matching the nameplate
data of each unit to the purchase order.

(

)

3.

Review the appropriate sections of this manual and verify
that the mechanical and electrical installation procedures
are complete.
Review any option instructions and job schematics provided
with the SED2.
CAUTION:
Failure to comply with mechanical and electrical installation
requirements may void the product warranty.

(

)

4.

Verify that the 50/60 Hz DIP switch has been set to the
appropriate setting, as instructed in the Motor Frequency
and Unit of Measurement DIP Switches section of this
manual.

Siemens Building Technologies, Inc.

57

SED2 VFD Startup, Operation, and Maintenance Manual
(

)

5.

Inspect the security of the input power wiring, ground
connections, motor wiring, and all control circuit
connections, as identified in the SED2 documentation.
IMPORTANT:

Verify that the cross–section and length of
the input power and motor cables are
correct.

IMPORTANT:

Confirm that the input power connects to
the SED2 input terminals: (L1, L2, L3)
and NOT to the output motor terminals:
(U, V, W).

IMPORTANT:

(

)

6.

Verify that all input power wires (L1, L2, L3)
and motor wires (U, V, W) are securely
tightened down to their lugs. Loose wire
connections may cause problems at any
time, and are not covered under warranty.

Review the installer’s as-wired schematic. Determine where
the motor safety circuit is connected. Verify that the
customer’s emergency contacts are properly terminated in
the SED2 safety shutdown circuit or bypass option.
Verify that all other field-installed wires are correctly
terminated (including the shields).

(

)

7.

Verify the motor is free to move mechanically.

(

)

8.

For pump applications, verify the medium (such as water) is
available (no dry run).

(

)

9.

Record the motor(s) nameplate information:
Voltage:

Service Factor:

Efficiency %:

Full Load Amps (FLA):

RPM:

Hp:

(

)

10.

Verify that the input power voltage matches the rating of the
SED2.

(

)

11.

Verify that the motor is wired for the application voltage.

(

)

12.

IMPORTANT:

Verify that the motor rated full load amps
(FLA) does NOT exceed the rated output
current of the SED2 controlling it.

When multiple motors are simultaneously operated by the
SED2, the sum of all motor rated FLA values must be less
than or equal to that of the SED2 controlling them.

58

Siemens Building Technologies, Inc.

Commissioning

(

)

13.

Record any other connections to the SED2 by terminal
number to determine if special programming is required.
Record any changes in Appendix A: Parameters, Defaults,
and Settings.

(

)

14.

Make certain the immediate area around the SED2 is free of
debris and miscellaneous items.

(

)

15.

If applicable, verify that the building automation system logic
is ready to perform adequately for start, stop, and speed
command functions.

This concludes the preparation process for SED2 startup.
Keep this manual, option schematics, and any other instructions sent
with the SED2 easily accessible to assist you through the remainder of
this startup process.

SED2 (stand-alone) Startup
Procedure
NOTE:
Check
(

)

For SED2 with bypass option, see the documentation
provided with bypass for startup instructions.
Step
1.

Make sure that all three power phases are present and that
the input voltage is correct for the SED2 being started.
Apply SED2 power and verify that the SED2 display is on.
If the display indicates a fault, press

(

)

2.

to reset it.

Perform quick commissioning according to the Quick
Commissioning Procedure section in this manual.
On completion of the quick commissioning procedure,
proceed to step 3.

(

(

)

)

3.

4.

to return to the SED2 operating mode.

Press

and

Press

to place SED2 in Hand mode.

To start the SED2, press
(green start pushbutton). The
SED2 will ramp up to 10 Hz (or minimum speed). Verify
that the direction of motor rotation is correct.
CAUTION:
If the direction of motor rotation is wrong, turn power Off!

Siemens Building Technologies, Inc.

59

SED2 VFD Startup, Operation, and Maintenance Manual
DANGER:
Wait for 5 minutes. Always wait 5 minutes after
disconnecting the SED2 from the power source before
performing any work. The DC link capacitors of all SED2s
remain charged with dangerous voltages for 5 minutes
after all supplies have been disconnected. When working
on open equipment, note that live parts are exposed. Do
not touch these parts.
Swap wires on the motor terminals (U, V) or on the output
terminals of the motor overload relay. Tighten the terminal
lugs, reapply power, and recheck the direction of motor
rotation.
(

)

5.

With correct motor rotation, manually run the SED2
throughout its entire operating range while observing
operation.
If the SED2 trips on over-current during acceleration,
increase the acceleration time rate via parameter P1120.
If the SED2 trips on over-voltage during deceleration,
adjust the deceleration time rate via parameter P1121.
If excessive vibration of the driven load is noted at specific
frequencies, use Skip Frequency parameters P1091
through P1094 to eliminate this vibration.

(

)

6.

Determine whether the remote speed reference is a 0 to
10 Vdc or a 4 to 20 mA signal. Connect or verify
connection of signal wires. Set or verify that analog input
DIP switch has been set to the appropriate setting as
instructed in the Analog Input DIP Switches section of this
manual.

(

)

7.

Check the signal for proper polarity. Observe if the remote
speed command can achieve the minimum and maximum
speeds desired. If not, scale as required. The signal value
can be read at r0752 and the scaled value can be read at
r0754.

(

)

8.

Make additional SED2 application parameter settings as
required and record them in Appendix A: Parameters,
Defaults, and Settings.

(

)

9.

Press

to place SED2 in Auto mode.

This completes the startup procedure for the SED2.

60

Siemens Building Technologies, Inc.

Commissioning

Quick Commissioning Procedure
Parameter P0010 is the Commissioning Parameter Filter. It allows you to
select a group of parameters that can be used for quick commissioning,
including motor data (Figure 39), and motor ramp-up and ramp-down
settings.
It is important to use parameter P0010 to commission the SED2, P0003
to select the access level for using parameters, and P0004 to filter the
parameters according to their functionality. When Commissioning
Parameter Filter P0010=1, it initiates the quick commissioning
procedure.
It is recommended that you use the quick commissioning procedure.
However, experienced users may commission the equipment without the
P0004 filter functions.
At the end of the quick commissioning procedure, set parameter
P3900=1. This setting performs the necessary motor calculations and
sets all remaining parameters (those not included in P0010=1) to the
factory default values. If P3900 is set to a value greater than 0, P0010 is
automatically reset to 0. (If P0010=1, the SED2 cannot start.) The
process of performing motor calculations and setting all parameters to
factory default values is only possible via quick commissioning.
Parameter
P0003

Description

Action

User Access Level
Allows you to access more
parameters.
1
2
3

= Standard
= Extended
= Expert

Setting/ Default
Setting = 3

to access
1. Press
parameter r0000 and to
enter the SED2 parameter
mode.

Default = 1

2. Press
to advance to
parameter P0003.
3. Press
to access the
parameter values level.
4. Press
to advance to 3
(expert level).
to confirm and
5. Press
save the P0003=3 setting.

NOTE:
1. Before starting quick commissioning, set P0003=3 to ensure all necessary
parameters are available during quick commissioning.

Siemens Building Technologies, Inc.

61

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter
P0010

Description

Action

Quick Commissioning
0
1
30

= Ready to Run
= Quick
Commissioning
= Factory Setting

Setting/ Default
Setting = 1

1. Press
to access
parameter r0000 and to
enter the SED2 parameter
mode.

Default = 0

2. Repeatedly press
to
advance to parameter
P0010.
to access the
3. Press
parameter values level.
4. Press
to 1.

to advance

5. Press
to confirm and
save the P0010=1 setting.

P0100

62

NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is
automatically set back to 0.
Operation for Europe/
Setting = 1
to advance to
1. Press
N. America
parameter P0100.
Default = 0 or 1
0 = 50 Hz, kW (Europe),
2. Press
to access the
factory default
(Default is
parameter values level.
1 = 60 Hz, hp
determined by
(North America)
the setting of the
3. Press
to advance to 1. Motor
2 = 60 Hz, kW
Frequency and
(North America)
4. Press
to confirm and
Unit of
save the P0100=1 setting.
Measurement
The setting of Motor
DIP switches.)
Frequency and Unit of
Measurement DIP switch 2
overrides P0100 settings 0
and 1.
See the Motor Frequency
and Unit of Measurement
DIP Switch Settings section
in this manual for details.
NOTES:
1. Stop the SED2 (that is, disable all pulses) before changing this parameter.
2. Changing P0100 resets all rated motor parameters as well as other
parameters that depend on the rated motor parameters (such as P0340,
Calculation of Motor Parameters).

Siemens Building Technologies, Inc.

Commissioning

Parameter
P0304 *

Description

Action

Rated Motor Voltage
10V to 2000V

to advance to
1. Press
parameter P0304.

Rated motor voltage (V)
from motor nameplate.

2. Press
to access the
parameter values level.

Setting/ Default
Motor
nameplate
Default = Varies
by model

to advance to
3. Press
nominal voltage.
4. Press
to confirm and
save the setting.
P0305 *

Rated Motor Current
0A to 10,000A

to advance to
1. Press
parameter P0305.

Rated motor current (A)
from motor nameplate.

2. Press
to access the
parameter values level.

Motor
nameplate
Default = Varies
by model

3. Press
to advance to
nominal current.
4. Press
to confirm and
save the setting.
P0307 *

Rated Motor Power
0 kW or hp to 2000 kW
or hp
Rated motor power (kW or
hp) from motor nameplate.

to advance to
1. Press
parameter P0307.
2. Press
to access the
parameter values level.

Motor
nameplate
Default = Varies
by model

to advance to
3. Press
nominal power.
If P0100=1 (60 Hz, hp,
North America), then motor
4. Press
to confirm and
power is in hp.
save the setting.
* Motor related parameters.

Siemens Building Technologies, Inc.

63

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter
P0308 *,
or
P0309 *

Description
Rated Motor cosPhi
(P0308), or
Rated Motor Efficiency
(P0309)
0.000 to 1.000 (P0308) or
0.0 to 99.9 (P0309)

Action
to advance to
1. Press
parameter P0308 or P0309.
2. Press
to access the
parameter values level.

3. Press
to advance to
nominal cosPhi or motor
Rated motor cosPhi or
efficiency.
motor efficiency from motor
nameplate.
4. Press
to confirm and
save the setting.
If P0100=0 or 2 and

Setting/ Default
Motor
nameplate
P0308 Default =
0.000
P0309 Default =
varies
(hp/voltage
dependent)

P0307=kW, P0308
displays;
if P0100=1 and P0307=hp,
P0309 displays.
P0309=100% corresponds
to superconducting.

P0310 *

NOTE:
This parameter is available
when P0003 = 3 and
P0010 = 1.
Rated Motor Frequency
12 Hz to 650 Hz

to advance to
1. Press
parameter P0310.

Motor
nameplate
60 Hz

to access the
Rated motor frequency (Hz) 2. Press
parameter values level.
from motor nameplate.

Default = 50 Hz/
60 Hz

3. Press
to advance to
Pole pair number is
nominal frequency (60 Hz).
recalculated automatically if
the parameter is changed.
to confirm and
4. Press
save the setting.

Default is
dependent on
the setting of the
Motor
Frequency and
Unit of
Measurement
DIP switches.

* Motor related parameters.

64

Siemens Building Technologies, Inc.

Commissioning

Parameter
P0311 *

Description

Action

Rated Motor Speed
0 to 40,000 1/min

to advance to
1. Press
parameter P0311.

Rated motor speed (rpm)
from motor nameplate.

2. Press
to access the
parameter values level.

A setting of 0 causes an
internal calculation of this
value.

to advance to
3. Press
nominal motor speed.

Setting/ Default
Motor
nameplate
Default = 0

Vector control and V/f
control with speed controller
require this value.

4. Press
to confirm and
save the setting.

Slip compensation in V/f
control requires this value
for correct operation.

P0640

Pole pair number is
recalculated automatically if
the parameter is changed.
Motor Overload Factor
10% to 400%

Site setting
to advance to
1. Press
parameter P0640.

Default = 110

2. Press
to access the
Limited to the maximum
parameter values level.
SED2 output current rating
or to 400% of the rated
to advance to
current (P0305), whichever 3. Press
desired value.
is lower.
4. Press
to confirm and
NOTE:
save the setting.
This parameter is available
when P0003 = 3 and
P0010 = 1.
* Motor related parameters.

Siemens Building Technologies, Inc.

65

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter
P0700[0]
**

P0700[1]
**

Description

Action

Selection of Command
Source
(Start Command)

to advance to
1. Press
parameter P0700.

Selects the command
source as follows:

2. Press
to access the
parameter indexes.

Setting/ Default
Setting = 2
Default = 2

3. Press
to advance to
0 = Factory default
index [0], IN000, AUTO.
setting
1 = BOP (keypad)
to confirm index
2 = Terminal digital input 4. Press
selection.
4 = USS on BOP link
(AOP)
5. Press
to advance to 2.
5 = USS on COM link
6 = CB (communications
6. Press
to confirm and
board or module) on
save the setting.
COM link (P1/N2)
NOTE:
Changing this parameter resets (to default) all setting on the selected item. For
example, changing from 1 to 2 resets all digital inputs to default settings.
Selection of Command
Setting = 1
to advance to
1. Press
Source
index [1], IN001, HAND.
(Start Command)
Default = 1
Selects the command
source as follows:

2. Press
to confirm index
selection.

3. Press
to advance to 1.
0 = Factory default
setting
4. Press
to confirm and
1 = BOP (keypad)
save the setting.
2 = Terminal digital input
4 = USS on BOP link
again to return to
5. Press
(AOP)
the parameter selection
5 = USS on COM link
level.
6 = CB (communications
board or module) on
COM link (P1/N2)
NOTE:
Changing this parameter resets (to default) all setting on the selected item. For
example, changing from 1 to 2 resets all digital inputs to default settings.
** Parameters have two index settings: IN000=Auto and IN001=Hand.

66

Siemens Building Technologies, Inc.

Commissioning

Parameter
P1000[0]
**

Description
Selection of Frequency
Setpoint
(Speed Command
Source)
Selects the frequency
setpoint source as follows:

P1000[1]
**

1 = Motor potentiometer
setpoint/
BOP keypad
2 = Analog input
3 = Fixed frequency
setpoint
4 = USS on BOP
Link/AOP
5 = USS on COM link
6 = CB
(communications
board or module) on
COM link/
P1-N2
communications
Selection of Frequency
Setpoint
(Speed Command
Source)
Selects the frequency
setpoint source as follows:

Action

Setting/ Default
Setting = 2

to advance to
1. Press
parameter P1000.

Default = 2

2. Press
to access the
parameter indexes.
to advance to
3. Press
index [0], IN000, AUTO.
4. Press
to confirm index
selection.
5. Press

to advance to 2.

6. Press
to confirm and
save the setting.

Setting = 1
to advance to
1. Press
index [1], IN001, HAND.

Default = 1

2. Press
to confirm index
selection.

3. Press
to advance to 1.
1 = Motor potentiometer
4. Press
to confirm and
setpoint/
save the setting.
BOP keypad
2 = Analog input
5. Press
again to return to
3 = Fixed frequency
the parameter selection
setpoint
level.
4 = USS on BOP
Link/AOP
5 = USS on COM link
6 = CB (communications
board or module) on
COM link/
P1-N2
communications
** Parameters have two index settings: IN000=Auto and IN001=Hand.

Siemens Building Technologies, Inc.

67

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter
P1080

Description
Minimum Motor
Frequency

Action

Setting/ Default
Site Setting

to advance to
1. Press
parameter P1080.

(20-30% Max)

0 Hz to 650 Hz

P1082

Minimum motor frequency
at which the motor will run
irrespective of the
frequency setpoint. This
value applies to both
clockwise and
counterclockwise rotation.
Maximum Motor
Frequency

2. Press
to access the
parameter values level.
3. Press
to advance to
desired value.
to confirm and
4. Press
save the setting.

Site Setting
to advance to
1. Press
parameter P1080.

0 Hz to 650 Hz
2. Press
to access the
parameter values level.
Maximum motor frequency
at which the motor will run
to advance to
regardless of the frequency 3. Press
desired value.
setpoint. This value applies
to both clockwise and
to confirm and
counterclockwise rotation. 4. Press
save the setting.

P1120

Default = 10

Default = 50 or
60
(Default is
determined by
the setting of the
Motor
Frequency and
Unit of
Measurement
DIP switches.)

NOTE:
This value is limited internally to 200 Hz or five times the rated motor frequency
(P0305) when P1300is greater than or equal to 20 (control mode=vector
control). The value displays via r0209 (maximum frequency).
Ramp-up Time
Site Setting
to advance to
1. Press
parameter P1120.
Default = 10
0s to 650s
2. Press
to access the
parameter values level.

Typical fan =
120s.

3. Press
to advance to
desired value.

Typical pump =
30s.

to confirm and
4. Press
save the setting.
NOTES:
1. Setting the ramp-up time too short can cause the SED2 to trip (F0001
overcurrent, F0002 overvoltage, or F0003 undervoltage).
2. If using an external frequency setpoint with set ramp rates (such as from a
PLC), achieve optimum SED2 performance by setting ramp times (P1120
and P1121) slightly shorter than those of the PLC.

68

Siemens Building Technologies, Inc.

Commissioning

Parameter
P1121

Description

Action

Ramp-down Time
0s to 650s

3.

Setting/ Default
Site Setting

1. Press
to advance to
parameter P1121.

Default = 30

2. Press
to access the
parameter values level.

Typical fan =
120s.

to advance to
3. Press
desired value.

Typical pump =
30s.

4. Press
to confirm and
save the setting.

P3900

NOTES:
1. Setting the ramp-up time too short can cause the SED2 to trip (F0001
overcurrent, F0002 overvoltage, or F0003 undervoltage).
2. If using an external frequency setpoint with set ramp rates (such as from a
PLC), achieve optimum SED2 performance by setting ramp times (P1120
and P1121) slightly shorter than those of the PLC.
End Quick
Setting = 1
to advance to
1. Press
Commissioning
parameter P3900.
Default = 0
0 = End without motor
to access the
calculation or factory 2. Press
parameter values level.
reset.
1 = End with motor
3. Press
to advance to 1.
calculation and
factory reset
4. Press
to confirm the
(recommended on
setting.
SED2 without
bypass option).
2 = End with motor
calculation and with
I/O reset
(recommended on
SED2 with bypass
option).
3 = End with motor
calculation but
without I/O reset.
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is less than 0 on completion of commissioning, P0010 is
automatically set back to 0.

Siemens Building Technologies, Inc.

69

SED2 VFD Startup, Operation, and Maintenance Manual

Additional Parameter Settings
NOTE:

If Display Selection for r0000, parameter P0005=21 (actual
frequency), then the BOP display alternately shows setpoint
values and the actual value (0 Hz).

Flying Start
Parameter
P1200

Description
Flying Start

Action

Setting/ Default
Minimum: 0
Default: 0
Maximum: 6

to enter the
1. Press
SED2 parameter mode
Starts SED2 into a spinning
and to display r0000.
motor by rapidly changing the
output frequency of the SED2
to advance
until the actual motor speed is 2. Press
to parameter P1200.
found. Then, the motor runs up
to setpoint using the normal
3. Press
to access the
ramp time.
parameter values level.
0 = Flying start disabled
4. Press
to advance
1 = Flying start is always
to
desired
setting.
active, start in direction of
setpoint
5. Press
to confirm
2 = Flying start is active if
and save the setting.
power on, fault, OFF2,
start in direction of
setpoint
3 = Flying start is active if
fault, OFF2, start in
direction of setpoint
4 = Flying start is always
active, only in direction of
setpoint
5 = Flying start is active if
power on, fault, OFF2,
only in direction of
setpoint
6 = Flying start is active if
fault, OFF2, only in
direction of setpoint
NOTES:
1. Flying start is useful for motors with high inertia loads.
2. Settings 1 to 3 search in both directions. Settings 4 through 6 search only in
direction of setpoint.
3. Flying start must be used in cases where the motor may still be turning
(such as after a brief input power break) or can be driven by the load.
Otherwise, overcurrent trips occur.
4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start
may have to be optimized by reducing the values in P1203 and P1202.

70

Siemens Building Technologies, Inc.

Commissioning

Parameter
P1202

Description

Action

Motor Current: Flying Start

Setting/ Default
Minimum: 10

to enter the
1. Press
SED2 parameter mode
Defines search current used for
and to display r0000.
flying start. Value is in % based
on the rated motor current
2. Press
to advance
(P0305).
to parameter P1200.

Default: 100
Maximum: 200

3. Press
to access the
parameter values level.
4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.

P1203

NOTE:
Reducing the search current may improve performance for flying start if the
inertia of the system is not very high.
Search Rate: Flying Start
Minimum: 10
to enter the
1. Press
SED2 parameter mode Default: 100
Sets factor by which the output
and to display r0000.
frequency changes during flying
start to synchronize with the
Maximum: 200
to advance
2. Press
turning motor. This value,
to parameter P1202.
entered in % relative to the
default time factor, defines the
to access the
3. Press
initial gradient and influences
parameter values level.
the time taken to search for the
motor frequency.
4. Press
to advance
to desired value.
The search time is the time
taken to search through all
frequencies between
f_max + 2 × f_slip to 0 Hz.

5. Press
to confirm
and save the setting.

NOTES:
1. P1203=100% is defined as giving a rate of 2% of f_slip,nom/ms.
2. P1203=200% would result in a rate of frequency change of 1% of
f_slip,nom/ms.
3. A higher value produces a flatter gradient, and thus a longer search time. A
lower value has the opposite effect.

Siemens Building Technologies, Inc.

71

SED2 VFD Startup, Operation, and Maintenance Manual

Automatic Restart
CAUTION:
Setting 2 through 5 can cause the motor to restart unexpectedly.

Parameter
P1210

Description

Action

Automatic Restart
Enables SED2 restart after a
supply power break or after a
fault.

Setting/ Default
Minimum: 0

to enter the
1. Press
SED2 parameter mode
and to display r0000.

Default: 1
Maximum: 5

2. Press
to advance
to parameter P1210.

Setting: 3
= Disabled
= Trip reset after power
3. Press
to access the
on (P1211 disabled)
parameter values level.
2 = Restart after supply
power blackout
4. Press
to advance
(P1211 disabled)
to desired setting.
3 = Restart after brownout
or fault
5. Press
to confirm
(P1211 enabled)
and save the setting.
4 = Restart after supply
power brownout
(P1211 disabled)
5 = Restart after blackout
or fault
(P1211 disabled)
NOTES:
0
1

1. Auto restart requires a constant ON command (such as via a digital input).
2. P1200 flying start must be used in cases where the motor may still be
turning, such as after a brief input power break, or can be driven by the
load.
3. A supply power brownout is when the power is interrupted and reapplied
before the operator panel display has gone dark. It is a very short supply
power break where the DC link has not fully collapsed
4. A supply power blackout is when the operator panel display has gone
dark before the power is reapplied. It is a long supply power break where
the DC link has fully collapsed.

72

Siemens Building Technologies, Inc.

Commissioning

Parameter
P1211

Description

Action

Number of Restart Attempts

Setting/ Default
Minimum: 0

to enter the
1. Press
SED2 parameter mode
and to display r0000.

Specifies number of times
SED2 will attempt to restart
after supply power brownout or
to advance
fault, if P1210 automatic restart 2. Press
to parameter P1211.
is activated.

Default: 3
Maximum: 10

3. Press
to access the
parameter values level.
4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.
P1212

Time to First Restart

Minimum: 0

to enter the
1. Press
SED2 parameter mode
Selects the time (seconds)
and to display r0000.
before the SED2 is restarted for
the first time if P1210 automatic
to advance
2. Press
restart is activated
to parameter P1212.

Default: 30
Maximum: 1000

3. Press
to access the
parameter values level.
4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.
P1213

Restart Time Increment

Minimum: 0
to enter the
1. Press
SED2 parameter mode
and to display r0000.

Selects the amount (seconds)
that the restart time is
incremented for each restart of
2. Press
to advance
the SED2 if P1210 automatic
to parameter P1213.
restart is activated

Default: 30
Maximum: 1000

3. Press
to access the
parameter values level.
4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.

Siemens Building Technologies, Inc.

73

SED2 VFD Startup, Operation, and Maintenance Manual

Vdc Controller
Parameter
P1240

Description
Configuration of Vdc
Controller
Enables/disables Vdc
controller.

Action

Setting/ Default
Minimum: 0

to enter the
1. Press
SED2 parameter mode
and to display r0000.

Default: 1
Maximum: 3

to advance
2. Press
to parameter P1240.
The Vdc controller dynamically
controls the DC link voltage to
3. Press
to access the
prevent overvoltage trips on
parameter values level.
high inertia systems.
Vdc-max automatically
increases ramp-down times to
keep the DC link voltage
(r0026) within limits.
0
1
2
3

4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.

= Vdc controller disabled
= Vdc-max controller
enabled
= Reserved
= Reserved

Pulse Frequency
Parameter
P1800

Description

Action

Pulse Frequency
Sets pulse frequency (kHz) of
power switches in SED2. The
frequency can be changed in
increments of 2 kHz.

Setting/ Default
Minimum: 2

to enter the
1. Press
SED2 parameter mode
and to display r0000.
2. Press
to advance
to parameter P1800.

Default:
Varies by model
(hp/voltage
dependent)

Pulse frequencies > 4 kHz
Maximum: 16
to access the
selected on 380V to 480V units 3. Press
parameter values level.
reduce the maximum
continuous motor current.
4. Press
to advance
to desired value.
5. Press
to confirm
and save the setting.
NOTES:
1. Minimum pulse frequency depends on P1082 (maximum frequency) and
P0310 (rated motor frequency).
2. At 4 kHz, full output current is obtained up to 50 degrees C (CT mode); over
50 degrees C, full output may be obtained at 8 kHz.
3. If silent operation is not absolutely necessary, lower pulse frequencies may
be selected to reduce SED2 losses and radio-frequency emissions.
4. Under certain circumstances, the SED2 may reduce the switching
frequency to provide protection against over-temperature.

74

Siemens Building Technologies, Inc.

Commissioning

Reset to Factory Defaults
Parameter
P0010
P0970

Description

Action

Reset to Factory Default
Resets SED2 parameters to the
factory defaults.

to enter the
1. Press
SED2 parameter mode
and to display r0000.
to advance
2. Press
to parameter P1010.

Setting/ Default
P0010:
Setting = 30
Default = 0
P0970:
Setting = 1
Default = 0

to access the
3. Press
parameter values level.
4. Press
to 30.

to advance

5. Press
to confirm
and save the setting.
6. Press
to go to
parameter P0970.
7. Press
to 1.

to advance

8. Press
to confirm
and save the setting.
NOTES:
1. First set P0010=30.
2. Stop SED2 (that is, disable all pulses) before you reset parameters to
factory default values.
3. The following parameters retain their values after a factory reset:
• P0918 (address of CB, communications board or module)
• P2010 (USS baud rate)
• P2011 (USS address)
4. The reset process takes about 10 seconds.
5. Appendix A: Parameters, Defaults, and Settings lists SED2 parameters and
their factory defaults.

Siemens Building Technologies, Inc.

75

SED2 VFD Startup, Operation, and Maintenance Manual

Network Communications
Table 8 lists the parameters required for correct APOGEE™ system FLN
communications and control of the SED2.
CAUTION:
Changes made to the parameters other than what is listed in
Table 8 can result in damaging the drive or building equipment.
Table 8. Parameters for Network Communications.
Parameter

Value

P0003:
User access
Level

Set to 3 to allow access to required parameters.

P2040:
CB telegram
off time

Set to 0 (watchdog disabled) to tell the SED2 to start looking
for communication via the setting of P2041.

P2041[0]:
CB parameter

Set to 1 for FLN (P1) control.
(Set to 2 for FLN (N2) control.)

P0918:
CB address

Set to 99 for (P1) addressing of the device.
(Set to 3 for (N2) addressing of the device.)
Unit must be powered down to establish P1 communications,
and then the address is assigned.
The address will return to the default of 99 when the drive is
powered down.

P0700[0]

Set to 6 tells the SED2 to look for a start command from the
network in the auto mode.

P1000[0]

Set to 6 tells the SED2 to look for its speed source from the
network in the auto mode.

Since there is a limited life to EEPROM writes, set the Network Fault
Indicator to 0 only when troubleshooting a communications problem.
If a factory reset of parameters is desired, set P0010 to 30 and then set
P0970 to 1.
Appendix B: SED2 Point Maps provides a SED2 P1 point map for
®
APOGEE Automation Systems and a SED2 N2 point map for Johnson
Controls, Inc. systems.

76

Siemens Building Technologies, Inc.

Commissioning

Changing Individual Parameter Digits
To quickly change the value of a parameter, modify the individual digits
in the display as follows:
1. Verify that you are at the parameter values level by following these
steps:
a. Press

to enter the parameter level.

b. Press

to advance to the desired parameter.

c. Press

to access the parameter values level.

2. Press

the right-most digit starts to flash.

3. Modify the value of this digit with the
4. Press

and

pushbuttons.

again. The next digit starts flashing.

5. Repeat steps 3 and 4 until the required value displays.
6. Press

to exit the parameter values level.

Siemens Building Technologies, Inc.

77

SED2 VFD Startup, Operation, and Maintenance Manual

Maintenance
Perform SED2 maintenance semi-annually. Estimated maintenance time
is one hour.

Prerequisites
1. Confer with customer and log any comments about specific SED2s.
2. Verify with customer that SED2 can be serviced and explain the
service steps.
3. Document last trip error (if any).
4. Verify SED2 Emergency Services are de-energized.
5. De-energize unit.
6. Follow standard lockout, tag-out procedures and verify that input
power is removed.

General Inspection and Cleaning
NOTE:

See the appropriate sections in this manual for mechanical
and electrical installation instructions.

1. Open unit.
2. Inspect unit and verify that all connections have continuity.
3. Visually inspect unit for signs of arching or overheating.
4. Vacuum and dust unit interior using a non-static generating device.
5. Verify environmental conditions conform to drive specifications.
6. Inspect outer casing for cleanliness and corrosion.

Muffin Fan Inspection and Cleaning
1. Clean dirt or debris from fan housing and blades.
2. Check fan bearings.

78

•

You should not be able to move the blades forward or backward.

•

The blades should free wheel and not appear to be binding.

Siemens Building Technologies, Inc.

Maintenance

•

There should be no mechanical whining sound made from the
fan

3. Close unit.
4. Remove lockout, tag-out materials.

Re-energize Unit
1. Verify 3-phase power supply is within SED2 ratings.
2. Check for input phase balance legs: A to B, B to C, and C to A.
Phase balance should be within 10V to 15V of each other.

DC Bus Integrity Test
1. At this time, the SED2 should have power applied but not be enabled
to run.
2. Check the Actual DC Link Voltage using parameter r0026 index 000
and 001.
•

With index 000 displayed, there should be no more than a 25V
fluctuation.

•

With index 001 displayed, there should be no more than a 25V
fluctuation.

Contactors and Switches
Verify with infrared temperature that no hot spots have occurred in
contactors and switches.

Motor Bearing Wear
To determine motor bearing wear, use an amphere probe at 60 Hz on
SED2 motor output leads to document full running amps.

Siemens Building Technologies, Inc.

79

SED2 VFD Startup, Operation, and Maintenance Manual

Troubleshooting
Reading Faults
•

OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK,
1=Fault).

•

LAST FAULT (r0947(0)) shows the code for the most recent fault.
Fault history displays according to Figure 40, where:
F1 = The first active fault (not yet acknowledged)
F2 = The second active fault (not yet acknowledged)
F1e = The occurrence of the fault acknowledgement for F1 and F2.
This moves the value in the two indexes down to the next pair of
indexes, where they are stored. Indexes 0 and 1 contain the active
faults. When faults are acknowledged, indexes 0 and 1 are reset to 0.
0
F1
1

ACTIVE FAULT
CODES
F2
F1e

F1e

2
MOST RECENT
FAULT CODES - 1

3
F1e

F1e

4
MOST RECENT
FAULT CODES - 2

5
F1e

F1e

6

7

MOST RECENT
FAULT CODES - 3

Figure 40. Display of Fault History.

80

Siemens Building Technologies, Inc.

Troubleshooting

•

For example:
If the SED2 trips on undervoltage and then receives an external trip
before the undervoltage is acknowledged, you will obtain:
Index 0 = 3, undervoltage
Index 1 = 85, external trip
Whenever a fault in index 0 is acknowledged (F1e), the fault history
shifts as indicated in the diagram.

•

Indexes:
r0947[0] = Recent fault trip –, fault 1
r0947[1] = Recent fault trip –, fault 2
r0947[2] = Recent fault trip -1, fault 3
r0947[3] = Recent fault trip -1, fault 4
r0947[4] = Recent fault trip -2, fault 5
r0947[5] = Recent fault trip -2, fault 6
r0947[6] = Recent fault trip -3, fault 7
r0947[7] = Recent fault trip -3, fault 8
Index 2 is used only if a second fault occurs before the first fault is
acknowledged.

Resetting Faults
•

Press

•

OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK,
1=Fault). It can be acknowledged with FAULT ACK (r0054, bit 7).
Setting FAULT ACK (r0054, bit 7) resets the fault (1=Reset Fault).

•

It is possible that motor performance may be affected at low
frequencies if parameter P1310 falls under 50% (default value).

•

It is recommended to make provision to reset faults automatically if
the unit is operated in auto mode.

to reset a fault condition manually.

Siemens Building Technologies, Inc.

81

SED2 VFD Startup, Operation, and Maintenance Manual

Troubleshooting the Operator Panel
If the display shows P – – – – or it is a blank screen, make certain
connection pins are not bent on the I/O module (Figure 41) and that
connection openings on the back of the operator panel are free from
obstructions (Figure 42).

NOTE:

For Frame Size D through F, verify ribbon cable connector is
not loose or damaged. Verify functionality of the operator
panel by plugging it directly into the control module.

VERIFY THAT
CONNECTION
PINS ARE
NOT BENT
VERIFY THAT
INDICATING
LIGHTS ARE
ILLUMINATING

VERIFY THAT
CONNECTION
OPENINGS ARE
FREE FROM
OBSTRUCTIONS

Figure 41. Connection Pins on I/O
Module.

82

Figure 42. Connection Openings on
Back Side of Operator Panel.

Siemens Building Technologies, Inc.

Troubleshooting

Troubleshooting Using the Operator
Panel
NOTE:

The voltage and current range of the SED2 must match the
motor data.

If the motor does not start with the ON command:
1. Check if Commissioning Parameter Filter P0010=0 (factory setting).
2. Check if there is a valid ON signal.
3. Check if Selection of Command Source parameter P0700[0]=2 (for
digital input control) or P0700[1]=1 (for BOP control).
4. Check if the correct setpoint is available (0 to 10V on terminal 3), or if
the setpoint was entered in the correct location for the setpoint
source (Selection of Frequency Setpoint parameter P1000[0]=2).
If the motor does not start after checking these parameters, reset the
SED2 to the factory-default parameter values according to the Reset to
Factory Defaults section in this manual.
Use a switch between terminals 5 and 9 on the control terminal bar. The
SED2 should now run according to the default setpoint at the analog
input.
Use r0722 to check on/off status of digital inputs. Use r0752 to check the
smoothed value of analog inputs.

Siemens Building Technologies, Inc.

83

SED2 VFD Startup, Operation, and Maintenance Manual

Fault Codes
Error
F0001,
Overcurrent

Cause

Diagnosis/Remedy

• Motor power (P0307) is
• Motor power (P0307) SED2
greater than SED2 power
power (P0206).
(P0206).
• Cable length limits must not be
exceeded.
• Motor lead short circuit.
• Ground faults.
• Motor is pulling more
current than rating
because of mechanical
issues.

Drive
Reaction
Off2

• Short circuits or ground faults in
motor cable and motor.
• Motor parameters must match
the motor in use.
• Value of stator resistance
(P0350) must be correct.
• Motor is obstructed or
overloaded.
• Increase ramp-up time.
• Reduce boost level.

84

Siemens Building Technologies, Inc.

Troubleshooting

Error
F0002,
Overvoltage

Cause
• DC link voltage (r0026)
exceeds trip level.

Diagnosis/Remedy

Drive
Reaction

• Supply voltage must lie within the Off2
limits indicated on the SED2
rating plate.

• Overvoltage can be
caused either by the input • DC link voltage controller must be
supply voltage being too
enabled (P1240) and
high or if motor is in
parameterized correctly.
regenerative mode.
• Ramp-down time (P1121) must
match inertia of load.
• Regenerative mode can
be caused by fast ramp
• Loose wire on output.
downs or if the motor is
driven from an active
• Set P1800=2 to reduce pulse
load.
size.
• Review quick commissioning with
User Access Level P0003=3
(expert) and specify a value for
P0309, rated motor efficiency.
• On systems with multiple motors,
one may be pushing the other.
• System electrical disturbance
may need correction.
• If the SED2 faults on F0002
(overvoltage) on a start
command, flying start may have
to be optimized. This is typically
done by reducing the values in
P1203 and P1202.
NOTE: Higher inertia requires long
ramp-down times.

F0003,
• Input power supply failed. • Supply voltage must lie within the Off2
Undervoltage
limits indicated on the SED2
• Shock load outside the
rating plate.
specified limits.
• Supply voltage must not be
susceptible to temporary failures
or voltage reductions outside
tolerance.
• Use Ramp-up Time P1120 to
increment the ramp-up time.

Siemens Building Technologies, Inc.

85

SED2 VFD Startup, Operation, and Maintenance Manual

Error

Cause

Diagnosis/Remedy

Drive
Reaction

F0004,
SED2 overtemperature

• Ventilation is inadequate. • Fan must turn when the SED2 is Off2
running.
• Fan is inoperative.
• Pulse frequency must be set to a
• The ambient temperature
lower value.
is too high.
• Ambient temperature could be
higher than specified for the
SED2.

F0005,
SED2 I2t

• The SED2 is overloaded. • Load cycle must lie within the
limits specified.
• Duty cycle is outside the
tolerance.
• Motor power (P0307) ≤ SED2
power (P0206).
• Motor power (P0307)
exceeds the SED2 power
(P0206).

F0011, Motor • Motor is overloaded
overtemperature • Protection is too finely
tuned for the duty cycle.
• Rated Motor Efficiency
P0309 is not accurate.

• Make sure that the load duty
cycle (temporary overload) lies
within the limits specified.

Off2

Off2

• Verify P0640 is set for the
application.
• Verify motor efficiency setup via
P0309 equals motor nameplate
data.
NOTE: Set P0003=3 and P0010=1
and then advance to P0309. Set
efficiency to motor rated efficiency,
or 99. Advance to P3900=3.

F0012,
SED2
temperature
signal lost

Wire breakage of the SED2 —
temperature sensor (heat
sink).

F0015, Motor • Breakage or short-circuit
temperature
of the motor temperature
signal lost
sensor.

—

Off2

Off2

• If a signal loss is
detected, temperature
monitoring switches to
monitoring the thermic
motor image.
F0020, 1
phase for
input power
supply
missing

86

One of the 3 phases of the
input power supply voltage
is missing.

Check wiring of the 3 phases at the Off2
SED2 input supply voltage.

Siemens Building Technologies, Inc.

Troubleshooting

Error

Cause

F0021,
The ground fault occurs if
Ground fault the sum of the phase
currents is higher than 5%
of the nominal SED2
current.

Diagnosis/Remedy

Drive
Reaction

—

Off2

• Check for loose output or short.

Off2

NOTE: This error
message occurs on SED2s
with three current sensors;
that is, for SED2s of frame
sizes D to F.
F0022,
The fault is caused by the
Power stack following events:
fault
(1) dc link overcurrent =
short circuit of IGBT.

• Possible drive component failure.

(2) short circuit of dc link
chopper
(3) ground fault.
Frame sizes A to C =
(1),(2),(3).
Frame sizes D to E =
(1),(2).
Frame size F = (2).
Since all these faults are
assigned to one signal on
the power stack, it is not
possible to establish which
one actually occurred.
F0023, Fault On-phase is interrupted at
at SED2
the SED2 output.
output

—

Off2

F0024,
Rectifier
overtemperature

• Ventilation is inadequate. • Fan must turn when the SED2 is —
running.
• Fan is inoperative.
• Pulse frequency (P1800) must be
• Ambient temperature is
set to default value 4 kHz.
too high.

F0030, Fan
fault

Fan no longer works.

• Fault cannot be masked while the Off2
options module (BOP or AOP) is
connected.
• Replace the fan.

Siemens Building Technologies, Inc.

87

SED2 VFD Startup, Operation, and Maintenance Manual

Error

Cause

F0041,
• Motor data identification
Motor data
failed
identification
• Alarm value = 0: Load is
failure
missing

Diagnosis/Remedy
0: Check if the motor is
connected to the SED2.

Drive
Reaction
Off2

1-40: Check if the motor data in
P0304 to P0311 are correct.

• Alarm value = 1: Current Check the type of motor wiring
limit value reached during required (star, delta).
identification.
• Alarm value = 2:
Identified stator
resistance less than 0.1%
or more than 100%.
• Alarm value = 3:
Identified rotor resistance
less than 0.1% or more
than 100%.
• Alarm value = 4:
Identified stator reactance
less than 50% or more
than 500%.
• Alarm value = 5:
Identified input power
reactance less than 50%
or more than 500%.
• Alarm value = 6:
Identified rotor time
constant less than 10 ms
or more than 5s.
• Alarm value = 7:
Identified total leakage
reactance less than 5% or
more than 50%.
• Alarm value = 8:
Identified stator leakage
reactance less than 25%
or more than 250%.
• Alarm value = 9:
Identified rotor leakage
reactance less than 25%
or more than 250%.
(Continued)

88

Siemens Building Technologies, Inc.

Troubleshooting

Error

Cause

Diagnosis/Remedy

Drive
Reaction

(Continued) • Alarm value = 20:
0: Check if the motor is
Off2
Identified IGBT ONconnected to the SED2.
F0041,
voltage less than 0.5 or
Motor data
1-40: Check if the motor data in
more than 10V.
identification
P0304 to P0311 are correct.
• Alarm value = 30: Current
failure
controller at voltage limit. Check the type of motor wiring
required (star, delta).
• Alarm value = 40:
Inconsistency of identified
data set, at least one
identification failed.
Percentage values based
on impedance
Zb =
Vmot,nom/sqrt(3)/Imot,nom.
F0051,
Parameter
EEPROM
fault

Read or write failure while
saving non-volatile
parameter

Reset SED2 to factory setting and
perform quick commissioning.

F0052,
Read failure for power stack Replace SED2.
Power stack information or invalid data.
fault
F0053, I/O
EEPROM
fault

Read failure for I/O
EEPROM information or
invalid data.

• Check the data.

F0054,
Wrong I/O
connection

I/O connection is invalid.

• Check data flow.

F0060, ASIC Internal communication
timeout
error.

Off2

Off2

• Replace the I/O module.
Off2

• Replace I/O module.
• If error reappears, replace SED2. Off2
• Contact your supplier.

F0070, CB
No setpoints from CB
Check CB (communications board
setpoint fault (communications board or or module) and communications
module) during telegram off partner.
time.
F0071, USS No setpoints from USS
(BOP link)
during telegram off time.
setpoint fault

• Check communications to data
transmission module.

F0072, USS No setpoints from USS
(COM link)
during telegram off time
setpoint fault

Check USS master.

Siemens Building Technologies, Inc.

Off2

Off2

Off2

• Check USS master.
Off2

89

SED2 VFD Startup, Operation, and Maintenance Manual

Error

Cause

Diagnosis/Remedy

Drive
Reaction

F0080,
• Broken wire at analog
Analog input
input.
signal lost
• Signal level outside
defined limits.

—

F0085,
External fault triggered via
External fault input terminals.

Off2
• Disable input terminals for fault
trigger, or eliminate external fault.

Off2

• Check if digital input is set to ON.
F0101, Stack Software or processor error. Run self-test routines.
overflow

Off2

F0221, PID
feedback
below min.
value

PID feedback below
minimum value of P2268,
minimum value for PID
feedback.

• Change value of P2268.

F0222

PID feedback above
maximum value.

• PID feedback, maximum value of Off2
P2267 (maximum value for PID
feedback).

Off2

• Adjust feedback amplification.

• Adjust feedback amplification.
F0450, BIST Alarm value:
tests failure
1. Some power section
tests have failed.

• SED2 may run, but some
functions do not work properly.

Off2

• Replace the SED2.

2. Some control module
tests have failed.
4. Some functional tests
have failed.
8. Some I/O module tests
have failed.
16. Internal RAM failed on
power-up check.

90

Siemens Building Technologies, Inc.

Troubleshooting

Error
F0452, Belt
failure
detected

Cause
Load condition changes at
the motor indicate a belt
failure or mechanical fault.

Diagnosis/Remedy
• Motor belt OK? Is the motor
obstructed or seized?

Drive
Reaction
Off2

• If external speed sensor is used,
check proper function. Also
check:
— P0409 (pulses/sec at rated
frequency)
— P2191 (belt failure speed
tolerance monitoring)
— P2192 (delay time for
P2191).
• For belt failure detection without
sensor, check:
— P2182 (threshold frequency
f1)
— P2183 (threshold frequency
f2)
— P2184 (threshold frequency
f3)
— P2185 (upper torque
threshold 1)
— P2186 (lower torque
threshold 1)
— P2187 (upper torque
threshold 2)
— P2188 (lower torque
threshold 2)
— P2189 (upper torque
threshold 3)
— P2190 (lower torque
threshold 3)
— P2192 (delay for belt failure).
• Lubricate the motor if necessary.

Siemens Building Technologies, Inc.

91

SED2 VFD Startup, Operation, and Maintenance Manual

Warning Messages
Error

Cause

A0501, Current • Motor power>SED2 power.
limit
• Motor cables are too long.
• Ground faults.

Diagnosis and Remedy
• Check belt tension.

Drive
Reaction
—

• Motor power (P0307)
>SED2 power (P0206).
• Cable length limits must
not be exceeded.
• Motor cable and motor
must not have short
circuits or ground faults.
• Motor parameters must
match the motor in use.
• Value of stator resistance
(P0350) must be correct.
• The motor must not be
obstructed or overloaded.
• Check belt tension, if
applicable.
• Increase ramp-up time.
• Reduce boost level.

A0502,
Overvoltage
limit

Overvoltage limit is reached.
This warning may appear on
ramp-down if the DC link is
disabled (P1240 = 0).

If this warning is displayed —
permanently, check the
SED2 input voltage or
extend the ramp-down time
for the SED2.

A0503,
Undervoltage
limit

Input power failed.

Check input supply voltage. —

A0504, SED2
overtemperature

The warning level of the SED2 • The ambient temperature
heat sink temperature (r0037) is must lie within the limits
exceeded.
specified.

The input power and
consequently the DC link
voltage (r0026) are below the
defined threshold value.

This results in a reduced pulse
frequency and/or a reduced
output frequency (dependent
on parameter setting in
(P0610).

92

—

• The load conditions and
duty cycle must lie within
the specified conditions.
• The fan must turn when
the SED2 is running.

Siemens Building Technologies, Inc.

Troubleshooting

Error
A0505, SED2
I2t

Cause
Warning level exceeded. The
current supply is reduced if
parameter P0610=1.

Diagnosis and Remedy
Check that the duty cycle
lies within the limits
specified.

Drive
Reaction
—

Motor power
(P0307)>SED2 power
(P0206).
A0506, SED2
duty cycle

Difference between the heat
sink temperature and IGBT
exceeds the warning levels.

A5011, Motor • Motor is overloaded.
overtemperature I2t • Duty cycle is outside the
tolerance.

Make sure that the load
—
duty cycles (temporary
overload) lie within the limits
specified.
• Correct overload.

—

• Adjust duty cycle.
• Re-run quick
commissioning.
• Verify motor efficiency
setup via P0309 equals
motor nameplate data.
NOTE: Set P0003=3 and
P0010=1 and then advance
to P0309. Set efficiency to
motor rated efficiency, or
99. Advance to P3900=3.

A0520,
Rectifier overtemperature

Warning level of the rectifier
heat sink temperature is
exceeded.

• Ambient temperature must —
lie within the limits
specified.
• Load conditions and duty
cycle must lie within the
specified conditions.
• Fan must turn when the
SED2 is running.

A0523, SED2
output fault

On-phase is interrupted at the
SED2 output.

—

—

A0541, Motor
data
identification
enabled

Motor data identification
(P1910) selected or running.

—

—

A0600, RTOS
data loss

—

—

—

Siemens Building Technologies, Inc.

93

SED2 VFD Startup, Operation, and Maintenance Manual

Error
A0910, Vdc
(max.)
controller
disabled

Cause

Diagnosis and Remedy

• Vdc maximum controller
disabled as not able to keep
the DC link voltage (r0026)
within threshold limits.

• Input voltage must lie
within specified range.

• Permanent supply
overvoltage.

• In some cases, brake
resistance must be
applied.

• Occurs if the motor is driven
by a load forcing the motor to
go into energy recovery
operation.

Drive
Reaction
—

• Load must be adjusted.

• Occurs during ramp-down of
very high duty cycles.
A0911, Vdc
(max.)
controller
enabled

Vdc maximum controller is
enabled.

Increase ramp-down time.

—

Ramp-down times are
increased automatically to keep
the DC link voltage (r0026)
within the limits specified.

—
A0912, Vdc
• Vdc minimum controller
(min) controller
enabled if the DC link voltage
enabled
(r0026) drops below the
minimum value.

—

• Motor kinetic energy is used
to buffer the DC link voltage
and thus slow the SED2.
• Temporary supply failures do
not automatically lead to
undervoltage shutdown.
A0920, Analog • Analog input parameters
input
must not be set to identical
parameters not
values, as illogical values
set properly
would result.

—

—

• Index 0: Parameter settings
for output identical.
• Index 1: Parameter settings
for input identical.
• Index 2: Parameter settings
for input do not correspond to
analog input type.

94

Siemens Building Technologies, Inc.

Troubleshooting

Error

Cause

A0921, Analog • Analog output parameters
output
must not be set to identical
parameters not
values, as illogical values
set properly
would result.

Diagnosis and Remedy

Drive
Reaction

—

—

—
A0922, No load • No load is applied to the
applied to
SED2.
SED2
• Some functions may not work
as under normal load
conditions.

—

A0923, Both
JOG left and
JOG right are
requested

—

• Index 0: Parameter settings
for output identical.
• Index 1: Parameter settings
for input identical.
• Index 2: Parameter settings
for output do not correspond
to analog output type.

Both JOG right and JOG left
—
have been requested. This
freezes the RFG (ramp function
generator) output frequency at
its current value.

A0952, Belt
Load conditions at the motor
failure detected indicate a belt failure or
mechanical fault.

Siemens Building Technologies, Inc.

• No breakage, seizure, or —
obstruction of SED2 train.
• Correct operation of
external speed sensor, if
in use.

95

SED2 VFD Startup, Operation, and Maintenance Manual

Replacement Parts
Replacement Part Description

Part Number

Frame Size A, Fan Assembly, 3-Wire

SED2-FAN-20A

Frame Size B, Fan Assembly, 3-Wire

SED2-FAN-20B

Frame Size C, Fan Assembly, 3-Wire

SED2-FAN-20C

DIM Module Assembly, Frame Sizes D through F

SED2-DIMMOD-DF

Frame Size D & E, Fan Assembly 1 (ADDA)

SED2-FAN-20DE1

Frame Size D & E, Fan Assembly 2 (PAPST)

SED2-FAN-20DE2

Frame Size F, Fan Assembly

SED2-FAN-20F

I/O Module MM436 (SBT) Frame Size A through F

SED2-IOBD1

Terminal Cover, Frame Size A through C

SED2-COV1-ABC

420/440 Frame Size B, Power Connections Cover

SED2-COV2-B

420/440 Frame Size C, Power Connections Cover

SED2-COV2-C

Frame Size B, Fan Assembly IP54 (SBT)

SED2-FAN-54B

Frame Size C, Fan Assembly IP54 (SBT)

SED2-FAN-54C

Frame Size D & E, Fan Assembly IP54 (SBT)

SED2-FAN-54DE

Frame Size F, Fan Assembly IP54 (SBT

SED2-FAN-54F

96

Siemens Building Technologies, Inc.

Repair

Repair
Only Siemens service departments, repair centers authorized by
Siemens Building Technologies, Inc., or authorized personnel who are
fully acquainted with the SED2 may repair this equipment. Replace
defective parts or components using original manufacturer parts.
DANGER:
Always disconnect the power source before opening the
SED2.
Always wait 5 minutes after disconnecting the SED2 from
the power source before performing any work. The DC link
capacitors of all SED2s remain charged with dangerous
voltages for 5 minutes after all supplies have been
disconnected. When working on open equipment, note that
live parts are exposed. Do not touch these parts.
WARNING:
Only use this equipment for the purpose specified by the
manufacturer. Unauthorized modifications and the use of
spare parts and accessories that are not sold or
recommended by the manufacturer of the equipment can
cause fires, electric shocks, and injuries.

Siemens Building Technologies, Inc.

97

SED2 VFD Startup, Operation, and Maintenance Manual

Technical Specifications
Table 9. Drive Specifications.
Drive Specifications
Input voltage and
power (3 phase)
Input frequency
Output frequency
Power factor
VFD degree of
efficiency
Switch-on current
Auxiliary supply 24V
Overload capacity
Control method
PWM frequency
Fixed frequencies
Skip frequency bands
Setpoint resolution
Digital inputs
(sink/source)
Analog inputs
Relay outputs
Analog outputs
Serial interface

Protection level

Temperature ranges
Humidity
Operational altitudes

98

Description
200V to 240V, 3AC±10%.
380V to 480V, 3AC ±10%
500V to 600V, 3 AC ±10%
47 Hz to 63 Hz
0 Hz to 150 Hz
≥0.9
96% to 97%

1/2 hp to 60 hp
1/2 hp to 125 hp
1 hp to 125 hp

Less than nominal input current
Glavanically separated, unregulated auxiliary supply (18V to
32V) 100 mA
100% for 60 seconds, 150% for 3 seconds
Linear, parabolic and programmable V/f; and flux current control
low-power mode
2k Hz to 16k Hz (adjustable in 2k Hz increments)
15 programmable
4 programmable
0.01 Hz digital
0.01 Hz serial
10 bit analog
6: fully programmable and scalable isolated digital inputs,
switchable
2: 0 Vdc to 10 Vdc, 0/4 mA to 20 mA, can also be configured as
digital inputs or Ni 1000 input
2: configurable 30 Vdc /5A (resistive), 250 Vac 2A (inductive)
2: programmable (0/4 mA to 20 mA)
RS-485;
Protocols: USS, P1 and N2;
Transmission rate: Up to 38.4k Baud
IP20
NEMA Type 1 with protective shield and gland plate installed
NEMA Type 12/IP54
Operating: 14°F to 104°F (–10°C to 40°C)
Storage: –40°F to 158°F (–40°C to 70°C)
95% rh, non-condensing
Up to 3280 ft (1000m) above sea level without derating

Siemens Building Technologies, Inc.

Technical Specifications

Drive Specifications

Protection
features

Standards
CE conformity

Description
• Under-voltage
• Over-voltage
• Overload
• Ground fault
• Short circuit
• Stall prevention
• Locked motor
• Motor overtemperature l2 t, PTC
• Over-temperature
• Parameter PIN protection
UL, cUL, CE, C-tick
Conformity with EC Low Voltage Directive 73/23/EEC

Siemens Building Technologies, Inc.

99

SED2 VFD Startup, Operation, and Maintenance Manual

Appendix A: Parameters,
Defaults, and Settings
Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

r0000

Drive display (defined in
P0005)

—

—

—

—

All

r0002

Drive state (actual)

—

—

—

—

3

P0003

User access level

—

0

1

4

1

P0004

Parameter filter

—

0

0

22

1

P0005

Display selection for r0000

—

2

21

2294

2

P0006

Display mode for r0000

—

0

2

4

3

P0010

Commissioning parameter filter

—

0

0

30

1

P0011

Lock for user-defined
parameter

—

0

0

65535

3

P0012

Key for user-defined parameter

—

0

0

65535

3

P0013

User-defined parameter

—

0

0

65535

3

r0018

Firmware version

—

—

—

—

3

r0019

CO/BO: BOP control word

—

—

—

—

3

r0020

CO: Actual frequency setpoint

Hz

—

—

—

3

r0021

CO: Actual frequency

Hz

—

—

—

3

r0022

Actual Rotor speed

1/min

—

—

—

3

r0024

CO: Actual output frequency

Hz

—

—

—

3

r0025

CO: Actual output voltage

V

—

—

—

3

r0026

CO: Actual DC link output
voltage

V

—

—

—

3

r0027

CO: Actual output current

A

—

—

—

3

r0031

Actual torque

Nm

—

—

—

3

r0032

Actual power

—

—

—

—

3

r0035

CO: Actual Motor temperature

°C

—

—

—

3

r0039

CO: Energy consumption meter kWh

—

—

—

3

100

Siemens Building Technologies, Inc.

Appendix A: Parameters, Defaults, and Settings

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P0040

Reset energy consumption
meter

—

0

0

1

3

r0050

CO: Active command data set

—

—

—

—

3

r0052

CO/BO: Actual status word 1

—

—

—

—

3

r0053

CO/BO: Actual status word 2

—

—

—

—

3

r0054

CO/BO: Actual control word 1

—

—

—

—

3

r0055

CO/BO: Additional actual
control word

—

—

—

—

3

r0056

CO/BO: Status of motor control

—

—

—

—

3

r0061

Actual rotor speed

—

—

—

—

3

r0086

CO: Actual active current

A

—

—

—

3

P0100

Europe/North America power
settings [kW or hp]

—

0

0

2

1

r0200

Actual power stack code
number

—

—

—

—

3

r0206

Rated inverter power [kW]/[hp]

—

—

—

—

3

r0207

Rated inverter current

A

—

—

—

3

r0208

Rated inverter voltage

V

—

—

—

3

r0209

Maximum inverter current

A

—

—

—

3

P0304

Rated motor voltage

V

10

Varies

2000

1

P0305

Rated motor current

A

0.01

Varies

10000.00

1

P0307

Rated motor power

—

0.01

Varies

2000.00

1

P0308

Rated motor cosPhi

—

0.000

0.000

1.000

3

P0309

Rated motor efficiency

%

0.0

Varies

99.9

3

P0310

Rated motor frequency

Hz

12.00

50.00 or
60.00

650.00

1

P0311

Rated motor speed

1/min

0

Varies

40000

1

r0313

Motor pole pairs

—

—

—

—

3

P0340

Calculation of motor
parameters

—

0

0

4

3

P0350

Stator resistance (line-to-line)

ohm

0.00001

Varies

2000.0

3

r0395

CO: Total stator resistance [%]

%

—

—

—

3

P0400

Select encoder type

—

0

0

12

3

Siemens Building Technologies, Inc.

101

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P0409

Pulses per second at Rated
Frequency

—

1

25

500

3

P0501

Type of sensor

—

0

0

29

2

P0506

Parameter list

—

0

—

4000

3

P0507

Scalar values

—

0

1.0

9999.9

3

P0508

Unit

—

0

0

65535

3

P0509

String

—

0

0

65535

3

P0601

Motor temp. sensor

—

0

0

2

3

—

0

2

2

3

P0610

Motor

P0640

Motor overload factor [%]

%

10.0

110.0

400.0

3

P0700

Selection of command source

—

0

[0] 2,
[1] 1

6

1

P0701

Function of digital input 1

—

0

[0] 1,
[1] 0

99

2

P0702

Function of digital input 2

—

0

[0] 12,
[1] 0

99

2

P0703

Function of digital input 3

—

0

9

99

2

P0704

Function of digital input 4

—

0

15

99

2

P0705

Function of digital input 5

—

0

15

99

2

P0706

Function of digital input 6

—

0

15

99

2

P0707

Function of digital input 7

—

0

0

99

3

P0708

Function of digital input 8

—

0

0

99

3

P0718

CO/BO: Hand/Auto

—

0

0

1

3

r0722

CO/BO: Binary input values

—

-

-

-

3

P0725

PNP/NPN digital inputs

—

0

1

1

3

P0731

BI: Function of digital output 1

—

0:0

52:3

4000:0

2

P0732

BI: Function of digital output 2

—

0:0

52:2

4000:0

2

r0747

CO/BO: State of digital outputs

—

—

—

—

3

P0748

Invert digital outputs

—

0

0

7

3

r0752

Actual input of ADC (analog
input) [V] or [mA]

—

—

—

—

2

P0753

Smooth time ADC (analog
input)

ms

0

100

10000

3

102

I2t

temperature reaction

Siemens Building Technologies, Inc.

Appendix A: Parameters, Defaults, and Settings

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

r0754

Actual ADC (analog input)
value after scaling [%]

%

—

—

—

2

r0755

CO: Actual ADC (analog input)
after scaling [4000h]

—

—

—

—

3

P0756

Type of ADC (analog input)

—

0

0

5

2

P0757

Value x1 of ADC (analog input)
scaling [V/mA]

—

-50.0

0

150.0

2

P0758

Value y1 of ADC (analog input)
scaling

%

-99999.9

0.0

99999.9

2

P0759

Value x2 of ADC (analog input)
scaling [V/mA]

—

-50.0

10.0

150.0

2

P0760

Value y2 of ADC (analog input)
scaling

%

-99999.9

100.0

99999.9

2

P0761

Width of ADC (analog input)
deadband [V/mA]

—

0

0

150.0

3

P0771

CI: DAC (analog output)

—

0:0

21:0

4000:0

2

P0773

Smooth time DAC (analog
output)

ms

0

100

1000

3

r0774

Actual DAC (analog output)
value [V] or [mA]

—

—

—

—

3

P0776

Type of DAC (analog output)

—

0

1

1

3

P0777

Value x1 of DAC (analog
output) scaling

%

-99999.0

0.0

99999.0

2

P0778

Value y1 of DAC (analog
output) scaling

—

0

0

20

2

P0779

Value x2 of DAC (analog
output) scaling

%

-99999.0

100.0

99999.0

2

P0780

Value y2 of DAC (analog
output) scaling

—

0

10

20

2

P0781

Width of DAC (analog output)
deadband

—

0

0

20

3

P0809

Copy CDS (command data set)

—

0

0

2

3

P0810

BI: CDS (command data set)
bit 0 (Local/Remote)

—

0:0

718:0

4095:0

3

P0918

CB (communications board or
module) address

—

0

3

65535

3

P0927

Parameter changeable via

—

0

—

15

3

Siemens Building Technologies, Inc.

103

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

r0947

Last fault code

—

—

—

—

3

r0948

Fault time

—

—

—

—

3

r0949

Fault value

—

—

—

—

3

P0952

Total number of faults

—

0

0

8

3

r0967

Control word 1

—

—

—

—

3

r0968

Status word 1

—

—

—

—

3

P0970

Factory reset

—

0

0

1

1

P0971

Transfer data from RAM to
EEPROM

—

0

0

1

3

P1000

Selection of frequency setpoint

—

0

2

77

1

P1001

Fixed frequency 1

Hz

-650.0

0.00

650.00

3

P1002

Fixed frequency 2

Hz

-650.0

5.00

650.00

3

P1003

Fixed frequency 3

Hz

-650.0

10.00

650.00

3

P1004

Fixed frequency 4

Hz

-650.0

15.00

650.00

3

P1005

Fixed frequency 5

Hz

-650.0

20.00

650.00

3

P1006

Fixed frequency 6

Hz

-650.0

25.00

650.00

3

P1007

Fixed frequency 7

Hz

-650.0

30.00

650.00

3

P1008

Fixed frequency 8

Hz

-650.0

35.00

650.00

3

P1009

Fixed frequency 9

Hz

-650.0

40.00

650.00

3

P1010

Fixed frequency 10

Hz

-650.0

45.00

650.00

3

P1011

Fixed frequency 11

Hz

-650.0

50.00

650.00

3

P1012

Fixed frequency 12

Hz

-650.0

55.00

650.00

3

P1013

Fixed frequency 13

Hz

-650.0

60.00

650.00

3

P1014

Fixed frequency 14

Hz

-650.0

65.00

650.00

3

P1015

Fixed frequency 15

Hz

-650.0

65.00

650.00

3

P1016

Fixed frequency mode-Bit 0

—

1

1

3

3

P1017

Fixed frequency mode-Bit 1

—

1

1

3

3

P1018

Fixed frequency mode-Bit 2

—

1

1

3

3

P1019

Fixed frequency mode-Bit 3

—

1

1

3

3

P1020

BI: Fixed frequency selection
Bit 0

—

0:0

0:0

4000:0

3

104

Siemens Building Technologies, Inc.

Appendix A: Parameters, Defaults, and Settings

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P1021

BI: Fixed frequency selection
Bit 1

—

0:0

0:0

4000:0

3

P1022

BI: Fixed frequency selection
Bit 2

—

0:0

0:0

4000:0

3

P1023

BI: Fixed frequency selection
Bit 3

—

0:0

722:3

4000:0

3

r1024

CO: Act. fixed frequency

Hz

—

—

—

3

P1025

Fixed frequency mode – Bit 4

—

1

1

3

3

P1026

BI: Fixed frequency selection
Bit 4

—

0:0

722:4

4000:0

3

P1027

Fixed frequency mode – Bit 5

—

1

1

3

3

P1028

BI: Fixed frequency selection
Bit 5

—

0:0

722:5

4000:0

3

P1031

Setpoint memory of the motor
potentiometer

—

0

1

1

3

P1032

Inhibit reverse direction of
motor potentiometer

—

0

1

1

3

P1040

Setpoint of the motor
potentiometer

Hz

-650.00

10.00

650.00

2

r1050

CO: Act. Output frequency of
the motor potentiometer

Hz

—

—

—

3

r1078

CO: Total frequency setpoint

Hz

—

—

—

3

P1080

Minimum frequency

Hz

0.00

10.00

650.00

1

P1082

Maximum frequency

Hz

0.00

50.00/
60.00
Varies

150.00

1

P1091

Skip frequency 1

Hz

0.00

0.00

650.00

3

P1092

Skip frequency 2

Hz

0.00

0.00

650.00

3

P1093

Skip frequency 3

Hz

0.00

0.00

650.00

3

P1094

Skip frequency 4

Hz

0.00

0.00

650.00

3

P1101

Skip frequency bandwidth

Hz

0.00

2.00

10.00

3

P1110

BI: Inhibit neg. frequency
Setpoint

—

0:0

1

4000:0

3

P1120

Ramp-up time

s

0.00

10.00

650.00

1

P1121

Ramp-down time

s

0.00

30.00

650.00

1

Siemens Building Technologies, Inc.

105

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P1135

OFF3 ramp-down time

s

0.00

5.00

650.00

3

P1140

BI: RFG (ramp function
generator) enable

—

0:0

1:0

4000:0

3

P1141

RFG (ramp function generator)
start

—

0.00

1.0

4000.0

3

P1142

RFG (ramp function generator)
enable setpoint

—

0.00

1.0

4000.0

3

P1200

Flying start

—

0

0

6

3

P1202

Motor-current: flying start

%

10

100

200

3

P1203

Search rate: flying start

%

10

100

200

3

P1210

Automatic restart

—

0

1

5

3

P1211

Number of restart attempts

—

0

3

10

3

P1212

Time to first restart

s

0

30

1000

3

P1213

Restart time increment

s

0

30

1000

3

P1230

BI: Enable DC braking

—

0:0

0:0

4000:0

3

P1232

DC braking current

%

0

100

250

3

P1233

Duration of DC braking

s

0

0

250

3

P1236

Compound braking current

%

0

0

250

3

P1240

Configuration of Vdc controller

—

0

1

3

3

P1270

BI: Enable essential service

—

0:0

0:0

4000:0

3

P1300

Control mode

—

0

2

23

3

P1310

Continuous boost

%

0.0

50.0

250.0

3

P1311

Acceleration boost

%

0.0

0.0

250.0

3

P1312

Starting boost

%

0.0

0.0

250.0

3

P1335

Slip compensation

%

0.0

0.0

600.0

3

P1336

Slip limit

%

0

250

600

3

r1337

CO: V/f slip frequency

%

-

-

-

3

P1800

Pulse frequency

kHz

2

Varies

16

2

r1801

CO: Actual switching frequency kHz

—

—

—

3

P1820

Reverse output phase
sequence

—

0

0

1

3

P1910

Select motor data identification

—

0

0

20

3

106

Siemens Building Technologies, Inc.

Appendix A: Parameters, Defaults, and Settings

Parameter

Description

r1912

Identified stator resistance

P2000

Reference frequency

P2001

Unit
ohm

User
Setting

Min

Default

Max

Access
Level

—

—

—

3

Hz

1.00

50/60

650.00

2

Reference voltage

V

10

1000

2000

3

P2002

Reference current

A

0.10

Varies

10000.00

3

P2004

Reference power

—

—

—

—

3

P2009

USS normalization

—

0

0

1

3

P2010

USS baud rate

—

4

6

12

3

P2011

USS address

—

0

0

31

3

P2014

USS telegram off time

ms

0

0

65535

3

P2040

CB telegram off time

ms

0

20

65535

3

P2041

CB parameter

—

0

0

65535

3

r2050

PZD from CB

—

—

—

—

3

P2051

PZD to CB

—

0:0

52:0

4000:0

3

r2053

CB identification

—

—

—

—

3

r2054

CB diagnosis

—

—

—

—

3

P2100

Alarm number selection

—

0

0

65535

3

P2101

Stop reaction value

—

0

0

5

3

r2110

Warning number

—

—

—

—

3

P2111

Total number of warnings

—

0

0

4

3

r2114

Run time counter

—

—

—

—

3

P2115

AOP real time clock

—

0

0

65535

3

P2155

Threshold frequency f_1

Hz

0.00

30.00

650.00

3

P2156

Delay time of threshold
frequency f_1

ms

0

10

10000

3

P2167

Switch-off frequency f_off

Hz

0.00

1.00

10.00

3

P2168

Delay time T_off

ms

0

10

10000

3

P2181

Belt failure detection mode

—

0

0

6

3

P2182

Belt threshold frequency 1

Hz

0.00

5.00

650.00

3

P2183

Belt threshold frequency 2

Hz

0.00

30.00

650.00

3

P2184

Belt threshold frequency 3

Hz

0.00

50.00

650.00

2

P2185

Upper torque threshold 1

Nm

0.0

99999.0

99999.0

3

Siemens Building Technologies, Inc.

107

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P2186

Lower torque threshold 1

Nm

0.0

0.0

99999.0

3

P2187

Upper torque threshold 2

Nm

0.0

99999.0

99999.0

3

P2188

Lower torque threshold 2

Nm

0.0

0.0

99999.0

3

P2189

Upper torque threshold 3

Nm

0.0

99999.0

99999.0

3

P2190

Lower torque threshold 3

Nm

0.0

0.0

99999.0

3

P2191

Belt failure speed tolerance

Hz

0.00

3.00

20.00

3

P2192

Time delay for belt failure

s

0

10

65

3

r2197

CO/BO: Monitoring word 1

—

—

—

—

3

r2198

CO/BO: Monitoring word 2

—

—

—

—

3

P2200

BI: Enable PID controller

—

0:0

0:0

4000:0

3

P2201

Fixed PID setpoint 1

%

-200.00

0.00

200.00

3

P2202

Fixed PID setpoint 2

%

-200.00

10.00

200.00

3

P2203

Fixed PID setpoint 3

%

-200.00

20.00

200.00

3

P2204

Fixed PID setpoint 4

%

-200.00

30.00

200.00

3

P2205

Fixed PID setpoint 5

%

-200.00

40.00

200.00

3

P2206

Fixed PID setpoint 6

%

-200.00

50.00

200.00

3

P2207

Fixed PID setpoint 7

%

-200.00

60.00

200.00

3

P2208

Fixed PID setpoint 8

%

-200.00

70.00

200.00

3

P2209

Fixed PID setpoint 9

%

-200.00

80.00

200.00

3

P2210

Fixed PID setpoint 10

%

-200.00

90.00

200.00

3

P2211

Fixed PID setpoint 11

%

-200.00

100.00

200.00

3

P2212

Fixed PID setpoint 12

%

-200.00

110.00

200.00

3

P2213

Fixed PID setpoint 13

%

-200.00

120.00

200.00

3

P2214

Fixed PID setpoint 14

%

-200.00

130.00

200.00

3

P2215

Fixed PID setpoint 15

%

-200.00

130.00

200.00

3

P2216

Fixed PID setpoint mode-Bit 0

—

1

1

3

3

P2217

Fixed PID setpoint mode-Bit 1

—

1

1

3

3

P2218

Fixed PID setpoint mode-Bit 2

—

1

1

3

3

P2219

Fixed PID setpoint mode-Bit 3

—

1

1

3

3

P2220

BI: Fixed PID setpoint select Bit
0

—

0:0

0:0

4000:0

3

108

Siemens Building Technologies, Inc.

Appendix A: Parameters, Defaults, and Settings

Parameter

User
Setting

Min

Default

Max

Access
Level

Description

Unit

P2221

BI: Fixed PID setpoint select Bit
1

—

0:0

0:0

4000:0

3

P2222

BI: Fixed PID setpoint select Bit
2

—

0:0

0:0

4000:0

3

P2223

BI: Fixed PID setpoint select Bit
3

—

0:0

722:3

4000:0

3

r2224

CO: Act. fixed PID setpoint

%

—

—

—

3

P2225

Fixed PID setpoint mode-Bit 4

—

1

1

2

3

P2226

BI: Fixed PID setpoint select Bit
4

—

0:0

722:4

4000:0

3

P2227

Fixed PID setpoint mode-Bit 5

—

1

1

2

3

P2228

BI: Fixed PID setpoint select Bit
5

—

0:0

722:5

4000:0

3

P2231

Setpoint memory of PID-motor
potentiometer

—

0

1

1

3

P2232

Inhibit rev. direct. of PID-motor
potentiometer

—

0

1

1

3

P2240

Setpoint of PID-motor
potentiometer

%

-200.00

10.00

200.00

3

r2250

CO: Output setpoint of PIDmotor potentiometer

%

—

—

—

3

P2253

CI: PID setpoint

—

0:0

2250:0

4000:0

2

P2254

CI: PID trim

—

0:0

0:0

4000:0

3

P2261

PID setpoint filter

—

0.00

0.00

60.00

3

r2262

CO: Act. PID filtered setpoint

%

—

—

—

3

P2264

CI: PID feedback

—

0:0

755:1

4000:0

2

P2265

PID feedback filter time
constant

s

0.00

0.00

60.00

3

P2267

Max. value for PID feedback

%

-200.00

150.00

200.00

3

P2268

Min. value for PID feedback

%

-200.00

-50.00

200.00

3

P2269

Gain applied to PID feedback

—

0.00

100.00

500.00

3

P2270

PID feedback function selector

—

0

0

3

3

P2271

PID transducer type

—

0

0

1

3

r2272

CO: PID scaled feedback

%

—

—

—

3

r2273

CO: PID error

%

—

—

—

3

Siemens Building Technologies, Inc.

109

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter

Description

Unit

User
Setting

Min

Default

Max

Access
Level

P2274

PID derivative time

s

0

0

65535

2

P2279

PID neutral zone

%

0.00

0.00

100.00

3

P2280

PID proportional gain

—

0.000

1.200

65.000

2

P2285

PID integral time

s

0

30

65535

2

P2291

PID output upper limit

%

0.00

100.00

100.00

2

P2292

PID output lower limit

%

-200.00

0.00

200.00

2

P2293

PID limit ramp time

s

0.00

0.00

100.00

3

r2294

CO: Actual PID output

%

—

—

—

3

P2303

PID output offset

—

0.0

0.0

4000.0

2

P2304

PID opening time

—

0

0

65535

2

P2305

PID closing time

—

0

0

65535

2

P2306

PID actuator direction

—

0

1

1

2

P2370

Selection of motor staging stop
mode

—

0

0

1

3

P2371

Selection of external motor
configuration

—

0

0

8

3

P2372

Enable motor cycling

—

0

0

1

3

P2373

Motor staging hysteresis

%

0.0

20.0

200.0

3

P2374

Motor staging delay

s

0

30

650

3

P2375

Motor de-staging delay

s

0

30

650

3

P2376

Delay override

%

0.0

25.0

200.0

3

P2377

Delay override lockout timer

s

0

30

650

3

P2378

Staging frequency f, %fMax

%

0.0

50.0

120.0

3

r2379

CO/BO: Status of motor
staging

—

—

—

—

3

P2380

Motor hours run

h

0

0

100000

3

P2390

Hibernation setpoint

%

-200.00

0.00

200.00

3

P2391

Hibernation timer

s

0

0

254

3

P2392

Restart PID error

%

-200.00

0.00

200.00

3

P3900

End of quick commissioning

—

0

0

3

1

110

Siemens Building Technologies, Inc.

SED2 VFD Startup, Operation, and Maintenance Manual

Appendix B: SED2 Point
Maps
Table 10. SBT P1 Point Cross Reference to SED2.
Point Point
No. Type

Descriptor

Factory Eng.
Default Units
(SI
(SI
Units) Units)

Off
Text

On Text

SED2
Reference

01

LAO CTLR ADDRESS

99

–

–

–

SBT

02

LAO APPLICATION

2722

–

–

–

SBT

03

LAI

FREQ OUTPUT

0

HZ

–

–

r0021

05

LAI

SPEED

0

RPM

–

–

Calculated
based on
P0311

06

LAI

CURRENT

0

A

–

–

r0027

07

LAI

TORQUE

0

NM

–

–

r0031

08

LAI

ACTUAL POWER 0

HP/
KW

–

–

r0032

09

LAI

TOTAL KWH

0

KWH

–

–

r0039

13

LAI

DC BUS VOLT

0

V

–

–

r0026

14

LAI

REFERENCE

0

HZ

–

–

r0020

16

LAI

RATED PWR

0

HP/
KW

–

–

P0307

17

LAI

OUTPUT VOLTS

0

V

–

–

r0025

20

LAO OVRD TIME

1

HRS

–

–

21

LDI

FWD.REV

FWD

–

REV

FWD

r0054 bit 11

22

LDO CMD FWD.REV

FWD

–

REV

FWD

P0842(2)

23

LDI

STOP.RUN

STOP

–

RUN

STOP r0019 bit 1

24

LDO CMD STP.STRT

STOP

–

START

STOP P0840(2)

25

LDI

AT MAX FREQ

NO

–

MAX

NO

26

LDI

CONTROL MODE SERIAL –

SERIAL

LOCAL P0700(2)

27

LDI

ENABLED

OFF

–

ENABLED OFF

r0052 bit 0

28

LDI

READY TO RUN

OFF

–

READY

r0052 bit 1

111

OFF

Siemens Building Technologies, Inc.

SED2 VFD Startup, Operation, and Maintenance Manual
Table 10. SBT P1 Point Cross Reference to SED2.
Point Point
No. Type

Descriptor

Factory Eng.
Default Units
(SI
(SI
Units) Units)

Off
Text

On Text

SED2
Reference

29

LDO DAY.NIGHT

DAY

–

NIGHT

DAY

SBT

30

LAO CURRENT LIM

1400

PCT

–

–

r0067

31

LAO ACCEL TIME 1

500

SEC

–

–

read P1120

32

LAO DECEL TIME 1

500

SEC

–

–

read P1121

34

LDO SEL HND.AUTO

AUTO

–

AUTO

HAND P1000(2)

(reference)
35

LDO RUN ENABLE

ENABLE –

ENABLE

OFF

r0052 bit 0

40

LDO DIGITAL OUT 1

OFF

–

ON

OFF

P0731(2) read
at r0747

41

LDO

OFF

–

ON

OFF

P0732(2) read
at r0747

45

LAI

ANALOG IN 1

0

PCT

–

–

r0754(0)

46

LAI

ANALOG IN 2

0

PCT

–

–

r0754(1)

47

LAI

ANALOG OUT 1

0

PCT

–

–

–

48

LAI

ANALOG OUT 2

0

PCT

–

–

–

51

LAO FREQ REF

0

PCT

–

–

r0754(0)

52

LAI

0

PCT

–

–

r0754(0)

53

LAO FREQ MAX

2450

HZ

–

–

P1082

55

LAO PID SETP REF

8602

PCT

–

–

r0754(0)

56

LAI

0

PCT

–

–

r2294

57

LAO PID UP LMT

12288

PCT

–

–

P2291

58

LAO PID LO LMT

8192

PCT

–

–

P2292

59

LAI

PID OUTPUT

0

PCT

–

–

r2294

60

LAI

PI FEEDBACK

0

PCT

–

–

r2272

61

LAI

P GAIN

0

PCT

–

–

P2280

62

LAI

I GAIN

0

PCT

–

–

P2285

63

LAI

D GAIN

0

PCT

–

–

P2274

64

LDO ENABLE PID

0

ON

OFF

P2200

66

LAI

–

–

P2269

112

DIGITAL OUT 2

FREQ ACTUAL

PID SETP OUT

FEEDBK GAIN

0

PCT

Siemens Building Technologies, Inc.

Appendix B: SED2 Point Cross-Reference

Table 10. SBT P1 Point Cross Reference to SED2.
Point Point
No. Type

Descriptor

Factory Eng.
Default Units
(SI
(SI
Units) Units)

Off
Text

On Text

SED2
Reference

68

LAI

LOW PASS

0

–

–

–

–

71

LDI

DIGITAL IN 1

0

–

ON

OFF

r0722 bit 0

72

LDI

DIGITAL IN 2

0

–

ON

OFF

r0722 bit 1

73

LDI

DIGITAL IN 3

0

–

ON

OFF

r0722 bit 2

74

LDI

DIGITAL IN 4

0

–

ON

OFF

r0722 bit 3

75

LDI

DIGITAL IN 5

0

–

ON

OFF

r0722 bit 4

76

LDI

DIGITAL IN 6

0

–

ON

OFF

r0722 bit 5

80

LAO WDOG TIME

0

–

–

–

–

83

LAI

INVERTER VER

0

–

–

–

r0018

84

LAI

DRIVE MODEL

0

–

–

–

–

90

LAI

LAST FAULT

0

–

–

–

r0947(0)

91

LAI

1st FAULT

0

–

–

–

r0947(1)

92

LAI

2nd FAULT

0

–

–

–

r0947(2)

93

LAI

3rd FAULT

0

–

–

–

r0947(3)

94

LDI

OK FAULT

0

–

FAULT

OK

r0052 bit 3

95

LDO FAULT ACK

0

–

ON

OFF

r0054 bit 7

96

LDI

WARNING

0

–

WARN

OK

r0052 bit 7

97

LAI

LAST WARNING

0

–

–

–

r2110 (0)

99

LAO ERROR STATUS

0

–

–

–

–

Siemens Building Technologies, Inc.

113

SED2 VFD Startup, Operation, and Maintenance Manual

Table 11. JCI N2 Point Cross Reference to SED2.

Point
Number

Name

Default
Units
Value

Notes

On
Text

Off
Text

SED2
Ref.

Or Range
AI1

FREQ OUTPUT

0

HZ

No Override -650.00 to 650.00 r0024

AI2

SPEED

0

RPM

No Override -16250 to 16250

r0022

AI3

CURRENT

0

A

No Override 0 to 1638.35

r0027

AI4

TORQUE

0

NM

No Override -3250.0 to 3250.0 r0031

AI5

DC BUS VOLTS

0

V

No Override 0 to 32767

AI6

REFERENCE

0

HZ

No Override -650.00 to 650.00 r0020

AI7

OUTPUT VOLTS

0

V

No Override 0 to 32767

r0025

AI8

ANALOG IN 1

0

PCT

No Override -300.0 to 300.0

r0754/0

AI9

ANALOG IN 2

0

PCT

No Override -300.0 to 300.0

r0754/1

AI10

PI FEEDBACK

0

PCT

No Override -100.0 to 100.0

r2266

AI11

ANALOG OUT 1

0

PCT

No Override -100.0 to 100.0

r0774/0

AI12

ANALOG OUT 2

0

PCT

No Override -100.0 to 100.0

r0774/1

AI13

PID SETP OUT

0

PCT

No Override -100.0 to 100.0

r2250

AI14

PID OUTPUT

0

PCT

No Override -100.0 to 100.0

r2294

AI15

ACTUAL PWR

0

KW

No Override 0 to 327.67

r0032

AI16

TOTAL KWH

0

KWH

No Override 0 to 32767

r0039

AI17

FREQ ACTUAL

0

PCT

No Override -100.00 to 100.00 HIW

AO1

FREQ REF

0

PCT

–

BI1

ENABLED

0

–

No Override ON

OFF

ZSW:0

BI2

READY TO RUN

0

–

No Override READY

OFF

ZSW:1

BI3

STOP RUN

0

–

No Override RUN

STOP

ZSW:2

BI4

AT MAX FREQ

0

–

No Override MAX

NO

ZSW:10

BI5

CONTROL MODE 1

–

No Override SERIAL LOCAL ZSW:9

BI6

FAULT

0

–

No Override FAULT

OK

ZSW:3

BI7

WARNING

0

–

No Override WARN

OK

ZSW:7

BI8

DIGITAL IN 1

0

–

No Override ON

OFF

r0722:0

BI9

DIGITAL IN 2

0

–

No Override ON

OFF

r0722:1

114

0.00 to 100.00

r0026

HSW

Siemens Building Technologies, Inc.

Appendix B: SED2 Point Cross-Reference

Table 11. JCI N2 Point Cross Reference to SED2.

Point
Number

Name

Default
Units
Value

Notes

On
Text

Off
Text

SED2
Ref.

Or Range
BI10

DIGITAL IN 3

0

–

No Override ON

OFF

r0722:2

BI11

DIGITAL IN 4

0

–

No Override ON

OFF

r0722:3

BI12

DIGITAL IN 5

0

–

No Override ON

OFF

r0722:4

BI13

DIGITAL IN 6

0

–

No Override ON

OFF

r0722:5

BI14

FWD REV

0

–

No Override FWD

REV

ZSW:14

BO1

CMD START

0

–

–

START

STOP

STW:0

BO2

RUN ENABLE

1

–

–

ENABLE OFF

STW:3

BO3

FAULT ACK

0

–

–

ON

OFF

STW:7

BO4

HAND AUTO

0

–

–

HAND

AUTO

P0718

BO5

DIGITAL OUT 1

0

–

–

ON

OFF

P0731

BO6

DIGITAL OUT 2

0

–

–

ON

OFF

P0733

BO7

CMD FWD REV

0

–

–

REV

FWD

STW:11

BO8

ENABLE PID

0

–

–

ON

OFF

P2200

ADF1

ACCEL TIME 1

10.00

SEC

–

0.00 to 650.00

P1120

ADF2

DECEL TIME 1

10.00

SEC

–

0.00 to 650.00

P1121

ADF3

CURRENT LMT

150.0

PCT

–

10.0 to 400.0

P0640

ADF4

P GAIN

3.000

–

–

0.000 to 65.000

P2280

ADF5

I GAIN

0

SEC

–

0.000 to 60.000

P2285

ADF6

D GAIN

0

–

–

0.000 to 60.000

P2274

ADF7

FEEDBK GAIN

100.00 PCT

–

0.00 to 500.00

P2269

ADF8

LOW PASS

0

–

–

0.00 to 60.00

P2265

ADF9

PID SETP REF

0

PCT

–

-200.0 to 200.0

P2240

ADF10

PID UP LMT

100.0

PCT

–

-200.0 to 200.0

P2291

ADF11

PID LO LMT

0

PCT

–

-200.0 to 200.0

P2292

ADF12

FREQ MAX

50.00

HZ

–

1.00 to 650.00

P2000

ADF13

RATED PWR

0

KW

Read Only

0 to 327.67

r0206

ADF14

INVERTER VER

0

–

Read Only

0.00 to 327.67

r0018

ADI1

WDOG TIME

0

MS

–

9999

P2040

Siemens Building Technologies, Inc.

115

SED2 VFD Startup, Operation, and Maintenance Manual
Table 11. JCI N2 Point Cross Reference to SED2.

Point
Number

Name

Default
Units
Value

Notes

On
Text

Off
Text

SED2
Ref.

Or Range
ADI2

DRIVE MODEL

0

--

Read Only

0 to 32767

r0200

ADI3

LAST FAULT

0

--

Read Only

0 to 32767

r0947

ADI4

1ST FAULT

0

--

Read Only

0 to 32767

r0947

ADI5

2ND FAULT

0

--

Read Only

0 to 32767

r0947

ADI6

3RD FAULT

0

--

Read Only

0 to 32767

r0947

ADI7

LAST WARNING

0

--

Read Only

0 to 32767

r2110

116

Siemens Building Technologies, Inc.

SED2 VFD Startup, Operation, and Maintenance Manual

Glossary
Access Level
The degree of authorization a user has when using SED2 parameters.
Also see User Access Level parameter P0003.

ADC
Analog to Digital Converter; refers to analog inputs.

AOP
Advanced Operator Panel.

Boost
Applies an offset relative to the rated motor current. Boost is useful for
loads with high inertia. Also see Continuous Boost parameter P1310,
Acceleration Boost parameter P1311, and Starting Boost parameter
P1312.

BOP
Basic Operator Panel.

CDS
Command Data Set.

Control Mode
Controls relationship between speed of motor and voltage supplied by
SED2. Also see Control Mode parameter P1300.

DAC
Digital to Analog Converter; refers to analog outputs

DC Braking
Causes the motor to stop rapidly by applying a DC braking current
(current applied also holds motor shaft stationary). When the DC braking
signal is applied, the SED2 output pulses are blocked and the DC current
is not applied until the motor has been sufficiently demagnetized. Also
see Enable DC Braking parameter P1230).

EMC
Electromagnetic Compatibility.

117

Siemens Building Technologies, Inc.

SED2 VFD Startup, Operation, and Maintenance Manual

EMI
Electromagnetic Interference.

Fixed Frequency
Frequency setpoints that are based on selection of a predetermined
source.

Flying Start
Starts SED2 onto a spinning motor by rapidly changing the output
frequency of the SED2 until the actual motor speed has been found.
Then, the motor runs up to setpoint using the normal ramp time.

Inverter
Another term for a variable frequency drive (VFD).

IP20
IP20 is the enclosure rating for the standard SED2 from Europe; there is
no equivalent North American enclosure rating. An enclosure with an
IP20 rating is protected against penetration of solid objects greater than
0.47 inches (12mm) and it is protected against vertically falling drops of
water such as from condensation.

Mains
Another term for input line power.

Motor I2t Temperature
Provides a model for estimating the thermal motor value; used for
2
internal motor overload protection. Also see Motor I t Temperature
Reaction parameter P0610 and Motor temperature Sensor parameter
P0601.

Motor Pole Pairs
One of the pole pairs is called a winding.

NEMA Type 1
NEMA Type 1 SED2s include gland plates (frame sizes A through C) and
protection shields. An enclosure with a NEMA Type 1 rating is intended
for indoor use, primarily to provide a degree of protection against contact
with the enclosed equipment or for locations where unusual service
conditions do not exist. NEMA Type 1 enclosures protect the operator
from electric hazard and protect the equipment from falling material.

118

Siemens Building Technologies, Inc.

Glossary

NEMA Type 12/IP54
IP54 is a European enclosure rating; there is no equivalent North
American rating, although it exceed the NEMA Type 12 rating. An
enclosure with a NEMA Type 12 rating is intended for indoor use,
primarily to provide a degree of protection against dust, falling dirt, and
dripping non-corrosive liquids. An enclosure with an IP54 rating is
protected against dust (limited ingress, no harmful deposit) and it is
protected against water sprayed from all directions (limited ingress
permitted).

OFF1
The OFF1 command stops the SED2 within the selected ramp-down
time (P1121).

OFF2
The OFF2 command causes a free coasting of the motor to a standstill
(impulses for the power section of the SED2 are disabled).

OFF3
The OFF3 command causes the motor to decelerate rapidly.

Overcurrent
A SED2 fault condition that occurs, for example, when motor power is
greater than SED2 power. Also see Fault Code F0001.

Overvoltage
A SED2 fault condition that occurs, for example, when the input line
power is too high or if the motor is in regenerative mode (caused by fast
ramp downs or if the motor id drive from an active load). Also see Fault
Code F0002.

Parameter Filter
Functional categories of parameters that are available to a user. Also
see Parameter Filter P0004.

Siemens Building Technologies, Inc.

119

SED2 VFD Startup, Operation, and Maintenance Manual

Parameter Index/Indexes
Subsets of closely related information associated with a particular
parameter function.
For example, the following indexes are associated with P0700, P1000,
and digital input and output parameters:
IN000 (AUTO), 1st Command Data Set (CDS)
IN001 (HAND, 2nd Command Data Set (CDS)
The following indexes are associated with analog input and output
parameters:
IN000, Analog Input 1
IN001, Analog Input 2.

PID
Proportional, Integral, Derivative.

Quick Commissioning
Predefined procedure consisting of fundamental parameters to configure
the SED2 for operation.

Ramp-down Time
Time for the motor to ramp down. Also see Ramp-down Time parameter
P1121.

Ramp-up Time
Time for the motor to ramp up. Also see Ramp-up Time parameter
P1120.

RFG
Ramp Function Generator.

RFI
Radio Frequency Interference.

Skip Frequency
Frequencies that are skipped to avoid effects of mechanical resonance.
Also see Skip Frequency parameter P1091.

120

Siemens Building Technologies, Inc.

Glossary

Slip Compensation
Dynamically adjusts the output frequency of the SED2 so that the motor
speed is kept constant independent of the motor load. Also see Slip
Compensation parameter P1335.

Stator Resistance
Impedance produced from each motor winding.

Train (HVAC)
Sequence or succession of mechanical equipment.

Undervoltage
A SED2 fault condition that occurs, for example, when input line power
has failed or is outside the voltage reduction tolerance. Also see Fault
Code F0003.

VFD/VSD
Variable Frequency Drive/Variable Speed Drive. Both terms are used for
a device that controls the frequency or speed of another device such as
a fan or pump motor.

Siemens Building Technologies, Inc.

121

SED2 VFD Startup, Operation, and Maintenance Manual

Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
Tel: +1 847-215-1000
Fax +1 847-215-1093

Siemens Building Technologies, Ltd.
2 Kenview Blvd.
Brampton, Ontario
Canada L6T 5E4
Tel: +1 905-799-9937

Siemens Building Technologies AG
Gubelstrasse 22
CH-6301 Zug
Tel: +41 41 724 24 24
Fax +41 41 724 35 22

Siemens Building Technologies Ltd.
16/F, Laford Centre
838 Lai Chi Kok Road
Kowloon, Hong Kong
Tel: +852 2917 5700
Fax +852 2904 1126
www.sbt.siemens.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2003:09:10 20:58:38Z
Modify Date                     : 2003:10:07 09:23:26-05:00
Creator                         : PScript5.dll Version 5.2
Page Count                      : 132
Creation Date                   : 2003:09:10 20:58:38Z
Mod Date                        : 2003:10:07 09:23:26-05:00
Producer                        : Acrobat Distiller 5.0 (Windows)
Metadata Date                   : 2003:10:07 09:23:26-05:00
Title                           : Microsoft Word - 125-3201.doc
EXIF Metadata provided by EXIF.tools

Navigation menu