Techman_pw3000 18000 PW5000 TM (PW 8000 To 20000) 2012
User Manual: PW5000
Open the PDF directly: View PDF .
Page Count: 101
Download | ![]() |
Open PDF In Browser | View PDF |
Village Marine-PW 3000 Part Number: 95-0027 Pure Water Series PW 8,000-20,000 GPD Installation, Operation & Maintenance TABLE OF CONTENTS 1.0 SYSTEM DESCRIPTION 1 1.1 SPECIFICATIONS 1 1.1.1 PERFORMANCE CHARACTERISTICS 1 1.1.2 PHYSICAL CHARACTERISTICS 2 1.1.3 UTILITY REQUIREMENTS 2 1.1.4 ENVIRONMENTAL REQUIREMENTS 3 1.2 EQUIPMENT REQUIRED FOR OPERATION 3 1.2.1 CONSUMABLES 3 1.2.2 TEST EQUIPMENT 4 2.0 PREPARATION FOR USE, INSTALLATION AND INITIAL ADJUSTMENT 5 2.1 UNPACKING AND HANDLING 5 2.2 LOCATION 5 3.0 GENERAL THEORY OF OPERATION 9 3.1 REVERSE OSMOSIS THEORY 9 3.2 APPLICATION OF REVERSE OSMOSIS 10 3.3 PRODUCT WATER QUALITY STANDARDS 11 3.4 FACTORS AFFECTING PERMEATE PRODUCTION 11 3.4.1 VARIATIONS IN TEMPERATURE, PRESSURE AND SALINITY 11 3.4.2 TEMPERATURE CORRECTION FACTOR 12 3.5 OPERATIONAL DESCRIPTION 14 3.5.1 FILTRATION SYSTEM 14 3.5.2 REVERSE OSMOSIS SYSTEM 14 3.5.3 PRODUCT MONITORING SYSTEM 15 3.5.4 MEMBRANE CLEANING SYSTEM 15 3.6 WATER QUALITY MONITOR 16 3.6.1 PUSHBUTTONS 16 3.6.2 DISPLAYS AND LIGHTS 16 3.7 CONTROLS AND INSTRUMENTATION 16 i 4.0 OPERATION 19 4.1 START-UP PROCEDURE 19 4.2 SHUTDOWN PROCEDURES 21 4.2.1 SHUTDOWN PROCEDURE (SHORT TERM) 21 4.2.2 SHUTDOWN PROCEDURE (EXTENDED) 22 4.3 FRESH WATER FLUSH PROCEDURE 22 5.0 MAINTENANCE INSTRUCTIONS 23 5.1 GENERAL 23 5.2 RAW WATER STRAINER INSPECTION 24 5.3 FILTER ELEMENT CLEANING OR REPLACEMENT 24 5.4 DRIVE BELT INSPECTION AND REPLACEMENT 25 5.5 RO MEMBRANE CLEANING 26 5.5.1 CLEANING CHEMICALS 26 5.5.2 WHEN TO CLEAN 27 5.6 RO ELEMENT PRESERVATION 30 5.7 RESTARTING UNIT AFTER PRESERVATION 31 5.8 HIGH PRESS7URE PUMP OIL CHANGE 31 5.9 HIGH PRESSURE PUMP MOTOR LUBRICATION 31 5.10 INSPECTION LOG 31 6.0 PRESSURE VESSELS AND MEMBRANES 34 6.1 PRESSURE VESSEL DISASSEMBLY 34 6.3 PRESSURE VESSEL ASSEMBLY 36 7.0 PRESERVATION FOR STORAGE 38 8.0 TROUBLESHOOTING 38 9.0 SYSTEM DRAWINGS AND DIAGRAMS / PARTS LIST 39 ii LIST OF FIGURES Figure 2.0 - Recommended Installation (Below Water Line) ............................................ 5 Figure 2.1 - Proper Installation (Above Water Line) ......................................................... 6 Figure 3.0 - Simple (Reverse) Osmotic System ............................................................... 9 Figure 3.1 - Simplified Schematic of an RO System....................................................... 10 Figure 5.0 - Maintenance Task Chart ............................................................................. 23 Figure 5.1 - Sample Operational Log ............................................................................. 32 Figure 5.2 - Sample Discrepancy Report ....................................................................... 33 Figure 6.0 - Pressure Vessel End Plug .......................................................................... 34 Figure 6.1 - Brine Seal Orientation ................................................................................. 35 Figure 6.2 - End Plug Installation Aid ............................................................................. 36 LIST OF TABLES Table 1.0 - Performance Specification ............................................................................. 1 Table 1.1 - Unit Dimensions ............................................................................................. 2 Table 1.2 - Unit Weights................................................................................................... 2 Table 1.3 - HP Pump Horsepower.................................................................................... 2 Table 1.4 - Utility Requirements ....................................................................................... 2 Table 1.5 - Design Flow ................................................................................................... 3 Table 1.6 - Nominal Operating Conditions ....................................................................... 3 Table 1.7 - Consumables ................................................................................................. 4 Table 1.8 - Recommended Test Equipment..................................................................... 4 Table 3.0 - WHO Drinking Water Standards .................................................................. 11 Table 3.1 - Factors Affecting Permeate Quality.............................................................. 12 Table 3.2 - Temperature Correction Factors (TCF) ........................................................ 13 Table 3.3 - Instrumentation and Controls ....................................................................... 18 Table 4.0 - Valve/Switch Line Up - Initial Start-up .......................................................... 19 Table 5.0 - Filter Tank Parts List. ................................................................................... 24 Table 5.1 - Chemical Requirements ............................................................................... 26 Table 5.2 - Lubrication Requirements ............................................................................ 31 iii The following are the types of flags used in this technical manual. They designate safety related items and important operational instructions and should be given special attention when they appear in the text: WARNING CAUTION NOTE Text formatted in this manner concerns an operating procedure or practice that, if not strictly observed, can result in injury to personnel or loss of life. Text formatted in this manner concerns an operating procedure or practice that, if not strictly observed, can result in damage to or destruction of equipment. Text formatted in this manner concerns an operating procedure or condition that warrants special attention. iv 1.0 SYSTEM DESCRIPTION The Village Marine Tec. (VMT) Seawater Desalinator is a single-pass purification system that uses reverse osmosis (RO) as its method of seawater desalination. This unit produces potable (drinking) quality water with salt concentrations of < 500 ppm by removing approximately 99% of the dissolved salt in seawater. This manual covers the following models: PW3000, PW4000, PW5000, PW6000, PW7000, PW8000, PW10000, PW12000, PW16000 and PW20000. The principle of operation is the same for all models. Specific differences are noted, where applicable. 1.1 SPECIFICATIONS 1.1.1 PERFORMANCE CHARACTERISTICS Parameter Specification Raw water temperature range: Design RO element pressure: Max. RO element pressure: Max. feedwater residual chlorine: pH range (short term for cleaning): Membrane type: Nominal product water production: (2) PW-3000 PW-4000 PW-5000 PW-6000 PW-7000 PW-8000 PW-10000 PW-12000 PW-16000 PW-20000 (2) 1-40°C (33-108ºF) 800 psi 1000 psi < 0.1 ppm 4-10 (3-11) Thin film composite 2.1 gpm 2.8 gpm 3.5 gpm 4.2 gpm 4.9 gpm 5.6 gpm 6.9 gpm 8.3 gpm 11.1 gpm 13.9 gpm Raw water temperatures less than 25°C (77ºF) will result in less than rated product water output. Conversely, higher raw water temperatures will result in higher than rated output. Table 1.0 - Performance Specification PW-3000 to PW-20000 Manual 1 Last Revised 01/12 1.1.2 PHYSICAL CHARACTERISTICS PW30005000 84" 34" 35" Length Width Height PW6000 84" 44" 35" PW700012000 84" 48" 35" PW1600020000 84” 52” 43” Table 1.1 - Unit Dimensions Weight Weight PW3000 PW4000 PW5000 PW6000 PW7000 800 LB 900 LB 1000 LB 1050 LB 1500 LB PW8000 PW10000 PW12000 PW16000 PW20000 1600 LB 1800 LB 1900 LB 2200 LB 2250 LB Table 1.2 – Unit Weights 1.1.3 UTILITY REQUIREMENTS See the nameplate attached to top of the unit for power requirements. Motor HP Motor HP PW3000 PW4000 PW5000 PW6000 PW7000 10 10 15 15 15 PW8000 PW10000 PW12000 PW16000 PW20000 20 20 25 25 30 Table 1.3 – HP Pump Horsepower Design Pressure Design Pressure Minimum Maximum (psi) (psi) Raw water inlet 1 ½” ANSI Flange 0 50 Reject discharge* 1 ½” ANSI Flange 0 15 Product water discharge 1” ANSI Flange 0 15 Flush water inlet 1 ½” NPT 20 50 * Vacuum condition at shutdown is not acceptable, syphon breaker may be reqd. Utility Connection Table 1.4 - Utility Requirements PW-3000 to PW-20000 Manual 2 Last Revised 01/12 Unit Raw water inlet (gpm) Reject discharge (gpm) PW-3000 PW-4000 PW-5000 PW-6000 PW-7000 PW-8000 PW-10000 PW-12000 PW-16000 PW-20000 14 14 20 20 20 24 30 36 36 43 12 11 16 16 15 19 23 28 26 29 Product water discharge (gpm) 2.1 2.8 3.5 4.2 4.9 5.6 6.9 8.3 10.4 13.9 Table 1.5 – Nominal Design Flow 1.1.4 ENVIRONMENTAL REQUIREMENTS Parameter Specification Ambient temperature: 1-40°C (33-108ºF) List (permanent): Trim (fore and aft): Pitch: Roll: 15º + 30º ± 10º (6 sec cycle) ± 30º (12 sec cycle) Table 1.6 - Nominal Operating Conditions 1.2 EQUIPMENT REQUIRED FOR OPERATION 1.2.1 CONSUMABLES The following is the normal quantity of equipment consumed during 6 months of standard unit operation: NOTE Only Village Marine Tec approved filters and chemicals should be used. PW-3000 to PW-20000 Manual 3 Last Revised 01/12 QTY Description VMT Part No. PW3000-6000 PW7000-20000 Cleaning Chemical #1, 25 lbs 2 3 85-0045 Cleaning Chemical #2, 25 lbs Preservative Chemical #3, 25 lbs Filter, 100 ft2, 5 Micron Filter, 100 ft2, 20 Micron Flushing Filter Oil, HP Pump, Quart LP Pump Mech Seal Kit HP Pump Service Kits 2 1 6 6 2 20 1 1 3 1 6 6 2 20 1 1 85-0048 85-0049 33-5100 33-2100 See Parts Dwg 85-0050 90-0108 See Pump Manual Table 1.7 - Consumables 1.2.2 TEST EQUIPMENT The following table lists the basic equipment recommended to perform most types of verification testing and system maintenance. The salinity meter allows the operator to perform routine sampling of the RO membranes: Description VMT Part No. Kit, pH Test, 0-14 (10 strips): Meter, Handheld Analog, 0-5000 ppm: 10X Range Extender for Analog Meter: Alternate Digital Handheld meter, 0-1000 ppm: Solution, Calibration, 300 ppm: Solution, Calibration, 30,000 ppm: 90-0135 40-5000 40-5001 99-1990 90-1300 90-1301 Table 1.8 - Recommended Test Equipment PW-3000 to PW-20000 Manual 4 Last Revised 01/12 2.0 PREPARATION FOR USE, INSTALLATION AND INITIAL ADJUSTMENT 2.1 UNPACKING AND HANDLING Remove unit from shipping crate and inspect for shipping damage. CAUTION Do not allow unit or any components to be exposed to freezing temperatures. If it is anticipated that the unit may be exposed to freezing temperature, please contact VMT in advance for technical assistance. 2.2 LOCATION The RO unit should be installed in a dry, sheltered location protected from direct weather. Some type of drainage should be provided beneath the RO unit to allow standing water to drain when performing maintenance or repair (see system diagram in Section 9.0 for skid size, interface locations and minimum maintenance envelope requirements). For units without a pressurized feed, it is recommended that the RO unit be mounted in a location below the vessel's waterline. This will ensure a flooded suction to the unit at all times. It is important that the product water line is connected to the top of the storage tank with an air gap to prevent chlorinated water from siphoning back into the watermaker. Reject discharge line overboard and above water line. Raw water inlet, 1½” through hull with sea cock, as low as possible and towards the aft of the boat, forward of the drive. Figure 2.0 - Recommended Installation (Below Water Line without Pressurized Feed) PW-3000 to PW-20000 Manual 5 Last Revised 01/12 If it is not possible to mount the watermaker below the water line, the boost pump can lift to a maximum height of 15 feet (5 feet for 50 Hz units) above the water line with the boost pump removed from the frame and installed below the RO frame near the through hull. A check valve might be required in the suction line to maintain adequate system priming. Locating the system any more than 15 feet above the water line requires installation of external pumps to maintain a pressurized feed. It is important that the product water line is connected to the top of the storage tank to prevent chlorinated water from siphoning back into the watermaker. Reject discharge line overboard and above water line. Boost pump below water line with flooded suction. Raw water inlet, 1-1/2” through hull with sea cock, low as possible and towards the Aft of the vessel, forward of the drive. Figure 2.1 - Proper Installation (Above Water Line) Since every installation is unique, the mounting instructions are provided for guidance only. It is recommended that you use your own discretion as to the exact method of mounting and placement of any mounting bolts. 1) Place the RO unit in an appropriate location and use existing holes or drill new holes for a minimum of four point mounting by studs or bolts. Mount the RO unit securely making sure that the base of the unit is continuously supported. 2) Make the following plumbing connections to the RO unit's piping interfaces (refer to Section 9.0 for the exact piping interface locations): a) Connect the raw water supply (1½" flange connection inlet) to a clean seawater source. CAUTION PW-3000 to PW-20000 Manual 6 Last Revised 01/12 Inlet and discharge interconnecting lines should be constructed of a NONFERROUS material. Examples of some suitable materials are PVC, copper-nickel, 316 stainless steel pipe or a reinforced non-collapsing hose. Ferrous piping produces rust that will irreversibly foul the membrane and void the RO unit warranty. NOTE Avoid connecting the inlet piping to any water line that services any other piece of equipment. Air could be drawn through the RO unit causing damage to the RO unit's pumps. b) Connect the reject discharge 1½" flanged connection to an unobstructed line connected to an appropriate drain. If the reject is discharged overboard, the discharge port should be above the waterline. On above waterline installations where the reject goes down more that 10 feet to its outlet, install a vacuum breaker or vent to prevent any negative pressure or vacuum situation at shutdown. CAUTION The use of galvanized steel for product piping should be avoided as small amounts of rust may form that can be drawn back into the RO when the system is off. c) Connect the product water discharge 1" flanged connection to an unobstructed line that is connected to the TOP of the product water storage tank. If the storage tank water is chlorinated, a check valve or air gap should be installed in the product line as a precaution to prevent chlorine damage of the RO membranes. The air gap is often accomplished by teeing the product connection to a tank vent or tank fill line of suitable size. d) Connect the flush water inlet to the pressurized fresh water system on the vessel. Do not exceed 50 psi pressure. CAUTION Exposing the membranes to chlorinated water may cause irreversible damage and will void the RO unit warranty, so use the carbon flush filter supplied. 3) Connect the following RO unit's electrical interfaces: NOTE PW-3000 to PW-20000 Manual 7 Last Revised 01/12 Strictly observe all applicable electrical codes and regulations governing the installation and wiring of electrical equipment. Typical codes specify the type and size of conduit, wire diameter and class of wire insulation depending upon the amperage and environment. The power supply should always be of a greater service rating than the requirements of the RO unit. This will assure proper voltage even if power supply voltage is slightly less than required. Never connect the RO unit to a line that services another electrical device. The RO unit should have its own dedicated power supply and breaker. WARNING Disconnect electrical power to RO unit and the power source before connecting to RO unit interface. Failure to do so can cause serious injury or death to personnel. a) Connect the correct voltage/power supply to the three-phase or single phase supply point in the Motor Starter Box. Correct high pressure pump rotation is clockwise when viewing the motor fan (or counter-clockwise when viewing from the shaft and pulley end. Correct rotation for the low pressure boost pump is clockwise when viewing the motor fan. IMPORTANT NOTE Three phase power supplies will spin the motors and pumps either rotation direction, depending on the phase sequence of the three hot power legs. It is very important not to rotate the low pressure pump backwards. Even “bumping” the motor for one second can cause significant damage. The high pressure pump will not be damaged from running backwards. Either use a phase meter to determine the rotation, or use the high pressure pump only to check rotation and adjust the input power legs accordingly prior to checking the low pressure pump. If the low pressure pump is inadvertently “bumped” backwards, open the pump and check the impellor is secured on the motor shaft and spins freely prior to starting it again. b) Connect a suitable ground to the RO unit skid (as determined by the specifics of your installation). PW-3000 to PW-20000 Manual 8 Last Revised 01/12 3.0 GENERAL THEORY OF OPERATION 3.1 REVERSE OSMOSIS THEORY Reverse osmosis, like many other practical scientific methods, has been developed from processes first observed in nature. Osmosis is a naturally occurring phenomenon in which a semi-permeable membrane separates a pure and a concentrated solution (a semi-permeable membrane is defined as one that preferentially passes a particular substance). Every fluid has an inherent potential that is directly related to the type and amount of solids in solution. This potential, referred to as osmotic pressure, increases in proportion to relative concentration of a solution. A concentrated solution, therefore, has an osmotic pressure that is higher than that of a pure solution. In an osmotic system, the less concentrated solution will attempt to equalize the concentrations of both solutions by migrating across the semi-permeable membrane. When enough pure solution migrates across the membrane such that the inherent potential difference between the solutions is no longer higher than the osmotic pressure of the membrane, the purer solution will stop flowing. If the pressure on the concentrated solution is increased to above the osmotic pressure, fluid flow will be reversed. This condition, called Reverse Osmosis, can be established by artificially pressurizing the more concentrated solution using a high pressure pump. In this type of system, the concentrated solution (normally referred to as feedwater) will become more concentrated as pure water flows out of solution and across the membrane to the permeate side. Discounting the effects of feedwater temperature and salinity, the operating pressure normally required to produce significant amounts of pure water is at least twice the osmotic pressure of the membrane being used. ATMOSPHERIC PRESSURE (14.7 PSI) PURE SOLUTION HIGH PRESSURE (800 PSI) SALINE SOLUTION PURE SOLUTION SALINE SOLUTION SEMI-PERMEABLE MEMBRANE OSMOSIS REVERSE OSMOSIS Figure 3.0 - Simple (Reverse) Osmotic System PW-3000 to PW-20000 Manual 9 Last Revised 01/12 3.2 APPLICATION OF REVERSE OSMOSIS Seawater contains many kinds of solids dissolved in solution. The most prevalent is common table salt (sodium chloride). Other minerals that may be present in solution are substances that usually contain various compounds of calcium and sulfate. The sum of all of the solids dissolved in a particular sample of water is referred to as Total Dissolved Solids or TDS. Seawater normally averages 32,000 to 35,000 ppm (parts per million) TDS although variations of 5000 ppm are common in various parts of the world. The fundamental goal any desalination process is a significant reduction in the amount of dissolved solids in water. In a Reverse Osmosis desalination system, most of the dissolved solids do not pass through the membrane but are instead carried along the membrane surface. This rejected water, referred to as brine, becomes increasingly more concentrated as it flows along the surface of the membranes and is eventually piped to drain. The product water that flows through the membrane is referred to as permeate. The percentage of feedwater converted to permeate is called the recovery rate and is normally somewhere between 20% and 30%. For example, a unit with a 29% recovery rate will produce 29 gallons of permeate for every 100 gallons of feedwater with the remaining 71 gallons discharged to waste as brine. A higher than optimal recovery rate (which can be obtained by increasing the back pressure on the unit above the recommended range) results in greatly increased membrane fouling rates and a significant decrease in the operational life of the membranes. RAW WATER INLET FILTRATION SYSTEM FEEDWATER HIGH PRESSURE PUMPING SYSTEM FEEDWATER CLEANING SYSTEM BRINE REJECT DISCHARGE MEMBRANE ARRAY PERMEATE PERMEATE > 500PPM PRODUCT DISCHARGE PRODUCT MONITORING SYSTEM PERMEATE < 500PPM Figure 3.1 - Simplified Schematic of an RO System PW-3000 to PW-20000 Manual 10 Last Revised 01/12 It should be noted that no system is capable of removing all of the dissolved solids from seawater. The system is actually designed to reject approximately 99% of the TDS or, in other words, to allow 1% of the 35,000 ppm TDS in the seawater to pass into the product water. This yields water of less than 500 ppm, the recommended TDS for drinking water. A system such as this is said to have a salt passage percentage of 1% or a salt rejection of 99%. 3.3 PRODUCT WATER QUALITY STANDARDS This RO unit will produce permeate (product water) with a quality of < 500 ppm TDS and in accordance with World Health Organization (WHO) standards for drinking water. General specifications for acceptable drinking water quality are as follows: Constituent Ion/Molecule Maximum Limits (ppm) Nitrate Fluorine 10 .1 Sulfate 100 Magnesium Calcium Calcium Carbonate Iron Manganese Total Dissolved Solids Turbidity Oil Detergents (anionic) Phenols Bacteria - E Coli (per 100 ml) 30 75 100 .1 .05 500 5 .1 .2 .001 0 Table 3.0 - Drinking Water Standards 3.4 FACTORS AFFECTING PERMEATE PRODUCTION 3.4.1 VARIATIONS IN TEMPERATURE, PRESSURE AND SALINITY The following table illustrates how the quality and quantity of permeate produced in by RO system is affected by changes in temperature, salinity and pressure: PW-3000 to PW-20000 Manual 11 Last Revised 01/12 Permeate With constant.... Salinity and Pressure Temperature and Pressure Temperature and Salinity And increasing.... Temperature Salinity Pressure TDS Capacity Increases Increases Decreases Increases Decreases Increases Table 3.1 - Factors Affecting Permeate Quality NOTE If feedwater salt concentration decreases, the product water flow rate should not be allowed to increase more than 20% above rated flow. Reject pressure will need to be lowered to maintain rated flow in brackish water or fresh water applications. The RO system can be adjusted to maintain a constant permeate output when feedwater salinity is below nominal (near river mouths or in estuaries). The operator can do this by controlling system pressure manually via the back pressure regulator valve, V3, located in the system brine piping. For long pump life and low membrane fouling, VMT recommends that 800 psi is not exceeded except in situations of extreme low temperature feed water. CAUTION Operating the unit at more than 120% of rated capacity in low salinity water can damage the membranes and will void the RO unit warranty. 3.4.2 TEMPERATURE CORRECTION FACTOR As previously described, the output capacity of any RO unit is highly dependent on feedwater temperature. In order to quantify this relationship, theoretical data has been utilized to develop Temperature Correction Factors (TCF) to compensate measured flowrate to calculated flowrate at 25°C/77°F. This allows the operator to establish the baseline flow for a given temperature, allowing more accurate troubleshooting. The procedure for calculating the temperature compensated flow is as follows: 1) 2) Measure raw water temperature and determine the corresponding correction factor from Table 3.2 based on the measured temperature. Note the actual product flow rate at the Product Flow meter. Multiply the actual product flow meter flow rate by the correction factor from Table 3.2 to give theoretical temperature compensated flow under standard conditions (25°C). PW-3000 to PW-20000 Manual 12 Last Revised 01/12 Example: Raw water temp: TCF: Actual product flow: Calculation: Temperature Corrected flow: (167 gph is the normal flow for a PW4000) °C 15°C 1.47 113.5 (gph) 113.5 x 1.47 = 167 (gph) 167 (gph) Factor °C Factor °F Factor °F Factor 1 3.64 26 0.97 34 3.47 84 0.88 2 3.23 26 0.94 36 3.18 86 0.82 3 3.03 28 0.91 38 3.18 88 0.79 4 2.78 29 0.88 40 2.68 90 0.79 5 2.58 30 0.85 42 2.47 92 0.77 6 2.38 31 0.83 44 2.29 94 0.75 7 2.22 32 0.80 46 2.14 96 0.73 8 2.11 33 0.77 48 2.01 98 0.70 9 2.00 34 0.75 50 1.88 100 0.68 10 1.89 35 0.73 52 1.77 102 0.65 11 1.78 36 0.71 54 1.68 104 0.63 12 1.68 37 0.69 56 1.59 106 0.61 13 1.61 38 0.67 58 1.51 108 0.59 14 1.54 39 0.65 60 1.44 110 0.57 15 1.47 40 0.63 62 1.36 112 0.55 16 1.39 41 0.61 64 1.30 114 0.53 17 1.34 42 0.60 66 1.24 116 0.51 18 1.29 43 0.58 68 1.17 118 0.49 19 1.24 44 0.56 70 1.12 120 0.47 20 1.19 45 0.54 72 1.08 122 0.45 21 1.15 46 0.53 74 1.05 22 1.11 47 0.51 76 1.02 23 1.08 48 0.49 78 1.00 24 1.04 49 0.47 80 0.93 25 1.00 50 0.46 82 0.90 Table 3.2 - Temperature Correction Factors (TCF) PW-3000 to PW-20000 Manual 13 Last Revised 01/12 3.5 OPERATIONAL DESCRIPTION 3.5.1 FILTRATION SYSTEM Seawater supplied to the intake of the Village Marine RO desalination unit will initially flow through the raw water strainer, ST1, which removes large particulate matter. Once through the strainer, the raw water is supplied to the low pressure boost pump, P1, which raises the pressure of the water in order to provide enough positive feed pressure to flow through the filtration system and into the suction of the high pressure pump. For units equipped with a (optional) Media Filtration System: When a unit operates in areas where the raw water source of high turbidity or organic materials, VMT recommends installing a media filtration system (IMF). The media pump and filter, is installed upstream of the watermaker and will remove particles as small as 25 microns in diameter. The filtration media is comprised a multiple layers of specific materials that are specifically designed to remove suspended particulate matter from the raw water stream. The benefit is to significantly reduce the cleaning and replacement frequency for the micron filters. When the media filter is fully loaded (indicated by high filter differential pressure), the operator initiates a backwash cleaning cycle designed to flush trapped particulate matter out of the filter and into the system drain. Please see the IMF manual or IMF bulletin for further details. The raw water next passes through the micron filter array, F1 & F2, which is designed to reduce raw water turbidity to a nominal 5 microns in diameter. The micron filter array consists of one 20 micron filter cartridge and one 5 micron filter cartridge. Each filter housing contains one (1) filter element with an effective filtering area of 100 ft2 and is equipped with an integral air/oil separator bleed. Bleed is continuously discharged to the reject header and overboard. The discharge pressure from the filter housings is monitored by a pressure gauge, PG1, and pressure switch, PS1, that allow the operator to determine when the filter elements require cleaning or replacement. 3.5.2 REVERSE OSMOSIS SYSTEM The clean and filtered raw water (now referred to as feedwater) is supplied to the inlet of the high pressure pump, P2. This pump raises feedwater pressure to 800 psi, the nominal pressure required for optimal system recovery. The pressurized feedwater PW-3000 to PW-20000 Manual 14 Last Revised 01/12 then flows directly into the membrane array. The membrane array is an arrangement of fiberglass pressure vessels each containing a RO membrane element. The pressurized feedwater flows along the membrane elements where reverse osmosis takes place (see Section 3.1). The feedwater flow is divided into two streams - the high purity product stream (referred to as the permeate) and the increasingly concentrated reject stream (referred to as the brine or reject). After exiting the membrane array, the brine (which contains higher concentrations of salts) flows through the back pressure regulator valve, V3. This manually adjustable valve is used to control the back pressure through the membrane array. After passing through the back pressure regulator, the brine flows through the reject flow meter, FM1 and exits the RO unit. 3.5.3 PRODUCT MONITORING SYSTEM The product water stream (or permeate) flows past a conductivity sensor, which provides a signal to the water quality monitor. Depending on the concentration of total of dissolved solids (TDS) in the permeate stream, the following occurs: If permeate TDS is > 500 ppm, indicating poor quality water, a signal is sent to close the 2-way product diversion valve, V6. This causes permeate system pressure to rise until it equals the activation set point of the permeate relief valve, V7. With the relief valve open, the poor quality water is diverted to the reject stream and away from your storage tanks. A product pressure gauge, PG3 is supplied to enable accurate adjustment of the product relief valve to about 40 psi in most installations. If the permeate has < 500 ppm TDS, indicating good quality (drinking) water, a signal is sent to open the product diversion valve. The relief valve then shuts allowing the permeate to pass through the product flow meter, FM2 and then on to the potable water storage tank(s). 3.5.4 MEMBRANE CLEANING SYSTEM This RO unit includes a membrane cleaning system which provides a means for removing performance degrading organic foulants and scale deposits from the RO membranes (occurs approximately every 30 – 90 days during constant use). By using the filter housings as cleaning solution tanks, the pumps, a cleaning valve V5, and a high pressure bypass valve V4, the membranes can be chemically cleaned in place. Complete information and cleaning procedures can be found in Section 5.5. PW-3000 to PW-20000 Manual 15 Last Revised 01/12 3.6 WATER QUALITY MONITOR The Water Quality Monitor (MON) monitors and displays permeate salinity, temperature and accumulated unit operating hours. It also provides operational mode control of the system product valve. 3.6.1 PUSHBUTTONS Temperature – allows the operator to display permeate temperature (as opposed to the normal permeate salinity display). By changing a jumper located on the back of the monitor, the temperature can be displayed in ºF or ºC. Salinity Alarm Set Point – allows the operator to display and vary (via a control knob located on the back of the monitor) the salinity alarm set point. Mode – allows the operator to bypass the normal automatic operation and manually close the product valve (called DUMP mode, used, for instance, during cleaning). 3.6.2 DISPLAYS AND LIGHTS Normal Operation – a green light is illuminated when the product valve is energized and permeate is flowing through the product valve. Dump/Cleaning – a yellow light is illuminated when the product valve is de-energized and the product valve is closed. Salinity Alarm – a red, flashing light indicates that permeate quality is above the salinity set point. 3.7 CONTROLS AND INSTRUMENTATION The following table provides a brief description of each individual component along with an explanation of its function. It is intended as a supplement to the more detailed information contained in Section 9.0 – System/Equipment Drawings and Diagrams. Call Out Description Function F1 20 Micron Pre-filter Filters particles > 20 microns in diameter. F2 5 Micron Pre-filter Filters particles > 5 microns in diameter. PW-3000 to PW-20000 Manual 16 Last Revised 01/12 FM1 Reject Water Flow Meter Indicates the amount of reject water discharged from the RO unit. FM2 Product Water Flow Meter Indicates the amount of permeate produced by the RO unit. MON Water Quality Monitor See Section 3.6 for detailed description. MS1 LP Pump Magnetic Starter Provides ON/OFF control of LP pump. MS2 HP Pump Magnetic Starter Provides ON/OFF control of HP pump. P1 Low Pressure (LP) Boost Pump Pressurizes raw water to supply the cartridge filters, F1 and F2. P2 High Pressure (HP) Pump Pressurizes feed water to supply the membrane array at proper (high) pressure. PG1 Pre-Filter Pressure Gauge Indicates cartridge filter inlet and discharge pressure. PG2 High Pressure Gauge Indicates membrane array discharge (brine side) pressure. PG3 Product Water Pressure Indicates membrane array (permeate side) discharge pressure. PS1 Low Pressure Switch Will shut down pumps if the pressure is below setpoint. SR1 Product Conductivity Sensor Conductivity probe provides signal to water monitor (MON). ST1 Raw Water Strainer Removes large particulate matter from the raw water stream to prevent system fouling. SW1 LP Boost Pump Start Pushbutton Allows operator to START the LP boost pump. SW2 LP Boost Pump Stop Pushbutton Allows operator to STOP the LP boost pump. SW3 HP Pump Start Pushbutton Allows operator to START the HP pump. SW4 HP Pump Stop Pushbutton Allows operator to STOP the HP pump. V1 Filter Gauge Selector Valve Allows operator to select and read filter array inlet or discharge pressure on the gauge. PW-3000 to PW-20000 Manual 17 Last Revised 01/12 V3 HP Regulating Valve Maintains and controls system back pressure. V4 HP Bypass Valve Allows operator to bypass the HP Regulating Valve during start-up, shutdown and cleaning. V5 Cleaning Valve Used to re-circulate the brine during cleaning and preservation procedures. V6 Product Diversion Valve Based on its salinity, directs permeate to either the potable water tank(s) or to drain. V7 Product Water Relief Valve Discharges product water when Product Diversion Valve is closed. Typical setting 40 psi. V8 Filter Bleed Check Valve Prevents reject flow from back flowing through the filter housings into the feed water stream. V9 Trim Valve Adjust to get quiet operation at regulator V10 Flush Valve 3-way feedwater valve used to flush system Table 3.3 - Instrumentation and Controls PW-3000 to PW-20000 Manual 18 Last Revised 01/12 4.0 OPERATION 4.1 START-UP PROCEDURE NOTE The HP Pump should rotate in the counter-clockwise direction (when facing the protruding end of the shaft). 1) Check the HP pump oil level by observing sight gauge located on the pump. 2) On initial start up, check the drive belt tension by removing the belt guard. See Section 5.4 for detailed procedure. WARNING De-energize (lock out or disconnect) the electrical supply to RO unit before attempting to check or adjust drive belt tension. Serious injury to personnel can result if the RO unit is started while checking drive belt tension. 3) Open the raw saltwater supply to the unit. On pressurized feed systems, water may now be flowing through the watermaker. 4) On initial start up, check the tightness of all lines and fittings. 5) If equipped with an IMF or other media filter, backwash and rinse media filter as required for initial startup or after long periods of standby. With fresh fill of media, multiple backwash and rinse sequences will be required. See IMF manual. 6) Place the RO unit's valves and switches in the positions shown in Table 4.0. ID Description Position V3 V4 V5 V10 HP Regulating Valve High Pressure Bypass Valve Cleaning Valve Flush Valve Factory set to 800 psi Cleaning (open) Normal Flow Seawater Feed Table 4.0 - Valve/Switch Line Up - Initial Start-up PW-3000 to PW-20000 Manual 19 Last Revised 01/12 CAUTION Failure to open the High Pressure Bypass Valve (which is required to bleed any entrapped air) can result in hydraulic shock to the system. 6) Verify electrical power is supplied to the RO unit. CAUTION The low pressure (LP) boost pump should not be started if the feed system pressure as read on the inlet side of the Pre-filter Pressure gauge is more than 40 psi. Operate with only the HP pump if feed pressure is in excess of 40 psi to avoid overpressure to the feed water system components. 7) Start the pumps in turn, feed pump (if equipped), boost pump and then the HP pump. At least 10 psi must be indicated on the discharge side of the Pre-filter Pressure gauge. 8) Inspect all plumbing connections in the unit for leakage. Temperature variations during shipment may cause plumbing connections to seep when initially started on-site. Secure the unit and repair any leaks prior to proceeding. Once the leaks have been repaired, open the raw water source and re-start the unit. 9) When flow through the reject discharge flow meter appears to be free of air bubbles, place the High Pressure Bypass Valve, V4, in the closed position by slowly turning the handle in the clockwise direction. NOTE When the High Pressure Bypass Valve is closed, the salinity of the initial permeate produced may be temporarily high and will probably be enough to temporarily energize the salinity alarm. 10) Observe the system pressure on the discharge side of the RO Membrane Array Pressure gauge. For seawater applications, indicated pressure should be preset to 800 psi. If the indication is other than 800 psi, adjust the nut on top of the back pressure regulator valve, V3, using a wrench until the discharge side of the RO Membrane Array Pressure gauge indicates 800 psi. In conjunction with adjustment of the regulator, adjust the trim valve, V9, to find the quietest operating point. PW-3000 to PW-20000 Manual 20 Last Revised 01/12 WARNING Pressure, as indicated on the inlet side of the RO Membrane Array gauge, should never exceed 1000 psi. NOTE The system pressure required to produce equivalent amounts of permeate is lower for fresh water sources (approximately 200 psi) and brackish water sources (approximately 400 psi) than for seawater applications. Reduce system pressure as necessary to maintain system output at no more than 120% of rated capacity. 11) Normally, during start-up using seawater, the Salinity alarm (red) will remain lit for approximately 2 minutes. When the product water quality drops below 500 ppm TDS, the green lamp will light. The water quality monitor will then open the product diversion valve, which will direct the product water to the product water flow meter. If the green lamp does not light within 10 minutes, sample the product water from the pressure vessel sample valves and confirm with a handheld salinity meter. 12) Observe the Product Flow meter. This flow meter indicates, in gallons per minute (gpm), the product water flow rate. Record the product flow after 5 hours of operation (use the sample log sheet provided in Figure 5.1). This indication will provide the baseline used to determine RO membrane cleaning requirements. Normally, a drop of 10-15% in the temperature corrected product water production rate indicates the need for RO membrane cleaning (see Section 3.4 for a more detailed information concerning variations in product flow). 13) Observe the Reject Flow meter. This flow meter indicates, in gallons per minute (gpm) the reject flow rate from the RO array. Record the reject flow after the first 5 hours of operation (use the sample log sheet provided in Figure 5.1). 4.2 SHUTDOWN PROCEDURES 4.2.1 SHUTDOWN PROCEDURE (SHORT TERM) 1) Release the pressure from the system by turning the High Pressure Bypass Valve, V4, counter-clockwise to the Cleaning (open) position. 2) Secure the HP pump by pressing the red HP PUMP STOP button located on the front panel. PW-3000 to PW-20000 Manual 21 Last Revised 01/12 3) If required, secure the LP boost pump by pressing the red LP PUMP STOP button located on the front panel. 4) Secure the feedwater system by closing a feedwater valve upstream of the water maker or by turning the Flush Valve, V10, to the midway position. If the anticipated shutdown period will be 24 hours or more, flush the system as per Section 4.3 - Flushing Procedure. 4.2.2 SHUTDOWN PROCEDURE (EXTENDED) Since bacteria and biologic growth increases significantly the longer stagnant water is in contact with the membranes, the fresh flushing procedure (Section 4.3) should be used whenever the unit will be secured for more than 1 or 2 days. Although they do not attack the membranes or other system components directly, high concentrations of biological matter can block enough of the product water channels to cause a reduction of as much as 40% of the total system capacity. CAUTION Failure to follow the extended shutdown procedure can result in irreversible fouling to the RO membranes. Bacterial contamination can be avoided by following the following procedures: Flush the RO unit with non-chlorinated fresh water for 2 - 4 minutes. Reflush the RO unit for 2 - 4 minutes every 7 days. Or, Pickle the RO unit with a preservative solution. Refresh the preservative every 3 months. Follow the preservation instructions provided in Section 5.6. 4.3 FRESH WATER FLUSH PROCEDURE Note: Fresh flushing water should pass through the carbon flush filter supplied on the PW unit so it is non-chlorinated. Exposing the membranes to chlorinated water may cause irreversible membrane damage. The carbon filter element should be changed once per year or after 50 flushes. It is designed to remove normal concentrations of free chlorine (0.5 to 1.0 ppm). Do not flush with shock-chlorinated water. Once the watermaker is shut off and isolated, the flush procedure is: 1) Make sure the HP Bypass Valve, V4, is in the counterclockwise (open) position. 2) Turn the Flush Valve, V10, to the flush position to bring freshwater to the feed of the watermaker. 3) Start the LP boost pump. PW-3000 to PW-20000 Manual 22 Last Revised 01/12 4) Once you have observed fresh water flow through Reject Flow meter, run the system for an additional 2 to 4 minutes. For greater flushing flow, start the HP pump as well. 5) Secure the pumps. Return the Flush Valve, V10, to midway position, isolating the watermaker. 5.0 MAINTENANCE INSTRUCTIONS 5.1 GENERAL Clean and inspect strainer basket Labor Hours (approximate) As Required Annually Semi-Annually Quarterly Monthly Weekly Daily The service life of most of the system equipment is directly related to the raw water inlet conditions. Improper maintenance will also significantly reduce the life expectancy of the major unit components (such as the membranes, filters and pumps) as well as the reliability of the unit as a whole. Under normal conditions, and with proper maintenance, a reverse osmosis membrane (which is the major consumable item) should have an effective service life somewhere between 1 to 2 years heavy use. 0.3 Clean and inspect micron filter(s) 0.5 Replace filter(s) 0.5 Clean membranes 4.0 Replace membranes 2.0 Inspect pump drive belt 1.0 Check pump oil level 0.1 Change pump oil(1) 1.0 Lubricate pump motors Backflush media filter(2) (1) (2) 1.0 0.3 After first 50 hours and every 500 hours thereafter For units equipped with the optional media filtration system. Figure 5.0 - Maintenance Task Chart PW-3000 to PW-20000 Manual 23 Last Revised 01/12 5.2 RAW WATER STRAINER INSPECTION 1) Isolate the raw water supply and open the strainer housing. 2) Remove the screen from the strainer bowl. Remove any debris from screen and inspect the screen closely for damage. Replace as required. 3) Check the sealing gasket or o-ring is in good condition, and keeping the seal in place install the screen and reclose the strainer housing hand tight. Start the RO and check for leaks. 5.3 FILTER ELEMENT CLEANING OR REPLACEMENT The filter elements should be replaced when the discharge side of the pressure gauge drops below 5 psi or the differential pressure is 20 psi. Each PW3000-20000 employs a filter array consisting of one (1) 20 micron, 100 ft2 filter in series with one (1) 5 micron, 100 ft2 filter. VMT filters can be washed and re-used 2-3 times provided it is not contaminated with oil or organic growth. Description Micron filter, 20 micron, 100 ft2 Micron filter, 5 micron, 100 ft2 O-ring, filter lid, 100 ft2 Filter, complete assembly, 100 ft2 Qty VMT Part # 1 1 2 2 33-2100 33-5100 30-0405 30-4353 Table 5.0 - Filter Tank Parts List. CAUTION VMT filter cartridges are specifically designed for RO applications and constructed with an oil attractive polypropylene. Use of non-approved cartridges will void the RO unit warranty. Replace the filter element(s) using the following procedure: 1) Secure the RO unit. Close the raw water supply (external) to RO unit. 2) Loosen and remove the bolts or wing-nuts that hold the filter tank lid in place. Remove the tank lid. 3) Remove the filter element. If required, first break the filter seal by rocking the filter from side to side. PW-3000 to PW-20000 Manual 24 Last Revised 01/12 4) The filter element may be cleaned by flushing it with water to remove foreign matter from the filter pleats. If the filter element appears oil-fouled or is damaged in any way, discard it and install a new element. 5) Reinstall the filter element. Be sure to install the filter element with the end marked "TOP" upwards. Ensure a proper seal by pressing the filter element down into place until it reaches the bottom and is fully seated. 6) Reinstall the filter tank lid. Tighten the bolts or nuts. 7) After the filter element has been changed, operate the RO unit and check for leaks. 5.4 DRIVE BELT INSPECTION AND REPLACEMENT Proper adjustment of the HP pump drive belt(s) is essential for proper operation of the system. The drive belt(s) should be inspected for cracking, fraying and excessive wear. Replace the belts immediately it the inspection indicates that the belt(s) are damaged. WARNING Disconnect electrical supply to RO unit before attempting to check. Serious injury to personnel can result if RO unit is started when checking drive belt. 1) Remove the mounting screws that hold the left front panel in place and remove the panel. 2) Inspect drive belt carefully for wear and proper tension. The belt should deflect approximately ½ " when a force of 6-9 lbs is applied at a point halfway between the pulleys. Remember that cogged drive belts are never kept as tight as V drive belts, and overtightened belts will create a squealing sound and can damage bearings. Adjust the base plate as required to obtain proper belt tension. 3) If the drive belt is damaged or shows any evidence of excessive wear, replace the drive belt: a) Locate the HP pump's mounting nuts on the adjustable pump base. Loosen the nuts to relax the belt tension. b) Remove the old drive belt and install new one ensuring they are properly positioned in the pulleys. PW-3000 to PW-20000 Manual 25 Last Revised 01/12 4) c) Check the drive belt tension. Adjust the base plate as required to obtain proper belt tension. (d) Be sure to properly align the pump and motor pulleys using a straight edge (at a minimum). After the belt has been sufficiently tightened and aligned, secure the HP pump by tightening the pump mounting nuts. Replace the side panel on the RO unit 5.5 RO MEMBRANE CLEANING This section is designed to guide the operator in the periodic chemical cleaning of RO membrane elements used in the PW3000-20000 unit. The basic procedure for all cleaning and preservative treatments is the same - a specific chemical solution is circulated through the system for a pre-determined length of time. Cleaning Chemical #1 Cleaning Chemical #2 Preservative Chemical #3 PW3000-6000 PW7000-20000 5 to 15 lbs (8 to 25 cups) 4 to 12 lbs (7 to 20 cups) 4 lbs (6 cups) 6 to 20 lbs (10 to 33 cups) 5 to 15 lbs (8 to 25 cups) 5 lbs (8 cups) Table 5.1 - Chemical Requirements There is a large variance in the required amount of chemical due to several factors. If RO product water is used to flush the unit prior to cleaning, the quantity required will be on the lower side. If the fresh water flush is done with dock or city water that is hard, then the required amount will rise. If the unit is significantly fouled, the quantity also rises. The key is to use only enough chemical to achieve the desired pH (pH 11 for #1 and pH 3 for #2). Extreme pH will damage the membranes, so do not exceed the recommendations. For the first cleaning of a system, use the lower quantities and measure the pH after circulating as described below. Keep adding chemical as needed until the cleaning solution maintains the desired pH level. Keep a record of the total chemical needed, so that on subsequent cleanings the correct amount can be used without the needed pH measurements and adjustments. 5.5.1 CLEANING CHEMICALS The alkaline detergent (Cleaning Chemical #1) is used to remove biological matter and grime from the surface of the RO membranes. The acid cleaner (Cleaning Chemical #2) is used to remove mineral scale deposits. CAUTION PW-3000 to PW-20000 Manual 26 Last Revised 01/12 The use of chemicals or cleaning methods other than those outlined below will void the RO unit warranty. Non-ionic surfactants for membrane cleaning or other chemicals not approved in writing by VMT will void the RO unit warranty. 5.5.2 WHEN TO CLEAN During normal operations, mineral scale and biological matter will foul the RO membranes. These deposits build up over time and will eventually cause a loss of product water output, salt rejection capability, or both. The RO elements should be cleaned whenever the temperature corrected product water output drops by 10-15% from the initial baseline established during the first hours of operation with new membranes. Prior to cleaning the membranes, verify that any reduction in product output is not the result of a corresponding variation in raw water inlet temperature or salinity. See Section 3.4 for more detailed information. NOTE Product water output of the system is dependent upon feedwater temperature, RO feed pressure and feedwater salinity. Reductions in product water output due to these factors are normal and may not indicate the need for membrane cleaning. See Section 3.4 for more detail. Use the following procedure to clean the RO elements: 1) Flush the watermaker per section 4.3, so it is filled with fresh water, not seawater. 2) Dissolve the appropriate amount of Cleaning Chemical #1 (see Table 5.1) in a pail of fresh water. Make sure that that the chemical is completely dissolved (use warm water if necessary). NOTE Cleaning Chemical #1 is an alkaline detergent. Use appropriate safety precautions. 3) Verify the High Pressure Bypass Valve, V4, is in its Cleaning (open) position. 4) Place the Cleaning Valve, V5, in the Cleaning Flow position. 5) Remove the filter elements from both filter tanks and replace the 5 micron filter with a dedicated cleaning filter (5 micron). A dedicated cleaning filter should be used to prevent fouling of the operational filters. When the cleaning process is PW-3000 to PW-20000 Manual 27 Last Revised 01/12 complete the dedicated cleaning filter can be cleaned and set aside until the next membrane cleaning is required. Pour the chemical solution into the empty 20 micron filter housing and the 5 micron housing (drain water first as necessary) and reinstall the filter housing lids. 6) Start the LP boost pump. 7) Start the HP pump. At least 0 psi must be indicated on the discharge side of the Pre-filter Pressure gauge. Temporarily cracking open the flush valve will boost the cleaning loop pressure if required. a) After the chemical solution has circulated for 3 minutes, secure the pumps, release any loop pressure by momentarily moving the cleaning valve, V5, to the normal position and back to cleaning. Take a sample from the cleaning loop from the filter tank drain valve or by opening the tank lid. Measure the pH of the sample using a pH meter or test kit VMT# 90-0135. b) If the pH < 11 then add 10% more of the cleaning solution. Repeat this step until the pH = 11. c) Once a pH = 11 can be maintained start the LP and HP pumps and allow the cleaning solution to circulate for an additional 30-40 minutes. 8) Secure the HP and LP pumps. 9) Place the Cleaning valve, V5, in the Normal Flow position. 10) Open raw water supply to the RO unit external to the unit and make sure the Flushing Valve, V10, is turned to the Normal, seawater position. 11) Start the LP boost pump and HP pump. Allow both pumps to run for 5 minutes to flush the chemical solution from the unit. 12) Secure the HP pump and the LP boost pump. 13) Flush the watermaker, so it is filled with fresh water, not seawater. 14) Dissolve the appropriate amount of Cleaning Chemical #2 (see Table 5.1) in a pail of fresh water. Make sure that that the chemical is completely dissolved (use warm water if necessary). NOTE Cleaning Chemical #2 is an acid used for mineral scale removal. Use appropriate safety precautions when handling. PW-3000 to PW-20000 Manual 28 Last Revised 01/12 15) Place the Cleaning Valve, V5, in the Cleaning Flow position. 16) Remove the lid from the 20 micron filter tank, pour the cleaning solution into the tank (drain water first as necessary) and replace the lid. 17) Start the LP boost pump. 18) Start the HP pump. At least 0 psi must be indicated on the discharge side of the Pre-filter Pressure gauge, PG1. Temporarily cracking open the flush valve will boost the cleaning loop pressure if required. a) After the chemical solution has circulated for 3 minutes, secure the boost pump, release any loop pressure by momentarily moving the cleaning valve, V5, to the normal position and back to cleaning. Take a sample from the cleaning loop from the filter tank drain valve or by opening the tank lid. Measure the pH of the sample using test kit VMT# 90-0135. b) If the pH > 3 add 10% more of the cleaning solution. Repeat this step until the pH < 3. c) Once a pH of less then 3 can be maintained replace the filter tank lid, start the LP and HP pumps and allow the cleaning solution to circulate for an additional 30-40 minutes. 19) Secure the HP and LP pumps. 20) Place the Cleaning valve in the Normal Flow position. 21) Open raw water supply to the RO unit (external to the unit). 22) Start the LP boost pump and HP pump. Allow both pumps to run for 5 minutes to flush the chemical solution from the unit. 23) Secure the HP pump and the LP boost pump. 24) Close raw water supply to RO unit (external to the unit). 25) Remove, set aside and retain the cleaning filter for future use. Replace the operational 20 and 5 micron filter elements in the filter housings and replace both housing lids. 26) Place the unit back into service using the procedure contained in Section 4.1 Start-up Procedure. PW-3000 to PW-20000 Manual 29 Last Revised 01/12 5.6 RO ELEMENT PRESERVATION / PICKLING During periods when the RO unit is to be shut down for an extended period of time, it is necessary to circulate a preservative solution through the membranes to prevent the growth of biological organisms. Use the following procedure to preserve the RO elements: 1) Secure the raw water supply to RO unit (external to the unit). 2) Dissolve the appropriate amount of Cleaning Chemical #3 (see Table 5.1) in a pail of non-chlorinated product water. Make sure that that the chemical is completely dissolved (use warm water if necessary). NOTE Preservative Chemical #3 is a food-grade preservative. See warning label on package and observe all safety precautions on label. 3) Flush the watermaker, so it is filled with fresh water, not seawater (see section 4.3) 4) Make sure the High Pressure Bypass Valve is in the Cleaning (open) position. 5) Place the Cleaning Valve in the Cleaning Flow position. 6) Remove one of the filter housing lids (draining water as necessary) and pour in the preservative solution prepared in step #1. Reinstall the lid. Leave the filters elements in place. 7) Start the LP boost pump. 8) Start the HP pump. At least 0 psi must be indicated on the discharge side of the Pre-filter Pressure gauge. Temporarily cracking open the flush valve will boost the cleaning loop pressure if required. Allow the chemical solution to circulate for 10 minutes. 9) Secure the LP and HP pumps. 10) The system is now properly conditioned and may be left idle for an extended period of time. This preservation procedure (including the fresh flush to remove old pickling solution) should be repeated at least every 3 months during the shutdown. In colder climates the interval between preservation cycles may be extended to 6 months. PW-3000 to PW-20000 Manual 30 Last Revised 01/12 5.7 RESTARTING UNIT AFTER PRESERVATION Restart unit using the procedure contained in Section 4.1 - Start-up Procedure. Use the MODE button on the Water Quality Monitor to light the DUMP lamp for the first 15 minutes of production to make sure all preservative is flushed clear prior to filling the fresh water tanks. 5.8 HIGH PRESSURE PUMP OIL CHANGE See equipment literature in back of this manual for instructions for changing the oil on your particular pump. 5.9 MOTOR LUBRICATION Locate the grease fittings on the electric motor. Use a clean cloth to wipe this fitting clean. If applicable, remove any caps. Free the drain hole of any hard grease (use a piece of wire if necessary). Add 2-3 strokes of grease using a low pressure grease gun (see Table 5.2 for grease type). Location Type High pressure pump oil VMT pump oil #85-0050 High pressure pump motor grease Shell Oil Dolium R Texaco Premium RB Exxon Mobil PolyrexEM Chevron SRI O-rings & gaskets Glycerin or silicone lubricant Table 5.2 - Lubrication Requirements 5.10 INSPECTION LOG Figure 5.2 depicts a sample operation log for the PW3000-20000 RO unit. The operator of the RO unit should establish a program for entering the required data on a regular basis. Maintaining accurate operational data is the first, and most important, step in determining preventative maintenance requirements and reducing system downtime. The data maintained in the log must be provided by the Purchaser to make any RO element warranty claim. Figure 5.3 depicts a sample discrepancy report that may be used for reporting and tracking problems with the RO unit. PW-3000 to PW-20000 Manual 31 Last Revised 01/12 Date PG1, PG1, PG2 Product Total FM1, FM2 Water Pre-filter Pre-filter RO Array Water Operating Reject Product Temp, Inlet Discharge Discharge TDS Hours Flow Flow (°C) Pressure Pressure Pressure (ppm) Comments Figure 5.1 - Sample Operational Log PW-3000 to PW-20000 Manual 32 Last Revised 01/12 COMMENT/DISCREPANCY REPORT Village Marine Tec. RO Desalinator Model PW-3000 to PW-20000 Plant No: Log Task No: System Affected: Date: Time: Technician : Comment/Discrepancy: Corrective Action: Action Taken: Date Completed: Printed Name: Signature: Figure 5.2 - Sample Discrepancy Report PW-3000 to PW-20000 Manual 33 Last Revised 01/12 6.0 PRESSURE VESSEL AND MEMBRANES 6.1 PRESSURE VESSEL DISASSEMBLY NOTE It is not necessary to remove a pressure vessel from the RO unit for disassembly. 1) Disconnect all plumbing connections from the pressure vessel to be disassembled. 2) Remove the bolts holding each end plug in place with an Allen wrench. Place a mark on each end plug removed and its corresponding collar. This will ensure proper orientation during assembly. JACKING SCREW HOLES Figure 6.0 - Pressure Vessel End Plug 3) Locate the jacking screws on opposite sides of the end cap (see Figure 6.0). Screw in the correct size bolt until the end cap is pulled off. There are also prying slots on either side of the end plug to assist in removal. PW-3000 to PW-20000 Manual 34 Last Revised 01/12 Figure 6.1 - Brine Seal Orientation 4) Note which end of the pressure vessel the brine seal is visible from. This is the feed end of the pressure vessel. When reinstalling the RO membrane, the brine seal must be located at the feed end of the pressure vessel. Note the feed flow direction marked by a sticker on the outside of the pressure vessel, or trace the flow direction from the high pressure pump to confirm the high pressure flow direction. See Figure 6.1. CAUTION Never force a membrane out of a pressure vessel by applying pressure on the product water tube (center tube) as this will damage the membrane. If the membrane is difficult to remove, use a length of 2" plastic pipe to apply pressure on the protected end of membrane. 5) Whenever possible, remove the membrane from the discharge end of the pressure vessel (opposite the brine seal). This is accomplished by pushing on the membrane from the feed end of the pressure vessel until it is visible at the discharge end. Then grasp the protruding membrane and pull it out of pressure vessel. Place the membrane in a clean area. 6) Remove the product water o-rings and end plug o-ring from each end plug for inspection. The product water o-rings are internal o-rings located inside the center hole in the end cap. PW-3000 to PW-20000 Manual 35 Last Revised 01/12 6.2 1) PRESSURE VESSEL ASSEMBLY Clean all parts thoroughly. Inspect the o-rings on all fittings. Replace any parts that are damaged. NOTE Do not apply Teflon tape or other sealant to straight thread fittings such as those used on HP hose assemblies and their adapters. 2) Install the product water and end plug o-rings onto the end plugs. Lubricate the o-rings and entrances to the pressure vessel with glycerin or silicone lubricant. Locate the discharge end of pressure vessel. Install the end plug into the discharge end making sure to align the end plug holes and the mounting holes on the pressure vessel while paying particular attention to the reference mark (see Section 6.3.1, Step 2). Apply pressure to the end plug until screws can be threaded into the collars. If the end plug will not slide into the pressure vessel sufficiently, see Figure 6.2 for an installation aid. Install and hand tighten the screws. Figure 6.2 - End Plug Installation Aid 3) Lubricate the brine seal and product water tubes of RO membrane with glycerin or silicone lubricant. Do not use a petroleum based lubricant. Orient the membrane such that the end without the brine seal enters the feed end of the pressure vessel first. Slide the membrane into the pressure vessel until PW-3000 to PW-20000 Manual 36 Last Revised 01/12 resistance is felt. Continue to apply moderate pressure until the product water tube seats in the end plug. 4) Install the remaining end plug making sure to align the end plug holes with the mounting holes on the pressure vessel while paying particular attention to the reference mark (see Section 6.3.1, Step 2). Apply moderate pressure to the end plug until the screws can be threaded into the collar. If the end plug will not slide into the pressure vessel sufficiently, see Figure 6.2 for installation aid. Install and hand tighten the capscrews. 5) Make sure that antiseize compound is applied to each screw before the final tightening and torque the screws to 15 ft-lbs. 6) Reconnect all plumbing connections to pressure vessels. PW-3000 to PW-20000 Manual 37 Last Revised 01/12 7.0 PRESERVATION FOR STORAGE When the Village Marine Tec RO unit is to be shut down for an extended period of time, it is necessary take steps to prevent the growth of biological organisms and to prevent the water in the RO unit from freezing. Either continue to flush the unit with fresh water each week, or circulate a preservative solution (see section 5.6). If the unit will at any time be exposed to air temperatures of 32ºF (0ºC) or less, the membranes must be removed and the unit fully drained or the unit filled with an anti freeze solution such as propylene glycol. 8.0 TROUBLESHOOTING No amount of trouble shooting advice can replace common sense and direct plant knowledge gained through the operation and maintenance of your unit. However our experience taking tec calls suggests some points to check. 1. Always verify proper valve configuration for each of the operational modes selected. Verify valve positions for valves within the unit and also external valves are open as required. 2. Always check for positive pressure at the HP pump suction. Many problems stem from low or erratic feed water supply. Check filters, strainer, seacock, boost pumps, etc to be sure of flooded suction to the HP pump. 3. Always check for loose connections or broken wires when inspecting electrical parts. Checking for continuity and solid contact can sometimes avoid hours of troubleshooting effort. 4. Prior to cleaning or replacing membranes, verify that any reduction in product output is not the result of a corresponding variation in raw water inlet temperature or salinity. See Section 3.4 for more detailed information. Call or email us at the Village Marine Tec Service representative or distributor for assistance. PW-3000 to PW-20000 Manual 38 Last Revised 01/12 9.0 SYSTEM DRAWINGS AND DIAGRAMS AND PARTS LIST PW-3000 to PW-20000 Manual 39 Last Revised 01/12 "Use or disclosure of data contained on this sheet is subject to the restrictions on the title page of this proposal or quotation." "Use or disclosure of data contained on this sheet is subject to the restrictions on the title page of this proposal or quotation." "Use or disclosure of data contained on this sheet is subject to the restrictions on the title page of this proposal or quotation." Installation Layout PW-12000 PW-16000 PW-18000 The information contained herein is submitted as the privileged and confidential property of the Parker Hannifin Corporation pursuant to 5 U.S.C. Section 552 (b)(3) and (b)(4), the Freedom of Information Act, exemption Number 3 and Number 4. This information shall not be duplicated, used or disclosed in whole or in part outside the recipient organization without the express written consent of the Parker Hannifin Corporation." "This proposal or quotation includes data that shall not be disclosed outside the Government and shall not be duplicated, used, or disclosed in whole or in part for any purpose other than to evaluate this proposal or quotation. If, however, a contract is awarded to Parker Hannifin as a result of or in connection with the submission of this data, the Government shall have the right to duplicate, use or disclose the data to the extent provided in the resulting contract. This restriction does not limit the Government's right to use information contained in this data if it is obtained from another source without restriction. The data subject to this restriction are contained in sheet DWG 11311. 10.0 MANUFACTURER'S LITERATURE AND OPTIONS PW3000-18000 Manual 43 Last Revised 4/08 REVISION D TABLE OF CONTENTS _Toc293906105 INTRODUCTION..................................................................................................................................................................... 1 INITIAL START-UP INFORMATION...................................................................................................................................... 2 LUBRICATION..................................................................................................................................................................... 2 DISCHARGE PLUMBING ................................................................................................................................................... 2 STORAGE ........................................................................................................................................................................... 3 PREVENTIVE MAINTENANCE SCHEDULE......................................................................................................................... 4 MAINTENANCE RECORD ..................................................................................................................................................... 5 SERVICE................................................................................................................................................................................. 8 INTRODUCTION ................................................................................................................................................................. 8 TOOLS NEEDED ................................................................................................................................................................ 8 VALVE INSPECTION AND SERVICE ................................................................................................................................ 9 DETACHING THE MANIFOLD FROM THE CRANKCASE ................................................................................................ 9 SEAL REPLACEMENT ..................................................................................................................................................... 10 SERVICING THE CRANKCASE ....................................................................................................................................... 10 PLUG, OIL DRAIN, O-RING REPLACEMENT .................................................................................................................. 10 BEARING CAP O-RING/SEAL REPLACEMENT .............................................................................................................. 12 COVER, CRANKCASE O-RING REPLACEMENT ........................................................................................................... 12 CRANKSHAFT BEARING, CONNECTING ROD-PISTON SERVICE .............................................................................. 13 CRANKSHAFT REMOVAL................................................................................................................................................ 13 CRANKSHAFT INSTALLATION........................................................................................................................................ 15 SERVICING THE MANIFOLD ........................................................................................................................................... 17 ADAPTER O-RING REPLACEMENT ................................................................................................................................ 17 VALVE ASSEMBLY SERVICING ...................................................................................................................................... 17 MANIFOLD SEAL SERVICING ......................................................................................................................................... 19 ATTACHING THE MANIFOLD TO THE CRANKCASE .................................................................................................... 21 OIL CHANGE PROCEDURE ............................................................................................................................................ 21 5P50 DRAWINGS ................................................................................................................................................................. 22 LIST OF FIGURES Fig. 1: Oil Level Sight Glass Detail. ......................................................................................................................................................2 Fig. 2: Valve Assembly...........................................................................................................................................................................9 Fig. 3: Manifold Assembly Removal .....................................................................................................................................................9 Fig. 4: Plunger Assembly View ...........................................................................................................................................................10 Fig. 5: Plunger Retaining Nut Assembly ............................................................................................................................................11 Fig. 6: Seal Retainer .............................................................................................................................................................................11 Fig. 7: Bolt tightening sequence..........................................................................................................................................................13 Fig. 8 Keep parts organized.................................................................................................................................................................14 Fig. 9 Removal of the Crankshaft bearing.........................................................................................................................................15 Fig. 10 Correct Connecting Rod Pairing ............................................................................................................................................16 Fig. 11 Incorrect Connecting Rod Pairing..........................................................................................................................................16 Fig. 12: Manifold Assembly..................................................................................................................................................................17 Fig. 13: Valve Assembly.......................................................................................................................................................................18 Fig. 14: Orientation for Manifold Seal Servicing ...............................................................................................................................19 Fig. 15: Weep Ring Extraction ...........................................................................................................................................................20 Fig. 16: High-Pressure Seal Installation View..................................................................................................................................20 Fig. 17: Pump Assembly Orientation View ........................................................................................................................................21 LIST OF TABLES Table 2: Tool List For Pump Service....................................................................................................................................... 8 INTRODUCTION Aqua Pro Pumps “Titan Series” High Pressure Pumps are the product of our years of experience in the water treatment industry, and have been specifically designed and engineered for corrosive and high-pressure applications. Your new Aqua Pro Pump is made with dependable and proven technology to meet your highest demands. SPECIFICATIONS Specifications subject to change without notice. Pump type: Number of Plungers: Bore: Stroke: Oil Capacity: Oil Type: Maximum Inlet pressure: Maximum Fluid Temperature: Reciprocating Plunger 5 1.259” 1.516” 5.8 Qts. Village Marine Tec. High Pressure Pump Oil (Part No. 85-0050-quart size) Flooded (zero) to 60 PSI 120 degrees Fahrenheit (82 degrees Celsius) Model Number GPM Inlet Port Size Discharge Port Size Dimensions LxWxH Weight Shaft 5P50 20-50 1.5” MS16142-24 1” MS16142-16 18.5”x 14.5” x 9” 157 lbs. 1.625 1 5P50 Titan Series High Pressure Titanium Positive Displacement Pump INITIAL START-UP INFORMATION WARNING This is a positive displacement pump. A properly designed pressure relief safety valve must be installed in the discharge piping. Failure to install such a relief mechanism could result in personal injury or damage to the pump or system. Aqua Pro Pumps does not assume any liability or responsibility for the operation of a customer’s high-pressure system. The performance of the pump depends on the entire fluid system and will operate best with the proper installation of plumbing, operation, and maintenance of the pump. LUBRICATION It is recommended that the pump be filled with Village Marine Tec’s specially blended high pressure pump oil (PN 850050). To check the oil level, ensure the pump has stopped running. Observe oil level through the sight glass in the crankcase cover. The oil should be level with the mark on the sight glass (Fig. 1). Fig. 1: Oil Level Sight Glass Detail. NOTE Change the original oil in the pump after 50 hours of operation. After the initial oil change, the oil should be changed at 500-hour service intervals. Ensure drive belt is adequately sized for system and shaft bearings. Pulley alignment is critical to the proper operation of the system. To check for proper alignment, place a straight edge, square, or rule against the pulleys to make sure they are in line. Proper alignment of the drive pulleys will minimize crankshaft bearing and belt wear. Over-tensioning of the drive belt may cause pump crankshaft bearing damage. DISCHARGE PLUMBING CAUTION Start system with all valves open or with minimal flow restriction to avoid deadhead overpressure conditions and severe damage to the pump or system. Discharge regulating devices should be at minimum pressure setting at start-up. 2 CAUTION DO NOT RUN PUMP WITH FROZEN FLUID. DO NOT RUN PUMP DRY. STORAGE For extended storage or between uses in cold climates, drain all pumped fluids from pump and flush with antifreeze solution to prevent freezing and damage to the pump. 3 5P50 Titan Series High Pressure Titanium Positive Displacement Pump PREVENTIVE MAINTENANCE SCHEDULE The Required Maintenance Schedule specifies how often you should have your pump inspected and serviced. It is essential that your pump be serviced as scheduled to retain its high level of safety, dependability, and performance. Not performing these tasks could result in catastrophic failure. TASKS DAILY Inspect for Water Leaks/ Oil Leaks X Check Oil Level X WEEKLY Check Belt Tension X Inspect Plumbing X As Determined by Condition FIRST 50 HRS. EVERY 500 HRS. Inspect Pump Valves EVERY 1500 HRS. EVERY 10000 HRS. X Change Pump Oil X Replace Pump Valves X Replace Seals X X Crankcase Service and Inspect Connecting Rods and Crank Bearings X Manifold Rebuild X Replace Connecting Rods and Bearings 4 X MAINTENANCE RECORD Keep record of all maintenance activities to ensure maintenance is performed. Note trends and increase maintenance as necessary. HOURS RECOMMEND SERVICE 50 Oil 550 Oil 1050 Oil 1550 Valve Inspection, Oil 2050 Oil 2550 Oil 3050 Valve Inspection, Oil 3550 Oil 4050 Oil 4550 Valve Inspection, Oil 5050 Oil 5550 Oil 6050 Valve Inspection, Oil 6550 Oil 7050 Oil 7550 Valve Inspection, Oil 8050 Oil 8550 Oil 9050 Valve Inspection, Oil 9550 Oil 10000 Crankshaft Bearing, Manifold Rebuild, Oil ACTIONS / NOTES ACTUAL HOURS SIGNATURE DATE *HP seal is not routinely replaced during low pressure seal change. HP seal is replaced only in case of seal failure (see low-pressure troubleshooting, pg.6). ** Oil changes are mandatory at the specified hour intervals. 5 5P50 Titan Series High Pressure Titanium Positive Displacement Pump TROUBLESHOOTING Use the troubleshooting table below. If problems persist, contact your dealer. PROBLEM PROBABLE CAUSE SOLUTION Low Pressure Belt Slippage Make sure the correct belt is used. If the correct belt is used and the belt is slipping, then tighten. Replace belt if worn. Leaky discharge hose Check connections. Replace hose if worn or cracking. Pressure gauge inoperative or not registering correctly. Check pressure with new gauge and replace as needed. Air leak in inlet plumbing Use PTFE liquid or tape to seal the threads. Make certain that the PTFE does not go beyond the last thread. Doing so may damage the pump. Inlet suction strainer clogged or Clear the obstruction, or use adequate size for inlet improperly sized pump connection and fluid being pumped. Relief valve stuck, partially plugged or improperly sized Clean and reset relief valve to system pressure and correct bypass. Check supply tank for contamination. Worn or dirty valves Clean valve or replace with a rebuild kit. Worn high-pressure seals; Replace seals with rebuild kit. Install and maintain abrasives in pump fluid, severe proper filter, check line size and flow available to cavitation; inadequate water pump supply; stressful inlet conditions. Pulsation Pump runs Faulty pulsation dampener (if a extremely rough, pressure low pulsation dampener has been installed.) Slight water leakage from under the manifold Excessive oil leak between crankcase and pumping section (1 drop every 15 min) 6 Check pre-charge. Check manufacturer’s literature on recommended pressure. Restricted inlet, or air entering inlet plumbing Be sure that inlet hose is the proper size. Check filters and clean as needed. Check fittings and use PTFE liquid or tape for airtight connection. Valve or spring damage Clean or replace valve and spring, check inlet supply tank for contamination Seal damage Replace seals. Possible Condensation No fix needed. Worn low pressure seals Replace seals with seal kit, check inlet pressure and inspect ceramic plunger for damage. Worn crankcase oil seals Replace crankcase oil seals. PROBLEM PROBABLE CAUSE SOLUTION Oil leaking from crankshaft area Worn crankshaft oil seal Replace damaged oil seals. Bad bearing Replace bearing. Cut or worn o-ring on bearing cap Replace o-ring on bearing cap. Water in crankcase Humid air condensing into water Change oil every three months or 500 hours inside the crankcase Excessive play in the end of the crankshaft Worn bearing Replace bearing. Oil leaking in the rear portion Damaged or improperly installed Replace crankcase cover o-ring or drain-plug o-ring. of the crankcase crankcase cover, crankcase cover o-ring, drain-plug, or drainplug o-ring. Loud knocking noise in pump Pulley loose on crankshaft Restricted Inlet Check key and pulley bushing. Clear obstruction or replace valve. Worn bearing, connecting rod or Service crankcase. crankshaft. Worn belts Frequent or premature failure Running pump dry of the seals Abrasive material in the fluid being pumped Excessive temperature of pumped fluid (120 degrees F max.) Replace belts. NEVER RUN THE PUMP WITHOUT WATER. Install proper filtration on pump inlet plumbing. Reduce fluid inlet temperature to specifications. 7 5P50 Titan Series High Pressure Titanium Positive Displacement Pump SERVICE CAUTION Ensure pump is disconnected from the motor or any driving devices. Service the pump in a clean, dirt-free environment. Pump rebuild kits are available for valve or seal overhauls. Contact your dealer for ordering information. INTRODUCTION All tasks should be performed in a clean environment, free from dust and debris. It is imperative that the utmost cleanliness be maintained during the rebuild of your Aqua Pro Pump. The numbers following the parts are callout numbers. They correspond to the parts shown in the figures and in the assembly drawings at the end of the manual. READ THE INSTRUCTIONS COMPLETELY BEFORE ATTEMPTING TO PERFORM ANY SERVICE. Before assembling, clean all parts to make free of oil, grease, dirt, and lint. Use a lint-free cloth to wipe any part of the pump. NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Only silicon grease (PN. 21-1122) should be used on all o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. TOOLS NEEDED Table 2: Tool List for Pump Service 3/16” Allen Wrench Wrench Hex Jaw 1/4” Pick Allen Wrench 3/8” 12-point Socket Wrench Pry-bar 9/16" Socket/ Socket Wrench or Combination Wrench Snap Ring Pliers 15/16” Socket/ Socket Wrench or Combination Wrench Torque Wrench (50 ft.-lb.) 1" Seal Insertion Tool (PN 91-7228) Socket/ Socket Wrench or Combination Wrench 1-1/2” Socket/ Socket Wrench or Combination Wrench Weep Ring Removal Tool (PN 91-7230) Flat-Head Screwdriver Die M7 X 1.0 Phillips-head Screwdriver Bearing Puller Tap M7 X 1.0 Anti-Seize Lubricant (PN 85-0094) Silicon Grease (PN 21-1122) Ceramic Lubricant (PN 85-0087) Arbor press for Connecting Rod/Plunger Pin Press for Crankshaft removal Torque Wrench Red Loctite Dead Blow Hammer 8 VALVE INSPECTION AND SERVICE Valves may be serviced while the manifold assembly is attached to the crankcase assembly. In most cases, service can be completed while the pump is in place within the watermaker system. Remove ten valve plugs (44) from the manifold using a 1 ½“ socket wrench. Remove the valves (41) and springs (42) from each valve port. Inspect the curved valve surface for damage or distortion. A circular mark from the valve seat is normal, but should not advance to distorting the valve shape. If a valve is broken or pitted, use a flashlight to examine the seat inside the valve port. Inspection will ensure that the valve seat has not been damaged by debris. Depending on the condition, either replace or clean and reuse valves and springs. A set of 10 valve and 10 springs is available as PN 70-1057. Apply a light coat of silicon grease (PN 21-1122) to the valve plug o-ring (43). Apply anti-seize lubricant (PN 85-0094) to the valve plug threads. Assemble the valves, springs and plugs as shown in Fig. 9, and tighten the valve plugs back into the manifold. 44 43 42 41 Fig. 2: Valve Assembly DETACHING THE MANIFOLD FROM THE CRANKCASE Remove the 2 manifold nuts (53), see Fig. 13, with a 15/16” socket wrench or Combination Wrench. Loosen the manifold assembly by prying off the manifold using the slots in the crankcase as shown in Fig 2. Set the manifold assembly aside in a clean work area. If the manifold assembly locating dowel pins (50) fall out, reinsert them into the manifold alignment pin hole. Fig. 3: Manifold Assembly Removal 9 5P50 Titan Series High Pressure Titanium Positive Displacement Pump SEAL REPLACEMENT If condition based seal service is required (Seal Kit PN 70-3080), use the following instructions outlined in the OIL SEAL REPLACEMENT section. To determine the need of condition based service, look for signs of oil or water drip under the pump. Once the manifold is detached from the crankcase, the low pressure water seals (40) are exposed on the manifold surface and can easily be replaced. If undertaking the complete 10,000 hour service with kits 70-3075 and 70-3078, then follow the detailed instructions. SERVICING THE CRANKCASE The following are the procedures for servicing the crankcase assembly using the 5P50 Crankcase Rebuild Kit (PN. 70-3078). The manifold assembly must be detached from the crankcase to do the following service. PLUG, OIL DRAIN, O-RING REPLACEMENT Remove the oil drain plug (5) with a 1” wrench and drain the crankcase oil. Clean the drain plug (5), and remove the oring (4) with the aid of the pick if necessary. Replace the o-ring with the new one supplied with kit. Apply anti-seize lube to the threads of the drain plug (5) and reinstall. OIL SEAL REPLACEMENT Remove the seal retainer (33) and set aside, see Fig. 6. Remove the plunger retainer nut (32) with a 9/16” wrench and set aside. Remove the plunger retainer washer (31) and back-up ring (29), Fig. 5, and remove the ceramic plunger (8). Remove the keyhole washer (26), then remove the slinger (25), see Fig. 4. Using a flat head screwdriver and hammer, drive the screwdriver into the meat of the seal (6). Be careful not to scratch the inner or outer metal sealing surfaces. A quick twist of the screwdriver will remove the seal. Do not attempt to preserve the seal for reuse. Inspect the seal retainer washers for damage; if none is evident then reuse. NOTE A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Insert new plunger rod oil seal (6) into crankcase ensuring that the seal is fully seated. Place slinger (25) onto the plunger rod (8), followed by the keyhole washer (26) as shown in Fig. 4. Chase the thread of the plunger rod and the retainer stud with the tap and die to ensure the removal of any left over loctite prior to reassembly. 25 26 8 6 Fig. 4: Plunger Assembly View 10 NOTE Examine the ceramic plungers (27), Fig. 6, for cracks, heavy scoring, or unusual wear. Slide ceramic plungers (27) onto plunger rod, and insert the new plunger retainer washer (31) into the plunger. Clean the plunger retaining nuts (32), Fig. 5. With the aid of a pick remove the plunger retainer back-up ring (29) and the plunger retainer o-ring (30). Replace the o-ring (30) and back-up ring (29) with the new one supplied in the kit as shown in Fig. 5. 32 31 30 29 Fig. 5: Plunger Retaining Nut Assembly Apply Red Loctite # 262 to retainer stud (28) threads. Reinstall the plunger retainer nut (32) and torque to 100 in. lb. using a 9/16” socket. NOTE Be careful not to get the red loctite on any other components. Failure to use loctite on the retainer stud and nut could lead to catastrophic failure of the pump. Apply Aqua Pro’s special Ceramic Lubricant (PN. 85-0087) to the ceramic plungers (27). Slide the seal retainer (33) over the ceramic plungers (27). Make sure that the flanged side is in close proximity to the manifold assembly, and that the hole is oriented downward ensuring that the seal retainer has adequate water drainage. Slide manifold assembly over plungers and reinstall manifold nuts (53). 33 27 32 Fig. 6: Seal Retainer 11 5P50 Titan Series High Pressure Titanium Positive Displacement Pump BEARING CAP O-RING/SEAL REPLACEMENT You will need these tools and parts to do the following: 1/4" Allen Wrench Pick Seal, Oil, Crankshaft (16): PN. 70-0701 O-Ring, Bearing Cap (15): PN. 70-0703 Silicon Grease Lubricant: PN. 21-1122 Anti-Seize Lubricant: PN. 85-0094 Remove the 4 socket head cap screws (17) with a 1/4” Allen Wrench from each of bearing side plates (13), (14). With the aid of a pick remove the o-rings from the grooves and remove the crankshaft oil seal (16) from the pulley side bearing cap (14). CAUTION Crankshaft oil seal is press-fit at the factory, so care is to be exercised during removal to prevent any damage to sealing surface. NOTE A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Press new crankshaft oil seal (16) into pulley side bearing cap (14), install o-ring (15) in o-ring groove on the crankshaft bearing caps (13) and (14), and reinstall caps on pump. NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Install the 4 socket head cap screws (17) onto each of the bearing side plates and tighten with a 1/4” Allen Wrench. COVER, CRANKCASE O-RING REPLACEMENT In this procedure you will replace the o-rings on the crankcase cover as provided in the rebuild kit. You will need these tools and parts to do the following: 3/16” Allen Wrench Phillips-head Screwdriver Pick Silicone Grease Lubricant: PN. 21-1122 Red Loctite # 262 Anti-Seize Lubricant: PN. 85-0094 Unscrew the 12 crankcase cover screws (24) with the 3/16” Allen wrench. Remove the 6 sight glass retaining screws (23) with the Phillips-head screwdriver. Remove the sight glass retaining frame (22) and the sight glass (21). With the aid of the pick remove the sight glass o-ring (20), and remove the crankcase cover o-ring (18). 12 NOTE A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Install the new sight glass o-ring (20) and the crankcase cover o-ring (18) provided with the rebuild kit. NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Install the sight glass (21) and the sight glass frame (22). Apply Red Loctite #262 to the 6 sight glass retaining screws (23) and tighten. Reinstall the crankcase cover (19) and tighten the 10 crankcase cover screws (24) with the 3/16” Allen wrench in the sequence shown in Fig. 7. Fig. 7: Bolt tightening sequence CRANKSHAFT BEARING, CONNECTING ROD-PISTON SERVICE When feasible, it is recommended that any service to the Crankshaft (11), Connecting Rods (10), and Plunger Rods (8) be done by sending the pump back to the factory for rebuilding. CRANKSHAFT REMOVAL Crankshaft removal is not necessary for overhaul of seals. NOTE: The Manifold, Plunger assembly, Bearing Side Plates, and Crankcase Cover must be removed before attempting to remove the crankshaft. You will need these tools and parts to do the following: 3/8” 12-point Socket Wrench Arbor press for Connecting Rod/Plunger Pin Bearing Puller Snap Ringer Pliers Using a 23-point socket, unscrew the connecting rod Bolts (10) 13 5P50 Titan Series High Pressure Titanium Positive Displacement Pump (NOTICE: Unscrew one connecting rod cap at a time. Keep the bolts in the same hold it came out of. Store the connecting rod caps like the picture below in order from 1-5. Fig. 8) Fig. 8 Keep parts organized Push the connecting rod assembly in as far as possible away from the Crankshaft (11). Make sure the Connecting Rods (10) are clear from the path of the crankshaft. Rotate the Crankshaft (11) by hand to feel for smooth bearing movement. If movement is rough, Bearings (12) needs to be replaced. Inspect the bearing surface of the connecting rod end caps. Some scoring is considered acceptable, but irregular wear patterns are not. This is where the decision is made on whether to replace the connecting rods and crank bearings. If bearing surface passes inspection, reassembly can begin. If not already done, remove both Bearing Side Plates (13)(14). Using a press, press out the Crankshaft (11) from the key slotted side. The crankshaft should come out of the crankcase with one Bearing (12) on the non-key slotted side and one Bearing (12) still in the Crankcase (1). Pull off the Bearing (12) on the Crankshaft (11) with a bearing puller (fig. 9). 14 Fig. 9 Removal of the Crankshaft bearing Slide out the Connecting Rods (10) and the Plunger Rod Assembly (8). Check for abnormal wear or scoring. ***Note: Remember where each connecting rod came out of the crankcase. Keep them in the same order. The connecting Rods and Caps are numbered for this reason. (Lay down connecting rods and caps in order removed. Ensure connecting rods remain in order with caps.) Remove the Plunger Rod Seal (6). (Do this step only if not already done.) The Connecting Rod (10) is attached to the Plunger Rod Assembly (8) by a press fit Pin (9). Unless necessary, do not disassemble. CRANKSHAFT INSTALLATION You will need these tools and parts to do the following: Arbor press for Connecting Rod/Plunger Pin Press for Crankshaft removal Torque Wrench ¼” Allen wrench 3/8” 12-point Socket Wrench Silicone Grease – PN. 21-1122 Anti-seize lubricant – PN. 85-0094 Red Loctite Snap Ring Pliers Press in the Crankshaft Bearing (12) into the right Crankshaft bore of the Crankcase (1). If any wear, rough spinning, or looseness is noted, then use new bearings. (Freezing the bearing may help with the press fit.) Apply silicone grease onto the O-ring (15) and the Crankshaft Seal (16). Install the Bearing Plate O-ring (15) and Crankshaft Seal (16) into the pulley side Bearing Plate (14). 15 5P50 Titan Series High Pressure Titanium Positive Displacement Pump Apply a light coat of anti-seize to the 4 Socket Head Cap Screws (17). Install the pulley side Bearing Side Pate (14) using the 4 Socket Head Cap Screws (17) with a ¼” Allen wrench Insert Plunger oil Seal (6) into crankcase. Make sure that the seal is fully seated. (Do this step only if not already done.) Attach the Connecting Rod (10) and Plunger Rod Assembly (8) using the Press Fit Pin (9). Press the pins in using an arbor press (Freezing the Pins (9) and assembling while cold may help in this process.) Insert the Connecting Rod (10) and the Plunger Rod Assembly (8) in the Crankcase (1) in the same order as when they were take out. (The connecting rods are numbered 1, 2, 3… Make certain that the order is correct and that the connecting rod caps’ number corresponds to the connecting rods’ number. The number one Connecting Rod should be closest to the pulley side of the Crankshaft.) Push the connecting rod assembly in as far as possible away from the Crankshaft (11) insertion path. Make sure the Connecting Rods (10) are clear from the path of the crankshaft. Slide in the Crankshaft (11), keyed side first, from the right side of the Crankcase (1) to the left side, through the Crankshaft Bearing (12). A press may be needed to accomplish this step. The connecting rod bearing surfaces must exactly align with the plunger bores to avoid bending pressure on the connecting rods. Press in the left Crankshaft Bearing (38) (closed center hole side). Apply a light coat of silicone grease to the new Bearing Side Plate O-rings (15). Apply a light coast of anti-seize to the 4 Socket Head Cap Screws (17). Install the Closed Bearing Side Plate (13) using the 4 Socket Head Cap Screws (17) with a ¼” Allen Wrench. Apply red loctite to the threads of the Connecting Rod Cap Bolts. Install the Connecting Rod Caps to their corresponding Connecting Rods (10) (There are numbers inscribed on the connecting rods and the connecting rod caps. Make sure that they match up, e.g. 1 and 1, 2 and 2, and 3 and 3.) Pre torque the Connecting Rod Bolts to 100 in. lb. Then torque the Connecting Rod Bolts to 230 in. lb. with a 3/8” 12-point Socket Wrench Fig. 10 Correct Connecting Rod Pairing Fig. 11 Incorrect Connecting Rod Pairing ***Make sure the flat sides numbers are matched up together on the Connecting Rods (10) (like figure 10 not figure 11). 16 SERVICING THE MANIFOLD The following are the procedures for servicing the manifold assembly using the 5P50 Manifold Rebuild Kit (PN. 70-3075). The manifold assembly must be detached from the crankcase to do the following service. Fig. 12: Manifold Assembly ADAPTER O-RING REPLACEMENT You will need these tools and parts to do the following: Wrench Hex Jaw Pick O-Ring, Inlet Plug Adapter (43): PN. 70-3002 O-Ring, Discharge Plug Adapter (45): PN. 70-3074 Silicone Grease Lubricant: PN. 21-1122 Anti-Seize Lubricant: PN. 85-0094 Remove the Inlet/Discharge/Plug, (46), (47), (48), and (49) adapters from the manifold assembly with a hex jaw wrench. With the aid of a pick remove the o-rings (45) and (43) from each of the adapters. NOTE A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Install the new o-rings, (45) and (43), provided with the kit onto each of the adapters. NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Reinstall each of the adapters onto the manifold assembly, then tighten adapter with hex jaw wrench. VALVE ASSEMBLY SERVICING You will need these tools and parts to do the following: 1 1/2" Socket Wrench or Combination Wrench Pick Spring, Valve (42): PN. 70-7049 Assembly, Valve (41): PN. 70-3004 O-Ring, Valve Plug (43): PN. 70-3002 Silicone Grease Lubricant: PN. 21-1122 Anti-Seize Lubricant: PN. 85-0094 Lint-Free Cloths 17 5P50 Titan Series High Pressure Titanium Positive Displacement Pump NOTE Valves may be serviced while the manifold assembly is attached to the crankcase assembly. If manifold assembly has been removed from the crankcase assembly, place the assembly on a clean work surface. Remove all of the valve plug assemblies from the manifold assembly using a 1 1/2” socket wrench or combination wrench. Remove the valve (41) from the assembly, followed by the valve spring (42). With the aid of a pick remove the o-ring (43) from the valve plug. NOTE Valve plugs (44) will be reused. A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Clean and inspect all valve plugs (44) prior to reassembly. Once all valve plugs (44) are clean and dry, install new valve plug o-ring (43) onto valve plug (44). Install the valve spring (42) onto the valve plug (44). Press the valve (41) onto the valve spring (42). Complete valve assembly shown in Fig. 13. 44 43 42 41 Fig. 13: Valve Assembly NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Inspect the manifold (34) for debris or other fouling and clean if necessary. Inspect the valve seat surface in the manifold. Reinstall all the valve plug assemblies with a 1 1/2" socket wrench or combination wrench and tighten. 18 MANIFOLD SEAL SERVICING NOTE Pump manifold assembly must be detached from the crankcase assembly to service the seals. You will need these tools and parts to do the following: Snap Ring Pliers Tool, Seal Insertion: PN. 91-7228 Flat screw driver Seal, HP (36): PN. 70-2502 Ring, Snap (38): PN. 70-3009 Ring, Weep (37): PN. 70-3008 Seal, LP (40): PN. 70-2501 Silicone Grease Lubricant: PN. 21-1122 Lint-Free Cloths Routine seal service is the replacement of the exposed low pressure seal (40) only. The following instructions are for a complete manifold rebuild at the 10,000 hour service mark. For manifold seal servicing purposes the manifold must be placed with the valve plugs sitting on a flat surface and the plunger bores facing upward. This will facilitate service technician access to the seals for removal and installation, as shown in Fig. 14. Fig. 14: Orientation for Manifold Seal Servicing With a flat screw driver remove the low-pressure seal (40). Manually remove the low-pressure seal spacer (39). With the snap ring pliers remove the snap ring (38). Using the weep ring extracting tool, remove the weep ring (37) as shown in Fig. 15. NOTE Extraction of the weep rings is accomplished by inserting tool in relaxed state into the inner diameter of the rings, then tightening the expansion bolt to grip the ring. 19 5P50 Titan Series High Pressure Titanium Positive Displacement Pump Fig. 15: Weep Ring Extraction With a flat screwdriver remove the high-pressure seals (36). Manually remove the high-pressure seal spacer (35). Insert the high-pressure seal spacer (35) into the bore. NOTE A light coating of silicon grease (PN. 21-1122) should be used on all new o-rings and seals. Use of any other type of grease may result in o-ring or seal failure. Insert the high-pressure seal (36) into the bore until the seal is fully seated on the high-pressure seal spacer (35), using the seal insertion tool. See Fig. 12 for high-pressure seal installation view. Fig. 16: High-Pressure Seal Installation View Insert the weep ring (37) into the bore after the installation of the high-pressure seals (36), using the driver from the seal insertion tool. Install the snap ring (38) using the snap ring pliers. NOTE Ensure that the snap ring (38) is fully seated in the snap ring groove before continuing. Insert the low-pressure seal spacer (39), then install the new low-pressure seal (40). The manifold seal servicing is complete. 20 ATTACHING THE MANIFOLD TO THE CRANKCASE You will need these tools and parts to do the following: 15/16” Socket/ Socket Wrench or Combination Wrench Dead Blow Hammer Manifold Nut (53): PN. 70-1305 Ceramic Lubricant: PN. 85-0087 Anti-Seize Lubricant: PN. 85-0094 If a crankcase seal rebuild was not performed at this time then ensure that the dowel locating pins (50) are pressed into their corresponding hole. Ensure that ceramic lubricant is applied to the ceramic plunger assemblies and that the seal retainers are installed with the flange located away from the crankcase assembly. NOTE A light coating of Anti-Seize Lubricant (PN. 85-0094) should be applied on all threaded parts, unless otherwise stated. Align manifold assembly to crankcase assembly as shown in Fig. 13 and tighten the two manifold nuts (53) with a 15/16” socket wrench or combination wrench, torque to 90 ft-lbs. Fig. 17: Pump Assembly Orientation View OIL CHANGE PROCEDURE You will need these tools and parts to do the following: 1” Socket/ Socket Wrench Lint-free Cloths Funnel, 4 oz, plastic Village Marine High-Pressure Pump Oil, PN. 85-0050 Clean area around the oil filler cap (3) and the oil drain plug. Remove the oil filler cap, and then drain the crankcase oil. Once the used oil is completely drained, slowly add high-pressure pump oil to the level shown on the sight glass. Reinstall oil filler cap (3) and wipe off any excess oil. 21 5P50 Titan Series High Pressure Titanium Positive Displacement Pump 5P50 DRAWINGS 5P50 PUMP SPECIFICATIONS 5P50 CRANKCASE ASSEMBLY 5P50 MANIFOLD ASSEMBLY 5P50 MAIN ASSEMBLY 22 A B C D 70-3012 70-3016 70-3017 70-3411 70-3019 70-3020 70-3021 70-3022 70-3023 86-0151 86-0120 70-3060 70-3039 70-3040 70-3087 70-6101 86-0256 70-0701 70-0703 70-3081 70-3079 70-0439 70-3034 70-3098 70-3027 70-0344M 70-3006 70-3062 70-3046 30-1286 70-3044 70-6029 70-3082 PART NUMBER 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ITEM 4 DESCRIPTION O-RING, REAR COVER SCREW, SIDE CAP SEAL, OIL, CRANKSHAFT O-RING, BEARING CAP CAP,PULLEY BEARING,5P50,AL CAP, BEARING, CLOSED BEARING,TAPERED ROLLER,4130-STL CRANKSHAFT, 5P50 ASSY, CONNECTING ROD, 5P50 PIN, DOWEL ASSEMBLY, PLUNGER ROD STUD, MANIFOLD RETAINING SEAL, OIL, PLUNGER, 3P20/5P50 PLUG, OIL DRAIN O-RING, PLUG, OIL DRAIN CAP, OIL FILLER O-RING, OIL FILLER CAP CRANKCASE, TITAN SERIES 5P50, AL COVER, CRANKCASE, TITAN SERIES 5P50 RETAINER, SEAL NUT, PLUNGER RETAINER WASHER, PLUNGER RETAINER O-RING, PLUNGER RING, BACK-UP, SPLIT STUD, M7x1.0, 3.40, PLUNGER PLUNGER, CERAMIC WASHER, KEYHOLE SLINGER, PLUNGER SCREW, REAR COVER SCREW, SIGHT GLASS FRAME, SIGHT GLASS SIGHTGLASS, OIL, 3P20/5P100 O-RING, SIGHT GLASS QTY (70-3073) 1 8 1 2 1 1 2 1 5 5 5 2 5 1 1 1 1 1 1 5 5 5 5 5 5 5 5 5 12 6 1 1 1 NOTES: 1) ASSEMBLY PART NUMBERS ARE AS FOLLOWS: 70-3073 ASSY, CRANKCASE, 5P50 TITAN SERIES 70-3078 KIT, SERVICE, CRANKCASE, 5P50 70-3080 KIT, PUMP SEAL, 5P50 2) THE FOLLOWING PART NUMBERS ARE NOT SHOWN IN DRAWING BUT ARE INLCUDED IN EACH KIT: 21-1122 SILICON GREASE 85-0087 CERAMIC LUBRICANT 85-0094 ANTISIEZE 4 5 - - 5 5 5 - 3 QTY KIT QTY KIT (70-3078) (70-3080) 1 1 1 5 1 1 - - 5 5 5 1 3 24 19 18 20 21 22 14 2 23 17 2 12 10 9 8 3 5 .XXX±.005 LBS DATE 4/28/08 APPROVED BC 2/5/07 DATE 4/28/08 DATE 125 CHECKED BC DRAWN JR FINISH WEIGHT ± 1/32 ANGULAR ± 0°30" FRACTIONAL .XX±.010 .X±.020 DECIMALS UNLESS OTHERWISE SPECIFED DIMENSIONS & TOLERANCING ARE IN INCHES PER ANSI Y14.5 M & MIL-STD-100 11 15 MAT'L VARIOUS 16 2 25 30 13 31 32 33 1 ADDED PUMP SEAL KIT 1 7 REVISIONS DESCRIPTION INITIAL RELEASE MODIFIED BOM QTY TITLE 6 28 5/20/2011 DATE 2/5/2007 3/17/2010 27 1:8 DWG NO 1 70-3000 SHEET 2 OF 4 B REV 29 CC APPROVED BC CC ASSEMBLY, 5P50 CRANKCASE SCALE B SIZE TITLE 4 26 B REV. A A B C D A B C D 70-3050 70-3066 70-3065 70-3059 70-3064 70-3074 70-3001 70-3002 70-7049 70-3004 70-2501 70-3010 70-3009 70-3008 70-2502 70-0407 70-3005 PART NUMBER 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 ITEM 4 DESCRIPTION MANIFOLD, TITAN SERIES 5P50 RING, SPACER, HP SEAL SEAL, HIGH PRESSURE ASSEMBLY, WEEP RING,3P20/5P50 RING, RETAINING,3P20/5P50 SPACER, LOW PRESSURE SEAL SEAL, LP,3P20/5P50, XYLAN, BLUE PTFE ASSY, VALVE, 3P20/5P50 TITAN SERIES SPRING, VALVE, 3P20/5P50, TI O-RING, VALVE PLUG, VALVE, MS18229-16 O-RING, APTR, HOSE-BARB ADTR, 2.0 HB, MS18229-24 ADTR, FACE SEAL PLUG,MS18829-24 PLUG,MS18229-16,TI PIN,DOWEL - - 5 5 5 5 5 5 10 10 12 - 2 - - - - - - - - - - - 5 - - - - - - - - - - - - - - - - 10 10 - - - - - - - - 3 3 QTY QTY KIT QTY KIT QTY KIT (70-6120) (70-3075) (70-3080) (70-1057) 1 5 5 5 5 5 5 10 10 12 10 2 1 1 1 1 2 NOTES: 1) ASSEMBLY PART NUMBERS ARE AS FOLLOWS: 70-6120 ASSY, MANIFOLD, 5P50 TITAN SERIES 70-3075 KIT, REBUILD, MANIFOLD, 5P50 70-1057 KIT, PUMP VALVE 70-3080 KIT, PUMP SEAL, 5P50 2) THE FOLLOWING PART NUMBERS ARE NOT SHOWN IN DRAWING BUT ARE INLCUDED IN EACH KIT: 21-1122 SILICON GREASE 85-0087 ANTISIEZE 85-0094 CERAMIC LUBRICANT 4 48 50 49 43 34 40 2 39 2 38 35 45 DATE APPROVED DATE ± 1/32 DATE LBS ANGULAR ± 0°30" FRACTIONAL CHECKED DRAWN FINISH WEIGHT MAT'L .XXX±.005 .XX±.010 .X±.020 DECIMALS 125 UNLESS OTHERWISE SPECIFED DIMENSIONS & TOLERANCING ARE IN INCHES PER ANSI Y14.5 M & MIL-STD-100 37 36 SCALE B SIZE TITLE 46 47 41 42 43 ADDED PUMP AND SEAL KITS 1 REVISIONS DESCRIPTION INITIAL RELEASE MODIFIED BOM QTY TITLE, NOTE INCLUDES ITEMS NOT IN BOM TABLE DATE - 44 5/20/11 3/26/10 CC 1:1 DWG NO 1 70-3000 SHEET 3 OF 4 B REV CC APPROVED - ASSEMBLY, 5P50 MANIFOLD B A REV. - A B C D Pressure Vessel Assemblies For Seawater Elements Contact Information: Parker Hannifin Corporation Racor Division/Village Marine Tec. 2000 W. 135th St. Gardena, CA 90249 phone 310 516 9911 fax 310 538 3048 racor@parker.com www.villagemarine.com www.parker.com/racor Key Features: Racor Village Marine RO membrane pressure vessels feature non-metallic wetted surfaces for excellent corrosion resistance. Simple end plug design allows quick removal for element servicing. If the size you require is not shown please contact us for custom builds. • • • • • • Operating Pressure: 1000 psi/68 bar Shell: Filament Wound fiberglass Collars: 6061 T-6 Powdercoated aluminum End Plugs: Thermoplastic End Ring: 6061 T-6 Anodized aluminum on 2.5” and 4” size SS316 on 6” size Fasteners: SS316 Pressure Vessel Assemblies For Seawater Elements 7 2 3 4 5 6 1 Part Numbers: Item Description 1 Vessel Assembly** 2 Product O-ring 3 Quantity per Assembly 2.5” x 19” 2.5” x 38” 4” x 40” 6” x 40” 32-2519 32-2538 32-0444 32-6040 4 32-2116 32-2116 32-2116 32-2229 End Plug O-ring 2 32-2228 32-2228 32-4342 32-0640 4 End Plug 2 32-2513* 32-2513* 32-4012 32-6012 5 End Ring 2 32-4013 32-4013 32-4014 32-0096 6 Capscrews *** 86-0106 86-0106 86-0123 86-0136 1 1 32-0025 32-0098 32-0026 32-0099 Please Call 32-4001 Please Call 32-0001 5/2 7/3 22/10 45/20 7 Shell White Gray Weight (lbs/kg) Notes: *End Plug 32-2517 is also available for 2.5” vessels, which offers straight, coarse thread feed/reject port used on some VMT PW watermakers © 2009 Parker Hannifin Corporation **Membrane not included. For applicable membrane elements see bulletin No. 7897 (Aqua Pro RO Membranes) *** Capscrews: Order 6 per end plug on 2.5” size Order 8 per end plug on 4” size Order 10 per en plug on 6” size Print Reorder Number 7898 Rev- 10-15-2009 Aqua Pro® Sea Water RO Membranes Contact Information: Parker Hannifin Corporation Racor Division/Village Marine Tec. 2000 W. 135th St. Gardena, CA 90249 phone 310 516 9911 fax 310 538 3048 racor@parker.com www.villagemarine.com www.parker.com/racor Key Feature: Aqua Pro® thin film composite membranes deliver high salt rejection while maintaining high production rates to obtain the energy efficiency demanded by plant operators. By selecting the highest grade of materials and thoroughly testing performance, Racor Village Marine is able to offer the highest quality Aqua Pro® products. Aqua Pro® Sea Water RO Membranes Recommended Operating Limits: • Maximum Operating Pressure: 1000 psi • Maximum Operating Temperature: 113°F (45°C) • Maximum Feed Turbidity: 1 NTU • Free Chlorine Tolerance: 0 PPM • Maximum Feed Silt Density Index: SDI 5 • pH Range: Continuous Operation: 4-11 Short-term (30 min) Cleaning: 2.5-11 A B TYP D C 15° VMT Part No. Nominal Size Product Flow GPD m3/day Typical Salt Rejection % 33-2519 33-0238 33-0440 33-0036 2519 2538 4040 6040 220 - 0.83 550 - 2.08 1200 - 4.54 2500 - 9.47 99.4 99.4 99.4 99.4 A 19/48 38/96.5 40/101.6 40/101.6 Dimensions inches/cm B C 1.1/2.8 0.75/1.9 1.1/2.8 0.75/1.9 1.0/2.5 0.75/1.9 1.27/3.2 1.5/3.8 D 2.4/6.1 2.4/6.1 3.96/10.1 5.98/15.2 Notes: • • Keep elements moist at all times Permeate obtained from first two hours of operation should be discarded © 2009 Parker Hannifin Corporation • To prevent biological growth during storage, shipping, or system shutdowns it is recommended that elements be immersed in a protective solution. The standard storage solution for long or short term storage should contain 1.0 percent (by weight) sodium metabisulfite (food grade) • Standarized test conditions are 32,000 ppm NaCl at 77° F (25° C), with 800 psi feed. Production rates for individual elements may vary +/- 20% and rejection may vary +/- 0.4% Print Reorder Number 7897 Rev- 10-27-2009 Filter Housings FRP Shell with Nylon Caps 100X-FRP Racor Village Marine offers fiberglass filter housings specifically designed for seawater use. Simple but secure closure systems allow quick cartridge change. Aluminum collars are bonded to fiberglass shells offer superior corrosion resistance. The base and lid are nylon. The housings fit VMT pleated cartridge elements of 100 square feet area. Available in 0.5, 1, 5, 20, and 100 micron ratings. Contact Information: Parker Hannifin Corporation Racor Division/Village Marine Tec. 2000 W. 135th St. Gardena, CA 90249 phone: 310 516-9911 800 C-Parker fax: 310 538-3048 email: racor@parker.com www.villagemarine.com www.parker.com/racor Filter Housings FRP Shell with Nylon Caps 100X-FRP 8 Req’d 8 Req’d DWG 1 2 3 4 5 6 7 8 9 Description Part Number Filter Assembly Vessel Shell Base Lid O-Ring Nuts - Bottom Studs 30-4353 M4353-4 M1157-1 M4353-2 30-0405 86-0022 86-0264 Washer Wingnut Bolt - Bottom 86-0006 86-0269 86-0260 2 Req’d 8 Req’d 8 Req’d Specifications Design Pressure* Test Pressure 80 psi 120 psi Inlet 1.5” FPT Outlet Height Diameter 1.5” FPT 33”/84 cm 13”/33 cm 8 Req’d *Filter Housing Vessel is designed in accordance with ASME section x pressure vessel code. To maintain peak performance always use genuine Parker Racor Village Marine replacement parts. We reserve the right to change our specifications or standards without notice. © 2011 Parker Hannifin Corporation Print Reorder Number 7940 Rev-B 09-26-2011 Pleated Filters and Filter Cartridge Kits Contact Information: Parker Hannifin Corporation Racor Division/Village Marine Tec. 2000 W. 135th St. Gardena, CA 90249 phone: 310 516-9911 800 C-Parker fax: 310 538-3048 email: racor@parker.com www.villagemarine.com www.parker.com/racor The Village Marine Tec. line of pleated filters are designed specifically for the RO watermaker industry and are superior to wound or polyspun cartridges to give you a longer filter life as well as increasing flow rates and keeping cartridge size down. Available in a wide arrange of sizes and micron ranges to ensure that every type of watermaker filter need is taken care of. Stock sizes fit most standard filter housings, if the size you need is not shown please contact us with the dimensions required. Single use Cleaning and Preservative Cartridge Kits are designed specifically for small RO Systems. The Cartridges allow for easy and effective membrane maintenance. The Cleaning and Preservative Cartridge Kits eliminate the trouble and mess of measuring powdered chemicals and ensuring correct chemical concentrations. The Chemical cartridges fit directly into 2.5” x 10” or 4.5” x 10” housings and contain the correct amount of chemical for a single use. Pleated Filters and Filter Cartridge Kits Features: Pleated Filters • Polypropylene pleated construction • Longer service life over wound or polyspun cartridges • Easily cleaned and reused • Chemically compatible with a wide range of alkalies, most acids and saline solutions • 0.5, 1, 5, and 20 micron nominal ratings available • Pliable ends ensures filter seal to eliminate bypass • High packing density reduces filter size while keeping flow rates up Filter Cartridge Kits • Cartridge with Blue stripe contains cleaner #1, a biological cleaner to remove algae, fungi and bacteria • Cartridge with Red stripe contains cleaner #2, an acidic cleaner to remove scale from the membrane • Cartridge with Green stripe contains the preservative. This chemical is used for pickling the membranes • Cartridges are capable of being used in any housing that takes a standard 2.5” (64mm) x 10” (254mm) filter cartridges Pleated Sediment Elements Part Number Microns 33-0118 33-0117 33-0053 33-0052 33-0020 33-0005 33-0058 33-0057 33-0172 33-2100 33-5100 33-1100 33-1105 20 5 20 5 20 5 20 5 100 20 5 1 0.5 Filter Area ft3/m3 30/2.79 30/2.79 100/9.29 100/9.29 100/9.29 100/9.29 100/9.29 Diameter inch/cm 2.75/7 2.75/7 4.5/11.4 4.5/11.4 8.63/22 8.63/22 4.5/11.4 4.5/11.4 8.63/22 8.63/22 8.63/22 8.63/22 8.63/22 Length inch/cm 9.75/25 9.75/25 9.75/25 9.75/25 7.75/20 7.75/20 20/51 20/51 24.3/62 24.3/62 24.3/62 24.3/62 24.3/62 Carbon Flushing Filters Part Number 33-0311 33-0315 33-0083 Diameter inch/cm 2.75/7 4.5/11.4 4.5/11.4 Length inch/cm 9.75/25 9.75/25 20/50.8 Cartridge Filter Kits Description Part Number Contents Cleaning Kit 85-0102 Preservation Kit 85-0103 One Blue stripe cleaner #1 plus One Red stripe cleaner #2 Two Green stripe preservative To maintain peak performance always use genuine Parker-Racor/Village Marine Tec. replacement parts. We reserve the right to change our specifications or standards without notice. © 2009 Parker Hannifin Corporation Print Reorder Number 7905 Rev- 11-23-2009
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No Author : AKB2698 Create Date : 2008:12:23 09:31:56-08:00 Modify Date : 2013:08:30 14:27:47-07:00 Has XFA : No XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26 Producer : Adobe Acrobat 6.0 Creator Tool : Adobe Acrobat 6.0 Metadata Date : 2013:08:30 14:27:47-07:00 Format : application/pdf Title : Microsoft Word - techman_pw3000-18000 Creator : AKB2698 Document ID : uuid:65011a6e-2732-4555-b468-ed06166da1e3 Instance ID : uuid:a3d331e5-128d-4c03-84f4-103d57d243bf Page Count : 101EXIF Metadata provided by EXIF.tools