Programming Vista 128 4 Wire Smoke Reset
User Manual: Vista-128 4-Wire Smoke Reset AlarmHow.net Library
Open the PDF directly: View PDF
.
Page Count: 1
| Download | |
| Open PDF In Browser | View PDF |
Smoke Reset for 4-wire smokes On Vista 40/50/100/128/250/32 Works on any “Richey” panel Programming: program zone 3 (or any zone that cannot be used for 2-wire smokes)) as normal for FIRE. Program relay#1 for smoke reset: close/stay closed. Start ZT54, stop ZT57. Set 1*75 = 008 seconds. Action: When the appropriate zone sees a short (alarm), the panel will go into alarm on that zone. The first “off” sequence will silence the panel. The second “off” sequence will cause the panel to activate relay #3 for a smoke reset. During this reset, “W1” holds a short on the zone to prevent a trouble condition when the end of line relay looses power. For this to work, W1 MUST be tied to the (+) side of the zone and the reset must interrupt the (-) power. Note: If using more than 1 zone with 4-wire smokes, DO NOT use W1. Another document is available using the 4209u zone expander for multiple zones.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Tagged PDF : Yes Page Mode : UseThumbs XMP Toolkit : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39 Producer : Acrobat Distiller 5.0 (Windows) Create Date : 2002:08:13 16:57:13-04:00 Modify Date : 2011:05:13 08:17:13-05:00 Metadata Date : 2011:05:13 08:17:13-05:00 Creator Tool : Acrobat PDFMaker 5.0 for Word Format : application/pdf Creator : Ademco Title : Programming: program zone 5 (or 2-7 on V20/15) as normal for FIRE Document ID : uuid:e7432ed1-47a9-4ee4-8ba1-d92275f1b5eb Instance ID : uuid:47c25d71-efc2-4229-8f52-411b182969e5 Page Count : 1 Page Layout : SinglePage Author : AdemcoEXIF Metadata provided by EXIF.tools