FC-33
DC Selectable Input, Isolated Signal Conditioner

Input Selection

Adjustments

The signal conditioner can be configured for either DC milliamps or
DC volts. Input and Output signal types are 0 - 5V, 0 - 10V, 0 - 20mA ,
4 - 20mA .

The FC-33 has built-in self-calibration, but also has
OFFSET (zero) and SPAN (full scale) adjustments of the
input signal. If your application requires, different
span or offset (i.e. 3.6mA offset and 19.6mA span)
you can adjust accordingly.

1

2

3

4

5

6

7

8

0

example:
4 - 20mA input
4 - 20mA output

Application adjustments

1
Input Ranges

Output Ranges

0 - 5V

1 0 1 1
0 0 1 0

0 - 20mA

1 0 0 1
1 0 0 0

Description

The FC-33 has user selectable factory-calibration, but also has OFFSET
(zero) and SPAN (full scale) adjustments of the input signal.
The OFFSET (zero) has an adjustment range of 0 to 25% of full scale
input, the SPAN (full scale) has an adjustment of 80 to 102%
Application

1 2 3 4 5 6 7 8

0 - 10V
*4 -20mA

The FC-33 is a DIN rail mount, selectable input / output signal conditioner
with 1500VDC isolation between input and output and 1500VDC isolation
from 24 volt power and input / output. The field configurable input/output
types allow a wide ranging capability for 0 - 5V , 0 - 10V , 0 - 20mA ,
4 - 20mA .

Switch Position

0 - 5V

1 1 0 1

0 - 10V

1 0 0 0

0 - 20mA

0 1 0 0

4 - 20mA

0 0 0 0

Factory Default Settings
4 - 20mA

4 - 20mA

Calibrating the input signal level 1. Select the signal range (i.e. 4 - 20mA ).
2. Connect 24 volt power to the signal conditioner.
3. Connect the minimum input signal level.
4. Turn Switch 2 ON, press and hold the CAL
pushbutton until the LEVEL LED comes ON steady
(approx. 3 seconds), then release immediately. If the
pushbutton is NOT released while the Level LED is ON
steady, the signal conditioner will return to factory
calibration.
5. Repeat above sequence for maximum input signal.
6. Turn Switch 2 OFF.
To return to factory calibration1. Turn switch 2 ON, press and hold the CAL
pushbutton until the LEVEL LED comes ON steady and
then starts flashing (approx. 10 seconds), then release
the pushbutton. The unit has now been returned to
factory calibration.
2. Turn Switch 2 OFF.

1 0 0 0 0 0 0 0

* Must connect jumper from V+ to I+ for current input.
Specifications
Input Ranges

0-5V, 0-10V , 0-20mA , 4-20mA

General Specifications

Input impedance

250Ω ±0.1% current input
200KΩ / 400KΩ Voltage Input

Accuracy vs. Temperature

± 0.005% / °C (50ppm/°C)

Output Ranges

0-5V, 0-10V , 0-20mA , 4-20mA

Input Power

24VDC ±10% @ 50mA

Load Impedance

2KΩ minimum, voltage output
0Ω minimum, current output

Recommended Fuse

0.032A Littelfuse Series
217 current inputs

Maximum Load / Current

550Ω @ 24V sink/source

Isolation

Sample Duration Time

10mS

LEVEL LED

Filter Characteristic

-3dB @ 3Hz , -6dB/octave

1500VDC input - output
1500VDC power - input
1500VDC power - output
* applied for 1 second

This LED is a powerful tool when setting up the signal conditioner.
During normal operation the LED will blink at a proportional rate to the
selected input signal level. When performing field calibration the LED is
used for indication of the internal calibration process.

Linearity Error

0.05% FSO maximum

Maximum Inaccuracy of output 0.05% FSO @ 25°C
(Includes offset,span,linearity) 0.25% FSO @ 0 - 60°C

Stability

0.05% FSO maximum

Output Current

21mA maximum
(for mA output)

Approx . field cal. range

0 - 25%
(0 - 1.5V / 5V mode)
80% - 102%
(4 - 5.1V / 5V mode)

The FC-33 field configurable isolated input/output signal conditioner is
useful in eliminating ground loops and interfacing sensors to our PLC
analog input modules. The FC-33 has 3 way isolation, this feature solves
many types of configuration problems. For example, the signal
conditioner can be configured for sinking input and sourcing output. It
also allows signal translation from current input to voltage output or
voltage input to current output.
This feature would be useful when you have limited type and number
of channels in your system design, i.e. 8 channels of 4-20mA , 7 which
are used and one transmitter that is 0 - 10V .

CAL - Pushbutton
This pushbutton along with various switch settings, allows you to
calibrate the signal conditioner for your application or restore factory
default calibration.

Note: All data 0° - 60° C except where specified.
1
Internal Analog convertor resolution is 12 - bit.
CAUTION: PRODUCT MAY BE DAMAGED IF CURRENT OUTPUT (I+/I-)
AND VOLTAGE OUTPUT(V+/V-) ARE BOTH CONNECTED TO LOADS.
DO NOT TIE THE I+ TERMINAL TO THE V- TERMINAL.

Operating Temperature

0 to 60° C

(32 to 140°F)

Storage Temperature

-20 to 70°C (-4 to 158°F)

Relative Humidity

5 to 90% (non-condensing)

Environmental air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3-304

Module
Supply

+

−

Typical Connection -

Voltage
Transmitter

+
−

−

+

Module
Supply

ISOLATION

−

+

Module
Supply

Voltage Input and Current Output (example)
4 - 20 m A Sinking Output to Isolated 4-20 mA Sinking Input (example)

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS
A, B, C AND D OR NON-HAZARDOUS LOCATIONS ONLY.
WARNING – EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS
MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 / ZONE 2.
WARNING – EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO
BE NON-HAZARDOUS.

Rev.121112



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : DonS
Create Date                     : 2005:10:19 16:01:21Z
Modify Date                     : 2012:12:13 07:32:09-05:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Format                          : application/pdf
Creator                         : DonS
Title                           : FC_33.sdr
Creator Tool                    : SmartDraw Professional - [FC_33.sdr]
Metadata Date                   : 2012:12:13 07:32:09-05:00
Producer                        : Acrobat PDFWriter 5.0 for Windows NT
Document ID                     : uuid:42f158c3-2cf7-4aff-8758-f6f106940449
Instance ID                     : uuid:53e6f4c3-12c9-49bf-ad85-9f88a94ab60b
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu