D. CLASS A/CLASS B ZONE INSTALLATION (INITIATING ZONE MODULES)
Each Initiating Zone Module provides up to 2 class A (style D), 4 class B (style B) or 1 class A and 2 class B
zones of protection. This module accommodates both 2 and 4-wire smoke detectors, N.O. alarm initiating devices and N.O. or N.C. supervisory devices. Use any UL Listed N.O. or N.C. device not requiring power from
the Fire Control Panel such as pull stations, heat detectors, waterflow switches, etc. Use only those 2 and 4wire smoke detectors which are listed in Table 2 in section II.C 'Summary Of Specifications'. Each zone provides enough current (2mA) to power up to 16 of the 2-wire detectors listed in that section. Before proceeding,
position the module jumpers for the desired zone configuration as shown in Figure 4.
IMPORTANT!: N.C. supervisory devices are not permitted for NFPA71-central station installations, but are
permitted for NFPA 72A-local installations.
Insert the first module into slot 2 of the main board and connect the ribbon cable to the connector shown on the
Summary of Connections Diagram (Figures 8, 9). Wire connections from initiating devices to this module are
made on the main terminal block.if used, the second module plugs into slot 3, with its ribbon cable plugged into
the Auxiliary Terminal Block Board as shown in the Summary of Connections Diagram. Wire connections to
the second module are made to the Auxiliary Terminal Block Board.
When wiring initiating devices, be sure that the maximum zone wire run resistance does not exceed 100 ohms
for both the MS4812 and the MS4824. Observe polarity when wiring 2-wire smoke detectors. Be sure that
only 2 and 4wire smoke detectors are wired to zones that will be programmed for alarm verification (other devices may not be programmed for alarm verification).

FIGURE 4. ZONE CONFIGURATIONS FOR INITIATING ZONE MODULES (Previous Page)*
E. ADDRESSABLE SENSOR INSTALLATION (POLLING LOOP MODULES)
The Polling Loop module provides a supervised polling loop output for connection to addressable sensors. The
polling loop provides power to sensors and serves as a communication path between the control panel and sensors.
Each sensor is assigned a unique address ID number, set by an 8 position DIP switch, which is displayed at the keypad console when annunciating the sensor's status.
Each Polling Loop module 'provides up to 55mA of current for sensors. Fill out the polling loop loading worksheet
(Table 3) to determine the maximum number of sensors that can be connected to a single loop. A second module
can be installed, which provides a second 55mA polling loop output, if additional sensors are required. Note that
the maximum number of sensors supported by the system is 88. Do not connect one polling loop output to the other
polling loop output if two modules are used.
The first Polling Loop module is installed in slot 2 of the main board, and its ribbon cable plugs into the connector
on the main terminal block as shown in the Summary of Connections Diagram. The second module (if used) is installed in slot 3 of the main board with its ribbon cable connected to the connector on the Auxiliary Terminal Block
Board as shown in the Summary of Connections diagram.
Before installing sensors, be sure to assign unique ID numbers (from 9-96) using each sensor's DIP switch. Do not
assign the same number to more than one sensor. Refer to Table 4 in this section when setting DIP switches. Wire
sensors to the polling loop as shown in Figure 5. Observe the wire run length limitations listed in section II.C
Polling Loop module specifications. Sensors can be connected to a single wire run or groups of sensors can be
connected to separate wire runs without affecting the Fire Control Panel's ability to supervise individual sensors.
Be sure to observe sensor polarity when wiring.
CAUTION! Use of shielded wire or conduit reduces the maximum combined wire run length for multiple wire
runs (f rom one Polling Loop Module) f rom 4000 f eet (1 200m) to 2000 feet (600m), independent of wire gauge.
RIZ-1 Installation and Connection
When using the RIZ-1 module, be sure that the maximum wire run resistance does not exceed 100 ohms. Wire initiating devices to the RIZ-1 zone as shown in Figure 5. Be sure that only 4- wire smoke detectors are wired to the
zone if the zone will be programmed for alarm verification. The RIZ-1 mounts to any standard double gang electrical box using the four screws supplied with the module.
When using SDID, SDID-T, or CPID smoke detectors, or the BGID pull station, follow the instructions included
with these modules for proper installation.
TABLE 3. POLLING LOOP LOADING WORKSHEET

SENSOR/LOAD FACTOR

NUMBER INSTALLED

EFFECTIVE LOAD

(88 max.)

(55mA max.)

SDID: 0.36mA
SDID-T: 0.36mA
BGID: 0.56mA
CPID: .0.36mA
RIZ-1: 1.95mA
TOTALS:

For each addressable sensor type shown above, fill in the number of sensors to be installed, then calculate the
Effective load by muftiplying the number of installed sensors by the the load factor listed. Add the numbers in
each column. Verify that the total number of sensors installed does not exceed 88 and that the total load does not
exceed 55mA.
NOTE: Load Factor is defined as follows:
Load Factor = (standby current + alarm current) X 1/2
This load factor was chosen so that maximum polling loop current (55mA) is drawn when 1/2 of the installed sensors are in alarm states and 1/2 are in standby state.
FIGURE 5. POLLING LOOP CONNECTIONS

SWITCH POSITION
1 23 45 678

SWITCH POSITION
1 23 45 678

ON
OFF

ON
OFF
ID#

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF OFF on OFF OFF on = 9
OFF OFF on OFF on OFF =10
OFF OFF on OFF on on =11
OFF OFF on on OFF OFF =12
OFF OFF on on OFF on =13
OFF OFF on on on OFF =14
OFF OFF on on on on =15
OFF on OFF OFF OFF OFF =16
OFF on OFF OFF OFF on =17
OFF on OFF OFF on OFF=18
OFF on OFF OFF on on =19
OFF on OFF on OFF OFF =20
OFF on OFF on OFF on = 21
OFF on OFF on on OFF = 22
OFF on OFF on on on = 23
OFF on
on OFF OFF OFF= 24
OFF on
on OFF OFF on = 25
OFF on
on OFF on OFF= 26
OFF on
on OFF on on = 27
OFF on
on
on OFF OFF= 28
OFF on
on
on OFF on = 29
OFF on
on
on on OFF= 30
OFF on
on
on on
on = 31
on OFF OFF OFF OFF OFF=32
on OFF OFF OFF OFF on =33
on OFF OFF OFF on OFF=34
on OFF OFF OFF on
on =35
on OFF OFF on OFF OFF=36
on OFF OFF on OFF
on =37
on OFF OFF on on OFF =38
on OFF OFF on on
on =39
on OFF on
OFF OFF OFF=40
on OFF on
OFF OFF on =41
on OFF on
OFF on OFF=42
on OFF on
OFF on
on=43
on OFF on
on OFF OFF=44
on OFF on
on OFF
on=45
on OFF on
on on OFF= 46
on OFF on
on on
on= 47
on on OFF OFF OFF OFF =48
on on OFF OFF OFF on= 49
on on OFF OFF
on OFF=50
on on OFF OFF
on on =51
on on OFF
on OFF OFF =52

ID#
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF
on
on OFF
OFF
on on OFF
OFF
on on OFF
OFF
on on
on
OFF
on
on
on
OFF
on on
on
OFF
on on
on
OFF
on on
on
OFF
on on
on
OFF
on
on
on
OFF
on on
on
on OFF OFF OFF
on OFF
OFF OFF
on OFF OFF OFF
on OFF OFF OFF
on OFF OFF OFF
on OFF OFF OFF
on OFF OFF OFF
on OFF OFF OFF
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF OFF on
on OFF on
OFF
on OFF on OFF
on OFF on OFF
on OFF on OFF
on OFF on OFF
on OFF on OFF
on OFF on OFF
on OFF on OFF
on OFF on
on
on OFF on
on
on OFF on
on
on OFF
on
on
on OFF on
on
on OFF on
on
on OFF on
on
on OFF on
on
on on OFF OFF

on OFF on = 53
on
on OFF = 54
on
on on = 55
OFF
OFF OFF = 56
OFF
OFF on = 57
OFF
on OFF = 58
OFF
on on = 59
on
OFF OFF = 60
on
OFF on = 61
on
on OFF = 62
on
on
on = 63
OFF
OFF OFF = 64
OFF OFF
on = 65
OFF
on OFF = 66
OFF
on
on = 67
on
OFF OFF = 68
on
OFF
on = 69
on
on OFF = 70
on
on
on = 71
OFF OFF OFF = 72
OFF OFF
on = 73
OFF
on OFF = 74
OFF
on
on = 75
on
OFF OFF = 76
on
OFF on = 77
on
on OFF = 78
on
on
on = 79
OFF
OFF OFF = 80
OFF
OFF
on = 81
OFF
on OFF = 82
OFF
on
on = 83
on
OFF OFF = 84
on
OFF on = 85
on
on OFF = 86
on
on on = 87
OFF
OFF OFF = 88
OFF
OFF on = 89
OFF
on OFF = 90
OFF
on
on = 91
on
OFF OFF = 92
on
OFF on = 93
on
on OFF = 94
on
on on = 95
OFF OFF OFF = 96

TABLE 4. ADDRESSABLE SENSOR DIP SWITCH SETTING TABLE (Above)
TABLE 6. POWER SUPPLY LOADING WORKSHEET (Next)
Fill in the alarm and standby currents drawn from each output listed below. Add up the currents in both columns.
Verify that the total alarm current does not exceed the maximum current limit (67omA for MS4812; 585mA for
MS4824). Use the total standby current to choose the battery capacity needed to achieve 24 hours of standby time.

SLOT/DEVICE
FDC-UL
(Slot 1)
IZ412

MS4812
RATING
15mA standby
85mA alarm
36mA standby
100mA alarm

IZ424
DCID

MS4824
RATING
12mA standby
40mA alarm

SLOT 2

SLOT 3

SLOT 2

SLO

36mA standby
100mA alarm
85mA standby
75mA standby

DCID24
(Slot2/Slot3)

50mA standby
45mA alarm

RR12
(Slot 4)

60mA standby
100mA alarm

70mA standby
100mA alarm

ATR
(Slot 5)

40mA standby
90mA alarm

25mA standy
50mA alarm

ABM-12

3mA standby
53mA alarm

ABM-24
(Slot 6)

3mA standby
33mA alarm

Remote
Annunciator
Output (RDA)

75mA standby
140mA alarm

4-Wire
Smoke Detector

See Ratings
provided with
Detectors

TOTALS

STANDBY CURRENT ALARM CURRENT
(mA)
(mA)

45mA standby
85mA alarm

(See NOTE 2)

(160mA max.)

MS4812=420mA max.
MS4824=310mA max.

MS4812=670mA max.
MS4824= 585mA max.

NOTE 1: The MS4812 rating represents the modulelperipheral current draw from a 12V battery. The MS4824
rating represents the modulelperipheral current draw from the 24V battery.
NOTE 2: Amaximumof2RDAmodulesmaybeconnectedtotheRemoteAnnunciatorpoweroutput. Thisoutputprovides
28OmA at 12V. Each RDA draws l4OmA at 12V in alarm.

TABLES 7A AND 7B. BATTERY CAPACITY SELECTION TABLES
Use the appropriate table shown below to determine the battery capacity required to provide 24 hours of standby
time followed by 5 minutes of alarm time for the total standby current determined from the power supply loading
table above.

TOTAL STANDBY CURRENT

BATTERY CAPACITY

MAKE AND MODEL NUMBER

UP TO 80 mA

6 AH

Yuasa NP6-12 (12V)

UP TO 100mA

6.5 AH

Fire-Lite PS 1265 (12V)

UP TO 160mA

8 AH

Yuasa NP8-6 (6V)
Fire-Lite PS 682 (6V)
connect 2 in series*

UP TO 240mA

10 AH

Yuasa NP10-6 (6V)
connect 2 in series*

UP TO 310mA

13 AH

Fire-Lite PS 1265 (12V)
connect 2 in parallel*

UP TO MAX STANDBY CURRENT (420mA MAX.)

15 AH

Yuasa NP15-12 (12V)

TABLE 7A. MS4812 BATTERY SELECTION
* NOTE: Two pairs of battery cables are supplied. Splice one pair together to connect batteries in series. Use both
pairs for connecting batteries in parallel.
TABLE 7B. MS4824 BATTERY SELECTION
TOTAL STANDBY CURRENT

BATTERY CAPACITY

MAKE AND MODEL NUMBER

Up to 36mA

4AH

Yuasa NP4-12 (12V)
Connect 2 in series*

Up to 120mA

6AH

Yuasa NP6-12 (12V)
Connect 2 in series*

Up to140mA

6.5AH

FireLite PS1265 (12V)
Connect 2 in series*

Up to 200mA

8AH

Yuasa NP8-6 (6V)
Connect 4 in series*

Up to 285mA

10AH

Yuasa NP10-6 (6V)
Connect 4 in series*

Up to310mA

12AH

Yuasa NP6-12 (12V)
FireLite PS1265 (12V)
See note below

NOTE: Use four batteries. Connect two sets of 2 batteries in series, then connect both sets in paratial Observe polarity.
*NOTE: Three pairs of battery cables are provided. Use the red and black cables to connect batteries to terminal
block. Two pairs of redlblack cables are provided to allow batteries to be connected in parallel. Two white jumper
cables are provided to connect batteries in series (splice a red and black cable together to connect four batteries in
series)

V. TESTING THE SYSTEM
The system can execute the following tests: bell test, LED test, battery test, walk test and smoke detector test. The
bell test activates both bell circuits for the purposes of conducting a fire drill. The LED test checks that all LEDs
and all segments of the digital display are working properly. Upon completion of the LED test, the digital display
will display the system ID numbers of all tests in progress. The battery test checks the status of the battery. The
walk test is used to check the operation of alarm initiating devices. The smoke detector test allows testing of addressable smoke detectors from the KeypaJ/Console.
Bell Test
To execute a bell test, press the BELL TEST key. Depending upon operating option programming, both bell circuits will activate steadily or in march time. The TEST MODE LED will light. The TEST MODE LED remains
on and the bell circuits remain activated until the BELL TEST key is pressed again.
LED Test
To execute an LED test, press the DISPLAY key to enter the Display mode. The DISPLAY MODE LED will light
and all other LEDs will turn off. Then press the LED TEST key. All LEDs will light and the number '88' will appear in the digital display for 2 seconds. After 2 seconds, the digital display will display the ID numbers of tests
which are in progress. Tests in progress are displayed using the following system ID numbers:
50 = battery test in progress
51 = walk test in progress
52 = bell test in progress
Press the END key to return to the Normal mode.
Battery Test
To activate the battery test, press DISPLAY key + # key + 50. The Battery test function (code 50) allows a battery
test to be manually activated. This test forces the system to operate from the battery for a 1 0 minute period. If the
battery fails to maintain proper operating voltage at any time during the test, the test is aborted and the TROUBLE
LED will light. The system normally performs an automatic battery test every 12 hours, beginning 15 minutes from
power up.
Walk Test
To activate the Walk Test, press DISPLAY + # + 51. The Walk Test (code 51) allows a service person to verify
the operation of all zones and sensors which are programmed for alarm. When this mode is first activated, the external sounders will sound for 3 seconds and the communicator (if installed) will transmit a "Start of Walk Test'
message. To perform the test, simulate an alarm condition at each zone or sensor. The external sounder will sound
for half a second, every 2-5 seconds and the faulted zone or sensor address will be repeatedly flashed on the Control's display window, for as long as the alarm condition is present.
Smoke Detector Test
SDID/4192SD, SDID-T/4192SDT and CPID Smoke Detectors can be tested via the Console's keypad while in the
Walk Test Mode by entering the address of the detector to be tested. The external sounders will sound briefly and
the detector address will be displayed for 1 second, every 2-5 seconds. Each new address entered ends the test for
the previous address. If an address that is an installed sensor, but is not the address of an addressable smoke detector, is entered, the system will remain at this location waiting to hear from the unit selected. To get past this erroneous entry, enter 99 and testing can be continued. To completely end the smoke detector test, re-enter the last
smoke detector address tested. If an entered address has not been programmed, the keypad will beep 3 times. (This
feature can also be used to verify that any polling loop sensor's address has been programmed, by entering the desired address. If the keypad does not beep 3 times, the address has been programmed.)

Note that alarm reports are NOT sent to the Central station while the walk test is activated. To terminate the walk
test manually, re-enter [* + # +51]. The walk test will also automatically terminate 30 minutes after the last time a
key is pressed or a sensor is faulted. The communicator will transmit an 'End of Walk Test" message when the
walk test mode is terminated, either manually or automatically.
TABLE 9: SUMMARY OF KEYPAD FUNCTIONS
FUNCTION

KEYS

Normal Mode

To silence keypad buzzer

Press BUZZER SILENCE

To test external sounders

Press BELL TEST. (Press again to silence.)

To silence bells activated by alarm

Press BELL SILENCE

To reset the system

Press RESET

To disable a zone or addressable sensor

Press ZONE DISABLE (#) +
Zone or sensor ID number
(enter again to restore a disable zone)

Display Mode
To enter display mode

Press DISPLAY (*)

To display current alarms

Press DISPLAY (*) + ALARM (1)

To display current supervisory faults

Press DISPLAY (*) + SUPV. (2)

To display current sensor and system troubles

Press DISPLAY (*) + TROUBLE (3)

To display disabled zones

Press DISPLAY (*) + DISABLE (4)

To stop a scrolling display

Press STEP (6)
(Repeated depression causes manual scrolling
of ID numbers)

To return to scrolling display
To test keypad console LEDs and display
current tests in progress

Press SCAN (5)
(when in Display Mode)
Press (*) + LED TEST (7)
(test last 2 seconds)

To diplay alarm history

Press DISPLAY (*) + (#) + 91

To display supervisory history

Press DISPLAY (*) + (#) + 92

To display trouble history

Press DISPLAY (*) + (#) + 93

To disable Main Bell Circuit

Press DISPLAY (*) + (#) + 70
(Re-enter to enable)

To disable Aux. Bell Circuit

Press DISPLAY (*) + (#) + 71
(Re-enter to enable)

To disable Aux. Alarm Relay

Press DISPLAY (*) + (#) + 72
(Re-enter to enable)

To disable Aux. Trouble Relay

Press DISPLAY (*) + (#) + 73
(Re-enter to enable)

To disable Reversing Relay

Press DISPLAY (*) + (#) + 74
(Re-enter to enable)

To disable Digital Comm.

Press DISPLAY (*) + (#) + 75
(Re-enter to enable)

To activate battery test

Press DISPLAY (*) + (#) + 50
(test lasts 10 minutes)

To activate walk test

Press DISPLAY (*) + (#) + 51
(Re-enter to stop test)

To return to Normal Mode from Display Mode

Press END (9)

Programming Mode
To enter Program Mode

Press DISPLAY (*) + (#) + 10

To program a data field

Press (*) + Field Number + [Data to be entered]

To display a previously programmed field

Press (#) + Field Number
(when in Program Mode)

To clear the program

Press (*) + 90
(when in Program Mode)

To exit program mode with lockout

Press (*) + 98
(Re-entry to Program Mode is only within
30 seconds of power up.)

To exit program with lockout

Press (*) + 99
(Re-enter Program Mode anytime)

NOTE. Once In DISPLAY mode and the DISPLAY LED Is lit, it Is not necessary to press the DISPLAY (.)
keyagalntoonteradifterentDISPLAYmode. Simply press the appropriate key(s) for the display desired.
SPECIAL MESSAGES
FC:

Field Code error, occurs while programming fields. Re-enter data

OC:

Open Circuit. No communication If it appears on built-in console, check console's ribbon connector to

main terminal block. If h appears on RDA, check continuity of yellow data wire to RDA.

The following codes may appear while displaying trouble conditions and represent
system troubles:
A0

Polling loop short

Al

Future use

A2

Future Use

A3

Main Bell Circuit faulted

A4

Aux. Bell Circuit faulted

A5

Ground fault

A6

Telco Line I faulted

A7

Telco Line 2 faulted

A8

'Low battery

A9

AC Loss

AA

Kiss off failure

Ab

External sounders silenced

The following codes may appear while displaying disables:
E0 -Main Bell circuit disabled
El - Auxiliary Bell circuit disabled
E2 = Auxiliary Alarm relay,disabled
E3 - Auxiliary Trouble Relay disabled
E4 - Reversing Relay disabled
E5 - Digital Communicator disabled

The following codes may appear while displaying tests In progress:
50 Battery Test
51 Walk Test
52 Bell Test

Figure 8: MS4812 Summary of Connections Diagram

FIELD FUNCTION

LOCATIONS

[56] SUPERVISORY RETARD TIME
[57] BELL TIMEOUT PERIOD

X2 seconds (01-15)
X2 minutes (01-15)

[58] BELL AND RELAY OPTIONS
For march time bell sounding, enter 0
in location 1

Bell Stdy

[59] REPORT ROUTING
Alarm reports=locations 1&2
Non-Alarm reports=locations 3&4

alrm prim

Main t/o

Aux t/o

Not Used
0

alrm 2nd

non prim

enter 1 if yes,
0 if no

non 2nd
enter 1 if yes,
0 if no

[60] REPORT ROUTING AND OPTIONS
12 hour test report=0 in location 3

2nd bkup

prior order

24 hr rprt

test rprt
enter 1 if yes,
0 if no

Sescoa

4+2

high spd

Radionics

[61] PRIMARY DIALER FORMAT
[62] SECONDARY DIALER FORMAT
Ademco Low Speed=0 in loc. 1, 3 & 4
3+1/4+1 data format=0 in location 2

enter 1 if yes,
0 if no
enter 1 if yes,
0 if no

T/T Ln 2

T/T Ln 1

Not Used

Comm. instll?

[63] DIALER LINE OPTIONS
Rotary Service=0 in locatuions 1

[64] DIAL TONE WAIT, ACKNOWLEDGEMENTS
5 second wait=0 in locations 1&2
30 second ack=0 in location 3
500msec kissoff=0 in location 4

enter 1 if yes,
0 if no

11 sc wait

30 sc wait

60 sc wait

1.2 sc kissoff
enter 1 if yes,
0 if no

expd alrm

[65] EXPANDED REPORT OPTIONS
Expanded Zone/Sensor reports=loc. 1-3
Expanded system reports=location 4

[66] PABX ACCESS CODE
{Enter up to four 2-digit numbers, 00-15 each}
[67] PRIMARY SUBSCRIBER ACCOUNT NO.

supv trble

expd dsble

expd systm
enter 1 if yes,
0 if no

[70] PLUGGED-IN OPTIONS DCID2

DCID3

IZM2

IZM3
enter 1 if installed/0 if not

[71] FIRST TEST REPORT TIME DELAY

[72] SECONDARY SUBSCRIBER ACCT. NO.

X2 hours (00-15)

{Enter up to four 2-digit numbers, 00-15}

[73] FACTORY PROGRAMMED FIELD
Recore digits displayed, but
DO NOT CHANGE ANY VALUES!

Record digits
only!

[74] OTHER REPORT FORMATS/
ROTARY BACKUP (see fields 61&62) Expr Prim

Expr 2nd

Sens ID

Rotary Bkup
enter 1 if yes,
0 if no

[75] COMMUNICATION OPTIONS
Enter 1 to select checksum/0 if no
Enter 1 to disable dial tone detection/
0 if detection is desired

Cksm Prim

Cksm 2nd

Dial detc

Not Used
0

PROGRAMMING CHART FOR THE MS4812/MS4824 FIRE CONTROL PANEL
FIELD
FUNCTION
LOCATIONS
(enter 1 to select option, 0 if not desired)
1
2
3
4
5
6

7

8

[00] CLASS A SELECTION (zones only)
[01] MAIN BELL ACTIVATION
[02] AUX BELL ACTIVATION
[03] ALARM VERIFICATION
[04] WATERFLOW
[05] ALARM RELAY ACTIVATION
[06] DELAY REPORTING*
[07] SUPERVISORY SHORT

0

0

0

0

0

0

0

[08] SUPERVISORY OPEN
[09] SUPERVISORY RETARD
[10] REVERSING RELAY ACTIVATION

For home run wired zones, the location
number corresponds to the programmable group number.
For polling loop sensors, the location number corresponds to the programmable group number.

0

Each programmable group responds to the listed option according to the entry made: 1=yes/0=no.
(Enter Group Number 1-7. Enter 0 if not installed)
1
2
3

4

5

6

7

8

[11] SENSORS 9-16
[12] SENSORS 17-24
[13] SENSORS 25-32
[14] SENSORS 33-40
[15] SENSORS 41-48
[16] SENSORS 49-56
[17] SENSORS 57-64
[18] SENSORS 65-72
[19] SENSORS 73-80
[20] SENSORS 81-88
[21] SENSORS 89-96

IMPORTANT! Enter only zeros in all eight locatons of field 6.
1ST DIGIT
[22] GROUP 1 ALARM CODE
[23] GROUP 2 ALARM CODE
[24] GROUP 3 ALARM CODE
[25] GROUP 4 ALARM CODE
[26] GROUP 5 ALARM CODE
[27] GROUP 6 ALARM CODE
[28] GROUP 7 ALARM CODE
[29] GROUP 8 ALARM CODE
[30] GROUP 1 ALARM RESTORE CODE
[31] GROUP 2 ALARM RESTORE CODE
[32] GROUP 3 ALARM RESTORE CODE
[33] GROUP 4 ALARM RESTORE CODE
[34] GROUP 5 ALARM RESTORE CODE
[35] GROUP 6 ALARM RESTORE CODE
[36] GROUP 7 ALARM RESTORE CODE
[37] GROUP 8 ALARM RESTORE CODE

2ND DIGIT

(Enter 00-15 for all locations)

[38] SYSTEM TROUBLE CODE
[39] SYSTEM TROUBLE RESTORE CODE
[40] LOW BATTERY CODE
[41] LOW BATTERY RESTORE CODE
[42] AC LOSS CODE
[43] AC RESTORE CODE
[44] SYSTEM DISABLE CODE
[45] SYSTEM DISABLE RESTORE CODE
[46] ZONE TROUBLE CODE
[47] ZONE TROUBLE RESTORE CODE
[48] ZONE DISBALE CODE
[49] AONE DISABLE RESTORE CODE
[50] WALK TEST START CODE
[51] WALK TEST END CODE
[52] SUPERVISORY CODE
[53] SUPERVISORY RESTORE CODE
[54] 12/24 HOUR TEST CODE

0

0

0

[55] NOT USED

Programming Key Components
To enter Programming Mode

Press [*] + [#] + [10]

To Program a Data Field

Press [*] + [field number]

To Display Previous Data Field

Press [#] + [field number]

To Clear Entire Program

Press [*] + [90]

To Exit with Lock-Out Option

Press [*] + [98]

To Exit without Lock-Out Option

Press [*] +[ 99]

0

Error Messages
FC=Field Code Error, reenter data
OC=Open Circuit, no communication to Console from the Control Panel
Alarm Codes
PABX/Telco Codes
Code

Enter

Code

Enter

1-9

01-09

1-9

01-09

0

10

0

00 or 10

B

11

*

11

C

12

#

12

D

13

E

14

F

15

To disable any report, enter 0000
Note that digits are programmed and displayed from left to right.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Annotate, Fill forms, Extract, Assemble, Print high-res
Create Date                     : 1998:07:07 15:07:19
Producer                        : Acrobat Distiller 3.01 for Windows
Author                          : CAROLINAS
Creator                         : ADOBEPS4.DRV Version 4.10
Title                           : 4812.pub
Modify Date                     : 1998:07:07 15:19:23
Page Count                      : 17
EXIF Metadata provided by EXIF.tools

Navigation menu