Fire Lite.ms 9200ud.ms 9200ude
User Manual: fire-lite.ms-9200ud.ms-9200ude
Open the PDF directly: View PDF .
Download | |
Open PDF In Browser | View PDF |
PN: 51906:A ECN 02-398 Fire Alarm Control Panel MS-9200UD/MS-9200UDE IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. Document #51906 12/10/02 Revision: A Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because: • Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located. • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). LimWarLg.p65 01/10/2000 IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that: • Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH (noncondensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. LimWarLg.p65 01/10/2000 Notes 4 MS-9200UD PN 51906:A 12/10/02 Table of Contents SECTION 1: Product Description ........................................................................................................................12 1.1: Features and Options ...................................................................................................................................12 1.2: Specifications ..............................................................................................................................................14 1.2.1: Current Availability...........................................................................................................................15 1.3: Controls and Indicators ...............................................................................................................................16 1.4: Circuits ........................................................................................................................................................17 1.5: Digital Alarm Communicator/Transmitter ..................................................................................................17 1.6: Components.................................................................................................................................................18 1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................18 1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19 1.6.3: 300 Series Intelligent Addressable Devices......................................................................................20 1.6.4: Addressable Device Accessories.......................................................................................................20 1.7: Optional Modules ........................................................................................................................................21 1.8: Accessories..................................................................................................................................................21 1.8.1: PK-Plus Programming Utility ...........................................................................................................21 1.8.2: Dress Panel........................................................................................................................................21 1.8.3: Battery Box .......................................................................................................................................22 1.8.4: Battery Charger .................................................................................................................................22 1.8.4.1 CHG-75 Battery Charger ........................................................................................................22 1.8.4.2 CHG-120F Battery Charger ....................................................................................................22 1.8.5: Annunciators .....................................................................................................................................23 1.9: Getting Started.............................................................................................................................................24 1.10: Telephone Requirements and Warnings ....................................................................................................25 1.10.1: Telephone Circuitry.........................................................................................................................25 1.10.2: Digital Communicator.....................................................................................................................25 1.10.3: Telephone Company Rights and Warnings .....................................................................................26 SECTION 2: Installation .......................................................................................................................................27 2.1: Mounting Backbox......................................................................................................................................27 2.2: Mounting Transformer ................................................................................................................................28 2.3: Power...........................................................................................................................................................31 2.3.1: AC Power and Earth Ground Connection.........................................................................................31 2.3.2: Battery Power....................................................................................................................................31 2.3.3: DC Power Output Connection ..........................................................................................................31 2.4: Relays ..........................................................................................................................................................32 2.5: Notification Appliance Circuits ..................................................................................................................32 2.5.1: Configuring NACs ............................................................................................................................33 2.5.2: Style Y (Class B) NAC Wiring .........................................................................................................33 2.5.3: Style Z (Class A) NAC Wiring ........................................................................................................34 2.6: Remote Synchronization Output .................................................................................................................34 2.7: UL Power-limited Wiring Requirements ....................................................................................................35 2.8: Digital Communicator.................................................................................................................................36 2.9: Optional Module Installation ......................................................................................................................37 2.9.1: 4XTMF Transmitter Module Installation..........................................................................................38 2.9.2: Printer/PC..........................................................................................................................................40 2.9.3: Digital Communicator and Annunciators .........................................................................................41 2.9.3.1 ACM-8RF Relay Control Module ..........................................................................................41 2.9.3.2 BRKT-9600 Universal Bracket Installation ............................................................................41 2.9.3.3 ACM and AFM Series Annunciators ......................................................................................43 SECTION 3: Programming ...................................................................................................................................44 3.1: Programming Data Entry ............................................................................................................................44 3.2: User Programming ......................................................................................................................................45 3.3: Initial Power-up...........................................................................................................................................46 MS-9200UD P/N: 51906:A 12/10/02 5 Table of Contents 3.4: Programming Screens Description ..............................................................................................................46 3.5: Programming and Passwords ......................................................................................................................46 3.6: Master Programming Level.........................................................................................................................48 3.6.1: Autoprogram .....................................................................................................................................49 3.6.2: Point Program....................................................................................................................................50 3.6.2.1 Detector Programming ............................................................................................................50 3.6.2.1.1 Add Detector ........................................................................................................................50 3.6.2.1.2 Delete Detector .....................................................................................................................51 3.6.2.1.3 Edit Detector ........................................................................................................................51 3.6.2.2 Module Programming .............................................................................................................60 3.6.2.2.1 Add Module .........................................................................................................................60 3.6.2.2.2 Delete Module ......................................................................................................................61 3.6.2.2.3 Edit Module Screen for Monitor Module .............................................................................61 3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................70 3.6.3: Zone Setup.........................................................................................................................................77 3.6.3.1 Enable ......................................................................................................................................77 3.6.3.2 Disable .....................................................................................................................................78 3.6.3.3 Zone 97, 98 and 99 ..................................................................................................................78 3.6.3.4 Zones Installed ........................................................................................................................79 3.6.3.5 Zones Enabled .........................................................................................................................79 3.6.3.6 Zones Disabled ........................................................................................................................79 3.6.3.7 Zone Type ...............................................................................................................................80 3.6.3.8 Zones Available ......................................................................................................................81 3.6.4: Loop Setup ........................................................................................................................................81 3.6.4.1 Style .........................................................................................................................................81 3.6.4.2 Loop Protocol ..........................................................................................................................81 3.6.5: System Setup .....................................................................................................................................82 3.6.5.1 Trouble Reminder ...................................................................................................................83 3.6.5.2 Banner .....................................................................................................................................83 3.6.5.3 Time-Date ...............................................................................................................................84 3.6.5.3.1 Time .....................................................................................................................................84 3.6.5.3.2 Date ......................................................................................................................................85 3.6.5.3.3 Clock Format ........................................................................................................................85 3.6.5.3.4 Daylight Savings Time .........................................................................................................85 3.6.5.4 Timers .....................................................................................................................................86 3.6.5.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................86 3.6.5.4.2 Pre-signal Delay ...................................................................................................................87 3.6.5.4.3 Waterflow Delay ..................................................................................................................87 3.6.5.4.4 AC Loss Delay .....................................................................................................................88 3.6.5.5 NAC (Notification Appliance Circuit) ....................................................................................88 3.6.5.5.1 Enabled .................................................................................................................................89 3.6.5.5.2 Type ......................................................................................................................................90 3.6.5.5.3 Silenceable ...........................................................................................................................90 3.6.5.5.4 Auto Silence .........................................................................................................................91 3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................91 3.6.5.5.6 Zone ......................................................................................................................................92 3.6.5.5.7 Silence Inhibited ...................................................................................................................92 3.6.5.5.8 Sync Type .............................................................................................................................92 3.6.5.6 Relays ......................................................................................................................................93 3.6.5.7 Canadian Option ......................................................................................................................94 3.6.5.8 Waterflow Silenceable ............................................................................................................94 3.6.6: Verify Loop .......................................................................................................................................94 3.6.7: History...............................................................................................................................................95 3.6.7.1 View Events ............................................................................................................................95 3.6.7.2 Erase History ...........................................................................................................................95 3.6.8: Walktest .............................................................................................................................................96 6 MS-9200UD P/N: 51906:A 12/10/02 Table of Contents 3.6.9: Option Modules................................................................................................................................97 3.6.9.1 Annunciators/UDACT ............................................................................................................97 3.6.9.2 Onboard DACT .......................................................................................................................98 3.6.9.2.1 Onboard DACT Enable ........................................................................................................98 3.6.9.2.2 Primary Phone ......................................................................................................................99 3.6.9.2.3 Secondary Phone ..................................................................................................................99 3.6.9.2.4 Service Terminal ..................................................................................................................100 3.6.9.2.5 Central Station ......................................................................................................................102 3.6.9.2.6 Trouble Call Limit (Dialer Runaway Prevention) ...............................................................103 3.6.9.2.7 Manual Dial Mode ...............................................................................................................115 3.6.9.3 Printer/PC ................................................................................................................................116 3.6.10: Password Change ............................................................................................................................117 3.6.11: Clear Program .................................................................................................................................118 3.6.12: Program Check................................................................................................................................119 3.7: Maintenance Programming Level ...............................................................................................................121 3.7.1: Disable Point .....................................................................................................................................122 3.7.2: History...............................................................................................................................................123 3.7.3: Program Check..................................................................................................................................124 3.7.4: Walktest.............................................................................................................................................125 3.7.5: System ...............................................................................................................................................125 3.7.6: Zone Setup ........................................................................................................................................127 SECTION 4: Operating Instructions ....................................................................................................................129 4.1: Panel Control Buttons .................................................................................................................................129 4.1.1: Acknowledge/Step ............................................................................................................................129 4.1.2: Alarm Silence....................................................................................................................................129 4.1.3: Drill/Hold 2 Sec ................................................................................................................................129 4.1.4: Reset..................................................................................................................................................129 4.2: LED Indicators ............................................................................................................................................130 4.3: Normal Operation........................................................................................................................................131 4.4: Trouble Operation .......................................................................................................................................131 4.5: Alarm Operation..........................................................................................................................................133 4.6: Supervisory Operation.................................................................................................................................134 4.7: Process Monitor Operation..........................................................................................................................135 4.8: Hazard/Tornado Condition Operation .........................................................................................................135 4.9: Medical Alert Condition Operation.............................................................................................................135 4.10: NAC Operation .........................................................................................................................................135 4.11: Programmed Zone Operation ....................................................................................................................136 4.12: Disable/Enable Operation .........................................................................................................................136 4.13: Waterflow Circuits Operation ...................................................................................................................136 4.14: Detector Functions ....................................................................................................................................136 4.15: Time Functions: Real-Time Clock ............................................................................................................136 4.16: Synchronized NAC Operation ..................................................................................................................137 4.17: Coded Operation .......................................................................................................................................137 4.18: Presignal ....................................................................................................................................................137 4.19: Positive Alarm Sequence ..........................................................................................................................138 4.20: Special System Timers ..............................................................................................................................139 4.20.1: Silence Inhibit Timer.......................................................................................................................139 4.20.2: Autosilence Timer ...........................................................................................................................139 4.20.3: Trouble Reminder ...........................................................................................................................139 4.20.4: Waterflow Retard Timer..................................................................................................................139 4.20.5: Alarm Verification (None or One Minute)......................................................................................140 4.21: Walktest .....................................................................................................................................................140 4.22: Read Status ................................................................................................................................................141 4.22.1: System Point ...................................................................................................................................142 MS-9200UD P/N: 51906:A 12/10/02 7 Table of Contents 4.22.2: Zones ...............................................................................................................................................143 4.22.3: Power...............................................................................................................................................144 4.22.4: Trouble Reminder............................................................................................................................145 4.22.5: Timers..............................................................................................................................................145 4.22.6: NAC ................................................................................................................................................146 4.22.7: Relays ..............................................................................................................................................146 4.22.8: Program Check................................................................................................................................147 4.22.9: History.............................................................................................................................................147 4.22.10: Annunciators .................................................................................................................................148 4.22.11: Phone Line.....................................................................................................................................148 4.22.12: Central Station...............................................................................................................................149 4.22.13: Service Terminal............................................................................................................................150 4.22.14: Printer/PC ......................................................................................................................................150 4.22.15: Print ...............................................................................................................................................151 4.22.16: Time-Date......................................................................................................................................153 SECTION 5: Central Station Communications ...................................................................................................154 5.1: Transmittal Priorities ...................................................................................................................................157 SECTION 6: Remote Site Upload/Download .......................................................................................................159 6.1: Downloading Program.................................................................................................................................159 6.1.1: Security Features ...............................................................................................................................160 6.2: Downloading Initiated at Control Panel ......................................................................................................162 6.3: Downloading Initiated at a Service Terminal ..............................................................................................162 6.4: Uploading Initiated at a Service Terminal...................................................................................................163 SECTION 7: Power Supply Calculations .............................................................................................................164 7.1: Overview .....................................................................................................................................................164 7.2: Calculating the AC Branch Circuit..............................................................................................................164 7.3: Calculating the System Current Draw.........................................................................................................165 7.3.1: Overview ...........................................................................................................................................165 7.3.2: How to Use Table 7.3 on page 166 to Calculate System Current Draw ...........................................165 7.4: Calculating the Battery Size ........................................................................................................................167 7.4.1: NFPA Battery Requirements .............................................................................................................167 7.4.2: Selecting and Locating Batteries.......................................................................................................167 APPENDIX A: Software Zones ............................................................................................................................168 A.1: Correlations ...............................................................................................................................................168 APPENDIX B: Default Programming .................................................................................................................174 APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................175 APPENDIX D: Wire Requirements .....................................................................................................................179 8 MS-9200UD P/N: 51906:A 12/10/02 It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • • Underwriters Laboratories Standards NFPA 72 National Fire Alarm Code Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code Underwriters Laboratories Documents: UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired Other: EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ) Fire•Lite Documents: Fire•LiteDevice Compatibility SLC Wiring Manual AFM-16ATF & AFM-32AF AFM-16AF Annunciator ACS Series Annunciators CHG-120F Battery Charger CHG-75 Battery Charger LDM Series Lamp Driver Modules LCD-80F Remote Fire Annunciator ACM-8RF Relay Control Module MS-9200UD PN 51906:A 12/10/02 Document #15384 Document #51309 Document #15970 Document #15210 Document #51480 Document #50888 Document #51315 Document #50055 Document #51338 Document #50362 9 10 TRANSFORMER 1 MS-9200UD PN 51906:A HIGH VOLTAGE J10 1 2 3 JP4 4 3 CAUTION! CAUTION! 2 1 J11 TRANSFORMER 2 Transformer 1 Connector Transformer 2 Connector Nonresettable or Resettable Power Jumper selectable by JP4, 24 VDC filtered, power-limited (0.500 amps maximum) Supervision required. Nonresettable Power suitable for powering annunciators, Resettable Power suitable for powering smoke detectors.. Resettable Power - 24 VDC filtered, power-limited (0.500 amps maximum) to smoke detectors (IDC). Supervision required. Supervise with a power supervision relay A77-716B DC Power Outputs (24 VDC) 24 VDC filtered, supervised and power-limited. 0.040 amps maximum, follows NAC1 control circuit. Requires 4.7kohm End-of-Line resistor. Remote Synchronization Output + + - Notification Appliance Circuits - JP5 J1 + + + 120 VAC, 60 HZ, 3.0 amps 220/240 VAC, 50 Hz, 1.5 amps - + BATTERY J9 RELAY 1 NC C NC C JP2 RELAY 2 TB6NO NC NO C Trouble PS2 Keyboard Interface MINI DIN KEYBOARD CONN. J3 KEYPAD I/F A+ B- 4XTMF CUT TO MONITOR 4XTMF JP3 J6 J7 KISSOFF B (Non Power Limited) DACT Phone Line Jacks SEC. PHONE LINE J12 SEC. ACTIVE PRI. PHONE LINE J13 PRI. ACTIVE A shield SHIELD Cut this jumper to supervise the 4XTMF module when installed (see J5 & J6) J5 A- SLC SLC SLC B A B A A B + + - TB10 SLC B+ Cut this jumper to enable Supervisory relay when 4XTMF module is installed ACS + Refer to the SLC Wiring Manual for detailed information on wiring addressable devices for Style 4, 6 and 7. TERM (EIA-485) to LCD-80F O O U I U I T N T N + + - - SLC Loop OR Flash Memory Load Enable Switch. UP is normal position for switch. SW1 DOWN position allows loading of factory software upgrades. 24 VDC, nonpower-limited 18 Amp Hour maximum Battery J4 Remove this jumper to disable the FACP battery charger when using external charger. To disable ground fault detection, remove jumper/shunt from JP7 JP7 REMOVE TO DISABLE GND. FLT. Configure NACs for Claa A or Class B wiring using NACKEY card. Factory default is Class B. RELAY 3 TB7 NO TB5 NO NO NC C NC C Alarm* NO NC C Supervisory* (*Factory default relay programming) For EDP-listed equipment or personal computer with FACP Upload/Download Utility. 50 foot maximum within same room. EIA-232 to printer or personal computer ACS (EIA-485) to ACS Annunc. (power-limited, supervised) TB8 OUT+ IN+ OUT- IN- TB9 Contacts shown below in normal condition (AC power with no alarm, trouble or supervisory activity). Contact Ratings: 2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive) 2 Programmable Relays & 1 Fixed Trouble Relay ELRs 4.7K, ½W A Fail Safe Trouble NC NO C relay switches to the NO position during trouble conditions and under loss of all power. NAC #2 B B B B + + - NAC 2 4 4 2 Number + + + NAC #4 B+ A+ A- B2B+ 4B+ 4B- 2BNAC 2 CLASS A NAC 2 & 4 CLASS B TB4 B+ A+ A- B1B+ 3B+ 3B- 1BNAC 1 CLASS A NAC 1 & 3 CLASS B TB3 - B B B B + + - 1 3 3 1 + + + NAC #3 LCD DISPLAY JP6 + - + REMOTE PWR SUPPLY SYNC TB2 + + + NAC #1 NAC #1, #2, #3 & #4, Style Y (Class B) (Power Limited) 2.5 amps max. per circuit. JP6 configured for Class B using NACKEY card. (See Style Z illustrated near right edge of board). HOT NEUT EARTH TB11 + 24V - + 24V NON-RST RST POWER POWER TB1 2 1 Basic System Connections HIGH VOLTAGE 12/10/02 Red White Green Black DB9F 9 8 7 6 5 4 3 2 1 OR 5 4 3 2 1 TR D G XC T N V R D TB3 B A A B + + - - + + TB4 B A A B + + - - + + NAC #2 + NAC #1 & #2 Style Z (Class A) (Power Limited) 2.5 amps max. per circuit. JP6 configured for Class A using NACKEY card. NAC #1 + TB8 TB8 (option to DB-25) 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 TB8 Notification Appliance Circuits T R D G X C T N V R D Peripheral Devices and Their Documents: ACM-16ATF & ACM-32ATF Doc. # 51480 AFM-16ATF & AFM-32AF Doc. #15970 ACM-8RF Doc. #50362 ACS (EIA-485) Annunciators LDM-32F Doc. #50055 AFM-16AF Doc. #15210 Ack/Step TERM (EIA-485) Annunciators Silence Drill Hold 2 sec. Reset 1 SLC Loop Addressable Devices and SLC Wiring Doc. #51309 92udperi.cdr LCD-80F Doc. #51338 Battery Connector JP1 AM-1 ENABLE CUT FOR 240VAC ENABLE AC DELAY JP3 F1 15 ADDRESS SW 1 ON 068'31$ + - F3 JP2 OFF GND FLT DISABLE TB 3 A- B- A+ B+ - 15 HOT NEUT EAR TH 11 0 5 7 10 8 14 12 1 13 6 2 15 9 4 3 ONES TB 2 B AT BAT OUT OUT + + - TB 1 CHG-120F Charger Doc. #50888 AM-1 JP4 16 HR DELAY J4 JP5 F2 TENS 11 0 5 7 10 8 14 12 1 13 6 15 9 4 32 TB 4 J1 J2 J3 NC NO C + CHG-75 Charger Doc. # 51315 3URGXFW'HVFULSWLRQ )HDWXUHVDQG2SWLRQV Product Description SECTION 1 The Fire•Lite MS-9200UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features. The combination of Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UD FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software and remote power expansion. The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote and local programming of the control panel using the PK-Plus Upload/Download utility. In addition, the control panel may be programmed or interrogated off-site via the public switched telephone network. Any personal computer with Windows 95 or greater, and compatible modem with a speed of 14.4 kbps or faster and Fire•Lite Upload/ Download software kit PK-Plus, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. Note: Unless otherwise specified, the term MS-9200UD is used in this manual to refer to both the MS-9200UD and the MS-9200UDE FACPs (Fire Alarm Control Panels). Inventory When the MS-9200UD shipment is received, check to make certain that all parts have been included in the shipment. The MS-9200UD shipment should consist of one of each of the following: ✓ ✓ ✓ ✓ main circuit board with display backbox with door plastic bag containing screws, cables, key, etc. manual 1.1 Features and Options • • • • • • • • • • • • • • Built-in DACT (Digital Alarm Communicator/Transmitter) Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements 198 addressable device capacity (99 detectors and 99 control/relay/monitor modules) 99 software zones Onboard NACs (Notification Appliance Circuits) which can be configured as four Style Y (Class B) or two Style Z (Class A) circuits 3.0 amps total power for NACs and 24 VDC auxiliary power outputs expandable to 6.0 amps 3.6 amps total system power (includes battery charger) expandable to 6.6 amps Two programmable relay outputs and one fixed trouble relay Synchronization output for remote power supply applications Built-in Programmer Telephone Line Active LEDs Communication Confirmation (Kissoff) LED Touchtone/Rotary dialing Programmable Make/Break Ratio 068'31$ )HDWXUHVDQG2SWLRQV 3URGXFW'HVFULSWLRQ • EIA-232 Printer/PC interface (variable baud rate) • 80-character LCD display (backlit) • Real-time clock/calendar with daylight savings time control • History file with 1,000 event capacity • Advanced fire technology features: • ✓ Automatic drift compensation ✓ Maintenance alert ✓ Detector sensitivity test capability (NFPA 72 compliant) ✓ Automatic device type-code verification ✓ Point trouble identification Waterflow selection per module point • • • • • • • • • • • • • • • 068'31$ Alarm verification selection per detector point Walktest, silent or audible PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) Silence inhibit timer option per NAC Autosilence timer option per NAC Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability Selectable strobe synchronization per NAC Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, AFM annunciators or LCD-80F Remote annunciator Auto-program (learn mode) reduces installation time. Reports two devices set to the same address Password and key-protected nonvolatile memory User programmable password Fully programmable from local keypad or optional keyboard Upload/Download (local or remote) of program and data via integral DACT SLC operates up to 10,000 ft. (3,000 m) with twisted, shielded wire or 3,000 ft (900 m) with untwisted, unshielded wire Compatible with Fire•Lite’s newer series devices ✓ CP350, CP355: addressable Ionization Smoke Detector ✓ SD350(T), SD355(T), AD355: addressable Photo Smoke Detector (T= with Thermal Sensor) ✓ H350(R), H355(R), H355HT: Fast Response Heat Detector (R=Rate-of-Rise option, HT=High Temperature 190RF) ✓ D350P(R): addressable Photo Duct Detector (R=alarm relay option) ✓ B501BH & B501BHT Sounder Base ✓ B224RB Relay Base ✓ B224BI Isolator Base ✓ MMF-300: Monitor Module ✓ MMF-300-10: Monitor Module (10 Input Class B or 5 Input Class A) ✓ MDF-300: Dual Monitor Module (uses two consecutive SLC addresses) ✓ MMF-301: Miniature Monitor Module ✓ MMF-302: 2-wire Detector Module ✓ MMF-302-6: 2-wire Detector Module (6 Input Class B or 3 Input Class A) ✓ CMF-300: Control Module ✓ CMF-300-6: Control Module (6 Output Class B or 3 Output Class A) ✓ CRF-300: Relay Module ✓ CRF-300-6: Relay Module (6 Form-C relays) ✓ BG-12LX: Manual Pull Station ✓ I300: Isolator Module Product Description Specifications • Compatible with legacy Fire•Lite 300 Series devices: • ✓ CP300: addressable Ionization Smoke Detector ✓ SD300(T): addressable Photoelectric Smoke Detector (T= Thermal Sensor) ✓ C304: Control Module ✓ M300: Monitor Module ✓ M301: Miniature Monitor Module ✓ M302: 2-wire Detector Module ✓ BG-10LX: Manual Pull Station Optional 4XTMF module (conventional reverse polarity/city box transmitter) • Annunciators: ✓ ACM Series-LED Zone Annunciators ✓ LDM Graphic Annunciator Series ✓ LCD-80F Liquid Crystal Display point annunciator ✓ ACM-8RF Relay Module 1.2 Specifications Refer to Illustration on page 10 for terminal locations and connections. AC Power - TB11 MS-9200UD: 120 VAC, 60 Hz, 3.0 amps MS-9200UDE: 240 VAC, 50 Hz, 1.5 amps Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation Battery (Lead Acid Only) - J9 Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UD cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box. Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an external battery charger. Communication Loop - TB10 24 VDC nominal, 27.6 VDC maximum Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft. (900 m) untwisted, unshielded pair length Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit requires ferrite bead per FCC requirement Refer to SLC Loop manual for wiring information Notification Appliance Circuits - TB3 & TB4 Each Terminal Block provides connections for two Style Y (Class B) or one Style Z (Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs Style is configured using NACKEY card plugged into JP6 on main board Power-limited circuitry Maximum voltage drop in wiring: 2.0 VDC Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 15) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to Fire•Lite Device Compatibility Document for listed compatible devices Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7 Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 32 for information on power-limited relay circuit wiring 14 MS-9200UD PN 51906:A 12/10/02 Specifications Product Description Nonresettable Power (24 VDC Nominal) - TB1, Terminals 1 (+) & 2 (-) Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 10mVRMS Total DC current available from each output is up to 0.5 amps (see Figure 1.1) Power-limited circuit requires ferrite bead per FCC requirements Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3, Terminals 3 (+) & 4 (-) Maximum ripple voltage: 10 mVRMS Up to 0.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit requires ferrite bead per FCC requirements Refer to Fire•Lite Device Compatibility Document for listed compatible devices Remote Sync Output - TB2 Remote power supply synchronization output 24 VDC nominal Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit requires ferrite bead per FCC requirements EIA-485 (TERM) or EIA-232 (ACS) - TB8 EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +), 3 (Out -), 4 (In -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (Ground) EIA-485 (ACS) - TB9 ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead 1.2.1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer. TB1 Nonresettable or Resettable Power 1 2 3 Resettable Power for 4-Wire Smoke Detectors 4 0.5 amps max per circuit 0.5 amps max per circuit Standby 1 amp max per panel TB3 NAC #1 2 2.5 amps max 3 NAC #3 4 2.5 amps max per circuit TB4 NAC #2 1 2 NAC #4 3 4 Alarm 6 amps max per circuit 2.5 amps max Note: If NACs are configured as two Style Z (Class A) circuits, each circuit can handle 2.5 amps maximum. per circuit 2.5 amps max per circuit Refer to the battery calculations section for additional information. Figure 1.1 Current Availability MS-9200UD PN 51906:A 12/10/02 per panel 6.0 amps with optional second XRM-24(E) transformer. 3.0 amps max. with only standard transformer installed. powerdist9200ud.cdr 1 15 3URGXFW'HVFULSWLRQ &RQWUROVDQG,QGLFDWRUV 1.3 Controls and Indicators LCD Display The FACP uses an 80-character FIRE-LITE ALARMS INC (4 lines X 20 characters) high viewing angle LCD display. The SYSTEM ALL NORMAL display includes a long life LED 10:00A 012102 backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries. LED Indicators LED indicators are provided to annunciate the following conditions: • • • • • • • • • AC Power (green) Fire Alarm (red) Supervisory (yellow) Trouble (yellow) Maintenance/presignal (yellow) Alarm Silenced signals (yellow) Disabled (yellow) Battery fault (yellow) Ground fault (yellow) Key Panel Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad. Function keys: Acknowledge/Step Alarm Silence Drill Reset (lamp test) Service/program keys: • • • • • • • • • • AC POWER MAINTENANCE FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED TROUBLE BATTERY GROUND 2 1 4 5 ACK/STEP 1st 3 DEF ABC 6 EVENT ALARM SILENCE CLR Keys labeled 1 to 9 7 8 9 * key # key 0 # * -/. 0 (recall) key 1st Event key Figure 1.2 Membrane/Display Panel Clear key Escape key Mode key Four cursor keys (up, down, left and right) Enter key GHI JKL MNO PRS TUV WXY ENTER ESC DRILL HOLD 2 SEC MODE RESET QZ RECALL 9600kypd.cdr • • • • Local Piezo Sounder A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions. 068'31$ &LUFXLWV 3URGXFW'HVFULSWLRQ 1.4 Circuits SLC Communication Loop One SLC loop is provided standard on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices. Reference Manual Output Circuits The following output circuits are available on the FACP: • • • 24 VDC Resettable (smoke detector power) output - 0.5 amps maximum 24 VDC Nonresettable or Resettable power output - 0.5 amps maximum 24 VDC Battery Charger (up to 18 AH batteries) NAC (Notification Appliance Circuits) NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY card in JP6, are provided with various programmable features. Relays One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations: • • • • • • • • • • fire alarm trouble supervisory supervisory auto-resettable DACT communication failure process monitor process monitor auto-resettable hazard alert medical alert AC loss 1.5 Digital Alarm Communicator/Transmitter Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions: • • • • • • Line Seizure: takes control of the phone lines disconnecting any premises phones Off/On Hook: performs on and off-hook status to the phone lines Listen for dial tone: 440 Hz tone typical in most networks Dialing the Central Station(s) number: default is Touch-Tone, programmable to rotary For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly. Communicate in the following formats: ✓ 12 Tone Burst types: 20 pps (3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.) ✓ 3 Touchtone Types 4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID 068'31$ Product Description Components 1.6 Components Main Circuit Board See Page The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board. The circuit board is delivered in the MS-9200UD kit and must be mounted to the backbox (refer to circuit board illustration on page 10). Cabinet Standard XRM-24(E) 9200xfor.cdr Optional XRM-24(E) ms9200UD.cdr The MS-9200UD cabinet is red with a navy blue front overlay. The backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel, which mounts to the inside of the cabinet (required by ULC for Canadian installations). The dress panel must be installed to meet FM requirements. Transformer Assembly One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100 VA transformer XRM-24 (XRM-24E for the MS-9200UDE) is available to provide maximum system and accessory power (6.6 amp total). Batteries + - 9200batt.cdr Battery Cable P/N 75287 + The MS-9200UD cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120F and a UL listed battery box such as the BB55F. Batteries must be ordered separately. 1.6.1 Intelligent Addressable Detectors: Newer Series Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel. Refer to the Fire•Lite Device Compatibility Document for a list of approved detectors. Smoke Detectors (Photoelectric) The SD350 is an intelligent, addressable low profile photoelectric smoke detector which provides smoke sensing technology. The SD350T includes a 135o fixed thermal sensor. Smoke Detector (Ionization) The CP350 is an intelligent, addressable low profile ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’ 18 MS-9200UD PN 51906:A 12/10/02 &RPSRQHQWV 3URGXFW'HVFULSWLRQ Smoke Detector (Duct) The D350P is an intelligent, addressable photoelectric duct smoke detector. The D350RP includes an alarm relay. Heat Detectors The H350 is an intelligent heat detector with a thermistor sensing circuit for fast response, designed to provide open area protection with 50 foot (15 m) spacing capability. The H350R incorporates a thermal Rate-of-Rise circuit of 15RF (9.4RC). Detector Bases The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder base for intelligent, addressable smoke detectors. The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke detectors. It may be used to control auxiliary functions. The B224BI is an isolator base for intelligent, addressable smoke detectors. It functions similar to the I300 isolator module which allows loops to operate under fault conditions and automatically restore when the fault is removed. 1.6.2 Intelligent Addressable Modules: Newer Series The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. A blinking LED on a monitor module indicates communication between the module and the control panel. These devices can also be used when installed on older systems. Refer to the Fire•Lite Device Compatibility Document for a list of approved notification and initiating devices. Reference Manual Monitor Modules The MMF-300, MMF-300-10, MDF-300, MMF-302 and MMF-302-6 are addressable monitor modules for monitoring conventional initiating devices. The MMF-300 is used for normally open contact alarm initiating devices, such as manual pull stations, fourwire smoke detectors, heat detectors, waterflow, security contacts and supervisory devices. The MMF-300-10 functions the same as the MMF-300 except it provides 10 Class B or 5 Class A inputs. The MDF-300 is a dual monitor module (Class B only) which occupies two consecutive SLC addresses, with each module functionally the same as the MMF-300. The MMF-302 is used primarily for two-wire smokes detectors in addition to normally open contact devices. The MMF-302-6 functions the same as the MMF-302 except it provides 6 Class B or 3 Class A inputs. The supervised IDCs (Initiating Device Circuits) can be wired to the modules as NFPA Style B (Class B) or Style D (Class A) circuits. The modules are supplied with a thermoplastic cover for mounting to a 4-inch mounting box. Monitor Module (miniature) The addressable MMF-301 module is functionally similar to an MMF-300 but offered in a smaller package for mounting directly in the electrical box of the monitored device. Control Module The CMF-300 and CMF-300-6 are an addressable Control Modules used to connect NACs (Notification Appliance Circuits) to power and supervise compatible, UL-listed notification appliances. The CMF-300 provides one Class B or Class A output while the CMF-300-6 provides 6 Class B or 3 Class A outputs. The NACs can be wired to the module as supervised NFPA Style Y (Class B) or Style Z (Class A) circuits. The modules are supplied with a thermoplastic cover for mounting to a 4-inch square mounting box. 068'31$ 3URGXFW'HVFULSWLRQ &RPSRQHQWV Relay Module The CRF-300 and CRF-300-6 are a Control Relay Modules which are functionally similar to the CMF-300 but used as Form-C relay modules. The CRF-300 provides one Form-C relay while the CRF-300-6 provides six Form-C relays. Isolator Module The I300 loop isolator module is an automatic switch which opens the circuit voltage to the SLC loop branch(es) whenever a wire-to-wire short circuit is detected on that loop. The remainder of the communications loop leading up to the I300 will continue to operate, unaffected by the short. The isolator module is bidirectional, meaning that it can detect a fault condition between the input SLC terminals or output SLC terminals. The I300 is required to meet NFPA Style 7 requirements. Detector Annunciator The RA400Z is a remote single LED annunciator that can be wired directly to an addressable detector for annunciation of that detector’s alarm status. Manual Pull Station The BG-12LX is an addressable manual pull station featuring a key-lock reset. The pull station responds to an address set by the installer using the built-in rotary decimal switches on the pull station. The manual pull station includes the Fire•Lite key. 1.6.3 300 Series Intelligent Addressable Devices Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UD FACP. The address of 300 Series devices cannot be set above 99. Compatible devices include: • • • • • • • • SD300 Photoelectric Detector SD300T Photoelectric Detector with Thermal Sensor CP300 Ionization Detector M300 Monitor Module M301 Miniature Monitor Module M302 2-wire Monitor Module C304 Control/Relay Module BG-10LX Manual Pull Station 1.6.4 Addressable Device Accessories End-of-Line Resistor Assembly Fire•Lite P/N R-47K The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-ofLine Resistor assembly is used to supervise the MMF-302 module circuit. The resistors are included with each module. Power Supervision Relay The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances. N-ELR Mounting Plate The N-ELR is a single End-of-Line resistor plate. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control module circuit. 068'31$ Optional Modules Product Description 1.7 Optional Modules The MS-9200UD main circuit board includes option module connectors for the following module: 4XTMF Transmitter Module The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervision of the module. 1.8 Accessories 1.8.1 PK-Plus Programming Utility The PK-Plus Programming Utility can be used to program an MS-9200UD directly from most IBM compatible computers, including laptops and portables, equipped with a serial port. MS-9200UD program files can also be created and stored on the PC and then downloaded to the control panel. The PK-Plus Kit includes the MS-9200UD Windows-based Programming Utility software on CD-ROM with on-line help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately, is required for connection of the PC to the RS-232 (PC/Printer) terminals at TB8 of the MS9200UD main circuit board. Refer to the illustration on page 10 and the section titled "Printer/PC" on page 40, for the location and connections to this terminal. 1.8.2 Dress Panel An optional dress panel is available for the MS-9200UD. The dress panel restricts access to the system wiring while allowing access to the key panel. CAUTION: HIGH VOLTAGE UNDER PANEL MS-9200UD PN 51906:A 12/10/02 dp9600.cdr !! WARNING !! SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS CONTROL UNIT DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING 21 3URGXFW'HVFULSWLRQ $FFHVVRULHV 1.8.3 Battery Box BB-26 The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box is red and is provided with knockouts. BB-55F The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 25 AH or one 60 AH battery may also be housed in the battery box. 1.8.4 Battery Charger 1.8.4.1 CHG-75 Battery Charger 7KH&+*LVFDSDEOHRIFKDUJLQJXSWR$+OHDGDFLGEDWWHULHVZLWKWKH06 8')$&37KH)$&3EDWWHU\FKDUJHUPXVWEHGLVDEOHGE\UHPRYLQJMXPSHU -3ZKHQXVLQJWKH&+*7KHFKDUJHUDQGXSWR$+EDWWHULHVFDQEHKRXVHG LQWKH)LUH/LWH%%EDWWHU\ER[/DUJHUEDWWHULHVDQGWKHFKDUJHUFDQEHKRXVHG LQWKH)LUH/LWH%%)EDWWHU\ER[ZKLFKFDQEHPRXQWHGXSWRIHHWDZD\IURP WKHFRQWUROSDQHO5HIHUWRWKH&+*0DQXDOIRUDGGLWLRQDOLQIRUPDWLRQ 1.8.4.2 CHG-120F Battery Charger Reference Manual 7KH&+*)LVFDSDEOHRIFKDUJLQJXSWR$+OHDGDFLGEDWWHULHVZLWKWKH 068')$&37KH)$&3EDWWHU\FKDUJHUPXVWEHGLVDEOHGE\UHPRYLQJ MXPSHU-3ZKHQXVLQJWKH&+*)7KHEDWWHULHVDQGFKDUJHUFDQEHKRXVHGLQ WKH)LUH/LWH%%)EDWWHU\ER[ZKLFKFDQEHPRXQWHGXSWRIHHWDZD\IURPWKH FRQWUROSDQHO1RWHWKDWZKHQXVLQJWKH%%)IRUKRXVLQJWKHFKDUJHUDQG EDWWHULHVJUHDWHUWKDQ$+PXOWLSOH%%)VDUHUHTXLUHG5HIHUWRWKH &+*)0DQXDOIRUDGGLWLRQDOLQIRUPDWLRQ 068'31$ $FFHVVRULHV 3URGXFW'HVFULSWLRQ 1.8.5 Annunciators ACM Series LED Zone Type Annunciators The ACM Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the MS-9200UD. Reference Manual • • • • • • • 068'31$ ACM-16ATF Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and will accept up to three AEM-16ATF Expanders. AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs AFM-16ATF Annunciator Fixed Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It is fixed at address ‘1.’ ACM-32AF Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It has rotary address switches and will accept one AEM-32AF Expander. AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs AFM-16AF Annunciator Fixed Module annunciates 16 alarm zones with 16 red alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It is fixed at address ‘1.’ AFM-32AF Annunciator Fixed Module annunciates 32 alarm zones with 32 red LEDs. 3URGXFW'HVFULSWLRQ *HWWLQJ6WDUWHG LCD-80F Remote Fire Annunciator The LCD-80F annunciator is a compact 80-character backlit LCD remote fire annunciator that is capable of displaying English language text. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the LCD80F is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Reference Manual Reference Manual Communications between the control panel and the annunciator is accomplished over a serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be connected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote UL listed filtered power supply such as the Fire•Lite FCPS Series. For more detailed information, refer to the LCD-80F manual. LDM Series Lamp Driver Modules (Graphic Annunciator) The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for a maximum of three expander modules. The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions. Refer to the LDM Series Lamp Driver Modules manual for a complete description. 1.9 Getting Started The following is a brief summary of the minimal steps involved in bringing an MS9200UD on-line: • Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page 27) • Address and Install Intelligent Devices (refer to the SLC Wiring Manual) • Enter Autoprogramming (refer to "Autoprogram" on page 49) • Resolve Programming Conflicts • Go to Point Program to Enter Specific Data (refer to "Point Program" on page 50). Use the right and left arrow keys to navigate between devices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larm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 36 for an illustration of the proper installation of this equipment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nstallation SECTION 2 The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems. 2.1 Mounting Backbox ! The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies. See Page ✓ Mark and predrill holes in the wall for the top two keyhole mounting bolts using the dimensions illustrated in Figure 2.3 on page 29 ✓ Install two upper fasteners in the wall with the screw heads protruding ✓ Using upper ‘keyholes,’ place backbox over the two screws, level and secure ✓ Mark and drill the lower two holes ✓ Install remaining fasteners and tighten ✓ Screw supplied standoffs onto mounting studs in locations indicated below ✓ When the location is dry and free of construction dust, install the main circuit board by aligning the 8 mounting holes in the circuit board with the 8 mounting standoffs in the backbox as illustrated below ✓ Secure the circuit board to the standoffs with the supplied screws as indicated in following figure MS-9200UD Main Circuit Board TB 2 TB 1 TB 3 TB 4 TB 7 NO NC C TB 5 TB 6 NO NC C NO NC C JP 4 1 2 3 + 24V - + 24V NON-RST RST POWER POWER + - REMOTEPWR SUPPLY SYNC JP 6 B+ A+ A- B1B+ 3B+ 3 B- 1 BNAC 1 CLASS A NAC 1 & 3 CLASSB B+ A+ A- B2B+ 4B+ 4 B- 2 BNAC 2 CLASS A NAC 2 & 4 CLASSB RELAY3 RELAY1 TB 8 OU T + NI + OU T - N I - TB 9 A CS L C SL C SL C SL C TB 10 S B+ A+ B- A- S HIE L D A B RELAY2 JP 2 JP 1 RE MOVE TO DI SABLE GND . FLT. 4XTMF 1 2 3 JP 7 J5 J6 JP 3 CU T TO MONITOR 4XTMF SW1 KISS OFF CAUT ION! TRA N SFOR ME R 2 HIGH VOLTAGE PR I. AC TIVE LCD DIS PLAY TRA N SFOR ME R 1 J1 SEC. AC TIVE KEYPAD I/F J4 TB11 J13 J12 J3 J9 J10 HOT NEU T EARTH mounting studs - + BATTERY MIN I D IN KEYB OAR D CONN. PR I. PH ONE LIN E SEC. PH ONE LIN E 92udbdmn.cdr J7 JP 5 J11 mounting studs grounding stud MS-9200UD Backbox Figure 2.1 MS-9200UD Main Circuit Board Installation 068'31$ ,QVWDOODWLRQ 0RXQWLQJ7UDQVIRUPHU 2.2 Mounting Transformer One XRM-24(E) transformer is supplied standard with the control panel. An optional second XRM-24(E) transformer can be ordered and installed to provide maximum system power. Install the transformers in the locations indicated in the following illustration. 1. Mount the Standard XRM-24 Transformer in the lower transformer mounting location by positioning the wiring connector to the right as illustrated in the following figure. 2. Slide the bottom transformer mounting bracket into the embossed mounting pocket as illustrated. 3. Secure the top transformer mounting bracket to the mounting stud with the supplied screw. 4. If the optional second XRM-24 Transformer is being installed, mount it in the upper transformer mounting location by positioning the wiring connector to the right as illustrated in the following figure. 5. Slide the top transformer mounting bracket into the embossed mounting pocket as illustrated. 6. Secure the bottom transformer mounting bracket to the mounting stud with the supplied screw. 7. Connect the Standard XRM-24 Transformer plug to Transformer 1 Connector J10 on the FACP main circuit board 8. Connect the Optional XRM-24 Transformer plug to Transformer 2 Connector J11 on the FACP main circuit board. 9. Complete the installation as detailed in the following sections. Mounting Pocket Optional XRM-24 Transformer Mounting Studs Standard XRM-24 Transformer Mounting Pocket Figure 2.2 Transformer Mounting 068'31$ Mounting Transformer Installation 1.75“ 5.1 cm 2.00“ 2.00“ 2.00“ 2.00“ 2.00“ 2.00“ 4.45 cm 1.75“ 1.625“ (4.128 cm) 4.128 cm 1.62“ (4.11 cm) 1.63“ 4.1 cm 1.62“ 15.5“ (39.37 cm) 4.128 cm 1.625“ 12.00“ (30.48 cm) 4.1cm 1.62“ 1.453“ (3.69 cm) 10.0“ 25.4 cm 47.0cm 18.5“ 4.45cm 1.75“ 17.35 cm 6.83“ 4.45cm 1.75“ 4.1cm 1.583“ 1.63“ 4.128 cm 12.07 cm 4.75“ 1.50“ (3.81 cm) 9600encl.cdr 4.75“ 12.07 cm 1.75“ 4.45 cm Figure 2.3 MS-9200UD Cabinet Mounting MS-9200UD PN 51906:A 12/10/02 29 Installation Mounting Transformer Depth = 4.37" (11.1 cm) Top Door = 15.78" (40.08 cm) Backbox = 15.5" (39.37 cm) Depth = 4.78" (12.14 cm) Door = 18.67" (47.43 cm) Backbox = 18.5" (47.0 cm) Left Side Right Side Bottom 18.620" (47.3 cm) Depth = 4.75" (12.07 cm) 15.625" (39.688 cm) 21.620" (54.92 cm) Battery Box = 8.5" (21.59 cm) 9600cab.cdr 18.625" (47.308 cm) Trim Ring P/N:FC-TR Battery Box = 14.34" (36.42 cm) Figure 2.4 MS-9200UD Cabinet Dimensions 30 MS-9200UD PN 51906:A 12/10/02 Power Installation 2.3 Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized. 2.3.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, LCD DISPLAY J4 J1 60 Hz, 3.0 amps for the MS-9200UD or 240 VAC, 50 Hz, 1.5 amps for the MS-9200UDE. TB11 Overcurrent protection for this circuit must comply J9 with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 - + HOT NEUT EARTH BATTERY mm2) or larger wire with 600 volt insulation rating. Make certain that the AC mains circuit breaker is off before wiring any connections between the mains and the control panel. Connect wiring from the AC mains to TB11 on the FACP, being careful to observe proper connections. Connect a wire from the grounding stud in the cabinet to a known solid earth ground in the building. Refer to Figure 2.1 on page 27 for location of the stud. This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before installing the battery interconnect cable (refer to the following section). 2.3.2 Battery Power Interconnect Cable Before connecting the batteries to the FACP, make + certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer "Power Supply Calculations" on page 165, for calculation of the correct battery rating. - + See Page WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. 2.3.3 DC Power Output Connection All DC power outputs are power-limited and require a ferrite bead per FCC requirements (refer to "UL Power-limited Wiring Requirements" on page 35). Power-limited Resettable Power 0.5 amperes max., 24 VDC nominal filtered, resettable power can be drawn from TB1 Terminals 3(+) and 4(-) Power-limited Resettable or Nonresettable Power 0.5 amperes max., 24 VDC nominal filtered, resettable or nonresettable power can be drawn from TB1 Terminals 1(+) and 2(-) MS-9200UD PN 51906:A 12/10/02 JP4 1 2 3 TB1 + - + 1 2 3 4 92udtb1.cdr JP4 is used to configure TB1, Terminals 1 & 2 for: • Resettable Power - jumper pins 1 and 2 of JP4 as shown • Nonresettable Power - jumper pins 2 & 3 of JP4 Figure 2.5 Power Outputs - 24 VDC 31 ,QVWDOODWLRQ 5HOD\V 2.4 Relays The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive). Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors of power-limited and nonpowerlimited circuits. Refer to UL Power-limited wiring requirements. TB5 TB6 RELAY 3 RELAY 1 RELAY 2 NO NC C NO NC C NO NC C TB7 92udreyp.cdr Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail-safe relay which will transfer on any trouble or total power failure. Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories Figure 2.6 Relay Terminals 2.5 Notification Appliance Circuits See Page Reference Manual The control panel provides four Style Y (Class B) or two Style Z (Class A) NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to "Calculating the System Current Draw" on page 165). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the Fire•Lite FCPS Series field charger/power supplies. The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9200UD main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs" on page 33 for information on changing the NAC configuration to Style Z (Class A). 068'31$ 1RWLILFDWLRQ$SSOLDQFH&LUFXLWV ,QVWDOODWLRQ 2.5.1 Configuring NACs The Notification Appliance Circuits on the main circuit board are configured for Style Y (Class B) or Style Z (Class A) by properly orienting the NACKEY card in JP6 which is located at the top of the main circuit board near the NAC terminal blocks TB3 and TB4. The default configuration is for Style Y (Class B). Refer to Figure 2.7 for information on installing the NACKEY card. NACKEY Card • Style Z (Class A) - install NACKEY into JP6 with Class A pointing down toward circuit board as illustrated to the right. • Style Y (Class B) - install NACKEY into JP6 with Class B pointing down toward circuit board . NACKEY -PCA CLASS B CLASS A NACKEY must be inserted with text side facing in toward center of main circuit board as illustrated to the right. It is keyed to prevent incorrect insertion. 92nackey.cdr NACKEY -PCA JP6 Top edge of MS-9200UD Main Circuit Board TB3 TB4 NACKEY card slot JP6 Figure 2.7 NAC Configuration Using NACKEY 2.5.2 Style Y (Class B) NAC Wiring 4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7 kΩ, ½ watt P/N:71252 UL listed NAC 4 NAC 3 NAC 2 Polarized Bells + + + + Polarized Strobes + + + + Polarized Horns + + + + Notification Appliance Circuit polarity shown in alarm state circuit number TB3 B B B B + + - 1 3 3 1 B B B B + + - 2 4 4 2 Polarized Bells Polarized Strobes Polarized Horns Dummy Load all unused circuit 9200nacy.cdr NAC 1 TB4 Figure 2.8 NAC Style Y (Class B) Wiring 068'31$ Installation Remote Synchronization Output 2.5.3 Style Z (Class A) NAC Wiring 2 Style Z (Class A) Notification Appliance Circuits, supervised and power-limited Polarized Bell + + Polarized Strobe + + + + Polarized Horn NAC 1 Polarized Bell Polarized Strobe Polarized Horn B A A B + + - - B A A B + + - - 9200nacz.cdr Notification Appliance Circuit polarity shown in alarm state TB4 TB3 NAC 2 Figure 2.9 NAC Style Z (Class A) Wiring 2.6 Remote Synchronization Output Synchronization is a feature that controls the activationof notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in "Type" on page 90. Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB2 of the MS-9200UD to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP. The Remote Synchronization Output is power-limited and supervised and requires a ferrite bead (refer to "UL Power-limited Wiring Requirements" on page 35). A 4.7 kΩ resistor must be connected to the end of the wiring at the remote power supply. Remote Power Supply Sync Input Remote Sync Output 4.7 kΩ ELR TB1 MS-9200UD TB3 TB2 TB4 JP4 1 2 3 + 24V - + 24V NON-RST RST POWER POWER + - REMOTE PWR SUPPLY SYNC B+ A+ A- B1B+ 3B+ 3B- 1B- B+ A+ A- B2B+ 4B+ 4B- 2B- Figure 2.10 Remote Sync Output 34 MS-9200UD PN 51906:A 12/10/02 UL Power-limited Wiring Requirements Installation 2.7 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-9200UD is shown below. ),*85(7\SLFDO8/3RZHUOLPLWHG:LULQJ5HTXLUHPHQWV 3RZHUOLPLWHG&LUFXLWV 3RZHUOLPLWHG&LUFXLWV 1RQSRZHUOLPLWHG&LUFXLWV 1RQSRZHUOLPLWHG&LUFXLWV )HUULWH%HDGV )HUULWH%HDGV 3RZHUOLPLWHG&LUFXLWV maintain minimum 0.25” between power-limited and nonpower-limited circuits wiring $&3RZHU *URXQG6WUDS 1RQSRZHUOLPLWHG &LUFXLWV *URXQGLQJ6WXG XGXOSZFGU 7R%DWWHULHV *Ferrite Bead Installation Per FCC requirements, ferrite beads are required for the DC Power Outputs, Remote Power Supply Sync, ACS Output and SLC Circuit. Wrap wire around ferrite bead as shown. MS-9200UD PN 51906:A 12/10/02 Close ferrite bead. 35 ,QVWDOODWLRQ 'LJLWDO&RPPXQLFDWRU 2.8 Digital Communicator 7ZRLQGHSHQGHQWWHOHSKRQHOLQHVFDQEHFRQQHFWHGWRWKHFRQWUROSDQHO7HOHSKRQHOLQH FRQWUROFRPPDQGLVPDGHSRVVLEOHYLDGRXEOHOLQHVHL]XUHDVZHOODVXVDJHRIDQ5-; VW\OHLQWHUFRQQHFWLRQ1RWHWKDWLWLVFULWLFDOWKDWWKHSDQHO VGLJLWDOFRPPXQLFDWRUEH ORFDWHGDVWKHILUVWGHYLFHRQWKHLQFRPLQJWHOHSKRQHFLUFXLWWRSURSHUO\IXQFWLRQ Customer Premises Equipment and Wiring MS-9200UD Network Service Provider’s Facilities Computer RJ31X Jack Unused RJ-11 Jack MS-9200UD Telephone Line Telephone Network Demarcation Point Unused RJ-11 Jack Fax Machine Telephone Answering System Telephone Figure 2.1 DACT Installation 7KHFRQWUROSDQHO VGLJLWDOFRPPXQLFDWRULVEXLOWLQWRWKHPDLQFLUFXLWERDUG &RQQHFWLRQDQGZLULQJRIWZRSKRQHOLQHVLVUHTXLUHGDVVKRZQEHORZ (Secondary Lines) Incoming Telco Phone Lines Tip Ring KISSOFF PRI. ACTIVE J13 Green Wire Red Wire Tip Ring Ring To premise phones Tip Green Wire Red Wire (Primary Lines) Incoming Telco Phone Lines Ring To premise phones Tip 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Note:Shorting bars inside RJ31X Jack removed during male plug insertion SEC. ACTIVE J12 7 foot Cable MCBL-7 (ordered separately) PRI. PHONE LINE SEC. PHONE LINE Modular Female Connectors Male Plug Connectors Figure 2.2 Wiring Phone Jacks 068'31$ 2SWLRQDO0RGXOH,QVWDOODWLRQ ,QVWDOODWLRQ 2.9 Optional Module Installation WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. MS-9200UD Keypad/Display Removal Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display or access jumpers JP5 and JP7 or switch SW1, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/Display and rest the unit at the bottom of the main circuit board. Mounting Screw Access Hole TB2 TB1 TB3 TB4 TB7 NO NC C JP4 1 2 3 + 24V - + 24V NON-RST RST POWER POWER + - REMOTE PWR SUPPLY SYNC JP6 B+ A+ A- B1B+ 3B+ 3B- 1BNAC 1 CLASS A NAC 1 & 3 CLASS B B+ A+ A- B2B+ 4B+ 4B- 2BNAC 2 CLASS A NAC 2 & 4 CLASS B TB5 NO NC CTB6NO NC C RELAY 3 RELAY 1 TB8 OUT+ IN+ OUT- IN- TB9 ACS SLC SLC SLC SHIELD TB10SLC B+ A+ B- A- A B RELAY 2 JP2 JP1 REMOVE TO DISABLE GND. FLT. 4XTMF 1 2 3 JP7 J5 J6 JP3 CUT TO MONITOR 4XTMF SW1 J7 JP5 J11 KISSOFF CAUTION! TRANSFORMER 1 J1 SEC. ACTIVE KEYPAD I/F J4 TB11 J13 J12 J3 J9 J10 HOT NEUT EARTH - + BATTERY MINI DIN KEYBOARD CONN. PRI. PHONE LINE SEC. PHONE LINE 96dact1.cdr TRANSFORMER 2 HIGH VOLTAGE PRI. ACTIVE LCD DISPLAY Mounting Screw Access Holes Figure 2.3 Keypad/Display Removal 068'31$ ,QVWDOODWLRQ 2SWLRQDO0RGXOH,QVWDOODWLRQ 2.9.1 4XTMF Transmitter Module Installation The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service. Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems): Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings: Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UD. In addition, the System Trouble LED will turn on to indicate the Disconnect condition. Note: 4XTMF Module is not suitable for transmitting reverse polarity supervisory signal. }Remote Alarm (power-limited)* }Remote Trouble (power-limited)* } + - + 1 2 3 4 5 + 6 7 * Wiring from these terminals can exit the protected premises. Dummy load terminals No connection 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Municipal Box (nonpower-limited)* Box is not connected. Polarities are shown for module activation 4xtmfl.cdr Disconnect LED Disconnect Switch shown in disconnect position TBL Jumper Connect to FACP J10 & J11 Figure 2.4 4XTMF Transmitter Module 068'31$ Optional Module Installation Installation The following steps must be followed when installing the 4XTMF module: 1. Remove all power (Primary and Secodary) from the FACP before installing 4XTMF 2. Cut jumper JP3 on the main circuit board to allow the control panel to supervise the 4XTMF module 3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-9200UD main circuit board, being careful not to bend any pins 4. Secure 4XTMF module to standoffs with supplied screws. 5. Reapply power to the FACP 6. For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3 7. When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left 8. Test system for proper operation TB5 NO NC CTB6NO NC C Standoff RELAY 1 TB8 OUT+ IN+ OUT- IN- TB9 ACS SLC SLC SLC TB10 SLC B+ A+ B- A- SHIELD A B Standoff RELAY 2 JP2 JP1 J5 & J6 Connectors 1 2 3 4XTMF J5 4XTMF J6 Cut Jumper JP3 JP3 CUT TO MONITOR 4XTMF J7 KISSOFF J13 MS-9200UD SEC. ACTIVE J12 PRI. PHONE LINE SEC. PHONE LINE 92ud4xtm.cdr PRI. ACTIVE Figure 2.5 4XTMF Connectors to MS-9200UD Connectors NOTE: Jumper JP2 on the MS-9200UD main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be programmed as a supervisory relay. Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens MS-9200UD PN 51906:A 12/10/02 39 Installation Optional Module Installation 2.9.2 Printer/PC A serial printer or a PC (personal computer) may be connected to TB8 Terminals 1 - 4 on the FACP. The printer can be used to provide a hard-copy printout of real-time events, history file and walktest data. An IBM compatible PC can be connected to provide local FACP programming capabilities using the PK-Plus programming utility. Installation of either device requires panel programming to allow the FACP to communicate with the device. ! CAUTION! Do not connect a printer or PC to the MS-9200UD FACP if a ground fault exists on the control panel. Circuit damage may result. Remove all power (Primary and Secodary) before installing or removing any wiring. Installation Remote printers and PCs require separate primary power. Also required is the PRT/ PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/ PK-CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply power to the FACP and printer or PC. Note that a ground fault may occur on the FACP, dependent on the printer or PC being used, due to this connection. For this reason, it is important that there be no preexisting ground fault on the panel. Note that the printer may or may not be supervised as determined by user programming. Refer to "Printer/PC" on page 116. Red 5 4 3 2 1 White 9 8 7 6 Green PRT/PK-CABLE Black TX RCV DTR GRND ACS SLC SLC SLC SHIELD TB10 SLC B+ A+ B- A- A B Figure 2.6 Serial Printer and Computer Connections 9600tb7a.cdr TB8 OUT+ IN+ OUT- IN- TB9 Printer Configuration Refer to the documentation supplied with the printer for pertinent information about printer setup. Set the printer’s options as listed in the following table: COMMUNICATION SETUP BUFFER: DATA BITS: PARITY: STOP BIT: BAUD RATE: AUTOMATIC LINE FEED AUTOMATIC CARRIAGE RETURN LARGE 7 EVEN 1 STOP 2400/4800/9600 NO NO PC Configuration The Windows-based PK-Plus Programming Utility Kit contains CD-ROM with on-line help file. 40 MS-9200UD PN 51906:A 12/10/02 2SWLRQDO0RGXOH,QVWDOODWLRQ ,QVWDOODWLRQ 2.9.3 Digital Communicator and Annunciators 2.9.3.1 ACM-8RF Relay Control Module Reference Manual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niversal Bracket Installation 7KHRSWLRQDO%5.78QLYHUVDO%UDFNHWFDQEHXVHGWRPRXQWVSHFLILFPRGXOHV LQVLGHWKH068'FDELQHW7KH%5.7PRXQWVWRWZRVWXGVORFDWHGLQ WKHORZHUULJKWFRUQHURIWKHFRQWUROSDQHOFDELQHWDVLOOXVWUDWHGEHORZ,WLVVHFXUHG WRWKH3(0VWXGVRQWKHEDFNZDOORIWKHFDELQHWZLWKWZRVXSSOLHGKH[QXWV ,03257$17:KHQWKH%5.7LVLQVWDOOHGWKH068'FDELQHWFDQ KROGDPD[LPXPRIWZR$PS+RXUEDWWHULHVZLWKWKHRULHQWDWLRQLOOXVWUDWHG AC POWER MAINTENANCE FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED BATTERY TROUBLE GROUND 2 1 ABC 4 5 GHI 7 * DEF 6 JKL 8 PRS EVENT ALARM SILENCE CLR ENTER MNO 9 TUV 0 ACK/STEP 1st 3 ESC MODE # DRILL HOLD 2 SEC WXY RESET -/. QZ Mount BRKT-9600 to PEM studs on back of cabinet using supplied hex nuts. 92brkmnt.cdr RECALL MS-9200UD Cabinet Figure 2.7 BRKT-9600 Bracket Installation 068'31$ ,QVWDOODWLRQ 2SWLRQDO0RGXOH,QVWDOODWLRQ 0RGXOH,QVWDOODWLRQRQ%5.7 7KHIROORZLQJPRGXOHVFDQEHLQVWDOOHGLQVLGHWKH068'FDELQHWXVLQJWKH %5.78QLYHUVDO%UDFNHW ✓ UDACT-F Digital Alarm Communicator/Transmitter - installs at standoff location (A) ✓ ACM-8RF Annunciator Control Module (Relay) - installs at standoff location (A) 5HIHUWRWKHDSSURSULDWHPRGXOHPDQXDOIRUGHWDLOHGLQIRUPDWLRQRQPRGXOH RSHUDWLRQDQGZLULQJ 1. Install the two supplied standoffs in location (A) as indicated in Step 1 of the following illustration 2. Position the module bottom in the slot located in the bottom of the BRKT-9600 as indicated in Step 2 of the following illustration 3. Secure the module to the standoffs installed in the top of the BRKT-9600 with two mounting screws as indicated in Step 3 of the following illustration 4. Refer to the appropriate module manual for detailed information on wiring the module for power, communication, etc. 5. Install a maximum of two 12 Amp Hour batteries with the orientation illustrated in Figure 2.7. Larger batteries require a separate UL listed battery box 1RWH'RQRWEULQJZLULQJRUFRQGXLWLQWRWKHERWWRPRIWKHFDELQHWIRUWKLV DSSOLFDWLRQ BRKT-9600 BRKT-9600 (A) (A) BRKT-9600 standoffs mounting screws Step 1 module 96brcksd.cdr 9600brkt.cdr module Slot Step 2 Step 3 Figure 2.8 BRKT-9600 Module Installation Steps 068'31$ 2SWLRQDO0RGXOH,QVWDOODWLRQ ,QVWDOODWLRQ 2.9.3.3 ACM and AFM Series Annunciators $&0DQG$)06HULHV$QQXQFLDWRUVSURYLGHYLVXDOLQGLFDWLRQVRI)$&3VWDWXVLQ UHPRWHORFDWLRQV5HIHUWRWKHDSSURSULDWHDQQXQFLDWRUPDQXDOIRULQIRUPDWLRQRQ LQVWDOODWLRQZLULQJDQGRSHUDWLRQ $QQXQFLDWRUDGGUHVVLQJLVVSHFLILFWRWKH068'FRQWUROSDQHO7KHIROORZLQJ WDEOHGHVFULEHVWKHDQQXQFLDWRUDGGUHVVHVDQGWKHFRUUHVSRQGLQJDGGUHVVDEOH GHYLFHVWKDWZLOOEHDQQXQFLDWHGDWHDFKDQQXQFLDWRUDGGUHVV ACM Annunciator Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Annunciator Displays the Following Points 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 4 NACs SLC Loop, Module Addresses 1 - 64 not used SLC Loop, Module Addresses 65 - 99 not used not used SLC Loop, Detector Addresses 1 - 64 not used SLC Loop, Detector Addresses 65 - 99 not used not used not used not used not used not used not used not used not used 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 4 NACs SLC Loop, Module Addresses 1 - 64 not used SLC Loop, Module Addresses 65 - 99 not used not used SLC Loop, Detector Addresses 1 - 64 not used SLC Loop, Detector Addresses 65 - 99 not used not used not used 7KH068'PXVWEHSURJUDPPHGIRUWKHDQQXQFLDWRUVLQVWDOOHGRQWKHV\VWHP 5HIHUWR$QQXQFLDWRUV8'$&7RQSDJHIRULQIRUPDWLRQRQDQQXQFLDWRU SURJUDPPLQJ0DNHFHUWDLQWRSURJUDPWKHDQQXQFLDWRUDGGUHVVHVWKDWKDYHEHHQ SK\VLFDOO\LQVWDOOHGRQWKHV\VWHP 1RWH7KH*HQHUDO6\VWHP6WDWXV3RLQWVLQFOXGHWKHIROORZLQJ • • • • • • • • 068'31$ General Alarm General Trouble General Supervisory Alarm Silenced System Off Normal AC Loss Battery Fault NAC Fault 3URJUDPPLQJ SECTION 3 3URJUDPPLQJ'DWD(QWU\ Programming 3.1 Programming Data Entry Programming can be accomplished using the MS-9200UD keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board. The information presented in this section refers to programming the MS-9200UD via the onboard keypad. If an optional computer keyboard is connected to the MS-9200UD main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys. Keypad Keys 1st Event Home CLR Delete ESC Esc RECALL Insert * * # # A-Z A-Z 0-9 0-9 (on QZ key) Computer Keyboard Keys Space bar — — / / • • ENTER Enter ACK/STEP F1 SILENCE F2 DRILL F3 RESET F4 068'31$ 8VHU3URJUDPPLQJ 3URJUDPPLQJ 3.2 User Programming !! The MS-9200UD is completely field programmable and requires no special software skills. While programming the MS-9200UD, the fire protection capabilities of the control panel are enabled. Site-specific programming may be accomplished in three ways: • Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without the necessity of programming each device individually. Refer to "Autoprogram" on page 49 for a detailed description of Autoprogramming • Manual programming or editing, using the FACP keypad or a PC keyboard • Off-line Programming and Editing Feature - allows creation and editing of sitespecific custom programs using a Windows-based computer. For programs requiring a large amount of data entry, this method may be preferred. A PK-Plus programming kit can be ordered for this purpose The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below: FIRE-LITE ALARMS INC SYSTEM ALL NORMAL 10:00A 012102 Programming, Read Status and Manual Dial mode can be entered while the panel is in any mode of operation. If the panel is in alarm, the alarm condition must be acknowledged before entering any other mode. To access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE See Page Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status Mode which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to "Read Status" on page 141 for a detailed description of this feature. Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options. Pressing 3 will select the Manual Dial Mode which allows the user to enter a troubleshoot mode of operation. Exit Programming, Read Status and Manual Dial Mode The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data just entered will be lost. 068'31$ 3URJUDPPLQJ ,QLWLDO3RZHUXS User Programming Levels There are two user programming levels: • • User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change. 3.3 Initial Power-up The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system. After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and the following trouble message will be displayed. TROUBL IN SYSTEM NO DEVICES INSTALLED 09:03A 012102 3.4 Programming Screens Description See Page Three options are available when the Enter key is pressed: Read Status, Programming and Manual Dial Mode. The Read Status and Programming options have multiple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to "Master Programming Level" on page 48, for additional information on the various screens. The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice. Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is followed to view all option choices. 3.5 Programming and Passwords See Page There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in nonvolatile memory. The factory set passwords can be changed by the user as described in "Password Change" on page 117. If an invalid password is entered, the blinking cursor will return to the first password character position. To exit Programming, Read Status or Manual Dial mode at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved. 068'31$ 3URJUDPPLQJDQG3DVVZRUGV 3URJUDPPLQJ To access user Programming mode, press the Enter or Mode key. The LCD will display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE To enter the user Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER PASSWORD ***** Entering the Master level password (default 00000) will cause the following screen to appear: PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP If the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. 068'31$ 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO 3.6 Master Programming Level When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear: PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen. PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP Programming Screen #2 PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 068'31$ 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 3.6.1 Autoprogram PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is poweredup, it should be autoprogrammed. If the system is already programmed and Autoprogram is initiated, the system will only add default values for newly installed devices. When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop. While autoprogramming, the panel will display the following: AUTOPROGRAM AUTOPROGRAMMING! PLEASE WAIT Autoprogram Progress Screen When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display: # OF DET LOOP1 055 # OF MON LOOP1 035 # OF CON LOOP1 030 Autoprogram Result Screen #1 In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules installed. Pressing the ESC key will return the display to Programming Screen #1. 068'31$ 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO 3.6.2 Point Program PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 2, while viewing Programming Screen #1, will select the Point Program option and display the following screen: POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE Point Program Screen 3.6.2.1 Detector Programming 3UHVVLQJZKLOHYLHZLQJWKH3RLQW3URJUDP6FUHHQZLOODOORZWKHSURJUDPPHUWR DGGGHOHWHRUFKDQJHWKHSURJUDPPLQJRIDQDGGUHVVDEOHGHWHFWRU7KHIROORZLQJ VFUHHQZLOOEHGLVSOD\HGE\WKHFRQWUROSDQHO DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3.6.2.1.1 Add Detector 3UHVVLQJZKLOHYLHZLQJWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKHIROORZLQJVFUHHQ ZKLFKDOORZVWKHSURJUDPPHUWRDGGDQHZGHWHFWRUDGGUHVVWRSURJUDPPLQJ ADD DETECTOR ENTER DETECTOR# *** Add Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV :KHQWKHODVWGLJLWLVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG ADD DETECTOR DETECTOR# 005 IS ADDED 7KHSURJUDPPHUFDQFRQWLQXHDGGLQJGHWHFWRUVE\SUHVVLQJWKH(6&NH\ZKLFKZLOO UHWXUQWKHGLVSOD\WRWKH$GG'HWHFWRU6FUHHQ 068'31$ 0DVWHU3URJUDPPLQJ/HYHO DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3URJUDPPLQJ 3.6.2.1.2 Delete Detector 3UHVVLQJLQWKH'HWHFWRU6FUHHQZLOOGLVSOD\WKH'HOHWH'HWHFWRU6FUHHQZKLFK DOORZVWKHSURJUDPPHUWRGHOHWHDVSHFLILFGHWHFWRU DELETE DETECTOR ENTER DETECTOR# *** Delete Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV:KHQWKHODVW GLJLWLVNH\HGLQWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG DELETE DETECTOR DETECTOR# 005 IS DELETED 7KHSURJUDPPHUFDQFRQWLQXHGHOHWLQJGHWHFWRUVE\SUHVVLQJWKH(6&NH\ZKLFK ZLOOUHWXUQWKHGLVSOD\WRWKH'HOHWH'HWHFWRU6FUHHQ 3.6.2.1.3 Edit Detector TKHSURJUDPPHUFDQFKDQJHDGHWHFWRUVH[LVWLQJRUIDFWRU\GHIDXOWSURJUDPPLQJE\ SUHVVLQJLQWKH'HWHFWRU6FUHHQ7KHIROORZLQJVFUHHQZLOOEHGLVSOD\HG EDIT DETECTOR ENTER POINT ADDRESS *** Edit Detector Screen $IODVKLQJFXUVRUZLOODSSHDULQWKHSRVLWLRQRIWKHILUVWDVWHULVNWRWKHOHIW7KH SURJUDPPHUNH\VLQWKHWKUHHGLJLWGHWHFWRUDGGUHVVVXFKDV :KHQWKHODVWGLJLWLVNH\HGLQLIWKHVHOHFWHGDGGUHVVKDVQRWEHHQDGGHGWR SURJUDPPLQJDVFUHHQVKRZLQJLQIRUPDWLRQDERXWDGHYLFHZLWKWKHKLJKHVWDGGUHVV WKDWLVLQVWDOOHGZLOOEHGLVSOD\HG ,IQRGHWHFWRUVKDYHEHHQLQVWDOOHGRQWKHORRSWKHIROORZLQJZLOOEHGLVSOD\HG NO DETECTOR INSTALLED Edit Detector Screen #1 068'31$ 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO ,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJGHYLFHVXPPDU\VFUHHQV ZLOOEHGLVSOD\HG7KHVHVFUHHQVDOORZWKHSURJUDPPHUWRYLHZDOOGHYLFHVHWWLQJV DWDVLQJOHJODQFH3UHVVLQJWKHOHIWRUULJKWDUURZNH\VZLOODOORZWKHSURJUDPPHU WRUDSLGO\YLHZWKHGHYLFHVDWWKHSUHYLRXVRUQH[WDGGUHVV LILQVWDOOHG ,IDGHWHFWRU VXFKDVDSKRWRHOHFWULFGHWHFWRU ZLWKWKHVHOHFWHGDGGUHVVLVQRW SK\VLFDOO\LQVWDOOHGRQWKH6/&RUKDVDFRPPXQLFDWLRQIDXOWEXWWKHDGGUHVVLV SURJUDPPHGLQWKHV\VWHPWKHIROORZLQJVFUHHQZLOOEHGLVSOD\HG TROUBL SMOKE(PHOTO)ZNNN * 1D017 Edit Detector Screen #1 ,IWKHVHOHFWHGDGGUHVVKDVEHHQDGGHGWRSURJUDPPLQJDQGDGHWHFWRU VXFKDVD SKRWRHOHFWULFGHWHFWRU ZLWKWKHVHOHFWHGDGGUHVVLVSK\VLFDOO\LQVWDOOHGRQWKH6/& DQGLVFRPPXQLFDWLQJZLWKWKHFRQWUROSDQHOWKHIROORZLQJZLOOEHGLVSOD\HG NORMAL SMOKE (PHOTO) ZNNN V 1D017 Edit Detector Screen #1 7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGGHWHFWRUSUHVVWKHNH\ERDUGµGRZQ¶ DUURZNH\WRYLHZWKH(GLW'HWHFWRUVFUHHQV ,QWKHSUHFHGLQJH[DPSOH ✓ Normal - indicates that the detector with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓ - represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ ZNNN - represents the first of five possible software zones that the detector is assigned to (NNN = the three digit zone number from 000 - 099) ✓ V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) ✓ 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector and 017 = Detector Address 017) 068'31$ 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 7KHIROORZLQJH[DPSOHVVKRZWKHHGLWLQJRIDSKRWRHOHFWULFsmoke detector with address 017, located on the SLC loop: EDIT DETECTOR 1D017 1=ENABLED YES 2=TYPE SMOKE(PHOTO) 3=VERIFICATION OFF Edit Detector Screen #2 EDIT DETECTOR 1D017 1=WALKTEST NO 2=PAS NO 3=PRE-SIGNAL NO Edit Detector Screen #3 EDIT DETECTOR 1D017 1=ZONE ASSIGNMENT 00 ** ** ** ** Edit Detector Screen #4 EDIT DETECTOR 1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Detector Screen #5 (QDEOH'LVDEOH'HWHFWRU EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION Edit Detector Screen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✓ Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓ - represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the two digit zone number from 000 - 099) ✓ 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 012 = Module Address 012) ✓ W or * - indicates whether or not the device is programmed for Walktest (W = programmed for walktest, * = not programmed for walktest). 068'31$ 0DVWHU3URJUDPPLQJ/HYHO See Page 3URJUDPPLQJ ,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDFRQWUROPRGXOHDVFUHHQGLVSOD\LQJ LQIRUPDWLRQDERXWWKHFRQWUROPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDV VKRZQLQ(GLW0RGXOH6FUHHQIRU&RQWURO0RGXOHVRQSDJH ,IWKHVHOHFWHGDGGUHVVFRUUHVSRQGVWRDPRQLWRUPRGXOHDVFUHHQGLVSOD\LQJ LQIRUPDWLRQDERXWWKHPRGXOHZLWKWKHVHOHFWHGDGGUHVVZLOOEHGLVSOD\HGDV LOOXVWUDWHGLQWKHIROORZLQJ NORMAL MONITOR ZNNN 1M012 EDIT MONITOR 1M012 1=ENABLED YES 2=TYPE MONITOR Edit Monitor Screen #2 EDIT MONITOR 1=PRE-SIGNAL 2=PAS 1M012 NO NO Edit Monitor Screen #3 EDIT MONITOR 1M012 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Monitor Screen #4 EDIT MONITOR 1M012 1=ADJECTIVE/NOUN 2=DESCRIPTION ******************** Edit Monitor Screen #5 068'31$ 3URJUDPPLQJ 0DVWHU3URJUDPPLQJ/HYHO (QDEOH'LVDEOH0RGXOH 7R(QDEOHRU'LVDEOHWKHPRQLWRUPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW 0RGXOH6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG ZNNN SW 1M002 Edit Control Screen #1 ,QWKHSUHFHGLQJH[DPSOH ✓ Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) ✓ - represents the adjective and noun, which have been programmed, describing the location of the displayed device ✓ Control - indicates that the selected module is a control module ✓ S or * - represents Silenceable (S) or Nonsilenceable (*) ✓ W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled) ✓ ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from 000 - 099) ✓ 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module and 002 = Module Address 02) 068'31$ 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 7RFKDQJHWKHSURJUDPPLQJIRUWKHGLVSOD\HGPRGXOHSUHVVWKHNH\ERDUGGRZQ DUURZNH\WRYLHZWKHIROORZLQJ(GLW&RQWUROVFUHHQV EDIT CONTROL 1=ENABLED 2=TYPE CONTROL 3=SILENCEABLE YES YES Edit Control Screen #2 EDIT CONTROL 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Control Screen #3 EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Control Screen #4 EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 068'31$ (QDEOH'LVDEOH0RGXOH 7R(QDEOHRU'LVDEOHWKHFRQWUROPRGXOHSUHVVWKHNH\ZKLOHYLHZLQJWKH(GLW &RQWURO6FUHHQ(DFKSUHVVRIWKHNH\ZLOOWRJJOHWKHVFUHHQEHWZHHQ(QDEOHG Z000 10*00A 010801 1M001 After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing the Walktest Screen. The following screen will be displayed: WALKTEST RESULTS View Result Screen Use the up and down arrow keys to view all of the walktest results which will be displayed as illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. 068'31$ 0DVWHU3URJUDPPLQJ/HYHO 3URJUDPPLQJ 3.6.9 Option Modules PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 Options available for the MS-9200UD include ACM Series, Graphic and LCD annunciators, printer connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection for uploading and downloading panel data. Pressing 3 while viewing Programming Screen #3 will display the following screen: OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ONBOARD DACT 3=PRINTER/PC PR4800 Options Screen Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has been previously programmed into the system. 3.6.9.1 Annunciators/UDACT 3UHVVLQJZKLOHYLHZLQJWKH2SWLRQV6FUHHQZLOOFDXVHWKHFRQWUROSDQHOWRGLVSOD\ WKHIROORZLQJVFUHHQV ANNUNCIATOR 1=TERM ENABLED 2=ACS ENABLED 3=UDACT YES YES YES Annunciator Screen #1 ANNUNCIATOR 1=ACS INSTALLED Annunciator Screen #2 $7HUPLQDO0RGHDQQXQFLDWRU DQG$&60RGHDQQXQFLDWRUFDQEHLQVWDOOHGLQWKH 068'V\VWHP7RHQDEOHDQ\RIWKHVHGHYLFHVSUHVVWKHQXPEHU FRUUHVSRQGLQJWRWKHVHOHFWHGGHYLFHVKRZQLQ$QQXQFLDWRU6FUHHQVRWKDW INVREP 10:00A 010801 1D001 The information displayed in the above example provides the following information: • First line in display: ✓ The type of event; in this example TROUBL indicating a device trouble ✓ Device type identifier; in this example, SMOKE (PHOTO) indicates a Photoelectric smoke detector. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 51, "Edit Module Screen for Monitor Module" on page 61 and "Edit Module Screen for Control Modules" on page 70 for information on additional device types. • Second line in display: ✓ ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ✓ ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. • Third line in display: INVREP indicates an invalid reply from the addressable device. Other possible troubles include: ❒ SHORT - indicating a shorted circuit on an addressable device ❒ OPEN - indicating an open circuit on an addressable device ❒ DIRTY1 - maintenance alert indicating that a detector is near but below the allowed alarm limit and is in need of maintenance before the performance is compromised ❒ DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance since it has been within 80% of its alarm threshold for 24 hours ❒ INVREP - maintenance alert indicating a hardware problem in the detector ❒ TEST F - indicating a detector has failed the automatic test operation which functionally checks its sensing chamber and electronics ❒ INV ID - indicating that an incorrect device code (Type ID) has been programmed for an installed device (for example, Photo has been programmed but an Ion detector has been installed) • ❒ SW TBL - indicating a module has failed the testing of its Class A switching relay Fourth line in display: ✓ Time; the current time in this example is 10:00A which represents 10:00 AM ✓ Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 ✓ Device Address; 1D001 in this example 1 represents SLC Loop, D represents a detector and 001 represents device address 001 132 MS-9200UD PN 51906:A 12/10/02 Alarm Operation Operating Instructions Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the system Trouble LED to change from flashing to on steady. This block acknowledgment occurs regardless of the number of troubles, alarms and supervisory events active in the system. When the Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the ‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or after the Acknowledge/ Step key is pressed, the ‘clear trouble’ message is sent to the printer and history file. If all troubles clear and there are no supervisory or fire conditions active in the system, the system returns to normal mode operation and the System All Normal message is shown on the LCD display and sent to the history and printer files. The auto-restore feature will restore cleared troubles even if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except the Alarm Silenced LED will light. If multiple trouble conditions exist in the system, they will be automatically scrolled on the LCD display at a three second rate. If a combination of alarms, troubles and/or supervisory conditions simultaneously occur in the system, only the alarms are scrolled on the display. 4.5 Alarm Operation Alarm operation is similar to trouble operation with the following differences: • • • • • • • • • • • The piezo sounder produces a steady output as opposed to a pulsed output The Fire Alarm LED flashes 1 second On and 1 second Off The LCD displays Alarm along with the device name, type, address, adjective/ noun, associated zones and time/date Communicate the alarm to the Central Station Alarms latch and are not allowed to clear automatically Alarms activate software zones if so programmed Timers for Silence Inhibit, Autosilence and Trouble Reminder are started Alarms activate the general alarm relay and general alarm zone Z00 The trouble relay is not activated Store event in history buffer Terminate upload or download communications A typical alarm display would be as illustrated below: ALARM PULL STATION Z000 10:00A 010801 1M001 Note that the device type, which in this example is PULL STATION, can be any other programmable alarm type. The information displayed in the above example provides the following information: • First line in display: ✓ The type of event; in this example ALARM indicating an alarm condition ✓ Device type identifier; in this example, PULL STATION indicates a manual pull box. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 51, "Edit Module Screen for Monitor Module" on page 61 and "Edit Module Screen for Control Modules" on page 70 for information on additional device types. MS-9200UD PN 51906:A 12/10/02 133 Operating Instructions Supervisory Operation • Second line in display: ✓ ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ✓ ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. • Third line in display: Z000 indicates the zone programmed to this device which, in this example, is general alarm Zone 000. Note that a single device can be programmed to five different zones but only the first zone will be displayed. • Fourth line in display: ✓ Time; the current time in this example is 10:00A which represents 10:00 AM ✓ Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 ✓ Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module and 001 represents device address 001 4.6 Supervisory Operation Supervisory operation is similar to alarm operation but with the following differences: • The piezo sounder pulses ½ second On and ½ second Off • The Supervisory LED flashes ½ second On and ½ second Off • The LCD displays the status label Active Supervisory along with the device name, type, address, adjective/noun, associated zones and time/date • Communicate the supervisory condition to the Central Station • The supervisory relay is activated • The alarm relay is not activated • Silenced alarms are resounded • Timers are not started • Store event in history buffer • Terminate upload or download communications A typical Supervisory event would be displayed as illustrated in the following: ACTIVE SUPERVISORY Z000 10:00A 010801 1M001 Note that, like alarms, supervisory signals latch (except when programmed for supervisory autoresettable) and can be assigned to software zones. Supervisory alarms do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 133, for a description of the information displayed on the control panel LCD. 134 MS-9200UD PN 51906:A 12/10/02 Process Monitor Operation Operating Instructions 4.7 Process Monitor Operation Process Monitor operation will initiate the following events: • • • • • • • • The piezo sounder pulses ¼ second On and ¼ second Off The LCD displays a process monitor message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the process monitor condition to the Central Station Relays programmed for process monitoring will be activated The alarm relay is not activated Silenced alarms are not resounded Timers are not started Store event in history buffer Note that, like supervisories, process monitor signals latch (except when programmed for process monitor autoresettable) and can be assigned to software zones. 4.8 Hazard/Tornado Condition Operation Hazard/Tornado Condition operation will initiate the following events: • • • • • • • • • The piezo sounder pulses ½ second On, ½ second Off The LCD displays a hazard message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the hazard condition to the Central Station Relays programmed for hazard will be activated The alarm relay is not activated Silenced alarms are resounded Timers are not started Store event in history buffer Supervisory LED flashes ½ second On, ½ second Off Hazard conditions latch. They can be assigned to software zones. 4.9 Medical Alert Condition Operation Medical Alert Condition operation will initiate the following events: • • • • • • • • • The piezo sounder ½ second On, ½ second Off The LCD displays a medical alert message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the medical alert condition to the Central Station Relays programmed for medical alert will be activated The alarm relay is not activated Silenced alarms are resounded Timers are not started Store event in history buffer Supervisory LED flashes ½ second On, ½ second Off Medical alert conditions latch. They can be assigned to software zones. 4.10 NAC Operation There are four Style Y (Class B) or two Style Z (Class A) programmable NACs (Notification Appliance Circuits) resident on the MS-9200UD main circuit board. All NACs may be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded operation. Coded operation provides a choice between March Time, Temporal or California coding. MS-9200UD PN 51906:A 12/10/02 135 Operating Instructions Programmed Zone Operation 4.11 Programmed Zone Operation Each addressable detector and monitor module can be assigned to a maximum of five software alarm zones. A general alarm zone Z00 may be listed for output (control) points, but it is not necessary to list Z00 for input points, since this is the default zone for all alarm input devices. Zone Z00 is not activated by supervisory points. When an input device alarms and is not disabled, it activates all software zones assigned to it. An output device that is not disabled is turned on when any of the software zones to which it is programmed become active. Only alarms, hazards/tornado alerts can turn on any of the four main NACs. 4.12 Disable/Enable Operation Input points which are disabled do not cause an alarm or any zone activation. Disabled output points are held in the off state. All disabled points are treated as if they were in trouble, with the exception being the status label that will be displayed is DISABL. 4.13 Waterflow Circuits Operation If an alarm exists from a monitor module point that has a waterflow type code and its mapped NAC control module outputs are programmed for nonsilenceable operation, the Alarm Silence key will not function. Also, any output zone activated by a waterflow device will not be silenceable if the Waterflow Silenceable option is set to NO in system programming. 4.14 Detector Functions Maintenance Alert Each addressable detector is monitored by the control panel for its maintenance status. If a detector is near but below the allowed alarm limit, a ‘maintenance alert’ message will automatically be displayed, signaling that the detector is in need of servicing. Automatic Test Operation An automatic test of an addressable detector is performed each minute, resulting in a complete SLC loop test in approximately 5 hours (if the loop has the maximum number of devices installed). The detector’s sensing chamber and electronics are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. A System Reset will clear this trouble. Type Code Supervision The FACP monitors addressable hardware device codes at slow intervals. Mismatch of any type code, compared to the system program, will cause a device trouble. System Alarm Verification The control panel may be programmed to perform alarm verification to help eliminate the nuisance of false alarms. Alarm verification applies to smoke detectors only. Smoke Detector Data Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity of each detector at its location. A printout of each detector’s data can be retrieved from the FACP using an optional printer or Windows© HyperTerminal. Detector sensing ability can decrease with age and should be monitored as part of a system’s routine maintenance. 4.15 Time Functions: Real-Time Clock The MS-9200UD includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset. 136 MS-9200UD PN 51906:A 12/10/02 Synchronized NAC Operation Operating Instructions 4.16 Synchronized NAC Operation Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices. NAC synchronization can only be supported properly by the Remote Power Supply Sync Terminal, which follows NAC 1 programming. Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to operate. 4.17 Coded Operation The NAC circuits resident on the control panel main circuit board can be programmed for coded operation. The available pulse rates which can be programmed for coded operation are as follows: • • • Continuous: March Time: Temporal Code: • • California Code: Two-Stage Steady output with no pulsing Pulses at 120 ppm (pulses per minute) Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off 10 seconds On, 5 seconds Off Pulses at 20 ppm (pulses per minute) for 5 minutes and then changes to on steady 4.18 Presignal Presignal option programs an initiating device to delay the activation of NACs and/or control modules while allowing visual verification by a person. Once a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user programmed time duration of up to three minutes. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during the programmed time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon Presignal activation are as follows: ✓ ✓ ✓ ✓ onboard piezo sounds immediately control panel LCD display will indicate a presignal event and the active point control points programmed to Zone 98 will activate annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED ✓ outputs (NACs and control modules) of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes ✓ second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. MS-9200UD PN 51906:A 12/10/02 137 Operating Instructions Positive Alarm Sequence 4.19 Positive Alarm Sequence PAS (Positive Alarm Sequence) option will program an initiating device to delay panel activation (including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. When a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs are prevented from activating for 15 seconds. This inhibit time is factory set and cannot be changed. Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence the piezo sounder and start a timer which prevents activation of NACs for an additional time duration which can be user programmed for up to three minutes. After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during either time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon PAS activation are as follows: ✓ onboard piezo sounds immediately ✓ control panel LCD display will indicate a presignal event and the active point ✓ control points programmed to Zone 97 will activate ✓ annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED ✓ outputs (NACs and control modules) of associated zones will be inhibited from activating for a factory set duration of 15 seconds ✓ pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits output activation for additional time delay of up to three minutes which is user programmable ✓ second alarm occurring anytime during either time delay will cause immediate activation of all associated outputs ! PAS does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. PAS operation requires the approval of the local Authority Having Jurisdiction. Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS capability until the PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling devices will immediately place the control panel into alarm. This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. 138 MS-9200UD PN 51906:A 12/10/02 Special System Timers Operating Instructions 4.20 Special System Timers 4.20.1 Silence Inhibit Timer This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following an alarm. A new alarm during the initial 60 second period will not cause the timer to restart with a new 60 seconds. Silence Inhibit operation requires the approval of the local Authority Having Jurisdiction. 4.20.2 Autosilence Timer If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Having Jurisdiction. 4.20.3 Trouble Reminder If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the Alarm Silence key is pressed) and every two minutes during a trouble condition (after the Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder will occur until the alarm or fault is cleared. Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the trouble condition still exists. 4.20.4 Waterflow Retard Timer If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdiction. MS-9200UD PN 51906:A 12/10/02 139 Operating Instructions Walktest 4.20.5 Alarm Verification (None or One Minute) If alarm verification is selected, an addressable smoke detector's alarm is ignored for a retard time of 13 seconds and the detector's alarm condition is automatically reset. There will be no alarm indication at the FACP during the Retard period. A confirmation period of 47 seconds follows, during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs and indicate the alarm condition at the FACP. If a different detector alarms any time during the first detector's verification period, the panel will immediately activate all appropriate outputs and indicate the alarm condition at the FACP. If no additional detector alarms occur within 60 seconds of the first alarm (13 second retard plus 47 second confirmation), the timer resets and the panel is ready to verify any new detector alarms which may occur. 13 sec. 0 sec. Detector Alarm Verification (Retard + Confirmation) Detector Goes Into Alarm RETARD Alarm Ignored Different Detector Alarms During First Detector's Verification Period 60 sec. CONFIRMATION (47 seconds) Control Panel Processes Alarm if Same Detector is Still in Alarm Control Panel Immediately Processes Alarm Note: Alarm Verification is available only for addressable smoke detectors, not conventional smoke detectors. 4.21 Walktest Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but will store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest. Alarm/Shorted Condition When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those outputs have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an optional printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced with an asterisk (*). Open Condition Addressable devices as well as all main circuit board NACs are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs and control modules programmed for Walktest, then shut them off after eight seconds. While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. 140 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22 Read Status Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode. This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to prevent confusion. Read Status Entry When the operator presses the control panel Enter key, the LCD will display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view and print the programmed features and status of the control panel. The following screens will be displayed: READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Read Status Screen #1 READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NACS Read Status Screen #2 READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Read Status Screen #5 READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY READ STATUS 1=TIME-DATE Read Status Screen #3 Read Status Screen #6 MS-9200UD PN 51906:A 12/10/02 141 Operating Instructions Read Status 4.22.1 System Point READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed: Read Status Screen #1 READ SYSTEM POINT SELECT TYPE 1=DETECTOR 2=MODULE The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will change to the following screen: READ SYSTEM POINT ENTER DETECTOR# *** Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a detector with address 001 on the SLC loop is entered, a display similar to the following will appear: NORMAL SMOKE(PHOTO) NORTH CLASSROOM Z005 V 1D001 The information in the preceding display includes: 142 • NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.) • SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector) • NORTH CLASSROOM - the Adjective/Noun label for this device • Z005 - the first of five possible assigned software zones • 1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001 • V - Alarm Verification Enabled (V = Yes, * = No) • S - Silenceable for control modules (S = Yes, * = No) • W - Walktestable for control and monitor modules (W = Yes, * = No) MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information about the selected device, such as: • Enable/Disable Status • Device Type • Alarm Verification On/Off (for detectors) • Walktest Yes/No • PAS (Positive Alarm Sequence) Yes/No (for detectors and monitor modules) • Pre-Signal Yes/No (for detectors and monitor modules) • Zone Assignments (five maximum) • Adjective/Noun descriptor • Silenceable Yes/No (for control modules) 4.22.2 Zones READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed: Read Status Screen #1 ZONES 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zones Screen #1 ZONES 1=SPECIAL PURPOSE 2=ZONE TYPE Zones Screen #2 From the preceding screens, the control panel operator can view: MS-9200UD PN 51906:A 12/10/02 • Zones Installed - all software zones programmed into the system (99 maximum) • Zones Enabled - all software zones that are enabled • Zones Disabled - all software zones that have been disabled • Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal and 99 reserved for future use • Zone Type - the Type assigned to each installed zone (default is Alarm) 143 Operating Instructions Read Status 4.22.3 Power Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be displayed: POWER BATTERY 24 V RST 27.21V 25.31 Power Screen #1 CHARGER NAC 1 NAC 2 POWER 28.36V -1.49V -1.49V Power Screen #2 NAC 3 NAC 4 POWER -1.49V -1.49V Power Screen #3 A real-time display of the control panel voltages can be used to determine if a problem exists in the system. Note that Power Screen #3 will only be displayed if the NACKEY NAC option card is installed, in JP8 of the main circuit board, for Class B operation. The following table lists the circuit being measured, possible conditions and their respective voltage ranges: Circuit Condition Voltage Range Normal Battery (nominal) 27.05 to 28.15 VDC Low Battery 20.0 to 20.8 VDC No Battery 0 to 18.36 VDC 24V Resettable Normal 21.25 to 27.50 VDC 24V Nonresettable Normal 21.25 to 27.50 VDC Charger Normal 21.87 to 29.84 VDC Normal -1.3 to -1.6 VDC Open Circuit -2.3 to -2.5 VDC Short Circuit 0 to 1.0 VDC Battery NAC 1 or NAC 2 144 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22.4 Trouble Reminder READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NAC Pressing 1 while viewing Read Status Screen #2 will display the following screen: Read Status Screen #2 TROUBLE REMINDER TROUBLE REM ON The screen indicates whether the Trouble Reminder feature is On or Off. 4.22.5 Timers Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed: TIMERS PAS DELAY PRE SIGNAL WATERFLOW 000 000 000 TIMERS AC LOSS DELAY 4 These screens will indicate the delay time, in seconds, for each of the first three possible delay options. The AC Loss Delay time is displayed in hours. MS-9200UD PN 51906:A 12/10/02 145 Operating Instructions Read Status 4.22.6 NAC Pressing 3 while viewing Read Status Screen #2 will display the following screen: 1=NAC 1 2=NAC 2 NAC 3=NAC 3 4=NAC 4 Note that 3=NAC 3 and 4=NAC 4 will always be displayed regardless of how the NACKEY NAC option card is installed. The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed options for NAC 2, 3 to view the programmed options for NAC 3 or 4 to view the programmed options for NAC 4. The resulting screens will display the following information: • Enable/Disable Status • Circuit Type (Bell, Strobe, etc.) • Silenceable/Nonsilenceable • Auto Silence Enable/Disable and time delay (in minutes) • Coding Selection (Temporal, Steady, etc.) • Zone Assignments • Silence Inhibit Enabled/Disabled • Synchronization Type (System Sensor, Wheelock or Gentex) 4.22.7 Relays READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 Pressing 1 while viewing Read Status Screen #3 will display the following screen: RELAY 1=RELAY 1 2=RELAY 2 3=RELAY 3 The operator can view the programmed option for each relay by pressing the corresponding number key. 146 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22.8 Program Check Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be displayed: PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to one of the Notification Appliance Circuits. Use the up and down arrow keys to view all NACs. Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any output zones have not been programmed to at least one input zone. Use the up and down arrow keys to view all zones. Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to at least one output zone. Use the up and down arrow keys to view all zones. 4.22.9 History Pressing 3 while viewing Read Status Screen #3 will display the following screen: HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories, by pressing the corresponding number key. MS-9200UD PN 51906:A 12/10/02 147 Operating Instructions Read Status 4.22.10 Annunciators READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Pressing 1 while viewing Read Status Screen #4 will display the following screens: Read Status Screen #4 ANNUNCIATORS TERM ENABLED YES ACS ENABLED YES UDACT ENABLED NO Annunciator Screen #1 ANNUNCIATORS 1=ACS ADDRESS Annunciator Screen #2 Annunciator Screen #1 indicates if Terminal Mode, ACS Mode and UDACT options are enabled or disabled. Pressing ‘1’ while viewing Annunciator Screen #2 allows the operator to view the ACS Mode Annunciator addresses which have been programmed into the control panel. 4.22.11 Phone Line Pressing 2 while viewing Read Status Screen #4 will display the following screen: PHONE LINE PRIMARY TOUCHTONE SECONDARY TOUCHTONE This screen indicates the both the Primary and Secondary phone lines have been configured for touchtone dialing operation. 148 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22.12 Central Station READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Pressing 3 while viewing Read Status Screen #4 will display the following screens: Read Status Screen #4 CENTRAL STATION REPORTING ENABLED REPORT BOTH CALL LIMIT 10 Central Station Screen #1 CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE Central Station Screen #2 Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled, if the Reports will be sent to one or both the Primary and Secondary Central Station phone numbers and the Call Limit for DACT trouble calls within a 24 hour period. Central Station Screen #2 provides information on the Primary and Secondary Central Station programming which includes: MS-9200UD PN 51906:A 12/10/02 • Test Time Interval • Account Code • 24 Hour Test Time • Phone Number • Communication Format • Event Codes 149 Operating Instructions Read Status 4.22.13 Service Terminal READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Read Status Screen #5 Pressing 1 while viewing Read Status Screen #5 will display the following screens: SERVICE TERMINAL PANEL ID 2=TERMINAL 1 3=TERMINAL 2 Service Terminal Screen #1 SERVICE TERMINAL RING COUNT Service Terminal Screen #2 The Panel ID number is displayed as the first item in Service Terminal Screen #1. To view the phone number for each Service Terminal, press 2 for Terminal 1 or 3 for Terminal 2 while viewing Service Terminal Screen #1. The Ring Count is displayed in Service Terminal Screen #2. 4.22.14 Printer/PC Pressing 2 while viewing Read Status Screen #5 will display the following screens: PRINTER PC PRINTER PC PR4800 START BIT STOP BIT Printer/PC Screen #1 PRINTER PC DATA BITS PARITY Printer/PC Screen #2 The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. 150 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22.15 Print READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT To print program data or control panel status, press 3 while viewing Read Status Screen #5. The following screens will be displayed: Read Status Screen #5 PRINT 1=HISTORY 2=WALKTEST LOG 3=DETECTOR DATA Print Screen #1 PRINT 1=EXIT PRINTING Print Screen #2 Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory. Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on page 96 for additional information on the display. Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each addressable smoke detector connected to the system. A printout, similar to the following example, will be generated if an optional printer is connected to the FACP. DEVICE# DEVICE TYPE 1D001 1D002 1D003 1D004 1D005 1D006 1D007 1D008 1D009 SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) %DRIFT COMP 20 20 21 20 21 20 20 20 20 CHAMBER 1281 1281 1259 1309 1281 1322 1280 1215 1310 TIME/DATE 12:01AM 01-08-2001 12:01AM 01-08-2001 12:01AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 Chamber Value The Chamber value should be within the indicated range for the following smoke detectors: • SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.) • CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration of 0.50%/ft. to 1.44%/ft.) If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. MS-9200UD PN 51906:A 12/10/02 151 Operating Instructions Read Status Drift Compensation Drift compensation uses software algorithms that identify and compensate for longterm changes in the data readings from each addressable smoke detector. These longterm changes in detector data readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift compensation performs the following functions: • Allows a smoke detector to retain its original ability to detect actual smoke and resist false alarms, even as dirt and dust accumulate • Reduces maintenance requirements by allowing the control panel to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove transient noise signals, usually caused by electrical interference. Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector performance. When a detector reaches an unacceptable level, the control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance alert: Maintenance Level FACP Status Displays Indicates Low Chamber Value INVREP A hardware problem in the detector Maintenance Alert DIRTY1 Dust accumulation that is near but below the allowed limit. DIRTY 1 indicates the need for maintenance before the performance of the detector is compromised Maintenance Urgent DIRTY2 Dust accumulation above the allowed limit. Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: Maintenance Urgent DIRTY Maintenance Alert Acceptable Range Low Chamber Reading LOW VALUE Figure 4.1 Diagram of Maintenance Levels 152 MS-9200UD PN 51906:A 12/10/02 Read Status Operating Instructions 4.22.16 Time-Date READ STATUS 1=TIME-DATE The operator can view the daylight savings time and the month and week when daylight savings time will begin and end. Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED YES START MONTH APR START WEEK WEEK-1 DAYLIGHT SAVINGS END MONTH OCT END WEEK LAST-W MS-9200UD PN 51906:A 12/10/02 153 Central Station Communications SECTION 5 Read Status Central Station Communications The control panel transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately. The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will blink, the LCD display will indicate the phone line trouble and the trouble condition will be reported to the Central Station over the remaining operational phone line. The control panel comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any local premises phones sharing the same telephone line. All transmissions to the Central Stations will be sent over the primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup secondary phone line. Two phone numbers must be programmed, the primary Central Station phone number and the secondary Central Station phone number. All system reports will be transmitted to the primary Central Station phone number. Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful. If 10 total attempts to communicate are unsuccessful, a Communicator Failure report will be displayed. Note that as an option, all reports may also be sent to the secondary Central Station phone number. The MS-9200UD meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is: 1. Zone Alarms and Restores 2. Zone Troubles and Restores 3. System Troubles and Restores 4. 24-hour Test 154 MS-9200UD PN 51906:A 12/10/02 Read Status Central Station Communications The control panel is capable of reporting detailed messages depending upon the format in use. Table 5.1 shows the reporting structure for all formats. Table 5.1 Format Selection Format Format Format Format Report 3+1/4+1/Standard 4+1 Express 3+1/4+1/Expanded 4+2/Standard 4+2 Express 4+2/Expanded Alarm SSS(S) A SSS(S) A AAA(A) Z SSSS AA2 SSSS AZ Alarm Restore SSS(S) RA SSS(S) RA RARARA(RA) Z SSSS RARA2 SSSS RAZ Zone Trouble (Zone Open) SSS(S) TZ SSS(S) TZ TZTZTZ(TZ) Z SSSS TZTZ2 SSSS TZZ Zone Trouble Restore SSS(S) RTZ SSS(S) RTZ RTZRTZRTZ(RTZ) Z SSSS RTZRTZ2 SSSS RTZZ System Trouble SSS(S) TS SSS(S) TS TSTSTS(TS) Y SSSS TSTS2 SSSS TSY System Trouble Restore SSS(S) RTS SSS(S) RTS RTSRTSRTS(RTS) Y SSSS RTSRTS2 SSSS RTSY Zone Disable SSS(S) DZ SSS(S) DZ DZDZDZ(DZ) Z SSSS DZDZ2 SSSS DZZ Zone Disable Restore SSS(S) RDZ SSS(S) RDZ RDZRDZRDZ(RDZ) Z SSSS RDZRDZ2 SSSS RDZZ Low Battery SSS(S) L SSS(S) L LLL(L) L2 SSSS LL2 SSSS LL2 Low Battery Restore SSS(S) RL SSS(S) RL RLRLRL(RL) RL2 SSSS RLRL2 SSSS RLRL2 AC Loss SSS(S) P SSS(S) P PPP(P) P2 SSSS PP2 SSSS PP2 AC Loss Restore SSS(S) RP SSS(S) RP RPRPRP(RP) RP2 SSSS RPRP2 SSSS RPRP2 Fire Drill SSS(S) FD SSS(S) FD FDFDFD(FD) FD2 SSSS FDFD2 SSSS FDFD2 Fire Drill Restore SSS(S) RFD SSS(S) RFD RFDRFDRFD(RFD) RFD2 SSSS RFDRFD2 SSSS RFDRFD2 Supervisory Condition SSS(S) V SSS(S) V VVV(V) Z SSSS VV2 SSSS VZ Supervisory Condition Restore SSS(S) RV SSS(S) RV RVRVRV(RV) Z SSSS RVRV2 SSSS RVZ Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2 Upload or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2 Refer to Table 5.2 for an explanation of each letter code in Table 5.1 . Refer to Table 5.3 for a list of compatible receivers. MS-9200UD PN 51906:A 12/10/02 155 Central Station Communications Read Status Table 5.2 Format Selection Address Explanation Where SSS or SSSS A A2 Z RA RA2 TZ TZ2 RTZ RTZ2 TS TS2 RTS RTS2 DZ DZ2 RDZ RDZ2 L L2 RL RL2 P P2 RP RP2 FD FD2 RFD RFD2 V V2 RV RV2 X X2 Y UD UD2 = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = 7= 8= 9= A= B= C= D= E= F= = = Subscriber ID Alarm (1st digit) Alarm (2nd digit) Zone Number Alarm Restore (1st digit) Alarm Restore (2nd digit) Zone Trouble (1st digit) Zone Trouble (2nd digit) Zone Trouble Restore (1st digit) Zone Trouble Restore (2nd digit) System Trouble (1st digit) System Trouble (2nd digit) System Trouble Restore (1st digit) System Trouble Restore (2nd digit) Zone Disable (1st digit) Zone Disable (2nd digit) Zone Disable Restore (1st digit) Zone Disable Restore (2nd digit) Low Battery (1st digit) Low Battery (2nd digit) Low Battery Restore (1st digit) Low Battery Restore (2nd digit) AC Loss (1st digit) AC Loss (2nd digit) AC Loss Restore (1st digit) AC Loss Restore (2nd digit) Fire Drill (1st digit) Fire Drill (2nd digit) Fire Drill Restore (1st digit) Fire Drill Restore (2nd digit) Supervisory Condition (1st digit) Supervisory Condition (2nd digit) Supervisory Condition Restore (1st digit) Supervisory Condition Restore (2nd digit) Test Report (1st digit) Test Report (2nd digit) A trouble corresponding to the following: Ground Fault Low Battery not used Telco Primary Line Fault Telco Secondary Line Fault Main Bell Fault, Annunciator Bell Communication Fault to Primary Number Communication Fault to Secondary Number System Off Normal Fault/System Fault (Slave Operation, see Chapter 6) Upload/download (1st digit) Upload/download (2nd digit) Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number and the second digit corresponding to any system trouble condition. Only the first digit is programmable. 156 MS-9200UD PN 51906:A 12/10/02 Transmittal Priorities Central Station Communications 5.1 Transmittal Priorities The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order: 1. Alarms (highest priority level) ✓ Pull stations ✓ Waterflow ✓ Smoke detector ✓ Other alarm types 2. Supervisory Zone 3. System Troubles ✓ Zone disabled ✓ Fire drill ✓ AC fail (after delay) ✓ Zonal faults ✓ Earth fault ✓ Low battery ✓ Telephone line fault ✓ Notification Appliance Circuits fault ✓ Communication trouble ✓ Annunciator trouble ✓ System off normal 4. Restoral Reports ✓ Zone alarm ✓ Supervisory ✓ Zone(s) enabled ✓ Fire drill ✓ AC ✓ Zone fault ✓ Earth ✓ Battery ✓ Telephone line ✓ Notification Appliance Circuits ✓ Communication ✓ Annunciator trouble ✓ System off normal 5. 24 Hour Test (lowest priority) Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted reports to the Central Station. The Kissoff LED may turn on several times during communications with a Central Station. MS-9200UD PN 51906:A 12/10/02 157 Central Station Communications Transmittal Priorities The table below shows UL listed receivers which are compatible with the MS-9200UD. ✔ 1 4+2 Ademco Express ✔ ✔ ✔ (8) 2 3+1/Standard/1800/2300 ✔ ✔ ✔ ✔ (4) ✔ 3 3+1/Expanded/1800/2300 ✔ ✔ ✔ ✔ (4) 4 3+1/Standard/1900/1400 ✔ ✔ 5 3+1/Expanded/1900/1400 ✔ ✔ 6 4+1/Standard/1800/2300 ✔ ✔ 7 4+1/Expanded/1800/2300 ✔ 8 4+1/Standard/1900/1400 9 Surguard MLR-2 (9) ✔ Sescoa 3000R (7) 4+1 Ademco Express Radionics 6500 (5) 0 Radionics 6000 (6) Osborne Hoffman Models 1 & 2 FBI CP220FB ITI CS-4000 (3) Format # (Addresses 16 & 42) Ademco 685 (1) Silent Knight 9000 (2) Table 5.3 Compatible UL Listed Receivers ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (4) ✔ ✔ ✔ ✔ (4) ✔ ✔ ✔ ✔ (4) ✔ ✔ ✔ ✔ ✔ (4) ✔ ✔ ✔ ✔ ✔ ✔ (4) ✔ ✔ ✔ 4+1/Expanded/1900/1400 ✔ ✔ ✔ (4) ✔ ✔ ✔ A 4+2/Standard/1800/2300 ✔ ✔ ✔ (4) ✔ ✔ ✔ B 4+2/Expanded/1800/2300 ✔ ✔ ✔ (4) ✔ ✔ ✔ C 4+2/Standard/1900/1400 ✔ ✔ ✔ (4) ✔ ✔ ✔ D 4+2/Expanded/1900/1400 ✔ ✔ ✔ (4) ✔ ✔ ✔ E Ademco Contact ID ✔ ✔ ✔ F Not Used ✔ ✔ ✔ ✔ ✔ ✔ ✔ 1. With 685-8 Line Card with Rev. 4.4d software 2. With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software 3. Rev. 4.0 software 4. FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software 5. Model 6500 with Rev. 600 software 6. Mode 6000 with Rev. 204 software 7. With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software 8. Model 2 only 9. Version 1.62 software 158 MS-9200UD PN 51906:A 12/10/02 Downloading Program Remote Site Upload/Download Remote Site Upload/Download SECTION 6 The control panel may be programmed or interrogated off-site via the public switched telephone network. Any personal computer with Windows™ 95 or greater, with a 14.4 Kbaud compatible modem and Fire•Lite Upload/Download software kit P/N PK-Plus, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status, system voltages, time and date. CAUTION: After successfully downloading a program, make certain to perform the following steps: 1. Print out all programmed data via Print Mode or manually view programmed entries and compare to intended program data 2. Test all affected panel operations 3. Immediately correct any problems found 6.1 Downloading Program The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a secret code is loaded in by a Service Terminal. Future upload or download requests cause verification of the secret code by the control panel before processing of data is allowed. If the secret code is not verified, the control panel will terminate the request. While the control panel is communicating with the Service Terminal, one of the DACT’s red phone line active LEDs will remain on steady. At the conclusion of a successful download, the green Kissoff LED will turn on steady for five seconds and the red phone line active LED will turn off. In order to download the panel (whether initiated at the jobsite or remotely), the following must be true: ✓ The control panel must be in the Normal Mode of operation. Downloading is not possible if the panel is in any other mode ✓ There cannot be any active communications ongoing with a Central Station receiver ✓ All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station Two basic communication mechanisms are supported as follows: • Download with callback - the Service Terminal calls the control panel. The control panel answers the call, confirms the calling party then hangs up. The Service Terminal then waits for a callback from the control panel. After the control panel calls the Central Station and successfully reports that a request for downloading has been received, the control panel calls the Service Terminal back. Upon secret code verification, data transfers occur. When the data transfers are completed and the Service Terminal disconnects from the control panel, the panel calls the Central Station back to confirm either successful or unsuccessful results. • Download with callback disabled - the Service Terminal calls the control panel. No hang-up sequence occurs. Data transfers proceed. Note that Callback enable/disable is controlled by the master user at the Service Terminal on a per call basis. MS-9200UD PN 51906:A 12/10/02 159 Remote Site Upload/Download Downloading Program Anytime a download with callback is initiated, the first thing the control panel will do is one of the following: • contact the primary Central Station • contact the primary and secondary Central Stations • contact the first available Central Station phone number Once contact has been established, the control panel will report a ‘request for upload/ download’ message. Following ‘kissoff’ of the request by the Central Station(s), the control panel will then call the appropriate Service Terminal and begin the downloading process. Any time a download with callback disabled is initiated, the control panel and the Service Terminal will communicate and transfer data without first contacting a Central Station. When the data transfers are completed and the control panel disconnects from the Service Terminal, the control panel will call the Central Station and report one of the following conditions: • Upload/download request received • Upload and/or download request successful • Upload/download failed To prevent the 'request for upload/download' message(s) from being reported to the Central Station(s), make certain to disable all upload/download reports back to both Central Stations. During the downloading process, the fire protection remains active. Should a system trouble or alarm condition occur, the control panel immediately terminates downloading and processes the trouble or alarm locally and transmits the information to the Central Station(s). 6.1.1 Security Features Remote site upload and download with the control panel has been carefully designed to include key security features to ensure proper functionality. The key features are listed and explained below. Secret Code Verification A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code is created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of data, the control panel will verify the secret code transmitted by the Service Terminal. Time-out at Control Panel Upon answering an incoming call on either the primary or secondary Central Station phone line, the control panel will listen for a modem connection signal. If this signal is not received within 30 seconds, the control panel will disconnect the call. Upon successful connection (secret code verified and callback completed if applicable), if no communication occurs within five minutes, the panel will disconnect the call. Callback to Service Terminal Any time the control panel is requested to allow an upload or download, it will confirm the source of the incoming call, hang-up and call back the calling party (Service Terminal phone number). 160 MS-9200UD PN 51906:A 12/10/02 Downloading Program Remote Site Upload/Download Panel Identification Number The panel identification number is typically used to identify the panel to the Service Terminal when the control panel calls the Service Terminal. If more than one call comes into the Service Terminal, the control panel ID number is used to sort out the calling parties. Another use of this code allows for identical secret codes to be placed into multiple control panels at one jobsite, using the panel ID number to distinguish between the individual panels. Error Checking As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors occur, the call is disconnected and the report that the upload/download was not successful is called to the Central Station(s). Central Station Acknowledge There is an option, referred to as the ‘callback’ option, whereby the control panel will report to one or both Central Stations that a request for uploading or downloading has been received prior to processing the call. If the Central Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited. If acknowledged by the Central Station(s), another message is transmitted, informing the Central Station(s) that: • Downloading was successful • Uploading was successful • Uploading/downloading was not successful Central Station Data Protection The primary and secondary Central Station phone numbers, communications format, account code, test time and programmable event codes are vital Central Station information. These blocks of data are protected from partial programming due to faulty phone connections, line noise and other errors. This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors. MS-9200UD PN 51906:A 12/10/02 161 Remote Site Upload/Download Downloading Initiated at Control Panel 6.2 Downloading Initiated at Control Panel Before initiating the download procedure, make certain that the control panel is: ✓ In Normal Mode ✓ Central Station communications are off ✓ The communicator is in the standby state (red phone line active LEDs are off and Kissoff LEDs are off) Place the control panel into Program Mode and program one or both of the Service Terminal phone numbers. It is also advisable at this time to program the Panel Identification Number. This will allow the Service Terminal to easily identify incoming calls. Program the control panel for download operation. The control panel will now call the appropriate Service Terminal phone number and the downloading process will begin. Once the called Service Terminal identifies the incoming call (control panel), the downloading process is allowed to continue. Downloading progresses until all programmed information has been successfully loaded into the control panel. 6.3 Downloading Initiated at a Service Terminal Before initiating the download procedure, make certain that the control panel is: ✓ In Normal Mode ✓ Central Station communications are off ✓ The communicator is in the standby state (red phone line active LEDs are off and Kissoff LEDs are off) Once the control panel accepts/answers an incoming call, the panel will: 1. Establish basic modem connection 2. Verify secret code and panel identification number 3. Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9 will occur. If no callback is requested, only steps 8 and 9 will occur 4. Identify the Service Terminal location 5. Hang-up/disconnect call 6. Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If this message is accepted, the control panel will proceed to the next step 7. Return call to Service Terminal 8. After security clearance, begin downloading 9. Upon completion of download, call Central Station(s) back and report either a successful download or failed upload/download message (if programmed to do so) 162 MS-9200UD PN 51906:A 12/10/02 Uploading Initiated at a Service Terminal Remote Site Upload/Download 6.4 Uploading Initiated at a Service Terminal Items that may be uploaded from the control panel to a Service Terminal are: • All programmed data plus the real-time clock, time and date • Entire Walktest data file • Troubleshoot Mode system voltages • Entire event History file • Current system status Uploading is possible at any time provided the following conditions are true: ✓ The control panel must be in the Normal Mode of operation. Uploading is not possible if the panel is in any other mode ✓ There cannot be any active communications ongoing with a Central Station receiver ✓ All active events must be successfully 'kissed-off' by the Central Station (the communicator must be in a standby state with no new information waiting to be transmitted to a Central Station) Once an incoming call is accepted/answered by the control panel, the panel will: 1. Establish basic modem connection 2. Verify secret code and panel identification number 3. Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9 will occur. If no callback is requested, only steps 8 and 9 will occur 4. Identify the Service Terminal location 5. Hang-up/disconnect call 6. Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If this message is accepted, the control panel will proceed to the next step 7. Return call to Service Terminal 8. After security clearance, begin uploading 9. Upon completion of upload, call Central Station(s) back and report either a successful upload or failed upload/download message (if programmed to do so). During the uploading process, the fire protection remains active. Should a system trouble or alarm condition occur, the control panel immediately terminates uploading and processes the trouble or alarm locally and transmits the information to the Central Station(s). MS-9200UD PN 51906:A 12/10/02 163 Power Supply Calculations Overview Power Supply Calculations SECTION 7 7.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1. Calculating the total amount of AC branch circuit current required to operate the system 2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load 3. Calculating the size of batteries required to support the system if an AC power loss occurs 4. Selecting the proper batteries for your system 7.2 Calculating the AC Branch Circuit The control panel requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the control panel. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2) wire with 600 volt insulation for this branch circuit. Use Table 7.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system. Table 7.1 AC Branch Circuit Requirements Device Type Number of Devices MS-9200UD or MS-9200UDE 1 Current Draw (AC amps) X 3.00 or 1.50 = CHG-75 [ ] X 2.05 = CHG-120F [ ] X 2.00 = [ ] X [ ] Sum Column for AC Branch Current Required 164 Total Current per Device = = MS-9200UD PN 51906:A 12/10/02 Calculating the System Current Draw Power Supply Calculations 7.3 Calculating the System Current Draw 7.3.1 Overview The control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column 1 in Table 7.3 on page 166. The control panel must support a larger load current during a fire alarm condition. To calculate the fire alarm load on the power supply, use Calculation Column 2 in Table 7.3 on page 166. The secondary power source (batteries) must be able to power the system during a primary power loss. To calculate the non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on page 166. When calculating current draw and the battery size, note the following: • ‘Primary’ refers to the main power source for the control panel • ‘Secondary’ refers to the control panel’s backup batteries • All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and microamperes to full amperes. Table 7.2 Converting to Full Amperes To convert... Multiply Milliamperes (mA) to amperes (A) mA x 0.001 Microamperes (µ A) to amperes (A) µ A x 0.000001 Example 3 mA x 0.001 = 0.003A 300 µ A x 0.000001 = 0.0003 A 7.3.2 How to Use Table 7.3 on page 166 to Calculate System Current Draw Use Table 7.3 on page 166 to calculate current draws as follows: 1. Enter the quantity of devices in all three columns 2. Enter the current draw where required. Refer to the Fire•Lite Device Compatibility Document for compatible devices and their current draw 3. Calculate the current draws for each in all columns 4. Sum the total current for each column 5. Copy the totals from Column 2 and Column 3 to Table 7.4 on page 167 Following are the types of current that can be entered into Table 7.3 on page 166: ✓ Calculation Column 1 - The primary supply current load that the control panel must support during a non-fire alarm condition, with AC power applied. ✓ Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied. ✓ Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm condition during a loss of AC power. MS-9200UD PN 51906:A 12/10/02 165 Power Supply Calculations Calculating the System Current Draw Table 7.3 contains columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 167. Table 7.3 System Current Draw Calculations Device Type Main Circuit Board ACM-8RF ACM-16ATF ACM-32AF AEM-16ATF AEM-32AF AFM-16ATF AFM-32AF AFM-16AF UDACT-F LDM-32F LDM-E32F LCD-80F 4XTMF 4-wire Detector Heads Power Supervision Relays6 CP350 SD350 SD350T H350 H350R D350P D350RP B501BH & B501BHT7 B224RB Relay Base B224BI Isolator Base MMF-300 MMF-300-10 MDF-300 MMF-301 MMF-302 MMF-302-6 BG-12LX CMF-300 CMF-300-6 CRF-300 CRF-300-6 I300 NAC #18 NAC #2 NAC #3 NAC #4 Current Draw from TB3 (nonalarm9) Sum each column10 for totals Calculation Column 1 Primary, Non-Fire Alarm Current (amps) Qty 1 Calculation Column 2 Primary, Fire Alarm Current (amps) Total 0.300 Qty 1 Calculation Column 3 Secondary, Non-Fire Alarm Current (amps) [ ] X[current draw]= X[0.300]= X[0.030]= [ ] X [current draw] = X[0.325]= X[0.158]1= [ ] X[current draw]= X[0.255]= X[0.030]= [ ] X[0.040] [ ] X[0.056]2= [ ] X[0.040]= [ ] X[0.002] [ ] X[0.018]2= [ ] X[0.002]= [ ] X[0.040] [ ] ] X[0.040]= X[0.025] [ ] X[0.056]2= X[0.065]2= [ [ ] [ ] 1 max. [ ] [ ] [ ] [ ] [ ] [ ] X[0.025]= X[0.040] [ ] X[0.075]= [ ] X[0.040]= [ [ [ [ [ ] ] ] ] ] X[0.040]= X[0.002]= X[0.025]= X[0.005]= X[ ]= X[0.040] X[0.002] X[0.064] X[0.005]= X[ ]5= [ [ [ [ [ ] ] ] ] ] X[0.056]3= [ ] X[0.025]= [ ] X[0.025]= [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.001]= X[0.00050]= X[0.00045]= X[0.00040]= X[0.00350]= X[0.00075]= X[0.000375]= X[0.00027]= X[0.00200]= X[0.00023]= X[0.00039]= X[0.00225]= X[0.00027]= X[0.00145]= X[0.00040]= [ ]= Primary Non-Alarm = Total 0.325 X[0.018]= X[0.064]= X[0.011]4= X[ ]= maximum alarm draw for all devices [ [ [ [ ] ] ] ] X[ X[ X[ X[ [ ] [ Primary Alarm = 0.400 Qty 1 [ ] X[0.025]= [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.001]= X[0.00050]= X[0.00045]= X[0.00040]= X[0.00350]= X[0.00075]= X[0.000375]= X[0.00027]= X[0.00200]= X[0.00023]= X[0.00039]= X[0.00225]= X[0.00027]= X[0.00145]= X[0.00040]= [ ] Total 0.255 ]= ]= ]= ]= ]= [ ]= Secondary Non-Alarm = Table Footnote 1. 2. 3. 4. All eight ACM-8RF relays activated on a single module. All annunciator LEDs on LDM-32F with LEDs on If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps. 5. Refer to the Device Compatibility Document for standby current. 6. Must use compatible listed Power Supervision Relay. 7. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source. 8. Current limitation of Terminal TB3 & TB4 circuits is 2.5 amps per NAC. 9. The total standby current must include both the nonresettable/resettable (TB1 Terminals 1 & 2) and resettable (TB1 Terminals 3 & 4) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB3 & TB4 circuits is 2.5 amps per NAC output and 0.5 amps per auxiliary power output 10.Total current draw listed above cannot exceed 6.0 amps. 166 MS-9200UD PN 51906:A 12/10/02 Calculating the Battery Size Power Supply Calculations 7.4 Calculating the Battery Size Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 7.4 as follows: 1. Enter the totals from Table 7.3 on page 166, Calculation Columns 2 and 3 where shown 2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below) 3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours 4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH) 5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door Table 7.4 Total Secondary Power Requirements at 24 VDC Secondary Standby Load (total from Table 7.3 Calculation Column 3) [ ] Required Standby Time (24 or 60 hours) Primary Alarm Load (total from Table 7.3 Calculation Column 2) Required Alarm Time (for 5 min., enter 0.084, for 10 min., enter 0.168) [ X[ = AH = AH Sum of Standby and Alarm Ampere Hours = AH Multiply by the Derating Factor X 1.2 Battery Size, Total Ampere Hours Required = ] X[ ] ] AH 7.4.1 NFPA Battery Requirements • NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm • NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power 7.4.2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 7.4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require a UL listed external battery charger and cabinet such as the BB-26, BB-55F or other UL listed external battery cabinet. MS-9200UD PN 51906:A 12/10/02 167 Software Zones Correlations Software Zones APPENDIX A A.1 Correlations Setup and configuration of an addressable system is different than a conventional system. In a conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, etc.) to zones is accomplished through wiring. The wiring is direct from clearly marked panel terminals to any device assigned to a particular zone. Connection of output devices (horns, bells, strobes, etc.) in a conventional system is accomplished by direct wiring of the output devices to Notification Appliance Circuit terminals. In an addressable system, a minimum of a single pair of wires (SLC communication loop) is used to connect all addressable input and output devices. Communications between the FACP (Fire Alarm Control Panel) and all addressable devices takes place over the wire pair which originates from the FACP. Software programming is used to configure the system as opposed to direct wiring. Zone assignments are created via software means, hence the term software zones. Setup of an MS-9200UD software zone is accomplished by panel programming. Each addressable device can be assigned to a maximum of five software zones. Each software zone, however, may have from 1 to 991 addressable input devices assigned to it and from 1 to 991 addressable output devices assigned to it. Monitor and control modules comprise one group of 991 addresses, with each module having a unique address from 1 to 991. Detectors comprise a separate group of 991 addresses, each detector having a unique address from 1 to 991 in its group. Be careful not to duplicate addresses within any one group (modules and detectors). Refer to the following page for an example of zoning. In the example on the following page: • Zone 01 has the following addressable devices assigned to it: ✓ SD350 smoke detectors with addresses 01 and 02 ✓ MMF-300 monitor module with address 01 ✓ MMF-302 monitor module with address 02 and 03 ✓ CMF-300 control modules with addresses 05, 06, 07, 09 and 13 • Zone 02 has the following addressable devices assigned to it: ✓ MMF-302 monitor module with addresses 02 and 03 ✓ CP350 smoke detectors with addresses 03 and 04 ✓ CMF-300 control modules with addresses 08, 09 and 10 • Zone 03 has the following addressable devices assigned to it: ✓ SD350 smoke detectors with addresses 05, 06 and 07 ✓ MMF-302 control module with address 04 ✓ CMF-300 control modules with addresses 09, 11 and 12 The example points out some of the key assignment features of the MS-9200UD. Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below). Be careful to properly plan the installation prior to installing any devices. 168 MS-9200UD PN 51906:A 12/10/02 Correlations Software Zones Correlation of Input and Output Zones Input Devices Zones SD350 01 Output Devices CMF-300 13 SD350 02 CMF-300 05 ZONE 01 MMF-300 01 CMF-300 06 MMF-302 02 CMF-300 07 CMF-300 09 MMF-302 03 CP350 03 ZONE 02 CMF-300 08 CMF-300 10 CP300 04 SD350 05 CMF-300 11 SD350 06 ZONE 03 SD350 07 CMF-300 12 MMF-302 04 The zone correlations which are shown graphically above are also presented in Table A.1 on page 170 and Table A.2 on page 171. MS-9200UD PN 51906:A 12/10/02 169 Software Zones Correlations Table A.1 Detector Programming Sheet Example Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 170 Device Type SD350 SD350 CP350 CP350 SD350 SD350 SD350 Zone Number 1 1 2 2 3 3 3 DETECTOR ZONE ASSIGNMENT ADJ/NOUN Address Device Type FIRST HALL 51 ELEV. LOBBY 52 2ND FLOOR 53 ROOM 210 54 3RD FLOOR 55 MEZZANINE 56 MECH. ROOM 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 Zone Number ADJ/NOUN MS-9200UD PN 51906:A 12/10/02 Correlations Software Zones Table A.2 Module Programming Sheet Example Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Device Type MMF-300 MMF-302 MMF-302 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 MS-9200UD PN 51906:A MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 1 51 1, 2 52 1, 2 53 3 54 1 55 1 56 1 57 2 58 1, 2, 3 59 2 60 3 61 3 62 1 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 12/10/02 ADJ/NOUN 171 Software Zones Correlations Table A.3 Blank Detector Programming Sheet - 1 of 2 Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 172 Device Type Zone Number DETECTOR ZONE ASSIGNMENT ADJ/ Address Device NOUN Type 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 Zone Number ADJ/NOUN MS-9200UD PN 51906:A 12/10/02 Correlations Software Zones Table A.4 Blank Module Programming Sheet - 1 of 2 Address Device Type 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 MS-9200UD PN 51906:A MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 12/10/02 ADJ/NOUN 173 Default Programming Correlations Default Programming APPENDIX B The following table provides a list of the programming options and their factory default settings. Program Option Factory Default Factory Default Detector Programming Not Installed Daylight Savings Yes Detector Type Smoke-Photo Month Start Daylight Savings April Detector Verification Off Week Start Daylight Savings 1st Week Detector Walktest Yes Month End Daylight Savings October Detector PAS No Week End Daylight Last Week Detector Presignal No Verification No Detector Zone Assign. 000 only (future) Detector Adj/Noun none PAS Timer 0 Module Programming Not Installed Presignal Timer 0 Module Type Monitor Waterflow Retard Timer 0 Module Walktest Yes NAC 1, 2, 3 & 4 Enable Enabled Module PAS No NAC 1, 2, 3 & 4 Silenceable Yes Module Presignal No NAC 1, 2, 3 & 4 Type Bell Module Zone Assign. 000 only NAC 1, 2, 3 & 4 Sync Type System Sensor Module Adj/Noun none NAC 1, 2, 3 & 4 Autosilence 0 Zone 0 Enable Enabled NAC 1, 2, 3 & 4 Coding Steady Zone 1 Enable Enabled NAC 1, 2, 3 & 4 Zones Zone 000 only Zone 2 Enable Enabled NAC 1, 2, 3 & 4 Silence Inhibit 0 Zone 3 Enable Enabled Relay 1 Alarm .........................through.......... ..................... Relay 2 Trouble (fixed) Zone 96 Enable Enabled Relay 3 Supervisory Zones 97, 98 & 99 Enabled (future) No Annunciator Terminal Mode No (future) 174 Program Option Loop Style Style 4 Annunciator ACS Mode Loop Protocol CLIP UDACT No Trouble Reminder Off ACS Installed No Banner Fire•Lite Onboard DACT No Time Format 12 Hr Printer-PC No Hours Setting 12 Printer Baud 9600 Minutes Setting 00 Second Settings 00 AM-PM Setting AM Month Setting 01 Day Setting 01 Year Setting 00 MS-9200UD PN 51906:A 12/10/02 Correlations NFPA Standard-Specific Requirements NFPA Standard-Specific Requirements APPENDIX C The Fire•Lite MS-9200UD has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below: MS-9200UD Control Panel Contains the main control board, cabinet (backbox and door), main power supply transformer and power supply. Batteries Refer to "Power Supply Calculations" on page 164, for Standby Power Requirements. Initiating Devices Connected to one of the control panel's Initiating Device Circuits. Notification Appliances Connected to the control panel's Notification Appliance Circuits via a control module. The following additional equipment is needed for compliance with the NFPA 72 standards listed below: NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR: NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in "Digital Alarm Communicator/Transmitter" on page 17. OR 4XTMF Transmitter Module for connection to the Fire•Lite RS82 Remote Station Receiver. See Figure C.2, “Remote Station Connection Using 4XTMF Module,” on page 177, for installation instructions for this unit. NFPA 72 Auxiliary Fire Alarm System 4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit must be installed as illustrated in the section titled "4XTMF Transmitter Module Installation" on page 38 and as outlined in Figure C.1, “Municipal Box Connected to 4XTMF Transmitter Module,” on page 176. NFPA 72 Proprietary Fire Alarm System MS-9200UD Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3, “Proprietary Protective Signaling System,” on page 178, for installation instructions for this unit. MS-9200UD PN 51906:A 12/10/02 175 NFPA Standard-Specific Requirements Correlations NFPA 72 Auxiliary Fire Alarm System All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions. Notes: 1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP3 on the MS-9200UD main circuit board to supervise placement of 4XTMF module and circuit. 3. Cut JP2 on the MS-9200UD main circuit board to enable FACP Supervisory relay. 4. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed information. Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module FIRE + Municipal Box Circuit Gamewell Model M34-56 Local Energy Municipal Box Polarities shown in alarm condition Nonpower-limited + - 4XTMF Figure C.4 Municipal Box Connected to 4XTMF Transmitter Module 176 MS-9200UD PN 51906:A 12/10/02 Correlations NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP3 on the MS-9200UD main circuit board to supervise placement of the 4XTMF module. 2. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed information. Fire•Lite RS82 Remote Station Receiver UL listed. Refer to Fire•Lite Instruction Manual for Remote Station Receiver Model RS82. + + - Polarity Shown is Normal Standby Power-limited (Dummy load with a 4.7KΩ, ¼ watt resistor when no connection is made) Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. 4XTMF Transmitter Module Figure C.2 Remote Station Connection Using 4XTMF Module MS-9200UD PN 51906:A 12/10/02 177 NFPA Standard-Specific Requirements Correlations NFPA 72 Proprietary Protective Signaling Systems MS-9200UD Addressable Fire Control Panel MS-9200UD Main Board Form-C Alarm contact programmed to activate on General Alarm. Form-C Trouble contact which will automatically activate on any Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9200UD and the transmitter are supervised by the transmitter. 2. This MS-9200UD/Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System. Figure C.3 Proprietary Protective Signaling System 178 MS-9200UD PN 51906:A 12/10/02 Correlations Wire Requirements Wire Requirements APPENDIX D T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m). Connecting external system accessories to the MS-9200UD main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length for each MS-9200UD circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200UD circuit. Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders (such as MA/SS-24D) instead of more electronically noisy notification appliances such as electromechanical bells or horns. Table D.1 MS-9200UD Wire Specifications CIRCUIT CONNECTIONS WIRE REQUIREMENTS Circuit Type Circuit Function Wire Type and Limitations SLC loop (power-limited) Connects to Addressable Devices Twisted, shielded pair, 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops1 ACS/TERM (EIA-485) (power-limited) EIA-232 (power-limited) Connects to annunciator modules connects to remote printer and PC computer Initiating Device Circuit MMF-300 and MMF-301 (power-limited) Wire Gauge and Compatible Brands Untwisted, unshielded pair Twisted, shielded pair with a characteristic impedance of 120 ohms Twisted, shielded pair 3,000 (900 m) 6,000 (1,800 m) 12 AWG (3.25 mm2): Genesis 4410, Signal 98230, Belden 9583, WPW999 14 AWG (2.00 mm2):Genesis 4408 & 4608 Signal 98430, Belden 9581, WPW995 16 AWG (1.30 mm2): Genesis 4406 & 4606 Signal 98630, Belden 9575, WPW991 Direct Burial Cable Isotec NP713110VNQ-S 18 AWG (0.75 mm2): Genesis 4402 & 4602 Signal 98300, Belden 9574, WPW975 Direct Burial Cable Isotec NP714110VNQ-S 12-18 AWG (3.25 - 0.75 mm2) 18 AWG (0.75 mm2) 50 (15 m) 18 AWG (0.75 mm2) minimum 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm2) 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm2) Distance limitation set by 1.2 volt maximum line drop Distance limitation set by 1.2 volt maximum line drop Distance limitation set by 1.2 volt maximum line drop 20 (6 m) 12-18 AWG (3.25 - 0.75 mm2) MMF-302 (power-limited) Initiating Device Circuit CMF-300 (power-limited) Notification Appliance Circuit Maximum loop wire resistance is 40 ohms for the MMF-300 and 20 ohms for the MMF-301 No more than a 2.4 volt drop allowed at end of circuit. Maximum loop wire resistance is 25 ohms In alarm, no more than a 1.2 volt drop allowed at end of circuit 24 VDC filtered resettable (power-limited) 24 VDC nonresettable (power-limited) Connects to 4-wire smoke detectors No more than 1.2 volt drop allowed from supply source to end of any branch Connects to control modules, annunciators and accessories Remote secondary power source No more than 1.2 volt drop allowed from supply source to end of any branch CHG-120F or CHG-75 Recommended Max. Distance Feet (meters) 10,000 (3,000 m) 8,000 (2,400 m) 4,875 (1,450 m) 3,225 (980 m) 12 AWG (3.25 mm2) in conduit 12-18 AWG (3.25 - 0.75 mm2) 12-18 AWG (3.25 - 0.75 mm2) 12-18 AWG (3.25 - 0.75 mm2) Table Footnote 1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection. MS-9200UD PN 51906:A 12/10/02 179 Notes 180 MS-9200UD PN 51906:A 12/10/02 Index Numerics 24 Hour Test Time 106 300 Series addressable devices 20 4XTMF module 177, 178 coil resistance 38 current 38 installation 38 installation steps 39 see also Transmitter Module 14, 21 supervisory relay config. 39 voltage 38 A AC Branch Circuit calculations 165 AC Loss Delay 88 AC Power 31 current 14 current, maximum 31 voltage 14 wiring 14, 31 Account Code 105 Acknowledge/Step 16, 130 ACM 23 ACM LED annunciator 43 ACM Series see also annunciator 23 ACM-16ATF Annunciator 23 ACM-32AF Annunciator 23 ACM-8RF 14 contact rating 41 mounting to BRKT-9600 42 see also Relay Control Module 41 ACS LED annunciator 14 add Detector 50 add Module 60 addressable 12 addressable detectors see also detectors 14 Addressable Device Accessories 20 addressable modules 19 see also modules 13 addressing annunciators 43 see also device addressing 81 see also module or detector addressing 19 Adjective control module 74 list 57 monitor module 67 multiple entries 59 AEM-16ATF Annunciator 23 AEM-32AF Annunciator 23 AFM annunciator 43 AFM-16AF Annunciator 23 AFM-16ATF Annunciator 23 AFM-32AF Annunciator 23 Alarm 134 MS-9200UD PN 51906:A 12/10/02 Alarm Silence 16, 130 alarm verification 13, 54, 137, 141 annunciator 23 ACM 14, 43 ACM-8RF 14 LCD-80F 14 LDM Graphic 14 annunciator addressing 43 annunciator, graphic see also LDM Series 24 annunciator, remote see also LCD-80F 24 Automatic Test Operation 137 Autoprogramming 13, 45, 49 Autosilence 13, 140 NAC 91 auxiliary DC power 31 B backbox 18 see also cabinet 30 Backup Reporting 103 Banner 82 setting 83 battery 18 cable connection 31 charger 17 charger capacity 14 Charging Circuit 14 see also secondary power 14, 31 battery box 22 battery charger 22 disable 14 external 22 baud rate 117 BB-55F see also battery box 18, 22 BG-10LX see also manual pull station 20 BG-12LX see also manual pull station 20 BRKT-9600 bracket installation 41, 42 C C304 Control/Relay Module 20 cabinet 18 dimensions 29, 30 cabinet mounting 27 Calculate System Current Draw 166 Calculating the Battery Size 168 Callback 161 Canadian Option 82, 94 Central Station 102, 162 account code 105 communications 155 phone number 106 Phone Numbers 104 report style 116 181 Index CHG-120F see also battery charger 22 see also remote battery charger 14 CHG-75 see also battery charger 22 see also remote battery charger 14 Clasic Loop Interface Protocol 81 Class A 19, 32 Class B 19, 32 NAC wiring 33 CLIP mode see also Classic Loop Interface Protocol 81 Clock Format 85 CMF-300 control module 19 Coded Operation 138 Coding NAC 91 communications format 107, 108 Control Buttons 130 control module 19 description display 76 display 70 edit 70 enable/disable 71 noun 75 noun/adjective 73, 74 silenceable 73 type 72 type codes 72 Correlations 169 CP300 Ionization Detector 20 CP350 18 CRF-300 relay module 20 current AC Power 31 availability 15 maximum 15 Current Draw Calculations 167 D D350P 19 D350R 19 DACT enable 98 onboard 98 data see also detector data and sensitivity 137 Data Entry via computer keyboard 44 via keypad 44 data values see also detector data and sensitivity 13 Date setting 85 Daylight Savings Time 85 DC power nonresettable 31 resettable 31 see also auxiliary DC power 31 182 Default Programming 175 Delete Detector 51 Delete Module 61 Description control module 76 detector label 59 monitor module 69 Detector 14 add 50 adding description 56 delete 51 edit 51 enable/disable 53 screen display 52 type 54 verification 54 Detector Annunciator 20 detector data 137, 152, 153 acceptable range 152 printout 152 Detector Programming 50 device addressing 81 Digital Communicator 25 dimensions cabinet 29 DIRTY1 153 DIRTY2 153 Disable 78 Disable Point Maintenance Level 123 Downloading 160, 163 dress panel 18, 21 drift compensation 13, 153 definition 153 Drill 16, 130 E earth ground 31 edit control module 70 detector 51 detector screens 52 module, monitor 61 EIA-232 40 for PC/Printer connection 15 see also Printer/PC interface 13 EIA-485 for ACS annunciators 15 for LCD-80F 15 Enable 77 Enable/Disable control module 71 detector 53 module, monitor 64 End-of-Line Resistor Assembly 20 Enter key 47 Erase History 95 Error Checking 162 MS-9200UD PN 51906:A 12/10/02 Index event codes 108 exiting programming 45, 46 Read Status 45, 46 F FACP see also Fire Alarm Control Panel 12 Features 12 Fire Alarm Control Panel see also FACP 12 Format Selection Address 156 Form-C relay 17, 32, 41 G general alarm zone 66 see also zone Z00 56 ground fault 40 H H350 19 H350R 19 Hazard Condition 136 History 95 erase 95 Maintenance Level 124 view events 95 History file 13 I I300 see also Isolator Module 20 Indicators 16 Installation 27 intelligent 12 Inventory 12 INVREP 153 Isolator Module 20 K Key Panel 16 function keys 16 service/program keys 16 keyboard and keypad 44 Keypad/Display removal and installation 37 L lamp test 16 LCD display 13, 16 LCD-80F annunciator 14, 24 LDM Series annunciator 24 LDM-32 Graphic Annunciator 14 LED AC Power 131 Alarm Silenced 131 Battery 131 Disabled 131 Fire Alarm 131 Ground 131 Kiss-off 131 Maintenance 131 Primary Line Active 131 MS-9200UD PN 51906:A 12/10/02 Secondary Line Active 131 see also Indicators 16 Supervisory 131 Trouble 131 LED annunciator 23 Local Energy Municipal Box Service 38 Loop Setup 81 M M300 Monitor Module 20 M301 Miniature Monitor Module 20 M302 2-wire Monitor Module 20 main circuit, mounting 27 Maintenance Alert 13, 137 levels 153 maintenance alert 153 Maintenance Program Level 2 46, 122 Manual Dial Mode 116 Manual programming 45 Manual Pull Station 20 Master Program Level 1 46, 48 MDF-300 monitor module 19 Medical Alert 136 MMF-300 monitor module 19 MMF-300-10 19 MMF-301 monitor module (miniature) 19 MMF-302 monitor module 19 Mode key 47 Module 13 add 60 addressing 19 delete 61 edit monitor 61 enable/disable 64 see also addressable modules 19 Module Programming 60 Monitor module 19 adjective 67 enable/disable 64 noun 68 noun/adjective 66 type 64 type action 65 Type list 64 type selection 65 Mounting cabinet 27 main circuit board 27 municipal box transmitter see also 4XTMF module 38 N NAC 14, 17, 88, 90, 136 Auto Silence 91 coded 138 coding 91 current 14 End-of-Line Resistor 14 power 12 183 Index see also Notification Appliance Circuit 12, 32 silence inhibit 92 silenceable 90 Style configuration 33 Style Y wiring diagram 33 synchronized 138 type codes 90 voltage drop 14 voltage, operating 14 wiring Style 32 NAC enable/disable 89 NAC options 82 NACKEY card 33 N-ELR Mounting Plate 20 NFPA 72 Auxiliary Fire Alarm System 176, 177 NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service 176 NFPA 72 Proprietary Fire Alarm System 176 NFPA 72 Proprietary Protective Signaling Systems 179 NFPA 72 Remote Station Protective Signaling System 178 NFPA Battery Requirements 168 NFPA Standard 176 nonpower-limited relay connections 32 Nonresettable Power 17 current 15, 31 nonsilenceable waterflow 80, 94 Normal 132 normal display 45 Notification Appliance Circuit 14, 88 see also NAC 12, 32 Noun list 58 monitor module 68 multiple entries 59 Noun/Adjective 56, 58 control module 73 monitor module 66 O Off-line Programming 45 Operating Instructions 130 Operation alarm 134 disable/enable 137 hazard condition 136 medical alert 136 NAC 136 normal 132 process monitor 136 programmed zone 137 supervisory 135 trouble 132 waterflow 137 Option Modules 21, 37, 97 annunciators/UDACT 97 184 Printer/PC 117 Options 12 Output Circuits 17 P Panel ID 100 Panel Identification Number 162 PAS 55, 78, 139 see also Positive Alarm Sequence 13, 54 selection 66 PAS BYPASS 139 PAS timer 86 Password 13, 46 change 118 Maintenance Level 2 47, 122 Master Level 1 47 PC (personal computer) configuration 40 connection 40 ground fault 40 Phone Number 106 Piezo see also sounder 16 PK-Plus Programming Utility 21 Point Program 50 Positive Alarm Sequence 54, 139 see also PAS 13 power NAC 12 nonresettable 15 resettable smoke 15 system 12 power supply calculations 165 power-limited relay connections 32 Power-up first time 46 Pre-signal 13, 55, 78 function 138 selection 66 Pre-signal Delay timer 87 Pre-signal timer 86 Primary Phone 99 primary power see also AC Power 31 printer baud rate 117 configuration 40 connection 40 ground fault 40 setup 40 Printer/PC interface 13 Process Monitor 136 Program check 120 check correlations 120 clear 119 Program Check MS-9200UD PN 51906:A 12/10/02 Index Maintenance Level 125 program keys see also Key Panel 16 Programming 44, 45 autoprogramming 45 exiting 45 factory default 175 Level 1 46 Level 2 46 manual 45 Master Level 1 48 modules 60 off-line computer 45 via computer keyboard 44 via panel keypad 44 Programming Levels 46 Programming Screens 46 Programming Sheet 171, 172, 173 Programming Utility see also PK-Plus 21 PRT/PK-CABLE for PC/Printer connection 40 R RA400Z see also detector annunciator 20 Read Status 45, 142 annunciators 149, 150 exiting 45 history 148 NAC 147 power 145 Print 152 printer/PC 151 program check 148 relay 147 system point 143 Time-Date 154 timers 146 trouble reminder 146 zones 144 Real-Time Clock 137 Recall/Increment Function 59, 69, 76 Receivers 159 Relay 14, 17, 32, 93 connections 32 contact rating 14, 17, 32 fixed 32 Form-C 14, 93 programmable 12, 17, 32 programming 93 selections 93 trouble 12, 17, 32 Relay Control Module see also ACM-8RF 41 relay module 20 Relay options 82 Remote Station Service 38 MS-9200UD PN 51906:A 12/10/02 remote switch functions 13 remote sync output 15 Remote Synchronization 34 REN see also Ringer Equivalence Number 25 Report Style 116 Reporting Enable 102 Reset 16, 130 Resettable Power 17, 31 current 31 see also Smoke Detector Power 15 Ring Count 102 Ringer Equivalence Number 25 S SD300 Photoelectric Detector 20 SD300T Photoelectric Detector 20 SD350 18 SD350T 18 Secondary Phone 99 Secondary Power Requirements 168 Secret Code 161 Security Features 161 sensitivity 137, 153 see also smoke detector sensitivity 137 Service Terminal 100, 101 Signal rate 13 Signaling Line Circuit see also SLC 14 Silence Inhibit 13, 92, 140 Silenceable control module 73 NAC 90 waterflow 94 silenceable circuits synchronized signals 90 Silenceable waterflow 80 SLC 13, 17 current 14 reference manual 14 resistance 14 see also Signaling Line Circuit 12, 14 Style 17 voltage 14 wiring length 14 SLC Loop Protocol 81 SLC Style 81 smoke detector chamber reading 152 data 137, 152 sensitivity 13, 137 Smoke Detector Power current 15 Software Zones 12, 169 sounder 16 Specifications 14 strobe synchronization 13 Style 12 185 Index Style B 19 Style D 19 Style Y 19, 32 NAC wiring 33 NC configuration 33 Style Z 19, 32 NAC configuration 33 wiring 34 subscreen 46 Supervisory 135 supervisory relay configuring for 4XTMF 39 sync programming 89 see also synchronization 92 sync output 15 current 15 End-of-Line resistor 15 voltage 15 synchronization 34, 138, 147 by manufacturer 92 programming 92 see also strobe synchronization 13 synchronized 138 synchronized signals 138 and silenceable circuits 90 System Maintenance Level 126 System Point 143 system power 12 System Setup 82 T Telephone Circuitry 25 Telephone Company Rights and Warnings 26 telephone line 36 Terminal 101, 102 Test Time Interval 105, 106 Time and Date Maintenance Level 127 Time setting 84 Time-Date setting 82, 84 Time-out 161 Timers 82 Transformer Assembly 18 Transmittal Priorities 158 Transmitter Module 38 see also 4XTMF module 21 Trouble 132 trouble display 133 trouble relay 12 Trouble Reminder 82, 140, 146 trouble responses 133 Type control module 72 detector 54 monitor module 64 186 NAC 90 type code control module 72 supervision 137 verification 13 U UDACT-F mounting to BRKT-9600 42 UL power-limited wiring requirements 35 see also power-limited and nonpower-limited 32 Upload/Download 160 Uploading 164 V Verification detector 54 Verify Loops 94 View Events 95 voltage measurements 145 ranges 145 W Walktest 13, 54, 73, 96 audible 96 Maintenance Level 126 operation 141 selection 66 silent 96 waterflow nonsilenceable 80, 94 silenceable 80, 94 Waterflow Delay timer 86, 87 Waterflow Retard Timer 140 Waterflow Silenceable 82 Wire Requirements 180 wiring AC Power 31 earth ground 31 NAC Style Y 33 NAC Style Z 34 wiring control modules see also Style Y or Style Z 19 wiring modules see also Style B or Style D 19 wiring Style 12 X XRM-24 see Transformer Z Z00 56, 66 Z97 PAS zone 55 Z98 55 Zone 97 78 Zone 98 78 Zone Assignment 56, 66, 92 control module 73 Zone Setup 77 MS-9200UD PN 51906:A 12/10/02 Index Maintenance Level 128 zone type 80 list 80 Zone Z97 55 Zone Z98 pre-signal zone 55 Zones 144, 169 see also software zones 12 Zones Disabled 79 Zones Enabled 79 Zones Installed 79 zones per device 56 MS-9200UD PN 51906:A 12/10/02 187 Notes 068'31$ Notes 068'31$ Notes 068'31$ Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer. This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident. THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. LimWarLg.p65 01/10/2000 World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Warning : Invalid secondary xref table Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Fill forms, Extract, Assemble, Print high-resEXIF Metadata provided by EXIF.tools