XTP product insert Rev. 1
XTP Series Temperature
Transmitter Probes
ProSense Temperature Transmitter Probes
Part Number Measuring Range* Thread Size Length
XTP25N-030-N40140F
-40 to 140°F (-40 to 60°C)
1/4” MNPT
30mm
XTP25N-050-N40140F 50mm
XTP25N-100-N40140F 100mm
XTP25N-150-N40140F 150mm
XTP50N-030-N40140F
1/2” MNPT
30mm
XTP50N-050-N40140F 50mm
XTP50N-100-N40140F 100mm
XTP50N-150-N40140F 150mm
XTP25N-030-0300F
0 to 300°F (-17.8 to 148.9°C)
1/4” MNPT
30mm
XTP25N-050-0300F 50mm
XTP25N-100-0300F 100mm
XTP25N-150-0300F 150mm
XTP50N-030-0300F
1/2” MNPT
30mm
XTP50N-050-0300F 50mm
XTP50N-100-0300F 100mm
XTP50N-150-0300F 150mm
XTP25N-030-0100C
0 to 100°C (32 to 212°F)
1/4” MNPT
30mm
XTP25N-050-0100C 50mm
XTP25N-100-0100C 100mm
XTP25N-150-0100C 150mm
XTP50N-030-0100C
1/2” MNPT
30mm
XTP50N-050-0100C 50mm
XTP50N-100-0100C 100mm
XTP50N-150-0100C 150mm
* Transmitter probes are factory configured and ready for use out of the box. If changes are
desired, transmitter probes can be re-configured. See Programming section of these
instructions.
71341491
XTP product insert Rev. 1
1 Safety Instructions
1.1 Designated use
• The device is a compact temperature transmitter
probe for the acquisition and conversion of
temperature input signals for industrial
temperature measurement.
1.2 Installation, commissioning, operation
• The device must only be installed, connected
and commissioned by qualified and authorized
staff (e.g. electrical technicians) strictly adhering
to the instructions contained in this manual, the
applicable norms, legal regulations and certificates
(depending on the application).
• These authorized staff members must have read
and understood this manual and follow the
instructions it contains.
• Damaged devices must not be put into operation
and they must be labeled as defective.
1.3 Operational safety
• The device is safely built and tested according to
state-of-the-art technology and has left the factory
in perfect condition in regards to technical safety.
The applicable regulations and European
standards have been taken into account.
• Please observe the technical data on the
nameplate!
• The device must only be powered by a power
supply unit with a limited energy electric circuit
in accordance with IEC 31010-1: “SELV or Class
2 circuit”.
• Due to its design, the device is not repairable.
When later disposing of the device, please observe
local regulations.
Installation
Pipe installation of the XPS Series
• A: On angle brackets
• B: In smaller pipes, inclined
• C: Perpendicular to the direction of flow
• L = Insertion Length
1. Seal the process connection with Teflon tape
before you screw in the device.
2. Install the device before the process
application is started.
Minimum insertion length
Lmin = 30mm (1.18 in)
A B
C
L
Temperature limits
Maximium flow velocity based on insertion length
L Insertion length, during flow
v Flow velocity
Medium water at T = 50 °C (122 °F)
v (ft/s)
0 1 2 3 4 5
L (in)
6
0
5
10
15
20
25
30
35
40
0 30 60 90 120 150
L (mm)
v (m/s)
0
15
30
45
60
75
90
105
120
135
Max. Ambient
Temperature
Max. Process
Temperature
Up to 25°C (77°F) 150°C (302°F)
Up to 40°C (104°F) 135°C (275°F)
Up to 60°C (140°F) 120°C (248°F)
Up to 85°C (185°F) 100°C (212°F)
Process pressure limits
• 1450 psig (100bar) maximum
XTP product insert Rev. 1
Wiring
1086
Operating
Region
Supply Voltage (VDC)
35 V10 V
Load ( )
RLmax = (Vpowersupply-10V) / 0.023 A (current output)
e.g. (24V - 10V) / 0.023A = 608Ω
Load Impedance
Dimensions
mm [inches]
Dimensions
A B
1.18 in [30mm] 3.98 in [101mm]
1.97 in [50mm] 4.76 in [121mm]
3.94 in [100mm] 6.73 in [171mm]
5.91 in [150mm] 8.70 in [221mm]
Note: Wiring colors are based
on AutomationDirect
CD12L and CD12M
4-pole cable assemblies.
1 (BN) +
2 (WH) nc
3 (BU) -
4 (BK) nc
1
10...35 VDC
(4-20 mA)
3
0 V
(4-20 mA)
4
2
To prevent damage to the device do
not overtighten the M12 plug
1
POWER
SUPPLY
Load
Load
POWER
SUPPLY
1
+
+
- -
3
++
-
3
-
Sinking Load
Sourcing Load
XTP25 Series Units XTP50 Series Units
XTP product insert Rev. 1
XT-USB
Conguration
Cable
XT-M12 Adapter
XTP Series Powered from
USB port
Programming
Transmitter probes are factory configured and ready for use out of the box. If changes are desired,
transmitter probes can be re-configured using the XT-SOFT programming software, available as a
free download at www.automationdirect.com, an XT-USB configuration cable and an XT-M12 adapter
(purchased separately).
Settable Parameters Factory Settings
Standard Settings Measuring unit °C/°F Part number dependent
Measuring range (start and end values) -50 to 150°C (-58 to 302°F) maximum range Part number dependent
Expanded Settings
Fault condition reaction ≤ 3.6 mA or ≥ 21.0 mA ≥ 21mA
Output 4-20 mA or 20-4 mA 4-20 mA
Filter 0...8s 0s
Offset -9.9 to +9.9°C (-17.8 to 17.8°F) 0.0
Measurement point identification/TAG 8 alpha-numeric digits Test
Service Functions
Password (Release Code) 4 numeric digits 0000
Output simulation drives output to a
fixed value on/off off
XT-SOFT PC Configuration Software
Note: XT-SOFT version 1.27.13.0 or
later required for use with the XTP
series transmitters