Dorma Z 9000 Series Electric Trim Installation Instructions I9000et 05 09
User Manual: Dorma 9000 Series Electric Trim Installation Instructions Installation Instructions
Open the PDF directly: View PDF .
Page Count: 3
INSTALLATION INSTRUCTIONS
9000 SERIES "ELECTRIC"
TRIM INSTRUCTIONS
Specifications
LFSC LFSF
SOLENOID LEADS
(NON POLARIZED)
3/8"
(10 mm)
3/8" DIA.
(10 mm)
3/8" DIA.
(10 mm) 3/8"
(10 mm)
SOLENOID LEADS
(NON POLARIZED)
I9000ET-1 5/09(1135-61)
REQUIRES DORMA ES-100 POWER SUPPLY (Use as large of wire as possible when wiring power supply
and trim.) Power supply will handle two (2) pieces of electric trim. Supplies 4 amp in- rush.
All electric trim is "09" function. Key removable only when locked.
LFSC - Electric Unlock Fail Secure
LFSF - Electric Lock Fail Safe
Continuous Duty .15 amp hold @ 24VDC
Use caution during installation so wires do not get pinched. (See details below.)
When solenoid is energized, trim
remains in un-locked position. If
power is interrupted, ie. fire alarm
is activated, solenoid is de-ener-
gized and trim is set in locked
position.
When solenoid is energized, trim
remains in locked position. If
power is interrupted, ie. fire alarm
is activated, solenoid is de-ener-
gized and trim is set in un-locked
position.
OUTSIDE FACE ONLY
RACEWAY REQUIRED
FOR WIRE CONNECTION,
AT POWER CONDUIT.
WIRES SHOULD NOT
PASS THROUGH THE
TOUCHBAR AND RAIL TO
MAKE CONNECTION.
SEE TEMPLATE T-9021
(Must be ordered per function from factory.)
See back side for typical wiring diagram.
www.dorma-usa.com
OUTSIDE FACE ONLY
RACEWAY REQUIRED
FOR WIRE CONNECTION,
AT POWER CONDUIT.
WIRES SHOULD NOT
PASS THROUGH THE
TOUCHBAR AND RAIL TO
MAKE CONNECTION.
SEE TEMPLATE T-9021
95011790
NOTE: THIS PRODUCT REQUIRES 24VDC.
NOTE: Ref. Template T-9021 for door prep.
TYPICAL WIRING INSTRUCTIONS
9000 SERIES "ELECTRIC" TRIM
LFSC
LFSF
I9000ET-2 5/09
When solenoid is energized, trim
remains in un-locked position. If
power is interrupted, ie. fire alarm
is activated, solenoid is de-ener-
gized and trim is set in locked
position.
When solenoid is energized, trim
remains in locked position. If
power is interrupted, ie. fire alarm
is activated, solenoid is de-ener-
gized and trim is set in un-locked
position.
1 2 3456 7 8 9 10 11 12
CAUTION:
TURN OFF 120VAC POWER PRIOR TO
WHITE
BLACK
GREEN
(NEUTRAL)
(HOT)
(GROUND)
120 VAC
POWER LINE
(1.0 AMP MAX.)
From UPS
Power Source
Green Ground
Screw Located
On Chassis
TO
N.C. CONTACTS
IN FIRE ALARM
CONTROL PANEL.
DORMA MODEL ES100
24 VOLT DC POWER SUPPLY
FUSE PUSH
TO RESET
CIRCUIT
BREAKER
3.0 AMP
24VDC
3/4 AMP
120VAC
REPLACE WITH 3AG 3/4 AMP
SLO-BLOW TYPE FUSE ONLY
NO
CONNECTION
ZONE 2
ZONE 1
CONTROL
SWITCH
CONTROL
SWITCH
OUTPUT
TERMINALS
OUTPUT
TERMINALS
TO
N.C. CONTACTS
IN FIRE ALARM
CONTROL PANEL.
MAKING ANY CONNECTIONS TO TERMINALS.
This is a basic wiring diagram,
for additional wire diagrams or
project specific diagrams contact
the DORMA technical service
department at 1-800-523-8483.
www.dorma-usa.com