MODEL #5500
POWER SUPPLY

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

INSTALLATION INSTRUCTIONS

MODEL #5500
POWER SUPPLY
INSTALLATION INSTRUCTIONS

C

TYPICAL APPLICATION

5500 POWER SUPPLY BOARD
B
A

120 VAC
50/60 HZ
INPUT

A

B
C
D
E

Normally-closed dry
contact from Fire Alarm
Control panel (By others).
Fail Safe locking device.
Fail Secure locking
Normally closed access/egress controls.
Normally open access/egress controls.

5500 Enclosure
C
E

Enclosure Options:

A
A
D

B
B

C

-KLC, (Key Lock Cover)
-FACMR, (FAC Manual Reset)
-ATS, (Anti-Tamper Switch)
12/24V Selection
Switch

Note: ATS Wiring on Page 3.

TROUBLESHOOTING
Primary Fuse
1 Amp Slow Blow
115 VAC Input

Output Power
Switchable from
12VDC @ 3 amps.
24VDC @ 2 amps.

DB-5 & DB- 10
(Distribution Board)

Option connection.

PC (Power Cord) Option
Prewired 6’ long

Access control
legal release

12V BBU1-4
or BBU1-7

ELECTROMAGNETIC LOCK

No Output Power @ A
1
2
3
4

Check input line power.
Check line fuse.
Check F2 & F3 output fuses.
Check FAC (If applicable) terminals
1 & 2 must be wired to N/C contact.

Output Fuses
5 Amp slow blow

No Output @ B
5
6
7
8
9

5500 Manual

24V BBU2-7 or BBU2-7

Note: Start at ‘No Output Power @ A
Check jumper settings on CM/CMTD module(If applicable).
Check jumper setting on DB-5/DB-10 card.
Check for proper access switch contact status.
Check load & external wiring for short condition.
Reset Power Supply (With no load) by
disconnecting input power at 1 for 2 minutes.

Page #4

03/03

BBU (Battery Back-Up)
Option
5500 Manual

FAC Option

FAC Jumper
Cut if FAC Module
is installed in field

03/03

MODEL #5500
POWER SUPPLY

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

Kills all voltage outputs when interfaced
with emergency system dry contact.
LINE
120 VAC
50/60 HZ
INPUT

NEUT
GND

705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

INSTALLATION INSTRUCTIONS

Typical Application

FAC Option (Fire Alarm Control)

DynaLock

MODEL #5500
POWER SUPPLY
INSTALLATION INSTRUCTIONS

CMTD Option (Control Module with Time Delay)

FACMR Option
(FAC Manual Reset)

LINE
FAC
POWER
INPUT MODULE OUTPUT

e

A

Access Control Input, Dry Contacts Only.

B

SPDT Dry Contacts Rated 2A @ 24V.

Same as CM Option with Relock Time Delay

Reset Button
A

Normally-Closed Dry Contact from
Fire Alarm Control Panel (By others).
Cut Main Board Jumper when field installed.
Refer to Page #1 (FAC Jumper).

Module supplied with jumper
on terminals 1 & 2 as shown.

DB-5 & DB-10 Option (Distribution Board)
Two size distribution boards (5 or 10 position)
are available to provide individually fused
output terminals for each lock zone.

B

Adjustable for 1-80
Second delay on
relock time.

Opening normally closed contact removes
all output power until the normally open reset
button is momentarily pressed.

ILB Option (Interlock Logic Board)

DC Input from Power
Supply Main Board

Provides Four DPDT Relay Outputs

Connector for
CM/CMTD Modules

OUTPUT JUMPERS

1

2

*Resettable Fuse

ATS Option
(Anti-Tamper Switch)

Common Negative Terminal
Positive Inputs to Energize
Relay Coils

Contact held open with
Enclosure cover closed.
White

Note: Separate
ILB user manual
shows typical
wiring diagrams.

White

Contact closed with
Enclosure cover open.

3

White
White

Without Control Module Option

NOTE: ATS switch contacts
rated .25A @ 24V.

*Resetting is done by first correcting the overload then disconnecting
the load or turning off the line voltage for two minutes.

With Control Module Option

(Factory Setting)

CM Option (Control Module)

A

Accepts access/egress control
dry contact input. Provides
SPDT relay output.

Access Control Input,
Dry Contacts Only.

B

SPDT Dry Contacts
Rated 2A @ 24V.

A

B

Installation Information
Single Full
Size

LOCK CAPACITY CHART
Double Full
Single
Double
Size

Single Delay
Egress

Deadbolt

12VDC

6

3

6

3

3

3

24VDC

8

4

8

4

3

4

12 AWG

10 AWG

CURRENT DRAW UP TO 1/2 AMP
Voltage 20 AWG

18 AWG

16 AWG

14 AWG

12VDC

50Ft.

100Ft.

150Ft.

250Ft.

400Ft.

750Ft.

24VDC

100Ft.

200Ft.

300Ft.

500Ft.

750Ft.

1500Ft.

*This chart indicatess minimum recommended wire size, but local codes prevail
5500 Manual

Page #2

03/03

5500 Manual

Page #3

03/03

MODEL #5500
POWER SUPPLY

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

Kills all voltage outputs when interfaced
with emergency system dry contact.
LINE
120 VAC
50/60 HZ
INPUT

NEUT
GND

705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

INSTALLATION INSTRUCTIONS

Typical Application

FAC Option (Fire Alarm Control)

DynaLock

MODEL #5500
POWER SUPPLY
INSTALLATION INSTRUCTIONS

CMTD Option (Control Module with Time Delay)

FACMR Option
(FAC Manual Reset)

LINE
FAC
POWER
INPUT MODULE OUTPUT

e

A

Access Control Input, Dry Contacts Only.

B

SPDT Dry Contacts Rated 2A @ 24V.

Same as CM Option with Relock Time Delay

Reset Button
A

Normally-Closed Dry Contact from
Fire Alarm Control Panel (By others).
Cut Main Board Jumper when field installed.
Refer to Page #1 (FAC Jumper).

Module supplied with jumper
on terminals 1 & 2 as shown.

DB-5 & DB-10 Option (Distribution Board)
Two size distribution boards (5 or 10 position)
are available to provide individually fused
output terminals for each lock zone.

B

Adjustable for 1-80
Second delay on
relock time.

Opening normally closed contact removes
all output power until the normally open reset
button is momentarily pressed.

ILB Option (Interlock Logic Board)

DC Input from Power
Supply Main Board

Provides Four DPDT Relay Outputs

Connector for
CM/CMTD Modules

OUTPUT JUMPERS

1

2

*Resettable Fuse

ATS Option
(Anti-Tamper Switch)

Common Negative Terminal
Positive Inputs to Energize
Relay Coils

Contact held open with
Enclosure cover closed.
White

Note: Separate
ILB user manual
shows typical
wiring diagrams.

White

Contact closed with
Enclosure cover open.

3

White
White

Without Control Module Option

NOTE: ATS switch contacts
rated .25A @ 24V.

*Resetting is done by first correcting the overload then disconnecting
the load or turning off the line voltage for two minutes.

With Control Module Option

(Factory Setting)

CM Option (Control Module)

A

Accepts access/egress control
dry contact input. Provides
SPDT relay output.

Access Control Input,
Dry Contacts Only.

B

SPDT Dry Contacts
Rated 2A @ 24V.

A

B

Installation Information
Single Full
Size

LOCK CAPACITY CHART
Double Full
Single
Double
Size

Single Delay
Egress

Deadbolt

12VDC

6

3

6

3

3

3

24VDC

8

4

8

4

3

4

12 AWG

10 AWG

CURRENT DRAW UP TO 1/2 AMP
Voltage 20 AWG

18 AWG

16 AWG

14 AWG

12VDC

50Ft.

100Ft.

150Ft.

250Ft.

400Ft.

750Ft.

24VDC

100Ft.

200Ft.

300Ft.

500Ft.

750Ft.

1500Ft.

*This chart indicatess minimum recommended wire size, but local codes prevail
5500 Manual

Page #2

03/03

5500 Manual

Page #3

03/03

MODEL #5500
POWER SUPPLY

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

DynaLock
705 Emmett Street Bristol, CT 06011-2728
Phone:(860) 582-4761 Fax:(860) 585-0338

INSTALLATION INSTRUCTIONS

MODEL #5500
POWER SUPPLY
INSTALLATION INSTRUCTIONS

C

TYPICAL APPLICATION

5500 POWER SUPPLY BOARD
B
A

120 VAC
50/60 HZ
INPUT

A

B
C
D
E

Normally-closed dry
contact from Fire Alarm
Control panel (By others).
Fail Safe locking device.
Fail Secure locking
Normally closed access/egress controls.
Normally open access/egress controls.

5500 Enclosure
C
E

Enclosure Options:

A
A
D

B
B

C

-KLC, (Key Lock Cover)
-FACMR, (FAC Manual Reset)
-ATS, (Anti-Tamper Switch)
12/24V Selection
Switch

Note: ATS Wiring on Page 3.

TROUBLESHOOTING
Primary Fuse
1 Amp Slow Blow
115 VAC Input

Output Power
Switchable from
12VDC @ 3 amps.
24VDC @ 2 amps.

DB-5 & DB- 10
(Distribution Board)

Option connection.

PC (Power Cord) Option
Prewired 6’ long

Access control
legal release

12V BBU1-4
or BBU1-7

ELECTROMAGNETIC LOCK

No Output Power @ A
1
2
3
4

Check input line power.
Check line fuse.
Check F2 & F3 output fuses.
Check FAC (If applicable) terminals
1 & 2 must be wired to N/C contact.

Output Fuses
5 Amp slow blow

No Output @ B
5
6
7
8
9

5500 Manual

24V BBU2-7 or BBU2-7

Note: Start at ‘No Output Power @ A
Check jumper settings on CM/CMTD module(If applicable).
Check jumper setting on DB-5/DB-10 card.
Check for proper access switch contact status.
Check load & external wiring for short condition.
Reset Power Supply (With no load) by
disconnecting input power at 1 for 2 minutes.

Page #4

03/03

BBU (Battery Back-Up)
Option
5500 Manual

FAC Option

FAC Jumper
Cut if FAC Module
is installed in field

03/03



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Modify Date                     : 2006:06:28 12:22:56-04:00
Create Date                     : 2006:06:28 12:22:34-04:00
Metadata Date                   : 2006:06:28 12:22:56-04:00
Creator Tool                    : PageMaker 6.5
Format                          : application/pdf
Title                           : DynaLock E-Binder
Description                     : Version 6.02
Creator                         : Mike & JohnJr
Document ID                     : uuid:78f5b4c8-71eb-4325-b4f3-a4c09368db96
Instance ID                     : uuid:acf4e2a0-8b09-4a82-8f62-aa3f6e3479aa
Producer                        : Acrobat Distiller 6.0 (Windows)
Has XFA                         : No
Page Count                      : 4
Subject                         : Version 6.02
Author                          : Mike & JohnJr
EXIF Metadata provided by EXIF.tools

Navigation menu