EMI Air Conditioner/heat Pump(outside Unit) Manual L0612425
User Manual: EMI EMI Air conditioner/heat pump(outside unit) Manual EMI Air conditioner/heat pump(outside unit) Owner's Manual, EMI Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF
.
Page Count: 27
| Download | |
| Open PDF In Browser | View PDF |
S1 C/S 1H SINGLE-ZONE
SIDE DISCHARGE
J
i
E_l@
_ricaSgrig
i
5780 Success Dr.
Rome, NY 13440
www.enviromaster.com
INSTALLATION,
OPERATION
ANDMAINTENANCE
MANUAL
P/N
240005897,
Rev.
1.2[05/06]
Thismanual
isintended
asanaidtoaqualified
service
personnel
forproper
installation,
operation,
andmaintenance
ofEMIAmericaSeries
highefficiency condensing units.
Carefully
read these
to follow
these
instructions
instructions
maintenance,
possibly
injury, or death.
may
resulting
•
_
before
result
in fire,
attempting
installation
in improper
installation,
electrical
property
Failure
service,
damage,
or
personal
D
(1) Retain this manual and warranty
reference.
for future
'_'
installed correctly
and run the
one complete
cycle to make
Read
all instructions
before
the EMI AmericaSeries
ficiency condensing
unit.
(2) Before leaving the premises, review this
manual to be sure the unit has been
functions
shock,
or operation.
operation,
using
high efInstall or
locate this unit only in accordance
with these instructions.
Use this
unit for
sure it
unit only
described
for its intended
in this manual.
use
as
properly.
To obtain
technical
assistance
during
service
or warranty
Check
or after the installation
of this unit, check
our website
@ www.
enviromaster.com
or call
your installing
contractor
or distributor.
Our technical
service department
1-800-228-9364.
may
be contacted
When calling for assistance,
please
the following
information
ready:
• Model
Number
• Serial
Number
the rating
AmericaSeries
before installation
the voltage
shown
the electric
supply
plate
on the EMI
condensing
unit
to make certain
is the same
as
to the unit.
at
,AY
have
The EMI AmericaSeries
ing unit must
a properly
condens-
be connected
grounded
only to
electrical
sup-
ply. Do not fail to properly
this unit.
ground
Turn off the electrical
before
supply
servicing
the EMI AmericaSeries
condensing
unit.
• Date of installation
Do not use the EMI AmericaSeries
condensing
DANGER
unit if it has damaged
wiring, is not working
properly,
has been damaged
or dropped.
[Save
These
Instructions]
or
_'®D
b
"
The AmericaSeries
condensing
•
SlC/H
units are, air-cooled,
arranged
units
"
side
designed
will provide
high
specifically
to meet
cooling
efficiency
or ex-
Btuh and S1H
Btuh capacity
as identified
$2C
vertically
discharge,
ceed a 13 SEER rating.
The S1C 9,000-36,000
9,000-24,000
and
condensing
Dimensions"
section
and
• Large
cooling
capacity
for two evaporators,
as
suction
• Solid core filter drier (09 - 12 only)
• Crankcase
heater (09 - 12 $1H's)
(High
pressure
- Standard
- Standard
• Low
identified on page 24 in the "$2C Specifications and Dimensions"
section.
The S1C/H
condensing
of the
units
S1C/H
is simplified
and
$2C
Ambient
proximity
are
to an exterior
recessed
wall. Service
to reduce
valves
tampering
and
all 9,000-12,000
Btuh units are equipped
with a Duratec Performance
Package that
includes
an oversized
suction accumulator with
surge
management,
baffles
a factory
and
enhanced
installed
controls
j
• Field
0-9 &12 models,
optional
equipment
and
on other
12,000
Btuh S1H's)
(standard
(sea coast
coils
• LowAmbient
controls
to 32 ° F, specify
this option
on
use)
for operation
down
for SlC
or
$2C systems (standard
on SlH's)
that
will be operated
in cooling
mode at
outside
temperatures
installed
below 60 ° F (field
kit)
• Low Ambient
for operation
for SlC, S1H or $2C
factory for availability)
(18 awg minimum)
controls
age to the compressor
• Secure mounting pad or foundation
• Refrigerant
piping (if not purchased
EMI)
down to 0 ° F
systems
(consult
are required
when
for charging
(see charge
void
the warranty.
Ambient
and coil, and
A Field
Installed
Kit is good for operation
may
Low-
down to
32 ° F. This is accomplished
by cycling the
condenser
fan on and off, which will in turn
• High Volt Disconnect
piping
start
Btuh only)
models.
wiring
• Refrigerant
hard
for
on 9,000-
the system is asked to cool at outdoor temperatures below 60 ° F, this may cause dam-
• Low Volt wiring
from
heater
units (standard
cool
in-
Q
crankcase
cool
Low Ambient
• Power
operation
• Copper/copper
solid core
as
for
all S1H's)
• 115V (9,000-12,000
oil
is available
installed
Q_
straight
• Straight
filter drier and loss of charge switch. A field
installed crankcase
heater is standard
on
S1H
(heat pumps)
18K and above.
down to 32 ° F standard,
factory
stalled on all Sl H's (heat pumps)
by a 24V
control interconnection
from the evaporator
and multiple units can be lined up in close
switch)
on S1H's
on SlC's
and $2C are quiet units that can be recommended for both commercial
and residential
applications.
installation
accumulator
(09 - 12 only)
The $2C 18,000 (99) - 21,000 (92) and
23,000 (22) Btuh capacity condensing
units
will provide
contactor
• Loss of charge switch (09 - 12 only)
• Low voltage terminal connections
• H.RS.
on pages 22-23.
and fan motor
• Run capacitor
unit
for a single evaporator,
in the "S 1C Specifications
• Compressor
table
interconnect
on page
10)
maintain
viding
a constant
a steady
the air handler
low side pressure
cooling
effect
from frosting-up.
pro-
and keeping
• Locate
theunitasclosetotheindoor
sectionas possible.(SeeTubing
Specifications
chartonpape7.)
Side discharge
unit
allows for per•Iftheunitisusedforlowambient
cool- manent mounting through the feet. This is
due to the vertical
ingdownto32°F,thisoptionmustbe highly recommended
design
of
the
unit.
specified
toprevent
system
damage.
1. Loosen the screws on left and right sides
•Avoidhightrafficareas
andprevailing of the front panel. (De not remove these
windlocations.
screws.)
• Surface
mustbeflatandlevel.
• Mount unit above typical
levels.
snow fall
Ensure free flow of air through
Air must not recirculate
intake.
side
Air is drawn
discharged
from
through
through
the unit.
discharge
to
the coil and
the fan
grille.
A
minimum 48" clearance
is necessary
for
the condenser
discharge.
Rear intake
(coil
side)
Consider
clearance
is 12"
minimum.
how power will be run to the unit
from the power source. Refrigerant
piping
should be a direct line to the indoor unit.
2. Remove
the screws
on the front of the
panel.
3. To remove
1. Place the unit on a flat concrete
or pad if on the ground.
front panel:
surface
Roof mounting
should use a build up platform to avoid
intake of hot air from the roof.
2. in areas of heavy snowfall,
condensers should be set above the level of
maximum
anticipated
is usually
adequate).
snowfall
(12"
4. Slide front panel forward
screws and remove.
to clear side
1. All electrical
wiring
must be run accord-
ing to NEC and local codes.
Compressor
Accumulator
Capacitor
2. Refer to the unit rating
plate for voltage,
minimum
circuit ampacity
and over current protection
requirements.
Lag Bolts
5. Insert
lag bolts
the bottom
secure.
through
of the
the
unit and
holes
tighten
in
to
3. Use only HACR type breakers
or time
delay fuses. Select the wire size according to the ampacity
4. To access
wiring
adjacent
lag bolts through
the holes
electrical
connections
and
diagram:
a) Remove
6. Insert
rating.
the screws
on the side panel
to the back
panel.
in the
feet on the back of the unit and tighten
to secure.
7. Replace the front panel, do not
the side screws at this time.
tighten
b) The
screws
panel should
remove
them).
adjacent
already
to the
be loose
front
(don't
c.Slidethesidepanelouttoaccess
the 8.Check
wiringdiagram
fortherequired
high/low
electrical
connections
and number
oflowvoltagewirestoberun
wirediagram,
between
indoor
andoutdoor
sections.
Hig
Plastic
Note: Remove
from the holes
the plastic
and replace
tight strain relief fitting
grommet
fitting
5. Power
should
disconnect
the unit.
Edge
(Low
Low Volt
Guards
edge guards
with a water-
(High
V) and a split
V)
be run to a weather
box usually
6. From the disconnect
within
proof
3 feet of
box, run the power
through the 7/8" hole on the side of the
unit and into the electrical box and anchor with the strain
relief fitting.
7. Run wires to the high Volt pigtail in the control box and attach L1 and L2 connections.
Also run green wire to ground
wire.
9. Connect
the 24 Volt wiring matching
to color. Refer to the wiring
the inside
also
color
diagram
on
panel of the condenser,
and
refer to the wiring
diagram
indoor
on the
unit.
Low Volt interconnect
should
at
be
least
18 awg.
Thesystemwill supportrefrigerantrunstotheinsideunitofupto 100'
equivalent
feetwitha 35'riseincluded.
Theunitsarefurnished
withsweatconnections
and
areequipped
withrefrigerant
10.Toreplace
sidepanelslidetheslotted
fittingsforcharging
holesofthepanelontotheloosenedvalvesandSchrader
readings.
Thefollowscrews
ofthefrontpanelsothatthe andtakingpressure
ingprecautions
should
bemade:
edgeofthefrontpanel
covers
theedge • Becertainnoburrsremainonthe
ofthesidepanel.
fittings.
• Useonlycleanrefrigeration
tubing,
• Usetubebenders
toguardagainst
kinking.
• Avoidpipingonwetandrainydays
andinsulate suction line. Be certain
that plastic
when
Isolate
end caps
inserting
remain
through
in place
wall openings.
tubing from transmitting
vibra-
tion to the building or unit and avoid
contact with sharp edges. Refrigera-
11. Fasten
all remaining
loose
screws.
tion valves
should
a wet
rag
"heat
valves
while
be wrapped
sink"
brazing.
to
with
protect
• A P-trap
is recommended
tion
riser
feet
in height.
• When
the
is equal
the condenser
evaporator,
return
the
of oil back
• The placement
when
to or greater
the suc-
ricated
than
wholesaler
is installed
P-trap
will
20
above
help the
to the compressor.
of the
P-trap
should
trap
may
be purchased
or distributor
from
however
a
the trap
should be shallow as the (3) elbow configuration.
Each elbow is approximately
2 equivalent
approximately
feet.
One P-trap
12 equivalent
is equal to
feet.
be
at the halfway mark of the suction riser.
For example
if the suction riser is 30 feet
tall then a P-trap
15 foot
Figure
mark
is recommended
of the
suction
riser
at the
(see
• P-traps
are not required
at the foot of the
hot gas risers due to increased
1).
higher
oil flow at
temperatures.
• A P-trap may be fabricated using (2) street
elbows and (2) regular elbow. A prefab-
f
--
Condenser
Evaporator
1.Clean
theendsoftubingandinsertinto
fittinc
5.Attachmanifold
set.
ManifoldVaccum
Pump Micron
Gage
2.Protect
thevalvesbywrapping
witha
wetrag"heatsink"before
brazing.
6.Evacuate
lineto500microns
orlessto
ensure
allmoisture
hasbeenremoved
andtherearenoleaks.
3.Werecommend
theuseofashield(can
be madefromsomescrapmetal)to
protect
thepaint.
4.Brazetubingintofittings,
7.Oncecertain
ofa goodevacuation
and
leakfreejoints,back-seat
thevalves
(counter-clockwise)
to openandallow
factory
charge
tofilllinesandindoor
unit.
8. Chargeto properweight,charge 9.RefertoCharts
onpage12to"fine
basedonfeetofinterconnect
(tables
tune"therefrigerant
chargetomeet
starting
onpage10).
yourconditions.
IMPORTANT
NOTES:
1.Tofindthecharge
adjustment
andsystem
charge
foranyevaporator
andtubing
length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Charge + Line Adjustment
2. Round to the nearest ounce and allow for gauges and hoses.
S 1CA9
CACA12
.25
oz.
37 oz.
SICA8
CACA24
.56
oz.
51 oz.
S 1CA3
CACA36
.56
oz.
72 oz.
$1 CA9
WLHA09
.25
oz.
37 oz.
1i
z.i
SICA8
WLHA24
.56
oz.
$1 CAg
WLCAg0
.56 oz.
51 oz.
72 oz.
$2CA99
WLHA09
.25 oz.
28 oz./28 oz.
$2CA92
WLHA09+WLHA12
.25 oz.
28 oz./33 oz.
S2CA22
CACA12
.25 oz.
33 oz./33 oz.
ills2
The
with
units
refrigerant
are delivered
for the
and the evaporator.
installed
piping
refrigerant
Charging
is required.
charge
table
precharged
condenser
coil
of the field
Refer
for the
to the
proper
amount to be added for the applications
interconect
piping. Unit service valves are
solid brass,
for sweat
connections.
When
charging
and
sures/temperatures
with
switch
Low Ambient
should
temporarily
checking
on system
Option,
be jumped
to obtain
pres-
supplied
the fan cycle
out of the circuit
accurate
data.
Cooling
Cycle
Models
$1C9,
$1H9
with EMI's-WLH09
or CAC12
Cooling Cycle
Models $1C2, $1H2
with EMI's-WLHf2
(R-22 Ref.)
or CAC12
(R-22 Ref.)
Room Temp. (°F)
Room Temp. (°F)
Relative Humidity 50%
Relative Humidity 50%
"_ 300
._
.,c
,4
it
WL
i
.............
....
i""
85 °F ....
80°F _L
3
.....................................
.................
3
o... 35
_
i
...............................................................
85 °F ....
.....................................
..................
__
__
80 °F
75 °F .........
--
35
.....................
i.................
o.
o
u
o
65
75
85
Outdoor
95
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
u
65
75
85
Outdoor
95
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
Cooling
Models
Cycle
Cooling Cycle
Models $1C4, SIH4
SLC8, $1H8
with EMILe-WLH24
or CAC24
with EMI's-WLH24
(R-22 Ref.)
or CAC24
(R-22 Ref.)
340 Z
Room Temp. (°F)
Relative Humidit'
;
i
.................
h
_
85
_80
7s
..................
i....................................
O_
351
_°
15.
o
v
3
,.
_ 15
5
I_
0
65
75
85
Outdoor
95
35
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
_
5,
65
75
85
Outdoor
95
105
115
Temp, (°F)
Note: Minimum compressor superheat -5 ° F
Cooling Cycle
Models SlC3
withEMI's-WLC30(R-22 Ref.)
Cooling Cycle
Models $1C3
withEMI's-CAC36(R-22 Ref.)
Room Temp. (°F)
Relative Humidity 50%
Room Temp. (°F)
Relative Humidity 50%
300
z
I
1
i
÷
._
:,_.- "_'_
o
J
'.,-
75-
80 °F
7s°F.........
--
..................
85 °F ....
80 °F
3
i 75 °F.........
.....................
i.................
55 r
_, 25,
i
"'J
35.
35
...................
-i
o
................
,
i
i
1
i
im_mm
im,_m
i
E
.....
o=-
o
65
75
85
95
o
15-
E
o
5
..
105
Outdoor Temp. (°F)
Note: Only 1 superheat line (TXV)
115
65
75
85
Outdoor
95
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
Cooling
Models
Cycle
$1C6
with EMI's-WLC36
Cooling
Models
Cycle
$1C6
with EMI's-CAC36
(R-22 Ref.)
(R-22 Ref.)
340 _
Room Temp.(°F)
Relative
50%
___300
&
i
-
85 OF........................... i..................
80 °F
i
i
75 °F ..........
i
'
ii
35
I
i
_
i
J
i
i
i
i
i
5:
I
.<
....
...........
E
o
u
65
75
85
Outdoor
95
105
Temp. (°F)
Note: Only 1 superheat line (TXV)
115
65
75
85
Outdoor
95
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
Heat Cycle
Models $1H2
withEMI's-WLH12(R-22 Ref.)
Heat Cycle
Models $1H9
with EMI's-WLH09
10
20
30
(R-22 Ref.)
40
Outdoor Temp. {°F}
RH - 50%
50
60
10
20
30
40
Outdoor Temp. (°F)
RH - 50%
50
60
Heat Cycle
Models $1H8
withEMI's-WLH24(R-22 Ref.)
Heat Cycle
Models $1H4
withEMILs-WLH24
(R-22 Ref.)
Room Temp.(°F)
10
20
30
40
OutdoorTemp.(°F)
RH-50%
50
60
I0
20
30
40
Outdoor Temp, (°F)
RH - 50%
50
60
Cooting Cycle
Models S2C99
withEMFs-WLC09or CAC'i2
(R-22
Cooling Cycle
Models $2C22
withEMI's-WLC12or CAC'i2 (R-22 Ref.)
Ref./
m
......... ........
34ol
Room Temp.(°F)
Relative Humidity 50%
Room Temp.(°F)
" '
Relative Humidity 50%
1
3oo-
i
[ i
[ i
......i...............................
i
;
i
i
;s
_m3oo
g
2602
_-220
[ i
Z
i
_ , i
i 1
"1- 180Z
I
I
I
1
140L
...... .............................
...........................................
............
i
95
"_
85
_
75-
....
4-.
.... =, 7s-
3 65_
......""'-',....................
,i.............
o.
...........
_ ..................
f 8soF....
___80
_i..'"
F
:- !85°F.=
3
55
--
_
................................
80 °F
175 °F.........
..................
55.
m
35
_
35,
I
,._
25-
,,.[
_
15-
_
o
u
5
....................
o.
E
5-
o
65
75
85
Outdoor
I
95
105
115
Temp. (°F)
Note: Minimum compressor superheat -5 ° F
65
75
85
95
105
115
Outdoor Temp. (°F)
Note: Minimum compressor superheat -5 ° F
• Remove
• In low ambient cooling 9-12 Btuh units,
if a crankcase
heater
is installed,
power the
attempting
weather
system
24 hours
to start the unit
(below
vious
Charts
pages).
check
results
on Test
Record
The $1C/H
and $2C outdoor
bearing
system.
It operates
the
indoor section
at the command
of
or room thermostat.
system
units
of the
operation
described
in the manual
indoor section.
will
pertaining
be
operating
through
air
by
into and
collects
on the air
coil, it should be cleaned by "back-flushing"
with a spray of water or vacuuming.
TURN
OFF POWER
SUPPLY FIRST.
Outdoor
units may be cleaned
or waxed
if desired.
Use a non-abrasive
surfaces
only).
car
(on
metal
condensers
are
EMI America
Series
wax
designed
to operate
with EMI America
Series evaporators.
Both the condenser
(outdoor
unit)
unit)
and repair
and
not necessary,
evaporator
have a high volt service
motor.
adding
with
a perma-
Although
oiling
a few drops
the oiling ports twice yearly will extend
life of the motor. Do not over oil.
Panels should
Service
QUALIFIED
remain
should
service
is
through
the
on the unit at all
be performed
agency
by a
only.
regularly
passage
the coil. If debris
unit is equipped
lubricated
times.
efficiency
for free
This
nently
to the
EMI units are designed
and constructed
for reliability
and long life with
minimal
maintenance.
You can assure
inspecting
inspection
any deficiencies.
sections
are the compressor
peak
all access
using
on pre-
Sheet on page 25.
the
• Make final visual
before
in cool
(supplied
Unit Data
Therefore,
set. Mount
60 ° F).
• After doing a final system
the Operation
gauge
panels and make sure they are properly secured.
(indoor
connection.
All
going
EMI products
development
are subject
programs
to on-
so design
and specifications
may change
notice. Please consult the factory
information.
without
for more
Straight
cool condensers
are designed
to operate as a single stage cooling unit.
Heat
pump
operate
stage
as
condensers
are designed
a single
stage
unit.
For proper
heating
cooling
to
two
operation
Each is to be independently
the electrical
service panel.
connected
to
(See the unit
name
breaker
type
priate EMI indoor unit with unit mounted
controls and/or wall mounted
thermostat.
indoor
units
For
and
plate
size).
for the
correct
The outdoor
are also connected
a low volt interconnect
and
to each other
through
wiring. A 24V trans-
former located in the indoor
the low Volt power source.
unit provides
the unit must
two-stage
door unit must
tric strip heater.
be matched
heating
with
operation
be equipped
an appro-
the
in-
with an elec-
(R & Y) will
control
energize.
is satisfied
ature
rises
above
the compressor
,j_%4_
Condenser
er located
low-Volt
operation:
in the indoor
control
The transform-
unit provides
power
to the
When
the
and the room
the
set
indoor
temper-
temperature,
and fan will de-energize.
The anti-short
cycle timer (ASCT)
will
prevent
the compressor
from re-starting
for three minutes.
24V,
condenser
(outdoor
unit). This can be measured
across low-Volt terminals
"R" and "C".
Single
zone heat pump condensers
utilize a reversing
valve to provide
re-
_Y Defrost
controls
protection
(heat
with
pumps
short
only):
cycle
The
unit
is equipped with a logic control circuit designed to keep system operating
at peek
The 24V circuit
provides
control
verse cycle operation.
Therefore
the outdoor unit will act as either a condenser
or
to the indoor and outdoor
systems
includ-
an evaporator
comfort
(ASCT)
space.
in cool-
The defrost control
to keep the condenser
circuit is designed
coil free from frost
and ice during
mode.
there-by
providing
cooling
or heating to the indoor
The reversing
valve is energized
ing. Should
system
the
valve
will default
fail to actuate,
to the heating
the
mode of
operation.
_
Cooling
operation,
dual-zone:
Cooling
the control
single-zone
operation
(either
unit
wall mount thermostat)
tion between
low-Volt
"Y" along
only).
with
When
in cooling
perature
the indoor
that
or remote
"O" (heat
control
the
pumps
is placed
set point
tem-
below the room temperature,
the
reversing
with
mount
make a connecterminals
"R" and
"R" and
mode,
and
requires
valve will energize
(R & O heat
pumps only) along with the compressor
and outdoor fan (R & Y). When the indoor
control
is satisfied
ture falls
below
and the room
tempera-
the set temperature,
the
compressor
and fan will de-energize.
The
anti-short
cycle timer (ASCT) will prevent
the compressor
minutes.
_
Heating
Heating
from
operation
operation
re-starting
for three
(heat pumps
requires
only):
that the con-
trol (either
unit mount
or remote
wall
mount,
heat pump thermostat)
make a
connection
between
low-Volt
terminals
"R" and "Y" only. When
is placed
point
ture,
in heating
the indoor
mode,
with
control
the
efficiency.
ing a three
minute,
compressor
complished
anti-short
This
the precise
sequence
of the outdoor
valve and indoor auxiliary
Jt_ Defrost
timer
protection.
heating
through
cycle
initiation:
is ac-
switching
fan, reversing
heater.
The defrost-sensor
is located on either the end plate or the return bend of the condenser
coil. A defrost
cycle will initiate after the sensor closes
(approx.
30 ° F) and remains
closed for
the length
board
of time selected
(either
on the control
30, 60 or 90 minutes)*.
At the start of the defrost
versing
cooling
switch
cycle,
the re-
valve will change from heating to
mode. The condenser
fan will also
off there-by
temperature
allowing
pressure
to rise within
and
the condenser
coil to melting off any ice build-up. At the
same time the unit will switch on the indoor
electric
strip
heater
to
temper
the
cold air being discharged
from the evaporator unit. This will continue
until either
the defrost-sensor
opens
(approx.
60 ° F)
or a 10-minute
maximum
cycle time has
elapsed.
Defrost times will vary depending on outdoor
conditions.
temperature
When the defrost
plete the unit will return
and
moisture
cycle
to normal
is comheating
operation.
set
temperature
above room temperathe compressor
and outdoor
fan
*Factory
settings
9-30/{ Btu
utes, 36k Btu = 60 minutes
= 90 min-
The condenser will operate in heating for approximately 20 seconds. At that
point the unit will enter defrost mode for
approximately 2 seconds. During this time
the condenser fan will switch off, the reversing valve will energize and the defrost
board will energize the indoor electric
heat relay through the "W" terminal. After
the two second defrost cycle is complete,
the unit will switch back to heating operation for another 20 seconds. This process
will repeat until the jumpers are removed
from the test pins.
DFT TST
Defrost
ing
the
board
test
R and DF2
operation
can be initiated
pins
on
located
of the condensing
the
us-
circuit
unit. "Defrost
operation"
will be a time compressed
sion of the actual defrost cycle.
test
ver-
With the system "off", using two small
alligator clips, jumper the following
sets of
test pins.
"R and DF2" and
"DFT TST'.
AV Defrost control board: Apply power
to the indoor and outdoor units. Place the
indoor unit in heating mode with the set
point temperature well above room temperature, This is to ensure that the condenser will remain on during the entire
defrost test operation.
_" Low ambient operation:
If the unit
is equipped with low ambient fan control
for cooling, the fan will remain off (while in
cooling mode) until the condenser pressure reaches 210psi. The fan will then energize and run until the condenser pressure falls below 150psi. This will happen
only in the cooling mode (or when the reversing valve is energized). In heating (reversing valve not energized), the fan will
run continuous so long as the connection
is made between "R" and "Y'.
NO TE. All EMI products
are subject to ongoing development.
change without notice•
B
Design and specifications
may
Zl
_iii/
SlCA/SlHA9
24"
5"
36"
SlCA/SlHA2
24"
5"
36"
SlCA/SlHA8
32"
5"
36"
SlCA/SlHA4
32"
5"
40"
SlCA/SlHA3
38"
5"
44'_
SlCA/SlHA6
38"
5"
48'_
Easy access interconnect. _
on back of unit
Electrical
connections
m
1/2' Diameter
Lag Holes
BAI
W_
_9
_9
I2
_9
I8
)2
->4
)3
30
)8
}6
)8
9-12
98
18-24
156
30-36
210
SICA/S1
HA9, SICA/S1
HA2
SICA/S1
HA8, SICA/S1
HA2
SICA3,
SICA6
|m
[O_a|
_MP_]
115/60/1
8.1
m
m
9.8
15
11.9
5.2
2o
197
;;;;
/ol_ 1}
t
............
104
LlO4
115/60/1
208/230/60/1
4.3
208/230/60/1
5.3
197
6.4
15
208/230/60/1
6.2
197
7.6
15
208/230/60/1
8.8
197
10.8
15
208/230/60/1
11.6
197
14.1
2O
208/230/60/1
13.6
197
16.6
25
I
15
NOTE:
All EMI products
are subject
to ongoing
development.
change
without notice.
Design
and specifications
may
N{_i
vol_;
StH9A
.O
104
9.7
15
S1H9D
.2
197
5.1
15
SIH8D
.2
197
7.6
15
System
Performance
Data:
Matched
With
EMI AmerioaSeries
Indoor
Units
WLC/WLH
OAC
SIC/SIH
Single
Zone
SICA9
CACA12
9,000
13.0
.79
11.7
R22
SICA2
CACA12
12,000
13.0
.72
12.2
R22
S1CA8
CACA24
18,000
13.0
.76
12.3
R22
SICA4
CACA24
23.000
13.0
.67
11.8
R22
S1CA3
CACA36
30,000
13.5
.82
12.5
R22
SICA6
CACA36
36,000
13.0
.74
12.6
R22
eo
*
S1CA9
WLHAO9
9,000
13.0
.79
11.8
R22
S1CA2
WLHA12
12,000
14.0
.74
12.9
R22
S1CA8
WLHA24
18,000
14.0
.78
13.0
R22
S1CA4
WLHA24
24,000
13.0
.70
12.5
R22
S1CA3
WLCA30
30,000
13.0
.67
12.4
R22
SICA6
WLCA36
33,600
13.0
.65
11.8
R22
NNPF
S 1 HA9
S 1 HA2
WLHA09
WLHA12
9,000
12,000
8_200
10,200
13. I
13. I
7.7
7.7
S 1 HA8
WLHA24
18,000
16,400
13. _ I
7.7
S 1 HA4
WLHA24
23,000
20,600
13. }
5
12.C
R22
12.1
R22
12.1
R22
11._
R22
I
II
7.7
1
NOTE:
All EMI
products
are subject
to ongoing
developmenL
Design
and specifications
may
change
without
notice.
1/2_'Diameter Lag Holes
B
iiif
!!!iiiiiiiiiiiiiif_!
i
?
D
..............................
B ...............................
Easy
access
interconnects
on back of unit
99,92,22
connections
99
22,92
!
!
9900
208-230/60/1
2200
208-230/60/1
ex. - Model
Always
.....78
[] !!
HACR
;Mi_
8RKR
11volt
15
197
15
197
7
Circuit Designators'
9 = 9,000 Btuh * 2 = 12,000 Btuh
9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor
refer lo lhe rating plale
for Minimum
Circuit Ampacily
on all multiple
compressor
units
WLC
CAC
S2C
The Test
below
Unit
Performance
is provided
sheet
this information
ready when
for use by a qualified
Data
sure to include
the Model
service professional
in the event that there
is a problem with the unit. In order for our
Technical
serve
Service
you,
please
Department
complete
Number,
Serial Number
EvaporatorEnteringAir- DB
EvaporatorEntering Air - WB
i EvaporatorLeavingAir - DB
i EvaporatorLeavingAir - WB
EnteringAir
i LeavingAir
TemperatureSplit
i Compressor Suction - PSIG
Compressor Discharge - PSIG
i Compressor - Volts
Compressor - Ampe
OD Fan Motor- Volts
OD Fan Motor- Amps
ID Fan Motor- Volts
ID Fan Motor- Amps
TotalVolts
Compressor Suction
Compressor Discharge
Liquid Out Cond
Liquid before Expansion
Suction out Evaporator
DB - Temp Split at evap.
I
CompressorSuperheat
SubCooling
Support
@ 1-800-228-9364.
have
Date:
i Model Number
Make
Serial
Date of Installation.
Call our Technical
to better
and
calling.
Number,
Technician:
Mode:
I Cooling
Department
CAC
Cassette Evaporator
WL C/WLH
High Wall Evaporator
SIC&
SIH
Single Zone
Side Discharge
T2C, T3C & T4C
2, 3 & 4 Zone
Top Discharge
$2C
Dual Zone
ALL PRODUCT
LIMITED WARRANTY
Enviromaster International LLC (EMI) warrants to the purchaser/owner that EMI prod- I|
ucts will be free from defects in material and workmanship under the normal use and
I|
maintenance for a period of twetve months for all components and sixty months on unit I|
compressors from the date of original installation, or fifteen months for all components I|
and sixty-three months on unit compressors from the date of manufacture, whichever
I|
comes first.
II
WHAT WE WILL COVER
I|
EMI will replace any defective part returned to EMI's approved service organization with I|
a new or rebuilt part at no charge. The replacement part assumes that unused portion I|
of this warranty.
WHAT WE DON'T COVER
THIS WARRANTY DOES NOT INCLUDE LABOR or other costs incurred for repairing,
removing, installing, shipping, servicing, or handling of either defective or replacement
I_
I!
I|
I|
I|
parts.
II
EMI IS NOT RESPONSIBLE FOR:
• Normal maintenance
• Damage or repairs required as a consequence of faulty installation or application by
others.
• Failure to start due to voltage conditions, blown fuses, open circuit breakers, or other
damages due to the inadequacy or interruption of electrical service.
• Damage or repairs needed as a consequence of any misapplication, abuse, improper
servicing, unauthorized alteration, or improper operation.
• Damage as a result of floods, winds, fires, lightening, accidents, corrosive atmosphere,
or other conditions beyond the control of EMI.
• Parts not supplied or designated by EMt.
• Products installed outside the United States or Canada.
• Any damages to person or property of whatever kind, direct or indirect, special or
I|
I|
I|
I|
I|
I|
I|
I|
I|
I|
I|
I|
I|
consequential,
Whether resulting from
I_
III
LIMITATION OF WARRANTIES
I|
This warranty is exclusive and in lieu of any implied warranties of merchantability and I|
fitness for a particular purpose and all other warranties express or implied. The remedies I|
provided for in this warranty are exclusive and shall constitute the only liabilities on the part I|
of EMI including any statements
use or loss of use of the product.
made by any individual which shall be of no effect.
I
II
FOR SERVICE ul'_ I'(=r'_lK:
(1) Contact the Installer
(2) Call the nearest Distributor
(3) Contact the Factory
I|
Enviromaster
5780 Success
International
LLC II
Drive, Rome, NY 13440
www.enviromaster.com|
II
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 27 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 15:59:19 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools