EMI Air Conditioner/heat Pump(outside Unit) Manual L1003136

User Manual: EMI EMI Air conditioner/heat pump(outside unit) Manual EMI Air conditioner/heat pump(outside unit) Owner's Manual, EMI Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 40

DownloadEMI  Air Conditioner/heat Pump(outside Unit) Manual L1003136
Open PDF In BrowserView PDF
SICG/SIHG
S2CG/S2HG

Single-Zone
Dual-Zone

Side-Discharge Ductless Split-System
Condensing Units for R410 Refrigerant

2.6

I

i

3.5

i

5.3

S2CG

i

7.0

i

8.3

10.5

orS2HG

i

kW

i

i

Units

i

Installation,
Operation and
Maintenance
Manual

SICG
SIHG

S2CG
S2HG

P/N 240007754,

Rev. A [051509]

Contents
Verify

..............................................................

unit before

Mounting

the

Electrical

Wiring

Refrigerant

Starting

6
8

.......................................................

11

....................................................

13

Charts

........................................................

17

Unit

........................................................

28

the

Operation

4

.........................................................

Processing

Operation

2

..................................................

Unit ........................................................

Piping

Refrigerant

installing

and Maintenance

Single-zone

and Dual-zone

.................................................
Condenser

Sequence

28

of Operation

..........................

29

Single-zone
and Dual-zone
Condenser
Sequence of Operation,
Testing Defrost Operation
Using Test Pins ........................................

30

Specification

31

Test Unit

and Dimensions

Performance

EMI's Product

Line

................................................

Data Sheet .............................................

36

.......................................................

40

iiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiii

Retain this manual and warranty for
future reference. Before leaving the premises, review this manual to be sure the unit
has been installed correctly and run the
unit for one complete cycle to make sure
it functions properly.

Shipping damage MUST be reported
to the carrier IMMEDIATELY.
Examine the exterior. Remove cover
and examine compressor and piping
for signs of damage.

To obtain technical service or warranty
assistance during or after the installation
ofthis unit, contact your local representative. For alocal representative listing, visit
our web site:

Inspect each component for damage.
Concealed damage must be reported
to the carrier within IS days of the
receipt of the shipment.
The carrier must make proper notation
on the delivery receipt of all damage
identified and complete a carrier inspection report.
The purchaser must notify ECR International's Customer Service Department of all damage and is responsible
for filing any necessary claims with the
carrier.

For further assistance call:
When calling for assistance, please have
the following information

ready:

Model Number
Serial Number
iiiiiiiiiiiiiiii_
Date of installation

The EMI AmericaSeries high efficiency condensing unit is backed by EMI and ECR
International and is tested and rated in accordance with AHRI Standard 210/240-2008
and UL- 1995. Due to ongoing product development, product designs and specifications
may change without notice. Please contact the factory for more information.
Corniest

where

it count:_

2

P!N 2400077_4,

_ev

A {i0!3;_.5001

i i i i i i i i i:i i

iiiiiiiiiiiiiiiiii
Completely

read all instructions

This manual

is intended

as an aid to

iiiiiiiiiiiiiiiii

iiiiiiiiiiiiiiiiii
prior to assembling, installing, oper-

qualified

iiiiiiiiiiiiiiiiii
ating, orrepairingthisproduct.
iiiiiiiiiiiiiiiiii
Inspect all parts for damage prior to in-

installation, operation, and maintenance
of the EMI AmericaSeries high efficiency
condensing unit. Read these instructions

service personnel

for proper

................................
stallation and start-up. The EMI Ameri-

thoroughly and carefully before attempt -

.............................
caSeries high efficiency condensing unit
.......................
must be installed ONLY by q ualified

ing installation or operation. Failure to
follow these instructions may result in

iiiiiiiiiiiiiiiiiiiiiiiiii{i{!i!!!!i
installationpersonnel.

_mproper installation, operation, service,
or maintenance, possibly resulting in fire,
electrical shock, property damage, personal
injury, or death.
iiiiiiiiiiiiiiiii

Tampering

with

ous. Tamperingvoids
NOT attempt

iiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiii

Read all instructions

this unit is dangerallwarranties.

to modify

or change

unit. Install or locate this unit only in accordance with these instructions. Use this

DO

iiiiiiiiiiiiiiiii

this

iiiiiiiiiiiiiiiii
unitonlyforitsintendeduseasdescribed
iiiiiiiiiiiiiiiii
inthismanual.
iiiiiiiiiiiiiiiii
!!!!!!!!!!!!!!!!!
Checktheratingplateontheunitbefore

unit in any way.

iiiiiiiiiiiiiiiii
installationto
make certain thevoltage
iiiiiiiiiiiiiiiii
shownisthesameastheelectricsupplyto
the unit. The rating plate is located on the
iiiiiiiiiiiiiiiii

The EMI AmericaSeries must:
•

•

Be connectedto aproperlygrounded
electrical supply with the proper
voltage as stated on the rating plate.

iiiiiiiiiiiiiiiii
front

Have proper overcurrent protection
(i.e.time-delay fuse/HACRBreaker)
as listed on the rating plate.

iiiiiiiiiiiiiiiii
Wurnofftheelectricalsupplybeforeserviciiiiiiiiiiiiiiiii
"

iiiiiiiiiiiiiiiii
mgtheunit.

result in a fire, explosion, or electrical
shock causingproperty damage,personal
injury; or death.

240007754,

_{ev, A [05ff 5©9

panel only.

!!!!!!!!!!!!!!!!!
This unit must be connected only to a
iiiiiiiiiiiiiiiii
properly grounded electrical supply. Do
iiiiiiiiiiiiiiiii
!!!!!!!!!!!!!!!!!
not fail to properly ground this unit.

Failure to follow these instructions can

P/N

before using this

iiiiiiiiiiiiiiiii
Donotusetheunitifithasdamagedwiriiiiiiiiiiiiiiiii
ing, isnotworkingproperly,
iiiiiiiiiiiiiiiii
damaged or dropped.

$

orhasbeen

Mat:{÷

i_

tBe

USA

Controls and components
(Factory-installed or supplied)

Product description

The AmericaSeries S1CG/S1HG and S2CG/
S2HG condensing units are air-cooled, vertically-arranged side-discharge,high-efficiency
units designed specifically to meet or exceed
a 13 SEER rating.
The S1CG Models 09-36 and S 1HG Models
09-24 condensing units will provide cooling
and heating for a single evaporator, as identified on page 32 and page 33.
The S2CG/S2HG 18,000 (99), 21,000 (92)
and 24,000 (22) Btuh capacity condensing
units will provide cooling and heating for two
evaporators, as identified on page 34.
The

S1CG/S1HG

and S2CG/S2HG

•
•

•

•
•

Heat pump hard start
Cooling operation downto 32° F standard
on all units

•

Models 09-12 only:
- Large capacity suction accumulator
- Solid-core filter drier
Thermostatically-controlled crankcase heater (heat pump only)

Thermostatically-controlled
crankcase heater

Features

•

Compressor and fanmotor contactor
Run capacitor
Lowvoltage terminal connections
H.P.S. (High pressure switch) with
manual external reset

-

are

quiet units that can be recommended
for both
commercial
and residential
applications.

•

•
•
•
•

This feature energizes the crankcase
heater only when needed, saving unnecessarypower usage and increasing overall
system efficiency.

Installation of the S1CG/S1HG and
S2CG/S2HG condensing units is simplified by a 24v control interconnection
from the evaporator.
Multiple units can be lined up in close
proximity to an exterior wall.
Service valves are recessed to reduce
tampering.
All9,000-12,000 Btuh units are equipped
with a Duratec Performance Package that
includes an oversized suction accumulator with surge baffles and enhanced oil
management and a factory-installed solid
core filter drier.
A factory-installed crankcase heater is
standard on S1HG 09 &12 (thermostatically controlled) and S2HG models, and
is available as optional equipment on
other models.

Oomfo_t

where

it cou_'_ts

4

P!N 240007754,

Bey A [05£509I

System options

Installer-supplied

•

•
•
•
•

Power wiring
LowVoltwiring
(18 awgminimum)
Secure mounting pad or foundation
Refrigerant piping (ifnotpurchased
from
EMI)

•
•

High Volt Disconnect
Refrigerant for charging interconnect
ing (see charge table on page 15)

Corrosion-resistant
coil options (sea
coast and harsh environment usage):
Copper fin/copper tube condenser
coil
-

•

•

•

Coated aluminum
condenser coil

fin/copper

tube

LowAmbient
controls for cooling operation down to 0 ° F (standard equipment
can operate down to 32°F)
Optional field-installed
kit, when
specified, for cooling operation down
to O°F-- kit includes control, louvers
and wind baffle plus installation

Field-installed

pip-

.................
iiiiiiiiiiiiiiiii
Low Ambient controls are required
when the system is asked to cool at
outdoor temperatures below 32 ° F, this
may cause damage to the compressor
and coil, and may void the warranty. A
field-installed low-ambient
kit allows
operation down to 0 ° E

instructions
Low Ambient controls for operation
down to 0 ° F (consult factory for availability)
Models 09-12 only:
115v (single-zone only-SICG or
S1HG)
-

items

iiiiiiiiiiiiiiiii

This is accomplished
by cycling the
condenser fan on and off. This will,
in turn, maintain a constant low-side
pressure, providing a steady cooling
effect and keeping the air handler from
frosting-up.

thermostatically-con-

trolled crankcase heater for straight
cool units (S1CG or S2CG)

The optional kits include louvers/wind
baffle, crankcase heater, and/or outdoor
fan cycling switch, and installation instructions.

_/N

240007754,

Rev, A [05ff 509

5

Msd÷

i_

the

USA

Before installing,
•
•

•
•
•

consider:

2.

Locate the unit as close to the indoor section as possible. (see page 11.)
S 1CG/S2CG -- If the unit is used for low
ambient cooling down to 32°E S1CG/
S2CG require CCH.
Avoid high traffic areas and prevailing
wind locations.
Surface must be fiat and level.

In areas of heavy snowfall, condensers
should be set above the maximum anticipated snow line (12" is usually adequate
for most locations).

Unit Mounting

Instructions

Model S1CG is shown for example in the
following sequence.
The side- discharge unit allows forpermanent
mounting through the feet. This is highly
recommended due to the vertical design of
the unit.

Mount unit above typical snow fall level.
This is particularly important for heat
pump applications (S 1HG/S2HG).

1. Figure 1, Page 7:
- Bullet 1 -- Loosen the screws on left
and right sides of the front panel. (Do
not remove these screws.)
- Bullet 2 -- Remove the screws on the
front of the panel.
2. Figure 2, Page 7:
Slide front panel forward to clear side
screws and remove.
3. Figure 3, Page 7:
Insert lag bolts through the holes in the
bottom of the unit and tighten to secure.
4. Figure 4, Page 7:
Insert lag bolts through the holes in the
feet on the back of the unit and tighten
to secure.
5.

Site preparation

Replace the front panel, do not tighten
the side screws at this time.

Place the unit on a flat concrete surface
or pad if on the ground. Roof mounting
should use a build up platform to avoid
intake of hot air from the roofi

Oomfo_t

where

it cour_ts

@

P!N 240007754,

Rev A [05£50%

Figure 1

Remove front panel screws

Figure3

lag hole locations

A

Lag bolts

B

Filter drier

C

Compressor

D

Accumulator

E

Capacitor

Figure4

Figure2

Bottom

Lag holes in feet

Remove front panel

P/N 240007754, g{ev,A [05S5©9]

"d

Made i_ the USA

Figure5

Rating plate location

Figure6

Remove side panel screws

All electricalwiringmustberunaccording to NEC and local codes.

1. Figure S, Page 8 -- Refer to the unit rating plate for voltage, minimum circuit
ampacity and over current protection
requirements.
2. Use only HACR type breakers or time
delay fuses. Sdect the wire size according
to the ampacity rating.
3. To access electrical connections and wiring diagram:
a. Figure 6, Page 8 -- Remove the
screws on the side panel adjacent to
the back panel.
b. The screws adjacent to the front panel
should alreadybeloose (don't remove
them).
c. Slide the side panel out to access the
high/low electrical connections and
wire diagram.
d. Figure 7, Page 9 -- Remove the
plastic edge guards from the holes and
replace with a water-tight strain relief
fitting (High V) and a split grommet
fitting (low V)
4. Power should be run to a weather proof
disconnect box usually within 3 feet of
the unit.

Comfort

where

it cour_ts

8

P!N 240007754,

Bey A [05£509I

5.

Figure 8, Page 9 -- From the disconnect
box, run the power through the 7/8"
hole on the side of the unit and into the
electrical box. Anchor with the strain
relief fitting.

6.

Run wires to the high volt pigtail in the
control box and attach L1 and L2 con-

Figure7

Power entrances

Figure8

High voltage

connections

Figureg

Lowvoltage

connections

nections. Also run green wire to ground
wire.
7. Check wiring diagram for the required
number of low voltage wires to be run
between indoor and outdoor sections.
g.

Figure 9, Page 9 -- Connect the 24 volt
wiring matching color to color. Refer to
the wiring diagram on the inside panel of
the condenser, and also refer to the wiring diagram on the indoor unit. Low volt
interconnect should be at least 18 awg.

9.

See Figure 10, Page 10 and Figure 11,
Page 10 for completed wiring of SICG
and S2CG examples.

10. To replace side panel slide the slotted
holes of the panel onto the loosened
screws of the front panel so that the edge
of the front panel covers the edge of the
side panel.
11. Fasten all remaining loose screws.

P/N 240007754,

_tev, A [05S 509

9

Made in the USA

Figure 10

Completed

wiring, S1CG

Figure 12

Replacing

Figure 11

Completed

wiring, S2CG

Figure 13

Fasten loose screws

Comfort where it cou_'_ts

J,,,O

side panel

P!N 240007754, _SevA [05£50%

P-trap installation

Tubing specifications

•
The system will support refrigerant runs to
the inside unit as listed in Table 1, Page 11.
The units are furnished with sweat connections and are equipped with refrigerant valves
and Schrader fittings for charging and taking
pressure readings.

•

A P-trap is recommended when the
suction riser is equal to or greater than
show in Figure 14, Page 11 and Table 1,
Page 11.
When the condenser is installed above the
evaporator, the P-trap will help the return
of oil back to the compressor.

Figure 14

P-trap placement

(seeTable

Page 11 for dimensions

It is recommended that a filter drier be
ins tall e di n th e liq u idli ne, at th e in d oor

1,

H & P)

Condenser

unit
models
factory-installedonfilter
drier without
(i.e. 18K aand
larger).

H
maximum

Table 1

Sl CG/S2CG tubing

specifica-

tions (see Table 14, Page 11 )

P
maximum
Evaporator

•
12

1/4"

1/2"

•

24

3/8"

3/4"

•
36

P/N 240007754,

3/8"

Rev, A [05J 509]

3/4"

•

AP-trap maybe fabricatedusing (2) street
elbows and (2) regular elbow.
A prefabricated trap may be purchased
from a wholesaler or distributor however
the trap shouldbe shallow as with the (3)
elbow configuration.
Each elbowis approximately 2 equivalent
feet.

•

One P-trap is equal to approximately
12 equivalent feet.
P-traps are not required at the foot of the
hot gas risers due to increased oil flow at
higher temperatures.

J,,,J,,,

Made in the USA

Figure

15

Clean ends of tubing

• Avoid piping on wet and rainy days•
!!!!!!!!!!!!!!!!!

• Use only clean, refrigeration-grade
copper tubing.
• Use tubing benders
kinking.
• Be certain

to guard against

no burrs remain

on the

fittings•

• Cap ends of lines until ready for con..................
nectiÙns.

Figure 16

Wet rag "heat shield over valves

Figure 17

Make a shield to protect

• Be certain that plastic end caps remain
....................
in pl acew h eninsertin g th rou gh w all
......................
...............
openings
• Insulate the suction line•
iiiiiiiiiiiiiiii_i

• Isolate tubing from transmitting vibration to the building or unit and avoid
contact with sharp edges•
• Wrap refrigeration valves with a wet
rag "heat sink" to protect v alyes while
brazing. (See Figure 16, Page 12.)

Refrigerant

piping

1. Clean the ends of tubing and insert into
fittings (Figure 1S).
2.

paint

Protect valves by wrapping with a wet rag
"heat sink" before brazing (Figure 16).

3.

Use a shield to protect the paint as shown
in Figure 17. (The shield can be made
from scrap metal.)

4.

Braze tubing into fittings.

Comfort

where

it cou_'_ts

S,,,2

P!N 240007754,

_SevA [05£50%

Charging the unit

Figure 18

Manifold

set connections

at unit

1. Attach manifold set (Figure 18).
2. Evacuate line to 500 microns or less to
ensure all moisture has been removed and
there are no leaks (Figure 18).
3. Once certain of a good evacuation and
leak free joints, back-seat the valves
(counter-clockwise) to open and allow
factory charge to filllines and indoor unit
(Figure 18, Page 13).

i ii i i!i!iiiiii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Refer to refrigerant charge table for specified charge.
4.

Charge to proper weight, charge based
on feet of interconnect (see tables on
page 15). Only add/remove 410A in
liquid form.

5.

Refer to charts beginning on page 17 to
"fine tune" the refrigerant charge to meet
your conditions.

M1 systems require field charge adjustments. Refer to the "Refrigerant Charge
Tables" for proper weight charge and
to the supplied "Single-zone Operation
Charts" for proper system pressures and
temperature at different outdoor conditions. Superheat should be used for final
system charge.

Figure 19

Manifold

A

Manifold

C

Micron

Figure 20

set up for evacuation

B

Vacuum pump

gage

Charging

Charging should be done with a dial-acharge or weighed in with a scale.
When charging and checking pressures/
temperatures on system supplied with
Low Ambient Option, the fan cycle
switch should be jumped out of the
circuit temporarily to obtain accurate
.................
data.
P/N 240007754,

_tev, A [05S 5©9

S,,,3

['VSadein the USA

It is illegal to discharge refrigerant into
iiiiiiiiiiiiii{'ii{i!iiiiiiiiiiiiiiiiiii
i theatmosphere.
Useproperreclaiming
methods&
equipmentwheninstalling
or servicin g thi s unit.
...................

The units are delivered pre-charged with
refrigerant for the condenser coil and the
evaporator. Charging of the fieldinstalled piping is required. Refer to the refrigerant charge
table for the proper amount to be added for
the applications interconnect piping. Unit
service valves are solid brass, for sweat connections.

Comfort

where

it counts

iiiiiiiiiiiiiiii;
iiiiiiiiiiiiiiii_
iiiiiiiiiiiiiii_

iiiiiiiiiiiiiiiiii
Pressuretest all field installed piping
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
with nitrogen. Using a suitable vacuum
iiiiiiiiiiiiiiiiii
pump, evacuate the tubing and indoor
iiiiiiiiiiiiiiiiii
unit to SO0microns or less, with service
iiiiiiiiiiiiiiiiii
valves remaining front seated (closed).
iiiiiiiiiiiiiiiiii

iiiiiiiiiiiiiiiiii
Before releasing the refrigerant from the
iiiiiiiiiiiiiiiiii
condenser,

be sure the manifold gauge

set is closed so as not to lose vacuum
iiiiiiiiiiiiiiiiii
when shutting down the pump.
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii

Release refrigerant from the condensing
unit by back seating the service valve. Mlen wrenches are used to open the valve.
Replace valve caps. DO NOT back seat
the valves past the snap flanges that hold
the valve core in place.

S,,,4

P!N 240007754,

_SevA [05£50%

iiiiiiiiiiiiiiiii:
1. To find the charge adjustment
length:
iiii!}iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Line Adjustment
!!!!!!!!!!,s_s_
!!!!!!!!!!!,s_s_

2

S1CG/S1HG

S 1CG9

= (Line Charge/FT} x Line Length

CAH09

refrigerant

.25 oz/ft

and allow for gauges and hoses.

charge

table

39.5

$1HG9

WLH09/UNH09

(23 g/m)

S 1CG8

CAH24

.64 oz/ft

$1CG3

CAC36

.64 oz/ft

65.25

$1HG8

WLH24/UNH24

.25 oz/ft

97.5

S1HG9

.64 oz/ft
WLH24/UNH24

.64 oz/ft

63.0

CAH09

.25 oz/ft

51.52

(23 g/m)

S1HG8

39.5

(23 g/m)

S1CG8

51.52

(59 g/m)

(59 g/m)

WLH09/UNH09

.25 oz/ft
(23 g/m)

(59 g/m)

S1CG9

and tubing

System Total = Factory Charge + Line Adjustment

iiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!i!!!!i
2 Round to the nearest ounce
Table

and system charge for any evaporator

CAH24

.64 oz/ft

63.0

(59 g/m)

65.25

(59 g/m)

$1CG3

WLC30/UNC36

.64 oz/ft

97.5

(59 g/m)

P/N

240007754,

_{ev, A [05]

50%

S,,,5

Ma(_e

in

the

USA

iiiiiiiiiiiiiiiiii
1. To find the charge adjustment and system charge for any evaporator and tubing
length
.............................

Line Adjustment

........................

System Total

= (Line Charge/FT)

x Line Length

= Factory Charge + Line Adjustment

..................
2. Round to the nearest ounce and allow for gauges and hoses.

Table 3

S2CG/S2HG refrigerant

.25 oz/ft
$2CG99

$2CG92

(2)WLHG09

WLHG09+WLHG12

charge table

40/40

$2HG99

(23 g/m)

.25 oz/ft

40/34

$2HG92

(2) WLHG09

WLHG09+WLHG12

(23 g/m)

$2CG22

(2) CAHG12

$2CG99

UNHG09

.25 oz/ft
(23 g/m)

.25 oz/ft

Comfort

UNHG09+UNHG12
_:

where

it counts

25 oz/ft
"
,
(23 g/m)

40/40

.25 oz/ft

40/34

(23 g/m)

34/34

$2HG22

40/40

$2HG99

(2) CAHG 12

UNHG09

.25 oz/ft

34/34

(23 g/m)

.25 oz/ft

40/40

(23 g/m)

(23 g/m)

$2CG92

.25 oz/ft
(23 g/m)

40/34

$2HG92

S,,,6

UNHG09+UNHG12

.25 oz/ft
, ,
(23 g/m)

P!N 240007754,

_ev

40/34

A [05£50%

Cooting
Cycte
Model
S1CGgO00
&StHG9000

Cooling
Cycle
Model
S1CG9000
&S1HG9000

withEMI's-WLH09
&UNH09
(R-410A
Ret)

withEMI's-CAHG09
(R-410A
Ref,)

55O

550

490

490

430

430

o_ 370

370

310

310

250

250

170

170

150

150

_.

o_

_

o_ 130

m

110

110

90

90

35

35

25

8

130

_-

25

15

15

65

75

85

95

105

115

65

Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F

P/N 240007754, _ev, A [05S509

75

85

95

105

115

Outdoor
Ternp
(° F)
Note:
Minimum
compressor
superheat
5° F

_,,,7

['_$a_:_÷
in the USA

mul

Amica vies
Cooling
Cycle
Model
S1CG2000
$S1HG2000

Cooling
Cycle
Model
S1CG2000
&S1HG2000

withEMI's-WLHG12
&UNHG12
(R-410A
Reh)

withEMI's-CAHG12
(R-410A
Ref,)

55O

550

490

490

430

_

430

9_

_=

_,

_.

370

370

310

310

25O

25O

170

170

150

_

150

130

130

110

110

90

o_

35

N-

25

_4

_

15

_

35

65

75

85

95

105

115

15

65

Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F

Comfort where it cou_'_ts

25

75

85

95

105

115

Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5°F

S,,,8

P!N 240007754, Rev A [05£50%

Cooling
Cycle
Model
S1CG8000
&S1HGS000

Cooling
Cycle
Model
S1CG8000
&S1HG8000

withEMI's-WLHG24
&UNHG24
(R-410A
Ref,)

_-

withEMI's-CAHG24
(R-410A
Ref,)

550

550

49O

490

430

_

430

370

_-

370

310

310

250

250

170

170

150
Ao

2g_

8

_

150

130

130

110

110

90

90

35

35

25

_-

25

15

8

15

5
65

75

85

95

105

115

Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F

P/N 240007754, _ev, A [O5S509

65

75

85

95

105

115

Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5°F

_,,,9

r'_$a_:_÷
in the USA

Cooling
Cycle
Model
S1CG4000
&S1HG4000
with
EMrs-WLHG24
&UNHG24
(R-410A
Ref,)
550

Cooling
Cycle
Model
S1CG4000
&S1HG4000
withEMrsCAHG24
(R-410A
Ref,)

550

Room
Temp(°F)
Relative
Humidit'

490

490

-_ 43o

-_ 43o

_-

_-

370

370

170

170

150

250

I_

250

150

310

I_

310

_

13o_-_@

_

13o

110

_-

110

90 _
35

__

90
35

25 _

_

25

_

15

_-15

75

85
95
105
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
50F

Comfort where it oou['}ts

115

65

20

75

85
95
105
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F

115

P!N 240007754, Rev A Z05£50%

Cooling
Cycle
Model
SLOG3000

Cooling
Cycle
Model
S1CG3000

withEMI's-WLCG30
&UNCG30
(R-410A
Ref.)

withEMI's-CACG30
(R-410A
Ref.)

55O

550

490

490

430

_

430

_- 370

_-

370

_

310

310

250

250

170

170

150

_.

130

o_ 130

110

110

90

90

150

35

_-

25

8

15

£

75

85
95
105
Outdoor
Temp
(oF)
Note:
Minimum
compressor
superheat
50F

P/N 240007754, _ev, A lOSS509

115

25

65

2]...

75

85
95
105
Outdoor
Temp
(oF)
Note:
Minimum
compressor
superheat
50F

115

['_$ac:_÷
in the USA

Cooling
Cycle
Model
S1CG6000

Heating
Cycle
Model
S1HGgO00
withEMI'sWLHG09
&UNHG09
(R-410A
Ref,)

withEMI's-CACG36
(R-410A
Ref,)

55O

380

Room
Temp
(°F)
Relative
Humidb

490

350

430

_

320

_- 370

a-

290

310

260

250

230

170

130

150
_
q

ilili

130

110

_

110

_

9O

70

II

I

90

50

_"

35

30

_-

25

N8

15

€

20
10

65

75

85

95

105

115

10

Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5oF

Comfort where it cou_'_ts

20

30

40

50

60

Outdoor
Temp
(°F)

22

P!N 240007754, _SevA [05£50%

Heating
Cycle
Model
S1HGgO00
withEMI'sCAHG09
(R-410A
Ref,)

Heating
Cycle
Model
S1HG2000
withEMI's-WLHG12
&UNHG12
(R-410A
Ref,)

380

38O

350

350

_

320

_

320

";-

290

_-

290

_-

260

260

230

230

130

130

11o

_

110

90

_-

90

o

70

50

30

30

8

20

20

}

lO

I0

10

20

30

40

50

60

Outdoor
Temp
(°F)

P/N 240007754, Rev, A [05S509

30

40

50

Outdoor
Temp
(oF)

23

Made in the USA

Model
s1HGZOUO
withEMI's-CAH12
(R-410A
Ref,)

MOdel
b lIflbZUUU
withEMrs-WLHG12
& UNHG12
(R-410A
Ref,)

380

38O

350

350

_

320

_

320

_-

290

_-

290

260

260

230

230

130

130

_

110

11o

_-

90

_-

90

50

_-

30

30

20

20

10

I0

20

30

40

50

60

Outdoor
Temp
(oF)

Comfort where it oou['}ts

10

20

30

40

50

60

Outdoor
Temp
(oF)

24

P!N 240007754, Rev A [05£50%

Model
5]HGZOO0
withEMI's-CAH12
(R-410A
Ref,)

MOdel
bllflb_ddd
withEMrs-WLHG24
&UNHG24
(R-410A
Ref,)

380

38O

350

350

_

320

_

320

";-

290

_-

290

_-

260

260

230

230

130

130

11o

_

110

90

_-

90

o

70

50

30

30

8

20

20

}

lO

I0

10

20

30

40

50

60

Outdoor
Temp
(°F)

P/N 240007754, Rev, A [05S509

30

40

50

Outdoor
Temp
(oF)

25

Made in the USA

Model
SlHGSOO0
with
EMrsCAH24
(R-410A
Ref,)

MOdelb llflbqUUg

withEMrs-WLHG24
&UNHG24
(R-410A
Ref,)

380

38O

350

350

_

320

_

320

_-

290

_-

290

260

260

230

230

130

130

_

110

11o

_-

90

_-

90

50

_-

30

30

20

20

10

I0

20

30

40

50

60

Outdoor
Temp
(oF)

Comfort where it oou['_ts

10

20

30

40

50

60

Outdoor
Temp
(oF)

26

P!N 240007754, Rev A [05£50%

Model
5]HG4OUO
with
EMI'sCAH24
(R-410A
Ref,)

380
350

_

320

";-

290

260

230

130

110
A-

90

o

30

8

20

0
10

20

30

40

50

60

Outdoor
Temp
(°F)

P/N 240007754, Rev, A [05S509

27

Ma(_ein the USA

9,000-

The S 1CG/S

12,000 Btuh units

sections

In low ambient cooling, ifa crankcase heater is
installed, power the system 24 hours before
attempting to start the unit in cool weather
(below 60 ° F).

1HG and S2CG/S2HG

are the compressor

bearing

outdoor
units

of

the system. It operates at the command
of the
indoor section or room thermostat.
Therefore,
the system operation
will be described
in the
manual pertaining
to the indoor section.

EMI units are designed and constructed
for reliability and long life with minimal
maintenance. You can assure peak operating
efficiency by regularly inspecting for free air
passage into and through the coil. If debris
collects on the air coil, it should be cleaned
by "back-flushing" with a spray of water or
vacuuming.
TURN OFF POWER SUPPLY
FIRST. Outdoor units may be cleaned or
waxed if desired. Use a non-abrasive car wax
(on metal surfaces only).

Test unit data sheet

After doing a final system check using the
Operation Charts (supplied on previous
pages).
Record results on Test Unit Data Sheet on
page 36.

Before leaving
Remove gauge set. Mount all access panels
and make sure they are properly secured.

This unit is equipped with a permanently
lubricated motor. Mthough oiling is not necessary; adding a few drops through the oiling
ports twice yearly will extend the life of the
motor. Do not over oil.

Make final visual inspection and repair any
deficiencies.

Panels

should

remain

on the unit at all times.

Service should be performed
service agency only.

A hard start kit may be required for units
in low voltage applications.

by a qualified

Specific changes
All EMI products are subject to ongoing
development programs so design and specifications may change without notice. Please
consult the factory for more information.

Comfort

where

it cour_ts

28

P!N 240007754,

_SevA [05£50%

EMI AmericaSeries condensers are designed
to operate with EMI AmericaSeries evaporators. Both the condenser (outdoor unit) and
evaporator (indoor unit) have a high volt service connection. Each is to be independently
connected to the electrical service panel. (See
the unit name plate for the correct breaker
type and size). The outdoor and indoor units
are also connected to each other through a low
volt interconnect wiring. A 24v transformer
located in the indoor unit provides the low volt
power source.

temperature below the room temperature, the
reversing valvewill energize (R & O heat pumps
only) along with the compressor and outdoor
fan (R & Y). When the indoor control is satisfied and the room temperature falls below the
set temperature, the compressor and fan will
de-energize. The anti-short cycle timer (ASCT)
will prevent the compressor from re-starting for
three minutes.
Heating operation
Heating operation requires that the control
(either unit mount or remote wall mount, heat
pump thermostat) make a connection between
low-Volt terminals "R" and "Y" only. When the
indoor control is placed in heating mode, with
the set point temperature above room temperature, the compressor and outdoor fan (R
& Y) will energize. When the indoor control is
satisfied and the room temperature rises above
the set temperature, the compressor and fanwill
de-energize. The anti-short cycle timer (ASCT)
will prevent the compressor from re-starting for
three minutes.

Straight cool condensers are designed to operate as a single stage cooling unit. Heat pump
condensers are designed to operate as a single
stage cooling two stage heating unit. For proper
operation the unit must be matchedwith an appropriate EMI indoor unit with unit mounted
controls and/or wall mounted thermostat. For
two-stage heating operation the indoor unit
must be equipped with an electric strip heater.

.............................
For remote wall mounted thermostat
.........................
operation be sure to select EMI p/n

Defrost controls with short cycle
protection (heat pumps only}

iiiiiiiiiiiiiiiiiiiiiiiii!i!i!!i
240004180orasuitable24v,
twostage
heating, heat pump thermostat.
Condenser
The

The unit is equipped with
designed to keep system
ficiency. The 24v circuit
the indoor and outdoor
three minute, anti-short
compressor protection.

operation

transformer

located

in the indoor

unit

provides
24v, low-volt control power to the
condenser (outdoor unit). This canbemeasured
across low-volt terminals "R" and "C".

The defrost control circuit is designed to keep
the condenser coil free from frost and ice during
heatingmode. This is accomplished through the
precise switching sequence of the outdoor fan,
reversing valve and indoor auxiliary heater.

Heat pump condensers utilize areversing valve
to provide reverse cycle operation. Therefore
the outdoor unit will act as either a condenser
or an evaporator there-by providing comfort
cooling or heating to the indoor space. The
reversing valve is energized in cooling. Should
the valve fail to actuate, the system will default
to the heating mode of operation.

Defrost

Cooling operation requires that the control
(either unit mount or remote wall mount thermostat) make a connection between low-volt
terminals "R" and "Y" along with "R" and "O"
(heat pumps only). When the indoor control
is placed in cooling mode, with the set point
240007754,

_{ev, A [05ff 5©9

initiation

The defrost-sensor is located on either the end
plate or the return bend of the condenser coil.
A defrost cycle will initiate after the sensor
doses (approx. 30 ° F) and remains closed for
the length of time selected on the control board
(either 30, 60 or 90 minutes)*.

Cooling operation, single- and dual-zone

P/N

a logic control circuit
operating at peek efprovides control to
systems including a
cycle timer (ASCT)

At the start of the defrost cycle, the reversing valve will change from heating to cooling
mode. The condenser fan will also switch off
there-by allowing pressure and temperature
29

rVSat_e in

the

USA

BI

m

W

to rise within

_

the condenser

)i
iii!i
5 i);
_!!_
))))_!!_
)i:iJ
<);
)i'ii
= @ )!;i¸iii!¸¸¸
))
_;;!ii)i:iJ
<);
i_ii
_;i;iii
¸i:);!
)_[i;_!i;
)))i
¸ii
)i
!i!_
)?ii
_;!ii
)i'ii
0 _!i!_
¸!15/!
_!!ii
i?ii
Li;!!!_
)) _

coil to melt off

Figure 21

any ice build-up. At the same time the unit will
switch on the indoor electric strip heater to
temper the cold air being discharged from the
evaporator unit. This will continue until either
the defrost-sensor
opens (approx. 60 ° F) or a
10-minute
maximum
cycle time has elapsed.
Defrost times will vary depending
on outdoor
temperature
and moisture
conditions.
When
the defrost cycle is complete the unit will return
to normal heating operation.
*Factory settings

9-24k

result in injury

or electric

DFT TST

If the condenser
coil is heavily frosted
up with ice, it is likely that the "Defrost
Sensor" is already closed. In this case the
"R and DFT" jumper can be eliminated.
To initiate
defrost,
momentarily
jump
pins marked "DFT TST" until the defrost
cycle begins. The unit will remain
in
defrost mode until the condenser
coil is
defrosted and then it will return to heating mode. When testing is complete
be
sure to remove the jumper(s).
DO NOT
leave the unit in test mode with jumper (s)

With the system "off", using two small alligator
clips, jumper the following sets of test pins. "R
and DF2" and "DFT TST".
board

Apply power to the indoor and outdoor units.
Place the indoor unit in heating mode with the
set point temperature
well above room temperature. This is to ensure that the condenser
will remain
operation.

on during

the entire

defrost

test
Low ambient

The condenser
will operate in heating for approximately 20 seconds. At that point the unit
will enter defrost mode for approximately
2
seconds. During this time the condenser
fan
will switch off, the reversing valve will energize
and the defrost board will energize the indoor
electric heat relay through the "W" terminal.
After the two second defrost cycle is complete,
the unit will switch back to heating operation
for another 20 seconds. This process will repeat until the jumpers are removed from the

operation

Ifthe unit is equipped with low ambient fan control for cooling, the fan will remain off (while
in cooling mode) until the condenser pressure
reaches 340 psi. The fan will then energize and
run until the condenser pressure falls below
247 psi. This will happen only in the cooling
mo de (or when the reversing valve is energized).
In heating (reversing valve not energized), the
fan will run continuous so long as the connection is made between "R" and "Y".

test pins.
Comfort where it cour_ts

R and DF2

shock.

Defrost operation
can be initiated using the
test pins located on the circuit board of the
condensing
unit. "Defrost test operation"
will
be a time compressed
version of the actual
defrost cycle.

Defrost control

board (SlHshown)

Btu = 90 minutes

Beforeremovingtheaccesspanelstothe
unit make sure that all power is disconnectedfromtheunit.
Failureto do so could

)))))))))))))),=
))))))))))))))),

Defrost control

30

P!N 240007754, Bey A [05150%

iiiiiiiiiii
.... i!ii!i!!i!iiiiiiiiiiiii
i iii iii! i !il
Performance
data listed in this manualis subject to change without notice. For the most current unit/system
performance
data, please refer to the ECR International
listing of certified
products in the AHPd directory; at www.ahridirectory.org.
Due

to ongoing

product

development,

designs,

specifications,

and performance

are

subject to change without notice. Please consult the factory for further information.

E
1/2" Diameter

Lag Holes

_iii};_iiN#iii/iiiiiii[iiii!!iiiiiiii_:iiiiiiiiii_iii_iii;;iiiiiiliii#_
iii
_

A-_

!:_%iii_ii_;iiiiii!ii_;i;ii!_iiiii!!iii,;,},iiiiiii_iiiii/ii!i!i!iii_ii!
I il
...................................
B ........................................
A

Electrical connections

Table 4

Dimensional

S1CG/S1 HG9

data, sound data and shipping

Easy access interconnects
on back of unit

weights

4 sis
(117)

14 u/_o
(373)

3
(76)

12 z/_
(316)

24
(610)

15
(381)

36
(914)

59

98

32
(813)

15
(381)

36
(914)

62

156

38

S1CG/S1HG8

18

4 _/_,
(117)

22 _/_6
(570)

3
(76)

12 7/_6
(316)

S1CG3

3O

7
(178)

23 _s/_,
(608)

3
(76)

127/_o

44
(1118)

210

(965)

15
(381)

68

(316)

23 _s/_,
(608)

3
(76)

12 7/_6
(316)

38
(965)

15
(381)

44
(1219)

68

159

23 _s/_6

3
(76)

12 7/_6
(316)

38
(965)

15
(381)

44
(1219)

68

187

S2CG/S2HG99

9 + 9

7
(178)

S2CG/S2HG92

9+12

(178)

7

P/N

240007754,

Rev, A [O5_ 509

(608)

3[_ii,

['?_ade in

the

USA

mun

W

Table 5

$I CG electrical

BIIII

SICG2A

Amic@ies

.... iiiiS_i_43i!ii!!_:!_ii%_qi_
il}ii_iiii!4_!i_ii!!!i:Lii
¸ _!i!i_ii_sii:_i
i_iii_!i!iiiiiiiii3i3q!i_i!_iii3_i:_ili!_
i!Y/81i(iiL!_ii!i_il
....

115/60/I

specifications

1.4

0.125

9.9

53

11.3

104

13.8

20

SICG2D

208/230/60/I

0.8

0.125

5.2

27

6.0

197

7.3

15

SICG4D

208/230/60/I

0.8

0.125

8.0

43

8.8

197

10.8

15

SICG6D

208/230/60/I

1.8

0.330

12.7

74

14.5

197

17.7

30

S1 CG performance
Table 6

Cooling

$1CG9

WLHG09

S1CG8

WLHG24

S1CG3

WLCG30

Table 7

Cooling

$1CG9

UNHG09

S1CG8

UNHG24

S1CG3

UNCG36

Table 8

Cooling

S1CG9

S1CG8

S1CG3

(Do_l"_l_t

where

it counts

Indoor

Units

systems with wall units
13.0

0.74

12.2

R410A

18,000

13.0

0.77

12.0

R410A

28,200

13.0

0.79

11.7

R410A

systems with universal

units

13.0

0.74

12.2

R410A

18,000

13.0

0.77

12.0

R410A

28,200

13.0

0.79

11.7

R410A

systems with cassette units (__ = G or H)
9,000

CAH24

data: Matched with EMI AmericaSeries

13.0

0.77

11.4

R410A

13.0

0.75

12.7

R410A

13.0

0.77

12.4

R410A

$2

P!N 2400077_4,

Rev

A I0!S:£50%

Table 9

SI HG electrical

SIHG9A

115/60/I

specifications

1.4

0.125

7.5

47

8.9

104

10.8

15

S1HG9D

208/230/60/1

0.8

0.125

3.9

20

4.7

197

5.7

15

S1HG8D

208/230/60/1

0.8

0.125

5.9

43

6.7

197

8.2

15

1

$1 HG performance
Table 10

S 1HG9

Table 11

S1HG9

Table 12

S1HGg000

S1HGS000

data: Matched with EMI AmericaSeries

Indoor Units

Heat pump systems with wall units

WLHG09

%000

%000

13.0

7.7

Heat pump systems with universal

UNHG09

13.0

0.72

12.8

3.3

R410A

units

7.7

0.72

Heat pump systems with cassette units (_ = G or H)

9

9,000

8,200

13.0

7.7

0.74

11.8

3.2

R410A

24

18,000

16,400

13.0

7.7

0.76

12.1

3.4

R410A

CAH

CAH

WL C/WL H

CAC/
CAH

SICG/SIHG
Single zone

P/N

240007754,

Rev, A [05S 5©9]

33

U N CI U N H

Made

in

the

USA

Table 13

9200

S2CG electrical

i208/230/60/1

0.8

S2CG performance
Table 14

S2CG cooling

WLHG09+WLHG09

WLHG09+WLHG

Table lS

12

specifications

0.125

3.9

20

5.2

27

8.8

data: Matched with EMI AmericaSeries

197

10

15

Indoor Units

systems with two wall units

$2CG99

18,000

13.0

0.80

11.9

R410A

$2CG92

21,000

13.0

0.74

12.0

R410A

S2CGcooling systems with two universal units

UNHG09

+ UNHG09

$2CG99

18,000

13.0

0.80

11.9

R410A

UNHG09

+ UNHGI 2

$2CG92

21,000

13.0

0.74

12.0

R410A

11.5

R410A

Table 16

CAH_09

S2CG cooling

+ CAH09

......................
CAH 09+CAIq

CAC/
CAH

systems with two cassette units (__ = G or H)

$2CG99

18,000

! _ .................. $2CG92 ............................

13.0

0.75

...............
13.0 ........................................
0:75 .....................
iI................
]1:5 .............................
E_4]0_ .............

mmumm

A

_mW

Table 17

9200

SPiB8

S2HG electrical

208/230/60/1

0.8

S2HG performance
Table 18

Table 19

specifications

0.125

3.9

20

5.2

27

8.8

i!

data: Matched with EMI AmericaSeries

197

10

15

Indoor Units

Heat pump systems with wall units

WLHG09+WLHG09

WLHG09+WLHG

::: :

....
iiiiS_i_ii3i!ii!!_:!_ii%;qi_
il}ii_iiii!:q!_;i_;i!!!i:i:i
¸_;i!i;ii_sSi
i_iii_;i!iiiiiiii;i3i3q!i_i!_iii3_i;_ilis
i!YISi/i_L!_ii!i;il
....

12

$2HG99

18,000

17,600

13.0

7.7

0.80

11.9

3.3

R410A

$2HG92

21,000

20,000

13.0

7.7

0.74

12.0

3.3

R410A

Heat pump systems with universal

units

UNHG09

+ UNHG09

$2HG99

18,000

18,000

13.0

7.7

0.80

11.9

3.3

R410A

UNHG09

+ UNHG12

$2HG92

21,000

20,000

13.0

7.7

0.74

12.0

3.3

R410A

Table 20

Heat pump systems with cassette units (_ = G or H)

WL C/WL H

CAC/
CAH

S2CG/S2HG
Dual zone

P/N

240007-/54,

_ev, A [05S 509]

$5

UNC/UNH

Ma(_e

in

the

USA

i!!!!_!_!_i_i_i!iiiiiiiiiiii_!_ii_!_i_!i_i_ii_i!!i_i_i_i_iiiiiii_i!_!!!i_
_ii_i!_ii_i!_ii_ii_i_!!_i_!!
_i!_i_ii_i_ii_!i_i_ii_i_!i_ii_ii_ii_ii_il
_i_i_!_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_!_!_!
_I_!I_I_!I_II_I!!II!I
_i_!!_i_!!_i!!ii!ii!ii
_!_!_!_!_!_i_i_

Technician:

, Se_!a!Number..................................................................................................................................
_ iMede! ....................
c°°!!n_! ......................................................................................

Evaporator Entering Air - WB
Evaporator Leaving Air- DB

i

Leaving Air

Compressor Suction - PSIG

Compressor - Volts
............................................................................................................................................................................................................................
.......................................................................................................................
_OD Fan Motor - Volts

ID Fan Motor- Amps
:.................................................................................................................................................................
_
.....................................................................................................................
Total Volts

Compressor Suction
Compressor Discharge
Liquid Out Cond.

i
......................................................................................................................

Liquid before Expansion
Suction out Evaporator

DB - Temp Split at evap.

Compressor Superheat

Comfort

where

it cou_'_ts

$G

P!N 240007754,

_ev A [05£50%

_/N

240007754,

_tev, A [05ff 5©9

$7

Made

in

the

USA

Bi

Comfort

i

W

where

....:i
iiii_!i,
ii
i!ii
ii
ii
:_i:i
iiii
I::i_
i_
i_= 0 iii[Ji
ii_
i¸_ii!_i
_ I:
!!0 i_i_
_!i_
ii:_
_i:l
i!_ii
¸_!i!i_
ii
!i_i!:i_
!!
i__ii!ii
i_ii
_i;;
ili!_
i!_¢_I
_ii_i
ii_
i_!i
_ii!i_
ii =_

it cou_'_ts

38

P!N 240007754,

tSev A [05£50%

_£N 240007754,

_tev, A [05ff 5©9

$9

Matte

in

the

USA

WLC/WL H
High Wall Air Handler

UNC/UNH
Air Handler

SICG
Single Zone
Side Discharge

S2CG &,
Dual Zone
Side Discharge



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 40
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sun Mar 14 04:17:23 2010
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu