EMI Air Conditioner/heat Pump(outside Unit) Manual L1003136
User Manual: EMI EMI Air conditioner/heat pump(outside unit) Manual EMI Air conditioner/heat pump(outside unit) Owner's Manual, EMI Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF
.
Page Count: 40
| Download | |
| Open PDF In Browser | View PDF |
SICG/SIHG
S2CG/S2HG
Single-Zone
Dual-Zone
Side-Discharge Ductless Split-System
Condensing Units for R410 Refrigerant
2.6
I
i
3.5
i
5.3
S2CG
i
7.0
i
8.3
10.5
orS2HG
i
kW
i
i
Units
i
Installation,
Operation and
Maintenance
Manual
SICG
SIHG
S2CG
S2HG
P/N 240007754,
Rev. A [051509]
Contents
Verify
..............................................................
unit before
Mounting
the
Electrical
Wiring
Refrigerant
Starting
6
8
.......................................................
11
....................................................
13
Charts
........................................................
17
Unit
........................................................
28
the
Operation
4
.........................................................
Processing
Operation
2
..................................................
Unit ........................................................
Piping
Refrigerant
installing
and Maintenance
Single-zone
and Dual-zone
.................................................
Condenser
Sequence
28
of Operation
..........................
29
Single-zone
and Dual-zone
Condenser
Sequence of Operation,
Testing Defrost Operation
Using Test Pins ........................................
30
Specification
31
Test Unit
and Dimensions
Performance
EMI's Product
Line
................................................
Data Sheet .............................................
36
.......................................................
40
iiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiii
Retain this manual and warranty for
future reference. Before leaving the premises, review this manual to be sure the unit
has been installed correctly and run the
unit for one complete cycle to make sure
it functions properly.
Shipping damage MUST be reported
to the carrier IMMEDIATELY.
Examine the exterior. Remove cover
and examine compressor and piping
for signs of damage.
To obtain technical service or warranty
assistance during or after the installation
ofthis unit, contact your local representative. For alocal representative listing, visit
our web site:
Inspect each component for damage.
Concealed damage must be reported
to the carrier within IS days of the
receipt of the shipment.
The carrier must make proper notation
on the delivery receipt of all damage
identified and complete a carrier inspection report.
The purchaser must notify ECR International's Customer Service Department of all damage and is responsible
for filing any necessary claims with the
carrier.
For further assistance call:
When calling for assistance, please have
the following information
ready:
Model Number
Serial Number
iiiiiiiiiiiiiiii_
Date of installation
The EMI AmericaSeries high efficiency condensing unit is backed by EMI and ECR
International and is tested and rated in accordance with AHRI Standard 210/240-2008
and UL- 1995. Due to ongoing product development, product designs and specifications
may change without notice. Please contact the factory for more information.
Corniest
where
it count:_
2
P!N 2400077_4,
_ev
A {i0!3;_.5001
i i i i i i i i i:i i
iiiiiiiiiiiiiiiiii
Completely
read all instructions
This manual
is intended
as an aid to
iiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
prior to assembling, installing, oper-
qualified
iiiiiiiiiiiiiiiiii
ating, orrepairingthisproduct.
iiiiiiiiiiiiiiiiii
Inspect all parts for damage prior to in-
installation, operation, and maintenance
of the EMI AmericaSeries high efficiency
condensing unit. Read these instructions
service personnel
for proper
................................
stallation and start-up. The EMI Ameri-
thoroughly and carefully before attempt -
.............................
caSeries high efficiency condensing unit
.......................
must be installed ONLY by q ualified
ing installation or operation. Failure to
follow these instructions may result in
iiiiiiiiiiiiiiiiiiiiiiiiii{i{!i!!!!i
installationpersonnel.
_mproper installation, operation, service,
or maintenance, possibly resulting in fire,
electrical shock, property damage, personal
injury, or death.
iiiiiiiiiiiiiiiii
Tampering
with
ous. Tamperingvoids
NOT attempt
iiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiii
Read all instructions
this unit is dangerallwarranties.
to modify
or change
unit. Install or locate this unit only in accordance with these instructions. Use this
DO
iiiiiiiiiiiiiiiii
this
iiiiiiiiiiiiiiiii
unitonlyforitsintendeduseasdescribed
iiiiiiiiiiiiiiiii
inthismanual.
iiiiiiiiiiiiiiiii
!!!!!!!!!!!!!!!!!
Checktheratingplateontheunitbefore
unit in any way.
iiiiiiiiiiiiiiiii
installationto
make certain thevoltage
iiiiiiiiiiiiiiiii
shownisthesameastheelectricsupplyto
the unit. The rating plate is located on the
iiiiiiiiiiiiiiiii
The EMI AmericaSeries must:
•
•
Be connectedto aproperlygrounded
electrical supply with the proper
voltage as stated on the rating plate.
iiiiiiiiiiiiiiiii
front
Have proper overcurrent protection
(i.e.time-delay fuse/HACRBreaker)
as listed on the rating plate.
iiiiiiiiiiiiiiiii
Wurnofftheelectricalsupplybeforeserviciiiiiiiiiiiiiiiii
"
iiiiiiiiiiiiiiiii
mgtheunit.
result in a fire, explosion, or electrical
shock causingproperty damage,personal
injury; or death.
240007754,
_{ev, A [05ff 5©9
panel only.
!!!!!!!!!!!!!!!!!
This unit must be connected only to a
iiiiiiiiiiiiiiiii
properly grounded electrical supply. Do
iiiiiiiiiiiiiiiii
!!!!!!!!!!!!!!!!!
not fail to properly ground this unit.
Failure to follow these instructions can
P/N
before using this
iiiiiiiiiiiiiiiii
Donotusetheunitifithasdamagedwiriiiiiiiiiiiiiiiii
ing, isnotworkingproperly,
iiiiiiiiiiiiiiiii
damaged or dropped.
$
orhasbeen
Mat:{÷
i_
tBe
USA
Controls and components
(Factory-installed or supplied)
Product description
The AmericaSeries S1CG/S1HG and S2CG/
S2HG condensing units are air-cooled, vertically-arranged side-discharge,high-efficiency
units designed specifically to meet or exceed
a 13 SEER rating.
The S1CG Models 09-36 and S 1HG Models
09-24 condensing units will provide cooling
and heating for a single evaporator, as identified on page 32 and page 33.
The S2CG/S2HG 18,000 (99), 21,000 (92)
and 24,000 (22) Btuh capacity condensing
units will provide cooling and heating for two
evaporators, as identified on page 34.
The
S1CG/S1HG
and S2CG/S2HG
•
•
•
•
•
Heat pump hard start
Cooling operation downto 32° F standard
on all units
•
Models 09-12 only:
- Large capacity suction accumulator
- Solid-core filter drier
Thermostatically-controlled crankcase heater (heat pump only)
Thermostatically-controlled
crankcase heater
Features
•
Compressor and fanmotor contactor
Run capacitor
Lowvoltage terminal connections
H.P.S. (High pressure switch) with
manual external reset
-
are
quiet units that can be recommended
for both
commercial
and residential
applications.
•
•
•
•
•
This feature energizes the crankcase
heater only when needed, saving unnecessarypower usage and increasing overall
system efficiency.
Installation of the S1CG/S1HG and
S2CG/S2HG condensing units is simplified by a 24v control interconnection
from the evaporator.
Multiple units can be lined up in close
proximity to an exterior wall.
Service valves are recessed to reduce
tampering.
All9,000-12,000 Btuh units are equipped
with a Duratec Performance Package that
includes an oversized suction accumulator with surge baffles and enhanced oil
management and a factory-installed solid
core filter drier.
A factory-installed crankcase heater is
standard on S1HG 09 &12 (thermostatically controlled) and S2HG models, and
is available as optional equipment on
other models.
Oomfo_t
where
it cou_'_ts
4
P!N 240007754,
Bey A [05£509I
System options
Installer-supplied
•
•
•
•
•
Power wiring
LowVoltwiring
(18 awgminimum)
Secure mounting pad or foundation
Refrigerant piping (ifnotpurchased
from
EMI)
•
•
High Volt Disconnect
Refrigerant for charging interconnect
ing (see charge table on page 15)
Corrosion-resistant
coil options (sea
coast and harsh environment usage):
Copper fin/copper tube condenser
coil
-
•
•
•
Coated aluminum
condenser coil
fin/copper
tube
LowAmbient
controls for cooling operation down to 0 ° F (standard equipment
can operate down to 32°F)
Optional field-installed
kit, when
specified, for cooling operation down
to O°F-- kit includes control, louvers
and wind baffle plus installation
Field-installed
pip-
.................
iiiiiiiiiiiiiiiii
Low Ambient controls are required
when the system is asked to cool at
outdoor temperatures below 32 ° F, this
may cause damage to the compressor
and coil, and may void the warranty. A
field-installed low-ambient
kit allows
operation down to 0 ° E
instructions
Low Ambient controls for operation
down to 0 ° F (consult factory for availability)
Models 09-12 only:
115v (single-zone only-SICG or
S1HG)
-
items
iiiiiiiiiiiiiiiii
This is accomplished
by cycling the
condenser fan on and off. This will,
in turn, maintain a constant low-side
pressure, providing a steady cooling
effect and keeping the air handler from
frosting-up.
thermostatically-con-
trolled crankcase heater for straight
cool units (S1CG or S2CG)
The optional kits include louvers/wind
baffle, crankcase heater, and/or outdoor
fan cycling switch, and installation instructions.
_/N
240007754,
Rev, A [05ff 509
5
Msd÷
i_
the
USA
Before installing,
•
•
•
•
•
consider:
2.
Locate the unit as close to the indoor section as possible. (see page 11.)
S 1CG/S2CG -- If the unit is used for low
ambient cooling down to 32°E S1CG/
S2CG require CCH.
Avoid high traffic areas and prevailing
wind locations.
Surface must be fiat and level.
In areas of heavy snowfall, condensers
should be set above the maximum anticipated snow line (12" is usually adequate
for most locations).
Unit Mounting
Instructions
Model S1CG is shown for example in the
following sequence.
The side- discharge unit allows forpermanent
mounting through the feet. This is highly
recommended due to the vertical design of
the unit.
Mount unit above typical snow fall level.
This is particularly important for heat
pump applications (S 1HG/S2HG).
1. Figure 1, Page 7:
- Bullet 1 -- Loosen the screws on left
and right sides of the front panel. (Do
not remove these screws.)
- Bullet 2 -- Remove the screws on the
front of the panel.
2. Figure 2, Page 7:
Slide front panel forward to clear side
screws and remove.
3. Figure 3, Page 7:
Insert lag bolts through the holes in the
bottom of the unit and tighten to secure.
4. Figure 4, Page 7:
Insert lag bolts through the holes in the
feet on the back of the unit and tighten
to secure.
5.
Site preparation
Replace the front panel, do not tighten
the side screws at this time.
Place the unit on a flat concrete surface
or pad if on the ground. Roof mounting
should use a build up platform to avoid
intake of hot air from the roofi
Oomfo_t
where
it cour_ts
@
P!N 240007754,
Rev A [05£50%
Figure 1
Remove front panel screws
Figure3
lag hole locations
A
Lag bolts
B
Filter drier
C
Compressor
D
Accumulator
E
Capacitor
Figure4
Figure2
Bottom
Lag holes in feet
Remove front panel
P/N 240007754, g{ev,A [05S5©9]
"d
Made i_ the USA
Figure5
Rating plate location
Figure6
Remove side panel screws
All electricalwiringmustberunaccording to NEC and local codes.
1. Figure S, Page 8 -- Refer to the unit rating plate for voltage, minimum circuit
ampacity and over current protection
requirements.
2. Use only HACR type breakers or time
delay fuses. Sdect the wire size according
to the ampacity rating.
3. To access electrical connections and wiring diagram:
a. Figure 6, Page 8 -- Remove the
screws on the side panel adjacent to
the back panel.
b. The screws adjacent to the front panel
should alreadybeloose (don't remove
them).
c. Slide the side panel out to access the
high/low electrical connections and
wire diagram.
d. Figure 7, Page 9 -- Remove the
plastic edge guards from the holes and
replace with a water-tight strain relief
fitting (High V) and a split grommet
fitting (low V)
4. Power should be run to a weather proof
disconnect box usually within 3 feet of
the unit.
Comfort
where
it cour_ts
8
P!N 240007754,
Bey A [05£509I
5.
Figure 8, Page 9 -- From the disconnect
box, run the power through the 7/8"
hole on the side of the unit and into the
electrical box. Anchor with the strain
relief fitting.
6.
Run wires to the high volt pigtail in the
control box and attach L1 and L2 con-
Figure7
Power entrances
Figure8
High voltage
connections
Figureg
Lowvoltage
connections
nections. Also run green wire to ground
wire.
7. Check wiring diagram for the required
number of low voltage wires to be run
between indoor and outdoor sections.
g.
Figure 9, Page 9 -- Connect the 24 volt
wiring matching color to color. Refer to
the wiring diagram on the inside panel of
the condenser, and also refer to the wiring diagram on the indoor unit. Low volt
interconnect should be at least 18 awg.
9.
See Figure 10, Page 10 and Figure 11,
Page 10 for completed wiring of SICG
and S2CG examples.
10. To replace side panel slide the slotted
holes of the panel onto the loosened
screws of the front panel so that the edge
of the front panel covers the edge of the
side panel.
11. Fasten all remaining loose screws.
P/N 240007754,
_tev, A [05S 509
9
Made in the USA
Figure 10
Completed
wiring, S1CG
Figure 12
Replacing
Figure 11
Completed
wiring, S2CG
Figure 13
Fasten loose screws
Comfort where it cou_'_ts
J,,,O
side panel
P!N 240007754, _SevA [05£50%
P-trap installation
Tubing specifications
•
The system will support refrigerant runs to
the inside unit as listed in Table 1, Page 11.
The units are furnished with sweat connections and are equipped with refrigerant valves
and Schrader fittings for charging and taking
pressure readings.
•
A P-trap is recommended when the
suction riser is equal to or greater than
show in Figure 14, Page 11 and Table 1,
Page 11.
When the condenser is installed above the
evaporator, the P-trap will help the return
of oil back to the compressor.
Figure 14
P-trap placement
(seeTable
Page 11 for dimensions
It is recommended that a filter drier be
ins tall e di n th e liq u idli ne, at th e in d oor
1,
H & P)
Condenser
unit
models
factory-installedonfilter
drier without
(i.e. 18K aand
larger).
H
maximum
Table 1
Sl CG/S2CG tubing
specifica-
tions (see Table 14, Page 11 )
P
maximum
Evaporator
•
12
1/4"
1/2"
•
24
3/8"
3/4"
•
36
P/N 240007754,
3/8"
Rev, A [05J 509]
3/4"
•
AP-trap maybe fabricatedusing (2) street
elbows and (2) regular elbow.
A prefabricated trap may be purchased
from a wholesaler or distributor however
the trap shouldbe shallow as with the (3)
elbow configuration.
Each elbowis approximately 2 equivalent
feet.
•
One P-trap is equal to approximately
12 equivalent feet.
P-traps are not required at the foot of the
hot gas risers due to increased oil flow at
higher temperatures.
J,,,J,,,
Made in the USA
Figure
15
Clean ends of tubing
• Avoid piping on wet and rainy days•
!!!!!!!!!!!!!!!!!
• Use only clean, refrigeration-grade
copper tubing.
• Use tubing benders
kinking.
• Be certain
to guard against
no burrs remain
on the
fittings•
• Cap ends of lines until ready for con..................
nectiÙns.
Figure 16
Wet rag "heat shield over valves
Figure 17
Make a shield to protect
• Be certain that plastic end caps remain
....................
in pl acew h eninsertin g th rou gh w all
......................
...............
openings
• Insulate the suction line•
iiiiiiiiiiiiiiii_i
• Isolate tubing from transmitting vibration to the building or unit and avoid
contact with sharp edges•
• Wrap refrigeration valves with a wet
rag "heat sink" to protect v alyes while
brazing. (See Figure 16, Page 12.)
Refrigerant
piping
1. Clean the ends of tubing and insert into
fittings (Figure 1S).
2.
paint
Protect valves by wrapping with a wet rag
"heat sink" before brazing (Figure 16).
3.
Use a shield to protect the paint as shown
in Figure 17. (The shield can be made
from scrap metal.)
4.
Braze tubing into fittings.
Comfort
where
it cou_'_ts
S,,,2
P!N 240007754,
_SevA [05£50%
Charging the unit
Figure 18
Manifold
set connections
at unit
1. Attach manifold set (Figure 18).
2. Evacuate line to 500 microns or less to
ensure all moisture has been removed and
there are no leaks (Figure 18).
3. Once certain of a good evacuation and
leak free joints, back-seat the valves
(counter-clockwise) to open and allow
factory charge to filllines and indoor unit
(Figure 18, Page 13).
i ii i i!i!iiiiii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Refer to refrigerant charge table for specified charge.
4.
Charge to proper weight, charge based
on feet of interconnect (see tables on
page 15). Only add/remove 410A in
liquid form.
5.
Refer to charts beginning on page 17 to
"fine tune" the refrigerant charge to meet
your conditions.
M1 systems require field charge adjustments. Refer to the "Refrigerant Charge
Tables" for proper weight charge and
to the supplied "Single-zone Operation
Charts" for proper system pressures and
temperature at different outdoor conditions. Superheat should be used for final
system charge.
Figure 19
Manifold
A
Manifold
C
Micron
Figure 20
set up for evacuation
B
Vacuum pump
gage
Charging
Charging should be done with a dial-acharge or weighed in with a scale.
When charging and checking pressures/
temperatures on system supplied with
Low Ambient Option, the fan cycle
switch should be jumped out of the
circuit temporarily to obtain accurate
.................
data.
P/N 240007754,
_tev, A [05S 5©9
S,,,3
['VSadein the USA
It is illegal to discharge refrigerant into
iiiiiiiiiiiiii{'ii{i!iiiiiiiiiiiiiiiiiii
i theatmosphere.
Useproperreclaiming
methods&
equipmentwheninstalling
or servicin g thi s unit.
...................
The units are delivered pre-charged with
refrigerant for the condenser coil and the
evaporator. Charging of the fieldinstalled piping is required. Refer to the refrigerant charge
table for the proper amount to be added for
the applications interconnect piping. Unit
service valves are solid brass, for sweat connections.
Comfort
where
it counts
iiiiiiiiiiiiiiii;
iiiiiiiiiiiiiiii_
iiiiiiiiiiiiiii_
iiiiiiiiiiiiiiiiii
Pressuretest all field installed piping
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
with nitrogen. Using a suitable vacuum
iiiiiiiiiiiiiiiiii
pump, evacuate the tubing and indoor
iiiiiiiiiiiiiiiiii
unit to SO0microns or less, with service
iiiiiiiiiiiiiiiiii
valves remaining front seated (closed).
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
Before releasing the refrigerant from the
iiiiiiiiiiiiiiiiii
condenser,
be sure the manifold gauge
set is closed so as not to lose vacuum
iiiiiiiiiiiiiiiiii
when shutting down the pump.
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
iiiiiiiiiiiiiiiiii
Release refrigerant from the condensing
unit by back seating the service valve. Mlen wrenches are used to open the valve.
Replace valve caps. DO NOT back seat
the valves past the snap flanges that hold
the valve core in place.
S,,,4
P!N 240007754,
_SevA [05£50%
iiiiiiiiiiiiiiiii:
1. To find the charge adjustment
length:
iiii!}iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Line Adjustment
!!!!!!!!!!,s_s_
!!!!!!!!!!!,s_s_
2
S1CG/S1HG
S 1CG9
= (Line Charge/FT} x Line Length
CAH09
refrigerant
.25 oz/ft
and allow for gauges and hoses.
charge
table
39.5
$1HG9
WLH09/UNH09
(23 g/m)
S 1CG8
CAH24
.64 oz/ft
$1CG3
CAC36
.64 oz/ft
65.25
$1HG8
WLH24/UNH24
.25 oz/ft
97.5
S1HG9
.64 oz/ft
WLH24/UNH24
.64 oz/ft
63.0
CAH09
.25 oz/ft
51.52
(23 g/m)
S1HG8
39.5
(23 g/m)
S1CG8
51.52
(59 g/m)
(59 g/m)
WLH09/UNH09
.25 oz/ft
(23 g/m)
(59 g/m)
S1CG9
and tubing
System Total = Factory Charge + Line Adjustment
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!i!!!!i
2 Round to the nearest ounce
Table
and system charge for any evaporator
CAH24
.64 oz/ft
63.0
(59 g/m)
65.25
(59 g/m)
$1CG3
WLC30/UNC36
.64 oz/ft
97.5
(59 g/m)
P/N
240007754,
_{ev, A [05]
50%
S,,,5
Ma(_e
in
the
USA
iiiiiiiiiiiiiiiiii
1. To find the charge adjustment and system charge for any evaporator and tubing
length
.............................
Line Adjustment
........................
System Total
= (Line Charge/FT)
x Line Length
= Factory Charge + Line Adjustment
..................
2. Round to the nearest ounce and allow for gauges and hoses.
Table 3
S2CG/S2HG refrigerant
.25 oz/ft
$2CG99
$2CG92
(2)WLHG09
WLHG09+WLHG12
charge table
40/40
$2HG99
(23 g/m)
.25 oz/ft
40/34
$2HG92
(2) WLHG09
WLHG09+WLHG12
(23 g/m)
$2CG22
(2) CAHG12
$2CG99
UNHG09
.25 oz/ft
(23 g/m)
.25 oz/ft
Comfort
UNHG09+UNHG12
_:
where
it counts
25 oz/ft
"
,
(23 g/m)
40/40
.25 oz/ft
40/34
(23 g/m)
34/34
$2HG22
40/40
$2HG99
(2) CAHG 12
UNHG09
.25 oz/ft
34/34
(23 g/m)
.25 oz/ft
40/40
(23 g/m)
(23 g/m)
$2CG92
.25 oz/ft
(23 g/m)
40/34
$2HG92
S,,,6
UNHG09+UNHG12
.25 oz/ft
, ,
(23 g/m)
P!N 240007754,
_ev
40/34
A [05£50%
Cooting
Cycte
Model
S1CGgO00
&StHG9000
Cooling
Cycle
Model
S1CG9000
&S1HG9000
withEMI's-WLH09
&UNH09
(R-410A
Ret)
withEMI's-CAHG09
(R-410A
Ref,)
55O
550
490
490
430
430
o_ 370
370
310
310
250
250
170
170
150
150
_.
o_
_
o_ 130
m
110
110
90
90
35
35
25
8
130
_-
25
15
15
65
75
85
95
105
115
65
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F
P/N 240007754, _ev, A [05S509
75
85
95
105
115
Outdoor
Ternp
(° F)
Note:
Minimum
compressor
superheat
5° F
_,,,7
['_$a_:_÷
in the USA
mul
Amica vies
Cooling
Cycle
Model
S1CG2000
$S1HG2000
Cooling
Cycle
Model
S1CG2000
&S1HG2000
withEMI's-WLHG12
&UNHG12
(R-410A
Reh)
withEMI's-CAHG12
(R-410A
Ref,)
55O
550
490
490
430
_
430
9_
_=
_,
_.
370
370
310
310
25O
25O
170
170
150
_
150
130
130
110
110
90
o_
35
N-
25
_4
_
15
_
35
65
75
85
95
105
115
15
65
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F
Comfort where it cou_'_ts
25
75
85
95
105
115
Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5°F
S,,,8
P!N 240007754, Rev A [05£50%
Cooling
Cycle
Model
S1CG8000
&S1HGS000
Cooling
Cycle
Model
S1CG8000
&S1HG8000
withEMI's-WLHG24
&UNHG24
(R-410A
Ref,)
_-
withEMI's-CAHG24
(R-410A
Ref,)
550
550
49O
490
430
_
430
370
_-
370
310
310
250
250
170
170
150
Ao
2g_
8
_
150
130
130
110
110
90
90
35
35
25
_-
25
15
8
15
5
65
75
85
95
105
115
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F
P/N 240007754, _ev, A [O5S509
65
75
85
95
105
115
Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5°F
_,,,9
r'_$a_:_÷
in the USA
Cooling
Cycle
Model
S1CG4000
&S1HG4000
with
EMrs-WLHG24
&UNHG24
(R-410A
Ref,)
550
Cooling
Cycle
Model
S1CG4000
&S1HG4000
withEMrsCAHG24
(R-410A
Ref,)
550
Room
Temp(°F)
Relative
Humidit'
490
490
-_ 43o
-_ 43o
_-
_-
370
370
170
170
150
250
I_
250
150
310
I_
310
_
13o_-_@
_
13o
110
_-
110
90 _
35
__
90
35
25 _
_
25
_
15
_-15
75
85
95
105
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
50F
Comfort where it oou['}ts
115
65
20
75
85
95
105
Outdoor
Temp
(° F)
Note:
Minimum
compressor
superheat
5°F
115
P!N 240007754, Rev A Z05£50%
Cooling
Cycle
Model
SLOG3000
Cooling
Cycle
Model
S1CG3000
withEMI's-WLCG30
&UNCG30
(R-410A
Ref.)
withEMI's-CACG30
(R-410A
Ref.)
55O
550
490
490
430
_
430
_- 370
_-
370
_
310
310
250
250
170
170
150
_.
130
o_ 130
110
110
90
90
150
35
_-
25
8
15
£
75
85
95
105
Outdoor
Temp
(oF)
Note:
Minimum
compressor
superheat
50F
P/N 240007754, _ev, A lOSS509
115
25
65
2]...
75
85
95
105
Outdoor
Temp
(oF)
Note:
Minimum
compressor
superheat
50F
115
['_$ac:_÷
in the USA
Cooling
Cycle
Model
S1CG6000
Heating
Cycle
Model
S1HGgO00
withEMI'sWLHG09
&UNHG09
(R-410A
Ref,)
withEMI's-CACG36
(R-410A
Ref,)
55O
380
Room
Temp
(°F)
Relative
Humidb
490
350
430
_
320
_- 370
a-
290
310
260
250
230
170
130
150
_
q
ilili
130
110
_
110
_
9O
70
II
I
90
50
_"
35
30
_-
25
N8
15
€
20
10
65
75
85
95
105
115
10
Outdoor
Temp
(°F)
Note:
Minimum
compressor
superheat
5oF
Comfort where it cou_'_ts
20
30
40
50
60
Outdoor
Temp
(°F)
22
P!N 240007754, _SevA [05£50%
Heating
Cycle
Model
S1HGgO00
withEMI'sCAHG09
(R-410A
Ref,)
Heating
Cycle
Model
S1HG2000
withEMI's-WLHG12
&UNHG12
(R-410A
Ref,)
380
38O
350
350
_
320
_
320
";-
290
_-
290
_-
260
260
230
230
130
130
11o
_
110
90
_-
90
o
70
50
30
30
8
20
20
}
lO
I0
10
20
30
40
50
60
Outdoor
Temp
(°F)
P/N 240007754, Rev, A [05S509
30
40
50
Outdoor
Temp
(oF)
23
Made in the USA
Model
s1HGZOUO
withEMI's-CAH12
(R-410A
Ref,)
MOdel
b lIflbZUUU
withEMrs-WLHG12
& UNHG12
(R-410A
Ref,)
380
38O
350
350
_
320
_
320
_-
290
_-
290
260
260
230
230
130
130
_
110
11o
_-
90
_-
90
50
_-
30
30
20
20
10
I0
20
30
40
50
60
Outdoor
Temp
(oF)
Comfort where it oou['}ts
10
20
30
40
50
60
Outdoor
Temp
(oF)
24
P!N 240007754, Rev A [05£50%
Model
5]HGZOO0
withEMI's-CAH12
(R-410A
Ref,)
MOdel
bllflb_ddd
withEMrs-WLHG24
&UNHG24
(R-410A
Ref,)
380
38O
350
350
_
320
_
320
";-
290
_-
290
_-
260
260
230
230
130
130
11o
_
110
90
_-
90
o
70
50
30
30
8
20
20
}
lO
I0
10
20
30
40
50
60
Outdoor
Temp
(°F)
P/N 240007754, Rev, A [05S509
30
40
50
Outdoor
Temp
(oF)
25
Made in the USA
Model
SlHGSOO0
with
EMrsCAH24
(R-410A
Ref,)
MOdelb llflbqUUg
withEMrs-WLHG24
&UNHG24
(R-410A
Ref,)
380
38O
350
350
_
320
_
320
_-
290
_-
290
260
260
230
230
130
130
_
110
11o
_-
90
_-
90
50
_-
30
30
20
20
10
I0
20
30
40
50
60
Outdoor
Temp
(oF)
Comfort where it oou['_ts
10
20
30
40
50
60
Outdoor
Temp
(oF)
26
P!N 240007754, Rev A [05£50%
Model
5]HG4OUO
with
EMI'sCAH24
(R-410A
Ref,)
380
350
_
320
";-
290
260
230
130
110
A-
90
o
30
8
20
0
10
20
30
40
50
60
Outdoor
Temp
(°F)
P/N 240007754, Rev, A [05S509
27
Ma(_ein the USA
9,000-
The S 1CG/S
12,000 Btuh units
sections
In low ambient cooling, ifa crankcase heater is
installed, power the system 24 hours before
attempting to start the unit in cool weather
(below 60 ° F).
1HG and S2CG/S2HG
are the compressor
bearing
outdoor
units
of
the system. It operates at the command
of the
indoor section or room thermostat.
Therefore,
the system operation
will be described
in the
manual pertaining
to the indoor section.
EMI units are designed and constructed
for reliability and long life with minimal
maintenance. You can assure peak operating
efficiency by regularly inspecting for free air
passage into and through the coil. If debris
collects on the air coil, it should be cleaned
by "back-flushing" with a spray of water or
vacuuming.
TURN OFF POWER SUPPLY
FIRST. Outdoor units may be cleaned or
waxed if desired. Use a non-abrasive car wax
(on metal surfaces only).
Test unit data sheet
After doing a final system check using the
Operation Charts (supplied on previous
pages).
Record results on Test Unit Data Sheet on
page 36.
Before leaving
Remove gauge set. Mount all access panels
and make sure they are properly secured.
This unit is equipped with a permanently
lubricated motor. Mthough oiling is not necessary; adding a few drops through the oiling
ports twice yearly will extend the life of the
motor. Do not over oil.
Make final visual inspection and repair any
deficiencies.
Panels
should
remain
on the unit at all times.
Service should be performed
service agency only.
A hard start kit may be required for units
in low voltage applications.
by a qualified
Specific changes
All EMI products are subject to ongoing
development programs so design and specifications may change without notice. Please
consult the factory for more information.
Comfort
where
it cour_ts
28
P!N 240007754,
_SevA [05£50%
EMI AmericaSeries condensers are designed
to operate with EMI AmericaSeries evaporators. Both the condenser (outdoor unit) and
evaporator (indoor unit) have a high volt service connection. Each is to be independently
connected to the electrical service panel. (See
the unit name plate for the correct breaker
type and size). The outdoor and indoor units
are also connected to each other through a low
volt interconnect wiring. A 24v transformer
located in the indoor unit provides the low volt
power source.
temperature below the room temperature, the
reversing valvewill energize (R & O heat pumps
only) along with the compressor and outdoor
fan (R & Y). When the indoor control is satisfied and the room temperature falls below the
set temperature, the compressor and fan will
de-energize. The anti-short cycle timer (ASCT)
will prevent the compressor from re-starting for
three minutes.
Heating operation
Heating operation requires that the control
(either unit mount or remote wall mount, heat
pump thermostat) make a connection between
low-Volt terminals "R" and "Y" only. When the
indoor control is placed in heating mode, with
the set point temperature above room temperature, the compressor and outdoor fan (R
& Y) will energize. When the indoor control is
satisfied and the room temperature rises above
the set temperature, the compressor and fanwill
de-energize. The anti-short cycle timer (ASCT)
will prevent the compressor from re-starting for
three minutes.
Straight cool condensers are designed to operate as a single stage cooling unit. Heat pump
condensers are designed to operate as a single
stage cooling two stage heating unit. For proper
operation the unit must be matchedwith an appropriate EMI indoor unit with unit mounted
controls and/or wall mounted thermostat. For
two-stage heating operation the indoor unit
must be equipped with an electric strip heater.
.............................
For remote wall mounted thermostat
.........................
operation be sure to select EMI p/n
Defrost controls with short cycle
protection (heat pumps only}
iiiiiiiiiiiiiiiiiiiiiiiii!i!i!!i
240004180orasuitable24v,
twostage
heating, heat pump thermostat.
Condenser
The
The unit is equipped with
designed to keep system
ficiency. The 24v circuit
the indoor and outdoor
three minute, anti-short
compressor protection.
operation
transformer
located
in the indoor
unit
provides
24v, low-volt control power to the
condenser (outdoor unit). This canbemeasured
across low-volt terminals "R" and "C".
The defrost control circuit is designed to keep
the condenser coil free from frost and ice during
heatingmode. This is accomplished through the
precise switching sequence of the outdoor fan,
reversing valve and indoor auxiliary heater.
Heat pump condensers utilize areversing valve
to provide reverse cycle operation. Therefore
the outdoor unit will act as either a condenser
or an evaporator there-by providing comfort
cooling or heating to the indoor space. The
reversing valve is energized in cooling. Should
the valve fail to actuate, the system will default
to the heating mode of operation.
Defrost
Cooling operation requires that the control
(either unit mount or remote wall mount thermostat) make a connection between low-volt
terminals "R" and "Y" along with "R" and "O"
(heat pumps only). When the indoor control
is placed in cooling mode, with the set point
240007754,
_{ev, A [05ff 5©9
initiation
The defrost-sensor is located on either the end
plate or the return bend of the condenser coil.
A defrost cycle will initiate after the sensor
doses (approx. 30 ° F) and remains closed for
the length of time selected on the control board
(either 30, 60 or 90 minutes)*.
Cooling operation, single- and dual-zone
P/N
a logic control circuit
operating at peek efprovides control to
systems including a
cycle timer (ASCT)
At the start of the defrost cycle, the reversing valve will change from heating to cooling
mode. The condenser fan will also switch off
there-by allowing pressure and temperature
29
rVSat_e in
the
USA
BI
m
W
to rise within
_
the condenser
)i
iii!i
5 i);
_!!_
))))_!!_
)i:iJ
<);
)i'ii
= @ )!;i¸iii!¸¸¸
))
_;;!ii)i:iJ
<);
i_ii
_;i;iii
¸i:);!
)_[i;_!i;
)))i
¸ii
)i
!i!_
)?ii
_;!ii
)i'ii
0 _!i!_
¸!15/!
_!!ii
i?ii
Li;!!!_
)) _
coil to melt off
Figure 21
any ice build-up. At the same time the unit will
switch on the indoor electric strip heater to
temper the cold air being discharged from the
evaporator unit. This will continue until either
the defrost-sensor
opens (approx. 60 ° F) or a
10-minute
maximum
cycle time has elapsed.
Defrost times will vary depending
on outdoor
temperature
and moisture
conditions.
When
the defrost cycle is complete the unit will return
to normal heating operation.
*Factory settings
9-24k
result in injury
or electric
DFT TST
If the condenser
coil is heavily frosted
up with ice, it is likely that the "Defrost
Sensor" is already closed. In this case the
"R and DFT" jumper can be eliminated.
To initiate
defrost,
momentarily
jump
pins marked "DFT TST" until the defrost
cycle begins. The unit will remain
in
defrost mode until the condenser
coil is
defrosted and then it will return to heating mode. When testing is complete
be
sure to remove the jumper(s).
DO NOT
leave the unit in test mode with jumper (s)
With the system "off", using two small alligator
clips, jumper the following sets of test pins. "R
and DF2" and "DFT TST".
board
Apply power to the indoor and outdoor units.
Place the indoor unit in heating mode with the
set point temperature
well above room temperature. This is to ensure that the condenser
will remain
operation.
on during
the entire
defrost
test
Low ambient
The condenser
will operate in heating for approximately 20 seconds. At that point the unit
will enter defrost mode for approximately
2
seconds. During this time the condenser
fan
will switch off, the reversing valve will energize
and the defrost board will energize the indoor
electric heat relay through the "W" terminal.
After the two second defrost cycle is complete,
the unit will switch back to heating operation
for another 20 seconds. This process will repeat until the jumpers are removed from the
operation
Ifthe unit is equipped with low ambient fan control for cooling, the fan will remain off (while
in cooling mode) until the condenser pressure
reaches 340 psi. The fan will then energize and
run until the condenser pressure falls below
247 psi. This will happen only in the cooling
mo de (or when the reversing valve is energized).
In heating (reversing valve not energized), the
fan will run continuous so long as the connection is made between "R" and "Y".
test pins.
Comfort where it cour_ts
R and DF2
shock.
Defrost operation
can be initiated using the
test pins located on the circuit board of the
condensing
unit. "Defrost test operation"
will
be a time compressed
version of the actual
defrost cycle.
Defrost control
board (SlHshown)
Btu = 90 minutes
Beforeremovingtheaccesspanelstothe
unit make sure that all power is disconnectedfromtheunit.
Failureto do so could
)))))))))))))),=
))))))))))))))),
Defrost control
30
P!N 240007754, Bey A [05150%
iiiiiiiiiii
.... i!ii!i!!i!iiiiiiiiiiiii
i iii iii! i !il
Performance
data listed in this manualis subject to change without notice. For the most current unit/system
performance
data, please refer to the ECR International
listing of certified
products in the AHPd directory; at www.ahridirectory.org.
Due
to ongoing
product
development,
designs,
specifications,
and performance
are
subject to change without notice. Please consult the factory for further information.
E
1/2" Diameter
Lag Holes
_iii};_iiN#iii/iiiiiii[iiii!!iiiiiiii_:iiiiiiiiii_iii_iii;;iiiiiiliii#_
iii
_
A-_
!:_%iii_ii_;iiiiii!ii_;i;ii!_iiiii!!iii,;,},iiiiiii_iiiii/ii!i!i!iii_ii!
I il
...................................
B ........................................
A
Electrical connections
Table 4
Dimensional
S1CG/S1 HG9
data, sound data and shipping
Easy access interconnects
on back of unit
weights
4 sis
(117)
14 u/_o
(373)
3
(76)
12 z/_
(316)
24
(610)
15
(381)
36
(914)
59
98
32
(813)
15
(381)
36
(914)
62
156
38
S1CG/S1HG8
18
4 _/_,
(117)
22 _/_6
(570)
3
(76)
12 7/_6
(316)
S1CG3
3O
7
(178)
23 _s/_,
(608)
3
(76)
127/_o
44
(1118)
210
(965)
15
(381)
68
(316)
23 _s/_,
(608)
3
(76)
12 7/_6
(316)
38
(965)
15
(381)
44
(1219)
68
159
23 _s/_6
3
(76)
12 7/_6
(316)
38
(965)
15
(381)
44
(1219)
68
187
S2CG/S2HG99
9 + 9
7
(178)
S2CG/S2HG92
9+12
(178)
7
P/N
240007754,
Rev, A [O5_ 509
(608)
3[_ii,
['?_ade in
the
USA
mun
W
Table 5
$I CG electrical
BIIII
SICG2A
Amic@ies
.... iiiiS_i_43i!ii!!_:!_ii%_qi_
il}ii_iiii!4_!i_ii!!!i:Lii
¸ _!i!i_ii_sii:_i
i_iii_!i!iiiiiiiii3i3q!i_i!_iii3_i:_ili!_
i!Y/81i(iiL!_ii!i_il
....
115/60/I
specifications
1.4
0.125
9.9
53
11.3
104
13.8
20
SICG2D
208/230/60/I
0.8
0.125
5.2
27
6.0
197
7.3
15
SICG4D
208/230/60/I
0.8
0.125
8.0
43
8.8
197
10.8
15
SICG6D
208/230/60/I
1.8
0.330
12.7
74
14.5
197
17.7
30
S1 CG performance
Table 6
Cooling
$1CG9
WLHG09
S1CG8
WLHG24
S1CG3
WLCG30
Table 7
Cooling
$1CG9
UNHG09
S1CG8
UNHG24
S1CG3
UNCG36
Table 8
Cooling
S1CG9
S1CG8
S1CG3
(Do_l"_l_t
where
it counts
Indoor
Units
systems with wall units
13.0
0.74
12.2
R410A
18,000
13.0
0.77
12.0
R410A
28,200
13.0
0.79
11.7
R410A
systems with universal
units
13.0
0.74
12.2
R410A
18,000
13.0
0.77
12.0
R410A
28,200
13.0
0.79
11.7
R410A
systems with cassette units (__ = G or H)
9,000
CAH24
data: Matched with EMI AmericaSeries
13.0
0.77
11.4
R410A
13.0
0.75
12.7
R410A
13.0
0.77
12.4
R410A
$2
P!N 2400077_4,
Rev
A I0!S:£50%
Table 9
SI HG electrical
SIHG9A
115/60/I
specifications
1.4
0.125
7.5
47
8.9
104
10.8
15
S1HG9D
208/230/60/1
0.8
0.125
3.9
20
4.7
197
5.7
15
S1HG8D
208/230/60/1
0.8
0.125
5.9
43
6.7
197
8.2
15
1
$1 HG performance
Table 10
S 1HG9
Table 11
S1HG9
Table 12
S1HGg000
S1HGS000
data: Matched with EMI AmericaSeries
Indoor Units
Heat pump systems with wall units
WLHG09
%000
%000
13.0
7.7
Heat pump systems with universal
UNHG09
13.0
0.72
12.8
3.3
R410A
units
7.7
0.72
Heat pump systems with cassette units (_ = G or H)
9
9,000
8,200
13.0
7.7
0.74
11.8
3.2
R410A
24
18,000
16,400
13.0
7.7
0.76
12.1
3.4
R410A
CAH
CAH
WL C/WL H
CAC/
CAH
SICG/SIHG
Single zone
P/N
240007754,
Rev, A [05S 5©9]
33
U N CI U N H
Made
in
the
USA
Table 13
9200
S2CG electrical
i208/230/60/1
0.8
S2CG performance
Table 14
S2CG cooling
WLHG09+WLHG09
WLHG09+WLHG
Table lS
12
specifications
0.125
3.9
20
5.2
27
8.8
data: Matched with EMI AmericaSeries
197
10
15
Indoor Units
systems with two wall units
$2CG99
18,000
13.0
0.80
11.9
R410A
$2CG92
21,000
13.0
0.74
12.0
R410A
S2CGcooling systems with two universal units
UNHG09
+ UNHG09
$2CG99
18,000
13.0
0.80
11.9
R410A
UNHG09
+ UNHGI 2
$2CG92
21,000
13.0
0.74
12.0
R410A
11.5
R410A
Table 16
CAH_09
S2CG cooling
+ CAH09
......................
CAH 09+CAIq
CAC/
CAH
systems with two cassette units (__ = G or H)
$2CG99
18,000
! _ .................. $2CG92 ............................
13.0
0.75
...............
13.0 ........................................
0:75 .....................
iI................
]1:5 .............................
E_4]0_ .............
mmumm
A
_mW
Table 17
9200
SPiB8
S2HG electrical
208/230/60/1
0.8
S2HG performance
Table 18
Table 19
specifications
0.125
3.9
20
5.2
27
8.8
i!
data: Matched with EMI AmericaSeries
197
10
15
Indoor Units
Heat pump systems with wall units
WLHG09+WLHG09
WLHG09+WLHG
::: :
....
iiiiS_i_ii3i!ii!!_:!_ii%;qi_
il}ii_iiii!:q!_;i_;i!!!i:i:i
¸_;i!i;ii_sSi
i_iii_;i!iiiiiiii;i3i3q!i_i!_iii3_i;_ilis
i!YISi/i_L!_ii!i;il
....
12
$2HG99
18,000
17,600
13.0
7.7
0.80
11.9
3.3
R410A
$2HG92
21,000
20,000
13.0
7.7
0.74
12.0
3.3
R410A
Heat pump systems with universal
units
UNHG09
+ UNHG09
$2HG99
18,000
18,000
13.0
7.7
0.80
11.9
3.3
R410A
UNHG09
+ UNHG12
$2HG92
21,000
20,000
13.0
7.7
0.74
12.0
3.3
R410A
Table 20
Heat pump systems with cassette units (_ = G or H)
WL C/WL H
CAC/
CAH
S2CG/S2HG
Dual zone
P/N
240007-/54,
_ev, A [05S 509]
$5
UNC/UNH
Ma(_e
in
the
USA
i!!!!_!_!_i_i_i!iiiiiiiiiiii_!_ii_!_i_!i_i_ii_i!!i_i_i_i_iiiiiii_i!_!!!i_
_ii_i!_ii_i!_ii_ii_i_!!_i_!!
_i!_i_ii_i_ii_!i_i_ii_i_!i_ii_ii_ii_ii_il
_i_i_!_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_!_!_!
_I_!I_I_!I_II_I!!II!I
_i_!!_i_!!_i!!ii!ii!ii
_!_!_!_!_!_i_i_
Technician:
, Se_!a!Number..................................................................................................................................
_ iMede! ....................
c°°!!n_! ......................................................................................
Evaporator Entering Air - WB
Evaporator Leaving Air- DB
i
Leaving Air
Compressor Suction - PSIG
Compressor - Volts
............................................................................................................................................................................................................................
.......................................................................................................................
_OD Fan Motor - Volts
ID Fan Motor- Amps
:.................................................................................................................................................................
_
.....................................................................................................................
Total Volts
Compressor Suction
Compressor Discharge
Liquid Out Cond.
i
......................................................................................................................
Liquid before Expansion
Suction out Evaporator
DB - Temp Split at evap.
Compressor Superheat
Comfort
where
it cou_'_ts
$G
P!N 240007754,
_ev A [05£50%
_/N
240007754,
_tev, A [05ff 5©9
$7
Made
in
the
USA
Bi
Comfort
i
W
where
....:i
iiii_!i,
ii
i!ii
ii
ii
:_i:i
iiii
I::i_
i_
i_= 0 iii[Ji
ii_
i¸_ii!_i
_ I:
!!0 i_i_
_!i_
ii:_
_i:l
i!_ii
¸_!i!i_
ii
!i_i!:i_
!!
i__ii!ii
i_ii
_i;;
ili!_
i!_¢_I
_ii_i
ii_
i_!i
_ii!i_
ii =_
it cou_'_ts
38
P!N 240007754,
tSev A [05£50%
_£N 240007754,
_tev, A [05ff 5©9
$9
Matte
in
the
USA
WLC/WL H
High Wall Air Handler
UNC/UNH
Air Handler
SICG
Single Zone
Side Discharge
S2CG &,
Dual Zone
Side Discharge
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 40 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Mar 14 04:17:23 2010 Author : Title : Subject :EXIF Metadata provided by EXIF.tools