EMI Air Conditioner/heat Pump(outside Unit) Manual L1003136
User Manual: EMI EMI Air conditioner/heat pump(outside unit) Manual EMI Air conditioner/heat pump(outside unit) Owner's Manual, EMI Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
SICG/SIHG S2CG/S2HG Single-Zone Dual-Zone Side-Discharge Ductless Split-System Condensing Units for R410 Refrigerant 2.6 I i 3.5 i 5.3 S2CG i 7.0 i 8.3 10.5 orS2HG i kW i i Units i Installation, Operation and Maintenance Manual SICG SIHG S2CG S2HG P/N 240007754, Rev. A [051509] Contents Verify .............................................................. unit before Mounting the Electrical Wiring Refrigerant Starting 6 8 ....................................................... 11 .................................................... 13 Charts ........................................................ 17 Unit ........................................................ 28 the Operation 4 ......................................................... Processing Operation 2 .................................................. Unit ........................................................ Piping Refrigerant installing and Maintenance Single-zone and Dual-zone ................................................. Condenser Sequence 28 of Operation .......................... 29 Single-zone and Dual-zone Condenser Sequence of Operation, Testing Defrost Operation Using Test Pins ........................................ 30 Specification 31 Test Unit and Dimensions Performance EMI's Product Line ................................................ Data Sheet ............................................. 36 ....................................................... 40 iiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiii Retain this manual and warranty for future reference. Before leaving the premises, review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly. Shipping damage MUST be reported to the carrier IMMEDIATELY. Examine the exterior. Remove cover and examine compressor and piping for signs of damage. To obtain technical service or warranty assistance during or after the installation ofthis unit, contact your local representative. For alocal representative listing, visit our web site: Inspect each component for damage. Concealed damage must be reported to the carrier within IS days of the receipt of the shipment. The carrier must make proper notation on the delivery receipt of all damage identified and complete a carrier inspection report. The purchaser must notify ECR International's Customer Service Department of all damage and is responsible for filing any necessary claims with the carrier. For further assistance call: When calling for assistance, please have the following information ready: Model Number Serial Number iiiiiiiiiiiiiiii_ Date of installation The EMI AmericaSeries high efficiency condensing unit is backed by EMI and ECR International and is tested and rated in accordance with AHRI Standard 210/240-2008 and UL- 1995. Due to ongoing product development, product designs and specifications may change without notice. Please contact the factory for more information. Corniest where it count:_ 2 P!N 2400077_4, _ev A {i0!3;_.5001 i i i i i i i i i:i i iiiiiiiiiiiiiiiiii Completely read all instructions This manual is intended as an aid to iiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiiii prior to assembling, installing, oper- qualified iiiiiiiiiiiiiiiiii ating, orrepairingthisproduct. iiiiiiiiiiiiiiiiii Inspect all parts for damage prior to in- installation, operation, and maintenance of the EMI AmericaSeries high efficiency condensing unit. Read these instructions service personnel for proper ................................ stallation and start-up. The EMI Ameri- thoroughly and carefully before attempt - ............................. caSeries high efficiency condensing unit ....................... must be installed ONLY by q ualified ing installation or operation. Failure to follow these instructions may result in iiiiiiiiiiiiiiiiiiiiiiiiii{i{!i!!!!i installationpersonnel. _mproper installation, operation, service, or maintenance, possibly resulting in fire, electrical shock, property damage, personal injury, or death. iiiiiiiiiiiiiiiii Tampering with ous. Tamperingvoids NOT attempt iiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiii Read all instructions this unit is dangerallwarranties. to modify or change unit. Install or locate this unit only in accordance with these instructions. Use this DO iiiiiiiiiiiiiiiii this iiiiiiiiiiiiiiiii unitonlyforitsintendeduseasdescribed iiiiiiiiiiiiiiiii inthismanual. iiiiiiiiiiiiiiiii !!!!!!!!!!!!!!!!! Checktheratingplateontheunitbefore unit in any way. iiiiiiiiiiiiiiiii installationto make certain thevoltage iiiiiiiiiiiiiiiii shownisthesameastheelectricsupplyto the unit. The rating plate is located on the iiiiiiiiiiiiiiiii The EMI AmericaSeries must: • • Be connectedto aproperlygrounded electrical supply with the proper voltage as stated on the rating plate. iiiiiiiiiiiiiiiii front Have proper overcurrent protection (i.e.time-delay fuse/HACRBreaker) as listed on the rating plate. iiiiiiiiiiiiiiiii Wurnofftheelectricalsupplybeforeserviciiiiiiiiiiiiiiiii " iiiiiiiiiiiiiiiii mgtheunit. result in a fire, explosion, or electrical shock causingproperty damage,personal injury; or death. 240007754, _{ev, A [05ff 5©9 panel only. !!!!!!!!!!!!!!!!! This unit must be connected only to a iiiiiiiiiiiiiiiii properly grounded electrical supply. Do iiiiiiiiiiiiiiiii !!!!!!!!!!!!!!!!! not fail to properly ground this unit. Failure to follow these instructions can P/N before using this iiiiiiiiiiiiiiiii Donotusetheunitifithasdamagedwiriiiiiiiiiiiiiiiii ing, isnotworkingproperly, iiiiiiiiiiiiiiiii damaged or dropped. $ orhasbeen Mat:{÷ i_ tBe USA Controls and components (Factory-installed or supplied) Product description The AmericaSeries S1CG/S1HG and S2CG/ S2HG condensing units are air-cooled, vertically-arranged side-discharge,high-efficiency units designed specifically to meet or exceed a 13 SEER rating. The S1CG Models 09-36 and S 1HG Models 09-24 condensing units will provide cooling and heating for a single evaporator, as identified on page 32 and page 33. The S2CG/S2HG 18,000 (99), 21,000 (92) and 24,000 (22) Btuh capacity condensing units will provide cooling and heating for two evaporators, as identified on page 34. The S1CG/S1HG and S2CG/S2HG • • • • • Heat pump hard start Cooling operation downto 32° F standard on all units • Models 09-12 only: - Large capacity suction accumulator - Solid-core filter drier Thermostatically-controlled crankcase heater (heat pump only) Thermostatically-controlled crankcase heater Features • Compressor and fanmotor contactor Run capacitor Lowvoltage terminal connections H.P.S. (High pressure switch) with manual external reset - are quiet units that can be recommended for both commercial and residential applications. • • • • • This feature energizes the crankcase heater only when needed, saving unnecessarypower usage and increasing overall system efficiency. Installation of the S1CG/S1HG and S2CG/S2HG condensing units is simplified by a 24v control interconnection from the evaporator. Multiple units can be lined up in close proximity to an exterior wall. Service valves are recessed to reduce tampering. All9,000-12,000 Btuh units are equipped with a Duratec Performance Package that includes an oversized suction accumulator with surge baffles and enhanced oil management and a factory-installed solid core filter drier. A factory-installed crankcase heater is standard on S1HG 09 &12 (thermostatically controlled) and S2HG models, and is available as optional equipment on other models. Oomfo_t where it cou_'_ts 4 P!N 240007754, Bey A [05£509I System options Installer-supplied • • • • • Power wiring LowVoltwiring (18 awgminimum) Secure mounting pad or foundation Refrigerant piping (ifnotpurchased from EMI) • • High Volt Disconnect Refrigerant for charging interconnect ing (see charge table on page 15) Corrosion-resistant coil options (sea coast and harsh environment usage): Copper fin/copper tube condenser coil - • • • Coated aluminum condenser coil fin/copper tube LowAmbient controls for cooling operation down to 0 ° F (standard equipment can operate down to 32°F) Optional field-installed kit, when specified, for cooling operation down to O°F-- kit includes control, louvers and wind baffle plus installation Field-installed pip- ................. iiiiiiiiiiiiiiiii Low Ambient controls are required when the system is asked to cool at outdoor temperatures below 32 ° F, this may cause damage to the compressor and coil, and may void the warranty. A field-installed low-ambient kit allows operation down to 0 ° E instructions Low Ambient controls for operation down to 0 ° F (consult factory for availability) Models 09-12 only: 115v (single-zone only-SICG or S1HG) - items iiiiiiiiiiiiiiiii This is accomplished by cycling the condenser fan on and off. This will, in turn, maintain a constant low-side pressure, providing a steady cooling effect and keeping the air handler from frosting-up. thermostatically-con- trolled crankcase heater for straight cool units (S1CG or S2CG) The optional kits include louvers/wind baffle, crankcase heater, and/or outdoor fan cycling switch, and installation instructions. _/N 240007754, Rev, A [05ff 509 5 Msd÷ i_ the USA Before installing, • • • • • consider: 2. Locate the unit as close to the indoor section as possible. (see page 11.) S 1CG/S2CG -- If the unit is used for low ambient cooling down to 32°E S1CG/ S2CG require CCH. Avoid high traffic areas and prevailing wind locations. Surface must be fiat and level. In areas of heavy snowfall, condensers should be set above the maximum anticipated snow line (12" is usually adequate for most locations). Unit Mounting Instructions Model S1CG is shown for example in the following sequence. The side- discharge unit allows forpermanent mounting through the feet. This is highly recommended due to the vertical design of the unit. Mount unit above typical snow fall level. This is particularly important for heat pump applications (S 1HG/S2HG). 1. Figure 1, Page 7: - Bullet 1 -- Loosen the screws on left and right sides of the front panel. (Do not remove these screws.) - Bullet 2 -- Remove the screws on the front of the panel. 2. Figure 2, Page 7: Slide front panel forward to clear side screws and remove. 3. Figure 3, Page 7: Insert lag bolts through the holes in the bottom of the unit and tighten to secure. 4. Figure 4, Page 7: Insert lag bolts through the holes in the feet on the back of the unit and tighten to secure. 5. Site preparation Replace the front panel, do not tighten the side screws at this time. Place the unit on a flat concrete surface or pad if on the ground. Roof mounting should use a build up platform to avoid intake of hot air from the roofi Oomfo_t where it cour_ts @ P!N 240007754, Rev A [05£50% Figure 1 Remove front panel screws Figure3 lag hole locations A Lag bolts B Filter drier C Compressor D Accumulator E Capacitor Figure4 Figure2 Bottom Lag holes in feet Remove front panel P/N 240007754, g{ev,A [05S5©9] "d Made i_ the USA Figure5 Rating plate location Figure6 Remove side panel screws All electricalwiringmustberunaccording to NEC and local codes. 1. Figure S, Page 8 -- Refer to the unit rating plate for voltage, minimum circuit ampacity and over current protection requirements. 2. Use only HACR type breakers or time delay fuses. Sdect the wire size according to the ampacity rating. 3. To access electrical connections and wiring diagram: a. Figure 6, Page 8 -- Remove the screws on the side panel adjacent to the back panel. b. The screws adjacent to the front panel should alreadybeloose (don't remove them). c. Slide the side panel out to access the high/low electrical connections and wire diagram. d. Figure 7, Page 9 -- Remove the plastic edge guards from the holes and replace with a water-tight strain relief fitting (High V) and a split grommet fitting (low V) 4. Power should be run to a weather proof disconnect box usually within 3 feet of the unit. Comfort where it cour_ts 8 P!N 240007754, Bey A [05£509I 5. Figure 8, Page 9 -- From the disconnect box, run the power through the 7/8" hole on the side of the unit and into the electrical box. Anchor with the strain relief fitting. 6. Run wires to the high volt pigtail in the control box and attach L1 and L2 con- Figure7 Power entrances Figure8 High voltage connections Figureg Lowvoltage connections nections. Also run green wire to ground wire. 7. Check wiring diagram for the required number of low voltage wires to be run between indoor and outdoor sections. g. Figure 9, Page 9 -- Connect the 24 volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and also refer to the wiring diagram on the indoor unit. Low volt interconnect should be at least 18 awg. 9. See Figure 10, Page 10 and Figure 11, Page 10 for completed wiring of SICG and S2CG examples. 10. To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel. 11. Fasten all remaining loose screws. P/N 240007754, _tev, A [05S 509 9 Made in the USA Figure 10 Completed wiring, S1CG Figure 12 Replacing Figure 11 Completed wiring, S2CG Figure 13 Fasten loose screws Comfort where it cou_'_ts J,,,O side panel P!N 240007754, _SevA [05£50% P-trap installation Tubing specifications • The system will support refrigerant runs to the inside unit as listed in Table 1, Page 11. The units are furnished with sweat connections and are equipped with refrigerant valves and Schrader fittings for charging and taking pressure readings. • A P-trap is recommended when the suction riser is equal to or greater than show in Figure 14, Page 11 and Table 1, Page 11. When the condenser is installed above the evaporator, the P-trap will help the return of oil back to the compressor. Figure 14 P-trap placement (seeTable Page 11 for dimensions It is recommended that a filter drier be ins tall e di n th e liq u idli ne, at th e in d oor 1, H & P) Condenser unit models factory-installedonfilter drier without (i.e. 18K aand larger). H maximum Table 1 Sl CG/S2CG tubing specifica- tions (see Table 14, Page 11 ) P maximum Evaporator • 12 1/4" 1/2" • 24 3/8" 3/4" • 36 P/N 240007754, 3/8" Rev, A [05J 509] 3/4" • AP-trap maybe fabricatedusing (2) street elbows and (2) regular elbow. A prefabricated trap may be purchased from a wholesaler or distributor however the trap shouldbe shallow as with the (3) elbow configuration. Each elbowis approximately 2 equivalent feet. • One P-trap is equal to approximately 12 equivalent feet. P-traps are not required at the foot of the hot gas risers due to increased oil flow at higher temperatures. J,,,J,,, Made in the USA Figure 15 Clean ends of tubing • Avoid piping on wet and rainy days• !!!!!!!!!!!!!!!!! • Use only clean, refrigeration-grade copper tubing. • Use tubing benders kinking. • Be certain to guard against no burrs remain on the fittings• • Cap ends of lines until ready for con.................. nectiÙns. Figure 16 Wet rag "heat shield over valves Figure 17 Make a shield to protect • Be certain that plastic end caps remain .................... in pl acew h eninsertin g th rou gh w all ...................... ............... openings • Insulate the suction line• iiiiiiiiiiiiiiii_i • Isolate tubing from transmitting vibration to the building or unit and avoid contact with sharp edges• • Wrap refrigeration valves with a wet rag "heat sink" to protect v alyes while brazing. (See Figure 16, Page 12.) Refrigerant piping 1. Clean the ends of tubing and insert into fittings (Figure 1S). 2. paint Protect valves by wrapping with a wet rag "heat sink" before brazing (Figure 16). 3. Use a shield to protect the paint as shown in Figure 17. (The shield can be made from scrap metal.) 4. Braze tubing into fittings. Comfort where it cou_'_ts S,,,2 P!N 240007754, _SevA [05£50% Charging the unit Figure 18 Manifold set connections at unit 1. Attach manifold set (Figure 18). 2. Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks (Figure 18). 3. Once certain of a good evacuation and leak free joints, back-seat the valves (counter-clockwise) to open and allow factory charge to filllines and indoor unit (Figure 18, Page 13). i ii i i!i!iiiiii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii Refer to refrigerant charge table for specified charge. 4. Charge to proper weight, charge based on feet of interconnect (see tables on page 15). Only add/remove 410A in liquid form. 5. Refer to charts beginning on page 17 to "fine tune" the refrigerant charge to meet your conditions. M1 systems require field charge adjustments. Refer to the "Refrigerant Charge Tables" for proper weight charge and to the supplied "Single-zone Operation Charts" for proper system pressures and temperature at different outdoor conditions. Superheat should be used for final system charge. Figure 19 Manifold A Manifold C Micron Figure 20 set up for evacuation B Vacuum pump gage Charging Charging should be done with a dial-acharge or weighed in with a scale. When charging and checking pressures/ temperatures on system supplied with Low Ambient Option, the fan cycle switch should be jumped out of the circuit temporarily to obtain accurate ................. data. P/N 240007754, _tev, A [05S 5©9 S,,,3 ['VSadein the USA It is illegal to discharge refrigerant into iiiiiiiiiiiiii{'ii{i!iiiiiiiiiiiiiiiiiii i theatmosphere. Useproperreclaiming methods& equipmentwheninstalling or servicin g thi s unit. ................... The units are delivered pre-charged with refrigerant for the condenser coil and the evaporator. Charging of the fieldinstalled piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconnect piping. Unit service valves are solid brass, for sweat connections. Comfort where it counts iiiiiiiiiiiiiiii; iiiiiiiiiiiiiiii_ iiiiiiiiiiiiiii_ iiiiiiiiiiiiiiiiii Pressuretest all field installed piping iiiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiiii with nitrogen. Using a suitable vacuum iiiiiiiiiiiiiiiiii pump, evacuate the tubing and indoor iiiiiiiiiiiiiiiiii unit to SO0microns or less, with service iiiiiiiiiiiiiiiiii valves remaining front seated (closed). iiiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiiii Before releasing the refrigerant from the iiiiiiiiiiiiiiiiii condenser, be sure the manifold gauge set is closed so as not to lose vacuum iiiiiiiiiiiiiiiiii when shutting down the pump. iiiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiiii iiiiiiiiiiiiiiiiii Release refrigerant from the condensing unit by back seating the service valve. Mlen wrenches are used to open the valve. Replace valve caps. DO NOT back seat the valves past the snap flanges that hold the valve core in place. S,,,4 P!N 240007754, _SevA [05£50% iiiiiiiiiiiiiiiii: 1. To find the charge adjustment length: iiii!}iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii Line Adjustment !!!!!!!!!!,s_s_ !!!!!!!!!!!,s_s_ 2 S1CG/S1HG S 1CG9 = (Line Charge/FT} x Line Length CAH09 refrigerant .25 oz/ft and allow for gauges and hoses. charge table 39.5 $1HG9 WLH09/UNH09 (23 g/m) S 1CG8 CAH24 .64 oz/ft $1CG3 CAC36 .64 oz/ft 65.25 $1HG8 WLH24/UNH24 .25 oz/ft 97.5 S1HG9 .64 oz/ft WLH24/UNH24 .64 oz/ft 63.0 CAH09 .25 oz/ft 51.52 (23 g/m) S1HG8 39.5 (23 g/m) S1CG8 51.52 (59 g/m) (59 g/m) WLH09/UNH09 .25 oz/ft (23 g/m) (59 g/m) S1CG9 and tubing System Total = Factory Charge + Line Adjustment iiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!i!!!!i 2 Round to the nearest ounce Table and system charge for any evaporator CAH24 .64 oz/ft 63.0 (59 g/m) 65.25 (59 g/m) $1CG3 WLC30/UNC36 .64 oz/ft 97.5 (59 g/m) P/N 240007754, _{ev, A [05] 50% S,,,5 Ma(_e in the USA iiiiiiiiiiiiiiiiii 1. To find the charge adjustment and system charge for any evaporator and tubing length ............................. Line Adjustment ........................ System Total = (Line Charge/FT) x Line Length = Factory Charge + Line Adjustment .................. 2. Round to the nearest ounce and allow for gauges and hoses. Table 3 S2CG/S2HG refrigerant .25 oz/ft $2CG99 $2CG92 (2)WLHG09 WLHG09+WLHG12 charge table 40/40 $2HG99 (23 g/m) .25 oz/ft 40/34 $2HG92 (2) WLHG09 WLHG09+WLHG12 (23 g/m) $2CG22 (2) CAHG12 $2CG99 UNHG09 .25 oz/ft (23 g/m) .25 oz/ft Comfort UNHG09+UNHG12 _: where it counts 25 oz/ft " , (23 g/m) 40/40 .25 oz/ft 40/34 (23 g/m) 34/34 $2HG22 40/40 $2HG99 (2) CAHG 12 UNHG09 .25 oz/ft 34/34 (23 g/m) .25 oz/ft 40/40 (23 g/m) (23 g/m) $2CG92 .25 oz/ft (23 g/m) 40/34 $2HG92 S,,,6 UNHG09+UNHG12 .25 oz/ft , , (23 g/m) P!N 240007754, _ev 40/34 A [05£50% Cooting Cycte Model S1CGgO00 &StHG9000 Cooling Cycle Model S1CG9000 &S1HG9000 withEMI's-WLH09 &UNH09 (R-410A Ret) withEMI's-CAHG09 (R-410A Ref,) 55O 550 490 490 430 430 o_ 370 370 310 310 250 250 170 170 150 150 _. o_ _ o_ 130 m 110 110 90 90 35 35 25 8 130 _- 25 15 15 65 75 85 95 105 115 65 Outdoor Temp (° F) Note: Minimum compressor superheat 5°F P/N 240007754, _ev, A [05S509 75 85 95 105 115 Outdoor Ternp (° F) Note: Minimum compressor superheat 5° F _,,,7 ['_$a_:_÷ in the USA mul Amica vies Cooling Cycle Model S1CG2000 $S1HG2000 Cooling Cycle Model S1CG2000 &S1HG2000 withEMI's-WLHG12 &UNHG12 (R-410A Reh) withEMI's-CAHG12 (R-410A Ref,) 55O 550 490 490 430 _ 430 9_ _= _, _. 370 370 310 310 25O 25O 170 170 150 _ 150 130 130 110 110 90 o_ 35 N- 25 _4 _ 15 _ 35 65 75 85 95 105 115 15 65 Outdoor Temp (° F) Note: Minimum compressor superheat 5°F Comfort where it cou_'_ts 25 75 85 95 105 115 Outdoor Temp (°F) Note: Minimum compressor superheat 5°F S,,,8 P!N 240007754, Rev A [05£50% Cooling Cycle Model S1CG8000 &S1HGS000 Cooling Cycle Model S1CG8000 &S1HG8000 withEMI's-WLHG24 &UNHG24 (R-410A Ref,) _- withEMI's-CAHG24 (R-410A Ref,) 550 550 49O 490 430 _ 430 370 _- 370 310 310 250 250 170 170 150 Ao 2g_ 8 _ 150 130 130 110 110 90 90 35 35 25 _- 25 15 8 15 5 65 75 85 95 105 115 Outdoor Temp (° F) Note: Minimum compressor superheat 5°F P/N 240007754, _ev, A [O5S509 65 75 85 95 105 115 Outdoor Temp (°F) Note: Minimum compressor superheat 5°F _,,,9 r'_$a_:_÷ in the USA Cooling Cycle Model S1CG4000 &S1HG4000 with EMrs-WLHG24 &UNHG24 (R-410A Ref,) 550 Cooling Cycle Model S1CG4000 &S1HG4000 withEMrsCAHG24 (R-410A Ref,) 550 Room Temp(°F) Relative Humidit' 490 490 -_ 43o -_ 43o _- _- 370 370 170 170 150 250 I_ 250 150 310 I_ 310 _ 13o_-_@ _ 13o 110 _- 110 90 _ 35 __ 90 35 25 _ _ 25 _ 15 _-15 75 85 95 105 Outdoor Temp (° F) Note: Minimum compressor superheat 50F Comfort where it oou['}ts 115 65 20 75 85 95 105 Outdoor Temp (° F) Note: Minimum compressor superheat 5°F 115 P!N 240007754, Rev A Z05£50% Cooling Cycle Model SLOG3000 Cooling Cycle Model S1CG3000 withEMI's-WLCG30 &UNCG30 (R-410A Ref.) withEMI's-CACG30 (R-410A Ref.) 55O 550 490 490 430 _ 430 _- 370 _- 370 _ 310 310 250 250 170 170 150 _. 130 o_ 130 110 110 90 90 150 35 _- 25 8 15 £ 75 85 95 105 Outdoor Temp (oF) Note: Minimum compressor superheat 50F P/N 240007754, _ev, A lOSS509 115 25 65 2]... 75 85 95 105 Outdoor Temp (oF) Note: Minimum compressor superheat 50F 115 ['_$ac:_÷ in the USA Cooling Cycle Model S1CG6000 Heating Cycle Model S1HGgO00 withEMI'sWLHG09 &UNHG09 (R-410A Ref,) withEMI's-CACG36 (R-410A Ref,) 55O 380 Room Temp (°F) Relative Humidb 490 350 430 _ 320 _- 370 a- 290 310 260 250 230 170 130 150 _ q ilili 130 110 _ 110 _ 9O 70 II I 90 50 _" 35 30 _- 25 N8 15 € 20 10 65 75 85 95 105 115 10 Outdoor Temp (°F) Note: Minimum compressor superheat 5oF Comfort where it cou_'_ts 20 30 40 50 60 Outdoor Temp (°F) 22 P!N 240007754, _SevA [05£50% Heating Cycle Model S1HGgO00 withEMI'sCAHG09 (R-410A Ref,) Heating Cycle Model S1HG2000 withEMI's-WLHG12 &UNHG12 (R-410A Ref,) 380 38O 350 350 _ 320 _ 320 ";- 290 _- 290 _- 260 260 230 230 130 130 11o _ 110 90 _- 90 o 70 50 30 30 8 20 20 } lO I0 10 20 30 40 50 60 Outdoor Temp (°F) P/N 240007754, Rev, A [05S509 30 40 50 Outdoor Temp (oF) 23 Made in the USA Model s1HGZOUO withEMI's-CAH12 (R-410A Ref,) MOdel b lIflbZUUU withEMrs-WLHG12 & UNHG12 (R-410A Ref,) 380 38O 350 350 _ 320 _ 320 _- 290 _- 290 260 260 230 230 130 130 _ 110 11o _- 90 _- 90 50 _- 30 30 20 20 10 I0 20 30 40 50 60 Outdoor Temp (oF) Comfort where it oou['}ts 10 20 30 40 50 60 Outdoor Temp (oF) 24 P!N 240007754, Rev A [05£50% Model 5]HGZOO0 withEMI's-CAH12 (R-410A Ref,) MOdel bllflb_ddd withEMrs-WLHG24 &UNHG24 (R-410A Ref,) 380 38O 350 350 _ 320 _ 320 ";- 290 _- 290 _- 260 260 230 230 130 130 11o _ 110 90 _- 90 o 70 50 30 30 8 20 20 } lO I0 10 20 30 40 50 60 Outdoor Temp (°F) P/N 240007754, Rev, A [05S509 30 40 50 Outdoor Temp (oF) 25 Made in the USA Model SlHGSOO0 with EMrsCAH24 (R-410A Ref,) MOdelb llflbqUUg withEMrs-WLHG24 &UNHG24 (R-410A Ref,) 380 38O 350 350 _ 320 _ 320 _- 290 _- 290 260 260 230 230 130 130 _ 110 11o _- 90 _- 90 50 _- 30 30 20 20 10 I0 20 30 40 50 60 Outdoor Temp (oF) Comfort where it oou['_ts 10 20 30 40 50 60 Outdoor Temp (oF) 26 P!N 240007754, Rev A [05£50% Model 5]HG4OUO with EMI'sCAH24 (R-410A Ref,) 380 350 _ 320 ";- 290 260 230 130 110 A- 90 o 30 8 20 0 10 20 30 40 50 60 Outdoor Temp (°F) P/N 240007754, Rev, A [05S509 27 Ma(_ein the USA 9,000- The S 1CG/S 12,000 Btuh units sections In low ambient cooling, ifa crankcase heater is installed, power the system 24 hours before attempting to start the unit in cool weather (below 60 ° F). 1HG and S2CG/S2HG are the compressor bearing outdoor units of the system. It operates at the command of the indoor section or room thermostat. Therefore, the system operation will be described in the manual pertaining to the indoor section. EMI units are designed and constructed for reliability and long life with minimal maintenance. You can assure peak operating efficiency by regularly inspecting for free air passage into and through the coil. If debris collects on the air coil, it should be cleaned by "back-flushing" with a spray of water or vacuuming. TURN OFF POWER SUPPLY FIRST. Outdoor units may be cleaned or waxed if desired. Use a non-abrasive car wax (on metal surfaces only). Test unit data sheet After doing a final system check using the Operation Charts (supplied on previous pages). Record results on Test Unit Data Sheet on page 36. Before leaving Remove gauge set. Mount all access panels and make sure they are properly secured. This unit is equipped with a permanently lubricated motor. Mthough oiling is not necessary; adding a few drops through the oiling ports twice yearly will extend the life of the motor. Do not over oil. Make final visual inspection and repair any deficiencies. Panels should remain on the unit at all times. Service should be performed service agency only. A hard start kit may be required for units in low voltage applications. by a qualified Specific changes All EMI products are subject to ongoing development programs so design and specifications may change without notice. Please consult the factory for more information. Comfort where it cour_ts 28 P!N 240007754, _SevA [05£50% EMI AmericaSeries condensers are designed to operate with EMI AmericaSeries evaporators. Both the condenser (outdoor unit) and evaporator (indoor unit) have a high volt service connection. Each is to be independently connected to the electrical service panel. (See the unit name plate for the correct breaker type and size). The outdoor and indoor units are also connected to each other through a low volt interconnect wiring. A 24v transformer located in the indoor unit provides the low volt power source. temperature below the room temperature, the reversing valvewill energize (R & O heat pumps only) along with the compressor and outdoor fan (R & Y). When the indoor control is satisfied and the room temperature falls below the set temperature, the compressor and fan will de-energize. The anti-short cycle timer (ASCT) will prevent the compressor from re-starting for three minutes. Heating operation Heating operation requires that the control (either unit mount or remote wall mount, heat pump thermostat) make a connection between low-Volt terminals "R" and "Y" only. When the indoor control is placed in heating mode, with the set point temperature above room temperature, the compressor and outdoor fan (R & Y) will energize. When the indoor control is satisfied and the room temperature rises above the set temperature, the compressor and fanwill de-energize. The anti-short cycle timer (ASCT) will prevent the compressor from re-starting for three minutes. Straight cool condensers are designed to operate as a single stage cooling unit. Heat pump condensers are designed to operate as a single stage cooling two stage heating unit. For proper operation the unit must be matchedwith an appropriate EMI indoor unit with unit mounted controls and/or wall mounted thermostat. For two-stage heating operation the indoor unit must be equipped with an electric strip heater. ............................. For remote wall mounted thermostat ......................... operation be sure to select EMI p/n Defrost controls with short cycle protection (heat pumps only} iiiiiiiiiiiiiiiiiiiiiiiii!i!i!!i 240004180orasuitable24v, twostage heating, heat pump thermostat. Condenser The The unit is equipped with designed to keep system ficiency. The 24v circuit the indoor and outdoor three minute, anti-short compressor protection. operation transformer located in the indoor unit provides 24v, low-volt control power to the condenser (outdoor unit). This canbemeasured across low-volt terminals "R" and "C". The defrost control circuit is designed to keep the condenser coil free from frost and ice during heatingmode. This is accomplished through the precise switching sequence of the outdoor fan, reversing valve and indoor auxiliary heater. Heat pump condensers utilize areversing valve to provide reverse cycle operation. Therefore the outdoor unit will act as either a condenser or an evaporator there-by providing comfort cooling or heating to the indoor space. The reversing valve is energized in cooling. Should the valve fail to actuate, the system will default to the heating mode of operation. Defrost Cooling operation requires that the control (either unit mount or remote wall mount thermostat) make a connection between low-volt terminals "R" and "Y" along with "R" and "O" (heat pumps only). When the indoor control is placed in cooling mode, with the set point 240007754, _{ev, A [05ff 5©9 initiation The defrost-sensor is located on either the end plate or the return bend of the condenser coil. A defrost cycle will initiate after the sensor doses (approx. 30 ° F) and remains closed for the length of time selected on the control board (either 30, 60 or 90 minutes)*. Cooling operation, single- and dual-zone P/N a logic control circuit operating at peek efprovides control to systems including a cycle timer (ASCT) At the start of the defrost cycle, the reversing valve will change from heating to cooling mode. The condenser fan will also switch off there-by allowing pressure and temperature 29 rVSat_e in the USA BI m W to rise within _ the condenser )i iii!i 5 i); _!!_ ))))_!!_ )i:iJ <); )i'ii = @ )!;i¸iii!¸¸¸ )) _;;!ii)i:iJ <); i_ii _;i;iii ¸i:);! )_[i;_!i; )))i ¸ii )i !i!_ )?ii _;!ii )i'ii 0 _!i!_ ¸!15/! _!!ii i?ii Li;!!!_ )) _ coil to melt off Figure 21 any ice build-up. At the same time the unit will switch on the indoor electric strip heater to temper the cold air being discharged from the evaporator unit. This will continue until either the defrost-sensor opens (approx. 60 ° F) or a 10-minute maximum cycle time has elapsed. Defrost times will vary depending on outdoor temperature and moisture conditions. When the defrost cycle is complete the unit will return to normal heating operation. *Factory settings 9-24k result in injury or electric DFT TST If the condenser coil is heavily frosted up with ice, it is likely that the "Defrost Sensor" is already closed. In this case the "R and DFT" jumper can be eliminated. To initiate defrost, momentarily jump pins marked "DFT TST" until the defrost cycle begins. The unit will remain in defrost mode until the condenser coil is defrosted and then it will return to heating mode. When testing is complete be sure to remove the jumper(s). DO NOT leave the unit in test mode with jumper (s) With the system "off", using two small alligator clips, jumper the following sets of test pins. "R and DF2" and "DFT TST". board Apply power to the indoor and outdoor units. Place the indoor unit in heating mode with the set point temperature well above room temperature. This is to ensure that the condenser will remain operation. on during the entire defrost test Low ambient The condenser will operate in heating for approximately 20 seconds. At that point the unit will enter defrost mode for approximately 2 seconds. During this time the condenser fan will switch off, the reversing valve will energize and the defrost board will energize the indoor electric heat relay through the "W" terminal. After the two second defrost cycle is complete, the unit will switch back to heating operation for another 20 seconds. This process will repeat until the jumpers are removed from the operation Ifthe unit is equipped with low ambient fan control for cooling, the fan will remain off (while in cooling mode) until the condenser pressure reaches 340 psi. The fan will then energize and run until the condenser pressure falls below 247 psi. This will happen only in the cooling mo de (or when the reversing valve is energized). In heating (reversing valve not energized), the fan will run continuous so long as the connection is made between "R" and "Y". test pins. Comfort where it cour_ts R and DF2 shock. Defrost operation can be initiated using the test pins located on the circuit board of the condensing unit. "Defrost test operation" will be a time compressed version of the actual defrost cycle. Defrost control board (SlHshown) Btu = 90 minutes Beforeremovingtheaccesspanelstothe unit make sure that all power is disconnectedfromtheunit. Failureto do so could )))))))))))))),= ))))))))))))))), Defrost control 30 P!N 240007754, Bey A [05150% iiiiiiiiiii .... i!ii!i!!i!iiiiiiiiiiiii i iii iii! i !il Performance data listed in this manualis subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certified products in the AHPd directory; at www.ahridirectory.org. Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult the factory for further information. E 1/2" Diameter Lag Holes _iii};_iiN#iii/iiiiiii[iiii!!iiiiiiii_:iiiiiiiiii_iii_iii;;iiiiiiliii#_ iii _ A-_ !:_%iii_ii_;iiiiii!ii_;i;ii!_iiiii!!iii,;,},iiiiiii_iiiii/ii!i!i!iii_ii! I il ................................... B ........................................ A Electrical connections Table 4 Dimensional S1CG/S1 HG9 data, sound data and shipping Easy access interconnects on back of unit weights 4 sis (117) 14 u/_o (373) 3 (76) 12 z/_ (316) 24 (610) 15 (381) 36 (914) 59 98 32 (813) 15 (381) 36 (914) 62 156 38 S1CG/S1HG8 18 4 _/_, (117) 22 _/_6 (570) 3 (76) 12 7/_6 (316) S1CG3 3O 7 (178) 23 _s/_, (608) 3 (76) 127/_o 44 (1118) 210 (965) 15 (381) 68 (316) 23 _s/_, (608) 3 (76) 12 7/_6 (316) 38 (965) 15 (381) 44 (1219) 68 159 23 _s/_6 3 (76) 12 7/_6 (316) 38 (965) 15 (381) 44 (1219) 68 187 S2CG/S2HG99 9 + 9 7 (178) S2CG/S2HG92 9+12 (178) 7 P/N 240007754, Rev, A [O5_ 509 (608) 3[_ii, ['?_ade in the USA mun W Table 5 $I CG electrical BIIII SICG2A Amic@ies .... iiiiS_i_43i!ii!!_:!_ii%_qi_ il}ii_iiii!4_!i_ii!!!i:Lii ¸ _!i!i_ii_sii:_i i_iii_!i!iiiiiiiii3i3q!i_i!_iii3_i:_ili!_ i!Y/81i(iiL!_ii!i_il .... 115/60/I specifications 1.4 0.125 9.9 53 11.3 104 13.8 20 SICG2D 208/230/60/I 0.8 0.125 5.2 27 6.0 197 7.3 15 SICG4D 208/230/60/I 0.8 0.125 8.0 43 8.8 197 10.8 15 SICG6D 208/230/60/I 1.8 0.330 12.7 74 14.5 197 17.7 30 S1 CG performance Table 6 Cooling $1CG9 WLHG09 S1CG8 WLHG24 S1CG3 WLCG30 Table 7 Cooling $1CG9 UNHG09 S1CG8 UNHG24 S1CG3 UNCG36 Table 8 Cooling S1CG9 S1CG8 S1CG3 (Do_l"_l_t where it counts Indoor Units systems with wall units 13.0 0.74 12.2 R410A 18,000 13.0 0.77 12.0 R410A 28,200 13.0 0.79 11.7 R410A systems with universal units 13.0 0.74 12.2 R410A 18,000 13.0 0.77 12.0 R410A 28,200 13.0 0.79 11.7 R410A systems with cassette units (__ = G or H) 9,000 CAH24 data: Matched with EMI AmericaSeries 13.0 0.77 11.4 R410A 13.0 0.75 12.7 R410A 13.0 0.77 12.4 R410A $2 P!N 2400077_4, Rev A I0!S:£50% Table 9 SI HG electrical SIHG9A 115/60/I specifications 1.4 0.125 7.5 47 8.9 104 10.8 15 S1HG9D 208/230/60/1 0.8 0.125 3.9 20 4.7 197 5.7 15 S1HG8D 208/230/60/1 0.8 0.125 5.9 43 6.7 197 8.2 15 1 $1 HG performance Table 10 S 1HG9 Table 11 S1HG9 Table 12 S1HGg000 S1HGS000 data: Matched with EMI AmericaSeries Indoor Units Heat pump systems with wall units WLHG09 %000 %000 13.0 7.7 Heat pump systems with universal UNHG09 13.0 0.72 12.8 3.3 R410A units 7.7 0.72 Heat pump systems with cassette units (_ = G or H) 9 9,000 8,200 13.0 7.7 0.74 11.8 3.2 R410A 24 18,000 16,400 13.0 7.7 0.76 12.1 3.4 R410A CAH CAH WL C/WL H CAC/ CAH SICG/SIHG Single zone P/N 240007754, Rev, A [05S 5©9] 33 U N CI U N H Made in the USA Table 13 9200 S2CG electrical i208/230/60/1 0.8 S2CG performance Table 14 S2CG cooling WLHG09+WLHG09 WLHG09+WLHG Table lS 12 specifications 0.125 3.9 20 5.2 27 8.8 data: Matched with EMI AmericaSeries 197 10 15 Indoor Units systems with two wall units $2CG99 18,000 13.0 0.80 11.9 R410A $2CG92 21,000 13.0 0.74 12.0 R410A S2CGcooling systems with two universal units UNHG09 + UNHG09 $2CG99 18,000 13.0 0.80 11.9 R410A UNHG09 + UNHGI 2 $2CG92 21,000 13.0 0.74 12.0 R410A 11.5 R410A Table 16 CAH_09 S2CG cooling + CAH09 ...................... CAH 09+CAIq CAC/ CAH systems with two cassette units (__ = G or H) $2CG99 18,000 ! _ .................. $2CG92 ............................ 13.0 0.75 ............... 13.0 ........................................ 0:75 ..................... iI................ ]1:5 ............................. E_4]0_ ............. mmumm A _mW Table 17 9200 SPiB8 S2HG electrical 208/230/60/1 0.8 S2HG performance Table 18 Table 19 specifications 0.125 3.9 20 5.2 27 8.8 i! data: Matched with EMI AmericaSeries 197 10 15 Indoor Units Heat pump systems with wall units WLHG09+WLHG09 WLHG09+WLHG ::: : .... iiiiS_i_ii3i!ii!!_:!_ii%;qi_ il}ii_iiii!:q!_;i_;i!!!i:i:i ¸_;i!i;ii_sSi i_iii_;i!iiiiiiii;i3i3q!i_i!_iii3_i;_ilis i!YISi/i_L!_ii!i;il .... 12 $2HG99 18,000 17,600 13.0 7.7 0.80 11.9 3.3 R410A $2HG92 21,000 20,000 13.0 7.7 0.74 12.0 3.3 R410A Heat pump systems with universal units UNHG09 + UNHG09 $2HG99 18,000 18,000 13.0 7.7 0.80 11.9 3.3 R410A UNHG09 + UNHG12 $2HG92 21,000 20,000 13.0 7.7 0.74 12.0 3.3 R410A Table 20 Heat pump systems with cassette units (_ = G or H) WL C/WL H CAC/ CAH S2CG/S2HG Dual zone P/N 240007-/54, _ev, A [05S 509] $5 UNC/UNH Ma(_e in the USA i!!!!_!_!_i_i_i!iiiiiiiiiiii_!_ii_!_i_!i_i_ii_i!!i_i_i_i_iiiiiii_i!_!!!i_ _ii_i!_ii_i!_ii_ii_i_!!_i_!! _i!_i_ii_i_ii_!i_i_ii_i_!i_ii_ii_ii_ii_il _i_i_!_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_i_!_!_! _I_!I_I_!I_II_I!!II!I _i_!!_i_!!_i!!ii!ii!ii _!_!_!_!_!_i_i_ Technician: , Se_!a!Number.................................................................................................................................. _ iMede! .................... c°°!!n_! ...................................................................................... Evaporator Entering Air - WB Evaporator Leaving Air- DB i Leaving Air Compressor Suction - PSIG Compressor - Volts ............................................................................................................................................................................................................................ ....................................................................................................................... _OD Fan Motor - Volts ID Fan Motor- Amps :................................................................................................................................................................. _ ..................................................................................................................... Total Volts Compressor Suction Compressor Discharge Liquid Out Cond. i ...................................................................................................................... Liquid before Expansion Suction out Evaporator DB - Temp Split at evap. Compressor Superheat Comfort where it cou_'_ts $G P!N 240007754, _ev A [05£50% _/N 240007754, _tev, A [05ff 5©9 $7 Made in the USA Bi Comfort i W where ....:i iiii_!i, ii i!ii ii ii :_i:i iiii I::i_ i_ i_= 0 iii[Ji ii_ i¸_ii!_i _ I: !!0 i_i_ _!i_ ii:_ _i:l i!_ii ¸_!i!i_ ii !i_i!:i_ !! i__ii!ii i_ii _i;; ili!_ i!_¢_I _ii_i ii_ i_!i _ii!i_ ii =_ it cou_'_ts 38 P!N 240007754, tSev A [05£50% _£N 240007754, _tev, A [05ff 5©9 $9 Matte in the USA WLC/WL H High Wall Air Handler UNC/UNH Air Handler SICG Single Zone Side Discharge S2CG &, Dual Zone Side Discharge
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 40 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Mar 14 04:17:23 2010 Author : Title : Subject :EXIF Metadata provided by EXIF.tools