Emerson 100 Kw Lph100 Load Bank Brochures And Data Sheets
2015-03-30
: Emerson Emerson-100-Kw-Lph100-Load-Bank-Brochures-And-Data-Sheets-680333 emerson-100-kw-lph100-load-bank-brochures-and-data-sheets-680333 emerson pdf
Open the PDF directly: View PDF .
Page Count: 2
Avtron LPH100
Compact, Portable Load Bank - 100 KW
Testing Your Emergency Standby
Generator with a Load Bank Means
Reliability When it Matters Most.
• Rated for Continuous Operation
• Compact, Portable, Easy to
Transport and Operate
• Large Load Capacity -
up to 100 KW
• Lightweight Aluminum and
Aluminized Steel Enclosure with
Casters
• Convenient Operator Controls
with Digital Metering and Data
Logging Software included
Key Features
Superior Avtron quality combined with
simple operation and maintenance will
provide years of trouble free service.
Avtron’s extensive line of Load Bank and
Industrial Resis tor Products are solid
performers used throughout the world.
For total technical support or additional
information, please contact Avtron at
(216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
The Avtron Model LPH100 Load Bank is a portable, self-
contained AC resistive model designed for indoor use.
The Avtron LPH00 Load Bank gives users the freedom of a high capacity load in an ultra-compact
package. The LPH100 is ideal for routine testing and maintenance of AC power sources such as
stand-by-emergency generators and UPS systems. The load bank is rated at 100 KW at 480 VAC
and 93.75 KW at 240 VAC at 3 phase, 60 Hz.
This versatile load bank weighs only 105 lbs. [48 kg] and is less than half the weight and size
of traditional load banks of similar capacity. The load bank features horizontal air discharge to
provide a low profile design. Quick-connect load terminals and simple operation allow the load
bank to be set up and operated by a single technician, saving valuable time in the field.
The load bank controls and cooling fans are powered by any standard 120 VAC, single phase
wall outlet with detachable line cord provided. An integral control panel is provided for load
bank operation and includes the necessary controls and status indicators.
The LPH100 Load Bank features the standard in Digital Metering which includes the Avtron
Advanced Digital Monitoring System (ADMS™). The ADMS meter provides faceplate digital
display of Volts, Amps, Frequency, and KW. The Communicator EXT™ Data Logging Software
allows Real Time Data Acquisition and trending of all meter parameters from your Laptop PC
or PDA. An Infrared/USB interface cable is included for “Plug and Play” convenience.
LPH100 100 KW
Compact, Portable
Avtron Load Bank.
EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
Emerson Network Power
Avtron • 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
Avtron LPH100
Compact, Portable Load Bank - 100 KW
Communicator EXT™ is a trademark of Electro Industries/GaugeTech. ADMS™ is a trademark of Avtron.
Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 428• Rev. G
Specications subject to change without notice.
AIR
FLOW
CONTROL
PANEL LOAD CONNECTION PANEL
25.16 [638.97]
14.75 [375.00]
29.12
[740.00]
2.63 [67.00]
16.25 [413.00]
GND
B
AC
120 VAC
All dimensions are in inches [millimeters].
Construction
A compact aluminized steel enclosure with
screened inlet and exhaust openings. Four
swivel casters provide mobility. Heavy duty
lifting handles are also provided.
Control Power
The load bank requires control power of 120
VAC, single phase, 60 Hz (line cord provided).
Cooling
The resistive elements are air cooled by four
high velocity muffin fans for quiet operation.
Controls
The operator control panel includes a MAS-
TER LOAD ON-OFF switch, load step ON-OFF
industrial toggle switches, a BLOWER ON-OFF
switch, and a LOAD VOLTAGE selector switch
(Dual Voltage model only).
Digital Metering
Avtron Advanced Digital Monitoring System
(ADMS™) is provided for display of Volts,
Amps, Frequency, and KW. ADMS™ also
includes Communicator EXT™ Data Logging
Software.
Safety Circuits
The LPH100 Load Bank features main line
circuit fusing, wrong voltage protection (Dual
Voltage model only), and overtemperature
protection.
Load Capacity Ratings: (3 phase, 60 Hz)
Available Load Step Resolution: 5 KW
Rated KW Rated
Voltage
Load Step
Resolution
100
93.75
480
240
5, 10, 10, 25, 50
3.75, 7.5, 7.5, 25, 50
Load Bank Weight (approx.)
105 lbs. [48 kg]
Options
• 20' cable set with connectors
• Heavy duty shipping case
NOTE Designs for international 50/60 Hz voltages or custom
DC designs are also available. Consult factory.