Emerson 67D Series Pressure Reducing Regulators Data Sheet

2015-03-30

: Emerson Emerson-67D-Series-Pressure-Reducing-Regulators-Data-Sheet-681010 emerson-67d-series-pressure-reducing-regulators-data-sheet-681010 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadEmerson Emerson-67D-Series-Pressure-Reducing-Regulators-Data-Sheet-  Emerson-67d-series-pressure-reducing-regulators-data-sheet
Open PDF In BrowserView PDF
Bulletin 71.1:67D
April 2012

67D Series Pressure Reducing Regulators

P1183

P1182

TYPE 67D OR 67DR REGULATOR

TYPE 67DF OR 67DFR FILTERED REGULATOR

Figure 1.  67D Series Pressure Reducing Regulators

  •  Optional Smart Bleed™
     Construction
  •  Optional Stainless 
     Steel Construction
  •  Compact and Light Weight

  •  Easy Maintenance
  •  Optional Integral Filter
  •  Optional Internal Relief Valve
  •  Rugged Construction

D103152X012

  •  No Air Loss

www.fi sherregulators.com

Bulletin 71.1:67D
Introduction
The 67D Series regulators are typically used to deliver constant reduced pressure of gaseous fluids to pilot-operated
controllers and other pneumatic instrumentation. As shown in the Available Configurations table, an assortment of regulators
is available to meet diverse flow requirements.

Features
  •  Compact—The 67D Series regulators are 	
  engineered for outstanding performance in a 	
  compact, lightweight package.

  •  Smart Bleed™—Opens to exhaust downstream 	
pressure when inlet pressure drops below outlet 	
pressure. Recommended for dead-end service.

  •  Pilot Supply Regulator—Improves the accuracy
of two-path control regulators by reducing inlet 	
sensitivity caused by fluctuating inlet pressures.

  •  Integral Filter—The Types 67DF, 67DFR, 67DFS, 	
and 67DFSR have an integral filter ensuring clean 	
downstream air supply.

  •  Pressure Loading Regulator—Provides accuracy and 	
improved performance in dirty steam service by 	
	
eliminating the need for a pilot regulator.

  •  Ease of Maintenance—No special tools are 	
	
required to perform maintenance, and all maintenance 	
can be performed with the regulator in the line. Filter 	
elements are easily replaced.

  •  Sour Gas Service Capability—NACE International MR0175 	
and MR0103 compliant construction available.
  •  Optional Stainless Steel Construction—The 	
	
Types 67DS, 67DSR, 67DFS, and 67DFSR 	
	
provide high resistance to corrosion, which is especially 	
beneficial for offshore applications.
  •  Full Usable Capacity—Fisher® regulators are 	
laboratory tested.  100% of the published capacities 	
can be used with confidence.
  •  Internal Relief—The Types 67DR, 67DSR, 67DFR, 	
and 67DFSR have an internal relief valve with a soft seat 	
for reliable shutoff with no discernible leakage. These 	
regulators are recommended for 	conserving plant air.

2

	
	
	

  •  Rugged Construction—The 67D Series regulators 	
are engineered for longer service life with minimal 	 	
maintenance requirements.
  •  Dual Second Outlets—Body side outlets for
pressure gauge or other uses.
  •  Corrosion Resistant Fasteners—Bolting and 	
adjusting screw are double zinc-chromated for 	
enhanced corrosion resistance. Optional stainless 	
steel bolting and adjusting screw are also available.

	

	

Bulletin 71.1:67D
Specifications
Available Configurations
Type 67D: Direct-operated regulator with
aluminum body and without internal relief
Type 67DR: Aluminum body with internal relief
Type 67DS: Stainless steel body without 	
internal relief
Type 67DSR: Stainless steel body with internal relief
Type 67DF: Aluminum body with filter and without 	
internal relief
Type 67DFR: Aluminum body with filter and
internal relief
Type 67DFS: Stainless steel body with filter and without
internal relief
Type 67DFSR: Stainless steel body with filter and 	
internal relief
See also Table 1
Body Size, Inlet and Outlet Connection Style
	
1/2 NPT
Construction Materials
	
See Table 3
Maximum Inlet Pressure (Body Rating)(1)
	
All filtered models: 250 psig / 17.2 bar
	
All unfiltered models: 400 psig / 27.6 bar
Outlet Pressure Ranges
	
See Table 2
Maximum Emergency Outlet Pressure(1)
	
150 psi / 10.3 bar over outlet pressure setting up to a 	
maximum of 250 psi / 17.2 bar
Flow Capacities
	
See Table 4 and Capacity Information section
Wide-Open Flow Coefficients
	
Main Valve: Cg: 45.24; Cv: 1.33; C1: 35.02;
	
Internal Relief Valve: Cg: 1.45; Cv: 0.045; C1: 32.8
IEC Sizing Coefficients
	
Xt: 0.75
Types 67DR, 67DSR, 67DFR, and 67DFSR Internal
Relief Performance
	
Low capacity for minor seat leakage only, other
	
overpressure protection must be provided if inlet
	
pressure can exceed the maximum pressure rating
	
of downstream equipment or exceeds maximum
	
outlet pressure rating of the regulator.
Approximate Weights
	
Types 67D and 67DR: 1.2 pound / 0.5 kg
	
Types 67DF and 67DFR: 2.0 pounds / 0.9 kg
	
Types 67DS and 67DSR: 2.8 pounds / 1.2 kg
	
Types 67DFS and 67DFSR: 4.6 pounds / 2.1 kg

Smart Bleed™ Check Valve Setpoint
	
6 psi / 0.41 bar differential
Pressure Registration
	Internal
Spring Case Vent Location
	
Aligned with inlet standard, other positions optional
Drain Valve Location
	
Aligned in the center of the dripwell
Temperature Capabilities(1)
	
With Nitrile (NBR)
	
Standard Bolting: -20 to 180°F / -29 to 82°C
	
Stainless Steel Bolting: -40 to 180°F / -40­to 82°C
	
With Fluorocarbon (FKM):
Polyethylene Filter(4) (Standard):
0 to 180°F / -18 to 82°C 	
	 Polyvinylidene (PVDF), Stainless Steel,
or Glass Filter (Optional):
0 to 300°F / -18 to 149°C
	
With Silicone (VMQ)(2) diaphragm, Low Temperature
       Nitrile (NBR) O-rings, and Low Temperature 	
       bolting: -60 to 180°F / -51 to 82°C
	
With Gauges: -40 to 180°F / -40 to 82°C
	
With Automatic drain: 40 to 175°F / 4 to 79°C
Types 67DF, 67DFR, 67DFS, and 67DFSR Filter Capabilities
	
Micron Rating:
  Polyethylene Filter(4) (Standard): 5 microns
Glass Fiber Filter (Optional): 5 microns
PVDF Filter (Optional): 40 microns
  Stainless Steel Filter (Optional): 40 microns
Options
	
All Types
	
• Handwheel adjusting screw
	
• NACE International MR0175 or MR0103(3) construction
	
• Panel mount (includes spring case with 1/4 NPT		
vent, handwheel, and panel mounting nut)
	
• Closing cap (available on spring case with
	
1/4 NPT vent)
	
• Fluorocarbon (FKM) elastomers for high
	
temperatures and/or corrosive chemicals
	
• Silicone (VMQ) elastomers for cold temperatures
	
• Fixed Bleed Restriction
	
• Triple scale outlet pressure gauge (brass or
	
stainless steel)
	
• Stainless steel stem and valve plug
	
• Pipe plug in second outlet
	
Types 67DFR and 67DFSR only
	
• Smart Bleed internal check valve
	
Types 67DF, 67DFR, 67DFS, and 67DFSR
	
• Stainless steel drain valve

1. The pressure/temperature limits in this Bulletin and any applicable standard or code limitation should not be exceeded.
2. Silicone (VMQ) is not compatible with hydrocarbon gas.
3. Product complies with the material requirements of NACE International MR0175 or MR0103. Environmental limits may apply.
4.  Do not use in high aromatic hydrocarbon service.

3

Bulletin 71.1:67D
Table 1. Available Configurations
CONSTRUCTION FEATURES
TYPE

With Internal
Relief

With Filter

OPTIONAL FEATURES
Smart BleedTM
Internal Check
Valve Airset

Drain Valve

BODY MATERIAL
External
Fixed Bleed

Aluminum

67D

Stainless Steel

X

67DR

X

X

X

X

X

67DS

X

67DSR
67DF

X

67DFR

X

X

67DFS

X

X

X

X

X

67DFSR

X

X
X

X

X

X

X

X

X

X

X

Table 2. Outlet Pressure Ranges and Control Spring Data
TYPES

CONTROL SPRING DATA

OUTLET PRESSURE RANGES

67D, 67DR,
67DF, and 67DFR

67DS, 67DSR,
67DFS, and 67DFSR

Part Number

Wire Diameter

Free Length

Material

Color Code

Inches

mm

Inches

mm

0.135
0.156
0.170
0.207

3.43
3.96
4.32
5.26

1.43
1.43
1.43
1.43

36.2
36.2
36.2
36.2

psig

bar

0 to 20
0 to 35
0 to 60
0 to 125

0 to 1.4
0 to 2.4
0 to 4.1
0 to 8.6

GE07809T012
T14059T0012
T14058T0012
T14060T0012

Music Wire

Green stripe
Silver
Blue stripe
Red stripe

0 to 35
0 to 60
0 to 125

0 to 2.4
0 to 4.1
0 to 8.6

T14113T0012
T14114T0012
T14115T0012

Inconel®

Silver stripe
Blue
Red

0.156
0.172
0.207

3.96
4.37
5.26

1.43
1.43
1.43

36.2
36.2
36.2

0 to 20
0 to 35
0 to 60
0 to 125
0 to 150

0 to 1.4
0 to 2.4
0 to 4.1
0 to 8.6
0 to 10.3

10C1729X012
T14113T0012
T14114T0012
T14115T0012
10C1730X012

Inconel®

Green
Silver stripe
Blue
Red
Black

0.135
0.156
0.172
0.207
0.250

3.43
3.96
4.37
5.26
6.35

1.50
1.43
1.43
1.43
1.77

38.1
36.2
36.2
36.2
44.9

Table 3. Construction Materials
MATERIAL
BODY AND  
SPRING CASE
SPRING RETAINER

TYPES
67D and 67DR

67DF and 67DFR

67DS and 67DSR

Aluminum (ASTM B85/Alloy 380)
Aluminum

67DFS and 67DFSR

CF8M/CF3M Stainless steel

Zinc-plated steel

316L Stainless steel

UPPER SPRING SEAT

Zinc-plated steel

DIAPHRAGM PLATE

Chromate conversion coated Aluminum

CONTROL SPRING

Plated steel or Inconel® (NACE)

Inconel®

Brass, Aluminum, or Stainless steel

316L Stainless steel

316 Stainless steel

VALVE STEM  
VALVE PLUG
VALVE SPRING

Stainless steel or Inconel® (NACE)

DIAPHRAGM
AND O-RINGS

Nitrile (NBR), Fluorocarbon (FKM), Low Temp Nitrile (NBR), or Silicone (VMQ)(1)

SOFT SEAT AND GASKETS

Nitrile (NBR) or Fluorocarbon (FKM)

BOLTING AND
ADJUSTING SCREW

Zinc-plated steel or Stainless steel

HANDWHEEL
FILTER RETAINER

Zinc-plated steel
----

316 Stainless steel

FILTER ELEMENT

316 Stainless steel

----

Plastic, Glass fiber,
or Stainless steel

----

Plastic, Glass fiber or
Stainless steel

DRAIN VALVE

----

Brass or
18-8 Stainless steel

----

316 Stainless steel or
18-8 Stainless steel

DRIPWELL

----

Aluminum
(ASTM B85/Alloy 380)

----

CF8M/CF3M Stainless steel

1. Silicone (VMQ) diaphragm is only available with internal relief (Types 67DR, 67DSR, 67DFR, and 67DFSR).
Inconel® is a mark owned by Special Metals Corporation.

4

Zinc-plated steel or Stainless steel
----

Type XXXX
Bulletin 71.1:67D

TYPE 67DF OR 67DFS

TYPE 67D OR 67DS

M1153

M1154

INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE

TYPE 67DR OR 67DSR

TYPE 67DFR OR 67DFSR

SMART BLEED™ OPTION FOR 
TYPE 67DFR OR 67DFSR

Figure 2.  67D Series Operational Schematics

Principle of Operation (Figure 2)

INLET PRESSURE
OUTLET
PRESSURE
Downstream pressure
is registered
internally on the lower side of
ATMOSPHERIC
PRESSURE
the diaphragm. When
the downstream
pressure is at or above
the set pressure,LOADING
the valve plug
is held against the orifice and
PRESSURE
INTERMEDIATE
PRESSURE
there is no flow through
the regulator.
When demand increases,
downstream pressure
drops
slightlyPRESSURE
allowing the spring to
PILOT
SUPPLY
extend, moving the stem down and the valve plug away from the
orifice. This allows flow through the regulator.

Internal Relief 
(Types 67DR, 67DSR, 67DFR, and 67DFSR) 
If for some reason, outside of normal operating conditions,
the downstream pressure exceeds the setpoint of the
regulator, the force created by the downstream pressure
will lift the diaphragm until the diaphragm is lifted off the
relief seat. This allows flow through the token relief. The
relief valve on the Type 67DR, 67DSR, 67DFR, or 67DFSR
is an elastomer plug that prevents leakage of air from
the downstream to atmosphere during normal operation,
thereby conserving plant air.

Smart Bleed™ Airset
In some cases, it is desired to exhaust downstream pressure
if inlet pressure is lost or drops below the setpoint of the
regulator. For example, if the regulator is installed on
equipment that at times has no flow demand but is expected
to backflow on loss of inlet pressure. The Type 67DFR or
67DFSR can be ordered with the Smart Bleed option which
includes an internal check valve for this application. During

operation, if inlet pressure is lost, or decreases below the
setpoint of the regulator, the downstream pressure will back
flow upstream through the regulator and check valve. This
option eliminates the need for a fixed bleed downstream of
the regulator, thereby conserving plant air.
Note
During normal operation the check valve’s metal 
to metal seat allows limited fl ow through the 
regulator from the inlet to outlet, even when 
there is no downstream demand.  To prevent 
downstream pressure buildup, the Smart Bleed 
option is only avilable with the internal relief 
version of the 67 Series. 

Installation
The 67D Series regulators may be installed in any position.
Spring case vents must be protected against the entrance
of rain, snow, debris, or any other foreign material that might
plug the vent openings. The inlet connection is marked “In”
and the main outlet connection is marked “Out”. If a pressure
gauge is not installed in one of the two secondary outlet
connections, plug the unused connections. See Figures 4
and 5 for dimensions.
Emerson Process Management Regulator Technologies,
Inc. provides an instruction manual with every regulator
shipped. Refer to this for complete installation, operation and
maintenance instructions. Included is a complete listing of
individual parts and recommended spare parts.

5

Bulletin 71.1:67D
Overpressure Protection

Note

The 67D Series regulators have maximum outlet pressure
ratings that are lower than their maximum inlet pressure
ratings. A pressure-relieving or pressure-limiting device is
needed if inlet pressure can exceed the maximum outlet
pressure rating.
Types 67DR, 67DSR, 67DFR, and 67DFSR regulators have
a low capacity internal relief valve for minor seat leakage only.
Other overpressure protection must be provided if the maximum
inlet pressure can exceed the maximum pressure rating of the
downstream equipment or exceeds maximum outlet pressure
rating of the Type 67DR, 67DSR, 67DFR, or 67DFSR regulator.
Overpressuring any portion of a regulator or associated
equipment may cause leakage, parts damage, or personal
injury due to bursting of pressure-containing parts or
explosion of accumulated gas. Regulator operation within
ratings does not preclude the possibility of damage from
external sources or from debris in the pipeline. A regulator
should be inspected for damage periodically and after any
overpressure condition.
Refer to the Capacity Information section and the WideOpen Flow Coefficients for Relief Valve Sizing in the
Specifications section on page 3 to determine the required
relief valve capacity.

Capacity Information
Table 4 shows the air regulating capacities of the 		
67D Series regulators at selected inlet pressures and 	
outlet pressure settings. Flows are shown in SCFH (at
60°F and 14.7 psia) and in Nm3/h (at 0°C and 1.01325 bar) 	
of air.

The 67D Series regulators may be sized for 100%
flow using capacities as shown in Table 4.  It is
not necessary to reduce published capacities.
To determine the equivalent capacities for other gases,
multiply the table capacity by the following appropriate
conversion factor: 1.29 for 0.6 specific gravity natural gas,
0.810 for propane, 0.707 for butane, or 1.018 for nitrogen.
For gases of other specific gravities, divide the table
capacities by the square root of the appropriate specific
gravity. To find wide-open flow capacities for relief sizing at
any inlet pressure, perform one of the following procedures.
Then, if necessary, convert using the factors provided above.
For critical pressure drops (absolute outlet pressure equal
to or less than one-half of absolute inlet pressure), use the
following formula:
Q = (P1)(Cg)
For pressure drops lower than critical (absolute outlet
pressure greater than one-half of absolute inlet pressure),
use the following formula:

Q =
where,
    Q	 =
   P1	=
   Cg	 =
    G	 =
    T	
=
   C1	 =
    P	 =

520
C P SIN
GT g 1

)

3417
C1

P
P1

)

DEG

gas flow rate, SCFH
absolute inlet pressure, psia (P1 gauge + 14.7)
gas sizing coefficient
specific gravity of the gas
absolute temperature of gas at inlet, °Rankine
flow coefficient (Cg ÷ Cv)
pressure drop across the regulator, psi

Then, if capacity is desired in normal cubic meters per hour 	
(at 0°C and 1.01325 bar), multiply SCFH by 0.0268.
POSITION 3

NACE Universal Compliance
POSITION 4

POSITION 2

The manufacturing processes and materials used by
Regulator Technologies assure that all products specified
for sour gas service comply with the chemical, physical, and
metallurgical requirements of NACE MR0175 and/or NACE
MR0103.  Customers have the responsibility to specify
correct materials.  Environmental limitations may apply and
shall be determined by the user.

GE31784

POSITION 1 (ALIGNED WITH INLET) (STANDARD)

Figure 3. 67D Series Vent Positions

6

Optional materials are available for applications handling sour
gases. These constructions comply with the recommendations
of NACE International sour service standards.

Bulletin 71.1:67D
Table 4. 67D Series Flow Capacities
OUTLET PRESSURE
RANGE, SPRING PART
NUMBER AND  
COLOR CODE

OUTLET
PRESSURE
psig

5

0 to 20 psig / 0 to 1.4 bar
GE07809T012
(Green Stripe)
10C1729X012
(Green)

10

20

15

0 to 35 psig / 1 to 2.4 bar
T14059T0012 (Silver)
T14113T0012
(Silver Stripe)

20

35

INLET
PRESSURE

bar

psig

bar

0.34

25
50
75
100
150
200
250
400(1)

CAPACITIES IN SCFH / Nm3/h OF AIR
Types 67D, 67DR, 67DS, and 67DSR
5% Droop

10% Droop

Types 67DF, 67DFR, 67DFS, and 67DFSR

20% Droop

5% Droop

10% Droop

20% Droop

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

1.7
3.4
5.2
6.9
10.3
13.8
17.2
27.6

320
740
1000
750
850
240
290
370

8.6
19.8
26.8
20.1
22.8
6.4
7.8
9.9

530
1100
2700
3600
3200
810
460
590

14.2
29.5
72.4
96.5
85.8
21.7
12.3
15.8

950
2200
3200
4100
6100
6300
6300
2700

25.5
59.0
85.8
110
163
169
169
72.4

320
400
460
590
780
940
1000
----

8.6
10.7
12.3
15.8
20.9
25.2
26.8
----

400
540
850
2800
1700
1700
1800
----

10.7
14.5
22.8
75.0
45.6
45.6
48.2
----

600
1100
2600
2900
3900
2200
2200
----

16.1
29.5
69.7
77.7
105
59.0
59.0
----

0.69

25
50
75
100
150
200
250
400(1)

1.7
3.4
5.2
6.9
10.3
13.8
17.2
27.6

450
1100
2600
3900
3400
1200
850
470

12.1
29.5
69.7
104
91.1
32.2
22.8
12.6

790
1900
3200
4400
6600
7800
8000
3400

21.2
50.9
85.8
118
177
209
214
91.1

1100
2700
3900
5100
7400
7800
8000
4700

29.5
72.4
105
137
198
209
214
126

390
600
870
1100
2200
1900
2000
----

10.5
16.1
23.3
29.5
59.0
50.9
53.6
----

570
750
2100
3300
3200
2300
2400
----

15.3
20.1
56.3
88.4
85.8
61.6
64.3
----

830
1700
3100
3900
4800
4900
3300
----

22.2
45.6
83.1
105
129
131
88.4
----

1.4

50
75
100
150
200
250
400(1)

3.4
5.2
6.9
10.3
13.8
17.2
27.6

1500
2600
4500
6700
9000
11,200
5500

40.2
69.7
121
180
241
300
147

2100
3500
4900
7200
9400
11,200
6100

56.3
93.8
131
193
252
300
163

2600
3800
5100
7600
10,000
11,200
9100

69.7
102
137
204
268
300
244

870
1600
3600
4000
3300
2900
----

23.3
42.9
96.5
107
88.4
77.7
----

1500
2600
4300
6600
4700
5100
----

40.2
69.7
115
177
126
137
----

2100
3400
4600
6600
6900
7100
----

56.3
91.1
123
177
185
190
----

1.0

25
50
75
100
150
200
250
400(1)

1.7
3.4
5.2
6.9
10.3
13.8
17.2
27.6

480
860
1200
2000
5000
1000
500
820

12.9
23.0
32.2
53.6
134
26.8
13.4
22.0

760
1500
2700
3900
5900
7600
8900
6400

20.4
40.2
72.4
104
158
204
239
172

1000
2200
3700
4800
7200
8800
9200
7400

26.8
59.0
99.2
129
193
236
247
198

360
720
870
1100
3400
2600
2700
----

9.7
19.3
23.3
29.5
91.1
69.7
72.4
----

520
1300
2100
3700
5700
4100
3300
----

14.0
34.8
56.3
99.2
153
110
88.4
----

800
2100
3500
4400
6400
5900
6000
----

21.4
56.3
93.8
118
172
158
161
----

1.4

25
50
75
100
150
200
250
400(1)

1.7
3.4
5.2
6.9
10.3
13.8
17.2
27.6

370
770
1100
1800
6200
2900
4900
830

9.9
20.6
29.5
48.2
166
77.7
131
22.2

570
1200
2600
4500
7000
7500
11,000
8300

15.3
32.2
69.7
121
188
201
295
222

810
1900
3800
5200
7500
7800
11,000
8300

21.7
50.9
102
139
201
209
295
222

420
880
1100
1800
3900
5600
4400
----

11.3
23.6
29.5
48.2
104
150
118
----

570
1500
2400
3800
6600
8700
8800
----

15.3
40.2
64.3
102
177
233
236
----

940
2300
3900
4800
7000
8700
8800
----

25.2
61.6
105
129
188
233
236
----

2.4

50
75
100
150
200
250
400(1)

3.4
5.2
6.9
10.3
13.8
17.2
27.6

1000
2000
2900
6700
9000
11,100
7600

26.8
53.6
77.7
180
241
297
204

1700
3200
4500
7100
9500
11,900
9300

45.6
85.8
121
190
255
319
249

2200
3700
5100
7600
9900
12,500
12,800

59.0
99.2
137
204
265
335
343

840
1500
2000
6300
8800
6000
----

22.5
40.2
53.6
169
236
161
----

1300
2500
3900
6800
9000
10,000
----

34.8
67.0
104
182
241
268
----

2000
3300
4700
7000
9000
10,000
----

53.6
88.4
126
188
241
268
----

  1. Inlet pressures above 250 psig / 17.2 bar with a maximum of 400 psig / 27.6 bar are only available on unfiltered models (Types 67D, 67DR, 67DS, and 67DSR).

- continued -

7

Bulletin 71.1:67D
Table 4. 67D Series Flow Capacities (continued)

OUTLET PRESSURE
RANGE, SPRING PART
NUMBER AND COLOR
CODE

OUTLET
PRESSURE

INLET
PRESSURE

psig

bar

psig

bar

2.4

50
75
100
150
200
250
400(1)

5% Droop

10% Droop

Types 67DF, 67DFR, 67DFS, and 67DFSR

20% Droop

5% Droop

10% Droop

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

3.4
5.2
6.9
10.3
13.8
17.2
27.6

850
1400
1900
6600
9200
11,200
1100

22.8
37.5
50.9
177
247
300
29.5

1400
2500
4100
7100
9600
11,500
11,900

37.5
67.0
110
190
257
308
319

2100
3600
5100
7600
10,200
11,500
11,900

53.6
96.5
137
204
273
308
319

690
1000
1600
3100
7200
9500
----

18.5
26.8
42.9
83.1
193
255
----

1100
1900
2700
5600
8400
9500
----

29.5
50.9
72.4
150
225
255
----

1800
2900
4300
6600
8900
9500
----

48.2
77.7
115
177
239
255
----

4.1

75
100
150
200
250
400(1)

5.2
6.9
10.3
13.8
17.2
27.6

1200
2100
4300
9200
11,900
4000

32.2
56.3
115
247
319
107

2200
3600
6900
9700
12,400
18,000

59.0
96.5
185
260
332
482

3000
4600
7600
10,200
12,800
18,000

80.4
123
204
273
343
482

920
1500
2600
4300
9500
----

24.7
40.2
69.7
115
255
----

1600
2500
5200
8300
10,600
----

42.9
67.0
139
222
284
----

2600
4000
6600
8800
11,100
----

69.7
107
177
236
297
----

4.1

75
100
135
150
200
250
400(1)

5.2
6.9
9.3
10.3
13.8
17.2
27.6

690
1000
1500
1700
2500
5600
3500

18.5
26.8
40.2
45.6
67.0
150
93.8

1200
1900
3000
3500
6000
8100
17,900

32.2
50.9
80.4
93.8
161
217
480

2000
3000
4600
5300
7700
9300
17,900

53.6
80.4
123
142
206
249
480

670
1000
1300
1400
1800
2400
----

18.0
26.8
34.8
37.5
48.2
64.3
----

1100
1800
2500
2800
4100
6600
----

29.5
48.2
67.0
75.0
110
177
----

2000
2900
4300
5200
7600
10,200
----

53.6
77.7
115
139
204
273
----

5.5

100
135
150
200
250
400(1)

6.9
9.3
10.3
13.8
17.2
27.6

1000
1600
1900
2900
4200
3700

26.8
42.9
50.9
77.7
113
99.2

1700
3000
3700
6000
10,200
19,900

45.6
80.4
99.2
161
273
533

2900
4600
5400
7700
12,200
10,400

77.7
123
145
206
327
279

960
1500
1700
2200
2900
----

25.7
40.2
45.6
59.0
77.7
----

1700
2800
3100
4800
7100
----

45.6
75.0
83.1
129
190
----

3000
4600
5300
8000
10,600
----

80.4
123
142
214
284
----

125

8.6

135
150
200
250
400(1)

9.3
10.3
13.8
17.2
27.6

1500
2100
3800
5800
6800

40.2
56.3
102
155
182

2500
3200
5600
7800
19,400

67.0
85.8
150
209
520

3500
4300
6700
9000
20,900

93.8
115
180
241
560

1600
1800
2900
4100
----

42.9
48.2
77.7
110
----

2700
3200
5200
7800
----

72.4
85.8
139
209
----

4400
5200
8000
10,400
----

118
139
214
279
----

110

7.6

150
200
250
400(1)

10.3
13.8
17.2
27.6

1900
2700
3400
4200

50.9
72.4
91.1
113

3300
4800
6200
11,300

88.4
129
166
303

5500
8300
10,500
19,100

147
222
281
512

2000
2600
3400
----

53.6
69.7
91.1
----

3400
4800
6000
----

91.1
129
161
----

5600
8000
10,400
----

150
214
279
----

135

9.3

150
200
250
400(1)

10.3
13.8
17.2
27.6

1800
3000
3900
6400

48.2
80.4
105
172

3300
5400
6700
13,300

88.4
145
180
356

5600
8300
10,700
19,300

150
222
287
517

1800
2800
3700
----

48.2
75.0
99.2
----

3200
5100
6600
----

85.8
137
177
----

5500
8200
11,000
----

147
220
295
----

150

10.3

200
250
400(1)

13.8
17.2
27.6

2900
4000
6400

77.7
107
172

5200
7400
13,900

139
198
373

8300
11,000
19,700

222
295
528

2900
4100
----

77.7
110
----

5200
7300
----

139
196
----

8200
11,000
----

220
295
----

60

60

80

  1. Inlet pressures above 250 psig / 17.2 bar with a maximum of 400 psig / 27.6 bar are only available on unfiltered models (Types 67D, 67DR, 67DS, and 67DSR).
  2. Available for Types 67DS, 67DSR, 67DFS, and 67DFSR only.

Ordering Information
When ordering, complete the Ordering Guide on pages 11
and 12. Refer to the Specifications section on page 3.
Review the description to the right of each specification and
the information in each referenced table or figure. Specify
your choice whenever a selection is offered.

8

20% Droop

Nm3/h

0 to 60 psig /
0 to 4.1 bar
T14058T0012 (Blue Stripe)
T14114T0012 (Blue)

0 to 150 psig /
0 to 10.3 bar(2)
10C1730X012 (Black)

Types 67D, 67DR, 67DS, and 67DSR

SCFH

35

0 to 125 psig /
0 to 8.6 bar
T14060T0012 (Red Stripe)
T14115T0012 (Red)

CAPACITIES IN SCFH / Nm3/h OF AIR

Bulletin 71.1:67D
C
F

D

G

E

VENT

SIDE OUTLET
1/4 NPT

B MAX

OUTLET
CONNECTION
1/2 NPT

INLET CONNECTION
1/2 NPT
SIDE OUTLET
1/4 NPT

A

OPTIONAL
GAUGE

GG01138

TYPE 67D OR 67DR
1.44 /
37

C

F

D

G

E

CLOSING CAP

VENT
1/4 NPT
SIDE OUTLET
1/4 NPT

B

1.33 /
34

SIDE OUTLET
1/4 NPT

OUTLET CONNECTION
1/2 NPT

INLET CONNECTION
1/2 NPT

A

OPTIONAL
GAUGE

GG01145

INCHES /
mm

TYPE 67DS OR 67DSR
STANDARD DIMENSIONS FOR GAUGE OPTION

STANDARD DIMENSIONS

Figure 4. Types 67D, 67DR, 67DS, and 67DSR Dimensions
Table 5. Types 67D, 67DR, 67DS, and 67DSR Dimensions
DIMENSIONS
TYPES

A
Inches

67D and 67DR
67DS and 67DSR

2.35

B
mm
60

C

Inches

mm

3.66

93

5.12

130

D

E

F

G

Inches

mm

Inches

mm

Inches

mm

Inches

mm

Inches

mm

4.54

115

2.98

76

1.49

38

2.75

70

0.63

16

9

Bulletin 71.1:67D
C

F

D

VENT

G

E

OUTLET CONNECTION
1/2 NPT

INLET CONNECTION
1/2 NPT
B MAX
H

OPTIONAL
GAUGE

SIDE OUTLET
1/4 NPT

MOUNTING HOLES
FOR 5/16 / 7.9
DIAMETER BOLTS

A

2.92 / 74

SIDE OUTLET
1/4 NPT
I
GG01139

TYPE 67DF OR 67DFR
C
F

D
G

E

CLOSING CAP

VENT
1/4 NPT
SIDE OUTLET
1/4 NPT

B

OUTLET CONNECTION
1/2 NPT

INLET CONNECTION
1/2 NPT

1.33 /
34

SIDE OUTLET
1/4 NPT

H

OPTIONAL
GAUGE

MOUNTING HOLES
FOR 5/16 / 7.9
DIAMETER BOLTS

A
I

INCHES /
mm

GG01135

TYPE 67DFS OR 67DFSR
STANDARD DIMENSIONS FOR GAUGE OPTION

STANDARD DIMENSIONS

Figure 5. Types 67DF, 67DFR, 67DFS, and 67DFSR Dimensions
Table 6. Types 67DF, 67DFR, 67DFS, and 67DFSR Dimensions
DIMENSIONS
TYPES

A

B

C

Inches

mm

Inches

5.93

151

3.66

93

67DFS and 67DFSR 6.27

159

5.12

130

67DF and 67DFR

10

mm

D

E

F

G

H

I

Inches

mm

Inches

mm

Inches

mm

Inches

mm

Inches

mm

Inches

mm

4.54

115

2.98

76

1.49

38

2.88

73

0.63

16

0.69

18

Inches mm
2.25

57

Bulletin 71.1:67D
Ordering Guide
Type (Select One)
  67D (aluminum without internal relief)***
  67DR (aluminum with internal relief)***
  67DS (stainless steel without
internal relief)***
  67DSR (stainless steel with internal relief)***
  67DF (aluminum with filter and without
internal relief)***
  67DFR (aluminum with filter and
internal relief)***
  67DFS (stainless steel with filter and without
internal relief)***
  67DFSR (stainless steel with filter and
internal relief)***

Filter Material (Select One)
  Polyethylene (5 microns) (standard)***
  Glass (5 microns)***
  Polyvinylidene (PVDF) (40 microns)***
  Stainless steel (40 microns)***

	

Quantity (Specify)  
Spring Case Style (Select One)
  Drilled hole vent (Types 67D, 67DR, 67DF, and
  67DFR standard)***
    1/4 NPT vent (Types 67DS, 67DSR, 67DFS, 	
and 67DFSR standard)***
  Single hole panel mount***
Adjusting Screw  (Select One)
  Square head (Types 67D, 67DR, 67DF,
67DFR standard)*** 	 
  Square head with closing cap (Types 67DS, 	
67DSR, 67DFS, and 67DFSR standard)***
  Handwheel***
Outlet Pressure Range (Select One)
  0 to 20 psig / 0 to 1.4 bar***
  0 to 35 psig / 0 to 2.4 bar***
  0 to 60 psig / 0 to 4.1 bar***
  0 to 125 psig / 0 to 8.6 bar***
  0 to 150 psig / 0 to 10.3 bar (Types 67DS, 67DSR, 	
    67DFS, and 67DFSR only)***
Diaphragm, O-Rings, and Valve Seat Plug (Select One)
    Nitrile (NBR) (standard)***
    Fluorocarbon (FKM)**
Silicone (VMQ) diaphragm, Low Temperature
Nitrile (NBR) O-rings, and Nitrile (NBR) valve seat*

	

Drain Valve (Select One)
  Brass (Types 67DF and 67DFR standard)***
  Stainless steel (Types 67DFS and
67DFSR standard)***
  Automatic Drain with Nitrile (NBR) elastomers***
  Automatic Drain with Fluorocarbon (FKM) elastomers**
Spring Case Vent Location (Select One)
  Position 1 - Aligned with inlet (standard)***
  Position 2
  Position 3
  Position 4
External Fixed Bleed for Type 67DR, 67DSR, 67DFR, or
67DFSR (Optional)
   Yes**
Smart Bleed™ Internal Check Valve Airset            
(Optional - Types 67DFR and 67DFSR only)
  Yes**
Second Outlet (Select One)
  Open (Types 67D, 67DR, 67DF, and
67DFR standard)***
  Plugged with pipe plug (Types 67DS, 67DSR, 	
67DFS, and 67DFSR standard)***
  Pressure Gauge (see below)
Triple Scale Pressure Gauge (Optional)
  Brass Gauge or     Stainless Steel Gauge
 
  0 to 30 psig / 0 to 0.2 MPa / 0 to 2.1 bar***
 
  0 to 60 psig / 0 to 0.4 MPa / 0 to 4.1 bar***
 
  0 to 160 psig / 0 to 1.1 MPa / 0 to 11.0 bar***
- continued -

11

Bulletin 71.1:67D
Ordering Guide (continued)
NACE International MR0175 Construction (Optional)(1)
  Yes (not available with gauge)**
NACE International MR0103 Construction (Optional)
  Yes (not available with gauge)**
Replacement Parts Kit (Optional)
  Yes, send one replacement parts kit to match
this order.
1. Product complies with the material requirements of NACE International MR0175.
Environmental limits may apply.

Pressure (Please designate units):
Maximum Inlet Pressure (P1max)
Minimum Inlet Pressure (P1min)
Downstream Pressure Setting(s) (P2)
Maximum Flow (Qmax)

Regulators Quick Order Guide
***
**
*

Specification Worksheet
Application (Please designate units):
Specific Use
Line Size
Gas Type and Specific Gravity
Gas Temperature
Does the Application Require Overpressure Protection? 	
   Yes   No    If yes, which is preferred:
   Relief Valve
   Monitor Regulator
  Shut-off Device
Is overpressure protection equipment selection assistance
desired?

Readily Available for Shipment
Allow Additional Time for Shipment
Special Order, Constructed from Non-Stocked Parts.
Consult Your local Sales Office for Availability.

Availability of the product being ordered is determined by the component
with the longest shipping time for the requested construction.

Performance Required:
Accuracy Requirements?
Need for Extremely Fast Response?
Other Requirements:

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Tescom Corporation

USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
    +1 800 447 1250

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9000

Asia-Pacific
Singapore 128461, Singapore
Tel: +65 6770 8337

Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Gallardon 28320, France
Tel: +33 2 37 33 47 00

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9499

Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.fisherregulators.com

The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.

©Emerson Process Management Regulator Technologies, Inc., 2009, 2012; All Rights Reserved



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c003 61.141987, 2011/02/22-12:03:51
Create Date                     : 2012:04:12 22:38:13+08:00
Metadata Date                   : 2012:04:12 22:38:19+08:00
Modify Date                     : 2012:04:12 22:38:19+08:00
Creator Tool                    : Adobe InDesign CS5.5 (7.5.2)
Page Image Page Number          : 1, 2
Page Image Format               : JPEG, JPEG
Page Image Width                : 256, 256
Page Image Height               : 256, 256
Page Image                      : (Binary data 8550 bytes, use -b option to extract), (Binary data 7406 bytes, use -b option to extract)
Instance ID                     : uuid:9415a6e7-c6c3-4821-956b-93305d78a667
Document ID                     : xmp.did:B69C52AB0478E111B0BEF7B1D3264533
Original Document ID            : adobe:docid:indd:84718b4c-cbe2-11df-8db0-c677d938d1d2
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:3A3B50AB0478E111B0BEF7B1D3264533
Derived From Document ID        : adobe:docid:indd:84718b4c-cbe2-11df-8db0-c677d938d1d2
Derived From Original Document ID: adobe:docid:indd:84718b4c-cbe2-11df-8db0-c677d938d1d2
Derived From Rendition Class    : default
History Action                  : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved
History Instance ID             : xmp.iid:1F2F79A67A77E111B4D1F2532FBAF389, xmp.iid:202F79A67A77E111B4D1F2532FBAF389, xmp.iid:5E0849777B77E111B4D1F2532FBAF389, xmp.iid:600CE8B97B77E111B4D1F2532FBAF389, xmp.iid:BF818EFD7B77E111B4D1F2532FBAF389, xmp.iid:99982C0D7E77E111B4D1F2532FBAF389, xmp.iid:4D9975A17E77E111B4D1F2532FBAF389, xmp.iid:992BB1028277E111B4D1F2532FBAF389, xmp.iid:E6CE8E808277E111B4D1F2532FBAF389, xmp.iid:24AD0DD78277E111B4D1F2532FBAF389, xmp.iid:57B1FFFD8277E111B4D1F2532FBAF389, xmp.iid:61DFC9338377E111B4D1F2532FBAF389, xmp.iid:787EF64B8377E111B4D1F2532FBAF389, xmp.iid:3BDDBC8B8377E111B4D1F2532FBAF389, xmp.iid:D5521E7D8477E111B4D1F2532FBAF389, xmp.iid:945D96D68477E111B4D1F2532FBAF389, xmp.iid:7C1562F58477E111B4D1F2532FBAF389, xmp.iid:5B7E283F8577E111B4D1F2532FBAF389, xmp.iid:2D3C1D618577E111B4D1F2532FBAF389, xmp.iid:C85186798577E111B4D1F2532FBAF389, xmp.iid:1626438C8577E111B4D1F2532FBAF389, xmp.iid:DDAA0DC18577E111B4D1F2532FBAF389, xmp.iid:FBDD6BD68577E111B4D1F2532FBAF389, xmp.iid:FA0E2EEE8577E111B4D1F2532FBAF389, xmp.iid:259A631E8877E111B4D1F2532FBAF389, xmp.iid:8B238DC48877E111B4D1F2532FBAF389, xmp.iid:76642D5C8977E111B4D1F2532FBAF389, xmp.iid:143001D98977E111B4D1F2532FBAF389, xmp.iid:1CA682528A77E111B4D1F2532FBAF389, xmp.iid:26D13FE88A77E111B4D1F2532FBAF389, xmp.iid:3A3B50AB0478E111B0BEF7B1D3264533, xmp.iid:B69C52AB0478E111B0BEF7B1D3264533, xmp.iid:B79C52AB0478E111B0BEF7B1D3264533, xmp.iid:2E1D6BDF0978E111B0BEF7B1D3264533, xmp.iid:A4220B820A78E111B0BEF7B1D3264533, xmp.iid:4CB8018A0D78E111B0BEF7B1D3264533, xmp.iid:61A6F5990E78E111B0BEF7B1D3264533, xmp.iid:B71149DE0E78E111B0BEF7B1D3264533, xmp.iid:A9BBD5EE0E78E111B0BEF7B1D3264533, xmp.iid:0CC2BC3F1078E1119BFEFFC4C0AF1396, xmp.iid:DD4ED2551178E1119BFEFFC4C0AF1396, xmp.iid:7BA933849679E1118D79E9B83F0D75CE, xmp.iid:2ECA87AB9D79E11182E8E3436C3D70FB, xmp.iid:D8F25B45517AE111ABA3E6B2FB0761EA, xmp.iid:17D1E26F7A7AE111ABA3E6B2FB0761EA, xmp.iid:C554A316AD84E111BD06E683BEE84A88
History When                    : 2012:03:27 03:34:06+08:00, 2012:03:27 03:34:06+08:00, 2012:03:27 03:39:56+08:00, 2012:03:27 03:41:48+08:00, 2012:03:27 03:43:41+08:00, 2012:03:27 03:58:26+08:00, 2012:03:27 04:02:35+08:00, 2012:03:27 04:26:47+08:00, 2012:03:27 04:30:18+08:00, 2012:03:27 04:32:43+08:00, 2012:03:27 04:33:48+08:00, 2012:03:27 04:35:19+08:00, 2012:03:27 04:35:59+08:00, 2012:03:27 04:37:46+08:00, 2012:03:27 04:44:31+08:00, 2012:03:27 04:47:01+08:00, 2012:03:27 04:47:53+08:00, 2012:03:27 04:49:57+08:00, 2012:03:27 04:50:54+08:00, 2012:03:27 04:51:35+08:00, 2012:03:27 04:52:06+08:00, 2012:03:27 04:53:35+08:00, 2012:03:27 04:54:10+08:00, 2012:03:27 04:54:50+08:00, 2012:03:27 05:10:30+08:00, 2012:03:27 05:15:09+08:00, 2012:03:27 05:19:23+08:00, 2012:03:27 05:22:53+08:00, 2012:03:27 05:26:17+08:00, 2012:03:27 05:30:28+08:00, 2012:03:27 20:02:04+08:00, 2012:03:27 20:02:04+08:00, 2012:03:27 20:05:39+08:00, 2012:03:27 20:39:19+08:00, 2012:03:27 20:43:52+08:00, 2012:03:27 21:05:34+08:00, 2012:03:27 21:13:10+08:00, 2012:03:27 21:15:05+08:00, 2012:03:27 21:15:32+08:00, 2012:03:27 21:24:58+08:00, 2012:03:27 21:32:44+08:00, 2012:03:29 19:58:36+08:00, 2012:03:29 20:49:49+08:00, 2012:03:30 18:15:27+08:00, 2012:03:30 23:10:07+08:00, 2012:04:12 22:37:54+08:00
History Software Agent          : Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5, Adobe InDesign 7.5
History Changed                 : /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata
Doc Change Count                : 4766
Format                          : application/pdf
Producer                        : Adobe PDF Library 9.9
Trapped                         : False
Page Count                      : 12
Creator                         : Adobe InDesign CS5.5 (7.5.2)
EXIF Metadata provided by EXIF.tools

Navigation menu