Emerson 95 Series Pressure Reducing Regulators Data Sheet

2015-03-30

: Emerson Emerson-95-Series-Pressure-Reducing-Regulators-Data-Sheet-681030 emerson-95-series-pressure-reducing-regulators-data-sheet-681030 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 40

DownloadEmerson Emerson-95-Series-Pressure-Reducing-Regulators-Data-Sheet-  Emerson-95-series-pressure-reducing-regulators-data-sheet
Open PDF In BrowserView PDF
Bulletin 71.1:95
November 2009

95 Series Industrial Pressure Regulators

W1894-1 / IL

W1894-1 / IL

TYPE 95LD

TYPE 95HD

W6195 / IL

TYPE 95LD (FLANGED)

W5091 / IL

W5092 / IL

TYPE 95L

TYPE 95H

D100117X012

Figure 1. 95 Series Pressure Reducing Regulators

www.fisherregulators.com

Bulletin 71.1:95
Introduction
The 95 Series regulators are compact, large-capacity,
direct-operated pressure regulators (see Figures 1 and 2).
The units are available in NPS 1/4 through 2 (DN 15
through 50) sizes and are offered in several different
end connection configurations. They are designed
to handle pressures up to 600 psig (41,4 bar) and
temperatures up to 650°F (343°C).
This product can help solve the toughest pressure
control applications. Typical applications include
superheated steam, steam injection, steam tracing,
nitrogen purging, boiler feed water, process chemicals,
cooling water, test fixtures, wash tanks, sterilizers/
autoclaves, fuel lines, pneumatic supply, and
many others.

Features
  •  Handwheels—Allow easy pressure setting changes
    and are standard on Types 95LD, 95HD, and optional
    on the NPS 1/2 (DN 15) body size of the Types 95L
    and 95H regulators. Tee-handles are optional on all
    other Types 95L and 95H body sizes.
  •  Versatile—Can be used with all process media 	
  including air, steam, gas, water, liquids (oils and 	
  process chemicals), and oxygen.
  •  Tight Shutoff With Elastomer Seats—Metal seats
    available for high temperatures.
  •  Direct-Operated—Design maximizes speed
  of response.
  •  Robust—Up to 600 psig (41,4 bar) inlet pressure.
  •  P1 = P2—Inlet equals outlet rating in 95H Series up
    to 600 psig (41,4 bar).

    cryogenics, and superheated steam. These 		
  constructions comply with the recommendations 	
of NACE International Standards MR0175
and MR0103.
  •  Large Turndown Ratio—No need for low Cv trims at
    low flows.
  •  Graphite Gaskets—For high temperature 	
applications up to 650°F (343°C) (optional).

	

  •  Set Pressures to 400 Psig (27,6 bar)
  •  Multiple End Connection Options—To match
    your application.
  •  Easy Maintenance—Seating parts are easily
    accessible by removing the plug on the bottom of
    the regulator.

Principle of Operation
The 95 Series (refer to Figure 2) is a direct-operated
regulator. Downstream pressure is registered
internally through the body to the under side of the
diaphragm. When the downstream pressure is at or
above the set pressure, the disk is held against the
orifice, and there is no flow through the regulator.
When demand increases, downstream pressure drops
slightly allowing the spring to extend, moving the stem
down and the disk away from the orifice. This allows
flow through the body to the downstream system.
Types 95H, 95L, 95HP, and 95HT use spring force to
regulate outlet pressure. Types 95HD and 95LD use
spring force to maintain a differential pressure between
spring case loading pressure and outlet pressure.

Installation

  •  Rugged Construction—Available in a variety of
    materials including Cast iron, Carbon steel, Stainless
    steel, Monel®, Hastelloy® C, Perfluoroelastomer 	
  (FFKM), and Fluorocarbon (FKM) to address the
  toughest service conditions. Severe service
  elastomers and corrosion resistant trims are also
  available -­excellent fluid compatibility.

The 95 Series regulators may be installed in any
position, as long as flow will be in the same direction as
that indicated by the body arrow. The Types 95H, 95L,
95HT, and 95HP regulators should be installed so that
their spring case vents are protected from anything that
might clog them.

  •  Differential Pressure Capability—Spring-loaded
    Polytetrafluoroethylene (PTFE) packing and tapped 	
connections permit pressure loading of the
	
Types 95LD and 95HD spring cases.

Emerson™ provides an instruction manual with
every regulator shipped. Refer to this for complete
installation, operation, and maintenance instructions.
Included is a complete listing of individual parts and
recommended spare parts.

  •  Special Service Capabilities—Optional materials
    are available for applications handling sour gases,
Monel® is a trademark of Special Metals Corporation.
Hastelloy® C is a trademark of Haynes International, Inc.

2

Bulletin 71.1:95
Specifications
Available Configurations
	
Type 95L: Low-pressure regulator for 2 to 30 psig 	
	
(0,14 to 2,1 bar) outlet pressures
	
Type 95H: High-pressure regulator for 5 to 150 psig
	
(0,35 to 10,3 bar) outlet pressures
	
Type 95LD: Low-pressure differential regulator for
	
2 to 30 psi (0,14 to 2,1 bar) differential 		
	
pressures with handwheel and packing box
	
Type 95HD: High-pressure differential regulator for
	
5 to 150 psi (0,35 to 10,3 bar) differential
	
pressures with handwheel and packing box
	
Type 95HP: High-pressure regulator for 15 to
	
400 psig (1,0 to 27,6 bar) outlet pressures
	
(soft-seated)
	
Type 95HT: High-pressure/high temperature
	
regulator for 15 to 300 psig (1,0 to 20,7 bar) outlet
	
pressures (metal seat) and up to 650°F (343°C)
	
Body and Orifice Sizes
	
NPS 1/4 body: 1/4-inch (6,4 mm) orifice
	
NPS 1/2 (DN 15) body: 3/8-inch (9,5 mm) orifice
	
NPS 3/4 and 1 (DN 20 and 25) bodies:
	
9/16-inch (14 mm) orifice
	
NPS 1-1/2 and 2 (DN 40 and 50) bodies:
	
1-1/16-inch (27 mm) orifice
End Connection Styles
	
NPT, ASME flanged; all sizes are fabricated with
	
slip-on flanges and are 14-inch face-to-face
	
(EN flanged; 356 mm face-to-face), CL150 RF, 		
	
CL300 RF, PN 16/25/40 RF, or SWE
Maximum Cold Working Pressures of Body Size
and Material
	
See Table 3
Outlet or Differential Pressure Ranges
	
See Table 5

Maximum Temperature Ranges of Diaphragm and
Seat Materials(1)(2)
MATERIAL

TEMPERATURE RANGE

Nitrile (NBR)
Neoprene (CR)
Fluorocarbon(FKM)(3)
Ethylenepropylene (EPDM)
Perfluoroelastomer (FFKM)
PTFE
Stainless steel

-40° to 180°F (-40° to 82°C)
-40° to 180°F (-40° to 82°C)
0° to 300°F (-18° to 149°C)
-40° to 275°F (-40° to 135°C)
0° to 425°F (-18° to 218°C)
-40° to 400°F (-40° to 204°C)
-40° to 650°F (-40° to 343°C)

Spring Case Construction
	
Vent is a drilled untapped hole (standard).
	
NPT (optional) See Figure 2
	
On Types 95HD and 95LD, the NPT tapped vent
   is standard.
Maximum Temperature Ranges of
Body Materials(1)(2)
TYPES

BODY AND SPRING
CASE MATERIALS

TEMPERATURE RANGE

95L, 95LD
95H, 95HD

Cast Iron
Steel
Stainless steel

-40° to 406°F (-40° to 208°C)
-20° to 450°F (-29° to 232°C)
-40° to 450°F (-40° to 232°C)

95HP

Steel
Stainless steel

-20° to 450°F (-29° to 232°C)
-40° to 450°F (-40° to 232°C)

95HT

Steel
Stainless steel

-20° to 650°F (-29° to 343°C)
-40° to 550°F (-40° to 288°C)

Pressure Setting Adjustment
Adjusting screw (standard), Handwheel/Tee 		
handle (optional) NPS 1/2 (DN 15) bodies have a 	
handwheel all other sizes have tee handles.
	
Types 95LD and 95HD: Handwheel for adjustment
Pressure Registration
	
Internal
Typical Regulating Capacities
	
Air: See Tables 8, 9, 10, 11, and 12
	
Steam: See Tables 13, 14, 15, 16, and 17
	
Water: See Tables 18, 19, 20, 21, and 22

    1. The pressure/temperature limits in this bulletin, and any applicable standard or code limitation for this regulator should not be exceeded.
   2. Pressures and/or the body end connection may decrease these maximum temperatures.
   3. Fluorocarbon (FKM) is limited to 200°F (93°C) hot water.

- continued -

3

Bulletin 71.1:95
Specifications (continued)
Shutoff Classification Per ANSI/FCI 70-3-2004		
	
Metal Seats: Class IV
	
PTFE: Class lV
	
Elastomer Seats: Class VI or better
Flow and Sizing Coefficients
	
See Table 4
Pressure Connections
	
See Figure 4
Construction Materials
	
See Table 6
Common Services and Material Compatibility
	
See Table 7

Approximate Weights
	
95H Series
	
NPS 1/4 body: 4 pounds (2 kg)
	
NPS 1/2 (DN 15) body: 8 pounds (4 kg)
	
NPS 3/4 and 1 (DN 20 and 25) bodies:
	
20 pounds (9 kg)
	
NPS 1-1/2 and 2 bodies (DN 40 and 50):
	
73 pounds (33 kg)
	
95L Series
	
NPS 1/4 body: 6 pounds (3 kg)
	
NPS 1/2 (DN 15) body: 12 pounds (5 kg)
	
NPS 3/4 and 1 (DN 20 and 25) bodies:
	
32 pounds (15 kg)

SPRING

CONTROL
SPRING

DIAPHRAGM

DIAPHRAGM HEAD
ASSEMBLY

STEM
ASSEMBLY

PITOT TUBE

VALVE PLUG
SPRING
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
A6554

TYPE 95L WITH METAL SEAT AND DIAPHRAGM
(ALSO TYPICAL OF TYPE 95H OR 95HT)

Figure 2. 95 Series Operational Schematic

4

METAL DIAPHRAGMS

GASKET

TYPE 95L WITH TWO METAL DIAPHRAGMS
(ALSO TYPICAL OF 95H OR 95HT, EXCEPT
ONLY TYPE 95L, NPS 1/4, 2 TO 6 PSI (0,14 to 0,41 bar) RANGE)

SPRING

METAL DIAPHRAGM

GASKET

TYPE 95L (NPS 1/4, 2 TO 6 PSI (0,14 to 0,41 bar) RANGE)
WITH METAL DIAPHRAGM

Bulletin 71.1:95
HANDWHEEL

CONTROL SPRING
UPPER SPRING SEAT

metal diaphragms
(key 12)

SPRING (key 11)
ELASTOMER
DIAPHRAGM

GASKETS (key 19)
ORIFICE

TYPE 95HD WITH TWO METAL DIAPHRAGMS
(EXCEPT ONLY TYPE 95HD, NPS 1/4,
2 TO 6 PSI (0,14 to 0,41 bar) RANGE)

VALVE PLUG
GUIDE
INLET PRESSURE
OUTLET PRESSURE
LOADING PRESSURE
M1006

TYPE 95HD WITH ELASTOMER SEAT AND DIAPHRAGM
(ALSO TYPICAL OF TYPE 95LD)

Figure 2. 95 Series Operational Schematic (continued)
air flow in Nm3/h

outlet pressure, psig

107

161

214

268

322

375

429

482

536
1,4

18

1,2

16

1,1

14

0,97

200 psig
(13,8 bar)
at inlet

12
10

0,69

100 psig
(6,9 bar)
at inlet

25 psig (1,7 bar)
at inlet

8

0,83

0,55

50 psig (3,5 bar) at inlet
6

outlet pressure, bar

53,6
20

0,41
initial setpoint = 15 psig (1,0 bar)
at 300 SCFH (8,0 Nm3/h) flow rate
with 100 psig (6,9 bar) at inlet

4

capacity at
10% droop

0,28

capacity at
20% droop

2

0,14

0

0
0

2

4

6

8

10

12

14

16

18

20

air flow in thousands of SCFH
CE4967-A
B0392-2 / IL

Figure 3. Air Flow Performance Curves of a NPS 1 (DN 25) Type 95L Regulator

5

Bulletin 71.1:95
Table 1. Sizing Types 95HD and 95LD Pressure Regulators
steps

1.  Determine service conditions.

2.  Select type number and spring range
   using Tables 3 and 5.

3.  Using the Fisher® Sizing Program,
   calculate Cg from data given in the
capacity tables. Use the table inlet
pressure closest to the service condition.
Also calculate using the table outlet
pressure which is closest to the
spring bias.

4.  Use the information in Step 3 to calculate
   Cg using the Fisher Sizing Program.

5.  Calculate flow for application based upon
   actual conditions and calculated Cg.

EXAMPLE - PSIG
P1 = 135 psig, P2 = 25 to 40 psig,
Bias = 10 psig
Loading pressure = 15 to 30 psig
Qmax = 1100 SCFH air
Specific Gravity = 1
Allowable droop = 20%
Line size = 1/2-inch
Since the bias set is 10 psig, select the Type 95LD
with a 5 to 15 psig spring range. (The Type 95LD
will withstand the pressure for the application, and
also has the lightest spring available.)
For the purpose of sizing, use the spring setpoint
   (bias) of 10 psi as outlet pressure, and an inlet
   pressure of 150 psig.
The closest capacity data in Tables 4 and 8
   shows the following:
C1 = 35 (Table 4)
P1table = 150 psig
P2table = 10 psi
Droop = 10 psig x 20% = 2 psig
∆Ptable = 150 psig - (10 psig - 2 psig) = 142 psid
Q = 1400 SCFH for size NPS 1/2 Type 95LD at
    20% droop

EXAMPLE - bar
P1 = 9,31 bar, P2 = 1,7 to 2,8 bar,
Bias = 0,69 bar
Loading pressure = 1,0 to 2,1 bar
Qmax = 29,5 Nm3/h air
Specific Gravity = 1
Allowable droop = 20%
Line size = 13 mm
Since the bias set is 0,69 bar, select the Type 95LD
with a 0,34 to 1,0 bar spring range. (The Type 95LD
will withstand the pressure for the application, and also
has the lightest spring available.)
For the purpose of sizing, use the spring setpoint
   (bias) of 0,69 bar as outlet pressure, and an inlet
   pressure of 10,3 bar.
The closest capacity data in Tables 4 and 8 shows
   the following:
C1 = 35 (Table 4)
P1table = 10,3 bar
P2table = 0,69 bar
Droop = 0,69 bar x 20% = 0,14 bar
∆Ptable = 10,3 bar - (0,69 bar - 0,14 bar) = 9,8 bar d
Q = 37,5 Nm3/h for size DN 15 Type 95LD at
    20% droop

Cg calculated = 8.5

Cg calculated = 8.5

P1 = 135 psig
P2max = 40 psi
Droop = 10 psig x 20% = 2 psig
∆P actual = 135 psig - (40 psig - 2 psig) = 97 psid
Cg calculated = 8.5
Q = 1248 SCFH air with droop equal to
    20% of spring bias

P1 = 9,3 bar
P2max = 2,8 bar
Droop = 0,69 bar x 20% = 0,14 bar
∆P actual = 9,3 bar - (2,8 bar - 0,14 bar) = 6,7 bar d
Cg calculated = 8.5
Q = 33,4 Nm3/h air with droop equal to
    20% of spring bias

Table 2. Back Calculating Sizing Coefficients
steps
1.  Determine service conditions.
2.  Select Type number and spring range
   using Tables 3 and 5.
3.  Because the capacity table for a Type 95L
   in Table 18 does not provide data for the
    exact application, choose the values from
    the table that most closely match the
    application. An NPS 1 (DN 25) Type 95L
fits the closest.
4.  Use information in Step 3 to calculate Cv
   using Fisher® Sizing Program.
5.  Determine flow capacity of Type 95 with
   actual conditions using Cv calculated from
   Step 4.

EXAMPLE - PSIG
P1 = 25 psig, P2 = 18 psig, Qmax = 10 GPM,
Medium = Water
The Type 95L with a 13 to 30 psig pressure range,
will provide the lightest spring for the application.
P1table = 30 psig
P2table = 20 psig
Droop = 20 psig x 20% = 4 psig
∆Ptable = 30 psig - (20 psig - 4 psig) = 14 psid
Q = 13 GPM
Km = 0.67 (See Table 4)

EXAMPLE - bar
P1 = 1,7 bar, P2 = 1,2 bar,
Medium = Water, Qmax = 37,8 l/min
The Type 95L with a 0,90 to 2,1 bar pressure range,
  will provide the lightest spring for the application.
P1table = 2,1 bar
P2table = 1,4 bar
Droop = 1,4 bar x 20% = 0,28 bar
∆Ptable = 2,1 bar - (1,4 bar - 0,28 bar) = 0,97 bar d
Q = 49,2 l/min
Km = 0.67 (See Table 4)

Cv calculated = 3.47

Cv calculated = 3.41

Cv = 3.47
P1 = 25 psig
P2 = 18 psig
Droop = 18 psig x 20% = 3.6 psig
∆P actual = 25 psig - (18 psig - 3.6 psig) = 10.6 psid
Q calculated = 11.3 GPM

Cv = 3.41
P1 = 1,7 bar
P2 = 1,2 bar
Droop = 1,2 bar x 20% = 0,25 bar
∆P actual = 1,7 bar - (1,2 bar - 0,25 bar) = 0,73 bar d
Q calculated = 42,8 l/min

Table 3. Maximum Cold Working Pressures of Body Size and Material(1)(2)
TYPES

BODY SIZES, NPS

95L and 95LD

All Sizes

95H and 95HD

All Sizes

95HP

All Sizes

95HT

1/4 to 1 (DN 25)
1-1/2, 2 (DN 40, 50)

BODY AND SPRING
CASE MATERIALS
Cast Iron
Steel
Stainless steel
Cast Iron
Steel
Stainless steel
Steel
Stainless steel
Steel
Stainless steel
Steel
Stainless steel

MAXIMUM INLET PRESSURE,
PSIG (bar)
250 (17,2)
300 (20,7)
300 (20,7)
250 (17,2)
300 (20,7)
300 (20,7)
600 (41,4)
600 (41,4)
600 (41,4)
600 (41,4)
600 (41,4)
600 (41,4)

  1.  The pressure/temperature limits in this bulletin, and any applicable standard or code limitation should not be exceeded.
  2.  Temperature and/or the body end connection may decrease these maximum pressures.

6

MAXIMUM OUTLET PRESSURE,
PSIG (bar)
50 (3,4)
125 (8,6)
125 (8,6)
250 (17,2)
300 (20,7)
300 (20,7)
600 (41,4)
550 (37,9)
600 (41,4)
550 (37,9)
450 (31,0)
450 (31,0)

Bulletin 71.1:95
Table 4. Flow and Sizing Coefficients for all 95 Series Regulators
BODY SIZE,
NPS (DN)

WIDE-OPEN COEFFICIENTS (FOR RELIEF SIZING)
Cv

Cg

Cs

1/4

0.8

28

1.40

1/2 (15)

1.9

67

3.35

3/4, 1 (20, 25)

4.4

156

7.80

1-1/2, 2 (40, 50)

12.5

475

23.75

C1

IEC SIZING COEFFICIENTS

Km

XT

0.83
35

0.71

0.775

0.67
38

0.83

0.913

FD

FL

0.58

0.91

0.58

0.84

0.44

0.82

0.37

0.91

  Km = FL2

Table 5. Body Sizes and Pressure Ranges
TYPES

95L and 95LD

BODY SIZES,
NPS (DN)

SPRING WIRE
DIAMETER

SPRING
FREE LENGTH

SPRING PART NUMBER
AND COLOR

Psi/Psig

bar

Inches

mm

Inches

mm

1/4

2 to 6
5 to 15
13 to 30

0,14 to 0,41
0,35 to 1,0
0,90 to 2,1

0.148
0.172
0.207

3,76
4,37
5,26

2.00
2.00
1.94

50,8
50,8
49,2

1E392527022 Yellow
1E392627012 Green
1E392727142 Red

1/2 (15)

2 to 6
5 to 15
13 to 30

0,14 to 0,41
0,35 to 1,0
0,90 to 2,1

0.207
0.234
0.281

5,26
5,94
7,14

2.50
2.57
2.44

63,5
65,2
62,0

1E395627022 Yellow
1D7455T0012 Green
1E395727192 Red

3/4, 1 (20, 25)

2 to 6
5 to 15
13 to 30

0,14 to 0,41
0,35 to 1,0
0,90 to 2,1

0.306
0.343
0.406

7,77
8,71
10,3

4.00
4.00
4.00

102
102
102

1E398927022 Yellow
1E399027142 Green
1E399127162 Red

1/4

15 to 30
25 to 75
70 to 150

1,0 to 2,1
1,7 to 5,2
4,8 to 10,3

0.148
0.172
0.207

3,76
4,37
5,26

2.00
2.00
1.94

50,8
50,8
49,2

1E392527022 Yellow
1E392627012 Green
1E392727142 Red

1/2 (15)

15 to 30
25 to 75
70 to 150

1,0 to 2,1
1,7 to 5,2
4,8 to 10,3

0.207
0.234
0.281

5,26
5,94
7,14

2.50
2.57
2.44

63,5
65,2
62,0

1E395627022 Yellow
1D7455T0012 Green
1E395727192 Red

3/4, 1 (20, 25)

15 to 30
25 to 75
70 to 150

1,0 to 2,1
1,7 to 5,1
4,8 to 10,3

0.306
0.343
0.406

7,77
8,71
10,3

4.00
4.00
4.00

102
102
102

1E398927022 Yellow
1E399027142 Green
1E399127162 Red

1-1/2, 2 (40, 50)

5 to 80
60 to 120
100 to 140
120 to 150

0,35 to 5,5
4,1 to 8,3
6,9 to 9,7
8,3 to 10,3

0.531
0.562
0.593
0.656

13,5
14,3
15,1
16,7

6.56
6.56
6.50
6.56

167
167
165
167

1E795327082 Light Blue
1E795427082 Light Gray
1E793327082 Yellow
1P788827082 Black

1/4

15 to 100
80 to 300

1,0 to 6,9
5,5 to 20,7

0.192
0.282

4,88
7,16

1.96
1.96

49,8
49,8

14B9941X012 Unpainted
14B9940X012 Unpainted

1/2 (15)

15 to 100
80 to 300

1,0 to 6,9
5,5 to 20,7

0.282
0.375

7,16
9,52

2.50
2.50

63,5
63,5

14B9943X012 Unpainted
14B9942X022 Unpainted

3/4, 1 (20, 25)

15 to 100
80 to 300

1,0 to 6,9
5,5 to 20,7

0.437
0.562

11,1
14,3

4.03
4.03

102
102

14B9944X022 Unpainted
14B9945X022 Unpainted

1-1/2, 2 (40, 50)

15 to 100
60 to 260

1,0 to 6,9
4,1 to 17,9

0.625
0.812

15,9
20,6

6.70
6.70

170
170

17B1704X012 Unpainted
17B1705X012 Unpainted

1/4

15 to 100
80 to 400

1,0 to 6,9
5,5 to 27,6

0.192
0.282

4,88
7,16

1.96
1.96

49,8
49,8

14B9941X012 Unpainted
14B9940X012 Unpainted

1/2 (15)

15 to 100
80 to 400

1,0 to 6,9
5,5 to 27,6

0.282
0.375

7,16
9,52

2.50
2.50

63,5
63,5

14B9943X012 Unpainted
14B9942X022 Unpainted

3/4, 1 (20, 25)

15 to 100
80 to 400

1,0 to 6,9
5,5 to 27,6

0.437
0.562

11,1
14,3

4.03
4.03

102
102

14B9944X022 Unpainted
14B9945X022 Unpainted

1-1/2, 2 (40, 50)

15 to 100
60 to 300

1,0 to 6,9
4,1 to 20,7

0.625
0.812

15,9
20,6

6.70
6.70

170
170

17B1704X012 Unpainted
17B1705X012 Unpainted

95H and 95HD

95HT

95HP

 

OUTLET OR DIFFERENTIAL
PRESSURE RANGE(1)

1. For Types 95LD and 95HD regulators, the pressure ranges indicate the differential pressure that can be obtained with the indicated spring. The differential pressure (spring setting) is
added to the spring case loading pressure to determine the actual outlet pressure.

7

Bulletin 71.1:95
Table 6.  Construction Materials
MAIN VALVE MATERIALS
Body

Spring Case

Regulator Spring

Valve Plug Spring

Cast Iron
WCC/WCB Steel
CF8M Stainless steel
Hastelloy® C
Monel®

Cast Iron
WCC/WCB Steel
CF8M Stainless steel

Zinc-plated Steel (standard)
Inconel®
302 Stainless steel
17-7PH

302 Stainless steel (standard)
Inconel®

Trim Materials:
ELASTOMER SEAT
Part Name

Standard

Optional

Neoprene (CR) or Fluorocarbon (FKM)

302 Stainless steel
Ethylenepropylene (EPDM)
Monel®
Hastelloy® C
PTFE protector available with
elastomeric diaphragm

Diaphragm

PTFE
Nitrile (NBR)
Ethylenepropylene (EPDM)
Perfluoroelastomer (FFKM)

Disk
Disk Holder
Valve Plug Guide
Valve Plug

Brass or 416 Stainless steel

316 Stainless steel
Monel®
Hastelloy® C

Grade 5 Steel

B8M, B7

Orifice
Stem Assembly
Bolting

METAL SEAT
Diaphragm

302 Stainless steel(1)

Disk

416 Stainless steel

Disk Holder

Brass or 416 Stainless steel

Valve Plug

416 Stainless steel

Valve Plug Guide
Orifice

Monel®
Hastelloy® C

316 Stainless steel
Monel®
Hastelloy® C

Brass or 416 Stainless steel

Stem Assembly
Gaskets

Composition

Graphite

Bolting

Grade 5 Steel

B8M, B7

1. Two diaphragms are required if metal diaphragm is to be used except only for Type 95L, NPS 1/4, 2 to 6 psi (0,14 to 0,41 bar) range which uses only one metal diaphragm.

8

Bulletin 71.1:95
Table 7. Compatibility
CORROSION INFORMATION

Monel®

Hastelloy® C

Hastelloy® C

416
Stainless Steel

Monel®

316
Stainless Steel

416
Stainless Steel

302 or 304
Stainless Steel

316
Stainless Steel

C
C
A
A
A

C
C
A
A
A

B
A
A
A
A

B
A
A
A
A

C
C
A
A
A

B
B
A
A
A

A
A
A
A
A

Hydrochloric Acid (Air free)
Hydrogen
Hydrogen Peroxide
Hydrogen Sulfide, Liquid
Magnesium Hydroxide

Aluminum Sulfate
Ammonia
Ammonium Chloride
Ammonium Nitrate
Ammonium Sulfate

C
A
C
A
C

C
A
C
C
C

A
A
B
A
B

A
A
B
A
A

C
A
C
C
C

B
A
B
C
A

A
A
A
A
A

Ammonium Sulfite
Beer
Benzene (Benzol)
Benzoic Acid
Boric Acid

C
B
A
C
C

C
B
A
C
C

A
A
A
A
A

A
A
A
A
A

B
B
A
A
B

C
A
A
A
A

Butane
Calcium Chloride (Alkaline)
Carbon Dioxide, Dry
Carbon Dioxide, Wet
Carbon Disulfide

A
B
A
C
A

A
B
A
C
A

A
C
A
A
A

A
B
A
A
A

A
C
A
A
B

Carbon Tetrachloride
Carbonic Acid
Chlorine Gas, Dry
Chlorine Gas, Wet
Chlorine, Liquid

B
C
A
C
C

B
C
A
C
C

B
B
B
C
C

B
B
B
C
C

Chromic Acid
Citric Acid
Coke Oven Gas
Copper Sulfate
Ether

C
I.L.
A
C
B

C
C
A
C
B

C
B
A
B
A

Ethyl Chloride
Ethylene
Ethylene Glycol
Formaldehyde
Formic Acid

C
A
A
B
I.L.

C
A
A
B
C

B
B
A
A
C

B
B
A
A
C

Freon, Wet
Freon, Dry
Gasoline, Refined
Glucose
Hydrochloric Acid (Aerated)

Cast Iron

302 or 304
Stainless Steel

Acetic Acid, Air Free
Acetic Acid Vapors
Acetone
Acetylene
Alcohols

Fluid

Carbon Steel

Cast Iron

Material

Carbon Steel

Material

C
A
I.L.
C
A

C
A
A
C
A

C
A
A
A
A

C
A
A
A
A

C
A
B
C
A

C
A
A
C
A

B
A
B
A
A

Methanol
Methyl Ethyl Ketone
Natural Gas
Nitric Acid
Petroleum Oils, Refined

A
A
A
C
A

A
A
A
C
A

A
A
A
A
A

A
A
A
B
A

A
A
A
C
A

A
A
A
C
A

A
A
A
B
A

A
A
A
A
A

Phosphoric Acid (Air Free)
Phosphoric Acid Vapors
Potassium Chloride
Potassium Hydroxide
Propane

C
C
B
B
A

C
C
B
B
A

A
B
A
A
A

A
B
A
A
A

C
C
C
B
A

B
C
B
A
A

A
I.L.
A
A
A

A
A
A
A
B

A
A
A
A
A

Silver Nitrate
Sodium Acetate
Sodium Carbonate
Sodium Chloride
Sodium Chromate

C
A
A
C
A

C
A
A
C
A

A
B
A
B
A

A
A
A
B
A

B
A
B
B
A

C
A
A
A
A

A
A
A
A
A

C
A
C
C
C

A
A
A
C
C

A
A
A
B
A

Sodium Hydroxide
Stearic Acid
Sulfur
Sulfur Dioxide, Dry
Sulfur Trioxide, Dry

A
A
A
A
A

A
C
A
A
A

A
A
A
A
A

A
A
A
A
A

B
B
A
B
B

A
B
A
A
A

A
A
A
A
A

B
A
A
B
A

C
B
A
A
A

A
B
B
C
A

A
A
A
A
A

Sulfuric Acid (Aerated)
Sulfuric Acid (Air Free)
Sulfurous Acid
Trichloroethylene
Water, Boiler Feed

C
C
C
B
B

C
C
C
B
C

C
C
B
B
A

C
C
B
A
A

C
C
C
B
B

C
B
C
A
A

A
A
A
A
A

A
A
A
A
B

A
A
A
A
B

B
A
A
A
C

A
A
A
A
A

A
A
I.L.
A
A

Water, Distilled
Water, Sea
Zinc Chloride
Zinc Sulfate

A
B
C
C

A
B
C
C

A
B
C
A

A
B
C
A

B
C
C
B

A
A
C
A

A
A
A
A

B
A
A
A
C

A
A
A
A
C

I.L.
I.L.
A
A
C

A
A
A
A
C

A
A
A
A
B

Fluid

----

---- ---- ---- ---- ---- ---- ----

A—Recommended
B—Minor to moderate effect. Proceed with caution.
C—Unsatisfactory
I.L.—Information lacking

- continued -

9

Bulletin 71.1:95
Table 7. Compatibility (continued)
FLUID INFORMATION
Fluid

Neoprene
(CR)

Nitrile
(NBR)

Fluorocarbon
(FKM)

EPDM

Fluid

Acetic Acid (30%)
Acetone
Alcohol, Ethyl
Alocohol, Methyl
Ammonia, Anhydrous
Ammonia, Gas, (Hot)
Benzene
Brine (Calcium Chloride)
Butadiene Gas
Butane, Gas
Butane, Liquid
Carbon Tetrachloride
Chlorine, Dry
Chlorine, Wet
Coke Oven Gas
Ethyl Acetate
Ethylene Glycol
Freon 11
Freon 12

c
b
a
a+
A
B
C
A
B
A
B
C
C
C
C
C
A
B
A+

B
C
A
A
C
C
C
A
C
A+
A
C
C
C
B
C
A
A
A

B
C
B
C
C
C
A
B
B
A
A
A
A
A
A+
C
A
A+
B

A
A
A
A
A
B
C
A
C
C
C
C
C
C
C
B
A
C
B

Freon 22
Freon 114
Gasoline
Hydrogen Gas
Hydrogen Sulfide (Dry)
Hydrogen Sulfide (Wet)
Jet Fuel (JP-4)
Natural Gas
Natural Gas + H2S (Sour Gas)
Nitric Acid (10%)
Nitric Acid (50 to 100%)
Nitrogen
Oil (Fuel)
Propane
Sea Water
Sulfur Dioxide
Sulfuric Acid (to 50%)
Sulfuric Acid (50 to 100%)
Water (Ambient)
Water at 200°F (93°C)

Neoprene Nitrile
(CR)
(NBR)
A+
A
B
A
A
B
C
A
A
B
C
A
B
A
B
A
B
C
A
C

C
A
A+
A
C
C
A
A+
B
C
C
A
A+
A
A
C
C
C
A
B

Fluorocarbon
(FKM)

EPDM

C
B
A
A
C
C
A
A
C
A
A
A
A
A
A
A
A
A
A
B

A
A
C
A
A
A
I.L.
C
C
C
C
A
C
C
A
A
B
B
A
A

A+ —Best possible selection
A—Recommended
B—Minor to moderate effect. Proceed with caution.
C—Unsatisfactory
I.L.—Information lacking

Universal NACE Compliance
Optional materials are available for applications
handling sour gases. These constructions comply
with the recommendations of NACE International sour
service standards.
The manufacturing processes and materials used by
Emerson assure that all products specified for sour
gas service comply with the chemical, physical, and
metallurgical requirements of NACE MR0175 ISO
and/or NACE MR0103. Customers have the
responsibility to specify correct materials.
Environmental limitations may apply and shall be
determined by the user.

Capacity Data
The capacity information on the following pages is
based on three droop factors, 10%, 20%, and 40%.
Droop is deviation from the setpoint of the regulator,
and is usually stated in percentage of setpoint value.
For example, refer to the air flow rate curve in
Figure 3. The regulator is set for 15 psig (1,0 bar)
at the outlet, with 100 psig (6,9 bar) at the inlet and a
300 SCFH (8,0 Nm3/h) flow rate. Capacity at 10%
droop is read at the intersection of a line projected

10

horizontally to the right from the 13.5 psig (0,93 bar)
outlet pressure point and the 100 psig (6,9 bar) inlet
curve. The 13.5 psig (0,93 bar) is derived by applying
the droop factor of 10% to the regulator setting of
15 psig (1,0 bar). The same method is employed for
20% droop, except the capacity value is read at the
12 psig (0,83 bar) outlet pressure point, 20% less than
the 15 psig (1,0 bar) setting.
For highest capacity and the most accurate control
within a particular type of the 95 Series regulators,
use the lowest range spring that can be adjusted
to the desired setpoint (see Table 5 for part numbers
of appropriate springs for each body size). See
Table 1 for sizing example for the Types 95HD and
95LD regulators.
If closer control is necessary, a regulator of larger
capacity or different design should be selected, so
that the necessary flow can be obtained with a smaller
droop factor.
Sometimes it may be necessary to interpolate
the capacity table data to determine capacity for
outlet settings not given. To maintain accuracy, it is
important when interpolating to stay within a spring
range if possible. The following is a procedure for
interpolating the data to calculate flow:
  1.  Determine which spring is to be used.
  2.  Find the two outlet settings (P2a and P2b) that
     bracket the actual outlet pressure P2.

Bulletin 71.1:95
  3.  For a given body size and inlet pressure, find the
     capacity Qa for P2a and Qb for P2b.
  4.  Use the following formula to determine the
     interpolated capacity (Q).
Qb - Qa
	

P2b - P2a

=

Qb - Q
P2b - P2

Example:
P1 = 100 psig (6,9 bar)
NPS 1/4 Type 95H with 15 to 30 psig
(1,0 to 2,1 bar) spring range
P2 = 20 psig (1,4 bar)
Determine air capacity, Q.
Solution:
Qa = 1100 SCFH (29,5 Nm3/h)
P2a = 15 psig (1,0 bar)
Qb = 1600 SCFH (42,9 Nm3/h)
P2b = 30 psig (2,1 bar)
1600 - 1100
30 - 15

=

=

1600 - Q
30 - 20

42,9 - Q
2,1 - 1,4

Q = 34,0 Nm3/h
			

Then, if capacity is desired in Nm3/h at 0°C and
1,10325 bar, multiply SCFH by 0.0268.
Capacities in Tables 8, 9, 10, and 11 are for regulators
using elastomer diaphragms. Depending on regulator
construction, a multiplier must be used to convert to
capacities for regulators using metal diaphragms.
To determine wide-open flow capacity for relief valve
sizing of air at a temperature of 60°F, use the equation
for critical pressure drops (absolute outlet pressure
equal to one-half or less than one-half the absolute
inlet pressure).
Q = P1(abs)Cg

Q = 1270 SCFH
42,9 - 29,5
2,1 - 1,0

following appropriate conversion factors: 1.29 for 0.6
specific gravity natural gas, 0.808 for propane, 0.707
for butane, or 1.018 for nitrogen. For gases of other
specific gravities, divide by the square root of the
appropriate specific gravity.

Note

The same interpolation procedure can
be used for different inlet pressures.
An alternative method for interpolating capacities is to
back calculate Cv’s as shown in Table 2.
Contact your local Sales Office if you should have
any questions about selecting the proper regulator.

Air Capacities
Regulating capacities at selected pressures and outlet
pressure flows are given in SCFH (60°F and 14.7 psia)
of air. To determine the equivalent capacities for
other gases, multiply the table capacities by the

where,
Q = Gas flow, SCFH (60°F and 14.7 psia)
P1(abs) = Absolute inlet pressure, psia (add 14.7 psi to
gauge inlet pressure to obtain absolute inlet pressure)
Cg = Wide-open gas sizing coefficient from Table 4
For pressure drops lower than critical (absolute outlet
pressure greater than one-half the absolute inlet
pressure), use the sizing nomographs in Fisher®
Catalog 10, or the Fisher Sizing Program.
To obtain capacities in Nm3/h at 0°C and 1,01325 bar,
multiply the capacity determined in SCFH by 0.0268.

Steam Capacities
Capacities in Tables 13, 14, 15, 16, and 17 are in
pounds/h of saturated steam. To obtain capacities
in kg/h, multiply the capacities given in the table by
0.4535. Capacities have been calculated for stainless
steel diaphragms only since steam service exceeds
the elastomer diaphragm temperature limits.

11

Bulletin 71.1:95
Water Capacities

To determine wide-open flow capacity for relief valve
sizing of steam, use the equation for critical pressure
drops (absolute outlet pressure equal to one-half or
less than one-half absolute inlet pressure).

All water capacities in Tables 18, 19, 20, 21, and 22
are in GPM. Capacities in Tables 18, 19, and 21
are for regulators using only elastomer diaphragms.
Depending on regulator size, a multiplier, given in
these tables, must be used to convert to capacities for
regulators using metal diaphragms.

Q = P1(abs)Cs
where,
Q = Steam flow, pounds/h

To determine flow capacity for liquid relief valve sizing,
refer to Fisher® Catalog 10, or the Fisher Sizing
Program using the Cv coefficients given in Table 4.
The Km values listed in Table 4 can be used to predict
choked flow on liquid service.

P1(abs) = Absolute inlet pressure, psia (add 14.7 psi to
gauge inlet pressure to obtain absolute inlet pressure)
Cs = Wide-open steam sizing coefficient from Table 4
For pressure drops lower than critical (absolute
outlet pressure greater than one-half absolute inlet
pressure), use the sizing nomographs in Fisher
Catalog 10, or the Fisher Sizing Program.

To convert capacities to m3/h, multiply GPM by 0.2271.

Table 8. Air SCFH (Nm3/h) Capacities(1) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with Elastomer Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet
Setting,
Psig/
Psi
(bar)

REGULATOR BODY SIZE, NPS (DN)
1/4

Inlet
Psig (bar)

1/2 (15)

Droop

Droop

1 (25)

Droop

Droop

10%

20%

10%

20%

10%

20%

10%

20%

2 (0,14)

10
20
30
50
75
100
150
200
250

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

150 (4,0)
200 (5,4)
250 (6,7)
250 (6,7)
250 (6,7)
250 (6,7)
280 (7,5)
280 (7,5)
330 (8,8)

280 (7,5)
300 (8,0)
380 (10,2)
380 (10,2)
380 (10,2)
380 (10,2)
400 (10,7)
400 (10,7)
430 (11,5)

300 (8,0)
350 (9,4)
350 (9,4)
350 (9,4)
350 (9,4)
350 (9,4)
380 (10,2)
400 (10,7)
450 (12,1)

400 (10,7)
500 (13,4)
530 (14,2)
530 (14,2)
530 (14,2)
530 (14,2)
550 (14,7)
550 (14,7)
600 (16,1)

680 (18,2)
850 (22,8)
1100 (29,5)
1500 (40,2)
2100 (56,3)
2500 (67,0)
2500 (67,0)
2500 (67,0)
2500 (67,0)

1200 (32,2)
1700 (45,6)
2200 (59,0)
2900 (77,7)
3800 (102)
4200 (113)
4600 (123)
4700 (126)
4700 (126)

800 (21,4)
1000 (26,8)
1300 (34,8)
1700 (45,6)
2500 (67,0)
3000 (80,4)
3000 (80,4)
3000 (80,4)
3000 (80,4)

1400 (37,5)
2000 (53,6)
2600 (69,7)
3400 (91,1)
4500 (121)
5000 (134)
5400 (145)
5600 (150)
5600 (150)

5 (0,35)

10
20
30
50
75
100
150
200
250

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

200 (5,4)
300 (8,0)
400 (10,7)
450 (12,1)
450 (12,1)
500 (13,4)
500 (13,4)
500 (13,4)
500 (13,4)

380 (10,2)
530 (14,2)
600 (16,1)
600 (16,1)
630 (16,9)
630 (16,9)
630 (16,9)
630 (16,9)
630 (16,9)

400 (10,7)
500 (13,4)
550 (14,7)
600 (16,1)
650 (17,4)
700 (18,8)
700 (18,8)
700 (18,8)
700 (18,8)

600 (16,1)
750 (20,1)
850 (22,8)
850 (22,8)
900 (24,1)
900 (24,1)
900 (24,1)
900 (24,1)
900 (24,1)

1100 (29,5)
1900 (50,9)
2300 (61,6)
3500 (93,8)
3800 (102)
4200 (113)
4200 (113)
4200 (113)
4200 (113)

1700 (45,6)
3400 (91,1)
4200 (113)
5500 (147)
6800 (182)
7200 (193)
7600 (204)
8300 (222)
8300 (222)

1300 (34,8)
2200 (59,0)
2800 (75,0)
4200 (113)
4500 (121)
5000 (134)
5000 (134)
5000 (134)
5000 (134)

2000 (53,6)
4000 (107)
5000 (134)
6500 (174)
8000 (214)
8500 (228)
9000 (241)
9800 (263)
10 000 (268)

2 to 6
(0,14 to 0,41)

  1. To obtain capacities for regulators using metal diaphragms, multiply the table values by 0.8.

- continued -

12

3/4 (20)

Bulletin 71.1:95
Table 8. Air SCFH (Nm3/h) Capacities(1) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with Elastomer 			
Diaphragm (continued)
PRESSURE
RECOMMENDED
OUTLET
Outlet
PRESSURE
Inlet
Setting,
RANGE,
Psig/Psi
PSIG/PSI (bar)
(bar)
Psig (bar)

1/4

1/2 (15)

Droop

3/4 (20)

Droop

1 (25)

Droop

10%

20%

10%

20%

10%

Droop
20%

10%

20%

10 (0,69)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

500 (13,4)
600 (16,1)
750 (20,1)
750 (20,1)
750 (20,1)
750 (20,1)
750 (20,1)
750 (20,1)

680 (18,2)
850 (22,8)
930 (24,9)
930 (24,9)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)

750 (20,1)
900 (24,1)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)

1100 (29,5)
1200 (32,2)
1400 (37,5)
1400 (37,5)
1400 (37,5)
1400 (37,5)
1400 (37,5)
1400 (37,5)

1700 (45,6)
2100 (56,3)
2800 (75,0)
4700 (126)
6400 (172)
7700 (206)
8500 (228)
8500 (228)

2500 (67,0) 2000 (53,6)
4200 (113)
2500 (67,0)
5300 (142)
3300 (88,4)
8500 (228)
5500 (147)
9300 (249)
7500 (201)
12 000 (322) 9000 (241)
13 000 (348) 10 000 (268)
13 000 (348) 10 000 (268)

3000 (80,4)
5000 (134)
6300 (169)
10 000 (268)
11 000 (295)
14 000 (375)
15 000 (402)
15 000 (402)

15 (1,0)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

450 (12,1)
700 (18,8)
900 (24,1)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)
1000 (26,8)

700 (18,8)
1000 (26,8)
1200 (32,2)
1200 (32,2)
1300 (34,8)
1300 (34,8)
1300 (34,8)
1300 (34,8)

800 (21,4)
1100 (29,5)
1300 (34,8)
1400 (37,5)
1400 (37,5)
1400 (37,5)
1400 (37,5)
1400 (37,5)

1200 (32,2)
1500 (40,2)
1600 (42,9)
1650 (44,2)
1800 (48,2)
1800 (48,2)
1800 (48,2)
1800 (48,2)

1900 (50,9)
3200 (85,8)
5100 (137)
6800 (182)
8500 (228)
11 000 (295)
11 000 (295)
11 000 (295)

2700 (72,4)
4500 (121)
7200 (193)
9300 (249)
13 000 (348)
15 000 (402)
15 000 (402)
15 000 (402)

2200 (59,0)
3800 (102)
6000 (161)
8000 (214)
10 000 (268)
13 000 (348)
13 000 (348)
13 000 (348)

3200 (85,8)
5300 (142)
8500 (228)
11 000 (295)
15 000 (402)
18 000 (482)
18 000 (482)
18 000 (482)

20 (1,4)

30
40
50
75
100
150
200
250

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

550 (14,7)
750 (20,1)
900 (24,1)
1100 (29,5)
1100 (29,5)
1100 (29,5)
1100 (29,5)
1100 (29,5)

850 (22,8)
1100 (29,5)
1300 (34,8)
1500 (40,2)
1500 (40,2)
1500 (40,2)
1500 (40,2)
1500 (40,2)

1100 (29,5)
1300 (34,8)
1400 (37,5)
1500 (40,2)
1600 (42,9)
1600 (42,9)
1600 (42,9)
1600 (42,9)

1500 (40,2)
1700 (45,6)
1800 (48,2)
2000 (53,6)
2100 (56,3)
2100 (56,3)
2100 (56,3)
2100 (56,3)

2500 (67,0)
3800 (102)
4600 (123)
6800 (182)
8000 (214)
10 000 (268)
13 000 (348)
13 000 (348)

3800 (102)
3000 (80,4)
5500 (147)
4500 (121)
6800 (182)
5500 (147)
9300 (249)
8000 (214)
13 000 (348) 9500 (255)
15 000 (402) 12 000 (322)
17 000 (456) 15 000 (402)
17 000 (456) 15 000 (402)

4500 (121)
6500 (174)
8000 (214)
11 000 (295)
15 000 (402)
18 000 (482)
20 000 (536)
20 000 (536)

25 (1,7)

40
50
75
100
150
200
250

(2,76)
(3,45)
(5,17)
(6,90)
(10,3)
(13,8)
(17,2)

900 (24,1)
1200 (32,2)
1400 (37,5)
1500 (40,2)
1600 (42,9)
1600 (42,9)
1600 (42,9)

1200 (32,2)
1600 (42,9)
2000 (53,6)
2500 (67,0)
2500 (67,0)
2500 (67,0)
2500 (67,0)

1600 (42,9)
1900 (50,9)
2000 (53,6)
2100 (56,3)
2200 (59,0)
2200 (59,0)
2200 (59,0)

2400 (64,3)
2500 (67,0)
2800 (75,0)
3300 (88,4)
3300 (88,4)
3300 (88,4)
3300 (88,4)

4200 (113)
5100 (137)
7200 (193)
8500 (228)
10 000 (268)
13 000 (348)
13 000 (348)

5500 (147)
6800 (182)
9300 (249)
13 000 (348)
17 000 (456)
21 000 (563)
21 000 (563)

5000 (134)
6000 (161)
8500 (228)
10 000 (268)
12 000 (322)
16 000 (429)
16 000 (429)

6500 (174)
8000 (214)
11 000 (295)
15 000 (402)
20 000 (536)
25 000 (670)
25 000 (670)

30 (2,1)

40
50
75
100
150
200
250

(2,76)
(3,45)
(5,17)
(6,90)
(10,3)
(13,8)
(17,2)

900 (24,1)
1200 (32,2)
1700 (45,6)
1800 (48,2)
1900 (50,9)
1900 (50,9)
1900 (50,9)

1200 (32,2)
1500 (40,2)
2300 (61,6)
2500 (67,0)
2500 (67,0)
2500 (67,0)
2500 (67,0)

1800 (48,2)
2000 (53,6)
2300 (61,6)
2400 (64,3)
2500 (67,0)
2500 (67,0)
2500 (67,0)

2400 (64,3)
2700 (72,4)
3200 (85,8)
3600 (96,5)
3600 (96,5)
3600 (96,5)
3600 (96,5)

3400 (91,1)
4200 (113)
7100 (190)
8500 (228)
11 000 (295)
14 000 (375)
14 000 (375)

5100 (137)
6400 (172)
9300 (249)
13 000 (348)
17 000 (456)
22 000 (590)
22 000 (590)

4000 (107)
5000 (134)
8400 (225)
10 000 (268)
13 000 (348)
17 000 (456)
17 000 (456)

6000 (161)
7500 (201)
11 000 (295)
15 000 (402)
20 000 (536)
26 000 (697)
26 000 (697)

5 to 15
(0,35 to 1,0)

13 to 30
(0,90 to 2,1)

REGULATOR BODY SIZE, NPS (DN)

1. To obtain capacities for regulators using metal diaphragms, multiply the table values by 0.8.

13

Bulletin 71.1:95
Table 9. Air SCFH (Nm3/h) Capacities(1) for NPS 1/4 through 1/2 (DN 15) Types 95H and 95HD Regulators with Elastomer Diaphragm
RECOMMENDED
OUTLET
PRESSURE,
PSIG/PSI (bar)

PRESSURE
Outlet
Setting,
Psig/Psi
(bar)

1/4

Inlet
Psig (bar)

10%

20%

Droop
40%

10%

20%

40%

15 (1,0)

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

680 (18,2)
750 (20,1)
840 (22,5)
1100 (29,5)
1100 (29,5)
1400 (37,5)
1900 (50,9)
1700 (45,6)
2000 (53,6)

1000
1000
1200
1500
1600
2100
2300
2400
2700

(26,8)
(26,8)
(32,2)
(40,2)
(42,9)
(56,3)
(61,6)
(64,3)
(72,4)

1300
1200
1300
2000
2500
2800
3000
3200
3300

(34,8)
(32,2)
(34,8)
(53,6)
(67,0)
(75,0)
(80,4)
(85,8)
(88,4)

900 (24,1)
900 (24,1)
900 (24,1)
1200 (32,2)
1400 (37,5)
1800 (48,2)
2200 (59,0)
2100 (56,3)
2700 (72,4)

1400
1500
1500
1800
2100
2400
2800
3100
3300

(37,5)
(40,2)
(40,2)
(48,2)
(56,3)
(64,3)
(75,0)
(83,1)
(88,4)

2200
2300
2200
2700
2900
3200
3600
3900
4300

(59,0)
(61,6)
(59,0)
(72,4)
(77,7)
(85,8)
(96,5)
(105)
(115)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

610 (16,3)
780 (20,9)
1500 (40,2)
1600 (42,9)
2200 (59,0)
2800 (75,0)
2800 (75,0)
3200 (85,8)

750 (20,1)
960 (25,7)
1700 (45,6)
2500 (67,0)
3500 (93,8)
4200 (113)
4100 (110)
4600 (123)

1100
1300
2500
3000
4400
4800
4900
5000

(29,5)
(34,8)
(67,0)
(80,4)
(118)
(129)
(131)
(134)

1500
1300
1800
2000
2400
3100
3500
4000

(40,2)
(34,8)
(48,2)
(53,6)
(64,3)
(83,1)
(93,8)
(107)

2300
2100
2800
3000
3800
4300
4600
4900

(61,6)
(56,3)
(75,0)
(80,4)
(102)
(115)
(123)
(131)

3500
3400
4200
4400
5300
5800
6300
6600

(93,8)
(91,1)
(113)
(118)
(142)
(155)
(169)
(177)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

1000
1200
1400
2100
2600
3600
4000

(26,8)
(32,2)
(37,5)
(56,3)
(69,7)
(96,5)
(107)

1300
1600
2300
3300
4500
5800
6200

(34,8)
(42,9)
(61,6)
(88,4)
(121)
(155)
(166)

1700
2400
3200
4600
6000
6500
7000

(45,6)
(64,3)
(85,8)
(123)
(161)
(174)
(188)

1200
1400
2100
2500
3100
3100
3500

(32,2)
(37,5)
(56,3)
(67,0)
(83,1)
(83,1)
(93,8)

2000
2300
2900
3700
4600
4500
5100

(53,6)
(61,6)
(77,7)
(99,2)
(123)
(121)
(137)

3800
3900
5000
5700
6500
6900
7300

(102)
(105)
(134)
(153)
(174)
(185)
(196)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

1600
2200
2500
3700
4900
5100

(42,9)
(59,0)
(67,0)
(99,2)
(131)
(137)

2400
3200
3900
5400
6500
7600

(64,3)
(85,8)
(105)
(145)
(174)
(204)

3000
3800
4600
6000
6700
9000

(80,4)
(102)
(123)
(161)
(180)
(241)

2300
2600
3200
3700
4000
4700

(61,6)
(69,7)
(85,8)
(99,2)
(107)
(126)

3700
4300
4700
5500
6100
7100

(99,2)
(115)
(126)
(147)
(163)
(190)

6200 (166)
7300 (196)
7700 (206)
8500 (228)
9500 (255)
10 000 (268)

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

2000
2000
2600
2800
3300
4000

(53,6)
(53,6)
(69,7)
(75,0)
(88,4)
(107)

2800
3500
4100
4600
5800
6900

(75,0)
(93,8)
(110)
(123)
(155)
(185)

3700
4500
5300
5900
7300
8600

(99,2)
(121)
(142)
(158)
(196)
(230)

3400
4000
4800
5200
4300
8000

(91,1)
(107)
(129)
(139)
(115)
(214)

5800 (155)
6800 (182)
7800 (209)
8200 (220)
8900 (239)
11 000 (295)

8800 (236)
11 000 (295)
12 000 (322)
13 000 (348)
14 000 (375)
15 000 (402)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

2000
2800
3400
3600
3800
4600

(53,6)
(75,0)
(91,1)
(96,5)
(102)
(123)

3000
4200
4300
5600
6200
7200

(80,4)
(113)
(115)
(150)
(166)
(193)

4200
5100
6000
6600
7300
8700

(113)
(137)
(161)
(177)
(196)
(233)

5200
5000
5500
6800
6900
7000

(139)
(134)
(147)
(182)
(185)
(188)

8200 (220)
9000 (241)
9300 (249)
11 000 (295)
13 000 (348)
13 000 (348)

11 000
13 000
14 000
16 000
17 000
19 000

(295)
(348)
(375)
(429)
(456)
(509)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

2500
3000
3300
4000
5400

(67,0)
(80,4)
(88,4)
(107)
(145)

3800
4300
5400
6300
7600

(102)
(115)
(145)
(169)
(204)

4900
5700
6600
7300
8400

(131)
(153)
(177)
(196)
(225)

5600
6500
7100
9000
8700

(150)
(174)
(190)
(241)
(233)

9500 (255)
11 000 (295)
12 000 (322)
14 000 (375)
15 000 (402)

12 000
14 000
16 000
18 000
20 000

(322)
(375)
(429)
(482)
(536)

25 to 75
(1,7 to 5,2)

  1. To obtain capacities for regulators using metal diaphragms, multiply the table values by 0.6.

- continued -

14

1/2 (15)

Droop

30
40
50
75
100
150
200
250
300

15 to 30
(1,0 to 2,1)

70 to 150
(4,8 to 10,3)

REGULATOR BODY SIZES, NPS (DN)

Bulletin 71.1:95
Table 9. Air SCFH (Nm3/h) Capacities(1) for NPS 3/4 through 1 (DN 20 through 25) Types 95H and 95HD Regulators with Elastomer 		
Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE,
PSIG/PSI (bar)

PRESSURE
Outlet
Setting,
Psig/Psi
(bar)

Inlet
Psig (bar)

10%

1 (25)

Droop

Droop
40%

10%

20%

40%

(83,1)
(102)
(115)
(147)
(161)
(188)
(214)
(233)
(257)

4900 (131)
6200 (166)
6800 (182)
8400 (225)
9000 (241)
10 000 (268)
11 000 (295)
11 000 (295)
12 000 (322)

2200 (59,0)
2600 (69,7)
3400 (91,1)
4800 (129)
5400 (145)
7000 (188)
8700 (233)
8500 (228)
10 000 (268)

3300 (88,4)
4200 (113)
5400 (145)
7000 (188)
8000 (214)
10 000 (268)
11 700 (314)
12 000 (322)
14 000 (375)

5400 (145)
6500 (174)
8200 (220)
11 000 (295)
12 000 (322)
15 000 (402)
16 000 (429)
17 000 (456)
18 000 (482)

2900 (77,7)
4000 (107)
5700 (153)
6300 (169)
7700 (206)
9200 (247)
9000 (241)
10 000 (268)

4500 (121)
6000 (161)
8500 (228)
9800 (263)
12 000 (322)
12 000 (322)
13 000 (348)
14 000 (375)

6200 (166)
7800 (209)
12 000 (322)
14 000 (375)
16 000 (429)
17 000 (456)
18 000 (482)
19 000 (509)

3200 (85,8)
4000 (107)
5400 (145)
7400 (198)
10 000 (268)
12 000 (322)
14 000 (375)
15 000 (402)

5200 (139)
6600 (177)
9300 (249)
11 000 (295)
15 000 (402)
18 000 (482)
20 000 (536)
21 000 (563)

6600 (177)
8300 (222)
12 000 (322)
16 000 (429)
22 000 (590)
26 000 (697)
27 000 (724)
28 000 (750)

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

4000 (107)
6000 (161)
7400 (198)
8300 (222)
11 000 (295)
12 000 (322)
12 000 (322)

6700 (180)
8600 (230)
11 000 (295)
13 000 (348)
17 000 (456)
18 000 (482)
18 000 (482)

9000 (241)
12 000 (322)
15 000 (402)
21 000 (563)
24 000 (643)
25 000 (670)
26 000 (697)

4400 (118)
6300 (169)
7000 (188)
16 000 (429)
15 000 (402)
17 000 (456)
19 000 (509)

7200 (193)
9600 (257)
13 000 (348)
18 000 (482)
24 000 (643)
26 000 (697)
27 000 (724)

9200 (247)
12 000 (322)
16 000 (429)
24 000 (643)
31 000 (831)
36 000 (965)
38 000 (1018)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

8000 (214)
11 000 (295)
12 000 (322)
14 000 (375)
16 000 (429)
16 000 (429)

12 000
16 000
18 000
21 000
24 000
25 000

(322)
(429)
(482)
(563)
(643)
(670)

15 000
19 000
22 000
24 000
26 000
28 000

8700 (233)
13 000 (348)
13 000 (348)
17 000 (456)
22 000 (590)
23 000 (616)

13 000
17 000
21 000
28 000
33 000
35 000

(348)
(456)
(563)
(750)
(884)
(938)

15 000 (402)
20 000 (536)
25 000 (670)
32 000 (858)
38 000 (1018)
45 000 (1206)

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

8500 (228)
12 000 (322)
13 000 (348)
15 000 (402)
15 000 (402)
19 000 (509)

14 000
18 000
21 000
23 000
25 000
29 000

(375)
(482)
(563)
(616)
(670)
(777)

18 000 (482)
22 000 (590)
26 000 (697)
30 000 (804)
37 000 (992)
41 000 (1099)

11 000
14 000
16 000
16 000
21 000
26 000

(295)
(375)
(429)
(429)
(563)
(697)

16 000 (429)
20 000 (536)
25 000 (670)
27 000 (724)
34 000 (911)
38 000 (1018)

19 000 (509)
23 000 (616)
28 000 (750)
32 000 (858)
39 000 (1045)
46 000 (1233)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

12 000
13 000
16 000
17 000
18 000
21 000

(322)
(348)
(429)
(456)
(482)
(563)

18 000
21 000
25 000
28 000
29 000
32 000

(482)
(563)
(670)
(750)
(777)
(858)

21 000 (563)
25 000 (670)
29 000 (777)
33 000 (884)
37 000 (992)
45 000 (1206)

13 000
15 000
17 000
19 000
20 000
26 000

(348)
(402)
(456)
(509)
(536)
(697)

20 000 (536)
23 000 (616)
28 000 (750)
30 000 (804)
34 000 (911)
41 000 (1099)

23 000 (616)
27 000 (724)
31 000 (831)
35 000 (938)
39 000 (1045)
46 000 (1233)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

14 000
16 000
20 000
20 000
23 000

(375)
(429)
(536)
(536)
(616)

20 000
24 000
29 000
30 000
37 000

(536)
(643)
(777)
(804)
(992)

29 000 (777)
29 000 (777)
33 000 (884)
37 000 (992)
45 000 (1206)

16 000
20 000
22 000
26 000
31 000

(429)
(536)
(590)
(697)
(831)

22 000
26 000
30 000
35 000
44 000

26 000 (697)
30 000 (804)
35 000 (938)
39 000 (1045)
46 000 (1233)

15 (1,0)

30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

2200
2700
2900
3800
4000
5000
6000
6800
7400

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

50 (3,4)

60
75
100
150
200
250
300

15 to 30
(1,0 to 2,1)

25 to 75
(1,7 to 5,2)

70 to 150
(4,8 to 10,3)

REGULATOR BODY SIZES, NPS (DN)
3/4 (20)

(59,0)
(72,4)
(77,7)
(102)
(107)
(134)
(161)
(182)
(198)

20%
3100
3800
4300
5500
6000
7000
8000
8700
9600

(402)
(509)
(590)
(643)
(697)
(750)

(590)
(697)
(804)
(938)
(1179)

  1. To obtain capacities for regulators using metal diaphragms, multiply the table values by 0.6.

15

Bulletin 71.1:95
Table 10. Air SCFH (Nm3/h) Capacities for NPS 1-1/2 through 2 (DN 40 through 50) Types 95H and 95HD Regulators with Either 		
Elastomer or Stainless Steel Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet
Setting,
Psig/Psi
(bar)

100 to 140
(6,9 to 9,7)

120 to 150
(8,3 to 10,3)

16

Inlet
Psig (bar)

2 (50)

Droop

Droop
20%

40%

5 (0,35)

10
20
30
50
75
100
150
200
250
300

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

950 (25,5)
2100 (56,3)
2500 (67,0)
3500 (93,8)
5000 (134)
6500 (174)
8500 (228)
12 000 (322)
15 000 (402)
18 000 (482)

1000 (26,8)
2500 (67,0)
3000 (80,4)
4000 (107)
6000 (161)
8000 (214)
11 000 (295)
14 000 (375)
17 000 (456)
20 000 (536)

1500 (40,2)
4300 (115)
5000 (134)
6000 (161)
8000 (214)
9500 (255)
12 000 (322)
17 000 (456)
19 000 (509)
21 000 (563)

1000 (26,8)
1800 (48,2)
3400 (91,1)
4000 (107)
5500 (147)
9000 (241)
15 000 (402)
16 000 (429)
18 000 (482)
19 000 (509)

1100 (29,5)
2000 (53,6)
4600 (123)
5500 (147)
7000 (188)
12 000 (322)
18 000 (482)
19 000 (509)
20 000 (536)
21 000 (563)

1500 (40,2)
2600 (69,7)
7300 (196)
9000 (241)
11 000 (295)
14 000 (375)
21 000 (563)
21 000 (563)
22 000 (590)
23 000 (616)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

3400 (91,1)
4500 (121)
6000 (161)
8000 (214)
12 000 (322)
20 000 (536)
25 000 (670)
29 000 (777)

6100 (163)
9000 (241)
12 000 (322)
15 000 (402)
21 000 (563)
31 000 (831)
35 000 (938)
38 000 (1018)

10 000 (268)
14 000 (375)
18 000 (482)
23 000 (616)
35 000 (938)
38 000 (1018)
41 000 (1099)
44 000 (1179)

4500 (121)
8000 (214)
15 000 (402)
24 000 (643)
44 000 (1179)
48 000 (1286)
51 000 (1367)
53 000 (1420)

6200 (166)
10 000 (268)
20 000 (536)
30 000 (804)
50 000 (1340)
55 000 (1474)
58 000 (1554)
59 000 (1581)

11 000 (295)
15 000 (402)
25 000 (670)
35 000 (938)
54 000 (1447)
58 000 (1554)
60 000 (1608)
61 000 (1635)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

6300 (169)
9000 (241)
10 000 (268)
13 000 (348)
21 000 (563)
31 000 (831)
39 000 (1045)

10 000 (268)
14 000 (375)
19 000 (509)
28 000 (750)
36 000 (965)
45 000 (1206)
51 000 (1367)

20 000 (536)
32 000 (858)
45 000 (1206)
61 000 (1635)
64 000 (1715)
66 000 (1769)
67 000 (1796)

6500 (174)
12 000 (322)
20 000 (536)
30 000 (804)
43 000 (1152)
55 000 (1474)
65 000 (1742)

11 000 (295)
20 000 (536)
40 000 (1072)
68 000 (1822)
75 000 (2010)
80 000 (2144)
84 000 (2251)

21 000 (563)
35 000 (938)
55 000 (1474)
75 000 (2010)
83 000 (2224)
86 000 (2305)
89 000 (2385)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

14 000 (375)
17 000 (456)
20 000 (536)
23 000 (616)
33 000 (884)
43 000 (1152)

22 000 (590)
30 000 (804)
39 000 (1045)
49 000 (1313)
57 000 (1528)
65 000 (1742)

42 000 (1126)
55 000 (1474)
71 000 (1903)
81 000 (2171)
85 000 (2278)
88 000 (2358)

15 000 (402)
20 000 (536)
26 000 (697)
50 000 (1340)
70 000 (1876)
90 000 (2412)

28 000 (750)
45 000 (1206)
69 000 (1849)
90 000 (2412)
110 000 (2948)
120 000 (3216)

50 000 (1340)
65 000 (1742)
76 000 (2037)
96 000 (2573)
110 000 (2948)
120 000 (3216)

100 (6,9)

125
150
175
225
250
300

(8,6)
(10,3)
(12,1)
(15,5)
(17,2)
(20,7)

11 000 (295)
22 000 (590)
25 000 (670)
28 000 (750)
33 000 (884)
40 000 (1072)

29 000 (777)
37 000 (992)
47 000 (1260)
62 000 (1662)
70 000 (1876)
88 000 (2358)

50 000 (1340)
64 000 (1715)
75 000 (2010)
95 000 (2546)
110 000 (2948)
120 000 (3216)

12 000 (322)
25 000 (670)
33 000 (884)
28 000 (750)
45 000 (1206)
55 000 (1474)

30 000 (804)
45 000 (1206)
52 000 (1394)
62 000 (1662)
70 000 (1876)
80 000 (2144)

54 000 (1447)
71 000 (1903)
90 000 (2412)
95 000 (2546)
130 000 (3484)
150 000 (4020)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

21 000 (563)
25 000 (670)
28 000 (750)
30 000 (804)
35 000 (938)
42 000 (1126)

40 000 (1072)
47 000 (1260)
54 000 (1447)
60 000 (1608)
70 000 (1876)
85 000 (2278)

64 000 (1715)
74 000 (1983)
90 000 (2412)
100 000 (2680)
110 000 (2948)
130 000 (3484)

22 000 (590)
32 000 (858)
39 000 (1045)
46 000 (1233)
56 000 (1501)
86 000 (2305)

40 000 (1072)
50 000 (1340)
70 000 (1876)
100 000 (2680)
120 000 (3216)
150 000 (4020)

65 000 (1742)
75 000 (2010)
90 000 (2412)
110 000 (2948)
130 000 (3484)
150 000 (4020)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

19 000 (509)
23 000 (616)
29 000 (777)
35 000 (938)
45 000 (1206)

32 000 (858)
44 000 (1179)
61 000 (1635)
70 000 (1876)
90 000 (2412)

54 000 (1447)
79 000 (2117)
100 000 (2680)
120 000 (3216)
150 000 (4020)

20 000 (536)
24 000 (643)
29 000 (777)
49 000 (1313)
86 000 (2305)

33 000 (884)
45 000 (1206)
61 000 (1635)
96 000 (2573)
140 000 (3752)

55 000 (1474)
80 000 (2144)
100 000 (2680)
120 000 (3216)
150 000 (4020)

5 to 80
(0,35 to 5,5)

60 to 120
(4,1 to 8,3)

regulator body size, nps (dn)
1-1/2 (40)

10%

20%

40%

10%

Bulletin 71.1:95
Table 11. Air SCFH (Nm3/h) Capacities for NPS 1/4 through 1/2 (DN 15) Type 95HP Regulators with Elastomer Diaphragms(1)

recommended
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)
1/4

Inlet

Droop

Droop
20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

300 (8,0)
350 (9,4)
380 (10,2)
530 (14,2)
800 (21,4)
1100 (29,5)
1200 (32,2)
1500 (40,2)
1700 (45,6)
1800 (48,2)
1900 (50,9)
2100 (56,3)

550 (14,7)
580 (15,5)
600 (16,1)
750 (20,1)
1200 (32,2)
1600 (42,9)
1700 (45,6)
2100 (56,3)
2300 (61,6)
2300 (61,6)
2400 (64,3)
2600 (69,7)

850 (22,8)
1000 (26,8)
1200 (32,2)
1300 (34,8)
2000 (53,6)
2400 (64,3)
2800 (75,0)
2900 (77,7)
2900 (77,7)
2900 (77,7)
3000 (80,4)
3200 (85,8)

600 (16,1)
620 (16,6)
700 (18,8)
900 (24,1)
1100 (29,5)
1700 (45,6)
2100 (56,3)
2400 (64,3)
2700 (72,4)
3300 (88,4)
3900 (105)
4500 (121)

850 (22,8)
900 (24,1)
1200 (32,2)
1500 (40,2)
1700 (45,6)
2300 (61,6)
2800 (75,0)
3000 (80,4)
3300 (88,4)
3800 (102)
4200 (113)
4800 (129)

1400 (37,5)
1500 (40,2)
1700 (45,6)
1800 (48,2)
2600 (69,7)
3100 (83,1)
3500 (93,8)
3800 (102)
4000 (107)
4300 (115)
4500 (121)
4900 (131)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

430 (11,5)
500 (13,4)
700 (18,8)
800 (21,4)
1400 (37,5)
2000 (53,6)
2200 (59,0)
2400 (64,3)
2800 (75,0)
2800 (75,0)
2800 (75,0)

750 (20,1)
900 (24,1)
1200 (32,2)
1700 (45,6)
2500 (67,0)
3000 (80,4)
3300 (88,4)
3500 (93,8)
3900 (105)
3900 (105)
3900 (105)

1100 (29,5)
1600 (42,9)
2100 (56,3)
2900 (77,7)
3800 (102)
4200 (113)
4300 (115)
4300 (115)
4300 (115)
4300 (115)
4300 (115)

900 (24,1)
1200 (32,2)
1300 (34,8)
1800 (48,2)
2100 (56,3)
2600 (69,7)
3000 (80,4)
3500 (93,8)
4100 (110)
4800 (129)
5300 (142)

1500 (40,2)
1600 (42,9)
2100 (56,3)
2600 (69,7)
3200 (85,8)
3800 (102)
4000 (107)
4700 (126)
5200 (139)
5900 (158)
6200 (166)

1900 (50,9)
2000 (53,6)
3600 (96,5)
4100 (110)
4800 (129)
5100 (137)
5600 (150)
5900 (158)
6300 (169)
6400 (172)
7100 (190)

50 (3,4)

60
75
100
150
200
250
300
400
500
600

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

700 (18,8)
730 (19,6)
1400 (37,5)
2200 (59,0)
3000 (80,4)
3500 (93,8)
3500 (93,8)
4000 (107)
4400 (118)
5000 (134)

1300 (34,8)
1500 (40,2)
2500 (67,0)
3600 (96,5)
4600 (123)
4700 (126)
5500 (147)
5700 (153)
5700 (153)
5700 (153)

1900 (50,9)
2500 (67,0)
3200 (85,8)
4700 (126)
5500 (147)
5800 (155)
6200 (166)
6200 (166)
6200 (166)
6200 (166)

1500 (40,2)
1700 (45,6)
2300 (61,6)
2800 (75,0)
3500 (93,8)
3800 (102)
4400 (118)
5200 (139)
5700 (153)
6000 (161)

2500 (67,0)
3100 (83,1)
3800 (102)
4800 (129)
5700 (153)
6000 (161)
6400 (172)
7000 (188)
7400 (198)
8200 (220)

4000 (107)
5000 (134)
6000 (161)
6800 (182)
7800 (209)
8100 (217)
8800 (236)
9300 (249)
9600 (257)
10 000 (268)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

2000 (53,6)
3100 (83,1)
3600 (96,5)
4500 (121)
5000 (134)
6100 (163)
7000 (188)
7800 (209)
7800 (209)

3200 (85,8)
4100 (110)
5100 (137)
5700 (153)
6700 (180)
8300 (222)
10 000 (268)
11 000 (295)
12 000 (322)

3900 (105)
4700 (126)
5500 (147)
6200 (166)
7800 (209)
9000 (241)
11 000 (295)
12 000 (322)
12 000 (322)

4100 (110)
5000 (134)
5700 (153)
5700 (153)
6500 (174)
7200 (193)
7800 (209)
8700 (233)
9000 (241)

6700 (180)
8000 (214)
8800 (236)
9300 (249)
10 000 (268)
11 000 (295)
12 000 (322)
13 000 (348)
14 000 (375)

9000 (241)
11 000 (295)
13 000 (348)
14 000 (375)
15 000 (402)
16 000 (429)
17 000 (456)
17 000 (456)
18 000 (482)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

2100 (56,3)
2200 (59,0)
2800 (75,0)
3100 (83,1)
3300 (88,4)
3700 (99,2)
5200 (139)
6300 (169)
7000 (188)

2800 (75,0)
3200 (85,8)
4000 (107)
4300 (115)
4900 (131)
5700 (153)
7500 (201)
9500 (255)
11 000 (295)

4100 (110)
4700 (126)
5600 (150)
6100 (163)
6600 (177)
7900 (212)
11 000 (295)
13 000 (348)
16 000 (429)

3000 (80,4)
3500 (93,8)
4000 (107)
4000 (107)
4400 (118)
5200 (139)
6500 (174)
7900 (212)
9300 (249)

5200 (139)
6000 (161)
6500 (174)
6700 (180)
7000 (188)
8200 (220)
10 000 (268)
12 000 (322)
14 000 (375)

8600 (230)
9500 (255)
11 000 (295)
11 000 (295)
12 000 (322)
14 000 (375)
15 000 (402)
18 000 (482)
21 000 (563)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

3200 (85,8)
3800 (102)
4200 (113)
4800 (129)
5700 (153)
6300 (169)
6700 (180)
7200 (193)

4500 (121)
5400 (145)
6600 (177)
7500 (201)
8500 (228)
9700 (260)
11 000 (295)
13 000 (348)

6400 (172)
7200 (193)
8700 (233)
10 000 (268)
12 000 (322)
13 000 (348)
15 000 (402)
18 000 (482)

5500 (147)
5600 (150)
6500 (174)
7500 (201)
8800 (236)
9600 (257)
11 000 (295)
11 000 (295)

9300 (249)
10 000 (268)
11 000 (295)
13 000 (348)
14 000 (375)
15 000 (402)
17 000 (456)
19 000 (509)

15 000 (402)
17 000 (456)
19 000 (509)
20 000 (536)
22 000 (590)
24 000 (643)
26 000 (697)
30 000 (804)

15 to 100
(1,0 to 6,9)

80 to 300
(5,5 to 20,7)

Psig (bar)

1/2 (15)

10%

20%

40%

10%

  1. To obtain capacities for Type 95HT (metal diaphragm), multiply the table values by 0.6.

- continued -

17

Bulletin 71.1:95
Table 11. Air SCFH (Nm3/h) Capacities for NPS 1/4 through 1/2 (DN 15) Type 95HP Regulators with Elastomer
Diaphragms(1) (continued)
recommended
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

	

1/2 (15)

Droop

Droop
20%

40%

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

4100 (110)
4200 (113)
5000 (134)
5200 (139)
5800 (155)
6300 (169)
6700 (180)
7200 (193)

5800 (155)
6600 (177)
7500 (201)
8600 (230)
9700 (260)
11 000 (295)
12 000 (322)
13 000 (348)

7700 (206)
8400 (225)
10 000 (268)
12 000 (322)
13 000 (348)
15 000 (402)
16 000 (429)
18 000 (482)

7600 (204)
7200 (193)
8000 (214)
9200 (247)
9700 (260)
10 000 (268)
11 000 (295)
12 000 (322)

12 000 (322)
13 000 (348)
14 000 (375)
16 000 (429)
17 000 (456)
18 000 (482)
20 000 (536)
20 000 (536)

19 000 (509)
20 000 (536)
23 000 (616)
26 000 (697)
28 000 (750)
31 000 (831)
34 000 (911)
36 000 (965)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

5200 (139)
5600 (150)
6000 (161)
6400 (172)
6800 (182)
7200 (193)

7700 (206)
8800 (236)
9900 (265)
11 000 (295)
12 000 (322)
13 000 (348)

10 000 (268)
12 000 (322)
13 000 (348)
15 000 (402)
17 000 (456)
18 000 (482)

9000 (241)
9500 (255)
10 000 (268)
11 000 (295)
11 000 (295)
12 000 (322)

16 000 (429)
17 000 (456)
18 000 (482)
19 000 (509)
20 000 (536)
21 000 (563)

24 000 (643)
28 000 (750)
31 000 (831)
34 000 (911)
37 000 (992)
41 000 (1099)

400 (27,6)

500 (34,5)
600 (41,4)

7000 (188)
7200 (193)

13 000 (348)
14 000 (375)

17 000 (456)
19 000 (509)

11 000 (295)
12 000 (322)

20 000 (536)
21 000 (563)

38 000 (1018)
42 000 (1126)

80 to 300
(5,5 to 20,7)

80 to 400
(5,5 to 27,6)
Type 95HP Only

	

regulator body size, NPS (dn)
1/4

Inlet
Psig (bar)

	

10%

20%

40%

10%

  1. To obtain capacities for Type 95HT (metal diaphragm), multiply the table values by 0.6.

Table 11. Air SCFH (Nm3/h) Capacities for NPS 3/4 through 1 (DN 20 through 25) Type 95HP Regulators with Elastomer
Diaphragms(1) (continued)
recommended
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)

Inlet

3/4 (20)

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1300 (34,8)
1300 (34,8)
1500 (40,2)
2400 (64,3)
3100 (83,1)
4000 (107)
4500 (121)
5500 (147)
6500 (174)
8200 (220)
10 000 (268)
12 000 (322)

1800 (48,2)
2100 (56,3)
2400 (64,3)
3200 (85,8)
4300 (115)
5000 (134)
6200 (166)
7000 (188)
8000 (214)
9500 (255)
11 000 (295)
13 000 (348)

2900 (77,7)
2900 (77,7)
3400 (91,1)
4600 (123)
6000 (161)
7600 (204)
8300 (222)
9200 (247)
10 000 (268)
12 000 (322)
13 000 (348)
15 000 (402)

1200 (32,2)
1300 (34,8)
1900 (50,9)
2600 (69,7)
3000 (80,4)
4500 (121)
5500 (147)
6500 (174)
7500 (201)
9000 (241)
11 000 (295)
12 000 (322)

1600 (42,9)
2000 (53,6)
2700 (72,4)
3800 (102)
4700 (126)
6400 (172)
7500 (201)
9000 (241)
10 000 (268)
12 000 (322)
14 000 (375)
16 000 (429)

2500 (67,0)
3000 (80,4)
3800 (102)
5400 (145)
7000 (188)
9600 (257)
13 000 (348)
13 000 (348)
14 000 (375)
17 000 (456)
20 000 (536)
22 000 (590)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1700 (45,6)
2200 (59,0)
3000 (80,4)
4100 (110)
5000 (134)
6000 (161)
7400 (198)
8500 (228)
11 000 (295)
13 000 (348)
15 000 (402)

2800 (75,0)
3500 (93,8)
4500 (121)
6100 (163)
7200 (193)
9000 (241)
10 000 (268)
12 000 (322)
14 000 (375)
15 000 (402)
17 000 (456)

4600 (123)
5700 (153)
7200 (193)
9500 (255)
12 000 (322)
14 000 (375)
14 000 (375)
16 000 (429)
18 000 (482)
21 000 (563)
22 000 (590)

1900 (50,9)
2300 (61,6)
3300 (88,4)
4000 (107)
6400 (172)
6500 (174)
8000 (214)
9000 (241)
12 000 (322)
15 000 (402)
17 000 (456)

2900 (77,7)
3300 (88,4)
4800 (129)
6000 (161)
9500 (255)
11 000 (295)
14 000 (375)
15 000 (402)
18 000 (482)
22 000 (590)
24 000 (643)

4700 (126)
5800 (155)
8400 (225)
11 000 (295)
15 000 (402)
18 000 (482)
20 000 (536)
22 000 (590)
25 000 (670)
30 000 (804)
32 000 (858)

15 to 100
(1,0 to 6,9)

Psig (bar)

  1. To obtain capacities for Type 95HT (metal diaphragm), multiply the table values by 0.6.

- continued -

18

	

Bulletin 71.1:95
Table 11. Air SCFH (Nm3/h) Capacities for NPS 3/4 through 1 (DN 20 through 25) Type 95HP Regulators with Elastomer
Diaphragms(1) (continued)
recommended
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)
3/4 (20)

Inlet

Droop

Droop
20%

40%

50 (3,4)

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

2800 (75,0)
3800 (102)
5000 (134)
7500 (201)
8000 (214)
10 000 (268)
11 000 (295)
14 000 (375)
16 000 (429)
19 000 (509)

5000 (134)
6200 (166)
8500 (228)
12 000 (322)
13 000 (348)
15 000 (402)
16 000 (429)
19 000 (509)
20 000 (536)
24 000 (643)

8000 (214)
10 000 (268)
14 000 (375)
18 000 (482)
21 000 (563)
22 000 (590)
24 000 (643)
26 000 (697)
27 000 (724)
31 000 (831)

3000 (80,4)
4000 (107)
5400 (145)
9000 (241)
10 000 (268)
13 000 (348)
15 000 (402)
16 000 (429)
18 000 (482)
20 000 (536)

5000 (134)
6400 (172)
9300 (249)
14 000 (375)
16 000 (429)
21 000 (563)
23 000 (616)
26 000 (697)
30 000 (804)
33 000 (884)

8500 (228)
11 000 (295)
15 000 (402)
22 000 (590)
26 000 (697)
32 000 (858)
34 000 (911)
38 000 (1018)
42 000 (1126)
47 000 (1260)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

8500 (228)
11 000 (295)
12 000 (322)
13 000 (348)
16 000 (429)
18 000 (482)
22 000 (590)
25 000 (670)
29 000 (777)

14 000 (375)
18 000 (482)
20 000 (536)
22 000 (590)
26 000 (697)
29 000 (777)
32 000 (858)
36 000 (965)
39 000 (1045)

18 000 (482)
22 000 (590)
26 000 (697)
30 000 (804)
37 000 (992)
42 000 (1126)
46 000 (1233)
53 000 (1420)
55 000 (1474)

8800 (236)
11 000 (295)
14 000 (375)
16 000 (429)
20 000 (536)
21 000 (563)
28 000 (750)
36 000 (965)
43 000 (1152)

15 000 (402)
19 000 (509)
23 000 (616)
26 000 (697)
33 000 (884)
35 000 (938)
45 000 (1206)
56 000 (1501)
66 000 (1769)

18 000 (482)
23 000 (616)
26 000 (697)
31 000 (831)
39 000 (1045)
46 000 (1233)
62 000 (1662)
78 000 (2090)
95 000 (2546)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

7000 (188)
7000 (188)
9500 (255)
10 000 (268)
12 000 (322)
13 000 (348)
16 000 (429)
18 000 (482)
20 000 (536)

11 000 (295)
13 000 (348)
15 000 (402)
16 000 (429)
19 000 (509)
20 000 (536)
25 000 (670)
30 000 (804)
34 000 (911)

19 000 (509)
21 000 (563)
24 000 (643)
27 000 (724)
29 000 (777)
33 000 (884)
39 000 (1045)
46 000 (1233)
52 000 (1394)

7800 (209)
7500 (201)
8500 (228)
9500 (255)
10 000 (268)
12 000 (322)
17 000 (456)
21 000 (563)
26 000 (697)

13 000 (348)
13 000 (348)
15 000 (402)
16 000 (429)
18 000 (482)
23 000 (616)
29 000 (777)
36 000 (965)
43 600 (1168)

20 000 (536)
23 000 (616)
25 000 (670)
29 000 (777)
32 000 (858)
38 000 (1018)
48 000 (1286)
59 000 (1581)
69 000 (1849)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

11 000 (295)
14 000 (375)
17 000 (456)
21 000 (563)
21 000 (563)
25 000 (670)
27 000 (724)
30 000 (804)

20 000 (536)
24 000 (643)
28 000 (750)
34 000 (911)
35 000 (938)
41 000 (1099)
45 000 (1206)
50 000 (1340)

30 000 (804)
35 000 (938)
42 000 (1126)
49 000 (1313)
55 000 (1474)
62 000 (1662)
68 000 (1822)
75 000 (2010)

12 000 (322)
14 000 (375)
18 000 (482)
20 000 (536)
22 000 (590)
25 000 (670)
27 000 (724)
30 000 (804)

21 000 (563)
23 000 (616)
31 000 (831)
37 000 (992)
40 000 (1072)
46 000 (1233)
51 000 (1367)
59 000 (1581)

31 000 (831)
35 000 (938)
44 000 (1179)
55 000 (1474)
59 000 (1581)
69 000 (1849)
76 000 (2037)
90 000 (2412)

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

15 000 (402)
18 000 (482)
22 000 (590)
22 000 (590)
25 000 (670)
26 000 (697)
27 000 (724)
31 000 (831)

25 000 (670)
30 000 (804)
36 000 (965)
37 000 (992)
42 000 (1126)
44 000 (1179)
45 000 (1206)
52 000 (1394)

36 000 (965)
41 000 (1099)
50 000 (1340)
55 000 (1474)
61 000 (1635)
65 000 (1742)
74 000 (1983)
80 000 (2144)

16 000 (429)
17 000 (456)
24 000 (643)
24 000 (643)
28 000 (750)
31 000 (831)
34 000 (911)
38 000 (1018)

27 000 (724)
31 000 (831)
39 000 (1045)
43 000 (1152)
50 000 (1340)
56 000 (1501)
62 000 (1662)
68 000 (1822)

38 000 (1018)
42 000 (1126)
51 000 (1367)
59 000 (1581)
68 000 (1822)
76 000 (2037)
85 000 (2278)
93 000 (2492)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

21 000 (563)
24 000 (643)
27 000 (724)
30 000 (804)
33 000 (884)
36 000 (965)

37 000 (992)
41 000 (1099)
46 000 (1233)
50 000 (1340)
55 000 (1474)
59 000 (1581)

48 000 (1286)
57 000 (1528)
67 000 (1796)
76 000 (2037)
86 000 (2305)
95 000 (2546)

22 000 (590)
26 000 (697)
31 000 (831)
35 000 (938)
40 000 (1072)
44 000 (1179)

38 000 (1018)
47 000 (1260)
55 000 (1474)
64 000 (1715)
72 000 (1930)
81 000 (2171)

49 000 (1313)
58 000 (1554)
69 000 (1849)
79 000 (2117)
90 000 (2412)
100 000 (2680)

400 (27,6)

500 (34,5)
600 (41,4)

35 000 (938)
40 000 (1072)

60 000 (1608)
65 000 (1742)

90 000 (2412)
100 000 (2680)

42 000 (1126)
50 000 (1340)

80 000 (2144)
85 000 (2278)

95 000 (2546)
110 000 (2948)

80 to 300
(5,5 to 20,7)

Psig (bar)

1 (25)

60
75
100
150
200
250
300
400
500
600

15 to 100
(1,0 to 6,9)

80 to 400
(5,5 to 27,6)
Type 95HP Only

	

10%

20%

40%

10%

  1. To obtain capacities for Type 95HT (metal diaphragm), multiply the table values by 0.6.

19

Bulletin 71.1:95
Table 12. Air SCFH (Nm3/h) Capacities for NPS 1-1/2 through 2 (DN 40 through 50) Types 95HT (Metal Diaphragm) and 95HP 		
(Elastomer Diaphragm) Regulators
pressure
RECOMMENDED
OUTLET
Outlet
PRESSURE
Inlet
Setting,
RANGE,
Psig
(bar)
PSIG (bar)
Psig (bar)

Regulator Body Size, NPS (dn)
1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1800 (48,2)
3800 (102)
4500 (121)
5800 (155)
7000 (188)
10 000 (268)
14 000 (375)
18 000 (482)
21 000 (563)
25 000 (670)
28 000 (750)
30 000 (804)

2800 (75,0)
5000 (134)
6000 (161)
8000 (214)
9500 (255)
13 000 (348)
18 000 (482)
22 000 (590)
25 000 (670)
28 000 (750)
30 000 (804)
32 000 (858)

3800 (102)
7000 (188)
8000 (214)
11 000 (295)
14 000 (375)
19 000 (509)
24 000 (643)
27 000 (724)
29 000 (777)
31 000 (831)
33 000 (884)
35 000 (938)

2000 (53,6)
4000 (107)
5000 (134)
8000 (214)
10 000 (268)
20 000 (536)
31 000 (831)
31 000 (831)
31 000 (831)
32 000 (858)(1)
33 000 (884)(1)
34 000 (911)(1)

3000 (80,4)
6000 (161)
8000 (214)
12 000 (322)
16 000 (429)
25 000 (670)
33 000 (884)
33 000 (884)
33 000 (884)
34 000 (911)(1)
35 000 (938)(1)
36 000 (965)(1)

4000 (107)
8000 (214)
12 000 (322)
20 000 (536)
26 000 (697)
32 000 (858)
36 000 (965)
37 000 (992)
37 000 (992)
38 000 (1018)(1)
39 000 (1045)(1)
39 000 (1045)(1)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

4500 (121)
5500 (147)
6500 (174)
8000 (214)
12 000 (322)
17 000 (456)
23 000 (616)
28 000 (750)
34 000 (911)
37 000 (992)
39 000 (1045)

6300 (169)
7500 (201)
9500 (255)
12 000 (322)
19 000 (509)
28 000 (750)
35 000 (938)
39 000 (1045)
41 000 (1099)
42 000 (1126)
43 000 (1152)

11 000 (295)
13 000 (348)
17 000 (456)
23 000 (616)
30 000 (804)
36 000 (965)
40 000 (1072)
44 000 (1179)
48 000 (1286)
50 000 (1340)
52 000 (1394)

4500 (121)
5500 (147)
7500 (201)
12 000 (322)
35 000 (938)
49 000 (1313)
53 000 (1420)
55 000 (1474)
56 000 (1501)(1)
57 000 (1528)(1)
58 000 (1554)(1)

7000 (188)
9000 (241)
14 000 (375)
23 000 (616)
43 000 (1152)
52 000 (1394)
56 000 (1501)
58 000 (1554)
60 000 (1608)(1)
61 000 (1635)(1)
62 000 (1662)(1)

13 000 (348)
15 000 (402)
25 000 (670)
39 000 (1045)
49 000 (1313)
56 000 (1501)
60 000 (1608)
61 000 (1635)
63 000 (1688)(1)
64 000 (1715)(1)
65 000 (1742)(1)

50 (3,4)

60
75
100
150
200
250
300
400
500
600

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

6500 (174)
8500 (228)
12 000 (322)
18 000 (482)
24 000 (643)
30 000 (804)
36 000 (965)
46 000 (1233)
54 000 (1447)
60 000 (1608)

11 000 (295)
13 000 (348)
18 000 (482)
28 000 (750)
37 000 (992)
45 000 (1206)
50 000 (1340)
57 000 (1528)
62 000 (1662)
67 000 (1796)

21 000 (563)
27 000 (724)
35 000 (938)
48 000 (1286)
58 000 (1554)
62 000 (1662)
65 000 (1742)
66 000 (1769)
69 000 (1849)
72 000 (1930)

8000 (214)
17 000 (456)
30 000 (804)
50 000 (1340)
63 000 (1688)
72 000 (1930)
78 000 (2090)
84 000 (2251)(1)
88 000 (2358)(1)
92 000 (2466)(1)

13 000 (348)
22 000 (590)
36 000 (965)
56 000 (1501)
73 000 (1956)
80 000 (2144)
85 000 (2278)
89 000 (2385)(1)
92 000 (2466)(1)
95 000 (2546)(1)

27 000 (724)
40 000 (1072)
50 000 (1340)
70 000 (1876)
81 000 (2171)
88 000 (2358)
91 000 (2439)
94 000 (2519)(1)
97 000 (2600)(1)
100 000 (2680)(1)

100 (6,9)

125
150
200
250
300
400
500
600

(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

20 000 (536)
23 000 (616)
30 000 (804)
38 000 (1018)
48 000 (1286)
65 000 (1742)
75 000 (2010)
82 000 (2198)

32 000 (858)
38 000 (1018)
55 000 (1474)
65 000 (1742)
75 000 (2010)
85 000 (2278)
95 000 (2546)
103 000 (2760)

60 000 (1608)
72 000 (1930)
92 000 (2466)
96 000 (2573)
98 000 (2626)
100 000 (2680)
102 000 (2734)
105 000 (2814)

40 000 (1072)
50 000 (1340)
82 000 (2198)
98 000 (2626)
107 000 (2868)
117 000 (3136)(1)
127 000 (3404)(1)
133 000 (3564)(1)

45 000 (1206)
63 000 (1688)
97 000 (2600)
110 000 (2948)
117 000 (3136)
125 000 (3350)(1)
130 000 (3484)(1)
135 000 (3618)(1)

70 000 (1876)
86 000 (2305)
107 000 (2868)
121 000 (3243)
127 000 (3404)
133 000 (3564)(1)
135 000 (3618)(1)
138 000 (3698)(1)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

16 000 (429)
18 000 (482)
20 000 (536)
22 000 (590)
30 000 (804)
36 000 (965)
42 000 (1126)
48 000 (1286)
52 000 (1394)

26 000 (697)
30 000 (804)
33 000 (884)
38 000 (1018)
42 000 (1126)
52 000 (1394)
72 000 (1930)
85 000 (2278)
95 000 (2546)

49 000 (1313)
55 000 (1474)
63 000 (1688)
72 000 (1930)
80 000 (2144)
95 000 (2546)
120 000 (3216)
130 000 (3484)
140 000 (3752)

17 000 (456)
18 000 (482)
20 000 (536)
22 000 (590)
32 000 (858)
50 000 (1340)
96 000 (2573)
110 000 (2948)
125 000 (3350)

26 000 (697)
30 000 (804)
34 000 (911)
40 000 (1072)
50 000 (1340)
75 000 (2010)
136 000 (3645)
160 000 (4288)
170 000 (4556)

59 000 (1581)
70 000 (1876)
80 000 (2144)
96 000 (2573)
111 000 (2975)
135 000 (3618)
166 000 (4449)
185 000 (4958)
195 000 (5226)

200 (13,8)

225
250
300
350

(15,5)
(17,2)
(20,7)
(24,1)

27 000 (724)
29 000 (777)
40 000 (1072)
46 000 (1233)

51 000 (1367)
54 000 (1447)
72 000 (1930)
82 000 (2198)

92 000 (2466)
99 000 (2653)
128 000 (3430)
140 000 (3752)

28 000 (750)
30 000 (804)
42 000 (1126)
54 000 (1447)

52 000 (1394)
55 000 (1474)
80 000 (2144)
97 000 (2600)

106 000 (2841)
100 000 (2680)
142 000 (3806)
160 000 (4288)

15 to 100
(1,0 to 6,9)

60 to 260
(4,1 to 17,9)

  1. Capacities limited due to boost.

- continued -

20

Bulletin 71.1:95
Table 12. Air SCFH (Nm3/h) Capacities for NPS 1-1/2 through 2 (DN 40 through 50) Types 95HT (Metal Diaphragm) and 95HP 		
(Elastomer Diaphragm) Regulators (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

Inlet
Psig (bar)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

200 (13,8)

400
450
500
600

(27,6)
(31,0)
(34,5)
(41,4)

54 000 (1447)
62 000 (1662)
72 000 (1930)
90 000 (2412)

100 000 (2680)
110 000 (2948)
120 000 (3216)
130 000 (3484)

165 000 (4422)
180 000 (4824)
190 000 (5092)
200 000 (5360)

76 000 (2037)
80 000 (2144)
100 000 (2680)
125 000 (3350)

166 000 (4449)
160 000 (4288)
170 000 (4556)
180 000 (4824)

196 000 (5253)
200 000 (5360)
215 000 (5762)
230 000 (6164)

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

30 000 (804)
45 000 (1206)
56 000 (1501)
64 000 (1715)
71 000 (1903)
74 000 (1983)
81 000 (2171)
84 000 (2251)

60 000 (1608)
80 000 (2144)
102 000 (2734)
110 000 (2948)
120 000 (3216)
129 000 (3457)
138 000 (3698)
145 000 (3886)

102 000 (2734)
130 000 (3484)
154 000 (4127)
169 000 (4529)
180 000 (4824)
190 000 (5092)
198 000 (5306)
205 000 (5494)

30 000 (804)
40 000 (1072)
57 000 (1528)
74 000 (1983)
84 000 (2251)
93 000 (2492)
102 000 (2734)
110 000 (2948)

60 000 (1608)
80 000 (2144)
108 000 (2894)
140 000 (3752)
155 000 (4154)
168 000 (4502)
175 000 (4690)
182 000 (4878)

103 000 (2760)
125 000 (3350)
168 000 (4502)
194 000 (5199)
215 000 (5762)
225 000 (6030)
235 000 (6298)
245 000 (6566)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

53 000 (1420)
64 000 (1715)
80 000 (2144)
95 000 (2546)
104 000 (2787)
112 000 (3002)

94 000 (2519)
115 000 (3082)
130 000 (3484)
145 000 (3886)
158 000 (4234)
168 000 (4502)

150 000 (4020)
180 000 (4824)
200 000 (5360)
220 000 (5896)
235 000 (6298)
250 000 (6700)

54 000 (1447)
70 000 (1876)
90 000 (2412)
110 000 (2948)
128 000 (3430)
136 000 (3645)

97 000 (2600)
128 000 (3430)
145 000 (3886)
163 000 (4368)
181 000 (4851)
199 000 (5333)

151 000 (4047)
192 000 (5146)
220 000 (5896)
240 000 (6432)
260 000 (6968)
280 000 (7504)

60 to 260
(4,1 to 17,9)

60 to 300
(4,1 to 20,7)
Type 95HP Only

Regulator Body Size, NPS (dn)
1-1/2 (40)

  1. Capacities limited due to boost.

Table 13. Steam Capacities(1) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with Stainless Steel Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet
Setting,
Psig/Psi
(bar)

REGULATOR BODY SIZE, NPS (dn)

Inlet

1/2 (15)

3/4 (20)

1 (25)

Droop

Droop

Droop

Droop

10%

20%

10%

20%

10%

20%

10%

20%

2 (0,14)

10
20
30
50
75
100
150
200
250

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

6.0 (2,7)
8.0 (3,6)
10 (4,5)
10 (4,5)
10 (4,5)
10 (4,5)
11 (5,0)
11 (5,0)
13 (5,9)

11 (5,0)
12 (5,4)
15 (6,8)
15 (6,8)
15 (6,8)
15 (6,8)
16 (7,3)
16 (7,3)
17 (7,7)

12 (5,4)
14 (6,4)
14 (6,4)
14 (6,4)
14 (6,4)
14 (6,4)
15 (6,8)
16 (7,3)
18 (8,2)

16 (7,3)
20 (9,1)
21 (9,5)
21 (9,5)
21 (9,5)
21 (9,5)
22 (10,0)
22 (10,0)
24 (10,9)

27 (12,2)
34 (15,4)
44 (20,0)
60 (27,2)
84 (38,1)
100 (45,4)
100 (45,4)
100 (45,4)
100 (45,4)

48 (21,8)
68 (30,8)
88 (39,9)
120 (54,4)
150 (68,0)
170 (77,1)
180 (81,6)
190 (86,2)
190 (86,2)

32 (14,5)
40 (18,1)
52 (23,6)
68 (30,8)
100 (45,4)
120 (54,4)
120 (54,4)
120 (54,4)
120 (54,4)

56 (25,4)
80 (36,3)
100 (45,4)
140 (63,5)
180 (81,6)
200 (90,7)
220 (99,8)
220 (99,8)
220 (99,8)

5 (0,35)

10
20
30
50
75
100
150
200
250

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

8.0 (3,6)
12 (5,4)
16 (7,3)
18 (8,2)
18 (8,2)
20 (9,1)
20 (9,1)
20 (9,1)
20 (9,1)

15 (6,8)
21 (9,5)
24 (10,9)
24 (10,9)
25 (11,3)
25 (11,3)
25 (11,3)
25 (11,3)
25 (11,3)

16 (7,3)
20 (9,1)
22 (10,0)
24 (10,9)
26 (11,8)
28 (12,7)
28 (12,7)
28 (12,7)
28 (12,7)

24 (10,9)
30 (13,6)
34 (15,4)
34 (15,4)
36 (16,3)
36 (16,3)
36 (16,3)
36 (16,3)
36 (16,3)

44 (20,0)
76 (34,5)
92 (41,7)
140 (63,5)
150 (68,0)
170 (77,1)
170 (77,1)
170 (77,1)
170 (77,1)

68 (30,8)
140 (63,5)
170 (77,1)
220 (99,8)
270 (122)
290 (132)
300 (136)
330 (150)
330 (150)

52 (23,6)
88 (39,9)
110 (49,9)
170 (77,1)
180 (81,6)
200 (90,7)
200 (90,7)
200 (90,7)
200 (90,7)

80 (36,3)
160 (72,6)
200 (90,7)
260 (118)
320 (145)
340 (154)
360 (163)
390 (177)
400 (181)

10 (0,69)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

20 (9,1)
24 (10,9)
30 (13,6)
30 (13,6)
30 (13,6)
30 (13,6)
30 (13,6)
30 (13,6)

27 (12,2)
34 (15,4)
37 (16,8)
37 (16,8)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)

30 (13,6)
36 (16,3)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)

44 (20,0)
48 (21,8)
56 (25,4)
56 (25,4)
56 (25,4)
56 (25,4)
56 (25,4)
56 (25,4)

68 (30,8)
84 (38,1)
110 (49,9)
190 (86,2)
260 (118)
310 (141)
340 (154)
340 (154)

100 (45,4)
170 (77,1)
210 (95,3)
340 (154)
370 (168)
480 (218)
520 (236)
520 (236)

80 (36,3)
100 (45,4)
130 (59,0)
220 (99,8)
300 (136)
360 (163)
400 (181)
400 (181)

120 (54,4)
200 (90,7)
250 (113)
400 (181)
440 (200)
560 (254)
600 (272)
600 (272)

15 (1,0)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

18 (8,2)
28 (12,7)
36 (16,3)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)
40 (18,1)

28 (12,7)
40 (18,1)
48 (21,8)
48 (21,8)
52 (23,6)
52 (23,6)
52 (23,6)
52 (23,6)

32 (14,5)
44 (20,0)
52 (23,6)
56 (25,4)
56 (25,4)
56 (25,4)
56 (25,4)
56 (25,4)

48 (21,8)
60 (27,2)
64 (29,0)
68 (30,8)
72 (32,7)
72 (32,7)
72 (32,7)
72 (32,7)

76 (34,5)
130 (59,0)
200 (90,7)
270 (122)
340 (154)
440 (200)
440 (200)
440 (200)

110 (49,9)
180 (81,6)
290 (132)
370 (168)
520 (236)
600 (272)
600 (272)
600 (272)

88 (39,9)
150 (68,0)
240 (109)
320 (145)
400 (181)
520 (236)
520 (236)
520 (236)

130 (59,0)
210 (95,3)
340 (154)
440 (200)
600 (272)
720 (327)
720 (327)
720 (327)

2 to 6
(0,14 to 0,41)

5 to 15
(0,35 to 1,0)

Psig (bar)

1/4

  1.  Capacities are in pounds/h (kg/h) of saturated steam.

- continued 21

Bulletin 71.1:95
Table 13. Steam Capacities(1) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with Stainless Steel
Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

13 to 30
(0,90 to 2,1)

PRESSURE
Outlet
Setting,
Psig/Psi
(bar)

REGULATOR BODY SIZE, NPS (dn)

Inlet
Psig (bar)

1/4

1/2 (15)

3/4 (20)

1 (25)

Droop

Droop

Droop

Droop

10%

20%

10%

20%

10%

20%

10%

20%

20 (1,4)

30
40
50
75
100
150
200
250

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

22 (10,0)
30 (13,6)
36 (16,3)
44 (20,0)
44 (20,0)
44 (20,0)
44 (20,0)
44 (20,0)

34 (15,4)
44 (20,0)
52 (23,6)
60 (27,2)
60 (27,2)
60 (27,2)
60 (27,2)
60 (27,2)

44 (20,0)
52 (23,6)
56 (25,4)
60 (27,2)
64 (29,0)
64 (29,0)
64 (29,0)
64 (29,0)

60 (27,2)
68 (30,8)
72 (32,7)
80 (36,3)
84 (38,1)
84 (38,1)
84 (38,1)
84 (38,1)

100 (45,4)
150 (68,0)
180 (81,6)
270 (122)
320 (145)
400 (181)
520 (236)
520 (236)

100 (45,4)
150 (68,0)
180 (81,6)
270 (122)
320 (145)
400 (181)
520 (236)
520 (236)

120 (54,4)
180 (81,6)
220 (99,8)
320 (145)
380 (172)
480 (218)
600 (272)
600 (272)

180 (81,6)
260 (118)
320 (145)
440 (200)
600 (272)
720 (327)
800 (363)
800 (363)

25 (1,7)

40
50
75
100
150
200
250

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

36 (16,3)
48 (21,8)
56 (25,4)
60 (27,2)
64 (29,0)
64 (29,0)
64 (29,0)

48 (21,8)
64 (29,0)
80 (36,3)
100 (45,4)
100 (45,4)
100 (45,4)
100 (45,4)

64 (29,0)
76 (34,5)
80 (36,3)
84 (38,1)
88 (39,9)
88 (39,9)
88 (39,9)

96 (43,5)
100 (45,4)
110 (49,9)
130 (59,0)
130 (59,0)
130 (59,0)
130 (59,0)

170 (77,1)
200 (90,7)
290 (132)
340 (154)
400 (181)
520 (236)
520 (236)

220 (99,8)
270 (122)
370 (168)
520 (236)
680 (308)
840 (381)
840 (381)

200 (90,7)
240 (109)
340 (154)
400 (181)
480 (218)
640 (290)
640 (290)

260 (118)
320 (145)
440 (200)
600 (272)
800 (363)
1000 (454)
1000 (454)

30 (2,1)

40
50
75
100
150
200
250

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

36 (16,3)
48 (21,8)
68 (30,8)
72 (32,7)
76 (34,5)
76 (34,5)
76 (34,5)

48 (21,8)
60 (27,2)
92 (41,7)
100 (45,4)
100 (45,4)
100 (45,4)
100 (45,4)

72 (32,7)
80 (36,3)
92 (41,7)
96 (43,5)
100 (45,4)
100 (45,4)
100 (45,4)

96 (43,5)
110 (49,9)
130 (59,0)
140 (63,5)
140 (63,5)
140 (63,5)
140 (63,5)

140 (63,5)
170 (77,1)
280 (127)
340 (154)
440 (200)
560 (254)
560 (254)

200 (90,7)
260 (118)
370 (168)
520 (236)
680 (308)
880 (399)
880 (399)

160 (72,6)
200 (90,7)
340 (154)
400 (181)
520 (236)
680 (308)
680 (308)

240 (109)
300 (136)
440 (200)
600 (272)
800 (363)
1000 (454)
1000 (454)

  1. Capacities are in pounds/h (kg/h) of saturated steam.

Table 14. Steam Capacities(1) for NPS 1/4 through 1/2 (DN 15) Types 95H and 95HD Regulators with Metal Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

Pressure
Outlet Setting,
Psig/Psi (bar)

regulator body size, NPS (dn)
1/4

Inlet
Psig (bar)

10%

Droop

20%

27
27
27
36
42
54
66
63
81

(12,2)
(12,2)
(12,2)
(16,3)
(19,1)
(24,5)
(29,9)
(28,6)
(36,7)

15 (1,0)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

18 (8,2)
23 (10,4)
45 (20,4)
48 (21,8)
66 (29,9)
84 (38,1)
84 (38,1)
96 (43,5)

23 (10,4)
29 (13,2)
51 (23,1)
75 (34,0)
110 (49,9)
130 (59,0)
120 (54,4)
140 (63,5)

33 (15,0)
39 (17,7)
75 (34,0)
90 (40,8)
130 (59,0)
140 (63,5)
150 (68,0)
150 (68,0)

45 (20,4)
39 (17,7)
54 (24,5)
60 (27,2)
72 (32,7)
93 (42,2)
110 (49,9)
120 (54,4)

69 (31,3)
63 (28,6)
84 (38,1)
90 (40,8)
110 (49,9)
130 (59,0)
140 (63,5)
150 (68,0)

110
100
130
130
160
170
190
200

(49,9)
(45,4)
(59,0)
(59,0)
(72,6)
(77,1)
(86,2)
(90,7)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

30 (13,6)
36 (16,3)
42 (19,1)
63 (28,6)
78 (35,4)
110 (49,9)
120 (54,4)

39 (17,7)
48 (21,8)
69 (31,3)
99 (44,9)
140 (63,5)
170 (77,1)
190 (86,2)

51 (23,1)
72 (32,7)
96 (43,5)
140 (63,5)
180 (81,6)
200 (90,7)
210 (95,3)

36
42
63
75
93
93
110

60 (27,2)
69 (31,3)
87 (39,5)
110 (49,9)
140 (63,5)
140 (63,5)
150 (68,0)

110
120
150
170
200
210
220

(49,9)
(54,4)
(68,0)
(77,1)
(90,7)
(95,3)
(99,8)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

48 (21,8)
66 (29,9)
75 (34,0)
110 (49,9)
150 (68,0)
150 (68,0)

72 (32,7)
96 (43,5)
120 (54,4)
160 (72,6)
200 (90,7)
230 (104)

90 (40,8)
110 (49,9)
140 (63,5)
180 (81,6)
200 (90,7)
270 (122)

69 (31,3)
78 (35,4)
96 (43,5)
110 (49,9)
120 (54,4)
140 (63,5)

110
130
140
170
180
210

190
220
230
260
290
300

(86,2)
(99,8)
(104)
(118)
(132)
(136)

(16,3)
(19,1)
(28,6)
(34,0)
(42,2)
(42,2)
(49,9)

42
45
45
54
63
72
84
93
99

(19,1)
(20,4)
(20,4)
(24,5)
(28,6)
(32,7)
(38,1)
(42,2)
(44,9)

40%

30
30
36
45
48
63
69
72
81

- continued -

(17,7)
(16,3)
(17,7)
(27,2)
(34,0)
(38,1)
(40,8)
(43,5)
(44,9)

20%

20 (9,1)
23 (10,4)
25 (11,3)
33 (15,0)
33 (15,0)
42 (19,1)
57 (25,9)
51 (23,1)
60 (27,2)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

39
36
39
60
75
84
90
96
99

10%

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

25 to 75
(1,7 to 5,2)

(13,6)
(13,6)
(16,3)
(20,4)
(21,8)
(28,6)
(31,3)
(32,7)
(36,7)

40%

30
40
50
75
100
150
200
250
300

15 to 30
(1,0 to 2,1)

22

1/2 (15)

Droop

(49,9)
(59,0)
(63,5)
(77,1)
(81,6)
(95,3)

66 (29,9)
69 (31,3)
66 (29,9)
81 (36,7)
87 (39,5)
96 (43,5)
110 (49,9)
120 (54,4)
130 (59,0)

Bulletin 71.1:95
Table 14. Steam Capacities(1) for NPS 1/4 through 1/2 (DN 15) Types 95H and 95HD Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
psig/PSI (bar)

70 to 150
(4,8 to 10,3)

Pressure
Outlet Setting,
Psig/Psi (bar)

regulator body size, nps (dn)
1/4

Inlet
Psig (bar)

1/2 (15)

Droop
10%

20%

Droop
40%

10%

20%

40%

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

60 (27,2)
60 (27,2)
78 (35,4)
84 (38,1)
99 (44,9)
120 (54,4)

84 (38,1)
110 (49,9)
120 (54,4)
140 (63,5)
170 (77,1)
210 (95,3)

110
140
160
180
220
260

(49,9)
(63,5)
(72,6)
(81,6)
(99,8)
(118)

100
120
140
160
130
240

(45,4)
(54,4)
(63,5)
(72,6)
(59,0)
(109)

170
200
230
250
270
330

(77,1)
(90,7)
(104)
(113)
(122)
(150)

260
330
360
390
420
450

(118)
(150)
(163)
(177)
(191)
(204)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

60 (27,2)
84 (38,1)
100 (45,4)
110 (49,9)
110 (49,9)
140 (63,5)

90 (40,8)
130 (59,0)
130 (59,0)
170 (77,1)
190 (86,2)
220 (99,8)

130
150
180
200
220
260

(59,0)
(68,0)
(81,6)
(90,7)
(99,8)
(118)

160
150
170
200
210
210

(72,6)
(68,0)
(77,1)
(90,7)
(95,3)
(95,3)

250
270
280
330
390
390

(113)
(122)
(127)
(150)
(177)
(177)

330
390
420
480
510
570

(150)
(177)
(191)
(218)
(231)
(259)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

75 (34,0)
90 (40,8)
99 (44,9)
120 (54,4)
160 (72,6)

110
130
160
190
230

150
170
200
220
250

(68,0)
(77,1)
(90,7)
(99,8)
(113)

170
200
210
270
260

(77,1)
(90,7)
(95,3)
(122)
(118)

290
330
360
420
450

(132)
(150)
(163)
(191)
(204)

360
420
480
540
600

(163)
(191)
(218)
(245)
(272)

(49,9)
(59,0)
(72,6)
(86,2)
(104)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

Table 14. Steam Capacities(1) for NPS 3/4 through 1 (DN 20 through 25) Types 95H and 95HD Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig/PSI (bar)

pressure
Outlet Setting,
Psig/Psi (bar)

regulator body size, NPS (dn)
Inlet

1 (25)

Droop

Droop

10%

20%

10%

20%

15 (1,0)

30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

66 (29,9)
81 (36,7)
87 (39,5)
110 (49,9)
120 (54,4)
150 (68,0)
180 (81,6)
200 (90,7)
220 (99,8)

93 (42,2)
110 (49,9)
130 (59,0)
170 (77,1)
180 (81,6)
210 (95,3)
240 (109)
260 (118)
290 (132)

150
190
200
250
270
300
330
330
360

(68,0)
(86,2)
(90,7)
(113)
(122)
(136)
(150)
(150)
(163)

66 (29,9)
78 (35,4)
100 (45,4)
140 (63,5)
160 (72,6)
210 (95,3)
260 (118)
260 (118)
300 (136)

99 (44,9)
130 (59,0)
160 (72,6)
210 (95,3)
240 (109)
300 (136)
360 (163)
360 (163)
420 (191)

160
200
250
330
360
450
480
510
540

(72,6)
(90,7)
(113)
(150)
(163)
(204)
(218)
(231)
(245)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

87 (39,5)
120 (54,4)
170 (77,1)
190 (86,2)
230 (104)
280 (127)
270 (122)
300 (136)

140
180
260
290
360
360
390
420

(63,5)
(81,6)
(118)
(132)
(163)
(163)
(177)
(191)

190
230
360
420
480
510
540
570

(86,2)
(104)
(163)
(191)
(218)
(231)
(245)
(259)

96 (43,5)
120 (54,4)
160 (72,6)
220 (99,8)
300 (136)
360 (163)
420 (191)
450 (204)

160
200
280
330
450
540
600
630

(72,6)
(90,7)
(127)
(150)
(204)
(245)
(272)
(286)

200
250
360
480
660
780
810
840

(90,7)
(113)
(163)
(218)
(299)
(354)
(367)
(381)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

120
180
220
250
330
360
360

(54,4)
(81,6)
(99,8)
(113)
(150)
(163)
(163)

200
260
330
390
510
540
540

(90,7)
(118)
(150)
(177)
(231)
(245)
(245)

270
360
450
630
720
750
780

(122)
(163)
(204)
(286)
(327)
(340)
(354)

130
190
210
480
450
510
570

(59,0)
(86,2)
(95,3)
(218)
(204)
(231)
(259)

220
290
390
540
720
780
810

(99,8)
(132)
(177)
(245)
(327)
(354)
(367)

280
360
480
720
930
1100
1100

(127)
(163)
(218)
(327)
(422)
(499)
(499)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

240
330
360
420
480
480

(109)
(150)
(163)
(191)
(218)
(218)

360
480
540
630
720
750

(163)
(218)
(245)
(286)
(327)
(340)

450
570
660
720
780
840

(204)
(259)
(299)
(327)
(354)
(381)

260
390
390
510
660
690

(118)
(177)
(177)
(231)
(299)
(313)

390
510
630
840
990
1100

(177)
(231)
(286)
(381)
(449)
(499)

450 (204)
600 (272)
750 (340)
960 (435)
1100 (499)
1400 (635)

15 to 30
(1,0 to 2,1)

25 to 75
(1,7 to 5,2)

Psig (bar)

3/4 (20)
40%

40%

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

- continued -

23

Bulletin 71.1:95
Table 14. Steam Capacities(1) for NPS 3/4 through 1 (DN 20 through 25) Types 95H and 95HD Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG/PSI (bar)

70 to 150
(4,8 to 10,3)

pressure
Outlet Setting,
Psig/Psi (bar)

regulator body size, NPS (dn)
Inlet

Psig (bar)

10%

3/4 (20)

1 (25)

Droop

Droop
20%

40%

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

260
360
390
450
450
570

(118)
(163)
(177)
(204)
(204)
(259)

420
540
630
690
750
870

20%
(191)
(245)
(286)
(313)
(340)
(395)

540 (245)
660 (299)
780 (354)
900 (408)
1100 (499)
1200 (544)

40%

330
420
480
480
630
780

10%
(150)
(191)
(218)
(218)
(286)
(354)

480 (218)
600 (272)
750 (340)
810 (367)
1000 (454)
1100 (499)

570 (259)
690 (313)
840 (381)
960 (435)
1200 (544)
1400 (635)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

360
390
480
510
540
630

(163)
(177)
(218)
(231)
(245)
(286)

540
630
750
840
870
960

(245)
(286)
(340)
(381)
(395)
(435)

630 (286)
750 (340)
870 (395)
990 (449)
1100 (499)
1400 (635)

390
450
510
570
600
780

(177)
(204)
(231)
(259)
(272)
(354)

600 (272)
690 (313)
840 (381)
900 (408)
1000 (454)
1200 (544)

690 (313)
810 (367)
930 (422)
1100 (499)
1200 (544)
1400 (635)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

420
480
600
600
690

(191)
(218)
(272)
(272)
(313)

600
720
870
900
1100

(272)
(327)
(395)
(408)
(499)

870 (395)
870 (395)
990 (449)
1100 (499)
1400 (635)

480
600
660
780
930

(218)
(272)
(299)
(354)
(422)

660 (299)
780 (354)
900 (408)
1100 (499)
1300 (590)

780 (354)
900 (408)
1100 (499)
1200 (544)
1400 (635)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

Table 15. Steam Capacities(1) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95H and 95HD Regulators with Metal Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig/PSI (bar)

5 to 80
(0,35 to 5,5)

pressure
Outlet Setting,
Psig/Psi (bar)

regulator body size, nps (dn)
Inlet

Psig (bar)

1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

5 (0,35)

10
20
30
50
75
100
150
200
250
300

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

48 (21,8)
110 (49,9)
130 (59,0)
180 (81,6)
250 (113)
330 (150)
430 (195)
600 (272)
750 (340)
900 (408)

50 (22,7)
130 (59,0)
150 (68,0)
200 (90,7)
300 (136)
400 (181)
550 (249)
700 (318)
850 (386)
1000 (454)

75 (34,0)
220 (99,8)
250 (113)
300 (136)
400 (181)
480 (218)
600 (272)
850 (386)
950 (431)
1100 (499)

50 (22,7)
90 (40,8)
170 (77,1)
200 (90,7)
280 (127)
450 (204)
750 (340)
800 (363)
900 (408)
950 (431)

55 (24,9)
100 (45,4)
230 (104)
280 (127)
350 (159)
600 (272)
900 (408)
950 (431)
1000 (454)
1100 (499)

75 (34,0)
130 (59,0)
370 (168)
450 (204)
550 (249)
700 (318)
1100 (499)
1100 (499)
1100 (499)
1200 (544)

15 (1,0)

30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

130 (59,0)
180 (81,6)
230 (104)
300 (136)
380 (172)
500 (227)
750 (340)
900 (408)
1100 (499)

150 (68,0)
230 (104)
300 (136)
400 (181)
480 (218)
610 (277)
950 (431)
1100 (499)
1300 (590)

250 (113)
400 (181)
480 (218)
650 (295)
800 (363)
1000 (454)
1200 (544)
1400 (635)
1500 (680)

140 (63,5)
190 (86,2)
240 (109)
350 (159)
500 (227)
750 (340)
1000 (454)
1200 (544)
1300 (590)

200 (90,7)
280 (127)
350 (159)
540 (245)
750 (340)
1000 (454)
1200 (544)
1400 (635)
1500 (680)

280 (127)
400 (181)
600 (272)
1100 (499)
1300 (590)
1500 (680)
1600 (726)
1700 (771)
1800 (816)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

170 (77,1)
230 (104)
300 (136)
400 (181)
600 (272)
1000 (454)
1300 (590)
1500 (680)

300 (136)
450 (204)
600 (272)
750 (340)
1100 (499)
1600 (726)
1800 (816)
1900 (862)

500 (227)
700 (318)
900 (408)
1200 (544)
1800 (816)
1900 (862)
2100 (953)
2200 (998)

230 (104)
400 (181)
750 (340)
1200 (544)
2200 (998)
2400 (1089)
2600 (1179)
2700 (1225)

310 (141)
500 (227)
1000 (454)
1500 (680)
2500 (1134)
2800 (1270)
2900 (1315)
3000 (1361)

550 (249)
750 (340)
1300 (590)
1800 (816)
2700 (1225)
2900 (1315)
3000 (1361)
3100 (1406)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

- continued -

24

Bulletin 71.1:95
Table 15. Steam Capacities(1) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95H and 95HD Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig/PSI (bar)

pressure
Inlet

Outlet Setting,
Psig/Psi (bar)

Psig (bar)

100 to 140
(6,9 to 9,7)

120 to 150
(8,3 to 10,3)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

300 (136)
450 (204)
500 (227)
640 (290)
1100 (499)
1600 (726)
2000 (907)

550 (249)
700 (318)
950 (431)
1400 (635)
1800 (816)
2300 (1043)
2600 (1179)

1000 (454)
1600 (726)
2300 (1043)
3100 (1406)
3200 (1452)
3300 (1497)
3400 (1542)

330 (150)
600 (272)
1000 (454)
1500 (680)
2200 (998)
2800 (1270)
3300 (1497)

600 (272)
1000 (454)
2000 (907)
3400 (1542)
3800 (1724)
4000 (1814)
4200 (1905)

1100 (499)
1800 (816)
2800 (1270)
3800 (1724)
4200 (1905)
4300 (1950)
4500 (2041)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

700 (318)
850 (386)
1000 (454)
1200 (544)
1700 (771)
2200 (998)

1100 (499)
1500 (680)
2000 (907)
2500 (1134)
2900 (1315)
3300 (1497)

2100 (952)
2800 (1270)
3600 (1633)
4100 (1860)
4300 (1950)
4400 (1996)

750 (340)
1000 (454)
1300 (590)
2500 (1134)
3500 (1588)
4500 (2041)

1400 (635)
2300 (1043)
3500 (1588)
4500 (2041)
5500 (2495)
6000 (2722)

2500
3300
3800
4800
5500
6000

(1134)
(1497)
(1724)
(2177)
(2495)
(2722)

100 (6,9)

125
150
175
225
250
300

(8,6)
(10,3)
(12,1)
(15,5)
(17,2)
(20,7)

550 (249)
1100 (499)
1300 (590)
1400 (635)
1700 (771)
2000 (907)

1500 (680)
1900 (862)
2400 (1089)
3100 (1406)
3500 (1588)
4400 (1996)

2500
3200
3800
4800
5500
6000

(1134)
(1452)
(1724)
(2177)
(2495)
(2722)

600 (272)
1300 (590)
1700 (771)
1400 (635)
2300 (1043)
2800 (1270)

1500 (680)
2300 (1043)
2600 (1179)
3100 (1406)
3500 (1588)
4000 (1814)

2700
3600
4500
4800
6500
7500

(1225)
(1633)
(2041)
(2177)
(2948)
(3402)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

1100
1300
1400
1500
1800
2100

(499)
(590)
(635)
(680)
(816)
(953)

2000 (907)
2400 (1089)
2700 (1225)
3000 (1361)
3500 (1588)
4300 (1950)

3200
3700
4500
5000
5500
6500

(1452)
(1678)
(2041)
(2268)
(2495)
(2948)

1100 (499)
1600 (726)
2000 (907)
2300 (1043)
2800 (1270)
4300 (1950)

2000 (907)
2500 (1134)
3500 (1588)
5000 (2268)
6000 (2722)
7500 (3402)

3300
3800
4500
5500
6500
7500

(1497)
(1724)
(2041)
(2495)
(2948)
(3402)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

950 (431)
1200 (544)
1500 (680)
1800 (816)
2300 (1043)

1600 (726)
2200 (998)
3100 (1406)
3500 (1588)
4500 (2041)

2700
4000
5000
6000
7500

(1225)
(1814)
(2268)
(2722)
(3402)

1000 (454)
1200 (544)
1500 (680)
2500 (1134)
4300 (1950)

1700 (771)
2300 (1043)
3100 (1406)
4800 (2177)
7000 (3175)

2800
4000
5000
6000
7500

(1270)
(1814)
(2268)
(2722)
(3402)

5 to 80
(0,35 to 5,5)

60 to 120
(4,1 to 8,3)

regulator body size, nps (dn)
1-1/2 (40)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

Table 16. Steam Capacities(1) for NPS 1/4 through 1/2 (DN 15) Type 95HT Regulators with Metal Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig (bar)

Pressure
Outlet Setting,
Psig (bar)

REGULATOR BODY SIZE, NPS (DN)
1/4

Inlet
Psig (bar)

1/2 (15)

Droop
10%

20%

Droop
40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

9 (4,1)
11 (5,0)
11 (5,0)
16 (7,3)
24 (10,9)
33 (15,0)
36 (16,3)
45 (20,4)
51 (23,1)
54 (24,5)
57 (25,9)
63 (28,6)

17 (7,7)
17 (7,7)
18 (8,2)
23 (10,4)
36 (16,3)
48 (21,8)
51 (23,1)
63 (28,6)
69 (31,3)
69 (31,3)
72 (32,7)
78 (35,4)

26
30
36
39
60
72
84
87
87
87
90
96

30 (2,1)

40
50
75
100
150
200

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)

13 (5,9)
15 (6,8)
21 (9,5)
24 (10,9)
42 (19,1)
60 (27,2)

23
27
36
51
75
90

33 (15,0)
48 (21,8)
63 (28,6)
87 (39,5)
110 (49,9)
130 (59,0)

15 to 100
(1,0 to 6,9)

(10,4)
(12,2)
(16,3)
(23,1)
(34,0)
(40,8)

(11,8)
(13,6)
(16,3)
(17,7)
(27,2)
(32,7)
(38,1)
(39,5)
(39,5)
(39,5)
(40,8)
(43,5)

10%

20%

40%

18 (8,2)
19 (8,6)
21 (9,5)
27 (12,2)
33 (15,0)
51 (23,1)
63 (28,6)
72 (32,7)
81 (36,7)
99 (44,9)
120 (54,4)
140 (63,5)

26 (11,8)
27 (12,2)
36 (16,3)
45 (20,4)
51 (23,1)
69 (31,3)
84 (38,1)
90 (40,8)
99 (44,9)
110 (49,9)
130 (59,0)
140 (63,5)

42 (19,1)
45 (20,4)
51 (23,1)
54 (24,5)
78 (35,4)
93 (42,2)
110 (49,9)
110 (49,9)
120 (54,4)
130 (59,0)
140 (63,5)
150 (68,0)

27
36
39
54
63
78

45
48
63
78
96
110

57 (25,9)
60 (27,2)
110 (49,9)
120 (54,4)
140 (63,5)
150 (68,0)

(12,2)
(16,3)
(17,7)
(24,5)
(28,6)
(35,4)

(20,4)
(21,8)
(28,6)
(35,4)
(43,5)
(49,9)

  1. Capacities are based in pounds/h (kg/h) of saturated steam.

- continued -

25

Bulletin 71.1:95
Table 16. Steam Capacities(1) for NPS 1/4 through 1/2 (DN 15) Type 95HT Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig (bar)

Pressure
Outlet Setting,
Psig (bar)

REGULATOR BODY SIZE, NPS (DN)
1/4

Inlet
Psig (bar)

10%

20%

Droop
40%

10%

20%

40%

30 (2,1)

250
300
400
500
600

(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

66
72
84
84
84

(29,9)
(32,7)
(38,1)
(38,1)
(38,1)

99 (44,9)
110 (49,9)
120 (54,4)
120 (54,4)
120 (54,4)

130
130
130
130
130

(59,0)
(59,0)
(59,0)
(59,0)
(59,0)

90 (40,8)
110 (49,9)
120 (54,4)
140 (63,5)
160 (72,6)

120
140
160
180
190

(54,4)
(63,5)
(72,6)
(81,6)
(86,2)

170
180
190
190
210

(77,1)
(81,6)
(86,2)
(86,2)
(95,3)

75 (5,2)

100
125
150
200
250
300
400
500
600

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

45 (20,4)
60 (27,2)
72 (32,7)
99 (44,9)
120 (54,4)
150 (68,0)
170 (77,1)
200 (90,7)
210 (95,3)

75 (34,0)
96 (43,5)
120 (54,4)
140 (63,5)
190 (86,2)
220 (99,8)
250 (113)
280 (127)
280 (127)

96 (43,5)
120 (54,4)
140 (63,5)
190 (86,2)
230 (104)
250 (113)
270 (122)
290 (132)
290 (132)

84 (38,1)
110 (49,9)
120 (54,4)
150 (68,0)
160 (72,6)
170 (77,1)
200 (90,7)
210 (95,3)
240 (109)

150
170
190
230
240
260
280
300
330

(68,0)
(77,1)
(86,2)
(104)
(109)
(118)
(127)
(136)
(150)

220
260
300
330
330
360
390
390
420

(99,8)
(118)
(136)
(150)
(150)
(163)
(177)
(177)
(191)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

60 (27,2)
93 (42,2)
110 (49,9)
140 (63,5)
150 (68,0)
180 (81,6)
210 (95,3)
230 (104)
230 (104)

96 (43,5)
120 (54,4)
150 (68,0)
170 (77,1)
200 (90,7)
250 (113)
300 (136)
330 (150)
360 (163)

120
140
170
190
230
270
330
360
360

(54,4)
(63,5)
(77,1)
(86,2)
(104)
(122)
(150)
(163)
(163)

120
150
170
170
200
220
230
260
270

(54,4)
(68,0)
(77,1)
(77,1)
(90,7)
(99,8)
(104)
(118)
(122)

200
240
260
280
300
330
360
390
420

(90,7)
(109)
(118)
(127)
(136)
(150)
(163)
(177)
(191)

270
330
390
420
450
480
510
510
540

(122)
(150)
(177)
(191)
(204)
(218)
(231)
(231)
(245)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

63 (28,6)
66 (29,9)
84 (38,1)
93 (42,2)
99 (44,9)
110 (49,9)
160 (72,6)
190 (86,2)
210 (95,3)

84 (38,1)
96 (43,5)
120 (54,4)
130 (59,0)
150 (68,0)
170 (77,1)
230 (104)
290 (132)
330 (150)

120
140
170
180
200
240
330
390
480

(54,4)
(63,5)
(77,1)
(81,6)
(90,7)
(109)
(150)
(177)
(218)

90 (40,8)
110 (49,9)
120 (54,4)
120 (54,4)
130 (59,0)
160 (72,6)
200 (90,7)
240 (109)
280 (127)

160
180
200
200
210
250
300
360
420

(72,6)
(81,6)
(90,7)
(90,7)
(95,3)
(113)
(136)
(163)
(191)

260
290
330
330
360
420
450
540
630

(118)
(132)
(150)
(150)
(163)
(191)
(204)
(245)
(286)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

96 (43,5)
110 (49,9)
130 (59,0)
140 (63,5)
170 (77,1)
190 (86,2)
200 (90,7)
220 (99,8)

140
160
200
230
260
290
330
390

(63,5)
(72,6)
(90,7)
(104)
(118)
(132)
(150)
(177)

190
220
260
300
360
390
450
540

(86,2)
(99,8)
(118)
(136)
(163)
(177)
(204)
(245)

170
170
200
230
260
290
330
330

(77,1)
(77,1)
(90,7)
(104)
(118)
(132)
(150)
(150)

280
300
330
390
420
450
510
570

(127)
(136)
(150)
(177)
(191)
(204)
(231)
(259)

450
510
570
600
660
720
780
900

(204)
(231)
(259)
(272)
(299)
(327)
(354)
(408)

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

120
130
150
160
170
190
200
220

(54,4)
(59,0)
(68,0)
(72,6)
(77,1)
(86,2)
(90,7)
(99,8)

170
200
230
260
290
330
360
390

(77,1)
(90,7)
(104)
(118)
(132)
(150)
(163)
(177)

230
250
300
360
390
450
480
540

(104)
(113)
(136)
(163)
(177)
(204)
(218)
(245)

230
220
240
280
290
300
330
360

(104)
(99,8)
(109)
(127)
(132)
(136)
(150)
(163)

360
390
420
480
510
540
600
600

(163)
(177)
(191)
(218)
(231)
(245)
(272)
(272)

570 (259)
600 (272)
690 (313)
780 (354)
840 (381)
930 (422)
1000 (454)
1100 (499)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

160
170
180
190
200
220

(72,6)
(77,1)
(81,6)
(86,2)
(90,7)
(99,8)

230
260
300
330
360
390

(104)
(118)
(136)
(150)
(163)
(177)

230
260
300
330
360
390

(104)
(118)
(136)
(150)
(163)
(177)

270
290
300
330
330
360

(122)
(132)
(136)
(150)
(150)
(163)

480
510
540
570
600
630

(218)
(231)
(245)
(259)
(272)
(286)

720 (327)
840 (381)
930 (422)
1000 (454)
1100 (499)
1200 (544)

15 to 100
(1,0 to 6,9)

80 to 300
(5,5 to 20,7)

  1.  Capacities are based in pounds/hour (kg/h) of saturated steam.

- continued -

26

1/2 (15)

Droop

Bulletin 71.1:95
Table 16. Steam Capacities(1) for NPS 3/4 through 1 (DN 20 through 25) Type 95HT Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)

Inlet

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

39 (17,7)
39 (17,7)
45 (20,4)
72 (32,7)
93 (42,2)
120 (54,4)
140 (63,5)
170 (77,1)
200 (90,7)
250 (113)
300 (136)
360 (163)

54 (24,5)
63 (28,6)
72 (32,7)
96 (43,5)
130 (59,0)
150 (68,0)
190 (86,2)
210 (95,3)
240 (109)
290 (132)
330 (150)
390 (177)

87 (39,5)
87 (39,5)
100 (45,4)
140 (63,5)
180 (81,6)
230 (104)
250 (113)
280 (127)
300 (136)
360 (163)
390 (177)
450 (204)

36 (16,3)
39 (17,7)
57 (25,9)
78 (35,4)
90 (40,8)
140 (63,5)
170 (77,1)
200 (90,7)
230 (104)
270 (122)
330 (150)
360 (163)

48 (21,8)
60 (27,2)
81 (36,7)
110 (49,9)
140 (63,5)
190 (86,2)
230 (104)
270 (122)
300 (136)
360 (163)
420 (191)
480 (218)

75 (34,0)
90 (40,8)
110 (49,9)
160 (72,6)
210 (95,3)
290 (132)
360 (163)
390 (177)
420 (191)
510 (231)
600 (272)
660 (299)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

51 (23,1)
66 (29,9)
90 (40,8)
120 (54,4)
150 (68,0)
180 (81,6)
220 (99,8)
260 (118)
330 (150)
390 (177)
450 (204)

84 (38,1)
110 (49,9)
140 (63,5)
180 (81,6)
220 (99,8)
270 (122)
300 (136)
360 (163)
420 (191)
450 (204)
510 (231)

140
170
220
290
360
420
420
480
540
630
660

57 (25,9)
69 (31,3)
99 (44,9)
120 (54,4)
190 (86,2)
200 (90,7)
240 (109)
270 (122)
360 (163)
450 (204)
510 (231)

87 (39,5)
99 (44,9)
140 (63,5)
180 (81,6)
290 (132)
330 (150)
420 (191)
450 (204)
540 (245)
660 (299)
720 (327)

140
170
250
330
450
540
600
660
750
900
960

75 (5,2)

100
125
150
200
250
300
400
500
600

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

190
220
280
330
390
420
510
600
720

(86,2)
(99,8)
(127)
(150)
(177)
(191)
(231)
(272)
(327)

330
360
450
540
630
660
750
870
930

(150)
(163)
(204)
(245)
(286)
(299)
(340)
(395)
(422)

450 (204)
540 (245)
660 (299)
810 (367)
930 (422)
990 (449)
1100 (499)
1200 (544)
1300 (590)

190
240
290
390
480
510
600
720
750

(86,2)
(109)
(132)
(177)
(218)
(231)
(272)
(327)
(340)

300 (136)
420 (191)
510 (231)
660 (299)
780 (354)
900 (408)
960 (435)
1100 (499)
1200 (544)

420 (191)
570 (259)
690 (313)
930 (422)
1100 (499)
1300 (590)
1700 (771)
2100 (953)
2500 (1134)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

260
330
360
390
480
540
660
750
870

(118)
(150)
(163)
(177)
(218)
(245)
(299)
(340)
(395)

420
540
600
660
780
870
960
1100
1100

(191)
(245)
(272)
(299)
(354)
(395)
(435)
(499)
(499)

540 (245)
660 (299)
780 (354)
900 (408)
1100 (499)
1300 (590)
1400 (635)
1600 (726)
1700 (771)

260 (118)
330 (150)
420 (191)
480 (218)
600 (272)
630 (286)
840 (381)
1100 (499)
1300 (590)

450 (204)
570 (259)
690 (313)
780 (354)
990 (449)
1100 (499)
1400 (635)
1700 (771)
2000 (907)

540 (245)
690 (313)
780 (354)
930 (422)
1200 (544)
1400 (635)
1900 (862)
2300 (1043)
2900 (1315)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

210
210
290
300
360
390
480
540
600

(95,3)
(95,3)
(132)
(136)
(163)
(177)
(218)
(245)
(272)

330 (150)
390 (177)
450 (204)
480 (218)
570 (259)
600 (272)
750 (340)
900 (408)
1000 (454)

570 (259)
630 (286)
720 (327)
810 (367)
870 (395)
990 (449)
1200 (544)
1400 (635)
1600 (726)

230
230
260
290
300
360
510
630
780

(104)
(104)
(118)
(132)
(136)
(163)
(231)
(286)
(354)

390 (177)
390 (177)
450 (204)
480 (218)
540 (245)
690 (313)
870 (395)
1100 (499)
1300 (590)

600 (272)
690 (313)
750 (340)
870 (395)
960 (435)
1100 (499)
1400 (635)
1800 (816)
2100 (953)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

330
420
510
630
630
750
810
900

(150)
(191)
(231)
(286)
(286)
(340)
(367)
(408)

600 (272)
720 (327)
840 (381)
1000 (454)
1100 (499)
1200 (544)
1400 (635)
1500 (680)

900 (408)
1100 (499)
1300 (590)
1500 (680)
1700 (771)
1900 (862)
2000 (907)
2300 (1043)

360
420
540
600
660
750
810
900

(163)
(191)
(245)
(272)
(299)
(340)
(367)
(408)

630 (286)
690 (313)
930 (422)
1100 (499)
1200 (544)
1400 (635)
1500 (680)
1800 (816)

930 (422)
1100 (499)
1300 (590)
1700 (771)
1800 (816)
2100 (953)
2300 (1043)
2700 (1225)

15 to 100
(1,0 to 6,9)

80 to 300
(5,5 to 20,7)

Psig (bar)

3/4 (20)

(63,5)
(77,1)
(99,8)
(132)
(163)
(191)
(191)
(218)
(245)
(286)
(299)

(63,5)
(77,1)
(113)
(150)
(204)
(245)
(272)
(299)
(340)
(408)
(435)

  1. Capacities are based in pounds/hour (kg/h) of saturated steam.

- continued -

27

Bulletin 71.1:95
Table 16. Steam Capacities(1) for NPS 3/4 through 1 (DN 20 through 25) Type 95HT Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)

Inlet
10%

1 (25)

Droop

Droop

20%

40%

10%

20%

40%

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

450
540
660
660
750
780
810
930

(204)
(245)
(299)
(299)
(340)
(354)
(367)
(422)

750 (340)
900 (408)
1100 (499)
1100 (499)
1300 (590)
1300 (590)
1400 (635)
1600 (726)

1100 (499)
1200 (544)
1500 (680)
1700 (771)
1800 (816)
2000 (907)
2200 (998)
2400 (1089)

480 (218)
510 (231)
720 (327)
720 (327)
840 (381)
930 (422)
1000 (454)
1100 (499)

810 (367)
930 (422)
1200 (544)
1300 (590)
1500 (680)
1700 (771)
1900 (862)
2000 (907)

1100 (499)
1300 (590)
1500 (680)
1800 (816)
2000 (907)
2300 (1043)
2600 (1179)
2800 (1270)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

630
720
810
900
990
1100

(286)
(327)
(367)
(408)
(449)
(499)

1100
1200
1400
1500
1700
1800

1400 (635)
1700 (771)
2000 (907)
2300 (1043)
2600 (1179)
2900 (1315)

660 (299)
780 (354)
930 (422)
1100 (499)
1200 (544)
1300 (590)

1100 (499)
1400 (635)
1700 (771)
1900 (862)
2200 (998)
2400 (1089)

1500 (680)
1700 (771)
2100 (953)
2400 (1089)
2700 (1225)
3000 (1361)

80 to 300
(5,5 to 20,7)

Psig (bar)

3/4 (20)

(499)
(544)
(635)
(680)
(771)
(816)

  1. Capacities are based in pounds/hour (kg/h) of saturated steam.

Table 17. Steam Capacities(1) for NPS 1-1/2 through 2 (DN 40 through 50) Type 95HT Regulators with Metal Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
Psig (bar)

15 to 100
(1,0 to 6,9)

Pressure
Outlet Setting,
Psig (bar)

regulator body size, NPS (dn)
Inlet

Psig (bar)

1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

90 (40,8)
190 (86,2)
230 (104)
290 (132)
350 (159)
500 (227)
700 (318)
900 (408)
1100 (499)
1300 (590)
1400 (635)
1500 (680)

140 (63,5)
250 (113)
300 (136)
400 (181)
480 (218)
650 (295)
900 (408)
1100 (499)
1300 (590)
1400 (635)
1500 (680)
1600 (726)

190 (86,2)
350 (159)
400 (181)
550 (249)
700 (318)
950 (431)
1200 (544)
1400 (635)
1500 (680)
1600 (726)
1700 (771)
1800 (816)

100 (45,4)
200 (90,7)
250 (113)
400 (181)
500 (227)
1000 (454)
1600 (726)
1600 (726)
1600 (726)
1600 (726)
1700 (771)
1700 (771)

150 (68,0)
300 (136)
400 (181)
600 (272)
780 (354)
1300 (590)
1700 (771)
1700 (771)
1700 (771)
1700 (771)
1800 (816)
1800 (816)

200 (90,7)
400 (181)
600 (272)
1000 (454)
1300 (590)
1600 (726)
1800 (816)
1900 (862)
1900 (862)
1900 (862)
1900 (862)
2000 (907)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

220 (99,8)
270 (122)
330 (150)
400 (181)
600 (272)
850 (386)
1200 (544)
1400 (635)
1700 (771)
1900 (862)
2000 (907)

320 (145)
380 (172)
480 (218)
600 (272)
950 (431)
1400 (635)
1800 (816)
2000 (907)
2100 (953)
2100 (953)
2200 (998)

550 (249)
650 (295)
850 (386)
1100 (499)
1500 (680)
1800 (816)
2000 (907)
2200 (998)
2400 (1089)
2500 (1134)
2600 (1179)

230 (104)
280 (127)
400 (181)
600 (272)
1800 (816)
2500 (1134)
2700 (1225)
2800 (1270)
2800 (1270)
2900 (1315)
2900 (1315)

350 (159)
450 (204)
700 (318)
1200 (544)
2200 (998)
2600 (1179)
2800 (1270)
2900 (1315)
3000 (1361)
3100 (1406)
3100 (1406)

630 (286)
750 (340)
1300 (590)
2000 (907)
2500 (1134)
2800 (1270)
3000 (1361)
3100 (1406)
3200 (1452)
3200 (1452)
3300 (1497)

50 (3,4)

60
75
100
150
200
250
300
400
500
600

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

330 (150)
430 (195)
600 (272)
900 (408)
1200 (544)
1500 (680)
1800 (816)
2300 (1043)
2700 (1225)
3000 (1361)

550 (249)
650 (295)
900 (408)
1400 (635)
1900 (862)
2300 (1043)
2500 (1134)
2900 (1315)
3100 (1406)
3400 (1542)

1100 (499)
1400 (635)
1800 (816)
2400 (1089)
2900 (1315)
3100 (1406)
3300 (1497)
3300 (1497)
3500 (1588)
3600 (1633)

400 (181)
850 (386)
1500 (680)
2500 (1134)
3200 (1452)
3600 (1633)
3900 (1769)
4200 (1905)
4400 (1996)
4600 (2087)

630 (286)
1100 (499)
1800 (816)
2800 (1270)
3700 (1678)
4000 (1814)
4300 (1950)
4500 (2041)
4600 (2087)
4800 (2177)

1400 (635)
2000 (907)
2500 (1134)
3500 (1588)
4100 (1860)
4400 (1996)
4600 (2087)
4700 (2132)
4900 (2223)
5000 (2268)

  1. Capacities are based in pounds/hour (kg/h) of saturated steam.

- continued -

28

Bulletin 71.1:95
Table 17. Steam Capacities(1) for NPS 1-1/2 through 2 (DN 40 through 50) Type 95HT Regulators with Metal Diaphragm (continued)
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
Psig (bar)

15 to 100
(1,0 to 6,9)

60 to 260
(4,1 to 17,9)

Pressure
Outlet/
Differential
Setting,
Psig (bar)

regulator body size, NPS (dn)
Inlet

Psig (bar)

1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

100 (6,9)

125
150
200
250
300
400
500
600

(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1000 (454)
1200 (544)
1500 (680)
1900 (862)
2400 (1089)
3300 (1497)
3800 (1724)
4100 (1860)

1600 (726)
1900 (862)
2800 (1270)
3300 (1497)
3800 (1724)
4300 (1950)
4800 (2177)
5200 (2359)

3000 (1361)
3600 (1633)
4600 (2087)
4800 (2177)
4900 (2223)
5000 (2268)
5100 (2313)
5300 (2404)

2000 (907)
2500 (1134)
4100 (1860)
4900 (2223)
5400 (2449)
5900 (2676)
6400 (2903)
6700 (3039)

2300 (1043)
3200 (1452)
4900 (2223)
5500 (2495)
5900 (2676)
6300 (2858)
6500 (2948)
6800 (3084)

3500 (1588)
4300 (1950)
5400 (2449)
6100 (2767)
6400 (2903)
6700 (3039)
6800 (3084)
6900 (3130)

100 (6,9)

125
150
175
225
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

800 (363)
900 (408)
1000 (454)
1100 (499)
1500 (680)
1800 (816)
2100 (953)
2400 (1089)
2600 (1179)

1300 (590)
1500 (680)
1700 (771)
1900 (862)
2100 (953)
2600 (1179)
3600 (1633)
4300 (1950)
4800 (2177)

2500 (1134)
2800 (1270)
3200 (1452)
3600 (1633)
4000 (1814)
4800 (2177)
6000 (2722)
6500 (2948)
7000 (3175)

850 (386)
900 (408)
1000 (454)
1100 (499)
1600 (726)
2500 (1134)
4800 (2177)
5500 (2495)
6300 (2858)

1300 (590)
1500 (680)
1700 (771)
2000 (907)
2500 (1134)
3800 (1724)
6800 (3084)
8000 (3629)
8500 (3856)

3000 (1361)
3500 (1588)
4000 (1814)
4800 (2177)
5600 (2540)
6800 (3084)
8300 (3765)
9300 (4218)
9800 (4445)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

1300 (590)
1400 (635)
2000 (907)
2300 (1043)
2700 (1225)
3100 (1406)
3600 (1633)
4500 (2041)

2500 (1134)
2700 (1225)
3600 (1633)
4100 (1860)
5000 (2268)
5500 (2495)
6000 (2722)
6500 (2948)

4600 (2087)
4900 (2223)
6400 (2903)
7000 (3175)
8300 (3765)
9000 (4082)
9500 (4309)
10 000 (4536)

1400 (635)
1500 (680)
2100 (953)
2700 (1225)
3800 (1724)
4000 (1814)
5000 (2268)
6300 (2858)

2600 (1179)
2800 (1270)
4000 (1814)
4900 (2223)
8300 (3765)
8000 (3629)
8500 (3856)
9000 (4082)

5300 (2404)
5000 (2268)
7100 (3221)
8000 (3629)
9800 (4445)
10 000 (4536)
10 800 (4899)
11 500 (5216)

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

1500 (680)
2300 (1043)
2800 (1270)
3200 (1452)
3600 (1633)
3700 (1678)
4100 (1860)
4200 (1905)

3000 (1361)
4000 (1814)
5100 (2313)
5500 (2495)
6000 (2722)
6500 (2948)
6900 (3130)
7300 (3311)

5100 (2313)
6500 (2948)
7700 (3493)
8500 (3856)
9000 (4082)
9500 (4309)
9900 (4491)
10 000 (4536)

1500 (680)
2000 (907)
2900 (1315)
3700 (1678)
4200 (1905)
4700 (2132)
5100 (2313)
5500 (2495)

3000 (1361)
4000 (1814)
5400 (2449)
7000 (3175)
7800 (3538)
8400 (3810)
8800 (3992)
9100 (4128)

5200 (2359)
6300 (2858)
8400 (3810)
9700 (4400)
11 000 (4990)
11 000 (4990)
12 000 (5443)
12 000 (5443)

  1. Capacities are based in pounds/hour (kg/h) of saturated steam.

Table 18. Water Capacities(1) in GPM (l/min) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with Elastomer Diaphragm
PRESSURE
RECOMMENDED
OUTLET
Outlet
PRESSURE
Inlet
Setting,
RANGE,
Psig/Psi
psig/PSI (bar)
Psig (bar)
(bar)

2 to 6
(0,14 to 0,41)

5 to 15
(0,35 to 1,0)

REGULATOR BODY SIZE, NPS (dn)
1/4

1/2 (15)

3/4 (20)

1 (25)

Droop

Droop

Droop

Droop

10%

20%

10%

20%

10%

20%

10%

20%

5 (0,35)

10
20
30
50
75
100
150
200
250

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

1.0 (3,8)
2.0 (7,6)
2.3 (8,7)
2.7 (10,2)
2.7 (10,2)
2.7 (10,2)
2.7 (10,2)
2.7 (10,2)
2.7 (10,2)

1.8 (6,8)
3.0 (11,4)
3.3 (12,5)
3.5 (13,2)
3.5 (13,2)
3.5 (13,2)
3.5 (13,2)
3.5 (13,2)
3.5 (13,2)

2.0 (7,6)
2.8 (10,6)
3.3 (12,5)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)

3.3 (12,5)
4.0 (15,1)
4.7 (17,8)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)

5.0 (18,9)
7.5 (28,4)
10 (37,8)
11 (41,6)
11 (41,6)
11 (41,6)
11 (41,6)
11 (41,6)
11 (41,6)

7.0 (26,5)
11 (41,6)
13 (49,2)
17 (64,3)
20 (75,7)
22 (83,3)
22 (83,3)
22 (83,3)
22 (83,3)

5.8 (22,0)
9.2 (34,8)
12 (45,4)
13 (49,2)
13 (49,2)
13 (49,2)
13 (49,2)
13 (49,2)
13 (49,2)

8.3 (31,4)
13 (49,2)
16 (60,6)
20 (75,7)
23 (87,1)
27 (102)
27 (102)
27 (102)
27 (102)

10 (0,69)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

1.8 (6,8)
2.5 (9,5)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)

2.7 (10,2)
3.5 (13,2)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)

3.7 (14,0)
4.0 (15,1)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)

5.0 (18,9)
5.2 (19,7)
5.3 (20,1)
5.3 (20,1)
5.3 (20,1)
5.3 (20,1)
5.3 (20,1)
5.3 (20,1)

7.0 (26,5)
10 (37,8)
12 (45,4)
12 (45,4)
12 (45,4)
12 (45,4)
12 (45,4)
12 (45,4)

10 (37,8)
13 (49,2)
17 (64,3)
20 (75,7)
22 (83,3)
22 (83,3)
22 (83,3)
22 (83,3)

8.3 (31,4)
12 (45,4)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)

12 (45,4)
16 (60,6)
20 (75,7)
25 (94,6)
27 (102)
27 (102)
27 (102)
27 (102)

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.8.

- continued -

29

Bulletin 71.1:95
Table 18. Water Capacities(1) in GPM (l/min) for NPS 1/4 through 1 (DN 25) Types 95L and 95LD Regulators with
Elastomer Diaphragm (continued)
PRESSURE
RECOMMENDED
OUTLET/
Outlet/
DIFFERENTIAL Differential
Inlet
PRESSURE
Setting,
RANGE,
Psig/Psi
Psig (bar)
psig/PSI (bar)
(bar)

5 to 15
(0,35 to 1,0)

13 to 30
(0,90 to 2,1)

REGULATOR BODY SIZE, NPS (dn)
1/4

1/2 (15)

Droop

3/4 (20)

Droop

1 (25)

Droop

Droop

10%

20%

10%

20%

10%

20%

10%

20%

15 (1,0)

20
30
50
75
100
150
200
250

(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

1.8 (6,8)
2.7 (10,2)
3.5 (13,2)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)
3.7 (14,0)

2.2 (8,3)
3.3 (12,5)
4.3 (16,3)
4.5 (17,0)
4.5 (17,0)
4.5 (17,0)
4.5 (17,0)
4.5 (17,0)

3.5 (13,2)
4.7 (17,8)
4.8 (18,2)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)

5.0 (18,9)
5.8 (22,0)
6.2 (23,5)
6.3 (23,8)
6.3 (23,8)
6.3 (23,8)
6.3 (23,8)
6.3 (23,8)

7.0 (26,5)
11 (41,6)
15 (56,8)
15 (56,8)
15 (56,8)
15 (56,8)
15 (56,8)
17 (64,3)

8.5 (32,2)
13 (49,2)
17 (64,3)
22 (83,3)
28 (106)
32 (121)
35 (132)
35 (132)

8.3 (31,4)
13 (49,2)
18 (68,1)
18 (68,1)
18 (68,1)
18 (68,1)
18 (68,1)
20 (75,7)

10 (37,8)
15 (56,8)
20 (75,7)
27 (102)
33 (125)
37 (140)
42 (159)
42 (159)

20 (1,4)

30
40
50
75
100
150
200
250

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

2.0 (7,6)
2.7 (10,2)
3.3 (12,5)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)
3.8 (14,4)

2.9 (11,0)
3.8 (14,4)
4.7 (17,8)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)

4.3 (16,3)
5.2 (19,7)
5.5 (20,8)
5.5 (20,8)
5.5 (20,8)
5.5 (20,8)
5.5 (20,8)
5.5 (20,8)

5.8 (22,0)
6.7 (25,4)
7.2 (27,3)
7.2 (27,3)
7.2 (27,3)
7.2 (27,3)
7.2 (27,3)
7.2 (27,3)

10 (37,8)
13 (49,2)
14 (53,0)
18 (68,1)
22 (83,3)
23 (87,1)
23 (87,1)
25 (94,6)

11 (41,6)
13 (49,2)
17 (64,3)
20 (75,7)
27 (102)
32 (121)
37 (140)
38 (144)

12 (45,4)
15 (56,8)
17 (64,3)
22 (83,3)
25 (94,6)
27 (102)
27 (102)
30 (114)

13 (49,2)
16 (60,6)
20 (75,7)
25 (94,6)
32 (121)
38 (144)
43 (163)
45 (170)

25 (1,7)

40
50
75
100
150
200
250

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

2.6 (9,8)
3.3 (12,5)
3.7 (14,0)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)

3.5 (13,2)
4.3 (16,3)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)

5.2 (19,7)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)
5.8 (22,0)

7.5 (28,4)
7.8 (29,5)
8.0 (30,3)
8.0 (30,3)
8.0 (30,3)
8.0 (30,3)
8.0 (30,3)

13 (49,2)
14 (53,0)
22 (83,3)
23 (87,1)
28 (106)
33 (125)
35 (132)

13 (49,2)
16 (60,6)
22 (83,3)
27 (102)
32 (121)
38 (144)
41 (155)

15 (56,8)
17 (64,3)
25 (94,6)
28 (106)
33 (125)
40 (151)
42 (159)

16 (60,6)
19 (71,9)
27 (102)
32 (121)
38 (144)
45 (170)
48 (182)

30 (2,1)

40
50
75
100
150
200
250

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)

2.3 (8,7)
3.2 (12,1)
4.3 (16,3)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)
4.8 (18,2)

3.0 (11,4)
4.0 (15,1)
5.7 (21,6)
6.3 (23,8)
6.3 (23,8)
6.3 (23,8)
6.3 (23,8)

5.3 (20,1)
6.5 (24,6)
6.7 (25,4)
6.7 (25,4)
6.7 (25,4)
6.7 (25,4)
6.7 (25,4)

7.3 (27,6)
8.3 (31,4)
9.2 (34,8)
9.2 (34,8)
9.2 (34,8)
9.2 (34,8)
9.2 (34,8)

10 (37,8)
13 (49,2)
20 (75,7)
24 (90,8)
32 (121)
37 (140)
40 (151)

12 (45,4)
15 (56,8)
22 (83,3)
27 (102)
33 (125)
40 (151)
43 (163)

12 (45,4)
16 (60,6)
23 (87,1)
28 (106)
37 (140)
43 (163)
47 (178)

14 (53,0)
18 (68,1)
25 (94,6)
32 (121)
40 (151)
47 (178)
50 (189)

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.8.

Table 19. Water Capacities(1) in GPM (l/min) or NPS 1/4 through 1/2 (DN 15) Types 95H and 95HD Regulators with Elastomer Diaphragm
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi (bar)

regulator body size, NPS (dn)

Inlet

1/2 (15)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

1.0 (3,8)
1.5 (5,7)
2.0 (7,6)
3.0 (11,4)
3.2 (12,1)
3.2 (12,1)
3.2 (12,1)
3.2 (12,1)
3.2 (12,1)

1.8 (6,8)
2.0 (7,6)
2.2 (8,3)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)
4.2 (15,9)

3.2 (12,1)
3.6 (13,6)
3.8 (14,4)
5.2 (19,7)
5.2 (19,7)
5.2 (19,7)
5.2 (19,7)
5.5 (20,8)
5.5 (20,8)

2.0 (7,57)
3.0 (11,4)
4.0 (15,1)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)
5.1 (19,3)
5.1 (19,3)
5.2 (19,7)

3.2 (12,1)
5.0 (18,9)
5.5 (20,8)
6.5 (24,6)
6.5 (24,6)
6.5 (24,6)
6.5 (24,6)
6.6 (25,0)
6.6 (25,0)

6.8 (25,7)
7.0 (26,5)
7.2 (27,3)
7.4 (28,0)
7.6 (28,8)
7.8 (29,5)
8.0 (30,3)
8.5 (32,2)
9.0 (34,1)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

1.0 (3,8)
1.2 (4,5)
2.5 (9,5)
3.5 (13,2)
4.0 (15,1)
4.0 (15,1)
4.0 (15,1)
4.0 (15,1)

1.8 (6,8)
2.0 (7,6)
3.3 (12,5)
3.8 (14,4)
4.2 (15,9)
5.0 (18,9)
5.0 (18,9)
5.0 (18,9)

2.5 (9,5)
2.8 (10,6)
4.7 (17,8)
7.0 (26,5)
9.0 (34,1)
10 (37,8)
11 (41,6)
12 (45,4)

2.8 (10,6)
3.5 (13,2)
4.0 (15,1)
5.0 (18,9)
6.0 (22,7)
6.5 (24,6)
6.5 (24,6)
7.0 (26,5)

4.9 (18,5)
5.7 (21,6)
5.9 (22,3)
6.1 (23,1)
6.5 (24,6)
6.9 (26,1)
7.0 (26,5)
7.5 (28,4)

9.5 (36,0)
10 (37,8)
13 (49,2)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)

15 to 30
(1,0 to 2,1)

Psig (bar)

1/4

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.6.

- continued -

30

Bulletin 71.1:95
Table 19. Water Capacities(1) in GPM (l/min) for NPS 1/4 through 1/2 (DN 15) Types 95H and 95HD Regulators
with Elastomer Diaphragm (continued)
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi
(bar)

Inlet
Psig (bar)

1/4

1/2 (15)

Droop

Droop

10%

20%

40%

10%

20%

40%

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

2.0 (7,6)
3.0 (11,4)
3.2 (12,1)
4.0 (15,1)
4.8 (18,2)
5.0 (18,9)
5.0 (18,9)

3.0 (11,4)
3.5 (13,2)
3.8 (14,4)
5.0 (18,9)
6.0 (22,7)
7.0 (26,5)
8.0 (30,3)

3.5 (13,2)
4.0 (15,1)
4.5 (17,0)
8.5 (32,2)
9.2 (34,8)
11 (41,6)
12 (45,4)

4.0 (15,1)
5.0 (18,9)
5.5 (20,8)
6.0 (22,7)
6.5 (24,6)
7.0 (26,5)
7.3 (27,6)

6.5 (24,6)
8.6 (32,6)
9.0 (34,1)
9.5 (36,0)
10 (37,8)
11 (41,6)
11 (41,6)

12 (45,4)
12 (45,4)
13 (49,2)
13 (49,2)
14 (53,0)
14 (53,0)
15 (56,8)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

2.0 (7,6)
2.5 (9,5)
3.5 (13,2)
4.3 (16,3)
6.5 (24,6)
6.5 (24,6)

4.0 (15,1)
4.2 (15,9)
5.5 (20,8)
6.7 (25,4)
10 (37,8)
11 (41,6)

6.5 (24,6)
7.5 (28,4)
8.5 (32,2)
9.1 (34,4)
12 (45,4)
13 (49,2)

9.5 (36,0)
10 (37,8)
11 (41,6)
11 (41,6)
11 (41,6)
11 (41,6)

12 (45,4)
14 (53,0)
15 (56,8)
15 (56,8)
15 (56,8)
15 (56,8)

15 (56,8)
18 (68,1)
21 (79,5)
23 (87,1)
23 (87,1)
23 (87,1)

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

2.5 (9,5)
2.7 (10,2)
2.8 (10,6)
3.0 (11,4)
3.5 (13,2)
4.4 (16,7)

4.0 (15,1)
4.0 (15,1)
4.2 (15,9)
5.1 (19,3)
5.5 (20,8)
6.6 (25,0)

5.8 (22,0)
6.7 (25,4)
7.2 (27,3)
8.5 (32,2)
9.6 (36,3)
10 (37,8)

7.0 (26,5)
8.0 (30,3)
9.0 (34,1)
9.5 (36,0)
10 (37,8)
11 (41,6)

11 (41,6)
14 (53,0)
15 (56,8)
15 (56,8)
16 (60,6)
16 (60,6)

16 (60,6)
19 (71,9)
21 (79,5)
23 (87,1)
24 (90,8)
24 (90,8)

125 (8,6)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

2.0 (7,6)
2.1 (8,0)
2.2 (8,3)
3.6 (13,6)
3.7 (14,0)
4.0 (15,1)

3.3 (12,5)
3.6 (13,6)
4.5 (17,0)
6.0 (22,7)
7.0 (26,5)
8.2 (31,0)

6.0 (22,7)
6.8 (25,7)
8.5 (32,2)
9.3 (35,2)
9.9 (37,5)
11 (41,6)

7.8 (29,5)
9.0 (34,1)
9.5 (36,0)
10 (37,8)
11 (41,6)
12 (45,4)

12 (45,4)
15 (56,8)
16 (60,6)
18 (68,1)
18 (68,1)
18 (68,1)

18 (68,1)
20 (75,7)
23 (87,1)
25 (94,6)
26 (98,4)
28 (106)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

2.5 (9,5)
2.6 (9,8)
3.0 (11,4)
3.5 (13,2)
4.0 (15,1)

3.9 (14,8)
4.2 (15,9)
5.0 (18,9)
5.7 (21,6)
7.0 (26,5)

6.5 (24,6)
7.2 (27,3)
9.0 (34,1)
9.9 (37,5)
11 (41,6)

8.7 (32,9)
10 (37,8)
12 (45,4)
13 (49,2)
13 (49,2)

14 (53,0)
17 (64,3)
19 (71,9)
20 (75,7)
20 (75,7)

19 (71,9)
22 (83,3)
24 (90,8)
26 (98,4)
28 (106)

25 to 75
(1,7 to 5,2)

70 to 150
(4,8 to 10,3)

regulator body size, NPS (dn)

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.6.

Table 19. Water Capacities(1) in GPM (l/min) for NPS 3/4 through 1 (DN 20 through 25) Types 95H and 95HD Regulators
with Elastomer Diaphragm (continued)
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

15 to 30
(1,0 to 2,1)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi
(bar)

15 (1,0)

regulator body size, NPS (dn)

Inlet
Psig (bar)
30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

3/4 (20)

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

7.0 (26,5)
8.0 (30,3)
9.0 (34,1)
12 (45,4)
13 (49,2)
15 (56,8)
19 (71,9)
20 (75,7)
20 (75,7)

10 (37,8)
12 (45,4)
14 (53,0)
18 (68,1)
19 (71,9)
22 (83,3)
25 (94,6)
27 (102)
28 (106)

15 (56,8)
18 (68,1)
20 (75,7)
26 (98,4)
28 (106)
31 (117)
35 (132)
37 (140)
40 (151)

8.0 (30,3)
8.0 (30,3)
8.5 (32,2)
13 (49,2)
19 (71,9)
25 (94,6)
32 (121)
33 (125)
34 (129)

11 (41,6)
13 (49,2)
15 (56,8)
21 (79,5)
26 (98,4)
36 (136)
37 (140)
37 (140)
38 (144)

16 (60,6)
20 (75,7)
23 (87,1)
29 (110)
34 (129)
42 (159)
44 (167)
46 (174)
48 (182)

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.6.

- continued -

31

Bulletin 71.1:95
Table 19. Water Capacities(1) in GPM (l/min) for NPS 3/4 through 1 (DN 20 through 25) Types 95H and 95HD Regulators
with Elastomer Diaphragm (continued)
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

15 to 30
(1,0 to 2,1)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi
(bar)

Inlet
Psig (bar)

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

9.0 (34,1)
11 (41,6)
15 (56,8)
17 (64,3)
21 (79,5)
24 (90,8)
25 (94,6)
26 (98,4)

13 (49,2)
16 (60,6)
21 (79,5)
24 (90,8)
30 (114)
31 (117)
35 (132)
36 (136)

17 (64,3)
21 (79,5)
28 (106)
33 (125)
40 (151)
46 (174)
49 (185)
53 (201)

8.5 (32,2)
11 (41,6)
16 (60,6)
19 (71,9)
30 (114)
35 (132)
36 (136)
37 (140)

14 (53,0)
18 (68,1)
25 (94,6)
31 (117)
39 (148)
48 (182)
53 (201)
54 (204)

17 (64,3)
22 (83,3)
29 (110)
34 (129)
42 (159)
49 (185)
55 (208)
60 (227)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

9.0 (34,1)
12 (45,4)
15 (56,8)
23 (87,1)
24 (90,8)
26 (98,4)
25 (94,6)

14 (53,0)
20 (75,7)
24 (90,8)
32 (121)
34 (129)
39 (148)
40 (151)

20 (75,7)
25 (94,6)
31 (117)
40 (151)
47 (178)
51 (193)
55 (208)

12 (45,4)
14 (53,0)
16 (60,6)
20 (75,7)
30 (114)
33 (125)
40 (151)

17 (64,3)
21 (79,5)
26 (98,4)
36 (136)
42 (159)
49 (185)
55 (208)

23 (87,1)
27 (102)
34 (129)
42 (159)
49 (185)
55 (208)
60 (227)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

16 (60,6)
20 (75,7)
23 (87,1)
28 (106)
32 (121)
33 (125)

23 (87,1)
29 (110)
33 (125)
41 (155)
43 (163)
49 (185)

28 (106)
33 (125)
39 (148)
47 (178)
52 (197)
56 (212)

16 (60,6)
21 (79,5)
24 (90,8)
29 (110)
37 (140)
39 (148)

24 (90,8)
31 (117)
37 (140)
46 (174)
50 (189)
56 (212)

30 (114)
36 (136)
42 (159)
49 (185)
55 (208)
60 (227)

100 (6,9)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

15 (56,8)
17 (64,3)
24 (90,8)
25 (94,6)
29 (110)
33 (125)

24 (90,8)
27 (102)
28 (106)
37 (140)
42 (159)
48 (182)

30 (114)
35 (132)
40 (151)
45 (170)
52 (197)
57 (216)

16 (60,6)
21 (79,5)
24 (90,8)
27 (102)
30 (114)
36 (136)

24 (90,8)
30 (114)
33 (125)
41 (155)
42 (159)
43 (163)

32 (121)
38 (144)
43 (163)
48 (182)
54 (204)
58 (220)

125 (8,6)

125
150
175
200
250
300

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)

19 (71,9)
23 (87,1)
27 (102)
32 (121)
34 (129)
36 (136)

25 (94,6)
32 (121)
36 (136)
40 (151)
44 (167)
47 (178)

32 (121)
37 (140)
42 (159)
47 (178)
51 (193)
57 (216)

17 (64,3)
22 (83,3)
24 (90,8)
29 (110)
32 (121)
38 (144)

27 (102)
33 (125)
35 (132)
38 (144)
42 (159)
44 (167)

35 (132)
40 (151)
47 (178)
49 (185)
53 (201)
59 (223)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

21 (79,5)
24 (90,8)
29 (110)
30 (114)
35 (132)

28 (106)
33 (125)
37 (140)
41 (155)
49 (185)

34 (129)
40 (151)
45 (170)
50 (189)
55 (208)

20 (75,7)
24 (90,8)
29 (110)
34 (129)
41 (155)

26 (98,4)
34 (129)
39 (148)
45 (170)
53 (201)

37 (140)
42 (159)
48 (182)
52 (197)
59 (223)

25 to 75
(1,7 to 5,2)

70 to 150
(4,8 to 10,3)

regulator body size, NPS (dn)
3/4 (20)

  1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.6.

Table 20. Water Capacities in GPM (l/min) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95H and 95HD Regulators
with Either Elastomer or Stainless Steel Diaphragm
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

5 to 80
(0,35 to 5,5)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi
(bar)

5 (0,35)

regulator body size, NPS (dn)

Inlet
Psig (bar)
10
20
30
50
75
100
150
200
250
300

(0,69)
(1,4)
(2,1)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

4.8 (18,2)
6.2 (23,5)
7.5 (28,4)
9.5 (36,0)
12 (45,4)
14 (53,0)
16 (60,6)
18 (68,1)
19 (71,9)
20 (75,7)

5.2 (19,7)
7.0 (26,5)
8.3 (31,4)
10 (37,8)
13 (49,2)
15 (56,8)
18 (68,1)
20 (75,7)
22 (83,3)
24 (90,8)

7.4 (28,0)
8.5 (32,2)
9.5 (36,0)
12 (45,4)
15 (56,8)
17 (64,3)
20 (75,7)
23 (87,1)
25 (94,6)
28 (106)

4.8 (18,2)
6.5 (24,6)
8.0 (30,3)
10 (37,8)
12 (45,4)
14 (53,0)
17 (64,3)
18 (68,1)
25 (94,6)
33 (125)

5.2 (19,7)
7.1 (26,9)
9.0 (34,1)
12 (45,4)
14 (53,0)
15 (56,8)
20 (75,7)
21 (79,5)
27 (102)
40 (151)

7.6 (28,8)
10 (37,8)
12 (45,4)
15 (56,8)
16 (60,6)
18 (68,1)
22 (83,3)
23 (87,1)
30 (114)
45 (170)

- continued -

32

Bulletin 71.1:95
Table 20. Water Capacities in GPM (l/min) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95H and 95HD Regulators with Either
Elastomer or Stainless Steel Diaphragm (continued)
RECOMMENDED
OUTLET/
DIFFERENTIAL
PRESSURE
RANGE,
PSIG/PSI (bar)

PRESSURE
Outlet/
Differential
Setting,
Psig/Psi
(bar)

100 to 140
(6,9 to 9,7)

120 to 150
(8,3 to 10,3)

Inlet
Psig (bar)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

8.0 (30,3)
10 (37,8)
12 (45,4)
14 (53,0)
17 (64,3)
21 (79,5)
23 (87,1)
24 (90,8)
25 (94,6)

9.0 (34,1)
11 (41,6)
13 (49,2)
18 (68,1)
21 (79,5)
27 (102)
32 (121)
34 (129)
35 (132)

11 (41,6)
14 (53,0)
18 (68,1)
25 (94,6)
32 (121)
43 (163)
52 (197)
54 (204)
55 (208)

7.0 (26,5)
9.5 (36,0)
11 (41,6)
15 (56,8)
18 (68,1)
21 (79,5)
24 (90,8)
27 (102)
32 (121)

10 (37,8)
13 (49,2)
15 (56,8)
19 (71,9)
22 (83,3)
28 (106)
31 (117)
40 (151)
50 (189)

14 (53,0)
17 (64,3)
20 (75,7)
26 (98,4)
32 (121)
40 (151)
43 (163)
50 (189)
65 (246)

30 (2,1)

40
50
75
100
150
200
250
300

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

13 (49,2)
15 (56,8)
18 (68,1)
21 (79,5)
24 (90,8)
27 (102)
30 (114)
33 (125)

18 (68,1)
21 (79,5)
26 (98,4)
30 (114)
36 (136)
41 (155)
47 (178)
55 (208)

27 (102)
30 (114)
40 (151)
49 (185)
64 (242)
80 (303)
110 (416)
130 (492)

13 (49,2)
14 (53,0)
18 (68,1)
22 (83,3)
26 (98,4)
30 (114)
31 (117)
32 (121)

18 (68,1)
20 (75,7)
25 (94,6)
30 (114)
36 (136)
41 (155)
45 (170)
52 (197)

27 (102)
30 (114)
39 (148)
48 (182)
63 (238)
77 (291)
90 (341)
110 (416)

50 (3,4)

60
75
100
150
200
250
300

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)

17 (64,3)
20 (75,7)
25 (94,6)
34 (129)
42 (159)
50 (189)
56 (212)

29 (110)
33 (125)
40 (151)
50 (189)
61 (231)
71 (269)
82 (310)

51 (193)
58 (220)
68 (257)
87 (329)
110 (416)
130 (492)
160 (606)

16 (60,6)
19 (71,9)
24 (90,8)
32 (121)
42 (159)
50 (189)
55 (208)

29 (110)
32 (121)
38 (144)
49 (185)
62 (235)
73 (276)
83 (314)

51 (193)
56 (212)
65 (246)
84 (318)
110 (416)
140 (530)
160 (606)

75 (5,2)

100
125
150
200
250
300

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)

19 (71,9)
31 (117)
38 (144)
52 (197)
57 (216)
65 (246)

30 (114)
56 (212)
65 (246)
74 (280)
85 (322)
95 (360)

60 (227)
85 (322)
110 (416)
120 (454)
140 (530)
160 (606)

20 (75,7)
27 (102)
34 (129)
45 (170)
56 (212)
68 (257)

30 (114)
49 (185)
60 (227)
71 (269)
85 (322)
100 (378)

60 (227)
85 (322)
110 (416)
120 (454)
140 (530)
160 (606)

100 (6,9)

125
150
175
225
250
300

(8,6)
(10,3)
(12,1)
(15,5)
(17,2)
(20,7)

23 (87,1)
41 (155)
40 (151)
52 (197)
62 (235)
70 (265)

30 (114)
44 (167)
55 (208)
83 (314)
96 (363)
100 (378)

75 (284)
87 (329)
100 (378)
130 (492)
140 (530)
180 (681)

24 (90,8)
33 (125)
41 (155)
54 (204)
65 (246)
100 (378)

32 (121)
45 (170)
57 (216)
84 (318)
100 (378)
130 (492)

76 (288)
89 (337)
110 (416)
130 (492)
140 (530)
160 (606)

125 (8,6)

150
175
200
225
250
300

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

28 (106)
29 (110)
30 (114)
36 (136)
38 (144)
39 (148)

51 (193)
60 (227)
64 (242)
70 (265)
76 (288)
82 (310)

80 (303)
90 (341)
110 (416)
110 (416)
120 (454)
140 (530)

29 (110)
31 (117)
33 (125)
36 (136)
45 (170)
69 (261)

52 (197)
61 (231)
71 (269)
82 (310)
95 (360)
120 (454)

83 (314)
95 (360)
110 (416)
120 (454)
130 (492)
150 (568)

150 (10,3)

175
200
225
250
300

(12,1)
(13,8)
(15,5)
(17,2)
(20,7)

29 (110)
32 (121)
35 (132)
40 (151)
55 (208)

52 (197)
55 (208)
63 (238)
70 (265)
94 (356)

90 (341)
100 (378)
110 (416)
120 (454)
140 (530)

33 (125)
34 (129)
37 (140)
43 (163)
55 (208)

54 (204)
58 (220)
64 (242)
73 (276)
95 (360)

92 (348)
100 (378)
110 (416)
130 (492)
150 (568)

5 to 80
(0,35 to 5,5)

60 to 120
(4,1 to 8,3)

regulator body size, NPS (dn)
1-1/2 (40)

33

Bulletin 71.1:95
Table 21. Water Capacities(1) in GPM (l/min) for NPS 1/4 through 1/2 (DN 15) Type 95HP Regulators with Elastomer Diaphragm
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (DN)
1/4

Inlet
Psig (bar)

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

0.6 (2,3)
0.9 (3,4)
1.2 (4,5)
1.4 (5,3)
1.8 (6,8)
2.4 (9,1)
2.8 (10,6)
2.9 (11,0)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)
3.0 (11,4)

1.3 (4,9)
1.5 (5,7)
1.8 (6,8)
2.6 (9,8)
3.0 (11,4)
4.0 (15,1)
4.8 (18,2)
5.0 (18,9)
5.2 (19,7)
5.5 (20,8)
5.5 (20,8)
5.5 (20,8)

2.9 (11,0)
3.1 (11,7)
3.2 (12,1)
4.5 (17,0)
5.0 (18,9)
6.4 (24,2)
7.0 (26,5)
8.0 (30,3)
9.0 (34,1)
10 (37,8)
11 (41,6)
12 (45,4)

2.6 (9,8)
2.7 (10,2)
2.8 (10,6)
3.0 (11,4)
3.5 (13,2)
4.0 (15,1)
4.8 (18,2)
4.8 (18,2)
4.5 (17,0)
5.4 (20,4)
5.6 (21,2)
6.2 (23,5)

3.2 (12,1)
3.5 (13,2)
3.8 (14,4)
4.6 (17,4)
5.0 (18,9)
5.5 (20,8)
6.0 (22,7)
6.2 (23,5)
6.2 (23,5)
6.5 (24,6)
6.7 (25,4)
7.0 (26,5)

5.2 (19,7)
5.5 (20,8)
6.2 (23,5)
6.6 (25,0)
7.0 (26,5)
7.0 (26,5)
7.7 (29,1)
7.8 (29,5)
7.5 (28,4)
7.8 (29,5)
8.0 (30,3)
8.5 (32,2)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1.0 (3,8)
1.4 (5,3)
2.0 (7,6)
2.4 (9,1)
2.7 (10,2)
3.0 (11,4)
4.0 (15,1)
4.4 (16,7)
4.4 (16,7)
4.4 (16,7)
4.4 (16,7)

2.0 (7,6)
2.4 (9,1)
3.7 (14,0)
4.1 (15,5)
5.0 (18,9)
5.5 (20,8)
6.0 (22,7)
6.5 (24,6)
6.5 (24,6)
6.5 (24,6)
6.5 (24,6)

3.7 (14,0)
4.0 (15,1)
5.5 (20,8)
6.7 (25,4)
8.0 (30,3)
10 (37,8)
11 (41,6)
12 (45,4)
12 (45,4)
13 (49,2)
13 (49,2)

2.6 (9,8)
3.0 (11,4)
4.0 (15,1)
4.5 (17,0)
5.0 (18,9)
5.8 (22,0)
6.0 (22,7)
6.0 (22,7)
6.5 (24,6)
6.6 (25,0)
6.9 (26,1)

4.4 (16,6)
5.0 (18,9)
6.2 (23,5)
6.5 (24,6)
7.0 (26,5)
7.2 (27,3)
8.0 (30,3)
8.2 (31,0)
8.4 (31,8)
8.6 (32,6)
8.7 (32,9)

7.2 (27,3)
7.8 (29,5)
8.8 (33,3)
9.8 (37,1)
10 (37,8)
10 (37,8)
11 (41,6)
11 (41,6)
11 (41,6)
12 (45,4)
11 (41,6)

75 (5,2)

100
125
150
200
250
300
400
500
600

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

2.8 (10,6)
3.3 (12,5)
4.3 (16,3)
4.8 (18,2)
5.6 (21,2)
5.8 (22,0)
6.0 (22,7)
6.1 (23,1)
6.2 (23,5)

4.5 (17,0)
5.8 (22,0)
6.7 (25,4)
8.2 (31,0)
10 (37,8)
11 (41,6)
11 (41,6)
11 (41,6)
11 (41,6)

5.9 (22,3)
7.2 (27,3)
8.3 (31,4)
10 (37,8)
12 (45,4)
13 (49,2)
15 (56,8)
15 (56,8)
16 (60,6)

5.5 (20,8)
6.2 (23,5)
6.5 (24,6)
8.0 (30,3)
8.2 (31,0)
8.7 (32,9)
8.8 (33,3)
8.7 (32,9)
9.0 (34,1)

9.0 (34,1)
10 (37,8)
12 (45,4)
12 (45,4)
12 (45,4)
12 (45,4)
12 (45,4)
13 (49,2)
13 (49,2)

13 (49,2)
16 (60,6)
18 (68,1)
19 (71,9)
19 (71,9)
19 (71,9)
19 (71,9)
19 (71,9)
20 (75,7)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

3.1 (11,7)
4.0 (15,1)
4.8 (18,2)
5.5 (20,8)
6.4 (24,2)
7.0 (26,5)
7.3 (27,6)
7.5 (28,4)
7.5 (28,4)

4.9 (18,5)
6.4 (24,2)
7.5 (28,4)
8.0 (30,3)
9.7 (36,7)
11 (41,6)
11 (41,6)
12 (45,4)
12 (45,4)

6.4 (24,2)
7.5 (28,4)
8.6 (32,6)
9.2 (34,8)
11 (41,6)
12 (45,4)
15 (56,8)
15 (56,8)
16 (60,6)

6.4 (24,2)
7.0 (26,5)
8.0 (30,3)
8.2 (31,0)
9.0 (34,1)
9.3 (35,2)
9.3 (35,2)
9.3 (35,2)
10 (37,8)

11 (41,6)
12 (45,4)
13 (49,2)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)
14 (53,0)
15 (56,8)

16 (60,6)
18 (68,1)
21 (79,5)
21 (79,5)
22 (83,3)
22 (83,3)
22 (83,3)
23 (87,1)
23 (87,1)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

1.5 (5,68)
2.0 (7,57)
2.4 (9,08)
2.4 (9,08)
3.0 (11,4)
3.6 (13,6)
3.6 (13,6)
3.7 (14,0)
4.6 (17,4)

2.8 (10,6)
3.4 (12,9)
3.8 (14,4)
4.2 (15,9)
4.8 (18,2)
5.3 (20,1)
6.0 (22,7)
6.1 (23,1)
7.0 (26,5)

5.6 (21,2)
6.6 (25,0)
6.8 (25,7)
7.0 (26,5)
8.2 (31,0)
9.0 (34,1)
9.5 (36,0)
10 (37,8)
12 (45,4)

5.5 (20,8)
5.7 (21,6)
6.0 (22,7)
6.2 (23,5)
6.4 (24,2)
6.5 (24,6)
8.0 (30,3)
7.8 (29,5)
9.1 (34,4)

7.5 (28,4)
8.5 (32,2)
9.0 (34,1)
9.5 (36,0)
10 (37,8)
10 (37,8)
12 (45,4)
12 (45,4)
13 (49,2)

14 (53,0)
15 (56,8)
16 (60,6)
17 (64,3)
17 (64,3)
17 (64,3)
18 (68,1)
20 (75,7)
22 (83,3)

200 (13,8)

225
250
300
400
500
600

(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

2.6 (9,84)
2.8 (10,6)
3.4 (12,9)
4.0 (15,1)
4.6 (17,4)
5.8 (22,0)

4.6 (17,4)
4.8 (18,2)
6.2 (23,5)
6.8 (25,7)
7.5 (28,4)
9.3 (35,2)

8.0 (30,3)
8.3 (31,4)
9.9 (37,5)
12 (45,4)
13 (49,2)
15 (56,8)

7.0 (26,5)
7.2 (27,3)
7.8 (29,5)
10 (37,8)
10 (37,8)
11 (41,6)

11 (41,6)
12 (45,4)
12 (45,4)
16 (60,6)
16 (60,6)
17 (64,3)

18 (68,1)
19 (71,9)
21 (79,5)
25 (94,6)
25 (94,6)
28 (106)

250 (17,2)

275
300
400
500
600

(19,0)
(20,7)
(27,6)
(34,5)
(41,4)

3.2 (12,1)
3.4 (12,9)
3.8 (14,4)
5.0 (18,9)
6.4 (24,2)

5.4 (20,4)
5.8 (22,0)
7.2 (27,3)
9.0 (34,1)
10 (37,8)

8.5 (32,2)
9.4 (35,6)
12 (45,4)
14 (53,0)
16 (60,6)

7.8 (29,5)
8.0 (30,3)
10 (37,8)
11 (41,6)
12 (45,4)

13 (49,2)
14 (53,0)
16 (60,6)
18 (68,1)
20 (75,7)

21 (79,5)
22 (83,3)
28 (106)
30 (114)
31 (117)

15 to 100
(1,0 to 6,9)

80 to 300
(5,5 to 20,7)

  1. To obtain capacities for regulator with metal diaphragms or for Type 95HT, multiply the table values by 0.6.

- continued -

34

1/2 (15)

Droop

Bulletin 71.1:95
Table 21. Water Capacities(1) in GPM (l/min) for NPS 1/4 through 1/2 (DN 15) Type 95HP Regulators
with Elastomer Diaphragm (continued)
REcOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (DN)

Inlet
Psig (bar)

1/4

1/2 (15)

Droop

Droop

10%

20%

40%

10%

20%

40%

(24,1)
(27,6)
(34,5)
(41,4)

3.8 (14,4)
4.0 (15,1)
5.2 (19,7)
6.5 (24,6)

7.0 (26,5)
7.5 (28,4)
9.0 (34,1)
11 (41,6)

11 (41,6)
12 (45,4)
14 (53,0)
16 (60,6)

9.5 (36,0)
10 (37,8)
10 (37,8)
13 (49,2)

15 (56,8)
17 (64,3)
19 (71,9)
21 (79,5)

24 (90,8)
27 (102)
29 (110)
33 (125)

5.3 (20,1)
6.6 (25,0)

9.2 (34,8)
12 (45,4)

14 (53,0)
17 (64,3)

11 (41,6)
14 (53,0)

20 (75,7)
22 (83,3)

30 (114)
35 (132)

80 to 300
(5,5 to 20,7)

300 (20,7)

350
400
500
600

80 to 400
(5,5 to 27,6)
Type 95HP only

400 (27,6)

500 (34,5)
600 (41,4)

1. To obtain capacities for regulator with metal diaphragms or for Type 95HT, multiply the table values by 0.6.

Table 21. Water Capacities(1) in GPM (l/min) for NPS 3/4 through 1 (DN 20 through 25) Type 95HP Regulators
with Elastomer Diaphragm (continued)
REcOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (DN)
Inlet

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

4.5 (17,0)
4.5 (17,0)
5.5 (20,8)
5.5 (20,8)
7.0 (26,5)
9.0 (34,1)
11 (41,6)
11 (41,6)
13 (49,2)
16 (60,6)
18 (68,1)
24 (90,8)

6.0 (22,7)
7.0 (26,5)
7.8 (29,5)
9.0 (34,1)
11 (41,6)
13 (49,2)
16 (60,6)
15 (56,8)
19 (71,9)
23 (87,1)
26 (98,4)
33 (125)

9.5 (36,0)
11 (41,6)
12 (45,4)
15 (56,8)
17 (64,3)
20 (75,7)
21 (79,5)
21 (79,5)
23 (87,1)
27 (102)
33 (125)
42 (159)

4.0 (15,1)
5.0 (18,9)
6.5 (24,6)
7.0 (26,5)
7.3 (27,6)
11 (41,6)
10 (37,8)
12 (45,4)
15 (56,8)
20 (75,7)
19 (71,9)
18 (68,1)

6.0 (22,7)
7.0 (26,5)
8.5 (32,2)
11 (41,6)
13 (49,2)
17 (64,3)
17 (64,3)
23 (87,1)
26 (98,4)
26 (98,4)
27 (102)
30 (114)

9.8 (37,1)
11 (41,6)
14 (53,0)
17 (64,3)
21 (79,5)
25 (94,6)
32 (121)
35 (132)
36 (136)
37 (140)
37 (140)
41 (155)

30 (2,1)

40
50
75
100
150
200
250
300
400
500
600

(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

5.2 (19,7)
6.0 (22,7)
7.0 (26,5)
9.0 (34,1)
12 (45,4)
14 (53,0)
16 (60,6)
17 (64,3)
16 (60,6)
23 (87,1)
30 (114)

7.3 (27,6)
10 (37,8)
13 (49,2)
16 (60,6)
19 (71,9)
21 (79,5)
24 (90,8)
22 (83,3)
25 (94,6)
33 (125)
38 (144)

15 (56,8)
17 (64,3)
20 (75,7)
24 (90,8)
28 (106)
30 (114)
31 (117)
32 (121)
34 (129)
44 (167)
51 (193)

5.5 (20,8)
7.0 (26,5)
9.0 (34,1)
11 (41,6)
13 (49,2)
14 (53,0)
18 (68,1)
21 (79,5)
24 (90,8)
25 (94,6)
30 (114)

8.0 (30,3)
11 (41,6)
15 (56,8)
19 (71,9)
24 (90,8)
26 (98,4)
33 (125)
34 (129)
39 (148)
40 (151)
42 (159)

14 (53,0)
17 (64,3)
23 (87,1)
30 (114)
35 (132)
44 (167)
47 (178)
52 (197)
54 (204)
56 (212)
58 (220)

75 (5,2)

100
125
150
200
250
300
400
500
600

(6,9)
(8,6)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

12 (45,4)
15 (56,8)
17 (64,3)
20 (75,7)
24 (90,8)
25 (94,6)
26 (98,4)
36 (136)
39 (148)

20 (75,7)
23 (87,1)
27 (102)
31 (117)
35 (132)
38 (144)
38 (144)
49 (185)
52 (197)

27 (102)
32 (121)
37 (140)
43 (163)
48 (182)
51 (193)
58 (220)
64 (242)
72 (273)

14 (53,0)
17 (64,3)
21 (79,5)
24 (90,8)
29 (110)
37 (140)
39 (148)
39 (148)
39 (148)

21 (79,5)
26 (98,4)
32 (121)
38 (144)
44 (167)
49 (185)
53 (201)
57 (216)
57 (216)

28 (106)
35 (132)
40 (151)
47 (178)
51 (193)
57 (216)
60 (227)
65 (246)
70 (265)

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

15 (56,8)
18 (68,1)
20 (75,7)
23 (87,1)
29 (110)
32 (121)
32 (121)
33 (125)
44 (167)

23 (87,1)
28 (106)
31 (117)
34 (129)
38 (144)
44 (167)
48 (182)
49 (185)
61 (231)

29 (110)
35 (132)
39 (148)
43 (163)
49 (185)
54 (204)
63 (238)
64 (242)
77 (291)

17 (64,3)
21 (79,5)
24 (90,8)
28 (106)
36 (136)
39 (148)
41 (155)
41 (155)
41 (155)

24 (90,8)
30 (114)
36 (136)
38 (144)
47 (178)
53 (201)
61 (231)
61 (231)
61 (231)

32 (121)
37 (140)
42 (159)
45 (170)
51 (193)
57 (216)
65 (246)
66 (250)
70 (265)

15 to 100
(1,0 to 6,9)

Psig (bar)

3/4 (20)

  1. To obtain capacities for regulators with metal diaphragms or for Type 95HT, multiply the table values by 0.6.

- continued -

35

Bulletin 71.1:95
Table 21. Water Capacities(1) in GPM (l/min) for NPS 3/4 through 1 (DN 20 through 25) Type 95HP Regulators
with Elastomer Diaphragm (continued)
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

80 to 300
(5,5 to 20,7)

80 to 400
(5,5 to 27,6)
Type 95HP only

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (DN)

Inlet
Psig (bar)

3/4 (20)

1 (25)

Droop

Droop

10%

20%

40%

10%

20%

40%

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

9.0 (34,1)
12 (45,4)
13 (49,2)
15 (56,8)
16 (60,6)
17 (64,3)
19 (71,9)
24 (90,8)
28 (106)

16 (60,6)
20 (75,7)
22 (83,3)
24 (90,8)
27 (102)
28 (106)
35 (132)
36 (136)
40 (151)

28 (106)
31 (117)
33 (125)
39 (148)
41 (155)
43 (163)
47 (178)
51 (193)
59 (223)

13 (49,2)
13 (49,2)
16 (60,6)
16 (60,6)
18 (68,1)
21 (79,5)
22 (83,3)
23 (87,1)
28 (106)

19 (71,9)
22 (83,3)
25 (94,6)
27 (102)
30 (114)
35 (132)
38 (144)
40 (151)
42 (159)

32 (121)
36 (136)
41 (155)
44 (167)
47 (178)
51 (193)
55 (208)
56 (212)
62 (235)

200 (13,8)

225
250
300
400
500
600

(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

16 (60,6)
17 (64,3)
19 (71,9)
24 (90,8)
25 (94,6)
30 (114)

25 (94,6)
28 (106)
31 (117)
38 (144)
40 (151)
45 (170)

37 (140)
42 (159)
47 (178)
56 (212)
61 (231)
70 (265)

17 (64,3)
20 (75,7)
22 (83,3)
28 (106)
29 (110)
30 (114)

25 (94,6)
30 (114)
35 (132)
44 (167)
45 (170)
46 (174)

40 (151)
41 (155)
51 (193)
65 (246)
67 (254)
72 (273)

250 (17,2)

275
300
400
500
600

(19,0)
(20,7)
(27,6)
(34,5)
(41,4)

19 (71,9)
19 (71,9)
23 (87,1)
27 (102)
31 (117)

29 (110)
31 (117)
37 (140)
42 (159)
48 (182)

41 (155)
44 (167)
56 (212)
64 (242)
74 (280)

20 (75,7)
23 (87,1)
29 (110)
30 (114)
32 (121)

31 (117)
34 (129)
45 (170)
48 (182)
50 (189)

44 (167)
48 (182)
62 (235)
70 (265)
74 (280)

300 (20,7)

350
400
500
600

(24,1)
(27,6)
(34,5)
(41,4)

21 (79,5)
24 (90,8)
27 (102)
32 (121)

35 (132)
39 (148)
43 (163)
51 (193)

47 (178)
53 (201)
60 (227)
75 (284)

24 (90,8)
27 (102)
31 (117)
35 (132)

38 (144)
44 (167)
50 (189)
55 (208)

50 (189)
58 (220)
70 (265)
74 (280)

400 (27,6)

500 (34,5)
600 (41,4)

27 (102)
33 (125)

44 (167)
53 (201)

64 (242)
77 (291)

32 (121)
38 (144)

51 (193)
58 (220)

70 (265)
76 (288)

  1. To obtain capacities for regulators with metal diaphragms or for Type 95HT, multiply the table values by 0.6.

Table 22. Water Capacities in GPM (l/min) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95HT (Metal Diaphragm) and 95HP
(Elastomer Diaphragm) Regulators
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)

Inlet

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

15 (1,0)

30
40
50
75
100
150
200
250
300
400
500
600

(2,1)
(2,8)
(3,5)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

9.0 (34,1)
11 (41,6)
12 (45,4)
14 (53,0)
16 (60,6)
22 (83,3)
30 (114)
35 (132)
37 (140)
40 (151)
43 (163)
45 (170)

12 (45,4)
13 (49,2)
15 (56,8)
18 (68,1)
22 (83,3)
31 (117)
40 (151)
47 (178)
51 (193)
58 (220)
65 (246)
71 (269)

18 (68,1)
19 (71,9)
21 (79,5)
25 (94,6)
29 (110)
39 (148)
50 (189)
65 (246)
85 (322)
120 (454)
140 (530)
140 (530)

11 (41,6)
12 (45,4)
13 (49,2)
15 (56,8)
18 (68,1)
29 (110)
50 (189)
70 (265)
85 (322)
45(1) (170)(1)
47(1) (178)(1)
50(1) (189)(1)

14 (53,0)
16 (60,6)
17 (64,3)
21 (79,5)
26 (98,4)
50 (189)
92 (348)
95 (360)
100 (378)
63(1) (238)(1)
67(1) (254)(1)
70(1) (265)(1)

21 (79,5)
24 (90,8)
28 (106)
35 (132)
45 (170)
85 (322)
120 (454)
120 (454)
120 (454)
75(1) (284)(1)
77(1) (291)(1)
80(1) (303)(1)

50 (3,4)

60
75
100
150
200
250
300
400
500
600

(4,1)
(5,2)
(6,9)
(10,3)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

20 (75,7)
23 (87,1)
26 (98,4)
34 (129)
40 (151)
47 (178)
52 (197)
62 (235)
71 (269)
76 (288)

28 (106)
33 (125)
39 (148)
50 (189)
60 (227)
67 (254)
75 (284)
85 (322)
100 (378)
110 (416)

50 (189)
57 (216)
67 (254)
86 (326)
110 (416)
130 (492)
150 (568)
190 (719)
240 (908)
240 (908)

19 (71,9)
23 (87,1)
30 (114)
45 (170)
58 (220)
72 (273)
85 (322)
85(1) (322)(1)
92(1) (348)(1)
100(1) (378)(1)

31 (117)
38 (144)
52 (197)
80 (303)
100 (378)
120 (454)
130 (492)
110(1) (416)(1)
110(1) (416)(1)
120(1) (454)(1)

56 (212)
69 (261)
89 (337)
130 (492)
160 (606)
180 (681)
190 (719)
140(1) (530)(1)
140(1) (530)(1)
140(1) (530)(1)

15 to 100
(1,0 to 6,9)

Psig (bar)

1-1/2 (40)

  Gray areas indicate limited capacities due to boost effects.

- continued 36

Bulletin 71.1:95
Table 22. Water Capacities in GPM (l/min) for NPS 1-1/2 through 2 (DN 40 through 50) Types 95HT (Metal Diaphragm) and 95HP
(Elastomer Diaphragm) Regulators
RECOMMENDED
OUTLET
PRESSURE
RANGE,
PSIG (bar)

15 to 100
(1,0 to 6,9)

60 to 260
(4,1 to 17,9)

60 to 300
(4,1 to 20,7)
Type 95HP only

pressure
Outlet
Setting,
Psig (bar)

regulator body size, NPS (dn)

Inlet
Psig (bar)

1-1/2 (40)

2 (50)

Droop

Droop

10%

20%

40%

10%

20%

40%

100 (6,9)

125
150
175
200
250
300
400
500
600

(8,6)
(10,3)
(12,1)
(13,8)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

37 (140)
45 (170)
49 (185)
54 (204)
63 (238)
70 (265)
85 (322)
90 (341)
100 (378)

57 (216)
65 (246)
70 (265)
80 (303)
95 (360)
110 (416)
130 (492)
140 (530)
160 (606)

95 (360)
110 (416)
120 (454)
130 (492)
160 (606)
180 (681)
220 (833)
240 (908)
260 (984)

45 (170)
55 (208)
65 (246)
73 (276)
90 (341)
110 (416)
93(1) (352)(1)
100(1) (378)(1)
110(1) (416)(1)

75 (284)
110 (416)
120 (454)
140 (530)
170 (643)
190 (719)
120(1) (454)(1)
130(1) (492)(1)
140(1) (530)(1)

100 (378)
120 (454)
130 (492)
150 (568)
170 (643)
190 (719)
170 (1) (643)(1)
170(1) (643)(1)
180(1) (681)(1)

125 (8,6)

150
175
200
225
250
300
400
500
600

(10,3)
(12,1)
(13,8)
(15,5)
(17,2)
(20,7)
(27,6)
(34,5)
(41,4)

28 (106)
29 (110)
31 (117)
34 (129)
38 (144)
45 (170)
58 (220)
65 (246)
71 (269)

42 (159)
45 (170)
50 (189)
55 (208)
61 (231)
71 (269)
90 (341)
100 (378)
110 (416)

68 (257)
71 (269)
77 (291)
84 (318)
95 (360)
120 (454)
150 (568)
170 (643)
180 (681)

24 (90,8)
31 (117)
36 (136)
42 (159)
47 (178)
55 (208)
62 (235)
70 (265)
200 (757)

49 (185)
55 (208)
63 (238)
70 (265)
80 (303)
95 (360)
230 (871)
240 (908)
270 (1022)

84 (318)
87 (329)
91 (344)
96 (363)
110 (416)
140 (530)
240 (908)
260 (984)
290 (1098)

200 (13,8)

225
250
300
350
400
450
500
600

(15,5)
(17,2)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(41,4)

40 (151)
45 (170)
52 (197)
54 (204)
60 (227)
75 (284)
83 (314)
91 (344)

60 (227)
75 (284)
88 (333)
90 (341)
100 (378)
120 (454)
130 (492)
140 (530)

110 (416)
120 (454)
130 (492)
150 (568)
180 (681)
190 (719)
200 (757)
210 (795)

46 (174)
50 (189)
58 (220)
72 (273)
74 (280)
95 (360)
110 (416)
150 (568)

72 (273)
80 (303)
96 (363)
110 (416)
160 (606)
180 (681)
200 (757)
280 (1060)

120 (454)
130 (492)
150 (568)
170 (643)
220 (833)
240 (908)
260 (984)
290 (1098)

250 (17,2)

275
300
350
400
450
500
550
600

(19,0)
(20,7)
(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

46 (174)
50 (189)
60 (227)
65 (246)
70 (265)
81 (307)
82 (310)
85 (322)

77 (291)
85 (322)
96 (363)
100 (378)
120 (454)
130 (492)
140 (530)
150 (568)

130 (492)
140 (530)
150 (568)
180 (681)
200 (757)
220 (833)
230 (871)
240 (908)

50 (189)
55 (208)
65 (246)
70 (265)
90 (341)
100 (378)
120 (454)
130 (492)

86 (326)
89 (337)
100 (378)
130 (492)
160 (606)
170 (643)
190 (719)
250 (946)

140 (530)
150 (568)
170 (643)
190 (719)
210 (795)
230 (871)
250 (946)
260 (984)

300 (20,7)

350
400
450
500
550
600

(24,1)
(27,6)
(31,0)
(34,5)
(37,9)
(41,4)

55 (208)
60 (227)
70 (265)
80 (303)
88 (333)
90 (341)

94 (356)
110 (416)
120 (454)
140 (530)
150 (568)
150 (568)

140 (530)
180 (681)
200 (757)
220 (833)
230 (871)
250 (946)

60 (227)
75 (284)
97 (367)
110 (416)
120 (454)
140 (530)

110 (416)
120 (454)
150 (568)
180 (681)
210 (795)
240 (908)

160 (606)
180 (681)
200 (757)
220 (833)
240 (908)
250 (946)

  Gray areas indicate limited capacities due to boost effects.

Ordering Information
When ordering, specify:

Application Information
  1.  Type of gas/liquid being controlled (air, ammonia, 	
water, process chemicals, etc.); list any factors 	
such as impurities in the gas/liquid that may affect 	
the compatibility with the regulator trim parts.
  2.  Specific gravity of the gas/liquid
  3.  Temperature of the gas/liquid
  4.  Range of flowing inlet pressure to regulator
  5.  Outlet pressure setting or range

  6.  Flow rates
   a.  Minimum controlled flow
   b.  Normal flow
   c.  Maximum flow
  7.  Line size and end connection size of adjacent piping

Regulator Information
Refer to the Specifications section on page 2 and
carefully review the description to the right of each
specification and in the referenced tables. Specify
the desired selection wherever there is a choice to be
made. Always specify the regulator type number.

37

Bulletin 71.1:95
d

d
d

J

c (maximum)
C (MAXimum)

c (maximum)

e-npt

body size
B
B

b

body size

AE9236-F
A0811-2 / IL

7
(178)

a

TYPE 95HD REGULATOR
(DIMENSIONS ALSO APPLY TO
TYPE 95LD REGULATOR)

a

AJ3324-H
A0810-2 / IL

14
(356)

inches
(mm)

TYPE 95H REGULATOR
(DIMENSIONS ALSO APPLY TO
TYPES 95L, 95HT AND
95HP REGULATORS)

14A4040-D / IL

FLANGED BODIES AVAILABLE IN
NPS 1/2 THROUGH 2 (DN 15 through 50)
BODY SIZES
type 95l regulator

body size,
NPS (dn)

A
Cast Iron

B

Steel/SST

Inch

mm

Inch

C

mm

Inch

mm

Inch

D
mm

Inch

mm

1/4

2.25

57

2.75

70

1.81

46

4.62

117

5.06

129

1/2 (15)

3.88

99

4.00

102

1.81

46

6.12

155

7.00

178

3/4,1
(20, 25)

4.88

124

5.00

127

2.25

57,2

9.12

232

10.19

259

1/4

2.25

57

2.75

70

1.81

46

4.50

114

3.19

81

1/2 (15)

3.88

99

4.00

102

1.81

46

6.00

152

4.25

108

3/4, 1
(20, 25)

4.88

124

5.00

127

2.25

57

9.12

232

6.06

154

1-1/2, 2
(40, 50)

7.25

184

7.38

187

2.79

71

14.69

373

8.19

208

types 95h, 95ht, and 95hp regulators

type 95ld regulator
body size,
NPS (DN)

A
Cast Iron

B

Steel

C

D

E (NPT)

J

Inch

mm

Inch

mm

Inch

mm

Inch

mm

Inch

mm

Inch

Inch

1/4

2.25

57

2.75

70

1.81

46

7.94

202

5.06

129

1/8

2.75

mm
70

1/2 (15)

3.88

99

4.00

102

1.81

46

10.12

257

7.00

178

1/4

4.00

102

3/4, 1
(20, 25)

4.88

124

5.00

127

2.25

57

15.31

389

10.19

259

1/4

4.00

102

1/4

2.25

57

2.75

70

1.81

46

7.88

200

3.19

81

1/8

2.75

70

1/2 (15)

3.88

99

4.00

102

1.81

46

10.00

254

4.25

108

1/4

4.00

102

3/4, 1
(20, 25)

4.88

124

5.00

127

2.25

57

15.12

384

6.06

154

1/4

4.00

102

1-1/2, 2
(40, 50)

7.25

184

7.38

187

2.79

71

18.31

465

8.19

208

1/4

6.75

171

type 95hd regulator

Figure 4. Dimensions

38

Bulletin 71.1:95
Ordering Guide
Type (Select One)
    95L (Low pressure)
    95LD (Low pressure differential)
    95H (High pressure)
    95HD (High pressure differential, must be steel or 	
  stainless steel construction)
    95HP (High pressure, soft-seated)
    95HT (High pressure/temperature, must be steel or 	
  stainless steel construction)
Body Size (Select One)
    1/4 NPT
    NPS 1/2 (DN 15)
    NPS 3/4 (DN 20)
    NPS 1 (DN 25)
    NPS 1-1/2 (DN 40) (not available for 95L Series)
    NPS 2 (DN 50) (not available for 95L Series)
Body Material and End Connection Style(1)
(Select One)
Cast iron
    NPT***

Spring Case Material (Select One)
    Cast iron (standard for cast iron bodies)***
    WCC Steel (standard for steel or stainless
  steel bodies)***
    CF8M Stainless steel (optional for stainless
  steel bodies)**
Trim Material – See Table 6 (Select Metal or Elastomer)
Metal Seat (Select One)
    416 Stainless steel (standard)***
    316 Stainless steel**
    Hastelloy® C*
    Monel®*
Elastomer Seat (Select one from each column)
Disk Holder	   Disk
    Brass***	      Neoprene (CR) or Nitrile (NBR)***
    416 SST***	      Fluorocarbon (FKM)
    316 SST**	      PTFE
    Hastelloy® C*     Ethylenepropylene (EPDM)*
    Monel®*	      Perfluoroelastomer (FFKM)*

WCC Steel
    NPT***
    CL150 RF**
    CL300 RF**
    PN 16/25/40**
    SWE**

Outlet or Differential Pressure Range (Select One)

CF8M Stainless steel
    NPT***
    CL150 RF**
    CL300 RF**
    PN 16/25/40**
    SWE**

  NPS 1/4 through 3/4 (DN 20) body sizes
     15 to 30 psig/psi (1,0 to 2,1 bar), Yellow***
      25 to 75 psig/psi (1,7 to 5,2 bar), Green***
     70 to 150 psig/psi (4,8 to 10,3 bar), Red***

Hastelloy® C
    NPT*
    CL150 RF*
    CL300 RF*
    PN 16/25/40*
    SWE*
Monel®
    NPT*
    CL150 RF*
    CL300 RF*
    PN 16/25/40*
    SWE*

Type 95L or 95LD
    2 to 6 psig/psi (0,14 to 0,41 bar), Yellow***
    5 to 15 psig/psi (0,35 to 1,0 bar), Green***
    13 to 30 psig/psi (0,90 to 2,1 bar), Red***
Type 95H or 95HD

  NPS 1-1/2 and 2 (DN 40 and 50) body sizes
     5 to 80 psig/psi (0,35 to 5,5 bar), Light Blue***
      60 to 120 psig/psi (4,1 to 8,3 bar), Light Gray***
     100 to 140 psig/psi (6,9 to 9,7 bar), Yellow***
     120 to 150 psig/psi (8,3 to 10,3 bar), Black***
Type 95HT
  NPS 1/4 through 3/4 (DN 20) body sizes
     15 to 100 psig (1,0 to 6,9 bar), Unpainted***
      80 to 300 psig (5,5 to 20,7 bar), Unpainted***
  NPS 1-1/2 and 2 (DN 40 and 50) body sizes
     15 to 100 psig (1,0 to 6,9 bar), Unpainted***
      60 to 260 psig (4,1 to 17,9 bar), Unpainted***

- continued 1. SWE, CL150 RF, CL300RF, and PN 16/25/40 are not available in NPS 1/4 body size.

39

Bulletin 71.1:95
Ordering Guide (Continued)
Type 95HP
  NPS 1/4 through 1 (DN 15 through 25) body sizes
     15 to 100 psig (1,0 to 6,9 bar), Unpainted***
      80 to 400 psig (5,5 to 27,6 bar), Unpainted***
  NPS 1-1/2 and 2 (DN 40 and 50) body sizes
     15 to 100 psig (1,0 to 6,9 bar), Unpainted***
      60 to 300 psig (4,1 to 20,7 bar), Unpainted***
Replacement Parts Kit (Optional)
    Yes, send one replacement parts kit to match
  this order.

Pressure:
Maximum Inlet Pressure (P1max)
Minimum Inlet Pressure (P1min)
Downstream Pressure Setting(s) (P2)
Maximum Flow (Qmax)

Regulators Quick Order Guide
***
**
*

Specification Worksheet
Application:
Specific Use
Line Size
Gas Type and Specific Gravity
Gas Temperature
Does the Application Require Overpressure Protection?
     Yes     No     If yes, which is preferred:
     Relief Valve     Monitor Regulator     Shutoff Device
Is overpressure protection equipment selection
assistance desired?

Readily Available for Shipment
Allow Additional Time for Shipment
Special Order, Constructed from Non-Stocked Parts.
Consult your local Sales Office for Availability.

Availability of the product being ordered is determined by the component with the
longest shipping time for the requested construction.

Performance Required:
Accuracy Requirements?
Need for Extremely Fast Response?
Other Requirements:

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Tescom Corporation

USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574

USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574

USA - Headquarters
Elk River, Minnesota 55330-2445 USA
Tel: 1-763-241-3238

Asia-Pacific
Shanghai, China 201206
Tel: +86 21 2892 9000

Asia-Pacific
Singapore, Singapore 128461
Tel: +65 6777 8211

Europe
Bologna, Italy 40013
Tel: +39 051 4190611

Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Gallardon, France 28320
Tel: +33 (0)2 37 33 47 00

Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100

Europe
Selmsdorf, Germany 23923
Tel: +49 (0) 38823 31 0

For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a
business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.

©Emerson Process Management Regulator Technologies, Inc., 1963, 2009; All Rights Reserved



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c006 1.236519, Wed Jun 14 2006 08:31:24
Create Date                     : 2010:02:09 17:52:03+08:00
Metadata Date                   : 2010:02:09 17:52:15+08:00
Modify Date                     : 2010:02:09 17:52:15+08:00
Creator Tool                    : Adobe InDesign CS3 (5.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 8932 bytes, use -b option to extract)
Instance ID                     : uuid:930b793c-19a4-4cb8-9a8d-5afb95e0b08a
Document ID                     : adobe:docid:indd:90d8524b-155b-11df-9f0b-87e31fff4bfd
Rendition Class                 : proof:pdf
Derived From Instance ID        : 90d8524a-155b-11df-9f0b-87e31fff4bfd
Derived From Document ID        : adobe:docid:indd:90d85249-155b-11df-9f0b-87e31fff4bfd
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 75.00, 75.00, 300.00, 300.00, 304.80, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 75.00, 75.00, 300.00, 300.00, 304.80, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:f8cb9cde-23c5-11da-bf8f-000a95badf96, uuid:D419ABBA418ADD11BC95C0D0F8DB97F4, uuid:852BE4C03C8ADD11BC95C0D0F8DB97F4, uuid:CD19ABBA418ADD11BC95C0D0F8DB97F4, uuid:6810AE83428ADD11BC95C0D0F8DB97F4, uuid:6C92E837478ADD11BC95C0D0F8DB97F4, uuid:bb6dd554-eaa3-4a50-8e69-b7c9becda979, uuid:bb6dd554-eaa3-4a50-8e69-b7c9becda979, uuid:420fdf51-1d27-4155-a02b-d53bc2c47c70, uuid:420fdf51-1d27-4155-a02b-d53bc2c47c70, uuid:9824fb24-e043-42aa-ad5a-d4725352ced6, uuid:9824fb24-e043-42aa-ad5a-d4725352ced6, uuid:efa0a845-0c3a-4132-acc6-cb48e42eb631, uuid:64ce1907-f2ec-4381-8d35-0291c7a559b0, uuid:537fcf50-1ea6-43ec-80ae-28ced0b4cfa6, uuid:dcf36ab0-c0a0-4be1-b9bf-6e639ba8df5e, uuid:1069f225-b4c1-4692-8403-5f112da1b54c, uuid:f8cb9cde-23c5-11da-bf8f-000a95badf96
Manifest Reference Document ID  : uuid:D319ABBA418ADD11BC95C0D0F8DB97F4, uuid:842BE4C03C8ADD11BC95C0D0F8DB97F4, uuid:CC19ABBA418ADD11BC95C0D0F8DB97F4, uuid:6710AE83428ADD11BC95C0D0F8DB97F4, uuid:6B92E837478ADD11BC95C0D0F8DB97F4, uuid:42B93DBC2457DD119771F87996BAE461, uuid:42B93DBC2457DD119771F87996BAE461, uuid:17D22781088BDE11920FEF4DE55FBE0C, uuid:17D22781088BDE11920FEF4DE55FBE0C, uuid:3B23B23DFB8ADD1183EB9D24B24737EF, uuid:3B23B23DFB8ADD1183EB9D24B24737EF, uuid:19003DD00C8BDD118FF6ECFB5FCE2F92, uuid:57769E97348BDE11A623AD20AD5A7FF2, uuid:DF57AE89A38BDD118757D8EF90251725, uuid:DD57AE89A38BDD118757D8EF90251725, uuid:E157AE89A38BDD118757D8EF90251725
Format                          : application/pdf
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 40
Creator                         : Adobe InDesign CS3 (5.0)
EXIF Metadata provided by EXIF.tools

Navigation menu