Industrial Power for
Business-Critical Continuity
Custom-designed AC UPS systems to secure industrial processes
The Chloride CP-60Z is available from 5 to 60kVA in single-phase or three-phase
output conguration. It offers a wide choice of DC battery voltages (110V, 220V
or 400V) and of output voltages (from 1x110 V to 3x415V) to best t the applica-
tion.
The UPS uses patented digital Vector Control technology which increases the UPS
performances, enables active conditioning of the load and allows personalised
system settings.
The Chloride CP-60Z can be adapted for project-specic requirements. A wide
choice of industrialized extras allow system customization according to the most
demanding technical specications.
To further improve load availability and process reliability, the system is able to
operate in dual parallel conguration, centralized or distributed, with single or
dual batteries, and can include AC bus-tie.
The Chloride CP-60Z industrial
Uninterruptible Power Supply (UPS)
system is the result of latest industrial
requirements combined with R&D
innovations to offer an improved
efciency and reduced operating costs
industrial UPS.
The Chloride CP range is designed to meet
the stringent electrical and mechanical
requirements in industrial environments.
Each Chloride CP product is based on inter-
changeable sub-assemblies to allow full
customization, in compliance with client’s
technical specication and with project
documentation requirements.
Benets
Energy savings - Improved efciency means
reduced power consumption and smaller air
conditioning system
Project savings - Higher input power factor and
lower inrush current allow smaller upstream
transformer, switchgear and cables and reduce
line current and losses in the cables.
Safe and easy maintenance - Segregated
manual bypass and front access to major com-
ponents improve safety and reduce MTTR
Asset Management System - The UPS is com-
patible with the Emerson AMS Suite Intelligent
Device Manager which helps to ensure an
efcient preventive maintenance
Key Features
Low Ripple Voltage to reduce battery stress
and optimize its lifetime
Low inrush current < 4In (12-pulse) not to
oversize mains power supply
SCR-based rectier, 6 or 12 pulses, with
improved operation to signicantly reduce
the mains’ pollution (THDi) and the input RMS
current
Proven reliability: The unique design allows
the UPS to continuously operate at full load at a
permanent 40°C ambient temperature
Galvanic isolation: input and output transfor-
mers are standard on the complete range.
Ingress protection IP42 is provided as
standard to operate in the most demanding
environments
Compatibility with Nickel-Cadmium and Lead-
Acid batteries, open or gas-recombination
types
Multilingual digital graphic display with
embedded event log
Wide choice of congurations, options, and
remote monitoring solutions
Applications
The Chloride CP-60Z is the best solution, both
cost effective and environmental friendly, to meet
industrial requirements of a wide range of sectors,
such as:
Oil & Gas, offshore and onshore
Rening and Petrochemical industries
Water infrastructures
Mining
Transportation (rail, metro, tramway)
Chloride CP-60Z AC UPS System
5 to 60kVA - 1ph and 3ph output
Industrial Power for
Business-Critical Continuity
Chloride CP-60Z AC UPS System
5 to 60 kVA - 1 ph and 3ph output
Options
Rectier 12-pulse SCR rectier
Special 3-ph input voltage (up to 3x690Vac)
Surge and/or lighning protections
Input circuit breaker
Battery Battery circuit protection box (Fuse or circuit breaker)
Battery reversed polarity detection
Battery Low Voltage Disconnection (LVD)
Battery black start
Battery room temperature sensor for battery charge compensation
DC earth fault detection
Output AC earth fault detection
Output fuse switch or circuit breaker
Reserve Reserve input circuit breaker
Reserve transformer (H class)
Reserve stabilizer (servo-controlled)
Stabilizer output isolator
System Dual congurations
AC distribution (circuit breakers)
Backfeed protection
Internal cabinet lighting
Auxiliary power socket
Anti-condensation heater
UPS cabinet temperature monitor
Special cabinet identication (Tag, nameplate)
Mechanical Top cable entry
Special frame color
Special feet height
Special keylock
Special gland plate
Lifting eyes
2mm panels thickness
Communication Front panel analogue meters (72x72, class 1 or class 1.5)
Transducers 4-20mA
Additional volt-free contacts
Modbus RTU (RS232 or RS485)
Modbus / TCP
Probus
IEC61850 protocol
PPVis monitoring software
AMS compatibility kit
Passive mimic panel
Active mimic panel with integrated LEDs
Special lamp indicator on front panel (22mm diameter)
Standards
Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 60950
IEC 61000-6-2 - IEC 61000-6-4
IEC 60529 / IEC 60439 / IEC 60076
Conformity EMC Directive 2004/108/CE
Low Voltage Directive (LVD) 2006/95/CE
CE Mark
Ratings - Output Power at cos phi 0.8 (kVA) vs battery voltage (Vdc)
110-120 Vdc 220-240 Vdc 400 Vdc
5 5 -
10 10 -
20 20 -
30 30 -
- 40 40
- 50 50
- 60 60
Technical Data
Input
Input voltage (other voltage on request) 400 VAC (380; 415) ±10%
Inrush current < 8 x In (6-pulse version)
< 4 x In (12-pulse version)
Power factor up to 0.94
Frequency range 50 Hz (60 Hz factory setting) ±5%
Intermediate DC circuit
Nominal DC voltage 110 / 120 / 220 / 240 / 400 VDC
Voltage stability ±1% in float mode, input within tolerance
±1.5% for parallel chargers
Voltage ripple (battery connected) 0.25% RMS, in oat mode
Current limitation I nominal
Charging characteristic IU according to DIN 41773
Output
Available ratings (see table above) from 5 to 60 kVA (at PF 0.8 lagging)
AC voltage:
Single phase
Three phase
230 VAC (220, 240) ; 110 VAC (115, 120)
400 VAC (380, 415) ; 220 VAC (190, 208)
Frequency 50 Hz (60 Hz factory setting)
Frequency stability:
with internal oscillator
with reserve synchronism
±0.05%
±3% (from 0.2 to 6% factory setting)
Voltage stability (0-100% load variation):
static
dynamic
±1% (±2% for parallel systems)
VFI SS 111 - complies to IEC62040-3, class 1
Overload inverter (in % of nominal power) 150%/1 min - 125%/10 min
Short-circuit clearance:
1-ph output (in % of nominal current)
3-ph output (in % of nominal current)
250%/100 ms - 175%/5 s
315%/100 ms - 220%/5 s (Ph-N)
Voltage distorsion:
with 100% linear load
with 100% non linear load
<3 %
≤5 % (complies with IEC 62040-1-2)
Allowable power factor 0.5 lagging to 0.5 leading
Allowable crest factor 3/1
Battery
Type Lead Acid or Nickel Cadmium,
vented or recombination
Autonomy From few minutes to several hours,
as required and specied
Battery current limitation 0.1C (lead acid) / 0.2C (Nickel Cadmium)
General Data
Rectier efciency up to 90 % (according to rating and cong.)
Operating temperature From 0 to 40 °C
Storage temperature From -20 °C to +70 °C (battery excluded)
Relative humidity <90 % non condensing at 20 °C
Operating altitude 1000 m (without system derating)
Cooling Fan-assisted with redundant monitored fans
External ingress protection IP 42
Noise less than 66 dB (according to rating)
Input / output isolation 2500 VAC / 1 minute
Frame colour RAL 7032
Dimensions Varying according to ratings and options
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson, Business-Critical Continuity and
Emerson Network Power are trademarks of
Emerson Electric Co. or one of its afliated companies.
©2013 Emerson Electric Co.
CP60Z-DSUK-Rev0-01/2013
AC Power
Connectivity
DC Power Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Embedded Computing
Embedded Power
Industrial Power Precision Cooling
Racks & Integrated Cabinets
Services
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power IS S.A.S
30 avenue Montgoler - BP90 - 69684 Chassieu Cedex - France
T: +33 (0)4 78 40 13 56 F: +33(0)4 78 90 58 90
Industrial.sales.Chloride@Emerson.com
EmersonNetworkPower.com

Navigation menu