Emerson Csb400 Series Pressure Reducing Regulators Instruction Manual

2015-03-30

: Emerson Emerson-Csb400-Series-Pressure-Reducing-Regulators-Instruction-Manual-681190 emerson-csb400-series-pressure-reducing-regulators-instruction-manual-681190 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 28

DownloadEmerson Emerson-Csb400-Series-Pressure-Reducing-Regulators-Instruction-Manual-  Emerson-csb400-series-pressure-reducing-regulators-instruction-manual
Open PDF In BrowserView PDF
CSB400 Series

Instruction Manual
Form 5836
June 2014

CSB400 Series Commercial / Industrial
Pressure Reducing Regulators

TYPICAL TYPE CSB400 REGULATOR

P1424

TYPICAL TYPE CSB403 REGULATOR WITH
INTEGRAL TRUE-MONITOR™ REGULATOR
P1426

TYPICAL TYPE CSB404 REGULATOR WITH
INTEGRAL TYPE VSX4 SLAM-SHUT MODULE

P1425

Figure 1. Typical CSB400 Series Pressure Reducing Regulators

Table of Contents

Introduction

Introduction .....................................................................1
Specifications .................................................................2
Principle of Operation .....................................................8
Installation and Overpressure Protection ..................... 11
Commissioning .............................................................15
Adjustment....................................................................15
Shutdown......................................................................17
Maintenance and Inspection.........................................19
Parts Ordering ..............................................................20
Parts List.......................................................................21

Scope of the Manual

www.fisherregulators.com

D103123X012

This Instruction Manual provides installation, maintenance
and parts ordering information for the CSB400 Series
regulators. Instructions and parts lists for other
equipment mentioned in this instruction manual are
found in separate manuals.

CSB400 Series
Specifications
The Specifications section lists the specifications for the CSB400 Series Regulators. The following information is stamped
on the nameplate of CSB400 Series: Type and Class, Maximum Outlet Pressure and Spring Range.

Available Configurations
See Table 1
Regulator Type: Differential Strength (DS)
Accuracy Class: Up to AC5
(depending on Outlet Pressure)
Lock-up Class: U
 p to SG10
(depending on Outlet Pressure)
Failure Mode: Fail Open (FO)
Body Sizes and End Connection Styles
See Table 5
Integral Strength (IS) Pressure Ratings(1)
See Table 3
Differential Strength (DS) Pressure Ratings and
Flow and Sizing Coefficients(1)
See Table 4
Operating Pressure Ranges(1)
Regulator: See Table 6
Integral True-Monitor™ Module: See Table 7
Slam-Shut Module: See Table 8
Maximum Outlet Pressures(1)
Emergency: 4.0 bar / 58 psig
To Avoid Internal Parts Damage:
Type CSB450: 1 bar / 14.5 psig above outlet
pressure setting
All other Types: 0.34 bar / 5 psig above outlet
pressure setting
Operating: 3.0 bar / 43.5 psig
Spring Case Vent Connection
1 NPT
Orifice Size

Pressure Registration
Internal, External or Dual (Internal and External)
Operating Temperature (TS)(1)(2)
According to PED Standards:
All Types: -20 to 66°C / -4 to 150°F
Non-PED with standard construction:
Types CSB400/CSB404, CSB420/CSB424:
-20 to 66°C / -4 to 150°F
Types CSB450/CSB454(3):
-30 to 66°C / -20 to 150°F
Non-PED with low temperature construction:
Types CSB400F/CSB404F(3), CSB420F/CB424F(3):
-30 to 66°C / -20 to 150°F
Approximate Weights
With Threaded body
	 Type CSB400: 4.1 kg / 9 pounds
	 Type CSB403: 9.1 kg / 20 pounds
	 Type CSB404: 5.0 kg / 11 pounds
With Flanged Body: 
Add 4.1 kg / 9 pounds to threaded weights
listed above
PED Conformity Statement and Information
The CSB400 Product Series is in conformity with the
Pressure Equipment Directive PED 97/23/EC. The
exceptions to this previous statement are the
Types CSB403 and CSB423. Both of these types are
not yet certified to conform with the PED Directive.
Pressure regulator does not require any
supplementary upstream safety accessory for
protection against overpressure compared with
its design pressure PS, when upstream reducing
station is sized for a max downstream incidental
MIPd <= 1.1 PS.
PED Related Information
See Table 2

17.5 mm / 11/16 inch
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2. Standard token relief set values listed in Table 8 are based on -20 to 60°C / -4 to 140°F.
3. Product has passed Emerson Process Management Regulator Technologies, Inc. (Regulator Technologies) testing for lockup, relief start-to-discharge and reseal down to -40°.

2

CSB400 Series
Table 1. Available Configurations
TYPE NUMBER
C

S

B

OPTIONS

4

PRESSURE CONSTRUCTION AND UPSTREAM MONITOR APPLICATIONS
0

Low Pressure Applications (Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)

1

Low Pressure, Upstream Monitoring Applications(1)(3) (Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)

2

Medium Pressure Applications (Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)

3

Medium Pressure, Upstream Monitoring Applications(1)(3) (Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)

5

High Pressure Applications(2) (Outlet Pressure: 0.50 to 3.0 bar / 7 to 43.5 psig)
OVERPRESSURE PROTECTION
0

Without Overpressure Protection Module

0F

Low Temperature Capability, Without Overpressure Protection Module

3

With Integral True-Monitor™ Module(4)

3F

Low Temperature Capability, With Integral True-Monitor Module(4)

4

With Type VSX4 Slam-shut Module(5)

4F

Low Temperature Capability, With Type VSX4 Slam-shut Module(5)
PRESSURE REGISTRATION
D

Dual Registration (Best solution for quick changing loads)

E

External Registration

I

Internal Registration
RELIEF
N

No Relief

T

Internal Token Relief

Example: Type number CSB424DT: Type CSB400 regulator constructed for medium pressure applications, with Type VSX4 slam-shut module,
Dual pressure registration and Internal Token relief.
1. Not available with Integral True-Monitor option.
2. Not available with Integral True-Monitor or Token Relief option.
3. Available with External Pressure Registration only.
4. Reference Instruction Manual D103126X012 for information regarding the Type TM600 Integral True-Monitor module.
5. Reference Instruction Manual D103127X012 for information regarding the Type VSX4 Slam-Shut module.

!

WARNING

Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or fire causing property damage and
personal injury or death.
Fisher® regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes,
rules and regulations and
Regulator Technologies instructions.
If the regulator vents gas or a leak
develops in the system, service to the unit
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service the
unit. Only a qualified person must install
or service the regulator.

Description
CSB400 Series regulators are typically installed on
industrial and commercial applications. See Table 1 for
Available Configurations. Low, Medium and High outlet
pressure constructions are available via Types CSB400,
CSB420 and CSB450, respectively, that provide outlet
setpoints ranging from 17 mbar to 3.0 bar / 7 inches w.c.
to 43.5 psig. Also available are upstream monitoring
configurations such as Types CSB410 and CSB430,
which are installed upstream of the primary regulator to
provide overpressure protection.
Types that include an “F” refer to the cold temperature
construction of the base Type number. For example, the
Type CSB404F provides a cold temperature construction
of the Type CSB404. Refer to the Operating Temperature
section found on the following page for additional
information regarding temperature capabilities and refer
to Table 7 for inlet pressure limitations. For types that
include an “F”, refer to the base type number for general
information such as Principles of Operation, Maintenance
instructions, Warnings and Cautionary notes.

3

FLUID GROUP
CAT
TEMP CLASS
SEAT

PS

FLUID GROUP

DN
PN

0062

SERIAL NO.

LOC
DOM
BODY
CATMATL
LOC

SEAT

TYPE

PSD

Pumax
TYPE
Wds
Pumax

Pmax
PSD
Matl
Case
Pmax

France
PED mfg: Chartres,
France

DN
PN

0062

TS

DOM

Std: EN334

PS

PATENT
PENDING

SERIAL NO.

REGULATOR
SLAM SHUT
TEMP CLASS

TS

PATENT
PENDING

SLAM SHUT

REGULATOR
Std: EN334

REGULATOR

REGULATOR
PED mfg: Chartres,

CSB400 Series

BODY
MATL

Wds

Matl
Case

Failure Mode
Failure Mode

Std: EN14382
SLAM SHUT

PED
mfg: Chartres,
Std:
EN14382
SLAM SHUTFrance

REGULATOR NAMEPLATES

RELAIS
RELAY

Pu Max
Max IN

PED mfg: Chartres,
France

MATL
CASERELAIS
RELAY
TYPE MATL
CASE
Wdso
OP rangeTYPE
Wdso
OP range

SLAM-SHUT NAMEPLATE

SERIAL NO.

TYPE NO.

P max
Pu Max
Max OUT
Max IN
P maxCLASS
PSD
Max OUT
Wdsu
PSD
CLASS
UP range

DOM

PATENT PENDING

LOC

MAX IN
DOM

PATENT PENDING

MAX EMER
LOC
OUT

Wdsu
UP range

MAX IN

TYPE NO.

RELIEF SERIAL NO.

ORIFICE

SPG RANGE

RELIEF
MAX OP
ORIFICE
SPG RANGE
OUT

MAX EMER
OUT

MAX OP
OUT

INTEGRAL TRUE-MONITOR NAMEPLATE

Figure 2. CSB400 Series Regulator, Slam-shut and Integral True-Monitor™ Nameplates and Labels
Table 2. PED Information
TYPE

DESCRIPTION

PED CATEGORY

FLUID GROUP

CSB400, CSB400F, CSB410, CSB420,
CSB420F, CSB430 and CSB450

Base regulator

I

CSB404, CSB404F, CSB414, CSB424,
CSB424F, CSB434 and CSB454

Regulator with Slam-Shut Module

IV

Groups 1 and 2 according to PED 97/23/EC, 1st
and 2nd family gas according to EN 437 or other
gases (compressed air, nitrogen).
The gas must be non-corrosive, clean
(filtration on inlet side necessary) and dry.

European EN Reference Standards

EN 334, EN 14382

Table 3. Integral Strength (IS) Pressure Ratings
MAXIMUM ALLOWABLE PRESSURE(1) /
MAXIMUM EMERGENCY INLET PRESSURE

TYPE

MAXIMUM OPERATING INLET PRESSURE(1)

PS

Pumax

bar

psig

bar

psig

4.0

58

4.0

58

CSB400, CSB400F, CSB404 and CSB404F
CSB420, CSB420F, CSB424 and CSB424F
CSB450 and CSB454
CSB410 and CSB414
CSB403, CSB403F, CSB423 and CSB423F
CSB403 and CSB423
1. For the Integral Strength (IS) version, the maximum value of PS and Pumax should be similar to the PSD used for the Differential Strength (DS) version.

Table 4. Differential Strength (DS) Pressure Ratings and Flow and Sizing Coefficients

TYPE

SPECIFIC MAXIMUM
ALLOWABLE
MAXIMUM
MAXIMUM
PRESSURE / MAXIMUM OPERATING INLET
EMERGENCY
EMERGENCY OUTLET
PRESSURE
INLET PRESSURE(1)
PRESSURE
PSD
bar

Pumax
psig

ORIFICE
SIZE

FLOW
COEFFICIENTS
WIDE OPEN

IEC SIZING
COEFFICIENTS

PS

bar

psig

bar

psig

CSB400F and CSB404F

6.0

87

12.0

174

CSB403F and CSB423F

6.0

87

10.0

145

10.0

145

10.0

145

mm

Inch

Cg

Cv

C1

XT

FD

FL

17.5

11/16

428

11

43

1.16

0.84

0.90

CSB403 and CSB423
CSB410 and CSB414
CSB430 and CSB434
CSB400 and CSB404
CSB420F and CSB424F
CSB420 and CSB424
CSB450 and CSB454

4.0

58
10.0

145

12.0

174

16.0

232

20.0

290

1. If ordered with a PN 16 flanged connection, PS rating is a maximum of 16.0 bar / 232 psig. PS rating may be lower than 16.0 bar / 232 psig as indicated by this table.

4

CSB400 Series
Table 5. Body Sizes, Material, End Connections and Pressure Ratings
BODY MATERIAL

INLET SIZE, NPS

OUTLET SIZE, NPS

1
1-1/4
1-1/2
2
1
1
1-1/4
1-1/2
2

1
1-1/4
1-1/2
2
1
1-1/4
1-1/4
1-1/2
2

DN 50 / 2

DN 50 / 2

DN 40 / 1-1/2(1)
1
1
1-1/4
1-1/2
1
1-1/4
1-1/2

DN 40 / 1-1/2(1)
2-1/4
1
1-1/4
1-1/2
1
1-1/4
1-1/2

Ductile Iron

WCC Steel

FACE-TO-FACE DIMENSION
mm
Inch
100
4
114
4.5
114
4.5
127
5
100
4
114
4.5
114
4.5
114
4.5
127
5
254
10
254
10
184
7.24
105
4.1
100
4
114
4.5
114
4.5
100
4
114
4.5
114
4.5

END CONNECTION

NPT

Rp

CL150 FF
PN 10/16
PN 16 Slip-On
Rp x GAZ
NPT

Rp

BODY PRESSURE RATING
bar
psig

20.0

290

16.0

232

20.0

290

1. Uses Rp 1-1/2 x 1-1/2 threaded body with PN 16 slip-on flanges.

Table 6. CSB400 Series Primary Regulator Outlet Pressure Ranges
OPERATING PRESSURE
RANGES, Wd

TYPE

SPRING
COLOR

SPRING WIRE
DIAMETER

SPRING FREE LENGTH

mbar

Inch w.c.

mm

Inch

mm

Inch

17 to 24

6.8 to 9.6

GE30191X012

Pink

2.03

0.080

152

6.00

24 to 35

9.6 to 14

GE43955X012

Orange Stripe

2.19

0.086

110

4.35

35 to 60

14 to 24.1

GE30201X012

Dark Green

3.23

0.127

110

4.35

54 to 100

21.7 to 40

GE30202X012

Tan

2.85

0.112

127

5.00

100 to 160

1.45 to 2.3 psig

GE35081X012

Purple Stripe

3.86

0.152

124

4.90

138 to 300

2.0 to 4.4 psig

GE30192X012

Dark Blue

4.27

0.168

118

4.65

276 to 517

4 to 7.5 psig

GE33121X012

Red

4.93

0.194

118

4.65

500 mbar to 1 bar

7.3 to 14.5 psig

GE30203X012

Light Blue

5.59

0.220

102

4.00

1 to 3 bar

14.5 to 43.5 psig

GE30204X012

Light Green

6.73

0.265

100

3.95

CSB400, CSB400F,
CSB403, CSB403F,
CSB404, CSB404F,
CSB410 and CSB414
CSB420, CSB420F,
CSB423, CSB423F,
CSB424, CSB424F,
CSB430 and CSB434
CSB450 and CSB454

PART
NUMBER

Table 7. Primary Regulator and Integral True-Monitor™ Outlet Pressure Ranges
PRIMARY REGULATOR
TYPE

CSB403
and
CB403F

CSB423
and
CB423F

Factory Setpoint

Set Pressure Range
Color

P/N

Pink

GE30191X012

mbar

psig

mbar

psig

20

8 in w.c.

17 to 24

6.8 to
9.6 in w.c.

24 to 35

9.6 to
14 in w.c.

Orange
GE43955X012
Stripe

35 to 60

14 to
24 in w.c.

Dark
Green

30

50

12 in w.c.

20 in w.c.

0.78 to
1.45

69

1

54 to 100

138

2

100 to 160 1.45 to 2.3

% of
REG. Set

Tan

GE30201X012

GE30202X012

Purple
GE35081X012
Stripe

207

3

138 to 300 2.0 to 4.4

345

5

276 to 517

Red

GE30192X012

GE33121X012

mbar

psig

No Token Relief
170%

Dark
Blue

4 to 7.5

INTEGRAL TRUE-MONITOR
Factory Token Relief Set(1)

35

14 in w.c.

No Token Relief
150%

45

18 in w.c.

No Token Relief
140%

70

1

No Token Relief
130%

90

1.3

No Token Relief
130%

180

2.6

No Token Relief
125%

260

3.8

No Token Relief
125%

430

6.25

Factory Setpoint(1)

Spring Range
Color

P/N

12 to
21 in w.c.

Blue

GE30189X012

45 to 75

18 to
30 in w.c.

Green

GE30196X012

1

65 to 99

26 to
40 in w.c.

Orange

GE30225X012

103

1.5

97 to 200

138

2

97 to 200

1.4 to 2.9

Black

GE30190X012

172

2.5

97 to 200

241

3.5

197 to 255

2.6 to 3.7

Purple

GE35081X012

276

4

345

5

248 to 414

3.6 to 6

Dark
Blue

GE30192X012

352 to 517

5.1 to 7.5

Red

GE33121X012

mbar

psig

mbar

psig

37

15 in w.c.

30 to 52

52

21 in w.c.

70

414

6

448

6.5

1. Recommended minimum Integral True-Monitor setpoints shown.

5

CSB400 Series
Table 8. Regulator and Slam-shut OPSO and UPSO Pressure Ranges
REGULATOR

SLAM-SHUT MODULE
Overpressure Shutoff (OPSO)

TYPE

CSB404,
CSB404F
and
CSB414

CSB424,
CSB424F
and
CSB434

CSB454(3)

Set Pressure
Range

mbar

psig

17 to
24

0.25 to
0.35

24 to
35

0.35 to
0.51

35 to
60

0.51 to
0.87

54 to
100

0.8 to
1.5

100 to
160

1.5 to
2.3

138 to
300

Standard
Setpoints

Token Relief
Set(1)(2)

mbar

psig

mbar

psig

20

0.29

34

0.49

Available
Token Relief
Minimum
Range Shown
Required
as a % of
Difference
Regulator
between Token
Setpoint
Relief and
OPSO Set
Min(2)

Max

mbar

psig

170%

215%

8

0.12

mbar

psig

43

0.62

OPSO Set
Range as a %
of Regulator
Setpoint

Min

Max

215%

270%

Standard
UPSO Set
Values(1) Pdsu

mbar

psig

10

0.15

21

0.30

36

0.52

45

0.65

11

0.16

27

0.39

41

0.59

51

0.74

14

0.20

30

0.44

45

0.65

57

0.83

15

0.22

35

0.50

53

0.76

67

0.96

18

0.26

50

0.70

70

1.0

90

1.3

25

0.36

30

0.44

38

0.54

50

0.73

75

1.1

80

1.2

150%

140%
60

0.87

84

1.2

75

1.10

98

1.4
130%

100

1.5

130

1.9

150

2.2

195

2.8
130%

160%

158%

140%

140%

10

16

20

40

160

2.3

208

3.0

2.0 to
4.4

300

4.4

375

5.4

125%

140%

50

276 to
517

4.0 to
7.5

500

7.3

625

9.1

125%

140%

500 to
1000

7.3 to
14.5

1000

14.5

----

----

----

1200

17.4

----

----

1500

21.6

----

2000

29.0

3000

43.5

1000 to 14.5 to
3000
43.5

Standard
OPSO Set
Values(1) Pdso

Underpressure Shutoff (UPSO)

0.14

0.23

190%

180%
108

1.57

128

1.85

0.29

170%
170

2.47

248

3.59

0.58

165%

200%

200%

190%

175%

UPSO Set
Range as a %
of Regulator
Setpoint

Min

Max

50%

56%

50%

60%

50%

70%

50%

70%

50%

70%

264

3.83

0.73

450

6.53

150%

165%

150

2.2

50%

70%

60

0.87

700

10.2

140%

180%

250

3.6

50%

70%

----

----

----

1320

19.2

112%

140%

500

7.3

50%

70%

----

----

----

----

1600

23.2

112%

133%

600

8.7

----

----

----

----

----

1900

27.6

112%

127%

750

10.9
50%

70%

----

----

----

----

----

----

2400

34.8

112%

120%

1000

14.5

----

----

----

----

----

----

3400

49.3

112%

113%

1500

21.8

1. Standard factory set shown. Factory set is at the Minimum value of the range indicated. Range indicated is a percentage of Setpoint. Percentage indicated is based on the Set Pressure Range
in which that setpoint resides. If non-standard sets are required, adherence must be made to constraints shown in Table 7, including Token Relief Set Range, OPSO and UPSO set range and
Minimum Required difference between Token Relief and OPSO Set.
2. Minimum Token Relief values apply to -20 to 60°C / -4 to 140°F service temperatures. For service below -20°C / -4°F, add 8 mbar / 0.12 psig to the minimum Token Relief value listed.
3. Token Relief is not available for the Type CSB454.

Example: If a non-standard setpoint is needed, see the following example for the proper use of Table 8.
Non-standard setpoint = 140 mbar / 2 psig, using the value presented above, the factory set of the token relief will be
1.3 x 140 = 182 mbar / 2.6 psig. The factory OPSO and UPSO set pressures are 165% and 50% of the non-standard
setpoint, respectively. The resulting settings are: OPSO = 231 mbar / 3.4 psig and UPSO = 70 mbar / 1 psig.

6

CSB400 Series
205 /
8.09

208 /
8.18

SPRING
REMOVAL(1)

SPRING
REMOVAL(2)

249 /
9.81
152 /
5.97

146 /
5.77

291 /
11.46
A
A

B

A/2

SLAM-SHUT
MODULE

A/2

171 /
6.72
275 /
10.81

54 /
2.13

307 /
12.08

45 /
1.79

151 /
5.95
A

A

A
A/2

A/2

A/2

1 NPT
SCREENED
VENT

TRUE-MONITOR™
MODULE

GE34270

mm / INCH

1. MAXIMUM SPRING REMOVAL CLEARANCE FOR BOTH THE PRIMARY REGULATOR AND INTEGRAL TRUE-MONITOR IS 158 mm / 6.2 inches.
2. MAXIMUM SPRING REMOVAL CLEARANCE FOR THE SLAM SHUT IS 80 mm / 3.1 inches.

Figure 3. CSB400 Series Dimensions

Table 9. CSB400 Series Dimensions

BODY SIZE, NPS

BODY END
CONNECTION STYLE

FACE-TO-FACE DIAMETER (A)
mm

Inch

1

100

4

1-1/4

114

4.5

1-1/2

NPT or Rp

2
DN 50 / 2

CL150 FF or PN 10/16

114

4.5

127

5

254

10

PITOT TUBE (B)
mm

Inch

97

3.8

1 x 1-1/4

Rp

114

4.5

1 x 2-1/4

Rp x GAZ

105

4.1

20

0.8

DN 40 / 1-1/2

PN 16 Slip-On

184

7.2

97

3.8

7

CSB400 Series

REGULATOR
ADJUSTING SCREW
REGULATOR
CONTROL SPRING

REGULATOR
ORIFICE

TOKEN RELIEF SPRING
REGULATOR
DISK

PUSHER POST

BALANCED PORT
ASSEMBLY

M1143

INLET PRESSURE

LEVER

EXTERNAL CONTROL LINE
(SENSE LINE)

VALVE STEM

OUTLET PRESSURE
ATMOSPHERIC PRESSURE

Figure 4. Type CSB400DT Dual Registered Regulator Operational Schematic

Additional overpressure protection options include
Types CSB403 and CSB423, which offer True-Monitor™
protection provided by an integral monitor module installed
on the inlet side of the valve body. This Integral True-Monitor
assumes control of the pressure to the downstream
system should the primary regulator fail to regulate. The
Types CSB404, CSB424 and CSB454 are examples of
CSB400 Series configurations that offer a slam-shut module
that shuts off the flow of gas to the downstream system in
the event of outlet pressure rising above or falling below the
predefined levels due to a failure.
Optional token relief is available, which acts as a lowcapacity internal relief valve to relieve minor overpressure
situations due to nicks or other minor damage to the
orifice or disk, or due to thermal expansion of the
downstream system.
Internal, external or dual outlet pressure registration is
available. Constructions with dual or external registration
require an external control line / sense line. For quick
changing loads, dual sense is recommended as it
provides the quickest response time.

8

Principle of Operation
Type CSB400 Base Regulator Operation
Refer to Figure 4. When downstream demand
decreases, the pressure under the regulator diaphragm
increases. This pressure overcomes the regulator
setting (which is set by the regulator control spring).
Through the action of the pusher post assembly, lever
and valve stem, the valve disk moves closer to the
orifice and reduces gas flow. If demand downstream
increases, pressure under the regulator diaphragm
decreases. Spring force pushes the pusher post
assembly downward, the valve disk moves away from
the orifice, and the gas flow increases downstream
as the regulator opens in response to the decreased
pressure underneath the regulator diaphragm.
Type numbers with a “T”, for example, Type CSB400IT,
provide a token or low-capacity relief. The Token relief
provides relief from minor overpressure caused by nicks
or dents on the orifice or by thermal expansion of gas in
the downstream line. Token relief also provides a token or
signal, in the form of odor, that an overpressure situation
is occurring.

CSB400 Series

REGULATOR
ADJUSTING SCREW

MONITOR ADJUSTING SCREW
REGULATOR ORIFICE

REGULATOR
CONTROL SPRING

MONITOR CONTROL SPRING

TOKEN RELIEF
SPRING
MONITOR DISK

EXTERNAL CONTROL
LINE (SENSE LINE)

MONITOR
LEVER

MONITOR
VALVE STEM

REGULATOR
VALVE STEM

MONITOR ORIFICE

MONITOR
OPENING SPRING

BALANCED PORT
ASSEMBLY

WIDE-OPEN INTEGRAL TRUE-MONITOR REGULATOR

PRESSURE RETAINING
PLUG (DO NOT
REMOVE WHILE UNIT
REGULATOR
IS PRESSURIZED)
LEVER
REGULATOR
PUSHER POST

PRIMARY REGULATOR

M1145

INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE

Figure 5. Type CSB403IT Internally Registered Primary Regulator with Externally Registered Integral True-Monitor™ Operational Schematic

OPSO ADJUSTING SCREW

OPSO SET SPRING

UPSO ADJUSTING SCREW

REGULATOR
ADJUSTING SCREW

UPSO SPRING
REGULATOR
CONTROL SPRING

SLAM-SHUT
ORIFICE

VENT

TOKEN RELIEF
SPRING

SENSE BLOCKING
SCREW

PROXIMITY
SWITCH PLUG

RESET KNOB
SLAM-SHUT DISK

VALVE STEM
REGULATOR ORIFICE

TYPE VSX4 SLAM-SHUT MODULE

LEVER

EXTERNAL CONTROL
LINE (SENSE LINE)

PRIMARY REGULATOR

M1146

INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE

Figure 6. Type CSB404ET Externally Registered Regulator and Slam-shut Operational Schematic

9

CSB400 Series
PROTECT VENT PIPE
WITH RAIN CAP

CSB400 SERIES
REGULATOR

NPS 2 TYPE 289H
RELIEF VALVE

REGULATOR VENT
POINTED DOWNWARD
GE27692

Figure 7. CSB400 Series Regulator Installed with the Vent Pointed Downward and with a
Type 289H Relief Valve for High Capacity Relief

Type CSB403 Integral
True-Monitor™ Operation
Type CSB403 combines the operation of a conventional
two-regulator wide-open monitor set into one body, see
Figure 5. The Integral True-Monitor is installed on the
inlet side of the body and serves to throttle flow and
maintain an acceptable downstream pressure in the
case where the primary regulator ceases to regulate
downstream pressure. During normal operation the
Integral True-Monitor is in a wide-open state as its
setpoint is set higher than the primary regulator. See
Table 7 for guidance regarding the setpoints of the
regulator and associated Integral True-Monitor sets.
If the downstream pressure should rise to the setpoint of
the Internal Monitor due to a loss of pressure control by
the primary regulator, the Integral True-Monitor
will assume control and regulate the flow to the
downstream system. If token relief is present, it will
relieve a small amount of gas to the atmosphere as an
indication that the Integral True-Monitor is controlling the
downstream pressure.
The Type CSB403 provides the option of internal or
external downstream pressure registration. External
registration requires a downstream sensing line. See
Figure 9 for guidance regarding installation of the
downstream control line. Refer to the Type TM600
Instruction Manual for additional details of Integral
True-Monitor operation.

10

Type CSB404 Slam-shut Operation
The Type VSX4 slam-shut module on the Type CSB404
regulator is a fast acting shut-off device that provides
overpressure (OPSO) or over and underpressure
(OPSO / UPSO) protection by completely shutting off the
flow of gas to the downstream system. See Table 8 for
guidance regarding the typical setpoints of the regulator
and associated slam-shut OPSO and also the combined
OPSO and UPSO setpoints. The Type VSX4’s actions
are independent of the Type CSB404 regulator and of
variations to the inlet pressure. The Type VSX4 comes
standard with external downstream pressure registration,
with the option for internal registration only on the Rp 1
x 2-1/4 GAZ body. External registration requires a
downstream sensing line. See Figure 10 for guidance
regarding installation of the downstream control line.
The Type VSX4 shut-off disk is normally in the open
(reset) position, see Figure 6. If the downstream
pressure below the slam-shut diaphragm increases (or
decreases) until it reaches the slam-shut setpoint, this
diaphragm moves upward (or downward) to release
the trip mechanism which allows the spring force on
the stem to push the disk against the seat, shutting off
all gas flow. To reset the slam shut after gas has been
shut off, refer to the Type VSX4 Instruction Manual for
additional details.

CSB400 Series
In order for the Underpressure Shutoff (UPSO) of any
slam shut to be triggered, the downstream pipe pressure
must drop below the UPSO setpoint. In the case of a
downstream line break, numerous factors can prevent
the downstream pipe pressure from decreasing below
the slam-shut UPSO setpoint. These factors include the
distance of pipe to the break, the diameter of the pipe,
size of the break and the number of restrictions, such as
valves, elbows and bends, downstream of the regulator
and/or slam-shut device. Due to these factors additional
protections should be installed to stop flow in the event
of a line break.

Installation and Overpressure Protection
Install in accordance with provisions of EN 12186 /
EN 12279.

!

WARNING

Personal injury or system damage may
result if this regulator is installed, without
appropriate overpressure protection, where
service conditions could exceed the limits
given in the Specifications section and/
or regulator nameplate. Regulator and
equipment installation should be adequately
protected from physical damage.
All vents should be kept open to permit
free flow of gas to the atmosphere. Protect
openings against entrance of rain, snow,
insects or any other foreign material that
may plug the vent or vent line. On outdoor
installations, point the spring case vent
downward to allow condensate to drain,
see Figures 7 through 10. This minimizes
the possibility of freezing and of water or
other foreign materials entering the vent
and interfering with proper operation.
For the Type CSB403 with Integral
True-Monitor™ or the Type CSB404 with
Slam shut, point the vents of both the
primary regulator and Integral
True-Monitor or slam shut downward
to allow condensate to drain. From the
factory, the Integral True-Monitor or
slam shut will always point in the same
direction as that of the primary regulator.

Under enclosed conditions or indoors,
escaping gas may accumulate and be an
explosion hazard. In these cases, the vent
should be piped away from the regulator
to the outdoors.
In case of complete disassembly of
the equipment (body included) from
the pipeline, care must be taken not to
bend, hit or otherwise damage the pitot
tube (key 83 Figure 15) that protrudes
beyond the body outlet. Damage to the
pitot tube could result in inaccurate
internal pressure registration and loss of
regulation quality.

CAUTION
CSB400 Series regulators have an
outlet pressure rating lower than their
inlet pressure rating. If actual inlet
pressure can exceed the outlet pressure
rating, outlet overpressure protection
is necessary. However, overpressuring
any portion of the regulators beyond the
limits in the Specifications section may
cause leakage, damage to regulator parts
or personal injury due to bursting of
pressure-containing parts.
Some type of external overpressure
protection should be provided to the
CSB400 Series if inlet pressure will be
high enough to damage downstream
equipment. Common methods of external
overpressure protection include relief
valves, monitoring regulators, shut-off
devices, and series regulation.
If the regulator is exposed to an
overpressure condition, it should be
inspected for any damage that may have
occurred. Regulator operation below the
limits specified in the Specifications section
and regulator nameplate does not preclude
the possibility of damage from external
sources or from debris in the pipeline.

11

CSB400 Series

MINIMUM OF 4 X OUTLET
PIPING DIAMETER

WIDE-OPEN MONITORING REGULATOR

PRIMARY WORKING REGULATOR

UPSTREAM
BLOCK VALVE

DOWNSTREAM
BLOCK VALVE

INLET PRESSURE
INLET
PRESSURE
OUTLET PRESSURE
OUTLET
PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE
PRESSURE
Figure
8. Type CSB400 “Series Monitor” Regulator Downstream Control Line Installation

Before installing the regulator, check for
damage which might have occurred in
shipment. Also check for dirt or foreign
matter which may have accumulated in
the regulator body or in the pipeline. Apply
pipe compound to the external threads of
the pipeline and install the regulator so that
flow is in the direction of the arrow cast on
the body. The diaphragm casing assembly
can be rotated to any position relative to the
body. Loosen the two cap screws (key 71,
Figure 11) in order to rotate the diaphragm
casing assembly.

General Installation Instructions
Before installing the regulator,
•	 Check for damage, which might have occurred
during shipment.
•	 Check for and remove any dirt or foreign material, which
may have accumulated in the regulator body.

12

•	 Blow out any debris, dirt or copper sulfate in the copper
tubing and the pipeline.
•	 Apply pipe compound to the external threads of the pipe
before installing the regulator.
•	 Make sure gas flow through the regulator is in the same
direction as the arrow on the body. “Inlet” and “Outlet”
connections are clearly marked.
•	 Verify that:
-	 Equipment limits of utilization (PS, TS) corresponds
to the desired operating conditions.
-	 The inlet is protected by an appropriate device(s) to
avoid exceeding the allowable limits (PS, TS).
•	 When designing a pressure reducing station using
a CSB regulator, make an analysis if it is necessary
to take into account the effects of wind, snow
and temperature to avoid unnecessary load and
movement to the flanges of the equipment.
•	 If needed, a support may be used under the piping
and regulator/slam-shut body to avoid excessive
pressure force on the regulator/slam shut.

CSB400 Series
PRIMARY REGULATOR

DOWNSTREAM
BLOCK VALVE

UPSTREAM
BLOCK VALVE
MINIMUM OF 4 X OUTLET
PIPING DIAMETER

M1062

INTEGRAL TRUE-MONITOR™

Figure 9. Type CSB403 Downstream Control Line Installation

PRIMARY REGULATOR

DOWNSTREAM
BLOCK VALVE

UPSTREAM
BLOCK VALVE
MINIMUM OF 4 X OUTLET
PIPING DIAMETER

SLAM SHUT

M1063

INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE

Figure 10. Type CSB404 Downstream Control Line Installation

13

CSB400 Series
Installation Location
•	 The installed regulator should be adequately
protected from vehicular traffic and damage from
other external sources.
•	 Install the regulator with the vent pointed vertically
down, see Figures 7 through 10. If the vent cannot
be installed in a vertically down position, the regulator
must be installed under a separate protective cover.
Installing the regulator with the vent down allows
condensation to drain, minimizes the entry of water
or other debris from entering the vent, and minimizes
vent blockage from freezing precipitation.
•	 Do not install the regulator in a location where there
can be excessive water accumulation or ice formation,
such as directly beneath a downspout, gutter or roof
line of building. Even a protective hood may not
provide adequate protection in these instances.
•	 Install the regulator so that any gas discharge
through the vent or vent assembly is over 0.91 m /
3 feet away from any building opening.

Regulators Subjected to Heavy
Snow Conditions
Some installations, such as in areas with heavy snowfall,
may require a hood or enclosure to protect the regulator
from snow load and vent freeze over.

Downstream Control Line Installation
!

WARNING

Failure to install a downstream control
line could result in a hazardous condition.
Install downstream control line(s) to the
slam-shut device when construction uses
external pressure registration.
The regulator and slam-shut device
will not control pressure or shutoff if a
downstream control line is not installed
on those constructions where external
pressure registration is required.

14

CSB400 Series regulators with an “ET” or “EN” in the
type number use external pressure registration. To
communicate the downstream pressure to the regulator,
connect a downstream control line tubing to the 3/4 NPT
control line tapping in the lower diaphragm casing and
connect the other end of the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Types CSB400 and CSB404 with external control
lines, use tubing with an outer diameter of 9.5 mm /
0.375 inch or larger. For Types CSB420, CSB424,
CSB450 and CSB454 with external control lines, use
tubing with an outer diameter of 13 mm / 0.5 inch or larger.
The Types CSB410, CSB414, CSB430 and CSB434
are dedicated wide-open monitoring regulators and are
installed upstream of a primary working regulator. Refer
to Figure 8 for installation of the downstream control
line. To communicate the downstream pressure to the
wide-open monitor regulator, connect a downstream
control line tubing to the 3/4 NPT control line tapping in
the lower diaphragm casing of the monitor regulator and
connect the other end of the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Types CSB410 and CSB414, use tubing with an
outer diameter of 9.5 mm / 0.375 inch or larger.
For Types CSB430 and CSB434, use tubing with an
outer diameter of 13 mm / 0.5 inch or larger.

Downstream Control Line Installation with
Integral True-Monitor™
Refer to Figure 9. When installing the Types CSB403
and CSB423 regulators, connect downstream control
line tubing to the lower casing of the primary regulator,
and run the tubing downstream of the regulator outlet
with a minimum distance of 4 times the outlet pipe
diameter. Connect a second, separate downstream
control line tubing to the lower casing of the Integral
True-Monitor, and run the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Type CSB403 with external control lines, use tubing
with an outer diameter of 9.5 mm / 0.375 inch or larger
for both the primary regulator and Integral True-Monitor.

CSB400 Series
For Type CSB423 with external control lines, use tubing
with an outer diameter of 13 mm / 0.5 inch or larger for
both the primary regulator and Integral True-Monitor™.

Downstream Control Line Installation
with Slam shut
Refer to Figure 10. When installing the Types CS404ET,
CS404EN, CSB424ET, CSB424EN and CSB454EN
regulators, connect downstream control line tubing to
the lower casing of the regulator and run the tubing
downstream of the regulator outlet with a minimum
distance of 4 times the outlet pipe diameter. Connect
a second, separate downstream control line tubing to
the lower casing of the slam shut and run the tubing
downstream of the regulator outlet a minimum distance
of 4 times the outlet pipe diameter.
For Type CSB404 with external control lines, use tubing
with an outer diameter of 9.5 mm / 0.375 inch or larger
for the primary regulator and 6.4 mm / 0.25 inch or larger
for the slam shut.
For Types CSB424 and CSB454 with external control lines,
use tubing with an outer diameter of 13 mm / 0.5 inch or
larger for the primary regulator and 6.4 mm / 0.25 inch or
larger for the slam shut.

Installation with External
Overpressure Protection
If the regulator is used in conjunction with a Type 289H
relief valve, it should be installed as shown in Figure 7.
The outside end of the vent line should be protected
with a rainproof assembly. The Type 289H is typically set
25 mbar / 10 inches w.c. higher than the outlet pressure
setting of the regulator, up to 75 mbar / 30 inches w.c.
outlet pressure. For pressure greater than this, set the
Type 289H 0.05 bar / 0.75 psi higher than the outlet
pressure setting of the regulator.

Vent Line Installation
The CSB400 Series regulators have a 1 NPT screened
vent opening in the spring case. If necessary to vent
escaping gas away from the regulator, install a remote
vent line in the spring case tapping. Vent piping should
be as short and direct as possible with a minimum
number of bends and elbows. The remote vent line
should have the largest practical diameter. Vent piping
on regulators with token relief must be large enough

to vent all relief valve discharge to atmosphere without
excessive backpressure and resulting excessive
pressure in the regulator.
For types with optional Token relief, this low capacity
relief is located in the spring case of the primary
regulator. If necessary to vent escaping gas away, install
a remote vent line in the spring case tapping of the
primary regulator as described above. Periodically check
all vent openings to be sure that they are not plugged
or obstructed.
CSB400 Series outlet pressure ranges are shown in
Table 6. Outlet pressure higher than 0.34 bar / 5 psig
above the setpoint may damage internal parts such as
the diaphragm head and valve disk. The maximum
emergency (casing) outlet pressure is 4.0 bar / 58 psig.

Commissioning
CAUTION
Pressure gauges must always be used to
monitor downstream pressure during Startup.
With the downstream system depressurized, use the
following procedure to start up the regulator.
1.	 Check to see that all appliances are turned off.
2.	 Slowly open the upstream shut-off valve.
3.	 Check inlet and outlet pressure for correct values.
4.	 Check all connections for leaks.
5.	 Turn on utilization equipment and recheck
the pressures.

Adjustment

Note

For types that include the Integral
True-Monitor module, refer to the
Instruction Manual for Type TM600
Integral True-Monitor for adjustment and
maintenance of the Integral True-Monitor.
For the types that include the slam-shut
module, refer to the Instruction Manual for
Type VSX4 slam shut for adjustment and
maintenance of the slam shut.

15

CSB400 Series
The range of allowable pressure settings
for the primary regulator is stamped on
the nameplate. If the required setting
is not within this range, substitute the
correct spring (as shown in Table 6). If the
spring is changed, re-stamp the nameplate
to indicate the new pressure range.
A pressure gauge must always be used
to monitor downstream pressure while
adjustments are being made.

For Types CSB400 and CSB420
1.	 Remove the closing cap (key 60, Figure 16).
2.	 To increase the outlet setting, turn the adjusting
screw (key 65) clockwise. To decrease the outlet
setting, turn the adjusting screw counterclockwise.
3.	 Replace the closing cap.

For Type CSB450
1.	 Loosen the hex nut (key 58, Figure 16).
2.	 To increase the outlet setting, turn the adjusting screw
(key 65, Figure 16) clockwise. To decrease the outlet
setting, turn the adjusting screw counterclockwise.
3.	 Tighten the hex nut.

CSB400 Series with Integral True-Monitor™
When adjusting the primary regulator and Integral
True-Monitor for operation, ensure that the pressure
differences between the primary regulator and the
integral monitor shown in Table 7 are observed. For
example, if the primary regulator setpoint is set at
20 mbar / 8 inches w.c., then the Integral True-Monitor
should be set at a minimum of 35 mbar / 14 inches w.c.
or higher.
To test the Integral True-Monitor operation, the primary
regulator setpoint must be adjusted above the Integral
True-Monitor’s setpoint to simulate a failure of the
primary regulator. If the spring range of the primary
regulator is sufficiently high, it can simply be adjusted
above the Integral True-Monitor’s setpoint by following
step 2 above. Otherwise, a different spring with a
setpoint higher than the Integral True-Monitor’s setpoint
must be installed to check the operation of the
Integral True-Monitor.

16

CSB400 Series with Slam shut
When adjusting the primary regulator and slam shut for
operation, refer to Table 8 for the OPSO setpoints and
also the combined OPSO and UPSO setpoints of the
slam shut for a given regulator spring ranges.

CAUTION
Equipment installed downstream the
Type VSX slam shut device can be
damaged if the following procedure for
resetting the Type VSX slam shut device
is not followed. This equipment
includes the integral Type VSX or
regulator configurations.

Step 1:
•	 To properly reset the Type VSX slam shut after it
has been tripped to the closed position, a flat-head
screwdriver must be inserted into the position shown
in Figure 8 on the backside of the reset button (refer
to Type VSX4 Instruction Manual, key 30, Figure 8).

Step 2:
•	 The screwdriver should be slowly rotated to gradually
pull the reset button (refer to Type VSX4 Instruction
Manual, key 30) away from the Type VSX device. This
slow movement allows for a slow bleed of the pressure
across the Type VSX slam shut’s disk and seat area.
The operator should be able to hear the pressure
bleeding through the system.

Step 3:
•	 When the pressure has equalized and the air
bleeding sound has dissipated, the reset button (refer
to Type VSX4 Instruction Manual, key 30) should be
pulled completely away from the Type VSX slam shut
device by hand until the internal shut-off mechanism
has been re-latched.

Step 4:
•	 Once the operator feels the click of the re-latch
occurring, the reset button (refer to Type VSX4
Instruction Manual, key 30) should be pushed
completely back into its original position.

CSB400 Series
L2
38

55

19

L2

L1

L2

L2

62

60

65

L2
100

96

TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS

4

20

5
7

19

L1

6

35
95

L1

77

L1

75

8
TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS

74

L2

51

25

TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS

L1

21

27

18

11

L1

13

L1

14

10

TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS

L1

22

S1

ERAA04154

APPLY LUBRICANTS (L) / SEALANT (S)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
L2 = ANTI-SEIZE LUBRICANT
S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Lubricants and sealant must be selected such that they meet the temperature requirements.

Figure 11. CSB400 Series Regulator Assembly

!

WARNING

In the case of a downstream line break,
numerous factors affect the capability to
evacuate gas from the pipeline. These
factors include the distance of pipe to the
break, the diameter of the pipe, size of the
break and the number of restrictions, such
as valves, elbows and bends, downstream
of the regulator and/or slam-shut device.
Due to these factors additional protections
should be installed to stop flow in the
event of a line break.

Shutdown
Installation arrangements may vary, but in any
installation it is important that the valves be opened
or closed slowly and that the outlet pressure be vented
before venting inlet pressure to prevent damage caused
by reverse pressurization of the regulator. The following
steps apply to the typical installation as indicated.
1.	 Open valves downstream of the regulator.
2.	 Slowly close the upstream shut-off valve.
3.	 Inlet pressure should automatically be released
downstream as the regulator opens in response to
the lowered pressure underside of the diaphragm.
4.	 Close outlet shut-off valve.

Dow Corning® is a mark owned by Dow Corning Corporation.

17

CSB400 Series
3
2
1
15

TORQUE:
7.1 TO 10.1 N•m /
63 TO 90 INCH-POUNDS

16

9

80

TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

76
S1

72

70
71

TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

17

ERAA04154

APPLY SEALANT (S)(1):
S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Sealant must be selected such that it meets the temperature requirements.
2. The torque range as specified is initial assembly torque. Due to elastomeric compression, the torque values indicated may decrease. Minimum inspection torque is 4 N•m / 35 inch-pounds.

Figure 11. CSB400 Series Regulator Assembly (continued)

18

CSB400 Series
Maintenance and Inspection
!

Note
For adjusting setpoints above 100 mbar /
1.5 psig, use a 13 mm / 1/2-inch hex driver,
a 13 mm / 1/2-inch socket or a 27 mm /
1-1/16-inch socket to turn the adjusting
screw (key 65).

WARNING

To avoid personal injury or equipment
damage, do not attempt any maintenance
or disassembly without first isolating
the regulator from system pressure and
relieving all internal pressure as described
in “Shutdown”.
Regulators that have been disassembled
for repair must be tested for proper
operation before being returned to
service. Only parts manufactured by
Regulator Technologies should be used
for repairing Fisher® regulators. Restart
gas utilization equipment according to
normal startup procedures.
Due to normal wear or damage that
may occur from external sources, this
regulator should be inspected and
maintained periodically. The frequency
of inspection and replacement depends
on the severity of service conditions,
test results found during the annual
test, and on applicable codes and
regulations. In accordance with applicable
National or Industry codes, standards
and regulations/recommendations, all
hazards covered by specific tests after
final assembly, before applying the CE
marking, shall also be covered after every
subsequent reassembly at installation site
in order to ensure that the equipment will
be safe throughout its intended life.
Periodic inspection must be performed
on the CSB400 Series that include the
Integral True-Monitor™ or slam-shut
overpressure protection modules to
ensure that they protect the downstream
system in the event the primary regulator
losses pressure control. This inspection
must test that the Integral True-Monitor or
slam-shut functions as intended.

Disassembly to Replace the Regulator
Main Diaphragm
1.	 Remove the closing cap (key 60, Figure 11) or loosen
hex locknut (key 58, Figure 16). Turn the adjusting
screw (key 65) or nut (key 58) counterclockwise to
ease spring (key 38) compression.
2.	 Remove the adjusting screw (key 65) and spring
(key 38).
3.	 Remove hex nuts (key 16, Figure 11) and cap screws
(key 15, Figure 11). Separate the upper spring case
(key 1) from the lower casing assembly (key 9).
Note
When disassembling a CSB400 Series
regulator, lift the upper spring case (key 1)
straight up in order to avoid hitting the
stem (key 44).
4.	 Slide the diaphragm assembly (key 55) away
from the body (key 70) to unhook the pusher
post (key 51) from the lever (key 10). Lift off the
diaphragm assembly (key 55).
5.	 a.	For none relieving units such as the
Types CSB400IN and CSB400EN, unscrew the
cap (key 45), see Figure 12, high-pressure NonRelief and low-pressure Non-Relief assemblies.
The cap fastens the R.V. spring seat (key 43)
to the pusher post (key 51). Unscrew the cap to
separate the R.V. spring seat (key 43), diaphragm
assembly (key 55) and pusher post (key 51).
	

b.	For units with internal token relief such as
Type CSB400IT, refer to Figure 12, unscrew the
adjusting upper seat (key 47). This will allow for
removal of the relief spring (key 41), R.V. spring
seat (key 43), diaphragm assembly (key 55) and
pusher post (key 51).

19

CSB400 Series
6.	 Reassemble the spring case (key 1) unit in the
reverse order of the above steps. Before tightening
the cap screws (key 15) or stem (key 44) into the
pusher post (key 51), place the loosely-assembled
diaphragm assembly (key 55) into position in the
lower casing (key 9), being sure that the pusher post
(key 51) is hooked on the lever (key 10). Rotate the
diaphragm (key 55A) so that the diaphragm and
lower casing (key 9) holes are aligned. Tighten the
stem (key 44) or diaphragm retainer (key 45) for HP
and LP non-relief assemblies.

Disassembly to Replace Valve Disk,
Balanced Port Assembly Diaphragm and
Regulator Orifice
1.	 Remove the bolts (key 71, Figure 11) which hold
the lower spring casing (key 9) to the body (key 70).
Separate the lower spring casing (key 9) from the
body (key 70).
2.	 Check the body O-ring (key 21) for wear. 
3.	 Remove the balanced port assembly (key 35,
Figures 11 and 13) from the body, make sure to
rotate the assembly toward the outlet of the body
as it is being removed to clear the sense tube
from the body.
4.	 Examine the valve disk (key 35K) for nicks, cuts
and other damage. If damage is present, it is
recommended to replace both the disk and also the
balanced port diaphragm (key 35F) and associated
diaphragm O-ring (key 35M), that comes into direct
contact with the inner flange of the balanced port
diaphragm. Start the process of replacing the disk
by disassembling the balanced port assembly.
Remove the four cap screws (key 35R) and then the
cap (key 35G).
5.	 Grasp the spring retainer (key 35C) and slide
the brazed housing (key 35A) away to expose
the diaphragm (key 35F) and disk (key 35K). Still
grasping the spring retainer (key 35C) insert a
5 mm Allen wrench into the disk screw (key 35E)
and unscrew.

Dow Corning® is a mark owned by Dow Corning Corporation.

20

6.	 Remove the disk (key 35K) and discard if damaged
Slide the diaphragm O-ring (key 35M) off the stem
(key 35B) along with the diaphragm (key 35F).
Slide the new diaphragm over the stem in the same
manner that it was removed, make sure that it
completely contacts the surface of the inner retainer
(key 35J).
7.	 Reassemble the Balanced Port assembly in reverse
order of the above. Ensure Dow Corning® 33 or
comparable extreme low temperature lubricant
completely coats the O-ring (key 35M), stem
(key 35B) and the center bore of the outer retainer
(key 35H).
8.	 Examine the seating edge of the orifice (key 25). If
it is nicked or rough, replace the orifice and O-ring
(key 27). If a slam shut or monitor is installed on
the backside of the body, refer to the applicable
Instruction Manual for inspection and removal of the
overpressure protection orifice (key 26) and O-ring
(key 27).
9.	 Reassemble the regulator in reverse order of the
above steps.

Regulator Reassembly
As indicated by the square callouts in Figures 11 to 17, it
is recommended that a good quality pipe thread sealant
be applied to pressure connections and fittings and a
good quality extreme low temperature lubricant, such
as Dow Corning® 33, be applied to O-rings. Also apply
an anti-seize compound to the adjusting screw threads,
orifice threads and other noted areas as needed.

Parts Ordering
The type number, orifice size, spring range and date of
manufacture are stamped on the nameplate. Always
provide this information in any correspondence with
your local Sales Office regarding replacement parts or
technical assistance.
When ordering replacement parts, reference the key
number of each needed part as found in the following
parts list. Separate kit containing all recommended
spare parts is available.

CSB400 Series
Parts List
Key	 Description		

Part Number

		
Spare Parts (Repair Parts Kit include keys 12, 19,
		 
21, 27, 35K, 55, 62, 75 and 77)
		   Type CSB400	
RCSB400X012
		   Type CSB403	
RCSB403X012
		   Type CSB404	
RCSB404X012
1		 Spring Case, Aluminum 	
GE24555X012
2		 Vent Screen, 18-8 Stainless steel 	
T1121338982
3		 Retaining Ring, Steel	
T1120925072
4		 Stabilizer Guide, 304 Stainless steel 	
GE27061X012
5		 Stabilizer, Acrylonitrile Butadiene Styrene (ABS)	
GE27063X012
6		 Stabilizer Spring, Stainless steel 	
GE35010X012
7		 Retainer Ring, Zinc-plated steel	
GE27024X012
8		 Stabilizer Screw, Zinc-plated steel (3 required)	
GE29724X012
9		 Lower Casing, Aluminum	
GE24289X012
10		 Lever, Steel	
		  Types CSB400, CSB403, CSB404,
		   CSB410 and CSB414	
GE28773X012
		  Types CSB420, CSB423, CSB424,
		   CSB430, CSB434, CSB450 and CSB454	
GE28772X012
11		 Valve Stem, Aluminum	
GE27812X012
12*		 O-ring, Nitrile (NBR)	
		  External Registration Only	
1E472706992
13		 Lever Pin, 18-8 Stainless steel
		  Types CSB400, CSB403, CSB404,
		   CSB410 and CSB414	
T14397T0012
		  Types CSB420, CSB423, CSB424, CSB430,
		   CSB434, CSB450 and CSB454 (2 required)	
T14397T0012
14		 Lever Screw, Steel
		  Types CSB400, CSB403, CSB404,
		   CSB410 and CSB414 (2 required)	
GE34243X012
		  Types CSB420, CSB423, CSB424, CSB430,
		   CSB434, CSB450 and CSB454 (4 required)	
GE34243X012
15		 Cap Screw, Steel (8 required) 	
GE32059X012
16		 Nut, Steel (8 required)	
GE32060X012
17		 Union Ring, Aluminum	
GE26590X012
18		 Snap Ring, 302 Stainless steel	
T1120637022
19*		 O-ring, Nitrile (NBR) (2 required)	
1K594906562
20		 Stem Guide, Aluminum 	
GE26027X012
21*		 O-ring, Nitrile (NBR)	
GE45216X012
22		 Pipe plug, 3/4 NPT, Steel	
		  Internal Registration Only	
GE34199X012
23		 Screw (For external registration only),
		  Steel (2 required)	
1E175828982
24*		 O-ring (For external registration only),
		  Nitrile (NBR) (2 required)	
17A0960X012
25	 	 Orifice	
		  Types CSB400F and CSB404F, Aluminum	
GG08494X012
		  All other Types, Brass	
GE31321X012
26		 OPP Orifice 18 mm / 0.69 inch
		  With Integral True-Monitor™ Orifice, Aluminum	
GE30003X012
		  With Slam-shut Orifice, Brass	
GE28684X012
27*		 O-ring, Nitrile (NBR) 	
		  Type CSB400 (1 required)	
10A3802X022
		  Type CSB403 (2 required)	
10A3802X022
		  Type CSB404 (2 required)	
10A3802X022
35		 Balanced Port Assembly for all bodies except GAZ
		 
Standard	GE31196X012
		  Low temperature “F” version 	
GE31196X022
35A 	 Brazed Housing	
GE31261X012
35B		 Stem, Stainless steel	
GE31191X012
35C		 Spring Retainer, Zinc-plated steel 	
GE31189X012
35D		 Spring, Stainless steel	
GE30193X012
35E		 Disk Screw, Zinc-plated steel 	
GE31190X012
35F*	 Diaphragm, Nitrile (NBR) / Fabric	
GE30439X012
35G	 Cap, Brass 	
GE31195X012

Key		

Description	

35H		 Outer Retainer, Brass	
35J		 Inner Retainer, Brass 	
35K*	 Disk Assembly, Brass / Nitrile (NBR)
		  
Standard version	
		   Low Temperature “F” version	
35M	 O-ring, Nitrile (NBR) (2 required)	
35N*	 O-ring, Nitrile (NBR)	
35R		 Screw, Steel (4 required)	
35S		 Pin, Zinc-plated steel	
35		 Balanced port assembly for Rp 1 x 2-1/4, GAZ Body
		  
Standard 	
		   Low temperature “F” version	
35A		 Brazed Housing	
35B		 Stem, Stainless steel	
35C		 Spring Retainer, Zinc-plated steel 	
35D		 Spring, Stainless steel	
35E		 Disk Screw, Zinc-plated steel	
35F*	 Diaphragm, Nitrile (NBR) / Fabric	
35G	 Cap, Brass	
35H		 Outer Retainer, Brass	
35J		 Inner Retainer, Brass 	
35K*	 Disk Assembly, Brass / Nitrile (NBR)
		  
Standard version 	
		   Low-temperature “F” version 	
35M	 O-ring, Nitrile (NBR) (2 required)	
35N*	 O-ring, Nitrile (NBR)	
35R		 Screw, Cap, Hex Socket, Steel (4 required) 	
38		 Spring	
		  17 to 24 mbar / 6.8 to 9.6 inches w.c., Pink	
		  24 to 35 mbar / 9.6 to 14 inches w.c., Orange Stripe	
		  35 to 60 mbar / 14 to 24 inches w.c., Dark Green 	
		  54 to 100 mbar / 0.78 to 1.5 psig, Tan	
		  100 to 160 mbar / 1.45 to 2.3 psig, Purple Stripe	
		  138 to 300 mbar / 2.0 to 4.4 psig, Dark Blue	
		  276 to 517 mbar / 4 to 7.5 psig, Red 	
		  500 mbar to 1 bar / 7.3 to 14.5 psig, Light Blue	
		  1 to 3 bar / 14.5 to 43.5 psig, Light Green	
40		 Upper Spring Seat, Steel
		  High Pressure, Zinc-plated steel	
41		 Relief Valve Spring, 302 Stainless steel	
		  Types CSB400, CSB403 and CSB404, Token 	
		  Types CSB420, CSB423 and CSB424, Token	
43		 Relief Valve Spring Seat, Zinc-plated steel
		  Types CSB400 and CSB420, Non-Relief 	
		  Type CSB450, Non-Relief	
 		  Types CSB400 and CSB420, Token 	
44		 Stem, Aluminum	
		  Types CSB400 and CSB420, Token 	
45		 Diaphragm Retainer, Zinc-plated steel
		  Types CSB400 and CSB420, Non-Relief	
		  Type CSB450, Non-Relief	
47		 Upper Spring Seat, Aluminum
		  Types CSB400 and CSB420, Token 	
48		 Restrictor Plate, Zinc-plated steel 	
		 
Token 	
51		 Pusher Post, Aluminum
		  Token	
		  Non-Relief	
53		 Solid Rivet, 18-8 Stainless steel 	
54		 Roller Pin, Brass	
55*	 	 Diaphragm Assembly, Steel / Nitrile (NBR) 	
		  Without Diaphragm Head Limiter 	
		  With Diaphragm Head Limiter	
55A Diaphragm 	
55B Diaphragm Head 	

Part Number
GE31187X012
GE31186X012
ERSA00457A0
GE31185X012
1E472706992
1U879006562
GE25968X012
GE31232X012
GE33822X012
GE33822X022
GE32505X012
GE31191X012
GE31189X012
GE30193X012
GE31190X012
GE30439X012
GE31195X012
GE31187X012
GE31186X012
ERSA00457A0
GE31185X012
1E472706992
1U879006562
GE25968X012
GE30191X012
GE43955X012
GE30201X012
GE30202X012
GE35081X012
GE30192X012
GE33121X012
GE30203X012
GE30204X012
GE32501X012
GE30194X012
GE42225X012	
GE27327X012
GE31677X012
GE28947X012
GE30895X012
GE30887X012
GE33850X012
GE33332X012
GE28948X012
ERAA00876A0
ERAA00875A0
GE29761X012
GE27060X012
GE31248X012
GE32140X012
---------------------

*Recommended spare part.

21

CSB400 Series

TORQUE:
6 TO 8 N•m /
50 TO 70 INCH-POUNDS

44

47

48

41

TORQUE:
6 TO 8 N•m /
50 TO 70 INCH-POUNDS

45
43

A 55B

43

A 55B

55A

NOTE DIRECTION
OF RETAINER RING
INSTALLATION

54

TOKEN RELIEF

A
55A

55B

109

NOTE DIRECTION
OF RETAINER RING
INSTALLATION

53

56

108

56

51

55A

107

51

HIGH-PRESSURE NON-RELIEF

54

TORQUE:
6 TO 8 N•m /
50 TO 70 INCH-POUNDS

45

43

51

56

53

NOTE DIRECTION
OF RETAINER RING
INSTALLATION

56
NOTE DIRECTION
OF RETAINER RING
INSTALLATION

LOW-PRESSURE NON-RELIEF

54

ERAA04154

APPLY ADHESIVE (A)(1):
A = ADHESIVE
NOTE: APPLY ADHESIVE ON THE FLAT SURFACE OF THE DIAPHRAGM PLATE THAT CONTACTS THE DIAPHRAGM, TOWARD THE OUTER PERIMETER,
AND AWAY FROM THE CENTER HOLE.
1. Adhesive must be selected such that it meets the temperature requirements.

Figure 12. CSB400 Series Diaphragm and Relief Assemblies

22

53

CSB400 Series
L1

L1
35F

35J

35S

35N

35H

35M

35M

S2

L1

TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS

35B

35C
35E

TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS

35D

35K

35R
35A

TORQUE:
0.9 TO 1.4 N•m /
8 TO 12 INCH-POUNDS

35G

STANDARD BALANCED PORT ASSEMBLY

L1
35F

35J

35N

L1
35H

35M

35B

S2

35M
L1

35C
TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS

TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS

35D

35E
35K

35R
35A

TORQUE:
0.9 TO 1.4 N•m /
8 TO 12 INCH-POUNDS

35G

BALANCED PORT ASSEMBLY FOR Rp 1 X 2-1/4 GAZ BODY
ERAA04154

APPLY LUBRICANT (L) / SEALANT (S)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
S2 = PERMANENT THREAD SEALANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.

Figure 13. Balance Trim Assemblies
Dow Corning® is a mark owned by Dow Corning Corporation.

23

CSB400 Series

L1
L1

L1

20

11

INTERNAL OR DUAL REGISTRATION
(NO SCREWS)

L1

12

L1

REF
HOLES “B”

L1

23

B

24
B

L1

20

11

EXTERNAL REGISTRATION
GE27692

APPLY LUBRICANT (L)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
1. Lubricant must be selected such that it meets the temperature requirements.

Figure 14. CSB400 Series Stem Guides

Dow Corning® is a mark owned by Dow Corning Corporation.

24

L1

TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS
INSTALL IN “B” HOLES
(THROUGH HOLES)

CSB400 Series
L1

75

L1

77
80

80

TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

74

74

76
76

77

75

L1

L1

101

S2

70

83

82

81

ERAA04154

TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS

GAZ BODY

DUCTILE / STEEL BODY
APPLY LUBRICANT (L) / SEALANT (S)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
S2 = PERMANENT THREAD SEALANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.

Figure 15. Standard Body Assembly and Rp 1 x 2-1/4 GAZ Body Assembly

L1

L2

L2

L1

65

62

38
38

60

40

62

58

L2

L2

65

61

57

100

96

CSB400 / CSB420 SERIES STANDARD

CSB450 SERIES HIGH PRESSURE

ERAA04154

APPLY LUBRICANT (L)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
L2 = ANTI-SEIZE LUBRICANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.

Figure 16. CSB400 Series Control Spring Adjustment Assemblies
Dow Corning® is a mark owned by Dow Corning Corporation.

25

CSB400 Series

TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

L2

L1

26

27

70

L1

L2

27

25

TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS

101

L
L2
26

INTEGRAL TRUE-MONITOR™ ASSEMBLY

L1

L2

27

25

L1
101

L2

27

70

L1

L2

27

25

TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS

101

26

TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS

TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS

SLAM-SHUT ASSEMBLY
ERAA04154

APPLY LUBRICANTS (L)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
L2 = ANTI-SEIZE LUBRICANT
1. Lubricants must be selected such that they meet the temperature requirements.

Figure 17. CSB400 Series Slam-shut and Integral True-Monitor Modules
Dow Corning® is a mark owned by Dow Corning Corporation.

26

2

CSB400 Series
Parts List (continued)
Key	 Description		
56		 Retaining Ring, Pusher Post Pin 	
57		 Bearing ball	
58		 Hex Nut, High-Pressure, 	
		 (CSB450 Series only) Steel	
60 		 Closing Cap, Low-Pressure, Aluminum 	
61		 Bonnet, High-Pressure, 	
		 (CSB450 Series only) Zinc-plated steel	
62*		 O-ring, Nitrile (NBR) 	
65		 Adjust Screw
		 
Low-Pressure, Aluminum	
		  High-Pressure, Steel	
70		 Body
		  Ductile Cast Iron
		  NPT:
		   1 	
		   1-1/4 	
		   1-1/2 	
		   2 	
		   Rp:
		    Rp 1	
		    Rp 1-1/4	
		    Rp 1-1/2 	
		    Rp 1 x 1-1/4 	
		    Rp 1 x 2-1/4, GAZ 	
		    Rp 2	
		  Flange:	
		    DN 50 / NPS 2, CL150 FF 	
		    DN 40 / NPS 1-1/2, PN 10/16 Slip-Flange	
		    DN 50 / NPS 2, PN 10/16	
		 
WCC Steel
		  NPT:
		   1 	
		   1-1/4	
		   1-1/2	
		   Rp
		    Rp 1 	
		    Rp 1-1/4	
		    Rp 1-1/2	

Part Number
GE33772X012
GE33131X012
GE33132X012
GE29244X012
GE32499X012
T10275X0012
GE27828X012
GE32500X012 	

GE26463X012
GE26465X012
GE26466X012
GE26467X012
GE26468X012
GE26469X012
GE26470X012
GE42505X012
GE26482X012 
GE26471X012
GE26480X012
GE44902X012
GE26481X012

Key		

Description	

71		 Bolt, Steel (2 required) 	
72		 Pipe Plug, 1/4 NPT	
		 
Steel	
		  316 Stainless steel	
74		 Blanking Plug, Aluminum	
75*		 O-ring, Metric, Nitrile (NBR)	
76		 Half Flange, Steel (2 required)	
77*		 Metric O-ring, Nitrile (NBR)	
80		 Cap Screw, Steel (4 required)	
81		 Slotted Spring Pin	
82		 Tube Gasket, Nitrile (NBR)	
83		 Pitot Tube, Aluminum	
90		 Nameplate	
91		 Warning Label 	
93		 Information Label 	
94		 Overlay Label 	
95		 Grommet, Nitrile (NBR)	
96	 	 Slip Disk, Stainless steel	
100		 Wire and Seal	
101		 Spring Pin, Steel	
104		 Hub, Zinc-plated steel (2 required) not shown	
105		 Flange Slip, Zinc-plated steel (2 required) not shown	
106		 O-ring, Nitrile (NBR) (2 required) not shown	
107		 Diaphragm Head Limiter, Zinc-plated steel	
108		 Diaphragm Protector, Zinc-plated steel	
109		 Pad, (CSB450 Series only) 	

Part Number
GE32061X012
1C333528992
1C3335X0012
GE31255X012
GF03442X012
GF01942X012
GF03443X012 
GE38176X012
GE32503X012
GE32502X012
GE31988X012
----------------------------------------GE35358X012
GG05787X012
T14088T0012
GE32724X012
GG02505X012
GG02508X012
GE41121X012
GE28761X012
GE42747X012
T13830T0012

GE26463X022
GE26465X022
GE26466X022
GE26468X022
GE26469X022
GE26470X022

27

CSB400 Series

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Tescom Corporation

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9000

Asia-Pacific
Singapore 128461, Singapore
Tel: +65 6770 8337

Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Chartres 28008, France
Tel: +33 2 37 33 47 00

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9499

Middle East and Africa
Dubai, United Arab Emirates
Tel: +011 971 4811 8100

Middle East and Africa
Dubai, United Arab Emirates
Tel: +011 971 4811 8100

For further information visit www.emersonprocess.com/regulators

The distinctive swirl pattern cast into every actuator
casing uniquely identifies the regulator as part of the
Fisher® brand Commercial Service Regulator family
and assures you of the highest-quality engineering,
performance, and support traditionally associated
with Fisher®, Francel™ and Tartarini™ regulators.
Visit www.fishercommercialservice.com to access
interactive applications.

The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees,
express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any
time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and
maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.

©Emerson Process Management Regulator Technologies, Inc., 2009, 2014; All Rights Reserved



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2014:06:11 22:34+08:00
Metadata Date                   : 2014:06:11 22:34:22+08:00
Modify Date                     : 2014:06:11 22:34:22+08:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:3cd2e37e-d905-47cd-8189-89718274108b
Original Document ID            : adobe:docid:indd:f3341ade-2c77-11df-9b4f-fe9a26d6f18e
Document ID                     : xmp.id:70857E6675F1E311BF43F541A4FB8EC5
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:6F857E6675F1E311BF43F541A4FB8EC5
Derived From Document ID        : xmp.did:D35CA5227ED7E311859D83F7AE387258
Derived From Original Document ID: adobe:docid:indd:f3341ade-2c77-11df-9b4f-fe9a26d6f18e
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2014:06:11 22:34+08:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 28
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu