Emerson Fisher 546 Data Sheet
2015-03-30
: Emerson Emerson-Fisher-546-Data-Sheet-681866 emerson-fisher-546-data-sheet-681866 emerson pdf
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X012 Fisherr 546 Electro‐Pneumatic Transducer Fisher 546 transducers receive a direct‐current input signal and use a torque motor, nozzle‐flapper, and pneumatic relay to convert the signal to a proportional pneumatic output signal. Nozzle pressure, which operates the relay, is also piped to the torque motor feedback bellows. This provides a comparison between input signal and nozzle pressure and reduces errors in nozzle pressure. The transducer can be mounted on a pneumatic diaphragm control valve actuator to provide accurate operation of the valve. The integrated high‐capacity pneumatic relay eliminates the need for additional boosters or relays for operation of control valves. The transducer also can be used to provide stable operation when its output signal is transmitted to small terminal volume chambers such as control bellows in pneumatic valve positioners. Features Fisher 546 Transducer Mounted on 657 Pneumatic Diaphragm Actuator W2115 n Vibration Resistance—High natural frequency of torque motor moving parts results in negligible vibration influence. n Easy Adjustment—Screwdriver adjustments for span and zero are conveniently located and have arrows indicating rotation to increase settings (as shown in figure 1). www.Fisher.com n Field‐Reversible Action—No additional parts required to reverse action. n Simple Relay Removal—Integrated pneumatic relay is mounted outside case and can be removed without disturbing electrical or pressure connections or impairing explosion safety. Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X012 Specifications Available Configuration Electro‐pneumatic signal transducer with explosion‐proof case and cover The 546 can ordered J with or J without a Fisher 67CFR filter regulator. The 51 mm (2 inch) supply pressure gauge mounted on the regulator may be J 0 to 30 psig or J 0 to 60 psig range Input Signals J 4 to 20 mA DC, J 10 to 50 mA DC, J 1 to 9 V DC, or J Two‐way split range using either half of one of the standard input signal spans Internal Resistance of Torque Motor 4 to 20 mA DC Input Signal: 176 ±10 ohms 10 to 50 mA DC Input Signal: 90 ±10 ohms 1 to 9 VDC Input Signal: 1300 ±50 ohms (temperature compensated circuit) Output Signals Ranges: J 0.2 to 1.0 bar (3 to 15 psig), J 0.4 to 2.0 bar (6 to 30 psig), J 0 to 1.2 bar (0 to 18 psig) or J 0 to 2.3 bar (0 to 33 psig) Action: Field-reversible between J direct and J reverse Supply Pressure(1) Recommended: 0.3 bar (5 psi) higher than upper range limit of output signal Maximum: 3.5 bar (50 psig) Average Steady‐State Air Consumption(2)(3) 0.44 m3/hr (16.5 scfh) at 1.4 bar (20 psi) supply pressure Maximum Output Air Capacity(2) At 1.4 bar (20 psig) Supply Pressure: 12.9 m3/hr (480 scfh) At 2.4 bar (35 psig) Supply Pressure: 18.5 m3/hr (690 scfh) Performance(4) Actuator Loading Time: see figure 3 Reference Accuracy: ±0.75% of output signal span Independent Linearity: ±0.50% of output signal span Open Loop Gain: 26 Frequency Response: Gain is attenuated 3 dB at 20 Hz with transducer output signal piped to a typical instrument bellows with 305 mm (12 inch) of 1/4 inch tubing Electromagnetic Interference (EMI): Tested per IEC 61326‐1 (Edition 1.1). Meets emission levels for Class A equipment (industrial locations) and Class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document). Immunity performance shown in table 1. Operative Ambient Temperature Limits(1) -40 to 66_C (-40 to 150_F) Electrical Classification Hazardous Area: CSA—Explosion-proof, Dust Ignition‐proof, Div 2 FM—Explosion‐proof, Non‐incendive Refer to table 2 for specific approval information. NEMA 3R, CSA Enclosure 3 NEMA 3R mounting orientation requires vent location to be below horizontal. Adjustments Zero and Span Adjustments: Screwdriver adjustments located inside case (see figure 1) Connections Supply Pressure: 1/4 NPT internal located on side of case (located on filter‐regulator if a 67CFR is mounted to transducer) Output Pressure: 1/4 NPT internal located on side of case Vent: 1/4 NPT internal with screen located on relay Electrical: 1/2 NPT internal located on bottom of case -continued- 2 Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X102 Specifications (continued) Construction Materials Case and Cover: Aluminum O‐Rings: Nitrile Flame Arrestors: Stainless steel Supporting Bracket/Torsion Member: Stainless steel Magnets: Alloy steel Nozzle: Stainless steel Feedback Bellows: Brass Relay Body: Aluminum Relay Restriction: Aluminum/Stainless steel Relay Diaphragm: Nitrile Relay Valve Plug and Seat Ring: Brass Mounting Mounting parts are available for J control valve actuator mounting, J pipestand (2 inch nominal) mounting, or J surface mounting Approximate Weight 4.1 kg (9 lb) NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology. 1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. 2. Normal m3/hr-‐Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh‐‐Standard cubic feet per hour (60_F and 14.7 psia). 3. Average flow rate determined at 12 mA and 0.6 bar (9 psig) output. 4. Performance values are obtained using a transducer with a 4 to 20 mA DC input signal and a 0.2 to 1.0 bar (3 to 15 psig) or a 0.4 to 2.0 bar (6 to 30 psig) output signal. Ambient temperature is 24_C (75_F). A transducer with other input or output signals may exceed these values. Figure 1. Zero and Span Adjustments (Cover Removed) ZERO ADJUSTMENT W5391 SPAN ADJUSTMENT 3 Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X012 Principle of Operation Refer to figure 2, and assume that the transducer is direct acting. As the DC milliamp signal increases, so does the magnetic field around the coils. This results in an increased magnetic attraction between the armature and the pole pieces. The armature rotates slightly clockwise to cover the nozzle, increasing pressure in the nozzle, the upper chamber of the relay, and the feedback bellows. Increased nozzle pressure and increased pressure in the upper chamber of the relay cause the relay supply port to open, increasing the output pressure to the actuator and the control valve. At the same time, the increased pressure in the feedback bellows acts to move the armature back to the equilibrium position. In this way, the new nozzle pressure is compared to the DC input signal by the force balance principle. As the DC input signal decreases, magnetic attraction is reduced and the armature rotates slightly in the counterclockwise direction to uncover the nozzle. Decreased nozzle pressure and decreased pressure in the upper chamber of the relay cause the relay exhaust port to open and allow output pressure to bleed to atmosphere. Pressure to the control valve is reduced until equilibrium is attained. Reverse‐acting transducers operate in a similar manner except that when the DC input signal increases, pressure to the actuator and control valve decreases. Figure 2. Transducer Schematic SPAN ADJUSTMENT (MAGNETIC SHUNT) FEEDBACK BELLOWS ZERO ADJUSTMENT PERMANENT MAGNET POLE PIECES ARMATURE COIL NOZZLE ARMATURE TORSION ROD EXHAUST OUTPUT PRESSURE OUTPUT CENTER SPACER ASSEMBLY NOZZLE PRESSURE FIXED RESTRICTION RELAY SUPPLY PRESSURE EXHAUST PRESSURE CP4285-A A1505-3 4 VALVE PLUG SUPPLY Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X102 Valve Stroking Time Installation Figure 3 shows relative times for loading and exhausting an actuator. Exhausting times are nominally 25 percent of the loading times. Stroking time depends upon the size of the actuator, travel, relay characteristics and the magnitude and rate of change of the input signal. If stroking time is critical, contact your Emerson Process Management sales office. Standard positions for actuator mounting and pipestand mounting are shown on the front cover and figure 4, respectively. Dimensions are shown in figure 4. Ordering Information To determine what ordering information is required, refer to the Specifications table. Carefully review the information under each specification and in the referenced table. Specify the desired choice wherever there is a selection to be made. Always specify the type number as identified in the Available Configurations specification. Figure 3. Output‐Time Relationship 100 OUTPUT (% OF 546 OUTPUT SPAN) 90 For transducers that are to be used in intrinsically safe installations, specify the rating required and the system with which the unit will be used. 80 70 LOADING 60 50 40 30 EXHAUSTING 20 10 0 0 19A1361‐A A3103 10 20 30 40 50 60 TIME (%) 70 80 90 100 When ordering actuator mounting parts, specify the actuator type, size, travel, and diaphragm pressure range. For all Fisher 657 and 667 actuators except size 80, specify whether actuator yoke or actuator casing mounting is desired (yoke mounting is only available on size 80 actuators). For split‐range operation, specify the portion of input signal to be used; e.g. 4 to 12 milliamps of a standard 4 to 20 milliamp signal. 5 Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X012 Figure 4. Dimensions 1/4 NPT SUPPLY CONNECTION WHEN FILTER REGULATOR IS FURNISHED 329 (12.94) 1/4 NPT OUTPUT CONNECTION 78 (3.06) 125 (4.94) 171 (6.75) 52 (2.06) 46 (1.81) 43 (1.69) 67 (2.62) 40 (1.56) 51 (2.00) 32 (1.25) 164 (6.44) 44 (1.75) 165 (6.50) 83 (3.25) 22 (0.88) 70 (2.75) 1/2 NPT CONDUIT CONNECTION 51 PIPE (2.00) CP7280-E A1249-1 51 (2.00) 1/4 NPT SUPPLY CONNECTION WHEN FILTER REGULATOR IS NOT FURNISHED 40 (1.56) PIPESTAND MOUNTING 1/4 NPT OUTPUT CONNECTION 78 (3.06) 329 (12.94) 40 (1.56) 51 (2.00) 16 (0.62) CP6477-E A1248-1 44 (1.75) 46 (1.81) 32 (1.25) 83 (3.25) 8.7 (0.34) 56 (2.25) 70 (2.75) 125 (4.94) 37 (1.44) 6.3 (0.25) 37 (1.44) 70 (2.75) 22 (0.88) 164 (6.44) 1/2 NPT CONDUIT CONNECTION ACTUATOR MOUNTING mm (INCH) 6 Product Bulletin 546 Transducer 62.1:546 September 2012 D200061X102 Table 1. Electromagnetic Immunity Performance Port Phenomenon Enclosure I/O signal/control Basic Standard Test Level Performance Criteria(1) Electrostatic discharge (ESD) IEC 61000‐4‐2 4 kV contact 8 kV air Radiated EM field IEC 61000‐4‐3 80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% A Rated power frequency magnetic field IEC 61000‐4‐8 60 A/m at 50 Hz A Burst (fast transients) IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV (line to ground only, each) B IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms with 1kHz AM at 80% A Conducted RF A Specification limit = ±1% of span 1. A=No degradation during testing. B = Temporary degradation during testing, but is self‐recovering. Table 2. Hazardous Area Classifications—CSA (Canada) Certification Body Certification Obtained Explosion-proof Class I, Division 1, Group C,D CSA Class II, Division 1, Groups E,F,G Class I, Division 2, Groups A,B,C,D Class II, Division 2, Groups F,G Temperature Code Enclosure Rating T5 (Tamb = 66_C) CSA ENC 3 T5 CSA ENC 3 Temperature Code Enclosure Rating T5 (Tamb = 60_C) NEMA 3R T5 NEMA 3R Table 3. Hazardous Area Classifications—FM (United States) Certification Body Certification Obtained Explosion-proof Class I, Division 1, Groups C,D FM Class II, Division 1, Groups E,F,G Class I, Division 2, Groups A,B,C,D Class II, Division 2, Groups F,G 7 Product Bulletin 62.1:546 September 2012 546 Transducer D200061X012 Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher is a mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore www.Fisher.com E 8 1989, 2012 Fisher Controls International LLC. All rights reserved.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39 Producer : Acrobat Distiller 8.3.1 (Windows) Modify Date : 2012:08:13 09:45:10-05:00 Create Date : 2012:08:13 09:17:52-05:00 Metadata Date : 2012:08:13 09:45:10-05:00 Format : application/pdf Title : untitled Document ID : uuid:f4410c69-5ed7-4ddd-9f39-f3b2860e6342 Instance ID : uuid:88ae7ba7-7f48-420d-b472-cc72fb2f925a Page Count : 8EXIF Metadata provided by EXIF.tools