Emerson Fisher Fieldvuedvc2000 Digital Valve Controller Quick Start Manual
2015-03-30
: Emerson Emerson-Fisher-Fieldvuedvc2000-Digital-Valve-Controller-Quick-Start-Manual-681720 emerson-fisher-fieldvuedvc2000-digital-valve-controller-quick-start-manual-681720 emerson pdf
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Fisher FIELDVUE™ DVC2000 Digital Valve Controller Contents Using this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Basic Setup and Calibration . . . . . . . . . . . . . . . . . . . . 18 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Hazardous Area Approvals and Special Instructions Instructions for “Safe Use”and Installations in Hazardous Locations . . . . . . . . . . . . . . . . . . . . . 33 Instrument Level HC, AD, PD AC Device Type 5 5 Device Revision 1 1 Hardware Revision 1&2 1&2 Firmware Revision 1, 2, 3, 4 & 5 1, 2, 3, 4 & 5 DD Revision 3 1 W8861 Note This guide provides installation, initial setup, and calibration information for the DVC2000 digital valve controller. See the FIELDVUE DVC2000 Digital Valve Controller Instruction Manual (D103176X012), available from your Emerson Process Management sales office, for additional information, or visit our website at www.FIELDVUE.com. www.Fisher.com Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Local Interface Flow Chart These items are identified by an alert icon on the default screen TRAVEL = 66.8% 14.6 MA 0.92 BAR Y 1 Y Home Screen TRAVEL DEVIATION SHUTDOWN ACTIVATED ! CHECK MOUNTING CHECK I/P CONVERTER CHECK SUPPLY Y FINDING 0% ... Y FINDING 50% ... FINDING 0% ... Y FINDING 50% ... Y MOVE VALVE TO 0% TRAVEL Y FINDING 50% ... Y AUTOTUNING COMPLETE Y AUTOTUNING FAILED USE MANUAL TUNING Y FINDING 100% ... Y FINDING 0% ... Y Y VALVE WILL MOVE PRESS FOR 3 SEC Y QUICK SETUP Y 2 Y B SAVE AND EXIT? PRESS Y AUTO Y MANUAL Y AUTO Y SAVE AND EXIT? PRESS QUICK OPEN LINEAR EQUAL % CUSTOM 1 SAVE AND EXIT? EXIT W/O SAVING? Y Y CONTROL ANALOG Y Only when transmitter / limit switch hardware is installed. Y LOCAL CONTROL ANALOG OR DIGITAL MANUAL 2 SAVE AND EXIT? PRESS 1 SAVE AND EXIT? EXIT W/O SAVING? B 8 USE OR TO SEND 20 mA Y USE OR TO SEND 4 mA Y Y Y mA OUT WILL CHANGE PRESS FOR 3 SEC Y B POSITION 7 TRANSMITTER CAL MANUAL SP = XXX TRAVEL = XXX CHARACTERISTIC LINEAR Y Y Y Y Y Y Y APPLY 20 mA THEN PRESS 5 mA ... 20 mA Y APPLY 4 mA THEN PRESS Y Y Y Y 4 mA ... 19 mA INPUT RANGE HIGH 20 mA 1 SAVE AND EXIT? EXIT W/O SAVING? Y B INPUT RANGE LOW 4 mA DAMPING NEUTRAL 1 +5 NEUTRAL -5 Y BAR PSI KPA CLOSED OPEN VALVE WILL MOVE PRESS FOR 3 SEC PRESSURE UNITS BAR Y Y Y ZERO CTL SIGNAL VALVE CLOSED Y ANALOG INPUT CALIBRATION TUNING C EXPERT, C,D,E,F,G H,I,J,K,L,M 5 DETAILED SETUP 1 AUTOTUNING IN PROGRESS... Y VALVE MAY MOVE PRESS FOR 3 SEC Y Y AUTOMATIC MANUAL B 6 MOVE VALVE TO 100% TRAVEL TUNING AUTOMATIC MANUAL Y Y VALVE WILL MOVE PRESS FOR 3 SEC Y Y Y 4 TUNING VALVE WILL MOVE PRESS FOR 3 SEC AUTOMATIC MANUAL B FINDING 100% ... Y Y CALIBRATION AUTOMATIC Y Y TRAVEL CALIBRATION 3 Y B Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Y Y FW3:1, HW1:2 TUNING = C Y SWITCH1 = OPEN SWITCH 2 = CLOSED Y Y REPLACE MAIN BOARD Y Only when transmitter / limit switch hardware is installed PROTECTION OFF 1 OFF ON Y Y Y QUICK SETUP COMPLETE 1 CALIBRATION COMPLETE 1 CALIBRATION FAILED 1 Y SAVE AND PRESS EXIT? + INVERT DISPLAY 180 Note: Hold + for 3 to 10 seconds + CANCEL (TAKES YOU TO THE HOME SCREEN) Note: Hold + for 3 to 10 seconds 1 SAVE AND EXIT? EXIT W/O SAVING? + + + LANGUAGE SELECTION Y Y Y Y 1 BELOW ABOVE DISABLED Y Y VALVE MAY MOVE PRESS FOR 3 SEC Y Y 125% ... -25% SWITCH2 CLOSED BELOW 10% Y Y ABOVE BELOW DISABLED SWITCH2 TRIP POINT 10% Y 125% ... -25% SWITCH1 CLOSED ABOVE 90% Y Only when transmitter / limit switch hardware is installed. SWITCH1 TRIP POINT 90% Y CLOSED OPEN Y Y TRANSMITTER 4 mA CLOSED SAVE AND EXIT? PRESS Y Note: Hold + + + for 3 to 10 seconds EXIT W/O SAVING? PRESS 1 Only when transmitter / limit switch hardware is installed THE FIELDVUE DVC2000 DIGITAL VALVE CONTROLLER IS A CORE COMPONENT OF THE PLANTWEB™ DIGITAL PLANT ARCHITECTURE. THE DIGITAL VALVE CONTROLLER POWERS PLANTWEB BY CAPTURING AND DELIVERING VALVE DIAGNOSTIC DATA. COUPLED WITH VALVELINK™ SOFTWARE, THE DVC2000 PROVIDES USERS WITH AN ACCURATE PICTURE OF VALVE PERFORMANCE, INCLUDING ACTUAL STEM POSITION, INSTRUMENT INPUT SIGNAL AND PNEUMATIC PRESSURE TO THE ACTUATOR. USING THIS INFORMATION, THE DIGITAL VALVE CONTROLLER DIAGNOSES NOT ONLY ITSELF, BUT ALSO THE VALVE AND ACTUATOR TO WHICH IT IS MOUNTED. 3 DVC2000 Digital Valve Controller April 2014 Quick Start Guide D103203X012 Use of this Guide This guide describes how to install the digital valve controller and setup and calibrate using the local operator interface. The interface consists of a liquid crystal display, four pushbuttons, and a switch for position transmitter configuration. The DVC2000 is supplied with one of three different language packs preinstalled, depending on the firmware revision and ordering option. Language pack options are shown in table 1. To configure the language, follow the procedure outlined in the Basic Setup section. The instrument must be powered with at least 8.5 volts and 3.5 mA to operate the local interface. Certain procedures require up to 20 mA of current. You can also setup and calibrate the instrument using a Field Communicator, a personal computer with ValveLink software or AMS Suite: Intelligent Device Manager. For information on using the software with a FIELDVUE instrument, refer to the appropriate user guide or help. Additional information for installing, operating, and maintaining the DVC2000 digital valve controller can be found in the related documents listed on page 32. Do not install, operate, or maintain a DVC2000 digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety cautions and warnings. Refer to Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations, on page 33, for approval specific safe use information. If you have any questions about these instructions, contact your Emerson Process Management sales office before proceeding. 4 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Installation Note The DVC2000 is not designed to correct for significant stem rotation on sliding stem actuators. WARNING Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before mounting the DVC2000 digital valve controller: D Always wear protective clothing, gloves, and eyewear when performing any installation procedures. D Do not remove the actuator from the valve while the valve is still pressurized. D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the control valve. D Use bypass valves or completely shut off the process to isolate the control valve from process pressure. Relieve process pressure from both sides of the control valve. D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. D Check with your process or safety engineer for any additional measures that must be taken to protect against process media. D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not applying force to the valve stem; this will allow for the safe removal of the stem connector. WARNING This product is intended for a specific range of application specifications, found in the Specifications table on page 29. Incorrect configuration of a positioning instrument could result in the malfunction of the product, property damage or personal injury. Note Refer to Hazardous Area Approvals and Special Instructions for “Safe Use" and Installations in Hazardous Locations, on page 33, for approval specific safe use and installation information. Valve / Actuator Mounting If ordered as a part of a control valve assembly, the factory will mount the digital valve controller on the actuator and calibrate the instrument. If you purchased the digital valve controller separately, you will need a mounting kit to mount the digital valve controller on the actuator. The following procedures are general guidelines you should consider when mounting the digital valve controller. See the instructions that come with the mounting kit for detailed information on mounting the digital valve controller to a specific actuator model. 5 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 The DVC2000 housing is available in four different configurations, depending on the actuator mounting method and threaded connection style. Figure 1 shows the available configurations. Figure 1. Housing Variations HOUSINGS FOR LINEAR AND ROTARY ACTUATORS HOUSINGS FOR FISHER GX ACTUATORS CONNECTIONS AVAILABLE: M20 CONDUIT AND G1/4 PNEUMATIC 1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC CONDUIT CONNECTIONS PNEUMATIC CONNECTIONS CONNECTIONS AVAILABLE: M20 CONDUIT AND G1/4 PNEUMATIC 1/2 NPT CONDUIT AND 1/4 NPT PNEUMATIC W9015 LINEAR, M8 ROTARY NAMUR, M6 W9591 CAPTIVE MOUNTING BOLTS, M8 The feedback system for the DVC2000 digital valve controller utilizes a magnetic field for true linkage‐less, non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used. CAUTION The magnet material has been specifically chosen to provide a long‐term stable magnetic field. However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment include, but are not limited to: transformers, DC motors, stacking magnet arrays. CAUTION General Guidelines for use of High Power Magnets with Positioners Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless of the positioner model, high power magnets can affect the positioner’s ability to control the valve. Technicians should avoid the use of high power magnets in close proximity with any positioner. Use of Magnetic Tools with the DVC2000 D Magnetic Tip Screw Drivers – Magnetic tip screw drivers should not be brought in close proximity to the DVC2000 or the magnetic feedback array (located at the back of the instrument) during process operations. D Calibrator Strap Magnets – These are high power magnets used to hold 4-20 ma calibrators. Normally, these calibrators would not be used while an instrument is controlling the process. High power magnets should be kept at least 15 cm (6 inches) from the DVC2000. 6 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Note As a general rule, do not use less than 50% of the magnet array for full travel measurement. Performance will decrease as the array is increasingly subranged. The linear magnet arrays have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor (on the back of the DVC2000 housing) has to remain within this range throughout the entire valve travel. See figure 2. The linear magnet arrays are symmetrical. Either end may be up. There are a variety of mounting brackets and kits that are used to mount the DVC2000 to different actuators. However, despite subtle differences in fasteners, brackets, and connecting linkages, the procedures for mounting can be categorized as follows: D Air‐to‐open sliding‐stem (linear) actuators D Air‐to‐close sliding‐stem (linear) actuators D Air‐to‐open Fisher GX actuator D Air‐to‐close GX actuator D Rotary actuators with travel up to 90 degrees See figure 3 for the different travel feedback magnet pieces. Figure 2. Travel Range VALID TRAVEL RANGE 50 mm (2 INCH) SHOWN Figure 3. Magnet Assemblies INDEX MARK ROTARY 90 SLIDING STEM (LINEAR) 50 mm (2‐INCH) MAGNET ASSEMBLY (ATTACHED TO VALVE STEM) W8830 SLIDING STEM (LINEAR) 25 mm (1‐INCH) NOTE: VALID TRAVEL RANGE INDICATED BY WHITE ARROWS W9014 7 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Sliding-Stem (Linear) Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. 2. Attach the mounting bracket to the actuator. 3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners because fine adjustment is required. CAUTION Do not install a magnet array that is shorter than the physical travel of the actuator. Loss of control will result from the magnet array moving outside the range of the index mark in the feedback slot of the DVC2000 housing. 4. Using the alignment template (supplied with the mounting kit), position the feedback array inside the retaining slot. 5. Align the magnet array as follows: D For air‐to‐open actuators (e.g. Fisher 667) vertically align the magnet array so that the center line of the alignment template is lined up as close as possible with the upper extreme of the valid travel range on the feedback array. See figure 4. D For air‐to‐close actuators (e.g. Fisher 657) vertically align the magnet array so that the center line of the alignment template is lined up as close as possible with the lower extreme of the valid travel range on the feedback array. See figure 5. Figure 4. Air‐to‐Open Magnet Array Alignment Figure 5. Air‐to‐Close Magnet Array Alignment ALIGNMENT TEMPLATE RETAINING SLOT ALIGNMENT TEMPLATE RETAINING SLOT LINE UP WITH LOWER EXTREME OF VALID TRAVEL RANGE LINE UP WITH UPPER EXTREME OF VALID TRAVEL RANGE W9718 8 W9719 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 6. Tighten the fasteners and remove the alignment template. Note Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 N•m (21 in•lbf) for 4 mm screws, and 5.08 N•m (45 in•lbf) for 5 mm screws. While tightening the fasteners using the hex key should be sufficient, blue (medium) thread locker may be used for additional security. 7. Mount the digital valve controller to the mounting bracket, using the mounting bolts. See figure 6. 8. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC2000 housing is within the valid range on the magnet assembly throughout the range of travel. See figure 2. 9. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow pointing away from the opening. See figure 7. Figure 6. Mounting Holes for Linear Actuators Figure 7. Conduit and Pneumatic Thread Variations ARROW P0INTING AWAY FROM PORT = OUTPUT TO ACTUATOR 1/4 NPT PNEUMATIC CONNECTIONS ARROW P0INTING TOWARDS THE PORT = AIR SUPPLY IN M8 THREADED MOUNTING HOLES W9015 G1/4 PNEUMATIC CONNECTIONS W9016 9 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Mounting on GX Actuators The DVC2000 digital valve controller mounts directly on the GX actuator without the need for a mounting bracket. However, in applications where the process temperature exceeds 80_C (176_F), it may be necessary to apply an insulating gasket between the actuator yoke and the DVC2000, as shown in figure 8. The heat conducted from the process line will transmit through the valve body and actuator and ultimately to the DVC2000. Temperature seen at the DVC2000 is a function of the ambient temperature as well as the process temperature. Guidelines on when to apply the high temperature gasket set are shown in figure 9. Figure 8. Mounting to Fisher GX Actuator with Insulating Gasket and O‐Ring. Figure 9. Guidelines for Applying High Process Temperature Solutions to the Fisher GX and FIELDVUE DVC2000 100 80 AMBIENT TEMP (C) 60 40 20 0 -20 -40 -100 -50 0 50 100 150 200 250 300 PROCESS TEMP (C) NOTES ZONE 1: STANDARD GX BONNET AND STANDARD DVC2000 MOUNTING APPLY. ZONE 2: REQUIRES GX EXTENSION BONNET OR HIGH TEMPERATURE DVC2000 GASKET SET. Note The GX extension bonnet option is an alternate way to address the high process temperature influence on the DVC2000. However, if the extension bonnet is used, the high temperature DVC2000 mounting kit is not required. 10 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 If the process and ambient temperatures exceed the limits indicated by zone 2, then the DVC2000 high temperature mounting kit can not be used. If temperatures exceed zone 2, you must use an extension bonnet or bracket mounted instrument. Identify the yoke side to mount the DVC2000 digital valve controller based on the actuator fail mode. Refer to the GX Control Valve and Actuator System instruction manual (D103175X012). 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. 2. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners because fine adjustment is required. CAUTION Do not install a magnet array that is shorter than the physical travel of the actuator. Loss of control will result from the magnet array moving outside the range of the index mark in the feedback slot of the DVC2000 housing. 3. Using the alignment template (supplied with the mounting kit), position the feedback array inside the retaining slot. 4. Align the magnet array as follows: D For air‐to‐open GX actuators vertically align the magnet array so that the center line of the alignment template is lined up as close as possible with the upper extreme of the valid travel range on the feedback array. See figure 10. D For air‐to‐close GX actuators vertically align the magnet array so that the center line of the alignment template is lined up as close as possible with the lower extreme of the valid travel range on the feedback array. See figure 11. Figure 10. Air‐to‐Open Fisher GX Magnet Array Alignment Figure 11. Air‐to‐Close Fisher GX Magnet Array Alignment ALIGNMENT TEMPLATE ALIGNMENT TEMPLATE RETAINING SLOT RETAINING SLOT LINE UP WITH UPPER EXTREME OF VALID TRAVEL RANGE W9218 LINE UP WITH LOWER EXTREME OF VALID TRAVEL RANGE W9219 11 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below. Note Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 N•m (21 in•lbf) for 4 mm screws, and 5.08 N•m (45 in•lbf) for 5 mm screws. While tightening the fasteners using the hex key should be sufficient, blue (medium) thread locker may be used for additional security. For Air‐to‐Open GX Actuators 6. Remove the top plug (R1/8) from the back of the DVC2000 housing. This pneumatic output port on the DVC2000 lines up with the integral GX actuator pneumatic port. See figure 12. Figure 12. Modifications for Fisher GX Actuator - Air‐to‐Open Construction Only REMOVE THE R1/8 PLUG INSTALL THE O‐RING BEFORE ASSEMBLING TO THE GX ACTUATOR ADD THE 1/4 NPT OR G1/4 PLUG W9019 M8 MOUNTING BOLTS 7. Install the plug (either G1/4 or 1/4 NPT, included in the mounting kit) to the external output pneumatic port. 8. Remove the cover of the digital valve controller. 9. Using a 6 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad on the side that has the open pneumatic port. Be sure to place the O‐ring between the digital valve controller's pneumatic output and the actuator mounting pad. Pneumatic tubing is not required because the air passages are internal to the actuator. 10. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC2000 housing is within the valid range on the magnet assembly throughout the range of travel. See figure 2. 11. Install a vent in the port on the upper diaphragm casing's air supply connection on the actuator yoke leg. 12 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Air‐to‐Close GX Actuators 6. Remove the cover of the digital valve controller. 7. Using a 6 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad. Note The O‐ring and G1/4 or 1/4 NPT plugs (supplied in the mounting kit) are not used with this actuator construction. 8. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should be positioned so that the index mark on the pole pieces (back of the positioner housing) is within the valid range on the magnet assembly throughout the range of travel. See figure 2. 9. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow pointing away from the opening. See figure 7. 10. Install a vent in the port on the lower diaphragm casing. Note When field converting a GX actuator from fail‐open to fail‐closed (or vice‐versa), you will need to change the plugs for the pneumatic passages in the DVC2000 housing. D To convert to fail‐closed, remove the R1/8 pneumatic plug on the back of the DVC2000 housing and install an O‐ring. Plug the external pneumatic output with a 1/4 NPT or G1/4 plug (depending on the housing version). Refer to figure 12. D To convert to fail‐open, remove the external pneumatic plug (1/4 NPT or G1/4 plug depending on the housing version). Install an R1/8 plug on the back of the DVC2000 housing. Install tubing between the pneumatic output connection of the DVC2000 to the pneumatic port on top of the actuator casing. 13 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Guidelines for Mounting on Quarter‐Turn (Rotary) Actuators The DVC2000 digital valve controller can be mounted to any quarter‐turn (rotary) actuator, as well as those that comply with the NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 13. Figure 13. For Rotary Actuators (with Typical Mounting Bracket Shown) M6 MOUNTING BOLTS (4) W8835 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. 2. Attach the magnet assembly to the actuator shaft. At mid‐travel, the flats on the magnet assembly should be approximately parallel to the channel on the back of the DVC2000 housing, as shown in figure 14. 3. Install the mounting bracket on the actuator. 4. Attach the digital valve controller to the mounting bracket using the 4 mounting bolts, as shown in figure 13. 5. Check for clearance between the magnet assembly and the positioner feedback slot. 6. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow pointing away from the opening. See figure 7. Figure 14. Magnetic Assembly Orientation on Quarter‐Turn Actuators ORIENTATION AT ONE TRAVEL EXTREME ORIENTATION AT MID‐TRAVEL (FLATS PARALLEL TO DVC2000 CHANNEL) 1 ORIENTATION AT THE OTHER TRAVEL EXTREME 1 THIS EXAMPLE SHOWS AN ACTUATOR WITH 90 TRAVEL. ON AN ACTUATOR THAT HAS LESS THAN 90 TRAVEL THE MAGNET ASSEMBLY MAY NOT BE PARALLEL AT THE MID-TRAVEL POINT. TO VERIFY THE MAGNET ASSEMBLY POSITION IS IN WORKING RANGE, CONFIRM TRAVEL COUNTS ARE WITHIN THE EXPECTED RANGE OF 175-3800 USING VALVELINK SOFTWARE OR A FIELD COMMUNICATOR. 14 W8836 Quick Start Guide D103203X012 DVC2000 Digital Valve Controller April 2014 Electrical and Pneumatic Connections The electrical and pneumatic connections on the digital valve controller are available with the following combinations: D 1/4 NPT supply and output with 1/2 NPT conduit connections D G1/4 supply and output with M20 conduit connections Supply Connections WARNING Severe personal injury or property damage may occur from process instability if the instrument air supply is not clean, dry and oil‐free. While use and regular maintenance of a filter that removes particles larger that 40 micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and industry instrument air quality standards for use with corrosive air or if you are unsure about the proper amount or method of air filtration or filter maintenance. Supply pressure must be clean, dry air or noncorrosive gas that meets the requirements of ISA Standard 7.0.01. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized. A Fisher 67CFR filter regulator with standard 5 micrometer filter, or equivalent, may be used to filter and regulate supply air. If pressure regulation is not required, a 10 micron in‐line filter may be used. Connect the nearest suitable supply source to the connection with the arrow pointing towards the opening (see figure 7). Electrical Connections WARNING Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion. Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval. Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or explosion. The valve may move in an unexpected direction when power is applied to the digital valve controller. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly when applying power to the instrument. The digital valve controller is normally powered by a control system output card. The use of shielded cable will ensure proper operation in electrically noisy environments. Wire size requirements are 14 AWG maximum, 26 AWG minimum. Be sure to follow the appropriate I.S. circuit guidelines when installing field wiring to the loop terminals as well as the limit switch and transmitter terminals. 15 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Wire the digital valve controller as follows: 1. Remove the main instrument cover. 2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using local and national electrical codes that apply to the application. 3. Connect the control system output card positive wire “current output” to the +11 terminal. Connect the control system output card negative (or return) wire “current output” to the -12 terminal. 4. Two ground terminals are available for connecting a safety ground, earth ground, or drain wire. These ground terminals are electrically identical. Make connections to these terminals following national and local codes and plant standards. 5. Replace the cover if the local interface is not being used for configuration or calibration. Options Boards All three options circuits (transmitter, switch 1 and switch 2) control current from an external power source similar to the operation of a 2‐wire transmitter. Limit Switches On units that are supplied with integral limit switches, additional terminals provide the field wiring connection point. The limit switches are isolated from each other and from the digital valve controller's primary feedback. If only one switch is to be used, you must use channel 1. Although electrically isolated per Intrinsic Safety requirements, channel 2 derives its power from channel 1. Therefore channel 2 cannot be used alone. Wire the limit switches as follows: 1. Remove the main instrument cover. 2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using local and national electrical codes that apply to the application. 3. Connect the control system input card positive wire “switch input” to the +41 terminal. Connect the control system input card negative wire “switch input” to the -42 terminal. Refer to figure 15. Figure 15. Loop, Transmitter, and Limit Switch Terminals HART COMMUNICATION TERMINATION POINTS W8838 16 +31/ -32 (TRANSMITTER) +11/ -12 (LOOP) +41/ -42 (SWITCH 1) +51/ -52 (SWITCH 2) Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 4. If a second switch is to be used, connect the control system input card positive wire “switch input” to the +51 terminal. Connect the control system input card negative wire “switch input” to the -52 terminal. 5. Proceed to the Basic Setup section to configure the switch action. 6. Replace the cover if the local interface is not being used for configuration or calibration. Position Transmitter On units that are supplied with an integral valve position transmitter, additional terminals provide the field wiring connection point. The position transmitter circuit in the DVC2000 derives its operating power from the 4‐20 mA control system input in the same manner as a 2‐wire transmitter. In addition, the transmitter function gets position information (through an opto‐isolator) from the digital valve controller so the 4‐20 mA position control loop must also be powered in order for the position transmitter to provide an output representing the valve position. Note In an Intrinsically Safe installation with the options in use, the wire pairs must be shielded. Additionally, to prevent cross‐wiring, the individual wires must not be exposed beyond the terminal barrier walls. Wire the position transmitter as follows: 1. Remove the main instrument cover. 2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using local and national electrical codes that apply to the application. 3. Connect the control system input card positive wire “current input” to the +31 terminal. Connect the control system input card negative wire “current input” to the -32 terminal. Refer to figure 15. 4. Replace the cover if the local interface is not being used for configuration or calibration. Vent By design, the instrument exhausts supply air into the area under the cover. The vent should be left open to prevent pressure buildup under the cover and to drain any moisture that may accumulate in the housing. The control valve assembly should be installed so that the primary vent provides gravitational draining. If a remote vent is required, the vent line must be as short as possible with a minimum number of bends and elbows. Communications Connections A HART communicating device, such as a Field Communicator or a personal computer running ValveLink software communicating through a HART modem, interfaces with the DVC2000 digital valve controller. You can connect at any point on the 4‐20 mA loop. Alternatively, convenient termination points are located on the termination board (figure 15). The instrument must be powered before digital communication will commence. 17 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Basic Setup and Calibration The local operator interface is available on all DVC2000 digital valve controllers. The interface consists of a liquid crystal display, four pushbuttons, and a switch for position transmitter configuration. The DVC2000 is supplied with one of three different language packs preinstalled, depending on the firmware revision and ordering option. Language pack options are shown in table 1. To configure the language, follow the procedure outlined in the Basic Setup section. The instrument must be powered with at least 8.5 volts and 3.5 mA to operate the local interface. Certain procedures require up to 20 mA of current. CAUTION When accessing the terminals or pushbuttons, proper means of electrostatic discharge protection is required. Failure to provide appropriate protection can cause the valve to move, resulting in valve/actuator instability. Status Information The first (home) screen on the LCD that is displayed after applying power to the instrument contains basic status information. On an instrument that is calibrated and operating properly, the flow chart in figure 16 shows the available information by pressing the right (") arrow key. Figure 16. Home Screen on the LCD Only with Optional Transmitter / Limit Switches TRAVEL = 66.8% 14.6 MA 0.92 BAR A " SWITCH 1 = OPEN SWITCH 2 = CLOSED A " FW3:1, HW1:2 TUNING = C A " PROTECTION OFF OFF ON TRAVEL=##.#%—Current valve travel in percent of calibrated travel. ##.# MA—Current input signal applied to the instrument in mA. ##.## BAR—Current pressure output to the actuator in the configured units (BAR, PSI or MPA). SWITCH1—Current status of the optional limit switch wired to terminals +41 and -42. SWITCH2—Current status of the optional limit switch wired to terminals +51 and -52. FW#—Version of firmware running in the device. HW#—Version of electronics hardware installed. The first number (# : #) represents the main board, the second number (# : #) represents the secondary electronics. TUNING = X—Current tuning set parameters configured in the device. PROTECTION—Indicates whether the local interface is protected or not. With protection ON, the instrument cannot be configured or calibrated with the local pushbuttons. 18 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Basic Setup WARNING Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application, these changes may upset process control which may result in personal injury or property damage. When the DVC2000 digital valve controller is ordered as part of a control valve assembly, the factory mounts the digital valve controller and sets up the instrument as specified on the order. When mounting to a valve in the field, the instrument needs to be setup to match the instrument to the valve and actuator. Before beginning basic setup, be sure the instrument is correctly mounted and powered electrically and pneumatically. Selecting the Language The DVC2000 is supplied with one of three different language packs preinstalled, depending on the firmware revision and the ordering option. See table 1 for language pack options. Table 1. Language Pack Options Firmware Revision 1 or 2 3 3 Standard Standard Optional English X X X Japanese X X X Chinese X X X French X X X German X X X Italian X X X Spanish X X X Language Pack Portuguese X Russian X Polish X Czech X Arabic X Only firmware revision 3 or later will allow you to download different language packs to the DVC2000 using ValveLink software. To access the language selection screen on the DVC2000 local interface press the four arrow keys simultaneously for three (3) seconds. Use the UP or DOWN (Y or B) arrow keys to select the appropriate language. Press the RIGHT (") arrow key to confirm your selection. 19 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Quick Setup When installing the DVC2000 digital valve controller on an actuator for the first time, the quick setup procedure will calibrate and tune the instrument automatically. Table 2 lists the values that are preconfigured at the factory. Table 2. Factory Default Settings Accessible from the Local Interface Setup Parameter Default Setting Zero Control Signal Open(1) Pressure Units BAR or PSIG Input Range Low 4 mA Input Range High 20 mA Characteristic Linear Transmitter (optional feature) 4 mA = Valve Closed Switch 1 Trip Point (optional feature) 90% Switch 1 Closed (optional feature) Above 90% Switch 2 Trip Point (optional feature) 10% Switch 2 Closed (optional feature) Below 10% 1. If the instrument is shipped mounted on an actuator, this value depends upon the actuator on which the instrument is mounted. WARNING During calibration the valve will move full stroke. Changes to the tuning set may also cause the valve / actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly. Note If optional limits switches are being used, power must be applied to the switch circuits throughout the quick setup routine. Failure to power the switches may result in incorrect switch orientation. Refer to the DETAILED SETUP procedure for further explanation of the parameters. To access the QUICK SETUP routine from the home screen, press the DOWN (B) arrow key and then the RIGHT (") arrow key. A warning will advise you that this procedure will cause the valve to move. Another RIGHT (") button press will begin the calibration process. Pressing the LEFT (A) arrow key will bring you back to the main menu. This procedure will automatically calibrate the instrument and apply tuning parameters specifically fit for the size of the actuator. To abort the procedure at any time, press the RIGHT (") and LEFT (A) arrow keys together for 3 seconds. When the procedure is complete, press the RIGHT (") arrow key to return to the status screen. If the RIGHT (") button is not pressed within 30 seconds, the device will automatically revert back to the status screen. Figure 17. Quick Setup TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP 20 A " VALVE WILL MOVE PRESS FOR 3 SEC " FINDING 0%... " QUICK SETUP COMPLETE Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Travel Calibration WARNING During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid. Note If optional limits switches are being used, power must be applied to the switch circuits throughout the automatic or manual calibration routine. Failure to power the switches may result in incorrect switch orientation. To manually calibrate the instrument or automatically calibrate the instrument without changing the tuning values, the TRAVEL CALIBRATION routine is available. To access this procedure from the home screen, press the DOWN (B) arrow key two times and then the RIGHT (") arrow key once. From there follow the prompts as illustrated in figure 18. Figure 18. Travel Calibration TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP " Y B " CALIBRATION AUTOMATIC A FINDING 100%... " FINDING 0%... " FINDING 50%... COMPLETE " CALIBRATION FAILED " VALVE WILL MOVE PRESS FOR 3 SEC AUTOMATIC MANUAL " MANUAL TRAVEL A CALIBRATION AUTO " CALIBRATION MOVE VALVE TO 100% TRAVEL " MOVE VALVE TO 0% TRAVEL " FINDING 50%... " SAVE & EXIT? PRESS SAVE & EXIT? EXIT W/O SAVING? Note If the valve is manually calibrated to travel less than the physical travel stops allow, manual tuning (page 22) may be required to optimize the valve response. Automatic calibration will provide status information as the procedure is running. Manual calibration will require you to first adjust the input current to move the valve and then to press the RIGHT (") arrow key. After manual calibration is complete, you will have the choice to save the calibration or exit the procedure without saving. If you exit without saving, the last saved calibration data will be restored. 21 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Tuning WARNING Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly. To manually tune the instrument or automatically tune the instrument without changing the calibration values, the TUNING routine is available. To access this procedure from the home screen, press the DOWN (B) arrow key three times and then the RIGHT (") arrow key once. From there follow the prompts as illustrated in figure 19 below. Figure 19. Tuning TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP Y B TRAVEL CALIBRATION " B VALVE WILL MOVE PRESS FOR 3 SEC COMPLETE " AUTOTUNING IN PROCESS... " TUNING A " AUTOMATIC A AUTOMATIC MANUAL " MANUAL TUNING AUTO " AUTOTUNING Y VALVE MAY MOVE PRESS FOR 3 SEC " TUNING A C EXPERT, C,D,E,F,G, H,I,J,K,L,M AUTOTUNE FAILED USE MANUAL TUNING " DAMPING NEUTRAL A +5, +4, +3, +2, +1 NEUTRAL -5, -4, -3, -2, -1 " SAVE & EXIT? PRESS SAVE & EXIT? EXIT W/O SAVING? Automatic tuning will provide status information as the procedure is running. Manual tuning will require you to choose from one of eleven tuning sets. Each tuning set provides a preselected value for the digital valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response. Table 3 lists the proportional gain, velocity gain, and minor loop feedback gain values for preselected tuning sets. Manual tuning is only recommended when the automatic tuning procedure results in failure. 22 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Table 3. Gain Values for Preselected Turning Sets Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback Gain C 5 2 55 D 6 2 55 E 7 2 55 F 8 2 52 G 9 2 49 H 10 2 46 I 11 2 44 J 12 1 41 K 14 1 38 L 16 1 35 M 18 1 35 A typical starting point for most small actuators is “C”. Using the UP (Y) and DOWN (B) arrow keys will apply the values immediately. You can then change the input current to observe the response. When you are satisfied with the response, press the RIGHT (") arrow key to fine tune the instrument. The UP (Y) and DOWN (B) arrow keys will apply more or less damping to fine tune the overshoot after a step input change. After manual tuning is complete, you will have the choice to save the tuning data or exit the procedure without saving. If you exit without saving, the last saved tuning data will be restored. Detailed Setup If the factory default configuration values need to be changed, the DETAILED SETUP procedure provides access. See figure 20 for the flowchart showing the sequence of screens. To access this procedure from the home screen, press the DOWN (B) arrow key four times. The RIGHT (") arrow key brings you into the configuration items. Once you are in a particular configuration item, use the UP (Y) and DOWN (B) arrow keys to select the appropriate choice. To exit this procedure, press the RIGHT (") arrow key and view the remaining configuration items until you reach the exit screen. If you exit without saving, the last saved configuration data will be restored. Below is an explanation of the configuration items. Zero Control Signal—Identifies whether the valve is fully OPEN or fully CLOSED when the input is 0%. If you are unsure how to set this parameter, disconnect the current source to the instrument. The resulting valve travel is the Zero Control Signal. This corresponds to setting the output pressure to zero. Pressure Units—Defines the pressure units in either PSI, BAR, or KPA. Input Range Low—This will correspond to 0% travel if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, this will correspond to 100% travel. Input Range High—This will correspond to 100% travel if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, this will correspond to 0% travel. Characteristic—Defines the relationship between the travel target and the ranged set point. Ranged set point is the input to the characterization function. If the Zero Control Signal is closed, then a set point of 0% corresponds to a ranged input of 0%. If the Zero Control Signal is open, a set point of 0% corresponds to a ranged input of 100%. Travel target is the output from the characterization function. Note Travel cutoffs are enabled by default on all units. 23 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 The factory default characteristic is LINEAR. You can also use a QUICK OPEN, EQUAL %, or CUSTOM function. However, the custom function is initially configured linear, unless you use a HART based host to reconfigure the custom points. Custom configuration can be selected, but the curve cannot be modified with the local interface. Figure 20. Detailed Setup Flow Chart TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP Y B TRAVEL CALIBRATION Y B TUNING Y B DETAILED SETUP " ZERO CTL SIGNAL VALVE CLOSED A " PRESSURE UNITS BAR Only with Optional Position Transmitter / Limit Switches TRANSMITTER A 4MA CLOSED CLOSED OPEN " INPUT RANGE LOW 4 MA BAR PSI KPA CLOSED OPEN " A A " INPUT RANGE HIGH 20 MA A " CHARACTERISTIC LINEAR 20MA ... 5MA 4MA ... 19MA A QUICK OPEN LINEAR EQUAL % CUSTOM Only with Optional Position Transmitter / Limit Switches " SWITCH1 TRIP POINT 90% 125% ... -25% A " SWITCH1 CLOSED A " SWITCH2 ABOVE 90% ABOVE BELOW DISABLED TRIP POINT 10% 125% ... -25% A " SWITCH2 CLOSED A " SAVE & EXIT? BELOW 10% BELOW ABOVE DISABLED PRESS SAVE & EXIT? EXIT W/O SAVING Transmitter—This configures the relationship between the valve travel and the position transmitter output signal. If you select CLOSED, the transmitter will send 4 mA when the valve is closed. If you select OPEN, the transmitter will send 4 mA when the valve is open. A switch is located on the options board to select the transmitter fail signal (high+ or low-). High+ will result in a current output of > 22.5 mA upon transmitter failure. Low- will result in a current output of < 3.6 mA. Refer to figure 21 for location and switch selection. 24 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 21. XMTR Switch TRANSMITTER SWITCH FOR FAIL SIGNAL + HIGH (SHOWN) OR -LOW W8839 Switch #1 Trip Point—Defines the threshold for the limit switch wired to terminals +41 and -42 in percent of calibrated travel. Switch #1 Closed—Configures the action of the limit switch wired to terminals +41 and -42. Selecting ABOVE configures the switch to be closed when the travel is above the trip point. Selecting BELOW configures the switch to be closed when the travel is below the trip point. Selecting DISABLED removes the icons and status from the display. Switch #2 Trip Point—Defines the threshold for the limit switch wired to terminals +51 and -52 in percent of calibrated travel. Switch #2 Closed—Configures the action of the limit switch wired to terminals +51 and -52. Selecting ABOVE configures the switch to be closed when the travel is above the trip point. Selecting BELOW configures the switch to be closed when the travel is below the trip point. Selecting DISABLED removes the icons and status from the display. Note Switch #2 is only operational if power is applied to switch #1 also. Switch #2 cannot be used alone. Position Transmitter Calibration Note This procedure will not move the control valve. The instrument will simulate an output for calibration purposes only. This procedure is only available on units that have the optional position transmitter hardware installed. The DVC2000 digital valve controller is shipped from the factory with the position transmitter already calibrated. You do not normally need to perform this procedure. However, if you suspect that this needs adjustment, follow the procedure below and refer to figure 22. 25 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 22. Position Transmitter Calibration TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP Y B TRAVEL CALIBRATION Y B TUNING Y B DETAILED SETUP Y B ANALOG INPUT CALIBRATION Y B POSITION TRANSMIITTER CAL " mA OUT WILL CHANGE PRESS FOR 3 SEC A " USE OR TO SEND 4MA A " USE OR A TO SEND 20MA " SAVE & EXIT? PRESS SAVE & EXIT? EXIT W/O SAVING? Connect a current meter in series with the transmitter output terminals (+31 & -32) and a voltage source (such as the DCS analog input channel). From the home screen, press the DOWN (B) arrow key six times and then press the RIGHT (") arrow key. 1. Use the UP (Y) and DOWN (B) arrow keys to manipulate the output current read by the current meter. When 4 mA is read by the meter, press the RIGHT (") arrow key. 2. Again, use the UP (Y) and DOWN (B) arrow keys to manipulate the output current read by the current meter. When 20 mA is read by the meter, press the RIGHT (") arrow key. If you want to keep this calibration, select SAVE AND EXIT. If you exit without saving, the last saved configuration data will be restored. Local Control This procedure allows the user to manually control the position of the valve (see figure 23). To enter this procedure from the home screen, press the DOWN (B) arrow key seven times and then press the RIGHT (") arrow key. If you select ANALOG, you will return to the home screen and the digital valve controller will respond to the loop current. If you select MANUAL, you will move to the screen that shows the travel setpoint and the actual valve travel. 26 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 The UP (Y) and DOWN (B) arrow keys will allow you to change the setpoint and therefore move the valve manually. To exit the manual mode, use the LEFT (A) arrow key to return to the choice list. Select ANALOG. Note When placing the instrument back into ANALOG, the valve will step back to the position commanded by the input current. Figure 23. Local Control TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP Y B TRAVEL CALIBRATION Y B TUNING Y B DETAILED SETUP Y B ANALOG INPUT CALIBRATION Y B POSITION TRANSMIITTER CAL Only with Optional Position Transmitter / Limit Switches Y B LOCAL CONTROL " CONTROL ANALOG A " MANUAL SP = XX TRAVEL = XX.X ANALOG MANUAL Diagnostic Messages, Codes and Details The DVC2000 digital valve controller is constantly diagnosing itself for abnormal conditions while powered‐up. The following messages will appear on the local user interface if a fault condition exists (identified on the default screen by the alert symbol ! ). SWITCH 1 ??? SWITCH 2 ???—The alert symbol in conjunction with the above text indicates that limit switch circuit 1 is not powered, or at least one of the switches is enabled. In order for either of the switches to work, switch circuit 1 must be powered. Switch 2 cannot be used alone. To eliminate the alert symbol, you can either apply 5 to 30 VDC to switch circuit 1 or disable both switches from DETAILED SETUP. 27 DVC2000 Digital Valve Controller April 2014 Quick Start Guide D103203X012 Once switch circuit 1 is powered properly, question marks (???) will indicate that the corresponding switch is disabled. Shutdown Activated— This screen appears if the positioner has shut down and no air is being delivered to the actuator. Therefore, the valve is at its fail‐safe position. An example of a source of this error is corrupt firmware code upon start‐up. The factory default setting for this error is disabled. Therefore, this alert will only be enabled by actively configuring it with a HART based host (e.g. Field Communicator, ValveLink Software). Travel Deviation— This error message indicates that there is a difference between the input signal (after characterization) and the actuator travel reading from the position feedback element. The default setting is 7% for 5 seconds. These settings can be configured through a HART communicating host on any instrument HC tier or higher. Possible sources of this error are insufficient air supply or excessive valve friction. Replace Main Board— A problem with the electronics has been detected. Sources of this error may include hardware or firmware problems. If this error is detected, the instrument may be operational, but performance will be degraded. Check Mounting— The valve position feedback reading is valid, but it is outside the operating range. Sources of this error include loose or bent mounting brackets or a misaligned magnet array. This error does not identify faulty components, but rather faulty installation or alignment. This alert is also called a Travel Sensor Failure. Check Supply— The valve is not able to reach its target position due to insufficient supply pressure. This error will most likely occur in conjunction with the Travel Deviation error. Check I/P Converter— A problem relating to the I/P converter has been detected. Sources of this error include: D Electronics problems indicated by the drive current read back being out of range D Low supply pressure indicated by an active drive signal alert D A stuck valve resulting in integrator wind‐up. Device Locked by HART— Another HART host (e.g. ValveLink software, AMS Suite: Intelligent Device Manager, or the Field Communicator) is communicating with the DVC2000. Typically this means that the instrument is “out of service”. In devices with firmware version 3 or later, you can clear this message by holding down the left button while cycling power to the DVC2000. This will place the instrument back “in service.” FIELDVUE Instruments—This is displayed when there are no languages loaded on the DVC2000. This could occur during firmware download. Pressure = ???—The actuator pressure reading is greater than 125% of the configured maximum supply pressure. For example, if the supply pressure range was set to 35 psi and the actual supply pressure was 45 psi, you will see ???'s when the DVC2000 is delivering full supply pressure to the actuator. If you reduce the supply pressure, or stroke the valve closed (air‐to‐open/fail closed setup), eventually there will be a point where numerical values appear. This configuration parameter can be changed through the Field Communicator (1‐1‐2‐2‐3) or ValveLink software (Detailed Setup > Pressure). 28 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Specifications Air Consumption(2) Available Configurations Supply pressure At 1.5 bar (22 psig) (3): 0.06 normal m3/h (2.3 scfh) At 4 bar (58 psig) (4): 0.12 normal m3/h (4.4 scfh) J Integral mounting to the GX actuator J Sliding‐stem applications J Quarter‐turn rotary applications Air Capacity(2) The DVC2000 digital valve controller can also be mounted on other actuators that comply with IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE 3845 and NAMUR mounting standards. Supply pressure At 1.5 bar (22 psig) (3): 4.48 normal m3/h (167 scfh) At 4 bar (58 psig) (4): 9.06 normal m3/h (338 scfh) Independent Linearity Input Signal ±0.5% of output span Analog Input Signal: 4‐20 mA DC, nominal; split ranging available. Minimum Voltage: Voltage available at instrument terminals must be 8.5 volts for analog control, 9.0 volts for HART communication. Maximum Voltage: 30 volts DC Minimum Control Current: 4.0 mA (below 3.5 mA may cause microprocessor restart) Overcurrent Protection: Input circuitry limits current to prevent internal damage. Reverse Polarity Protection: No damage occurs from reversal of loop current. Electromagnetic Compatibility Meets EN 61326‐1 (First Edition) Immunity—Industrial locations per Table 2 of the EN 61326‐1 standard. Performance is shown in table 4 below Emissions—Class A ISM equipment rating: Group 1, Class A Tested to NAMUR NE21 requirements. Vibration Testing Method Tested per ANSI/ISA‐75.13.01 Section 5.3.5. A resonant frequency search is performed on all three axes. The instrument is subjected to the ISA specified 1/2 hour endurance test at each major resonance, plus an additional two million cycles. Output Signal Pneumatic signal as required by the actuator, up to full supply pressure Minimum Span: 0.5 bar (7 psig) Maximum Span: 7 bar (101 psig) Action: Single Acting, direct Input Impedance The input impedance of the DVC2000 active electronic circuit is not purely resistive. For comparison to resistive load specifications, an equivalent impedance of 450 ohms may be used. This value corresponds to 9 V @ 20 mA. Supply Pressure(1) Recommended: 0.5 bar (7 psig) greater than the maximum actuator requirements Maximum: 7 bar (101 psig) Electrical Classification Hazardous Area: CSA—Intrinsically Safe and Non‐incendive FM—Intrinsically Safe and Non‐incendive ATEX—Intrinsically Safe IECEx—Intrinsically Safe Supply pressure must be clean, dry air or noncorrosive gas that meets the requirements of ISA Standard 7.0.01. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized Refer to Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations, starting on page 33, for additional information. Temperature Limits(1) Electrical Housing: CSA—IP66, Type 4X FM, ATEX, IECEx—IP66 -40 to 85_C (-40 to 185_F). LCD may not be readable below -20_C (-4 _F). -continued- 29 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Specifications (continued) Other Classifications/Certifications GOST‐R—Russian GOST‐R INMETRO—National Institute of Metrology, Quality and Technology (Brazil) KGS— Korea Gas Safety Corporation (South Korea) NEPSI—National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation (China) PESO CCOE—Petroleum and Explosives Safety Organisation - Chief Controller of Explosives (India) RTN—Russian Rostekhnadzor Contact your Emerson Process Management sales office for classification/certification specific information Connections Standard Supply and Output Pressure: G1/4 internal Electrical: M20 internal Optional Supply and Output Pressure: 1/4 NPT internal Electrical: 1/2 NPT internal Materials of Construction Housing and Cover: A03600 low copper aluminum alloy Elastomers: nitrile, fluorosilicone Stem Travel Minimum: 8 mm (0.3125 inch) Maximum: 102 mm (4 inches) Shaft Rotation Minimum: 45_ Maximum: 90_ Mounting Designed for direct actuator mounting. For weatherproof housing capability, the vent must be positioned at the lowest point of the instrument. Weight 1.5 kg (3.3 lbs) Options JAirset: 67CFR with filter Language Packs: J Standard: English, German, French, Italian, Spanish, Japanese, Chinese, Portuguese, Russian, Polish, and Czech J Optional: English, German, French, Italian, Spanish, Japanese, Chinese, and Arabic JPipe‐away vent JLimit Switches: Two isolated switches, configurable throughout calibrated travel range Supply Voltage: 5‐30 VDC OFF State: 0.5 to 1.0 mA ON State: 3.5 to 4.5 mA (above 5V) Reference Accuracy: 2% of travel span(5) JTransmitter: 4‐20 mA output, isolated Supply Voltage: 8‐30 VDC Fault Indication: offrange high or low Reference Accuracy: 1% of travel span(5) Declaration of SEP Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 / EC. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance. However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives. 1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. Note: Temperature limits vary based on hazardous area approval. 2. Normal m3/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia. 3. Low pressure relay: 0 to 3.4 bar (0 to 50 psig). 4. High pressure relay: 3.5 to 7.0 bar (51 to 102 psig). 5. Typical values when calibrated at temperature. 30 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Table 4. EMC Summary Results—Immunity Port Phenomenon Electrostatic discharge (ESD) Enclosure I/O signal/control Basic Standard Test Level Performance Criteria(1) IEC 61000‐4‐2 6 kV contact 8 kV air B Radiated EM field IEC 61000‐4‐3 80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80% A Rated power frequency magnetic field IEC 61000‐4‐8 30 A/m at 50 Hz, 60 sec A Burst (fast transients) IEC 61000‐4‐4 $1 kV A Surge IEC 61000‐4‐5 $1 kV (line to ground only, each) B Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 10 Vrms A Performance criteria is + / - 1% effect. 1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering. 31 DVC2000 Digital Valve Controller Quick Start Guide April 2014 D103203X012 Related Documents Other documents containing information related to the DVC2000 digital valve controller include: D Bulletin 62.1:DVC2000 - Fisher FIELDVUE DVC2000 Digital Valve Controller (D103167X012) D Fisher FIELDVUE DVC2000 Digital Valve Controller Instruction Manual (D103176X012) D INMETRO Hazardous Area Approvals for FIELDVUE DVC2000 Digital Valve Controller (D103780X012) D FIELDVUE Digital Valve Controller Split Ranging— Supplement to HART Communicating Fisher FIELDVUE Digital Valve Controller Instruction Manuals (D103262X012) D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM)— Supplement to HART Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103263X012) D Audio Monitor for HART Communications— Supplement to HART Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103265X012) D HART Field Device Specification— Fisher FIELDVUE DVC2000 Digital Valve Controller (D103783X012) D Using the HART Tri‐Loopt HART‐to‐Analog Signal Converter with Fisher FIELDVUE Digital Valve Controllers— Supplement to HART Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103267X012) All documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com. Educational Services For information on available courses for the DVC2000 digital valve controller, as well as a variety of other products, contact: Emerson Process Management Educational Services - Registration P.O. Box 190 Marshalltown, IA 50158-2823 Phone: 800-338-8158 or 641-754-3771 FAX: 641-754-3431 e‐mail: education@emerson.com 32 Quick Start Guide D103203X012 DVC2000 Digital Valve Controller April 2014 Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval. Note This information supplements the nameplate markings affixed to the product. Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales office for approval/certification information not listed here. WARNING Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification. CSA Intrinsically Safe, Non‐Incendive No special conditions for safe use. Refer to figure 24 for a typical DVC2000 CSA approval nameplate and figure 25 for installation drawing GE12444. Figure 24. Typical CSA Nameplate 33 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 25. CSA Installation Drawing EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE (CEC) PART 1: BARRIERS MUST BE CSA APPROVED WITH ENTITY PARAMETERS AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S I.S. INSTALLATION INSTRUCTIONS. THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS, NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax) AND THE CURRENT (Imax) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc) AND CURRENT (Isc) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED. FORMULAS - Vmax > Voc, Imax > Isc, Ci + Ccable < Ca, Li + Lcable < La ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS: PMAX Li CIRCUIT VMax (Ui) IMAX(Ii) Ci XMTR MAIN LS1 LS2 28Vdc 30Vdc 16Vdc 16Vdc 100mA 130mA 76mA 76mA 5nF 10.5nF 5nF 5nF 0 mH 0.55 mH 0 mH 0 mH 1W 1W 1W 1W WHERE MULTIPLE IS CIRCUITS ARE USED: EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE. I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES AS SPECIFIED IN DETAIL 1. CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED AREA (SEE DETAIL 1). XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL. HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION CLASS I, DIV. 1, GROUPS A,B,C,D, CLASS I, ZONE 0, GROUP IIC DVC2000 XMTR CSA APPROVED BARRIER MAIN CSA APPROVED BARRIER LS1 CSA APPROVED BARRIER LS2 CSA APPROVED BARRIER IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING. WARNING XMTR MAIN LS1 THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. CARE MUST BE TAKEN DURING INSTALLATION AND USE TO PREVENT IMPACT OR FRICTION. LS2 PARTITIONED AREA DETAIL 1 GE12444‐C FM Special Conditions of Use Intrinsically Safe, Non‐Incendive The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. Refer to figure 26 for a typical DVC2000 FM approval nameplate and figure 27 for installation drawing GE10683. 34 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 26. Typical FM Nameplate Figure 27. FM Installation Drawing INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) AND ANSI/ISA RP12.6. BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS, NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax) AND THE CURRENT (Imax) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc) AND CURRENT (Isc) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED. FORMULAS - Vmax > Voc, or Vt, Ci + Ccable < Ca, Pi > Po, or Pt Imax > Isc, or It, Li + Lcable < La WARNING THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. CARE MUST BE TAKEN DURING INSTALLATION AND USE TO PREVENT IMPACT OR FRICTION. HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION CLASS I, DIV. 1, GROUPS A,B,C,D CLASS I ZONE 0 Aex ia IIC DVC2000 ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS: CIRCUIT VMax (Ui) IMAX(Ii) Ci Li PMAX XMTR MAIN LS1 LS2 28Vdc 30Vdc 16Vdc 16Vdc 5nF 10.5nF 5nF 5nF 0 mH 0.55 mH 0 mH 0 mH 1W 1W 1W 1W 100mA 130mA 76mA 76mA XMTR FM APPROVED BARRIER MAIN FM APPROVED BARRIER LS1 FM APPROVED BARRIER LS2 FM APPROVED BARRIER WHERE MULTIPLE IS CIRCUITS ARE USED: EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE. I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES AS SPECIFIED IN DETAIL 1. CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED AREA (SEE DETAIL 1). XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL. XMTR MAIN CLASS I, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED IN NEC ARTICLE 501‐4(B). EQUIPMENT AND FIELD WIRING IS NON‐INCENDIVE WHEN CONNECTED TO APPROVED BARRIERS WITH ENTITY PARAMETERS. LS1 LS2 MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM. IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE FM APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING. PARTITIONED AREA DETAIL 1 GE10683‐D 35 DVC2000 Digital Valve Controller April 2014 Quick Start Guide D103203X012 ATEX Special Conditions for Safe Use Intrinsically Safe The equipment is an intrinsically safe equipment. It can be mounted in hazardous area. The terminal blocks can be only connected to certified intrinsically safe equipments and these combinations must be compatible as regard intrinsic safety rules. The equipment shall be connected in accordance with manufacturer's installation instructions in drawing GE14685 (figure 29). The equipment must not be submitted to mechanical impacts or frictions. Temperature Classification: T4 at Ta ≤ 80_C T5 at Ta ≤ 40_C Refer to figure 28 for a typical DVC2000 ATEX approval nameplate. Figure 28. Typical ATEX Nameplate 36 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 29. ATEX Installation Drawing INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE. BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. WARNING THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. CARE MUST BE TAKEN DURING INSTALLATION AND USE TO PREVENT IMPACT OR FRICTION. INTRINSICALLY SAFE APPARATUS MAY BE CONNECTED TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Ui) AND THE CURRENT (Ii) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Co) AND INDUCTANCE (Lo) DEFINED BY THE HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ASSOCIATED APPARATUS. IF THESE CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED. FORMULASUi > Uo ZONE 0, GROUP IIC Ii > Io Ci + Ccable < Co I.S. APPROVED Li + Lcable < Lo XMTR BARRIER Pi > Po ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS: CIRCUIT VMax (Ui) IMAX(Ii) Ci Li PMAX XMTR MAIN LS1 LS2 28Vdc 30Vdc 16Vdc 16Vdc 5nF 10.5nF 5nF 5nF 0 mH 0.55 mH 0 mH 0 mH 1W 1W 1W 1W 100mA 130mA 76mA 76mA MAIN I.S. APPROVED BARRIER LS1 I.S. APPROVED BARRIER LS2 I.S. APPROVED BARRIER DVC2000 WHERE MULTIPLE IS CIRCUITS ARE USED: EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE. I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES AS SPECIFIED IN DETAIL 1. CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED AREA (SEE DETAIL 1). XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL. XMTR MAIN RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM. LS1 LS2 IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING. PARTITIONED AREA DETAIL 1 GE14685‐C 37 DVC2000 Digital Valve Controller Quick Start Guide D103203X012 April 2014 IECEx Conditions of Certification Intrinsically Safe This equipment shall be connected in accordance with the manufacturer's installation instructions (drawing GE14581, figure 31) to intrinsic safety barriers that satisfy the following parameters for each set of terminals. Main 4-20 mA: Ui = 30 V, Ii = 130 mA, Pi = 1W, Li = 0.55 mH, Ci = 10.5 nF XMTR circuit: Ui = 28 V, Ii = 100 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF Limit Switch 1 (LS1): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF Limit Switch 2 (LS2): Ui = 16 V, Ii = 76 mA, Pi = 1W, Li = 0 mH, Ci = 5 nF Refer to figure 30 for a typical DVC2000 IECEx approval nameplate. Figure 30. Typical IECEx Nameplate 38 Quick Start Guide DVC2000 Digital Valve Controller D103203X012 April 2014 Figure 31. IECEx Installation Drawing INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE. WARNING THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. CARE MUST BE TAKEN DURING INSTALLATION AND USE TO PREVENT IMPACT OR FRICTION. BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. INTRINSICALLY SAFE APPARATUS MAY BE CONNECTED TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Ui) AND THE CURRENT (Ii) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Co) AND INDUCTANCE (Lo) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED. FORMULASUi > Uo Ii > Io Ci + Ccable < Co Li + Lcable < Lo Pi > Po ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS: PMAX Li CIRCUIT VMax (Ui) IMAX(Ii) Ci XMTR MAIN LS1 LS2 28Vdc 30Vdc 16Vdc 16Vdc 100mA 130mA 76mA 76mA 5nF 10.5nF 5nF 5nF 0 mH 0.55 mH 0 mH 0 mH HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, GROUP IIC XMTR I.S. APPROVED BARRIER MAIN I.S. APPROVED BARRIER LS1 I.S. APPROVED BARRIER LS2 I.S. APPROVED BARRIER DVC2000 1W 1W 1W 1W WHERE MULTIPLE I.S. CIRCUITS ARE USED: EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE. I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES AS SPECIFIED IN DETAIL 1. CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED AREA (SEE DETAIL 1). XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL. XMTR MAIN LS1 LS2 RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM. IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING. PARTITIONED AREA DETAIL 1 GE14581‐C 39 DVC2000 Digital Valve Controller April 2014 Quick Start Guide D103203X012 Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, PlantWeb, ValveLink, and Tri‐Loop are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the HART Communication Foundation. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore www.Fisher.com 402004, 2014. Fisher Controls International LLC. All rights reserved. E
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Has XFA : No XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26 Producer : Acrobat Distiller 10.0.0 (Windows) Creator Tool : BroadVision, Inc. Modify Date : 2014:02:25 09:32:04-06:00 Create Date : 2014:02:25 09:17:57-06:00 Metadata Date : 2014:02:25 09:32:04-06:00 Format : application/pdf Title : Creator : Document ID : uuid:6e2a5832-b748-4f3f-aff5-854815c5ee5f Instance ID : uuid:a23a58a6-b950-481b-9b0c-ccd073771598 Page Count : 40EXIF Metadata provided by EXIF.tools