Emerson Liebert Ds Precision Cooling System 28 105Kw Technical Specifications
2015-03-30
: Emerson Emerson-Liebert-Ds-Precision-Cooling-System-28-105Kw-Technical-Specifications-680436 emerson-liebert-ds-precision-cooling-system-28-105kw-technical-specifications-680436 emerson pdf
Open the PDF directly: View PDF .
Page Count: 176
Download | |
Open PDF In Browser | View PDF |
Liebert® DS™ Thermal Management Unit System Design Manual - 28-105kW (8-30 Tons), Downflow/Upflow, 60Hz Floor Mounted, Air-Cooled, Water/Glycol-Cooled, GLYCOOL Economizer Coil, Dual-Cool DX with Secondary Chilled Water Coil TABLE OF CONTENTS LIEBERT DS MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 COOLING CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2.0 BLOWER CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 3.0 AIR-COOLED SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 3.1 Capacity and Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2 Standard Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.3 Optional Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 3.4 Optional Low-Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 3.5 Dimensions—Liebert DS 028-042, Downflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . 16 3.6 Dimensions—Liebert DS 053-077, Downflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . 23 3.7 Dimensions—Liebert DS 105, Downflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . . . . . 32 3.8 Dimensions—Liebert DS 028-042, Upflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . . . . 38 3.9 Dimensions—Liebert DS 053-077, Upflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . . . . 45 3.10 Dimensions—Liebert DS 105, Upflow, Air-Cooled Models . . . . . . . . . . . . . . . . . . . . . . . . . . 52 3.11 Heat Rejection—Liebert MC, Fin/Tube and Piggyback Condensers . . . . . . . . . . . . . . . . . . . 57 3.11.1 Liebert MC Microchannel Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 3.12 Piping—Liebert MC™ Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 3.12.1 Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 3.12.2 Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 3.13 Ancillary Items—Air-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 4.0 WATER-COOLED, GLYCOL-COOLED AND GLYCOOL SYSTEMS . . . . . . . . . . . . . . . . . . . . .91 4.1 Capacity and Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 4.2 Standard Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 4.3 Optional Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 4.4 Optional Low-Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 4.5 Dimensions—Liebert DS 028-042, Downflow, Water/Glycol/GLYCOOL Models . . . . . . . . 107 4.6 Dimensions—Liebert DS 053-077, Downflow, Water/Glycol/GLYCOOL Models . . . . . . . . 111 4.7 Dimensions—Liebert DS 105, Downflow, Water/Glycol/GLYCOOL-Cooled Models . . . . . 116 4.8 Dimensions—Liebert DS 028-042, Upflow, Water/Glycol/GLYCOOL-Cooled Models . . . . 121 4.9 Dimensions—Liebert DS 053-077, Upflow, Water/Glycol/GLYCOOL-Cooled Models . . . . 125 4.10 Dimensions—Liebert DS 105, Upflow, Water/Glycol/GLYCOOL Models. . . . . . . . . . . . . . 129 4.11 Heat Rejection—Drycoolers and Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 4.11.1 4.11.2 4.11.3 4.11.4 4.11.5 4.11.6 4.11.7 4.11.8 4.11.9 4.12 Drycooler Selection—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Data—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping—Prop Fan Drycoolers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pump Packages & Expansion Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drycooler Selection—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights and Dimensions—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Data—Piggyback Drycoolers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Piping—Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 133 136 138 143 147 147 148 150 Ancillary Items—Water-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 i 5.0 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 1.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 2.0 PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 3.0 EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 ii Liebert DS Model Number LIEBERT DS MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D S 0 3 5 A U A 0 E I * * * * Air Distribution DS = Downflow Standard VS = Upflow Standard Factory Configuration Number Nominal kW 028, 035, 042, 053, 070, 077, 105 (8, 10, 12, 15, 20, 22, 30 tons) Humidification 0 - None I - Infrared S - Steam Generating Canister Cooling Type A = Air-Cooled D = Dual-Cooling, Air-Cooled W = Water/Glycol K = GLYCOOL (Liebert Economizer Coil) H = Dual-Cooling, Water-Cooled Reheat Type 0 - None E - 3-Stage Electric S - SCR Compressor U - Semi-Hermetic with Four-Step, R-407C S - Scroll, R-407C D - Digital Scroll, R-407C Fan Type 0 = Centrifugal Fans 1 = Electronically Commutated (EC) Fans Voltage A - 460/3/60 B - 575/3/60 C - 208/3/60 D - 230/3/60 2 - 380/3/60 Not all combinations of options are available on all units. Digital Scroll Compressors • Not available on 077 and 105 models • Not compatible with SCR reheat because digital scroll provides variable capacity control EC Fans, Direct-Drive • Not available on upflow (VS) configuration • Liebert Econ-O-Coil™ not available on 028, 035, 042 models with 208/230V Steam Generating Canister Humidifier • Not available on upflow (VS) configurations • Not available on EC fan configurations 575 Volt Option Limitations • Digital scroll compressors available only on 053, 070 models GLYCOOL Liebert Economizer Models • 105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing Turning Vanes • Not available on floor stands 6" (152.4mm) tall • Not available or required on units with EC fans 1 Liebert® DS™ Cooling Configurations 1.0 COOLING CONFIGURATIONS NOTE All field-installed piping must comply with applicable local, state and federal codes. AIR-COOLED Air-cooled unit piping is spun closed from the factory and contains a nitrogen holding charge. Each installation requires field-supplied refrigerant and piping to a condenser. GLYCOL-COOLED Glycol-cooled units are factory-charged and tested. Field-supplied and field-installed piping is required from the unit to the drycooler and pump package. GLYCOOL-INTEGRATED FLUID ECONOMIZER GLYCOOL units are factory-charged and tested. Field-supplied and field-installed piping is required from the unit to the drycooler and pump package. An additional Liebert Economizer coil is included for use when fluid temperatures are sufficiently low (below room temperature). Economizer cooling is provided by circulating cold glycol through this second coil, reducing or eliminating compressor operation. WATER-COOLED Water-cooled units are factory-charged and tested. Field-supplied and field-installed water piping is required from the unit to the cooling tower. DUAL-COOL This system has all of the features of a compressorized system, but adds a second cooling coil that is connected to a source of chilled water. Cooling is provided by circulating chilled water, when available, through this second coil and reducing compressor operation. Liebert® DS™ 2 Blower Configurations 2.0 BLOWER CONFIGURATIONS Figure 1 Blower configurations—Downflow, front and rear supply models, EC fans Return Air Return Air Filter Filter Front Front Coil Coil Blower Supply Air Raised Floor Blower Raised Floor Rear Supply, EC Fans Applicable to installations without raised floors Front Supply, EC Fans Applicable to installations without raised floors Figure 2 Supply Air Blower configurations—Downflow, bottom supply and under-floor supply models, EC fans Return Air Return Air Filter Filter Front Front Coil Coil Blower Blower Raised Floor Raised Floor Supply Air Floor Stand (optional) Supply Air Floor Stand (optional ) Supply Air Under-Floor Supply, EC Fans Bottom Supply, EC Fans 3 Liebert® DS™ Blower Configurations Figure 3 Blower configurations—Downflow, front and rear supply models, centrifugal fans Return Air Return Air Filter Filter Front Front Coil Coil Raised Floor Supply Air Turning Vane (optional ) Blower Raised Floor Floor Stand (optional) Supply Air Turning Vane (optional ) Front Supply, Forward-Curved Fans Liebert® DS™ Blower Rear Supply, Forward-Curved Fans 4 Floor Stand (optional) Blower Configurations Figure 4 Blower configurations—Upflow, front return models, centrifugal fans Supply Air Supply Air Blower Front Blower Front Coil Coil Filter Filter Return Air Return Air Top Supply, Front Throw Forward-Curved Fans Figure 5 Top Supply, Rear Throw Forward-Curved Fans Blower configurations—Upflow, rear return models, centrifugal fans Supply Air Front Supply Air Blower Front Coil Blower Coil Filter Filter Return Air Return Air Ductwork Top Supply, Front Throw, Forward-Curved Fans Ductwork Top Supply, Rear Throw, Forward-Curved Fans 5 Liebert® DS™ Air-Cooled Systems 3.0 AIR-COOLED SYSTEMS 3.1 CAPACITY AND PHYSICAL DATA Table 1 Performance Data—Air-cooled, EC fan, under-floor discharge Model Size 028 035 042 053 070 077 105 CAPACITY DATA with EC Fans Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Semi Hermetic Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 34.1 (116.4) Sensible kW (kBTUH) 34 (116) 42.1 (143.6) 47.9 (163.6) 61.7 (210.6) 72.4 (247.1) 79.2 (270.3) 103.3 (352.5) 41.4 (141.2) 47.9 (160.9) 61.6 (210.2) 72 (245.9) 78.9 (269.2) 98.9 (337.5) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 32.4 (110.5) Sensible kW (kBTUH) 31 (105.9) 40.1 (136.8) 45.7 (156.1) 58.3 (198.9) 68.8 (234.8) 75.3 (257.1) 99.1 (338.2) 37.5 (128.1) 45.7 (146.2) 56.8 (193.9) 66.4 (226.6) 72.9 (248.8) 90 (307.2) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 30.9 (105.3) Sensible kW (kBTUH) 27.5 (93.9) 38.3 (130.8) 43.8 (149.5) 55.4 (189) 65.6 (223.9) 72 (245.8) 95.2 (325) 33.3 (113.8) 43.8 (129.9) 50.8 (173.3) 59 (201.3) 64.9 (221.5) 80 (273.1) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 30 (102.5) 37.3 (127.4) 42.7 (145.8) 53.8 (183.6) 63.9 (218) 70.2 (239.7) 93.1 (317.6) Sensible kW (kBTUH) 25.3 (86.3) 30.7 (104.8) 42.7 (119.7) 46.7 (159.3) 54.2 (184.9) 59.7 (203.6) 73.8 (251.8) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 35.4 (120.8) Sensible kW (kBTUH) 35.2 (120) 40.2 (137.1) 45.5 (155.3) 63.5 (216.8) 75.8 (258.6) 81.3 (277.6) 103.6 (353.7) 40 (136.4) 45.3 (154.7) 63.2 (215.7) 74.9 (255.6) 80.6 (275.1) 99.1 (338.3) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 33.4 (113.9) 38.2 (130.4) 43.4 (148.1) 60.5 (206.5) 72.7 (248) 77.9 (265.8) 99.7 (340.2) Sensible kW 31.8 (108.7) (kBTUH) 36.5 (124.6) 41.6 (141.9) 58.3 (199.1) 68.9 (235) 74.1 (253) 90.3 (308.2) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 31.6 (107.8) Sensible kW (kBTUH) 28.2 (96.1) 36.5 (124.7) 41.6 (141.9) 57.8 (197.4) 69.9 (238.4) 74.9 (255.5) 96 (327.8) 32.5 (110.8) 37 (126.3) 52 (177.6) 61.4 (209.4) 65.9 (224.9) 80.4 (274.3) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 30.6 (104.3) Sensible kW (kBTUH) 25.8 (88.2) 35.6 (121.5) 40.6 (138.5) 56.4 (192.6) 68.3 (233) 73.2 (249.9) 93.8 (320.3) 29.9 (102.1) 34.1 (116.3) 47.9 (163.6) 56.5 (192.9) 60.6 (206.9) 74.1 (253) FAN SECTION - Downflow Models - EC Fans Under Floor Standard Air Volume, CFM (CMH) 0.2" External Static 4,400 (7,476) 5,200 (8,835) 6200 (10533.9) 8,000 (13,592) 9,600 (16,310) 11,000 (18,689) 13,700 (23,276) Standard Fan Motor, Nominal kW (total for all fans) 2.8 2.8 2.8 2.5 4.0 5.9 7.8 Number of Fans 1 1 1 2 2 2 3 1. Capacity data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance. 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. 3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only. Liebert® DS™ 6 Air-Cooled Systems Table 2 Performance data—Air-cooled, centrifugal fan Model Size 028 035 042 053 070 077 105 CAPACITY DATA with Centrifugal Fans Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Semi Hermetic Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 40.3 (137.6) 41.0 (140.0) 46.2 (157.6) 60.2 (205.3) 70.5 (240.6) 76.9 (262.6) 101.3 (345.6) Sensible kW 38.0 (129.6) 40.3 (137.6) (kBTUH) 45.5 (155.3) 59.7 (203.8) 69.7 (237.9) 76.2 (259.9) 96.6 (329.6) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 38.6 (131.8) 39.1 (133.3) Sensible kW 34.3 (117.2) 36.5 (124.6) (kBTUH) 43.9 (150) 57.2 (195.1) 67.2 (229.3) 73.4 (250.6) 97.1 (331.5) 41.2 (140.5) 54.8 (187.1) 63.8 (217.7) 69.8 (238.2) 87.7 (299.4) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 37.1 (126.5) 37.3 (127.2) Sensible kW 30.5 (104.2) 32.3 (110.3) (kBTUH) 42 (143.3) 54.4 (185.6) 64.1 (218.9) 70.2 (239.7) 93.3 (318.4) 36.4 (124.2) 48.7 (166.2) 56.5 (192.9) 61.8 (210.9) 77.8 (265.4) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 36.1 (123.3) 36.3 (123.8) Sensible kW 28.2 (96.3) (kBTUH) 29.7 (101.3) 40.9 (139.6) 52.9 (180.6) 62.5 (213.2) 68.6 (234) 91.0 (310.6) 33.4 (113.9) 44.7 (152.7) 51.9 (177.2) 56.7 (193.6) 71.5 (244.1) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 34.1 (116.4) 39.7 (135.5) 43.7 (149.2) 62.1 (212.1) 74.0 (252.6) 79.1 (270.1) 101.6 (346.9) Sensible kW 40.1 (136.9) 34.0 (116.0) (kBTUH) 43.6 (148.9) 61.3 (209.3) 72.3 (246.6) 77.8 (265.6) 96.8 (330.4) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 32.4 (110.5) 38.3 (130.8) 41.6 (141.9) 59.3 (202.5) 71.2 (243) 75.9 (259) 97.7 (333.5) Sensible kW 31.0 (105.9) 36.1 (123.2) (kBTUH) 39.9 (136.1) 56.1 (191.6) 65.9 (225) 71.1 (242.6) 88.0 (300.4) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 30.9 (105.3) 36.7 (125.4) Sensible kW 27.5 (93.9) (kBTUH) 32.1 (109.4) 39.8 (135.7) 56.9 (194.2) 68.5 (233.9) 73 (249.3) 94.1 (321.1) 35.3 (120.6) 49.9 (170.4) 58.6 (200.1) 63.1 (215.2) 78.1 (266.6) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 30.0 (102.5) 35.9 (122.4) Sensible kW 25.3 (86.3) (kBTUH) 29.5 (100.6) 38.8 (132.3) 55.5 (189.5) 67 (228.7) 71.4 (243.7) 91.9 (313.7) 32.4 (110.5) 46.0 (157) 54.0 (184.3) 58.0 (197.8) 71.9 (245.5) FAN SECTION - Downflow Models - Fixed Pitch, Two Belts Standard Air Volume - CFM (CMH) 0.2" external static 4,400 (7,476) 5,200 (8,835) 6,300 (10,704) 7,500 (12,743) 9,000 (15,291) 10,400 (17,670) 13,700 (23,276) Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5.0 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10.0 (7.5) 1 1 1 2 2 2 3 Number of Fans 1. Capacity data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance. 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. 3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only 7 Liebert® DS™ Air-Cooled Systems Table 3 Physical data—Air-cooled systems Model Size 028 035 042 053 070 077 105 EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin Face Area, sq. ft. (sq. m) Rows of Coil 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 3 3 3 3 3 3 3 REHEAT SECTION Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat Capacity - kW (kBTUH) - Standard Selection 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) Capacity, kW (kBTUH) - Optional 10.0 (34.1) Selection 10.0 (34.1) 10.0 (34.1) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) 22.0 (10.0) 22.0 (10.0) Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection) Capacity, kW (kBTUH) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 25.0 (85.3) HUMIDIFIER SECTION Infrared Humidifier (Steam canister humidifiers available on downflow models with centrifugal fans) Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (filter types cannot be mixed, must be all MERV 8 or all MERV 11) Downflow Models Quantity 3 @ 25x20 Nominal Size, inches 2 1 @ 25x16 3 3 4 4 4 4 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 Upflow Models (Front & Rear return) Filters located in separate filter box on rear return, located on lower unit panel Quantity Nominal Size, inches 4 4 4 6 6 6 8 25x20 25x20 25x20 25x20 25x20 25x20 25x20 PIPING CONNECTION SIZES - Air-cooled Liebert DS Indoor Unit (Not External Line Sizes) Liquid Line, O.D. Copper (2/unit) 1/2 1/2 1/2 5/8 5/8 5/8 5/8 Hot Gas Line, O.D. Copper (2/unit) 5/8 5/8 5/8 7/8 7/8 7/8 1-1/8 Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Condensate Drain w/Optional Condensate Pump, OD 1/2 1/2 1/2 1/2 1/2 1/2 1/2 OUTDOOR AIR-COOLED CONDENSER, STANDARD 95°F AMBIENT SELECTION; see Tables 44 and 49 for other selections Model (R-407C refrigerant) MCM080_8 MCM080_8 MCM080_8 MCM080_8 Number of Fans 2 2 2 2 MCM080_8 MCM080_8 MCL110_8 2 2 2 DUAL-COOL UNITS DATA, Water (0% Glycol), Net Capacity Data kW (kBTUH) CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower. 75°F DB, 61.1 WB (23.9°C DB, 16.2°C WB) 45% RH, 45°F EWT, 55°F LWT Based on Centrifugal Fans Total Capacity, kW (kBTUH) 26.2 (89.2) 29.8 (101.6) 32.2 (109.8) 49.9 (170.4) 55.3 (188.8) 57.7 (196.8) 75.8 (258.8) Sensible Capacity, kW (kBTUH) 24.9 (85) 28.8 (98.2) 31.6 (107.8) 46 (157.1) Flow Rate GPM (I/m) @ 10°F Rise 19 (71.9) 22.4 (84.8) 36.4 (138) Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 73 (249.1) 41.7 (158) 46 (174) 59.4 (225) 8.3 (24.81) 10.50 (31.39) 10.40 (31.09) 13.3 (39.8) 15.9 (47.6) 15.9 (47.5) 6600 (11213) 8000 (13592) 9600 (16310) 11000 (18689) 13,700 (23,256) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0) Airflow, CFM (CMH) 4400 (7475) 5500 (9344) 25.5 (96.5) 51.7 (176.4) 54.3 (185.4) Fluid Volumes Econ-O-Coil fluid volume, gal (l) 5 (19.0) 5 (19.0) 5 (19.0) Capacity data is rated per ASHRAE 127-2012 with a 5% tolerance Liebert® DS™ 8 Air-Cooled Systems Table 4 Model # Reheat Options Electric Standard, kW None Electric Standard kW None Electric, Downsized kW Electric, Downsized kW Humidifier Options Infrared Infrared None None Humidifier No Humidifier 230 460 575 208 230 460 575 208 Volts FLA DS028 DS035 80 40 30 70 70 35 30 82 80 78.9 39.2 30.5 47.3 80 40 30 60 FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 86.3 83.2 40.8 31.9 68.3 66.1 90 90 45 30 80 80 43 78.2 75.9 37.7 33 78.1 75.9 37.7 33 95.7 92.5 46 36 85.2 83 110 50 45 110 110 78.2 75.7 37.5 29.4 64.8 41.2 35.8 95.7 92.5 50 45 30 110 110 46 36 71.9 50 40 100 30 25 70 70 35 30 70 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 70 45 460 575 62.8 31.1 24.1 60 70 90 230 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 40 90 208 51.9 25.6 19.9 55 30 230 460 575 21.1 16.8 56.3 54.1 26.9 24.2 53.5 55 FLA 110 230 460 575 208 32 27.1 86.3 83.2 40.8 31.1 WSA 26.2 19.7 35 25 69 67 80 80 32.7 27.1 40 30 64.8 31.9 25.6 78.1 75.9 37.7 33 71.9 35.4 28.4 85.2 83 100 110 45 70 35 25 55.3 26.9 20.4 69 67 80 80 32.7 24.8 35 25 64.8 64.8 31.9 25.6 41.2 35.8 78.4 76.4 37.8 29.6 45 100 100 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5 35 110 50 45 35 FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45 FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43 175 175 80 60 175 175 80 139.2 134.8 61.4 50 139.2 134.8 61 60 80 60 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 175 175 80 60 150 150 70 50 50 175 175 150 150 70 50 112.6 112.6 49.4 38.4 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3 OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50 FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9 OPD 1. 2. 3. 4. 5. 6. 78.9 39.2 31.9 60.6 58.4 29.1 25.9 WSA FLA DS105 43 80 OPD DS077 208 82 OPD DS070 208 OPD OPD DS053 230 460 575 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 WSA OPD DS042 Electrical data—Air-cooled systems with EC fans 225 225 110 100 225 225 110 100 225 225 110 90 200 200 110 80 225 225 110 100 200 200 110 80 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. Steam canister humidifiers not available on models with EC fans. 9 Liebert® DS™ Air-Cooled Systems Table 5 Electrical data—Air-cooled systems with centrifugal fans Reheat Options Electric, Std. kW None Electric, Std. kW None Humidifier Options Infrared or Steam Generating Canister Infrared or Steam Generating Canister None None Model 028 028 035 035 042 042 Motor hp Volts 2.0 3.0 3.0t 5.0 5.0 7.5 208 230 460 208 230 460 070 5.0 5.0 230 460 575 208 230 460 575 66.4 63.2 31.8 25.2 55.4 52.5 26.6 23.9 66.4 63.2 31.8 24.7 42.1 41.4 20.8 16.5 81.1 77.3 38.9 31.5 59.7 56.8 28.8 25.6 81.1 77.3 38.9 30.2 46.4 45.7 23 18.2 OPD 80 80 60 30 25 40 30 70 70 35 30 80 80 40 30 60 FLA 69.5 66.0 33.2 26.4 58.5 55.3 28.0 25.1 69.5 66.0 33.2 25.9 45.2 44.2 22.2 17.7 WSA 84.2 80.1 40.3 33 62.8 59.6 30.2 26.8 84.2 80.1 40.3 31.4 49.5 48.5 24.4 19.4 OPD 90 80 40 30 80 70 FLA 72.9 69.4 34.5 26.4 65.3 62.1 30.6 26.1 72.9 69.4 34.5 26.4 52.0 51.0 24.8 18.7 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6 OPD 90 90 FLA 79.0 75.0 37.3 28.6 71.4 67.7 33.4 28.3 79.0 75.0 37.3 28.6 58.1 56.6 27.6 20.9 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8 OPD 100 100 FLA 86.5 82.7 41.6 36.1 86.4 WSA 104 99.3 49.9 39.1 93.5 OPD 110 110 FLA 94.0 89.5 45 45 50 35 35 50 90 90 125 110 40 90 35 90 80 90 40 45 35 70 70 35 25 89.8 45.1 38.9 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5 45.0 39.0 93.9 89.5 41 101.4 96 50 40 78.4 39.2 31.6 48.5 41.8 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4 110 41 74.8 73.8 37.6 27.9 WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9 70 110 100 44.8 35.4 80.6 110 125 125 89.3 100 30 45 150 50 45.0 39.0 94.0 45 40 25 71.6 35.8 28.7 50 80 30 41.4 32.5 73.1 110 80 60 82.5 110 35 60 41.6 36.1 86.5 50 45 30 82.7 50 35 90 100 110 45 30 100 110 60 35 80 WSA 111.5 106.1 53.3 42.0 101.0 96.6 OPD 053 208 FLA FLA 112.1 107.2 53.9 3.0 575 WSA OPD 053 575 50 125 60 50 125 110 60 49.2 39.5 112.1 107.2 53.9 125 60 50 150 125 70 50 110 110 50 50 45 40 FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9 79.4 40.4 30.1 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1 OPD 110 110 60 45 FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 99.5 98 46 34.5 150 150 70 50 125 125 70 50 150 150 70 50 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1 OPD 175 150 80 60 175 150 80 60 175 150 80 60 150 125 70 50 FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4 070 077 7.5 7.5 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0 OPD 175 FLA 145 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50 138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0 WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0 OPD 200 175 90 70 200 175 80 70 175 175 90 70 175 175 70 60 FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0 077 10.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0 OPD 200 200 90 70 200 200 90 70 200 175 90 70 175 FLA 177.4 170.2 88.4 72.6 177.4 170.2 88.4 72.6 169.9 166.6 84.5 66.1 150.8 105 10.0 175 148 80 60 76.8 61.0 WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3 OPD 250 225 125 100 250 225 125 100 225 225 110 90 225 200 110 90 FLA 192.3 184.2 95.4 78.6 192.3 184.2 95.4 78.6 185.3 180.6 91.5 72.1 166.2 162.0 83.8 67.0 105 15.0 WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3 OPD 1. 2. 3. 4. 5. 250 250 125 100 250 250 125 100 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. Liebert® DS™ 10 250 250 125 100 225 225 110 90 Air-Cooled Systems Table 5 Electrical data—Air-cooled systems with centrifugal fans (continued) Reheat Options Electric, Downsized kW Humidifier Options Model 028 028 035 035 042 042 053 053 070 070 077 077 105 105 1. 2. 3. 4. 5. Motor, hp 2.0 3.0 3.0 5.0 5.0 7.5 3.0 5.0 5.0 7.5 7.5 10.0 10.0 15.0 Infrared or Steam Generating Canister None Volts 208 230 460 575 208 230 460 575 FLA 55.4 52.5 26.6 23.9 52.6 50.3 25.3 19.6 WSA 63.9 61.2 30.8 25.6 63.9 61.2 30.8 23.8 OPD 70 70 35 30 70 70 35 25 FLA 58.5 55.3 28 25.1 55.7 53.1 26.7 20.8 WSA 67.0 64.0 32.2 26.8 67.0 64.0 32.2 25.0 OPD 80 70 35 30 70 70 35 25 FLA 65.3 62.1 30.6 26.1 59.1 56.5 28.0 21.3 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7 OPD 90 80 40 35 80 80 40 30 FLA 71.4 67.7 33.4 28.3 65.2 62.1 30.8 23.5 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9 OPD 90 90 45 35 90 80 40 30 FLA 86.4 82.7 41.6 36.1 73.1 71.6 35.8 28.7 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7 OPD 110 110 50 50 100 100 50 40 FLA 93.9 89.5 45.0 39.0 80.6 78.4 39.2 31.6 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6 OPD 125 110 60 50 110 110 50 45 FLA 101.4 96.0 49.2 39.5 84.3 80.8 40.9 31 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8 OPD 125 125 60 50 110 110 60 45 FLA 107.5 101.6 52.0 41.7 90.4 86.4 43.7 33.2 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0 OPD 125 125 70 50 125 125 60 45 FLA 126.1 120.2 57.6 46.1 99.7 98 46.5 35.4 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7 OPD 175 150 80 60 150 125 70 50 FLA 133.6 127.0 61.0 49.0 107.2 104.8 49.9 38.3 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6 OPD 175 175 80 60 150 150 70 50 FLA 145 138.4 64.0 52.6 118.4 116.2 52.4 41.0 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9 OPD 200 175 80 70 175 175 70 60 FLA 151.6 144.4 67.0 54.6 125.0 122.2 55.4 43.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9 OPD 200 200 90 70 175 175 80 60 FLA 177.4 170.2 88.4 72.6 150.8 148 76.8 61.0 WSA 192.4 185.2 96.3 78.9 175.2 168.6 86.0 67.4 OPD 250 225 125 100 225 200 110 90 FLA 192.8 184.2 95.4 78.6 166.2 162.0 83.8 67.0 WSA 207.8 199.2 103.3 84.9 190.6 182.6 93.0 73.4 OPD 250 250 125 100 225 225 110 90 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. 11 Liebert® DS™ Air-Cooled Systems Figure 6 Electrical field connections—Upflow and downflow models, single molded case switch disconnect with main fuses See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional Low-Voltage Terminal Package Connections for keys to numbered components. 2 OVERCURRENT PROTECTION DEVICES 15 Liebert IntelliSlot Housing 4 A B C D Alternate Location P64 6 60Hz CONTACTORS P67 CONTACTORS, RELAYS, & OVERLOAD PROTECTORS 13 E 5 1 17 18 82 83 88 89 Typical orientation of components shown. Component location varies by option and unit size 6 9 16 22 DOWNFLOW 3 DOWNFLOW LOW-VOLT SECTION 19 CAUTION UPFLOW 75 76 94 95 96 97 91 92 93 80 81 11 12 3 B A 24 23 58 59 84 85 21 7 10 8 Risk of broken or shorted low-voltage wiring. Field-installed low-voltage wiring must be routed with loop as shown to allow electric box to swing. 20 37C 38C 37B 38B 37 38 24 50 51 55 56 70 71 230 72 73 C D 49-3 49-1 SH 11 12 Item 12 Installation Conditions E 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway, or chase as high voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12" (305mm). 4. For runs greater than 350ft (107m), contact Emerson factory. Liebert® DS™ 12 Point of Hinged Low-Voltage Electric Box DS UPFLOW LOW VOLT SECTION DPN000807 Pg. 2, Rev. 8 Air-Cooled Systems Figure 7 Electrical field connections—Upflow and downflow models, dual fused disconnect switches See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional Low-Voltage Terminal Package Connections for keys to numbered components. 14 2 OVERCURRENT PROTECTION DEVICES 15 Liebert IntelliSlot Housing 4 A B C D 6 60Hz Alternate Location 15 P64 CONTACTORS P67 SECONDARY PRIMARY 13 CONTACTORS, RELAYS and OVERLOAD PROTECTORS E 6 1 17 18 Typical orientation of components shown. Component location varies by option and unit size 22 9 DOWNFLOW CAUTION: 19 16 UPFLOW 82 83 88 89 3 75 76 94 95 96 97 91 92 93 80 81 11 12 Risk of broken or shorted low-voltage wiring. Field-installed low-voltage wiring must be routed with loop as shown to allow electric box to swing. B A 23 24 3 DOWNFLOW LOW-VOLTAGE SECTION 58 59 84 85 21 7 20 10 8 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 D 11 49-3 49-1 SH C 12 Item 12 Installation Conditions E 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high-voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12" (305mm). 4. Contact Liebert factory for runs greater than 350ft. (107m). 5. All electrical loads may not be capable of being connected to both power feeds, with automatic transfer switch. Consult local representative for dual power configurations available. 13 Point of Hinged Low-Voltage Electric Box DS UPFLOW LOW-VOLTAGE SECTION DPN000807 Pg. 3, Rev. 8 Liebert® DS™ Air-Cooled Systems 3.2 STANDARD ELECTRICAL CONNECTIONS Source: DPN000807, Rev. 8 1. Primary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in bottom of box. 2. Secondary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in top of box. 3. Primary low voltage entrance—Quantity (3) 1.375" (35mm) diameter knockouts located in bottom of unit. 4. Secondary low voltage entrance—Quantity (3) 1. 375" (35mm) diameter knockouts located in top of box. 5. Three phase electrical service—Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three-phase service not by Emerson. 6. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for Liebert units. 7. Remote unit shutdown—Replace existing jumper between Terminals 37 & 38 with field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 & 50, 51, 55 & 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 & 76 for remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring. 10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is closed across Terminals 70 & 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. When a Liebert DS unit is paired with a Liebert MC series condenser, remove jumper between Terminal 71 and Terminal 230. Three wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the Liebert MC series condenser. Liebert® DS™ 14 Air-Cooled Systems 3.3 OPTIONAL ELECTRICAL CONNECTIONS Source: DPN000807, Rev. 8 11. Unit factory installed disconnect switch, Fuse Block and Main Fuses—Two types of disconnect switches are available: Non-Locking and Locking. The Non-Locking Type consists of a non-automatic molded case switch operational from the outside of the unit. Access to the high-voltage electric panel compartment can be obtained with the switch in either the On or Off position. The Locking Type is identical except access to the high-voltage electric panel compartment can be obtained only with the switch in the Off position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power is On. The molded case switch disconnect models contain separate main fuses. Units with fused disconnect have main fuses within the disconnect. Only fused disconnects are used on dual disconnect options. 12. Secondary disconnect switch and earth ground 13. Three-phase electrical service—Terminals are on top of disconnect switch. Three-phase service not by Emerson. 14. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 15. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 & 83 for lockout of reheat and humidifier. 16. Condensate alarm (with condensate pump option)—On pump high water indication, normally open dry contact is closed across Terminals 88 & 89 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 17. Remote humidifier—On any call for humidification, normally open dry contact is closed across Terminals 11 & 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring. 18. Auxiliary cool contact—On any call for Econ-O-coil operation, normally open dry contact is closed across Terminals 72 & 73 on dual cool units only. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 3.4 OPTIONAL LOW-VOLTAGE TERMINAL PACKAGE CONNECTIONS Source: DPN000807, Rev. 8 19. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C and 38C). Replace jumpers with field-supplied, normally closed switch having a minimum rating of 75VA, 24VAC. Use field-supplied Class 1 wiring. 20. Common alarm—On any alarm, two additional normally open dry contacts are closed across Terminals 94 & 95 and 96 & 97 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 21. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is closed across Terminals 84 & 85 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 22. Liebert Liqui-tect™ shutdown and dry contact—On Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 & 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 15 Liebert® DS™ Air-Cooled Systems 3.5 DIMENSIONS—LIEBERT DS 028-042, DOWNFLOW, AIR-COOLED MODELS The following figures are general illustrations that show the dimensional layout for a Liebert DS unit. Figure 8 Dimensions—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans Secondary Refrigerant Piping Entrance 56-7/8" Opening (1445mm) 33" (838mm) Filters are accessible 24-3/8" through top of unit only. (619mm) Downflow electrical Opening connections can be made from top or bottom of unit. Air Inlet Opening 35" (889mm) Secondary Entrance High-Volt Connection(s) TOP VIEW 3/4" (19mm) Bezels Secondary Entrance Low-Volt Connections Minimum required for filter replacement 5" (127mm) 73" (1854mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. DPN000796 Rev. 3 72" (1829mm) 2" (51mm) Table 6 FRONT VIEW Weights—downflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressors Dry Weight, Approximate, lb. (kg) Model Type Model Size: 028-042 Air-Cooled 1470 (668) Dual-Cool 1620 (736) Source: DPN000796, Rev. 3 Liebert® DS™ 16 Air-Cooled Systems Figure 9 Dimensions—downflow, air-cooled, 28-42kW (8-12 ton), front and/or rear discharge models 24" (610mm) Secondary Refrigerant Piping Entrance 56-7/8" (1445mm) Opening 33" (838mm) Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool 5" (127mm) 24-3/8" (619mm) Opening AIR INLET OPENING 35" (889mm) Secondary Entrance High-Voltage Connection(s) Minimum required for filter replacement Filters are accessible only through top of unit. 3/4" (19mm) Bezels TOP VIEW Secondary Entrance Low-Voltage Connections A 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 76" (1930mm) 33-1/2" (851mm) 19" (483mm) Air Outlet Opening 2" (51mm) FRONT VIEW 3-1/4" (83mm) B 3" (76mm) 33-3/8" 19" (848mm) (483mm) Air Outlet Opening 3-1/4" (81mm) 3" (77mm) REAR VIEW Customer Piping and Wiring Connections 1. For primary connection locations see standard submittals DPN000803, DPN000804 or DPN000900. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in 310697 compressor section. Pg. 1, Rev. 0 d) Or order additional SFA's to relocate connection locations Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll / Digital Model Air-Cooled Dual Cool Air-Cooled Dual Cool Dimensions, In. (mm) 028-042 1780 (809) 1930 (877) 1470 (668) 1620 (736) A B 86 (2184mm) 85 (2159) 73 (1854) 72" (1829) Source: 310697, Pg. 1, Rev. 0 17 Liebert® DS™ Air-Cooled Systems Figure 10 Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW All dimensions from rear corner of unit, including panels X SECTION A-A O 16-1/16" (408mm) BLOWER OUTLET Y R L1 L2 G1 G2 B 4" (102mm) 11-3/16" (284mm) 35" (889mm) ECS LV1 LV2 LV3 HUM CD E1 E2 ECR FRONT OF UNIT DPN000804 Rev. 3 73" (1854mm) Table 7 Piping data—downflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll Point Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) R Refrigerant Access 59-5/16 (1507) 14-3/4 (375) 11-3/16 x 4 (284 x 102) L1 Liquid Line System 1 69-15/16 (1776) 16-13/16 (411) 1/2" Cu Sweat L2 Liquid Line System 2 67-5/8 (1718) 16-13/16 (411) 1/2" Cu Sweat G1 Hot Gas Discharge 1 65-1/2 (1664) 16-13/16 (411) 5/8" Cu Sweat G2 Hot Gas Discharge 2 62-7/16 (1586) 16-13/16 (411) 5/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier) * 46 (1168) 29-1/2 (749) 3/4" FPT CD Condensate Drain (steam generating humidifier) * 46 (1168) 29-1/2 (749) 1-1/4" FPT HUM Humidifier Supply Line ECS ECR W/ Optional Pump 46 (1168) 29-1/2 (749) 1/2" Cu Sweat 53-1/2 (1359) 29 (737) 1/4" Cu Sweat Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8" Cu Sweat Econ-O-Coil Return 49-3/8 (1254) 30-3/4 (781) 1-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 55-1/2 (1410) 31-1/4 (794) 2-1/2" E2 Electrical Conn. (High Volt) 52-7/16 (1332) 31-1/4 (794) 2-1/2" LV1 Electrical Conn. (Low Volt) 2-1/4 (57) 27 (686) 7/8" LV2 Electrical Conn. (Low Volt) 2-1/4 (57) 29 (737) 7/8" LV3 Electrical Conn. (Low Volt) 2-1/4 (57) 31 (787) 7/8" B Blower Outlet 21-15/16 (557) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN000804, Rev. 3 Liebert® DS™ 18 Air-Cooled Systems Figure 11 Disassembly dimensions—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans Filter & Electric Box Assembly 39" (991mm) 76" (1930mm) Assembled Height Blower & Coil Assembly Compressor Assembly 76" (1930mm) 60-3/16" (1529mm) 37" (940mm) 33" (838mm) 13" (330mm) 59" (1499mm) 72" (1829mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. DPN000802 Rev. 2 Table 8 Component weights—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors Dry Weight, Approximate, lb. (kg) Air-Cooled Dual-Cool Compressor Assembly 490 (223) 490 (223) Filter and Electric Box Assembly 210 (96) 210 (96) Blower and Coil Assembly 770 (350) 920 (418) Component Source: DPN000802, Rev. 2 19 Liebert® DS™ Air-Cooled Systems Figure 12 Dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans Secondary Refrigerant Piping Entrance Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 56-7/8" Opening (1445mm) 33" (838mm) Air Inlet Opening 24-3/8" (619mm) Opening 35" (889mm) 3/4" Bezels (19mm) Secondary Entrance High Volt Connection(s) Secondary Entrance Low Volt Connections TOP VIEW 86" (2184mm) Minimum required for filter replacement 5" (127mm) 76" (1930mm) 34" (864mm) 2" (51mm) Table 9 Shaded area indicates a recommended minimum clearance for component access. 85" (2159mm) FRONT VIEW Weights—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Dry Weight, Approximate, lb. (kg) Model Type Model Size: 028-042 Air-Cooled 1780 (809) Dual-Cool 1930 (877) Source: DPN000795, Rev. 4 Liebert® DS™ 20 DPN000795 Rev. 4 Air-Cooled Systems Figure 13 Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW SECTION A-A X BLOWER OUTLET L1 L2 G1 G2 16-7/16" (418mm) Y 16-1/16" (408mm) B 35" (889mm) ECS LV1 LV2 LV3 HUM CD E1 E2 ECR FRONT OF UNIT DPN000803 Rev. 4 86" (2184mm) Point O R 4" (102mm) Table 10 All dimensions from rear corner of unit including panels Piping data—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102) R Refrigerant Access L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8" Cu Sweat Hot Gas Discharge 2 G2 CD 70-1/8 (1780) 16-3/4 (425) 5/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier)* 46 (1168) 29-1/2 (749) 3/4" FPT Condensate Drain (steam generating humidifier)* 46 (1168) 29-1/2 (749) 1-1/4" FPT 46 (1168) 29-1/2 (749) 1/2" Cu Sweat W/ Optional Pump HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4" Cu Sweat ECS Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8" Cu Sweat ECR Econ-O-Coil Return 49-3/8 (1254) 30-3/4 (781) 1-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 55-1/2 (1410) 31-1/4 (794) 2-1/2" E2 Electrical Conn. (High Volt) 52-7/16 (1332) 31-1/4 (794) 2-1/2" LV1 Electrical Conn. (Low Volt) 2-1/4 (57) 27 (686) 7/8" LV2 Electrical Conn. (Low Volt) 2-1/4 (57) 29 (737) 7/8" LV3 Electrical Conn. (Low Volt) B Blower Outlet 2-1/4 (57) 31 (787) 7/8" 21-15/16 (558) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN000803, Rev. 4 21 Liebert® DS™ Air-Cooled Systems Figure 14 Disassembly dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans Filter & Electric Box Assembly 39" (991mm) 39" 991mm Compressor Assembly 76" (1930mm) Assembled Height Blower & Coil Assembly 76" (1930mm) 60-3/16" (1529mm) 37" (940mm) 33" (838mm) 26" (660mm) 59" (1499mm) 85" (2159mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 11 DPN000801 Rev. 2 Component weights—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cooled Compressor Assembly 800 (364) 800 (364) Filter and Electric Box Assembly 210 (96) 210 (96) Blower and Coil Assembly 770 (350) 920 (418) Component Source: DPN000801, Rev. 2 Liebert® DS™ 22 Air-Cooled Systems 3.6 DIMENSIONS—LIEBERT DS 053-077, DOWNFLOW, AIR-COOLED MODELS Figure 15 Dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors with centrifugal fans Digital scroll compressors not available on DS 077. Second Refrigerant Piping Entrance 80" Opening (2032mm) 33" (838mm) 35" (889mm) Notes: Filters are accessible through top of unit only. 24-5/8" (619mm) Opening AIR INLET OPENING Secondary Entrance High-Volt Connection(s) Downflow electrical connections can be made from top or bottom of unit. 3/4" (19mm) Bezels TOP VIEW Secondary Entrance Low-Volt Connections Minimum required for filter replacement A 5" (127mm) 76" (1930mm) 34" (864mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access. B DPN000925 Rev. 2 FRONT VIEW Table 12 Weights—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors Dry Weight, lb (kg) Approximate Model No. DS 053 DS 070 DS 077 * Air Cooled 1920 (871) 1970 (894) 2020 (916) Dual Cool 2100 (953) 2150 (975) 2200 (998) Dimensions, in (mm) Air Cooled “A” 98 (2489) 98 (2489) 98 (2489) Air Cooled “B” 97 (2464) 97 (2464) 97 (2464) * Digital scroll compressors not available on DS 077 Source: DPN000925, Rev. 2 23 Liebert® DS™ Air-Cooled Systems Figure 16 Primary connection locations—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors with centrifugal fans Digital scroll compressors not available on DS 077. NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW SECTION A-A 16-1/16" (408mm) BLOWER OUTLET All dimensions from rear corner of unit including panels X O BLOWER OUTLET Y R 4" (102mm) L1 L2 G1 G2 12-3/16" (310mm) 35" (889mm) B1 B2 ECS HUM ECRCD LV1 LV2 LV3 E1 E2 98" (2489mm) FRONT OF UNIT Table 13 Piping data—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors *** Point R DPN000929 Rev. 4 Description Refrigerant Access X in. (mm) Y in. (mm) 81-3/4 (2076) 14-3/4 (374) Connection Size / Opening in. (mm) 12-3/16 x 4 (310 x 102) 53kW (15 ton) / 70 & 77kW (20 & 22 ton) L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2" / 5/8" Cu Sweat G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier)* 67-11/16 (1719) 30-1/2 (775) 3/4" FPT Condensate Drain (steam generating humidifier)* 67-11/16 (1719) 30-1/2 (775) 1-1/4" FPT W/ Optional Pump 67-11/16 (1719) 30-1/2 (775) 1/2" Cu Sweat CD 1/2" / 5/8" Cu Sweat HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4" Cu Sweat ECS** Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8" Cu Sweat ECR** Econ-O-Coil Return 72 (1829) 29 (737) 2-1/8" Cu Sweat E1 Electrical Conn. (High Volt) 78-1/2 (1994) 31-1/8 (790) 2-1/2" E2 Electrical Conn. (High Volt) 75-3/8 (1915) 31-1/8 (790) 2-1/2" LV1 Electrical Conn. (Low Volt) 1-7/8 (48) 28-1/2 (724) 7/8" LV2 Electrical Conn. (Low Volt) 1-7/8 (48) 30-1/4 (768) 7/8" LV3 Electrical Conn. (Low Volt) 1-7/8 (48) 32 (813) 7/8" Blower Outlet (15 x 15) 23-1/8 (587) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) Blower Outlet (15 x 11) 27-3/4 (705) 18-1/16 (459) 14-3/4 x 16-1/16 (375 x 408) Blower Outlet (15 x 15) 50-3/8 (1280) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) Blower Outlet (15 x 11) 54-3/8 (1381) 18-1/16 (459) 14-3/4 x 16-1/16 (375 x 408) B1 B2 * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 077. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN000929, Rev 4 Liebert® DS™ 24 Air-Cooled Systems Figure 17 Dimensions—downflow, air-cooled, 53-77kW (15-22 ton), front and/or rear discharge models with EC fans Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool Customer Piping and Wiring Connections 24" (610mm) 1. For primary connection locations see standard submittals DPN000928, DPN000929 or DPN000933. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in compressor section. d) Or order additional SFA's to relocate connection locations Minimum required for filter replacement Filters are accessible only through top of unit. 5" (127mm) Secondary Refrigerant Piping Entrance 80" (2032mm) Opening 35" (889mm) 33" (838mm) 25-5/8" (619mm) Opening AIR INLET OPENING Secondary Entrance High-Voltage Connection(s) 34" Shaded area indicates a (864mm) 3/4" recommended minimum (19mm) clearance for component access. Secondary Entrance Low-Voltage Connections TOP VIEW A 76" (1930mm) 15-1/8" (384mm) 29-1/4" (743mm) Air Outlet Opening 2" (51mm) 15-1/8" (384mm) 15-1/8" (384mm) 29-5/8" (752mm) Air Outlet Opening 29-5/8" (752mm) Air Outlet Opening 3-1/4" (83mm) FRONT VIEW B 15-1/8" (384mm) 3-1/4" (83mm) 29-1/4" (743mm) Air Outlet Opening REAR VIEW 310697 Pg. 2, Rev. 0 3-1/8" (79mm) Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll / Digital Dimensions, in. (mm) Model 53 70 77 * Air-Cooled Dual Cool Air-Cooled Dual Cool 2350 (1069) 2530 (1150 1920 (873) 2100 (955) 2400 (1091) 2580 (1173) 1970 (896) 2150 (978) 2450 (1114) 2630 (1196) 2020 (919) 2200 (1000) A B 109 (2769) 108 (2743) 98 (2489) 97 (2464) * Digital scroll compressors not available on 077 models Source: 310697, Pg. 2, Rev. 0 25 Liebert® DS™ Air-Cooled Systems Figure 18 Primary connection locations—downflow air-cooled 53-77kW (15-22 ton), scroll or digital scroll compressors with EC fans, front, rear or bottom discharge Digital scroll compressors not available on 077 models. NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW SECTION A-A All dimensions from rear corner of unit including panels X O Y R 4" (102mm) L1 L2 BLOWER OUTLET G1 G2 35" (889mm) 12-3/16" (310mm) ECS ECR CD E1 E2 B1 LV1 LV2 LV3 HUM 98" (2489mm) DPN002182 Rev. 1 FRONT OF UNIT Table 14 Point R Piping details—downflow air-cooled 53-77kW (15-22 ton) with EC fans, scroll or digital scroll compressors *** Description Refrigerant Access X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 81-3/4 (2076) 14-3/4 (374) 12-3/16x4 (310x102) 53kW (15 ton)/ 70 & 77kW (20 & 22 ton) L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier)* 68-3/8 (1737) 31-3/8 (797) 3/4 FPT 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat W/ Optional Pump HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat ECS** Econ-O-Coil Supply (DS Only) 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat ECR** Econ-O-Coil Return (DS Only) 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat E1 Electrical Conn. (High Volt) 78-1/2 (1994) 31-1/8 (790) 2-1/2 E2 Electrical Conn. (High Volt) 75-3/8 (1915) 31-1/8 (790) 2-1/2 LV1 Electrical Conn. (Low Volt) 2 (51) 29 (737) 7/8 LV2 Electrical Conn. (Low Volt) 2 (51) 30-7/8 (784) 7/8 LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8 B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8x30 (1483x762) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 077 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN002182, Rev. 1 Liebert® DS™ 26 Air-Cooled Systems Figure 19 Disassembly dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors Digital scroll compressors not available on DS 077. Filter & Electric Box Assembly Forward curved blowers shown. DA units only available with EC blowers, optional on DS units. 39" (991mm) Compressor Assembly Blower & Coil Assembly 76" (1930mm) 76" (1930mm) Assembled Height 59-7/16" (1509mm) 37" (940mm) DS053-DS077 = 15" (381mm) DA080,DA085 = 17" (432mm) 82" (2083mm) Assembled Length 97" (2464mm) NOTES: Drawing views are simplified with panels removed to show overall dimensions. DPN000927 See disassembly and handling instructions in installation manual. Rev. 4 33" (838mm) Table 15 Component weights—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressors * Dry Weight, Approximate, Including Panels, lb (kg) Component Air-Cooled Dual-Cool Compressor Assembly 540 (246) 540 (246) Filter and Electric Box Assembly 250 (114) 250 (114) Blower and Coil Assembly 1230 (560) 1410 (641) * Digital scroll compressors not available on DS 077 Source: DPN00927, Rev. 4 27 Liebert® DS™ Air-Cooled Systems Figure 20 Dimensions—downflow, air-cooled, 53-77kW (15-22 ton) with centrifugal fans, semi-hermetic compressors with centrifugal fans Second Refrigerant Piping Entrance 33" (838mm) 80" Opening (2032mm) Notes: Filters are accessible through top of unit only. 24-5/8" (625mm) Opening AIR INLET OPENING 35" (889mm) Downflow electrical connections can be made from top or bottom of unit. 3/4" Bezels (19mm) Secondary Entrance High-Volt Connection(s) TOP VIEW Secondary Entrance Low-Volt Connections Minimum required for filter replacement 109" (2769mm) 5" (125mm) 76" (1930mm) 34" (864mm) 108" (2743mm) 2" (51mm) Table 16 Shaded area indicates a recommended minimum clearance be provided for DPN000924 component access. Rev. 3 FRONT VIEW Weights—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors Dry Weight, Approximate, lb. (kg) Model Size Model Type 053 070 077 Air-Cooled 2350 (1069) 2400 (1091) 2450 (1114) Dual-Cool 2530 (1150) 2580 (1173) 2630 (1196) Source: DPN000924, Rev. 3 Liebert® DS™ 28 Air-Cooled Systems Figure 21 Primary connection locations—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors with centrifugal fans NOTE: Drawing not to scale. All dimensions from rear corner of unit including panels Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW X SECTION A-A 16-1/16" (408mm) BLOWER OUTLET O BLOWER OUTLET Y R 4" (102mm) L1 L2 G1 G2 B2 16-7/16" (418mm) 35" (889mm) B1 ECS LV1 LV2 LV3 HUMECR CD E1 E2 109" (2769mm) DPN000928 Rev. 4 FRONT OF UNIT Table 17 Point R L1 L2 G1 G2 Piping data—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (infrared humidifier or no humidifier) * CD Condensate Drain (steam generating humidifier)* W/ Optional Pump HUM Humidifier Supply Line ECS** Econ-O-Coil Supply ECR** Econ-O-Coil Return E1 Electrical Conn. (High Volt) E2 Electrical Conn. (High Volt) LV1 Electrical Conn. (Low Volt) LV2 Electrical Conn. (Low Volt) LV3 Electrical Conn. (Low Volt) Blower Outlet (15 x 15) B1 Blower Outlet (15 x 11) Blower Outlet (15 x 15) B2 Blower Outlet (15 x 11) X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 82-3/4 (2102) 13-7/8 (352) 16-7/16 x 4 (418 x 102) 53kW (15 tons) / 70 & 77kW (20 & 22 tons) 97 (2464) 93-5/16 (2370) 90-5/8 (2302) 88 (2235) 16-7/8 (428) 16-7/8 (428) 16-5/8 (422) 16-5/8 (422) 1/2" / 5/8" Cu Sweat 1/2" / 5/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 67-11/16 (1719) 30-1/2 (775) 3/4" FPT 67-11/16 (1719) 30-1/2 (775) 1-1/4" FPT 67-11/16 (1719) 76-1/2 (1943) 78-5/8 (1997) 72 (1829) 78-1/2 (1994) 75-3/8 (1915) 1-7/8 (48) 1-7/8 (48) 1-7/8 (48) 23-1/8 (587) 27-3/4 (705) 50-3/8 (1280) 54-3/8 (1381) 30-1/2 (775) 29 (736) 22-1/4 (565) 29 (737) 31-1/8 (790) 31-1/8 (790) 28-1/2 (724) 30-1/4 (768) 32 (813) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) 1/2" Cu Sweat 1/4" Cu Sweat 2-1/8" Cu Sweat 2-1/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408) 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling Systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN000928, Rev. 4 29 Liebert® DS™ Air-Cooled Systems Figure 22 Primary connection locations—downflow, air-cooled 53-77kW (15-22 ton), semi-hermetic compressors with EC fans, front, rear or bottom discharge NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). All dimensions from rear corner of unit including panels A A FRONT VIEW X O SECTION A-A Y R 4" (102mm) L1 L2 G1 G2 35" (889mm) BLOWER OUTLET 16-7/16" (418mm) ECS ECR CD E1 B1 LV1 LV2 LV3 HUM 109" (2769mm) DPN002179 Rev. 0 FRONT OF UNIT Table 18 Point R Piping details—downflow, air-cooled 53-77kW (15-22 ton) with EC fans, semi-hermetic compressors Description Refrigerant Access X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 82-3/4 (2102) 13-7/8 (352) 16-7/16 x 4 (4181x102) 53kW (15 ton) /70 & 77kw (20 & 22 ton) L1 Liquid Line System 1 97 (2464) 16-7/8 (428) 1/2 / 5/8 Cu Sweat L2 Liquid Line System 2 93-5/16 (2370) 16-7/8 (428) 1/2 / 5/8 Cu Sweat G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier)* 68-3/8 (1737) 31-3/8 (797) 3/4 FPT W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat HUM ECS** Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat ECR** Econ-O-Coil Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat E1 Electrical Conn. (High Volt) 78-1/2 (1994) 31-1/8 (790) 2-1/2 E2 Electrical Conn. (High Volt) 75-3/8 (1915) 31-1/8 (790) 2-1/2 LV1 Electrical Conn. (Low Volt) 2 (51) 29 (737) 7/8 LV2 Electrical Conn. (Low Volt) 2 (51) 30-7/8 (784) 7/8 LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8 B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8 x 30 (1483x762) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN002179, Rev. 0 Liebert® DS™ 30 Air-Cooled Systems Figure 23 Disassembly dimensions—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors with centrifugal fans Filter & Electric Box Assembly 39" (991mm) Compressor Assembly 76" (1930mm) Assembled Height Blower & Coil Assembly 76" (1930mm) 59-7/16" (1509mm) 37" (940mm) 33" (838mm) 26" (660mm) 82" (2083mm) 108" (2743mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. DPN000926 Rev. 4 Table 19 Component weights—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Component Compressor Assembly Air-Cooled Dual-Cool 970 (441) 970 (441) Filter and Electric Box Assembly 250 (114) 250 (114) Blower and Coil Assembly 1230 (560) 1410 (641) Source: DPN000926, Rev. 4 31 Liebert® DS™ Air-Cooled Systems 3.7 DIMENSIONS—LIEBERT DS 105, DOWNFLOW, AIR-COOLED MODELS Figure 24 Dimensions—downflow, air-cooled, 105kW (30 ton), standard scroll and semi-hermetic compressors with centrifugal fans Secondary Refrigerant Piping Entrance 102-13/16" (2611mm) Opening 33" (838mm) Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 24-3/8" Opening (619mm) AIR INLET OPENING 35" (889mm) Digital scroll compressors not available on DS 105. 3/4" (19mm) Bezels Secondary Entrance High-Volt Connection(s) Secondary Entrance Low-Volt Connections TOP VIEW Minimum required for filter replacement 132" (3353mm) 5" (127mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance be provided for component access. 131" (3327mm) DPN0001012 Rev. 4 FRONT VIEW Table 20 Weights—downflow, air-cooled, 105kW (30 ton), standard scroll and semi-hermetic compressors Forward-Curved Fans Compressor Type Cooling Type Semi-Hermetic Compressors Air-Cooled Scroll Compressors * Weight, lb. (kg) 3040 (1382) Dual-Cool 3400 (1545) Air-Cooled 2920 (1327) Dual-Cool 3280 (1491) * Digital scroll compressors not available on DS 105 Source: DPN001012, Rev. 4 Liebert® DS™ 32 Air-Cooled Systems Figure 25 Primary connection locations—downflow, air-cooled, 105kW (30 ton), standard scroll and semi-hermetic compressors with centrifugal fans Digital scroll compressors not available on 105 models. NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). G1 G2 R A A FRONT VIEW BLOWER OUTLET BLOWER OUTLET 4" (102mm) L1 L2 16-7/16" (418mm) B3 ECS X SECTION A-A 15-11/16" (398mm) Y 35" (889mm) B1 B2 LV1 LV2 LV3 CD E2 O BLOWER OUTLET ECR HUM E1 All dimensions from rear corner of unit including panels 131" (3327mm) DPN001014 Rev. 3 FRONT OF UNIT Table 21 Piping data—downflow, air-cooled, 105kW (30 ton), standard scroll*** and semi-hermetic compressors Point Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 109 (2769) 15-3/4 (400) 16-7/16 x 4 (418 x 102) R Refrigerant Access L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8" Cu Sweat L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8" Cu Sweat G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier)* 83-13/16 (2129) 30 (762) 3/4" FPT Condensate Drain (steam generating humidifier)* 83-13/16 (2129) 30 (762) 1-1/4" FPT 83-13/16 (2129) 30 (762) 1/2" Cu Sweat 102-3/4 (2610) 31-3/4 (806) 1/4" Cu Sweat CD W/ Optional Pump HUM Humidifier Supply Line ECS** Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8" Cu Sweat ECR** Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 98-1/8 (2492) 31-1/4 (794) 2-1/2" E2 Electrical Conn. (High Volt) 91 (2311) 31-1/4 (794) 2-1/2" LV1 Electrical Conn. (Low Volt) 2 (51) 28-1/4 (718) 7/8" LV2 Electrical Conn. (Low Volt) 2 (51) 30-1/4 (768) 7/8" LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8" B1 Blower Outlet 27-7/8 (708) 18 (457) 14-1/2 x 15-11/16 (368 x 398) B2 Blower Outlet 52-1/16 (1322) 18 (457) 14-1/2 x 15-11/16 (368 x 398) B3 Blower Outlet 76-1/4 (1937) 18 (457) 14-1/2 x 15-11/16 (368 x 398) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 105 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001014, Rev. 3 33 Liebert® DS™ Air-Cooled Systems Figure 26 Dimensions—downflow, air-cooled, 105kW (30 ton), front discharge models with EC fans Secondary Refrigerant Piping Entrance 102-7/8" (2611mm) Opening 33" (838mm) 24-3/8" (619mm) Opening AIR INLET OPENING 35" (889mm) Downflow electrical connections can be made from top or bottom of unit 3/4" (19mm) TOP VIEW Secondary Entrance High-Voltage Connection(s) Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool Secondary Entrance Low-Voltage Connections 132" (3353mm) 24" (610mm) Minimum required for filter replacement Filters are accessible only through top of unit. 5" (127mm) 76" (1930mm) 16-1/8" (410mm) 25-5/8" (649mm) Air Outlet Opening 16-1/8" (410mm) 24-7/8" (649mm) Air Outlet Opening 16-1/8" (410mm) 28-1/4" (718mm) Air Outlet Opening 30-7/8" (783mm) FRONT VIEW 57-1/2" (1459mm) 131" (3326mm) Customer Piping and Wiring Connections 3/4" (19mm) 34" Shaded area indicates a (864mm) recommended minimum clearance for component access. 1. For primary connection locations see standard submittals DPN001014 or DPN001015. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in 310697 compressor section. Pg. 3, Rev. 0 d) Or order additional SFA's to relocate connection locations Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll Model 105 Air-Cooled Dual Cool Air-Cooled Dual Cool 2774 (1258) 3134 (1422) 2654 (1204) 3014 (1367) Digital scroll compressors not available on DS 105 Source: 310697, Pg. 3, Rev. 0 Liebert® DS™ 34 Air-Cooled Systems Figure 27 Primary connection locations—downflow, air-cooled 105kW (30 ton), standard scroll and semi-hermetic compressors with EC fans, front, rear or bottom discharge Digital scroll compressors not available on 105 models. NOTE: Drawing not to scale. A Tolerance on all piping dimensions is ± 1/2" (13mm). A All dimensions from rear corner of unit including panels FRONT OF UNIT SECTION A-A X O Y G1 G2 R 4" (102mm) L1 L2 16-7/16" (418mm) 35" (889mm) BLOWER OUTLET ECS ECR CD E1 E2 B1 LV1 LV2 LV3 HUM 132" (3353mm) DPN002154 Rev. 0 FRONT VIEW Table 22 Piping data—downflow, air-cooled 105kW (30 ton) with EC fans, standard scroll*** and semi-hermetic compressors X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 109 (2769) 15-3/4 (400) 16-7/16 x 4 (418 x 102) Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8 Cu Sweat L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8 Cu Sweat G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8 Cu Sweat G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8 Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier)* 87-3/8 (2220) 31 (787) 3/4 FPT W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat ECS ** Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat ECR ** Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat E1 Electrical Conn. (High Volt) 98-1/8 (2492) 31 (788) 2-1/2 E2 Electrical Conn. (High Volt) 91 (2311) 31 (788) 2-1/2 LV1 Electrical Conn. (Low Volt) 2 (51) 29 (737) 7/8 LV2 Electrical Conn. (Low Volt) 2 (51) 30-7/8 (784) 7/8 LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8 B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965 x 762) Point Description R Refrigerant Access L1 * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 105 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN002154, Rev. 0 35 Liebert® DS™ Air-Cooled Systems Figure 28 Disassembly dimensions—downflow, air-cooled, 105kW (30 ton), standard scroll compressors with centrifugal Digital scroll compressors not available on 105 models. Filter & Electric Box Assembly 39" (991mm) 41-11/16" (1059mm) Compressor Assembly Blower & Coil Assembly 76" (1930mm) Assembled Height 59-7/16" (1510mm) 76" (1930mm) 37" (940mm) 33" (838mm) 26" (660mm) 105" (2667mm) 131" (3327mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 23 DPN001058 Rev. 2 Component weights—downflow, air-cooled, 105kW (30 ton), standard scroll compressors * Dry Weight, Approximate Including Panels, lb (kg) Forward-Curved Fans Air-Cooled Dual-Cool Compressor Assembly 830 (377) 830 (377) Filter and Electric Box Assembly 270 (123) 270 (123) Blower and Coil Assembly 1820 (827) 2180 (991) Component * Digital scroll compressors not available on DS 105 Source: DPN001058, Rev. 2 Liebert® DS™ 36 Air-Cooled Systems Figure 29 Disassembly dimensions—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors with centrifugal Filter & Electric Box Assembly 39" (991mm) 41 11/16" (1059mm) Compressor Assembly 76" (1930mm) Assembled Height Blower & Coil Assembly 76" (1930mm) 59-7/16” (1509mm) 37" (940mm) 33" (838mm) 26” (660mm) 105" (2667mm) 131" (3327mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 24 DPN001057 Rev. 2 Component weights—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Forward-Curved Fans Air-Cooled Dual-Cool Compressor Assembly 950 (432) 950 (432) Filter and Electric Box Assembly 270 (123) 270 (123) Blower and Coil Assembly 1820 (827) 2180 (991) Component Source: DPN001057, Rev. 2 37 Liebert® DS™ Air-Cooled Systems 3.8 DIMENSIONS—LIEBERT DS 028-042, UPFLOW, AIR-COOLED MODELS Figure 30 Dimensions—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans Alternate Refrigerant Piping Entrance Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. 33" (838mm) 35" (889mm) 3/4" (19mm) Bezels TOP VIEW High-Volt Connection(s) Low-Volt Connection(s) Minimum required for blower replacement 73" (1854mm) 1-1/2" (38mm) 24" (610mm) 76" (1930mm) 34" (864mm) 72" (1829mm) 2" (51mm) Table 25 Shaded area indicates a recommended minimum clearance for component access. FRONT VIEW DPN001163 Rev. 2 Weights—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors Dry Weight, Approximate, lb. (kg) Model Type Forward-Curved Fans Air-Cooled 1520 (689) Dual-Cool 1670 (758) Source: DPN001163, Rev. 2 Liebert® DS™ 38 Air-Cooled Systems Figure 31 Primary connection locations—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). 3 Field routed alternatives for refrigerant gas and liquid line connection points. 4 See submittal page DPN001120 for blower outlet and deck dimensional data. All dimensions from rear corner of unit including panels X 10-1/8" (257mm) 4-1/8" (105mm) 3. R1 ECR ECS HUM CPD BLOWER OUTLET 4. R2 L1 L2 G1 G2 4" (102mm) O Y 35" (889mm) 11-1/8" (283mm) 3. LV1 LV2 LV3 E1 E2 73" (1854mm) FRONT OF UNIT TOP VIEW 6" (152mm) 17-3/16" (437mm) R3 3. CGD* 3-7/8" (98mm) 17-1/16" L1 L2G1G2 (434mm) 14-1/4" (362mm) CGD* 15-7/8" (403mm) FRONT SECTION (Left Front Panel Not Shown) LEFT SIDE SECTION Table 26 Point Factory Location DPN001119 Rev. 2 Piping data—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors Description R1 3 Refrigerant Access (Top) R2 3 Refrigerant Access (Bottom) X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 60-1/2 (1537) 1-7/8" (48mm) 10-1/8 x 4-1/8 (257 x 105) 59-3/8" (1508mm) 14-3/4" (375mm) 11-1/8 x 4 (283 x 102) L1 Liquid Line System 1 70" (1778mm) 16-3/4 (425) 1/2" Cu Sweat L2 Liquid Line System 2 67-5/8" (1718mm) 16-3/4 (425) 1/2" Cu Sweat G1 Hot Gas Discharge 1 65-3/8" (1661mm) 16-5/8 (422) 5/8" Cu Sweat G2 Hot Gas Discharge 2 63" (1600mm) 16-5/8 (422) 5/8" Cu Sweat R3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437) CGD* Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat ECS** Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat ECR** Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 52-3/8 (1330) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 46-7/8 (1191) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" 3 LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL18825. Source: DPN001119, Rev. 2 39 Liebert® DS™ Air-Cooled Systems Figure 32 Disassembly dimensions—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with centrifugal fans Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly Filter & Coil Assembly 76" (1930mm) Assembled Height 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) 13" (330mm) 59" (1499mm) 72" Assembled Length (1829mm) NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 27 DPN001172 Rev. 1 Component weights—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cool Compressor Assembly 490 (223) 490 (223) Blower and Electric Box Assembly (Forward-Curved Fans) 510 (231) 510 (231) Filter and Coil Assembly 520 (236) 670 (304) Component Source: DPN001172, Rev. 1 Liebert® DS™ 40 Air-Cooled Systems Figure 33 Dimensions—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans Alternate Refrigerant Piping Entrance Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. 33" (838mm) 35" (889mm) 3/4" (19mm) Bezels TOP VIEW High-Volt Connection(s) 1-1/2" (38mm) Low-Volt Connection(s) Minimum required for blower replacement 86" (2184mm) 24" (610mm) 76" (1930mm) Shaded area indicates a recommended minimum clearance for component access. 2" (51mm) Table 28 34" (864mm) DPN001162 Rev. 2 85" (2159mm) FRONT VIEW Weights—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Dry Weight, Approximate, lb (kg) Model Type Forward-Curved Fans Air-Cooled 1830 (830) Dual-Cool 1980 (898) Source: DPN001162, Rev. 2 41 Liebert® DS™ Air-Cooled Systems Figure 34 Primary connection locations—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans All dimensions from rear corner of unit including panels X 22-1/2" (572mm) NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). 15-3/16" 3 Field-routed alternatives for refrigerant 35" (386mm) gas and liquid line connection points. (889mm) 4 See submittal page DPN001120 for 4" blower outlet and deck dimensional data. (102mm) 3 R2 ECR ECS HUM CPD 0 Blower Outlet 4 L1 L2 G1 G2 16-7/16" (418mm) 3 Y E1 LV1 LV2 LV3 E2 86" (2184mm) TOP VIEW 6" (152mm) 17-3/16" (437mm) R3 G1 G2 3 CGD * 3-7/8" (98mm) Table 29 R2 14-1/4" (362mm) 15-7/8" (403mm) LEFT SIDE SECTION VIEW 20-1/16" (509mm) L1 L2 CGD * Factory Location FRONT SECTION VIEW (Left Front Panel Not Shown) DPN001114 Rev. 2 Piping data—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Point R1 Front of Unit Description 3 Refrigerant Access (Top) 3 Refrigerant Access (Bottom) X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 60-11/16 (1542) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102) L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8" Cu Sweat G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8" Cu Sweat R3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437) CGD* Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat ECS** Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat 3 ECR** Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 52-3/8 (1330) 30" (762mm) 2-1/2" E2 Electrical Conn. (High Volt) 46-7/8 (1191) 30" (762mm) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001114, Rev. 2 Liebert® DS™ 42 Air-Cooled Systems Figure 35 Disassembly dimensions—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with centrifugal fans Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled\ Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) 26" (660mm) 85" (2159mm) Assembled Length 59" (1499mm) NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 30 DPN001171 Rev. 1 Component weights—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cool Compressor Assembly 800 (364) 800 (364) Blower and Electric Box Assembly (Forward-Curved Fans) 510 (231) 510 (231) Blower and Electric Box Assembly (EC Fans) 360 (163) 360 (163) Filter and Coil Assembly 520 (236) 670 (304) Component Source: DPN001171, Rev. 1 43 Liebert® DS™ Air-Cooled Systems Figure 36 Blower outlet and deck dimensions—upflow, air-cooled, 28-42kW (8-12 ton) with centrifugal fans 73" (1854mm) or 86" (2184mm) Ref E Blower Outlet * C A 35" (889mm) Ref B Blower Outlet Location - Top View Front of Unit * Duct flange not provided Top of Unit Blower Deck 1-1/2" (38mm) D 76" (1930mm) Ref Front or Rear Throw Air Supply Table 31 DPN001120 Rev. 3 Blower outlet and deck dimensions—upflow, air-cooled, 28-42kW (8-12 ton) Dimensional data, in. (mm) Model 28-42kW (8-12ton) Blower 15 x 15 15 x 11 Supply A B C D E Front Throw 15-7/8 (404) Rear Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 25 (635) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 25 (635) Front Throw 15-7/8 (404) 14-1/2 (368) 2-1/8 (54) 25-5/8 (651) 25 (635) Rear Throw 15-7/8 (404) 14-1/2 (368) 11-5/8 (295) 25-5/8 (651) 25 (635) Source: DPN001120, Rev. 3 Liebert® DS™ 44 Air-Cooled Systems 3.9 DIMENSIONS—LIEBERT DS 053-077, UPFLOW, AIR-COOLED MODELS Figure 37 Dimensions—upflow, air-cooled, 53-77kw (15-22 ton), scroll or digital scroll compressors with centrifugal fans Alternate Refrigerant Piping Entrance Digital scroll compressors not available on DS 077. 33" (838mm) 35" (889mm) High-Volt Connection(s) 1-1/2" (38mm) 3/4" (19mm) Bezels TOP VIEW Minimum required for blower replacement Low-Volt Connection(s) 98" (2489mm) 24" (610mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 97" (2464mm) 2" (51mm) FRONT VIEW NOTE: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. Table 32 DPN001166 Rev. 2 Weights - upflow, air-cooled, 53-77kw (15-22 ton)—scroll or digital scroll compressors Dry Weight, Approximate, lb (kg) Model # Compressor Type 053, 042 077 * Scroll/Digital Scroll Standard Scroll Fan Type Air-Cooled Dual-Cool Air-Cooled Dual-Cool Forward-Curved Blowers 2070 (939) 2250 (1021) 2070 (939) 2250 (1021) * Digital scroll compressors not available on DS 077 Source: DPN001166, Rev. 2 45 Liebert® DS™ Air-Cooled Systems Figure 38 Primary connection locations—upflow, air-cooled, 53-77kw (15-22 ton), scroll compressors with centrifugal fans Digital scroll compressors not available on DS 077. All dimensions from rear corner of unit including panels 12" (305mm) NOTES: 1. Drawing not to scale. 4" 2. Tolerance on all piping dimensions (102mm) is ± 1/2" (13mm). 4" 3. Field-routed alternatives for refrigerant 35" (102mm) gas and liquid line connection points. (889mm) 4. See submittal page DPN001191 for 12-13/16" blower outlet and deck dimensional data. Blower Outlet Blower Outlet (325mm) 6" (152mm) 98" (2489mm) Front of Unit TOP VIEW OF UNIT 17-3/16" (437mm) 14-1/4" (362mm) 3-7/8" (98mm) 15-7/8" (403mm) 17-1/16" (433mm) Factory Location LEFT SIDE SECTION VIEW OF UNIT FRONT SECTION VIEW OF UNIT (Left Front Panel Not Shown) DPN001213 Rev. 1 Table 33 Piping data - upflow, air-cooled, 53-77kw (15-22 ton)—scroll compressors *** Point Description X in. (mm) Y in. (mm) Connection Size / Opening, in. (mm) 12 x 4 (305 x 102) R1 3 Refrigerant Access (Top) 83-5/8 (2124) 2 (51) R2 3 Refrigerant Access (Bottom) 82-3/4 (2102) 14-3/4 (374) 12-3/16 x 4 (310 x 102) 53kW (15 ton) / 70 & 77kW (20 & 22 ton) L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2" / 5/8" Cu Sweat L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2" / 5/8" Cu Sweat G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8" / 1-1/8" Cu Sweat — — 6 x 17-3/16 (152 x 437) R3 3 Refrigerant Access (Side) CGD* Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2" Cu Sweat HUM Humidifier Supply Line 79-5-16 (2015) 9-7/8 (251) 1/4" Cu Sweat ECS Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8" Cu Sweat ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8" Cu Sweat E1 Electrical Conn. (High Volt) 75-3/8 (1915) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 69-7/8 (1775) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on dual-cool systems only. *** Digital scroll compressors not available on DS 077 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001213, Rev. 1 Liebert® DS™ 46 Air-Cooled Systems Figure 39 Disassembly dimensions—upflow, air-cooled, 53-77kw (15-22 ton), scroll or digital scroll compressors with centrifugal fans Digital scroll compressors not available on DS 077. Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) 82" (2083mm) 15" (381mm) 97" (2464mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. DPN001210 Rev. 1 Table 34 Component weights—upflow, air-cooled, 53-77kw (15-22 ton), scroll or digital scroll compressors Dry Weight, Approximate, Including Panels, lb (kg) Model # 053, 070 Compressor Component Compressor Assembly Blower and Electric Box Assembly Forward-Curved Fans Filter and Coil Assembly 077 Scroll/Digital Scroll Standard Scroll * Air-Cooled Dual-Cool Air-Cooled Dual-Cool 540 (246) 540 (246) 540 (246) 540 (246) 770 (349) 770 (349) 770 (349) 770 (349) 760 (345) 940 (426) 760 (345) 940 (426) * Digital scroll compressors not available on DS 077 Source: DPN001210, Rev. 1 47 Liebert® DS™ Air-Cooled Systems Figure 40 Dimensions—upflow, air-cooled 53-77kw (15-22 ton), semi-hermetic compressors with centrifugal fans Alternate Refrigerant Piping Entrance 33" (838mm) 35" (889mm) 3/4" (19mm) Bezels High-Volt Connection(s) 1-1/2" (38mm) TOP VIEW Low-Volt Connection(s) Minimum required for blower replacement 109" (2769mm) 24" (610mm) 76" (1930mm) 34" (864mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access. 108" (2743mm) FRONT VIEW NOTE: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. Table 35 DPN001165 Rev. 2 Weights—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors Dry weight, including panels, lb. (kg) 053 070, 077 Model Type Air-Cooled Dual-Cool Air-Cooled Dual-Cool Forward-Curved Fans 2350 (1069) 2530 (1150) 2500 (1134) 2680 (1216) Source: DPN001165, Rev. 2 Liebert® DS™ 48 Air-Cooled Systems Figure 41 Primary connection locations—upflow air-cooled 53-77kW (15-22 ton), semi-hermetic compressors with centrifugal fans All dimensions from rear corner of unit including panels 22-1/2" (572mm) NOTES: 15-3/16" 1. Drawing not to scale. 35" (386mm) 2. Tolerance on all piping dimensions (889mm) is ± 1/2" (13mm). 4" 3. Field-routed alternatives for refrigerant (102mm) gas and liquid line connection points. 4. See submittal page DPN001191 for blower outlet and deck dimensions. Blower Outlet X O Blower Outlet 16-7/16" (418mm) Y 6" (152mm) 109" (2769mm) TOP VIEW OF UNIT Front of Unit 17-3/16" (437mm) 3-7/8" (98mm) 14-1/4" (362mm) 20-1/16" (509mm) 15-7/8" (403mm) CGD * LEFT SIDE SECTION VIEW OF UNIT Table 36 DPN001212 Rev. 2 Piping data—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors Point Description R1 3 Refrigerant Access (Top) 3 Refrigerant Access (Bottom) R2 Factory Location FRONT SECTION VIEW OF UNIT (Left Front Panel Not Shown) X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 83-3/4 (2127) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386) 86 (2184) 13-7/8 (352) 16-7/16 x4 (418 x102) 53kW (15 ton) / 70 & 77kW (20 & 22 ton) L1 Liquid Line System 1 97 (2464) 16-3/4 (425) 1/2" / 5/8" Cu Sweat L2 Liquid Line System 2 93-5/16 (2370) 16-3/4 (425) 1/2" / 5/8" Cu Sweat G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437) CGD* Condensate Gravity Drain — — 3/4 FPT CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2" Cu Sweat HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4" Cu Sweat ECS Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8" Cu Sweat ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8" Cu Sweat E1 Electrical Conn. (High Volt) 75-3/8 (1915) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 69-7/8 (1775) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" R3 3 * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on dual-cool systems only. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001212, Rev. 2 49 Liebert® DS™ Air-Cooled Systems Figure 42 Disassembly dimensions—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressors with centrifugal fans Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) 26" (660mm) 82" (2083mm) 108" (2743mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 37 DPN001209 Rev. 1 Component weights—upflow air-cooled 53-77kw (15-22 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cool Compressor Assembly 970 (441) 970 (441) Blower and Electric Box Assembly Forward-Curved Fans 770 (349) 770 (349) Filter and Coil Assembly 760 (345) 940 (426) Component Source: DPN001209, Rev. 1 Liebert® DS™ 50 Air-Cooled Systems Figure 43 Blower outlet and deck dimensions—upflow 53-77kW (15-22 ton) with centrifugal fans 98" (2449mm) or 109" (2769mm) F E Blower Outlets * C A A 35" (889mm) Ref B B Blower Outlet Location - Top View Front of Unit * Duct flanges not provided. Top of Unit Blower Deck D 1-1/2" (38mm) 76" (1930mm) Ref. Front or Rear Air Throw Supply Table 38 DPN001191 Rev. 6 Blower outlet and deck dimension—upflow, 53-77kW (15-22 ton) Dimensional Data, in. (mm) Models 53-77kW (15-22 ton) Blower 15 x 15 15 x 11 B C Front Throw 15-7/8 (404) Supply A 18-5/8 (472) 2-1/8 (54) Rear Throw 15-7/8 (404) 18-5/8 (472) Front Throw 15-7/8 (404) 14-11/16 (373) D E F 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410) 11-5/8 (295) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410) 2-1/8 (54) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484) Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484) Source: DPN001191, Rev. 6 51 Liebert® DS™ Air-Cooled Systems 3.10 DIMENSIONS—LIEBERT DS 105, UPFLOW, AIR-COOLED MODELS Figure 44 Dimensions—upflow, air-cooled, 105kW (30 ton), semi-hermetic and scroll compressors with centrifugal fans Alternate Refrigerant Piping Entrance Digital scroll compressors not available on 105 models. 33" (838mm) 35" (889mm) 3/4" (19mm) Bezels High-Volt Connection(s) Low-Volt Connection(s) TOP VIEW 1-1/2" (38mm) Minimum required for blower replacement 132" (3353mm) 24" (610mm) 76" (1930mm) 34" (864mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access. 131" (3327mm) FRONT VIEW Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. Table 39 DPN001168 Rev. 1 Weights—upflow, air-cooled, 105kW (30 ton), semi-hermetic and scroll compressors * Dry Weight, Approximate, lb (kg) Semi-Hermetic Fan Type Forward-Curved Fans Scroll Air-Cooled Dual-Cool Air-Cooled Dual-Cool 3000 (1361) 3330 (1510) 2880 (1306) 3210 (1456) * Digital scroll compressors not available on DS 105. Source: DPN001168, Rev. 1 Liebert® DS™ 52 Air-Cooled Systems Figure 45 Primary connection locations—upflow, air-cooled, 105kW (30 ton), semi-hermetic and scroll compressors with centrifugal fans Digital scroll compressors not available on 105 models. All dimensions from rear corner of unit including panels 22-1/2" (572mm) 35" (889mm) 15-3/16" (386mm) 4" (102mm) R2 ECR ECS HUM CPD Blower Outlet Blower Outlet 16-7/16" (418mm) NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). 3. Field routed alternatives for refrigerant gas and liquid line connection points. 4. See submittal page DPN001192 for blower outlet and deck dimensional data. O X Blower Outlet LV1 LV3 LV2 E1 E2 Y LV4 132" (3353mm) TOP VIEW Front Of Unit 6" (152mm) R3 20-1/16" (509mm) 17-3/16" (437mm) 3-7/8" (98mm) G2 L1 L2G1 CGD* 14-1/4" (362mm) 15-7/8" (403mm) CGD* Factory Location FRONT SECTION VIEW (Left Front Panel Not Shown) LEFT SIDE SECTION VIEW Table 40 Point R1 R2 3 DPN001257 Rev. 0 Piping data—upflow, air-cooled 105kW (30 ton), semi-hermetic and scroll compressors *** X, in. (mm) Y, in. (mm) Connection Size / Opening Refrigerant Access (Top) 106-7/8 (2715) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386) Description Refrigerant Access (Bottom) 109-1/8 (2772) 13-7/8 (352) 16-7/16 x 4 (418 x 102) L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8" Cu Sweat L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8" Cu Sweat G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8" Cu Sweat G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8" Cu Sweat R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437) CGD* Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2" Cu Sweat HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4" Cu Sweat ECS** Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260) 2-5/8" Cu Sweat ECR** Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 98-1/2 (2502) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 93 (2362) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 41-1/8 (1045) 30-3/8 (772) 7/8" LV2 Electrical Conn. (Low Volt) 38-7/8 (987) 30-3/8 (772) 7/8" LV3 Electrical Conn. (Low Volt) 35-1/8 (892) 30-3/8 (772) 7/8" LV4 Electrical Conn. (Low Volt) 31-5/8 (803) 30-3/8 (772) 7/8" 3 * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on dual-cool systems only. *** Digital scroll compressors not available on DS 105 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001257, Rev. 0 53 Liebert® DS™ Air-Cooled Systems Figure 46 Disassembly dimensions—upflow, air-cooled, 105kW (30 ton), standard scroll compressors with centrifugal fans Digital scroll compressors not available on DS 105. Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1164mm) 33" (838mm) 26" (660mm) 105" (2667mm) 131" (3327mm Assembled Length NOTE: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 41 DPN001255 Rev. 1 Component weights—upflow, air-cooled, 105kW (30 ton), standard scroll compressors * Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cool Compressor Assembly 830 (376) 830 (376) Blower and Electric Box Assembly Forward-Curved Fans 1080 (490) 1080 (490) Filter and Coil Assembly 970 (440) 1300 (590) Component *Digital scroll compressors not available on DS 105 Source: DPN001255, Rev. 1 Liebert® DS™ 54 Air-Cooled Systems Figure 47 Disassembly dimensions—upflow, air-cooled, 105kW (30 ton), semi-hermetic compressors with centrifugal fans Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly Filter & Coil Assembly 76" (1930mm) Assembled Height 76" (1930mm) 45-13/16" (1164mm) 33" (838mm) 26" (660mm) 105" (2667mm) 131" (3327mm Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 42 DPN001254 Rev. 1 Component weights—upflow, air-cooled, 105kW (30 ton), semi-hermetic compressors Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled Dual-Cool Compressor Assembly 950 (431) 950 (431) Blower and Electric Box Assembly Forward-Curved Fans 1080 (490) 1080 (490) Filter and Coil Assembly 970 (440) 1300 (590) Component Source: DPN001254, Rev. 0 55 Liebert® DS™ Air-Cooled Systems Figure 48 Blower outlet and deck dimensions—upflow 105kW (30 ton), with centrifugal fans 132" (3353mm) G Blower Outlets * F E A A A 35" (889mm) Ref B B B C BLOWER OUTLET LOCATION - TOP VIEW Front of Unit * Duct flanges not provided TOP OF UNIT Blower Deck 1-1/2" (38mm) 76" (1930mm) Ref DPN001192 Rev. 1 Front or Rear Throw Air Supply Table 43 Blower outlet and deck dimension—upflow 105kW (30 ton), with centrifugal fans Dimensional Data, in. (mm) Blower 15 x 11 SUPPLY A B Front Throw 15-7/8 (404) 14-11/16 (373) C D 2-1/8 (54) E F G 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984) Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984) Source: DPN001192, Rev. 1 Liebert® DS™ 56 Air-Cooled Systems 3.11 HEAT REJECTION—LIEBERT MC, FIN/TUBE AND PIGGYBACK CONDENSERS 3.11.1 Liebert MC Microchannel Condensers Liebert MC Condenser Selection Table 44 Traditional open room (75°F/45RH return air conditions) Outdoor Design Ambient Temperature Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C) DS/VS028A MCM080_8 MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 DS/VS035A MCM080_8 MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 DS/VS042A MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 MCL110_8 DS/VS053A MCM080_8 MCM080_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8 DS/VS070A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8 DS/VS077A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8 DS/VS105A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8 Table 45 High-temperature return (85°F/33RH return air conditions) Outdoor Design Ambient Temperature Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C) DS/VS028A MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 MCM160_8 DS/VS035A MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 DS/VS042A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCM160_8 DS/VS053A MCL110_8 MCL110_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8 DS/VS070A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8 DS/VS077A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8 DS/VS105A MCM160_8 MCL220_8 MCL220_8 MCL220_8 MCL220_8 — Table 46 ™ Traditional open room (75°F/45RH return air conditions) Liebert QuietLine sound levels Outdoor Design Ambient Temperature Liebert DS Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) DS/VS028A MCM080E8 MCM080E8 MCL110E8 MCL110E8 MCL110E8 DS/VS035A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8 DS/VS042A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8 DS/VS053A MCL110E8 MCL110E8 MCM160E8 MCL220E8 MCL220E8 DS/VS070A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8 DS/VS077A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8 DS/VS105A MCM160E8 MCL220E8 Consult Factory 57 Liebert® DS™ Air-Cooled Systems ™ Dimensions—Liebert MC Figure 49 Condensers Condenser planning dimensions—MCM080, MCM160 with/without Liebert Lee-Temp™ 46-1/4" (1175mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. H G B Height to Top of Fan Guard A F Eyebolts for lifting condenser provided on four-fan models C 15-1/4" 387mm 46-1/4" (1175mm) G B Height to Top of Fan Guard A For dual circuit only 46" (1168mm) H 15-1/4" 387mm F 46-5/16" (1177mm) One-Fan Condenser Electric Box End C 39-5/16" (999mm) 44-3/8" (1127mm) 46" (1168mm) ANCHOR PLAN E D Leg supplied for each Liebert Lee-Temp kit on 2- & 4-fan models Provided On Four-Fan Models DPN002172, Rev 3 DPN002189, Rev. 4 Electric Box End ANCHOR PLAN (One-Fan Condenser) 39-5/16" (999mm) 44-3/8" (1127mm) 46-5/16" (1177mm) Liebert Model No. No. of Fans A in. (mm) B in. (mm) C in. (mm) D in. (mm) E in. (mm) MCM080 2 105-1/4 (2674) — 96-1/16 (2440) 94-7/16 (2398) — 18 (457) 31-5/8 (803) 39-5/8 (1006) MCM160 4 202-7/16 (5142) 113-1/2 (2883) 192-1/4 (4883) 94-7/16 (2398) 96-3/16 (2444) 36 (914) 49-5/8 (1260) 57-5/8 (1464) 48 (1219) 61-5/8 (1565) 69-5/8 (1768) 60 (1524) 73-5/8 (1870) 81-5/8 (2073) * Cross bracing required for legs longer than 18". Number of legs varies per model and options selected. Source: DPN002172, Rev. 3; DPN002189, Rev4 Liebert® DS™ 58 Leg Height G H F* in. (m.) in. (mm) in. (mm) Air-Cooled Systems Figure 50 Cabinet and anchor dimensions—Liebert MC Temp receivers ™ models MCL110 and MCL220 with Liebert Lee- Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. 55-5/8" (1413mm) Eyebolts for lifting condenser provided on 3&4 fan models Height to Top of Fan Guard 15-1/4" (387mm) For 55-1/2" Dual-Circuit (1409mm) Only 15-1/4" (387mm) Provided on 3- & 4- Fan Models (1) leg supplied for each Liebert Lee-Temp kit on 2, 3, & 4 fan models Electric Box End D E 48-3/4" (1239mm) 53-7/8" (1368mm) DPN002415 Rev. 3 54-3/8" (1381mm) ANCHOR PLAN Model No No. of Fans A in. (mm) B in. (mm) C in. (mm) D in. (mm) E in (mm) Leg Height F* in. (m.) MCL110 2 124 1/8 (3152) — 112-1/8 (2848) 110-1/2 (2806) — MCL220 4 236-5/16 (6003) 129-9/16 (3291) 224-3/8 5699) 110-1/2 (2806) 112-1/4 (2851) * Cross bracing required for legs longer than 18". Number of legs varies per model and options selected. Source: DPN002415, Rev. 3 59 G in. (mm) H in. (mm) 18 (457) 35-7/8 (911) 43-5/8 (1108) 36 (914) 53-7/8 (1368) 61-5/8 (1565) 48 (1219) 65-7/8 (1673) 73-5/8 (1870) 60 (1524) 77-7/8 (1978) 85-5/8 (2175) Liebert® DS™ Air-Cooled Systems Figure 51 Condenser planning dimensions—MCL110 and MCL220 55-5/8" (1413mm) Height to Top of Fan Guard Eyebolts for lifting condenser provided on 3&4 fan models Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. 55-1/2" (1409mm) ANCHOR PLAN E 53-7/8" (1368mm) 48-3/4" (1239mm) Electric Box End D Provided on 3- & 4- Fan Models DPN002416 Rev. 2 Model # # of Fans A in. (mm) B in. (mm) C in. (mm) D in. (mm) E in. (mm) Leg Height F * In. (mm) G In. (mm) H In. (mm) MCL110 2 124-1/8 (3152) — 112-1/8 (2848) 110-1/2 (2806) — 18 (457) 35-7/8 (911) 43-5/8 (1108) MCL220 4 236-5/16 (6003) 129-9/16 (3291) 224-3/8 (5699) 110-1/2 (2806) 112-1/4 (2851) 36 (914) 53-7/8 (1368) 61-5/8 (1565) 56-1/8 (1425) 48 (1219) 65-7/8 (1673) 73-5/8 (1870) * 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). Number varies according to model and options. Source: DPN002416, Rev. 2 Liebert® DS™ 60 Air-Cooled Systems Figure 52 Typical Liebert MC ™ condenser footprint—dimensions 13/16" 21mm 2-1/2" (64mm) 3-5/8" (93mm) 1-7/8" (48mm) 2-1/2" (64mm) 3-5/8" (93mm) 1/2"x1" (12.7mm x 25.4mm) Obround 1-7/8" (48mm) 61 Liebert® DS™ Air-Cooled Systems Electrical Data—Liebert MC™ Condensers Table 47 Liebert MC electrical data, three-phase, 60Hz condenser, Premium Version (EC control) Power Requirements FLA WSA OPD Model # Number of Fans 208/230V 380/415V 460V 208/230V 380/415V 460V 208/230V 380/415V 460V MCM080 2 4.6 2.8 2.8 5.5 3.3 3.3 15 15 15 MCM160 4 9.2 5.6 5.6 9.8 6.0 6.0 15 15 15 MCL110 2 11.4 5.6 5.6 12.8 6.3 6.3 15 15 15 MCL220 4 22.8 11.2 11.2 24.2 11.9 11.9 25 15 15 1. 2. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device. 208V–460V premium models must be connected to Wye 3-phase systems. Electrical Field Connections—Liebert MC Condensers Figure 53 Electrical field connections—Liebert MC Condensers premium efficiency control, with and without Liebert Lee-Temp Fan 2 Fan 1 Fan 2 Lee-Temp receiver tank (1 per circuit). NOTE: Standard heater pads are 150 watt each. (Optional 300 watt heater pads are available.) Standard heater pad voltage is 230V. (120V heater pad voltage is optional.) Electrical Connection Box with Cover Fan 1 Electrical service connection. Pigtails in electric handy box are factory-wired to Liebert Lee-Temp heater pads for field-connection of separate continuous electric source; wire not by Liebert 1 5A 5B 6 4 7 2 3 5C 8 10 9 DPN002169 Rev. 3 DPN002374 Pg. 2, Rev. 1 Liebert® DS™ 62 See Electrical Connections—Premium Efficiency Control, Liebert MC Condensers on page 63 for key to numbered components Air-Cooled Systems Electrical Connections—Premium Efficiency Control, Liebert MC Condensers Key Electrical Details; Source: DPN002169, Rev. 3 and DPN002374 Rev. 2 1. Three-phase electrical service—Terminals are on top of disconnect switch for one-fan and two-fan units. Terminals are on bottom of disconnect switch for three-fan and four-fan units. Three-phase service not by Emerson. See Note 5. 2. Earth ground—Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection. 3. Primary high voltage entrance—Three 7/8" (22.2mm) diameter knockouts located at the bottom of the enclosure. 4. SPD field connection terminals—High-voltage surge protection device (SPD) terminals. SPD is an optional device. 5. CANbus terminal connections—Field terminals for CANbus cable connection. • 5A is the CANbus connectors • TB49-1 is the input terminal for CANbus high • TB49-3 is the input terminal for CANbus low • TB50-1 is output terminal for CANbus high • TB50-3 is the output terminal for CANbus low • Each CANbus cable shield is connected to terminal “SH”, Item 9. • 5B is the “END OF LINE” jumper. • 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Emerson. See Note 2. 6. Remote unit shutdown—Replace exiting jumper between terminals TB38-1 and TB38-2 with field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied Class 1 wiring. 7. Alarm terminal connections a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common; TB74-2 is normally open; and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied Class 1 wiring. b. Shutdown Alarm Relay indicates when condenser loses power or when a critical alarm has occurred that shuts down the condenser unit. TB74-4 is common, TB74-5 is normally open and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied Class 1 wiring. 8. Indoor unit interlock and SPD alarm terminals a. On any call for compressor operation, normally open contact is closed across Terminals 70 & 71 for Circuit 1, and normally open contact is closed across Terminals 70 & 230 for Circuit 2 from indoor room unit. b. During SPD alarm, normally open contact is closed across Terminals 12 &13. SPD is an optional device. 9. CANbus shield terminal—Terminal for field connection of the CANbus field-supplied cables. Shield of CANbus field-supplied cables must not be connected to ground at the condenser. 10. Primary low voltage entrance—One 7/8" (22.2mm) diameter knockout that is free for customer low-voltage wiring. 63 Liebert® DS™ Air-Cooled Systems NOTES 1. Refer to specification sheet for unit voltage rating, full load amp and wire size amp ratings. 2. The CANbus wiring is field supplied and must be: • shielded • 22-18AWG stranded tinned copper, • twisted pair (minimum 8 twists per foot), • low capacitance (15pf/ft or less), • plenum rated (NEC type CMP) if required by local codes, • UV and moisture resistant or run within conduit once in an outdoor environment, and • must be temperature and voltage rated for conditions present. Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV resistant outdoor rated) Category 5, 5e or higher. 3. Do not run the CANbus cable in the same conduit, raceway, or chase as high voltage. 4. For CANbus network lengths greater than 350ft. (107m), contact Liebert factory. 5. All wiring must be sized and selected for insulation case per NEC and other local codes. 6. The electrically commutated (EC) motors included in the Liebert MC condensers are suitable for connection to power supplies with a solidly grounded neutral. (Some platforms can accept power supplies listed under Item b below. Contact the factory for more information.) a. Acceptable power supplies for 208 to 480V nominal units • 208V wye with solidly grounded neutral and 120V line to ground; • 380V wye with solidly grounded neutral and 220V line to ground; • 480V wye with solidly grounded neutral and 277V line to ground. b. Unacceptable power supplies for 208V to 480V nominal units: • wye with high resistance (or impedance) ground; • delta without ground or with floating ground; • delta with corner ground; or • delta with grounded center tap Liebert® DS™ 64 Air-Cooled Systems 3.12 PIPING—LIEBERT MC™ CONDENSERS Typical System Configurations—LIEBERT MC CONDENSERS Figure 54 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the outdoor condenser (with or without Liebert Lee-Temp™) and field-supplied interconnection piping. Figure 54 Liebert MC piping schematic with and without Liebert Lee-Temp Check Valve Relief Valve Service Valve Liquid Return Head Pressure Liebert Lee-Temp Receiver Control Valve Condenser Coil Optional Field-Installed Fusible Plug Condenser Coil Hot Gas Discharge Liebert Lee-Temp Liquid Sensing Bulb Evaporator Coil For rises over 25ft. (7.6m), trap every 20ft. (6m) or at evenly divided distances* Suction Service Valve Field installed relief valve(s) required for 50Hz EU CE units Service Check Valve Valve Compressor External Equalizer *Isolation Valve Hot Gas Discharge Expansion Solenoid Valve Valve Sight Glass Liquid Line Filter Drier Refrigerant Piping Field Piping Service/Schrader (Access) Connection No Valve Core Service/Schrader (Access) Connection With Valve Core * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance NOTES Single refrigeration circuit shown for clarity. Schematic representation shown. Do not use for specific connection locations. 65 *Isolation Trap at base of risers Valve over 5ft. (1.5m)* DPN002188 Rev. 1 Liebert® DS™ Air-Cooled Systems ™ Figure 55 Piping dimensions—Liebert MC ™ dual circuit condensers with Liebert Lee-Temp Hot Gas Line To Condenser Entering Hot Gas Line Metal Clamp Isolator Detail AA Position elbow to direct relief valve downward B View Fasten hot gas line to cabinet using flat surface clamps with isolators (field-supplied) Inverted traps in refrigerant See Detail A A lines are internal to Liquid Line From Condenser Leaving Liquid Line the condenser. Do not trap external to the unit. Hot Gas Line To Condenser Liebert-supplied piping assembly will include one or two valve and check valves, depending on condenser capacity and refrigerant GENERAL ARRANGEMENT R407C 2 and 4 Fan Piping Assembly Leaving Liquid Line R410A 2 Fan Piping Assembly R410A 4 Fan Piping Assembly Liquid Line From Condenser Field Piping Position elbow to direct relief valve downward C View Entering Hot Gas Line Note: 1. The following materials are supplied by Emerson for each circuit (shipped loose with condenser) for field installation: insulated Liebert Lee-Temp storage tank with sight glasses, head pressure control valve, check valve, rotalock valve and pressure relief valve. All other piping to be supplied and installed by others. 2. Consult factory for proper line sizing for runs longer than 150ft. (45.7m) equivalent length. DPN002426 Rev. 4 Table 48 Piping dimensions—Liebert MC dual circuit condensers with Liebert Lee-Temp Condenser Connections ODS, in. Liebert Lee-Temp Connections Liquid Hot Gas Tee IDS, in. Liquid Line to Lee-Temp Valve ODS, In. Receiver Out R407C IDS, in. Receiver Out R410A IDS, in. 7/8 5/8 7/8 5/8 5/8 5/8 2 1-1/8 7/8 1-1/8 7/8 7/8 7/8 MCM160 2 1-1/8 7/8 1-1/8 7/8 1-1/8 1-1/8 MCL220 2 1-3/8 1-1/8 1-3/8 1-1/8 1-1/8 1-1/8 Model # Circuit No. Hot Gas MCM080 2 MCL110 Source: DPN002426, Rev. 4 Liebert® DS™ 66 Air-Cooled Systems Figure 56 Piping connections—Liebert MC ™ dual circuit two-fan and four-fan units Vertical Leaving Liquid Line Inverted traps in refrigerant lines are internal to the condenser. Do not trap external to the unit. Horizontal Circuit #1 Entering Hot Gas Line Circuit #2 Field Piping Optional fusible plug service kit to be brazed into the liquid line(s) in either the vertical or horizontal position. (where required) (vertical position is preferred, horizontal position is optional.) for two circuit systems, one fusible plug kit will need to be installed in each circuit. Table 48 DPN002425 Rev. 3 Liebert MC piping connection sizes—Liebert MC dual-circuit, two-fan and four-fan units Connection Sizes, OD, in Model # # of Fans Hot Gas Line Liquid Line MCM080 2 7/8 5/8 MCL110 2 1-1/8 7/8 MCM160 4 1-1/8 7/8 MCL220 4 1-3/8 1-1/8 Source: DPN002425, Rev. 3 67 Liebert® DS™ Air-Cooled Systems 3.12.1 Fin/Tube Condensers Fin/Tube Selections Table 49 Liebert DS air-cooled condenser selection, finned-tubular design, R-407C Ambient Temperature °F (°C) Outdoor Condenser Outdoor Quiet-Line Condenser Liebert DS Model 95 (35) 100 (38) 105 (41) 95 (35) 100 (38) 105 (41) 028 CD*-205 CD*-205 CD*-251 CD*-214 CD*-214 CD*-286 035 CD*-205 CD*-205 CD*-251 CD*-214 CD*-214 CD*-286 042 CD*-205 CD*-251 CD*-308 CD*-286 CD*-286 CD*-409 053 CD*-251 CD*-308 CD*-415 CD*-286 CD*-409 CD*-409 070 CD*-308 CD*-415 CD*-415 CD*-409 CD*-477 CD*-572 077 CD*-308 CD*-415 CD*-616 CD*-409 CD*-572 CD*-572 105 CD*-415 CD*-616 CD*-616 CD*-572 N/A N/A Dimensions—Fin/Tube Condensers Table 50 Fin/tube condenser physical data and R-407C refrigerant required per condenser circuit Dual Circuit lb/circuit (kg/circuit) Connection Size, OD, In. Model Number Number of Fans Standard Models CD*165 2 CD*205 2 CD*251 3 CD*308 3 CD*415 4 CD*510 4 CD*616 6 Quiet-Line Models DCD*143 2 DCD*214 3 DCD*286 4 DCD*409 6 DCD*572 8 Liebert® DS™ Number of Circuits Hot Gas Liquid Net Weight lb (kg) FSC or VFD Liebert Lee-Temp (includes receiver) 2 2 2 2 2 2 2 7/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 5/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 425 (193) 495 (225) 500 (227) 670 (304) 840 (381) 1188 (539) 1380 (626) 5 (2.3) 7 (3.2) 10 (4.6) 11 (5.0) 24 (10.9) 29 (13.2) 26 (11.8) 26 (11.8) 54 (24.4) 36 (16.3) 55 (24.9) 102 (46.2) 142 (64.4) 108 (49.0) 2 2 2 2 2 1-1/8 1-1/8 1-1/8 1-5/8 2-1/8 7/8 7/8 7/8 1-1/8 1-1/8 515 (234) 840 (381) 1105 (501) 1380 (626) 2430 (1102) N/A N/A N/A N/A N/A 61 (27.7) 77 (34.9) 119 (54.0) 125 (55.8) 186 (84.4) 68 Air-Cooled Systems Figure 57 Fin/tube condenser dimensions, 2-fan model 43-9/16" (1106mm) 91-1/2" (2324mm) 37-7/8" (962mm) 18" (457mm) 84" (2134mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. 43-3/16" (1097mm) Figure 58 Fin/tube condenser dimensions, 3-fan and 4-fan models 43-9/16" (1106mm) 131-1/2" (3340mm) 37-7/8" (962mm) 43-9/16" (1106mm) 171-1/2" (4356mm) 18" (457mm) 124" (3150mm) 70" (1778mm) 37-7/8" (962mm) Eyebolts for Lifting 43-3/16" (1097mm) 18" (457mm) Note: Overall height to the top of fan guard 43-1/8" (1095mm) 164" (4166mm) 43-3/16" (1097mm) 69 Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. Liebert® DS™ Air-Cooled Systems Figure 59 Fin/tube condenser dimensions, 6-fan and 8-fan models 131-1/2" (3340mm) 87-1/8" (2213mm) 87-1/8" (2213mm) 171-1/2" (4356mm) 37-7/8" (962mm) 37-7/8" (962mm) 59" (1499mm) 18" (457mm) 86-3/4" (2203mm) Overalll height to the top of the fan guard is 43-1/8” (1095mm). Liebert® DS™ 18" (457mm) 124" (3150mm) 70" (1778mm) 1-1/2" (38mm) diameter hole for rigging (typ.4) 86-3/4" (2203mm) 70 164" (4166mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. Air-Cooled Systems Electrical Data—Fin/Tube Condensers Table 51 Fin/tube condenser data, 60Hz Model # 83, 104 165, 205 251, 308 415, 510 616 830, 1010 1 Fan 2 Fans 3 Fans 4 Fans 6 Fans 8 Fans Input Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD Fan Speed Controlled 208/230 460 6.0 15 — — — — — — — — — — — — — — — 2.5 3.1 15 — — — — — — — — — — — — — — — 575 1.9 2.4 15 — — — — — — — — — — — — — — — 208/230 — — — 8.3 9.5 15 11.8 13.0 15 15.3 16.5 20 23.6 24.8 30 30.6 31.8 40 — — — 4.2 4.8 15 5.9 6.5 15 7.6 8.2 15 11.8 12.4 15 15.2 15.8 20 — — — 3.3 3.8 15 4.7 5.2 15 6.1 6.6 15 9.4 9.9 15 12.2 12.7 15 3.7 4.6 15 7.2 8.1 15 10.7 11.6 15 14.2 15.1 20 N/A N/A N/A N/A N/A N/A 1.8 2.3 15 3.5 4.0 15 5.2 5.7 15 6.9 7.4 15 N/A N/A N/A N/A N/A N/A 460 1 4.8 3 575 VFD Controlled 208/230 460 3 Lee-Temp Controlled/Fan-Cycling 208/230 460 3 575 3.5 4.4 15 7.0 7.9 15 10.5 11.4 15 14.0 14.9 20 21.0 21.9 25 28.0 28.9 35 1.7 2.1 15 3.4 3.8 15 5.1 5.5 15 6.8 7.2 15 10.2 10.6 15 13.6 14.0 20 1.4 1.8 15 2.8 3.2 15 4.2 4.6 15 5.6 6.0 15 8.4 15 11.2 11.6 15 8.8 FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device Fin/tube condenser data, Liebert Quiet-Line™ (Liebert Lee-Temp™ controlled/fan-cycling), 60Hz Table 52 Model # ph 63 119, 127, 143 214 286 409 572 1 Fan 2 Fans 3 Fans 4 Fans 6 Fans 8 Fans Input Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD 208/230 460 575 3 1.8 2.3 15 3.6 4.1 15 5.4 5.9 15 7.2 7.7 15 10.8 11.3 15 14.4 14.9 20 0.9 1.1 15 1.8 2.0 15 2.7 2.9 15 3.6 3.8 15 5.4 5.6 15 7.2 7.4 15 0.7 0.9 15 1.4 1.6 15 2.1 2.3 15 2.8 3.0 15 4.2 4.4 15 5.6 5.8 15 FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device 71 Liebert® DS™ Air-Cooled Systems Electrical Field Connections—Liebert Fin/Tube Condensers Figure 60 Electrical field connections for Fan Speed Control fin/tube condensers Electric service connection terminals when factory disconnect is NOT supplied. Electric service connection and fuse block. Factory wired to 24V Class 2 control circuit. Electric service connection terminals when factory disconnect is supplied. Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box. Factory installed disconnect switch (optional). Electric service entrance. A 7/8" (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box. Factory-wired to components on electric panel. Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire. Earth ground connection (60Hz). Connection terminals for field supplied earth grounding wire when factory disconnect is NOT supplied. Earth ground connection (60Hz). Connection terminal for fieldsupplied earth grounding wire when factory disconnect is supplied. Electric service, not by Liebert. Single-phase for condenser models CSF, CDF with single fan motor. Three-phase for all other condenser models. DPN000666 Rev. 0 NOTE: Refer to specification sheet for full load amp and wire size amp ratings. Liebert® DS™ 72 Air-Cooled Systems Figure 61 Electrical field connections for VFD control fin/tube condensers Factory-wired to 24V control circuit. Control interlock (70, 71) Field-supplied Class 1 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box. Factory-installed fuse block on 60Hz units. Circuit breaker supplied in lieu of fuse block on 50Hz units. V F D SPD Factory-installed disconnect switch Alarm Connections Field-supplied 24V Class 1 wiring to remote alarm circuits Surge Protection Device (SPD) alarm contact connections (11, 12). Variable Frequency Drive (VFD) alarm contact connections (13, 14) Factory-wired to components on electric panel. Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire. Electric service connection terminals with factorysupplied disconnect Electric service entrance. A 7/8" (22.2mm) diameter hole in a 1-1/8 in (28.6mm) knockout provided in bottom of electric box. Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is supplied. Electric service, not by Emerson DPN001051 Rev. 1 NOTE: Refer to specification sheet for full load amp and wire size amp ratings. 73 Liebert® DS™ Air-Cooled Systems Figure 62 Electrical field connections for Liebert Lee-Temp control fin/tube condensers Lee-Temp receiver tank (1 per circuit). NOTE: Standard heater pads are 150 watts each. (Optional 300 watt heater pads are available.) Standard heater pad voltage is 230V. (120V heater pad voltage is optional.) Electrical connection box with cover. Electrical service connection. Pigtails in electric handy box are factory wired to LeeTemp heater pads for field connection of separate continuous electric source, wiring not by Emerson. Electric service connection and fuse block. Electric service connection terminals when factory disconnect is NOT supplied. Factory wired to 24V Class 2 control circuit. Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box. 70 71 Electric service connection terminals when factory disconnect is supplied. Factory-installed disconnect switch (optional). Factory-wired to components on electric panel. Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high-voltage component for field-supplied earth grounding wire. Electric service entrance. A 7/8 in (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box. Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory Earth ground connection (60Hz). disconnect is NOT supplied. Connection terminal for field-supplied Electric service. Three-phase for all models. Wiring not by Emerson. earth grounding wire when factory disconnect is supplied. DPN000683 Rev. 0 NOTE: Refer to specification sheet for full load amp and wire size amp ratings. Table 53 Liebert Lee-Temp receiver electrical data, fin/tube condensers Rated Voltage - Single Phase Watts/Receiver 120 150 300 200/208/230 450 150 300 450 Full Load Amps 1.4 2.8 4.2 0.7 1.4 2.1 Wire Size Amps 1.8 3.5 5.3 0.9 1.8 2.7 Maximum Overcurrent Protection Device, Amps 15 15 15 15 15 15 The Liebert Lee-Temp receiver requires a separate power feed for heaters. The condenser is not designed to supply power to the receiver. Liebert® DS™ 74 Air-Cooled Systems Piping—Fin/Tube Condensers Typical System Configurations—Fin/Tube Figure 64 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the outdoor condenser (VFD, Fan Speed Control or Liebert Lee-Temp) and field-supplied interconnection piping. Figure 63 Check Valve Piping schematic, air-cooled with semi-hermetic compressor with fin/tube condenser Relief ValveService Valve Liebert Lee-Temp Receiver Liquid Return Optional Sub-Cooling Coil Head Pressure Control Valve Optional Sub-Cooling Coil Inverted Trap on discharge and liquid lines to extend above base of coil by a minimum of 7-1/2" (190mm). CONDENSER COIL (FAN SPEED or VFD) CONDENSER COIL (Liebert Lee-Temp) Optional Field-Installed Fusible Plug Hot Gas Discharge LIEBERT LEE-TEMP For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided* LIQUID Service Valve Sensing Bulb Cylinder Unloader(s) EVAPORATOR COIL SUCTION Muffler COMPRESSOR Service External Valve Equalizer Check Valve **Muffler *Isolation Valve Hot Gas Discharge Expansion Solenoid Valve Valve Sight Glass Liquid Return Filter Drier NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. *Isolation Valve Trap at base of risers over 5ft. (1.5m)* * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance. Schematic representation shown. Do not use for specific connection locations. REFRIGERANT PIPING FIELD PIPING Service / Schrader (Access) Connection No Valve Core Service / Schrader (Access) Connection With Valve Core 75 ** Components supplied by Emerson and must be field-installed (70kW, 77 kW & 105kW models only) DPN000797 Rev. 6 Liebert® DS™ Air-Cooled Systems Figure 64 Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser Inverted Trap on discharge & liquid lines to extend above base of coil by a minimum of 7-1/2" (190mm). Service Valve LIQUID RETURN Head Pressure Control Valve Liebert Lee-Temp Receiver CONDENSER COIL (Liebert Lee-Temp) Optional field CONDENSER COIL (Fan Speed or VFD) Relief Valve Check Valve installed fusible plug Hot Gas Discharge FAN SPEED/VFD (Liebert Lee-Temp or VFD condenser is required with digital scroll) 28-42kW Digital Solenoid Valve 53-70kW Digital Solenoid Valve LIEBERT LEE-TEMP (Liebert Lee-Temp or VFD condenser is required with digital scroll) LIQUID EVAPORATOR COIL Sensing Bulb SUCTION * For rises over 25ft. (7.6m) trap every 20ft. (6m) or evenly divided Service Valve Check Service External Valve Compressor Valve Equalizer *Isolation Valve HOT GAS DISCHARGE Expansion Valve Solenoid Valve Sight Glass Filter Drier *Isolation Valve Trap at base of risers over * Components are not supplied 5ft. (1.5m) by Emerson but are recommended for proper circuit operation and maintenance. LIQUID RETURN Refrigerant Piping Field Piping Service/Schrader (Access) Connection; No Valve Core Service/Schrader (Access) Connection With Valve Core NOTES: Schematic representation shown. Do not use for specific connection locations. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. Liebert® DS™ 76 DPN000798 Rev. 5 Air-Cooled Systems Figure 65 VFD and Fan Speed Control condenser piping—Fin/tube condensers Optional fusible plug service kit to be brazed into the liquid line(s) in either the vertical or horizontal position (where required). (Vertical position is preferable, horizontal position is optional.) For two-circuit systems, one fusible plug kit must to be installed in each circuit. Entering Hot Gas Line Leaving Liquid Line Inverted Traps (field-supplied) to extend a minimum of 7-1/2" (190mm) above coil base Metal Clamp Vertical Horizontal See Detail A-A Isolator Detail A-A Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately to avoid coil damage and loss of charge. Figure 66 DPN001065 Rev. 1 Liebert Lee-Temp head pressure control condenser piping—Fin/tube condensers Inverted Traps (field-supplied) to extend 8" (203mm) above coil base Entering Hot Gas Line Hot Gas Line Liquid Line Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately to avoid coil damage and loss of charge. Metal Clamp Leaving Liquid Line See Detail A-A Position elbow to direct relief valve downward DPN000669 Rev. 2 Isolator Detail A-A 77 Liebert® DS™ Air-Cooled Systems 3.12.2 Piggyback Condensers Piggyback Selections Table 54 Liebert DS piggyback condenser selection Air-Cooled Condenser Selection Condenser Type Ambient Temp. °F (°C) 028 035 042 053 070 077 105 95 (35) PB-925 PB-925 PB-1100 PB-1350 N/A N/A N/A 100 (38) PB-1100 PB-1100 PB-1350 N/A N/A N/A N/A 105 (41) PB-1100 PB-1350 N/A N/A N/A N/A N/A Piggyback Table 55 Liebert DS Size Piggyback condenser airflow and static pressure data HP/RPM Ext. Static Pressure - in. (Pa) Model No. of Fans CFM / m / hr 0.25 (62.3) 0.50 (125) 0.75 (187) 1.0 (249) PB-350A 2 7600/12,920 2/580 3/650 3/720 3/790 PB-550A 2 6600/11,200 2/575 3/650 3/725 3/800 PB-675A 2 6900/11,730 2/605 3/680 3/750 3/820 PB-925A 2 12,500/21,250 7.5/760 7.5/810 7.5/870 7.5/920 PB-1100A 2 12,300/20,910 7.5/780 7.5/830 7.5/890 7.5/940 PB-1350A 2 16,500/28,050 10/640 10/695 10/740 15/790 3 Values are without filter box. External Static Pressure = filter pressure drop + other static drops. Source: DPN000695, Rev. 0 Liebert® DS™ 78 Air-Cooled Systems Dimensions—Indoor Piggyback Condensers Figure 67 Piggyback condenser planning dimensions E H K J R 1-1/8" (29mm) K sions Dimen Overall Overa ll Dim ensio ns Optional Fan Discharge Disconnect Switch (optional) S H J 35-1/8" (892mm) D B 72" (1829mm) R Fan Discharge Shaded areas indicate a recommended clearance of 34" (864mm) for component access. 5" (127mm) 1" (25.4mm) G Condenser Coil Inlet And Duct Connection C UNIT DIMENSIONAL DATA F Floor Level A NOTE: A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening. FLOOR CUTOUT DIMENSIONS Table 56 Model PB-350A PB-550A PB-675A PB-925A PB-1100A PB-1350A C Unit Base 10" (254mm) Drain Outlet Opening A Unit Base DPN000695 Rev. 0 Piggyback condenser dimensions, in. (mm) A B C D E F G H J K R S 72 (1829) 72 (1829) 72 (1829) 97 (2464) 97 (2464) 97 (2464) 74 (1880) 74 (1880) 74 (1880) 99 (2515) 99 (2515) 99 (2515) 31 (787) 31 (787) 31 (787) 33 (838) 33 (838) 33 (838) 32 (813) 32 (813) 32 (813) 34 (864) 34 (864) 34 (864) 1-1/8 (29) 1-1/8 (29) 1-1/8 (29) 3-1/8 (79) 3-1/8 (79) 3-1/8 (79) 33 (838) 33 (838) 33 (838) 45-1/2 (1156) 45-1/2 (1156) 45-1/2 (1156) 60 (1524) 60 (1564) 60 (1564) 85 (2159) 85 (2159) 85 (2159) 8-5/8 (219) 8-5/8 (219) 8-5/8 (219) 23-5/16 (592) 23-5/16 (592) 16-5/16 (421) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 63-7/8 (1622) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 19-1/8 (486) 13-3/16 (335) 13-3/16 (335) 13-3/16 (335) 23-1/2 (597) 23-1/2 (597) 16-13/16 (427) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 11-5/8 (295) Source: DPN000695, Rev. 0 Table 57 Piggyback condenser physical data, 60Hz Model Number of Circuits PB-350 PB-550 PB-675 PB-925 PB-1100 PB-1350 2 2 2 2 2 2 Connection Size, OD, In. Hot Gas Liquid Condenser Charge Per Circuit R-407C, lb (kg) 5/8 5/8 7/8 7/8 1-1/8 1-1/8 1/2 1/2 1/2 1/2 5/8 5/8 18 8.2) 17 (7.8) 25 (11.2) 22 (9.9) 34 (15.5) 34 (15.5) 79 Liebert® DS™ Air-Cooled Systems Electrical Data—Piggyback Condensers Table 58 Piggyback condenser electrical data, 60 Hz, 3 phase 208 230 460 1 575 hp FLA LRA FLA LRA FLA LRA FLA LRA 2.0 7.5 51.0 6.8 44.0 3.4 22.0 2.7 17.6 3.0 10.6 73.6 9.6 64.0 4.8 32.0 3.9 25.6 5.0 16.7 106.0 15.2 88.0 7.6 44.0 6.1 35.2 7.5 25.3 129.4 22.0 111.4 11.0 55.7 9.0 44.8 10.0 30.8 186.0 28.0 162.0 14.0 84.0 11.0 66.0 15.0 46.2 267.0 42.0 225.0 21.0 116.0 17.0 93.0 1. See Table 59 for separate power feed needed for Lee-Temp receiver heaters. 2. FLA: Full Load Amps; LRA: Lock Rotor Amps 3. Source: DPN000695, Rev. 0 Electrical Field Connections—Liebert Piggyback Condensers Figure 68 Electrical field connections for Liebert piggyback condensers Factory-installed unit disconnect switch (optional) Field-supplied disconnect switch when factory-installed unit disconnect switch is not provided. Three phase electric service not by Emerson Three-phase connection. Electric service connection terminals when factory disconnect switch is supplied Three-phase connection. Electric service connection terminals when factory disconnect switch is not supplied Factory-installed disconnect switch (optional) Electric conduit knockouts on bottom of wire raceway Knockout sizes 1-3/8" (34.9mm) or 1-3/4" (44.5mm) or 2 1/2" (63.5mm) Three-phase electric service not by Emerson Factory-wired to components on electric panel. Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire. 71 70 91 Liebert Lee-Temp electric service connection to terminals supplied from factory-wired Liebert Lee-Temp heater pads for field connection of separate continuous electrical source, not supplied by Emerson. 90 Factory-wired to components on electric panel Control interlock Field-supplied, Class 2 wiring to Terminals 70 & 71 to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter knockout provided in bottom of box Refer to specification sheet for full load amp and wire size amp ratings. Liebert® DS™ 80 DPN000697 Rev. 0 Air-Cooled Systems Table 59 Separate electrical supply requirements for Liebert Lee-Temp™ receivers, 60Hz, 1 Ph Voltage 120 120 208/230 208/230 Watts/Receiver 150 300 150 300 FLA 2.5 5.0 1.4 2.8 WSA 3.1 6.2 1.8 3.6 OPD 15 15 15 15 Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91. Figure 69 Electrical field connections for Liebert piggyback condensers Factory-installed unit disconnect switch (optional) Field-supplied disconnect switch when factory-installed unit disconnect switch is not provided. Three phase electric service not by Emerson Three-phase connection. Electric service connection terminals when factory disconnect switch is supplied Three-phase connection. Electric service connection terminals when factory disconnect switch is not supplied Factory-installed disconnect switch (optional) Electric conduit knockouts on bottom of wire raceway Knockout sizes 1-3/8" (34.9mm) or 1-3/4" (44.5mm) or 2 1/2" (63.5mm) Three-phase electric service not by Emerson Factory-wired to components on electric panel. 70 Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire. 71 91 Liebert Lee-Temp electric service connection to terminals supplied from factory-wired Liebert Lee-Temp heater pads for field connection of separate continuous electrical source, not supplied by Emerson. 90 Factory-wired to components on electric panel Control interlock Field-supplied, Class 2 wiring to Terminals 70 & 71 to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter knockout provided in bottom of box Refer to specification sheet for full load amp and wire size amp ratings. 81 DPN000697 Rev. 0 Liebert® DS™ Air-Cooled Systems Figure 70 Piggyback condenser piping and electrical connection locations See Note 2 See Note 1 See Note 2 See Note 1 A B C 1-13/16" (46mm) G 1-13/16" (46mm) C " E See Note 3 E D F D See Note 2 3" (76mm) 3" (76mm) 1" (25mm) Panel 1" (25mm) Panel 3" (76mm) 3" (76mm) See Note 2 See Note 2 3" (76mm) See Note 1 3" (76mm) E See Note 3 See Note 1 E See Note 3 12-5/8" (321mm) 9-11/16" (246mm) 12-5/8" (321mm) 4-1/2" (114mm) 4-1/2" (114mm) 9-11/16" (246mm) 7-7/8" (200mm) 7-7/8" (200mm) MODELS PB-350A THRU PB-1100A MODEL PB-1350A 5-1/2" (140mm) See Note 1 3-1/4" (85mm) See Note 2 Drain Outlet Location 1-1/4" (32mm) F.P.T. 3" (76mm) 8" (203mm) 6" (152mm) 3" (76mm) See Note 3 1-1/2" (38mm) ALL MODELS 1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical). 2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical). 3. Cover plate for access of liquid line and hot gas line. Table 60 DPN00696 Rev. 1 Dimensions—Piggyback condensers, in. (mm) Model C D E F G PB-350A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730) PB-550A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730) PB-675A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730) PB-925A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730) PB-1100A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730) PB-1350A 11-1/4 (286) 24 (610) 26-1/2 (673) 7 (178) 6 (152) — — Table 61 A B Piping connection sizes, ODS, in. (mm) Model Liquid Line Hot Gas Line Drain PB-350A 2 @ 1/2 (13) 2 @ 5/8 (16) 1-1/4 (32) PB-550A 2 @ 1/2 (13) 2 @ 5/8 (16) 1-1/4 (32) PB-675A 2 @ 1/2 (13) 2 @ 7/8 (22) 1-1/4 (32) PB-925A 2 @ 1/2 (13) 2 @ 7/8 (22) 1-1/4 (32) PB-1100A 2 @ 5/8 (16) 2 @ 1-1/8 (29) 1-1/4 (32) PB-1350A 2 @ 5/8 (16) 2 @ 1-1/8 (29) 1-1/4 (32) Liebert® DS™ 82 Air-Cooled Systems Figure 71 ™ Piping schematic—Liebert DS with piggyback condenser and Liebert Lee-Temp Condenser Coil Liquid Return from Condenser Coil Head Pressure Control with Integral Check Valve Rotalock Valve Check Valve Pressure Relief Valve Liebert Lee-Temp Receiver * Traps every 25 ft. (7.6m) of Rise Sight Glasses Evaporator Coil Service Valve Expansion Valve Solenoid Valve Sensing Bulb Sight Glass External Equalizer Filter Dryer * Shutoff Valve Service Valves Liquid Return to Unit Double discharge risers are required wWhen unit is operating below 30% of full capacity. Consult factory for proper selection. Muffler Cylinder Unloaders (Optional) * * Muffler Compressor Hot Gas Discharge * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance FACTORY PIPING ** Components supplied by Emerson and must be field-installed. OPTIONAL PIPING FIELD PIPING SINGLE CIRCUIT SHOWN DPN000692 Rev. 0 83 Liebert® DS™ Air-Cooled Systems 3.13 ANCILLARY ITEMS—AIR-COOLED SYSTEMS Figure 72 Floor stand dimensions—28-42kW (8-12 ton), downflow A+1-1/2" (38mm) (with feet) A 47-15/16" (1218mm) B 4-1/2" (114mm) 33" (838mm) 16-3/4" (425mm) 34-1/2" (876mm) (with feet) Supply air discharge opening Supply air discharge opening 1" (25mm) TYP. Gussets supplied on floor stands 12" (305 mm) tall and greater Optional turning vane shown as front air discharge. Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. 7/8" (23mm) Table 62 3" (76mm) Floor stand and floor planning dimensions—28-42kW (8-12 ton), downflow Dimensional Data, in. (mm) Height, in. (mm) Model A B Air-Cooled Semi-Hermetic Models and All Water/Glycol/GLYCOOL Models 85 (2159) 26 (660) Air-Cooled Scroll Models and Air-Cooled Digital Scroll Models 72 (1829) 13 (330) Source: DPN000820, Rev. 3 Liebert® DS™ 84 C* D turning vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) DPN000820 Rev. 3 Air-Cooled Systems Figure 73 Floor stand dimensions—53-77kW (15-22 ton), downflow A+1-1/2" (38mm) (with feet) A 69-3/4" (1772mm) B 34-1/2" (876mm) (with feet) 16-3/4" (425mm) Supply air discharge opening 33" (838mm) 1" (25mm) TYP. Gussets supplied on floor stands 12" (305 mm) tall and greater Supply air discharge opening 7/8" (23mm) Optional turning vane shown as front air discharge. 3" (76mm) Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. NOTE: Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. Table 63 DPN000930 Rev. 2 Floor stand and floor planning dimensions—53-77kW (15-22 ton), downflow Dimensional Data, in. (mm) Height, in. (mm) Model A B Air-Cooled Semi-Hermetic Models and All Water/Glycol/GLYCOOL Models 108 (2743) 26 (660) Air-Cooled Scroll Models and Air-Cooled Digital Scroll Models 97 (2464) 15 (381) C* D - Turning Vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) Source: DPN000930, Rev. 2 85 Liebert® DS™ Air-Cooled Systems Figure 74 Floor stand and floor planning dimension, downflow 53-77kW (15-22 tons) models with EC fans A B Piping Access Area 3/4" (19mm) 32" (813mm) Center Feet 31-1/2" (800mm) 32-3/4" (832mm) C Support Feet Centers 3/4" (19mm) D 3/4" (19mm) 7/8" (23mm) See Note 4 3" (76mm) 33" (838mm) 1" (25mm) E 1. This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert DS floor stand can be used if the fans are to remain in their original raised position. 2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). 3) The floor stand used with EC units is not symmetrical and its orientation to the Liebert DSE is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4. Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed. F* 35" (889mm) Overall Depth DPN002151 Rev. 1 * Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height C. Table 64 Floor stand and floor planning dimensions—53-77kW (15-22 ton), downflow with EC fans Dimensional Data in (mm) A B C D E F DS053-077, Air-Cooled Semi-Hermetic and all Water/Glycol/ GLYCOOL Models 108 (2743) 26 (660) 106.5 (2705) 108 (2743) 109.5 (2781) 24 (610) DS053-077, Air-Cooled Scroll and Air-Cooled Digital Scroll Models 97 (2464) 15 (381) 5.5 (2426) 97 (2464) 98.5 (2502) 30 (762) Liebert DS Model 36 (914) Source: DPN002151, Rev. 1 42 (1067) 48 (1219) Liebert® DS™ 86 Air-Cooled Systems Figure 75 Floor stand and floor planning dimensions—downflow 105kW (30 ton) models with EC fans, standard scroll and semi-hermetic compressors without turning vane Digital scroll compressors not available on 105 models. 132-1/2" (3366mm) (with feet) 131" (3327mm) 25" (635mm) 34-1/2" (876mm) 33" (with feet) (838mm) 74" (1880mm) 1" (25mm Typ.) Gussets supplied on floor stands 12" (305mm) tall and greater. 3" (76mm) NOTE: 1) This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert DS A* floor stand can be used if the fans are to remain in their original raised position. 35" 2) Right side of paneled unit is flush with right side of floor stand. (889mm) All other paneled sides overhang floor stand 1" (25mm). Overall 3) The floor stand used with EC units is not symmetrical and Depth its orientation to the Liebert DS is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed. *Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “A”. See Note 4 Height - A in. (mm) 24 (610) 30 (762) 36 (914) 42 (1067) 48 (1219) DPN002152 Rev. 1 87 Liebert® DS™ Air-Cooled Systems Figure 76 Floor stand dimensions—105kW (30 ton), downflow with turning vane and centrifugal fans 132-1/2" (3366mm) (with feet) 131" (3327mm) 91-3/4" (2330mm) 26" (660mm) 4-1/2" (114mm) 34-1/2" (876mm) (with feet) 33" (838mm) 16-3/4" (425mm) 1" (25mm) TYP. Supply air discharge opening Supply air discharge opening Gussets supplied on floor stands 12" (305 mm) tall and greater 7/8" (23mm) Optional turning vane shown as front air discharge. 3" (76mm) Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. C* D NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. Table 65 Floor stand and floor planning dimensions—105kW (30 ton), downflow Height, in. (mm) C* D Turning Vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) Source: DPN001059, Rev. 2 Liebert® DS™ 88 DPN001059 Rev. 2 Air-Cooled Systems Figure 77 Plenum dimensions—28-105kW (8-30 ton), upflow FRONT VIEWS REAR VIEWS WITH GRILLE WITH GRILLE Panel removable for condenser clean out access (Water/Glycol/GLYCOOL models only) WITHOUT GRILLE 34" (864mm) LEFT SIDE VIEWS CHECK ONE (1): B WITHOUT GRILLE A 1" (25mm) H RIGHT SIDE VIEWS CHECK ONE (1): WITH GRILLE 76" (1930mm) WITHOUT GRILLE SIDE VIEW - UNIT WITH PLENUM FRONT VIEW - UNIT WITH PLENUM Notes: 1. Typical 53-77kW (15-22 Tons) unit orientation shown with grille Plenum. View varies by unit size and Plenum selection. 2. All Plenums are shipped flat and must be field assembled. 3. Optional grille Plenum kits must include front or rear grille. 4. Non-grille Plenums are open on the top and not designed with duct flange. Table 66 WITH GRILLE WITHOUT GRILLE DPN001187 Rev. 1 Plenum dimensions, in. (mm)—28-105kW (8-30 ton), upflow Dimensions, in. (mm) Grille Size, in (mm) - Nominal Model A B 28-42kW (8-12 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 28-42kW (8-12 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 53-77kW (15-22 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 53-77kW (15-22 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 59-1/4 (1505) 59-1/4 (1505) 82-1/4 (2089) 82-1/4 (2089) 13-3/4 (349) 26-3/4 (679) 15-3/4 (400) 26-3/4 (679) 105kW (30 ton)—All Models 105-1/4 26-3/4 (2673) (679) Front/Rear Grilles 18 x 55 (457 x 1397) 18 x 55 (457 x 1397) 18 x 78 (457 x 1981) 18 x 78 (457 x 1981) (1) 18 x 20 (457 x 508) (1) 18 x 78 (457 x 1981) Side Grille 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) Height, in. (mm) H 20 (508) 24 (610) 30 (762) 36 (914) 18 x 20 (457 x 508) Source: DPN001187, Rev. 1 89 Liebert® DS™ Air-Cooled Systems Figure 78 Floor stand dimensions, piggyback condensers with centrifugal fans C B A 1" (25.4mm) * H ± 1-1/2" (38mm) For height selection refer to chart. See Table 68 for height selection Leg Support Center Leg Provided on 99" Cabinets on Models 18, 21 & 24" High Table 67 Floor stand dimensions, in. (mm) A B C PB-350A, PB-550A PB-675A 72 (1829) 36 (914) 31 (787) PB-925A, PB-1100A PB-1350A 97 (2464) 48-1/2 (1232) 33 (838) Model Source: DPN000727, Rev. 0 Table 68 Nominal Floor stand height selection, in. (mm) Range (Nominal ±1-1/2 *) 9 (229) 7-1/2 to 10-1/2 (191 to 267) 12 (305) 10-1/2 to 13-1/2 (267 to 343) 15 (381) 13-1/2 to 16-1/2 (343 to 419) 18 (458) 16-1/2 to 19-1/2 (419 to 495) 21 (553) 19-1/2 to 22-1/2 (495 to 572) 24 (610) 22-1/2 to 25-1/2 (572 to 648) Leveling feet are provided with ±1-1/2" (38mm) Adjustment from nominal height "H". Source: DPN000727, Rev. 0 Liebert® DS™ 90 DPN000727 Rev. 0 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.0 WATER-COOLED, GLYCOL-COOLED AND GLYCOOL SYSTEMS 4.1 CAPACITY AND PHYSICAL DATA Table 69 Performance data—Water-cooled, EC fans Model Size 28 35 42 053 070 077 105 CAPACITY DATA WITH EC FANS Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Semi Hermetic Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 42.1 (143.8) Sensible kW (kBTUH) 39.6 (135) 38.7 (132) 50.1 (171) 65.1 (220) 78.6 (268.3) 87.1 (297.1) 112.1 (382.3) 31.7 (108.2) 48.9 (166.9) 63.4 (212.9) 75.7 (258.2) 83.6 (285.4) 103.9 (354.6) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 40.5 (138.1) Sensible kW (kBTUH) 35.9 (122.4) 39.7 (135.4) 47.9 (163.4) 62.2 (212.1) 75.3 (256.9) 83.4 (284.7) 107.8 (367.7) 34.4 (117.3) 44.4 (151.4) 58 (197.7) 68.9 (235) 76 (259.5) 94.3 (321.9) 41.4 (141.4) 45.9 (156.7) 59.4 (202.6) 72 (245.8) 80 (273) 103.4 (352.9) 38.7 (131.9) 39.5 (134.7) 51.7 (176.4) 61.2 (209) 67.6 (230.8) 83.7 (285.7) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 38.9 (132.7) Sensible kW (kBTUH) 32 (109.3) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 38 (129.6) Sensible kW (kBTUH) 29.7 (101.4) 43.5 (43.5) 44.8 (152.9) 57.8 (197.2) 70.2 (239.6) 42.6 (42.6) 36.4 (124.3) 47.7 (162.8) 56.5 (192.9) 62.4 (212.8) 78 (266.2) 101 (344.6) 77.5 (264.3) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 35.2 (120) Sensible kW (kBTUH) 35.1 (119.9) 42 (143.3) 41.6 (142.1) 47.5 (162.1) 66.3 (224.1) 80.8 (275.6) 88.5 (301.9) 111.3 (379.9) 47.2 (161) 64.3 (215.6) 77 (262.6) 84.5 (288.3) 103.6 (353.4) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 34 (116.1) 40.1 (136.7) 45.4 (154.8) 63.3 (216.1) 77.5 (264.6) Sensible kW (kBTUH) 32.5 (111) 37.9 (129.4) 43.1 (147) 58.6 (200.1) 70 (238.9) 85 (290.2) 107.2 (365.9) 76.9 (262.3) 94.1 (321.1) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 32.8 (111.8) Sensible kW (kBTUH) 29.1 (99.2) 38.4 (131) 43.5 (148.4) 60.5 (206.5) 74.3 (253.5) 81.8 (279.1) 103.2 (352.2) 33.8 (115.2) 38.4 (130.9) 52.2 (178.3) 62.3 (212.7) 68.5 (233.6) 83.8 (285.9) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) Sensible kW (kBTUH) 32 (109.2) 37.5 (127.9) 42.5 (145) 58.9 (201.1) 72.5 (247.5) 79.9 (272.6) 100.9 (344.2) 26.8 (91.6) 31.2 (106.3) 35.4 (120.7) 48.3 (164.7) 57.7 (196.7) 63.2 (215.6) 77.5 (264.4) FAN SECTION - Downflow Models - EC Fans Under Floor Standard Air Volume, CFM (CMH) 4,400 (7,476) 5,200 (8,835) 0.2" external static 6200 (10534) 8,000 (13,592) 9,600 (16,310) 11,000 (18,689) 13700 (23276) Standard Fan Motor, Nominal kW (total for all fans) 2.8 2.8 2.8 2.5 4.0 5.9 7.8 Number of Fans 1 1 1 2 2 2 3 1. Canister humidifier not available with EC fans. 2. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. 3. 4. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only 91 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 70 Performance data—Water-cooled units with centrifugal fans Model Size 28 35 42 053 070 077 105 CAPACITY DATA WITH CENTRIFUGAL FANS Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Semi-Hermetic Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 41.5 (141.6) 42.4 (144.7) 48.4 (165.2) 62.1 (211.9) 76.9 (262.5) 85.0 (289.9) 110.3 (376.4) Sensible kW (kBTUH) 38.9 (132.8) 41.6 (141.9) 47.4 (161.7) 57 (194.6) 72.8 (248.4) 80.4 (274.4) 102.2 (348.7) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 39.8 (135.9) 40.4 (137.9) 46.1 (157.4) 59.7 (205.2) 73.7 (251.6) 81.5 (278.1) 106 (361.8) Sensible kW (kBTUH) 35.2 (120.2) 37.6 (128.3) 42.8 (146.1) 51.9 (180.6) 66.1 (225.5) 72.9 (248.8) 92.6 (315.9) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 38.3 (130.5) 38.6 (131.9) 44.2 (150.7) 57.2 (196.9) 70.6 (240.8) 78.2 (266.7) 101.7 (346.9) Sensible kW (kBTUH) 31.4 (107.1) 33.3 (113.8) 37.9 (129.3) 46.4 (162.1) 58.7 (200.3) 64.7 (220.8) 82 (279.8) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 37.3 (127.4) Sensible kW (kBTUH) 29.1 (99.2) 37.7 (128.5) 43.1 (146.9) 55.8 (191.9) 68.8 (234.7) 76.2 (260.1) 99.2 (338.6) 30.7 (104.7) 34.8 (118.8) 43 (150.6) 54.2 (184.9) 59.6 (203.5) 75.7 (258.4) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 34.5 (117.8) 40.9 (139.7) 45.8 (156.3) 64.9 (219.6) 79.0 (269.6) 86.5 (295.1) 109.6 (374) Sensible kW (kBTUH) 34.5 (117.7) 40.6 (138.5) 45.6 (155.5) 62.0 (207.9) 74.0 (252.5) 81.3 (277.3) 101.8 (347.5) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 33.4 (113.9) 39.0 (133.2) 43.6 (148.8) 62.2 (212.1) 75.9 (259.1) 83.1 (283.6) 105.5 (360) Sensible kW (kBTUH) 31.9 (108.8) 36.9 (125.8) 41.5 (141.6) 56.4 (192.6) 67.2 (229.3) 73.7 (251.5) 92.4 (315.2) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 32.1 (109.6) Sensible kW (kBTUH) 28.4 (97) 37.4 (127.5) 41.7 (142.3) 59.5 (202.9) 72.8 (248.5) 80 (272.9) 101.5 (346.3) 32.7 (111.7) 36.8 (125.5) 50.3 (171.5) 59.8 (203.9) 65.5 (223.7) 82.1 (280) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 31.4 (107) 36.5 (124.4) 40.7 (138.9) 57.9 (197.5) 71.1 (242.6) 78.1 (266.5) 99.1 (338.3) Sensible kW (kBTUH) 26.2 (89.4) 30.1 (102.8) 33.8 (115.2) 46.4 (158.4) 55.3 (188.6) 60.5 (206.4) 75.8 (258.5) FAN SECTION - Downflow Models - Fixed Pitch, Two Belts Standard Air Volume, CFM (CMH) 4,400 (7,476) 5,200 (8,835) 6200 (10534) 7,500 (12,743) 9,000 (15,291) 10,400 (17,670) 13,700 (23,276) 0.2" external static Standard Fan Motor, hp (kW) Number of Fans 2 (1.5) 3 (2.2) 5.0 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10.0 (7.5) 1 1 1 2 2 2 3 1. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. 3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only Liebert® DS™ 92 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 71 Physical data—Water-cooled units Model Size 028 035 042 053 070 077 105 EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin Face Area, sq. ft. (sq. m) Rows of Coil 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 3 3 3 3 3 3 3 REHEAT SECTION Electric Reheat - Three-stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat Capacity, kW (kBTUH), Standard Selection 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) Capacity, kW (kBTUH), Optional Selection 10.0 (34.1) 10.0 (34.1) 10.0 (34.1) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection) Capacity, kW (kBTUH) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) HUMIDIFIER SECTION Infrared Humidifier Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (filter types cannot be mixed, must be all MERV 8 or all MERV 11) Downflow Models Quantity 3 3 3 4 4 4 4 Nominal Size, inches 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 Upflow Models (Front & Rear return) Filters located in separate filter box on rear return, located on lower unit panel Quantity 4 4 4 6 6 6 8 WATER COOLED SYSTEM - SEMI-HERMETIC Compressors, based on 75°F/45% room conditions with EC Fans Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option THR, kBTUH (kW) 49.2 (167.7) 50.5 (172.3) 59.9 (204.3) 74.7 (255) 92.7 (316.5) 105.6 (360.4) 83°F (23.8°C) EWT, GPM (l/m) 28 (105.90) 29 (109.7) 34 (128.7) 43 (162.7) 53 (200.6) 60 (227.1) 139.3 (475.5) 79 (299.0) Pressure Drop, ft. of water (kPa), with valve 8.9 (26.70) 9.5 (28.4) 12.8 (38.3) 11.2 (33.5) 16.6 (49.6) 20.9 (62.5) 31.3 (93.6) STANDARD SCROLL Compressors Only WATER COOLED SYSTEM - DIGITAL SCROLL Compressors, based on 75°F/45% room conditions Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC Fans THR, BTUH (kW) 83°F (23.8°C) EWT, GPM (l/m) Pressure Drop, ft. of water (kPa), valve 41.6 (141.8) 49.8 (169.8) 57 (194.5) 75.8 (258.5) 95.3 (325.3) 107.2 (365.6) 134.7 (459.6) 24 (90.85) 28.5 (107.9) 32.5 (123) 44 (166) 55.5 (210.1) 62.5 (236.6) 78 (295.3) 6.6 (19.73) 9.2 (27.50) 11.8 (35.27) 11.7 (34.97) 18.1 (54.10) 22.6 (67.55) 30.6 (91.40) PIPING CONNECTION SIZES -Water-Cooled Liebert DS Indoor Unit Water Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Water Return, O.D. Copper 1-5/8 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Condensate Drain w/Optional Condensate Pump, OD 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 82.1 (280.1) DUAL-COOL UNITS CAPACITY DATA, Water (0% Glycol), Net Capacity Data kW (kBTUH) CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower. 75°F DB, 62.57 WB (23.9°C DB, 16.9°C WB) 45% RH, 45°F EWT, 55°F LWT; with EC Fans 26.2 (89.2) 29.8 (101.6) 32.2 (109.8) 49.9 (170.4) 58 (198.1) 57.7 (196.8) Sensible Capacity, kW (kBTUH) Total Capacity, kW (kBTUH) 24.9 (85) 28.8 (98.2) 31.6 (107.8) 46 (157.1) 53.2 (181.4) 54.3 (185.4) 4 (63.7) Flow Rate, GPM (I/m) @ 10°F Rise 19 (1.2) 22.4 (1.4) 25.5 (1.6) 36.4 (2.3) 389 (1.9) 446 (2.2) 137.76 (2.2) Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81) 15.9 (47.6) 18 (53.80) Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0) Unit Volume, Without Econ-O-Coil, gal, (l) 4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) 10.50 (31.39) 10.40 (31.09) 17.2 (51.41) FLUID VOLUMES 93 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 72 Performance data—Glycol-cooled units with EC fans Model Size 028 035 042 053 070 077 105 CAPACITY DATA with EC Fans Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 36.7 (125.3) 38.2 (130.4) 43.9 (149.9) 57.1 (194.8) 70 (238.9) 77.9 (265.7) 101.5 (346.3) Sensible kW (kBTUH) 36.4 (124.4) 38.2 (130.4) 43.9 (149.9) 56.7 (193.5) 69.7 (237.7) 77.3 (263.8) 97.7 (333.4) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 34.9 (119.1) 35.8 (122.3) 41.3 (141) 54.2 (185.1) 66.5 (226.8) 74.1 (252.9) 97.1 (331.4) Sensible kW (kBTUH) 33.1 (112.9) 35.4 (120.9) 40.7 (138.8) 52.1 (177.6) 63.9 (218.1) 71.0 (242.2) 89.1 (304) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 33.3 (113.6) 33.9 (115.8) 39.2 (133.8) 51.6 (176) 63.3 (215.9) 70.8 (241.5) 92.9 (317.1) Sensible kW (kBTUH) 29.4 (100.3) 31.5 (107.6) 36.2 (123.6) 46.4 (158.4) 57.0 (194.5) 63.2 (215.7) 79.0 (269.6) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 32.4 (110.6) Sensible kW (kBTUH) 27.1 (92.4) 32.9 (112.3) 38.1 (130) 50.0 (170.6) 61.4 (209.7) 68.9 (235.2) 90.6 (309) 29.0 (98.9) 33.3 (113.6) 42.7 (145.5) 52.4 (178.8) 58.2 (198.5) 72.7 (248.1) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 31.9 (108.7) 37.5 (128) 42.5 (145.2) 59.7 (203.6) 71.6 (244.5) 79.9 (272.6) 101.0 (344.6) Sensible kW (kBTUH) 31.9 (108.7) 37.5 (128) 42.5 (145.2) 59.5 (203) 71.0 (242.2) 78.9 (269.2) 97.4 (332.3) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 30.2 (103) Sensible kW (kBTUH) 30.1 (102.6) 35.3 (120.6) 40.1 (136.8) 56.7 (193.4) 68.3 (233.1) 76.3 (260.5) 96.9 (330.7) 35.1 (119.6) 39.8 (135.9) 54.8 (187) 65.1 (221.1) 72.3 (246.6) 89.0 (303.6) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) Sensible kW (kBTUH) 28.6 (97.6) 33.6 (114.7) 38.2 (130.2) 54.0 (184.1) 65.4 (223.2) 73.2 (249.8) 93.1 (317.6) 27.0 (92) 31.4 (107.1) 35.7 (121.8) 49.0 (167.2) 58.1 (198.4) 64.4 (219.7) 79.1 (270) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 27.7 (94.5) Sensible kW (kBTUH) 24.8 (84.5) 32.7 (111.6) 37.1 (126.8) 52.4 (178.7) 63.8 (217.6) 71.4 (243.8) 90.9 (310.1) 28.9 (98.6) 32.8 (112.1) 45.1 (153.9) 53.6 (182.8) 59.3 (202.3) 72.9 (248.8) FAN SECTION - Downflow Models - EC Fans Under Floor Standard Air Volume, CFM (CMH) 0.2" 4,400 (7,476) 5,200 (8,835) 6200 (10534) 8,000 (13,592) 9,600 (16,310) 11,000 (18,689) 13.700 (23,276) external static Standard Fan Motor, nominal kW (total for all fans) 2.8 2.8 2.8 2.5 4.0 5.9 7.8 Number of fans 1 1 1 2 2 2 3 1. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. 3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only Liebert® DS™ 94 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 73 Performance Data—Glycol-cooled units with centrifugal fans Model Size 028 035 042 053 070 077 105 CAPACITY DATA WITH CENTRIFUGAL FANS Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors Semi-Hermetic Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 36.1 (123.1) 37.2 (126.8) 42.3 (144.4) 57.1 (194.8) 68.3 (233.2) 75.9 (258.8) 99.8 (340.4) Sensible kW (kBTUH) 35.8 (122.2) 37.2 (126.8) 42.3 (144.4) 56.7 (193.5) 67.4 (229.9) 74.7 (254.9) 96.0 (327.4) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 34.2 (116.9) 34.8 (118.8) 39.6 (135.3) 54.2 (185.1) 65 (221.8) 72.3 (246.6) Sensible kW (kBTUH) 32.4 (110.7) 34.4 (117.3) 39.1 (133.4) 52.1 (177.6) 61.5 (209.7) 68.1 (232.5) 95.4 (325.5) 87.3 (298) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 32.7 (111.4) 32.9 (112.3) Sensible kW (kBTUH) 28.7 (98.1) 69.1 (235.6) 91.2 (311.2) 30.5 (104.1) 34.7 (118.3) 46.4 (158.4) 54.6 (186.4) 60.4 (206.2) 37.5 (128) 51.6 (176) 62 (211.5) 77.3 (263.7) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 31.8 (108.4) 31.9 (108.8) 36.4 (124.2) Sensible kW (kBTUH) 26.4 (90.2) 28.0 (95.4) 50 (170.6) 60.3 (205.7) 67.3 (229.5) 88.8 (303) 31.7 (108.2) 42.7 (145.5) 50.2 (171.4) 55.5 (189.5) 71 (242.2) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH 77.9 (265.7) 99.3 (338.7) Sensible kW (kBTUH) 31.2 (106.5) 36.5 (124.5) 40.8 (139.4) 57.8 (197.1) 68.7 (234.3) 76.1 (259.8) Total kW (kBTUH) 31.2 (106.5) 36.5 (124.5) 40.8 (139.4) 58.4 (199.3) 70.1 (239) 95.6 (326.3) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 29.6 (100.8) 34.3 (117) 38.3 (130.8) 55.6 (189.8) 66.9 (228.3) 74.5 (254.3) 95.2 (324.8) Sensible kW (kBTUH) 29.4 (100.4) 34 (116.1) 38.1 (130.2) 52.9 (180.5) 62.6 (213.5) 69.4 (236.7) 87.2 (297.7) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 28 (95.4) Sensible kW (kBTUH) 26.3 (89.8) 32.6 (111.2) 36.4 (124) 30.3 (103.5) 34.1 (116.3) 53.1 (181.1) 64.1 (218.8) 47.2 (161) 71.5 (244) 55.7 (190.1) 61.6 (210.1) 91.3 (311.6) 77.4 (264) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 27 (92.3) Sensible kW (kBTUH) 24.1 (82.3) 31.7 (108.1) 35.3 (120.6) 51.5 (175.7) 62.6 (213.5) 69.8 (238.1) 27.9 (95) 31.2 (106.5) 43.4 (148.1) 51.3 (175.2) 56.7 (193.4) 89.1 (304.2) 71.2 (242.9) FAN SECTION - Downflow Models - Fixed Pitch, Two Belts Standard Air Volume, CFM (CMH) 0.2" external static 4,400 (7,476) 5,200 (8,835) 6,300 (10,704) 7,500 (12,743) 9,000 (15,291) 10,400 (17,670) 13,700 (23,276) Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5.0 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10.0 (7.5) 1 1 1 2 2 2 3 Number of Fans 1. 2. 3. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only 95 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 74 Physical data—Glycol-cooled units Model Size 028 035 042 053 070 077 105 EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin Face Area, sq. ft. (sq. m) Rows of Coil 17.1 (1.6) 3 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 3 3 3 3 3 3 REHEAT SECTION Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat Capacity, kW (kBTUH), Standard Selection 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) Capacity, kW (kBTUH), Optional Selection 10.0 (34.1) 10.0 (34.1) 10.0 (34.1) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection) Capacity, kW (kBTUH) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) HUMIDIFIER SECTION Infrared Humidifier Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (filter types cannot be mixed, must be all MERV 8 or all MERV 11) Downflow Models Quantity 3 @ 25x20 Nominal Size, inches 2 1 @ 25x16 3 3 4 4 4 4 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel Quantity Nominal Size, inches 4 4 4 6 6 6 8 25x20 25x20 25x20 25x20 25x20 25x20 25x20 OUTDOOR DRYCOOLERS - STANDARD 95°F AMBIENT SELECTION; SEE Table 103 FOR OTHER SELECTIONS Model Number D-174 D-174 D-197 D-260 D-310 D-350 D-466 Number of Fans 2 2 2 3 3 3 4 CONDENSER FLOW REQUIREMENTS—with 40% ethylene glycol GLYCOL-COOLED SYSTEM -Semi-Hermetic Compressors, based on 75°F/45% room conditions with EC fans THR, kBTUH (kW) 45.4 (154.9) 46.6 (159.1) 55.4 (189) 69.8 (238.3) 87.2 (297.7) 100.2 (341.8) 133.9 (456.9) 104°F (40°C) EGT, GPM (l/m) 32 (121.1) 33.5 (135) 39 (148) 49 (185) 62 (234.7) 70 (265) 96 (363) Pressure Drop, ft. of water (kPa), 12.9 (38.5) 14 (41.9) 18.6 (55.7) 16 (47.7) 25 (74.7) 31.3 (93.6) 50.6 (151.3) GLYCOL-COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room conditions with EC Fans THR, BTUH (kW) 39.4 (134.5) 47.6 (162.4) 54.7 (186.8) 104°F (40°C) EGT, GPM (l/m) 28 (106) 33.5 (127) 39 (148) 72.7 (248) 52 (163.5) Standard Scroll Compressors with EC Fans 91.2 (311.1) 103.7 (353.7) 64 (242) 73.5 (278) 129 (440.1) 91.5 (264.9) Pressure Drop, ft. of water (kPa) 10.0 (29.80) 14.0 (41.85) 18.6 (55.60) 17.9 (53.50) 26.6 (79.51) 34.4 (102.82) 46.2 (138.09) PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit Glycol Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Glycol Return, O.D. Copper 1-5/8" (41) 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Condensate Drain w/Optional Condensate Pump, OD 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 Liebert® DS™ 96 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 75 Performance data—GLYCOOL units with EC fans Model Size 028 035 042 053 070 077 105 CAPACITY DATA with EC Fans Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 36.5 (124.6) 37.9 (129.3) 43.5 (148.4) 58.0 (197.9) 69.3 (236.3) 77.3 (263.7) 100.4 (342.6) Sensible kW (kBTUH) 36.3 (123.7) 37.9 (129.3) 43.5 (148.4) 58.0 (197.8) 68.9 (235.1) 76.1 (259.7) 96.3 (328.7) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 34.7 (118.4) 35.5 (121.2) 40.9 (139.5) 54.9 (187.4) 65.7 (224.2) 73.7 (251.5) 96.1 (327.8) Sensible kW (kBTUH) 32.9 (112.3) 35.1 (119.8) 40.2 (137.2) 53.4 (182.3) 63.2 (215.5) 69.5 (237.2) 87.7 (299.1) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH Total kW (kBTUH) 33.1 (112.9) Sensible kW (kBTUH) 29.2 (99.6) 33.6 (114.7) 38.8 (132.3) 52.1 (177.7) 62.5 (213.3) 70.5 (240.5) 91.9 (313.7) 31.2 (106.6) 35.8 (122) 47.8 (163) 56.3 (192) 61.8 (210.9) 77.7 (265.1) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 32.2 (109.9) Sensible kW (kBTUH) 26.9 (91.7) 32.6 (111.2) 37.7 (128.6) 50.4 (172.1) 60.7 (207.1) 68.7 (234.4) 89.6 (305.6) 28.7 (97.9) 32.8 (112) 43.9 (149.8) 51.7 (176.2) 56.9 (194.2) 71.5 (243.8) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll compressors with EC Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 31.7 (108) 37.2 (127.1) 42.1 (143.5) 59.1 (201.6) 70.9 (241.9) 77.3 (263.7) 99.9 (340.9) Sensible kW (kBTUH) 31.7 (108) 37.2 (127.1) 42.1 (143.5) 58.9 (201.1) 70.2 (239.6) 75.6 (257.9) 96.0 (327.6) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 30 (102.4) 35.1 (119.6) 39.6 (135.1) 56.1 (191.4) 67.6 (230.6) 73.9 (252.3) 95.9 (327.1) Sensible kW (kBTUH) 29.9 (102) 34.8 (118.6) 39.3 (134.1) 54.2 (185.1) 64.3 (219.5) 68.8 (234.8) 91.2 (298.8) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 28.4 (96.9) 33.3 (113.7) 37.6 (128.5) 53.4 (182.3) 64.7 (220.7) 70.9 (242) 92.0 (314.1) Sensible kW (kBTUH) 26.8 (91.4) 31.1 (106.1) 35.2 (120.1) 48.5 (165.5) 57.4 (195.8) 61.0 (208.3) 77.8 (265.4) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 27.5 (93.8) Sensible kW (kBTUH) 24.6 (83.9) 32.4 (110.7) 36.6 (125) 51.8 (176.9) 63.0 (215) 69.2 (236.1) 89.9 (306.6) 28.6 (97.6) 32.3 (110.4) 44.6 (152.2) 52.8 (180.2) 56.1 (191.5) 71.6 (244.5) FAN SECTION - Downflow Models - EC Fans Under Floor Standard Air Volume, CFM (CMH) 0.2" 4,400 (7,476) 5,200 (8,835) 6200 (10,534) external static 8,000 (13,592) 9,600 (16,310) 10,400 (17670) 13,500 (22937) Standard Fan Motor, nominal kW (total for all fans) 2.8 2.8 2.8 2.5 4.0 5.9 7.8 Number of fans 1 1 1 2 2 2 3 1. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. 2. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. 3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only 97 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 76 Performance data—GLYCOOL units with centrifugal fans Model Size 028 035 042 053 070 077 105 CAPACITY DATA WITH CENTRIFUGAL FANS Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors Semi-Hermetic Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 35.9 (122.4) 36.8 (125.7) 41.9 (142.8) 56.6 (193.2) 67.6 (230.8) 74.9 (255.7) 98.6 (336.5) Sensible kW (kBTUH) 35.6 (121.5) 36.8 (125.7) 41.9 (142.8) 56.2 (191.9) 66.7 (227.5) 73.8 (251.7) 94.6 (322.6) 71.4 (243.5) 94.3 (321.7) 60.8 (207.3) 67.2 (229.2) 89.5 (293) 61.3 (209) 68.1 (232.4) 90.1 (307.6) 53.9 (184) 59.4 (202.8) 75.9 (258.9) 59.6 (203.3) 66.3 (226.4) 87.8 (299.5) 49.5 (169) 54.6 (186.2) 69.7 (237.7) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 34.1 (116.2) 34.5 (117.7) 39.2 (133.7) 53.8 (183.4) 64.3 (219.4) Sensible kW (kBTUH) 32.3 (110) 34.1 (116.3) 38.6 (131.9) 51.6 (176) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 32.5 (110.7) 32.6 (111.1) 37.1 (126.5) 51.1 (174.4) Sensible kW (kBTUH) 28.5 (97.4) 30.2 (103) 34.2 (116.7) 45.9 (156.8) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 31.6 (107.7) 31.6 (107.7) 35.9 (122.7) Sensible kW (kBTUH) 26.2 (89.5) 27.6 (94.3) 49.5 (169) 31.2 (106.6) 42.2 (143.9) Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor Scroll Compressors Only Scroll or Digital Scroll Compressors with Centrifugal Fans 85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH Total kW (kBTUH) 31 (105.8) 36.2 (123.5) 40.4 (137.8) 57.9 (197.4) 69.3 (236.6) 76.8 (262) 98.1 (334.8) Sensible kW (kBTUH) 31 (105.8) 36.2 (123.5) 40.4 (137.8) 57.2 (195.3) 67.9 (231.8) 75.1 (256.2) 94.2 (321.5) 37.9 (129.3) 55.1 (187.9) 66.2 (225.9) 73.4 (250.6) 94.1 (321) 33.7 (115.1) 37.7 (128.6) 52.4 (178.8) 61.9 (211.1) 68.3 (233.1) 89.4 (292.7) 70.4 (240.3) 90.3 (307.9) 55 (187.6) 60.5 (206.6) 76 (259.3) 61.9 (211.1) 68.7 (234.4) 88.1 (300.5) 42.9 (146.4) 50.6 (172.7) 55.6 (189.8) 69.9 (238.3) 80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH Total kW (kBTUH) 29.4 (100.2) Sensible kW (kBTUH) 29.2 (99.8) 34 (116.1) 75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH Total kW (kBTUH) 27.8 (94.7) Sensible kW (kBTUH) 26.1 (89.1) 32.3 (110.2) 35.9 (122.5) 52.5 (179.1) 63.4 (216.4) 30 (102.5) 33.6 (114.7) 46.7 (159.2) 72°F DB, 60.0°F WB, 52.3°F DP (22.2°C DB, 15.6°C WB) 49.9% RH Total kW (kBTUH) 26.9 (91.6) 31.4 (107.1) 34.9 (119) Sensible kW (kBTUH) 23.9 (81.7) 27.6 (94.1) 30.8 (105) 51 (174) FAN SECTION - Downflow Models - Fixed Pitch, Two Belts Standard Air Volume, CFM (CMH) 0.2" external static 4,400 (7,476) 5,200 (8,835) 6,300 (10,704) 7,500 (12,743) 9,000 (15,291) 10,400 (17,670) 13,700 (23,276) Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5.0 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10.0 (7.5) 1 1 1 2 2 2 3 Number of Fans 1. 2. 3. Capacity data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance. Some options or combinations of options may result in reduced air flow—consult factory for recommendations. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only Liebert® DS™ 98 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 77 Physical data—GLYCOOL units Model Size 028 035 042 053 070 077 105 EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin Face Area, sq. ft. (sq. m) Rows of Coil 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 3 3 3 3 3 3 3 REHEAT SECTION Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat Capacity, kW (kBTUH), Standard Selection 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) Capacity, kW (kBTUH), Optional Selection 10.0 (34.1) 10.0 (34.1) 10.0 (34.1) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 25.0 (85.3) 25.0 (85.3) 25.0 (85.3) 30.0 (102.4) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection) Capacity, kW (kBTUH) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) HUMIDIFIER SECTION Infrared Humidifier Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (filter types cannot be mixed, must be all MERV 8 or all MERV 11) Downflow Models Quantity Nominal Size, inches 3 3 3 4 4 4 4 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 2 @ 25x20 1 @ 25x16 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel Quantity Nominal Size, inches 4 4 4 6 6 6 8 25x20 25x20 25x20 25x20 25x20 25x20 25x20 OUTDOOR DRYCOOLERS - STANDARD 95°F AMBIENT SELECTION; SEE Table 103 FOR OTHER SELECTIONS Model Number Number of Fans D-174 D-174 D-197 D-260 D-310 D-350 D-466 2 2 2 3 3 3 4 CONDENSER FLOW REQUIREMENTS—40% Ethylene Glycol GLYCOOL SYSTEM - Semi-Hermetic Compressors, Based on 75°F/45% Room Conditions with EC Fans THR, kBTUH (kW) 45.4 (154.9) 104°F (40°C) EGT, GPM (l/m) 32 (121) 46.6 (159) 33 (125) 55.5 (189.2) 70.6 (240.8) 87.2 (297.7) 40 (151) 49 (185) 62 (235) Pressure Drop, ft. of water (kPa), 12.9 (38.50) 13.6 (40.60) 19.6 (58.59) 16.0 (47.83) 25.0 (74.73) GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75°F/45% Room Conditions with EC Fans THR, BTUH (kW) 39.4 (134.5) 47.6 (162.4) 54.7 (186.8) 104°F (40°C) EGT, GPM (l/m) 28 (98.4) 33.5 (127) 39 (148) 72.7 (248) 99.4 (339.3) 133.6 (455.9) 71 (269) 95 (360) 32.2 (96.25) 49.6 (148.30) Standard Scroll with EC Fans 91.2 (311.1) 102.9 (351.1) 128.7 (439.1) 51 (193) 64 (242) Pressure Drop, ft. of water (kPa) 10.0 (29.89) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) 72 (273) 89 (337) 33.1 (98.84) 43.8 (130.92) PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit Glycol Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Glycol Return, O.D. Copper 1-5/8" (41) 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Condensate Drain w/Optional Condensate Pump, OD 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 ECON-O-COIL CAPACITY DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Capacity Data, kW (kBTUH) 75°F DB, 62.57°FWB (23.9°C, 16.9°C) 45% RH, 45°F EGT Room Conditions with EC Fans Total capacity kW(kBTUH) 24.3 (82.8) 27.5 (93.9) 30.4 (103.9) 45.9 (156.8) 53.4 (182.3) 57.2 (182.3) 71.3 (243.3) Sensible Capacity 24.1 (82.4) 27.5 (93.9) 30.4 (103.9) 44.7 (152.6) 51.8 (176.9) 55.3 (176.9) 69.8 (238.2) 28 (106) 33.5 (127) 72 (273) 89 (337) Flow rate, GPM (l/m) Pressure Drop, ft. of water (kPa) 18.4 (55.0) 39 (148) 51 (193) 64 (242) 25.7 (76.82) 33.8 (101.03) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78) FLUID VOLUMES Unit Volume Without Econ-O-Coil, gal (l) 4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) Unit Volume with Econ-O-Coil, gal (l) 9 (34.2) 9 (34.2) 9 (34.2) 14 (53.2) 14 (53.2) 14 (53.2) 17 (64.6) 99 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 78 Model # Reheat Options Electric Standard, kW None Electric Standard kW None Electric, Downsized kW Electric, Downsized kW Humidifier Options Infrared Infrared None None Humidifier No Humidifier 230 460 575 208 230 460 575 208 Volts FLA DS028 DS035 Electrical data—Water/glycol-cooled systems with EC fans 230 460 575 208 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 208 43 WSA 82 OPD 80 90 35 30 82 80 78.9 39.2 30.5 47.3 80 40 30 60 90 45 30 80 80 78.2 75.9 37.7 33 78.1 75.9 37.7 33 46 36 85.2 83 110 50 45 110 110 78.2 75.7 37.5 29.4 64.8 41.2 35.8 95.7 92.5 50 45 30 110 110 46 36 71.9 50 40 100 30 25 70 70 35 30 70 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 70 45 460 575 62.8 31.1 24.1 60 70 90 230 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 40 90 208 51.9 25.6 19.9 55 30 230 460 575 21.1 16.8 56.3 54.1 26.9 24.2 53.5 55 95.7 92.5 110 43 32 27.1 86.3 83.2 40.8 31.1 FLA 26.2 19.7 35 25 69 67 80 80 32.7 27.1 40 30 64.8 31.9 25.6 78.1 75.9 37.7 33 71.9 35.4 28.4 85.2 83 100 110 45 70 35 25 55.3 26.9 20.4 69 67 80 80 32.7 24.8 35 25 64.8 64.8 31.9 25.6 41.2 35.8 78.4 76.4 37.8 29.6 45 100 100 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5 35 110 50 45 35 FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45 FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43 175 175 80 60 175 175 80 139.2 134.8 61.4 50 139.2 134.8 61 60 80 60 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 175 175 80 60 150 150 70 50 50 175 175 150 150 70 50 112.6 112.6 49.4 38.4 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3 OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50 FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9 OPD 1. 2. 3. 4. 5. 6. 70 WSA FLA DS105 70 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 OPD DS077 30 86.3 83.2 40.8 31.9 68.3 66.1 OPD DS070 40 FLA OPD DS053 80 WSA OPD DS042 78.9 39.2 31.9 60.6 58.4 29.1 25.9 230 460 575 208 225 225 110 100 225 225 110 100 225 225 110 90 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. Steam canister humidifiers available on downflow models with centrifugal fans. Liebert® DS™ 100 200 200 110 80 225 225 110 100 200 200 110 80 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 79 Electrical data—Water/glycol-cooled systems with centrifugal fans Reheat Options Electric, Std. kW None Electric, Std. kW None Humidifier Options Infrared or Steam Generating Canister Infrared or Steam Generating Canister None None Model 028 028 035 035 042 042 Motor hp Volts 2.0 3.0 3.0 5.0 5.0 7.5 3.0 5.0 5.0 077 7.5 7.5 10.0 10.0 15.0 208 230 460 575 208 230 460 575 20.8 16.5 31.8 25.2 55.4 52.5 26.6 23.9 66.4 63.2 31.8 24.7 42.1 41.4 31.5 59.7 56.8 28.8 25.6 81.1 77.3 38.9 30.2 46.4 45.7 23 18.2 OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25 FLA 69.5 66.0 33.2 26.4 58.5 55.3 28.0 25.1 69.5 66.0 33.2 25.9 45.2 44.2 22.2 17.7 WSA 84.2 80.1 40.3 33 62.8 59.6 30.2 26.8 84.2 80.1 40.3 31.4 49.5 48.5 24.4 19.4 OPD 90 80 40 30 80 70 35 30 90 80 40 30 60 60 FLA 72.9 69.4 34.5 26.4 65.3 62.1 30.6 26.1 72.9 69.4 34.5 26.4 52.0 51.0 24.8 18.7 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6 OPD 90 90 45 35 90 80 40 35 90 90 45 35 70 70 FLA 79.0 75.0 37.3 28.6 71.4 67.7 33.4 28.3 79.0 75.0 37.3 28.6 58.1 56.6 27.6 20.9 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8 OPD 100 100 45 35 90 90 45 35 100 100 45 35 80 80 FLA 86.5 82.7 41.6 36.1 86.4 82.7 41.6 36.1 86.5 82.5 41.4 32.5 73.1 71.6 35.8 28.7 WSA 104 99.3 49.9 39.1 93.5 89.8 45.1 38.9 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5 OPD 110 110 50 50 110 110 50 50 110 110 50 45 100 100 FLA 94.0 89.5 45.0 39.0 93.9 89.5 45.0 39.0 94.0 89.3 44.8 35.4 80.6 78.4 39.2 31.6 WSA 111.5 106.1 53.3 42.0 101.0 41.8 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4 60 45 110 110 125 110 40 50 25 30 40 96.6 48.5 125 110 60 41 101.4 96 49.2 39.5 112.1 107.2 53.9 41 74.8 73.8 37.6 27.9 53.3 42.5 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9 70 50 110 110 53.9 WSA 137.5 131.6 66.2 125 35 25 50 112.1 107.2 150 30 60 FLA 70 50.8 109.4 104.0 50 125 125 60 50 50 125 150 110 125 50 50 45 40 FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9 79.4 40.4 30.1 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1 70 50 110 110 60 45 99.5 98 46 34.5 150 150 70 50 125 125 70 50 150 150 FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1 175 150 80 60 175 150 80 60 175 150 80 60 150 125 70 50 FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0 OPD 175 175 80 FLA 145 138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0 WSA 200 175 90 60 70 175 200 175 80 175 80 60 70 175 175 175 175 80 90 60 70 150 175 150 175 70 70 50 60 FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0 200 200 90 200 200 90 175 125 100 78.6 192.3 184.2 250 225 72.6 169.9 166.6 90 125 100 95.4 78.6 185.3 180.6 225 225 84.5 70 175 110 90 225 148 80 60 200 76.8 61.0 110 90 FLA 192.3 184.2 WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3 250 250 125 100 250 250 125 100 250 250 91.5 66.1 150.8 175 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3 95.4 88.4 200 WSA 225 72.6 177.4 170.2 70 177.4 170.2 250 88.4 70 FLA OPD 1. 2. 3. 4. 5. 575 38.9 OPD 105 460 63.2 OPD 105 230 77.3 OPD 077 208 66.4 OPD 070 575 81.1 OPD 070 460 FLA OPD 053 230 WSA OPD 053 208 125 72.1 166.2 162.0 83.8 67.0 100 225 225 110 90 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. 101 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 79 Electrical data—Water/glycol-cooled systems with centrifugal fans (continued) Reheat Options Electric, Downsized kW Humidifier Options Infrared or Steam Generating Canister None Model Motor, hp Volts 208 230 460 575 208 230 460 575 FLA 55.4 52.5 26.6 23.9 52.6 50.3 25.3 19.6 028 2.0 WSA 63.9 61.2 30.8 25.6 63.9 61.2 30.8 23.8 028 3.0 035 3.0 035 5.0 042 5.0 042 7.5 053 3.0 053 5.0 070 5.0 070 7.5 077 077 105 105 1. 2. 3. 4. 5. 7.5 10.0 10.0 15.0 OPD 70 70 35 30 70 70 35 25 FLA 58.5 55.3 28 25.1 55.7 53.1 26.7 20.8 WSA 67.0 64.0 32.2 26.8 67.0 64.0 32.2 25.0 OPD 80 70 35 30 70 70 35 25 FLA 65.3 62.1 30.6 26.1 59.1 56.5 28.0 21.3 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7 OPD 90 80 40 35 80 80 40 30 FLA 71.4 67.7 33.4 28.3 65.2 62.1 30.8 23.5 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9 OPD 90 90 45 35 90 80 40 30 FLA 86.4 82.7 41.6 36.1 73.1 71.6 35.8 28.7 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7 OPD 110 110 50 50 100 100 50 40 FLA 93.9 89.5 45.0 39.0 80.6 78.4 39.2 31.6 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6 OPD 125 110 60 50 110 110 50 45 FLA 101.4 96.0 49.2 39.5 84.3 80.8 40.9 31 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8 OPD 125 125 60 50 110 110 60 45 FLA 107.5 101.6 52.0 41.7 90.4 86.4 43.7 33.2 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0 OPD 125 125 70 50 125 125 60 45 FLA 126.1 120.2 57.6 46.1 99.7 98 46.5 35.4 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7 OPD 175 150 80 60 150 125 70 50 FLA 133.6 127.0 61.0 49.0 107.2 104.8 49.9 38.3 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6 OPD 175 175 80 60 150 150 70 50 FLA 145 138.4 64.0 52.6 118.4 116.2 52.4 41.0 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9 OPD 200 175 80 70 175 175 70 60 FLA 151.6 144.4 67.0 54.6 125.0 122.2 55.4 43.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9 OPD 200 200 90 70 175 175 80 60 FLA 177.4 170.2 88.4 72.6 150.8 148 76.8 61.0 WSA 192.4 185.2 96.3 78.9 175.2 168.6 86.0 67.4 OPD 250 225 125 100 225 200 110 90 FLA 192.8 184.2 95.4 78.6 166.2 162.0 83.8 67.0 WSA 207.8 199.2 103.3 84.9 190.6 182.6 93.0 73.4 OPD 250 250 125 100 225 225 110 90 Reduced reheat for 028, 035, and 042 models is 10kW. Reduced reheat for 053, 070, and 077 models is 15kW. Consult local representative for SCR reheat values. Reduced reheat for 105 kW models is 20kW. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum. Liebert® DS™ 102 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 79 Electrical field connections—Upflow and downflow models, single molded case switch disconnect with main fuses See 4.2 - Standard Electrical Connections, 4.3 Optional Electrical Connections and 4.4 - Optional Low-Voltage Terminal Package Connections for keys to numbered components. 2 OVERCURRENT PROTECTION DEVICES 15 Liebert IntelliSlot Housing 4 A B C D Alterna te Location P64 6 60Hz CONTACTORS P67 CONTACTORS, RELAYS, & OVERLOAD PROTECTORS 13 E 5 1 6 50 & 60Hz Downflow Typical orientation of components shown. Component location varies by option and unit size 17 18 9 16 22 CAUTION: 19 UPFLOW 3 82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 Risk of broken or shorted low volt wiring. Field installed low volt wiring must be routed with loop as shown to allow electric box to swing. B A 24 3 DOWNFLOW LOW-VOLT SECTION 23 58 59 84 85 21 7 10 8 20 37C 38C 37B 38B 37 38 24 50 51 55 56 70 71 230 72 73 C D 49-3 49-1 SH 11 12 E Item 12 Installation Conditions 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway, or chase as high voltage wires (120-600V). 3. Separate high volt wires from CAN wires by 12 inches. 4. For runs greater than 350ft(107m), contact Liebert factory. 103 Point of Hinged Low-Volt Electric Box LIEBERT DS UPFLOW LOW-VOLT SECTION DPN000807 Pg. 2, Rev. 7 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 80 Electrical field connections—Upflow and downflow models, dual fused disconnect switches See 4.2 - Standard Electrical Connections, 4.3 Optional Electrical Connections and 4.4 - Optional Low-Voltage Terminal Package Connections for keys to numbered components. 14 2 OVERCURRENT PROTECTION DEVICES 15 Liebert IntelliSlot Housing 4 A B C D 6 60Hz Alternate Location 15 P64 CONTACTORS P67 SECONDARY PRIMARY 13 CONTACTORS, RELAYS and OVERLOAD PROTECTORS E 6 1 17 18 Typical orientation of components shown. Component location varies by option and unit size 22 9 DOWNFLOW CAUTION: 19 16 UPFLOW 82 83 88 89 3 75 76 94 95 96 97 91 92 93 80 81 11 12 Risk of broken or shorted low-voltage wiring. Field-installed low-voltage wiring must be routed with loop as shown to allow electric box to swing. B A 23 24 3 DOWNFLOW LOW-VOLTAGE SECTION 58 59 84 85 21 7 20 10 8 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 D 11 49-3 49-1 SH C 12 Item 12 Installation Conditions E 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway or chase as high-voltage wires (120-600V). 3. Separate high-voltage wires from CAN wires by 12" (305mm). 4. Contact Liebert factory for runs greater than 350ft. (107m). 5. All electrical loads may not be capable of being connected to both power feeds, with automatic transfer switch. Consult local representative for dual power configurations available. Liebert® DS™ 104 Point of Hinged Low-Voltage Electric Box DS UPFLOW LOW-VOLTAGE SECTION DPN000807 Pg. 3, Rev. 8 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.2 STANDARD ELECTRICAL CONNECTIONS Source: DPN000807, Rev. 8 1. Primary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in bottom of box. 2. Secondary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts located in top of box. 3. Primary low voltage entrance—Quantity (3) 1.375" (35mm) diameter knockouts located in bottom of unit. 4. Secondary low voltage entrance—Quantity (3) 1. 375" (35mm) diameter knockouts located in top of box. 5. Three phase electrical service—Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three-phase service not by Emerson. 6. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for Liebert units. 7. Remote unit shutdown—Replace existing jumper between Terminals 37 & 38 with fieldsupplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. 8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between Terminals 24 & 50, 51, 55 & 56. Use field-supplied Class 1 wiring. Terminal availability varies by unit options. 9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 & 76 for remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring. 10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is closed across Terminals 70 & 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. When a Liebert DS unit is paired with a Liebert MC series condenser, remove jumper between Terminal 71 and Terminal 230. Three wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the Liebert MC series condenser. 105 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.3 OPTIONAL ELECTRICAL CONNECTIONS Source: DPN000807, Rev. 7 11. Unit factory installed disconnect switch, Fuse Block and Main Fuses—Two types of disconnect switches are available: Non-Locking and Locking. The Non-Locking Type consists of a non-automatic molded case switch operational from the outside of the unit. Access to the high-voltage electric panel compartment can be obtained with the switch in either the On or Off position. The Locking Type is identical except access to the high-voltage electric panel compartment can be obtained only with the switch in the Off position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power is On. The molded case switch disconnect models contain separate main fuses. Units with fused disconnect have main fuses within the disconnect. Only fused disconnects are used on dual disconnect options. 12. Secondary disconnect switch and earth ground 13. Three-phase electrical service—Terminals are on top of disconnect switch. Three-phase service not by Emerson. 14. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 15. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 & 83 for lockout of reheat and humidifier. 16. Condensate alarm (with condensate pump option)—On pump high water indication, normally open dry contact is closed across Terminals 88 & 89 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 17. Remote humidifier—On any call for humidification, normally open dry contact is closed across Terminals 11 & 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring. 18. Auxiliary cool contact—On any call for Econ-O-coil operation, normally open dry contact is closed across Terminals 72 & 73 on dual cool units only. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 4.4 OPTIONAL LOW-VOLTAGE TERMINAL PACKAGE CONNECTIONS Source: DPN000807, Rev. 7 19. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C and 38C). Replace jumpers with field-supplied, normally closed switch having a minimum rating of 75VA, 24VAC. Use field-supplied Class 1 wiring. 20. Common alarm—On any alarm, two additional normally open dry contacts are closed across Terminals 94 & 95 and 96 & 97 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 21. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is closed across Terminals 84 & 85 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. 22. Liebert Liqui-tect™ shutdown and dry contact—On Liebert Liqui-tect activation, normally open dry contact is closed across Terminals 58 & 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring. Liebert® DS™ 106 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.5 DIMENSIONS—LIEBERT DS 028-042, DOWNFLOW, WATER/GLYCOL/GLYCOOL MODELS Figure 81 Dimensions—water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors with centrifugal fans Condenser Cleanout Access 56-7/8" Opening (1445mm) 33" (838mm) Air Inlet Opening 35" (889mm) Secondary Condenser TOP VIEW Fluid Piping Entrance Secondary Entrance High-Volt Connection(s) 24-3/8" (619mm) Opening Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 3/4" (19mm) Bezels Required for condenser cleanout Secondary Entrance Low-Volt Connections Minimum required for filter replacement 24" (610mm) 86" (2184mm) 5" (127mm) 76" (1930mm) 34" (864mm) 2" (51mm) Table 80 Shaded area indicates a recommended minimum clearance for component access. DPN000894 FRONT VIEW 85" (2159mm) Rev. 4 Weights—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors Dry Weight, Approximate, lb. (kg) Model Size: 028-042 Model Type Semi-Hermetic Compressor Scroll or Digital Scroll Compressor Water/Glycol 1930 (877) GLYCOOL/Dual-Cool 2080 (945) Water/Glycol 1780 (809) GLYCOOL/Dual-Cool 1930 (877) Source: DPN000894, Rev. 4 107 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 82 Primary connection locations—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors with centrifugal fans NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A All dimensions from rear corner of unit including panels FRONT VIEW X SECTION A-A BLOWER OUTLET W 8" (203mm) WS WR O Y 16-1/16" (408mm) B 3-1/2" (89mm) 35" (889mm) ECS LV1 LV2 LV3 HUM CD E1 E2 ECR 86" (2184mm) DPN000900 Rev. 3 FRONT OF UNIT Table 81 Piping data—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors Point Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) W Water/Glycol/GLYCOOL Access 79-15/16 (2030) 9-1/16 (230) 3-1/2 x 8 (89 x 203) WS Water/Glycol/GLYCOOL Supply 82-15/16 (2107) 10-15/16 (278) 1-5/8" Cu Sweat Water/Glycol/GLYCOOL Return WR CD 82-15/16 (2107) 14-1/16 (357) 1-5/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier) * 46 (1168) 29-1/2 (749) 3/4" FPT Condensate Drain (steam generating humidifier) * 46 (1168) 29-1/2 (749) 1-1/4" FPT 46 (1168) 29-1/2 (749) 1/2" Cu Sweat W/ Optional Pump HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4" Cu Sweat ECS Dual-Cool Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8" Cu Sweat ECR Dual-Cool Return 49-13/16 (1265) 28-1/2 (724) 1-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 55-1/2 (1410) 31-1/4 (794) 2-1/2" E2 Electrical Conn. (High Volt) 52-7/16 (1332) 31-1/4 (794) 2-1/2" LV1 Electrical Conn. (Low Volt) 2-1/4 (57) 27 (686) 7/8" LV2 Electrical Conn. (Low Volt) 2-1/4 (57) 29 (737) 7/8" LV3 Electrical Conn. (Low Volt) 2-1/4 (57) 31 (787) 7/8" B Blower Outlet 21-15/16 (557) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN000900, Rev. 3 Liebert® DS™ 108 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 83 Dimensions—downflow, water/glycol/GLYCOOL systems, 28-42kW (8-12 ton), with EC fans, front and/or rear discharge models 24" (610mm) Secondary Refrigerant Piping Entrance 56-7/8" (1445mm) Opening 33" (838mm) Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool 5" (127mm) 24-3/8" (619mm) Opening AIR INLET OPENING 35" (889mm) Secondary Entrance High-Voltage Connection(s) Minimum required for filter replacement Filters are accessible only through top of unit. 3/4" (19mm) Bezels TOP VIEW Secondary Entrance Low-Voltage Connections A 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 76" (1930mm) 33-1/2" (851mm) 19" (483mm) Air Outlet Opening 2" (51mm) FRONT VIEW 3-1/4" (83mm) B 3" (76mm) 33-3/8" 19" (848mm) (483mm) Air Outlet Opening 3-1/4" (81mm) 3" (77mm) REAR VIEW Customer Piping and Wiring Connections 1. For primary connection locations see standard submittals DPN000803, DPN000804 or DPN000900. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in 310697 compressor section. Pg. 1, Rev. 0 d) Or order additional SFA's to relocate connection locations Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll / Digital Semi-Hermetic Scroll / Digital Model Dual Cool Dual Cool Water/Glycol GLYCOOL/Dual Cool Water/Glycol GLYCOOL/Dual Cool Dimensions 028-042 A B 1930 (877) 1620 (736) 1930 (877) 2080 (945) 1780 (809) 1930 (877) 86" (2184mm) 73" (1854mm) 85" (2159mm) 72" (1829mm) 86" (2184mm) 85" (2159mm) 86" (2184mm) 85" (2159mm) Source: 310697, Pg. 1, Rev. 0 109 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 84 Disassembly dimensions—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors with centrifugal fans Filter & Electric Box Assembly 39" (991mm) 76" (1930mm) Assembled Height Blower & Coil Assembly Compressor Assembly 76" (1930mm) 60-3/16" (1529mm) 37" (940mm) 33" (838mm) 26" (660mm) 59" (1499mm) 85" (2159mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. DPN000899 Rev. 2 Table 82 Component weights—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), downflow, all compressors Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Component Compressor Assembly Scroll or Digital Scroll Compressor Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 950 (432) 950 (432) 800 (364) 800 (364) Filter and Electric Box Assembly 210 (96) 210 (96) 210 (96) 210 (96) Blower and Coil Assembly 770 (350) 920 (418) 770 (350) 920 (418) Source: DPN000899, Rev. 2 Liebert® DS™ 110 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.6 DIMENSIONS—LIEBERT DS 053-077, DOWNFLOW, WATER/GLYCOL/GLYCOOL MODELS Figure 85 Dimensions—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow, all compressors with centrifugal fans Digital scroll compressors not available on 077 models Condenser Cleanout Access 80" (2032mm) Opening 33" (838mm) 24-5/8" (625mm) Opening Air Inlet Opening 35" (889mm Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. 3/4" (20mm) Bezels Secondary Condenser Fluid Piping Entrance TOP VIEW Secondary Entrance Low-Volt Connections Secondary Entrance High-Volt Connection(s) Required for condenser cleanout 24" (610mm) 109" (2769mm) Minimum required for filter replacement 5" (127mm) 76" (1930mm) 2" (51mm) Table 83 108" (2743mm) Shaded area indicates a recommended minimum clearance for component access. FRONT VIEW 34" (864mm) DPN000931 Rev. 4 Weights—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow, all compressors Model Size Compressor Type Cooling Type 053 lb (kg) 070 lb (kg) 077 * Standard Scroll Only lb (kg) Semi-Hermetic Compressor Water/Glycol 2650 (1205) 2700 (1228) 2750 (1250) GLYCOOL/Dual-Cool 2830 (1287) 2880 (1310) 2930 (1332) Scroll or Digital Scroll Compressor Water/Glycol 2220 (1010) 2270 (1032) 2320 (1055) GLYCOOL/Dual-Cool 2400 (1091) 2450 (1114) 2500 (1137) * Digital scroll compressors not available on DS 077 Source: DPN00931, Rev. 4 111 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 86 Dimensions—downflow, water/glycol, GLYCOOL systems, 53-77kW (15-22 ton), front and/or rear discharge models Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool Customer Piping and Wiring Connections 24" (610mm) 1. For primary connection locations see standard submittals DPN000928, DPN000929 or DPN000933. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in compressor section. d) Or order additional SFA's to relocate connection locations Minimum required for filter replacement Filters are accessible only through top of unit. 5" (127mm) Secondary Refrigerant Piping Entrance 80" (2032mm) Opening 35" (889mm) 33" (838mm) 25-5/8" (619mm) Opening AIR INLET OPENING Secondary Entrance High-Voltage Connection(s) 34" Shaded area indicates a (864mm) 3/4" recommended minimum (19mm) clearance for component access. Secondary Entrance Low-Voltage Connections TOP VIEW A 76" (1930mm) 15-1/8" (384mm) 29-1/4" (743mm) Air Outlet Opening B 15-1/8" (384mm) 29-1/4" (743mm) Air Outlet Opening 29-5/8" (752mm) Air Outlet Opening 3-1/4" (83mm) FRONT VIEW 2" (51mm) 15-1/8" (384mm) 15-1/8" (384mm) 29-5/8" (752mm) Air Outlet Opening 3-1/4" (83mm) REAR VIEW Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll / Digital Semi-Hermetic Scroll / Digital Model Dual Cool Dual Cool Water/Glycol GLYCOOL/Dual Cool Water/Glycol GLYCOOL/Dual Cool Dimensions, in. (mm) 53 70 77 A B 2530 (1150) 2100 (955) 2650 (1205) 2830 (1287) 2220 (1010) 2400 (1091) 2580 (1173) 2150 (978) 2700 (1228) 2880 (1310) 2270 (1032) 2450 (1114) 2630 (1196) 2200 (1000) 2750 (1250) 2930 (1332) 2320 (1055) 2500 (1137) 109 (2769) 98 (2489) 108 (2743) 97 (2464) 109 (2769) 108 (2743) 109 (2769) 85 (2159) Source: 310697, Pg. 2, Rev. 0 Liebert® DS™ 310697 Pg. 2, Rev. 0 3-1/8" (79mm) 112 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 87 Primary connection locations—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models with EC fans NOTE: Drawing not to scale. Tolerance on all piping dimensions A is ± 1/2" (13mm). A FRONT VIEW SECTION A-A All dimensions from rear corner of unit including panels X O 3-1/2" (89mm) 8" (203mm) Y W WS WR 35" (889mm) ECS ECR CD B1 LV1 LV2 LV3 E1 E2 HUM 109" (2769mm) DPN002183 Rev. 0 FRONT OF UNIT Table 84 Point Piping data—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow with EC fans Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) W Water/Glycol/GLYCOOL Access 103 (2616) 9 (229) 3-1/2 x 8 (89x203) WS Water/Glycol/GLYCOOL Supply 104-3/4 (2661) 11 (279) 2-1/8 Cu Sweat WR Water/Glycol/GLYCOOL Return 104-3/4 (2661) 15 (381) 2-1/8 Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier)* 68-3/8 (1737) 31-3/8 (797) 3/4 FPT W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat ECS** Dual-Cool Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat ECR** Dual-Cool Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat E1 Electrical Conn. (High Volt) 78-1/2 (1994) 31-1/8 (790) 2-1/2 E2 Electrical Conn. (High Volt) 75-3/8 (1915) 31-1/8 (790) 2-1/2 LV1 Electrical Conn. (Low Volt) 2 (51) 29 (737) 7/8 LV2 Electrical Conn. (Low Volt) 2 (51) 30-7/8 (784) 7/8 LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8 B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8x30 (1483x762) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN002183, Rev. 0 113 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 88 Primary connection locations—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow, all compressor models with centrifugal fans NOTE: Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). A A FRONT VIEW X SECTION A-A 3-1/2" (89mm) 8" (203mm) BLOWER OUTLET W WS WR 16-1/16" (408mm) All dimensions from rear corner of unit including panels O BLOWER OUTLET Y 35" (889mm) B1 B2 ECS HUM ECRCD E1 E2 LV1 LV2 LV3 109" (2769mm) DPN000933 Rev. 4 FRONT OF UNIT Table 85 Piping data—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow Point Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) W Water/Glycol/GLYCOOL Access 103 (2616) 9 (229) 3-1/2 x 8 (89 x 203) WS Water/Glycol/GLYCOOL Supply 104-3/4 (2661) 11 (279) 2-1/8" Cu Sweat WR Water/Glycol/GLYCOOL Return 104-3/4 (2661) 15 (381) 2-1/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier)* 67-11/16 (1719) 30-1/2 (775) 3/4" FPT CD Condensate Drain (steam generating humidifier)* 67-11/16 (1719) 30-1/2 (775) 1-1/4" FPT 67-11/16 (1719) 30-1/2 (775) 1/2" Cu Sweat HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4" Cu Sweat ECS** Dual-Cool Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8" Cu Sweat ECR** Dual-Cool Return 72 (1829) 29 (737) 2-1/8" Cu Sweat E1 Electrical Conn. (High Volt) 78-1/2 (1994) 31-1/8 (790) 2-1/2" E2 Electrical Conn. (High Volt) 75-3/8 (1915) 31-1/8 (790) 2-1/2" LV1 Electrical Conn. (Low Volt) 1-7/8 (48) 28-1/2 (724) 7/8" LV2 Electrical Conn. (Low Volt) 1-7/8 (48) 30-1/4 (768) 7/8" LV3 Electrical Conn. (Low Volt) 1-7/8 (48) 32 (813) 7/8" Blower Outlet (15 x 15) 23-1/8 (587) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) Blower Outlet (15 x 11) 27-3/4 (705) 18-1/16 (459) 14-3/4 x 16-1/16 (375 x 408) Blower Outlet (15 x 15) 50-3/8 (1280) 18-1/16 (459) 18-3/4 x 16-1/16 (476 x 408) Blower Outlet (15 x 11) 54-3/8 (1381) 18-1/16 (459) 14-3/4 x 16-1/16 (375 x 408) W/ Optional Pump B1 B2 * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN00933, Rev. 4 Liebert® DS™ 114 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 89 Disassembly dimensions—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow, all compressors with centrifugal or EC fans Digital scroll compressors not available on 077 models Filter & Electric Box Assembly 39" (991mm) Compressor Assembly 76" (1930mm) Assembled Height Blower & Coil Assembly 76" (1930mm) 59-7/16" (1509mm) 37" (940mm) 33" (838mm) 26" (660mm) 82" (2083mm) 108" Assembled Length (2743mm) NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 86 DPN000932 Rev. 3 Component weights—Water/glycol/GLYCOOL, 53-77kW (15-22 ton), downflow, all compressors * with centrifugal or EC fans Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Scroll or Digital Scroll Compressor Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool Compressor Assembly 1270 (578) 1270 (578) 840 (382) 840 (382) Filter and Electric Box Assembly 250 (114) 250 (114) 250 (114) 250 (114) Blower and Coil Assembly 1230 (560) 1410 (641) 1230 (560) 1410 (641) Component * Digital scroll compressors not available on DS 077 Source: DPN000932, Rev. 3 115 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.7 DIMENSIONS—LIEBERT DS 105, DOWNFLOW, WATER/GLYCOL/GLYCOOL-COOLED MODELS Figure 90 Dimensions—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic or scroll compressors with centrifugal or EC fans Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit. Condenser Cleanout Access 102-13/16" (2611mm) Opening 33" (838mm) 35" (889mm) AIR INLET OPENING 3/4" (19mm Bezels TOP VIEW Secondary Entrance Low-Volt Connections Secondary Entrance High-Volt Connection(s) Secondary Condenser Fluid Entrance Digital scroll compressors not available on 105 models 24-3/8" (619mm Opening 24" (610mm) 132" (3353mm) Required for condenser cleanout Minimum required for filter replacement 5" (127mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance be provided for component access. 131" (3327mm) FRONT VIEW Table 87 DPN001013 Rev. 4 Weights—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic and scroll compressors * Dry Weight, Approximate, lb (kg) Forward-Curved Fans EC Fans Compressor Type Air-Cooled Dual-Cool Air-Cooled Dual-Cool Semi-Hermetic 3410 (1550) 3770 (1714) 3144 (1426) 3504 (1589) Scroll 3290 (1495) 3650 (1659) 3024 (1372) 3384 (1535) * Digital scroll compressors not available on DS 105 Source: DPN001013, Rev. 4 Liebert® DS™ 116 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 91 Dimensions—downflow, water/glycol,GLYCOOL systems, 105kW (30 ton), front discharge models with EC fans Secondary Refrigerant Piping Entrance 102-7/8" (2611mm) Opening 33" (838mm) 24-3/8" (619mm) Opening AIR INLET OPENING 35" (889mm) Downflow electrical connections can be made from top or bottom of unit 3/4" (19mm) TOP VIEW Secondary Entrance High-Voltage Connection(s) Required for Condenser cleanout on Water/Glycol or GLYCOOL/Dual Cool Secondary Entrance Low-Voltage Connections 132" (3353mm) 24" (610mm) Minimum required for filter replacement Filters are accessible only through top of unit. 5" (127mm) 76" (1930mm) 16-1/8" (410mm) 25-5/8" (649mm) Air Outlet Opening 16-1/8" (410mm) 24-7/8" (649mm) Air Outlet Opening 16-1/8" (410mm) 28-1/4" (718mm) Air Outlet Opening 30-7/8" (783mm) FRONT VIEW 57-1/2" (1459mm) 131" (3326mm) Customer Piping and Wiring Connections 3/4" (19mm) 34" Shaded area indicates a (864mm) recommended minimum clearance for component access. 1. For primary connection locations see standard submittals DPN001014 or DPN001015. A floor stand at least 9" high is recommended if primary connections locations are to be used. 2. If no floor stand is used and unit is placed directly on the floor, then do the following: a) Use secondary connection locations (shown on standard floor planning submittals). b) Order a condensate pump. c) Field pipe condensate and humidier line (if ordered) to secondary connection point in 310697 compressor section. Pg. 3, Rev. 0 d) Or order additional SFA's to relocate connection locations Dry Weight, lb (kg) Approximate Compressor Type Semi-Hermetic Scroll / Digital Semi-Hermetic Scroll / Digital Model Dual Cool Dual Cool Water/Glycol GLYCOOL/Dual Cool Water/Glycol GLYCOOL/Dual Cool 105 3134 (1422) 3014 (1367) 3144 (1426) 3504 (1589) 3024 (1372) 3384 (1535) Source: 310697, Pg. 3, Rev. 0 117 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 92 Primary connection locations—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic or standard scroll compressors with EC fans Digital scroll compressors not available on 105 models NOTES Drawing not to scale. Tolerance on all piping dimensions is ± 1/2" (13mm). All dimensions from A A Rear corner of unit FRONT VIEW Including panels X SECTION A-A O W WS WR 8" (203mm) Y 35" (889mm) BLOWER OUTLET 3-1/2" (89mm) ECS ECR CD E1 E2 B1 LV1 LV2 LV3 HUM 132" (3353mm) FRONT OF UNIT Table 88 Point DPN002153 Rev. 0 Piping data—Water/glycol/GLYCOOL 105kW (30 ton), downflow with EC fans, semi-hermetic and standard scroll compressors *** Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) W Water/Glycol/GLYCOOL Access 125-15/16 (3199) 9 (229) 3-1/2 x 8 (89x203) WS Water/Glycol/GLYCOOL Supply 127-7/8 (3248) 10-1/16 (256) 2-1/8 Cu Sweat WR Water/Glycol/GLYCOOL Return 127-7/8 (3248) 13-1/4 (337) 2-1/8 Cu Sweat CD Condensate Drain (Infrared Humidifier or No Humidifier)* 87-3/8 (2220) 31 (787) 3/4 FPT W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat ECS Dual-Cool Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat ECR Dual-Cool Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat E1 Electrical Conn. (High Volt) 98-1/8 (2492) 31 (788) 2-1/2 E2 Electrical Conn. (High Volt) 91 (2311) 31 (788) 2-1/2 LV1 Electrical Conn. (Low Volt) 2 (51) 29 (737) 7/8 LV2 Electrical Conn. (Low Volt) 2 (51) 30-7/8 (784) 7/8 LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8 B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965x762) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 105 Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN002153, Rev. 0 Liebert® DS™ 118 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 93 Primary connection locations—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic or standard scroll compressors with centrifugal fans Digital scroll compressors not available on 105 models NOTE: Drawing not to scale. A A Tolerance on all piping dimensions is ± 1/2" (13mm). 8" (203mm) W WS WR FRONT VIEW 3-1/2" (89mm) ECS X SECTION A-A 15-7/8" (403mm) TYP ECR BLOWER OUTLET 14-1/2" (368mm) TYP BLOWER OUTLET Y 35" (889mm) B1 LV1 LV2 LV3 CD HUM E1 O BLOWER OUTLET B2 B3 All dimensions from rear corner of unit including panels E2 132" (3353mm) DPN001015 Rev. 3 FRONT OF UNIT Table 89 Point W Piping data—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic and standard scroll compressors *** Description Water/Glycol/GLYCOOL Access X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) 125-15/16 (3199) 9 (229) 3-1/2 x 8 (89 x 203) WS Water/Glycol/GLYCOOL Supply 127-7/8 (3248) 10-1/16 (256) 2-1/8" Cu Sweat WR Water/Glycol/GLYCOOL Return 127-7/8 (3248) 13-1/4 (337) 2-1/8" Cu Sweat Condensate Drain (infrared humidifier or no humidifier)* 83-13/16 (2129) 30 (762) 3/4" FPT Condensate Drain (steam generating humidifier)* 83-13/16 (2129) 30 (762) 1-1/4" FPT 83-13/16 (2129) 30 (762) 1/2" Cu Sweat 102-3/4 (2610) 31-3/4 (806) 1/4" Cu Sweat CD W/ Optional Pump HUM Humidifier Supply Line ECS** Dual-Cool Supply 101-7/8 (2588) 29 (737) 2-5/8" Cu Sweat ECR** Dual-Cool Return 94-9/16 (2402) 29 (737) 2-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 98-1/4 (2496) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 88-7/16 (2246) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 2 (51) 27-1/2 (796) 7/8" LV2 Electrical Conn. (Low Volt) 2 (51) 30-1/4 (768) 7/8" LV3 Electrical Conn. (Low Volt) 2 (51) 32 (813) 7/8" B1 Blower Outlet 28-1/4 (718) 18 (457) 14-1/2 x 15-7/8 (368 x 403) B2 Blower Outlet 52 (1321) 18 (457) 14-1/2 x 15-7/8 (368 x 403) B3 Blower Outlet 75-11/16 (1922) 18 (457) 14-1/2 x 15-7/8 (368 x 403) * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cooling systems only (four-pipe system) *** Digital scroll compressors not available on DS 105Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001015, Rev. 3 119 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 94 Disassembly dimensions—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic or standard scroll compressors with centrifugal and EC fans Digital scroll compressors not available on 105 models Filter & Electric Box Assembly 39" (991mm) 41-11/16" (1059mm) Compressor Assembly 76" (1930mm) Assembled Height Blower & Coil Assembly 76" (1930mm) 59-7/16" (1510mm) 37" (940mm) 33" (838mm) 105" (2667mm) 26" (660mm) 131" Assembled Length (3327mm) NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 90 DPN001060 Rev. 2 Component weights—Water/glycol/GLYCOOL 105kW (30 ton), downflow, semi-hermetic and standard scroll compressors Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Standard Scroll Compressor * Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool Compressor Assembly 1320 (600) 1320 (600) 1200 (545) 1200 (545) Filter and Electric Box Assembly 270 (123) 270 (123) 270 (123) 270 (123) Blower and Coil Assembly Forward-Curved Fans 1820 (827) 2180 (991) 1820 (827) 2180 (991) Component * Digital scroll compressors not available on DS 105 Source: DPN001060, Rev. 2 Liebert® DS™ 120 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.8 DIMENSIONS—LIEBERT DS 028-042, UPFLOW, WATER/GLYCOL/GLYCOOL-COOLED MODELS Figure 95 Dimensions—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors with centrifugal fans Condenser Cleanout Access 33" (838mm) 35" (889mm) 3/4" (19mm) Bezels Alternate Condenser Fluid Piping Entrance TOP VIEW Minimum required for blower replacement Low-Volt Connection(s) High-Volt Connection(s) 1-1/2" (38mm) Required for condenser cleanout 86" (2184mm) 24" (610mm) 76" (1930mm) 34" Shaded area indicates a (864mm) recommended minimum clearance for component access. Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. DPN001164 85" (2159mm) 2" (51mm) FRONT VIEW Rev. 2 Table 91 Weights—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors Dry weight, including panels, lb. (kg) Semi-Hermetic Compressor Scroll or Digital Scroll Compressor Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 1980 (898) 2130 (966) 1830 (830) 1980 (898) Forward-Curved Fans Source: DPN001164, Rev. 2 121 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 96 Primary connection locations—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors with centrifugal fans NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). All dimensions from rear corner of unit including panels X 3. Field routed alternatives for water/glycol connections. 4. See submittal page DPN001120 for blower outlet and deck dimensional data. O Blower Outlet W1, W2 8" 35" (203mm) (889mm) Y 2-7/8" (73mm) 3-1/2" (89mm) 86" (2184mm) TOP VIEW OF UNIT 6" (152mm) Front of Unit 17-3/16" (437mm) 3-7/8" (98mm) 14-1/4" (362mm) 15-7/8" (403mm) CGD* FRONT SECTION VIEW OF UNIT (Left Front Panel Not Shown) LEFT SIDE SECTION VIEW OF UNIT Table 92 DPN001179 Rev. 3 Piping data—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors Point Description X in. (mm) Y in. (mm) Connection Size / Opening in. (mm) W1 3 Water/Glycol/GLYCOOL Access (Bottom) 79-15/16 (2030) 9 (229) 3-1/2 3-1/2 x 8 (89 x 203) W2 3 Water/Glycol/GLYCOOL Access (Top) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203) W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437) WS 3 Water/Glycol/GLYCOOL Supply — — 1-5/8" CU Sweat 3 Water/Glycol/GLYCOOL Return — — 1-5/8" CU Sweat WR CGD * Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (282) 1/2" CU Sweat HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (232) 1/4" CU Sweat ECS ** Dual-Cool Supply 56 (1423) 7-5/16 (186) 1-5/8" CU Sweat ECR ** Dual-Cool Return 56 (1423) 4-1/2 (114) 1-5/8" CU Sweat E1 Electrical Conn. (High Volt) 55-3/8 (1407) 30-7/8 (784) 2-1/2" E2 Electrical Conn. (High Volt) 49-7/8 (1267) 30-7/8 (784) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on dual-cool systems only (four-pipe system). Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001179, Rev. 3 Liebert® DS™ 122 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 97 Disassembly dimensions—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors with centrifugal fans Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1163mm) 26" (660mm) 33" (838mm) 59" (1499mm) 85" (2159mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 93 DPN001173 Rev. 1 Component weights—Water/glycol/GLYCOOL, 28-42kW (8-12 ton), upflow, all compressors Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Scroll/Digital Scroll Compressor Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool Compressor Assembly 950 (432) 950 (432) 800 (364) 800 (364) Blower and Electric Box Assembly 510 (231) 510 (231) 510 (231) 510 (231) Filter and Coil Assembly 520 (236) 670 (304) 520 (236) 670 (304) Component Source: DPN001173, Rev. 1 123 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 98 Blower outlet location—28-42kW (8-12 ton), upflow with centrifugal fans 73" (1854mm) or 86" (2184mm) Ref E Blower Outlet * C A 35" (889mm) Ref B Blower Outlet Location - Top View Front of Unit * Duct flange not provided Top of Unit Blower Deck 1-1/2" (38mm) D 76" (1930mm) Ref Front or Rear Throw Air Supply Table 94 DPN001120 Rev. 3 Blower outlet and deck dimensions—28-42kW (8-12 ton), upflow Dimensional data, in. (mm) Model 28-42kW (8-12ton) Blower 15 x 15 15 x 11 Supply A B C D E Front Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 25 (635) Rear Throw 15-7/8 (404) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 25 (635) Front Throw 15-7/8 (404) 14-1/2 (368) 2-1/8 (54) 25-5/8 (651) 25 (635) Rear Throw 15-7/8 (404) 14-1/2 (368) 11-5/8 (295) 25-5/8 (651) 25 (635) Source: DPN001120, Rev. 3 Liebert® DS™ 124 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.9 DIMENSIONS—LIEBERT DS 053-077, UPFLOW, WATER/GLYCOL/GLYCOOL-COOLED MODELS Figure 99 Dimensions—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow, all compressors with centrifugal fans Condenser Cleanout Access Digital scroll compressors not available on 077 models. 33" (838mm) Required for 3/4" condenser cleanout (19mm) Bezels Minimum required for blower replacement 35" (889mm) Alternate Condenser Fluid Piping Entrance TOP VIEW High-Volt Connection(s) Low-Volt Connection(s) 109" (2769mm) 1-1/2" (38mm) 24" (610mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 2" (51mm) 108" (2743mm) FRONT VIEW NOTE: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. Table 95 DPN001167 Rev. 2 Weights—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow, all compressors Dry Weight, Approximate, lb (kg) Semi-Hermetic Compressor 053 Fan Type Forward-Curved Fans Scroll or Digital Scroll 070, 077 053, 070, 077 * Water/ Glycol GLYCOOL/ Dual-Cool Water/Glycol GLYCOOL/ Dual-Cool Water/Glycol GLYCOOL/ Dual-Cool 2650 (1205) 2830 (1287) 2800 (1270) 2980 (1352) 2370 (1075) 2550 (1157) * Digital scroll compressors not available on DS 077 Source: DPN001167, Rev. 2 125 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 100 Primary connection locations—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow with centrifugal fans All dimensions from rear corner of unit including panels NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions 8" is ± 1/2" (13mm). (203mm) 3. Field routed alternatives for water/glycol 35" connections. (889mm) 2-7/8" (73mm) 4. See submittal page DPN001191 for 3-1/2" blower outlet and deck dimensional data. Blower Outlet Blower Outlet (89mm) 109" (2769mm) Front of Unit TOP VIEW OF UNIT 6" (152mm) 17-3/16" (437mm) 3-7/8" (98mm) 14-1/4" (362mm) FRONT SECTION VIEW OF UNIT 15-7/8" (403mm) (Left Front Panel Not Shown) LEFT SIDE SECTION VIEW OF UNIT Table 96 DPN001214 Rev. 1 Piping data—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow X, in. (mm) Y, in. (mm) Connection Size / Opening Water/Glycol/GLYCOOL Access (Bottom) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203) 3 Water/Glycol/GLYCOOL Access (Top) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203) W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437) WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat WR 3 Point Description W1 3 W2 Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat CGD* Condensate Gravity Drain — — 3/4" FPT CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2" Cu Sweat HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4" Cu Sweat ECS Dual-Cool Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8" Cu Sweat ECR Dual-Cool Return 78-5/8 (1998) 4-5/8 (117) 2-1/8" Cu Sweat E1 Electrical Conn. (High Volt) 75-3/8 (1915) 30 (762) 2-1/2" E2 Electrical Conn. (High Volt) 69-7/8 (1775) 30 (762) 2-1/2" LV1 Electrical Conn. (Low Volt) 19-1/2 (495) 29-1/16 (738) 7/8" LV2 Electrical Conn. (Low Volt) 19-1/2 (495) 30-1/2 (775) 7/8" LV3 Electrical Conn. (Low Volt) 19-1/2 (495) 31-15/16 (811) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on dual-cool systems only. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001214, Rev. 1 Liebert® DS™ 126 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 101 Disassembly dimensional data—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow, all compressors with centrifugal fans Digital scroll compressors not available on 077 models. Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1163mm) 33" (838mm) 26" (660mm) 82" (2083mm) 108" (2743mm) Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Table 97 DPN001211 Rev. 1 Component weights—Water/glycol/GLYCOOL, 53-77kw (15-22 ton), upflow, all compressors Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Component Compressor Assembly Blower and Electric Box Assembly Forward-Curved Fans Filter and Coil Assembly Scroll or Digital Scroll Compressor * Water/Glycol GLYCOOL/Dual-cool Water/Glycol GLYCOOL/Dual-Cool 1270 (578) 1270 (578) 840 (382) 840 (382) 770 (349) 770 (349) 770 (349) 770 (349) 760 (345) 940 (426) 760 (345) 940 (426) * Digital scroll compressors not available on DS 077 Source: DPN001211, Rev. 1 127 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 102 Blower outlet and deck dimensions—53-77kW (15-22 ton), upflow, with centrifugal fans 98" (2449mm) or 109" (2769mm) F E Blower Outlets * C A A 35" (889mm) Ref B B Blower Outlet Location - Top View Front of Unit * Duct flanges not provided. Top of Unit Blower Deck D 1-1/2" (38mm) 76" (1930mm) Ref. Front or Rear Air Throw Supply Table 98 DPN001191 Rev. 6 Blower outlet and deck dimensions—53-77kW (15-22 ton), upflow, forward-curved fans Dimensional Data, in. (mm) Models Blower 15 x 15 53-77kW (15-22 ton) 15 x 11 Supply A B C D E F Front Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410) Rear Throw 15-7/8 (404) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410) Front Throw 15-7/8 (404) 14-11/16 (373) 2-1/8 (54) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484) Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484) Source: DPN001191, Rev. 6 Liebert® DS™ 128 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.10 DIMENSIONS—LIEBERT DS 105, UPFLOW, WATER/GLYCOL/GLYCOOL MODELS Figure 103 Dimensions—Water/glycol/GLYCOOL,105kW (30 ton), upflow, semi-hermetic and standard scroll compressors with centrifugal fans Alternate Refrigerant Piping Entrance Digital scroll compressors not available on 105 models. 33" (838mm) 35" (889mm) Alternate Condenser Fluid Piping Entrance TOP VIEW High-Volt Connection(s) 1-1/2" (38mm) 3/4" (19mm) Bezels Required for condenser cleanout Minimum required for blower replacement Low-Volt Connection(s) 132" (3353mm) 24" (610mm) 76" (1930mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access. 131" (3327mm) FRONT VIEW Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196. Table 99 34" (864mm) DPN001169 Rev. 1 Weights—Water/glycol/GLYCOOL,105kW (30 ton), upflow, semi-hermetic and standard scroll compressors * Dry Weight, Approximate, lb (kg) Semi- Hermetic Compressor Fan Type Forward-Curved Fans Standard Scroll Compressor Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 3370 (1529) 3700 (1678) 3250 (1474) 3580 (1624) * Digital scroll compressors not available on DS 105 Source: DPN001169, Rev. 1 129 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 104 Primary connection locations—Water/glycol/GLYCOOL,105kW (30 ton), upflow with centrifugal fans All dimensions from rear corner of unit including panels 35" (889mm) Blower Outlet 8" (203mm) Blower Outlet Blower Outlet 2-7/8" (73mm) 3-1/2" (89mm) LV1 LV3 NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is ± 1/2" (13mm). 3. Field routed alternatives for water/glycol connections. 4. See submittal page DPN001192 for blower outlet and deck dimensional data. LV2 LV4 132" (3353mm) Front Of Unit TOP VIEW OF UNIT 6" (152mm) W3 WS WR 17-3/16" (437mm) CGD* 3-7/8" (98mm) 14-1/4" (362mm) CGD* FRONT SECTION VIEW OF UNIT (Left Front Panel Not Shown) 15-7/8" (403mm) DPN001258 Rev. 0 LEFT SIDE SECTION VIEW OF UNIT Table 100 Piping data—Water/glycol/GLYCOOL,105kW (30 ton), upflow Point Description X Y Connection Size/ Opening W1 3 Water/Glycol/GLYCOOL Access (Bottom) 126-1/8" (3204mm) 9" (229mm) 3-1/2" x 8" (89mm x 203mm) W2 3 Water/Glycol/GLYCOOL Access (Top) 9" (229mm) 3-1/2" x 8" (89mm x 203mm) W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6" x 17-3/16" (152mm x 437mm) Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat CGD* Condensate Gravity Drain — — 3/4" FPT WS 3 WR 3 126-1/8" (3204mm) CPD Condensate Pump Discharge (Opt) 102-3/8" (2600mm) 13-5/8" (346mm) 1/2" Cu Sweat HUM Humidifier Supply Line 101-1/8" (2569mm) 13-1/8" (333mm) 1/4" Cu Sweat ECS Dual-Cool Supply 101-1/8" (2569mm) 10-1/4" (260mm) 2-5/8" Cu Sweat ECR Dual-Cool Return 101-1/8" (2569mm) 5-1/4" (133mm) 2-5/8" Cu Sweat E1 Electrical Conn. (High Volt) 98-1/2" (2502mm) 30" (762mm) 2-1/2" E2 Electrical Conn. (High Volt) 93" (2362mm) 30" (762mm) 2-1/2" LV1 Electrical Conn. (Low Volt) 41-1/8" (1045mm) 30-3/8" (772mm) 7/8" LV2 Electrical Conn. (Low Volt) 38-7/8" (987mm) 30-3/8" (772mm) 7/8" LV3 Electrical Conn. (Low Volt) 35-1/8" (892mm) 30-3/8" (772mm) 7/8" LV4 Electrical Conn. (Low Volt) 31-5/8" (803mm) 30-3/8" (772mm) 7/8" * Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825. Source: DPN001258, Rev. 0 Liebert® DS™ 130 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 105 Disassembly dimensions—Water/glycol/GLYCOOL,105kW (30 ton), upflow, all compressors with centrifugal fans Digital scroll compressors not available on 105 models. Blower & Electric Box Assembly 31-1/4" (794mm) Compressor Assembly 76" (1930mm) Assembled Height Filter & Coil Assembly 76" (1930mm) 45-13/16" (1164mm) 33" (838mm) 26" (660mm) 105" (2667mm) 131" (3327mm Assembled Length NOTES: Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. DPN001256 Rev. 1 Table 101 Component weights—Water/glycol/GLYCOOL,105kW (30 ton), upflow, all compressors Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Standard Scroll Compressor * Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool Compressor Assembly 1320 (599) 1320 (599) 1200 (544) 1200 (544) Blower and Electric Box Assembly Forward-Curved Fans 1080 (490) 1080 (490) 1080 (490) 1080 (490) Filter and Coil Assembly 970 (440) 1300 (590) 970 (440) 1300 (590) Component * Digital scroll compressors not available on DS 105 Source: DPN001256, Rev. 1 131 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 106 Blower outlet and deck dimensions—105kW (30 ton), upflow with centrifugal fans 132" (3353mm) G Blower Outlets * F E A A A 35" (889mm) Ref B B B C BLOWER OUTLET LOCATION - TOP VIEW Front of Unit * Duct flanges not provided TOP OF UNIT Blower Deck 1-1/2" (38mm) 76" (1930mm) Ref DPN001192 Rev. 1 Front or Rear Throw Air Supply Table 102 Blower outlet and deck dimensions—105kW (30 ton), upflow, forward-curved fans Dimensional Data, in. (mm) Blower 15 x 11 SUPPLY A B Front Throw 15-7/8 (404) 14-11/16 (373) C 2-1/8 (54) D E F G 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984) Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984) Source: DPN001192, Rev. 1 Liebert® DS™ 132 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11 HEAT REJECTION—DRYCOOLERS AND PUMPS 4.11.1 Drycooler Selection—Prop Fan Drycoolers Table 103 Liebert DS drycooler selection Drycooler Type Outdoor Drycooler Outdoor Quiet-Line Drycooler Liebert DS Model 95°F (35°C) 100°F (38°C) 105°F (41°C) 95°F (35°C) 100°F (38°C) 105°F (41°C) 028 D-174 D-225-16 D-310-16 D-173-16 D-205-16 D-356-32 035 D-174 D-225-16 D-350-16 D-178-16 D-205-16 D-356-32 042 D-225-16 D-310 D-419 D-205 D-347-32 D-453-32 053 D-260 D-350 D-491-32 DD-248 D-347-32 D-453-32 070 D-310 D-419 D-620-32 D-347-32 D-453-32 D-453-32 077 D-350 D-466 D-650-40 D-347-32 D-453-32 N/A 105 D-466 D-620-32 D-880-52 D-453 N/A N/A 4.11.2 Dimensions—Prop Fan Drycoolers Figure 107 Dimensions—2-fan fin/tube drycooler models 43-9/16" (1106mm) 91-1/2" (2324mm) 37-7/8" (962mm) 18" (457mm) 84" (2134mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. 43-3/16" (1097mm) 133 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 108 Dimensions—3- and 4-fan fin/tube drycooler models 43-9/16" (1106mm) 131-1/2" (3340mm) 37-7/8" (962mm) 43-9/16" (1106mm) 171-1/2" (4356mm) 18" (457mm) 124" (3150mm) 70" (1778mm) 37-7/8" (962mm) Eyebolts for Lifting 43-3/16" (1097mm) 18" (457mm) Note: Overall height to the top of fan guard 43-1/8" (1095mm) 164" (4166mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component access. 43-3/16" (1097mm) Figure 109 Dimensions—6- and 8-fan fin/tube drycooler models 131-1/2" (3340mm) 87-1/8" (2213mm) 87-1/8" (2213mm) 171-1/2" (4356mm) 37-7/8" (962mm) 37-7/8" (962mm) 59" (1499mm) 18" (457mm) 86-3/4" (2203mm) 124" (3150mm) Overalll height to the top of the fan guard is 43-1/8” (1095mm). Liebert® DS™ 18" (457mm) 70" (1778mm) 1-1/2" (38mm) diameter hole for rigging (typ.4) 86-3/4" (2203mm) 134 164" (4166mm) Emerson recommends a clearance of 36" (915mm) on each side for proper operation and component Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 104 Drycooler physical data Internal Volume, gal. (L) Net Weight lb. (kg) -033 1.2 (4.6) 390 (177) -069 2.4 (9.2) 410 (186) 3.7 (13.9) 430 (195) -109 4.9 (18.6) 450 (204) -112 5.8 (22.0) 470 (213) -139 4.8 (18.2) 565 (256) 6.9 (26.2) 605 (274) Model # -092 -174 -197 Number of Fans 1 2 9 (34) 645 (293) -225 11.1 (42.1) 685 (310) -260 10.0 (37.8) 826 (375) 13.1 (50.0) 886 (402) -310 3 -350 19.4 (73.3) 946 (429) -352 13.1 (49.6) 1040 (471) 17.4 (65.9) 1120 (508) 22.0 (83.3) 1150 (522) -491 26.3 (99.6) 1200 (544) -620 27.0 (102.2) 1940 (880) 33.0 (124.9) 2000 (907.2) 40.0 (151.4) 2060 (934.4) -419 -466 -650 4 6 -700 -790 -880 8 -940 35.0 (132.5) 2550 (1157) 44.0 (166.5) 2730 (1238.3) 52.0 (196.8) 2910 (1320) All drycooler fan motors are 3/4 hp. Table 105 Liebert Quiet-Line™ drycooler physical data Model # Number of Fans -040 -057 1 -060 -080 -111 2 -121 -158 -173 3 -178 -205 -248 -347 -356 -453 -498 4 6 8 Internal Volume, gal. (L) Net Weight lb. (kg) 2.4 (9.2) 410 (186) 3.7 (13.9) 430 (195) 4.9 (18.6) 450 (204) 4.8 (18.2) 565 (256) 6.9 (26.2) 605 (274) 9.0 (34.0) 645 (293) 10.0 (37.9) 825 (374) 13.1 (50.0) 885 (401) 19.4 (73.3) 860 (390) 13.1 (50.0) 1070 (485) 17.4 (65.9) 1160 (526) 27.0 (102.2) 1770 (803) 39.3 (148.8) 1890 (857) 35.0 (132.5) 2320 (1052) 52.6 (199.1) 2680 (1216) 135 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11.3 Electrical Data—Prop Fan Drycoolers Table 106 60Hz electrical values—Prop fan drycoolers without pump controls, standard models Drycooler Model Voltage 33, 69, 92, 109, 112 1 Fan 139, 174,197 225 2 Fans 260, 310, 350 3 Fans 352, 419, 466, 491 4 Fans 620, 650, 700 6 Fan 790, 880, 940 8 Fans FLA 4.8 — — — — — WSA 6.0 — — — — — OPD 15 — — — — — Phase 1 208/230 3 460 575 3 3 FLA 3.5 7.0 10.5 14.0 21.0 28.0 WSA 4.4 7.9 11.4 14.9 21.9 28.9 OPD 15 15 15 20 25 35 FLA 1.7 3.4 3.4 6.8 10.2 13.6 WSA 2.1 3.8 3.8 7.2 10.6 14.0 OPD 15 15 15 15 15 20 FLA 1.4 2.8 4.2 5.6 8.4 11.2 WSA 1.8 3.2 4.6 6.0 8.8 11.6 OPD 15 15 15 15 15 15 Table 107 60Hz electrical values—Prop fan drycoolers without pump controls, Liebert Quiet-Line models Drycooler Model Voltage 208/230 460 575 Liebert® DS™ Phase 40, 57, 60 1 Fan 80, 111, 121 2 Fans 158, 173, 178 3 Fans 205, 248 4 Fans 347, 356 6 Fans 453, 498 8 Fans 3 FLA 1.8 3.6 10.5 5.4 10.8 14.4 3 WSA 2.3 4.1 11.4 5.9 11.3 14.9 3 OPD 15 15 15 15 15 20 3 FLA 0.9 1.8 5.1 2.7 5.4 7.2 3 WSA 1.1 2.0 5.5 2.9 5.6 7.4 3 OPD 15 15 15 15 15 15 3 FLA 0.7 1.4 4.2 2.1 4.2 5.6 3 WSA 0.9 1.6 4.6 2.3 4.4 5.8 3 OPD 15 15 15 15 15 15 136 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 108 60Hz electrical values—Standard prop fan drycoolers with integral pump controls Number of Fans Model # Pump HP 2 3 4 6 8 139, 174, 197, 225 260, 310, 350 352, 419, 466, 491 620, 650, 700 790, 880, 940 FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD 208/230/3/60 0.75 10.5 11.4 15 14.0 14.9 20 17.5 18.4 25 24.5 25.4 30 31.5 32.4 40 1.5 13.6 15.3 20 17.1 18.8 25 20.6 22.3 25 27.6 29.3 35 34.6 36.3 40 2.0 14.5 16.4 20 18.0 19.9 25 21.5 23.4 30 28.5 30.4 35 35.5 37.4 45 3.0 17.6 20.3 30 21.1 23.8 30 24.6 27.3 35 31.6 34.3 40 38.6 41.3 50 5.0 23.7 27.9 40 27.2 31.4 45 30.7 34.9 50 37.7 41.9 50 44.7 48.9 60 7.5 31.2 37.3 60 34.7 40.8 60 38.2 44.3 60 45.2 51.3 70 52.2 58.3 80 10.0 37.8 45.5 70 41.3 49.0 70 44.8 52.5 80 51.8 59.5 90 58.8 66.5 90 15 53.2 64.8 110 56.7 68.3 110 60.2 71.8 110 67.2 78.8 110 74.2 85.8 125 0.75 5.0 5.4 15 6.7 7.1 15 8.4 8.8 15 11.8 12.2 15 15.2 15.6 20 1.5 6.4 7.2 15 8.1 8.9 15 9.8 10.6 15 13.2 14.0 20 16.6 17.4 20 2.0 6.8 7.7 15 8.5 9.4 15 10.2 11.1 15 13.6 14.5 20 17.0 17.9 20 460/3/60 3.0 8.2 9.4 15 9.9 11.1 15 11.6 12.8 15 15.0 16.2 20 18.4 19.6 25 5.0 11.0 12.9 20 12.7 14.6 20 14.4 16.3 20 17.8 19.7 25 21.2 23.1 30 7.5 14.4 17.2 25 16.1 18.9 25 17.8 20.6 30 21.2 24.0 30 24.6 27.4 35 10.0 17.4 20.9 30 19.1 22.6 35 20.8 24.3 35 24.2 27.7 40 27.6 31.1 45 15 24.4 29.7 50 26.1 31.4 50 27.8 33.1 50 31.2 36.5 50 34.6 39.9 60 0.75 4.1 4.5 15 5.5 5.9 15 6.9 7.3 15 9.7 10.1 15 12.5 12.9 15 1.5 5.2 5.8 15 6.6 7.2 15 8.0 8.6 15 10.8 11.4 15 13.6 14.2 20 2.0 5.5 6.2 15 6.9 7.6 15 8.3 9.0 15 11.1 11.8 15 13.9 14.6 20 3.0 6.7 7.7 15 8.1 9.1 15 9.5 10.5 15 12.3 13.3 15 15.1 16.1 20 5.0 8.9 10.4 15 10.3 11.8 15 11.7 13.2 15 14.5 16.0 20 17.3 18.8 20 7.5 11.8 14.1 20 13.2 15.5 20 14.6 16.9 25 17.4 19.7 25 20.2 22.5 30 575/3/60 10.0 13.8 16.6 25 15.2 18.0 25 16.6 19.4 30 19.4 22.2 30 22.2 25.0 35 15 19.8 24.1 40 21.2 25.5 40 22.6 26.9 40 25.4 29.7 45 28.2 32.5 45 137 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11.4 Piping—Prop Fan Drycoolers Figure 110 Typical piping arrangement, multiple prop fan drycoolers and multiple indoor units Expansion Tank Gal. (L) FS Drycooler No. 1 Model GPM (L/s) P: Ft (kPA) See Note 3 Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Total GPM (L/s): Pipe Diam.: In. (mm) P: Ft. (kPa) Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Drycooler No. 2 Model GPM (L/s) P: Ft (kPA) LEGEND Gate Valve Check Valve Butterfly Valve Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Relief Valve Union Ball Or Flow Control Valve FS Flow Switch Cooling Unit # Model GPM (L/s) P Ft (kPa): P:Pressure Drop Strainer Filter Notes: 1. Pressure and temperature gauges (or ports for same) are recommended to monitor component pressure drops and performance. 2. Flow measuring devices, drain and balancing valves to be supplied by others and located as required. 3. See product literature for installation guidelines and clearance dimensions. 4. Drawing shows dual pump package. Alternate pump packages with more pumps may be considered, consult supplier Liebert® DS™ 138 Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): Cooling Unit # Model GPM (L/s) P Ft (kPa): DPN000991 Rev. 0 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 109 Standard drycooler piping connection sizes and internal volume Drycooler Model # No. of Internal Coil Circuits No. of Fans Internal Volume, gal. (L) No. of Inlets/Outlets Inlet & Outlet Connection Size OD Copper, in. ID Sweat, in. 033 4* 1.2 (4.6) 1/1 1-3/8 — 069 4, 8* 2.4 (9.2) 1/1 1-3/8 — 092 6, 12*, 16 3.7 (13.9) 1/1 1-5/8 — 109 8 1/1 1-3/8 — 109 16* 1/1 2-1/8 — 112 8 112 16*, 26 139 8, 16* 174 8, 16*, 24 197 8, 16*, 32 225 16, 26* 260 16, 24* 310 16, 32* 350 16, 32* 350 48 352 16, 24* 419 16, 32* 466 26 466 40* 491 16 491 32, 48* 620 32, 64* 650 40, 52* 650 80 700 32, 64* 700 96 790 32, 64* 880 52 880 80* 940 32, 64 940 96* 1 4.9 (18.6) 1/1 1-3/8 — 1/1 2-1/8 — 4.8 (18.2) 1/1 2-1/8 — 6.9 (26.2) 1/1 2-1/8 — 9 (34) 1/1 2-1/8 — 11.1 (42.1) 1/1 2-1/8 — 10.0 (37.8) 1/1 2-1/8 — 13.1 (50.0) 1/1 2-1/8 — 5.8 (22.0) 2 3 1/1 2-1/8 — 1/1 2-5/8 — 13.1 (49.6) 1/1 2-1/8 — 17.4 (65.9) 1/1 2-1/8 — 1/1 2-1/8 — 1/1 25/8 — 1/1 2-1/8 — 1/1 2-5/8 — 19.4 (73.3) 4 22.0 (83.3) 26.3 (99.6) 27.0 (102.2) 6 33.0 (124.9) 40.0 (151.4) 35.0 (132.5) 8 44.0 (166.5) 52.0 (196.8) 2/2 — 2-1/8 2/2 — 2-1/8 4/4 — 2-1/8 2/2 — 2-1/8 4/4 — 2-1/8 2/2 — 2-1/8 2/2 — 2-1/8 4/4 — 2-1/8 2/2 — 2-1/8 4/4 — 2-1/8 * = Standard Circuiting 139 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 110 Liebert Quiet-Line drycooler piping connection sizes and internal volume Drycooler Model # No. of Internal Coil Circuits 040 4, 8* 057 12* 057 16 060 8 060 16* 080 8, 16* 111 16*, 24 121 No. of Fans Internal Volume gal. (L) 2.4 (9.2) 1 3.7 (13.9) 4.9 (18.6) Inlet & Outlet Connection Size OD Copper, in. ID Sweat, in. 1/1 1-3/8 — 1/1 1-5/8 — 1/1 2-1/8 — 1/1 1-3/8 — 1/1 2-1/8 — 4.8 (18.2) 1/1 2-1/8 — 6.9 (26.2) 1/1 2-1/8 — 16*, 32 9.0 (34.0) 1/1 2-1/8 — 158 16, 24* 10.0 (37.9) 1/1 2-1/8 — 173 16, 32* 13.1 (50.0) 1/1 2-1/8 — 178 16, 32* 1/1 2-1/8 — 178 48 1/1 2-5/8 — 205 16, 24* 13.1 (50.0) 1/1 2-1/8 — 248 16, 32* 17.4 (65.9) 1/1 2-1/8 — 347 32, 64* 27.0 (102.2) 2/2 — 2-1/8 356 32, 64* 2/2 — 2-1/8 356 96 4/4 — 2-1/8 453 32, 64* 498 32, 64 498 96* 2 3 19.4 (73.3) 4 6 39.3 (148.8) 35.0 (132.5) 8 52.6 (199.1) * = Standard circuiting Liebert® DS™ No. of Inlets/Outlets 140 2/2 — 2-1/8 2/2 — 2-1/8 4/4 — 2-1/8 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 111 Piping schematic—Water/glycol semi-hermetic compressor models Optional Dual Pump System Shown LIEBERT HEAT REJECTION CUSTOMER HEAT REJECTION ** EXPANSION TANK * Check Valves (on Dual Pump Systems only) DRYCOOLER (Glycol) COOLING TOWER AND PUMP SYSTEM BY OTHERS GLYCOL PUMPS * Pressure Port Aquastat Sensing Bulbs * Hose Bib * Shutoff Valve * Gate Valves *** Air Vents (typical) * Pressure Port Flow Switch Supplied with Dual Pump Systems * Shutoff Valve SUPPLY RETURN * Flow-Regulating Valve SUPPLY RETURN LIEBERT DS UNIT (and associated piping) RETURN LIQUID * Shutoff Valve * Shutoff Valve Sensing Bulb Cylinder Unloader(s) Service Valve SUPPLY Optional 3-Way Regulating Valve EVAPORATOR COIL SUCTION * Hose Bib Muffler COMPRESSOR Check Valve Two-Way Regulating Valve Service External Valve Equalizer DISCHARGE PARADENSER® CONDENSER Expansion Solenoid Sight Valve Glass Valve Bypass Valve Filter Drier NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. Sensor TO SECOND REFRIGERATION CIRCUIT Schematic representation shown. Do not use for specific connection locations. FACTORY PIPING FIELD PIPING OPTIONAL FACTORY PIPING Service / Schrader (Access) Connection No Valve Core Service / Schrader (Access) Connection With Valve Core 141 * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance ** Field-installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points DPN000895 Rev. 3 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 112 Piping schematic—Water/glycol scroll compressor models ** EXPANSION TANK LIEBERT HEAT REJECTION CUSTOMER HEAT REJECTION DRYCOOLER (Glycol) COOLING TOWER AND PUMP SYSTEM BY OTHERS GLYCOL PUMPS * Check Valves (on Dual Pump Systems only) * Gate Valves * Pressure Port Aquastat Sensing Bulbs * Hose Bib Optional Dual Pump System Shown * Shutoff Valve *** Air Vents (typical) * Pressure Port Flow Switch Supplied with Dual Pump Systems * Flow-Regulating Valve * Shutoff Valve RETURN SUPPLY SUPPLY RETURN LIEBERT DS UNIT (and associated piping) RETURN SUPPLY * Shutoff Valve * Shutoff Valve LIQUID Sensing Bulb Optional 3-Way Regulating Valve EVAPORATOR COIL * Hose Bib SUCTION Service Service Valve Valve External COMPRESSOR Check Equalizer Valve * Hose Bib Two-Way Regulating Valve DISCHARGE Bypass Valve PARADENSER® CONDENSER Expansion Solenoid Sight Filter Drier Valve Glass Valve NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. Schematic representation shown. This schematic does not imply or define elevations and component location, unless specifically noted. Sensor TO SECOND REFRIGERATION CIRCUIT FACTORY PIPING FIELD PIPING OPTIONAL FACTORY PIPING Service / Schrader (Access) Connection No Valve Core Service / Schrader (Access) Connection With Valve Core Liebert® DS™ 142 * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance ** Field-installed at highest point in system on return line to pumps DPN000896 *** Locate at tops of all risers and Rev. 3 any intermediate system high points Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11.5 Pump Packages & Expansion Tank Figure 113 Single pump package piping connections and dimension 17-1/4" (438.2mm) SINGLE PACKAGE 0.75 - 7.5 HP 2 1 3 19" (482.6mm) 2-7/8" (72.9mm) 15-7/8" (403.2mm) 1-3/4" (44.4mm) 6-3/8" (161.9mm) 8-3/4" (222.3mm) 12-1/4" (311.1mm) 30" (762mm) 17" (431.8mm) PUMP PACKAGE MOUNTING ANGLES (Angles are inside, bottom of pump package. View used for mounting reference.) 1 3" (76.2mm) diameter pump suction connection knockouts 2 3" (76.2mm) diameter pump discharge connection knockouts 4 3 7/8" (22.2mm) diameter electrical knockouts 4 4 1/2" (12.7mm) diameter holes for mounting 3/4" (19mm) C DPN000278 Rev. 0 A B Table 111 Mounting hole dimensions, in. (mm) A B C Single (0.75 - 7.5hp) 15-1/4 (387.4) 2-1/2 (63.5) 22-1/2 (571.5) Dual (0.75 - 5hp) 30-1/4 (768.4) 2-1/2 (63.5) 22-1/2 (571.5) Dual (7.5hp) 39-5/16 (998.5) 1-3/4 (44.5) 26-7/8 (682.6) Pump Package Source: DPN000278, Rev. 0 143 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 114 Dual pump package piping connections and dimensions DUAL PACKAGE 0.75 - 5 HP 2 See Figure 113 and Table 111 for mounting angles and dimensions 32-1/4" (819.2mm) 1 2 3 1 3 15-7/8" (403.2mm) 4-1/8" (104.8mm) 6-3/8" (161.9mm) " 2-7/8" (73mm) 8-3/4" (222.2mm) 19" (482.6mm) 1-3/4" (44.4mm) 12-1/4" (311.1mm) 30" (762mm) 23-3/4" (603.2mm) 27-1/4" (692.1mm) 32" (812.8mm) 1 3" (76.2mm) diameter pump suction connection knockouts 2 3" (76.2mm) diameter pump discharge connection knockouts 3 7/8" (22.2mm) diameter electrical knockouts 5 5" (127mm) diameter pump discharge connection hole 6 5" (127mm) diameter pump suction connection hole 32-3/8" (822.3mm) DUAL PACKAGE 7.5 HP 3 5 41-1/4" (1047.8mm) 6 5 6 19-15/16 (506.4mm) 11-7/8 (301.6mm) 15-7/8 (403.2mm) 33-3/16" (843mm) 16-3/8" (415.9mm) 29-3/16" (741.4mm) 6-1/2" (165.1mm) 41" (1041.4mm) Liebert® DS™ 144 DPN000328 Rev. 0 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 115 Pump package expansion tank 30-1/2" (774.7mm) Ø 9" (228.6mm) 1/2" F.P.T. Fitting 2-3/4" (69.9mm) 2-1/2" (63.5mm) 1" (25.4mm) 1-1/2" (38.1mm) 6-13/16" (173mm) 1/2" F.P.T. Fitting 17-1/4" (438.2mm) 7" (177.8mm) 4" (101.6mm) 1" (25.4mm) Ø 1/2" (12.7mm) 8 Holes 1-1/2" (38.1mm) 6-1/8" (155.6mm) 8.8 gal. (33.3 L) Expansion Tank 3" (76.2mm) DPN000329 Rev. 0 Expansion Tank (P/N 1C16717P1) This tank, included in a standard pump package, has an internal volume of 8.8 gal. (33 l) and a maximum pressure of 100 psi (690 kPa). This tank is sized for a typical “open” system with a fluid volume of less than 75 gal. (280l). When used in a “closed” system, volumes of up to 140 gal. (910l) can be accommodated. The use of a safety relief valve, field-supplied, is recommended for systems “closed” to atmospheric venting. Other piping accessories for filling, venting, or adjusting the fluid in the system, are recommended, but not included. Table 112 Glycol pump data Connections Electric @ 60Hz Pump HP NPT Suction Connection Female Discharge Connection ph 208 FLA 230 FLA 460 FLA 575 FLA 3/4 1-1/4" 3/4" 1 7.6 6.9 N/A N/A 3/4 1-1/4" 3/4" 3 3.5 3.2 1.6 1.3 1-1/2 1-1/4" 3/4" 3 6.6 6.0 3.0 2.4 2 1-1/4" 3/4" 3 7.5 6.8 3.4 2.7 3 1-1/2" 1" 3 10.6 9.6 4.8 3.9 5 1-1/2" 1-1/4" 3 16.7 15.2 7.6 6.1 7-1/2 3" 3" 3 24.2 22.0 11.0 9.0 • To Calculate Total Pump and Drycooler Full Load Amps (FLA): Total FLA = Pump FLA + Drycooler FLA • To Calculate Total Pump and Drycooler Wire Size Amps (WSA): Total WSA = Largest Motor FLA x 1.25 + Sum of other Motor FLA values • To Calculate Total Pump and Drycooler Maximum Overcurrent Protective Device (OPD): Total OPD = Largest Motor FLA x 2.25 + Sum of other Motor FLA values Select standard fuse size (15A, 20A, 25A, 30A, etc.) 145 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 116 Pump curve, 60 Hz 180 Curve A B C D E F Total Head, Feet/Water 160 140 F 120 E G D 100 80 60 HP 3/4 (1-ph) 3/4 (3-ph) 1.5 2 3 5 7.5 G C B A 40 20 0 10 20 30 40 50 60 70 80 120 160 200 250 300 400 Flow Rate, GPM Table 113 60Hz electrical values—Quiet-Line drycoolers with integral pump controls Number of Fans 3 Model # Pump H.P. 208/230/3/60 0.75 1.5 2.0 3.0 5.0 7.5 * 10.0 * 15 * 460/3/60 0.75 1.5 2.0 3.0 5.0 7.5 * 10.0 * 15 * 575/3/60 0.75 1.5 2.0 3.0 5.0 7.5 * 10.0 * 15 * 4 158, 173, 178 6 205, 248 8 347, 356 453, 498 FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD 8.9 12.0 12.9 16.0 22.1 29.6 36.2 51.6 9.8 13.7 14.8 18.7 26.3 35.7 43.9 63.2 15.0 20.0 20.0 25.0 40.0 50.0 70.0 100.0 10.7 13.8 14.7 17.8 23.9 31.4 38.0 53.4 11.6 15.5 16.6 20.5 28.1 37.5 45.7 65.0 15.0 20.0 20.0 30.0 40.0 60.0 70.0 110.0 14.3 17.4 18.3 21.4 27.5 35.0 41.6 57.0 15.2 19.1 20.2 24.1 31.7 41.1 49.3 68.6 20.0 25.0 25.0 30.0 45.0 60.0 80.0 110.0 17.9 21.0 21.9 25.0 31.1 38.6 45.2 60.6 18.8 22.7 23.8 27.7 35.3 44.7 52.9 72.2 25.0 25.0 30.0 35.0 50.0 60.0 80.0 110.0 4.3 5.7 6.1 7.5 10.3 13.7 16.7 23.7 4.7 6.5 7.0 8.7 12.2 16.5 20.2 29.0 15.0 15.0 15.0 15.0 15.0 25.0 30.0 45.0 5.2 6.6 7.0 8.4 11.2 14.6 17.6 24.6 5.6 7.4 7.9 9.6 13.1 17.4 21.1 29.9 15.0 15.0 15.0 15.0 20.0 25.0 35.0 50.0 7.0 8.4 8.8 10.2 13.0 16.4 19.4 26.4 7.4 9.2 9.7 11.4 14.9 19.2 22.9 31.7 15.0 15.0 15.0 15.0 20.0 30.0 35.0 50.0 8.8 10.2 10.6 12.0 14.8 18.2 21.2 28.2 9.2 11.0 11.5 13.2 16.7 21.0 24.7 33.5 15.0 15.0 15.0 15.0 20.0 30.0 35.0 50.0 3.4 4.5 4.8 6.0 8.2 11.1 13.1 19.1 3.7 5.1 5.5 7.0 9.7 13.4 15.9 23.4 15.0 15.0 15.0 15.0 15.0 20.0 25.0 40.0 4.1 5.2 5.5 6.7 8.9 11.8 13.8 19.8 4.4 5.8 6.2 7.7 10.4 14.1 16.6 24.1 15.0 15.0 15.0 15.0 15.0 20.0 25.0 40.0 5.5 6.6 6.9 8.1 10.3 13.2 15.2 21.2 5.8 7.2 7.6 9.1 11.8 15.5 18.0 25.5 15.0 15.0 15.0 15.0 15.0 20.0 25.0 40.0 6.9 8.0 8.3 9.5 11.7 14.6 16.6 22.6 7.2 8.6 9.0 10.5 13.2 16.9 19.4 26.9 15.0 15.0 15.0 15.0 15.0 25.0 30.0 40.0 Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be adjusted higher than calculations to compensate for maximum anticipated application temperatures. * May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before ordering. Liebert® DS™ 146 Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11.6 Drycooler Selection—Indoor Piggyback Drycoolers Table 114 Liebert indoor piggyback drycooler/DS matchup data Drycooler Selections Drycooler Type Liebert DS Model Ambient Temp. °F (°C) 028 035 042 053 070 077 95 (35) PD-133/150 PD-150 PD-223 PD-290 PD-333 PD-333 100 (38) PD-223 PD-223 PD-333 N/A N/A N/A 105 (41) PD-333 PD-333 PD-333 N/A N/A N/A Piggyback Drycooler Table 115 Indoor piggyback airflow and static pressure data HP/RPM Model Ext. Static Pressure - in. (Pa) No. of Fans CFM (m /hr) 0.25 (62.3) 0.50 (125) 0.75 (187) 1.0 (249) 2 6600 (11,200 2/575 3/650 3/725 3/800 2 6900 (11,730 2/605 3/680 3/750 3/820 2 2 2 12,500 (21,250 12,300 (20,910 16,500 (28,050 7.5/760 7.5/780 10/640 7.5/810 7.5/830 10/695 7.5/870 7.5/890 10/740 7.5/920 7.5/940 15/790 PD-102 PD-133 PD-150 PD-223 PD-290 PD-333 3 Values are without filter box. External Static Pressure = filter pressure drop + other static drops. Source: DPN000695, Rev. 0 4.11.7 Weights and Dimensions—Indoor Piggyback Drycoolers Figure 117 Dimensions—Indoor piggyback drycoolers E H K 1-1/8" (29mm) J R K Overall Optional Fan Discharge S D B D ns imensio Overa ll Dim ensio ns Disconnect Switch H J R 35-1/8" (892mm) 72" (1829mm) Fan Discharge Shaded areas indicate a recommended clearance of 34" (864mm) for component access. 5" (127mm) 1" (25.4mm) G Condenser Coil Inlet and Duct Connection 10" (254mm) Drain Outlet Opening C C Unit Base UNIT DIMENSIONS 15-7/16" (392mm) Floor Level A A Unit Base F Rear of Cabinet Note: A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening. DPN000710 Rev. 1 FLOOR CUTOUT DIMENSIONS 147 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Table 116 Dimensions—Indoor piggyback drycoolers, in (mm) A B C D E F G H J K R S 72 (1829) 72 (1829) 72 (1829) 97 (2464) 97 (2464) 97 (2464) 74 (1880) 74 (1880) 74 (1880) 99 (2515) 99 (2515) 99 (2515) 31 (787) 31 (787) 31 (787) 33 (838) 33 (838) 33 (838) 32 (813) 32 (813) 32 (813) 34 (864) 34 (864) 34 (864) 1-1/8 (29) 1-1/8 (29) 1-1/8 (29) 3-1/8 (79) 3-1/8 (79) 3-1/8 (79) 33 (838) 33 (838) 33 (838) 46-1/2 (1181) 46-1/2 (1181) 46-1/2 (1181) 60 (1524) 60 (1524) 60 (1524) 85 (2159) 85 (2159) 85 (2159) 8-5/8 (219) 8-5/8 (219) 8-5/8 (219) 23-5/16 (592) 23-5/16 (592) 16-5/16 (421) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 50-3/16 (1275) 63-7/8 (1622) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 16-1/16 (408) 19-1/8 (486) 13-3/16 (335) 13-3/16 (335) 13-3/16 (335) 23-1/2 (597) 23-1/2 (597) 16-13/16 (427) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 14-11/16 (373) 11-5/8 (295) Model PD-102 PD-133 PD-150 PD-223 PD-290 PD-333 1. A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening. 2. Source: DPN000710, Rev. 1 4.11.8 Electrical Data—Piggyback Drycoolers Table 117 Electrical data, piggyback drycoolers, 60Hz, 3 Ph Drycooler No Pumps Model PD-102 PD-133 PD-150 PD-223 PD-290 PD-333 Drycooler Standard Pump Package Total Unit Pump Only Drycooler - Optional Pump Package Pump Only Total Unit Total Unit Voltage Blower Motor HP FLA WSA OPD hp FLA FLA WSA OPD hp FLA WSA OPD 208 3 10.6 13.3 20 1.5 6.6 17.2 19.9 30 2 18.1 20.8 30 230 3 9.6 12.0 20 1.5 6.0 15.6 18 25 2 16.4 18.8 25 460 3 4.8 6.0 15 1.5 3.0 7.8 9 15 2 8.2 9.4 15 575 3 3.9 4.9 15 1.5 2.4 6.3 7.3 15 2 6.6 7.6 15 208 3 10.6 13.3 20 2 7.5 18.1 20.8 30 3 21.2 23.9 30 230 3 9.6 12.0 20 2 6.8 16.4 18.8 25 3 19.2 21.6 30 460 3 4.8 6.0 15 2 3.4 8.2 9.4 15 3 9.6 10.8 15 575 3 3.9 4.9 15 2 2.7 6.6 7.6 15 3 7.8 8.8 15 208 7.5 24.2 30.3 50 3 10.6 34.8 40.9 60 5 40.9 47 70 230 7.5 22.0 27.5 45 3 9.6 31.6 37.1 50 5 37.2 42.7 60 460 7.5 11.0 13.8 20 3 4.8 15.8 18.6 25 5 18.6 21.4 30 575 7.5 9.0 11.3 20 3 3.9 12.9 15.2 20 5 15.1 17.4 25 208 7.5 24.2 30.3 50 5 10.6 40.9 47 60 3 34.8 40.9 60 230 7.5 22.0 27.5 45 5 9.6 37.2 42.7 30 3 31.6 37.1 50 460 7.5 11.0 13.8 20 5 4.8 18.6 21.4 25 3 15.8 18.6 25 575 7.5 9.0 11.3 20 5 3.9 15.1 17.4 20 3 12.9 15.2 20 208 10 30.8 38.5 60 5 10.6 47.5 55.2 80 3 41.4 49.1 70 230 10 28.0 35.0 60 5 9.6 43.2 50.2 70 3 37.6 44.6 70 460 10 14.0 17.5 30 5 4.8 21.6 25.1 35 3 18.8 22.3 35 575 10 11.0 13.8 20 5 3.9 17.1 19.9 30 3 14.9 17.7 25 ph = phase; FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device Liebert® DS™ 148 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 118 Piping—Indoor piggyback drycooler models See Note 1 A E C B See Note 2 3" (76mm) D See Note 1 1" (25mm) 3" (76mm) C See Note 2 1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for Main Power Supply (Typ). 2. Cover plate for access of glycol piping inlet and outlet. 3. Piggyback drycooler connection sizes for supply and return glycol lines are the same as room unit supply and return lines. Note applies to PD-133. 12-5/8" (321mm) 9-11/16" (246mm) 2-1/2" (64mm) 7-7/8" (200mm) 5-1/2" (140mm) See Note 1 3" (76mm) Drain Outlet Location 1-1/4" (32mm) F.P.T. 6" 3" (152mm) 1-1/2" (76mm) (38mm) See Note 2 8" (203mm) DPN000711 Rev. 0 Table 118 Dimensions—Indoor piggyback drycoolers Table 119 Pipe connection sizes, ODS Model # Model # Glycol Supply Glycol Ret. A B C D E Drain PD-102 27-1/4 (692) 1-1/2 (38) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-102 1-5/8 (41) 1-1/4 (32) 1-1/4 (32) PD-133 27-1/4 (692) 1-1/2 (38) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-133 See Note 3 See Note 3 1-1/4 (32) PD-150 27-1/4 (692) 1-1/2 (38) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-150 2-1/8 (54) 1-1/4 (32) 1-1/4 (32) PD-223 27-1/4 (692) 1-1/2 (38) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-223 2-1/8 (54) 1-1/4 (32) 1-1/4 (32) PD-290 27-1/4 (692) 1-1/2 (38) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-290 2-1/8 (54) 1-1/4 (32) 1-1/4 (32) PD-333 29-1/2 (749 PD-333 2-1/8 (54) 1-1/4 (32) 1-1/4 (32) 6 (152) 6 (152) — — 149 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.11.9 System Piping—Piggyback Drycoolers Figure 119 Piping schematic—Liebert DS glycol-cooled models with centrifugal piggyback drycoolers Drycooler Electric Box Drycooler Coil Expansion Tank Glycol Pumps Pressure Tap Unions Valve Actuator Hose Bib * Air Vents * At Top Of Risers Aquastat Sensing Bulb Pressure Tap B Check Valves On Dual Pump Systems Only Pressure Tap Evaporator Coil Ball Valves Fluid Return To Pump AB A 3-Way Chilled Glycol Valve Fluid Supply From Pump Flow Switch Supplied With Dual Pump Systems Installed in Field Flow Regulating Valve * Solenoid Pressure Valve Tap Pressure Tap Optional Dual Pump System Shown Unions Expansion Valve External Equalizer Sight Glass Filter Dryer Sensing Bulb Cylinder Unloader (Optional) Service Valves Glycol Coolant Circuit One Required Per Unit Fluid Fluid Supply Return To Unit From Unit Shutoff Liquid Return Muffler Compressor Shutoff Valve Relief Valve Bypass Valve Condenser Optional 3-Way Glycol Regulating Valve Bypass Valve Valves * To Second Refrigeration Circuit 2-Way Glycol Regulating Valve SINGLE REFRIGERATION CIRCUIT SHOWN 2-Way Glycol Regulating Valve Hose * Bibs * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance Liebert® DS™ 150 FACTORY PIPING OPTIONAL PIPING FIELD PIPING DPN000706 REV 0 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 120 Piping schematic—Liebert DS GLYCOOL models with centrifugal piggyback drycoolers Drycooler Electric Box Drycooler Coil Expansion Tank Pressure Tap Valve Actuator A B Flow Switch Supplied w/ Dual Pump Systems Pressure Tap Pressure Tap Optional Dual Pump System Shown Aquastat Ball Valves Sensing Bulb Pressure Tap Fluid Return To Pump AB Fluid 3-Way Chilled Supply Glycol Valve From Pump Glycol Pumps Unions Check Valves On Dual Pump Systems Only Pressure Tap Econ-O-Coil Evaporator Coil Valve Actuator Expansion Valve Econ-O-Cycle Comparator Solenoid Valve 3-Way Chilled Glycol Valve Sight Glass External Equalizer Filter Dryer Cylinder Unloader (Optional) Muffler Econ-O-Coil Circuit Glycol Coolant Circuit One Required Per Unit Service Valves Liquid Return One Supplied Per Unit Sensing Bulb Compressor r Shutoff Valve Relief Valve Condenser 3-Way Glycol Regulating Valve Fluid Fluid Supply Return To Unit From Unit Shutoff Valves * To Second Refrigeration Circuit 3-Way Glycol Regulating Valve SINGLE REFRIGERATION CIRCUIT SHOWN FACTORY PIPING OPTIONAL PIPING FIELD PIPING * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance DPN000707 REV 0 Hose * Bibs 151 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems 4.12 ANCILLARY ITEMS—WATER-COOLED SYSTEMS Figure 121 Floor stand dimensions—28-42kW (8-12 ton), downflow A+1-1/2" (38mm) (with feet) A 47-15/16" (1218mm) B 4-1/2" (114mm) 33" (838mm) 16-3/4" (425mm) 34-1/2" (876mm) (with feet) Supply air discharge opening Supply air discharge opening 1" (25mm) TYP. Gussets supplied on floor stands 12" (305 mm) tall and greater Optional turning vane shown as front air discharge. Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. 7/8" (23mm) 3" (76mm) Table 120 Floor stand and floor planning dimensions—28-42kW (8-12 ton), downflow Dimensional Data, in. (mm) Height, in. (mm) Model A B Air-Cooled Semi-Hermetic Models and All Water/Glycol/GLYCOOL Models 85 (2159) 26 (660) Air-Cooled Scroll Models and Air-Cooled Digital Scroll Models 72 (1829) 13 (330) Source: DPN000820, Rev. 3 Liebert® DS™ 152 C* D turning vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) DPN000820 Rev. 3 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 122 Floor stand dimensions—53-77kW (15-22 ton), downflow A+1-1/2" (38mm) (with feet) A 69-3/4" (1772mm) B 34-1/2" (876mm) (with feet) 16-3/4" (425mm) Supply air discharge opening 33" (838mm) 1" (25mm) TYP. Gussets supplied on floor stands 12" (305 mm) tall and greater Supply air discharge opening 7/8" (23mm) Optional turning vane shown as front air discharge. 3" (76mm) Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. NOTE: Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. DPN000930 Rev. 2 Table 121 Floor stand and floor planning dimensions—53-77kW (15-22 ton), downflow Dimensions, in. (mm) Height, in. (mm) Model A B Air-Cooled Semi-Hermetic Models and All Water/Glycol/GLYCOOL Models 108 (2743) 26 (660) Air-Cooled Scroll Models and Air-Cooled Digital Scroll Models 97 (2464) 15 (381) C* D - Turning Vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) Source: DPN000930, Rev. 2 153 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 123 Floor stand dimensions—105kW (30 ton), downflow 132-1/2" (3366mm) (with feet) 26" (660mm) 131" (3327mm) 91-3/4" (2330mm) 4-1/2" (114mm) 34-1/2" (876mm) (with feet) 33" (838mm) 16-3/4" (425mm) 1" (25mm) TYP. Supply air discharge opening Supply air discharge opening Gussets supplied on floor stands 12" (305 mm) tall and greater 7/8" (23mm) Optional turning vane shown as front air discharge. 3" (76mm) Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. C* D NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C. Table 122 Floor stand and floor planning dimensions—105kW (30 ton), downflow Height, in. (mm) C* D turning vane 9 (229) 4 (111) 12 (305) 7 (187) 15 (381) 10 (264) 18 (457) 13 (340) 21 (533) 16 (416) 24 (610) 19 (492) Source: DPN001059, Rev. 2 Liebert® DS™ 154 DPN001059 Rev. 2 Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 124 Floor stand dimensions, piggyback drycoolers with centrifugal fans C B A 1" (25.4mm) * H ± 1-1/2" (38mm) For height selection refer to chart. Center Leg Provided on 99" Cabinets See Table 124 for height selection Leg Support on Models 18, 21 & 24" High DPN000727 Rev. 0 Table 123 Floor stand dimensions, in. (mm) A B C PD-102, PD-133, PD-150 72 (1829) 36 (914) 31 (787) PD-223, PD-290 PD-333 97 (2464) 48-1/2 (1232) 33 (838) Model Source: DPN000727, Rev. 0 Table 124 Floor stand height selection, in. (mm) Nominal Range (Nominal ±1-1/2 *) 9 (229) 7-1/2 to 10-1/2 (191 to 267) 12 (305) 10-1/2 to 13-1/2 (267 to 343) 15 (381) 13-1/2 to 16-1/2 (343 to 419) 18 (458) 16-1/2 to 19-1/2 (419 to 495) 21 (553) 19-1/2 to 22-1/2 (495 to 572) 24 (610) 22-1/2 to 25-1/2 (572 to 648) Leveling feet are provided with ±1-1/2" (38mm) Adjustment from nominal height “H”. Source: DPN000727, Rev. 0 155 Liebert® DS™ Water-Cooled, Glycol-Cooled and GLYCOOL Systems Figure 125 Plenum dimension—28-105kW (8-30 ton), upflow FRONT VIEWS REAR VIEWS WITH GRILLE WITH GRILLE Panel removable for condenser clean out access (Water/Glycol/GLYCOOL models only) WITHOUT GRILLE 34" (864mm) B WITHOUT GRILLE A 1" (25mm) LEFT SIDE VIEWS CHECK ONE (1): H RIGHT SIDE VIEWS CHECK ONE (1): WITH GRILLE 76" (1930mm) WITHOUT GRILLE SIDE VIEW - UNIT WITH PLENUM FRONT VIEW - UNIT WITH PLENUM Notes: 1. Typical 53-77kW (15-22 Tons) unit orientation shown with grille Plenum. View varies by unit size and Plenum selection. 2. All Plenums are shipped flat and must be field assembled. 3. Optional grille Plenum kits must include front or rear grille. 4. Non-grille Plenums are open on the top and not designed with duct flange. WITH GRILLE WITHOUT GRILLE DPN001187 Rev. 1 Table 125 Plenum dimensions, in. (mm)—28-105kW (8-30 ton), upflow Grille Size, in (mm) Nominal Dimensions, in. (mm) Front/Rear Grilles Model A B 28-42kW (8-12 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 28-42kW (8-12 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 53-77kW (15-22 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 53-77kW (15-22 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 59-1/4 (1505) 59-1/4 (1505) 82-1/4 (2089) 82-1/4 (2089) 13-3/4 (349) 26-3/4 (679) 15-3/4 (400) 26-3/4 (679) 105kW (30 ton)—All Models 105-1/4 (2673) 26-3/4 (679) Source: DPN001187, Rev. 1 Liebert® DS™ 156 18 x 55 (457 x 1397) 18 x 55 (457 x 1397) 18 x 78 (457 x 1981) 18 x 78 (457 x 1981) (1) 18 x 20 (457 x 508) (1) 18 x 78 (457 x 1981) Side Grille 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) Height in. (mm) H 20 (508) 24 (610) 30 (762) 36 (914) Guide Specifications 5.0 GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY These specifications describe requirements for a Data Center Cooling system. The system shall be designed to control temperature and humidity conditions in rooms containing computers or electronic equipment, with good insulation and vapor barrier. 1.2 DESIGN REQUIREMENTS The cooling system shall be a Liebert self-contained, factory-assembled unit with downflow or upflow air delivery. The system shall have a net total cooling capacity of ____ kW (BTUH) with a net sensible cooling capacity of ____ kW (BTUH) based on an entering air temperature of ____ °F (°C) dry bulb and ____ °F (°C) wet bulb, based on ASHRAE127 rating method and test method. Net capacities shall include losses due to fan motor heat. The unit is to be supplied with ____ volt ____ ph ____ Hz electrical service. The indoor cooling unit shall have a short circuit current rating (SCCR) of 65,000A RMS symmetrical, determined in accordance with the U.S. National Electric Code Section 409, Standard 508a SB, based on test data performed at certified third-party laboratories. 1.3 SUBMITTALS Submittals shall be provided after the agreement of the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical and Capacity Data; and Piping and Electrical Connection Drawings. 2.0 PRODUCT 2.1 FRAME The modular constructed frame shall be welded, formed sheet metal. It shall be protected against corrosion using the autophoretic coating process. The frame shall be capable of being separated into three parts in the field to accommodate rigging through small spaces. 2.1.1 Downflow Air Supply, Bottom Supply, Front Throw, Centrifugal fans The supply air shall exit from the bottom of the unit with the air thrown toward the front of the unit. 2.1.1 Downflow Air Supply, EC Fans The supply air shall exit from the bottom of the unit, with the ability to operate the fans within the floor stand (requires minimum 24" raised floor height), throwing the air in a horizontal direction. 2.1.1 Downflow Air Supply, Front Supply (or Rear Supply), EC Fans The supply air shall exit from the front of the unit utilizing direct drive EC fans. 2.1.1 Downflow Air Return The return air shall enter the unit from the top. 2.1.1 Upflow Top Air Supply, Front Throw The supply air shall exit from the top of the cabinet with the air throw towards the front. 2.1.1 Upflow Top Air Supply, Rear Throw The supply air shall exit from the top of the cabinet with the air throw towards the back. 2.1.1 Upflow Air Return, Front The return air shall enter the unit from the front of the cabinet through factory installed grilles. Grilles shall be painted black. 2.1.1 Upflow Air Return, Rear The return air shall enter the unit from the back of the cabinet. 157 Liebert® DS™ Guide Specifications 2.1.2 Exterior Panels The exterior panels shall be insulated with a minimum 1 in. (25mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall have captive 1/4 turn fasteners. The main unit color shall be ______. 2.1.2.1 Double-Skin Panels (Optional) The exterior panels shall be internally lined with 20 gauge sheetmetal, sandwiching the insulation between the panels, for easy cleaning. 2.2 FILTERS—DOWNFLOW UNIT The filter chamber shall be located within the cabinet, and filters shall be removable from the top of the unit. 2.2.1 Filters, 4" Filters shall be deep pleated 4" filters with an ASHRAE 52.2 MERV8 rating (45% ASHRAE 52.1) or ASHRAE 52.2 MERV11 rating (60-65% ASHRAE 52.1). 2.2.1 Filters, 2" Pre-Filter With 2" Filter Filters shall be 2" ASHRAE 52.2 MERV8 (40% ASHRAE 52.1) pre-filter, with 2" ASHRAE 52.2 MERV11 (60-65% ASHRAE 52.1) efficiency filter. 2.2.2 Extra Filter Set ____ extra set(s) of filters shall be provided per system. 2.3 FAN SECTION 2.3.1 Centrifugal Blower Section The blower section shall be designed for ___ CFM (CMH) at an external static pressure of ___ in. wg. (Pa). The fans shall be the centrifugal type, double width double inlet and shall be dynamically balanced as a completed assembly. The shaft shall be heavy duty steel with self-aligning, permanently sealed, pillow block bearings with a minimum L3 life of 200,000 hours. The fans shall draw air through the A-frame coil to ensure even air distribution and maximum coil performance. A static regain duct shall be factory-installed to the bottom of the blower on downflow units. 2.3.1.1 Motor The fan motor shall be ____ hp (kW) at 1750 rpm @60hz (1450 rpm @50hz), mounted to an automatic, spring tensioning base. The motor shall be removable from the front of the cabinet. 2.3.1.1.1 Premium Efficiency Motor The fan motor shall be Open Drip-Proof, Premium efficiency and shall meet NEMA Premium standard. Motor efficiency shall be ____%. 2.3.1.1.1 TEFC Motor (Optional) The motor shall be Totally Enclosed Fan Cooled for protection in harsh environments. 2.3.1.2 Drive Package The motor sheave and fan pulley shall be double-width, fixed-pitch. Two belts, sized for 200% of the fan motor horsepower shall be provided with the drive package. An auto-tension system shall provide constant tension on the belts. Belts, shaft, blower bearings, sheave and pulley shall be warranted for five years (parts only). Liebert® DS™ 158 Guide Specifications 2.3.1 Electronically Commutated (EC) Fan, Direct-Drive, Variable Speed The fans shall be plug/plenum type, single inlet and shall be dynamically balanced, and the drive package shall be direct drive, electronically commutated and variable speed. The fans shall be located to draw air over the A-frame coil to ensure even air distribution and maximum coil performance. EC fans shall be available on Downflow models only, and fans may be field- lowered into a raised floor with minimum height of 24" in order to achieve more efficient fan operation. EC fans may operate within the Liebert DS cabinet, instead of underfloor. DS053, DS070, DS077 fan motor(s) shall be nominal 4.15 hp each with a maximum operating speed of 1510 rpm; quantity, two. DS105 fan motor(s) shall be nominal 3.62 hp each, with a maximum operating speed of 2150 rpm; quantity, three. 2.4 HUMIDIFIER A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable moisture to be absorbed into the air stream. The humidifier capacity shall be ____lb./hr (kg/hr). The humidifier shall be removable from the front of the cabinet. 2.4.1 Infrared Humidifier The humidifier shall be of the infrared type consisting of high intensity quartz lamps mounted above and out of the water supply. The humidifier pan shall be stainless steel and arranged to be removable without disconnecting high voltage electrical connections. The complete humidifier section shall be pre-piped, ready for field connection to water supply. The humidifier shall be equipped with an automatic water supply system and shall have an adjustable water-overfeed to prevent mineral precipitation. A high-water detector shall shut down the humidifier to prevent overflowing. A factory-provided air-gap shall prevent backflow of the humidifier supply water. 2.4.1 Steam Generating Canister Humidifier A canister-type steam canister shall be factory-installed in the cooling unit and shall be controlled by the microprocessor control system. It shall be complete with disposable canister, all supply and drain valves, steam distributor and electronic controls. The need to change canister shall be indicated on the microprocessor control panel. The humidifier shall be designed to operate with water conductivity from 200-500 micromhos. An air-gap within the humidifier assembly shall prevent backflow of the humidifier supply water. Not available with EC fans or on upflow configurations. 2.5 REHEAT The indoor cooling unit shall include a factory-installed reheat to control temperature during dehumidification. 2.5.1 Three-Stage Electric Reheat The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction, protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The reheat elements shall be removable from the front of the cabinet. 2.5.1 SCR Electric Reheat The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction, protected by thermal safety switches, ____ kW (____ BTUH) controlled by multiple pulses to achieve tight temperature control. The reheat elements shall be removable from the front of the cabinet. Available on indoor units with standard Scroll compressors, only. 2.6 DUAL REFRIGERATION SYSTEM Each unit shall include two (2) independent refrigeration circuits and shall include hot gas mufflers (semi-hermetic compressors units only), liquid line filter driers, refrigerant sight glass with moisture indicator, externally equalized expansion valves and liquid line solenoid valves. Compressors shall be located outside the airstream and shall be removable and serviceable from the front of the unit. 159 Liebert® DS™ Guide Specifications 2.6.1 Semi-Hermetic Compressor With Four-Step Unloaders Control The compressor shall be semi-hermetic with a suction gas cooled motor, vibration isolators, thermal overloads, oil sight glass, automatic reset high pressure switch with control lockout after three failures, low pressure transducer, suction line strainer, crankcase heaters, service valves, reversible oil pumps for forced feed lubrication, a maximum operating speed of 1750 rpm. The system shall include cylinder unloaders on the semi-hermetic compressors. The unloaders shall be activated by solenoid valves which are controlled from the microprocessor control. In response to the return air temperature, the microprocessor control shall activate the unloader solenoids and the liquid line solenoids such that four stages of refrigeration cooling are obtained. The stages shall be: 1) one compressor, partially loaded, 2) two compressors partially loaded, 3) one compressor partially loaded, one compressor fully loaded, 4) two compressors fully loaded. On a call for dehumidification, the microprocessor control shall insure that at least one compressor is on full for proper humidity control. Hot Gas bypass shall not be an acceptable means of capacity control due to increased energy consumption. 2.6.1 Scroll Compressors The compressor shall be scroll-type with a variable capacity operation capability. Compressor solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor shall be suction gas cooled motor, vibration isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures, rotalock service valves, crankcase heaters, low pressure transducer, suction line strainer, and a maximum operating speed of 3500 rpm. Hot gas bypass shall not be an acceptable means of capacity control, due to increased energy consumption. 2.6.1 Digital Scroll Compressors The compressor shall be variable capacity, scroll-type, capable of operating between 20% and 100% compressor capacity. The compressor shall be suction gas cooled motor, vibration isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures, rotalock service valves, crankcase heaters, low pressure transducer, suction line strainer and a maximum operating speed of 3500 rpm. Hot gas bypass shall not be acceptable means of capacity control, due to increased energy consumption. 2.6.2 Evaporator Coil, DX Coil The evaporator coil shall be A-frame design with offset orientation and have ____sq. ft. (m2) face area, three rows deep. It shall be constructed of rifled copper tubes and aluminum fins and have a maximum face velocity of ____ ft. per minute (m/s) at ____ CFM (CMH). A stainless steel condensate drain pan shall be provided. 2.6.2.1 Polymeric Coating (Optional) The coil shall be coated with a high performance polymeric coating process to provide corrosion resistance within 2 to 12 pH range. 2.6.3 R-407C Refrigerant, non-HCFC The system shall be designed for use with R-407C refrigerant, which meets the EPA clean air act for phase-out of HCFC refrigerants. Liebert® DS™ 160 Guide Specifications 2.7 LIEBERT iCOM™ MICROPROCESSOR CONTROL WITH SMALL GRAPHIC DISPLAY The Liebert iCOM unit control shall be factory-set for Intelligent Control, which uses “fuzzy logic” and “predictive” methods. Proportional and Tunable PID shall also be user-selectable options. Internal unit component control shall include the following: Compressor Short Cycle Control—Prevents compressor short-cycling and needless compressor wear. System Auto Restart—The auto restart feature shall automatically restart the system after a power failure. Time delay is programmable. Sequential Load Activation—On initial startup or restart after power failure, each operational load is sequenced with a minimum of one second delay to minimize total inrush current. Econ-O-Coil Flush Cycles—Econ-O-Coils are periodically flushed to prevent a buildup of contaminants. Predictive Humidity Control—Calculates the moisture content in the room and prevents unnecessary humidification and dehumidification cycles by responding to changes in dew point temperature. The Liebert iCOM control shall be compatible with all Liebert remote monitoring and control devices. Options are available for BMS interface via Modbus, BACnet and SNMP. The Liebert iCOM control processor shall be microprocessor based with a 128x64 dot matrix graphic front monitor display and control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable while the unit panels are open or closed. The controls shall be menu driven. The display shall be organized into three main sections: User Menus, Service Menus and Advanced Menus. The system shall display user menus for active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in % of each function, date and time), total run hours, various sensors, display setup and service contacts. A password shall be required to make system changes within the service menus. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep mode, alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network setup, auxiliary boards and diagnostics/service mode. A password shall be required to access the advanced menus, which include the factory settings and password menus. The User Menus Shall be Defined as Follows: Active Alarms: Unit memory shall hold the 200 most recent alarms with time and date stamp for each alarm. Event Log: Unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event. Graphic Data View: Eight graphic records shall be available: return air temperature, return air humidity, supply air temperature, outdoor temperature and four custom graphs. Unit View - Status Overview: Simple or Graphical “Unit View” summary displays shall include temperature and humidity values, active functions (and percent of operation) and any alarms of the host unit. Total Run Hours: Menu shall display accumulative component operating hours for major components including compressors, Econ-O-Coil (FC), fan motor, humidifier and reheat. Various Sensors: Menu shall allow setup and display of optional custom sensors. The control shall include four customer accessible analog inputs for sensors provided by others. The analog inputs shall accept a 4 to 20 mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC if desired. The gains for each analog input shall be programmable from the front display. The analog inputs shall be able to be monitored from the front display. Display Setup: Customer shall pre-select the desired grouping of display languages at the time of the order from the following choices: Group 1: English, French, Italian, Spanish, German Group 2: English, Russian, Greek Group 3: English, Japanese, Chinese, Arabic Service Contacts: Menu shall allow display of local service contact name and phone number. 161 Liebert® DS™ Guide Specifications The Service Menus Shall be Defined as Follows: Setpoints: Menu shall allow setpoints within the following ranges: • Temperature Setpoint: 65-85ºF (18-29ºC)* • Temperature Sensitivity: +1-10ºF (0.6-5.6ºC) • Humidity Setpoint: 20-80% RH* • Humidity Sensitivity: 1-30% RH • High Temperature Alarm: 35-90ºF (2-32ºC) • Low Temperature Alarm: 35-90ºF (2-32ºC) • High Humidity Alarm: 15-85% RH • Low Humidity Alarm: 15-85% RH * The microprocessor may be set within these ranges, however, the unit may not be able to control to extreme combinations of temperature and humidity. Standby Settings/Lead-Lag: Menu shall allow planned rotation or emergency rotation of operating and standby units. Timers/Sleep Mode: Menu shall allow various customer settings for turning On/Off unit. Alarm Setup: Menu shall allow customer settings for alarm notification (audible/local/remote). The following alarms shall be available: • High Temperature • Low Temperature • High Humidity • Low Humidity • Compressor Overload (Optional) • Main Fan Overload (Optional) • Humidifier Problem • High Head Pressure • Change Filter • Fan Failure • Low Suction Pressure • Unit Off Audible Alarm: The audible alarm shall annunciate any alarm that is enabled by the operator. Common Alarm: A programmable common alarm shall be provided to interface user-selected alarms with a remote alarm device. Remote Monitoring: All alarms shall be communicated to the Liebert monitoring system with the following information: date and time of occurrence, unit number and present temperature and humidity. Sensor Calibration: Menu shall allow unit sensors to be calibrated with external sensors. Maintenance/Wellness Settings: Menu shall allow reporting of potential component problems before they occur. Options Setup: Menu shall provide operation settings for the installed components. System/Network Setup: Menu shall allow Unit-to-Unit (U2U) communication and setup for Teamwork modes of operation (up to 32 units). Teamwork Modes of Operation: Saves energy by preventing operation of units in opposite modes multiple units. Auxiliary Boards: Menu shall allow setup of optional expansion boards. Diagnostics/Service Mode: The Liebert iCOM control shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as on or off at the front display. Control outputs shall be able to be turned on or off from the front display without using jumpers or a service terminal. An LED on a circuit board will indicate each control output. The Advanced Menus Shall be Defined as Follows: Factory Settings: Configuration settings shall be factory-set based on the pre-defined component operation. Change Passwords: Menu shall allow new passwords to be set or changed. Liebert® DS™ 162 Guide Specifications 2.7 LIEBERT iCOM™ MICROPROCESSOR CONTROL WITH LARGE GRAPHIC DISPLAY (OPTIONAL) The Liebert iCOM unit control with large graphic display shall include all of the features as the Liebert iCOM with small graphic display, except that it includes a larger graphical display and shall include the additional features of: System View, Spare Parts List, Unit Diary. The Liebert iCOM control processor shall be microprocessor based with a 320x240 dot matrix graphic front monitor display panel and control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. System View - Status Overview: System View shall display a summary of operation for the total number of operating units within a Unit-to-Unit (U2U) configuration. Spare Parts List: Menu shall include a list of critical spare parts, their quantity and part numbers. Unit Diary: Menu shall include a free field area within the unit memory where unit history may be stored for reference. 2.7 LIEBERT iCOM WALL MOUNT LARGE GRAPHIC DISPLAY vNSA PANEL (OPTIONAL) The Liebert iCOM Large Graphic Display Kit shall include an ergonomic, aesthetically pleasing housing, a 320x240 dot matrix graphic display and a 120V power supply. The Wall Mount Large Graphic Display shall be used to allow remote location of a System View display and all features of the Large Graphic User, Service and Advanced menus for use with Liebert iCOM controlled products connected for Unit-to-Unit (U2U) communications. This panel is also used to network together so they can be place in 1 of the 3 team work modes and lead/lag standby rotation as well as cascade mode. 2.8 DUAL-COOLING CHILLED WATER COIL The dual-cooling source system shall consist of an air- or water-cooled compressorized (DX) system with the addition of a chilled water coil, a modulating control valve and a comparative temperature sensor. The system shall be able to function either as a modulating chilled water system or as a compressorized (DX) system, or a combination of both. The primary cooling mode shall be chilled water, if available. Switchover between the two cooling modes shall be performed automatically by the microprocessor control. Four (4) pipes shall be included on water/glycol systems: chilled water supply, chilled water water return, condenser water supply and condenser water return. Four pipes shall be included on air-cooled systems: chilled water supply, chilled water return, hot gas refrigerant line, liquid refrigerant line. 2.8.1 Dual-Cooling Source Control Valve The chilled water circuit shall include a three-way modulating valve. The microprocessor shall position the valve in response to room conditions. Cooling capacity will be controlled by bypassing chilled water around the coil. The modulating valve travel for dehumidification shall be proportional. 2.8.1 CuNi Coil Chilled Water Coil (Optional) A 70/30 CuNi chilled water shall be provided for Dual-Cooling units that are applied to a cooling tower loop or other open water system. This option is required on open cooling tower applications, and constant chilled water flow must be provided in order to periodically circulate chilled water through the coil when idle. 2.8.1.1 Polymeric Coating on Liebert Econ-O-Coil™ and DX Coil (Optional) The coil shall be coated with a high performance polymeric coating process to provide corrosion resistance on the exterior of the coil, within 2 to 12 pH range. 2.9 MISCELLANEOUS OPTIONS 2.9.1 Non-Locking Disconnect Switch (Optional) The manual disconnect switch shall be mounted in the high- voltage section of the electrical panel. The switch shall be accessible with the door closed. 163 Liebert® DS™ Guide Specifications 2.9.1 Locking Disconnect Switch (Optional) The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible from the outside of the unit with the door closed and prevent access to the high voltage electrical components until switched to the “OFF” position. 2.9.2 High-Temperature Sensor (Optional) The high-temperature sensor shall be factory-installed in the unit and shall be factory-set to 125ºF (52ºC). It shall immediately shut down the environmental control system when activated. The sensor shall be mounted with the sensing element in the return air. 2.9.3 Smoke Sensor (Optional) The smoke sensor shall immediately shut down the environmental control system and activate the alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the sensing element in the return air compartment. The smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes. The smoke sensor shall include a supervision contact closure. 2.9.4 Condensate Pump, Dual Float (Optional) The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft. (58 kPa) head. It shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition. 2.9.5 Low-Voltage Terminal Package (Optional) Factory-installed and wired terminals shall be provided for customer connection to lock out the reheat and humidifier upon contact closure. Two extra N/O common alarm contacts shall be provided. Two extra remote shutdown terminals shall be provided. 2.9.6 Remote Humidifier Contact (Optional) A pair of N/O contacts shall be provided for connection to a remote humidifier. 2.9.7 Main Fan Overload (Optional) A pair of N/O contacts shall be factory-installed and wired to indicate Main Fan Overload. 2.9.8 Compressor Overload (Optional) A pair of N/O contacts shall be factory-installed and wired to each compressor to indicate Compressor Overload. 2.10 AIR-COOLED SYSTEMS The indoor evaporator unit shall include refrigerant piping, with a factory holding charge of nitrogen. The hot-gas and liquid lines shall be spun shut and shall include a factory-installed Schrader valve. Field-relief of the Schrader valve shall indicate a leak-free system. Air-cooled systems shall be fieldpiped and wired to a condenser, using field-supplied refrigerant piping and wiring. The system shall be field-charged with refrigerant, supplied by others. 2.10.1 Standard Features—Air-Cooled Microchannel Condenser Design Condenser shall consist of microchannel condenser coil(s), propeller fan(s) direct-driven by individual fan motor(s), electrical controls, housing and mounting legs. The Liebert air-cooled condenser shall provide positive refrigerant head pressure control to the Precision Cooling indoor unit by adjusting heat rejection capacity. Microchannel coils shall provide superior heat transfer, reduce air-side pressure drop, increase energy efficiency and significantly reduce the system refrigerant volume required. EC fans and fan operating techniques shall provide reduced maximum sound levels. Various methods shall be available to match indoor unit type, maximum outdoor design ambient and maximum sound requirements. Liebert® DS™ 164 Guide Specifications 2.10.1.1 Aluminum Microchannel Coil Liebert microchannel coils shall be constructed of aluminum microchannel tubes, fins and manifolds. Tubes shall be flat and contain multiple, parallel flow microchannels and span between aluminum headers. Full-depth louvered aluminum fins shall fill spaces between the tubes. Tubes, fins and aluminum headers shall be oven brazed to form a complete refrigerant-to-air heat exchanger coil. Copper stub pipes shall be electric resistance welded to aluminum coils and joints protected with polyolefin to seal joints from corrosive environmental elements. Coil assemblies shall be factory leaktested at a minimum of 300 psig (2068kPag). Hot gas and liquid lines shall be copper and shall be brazed using nitrogen gas flow to the stub pipes with spun closed ends for customer piping connections. Complete coil/piping assembly shall be then filled and sealed with an inert gas holding charge for shipment. 2.10.1.1 Aluminum Microchannel Coil with E-Coat Aluminum microchannel coil with E-coat shall provide a flexible epoxy coating to all coil surface areas without material bridging between fins. E-coat shall increase coil corrosion protection and shall reduce heat rejection capacity degradation to less than 10% after a severe 2000 hour 5% neutral salt spray test (ref. ASTM B117). The coating process shall ensure complete coil encapsulation, and the color shall be black. 2.10.1.2 Fan Motor/Blade Assembly The fan motor/blade assembly shall have an external rotor motor, fan blades and fan/finger guard. Fan blades shall be constructed of cast aluminum or glass-reinforced polymeric material. Fan guards shall be heavy gauge, close meshed steel wire, coated with a black corrosion resistant finish. Fan terminal blocks shall be located in an IP54 enclosure located on the top of the fan motor. Fan assemblies shall be factory-balanced, tested before shipment and mounted securely to the condenser structure. 2.10.1.3 EC Fan Motor The EC Fan motors shall be electronically commutated for variable speed operation and shall have ball bearings. The EC fans shall provide internal overload protection through built-in electronics. Each EC fan motor shall have a built-in controller and communication module, linked via RS485 communication wire to each fan and the Premium Control Board, allowing each fan to receive and respond to precise fan speed inputs from the Premium Control Board. 2.10.1.4 Electrical Controls Electrical controls and service connection terminals shall be provided and factory wired inside the attached control panel section. A locking disconnect switch shall be factory-mounted and wired to the electrical panel and controlled via an externally mounted locking and lockable door handle. Only high-voltage supply wiring and low voltage indoor unit communication/interlock wiring are required at condenser installation. 2.10.1.5 EC Fan Speed & Premium Control The EC Fan/Premium Control System shall include an electronic control board, EC fan motor(s) with internal overload protection, refrigerant and ambient temperature thermistors and refrigerant pressure transducers. The control board shall receive an indoor unit run signal via field-supplied low voltage interlock wires to the compressor side switch, via field-supplied CANbus communication wires from the indoor unit's Liebert iCOM control (future feature) or via both. The control board shall use sensor and communication inputs to maintain refrigerant pressure by controlling each EC fan on the same refrigerant circuit to the same speed. 2.10.1.6 Cabinet The condenser cabinet shall be constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Internal structural support members, including coil support frame, shall be galvanized steel for strength and corrosion resistance. Panel doors shall be provided on two sides of each coil/fan section to permit coil cleaning. An electrical panel shall be contained inside a factory mounted, NEMA 3R weatherproof electrical enclosure. 165 Liebert® DS™ Guide Specifications 2.10.1.7 Mounting Legs 2.10.1.7.1 Standard Aluminum Legs Aluminum legs shall be provided to mount unit for vertical air discharge with rigging holes for hoisting the unit into position. Standard height is 18in. (457mm). 2.10.1.7.1 Optional Galvanized Steel Legs with Bracing Condensers shall be shipped with [36in. (914mm)] [48in. (1219mm)] [60in. (1524mm)] mounting legs with stabilization bracing. Legs, bracing and hardware shall be galvanized steel. 2.10.1 Air-Cooled Microchannel Condenser Accessories (Options) 2.10.1.1 Liebert Lee-Temp ™ Receiver Kit Liebert Lee-Temp Receiver Kit shall contain an insulated, heated receiver tank with sight glasses, mounting plate, mounting hardware, pressure relief valve, rotalock valve for refrigerant charge isolation and piping assembly with head pressure operated 3-way valve and check valve. Components shall be field-assembled to the condenser. The 3-way valve shall sense refrigerant head pressure and adjust the flooding charge in the condenser coil to adjust the condenser heat rejection capacity. The Liebert Lee-Temp heater shall be [(150W) (300W)], shall include an integral thermostat to maintain refrigerant temperature at a minimum of 85°F (29°C) and shall require a separate power supply of [(208/230-1-60) (120-1-60 volt)]. The Liebert Lee-Temp Kit shall function with Liebert MC variable speed fan motors and electronic controls that lower fan speed in lower outdoor ambient temperatures for maximum energy efficiency. This system shall allow system startup and positive head pressure control with ambient temperatures as low as -30°F (-34.4°C). 2.10.1.2 Fusible Plug Kit A fusible plug kit shall be field-installed on the liquid line for compliance with building codes requiring refrigerant relief during high temperature and building fire conditions. 2.10.1.3 IBC/OSHPD Seismic Certification and IBC Wind/Snow Load Complaint IBC/OSHPD Seismic Certification and IBC Wind/Snow Load Compliant condensers shall be provided with any applicable bracing and field installation instructions. Condensers shall bear a label certifying compliance with IBC/OSHPD requirements. 2.10.1.3.1 Seismic IBC/OSHPD (Optional) Install condenser in accordance with manufacturer's installation instructions provided with seismic option. Firmly anchor maintaining manufacturer's recommended clearances. Mounting requirement details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor spacing, concrete strength, special inspection and attachment to non-building structures must be outlined and approved by the Engineer of Record for the projection or building. Wiring and piping connections must permit movement in three dimensions and isolate the unit from field connections. Electrical conduit shall be flexible having at least one bend between the rigid connection at the unit cabinet and the connection to rigid conduit or foundation. The piping flexible connection or loop must be suitable for the operation pressure and temperature of the system. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 2.10.1 Standard Features—Air-Cooled Condenser, Fin-Tube Coil Design The Liebert-manufactured outdoor air-cooled condenser shall be the low-profile, multiple direct drive, propeller fan type. The condenser shall balance the heat rejection of the compressor at ____ °F (°C) ambient. The condenser shall be constructed of aluminum and contain a copper tube, aluminum fin coil arranged for (horizontal) (vertical) air discharge. 2.10.1.1 Fan Speed Head Pressure Control The winter control system for the air-cooled condenser shall be Liebert Fan Speed Control. The variable speed motor shall operate from 0 to 230 volts single phase, 10 to 1050 rpm. It shall be designed with ball bearings, permanent lubrication, internal overload protection, 40°C rise at full speed, 65°C rise at 10 rpm. The control system shall be complete with transducers, thermostats and electrical control circuit, factory prepackaged in the integral condenser control box. The transducer shall automatically sense the highest head pressure of either operating compressor and control the Liebert® DS™ 166 Guide Specifications variable speed fan on the air-cooled condenser to properly maintain the head pressure. The Liebert Fan Speed Control system shall provide positive startup and operation in ambient temperatures as low as -20°F (-28.9°C). The air-cooled condenser shall have a ____ volt, ____ ph ____ Hz power supply. ™ 2.10.1.2 Liebert Lee-Temp , Heated Receiver Head Pressure Control System The winter control system for the air-cooled condenser shall be Liebert Lee-Temp. The Liebert Lee-Temp system shall allow startup and positive head pressure control with ambient temperatures as low as -30°F (-34.4°C). The Liebert Lee-Temp package shall include the following components for each refrigeration circuit: insulated receiver, pressure relief valve, head pressure three-way control valve and rotalock valve for isolating the refrigerant charge. The Liebert Lee-Temp receiver shall be factory-insulated and mounted ready for the field connection to the air-cooled condenser. The Liebert Lee-Temp heater shall require a separate power supply of ____ volt, single phase. 2.10.1 Standard Features—Liebert Quiet-Line Condenser Fin-Tube Coil Design (Optional) Fan motors shall be 12-pole, 570 rpm, equipped with rain shields and permanently sealed ball bearings. Motors shall include built-in overload protection. Motors shall be rigidly mounted on die-formed galvanized steel supports. Disconnect switch shall be a standard feature. 2.10.2.1 Condenser Disconnect Switch (Optional) A disconnect switch shall be factory-mounted and wired to the condenser control panel, accessible from the exterior (standard on Quiet-Line models). 2.10 WATER/GLYCOL SYSTEMS The indoor evaporator unit shall include factory installed refrigerant piping, and factory charged with R-407C refrigerant. Water/glycol systems shall be field piped to an external heat rejection source such as a cooling tower (by others) or drycooler with pump package. 2.10.1 Paradenser™ Cleanable Shell and Tube Condenser The water-cooled condensers for each circuit shall be cleanable, shell-and-tube, counter flow type. The heads shall be removable to allow for cleaning of the water tubes. Condensers shall be rated for a maximum refrigerant pressure of 400 psi at 200°F (2758 kPa at 93.3°C). The condenser shall be capable of operating with R-407C refrigerant. The unit shall require ____ GPM (l/m) of ____ °F (°C) water and have a maximum pressure drop of ____ psi (kPa). 2.10.2 Water/Glycol Regulating Valve, Two-Way with Adjustable Bypass Valve The condenser shall be pre-piped with a two-way regulating valve which is head pressure actuated. A gate valve shall bypass the regulating valve. 2.10.2 Water/Glycol Regulating Valve, Three-Way The condenser shall be pre-piped with a three-way regulating valve which is head pressure actuated. 2.10.2 Pressure Rating, 150 psi (1034 kPa), Scroll and Semi-Hermetic Compressors The condenser water circuit shall be designed for a pressure of 150 psi (1034 kPa) 2.10.3 Pressure Rating, 350 psi (2413 kPa), Scroll and Semi-Hermetic Compressors The condenser water circuit shall be designed for a pressure of 350 psi (2413 kPa) 2.10.3 Pressure Rating, 350psi (2413 kPa), Digital Scroll Models The condenser water circuit shall be designed for a pressure of 350 psi (2413 kPa), using motorized ball-valves to control refrigerant head pressure. 167 Liebert® DS™ Guide Specifications 2.10.3 GLYCOOL Fluid Economizer Systems In addition to the DX (refrigerant) evaporator coil, a factory piped fluid economizer coil shall enable the system to operate in Economizer mode when the water/glycol temperature is at least 7°F lower than the return air temperature to the indoor unit. The system shall operate in partial economization, supplemented by DX operation and in full economization when fluid temperatures are low enough to offset room load. The economizer control system shall be factory installed and wired, and shall automatically control switchover between economizer mode and DX mode. 2.10.3.1 GLYCOOL™ (Economizer) Coil The GLYCOOL Economizer coil shall be constructed of copper tubes and aluminum fins. The coil shall be A-frame or V-frame in order to minimize air pressure drop and maximize cooling capacity, and shall be nested with the DX coil. The Econ-O-Coil shall be upstream of the DX coil to enable precooling of the air, during partial economizer operation. A constant flow of water shall be available to enable the system to periodically flush the economizer coil of sediments that could cause pit corrosion if not flushed out of the coil. The Economizer coil shall have a net Sensible Cooling Capacity of ____ BTUH (kW) with 45°F (7.2°C) entering glycol solution temperature. The total system shall require ____ GPM (l/s) and the total unit pressure drop shall not exceed ____ feet of water (kPa), when in the economizer mode of operation. 2.10.3.2 GLYCOOL Three-Way Control Valve The GLYCOOL Economizer coil shall be equipped with a fully proportional 3-way control valve, designed for a maximum operating pressure of 150psi (1034 kPa). This motorized control valve shall control the amount of flow to the economizer coil to control room temperature and relative humidity. 2.10.3.3 High-Pressure System, 350 psi (2413 kPa) (Option) The GLYCOOL Economizer system shall be designed for a water/glycol static pressure of 350 psi (2413 kPa). 2.10.4.3 CuNi Economizer Coil to Inhibit Coil Corrosion A 70/30 CuNi Econ-O-Coil shall be provided when the Econ-O-Coil is connected to a cooling tower loop or other open water system. This option is required on open cooling tower applications in order to inhibit internal coil corrosion, due to lack of proper water system treatment and lack of fluid circulation through the coil. 2.11 DRYCOOLER GLYCOL FLUID COOLER The drycooler shall be the low profile, slow speed, multiple direct drive, propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an integral electric control panel and disconnect switch. The drycooler shall be designed for ____ °F (°C) ambient. 2.11.1 Pump Package, Glycol System This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclosure. The pump shall be rated for ____ GPM (l/m) at ____ ft. of head (kPa) and operate on ____ volt, 3-phase, ____ Hz. 2.11.1 Dual Pump Package, Glycol System The dual pump package shall include pumps, enclosure, field-mounted flow switch and a separate factory-wired control box (including a lead/lag switch for the pumps). The standby pump shall automatically start upon failure of the lead pump. Each pump shall be rated for ____ GPM (l/s) at ____ feet of head (kPa). Liebert® DS™ 168 Guide Specifications 2.12 LIEBERT LIQUI-TECT® SENSORS Provide ____ (quantity) solid-state water sensors under the raised floor. 2.13 FLOOR STAND The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs with vibration isolation pads. The floor stand shall be ____ in. (mm) high. 2.13.1 Seismic Rated Floor Stand (Optional) The floor stand shall be seismic rated and shall be field-attached to the unit frame, and to the floor. 2.13.2 Floor Stand Turning Vane (Optional) A turning vane shall be supplied with the floor stand and shall be designed for the specified floor stand height. 2.14 RETURN AIR PLENUM FOR DOWNFLOW UNITS The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum shall be ___" high. A door shall be included in the front of the plenum to enable front filter access. Air shall enter the plenum from the top. 2.14 DISCHARGE AIR PLENUM FOR UPFLOW UNITS, WITH DISCHARGE GRILLE(S) The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum shall be ___" high. Discharge air grilles shall be painted black and shall be included on the [front], [rear], [left side], or [right side] of the plenum. 2.14 DISCHARGE AIR PLENUM FOR UPFLOW UNITS, WITHOUT DISCHARGE GRILLE(S) The air plenum shall be constructed of 20 gauge steel, powder coated to match unit color. The plenum shall be ___" high. Air shall discharge from the top of the plenum. 3.0 EXECUTION 3.1 INSTALLATION OF PRECISION AIR CONDITIONING UNITS 3.1.1 General Install precision air conditioning units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated and maintain manufacturer's recommended clearances. 3.1.2 Electrical Wiring Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor. 3.1.3 Piping Connections Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 3.1.4 Field Quality Control Start cooling units in accordance with manufacturer's startup instructions. Test controls and demonstrate compliance with requirements. These specifications describe requirements for a computer room environmental control system. The system shall be designed to maintain temperature and humidity conditions in the rooms containing electronic equipment. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements. 169 Liebert® DS™ Guide Specifications Liebert® DS™ 170 Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2013 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 SL-18815_REV5_11-13 Emerson Network Power Division: Liebert Web: www.emerson.com www.EmersonNetworkPower.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Create Date : 2013:11:20 16:58:53Z Creator : FrameMaker 9.0 Modify Date : 2013:11:21 10:46:47-05:00 XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Creator Tool : FrameMaker 9.0 Metadata Date : 2013:11:21 10:46:47-05:00 Producer : Acrobat Distiller 10.1.8 (Windows) Document ID : uuid:73f34390-433d-4bf8-8638-684500985e1c Instance ID : uuid:bb22748a-ccea-423d-a731-8ca436cff5a9 Format : application/pdf Page Mode : UseOutlines Page Count : 176EXIF Metadata provided by EXIF.tools