Emerson Liebert Intellislot Web 485 Design Installation And Maintenance Guide 29105

2015-01-05

: Emerson Emerson-Liebert-Intellislot-Web-485-Design-Installation-And-Maintenance-Guide-165182 emerson-liebert-intellislot-web-485-design-installation-and-maintenance-guide-165182 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadEmerson Emerson-Liebert-Intellislot-Web-485-Design-Installation-And-Maintenance-Guide- 29105  Emerson-liebert-intellislot-web-485-design-installation-and-maintenance-guide
Open PDF In BrowserView PDF
LIEBERT INTELLISLOT® WEB/485 CARD W ITH ADAPTER
Product Specification/Installation Sheet
Description
The IntelliSlot Web/485 Card with Adapter
provides 10/100baseT Ethernet Network and
Modbus connectivity for your Emerson Network
Power equipment.
Operating status is monitored and alarms are
communicated via the network, using SNMP
and/or HTTP protocols and over RS-485 using
the Modbus protocol.

Additional Features
• SNMP v1, v2c with MIB-II support
• HTTP/HTTPS 1.1
• Telnet

• BootP, DHCP per RFC2131
• Secure Sockets (SSL)
• Remote firmware updates via HTTP

Compatibility With Other Emerson Network Power Products
Precision Cooling Unit (Controller*)

* Controller Codes

• Liebert Challenger™ 3000 (L00, L15,
LSM, LAM)
• Liebert DataMate™ (L0B)
• Liebert Deluxe System/3™ (L10, L15,
LSM, LAM)
• Liebert Himod™ (LAM)
• Liebert Industrial Cooling Series™
(L10, LSM, LAM)
• Liebert Mini-Mate™ (L0B)
• Liebert Mini-Mate2™ (MM2)
• Liebert Mini-Mate2 8 Ton (L8T)
• Hiross™ Microface IGMnet
• PEC/Atlas™ (CEMS100/LECS15)

L00: Level 00
L0B: Level 0B
L10: Level 10
L15: Level 15
LSM: Standard
Microprocessor
LAM: Advanced
Microprocessor

Large UPS
•
•
•
•

Liebert Npower™
Liebert Series 300™
Liebert Series 600™/610™ (Single Module)
Liebert Series 610 System Control Cabinet
(Multi-Module)
• Hiross 7200 (EMEA)
• Hiross HiPulse™ (EMEA)
Power Management
•
•
•
•

Liebert Datawave®
Liebert FPC™
Liebert Precision Power Center™
Liebert Static Transfer Switches:
STS™, STS2-3 pole, STS2/PDU

Overall and Mounting Dimensions
0.6" (15.3mm)

7" (177.8mm)

2.8"
(71.1mm)

3.4"
(86.4mm)

0.8" (20.3mm)

Six holes, each
0.156" diameter

2.4"
(61mm)

4"
(101.6mm)

0.4" (10.2mm)
0.2" (5mm)
3.2"
(81.3mm)

1

Customer Wiring
Input power
(input to TB3)
Pin 1(+)
Pin 2(-)
Pin 3 (NC)

Network port
for NMS and
Web access

Modbus output
for BMS
(output from TB2)

DTE serial port
for configuration
(requires null-modem
connection)

TB1: Pin 1 (+), Pin 2 (-)
TB2: Pin 1 (+), Pin 2 (-)

IGMnet or Liebert SiteScan® Comms
from unit (input to TB1 or P1)
Refer to user manual for details

Specifications
Power
Requirements

AC Inputs

18 - 24 VAC; 50/60 Hz

DC Inputs

12 - 36VDC

Power Consumption

6VA maximum

Dimensions - W x D x H: in. (mm)
Weight

7 x 4 x 1.5 (178 x 102 x 38)

Net - oz. (kg)

7 (0.2)

Shipping - lb. (kg)

1.3 (0.6)

Ambient Operating Environment, °F (°C)

32 to 104 (0 to 40); 10% to 90% RH (non-condensing)

Ambient Storage Temperature, °F (°C)

-4 to 140 (-20 to 60)

Protection

Communication
Ports

SELV Isolated User Connections, Watchdog Timer Circuitry
Service Terminal (RS-232)

DB9F, DTE

Unit Input
Communications

TB1, 2-Position Terminal Block
P1, 20-PIN Vertical Header with Ejection Latches (for some UPS models)

Modbus (RS-485)

TB2, 2-Position Terminal Block

Ethernet Communications

RJ45

Wiring Specifications
Connection

Supported Wire Types

Maximum Wire Length

TB1 (RS-422)

18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 9461; Plenum - Belden 88761

1000 ft. (300m)

TB2 (RS-485)

18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 9461; Plenum - Belden 88761

3000 ft. (915m)

TB3 (Power Input)

18-22 AWG Stranded & Shielded; 18 AWG* recommended
Non Plenum - Belden 8770; Plenum - Belden 88770

20 ft. (6m)

DB9F Connector

DTE Null Modem Cable

50 ft. (15m)

RJ45 Connector

Standard Category 5 Cable

328 ft. (100m)

Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229

Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com

© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.

® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-29105_REV02_10-07
2



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2003:04:22 15:34:10Z
Creator Tool                    : FrameMaker 7.2
Modify Date                     : 2007:11:05 14:02:57-05:00
Metadata Date                   : 2007:11:05 14:02:57-05:00
Format                          : application/pdf
Creator                         : Owner
Title                           : 29105.fm
Document ID                     : uuid:8d139453-e1e1-4b62-96df-7728a1a31872
Instance ID                     : uuid:947fdb40-f372-46ac-8fd1-3b3b9125a4c4
Page Count                      : 2
Author                          : Owner
EXIF Metadata provided by EXIF.tools

Navigation menu