Liebert® PSA™

Quick-Start Guide - 500VA/650VA, 120V
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS

• Connect the UPS only to an earthed / grounded outlet that meets national and local
electrical safety guidelines.
• Locate the UPS near a wall outlet. Do not use an extension cord between the UPS and
the outlet.
• The Liebert PSA has been designed for small office/home office use only; it is NOT
recommended for use in life-support applications.
• In the event of an emergency, press the OFF button and disconnect the power cord
from the AC power supply to properly disable the UPS.
• Do not attach power strips or surge suppressors to the UPS.
• Do not attempt to service any parts inside the UPS except the batteries. Failure to adhere
to this could cause personal injury or equipment malfunction and void the warranty.
• For technical support:
• Visit www.liebert.com or
• Send an e-mail to upstech@emersonnetworkpower.com.

This manual contains important instructions that should be followed during
installation and maintenance of the UPS.
• Intended for installation in a controlled environment.
• Maximum ambient temperature 104°F (40°C).

! CAUTION
To reduce the risk of fire, connect only to a circuit provided with
20 amperes maximum branch circuit overcurrent protection in
accordance with the national code, ANSI/NFPA 70.
• Do not connect equipment that may overload the UPS or demand half-wave
rectification, such as a laser printer.

SETUP
Step 1 Inspect the Package

Step 5 Check the Site Wiring Fault Indicator

Inspect the package and the UPS upon receipt. Notify the carrier and dealer of visible
damage.

See figure at right for the location of the Site Wiring Indicator on the rear of
the UPS.
• Check the rear of the UPS to make sure the Site Wiring Fault indicator is
NOT illuminated.
Caution: If the Site Wiring Fault indicator is illuminated, have a qualified
electrician check the wall receptacle wiring and fix any problems.

Liebert
shutdown
software
CD

Step 6 Connect the Loads
The UPS has three battery backup outlets that
provide power when the UPS operates on battery (see Figure 2 below).

Quick-start
guide
USB
cable

• Plug the loads into the battery backup outlets
on the rear of the UPS.

UPS

Step 2 Decide Where to Place the UPS

Caution: Do not connect a laser printer to the
UPS.

The UPS must be placed indoors, protected from water, direct
sunlight and excessive heat.

Step 7 Connect the Network Surge Protection
The UPS has two RJ-45 jacks for network lines (see
Figure 2 below).

Provide at least 4" (100mm) of clearance on all sides of the unit
for proper ventilation.

• Connect a single-line network cable into the RJ-45
network surge protection IN jack on the rear of the
UPS.
• Connect an RJ-45 cable from the OUT jack on the
rear of the UPS to a port on a PC or network device
such as a router.

Step 3 Charge the UPS Battery Before
Use
The UPS battery is not charged before shipping. It MUST be charged before use.
• Connect the UPS power cord to a wall outlet and charge for at least eight hours.

Step 8 Set Up Liebert shutdown software

Note: If battery is placed in storage, charge the battery every six months if kept at
5°F to 85°F (-15°C to 29°C)—or every three months if kept at 86°F (30°C) or higher.

To start using the Liebert shutdown software:

Step 4 Start the UPS
After the battery is fully charged:
• Turn on the UPS by pressing the On/Off button (see Figure 1 below).
LED 1 should be illuminated (green), indicating the UPS is operating in Normal Mode.

• Install the Liebert shutdown software. See the software
user manual for installation instructions.
• Connect one end of the USB cable (supplied) to the USB
port on the rear of the UPS. Connect the other end to a
USB port on the computer. See the software user manual
for operating instructions.

UPS CONTROLS AND CONNECTIONS
Figure 1 - Front Panel LEDs

Figure 2 - Rear Panel

On/Off button
LED 1
(green)

LED 2 (red = fault;
amber = overload)

!

Utility
symbol

Overload
symbol

Network Power

Liebert PSA

™

RJ-45 jacks (2) network protection
Input
breaker

Fault
symbol

EMERSON

Site Wiring
Fault indicator

USB
interface

®

NEMA
5-15P
Battery backup
outlets (3)
NEMA 5-15R

Surge outlet (1)
NEMA 5-15R

AC Power System

UPS Status, Alarm Conditions and Alerts
Condition

LED

Color

Solid/Flashing

Audible Alarm

Normal Mode

LED 1

Green

Solid (steady glow)

(None)

Battery Mode

LED 1

Green

Flashes every 3 seconds

Every 3 seconds

Battery Low

LED 1

Green

Flashes every 1 second till end of discharge (EOD)

Every 1 second

Overload

LED 2

Amber

Solid (steady glow) until load drops or breaker trips

Continuous

Battery Replacement

LED 2

Red

Flashes every 1 second for 5 seconds only

Every 1 second for 5 seconds only

Fault

LED 2

Red

Solid (steady glow) until UPS shuts down after 5 seconds

Continuous until UPS shuts down

REPLACING THE BATTERY
To replace the battery:
1.

Turn off all connected loads, then turn off the UPS (batteries are NOT
hot-swappable).

2.

Use a Phillips head screwdriver to remove the two screws from the bottom
edge of the front panel.

3.

Slide the panel downward and remove it.

4.

Gently pull the battery out of the UPS.

5.

Remove the black wire from the negative (-) terminal and the red wire from
the positive (+) terminal.

6.

Verify that the replacement battery matches the dimensions and battery
type in the Specifications section below.

7.

Connect the battery leads to the new battery. Be sure to reconnect the red
wire to the positive (+) terminal and the black wire to the negative (-)
terminal.

Steps 2 and 3

Steps 4 and 5

Note: Small sparks may occur at the battery connectors during
reconnection.
8.

Slide the battery into the UPS.

9.

Close the front panel and replace the two screws from Step 2.

Dispose of the old battery properly at an appropriate recycling facility.

TROUBLESHOOTING
If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Emerson Network Power representative.
Problem

Possible Causes

Solutions

The UPS may not be turned on.

• Press the On/Off button to turn on the UPS.

The power cord may not be connected properly.

• Connect the power cord securely into a wall outlet.

The upstream input circuit breaker may be tripped.

• Reset the input circuit breaker.

LED 1 flashes (green) every 3 seconds, but there is
no output power.

Battery voltage may be too low.

• Recharge the UPS for 8 hours.

Alarm buzzer beeps continuously although utility
power is normal.

The UPS may be overloaded (check LED 2).

• Disconnect some equipment from the UPS.

UPS does not provide expected backup time.

The UPS battery reached end of life.

• Replace the internal battery.

The UPS is on and connected to input power, but fails
to operate properly.

Utility power may be outside the unit’s operating range.

• If utility power is normal, try reconnecting input
power and restarting the UPS.

Utility power is normal, but LED 1 is not illuminated.

SPECIFICATIONS
Model Number

PSA500MT3-120U

PSA650MT3-120U

500/300

650/390

Net Weight, lb. (kg)

14.1 (6.4)

14.6 (6.6)

Shipping Weight, lb. (kg)

15.9 (7.2)

16.3 (7.4)

Capacity (VA/W)

Dimensions - W x D x H, in. (mm)

3.7 x 14 x 6.7 (95 x 356 x 171)

On-Line Input Voltage

84-140VAC

On-Line Frequency

50/60Hz ±5Hz

Output Voltage (Utility Power Normal)

Typical 97-129VAC

Output Voltage (Battery Operation)

120VAC ±5%

On-Battery Wave Form

Stepped sinewave

Battery Type - VDC x Ah x Quantity

12V x 7Ah x 1

Typical Recharge Time

6-8 hours to 90%

Battery Run Time* - Full Load

3-5 minutes

Battery Run Time* - Half Load

10 minutes

Audible and Visual

Audible alarm / LED

Backup Outlets

NEMA 5-15R (3)

Surge Outlets

NEMA 5-15R (1)

Operating Temperature, °F (°C)

32 to 104 (0 to 40)

Storage Temperature, °F (°C)

5 to 104 (-15 to 40)

Operating / Storage Relative Humidity

0%-90%, non-condensing

EMI Classification

FCC Part 15 Class B

Agency
Safety
Transportation

UL 1778, c-UL Listed
ISTA Procedure 1A Certification

* Battery run time may vary depending on load

© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.

SL-23300_REV0_04-08

Technical Support / Service

United States

800-222-5877 (Outside U.S. 614-841-6755)
upstech@emersonnetworkpower.com
Web site: www.liebert.com

1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2003:07:16 21:05:42Z
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2008:05:06 12:49:02-04:00
Metadata Date                   : 2008:05:06 12:49:02-04:00
Format                          : application/pdf
Creator                         : .
Title                           : 
Document ID                     : uuid:3c6d062f-5494-4dce-bbc4-ca8ceb85451d
Instance ID                     : uuid:604c4d5b-ab19-4836-97b5-eb020449918f
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu