TI369F/00/enTechnical InformationFieldgate FXA320, FXA520Gateways / InterfacesGateway for Remote Monitoring of Sensors and Actuatorsvia Web BrowsersApplicationFieldgates enable remote monitoring of connected 4...20 mA sensors/actuators, either via telephone lines (analogue), Ethernet TCP/IP or mobile communications (GSM). The measured data is web compatible (HTTP, HTML, WML) and can, therefore, be analysed in the web browser without additional software.For remote diagnosis and remote configuration, HART sensors are suitable in conjunction with FXA520.Their integrated time control make Fieldgates suitable for all applications in which more distant measuring points have to be sporadically analysed. Configurable monitoring of limit values with alarm signalling via e-mail or SMS make it possible to react directly to changes on-site.The supported data transfer in XML format allows for simple further analysis and processing of the measured data, through to integration into complex planning systems.Your benefits• Communication via modem, Ethernet or GSM/GPRS• Uses standard Internet protocols(TCP/IP, http)• Simple configuration with web browsers without additional software• Visualisation via Internet/Intranet in the web browser and/or WAP mobile phone• Limit value monitoring with alarm signalling via e-mail or SMS• Synchronised time stamping of all measured values• XML data transfer allows for simple further processing of the measured dataFXA320• Optionally, four binary inputs with event counter function and frequency measurement• Two 4...20 mA current inputs with integrated loop power supply• Selectable active/passive current input (for 2-wire and 4-wire devices)• Integrated communication resistor (250 Ω) for configuration via CommuboxFXA520• Web server for remote monitoring of up to 30 measuring points• Up to 4 measured values can be displayed per device (HART)• Intrinsically safe version [EEx ia]IIC for applications in hazardous areas• Remote diagnosis and remote configuration of connected HART devices• Applicable in 4...20 mA SIL 2 Loops (IEC 61508)
Fieldgate FXA320, FXA5202Endress + HauserTable of contentsApplications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Vendor Managed Inventory   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Remote maintenance of measuring equipment (FXA520 only)  . . . . 3Communication interface  . . . . . . . . . . . . . . . . . . . . . . 4Internet connection  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Telephone network (analogue)  . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Mobile communications network (GSM) . . . . . . . . . . . . . . . . . . . . 5GPRS support  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Function and system design. . . . . . . . . . . . . . . . . . . . . 6Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Input  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Analogue 4...20 mA inputs  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10RS-485 interface (FXA 520 only)   . . . . . . . . . . . . . . . . . . . . . . . . 10HART channel 1&2 (FXA 520 only)   . . . . . . . . . . . . . . . . . . . . . . 11Binary inputs (FXA 320 only)  . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Output signal  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Overvoltage category as per EN 61010  . . . . . . . . . . . . . . . . . . . . 11Protection class   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Electrical connection   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Supply voltage  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Power consumption  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Operating conditions: Installation . . . . . . . . . . . . . . . 13Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Operating conditions: Environment. . . . . . . . . . . . . . 14Mounting location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Permitted ambient temperatures  . . . . . . . . . . . . . . . . . . . . . . . . . 14Climatic and mechanic application class  . . . . . . . . . . . . . . . . . . . 14Ingress protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Electromagnetic compatibility (EMC)  . . . . . . . . . . . . . . . . . . . . . 14Application in protection functions  . . . . . . . . . . . . . . . . . . . . . . . 14Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 15Design, dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Materials  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Plug-in connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Human interface  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Display elements   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Operating elements   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Operation concept  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 21CE mark   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Ex-approval  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  21Explosion protection   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  21Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . .  21Telecommunications Regulatory Compliance  . . . . . . 22Fieldgate analogue version  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Fieldgate GSM version  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  22- Federal Communications Commissions Notice  . . . . . . . . . . . . . 22- Federal Communications Commissions Statement   . . . . . . . . . .  22- Wireless Notices   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 23Fieldgate FXA320   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23Fieldgate FXA520   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Protective housing  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24DAT module   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24PC cable   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24Telephone cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24Fieldgate data access   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24Fieldgate OPC server  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24Java applets  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  25HART Client (FXA 520 only)  . . . . . . . . . . . . . . . . . . . . . . . . . . .  25Multiplexer (FXA 520 only)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25E+H power supply units (FXA 520 only) . . . . . . . . . . . . . . . . . . .  25E+H Multidrop Connector FXN520  . . . . . . . . . . . . . . . . . . . . . . 25Solarbox   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  25Documentation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Operating Instructions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  26Certificates   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  26Accessories   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  26
Fieldgate FXA320, FXA520Endress + Hauser 3ApplicationsVendor Managed Inventory By using Fieldgates to interrogate tank or silo levels remotely, suppliers of raw materials can provide their regular customers with information about the current supplies at any time and, for example, account for them in their own production planning. For their part, the Fieldgates monitor the configured level limits and, if required, automatically activate the next supply. The spectrum of options here ranges from a simple purchasing requisition via e-mail through to fully automatic order administration by coupling XML data into the planning systems on both sides.L00-FXA520xx-02-00-06-en-001Remote maintenance of measuring equipment (FXA520 only)Fieldgates not only transfer the current measured values, they also alert the responsible standby personnel, if required, via e-mail or SMS. In the event of an alarm or also when performing routine checks, service technicians can diagnose and configure connected HART devices remotely. All that is required for this is the corresponding HART operating software (e.g. ToF Tool - FieldTool Package, ReadWin, ...) for the connected device. Fieldgate passes on the information transparently, so that all options for the respective operating software are available remotely. Some on-site service operations can be avoided by using remote diagnosis and remote configuration and all others can at least be better planned and prepared.L00-FXA520xx-02-00-06-en-002Fieldgate FXA520Fieldgate FXA320Fieldgate FXA320supplier1...15 sensors 1...15 sensorscustomer Bcustomer Ccustomer Aanalogue 4...20 mAlimitswitches- ToF Tool - FieldTool Package- ReadWin- …Fieldgate FXA5201...15 sensors 1...15 sensors
Fieldgate FXA320, FXA5204Endress + HauserCommunication interfaceInternet connection If the Fieldgate dials into the Internet permanently via an Internet Service Provider, it is also possible for several users to access the Fieldgate simultaneously when using an analogue/GSM version. The other advantage is that the respective user does not require a modem as a receiver at the work place.Ethernet The 10 Base T Ethernet interface with RJ45 plug-in connection can be connected to the local network using a hub or switch. A standard network cable is used for this. In Ethernet operation, you always have access to the Fieldgate with a standard web browser, since the device is constantly available in the network. Several PCs can access the Fieldgate simultaneously.L00-FXA520xx-02-00-06-en-003Telephone network (analogue)The Fieldgate is connected to the available telephone network via an RJ11 (PSTN) plug connector. This form of communication is always a point-to-point connection and only one PC can communicate with the device at any one time. In this configuration, the Fieldgate has to be selected before each access, so that it is ready for online operation. For example, the Windows internal telecommunications network can be used for dialling. After this, the Fieldgate can be accessed with a standard web browser (e.g. Internet Provider).The Fieldgate is also capable of dialling itself into a central server, in order to deliver periodic measured values for example. Here, it is also possible to transfer the measured values via the Internet using an Internet Service Provider.L00-FXA520xx-02-00-06-en-004RJ 45RJ 45Fieldgate FXA520Fieldgate FXA320RJ 45RJ 45TA ERJ 11RJ 11FieldgateFXA520FieldgateFXA320- data telecomminication connectionWeb browserdial-up:- …PSTN (Public Switched Telephone Network)(e.g.. Telekom)
Fieldgate FXA320, FXA520Endress + Hauser 5Mobile communications network (GSM)If there is no Ethernet or telephone network available in the Fieldgate's operating location, the data can also be transferred via GSM using the mobile communications network.These communications versions can be configured as point-to-point connections or as freely accessible via the Internet/Intranet. A SIM card from a mobile communications network operator is required for GSM operation.Communication takes place via the data channel of the SIM card, which may require additional activation, depending on the GSM provider.L00-FXA520xx-02-00-06-en-005GPRS support GPRS (General Packet Radio Services) is a mobile communications technique, which exploits the advantages of packet-oriented data transmission and channel bundling.Different from normal GSM connections, no complete channel is reserved for the duration of the connection between the mobile device and the basis station, rather the data is packed into packets, which can be sent depending on requirement and capacity. Data transmission in packets enables not only greater transmission rates but also always-on-operation. The Fieldgate is thus permanently in a position to connect to the Internet, an Intranet or a mailbox, whereby data is only transferred as required if a new e-mail is sent or a new Internet page is called up. Here, you are only charged for the amount of data actually transmitted (and not for connection time). The GPRS mode of the Fieldgate GSM thus offers the easiest and most cost-effective option for connecting a measuring point permanently to the Internet or an Intranet. Thanks to always-on-operation, the WAP functions of the Fieldgate can also be used easily and cost-effectively.To use the available GPRS functions, the GSM/GPRS provider will need to allocate a public IP address. It will be necessary to determine in each individual case, whether this additional service is offered by the respective operator.Fieldgate FXA520Fieldgate FXA320PSTN (Public Switched Telephone Network)(e.g. Telekom)SIMCardSIMCard
Fieldgate FXA320, FXA5206Endress + HauserFunction and system designMeasuring system Configuration with analogue input 4...20 mA (FXA320 only)• Two devices can be connected directly.• Selectable active/passive current input.L00-FXA320xx-14-00-06-en-001Configuration with binary input (FXA320 only)• Four binary inputs with event counter function and frequency measurement.• Two 4...20 mA current inputs.L00-FXA320xx-14-00-06-en-002.FieldgateFXA320FieldgateFXA320100203040 50708090100!KEEPTIGHTWHENCIRCUITALIVEINEXPLOSIVEATMOSPHERE°C°F %K60Web browserHTTP script…AnalogueEthernetGSMpassiveactive(active)4...20 mA4-wire(passive)4...20 mALoop-PoweredCommubox FXA191ToF Tool - FieldTool PackageFieldgateFXA32024 VDCWeb browserHTTP script…AnalogueEthernetGSM
Fieldgate FXA320, FXA520Endress + Hauser 7HART - Point-to-Point configuration (FXA520 only)• Two devices can be connected directly• Can also be used in hazardous areas• Qualified for 4...20 mA SIL 2 Loops (IEC 61508)• Subsequent connection to available installation possible• A HART communication resistor is already integrated into the device• Additional connection of 4...20 mA sensors is also possibleL00-FXA520xx-14-00-06-en-007Configuration with analogue input 4...20 mA (FXA520 only)• Two devices can be connected directly• Can also be used in hazardous areas (e.g. RN221N)• Subsequent connection to available installation possibleL00-FXA520xx-14-00-06-en-006-Commubox FXA191Commubox FXA191ToF Tool -FieldToolPackageToF Tool - FieldTool Package.FieldgateFXA520FieldgateFXA520ENDRESS+HAUSERRN 221NENDRESS+HAUSERRN 221NWeb browserHTTP scriptToF Tool - FieldToolPackage…AnalogueEthernetGSMe.g. 2 x RN221N-B …e.g. RNS221-.4...20 mA4...20 mAFieldgateFXA520FieldgateFXA520ENDRESS+HAUSERRN 221NENDRESS+HAUSERRN 221NENDRESS+HAUSERRN 221NENDRESS+HAUSERRN 221NWeb browserHTTP scriptToF Tool - FieldToolPackage…AnalogueEthernetGSMe.g. 2 x RN221N-A …e.g. 2 x RN221N-B …
Fieldgate FXA320, FXA5208Endress + HauserHART Multiplexer configuration (FXA520 only)• Multiplexer, e.g. KFD2-HMM-16 from Pepperl• Up to 30 devices (2 x 15) can be connected• Subsequent connection to available installation possible• 4...20 mA still possibleNote!Detailed information on the configuration can be found in the operating instructions BA 268F/00.L00-FXA520xx-14-00-06-en-005RS 485Master MasterRNS221RS 485FieldgateFXA520.maximum 15 devicesWeb browserToF Tool - FieldTool PackageHTTP script…AnalogEthernetGSMHART-Multiplexere.g. Pepperl + FuchsKFD2-HMM-16HART-Multiplexere.g. Pepperl + FuchsKFD2-HMM-16maximum 15 devices
Fieldgate FXA320, FXA520Endress + Hauser 9HART - Multidrop configuration (FXA520 only)• Only HART communication possible• Up to 30 devices (2 x 15) can be connected• When the maximum number of devices are connected, observe the following:– Minimum operating voltage of the connected devices,– Voltage drop at the communication resistor,– HART conformity multi-drop of the connected devices,– Current consumption of the connected devices– Output characteristics of the power supply unit– All connected devices must first be allocated their own HART polling address• A HART communication resistor is already integrated into the device. When the internal communication resistor is used, the permitted number of devices in multi-drop operation is reduced due to the limited current-carrying capacity of the resistor.L00-FXA520xx-14-00-06-en-003All E+H measuring devices with the HART protocol can, therefore, be used to the full extent withthe FieldgateA current list of all E+H measuring devices that have the HART protocol can be found under:• www.hartcomm.org: "HART Products/Product Catalogue/ ...". All Endress+Hauser measuring devices with HART protocol can be connected to the Fieldgate.Even 4...20 mA devices without HART protocol can be operated in conjunction with the Fieldgate, e.g. limit switch (Liquiphant, ...). However, then only the measured value can be read. The remote maintenance function is not given for 4...20 mA devices because the HART protocol is required for this function.MultidropConnectorFXN520FieldgateFXA520supplyvoltage24 VWeb browserToF Tool - FieldTool PackageHTTP script…AnalogueEthernetGSMup to 15 devicesup to 15 devicesdevice address: 15    …    …    03                   02                    01channel 1 channel 2
Fieldgate FXA320, FXA52010 Endress + HauserInputAnalogue 4...20 mA inputs FXA5202 channels: joint ground of both channels, no galvanic isolation.FXA3202 channels with galvanic isolation. Can be used independently as active or passive input.RS-485 interface (FXA 520 only)Channel 1&2 - passiveMax. input voltage per channel 35 VMax. input current per channel 45 mAInput impedance approx. 100 ΩAccuracy ≤ 1 %Voltage drop (incl. diode against reverse polarity) ≤ 3 VConnection cable Instrument cable, unscreenedCable resistance max. 25 Ω per coreChannel 1&2 - activeOutput voltage 15 V ±5% / (22 mA)No-load voltage 23.5 V ±5%Output current max. 23 mAShort-circuit current max. 64 mAshort-circuit duration UnlimitedConnection cable Instrument cable, unscreenedCable resistance max. 25 Ω per coreChannel 1&2 - passiveMax. input voltage per channel 35 VMax. input current per channel 45 mAInput impedance 254 ΩAccuracy ≤ 0.5 %Voltage drop (incl. diode against reverse polarity) ≤ 6.4 VConnection cable Instrument cable, unscreenedCable resistance max. 25 Ω per coreGalvanic isolation  500 V RMSTermination resistor A-B 120 Ω fully integrated
Fieldgate FXA320, FXA520Endress + Hauser 11HART channel 1&2(FXA 520 only)The HART signal is capacitive coupled and decoupled via a communication resistorGalvanic isolation between HART channel 1 and channel 2Ex-isolation between field devices and internal circuits.Binary inputs (FXA 320 only) Galvanic isolation of all channels from the rest of the current circuits. Each 2 channels have the same reference potential.OutputOutput signal • A relay for alarm in the event of a fault• Switching-off the sensor's power supply (in the event of a fault, power-save mode) • Switching capacity of relay contacts:U~ maximum 253 VI~ maximum 2 AP~ maximum 500 VA at cos ϕ 0.7U- maximum 40 VI- maximum 2 AP- maximum 80 WOvervoltage category as per EN 61010 IIProtection class  II (double or reinforced insulation)Communication resistor in the 4...20 mA signal line Integrated 270 Ω communication resistor, for optional use, max. 45 mA!Short-circuit duration (without interrior communication resistor)Unlimited Output voltage U0 in the event of a fault (Ex) Max. 6.5 V Max. current for EEx ia (Ex) 5.97 mAMax. power output (Ex) 39 mWMaximum input voltage (Ex) 30 VMaximum input voltage (non-Ex) 45 VNumber of digital inputs 4Input signal voltage L-signal: -3 ... +5 VH-signal: +15 ... +30 VInput current with H-signal 5 mAMax. quiescent current with L-signal 1 mAMeasuring range of event counter function 0 ...12.5 kHzMeasuring range of frequency measurement 4.7 Hz (±1%) ... 12.5 kHz (±4%)
Fieldgate FXA320, FXA52012 Endress + HauserPower supplyElectrical connection Terminal blocksThe removable terminal blocks are isolated after intrinsically safe connections (on top of device) and non-intrinsically safe connections (on bottom of device). Furthermore, the terminal blocks are also different in colour. Blue for the intrinsically safe area and grey for the non-intrinsically safe area. These distinctions allow for safe cable routing. Connecting the devices(To the upper, blue terminal blocks).The two-core connecting wire between the Fieldgate FXA520 and HART devices can be a usual commercial instrument cable or cores in a multi-core cable for measuring purposes. If strong electromagnetic interferences have to be expected, e.g. from machines or radios, using a screened cable is recommended. Only connect the screening to the grounding connection in the device.The HART signal is decoupled passively without power supply.Operating the device in hazardous areas (FXA520 only)The national explosion protection directives for designing and routing the intrinsically safe signal cable must be observed. Maximum permitted values for capacity and inductivity can be found in the Safety Instructions of XA 188F.Connecting the supply voltage(Terminal 1 and 2)For the voltage versions, see the Ordering information on page 23. A fuse is built into the power supply circuit so that a fine-wire fuse does not need to be connected in series.The Fieldgate is equipped with reverse polarity protection.Supply voltage Alternating current version (AC):Voltage range: 85...253 V, 50/60 HzSafe galvanic isolation between mains power supply and internal circuitsDirect current version (DC):Voltage range: 20...60 VDC or 20 ... 30 VACReverse polarity protection guaranteed by bridge rectifierSafe galvanic isolation between mains power supply and internal circuitsPower consumptionFXA520 AC (at 253 VAC) DC (at 20 VDC)Analogue 6 VA 2 WEthernet 4.9 VA 1.5 WGSMSend mode 8 VA 4 WStandby 4.5 VA 1 WFXA320 AC (at 253 VAC) DC (at 20 VDC) Solar (at 10 VDC)Analogue 8 VA 3.5 W —Ethernet 8 VA 3.5 W —GSMSend mode 8 VA 4.8 W 4.6 WStandby 6 VA 2.9 W 2.8 W
Fieldgate FXA320, FXA520Endress + Hauser 13Operating conditions: InstallationInstallation instructions Mounting locationThe Fieldgate must be placed in a cabinet, away from hazardous areas. There is also a protective housing (IP65) for two devices available for outdoor installation. L00-FXA520xx-17-00-06-de-002OrientationVertical on DIN top-hat rail (HT 35 as per EN 60715).L00-FXA520xx-17-00-06-de-001min. IP 65EXEXEN 60715; HT 35 x 7.5EN 60715; HT 35 x 15ANALOGFXA 520LD
Fieldgate FXA320, FXA52014 Endress + HauserOperating conditions: EnvironmentMounting location Cabinet or protective housingPermitted ambient temperaturesFor individual mounting-20 C... +60 CFor series mounting without lateral spacing-20 C... +50 CStorage temperature-25 C... +85 C (preferably at +20 C)Installation in protective housing-20 C... +40 CMaximum two Fieldgates can be installed into a protective housing.Caution!The devices must be mounted such that they are protected from the weather and from impacts, and where possible in places that are not exposed to direct sunlight. This must be especially observed in regions with warm climates.Climatic and mechanic application class 3K3In accordance with DIN EN 60721-3-3 3M2In accordance with DIN EN 60721-3-3 Ingress protection IP 20, in accordance with EN 60529Electromagneticcompatibility (EMC)Interference Emission to EN 61326, Electrical Equipment Class B.Application in protection functions The FXA 520 can be attached back effect freely to protection functions that are classified in SIL 2 to IEC 61508.SFF11)  SFF = Safe Failure Fraction60%TI11)  TI = Test Interval between life testing of the protection function (in years)PFDavg22) PFDavg = Probability (average) of a dangerous Failure on Demand1 year 1,23 x 10-65 years 6,13 x 10-610 years 1,23 x 10-5
Fieldgate FXA320, FXA520Endress + Hauser 15Mechanical constructionDesign, dimensions Note!100 mm = 3.94 in• Housing: aligned housing (top-hat rail design) made of plastic• Installation: on top-hat rail as per EN 60715; HT 35x7.5 or EN 60715; HT 35x15• Ingress protection as per EN 60529; IP 20L00-FXA520xx-06-00-06-yy-002DimensionsL00-FXA520xx-06-00-00-de-001Min. 50 mmMin. 50 mmEXEXEXANALOGFXA 520LDANALOGFXA 520LDANALOGFXA 520LD45 mm95 mm112 mm108 mmANALOGFXA 520LD
Fieldgate FXA320, FXA52016 Endress + HauserWeight approx. 250 gMaterials HousingPolycarbonate Colour: light grey, RAL 7035Front coverPolyamide PA6 Colour: blue Fixing slide (for fastening on the top-hat rail)Polyamide PA6Colour: black, RAL 9005Terminals Connection cross-sectionmaximum 1 x 2.5 mm or 2 x 1.5 mmTerminal assignment Fieldgate FXA320L00-FXA520xx-04-00-06-en-012supply relaysensor 1sensor 2binary inputspassive aktivepassive aktive1215162627281112131478910222324ANALOGFXA 320LD7891011 12 13 1428262715 16N12L1L+ L-23 2422BI1BI3BI2BI4GND1GND2----++++
Fieldgate FXA320, FXA520Endress + Hauser 17Terminal assignment Fieldgate FXA520L00-FXA520xx-04-00-06-en-001Plug-in connections Connection socket for Ethernet Fieldgate versions:RJ45 socketConnection socket for GSM antenna:FME socket (male)Connection plug for DAT module:8-pin plug connector in 2.54 mm raster, 2 rowsConnection plug for PC cable:3-pin plug connector in 2.54 mm raster, 1 rowHART channel 2 (EEx ia)andHART channel 1 (EEx ia)supply relayanalogue input 4...20 mA270 / 0.55 W (communication resistor)Ω12151626272811121378921222324ANALOGFXA 520LD78911 12 13CH 1CH 228262715 16N12L1L+ L-23 2421 22--++CH1 CH2ABRS-4854..20 mAHART
Fieldgate FXA320, FXA52018 Endress + HauserHuman interfaceDisplay elementsL00-FXA320xx-07-00-06-xx-005Operating elements For the arrangement of the elements, see the diagram above.FXA320 onlyPosition Light emitting diode (LED) Meaning1 Green LED constant Displays the correct power supply2 Red LED constant Displays a faultRed LED flashes Displays a warning / On site communication via PC / Hardware is unlocked / system start3 Yellow LED Switching status of the built-in relay / LED on = relay tightens– LED off = relay de-energised– LED on = relay energised4 Yellow LED Displays a successful connection5 Yellow LED Displays a transfer activity / GSM version: field strength display if no connection67812 3CH 1CH 2459Position Element Meaning6 Socket  Connection socket for DAT module7 Button Button for hardware security locking and configuration reset8 Socket Connection socket for PC cable (service connector)Position Element Current input channel 1 (CH1) Current input channel 2 (CH2)9 Switch position (up) aktive aktiveSwitch position (down) passive passive
Fieldgate FXA320, FXA520Endress + Hauser 19Operation concept Fieldgate offers world-wide remote monitoring, remote diagnosis and remote configuration of Smart transmitters with the international used HART® protocol. Measured values become available world-wide via Internet and can be efficiently processed. A standard web browser is used for visualising and remote inquiry. Fieldgate displays parameters and measured values of field instruments on an HTML page. Max. 30 measured values can be displayed. Up to 4 measured values can be displayed per device.Fieldgate FXA520L00-FXAY2Kxx-20-13-00-en-301L00-FXA520xx-20-13-00-en-167
Fieldgate FXA320, FXA52020 Endress + HauserFieldgate FXA320L00-FXA320xx-20-13-00-en-001
Fieldgate FXA320, FXA520Endress + Hauser 21Certificates and approvalsCE mark The Fieldgate meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE label. Ex-approval FXA520see Ordering informationExplosion protection FXA520[EEx ia] IICIntrinsically safe circuitsValues for each circuit:Max. external values in accordance with the following table:If inductances and capacitances are concentrated the following values apply:Other standardsand guidelinesOther standards and guidelines that have been observed when designing and developing the Fieldgate. EN 60529Ingress protections for housing (IP code)EN 61010Safety requirements for electrical equipment for measurement, control and laboratory useEN 61326Interference emission (class B operating equipment), interference immunity (appendix A - industrial sector)EN 60950 (IEC 950)Safety of information technology equipmentVoltage Uo= 6.5 VDCCurrent Io= 6 mAPower Po= 9.8 mWGroup Capacitance Co [µF] Inductance Lo [mH]IIC 25 1000IIB 570 1000Group Capacitance Co [µF] Inductance Lo [mH]IIC221.50.515IIB10107125
Fieldgate FXA320, FXA52022 Endress + HauserTelecommunications Regulatory ComplianceFieldgate analogue version North AmericaFCC CFR 47, part 15 and part 68EuropeTelecoms Terminal Equipment Directive (98/13/EG)European approval TBR 21Fieldgate GSM version North AmericaFCC CFR 47 Part 15 and Part 24Federal Communications Commission Notice This device generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the device off and on, the user is encouraged to try to correct the interference by one or more of the following measures:– Reorient or relocate the receiving antenna.– Increase the separation between the equipment and receiver.– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.To ensure that the unit complies with current FCC regulations and safety requirements limiting both maximum RF output power and human exposure to radio frequency radiation, use an antennna with a maximum gain of 2dBi and a separation distance of at least 20 cm must be maintained between the unit's antenna and the body of the user and any nearby persons at all times and in all applications and uses.ModificationsThe FCC requires the user to be notified that any changes or modifications made to this device that are not expressly approved by Endress+Hauser may void the user's authority to operate the equipment.Federal Communications Commission StatementFCC-ID: LCG-FG-FXA52x-32xThis device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:(1) This device may not cause harmful interference, and(2) This device must accept any interference received, including interference that may cause undesired operation.Wireless NoticesIn some situations or environments, the use of wireless devices may be restricted. Such restrictions may apply aboard airplanes, in vehicles, in hospitals, near explosives, in hazardous locations, etc. If you are uncertain of the policy that applies to the use of this device, please ask for authorization to use it prior to turning it on.
Fieldgate FXA320, FXA520Endress + Hauser 23Ordering informationFieldgate FXA320Fieldgate FXA520Note!A PC cable is included in the scope of supply with FXA320/520.10 CertificatesA Version for non-hazardous areasF CSA, general purposeY Special version20 Power supplyA Power supply 85...253 VAC, 50/60 HzE Power supply 20...60 VDC, 20...30 VACG Solar panel connection 10...20 VDCY Special version30 Modem interface1 Ethernet - 10 Base T2 Analogue modem4 GSM modem without antenna9 Special version40 DAT moduleA without DAT moduleB with DAT moduleYSpecial version50 InputA 2-channel analogue (4...20 mA)B 2-channel analogue (4...20 mA) + 4 binaryFXA320- Complete product designation10 CertificatesA Version for non-hazardous areasG ATEX II (1) GD EEx ia IIC T6P FM IS - Class I, II, III, Division 1, Group A-GS CSA IS - Class I, II, III, Division 1, Group A-GY Special version20 Power supplyE Power supply 20...60 V DC, 20...30 V ACA Power supply 85...253 V AC, 50/60 HzY Special version30 Modem interface1 Ethernet - 10 Base T2 Analogue modem4 GSM modem without antenna9 Special version40 DAT moduleA without DAT moduleB with DAT moduleYSpecial versionFXA520- Complete product designation
Fieldgate FXA320, FXA52024 Endress + HauserAccessoriesNote!The following table gives an overview of possible application for the individual accessory parts with the Fieldgate FXA320 or FXA520. Protective housing The protective housing in protection class IP 66 is equipped with an integrated top-hat rail and is closed with a transparent cover that can also be lead sealed. Dimensions:W 180 / H 182 / D 165Colour:Light grey RAL 7035.Order number: 52010132.DAT module An external EEPROM, in which the configuration data is saved identically to the internal EEPROM, can be attached optionally via plug. For example, this allows for the FXA320/520 to be changed in the event of a defect, without losing the customer-specific configuration data. Order number: 52013311.PC cable A PC can be connected to the FXA320/520 for configuration purposes via a serial RS 232 connection. Order number: 52013984.Telephone cable RJ11 (analogue plug, double-sided, length: 5 m). Order number: 52014031.Fieldgate data access Fieldgate Data Access software assists with the collection of data from different Fieldgates. The fetching of data is controlled via entries in the Scheduler. Time control can be via periodic intervals or at user-defined times. Under Windows NT4 / 2000 / XP, collection of the data can accomplished via a "system service", which runs in the background. The data are saved in CSV format. Further processing of the data can be carried out with, e.g. Excel.Fieldgate OPC server The Fieldgate OPC server provides an interface between one or more Endress+Hauser Fieldgate devices and all possible OPC Data Access 2.0 compatible Clients. The Fieldgate can be connected via a dial-up modem or through a TCP/IP network.Java applets Java applets for a customised view of the screen.Accessory Fieldgate FXA320 Fieldgate FXA520Protective housing X XDAT module X XPC cable X XTelephone cable (analogue version only) is required is requiredFieldgate data access X XFieldgate OPC server X XJava applets X XAntenna (GSM version only) is required is requiredHART Client (FXA 520 only) — XMultiplexer (FXA 520 only) — XE+H power supply units (FXA 520 only) — X
Fieldgate FXA320, FXA520Endress + Hauser 25Antenna Antenna for communication via mobile communications (GSM):• Triband flat antenna.Order number: 52018396.• Dual band station antenna.Order number: 52018395.HART Client (FXA 520 only) The HART Client is a free add-on which is required for remote configuration via HARTtools (e.g. with ToF Tool - FieldTool Package, ReadWin, ...). You can download the current software version from the Internet from the Endress+Hauser product pages (download: http://www.endress.com).Multiplexer (FXA 520 only) Accessories for HART Multiplexer system (from Pepperl+Fuchs):• HART Multiplexer Master KFD2-HMM-16.Order number: 52017691.• Master-interface connecting cable.Order number: 52017687.• HART Multiplexer slave KFD0-HMS-16.Order number: 52020232.• Master-slave connecting cable.Order number: 52020233.• Interface module without communication resistor.Order number: 52017689.• Interface module with communication resistor.Order number: 52017690.• Switched-mode power supply.Order number: 52017688.E+H power supply units (FXA 520 only)RMA422Multifunctional 1-2-channel top-hat rail device with intrinsically safe current inputs and transmitter power supply, limit value monitoring, mathematics functions and 1-2 analogue outputs.RNS221Power supply unit for supplying power to two two-wire sensors or transmitters in non-hazardous areas.RN221NIsolator with power supply for safely isolating 4...20 mA standard signal circuits.RMA421Multifunctional 1-channel top-hat rail device with universal input, transmitter power supply, limit value monitoring and analogue output.E+H Multidrop Connector FXN520Operated several devices in multi-drop operation for FXA520. Order number: 52023652.Solarbox Self-sufficient current supply unit for FXA320 with solar panel.
Fieldgate FXA320, FXA52026 Endress + HauserDocumentationOperating Instructions KA 193F/00/a6Mounting and installation instructions for Fieldgate FXA520. Order number: 52013633.KA 215F/00/a6Mounting and installation instructions for Fieldgate FXA320. Order number: 52020867.BA 258F/00/enOperating Instructions for Fieldgate FXA520 (online help in the Internet browser).BA 282F/00/enOperating Instructions for Fieldgate FXA320 (online help in the Internet browser).BA 273F/00/enOperating instructions for Fieldgate Data Access software (download via the Internet).Ba 272F/00/enOperating instructions for Fieldgate OPC server software (download via the Internet).Certificates XA 188F-A/00/a3Safety Instructions for electrical operating equipment for hazardous areas.Order number: 52013636. ZD 086F/00/enControl Drawings (FM). Order number: 52013634.ZD 087F/00/enControl Drawings (CSA). Order number: 52013635.Accessories BA 265F/00/deCable for the HART Multiplexer-System. Order number: 52017693.BA 266F/00/enInterface Modul without Communication resistor. Order number: 52017694.BA 267F/00/deInterface Modul with Communication resistor. Order number: 52017695.BA 268F/00/enHART-Multiplexer Master KFD2-HMM-16. Order number: 52017696.BA 283F/00/enHART Multiplexer slave KFD0-HMS-16. Order number: 52021044.BA 269F/00/enSwitched power supply. Order number: 52017698.TI 391F/00/enSolarbox for Fieldgate FXA320. Order number: 52023595.
Fieldgate FXA320, FXA520Endress + Hauser 27
Fieldgate FXA320, FXA520International Head QuarterEndress+HauserGmbH+Co. KGInstruments InternationalColmarer Str. 679576 Weil am RheinDeutschlandTel. +49 76 21 9 75 02Fax +49 76 21 9 75 34 5www.endress.cominfo@ii.endress.comTI369F/00/en/04.04FM+SGML 6.0 ProMoDo