Enlighted SU4E Compact Sensor User Manual PowerPoint Presentation

Enlighted, Inc. Compact Sensor PowerPoint Presentation

User Guide

Page 5 Page 6 94-00552-02 Rev07 Page 1
Technical Support
For questions regarding the installation or operation of this
product, contact Enlighted
Technical Support: support@enlightedinc.com
Company Contact Information
Location: 930 Benecia Ave, Sunnyvale, CA 94085
Phone: +1.650.964.1094
Web: enlightedinc.com
FCC and Industry Canada Compliance Information
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
This device complies with Part 15 of the FCC Rules and Industry Canada
license-exempt RSS standard(s). Operation is subject to the following two
conditions:
this device may not cause harmful interference, AND
this device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by Enlighted Inc.
could void the user's authority to operate the equipment.
Le présent appareil est conforme aux CNR d'Industrie Canada
applicables aux appareils radio exempts de licence. L'exploitation est
autorisée aux deux conditions suivantes:
l'appareil ne doit pas produire de brouillage, ET
l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique
subi, même si le brouillage est susceptible d'en compromettre le
fonctionnement.
CE
This device complies with the essential requirements and other relevant
requirements of the R&TTE Directive (1999/5/EC). The equipment is Class 1
radio equipment which can be placed on the market and be put into
service without restrictions in accordance with article 1(3) of Commission
Decision 2000/299/EC (Version July 2014).
Copyright © 2016 Enlighted Inc. All rights reserved.
All other brand or product names are trademarks of
their respective companies or organizations.
6-wire Compact Sensor
(SU-4E)
Installation Instructions
Model: SU-4E
No: SU-4E-01
FCC ID: AQQ-SU4E01
IC: 10138A-SU4E01
Figure 1: Compact Sensor
Shipped Components
Enlighted Compact Sensor Unit
Tools you may Need
1” Drill bit
Hand drill
Page 2 Page 3 Page 4
Step Description
1.
Switch off the circuit breaker supplying power to the light.
2.
Mount the Control Unit (CU) behind the ceiling tile or in a UL
approved enclosure. Refer to the
Control Unit Installation
Guide
.
3.
Connect the
RJ-12 connector end of the Compact Sensor
cable to the Control Unit. See Figure 5.
4.
Note
: The sensor is designed to mount in a 15/16th inch hole
in the ceiling tile.
Make a small circular cut in the ceiling tile.
5.
Pull the 6
-
pin end of the Compact Sensor cable through the
hole in the tile. See Figure 2.
6.
Insert the end of the wire into the sensor’s 6
-pin connector.
See Figure 2.
7.
Push the spring arms together and insert the sensor through
the hole in the tile
. See Figure 2.
8.
Turn the power on by switching on the circuit breaker.
Tile Mount Sensor Installation
Figure 2: Tile Mount Sensor
Fixture Mount Sensor Installation
Step Description
1.
Switch off the circuit breaker supplying power to the light.
2.
Mount the Control Unit in the ballast cavity of the fixture or
in a UL approved enclosure.
3.
Connect the RJ
-12 connector end of the Compact Sensor
cable to the Control Unit
. See Figure 5.
4.
Note: The sensor is designed to mount in a ½ inch trade size
knockout on a fixture.
Determine the location for the sensor in the fixture and cut
a ½ inch knockout in the fixture. See Figure 3.
5.
Unthread the spring arms from the Compact Sensor.
6.
Insert the Compact Sensor
through the hole in the fixture.
Use the spring arms from behind the sensor to fasten the
Compact Sensor. See Figure 4.
7.
Insert the 6
-pin end of the Compact Sensor cable to the
6
-pin connector on the sensor.
8.
Turn the power on by switching on the circuit breaker
.
Caution
Installation and maintenance must be performed by a
qualified electrician in accordance with local, state, and
national electrical codes (NEC) and requirements.
Spring
arms Push the spring
arms together
and insert the
sensor
Figure 5: Wiring Connection
Figure 4: Fixture Mount Sensor
Figure 3: Sensor location
in a fixture
LED Status Description/Solution
LED not on Check power and wiring
Purple solid All LEDs are on during boot time for 5-6
seconds
Green blinking Sensor commissioned and working
Red blinking Incompatibility between LED driver and sensor
Replace LED driver and if not resolved,
replace sensor.
Red solid Faulty sensor replace sensor
Green solid Sensor installed, initialized, and
uncommissioned waiting for discovery.
Blue solid Image being upgraded or BLE Reset
LED Description

Navigation menu