Fluke 114 Data Sheet

The-Fluke-114-Digital-Multimeter-Data-Sheet-Brochure The-Fluke-114-Digital-Multimeter-Data-Sheet-Brochure

2015-09-09

: Fluke Fluke-114-Data-Sheet-805284 fluke-114-data-sheet-805284 fluke pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadFluke Fluke-114-Data-Sheet-  Fluke-114-data-sheet
Open PDF In BrowserView PDF
Fluke 114

Electrical Multimeter
Technical Data

Compact true-rms
meter for electrical
troubleshooting
The Fluke 114 is the troubleshooting
tool for “go/no-go” testing. It includes
a feature to prevent false readings
caused by ghost voltage.

Features include:

•	 AutoVolt: automatic ac/dc voltage selection
•	 Large white LED backlight to work in poorly lit areas
•	 Resistance and continuity
•	 Min/Max/Average to record signal fluctuations
•	 CAT III 600 V safety rated
General specifications
Accuracy is specified for 1 year after calibration, at operating 	
temperatures of 18 °C to 28 °C, with relative humidity at 	
0 % to 90 %.
The accuracy specifications take the form of: 	
± ( [ % of Reading ] + [ Counts ] )

Actual size

R

N10140

Maximum voltage between
any terminal and earth
ground

600 V

Surge protection

6 kV peak per IEC 61010-1 600 V
CAT III, Pollution Degree 2

Display

Digital: 6,000 counts, updates 4/sec

Bar graph

33 segments, updates 32/sec

Operating temperature

-10 °C to + 50 °C

Storage temperature

-40 °C to + 60 °C

Battery

9 volt Alkaline, NEDA 1604A/	
IEC 6LR61

Battery life

400 hours typical, without backlight

Accuracy specifications
Measurement

Range

Resolution

Accuracy ± ([% of reading] + [counts])

DC millivolts

600.0 mV

0.1 mV

0.5 % + 2

DC volts

6.000 V

0.001 V

60.00 V

0.01 V

0.5 % + 2

600.0 V

0.1 V

Auto volts

600.0 V

0.1 V

2.0 % + 3 (dc, 45 Hz to 500 Hz)	
4.0 % + 3 (500 Hz to 1 kHz)

AC millivolts1 true-rms

600.0 mV

0.1 mV

1.0 % + 3 (dc, 45 Hz to 500 Hz)	
2.0 % + 3 (500 Hz to 1 kHz)

AC volts1 true-rms

6.000 V

0.001 V

60.00 V

0.01 V

1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)

600.0 V

0.1 V

Continuity

600 W

1W

Beeper on < 20 W, off > 250 W; detects
opens or shorts of 500 µs or longer.

Ohms

600.0 W

0.1 W

0.9 % + 2

6.000 kW

0.001 kW

60.00 kW

0.01 kW

600.0 kW

0.1 kW

6.000 MW

0.001 MW

40.00 MW

0.01 MW

0.9 % + 1

1.5 % + 2

Notes:
1	All ac voltage ranges are specified from 1 % to 100% of range. Because inputs below 1 % of range are not specified,
it is normal for this and other true-rms meters to display non-zero readings when the test leads are disconnected
from a circuit or are shorted together. For volts, crest factor of ≤ 3 at 4000 counts, decreasing linearly to 1.5 at full
scale. AC volts is ac-coupled. Auto-V LoZ, and ac mV are dc-coupled.

Ordering Information
Fluke-114	

Electrical Multimeter

Included
TL75 Test leads, holster, User’s manual 	
and 9 V battery (installed).

  Fluke Corporation     114 Electrical Multimeter

Fluke.	Keeping your world
	
up and running.™
Fluke Corporation	
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.	
PO Box 1186, 5602 BD 	
Eindhoven, The Netherlands
For more information call:	
In the U.S.A. (800) 443-5853 or 	
Fax (425) 446-5116	
In Europe/M-East/Africa (31 40) 2 675 200 or 	
Fax (31 40) 2 675 222	
In Canada (800)-36-FLUKE or 	
Fax (905) 890-6866	
From other countries +1 (425) 446-5500 or 	
Fax +1 (425) 446-5116	
Web access: http://www.fluke.com
©2006 Fluke Corporation. All rights reserved. 	
Specifications subject to change without notice.	
Printed in U.S.A. 10/2006  2634055 D-EN-N Rev B



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
XMP Toolkit                     : 3.1.1-111
About                           : 97d94883-b41c-11da-8bad-9fc86f8d818c
Create Date                     : 2006:10:27 10:11:34-07:00
Metadata Date                   : 2006:10:27 10:11:41-07:00
Modify Date                     : 2006:10:27 10:11:41-07:00
Creator Tool                    : Adobe InDesign CS2 (4.0.4)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 12451 bytes, use -b option to extract)
Instance ID                     : uuid:36b2cc9c-65de-11db-a715-000a95b26bba
Document ID                     : adobe:docid:indd:d6506f71-65c4-11db-9e2f-f0739d794614
Rendition Class                 : proof:pdf
Derived From Instance ID        : d6506f70-65c4-11db-9e2f-f0739d794614
Derived From Document ID        : adobe:docid:indd:d6506f6f-65c4-11db-9e2f-f0739d794614
Manifest Link Form              : ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 300.00
Manifest Placed Y Resolution    : 72.00, 300.00
Manifest Placed Resolution Unit : Inches, Inches
Manifest Reference Instance ID  : uuid:9CD88E088D7311DA8E63A96017394172, uuid:E215797A8FD011DA90528B3EDA69C662
Manifest Reference Document ID  : adobe:docid:photoshop:30fd97a4-8e80-11da-b8aa-83145fb99710, adobe:docid:photoshop:dfb77d80-b40e-11da-b05c-92fc7c44ba2f
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 2
Creator                         : Adobe InDesign CS2 (4.0.4)
EXIF Metadata provided by EXIF.tools

Navigation menu