Fluke 1743 Data Sheet
2015-09-09
: Fluke Fluke-1743-Data-Sheet-809059 fluke-1743-data-sheet-809059 fluke pdf
Open the PDF directly: View PDF .
Page Count: 2
Technical Data
3000A/6000A Flex 4
for 174x and 173x PQ Analyzers
Electrical specifications
Input ranges || L1, L2, L3, N 30/300/3000/6000 A ac
Measuring range 0.8 A to 6000 A ac
Intrinsic error <2 % of ||
Position influence max. ± 2 % of m.v. for distance conductor to measuring head >30 mm
Stray field influence <± 2 A for |ext = 500 A ac and distance to measuring head >200 mm
Temperature coefficient <0.05 % / K
Current transformer ratio : ≤ 999 kA / ≤ ||
Ratio selection by job programming for 174x series
by setup menu for 1735
Connection 3-phase, 3-phase + N
2-phase L1 and L3 (2W-meter-method)
7 pole connector
These current probe sets have been
designed for applications with Fluke
1735 and Fluke 1740 series products for
accurate non-intrusive measurement of
AC currents. Using latest technologies
(integrated memory for calibration data)
provides current ranges from 0.8 A up
to 6000 A in a frequency range of 40 Hz
to 5 kHz. The flexis are approved for the
required installation category.
2 Fluke Corporation 3000A/6000A Flex 4 for 174x and 173x PQ Analyzers
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2009 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 11/2009 3564612A D-EN-N
Modification of this document is not permitted
without written permission from Fluke Corporation.
Fluke. Keeping your world
up and running.®
General specifications
Cable length 4 m
Length of measuring head 122 cm
Operating temperature range -10 °C to +70 °C
Storage temperature range -20 °C to +90 °C
Operating humidity 10 % to 80 % (non-condensing)
Weight 1.5 kg
Environment temperature range +18 °C to +26 °C
Humidity 20 % to 75 % r.h.
Current Nominal value |n, sinusoidal waveform, 48 Hz to 65 Hz, distortion factor:
< 1 %, no dc component, stray field <40 A/m, conductor centred within
LEM~flex
Safety standards IEC/EN61010-1:2001
IEC/EN61010-2-032:2002
IEC/EN61010-031:2002
EMC standards IEC/EN 61326-1:2006
Safety 1000 V CAT III, 600 V CAT IV, pollution degree 2
The application of the LEM~flex on uninsulated conductors is limited to 1000 V ac r.m.s. or dc to ground and frequencies below 1 kHz.
Symbols
Do not apply around or remove from HAZARDOUS LIVE conductors, without using protective gloves.
Product is protected by double insulation.
Risk of Danger. Important information. See Instruction Sheet.
Canadian Standards Association has certified that the product meets applicable U.S. and Canadian Standards.
Conforms to relevant European Union directives.
Ordering information
3000/6000A FLEX 4: 3024472
3000A/6000A 36 inch Flexi Probe, 4 Phase