Fluke 434 Series Ii Application Note 2403043
2015-09-09
: Fluke Fluke-434-Series-Ii-Application-Note-808973 fluke-434-series-ii-application-note-808973 fluke pdf
Open the PDF directly: View PDF .
Page Count: 2
Application Note
Lighting is a major load for many large facilities.
Evaluating these circuits is important for both
energy conservation and power quality. Keep in
mind that commercial lighting loads are wired single
phase, with the loads connected from phase to
neutral. Typically, the phase-to-phase voltage is
480 V, with the phase-to-neutral voltage at 277 V.
Measurements must be taken at the lighting panel,
on all phases, since power consumption and Power
Factor could vary on each phase.
1. Power consumption
Excessive phase unbalance can
cause voltage unbalance, which
in turn can affect three-phase
motor loads. For example, in this
three-phase reading, phase A is
considerably higher than B and
C, when all three phases should
be equal.
From the Fluke Digital Library @ www.fluke.com/library
Troubleshooting
commercial
lighting loads
Measurements on commercial lighting loads
Measurement Look for
1. Power consumption (kW) Balance among three phases.
2. Power Factor (DPF and PF) Magnetic ballast will have low DPF. Electronic ballast may have low total PF, although new
generations of ballast often have harmonic mitigation built-in.
3. Total Harmonic Distortion (%THD) Current %THD <20 % is desirable.
4. Voltage Stability Unstable voltage can cause lights to flicker.
2. Power Factor
Ballast with low PF might have
lower cost-of-purchase but
higher cost-of-operation. This
phasor diagram illustrates the
unbalance along with the power
factor.
3. Total Harmonic Distortion
Current THD should be consid-
ered when selecting ballast,
especially if there is a possibility
of transformer overloading. The
bar graph pinpoints the 5th and
7th harmonics as the larger
contributors.
2 Fluke Corporation Troubleshooting commercial lighting loads
The Fluke 43B Power Quality Analyzer trends
voltage (top) and current (bottom) simultane-
ously. Current swells/ inrush caused voltage
sags, indicating that a load downstream from
the measurement point is the cause of the
disturbance.
The Fluke 430 Series Power Quality Analyzers
trend all three phases and compares interac-
tion between the loads.
4. Voltage stability
The sags and swells mode of
power quality analyzers is
especially useful for recording
repetitive voltage sags which can
show up as flickering lights. Both
current and voltage are moni-
tored simultaneously. This helps
us tell if sags are downstream of
the measuring point (load-
related) or upstream (source-
related). For example, if voltage
sags while current swells, a
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-51
16
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 10/2004 2403043 A-US-N Rev A
Fluke. Keeping your world
up and running.
Ø1
Ø2
Ø3
N
Lighting Panel
ABC
277 V Phase-to-Neutral
480 V Phase-to-Phase
Single phase analyzers measure each ballast separately, requiring manual calculations.
Three phase analyzers measure all three phases simultaneously and perform the calcula-
tions automatically.
downstream current inrush likely
caused the sag. If both voltage
and current sag, some event
upstream caused the sags.
It could be an upstream load
like a motor on a parallel branch
circuit which drew down the
feeder voltage. Or it could be
source voltage-related, for
example, a lightning strike or
breaker trip/reclosure on the
utility distribution system.