Friedrich Air Conditioner Eq08M11 Users Manual Xstar_ServMan_02 21 11
XQ05M10 to the manual 8800c6a3-bee2-46a0-87cc-ea4c3810f2ad
2015-02-02
: Friedrich Friedrich-Friedrich-Air-Conditioner-Eq08M11-Users-Manual-428249 friedrich-friedrich-air-conditioner-eq08m11-users-manual-428249 friedrich pdf
Open the PDF directly: View PDF .
Page Count: 47
Download | |
Open PDF In Browser | View PDF |
Service Manual 2 0 11 Room Air Conditioners Tem pe ratur e Cooler W arm er Cool Pow er Fan Fan Only Speed Tim er Oper ation On/ Start Stop M one y Saver® SetHr . R-410A Models Cool Only * * * 115-Volt: XQ05M10 , XQ06M10 , XQ08M10 , XQ10M10 * Cool with Electric Heat 115-Volt: EQ08M11 X-Star-ServMan (1-11) * * Last character may vary. Table Of Contents Important Safety Information .......................................................................................................................................... 2-4 Unit Identification ............................................................................................................................................................... 5 Performance Data ............................................................................................................................................................. 6 Chassis Specifications ...................................................................................................................................................... 6 Installation Information/Sleeve Dimensions ...................................................................................................................... 6 Electrical Data ................................................................................................................................................................... 7 Before Operating the Unit ................................................................................................................................................. 8 For Best Cooling Performance and Energy Efficiency ...................................................................................................... 8 How to Operate the XQ ..................................................................................................................................................... 9 How to Use the XQ Remote Control ............................................................................................................................... 10 How to Operate the EQ ................................................................................................................................................... 10 Electronic Control Sequence of Operation ...................................................................................................................... 11 Functional Component Definition .................................................................................................................................... 12 Components Testing .................................................................................................................................................. 13-16 Refrigeration Sequence of Operation ............................................................................................................................. 17 R-410A Sealed System Repair Considerations .............................................................................................................. 18 Sealed Refrigeration System Repairs ........................................................................................................................ 19-22 Compressor Checks ................................................................................................................................................... 23-24 Compressor Replacement .......................................................................................................................................... 25-26 Routine Maintenance ................................................................................................................................................. 27-28 Performance Test Data Sheet ......................................................................................................................................... 29 Troubleshooting ......................................................................................................................................................... 30-36 Wiring Diagrams ........................................................................................................................................................ 37-38 Instructions for using Cooling Load Estimate Form ........................................................................................................ 39 Cooling Load Estimate Form ........................................................................................................................................... 40 Heat Load Form ......................................................................................................................................................... 41-42 Warranty .......................................................................................................................................................................... 43 Technical Assistance ....................................................................................................................................................... 44 1 IMPORTANT SAFETY INFORMATION The information contained in this manual is intended for use by a qualified service technician who is familiar with the safety procedures required for installation and repair, and who is equipped with the proper tools and test instruments required to service this product. Installation or repairs made by unqualified persons can result in subjecting the unqualified person making such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical shock which can be serious or even fatal. Safety warnings have been placed throughout this manual to alert you to potential hazards that may be encountered. If you install or perform service on equipment, it is your responsibility to read and obey these warnings to guard against any bodily injury or property damage which may result to you or others. Your safety and the safety of others are very important. We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages. This is a Safety Alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING” or “CAUTION”. These words mean: WARNING You can be killed or seriously injured if you do not follow instructions. CAUTION You can receive minor or moderate injury if you do not follow instructions. All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what will happen if the instructions are not followed. NOTICE A message to alert you of potential property damage will have the word “NOTICE”. Potential property damage can occur if instructions are not followed. PERSONAL INJURY OR DEATH HAZARDS ELECTRICAL HAZARDS: 2 • Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenance, or service. • Make sure to follow proper lockout/tag out procedures. • Always work in the company of a qualified assistant if possible. • Capacitors, even when disconnected from the electrical power source, retain an electrical charge potential capable of causing electric shock or electrocution. • Handle, discharge, and test capacitors according to safe, established, standards, and approved procedures. • Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary to test or troubleshoot equipment with the power on to the unit. • Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air conditioning unit while cleaning. • Electrical component malfunction caused by water could result in electric shock or other electrically unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry. • Never operate the A/C unit with wet hands. • Use air conditioner on a single dedicated circuit within the specified amperage rating. • Use on a properly grounded outlet only. • Do not remove ground prong of plug. • Do not cut or modify the power supply cord. • Do not use extension cords with the unit. • Follow all safety precautions and use proper and adequate protective safety aids such as: gloves, goggles, clothing, adequately insulated tools, and testing equipment etc. • Failure to follow proper safety procedures and/or these warnings can result in serious injury or death. REFRIGERATION SYSTEM HAZARDS: • Use approved standard refrigerant recovering procedures and equipment to relieve pressure before opening system for repair. • Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor to moderate injury. • Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s flame or hot surfaces can cause serious burns. • Make sure to protect personal and surrounding property with fire proof materials. • Have a fire extinguisher at hand while using a torch. • Provide adequate ventilation to vent off toxic fumes, and work with a qualified assistant whenever possible. • Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for leaks, flushing etc. • Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves, safety glasses, clothing etc. • Failure to follow proper safety procedures and/or these warnings can result in serious injury or death. MECHANICAL HAZARDS: • Extreme care, proper judgment and all safety procedures must be followed when testing, troubleshooting, handling, or working around unit with moving and/or rotating parts. • Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and other unit components especially the sharp fins of the indoor and outdoor coils. • Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc. • Failure to follow proper safety procedures and/or these warnings can result in serious injury or death. 3 PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: • Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specified amperage rating. • Connect to a properly grounded outlet only. • Do not remove ground prong of plug. • Do not cut or modify the power supply cord. • Do not use extension cords with the unit. • Failure to follow these instructions can result in fire and minor to serious property damage. WATER DAMAGE HAZARDS: • Improper installation maintenance, or servicing of the air conditioner unit, or not following the above Safety Warnings can result in water damage to personal items or property. • Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit. • Do not drill holes in the bottom of the drain pan or the underside of the unit. • Failure to follow these instructions can result in result in damage to the unit and/or minor to serious property damage. INTRODUCTION This service manual is designed to be used in conjunction with the operation and installation manual provided with each unit. This service manual was written to assist the professional HVAC service technician to quickly and accurately diagnose and repair any malfunctions of this product. This manual, therefore, will deal with all subjects in a general nature. (i.e. All text will pertain to all models). IMPORTANT: It will be necessary for you to accurately identify the unit you are servicing, so you can be certain of a proper diagnosis and repair. (See Unit Identification.) Compressor Condenser Coil Front Cover Discharge Air System Controls Outdoor Grille Evaporator Coil Sleeve Return Air Grille/Filter Blower Wheel Blower Motor 4 Basepan Condenser Fan Blade UNIT IDENTIFICATION Model Number Code X Q 08 M 1 0 A - A 9th Digit – Engineering Suffix Indicates Modification (Subject to change) 1st Digit – Function E = Electric Heat X = Straight Cool 8th Digit – Marketing Suffix Indicates Modification (Subject to change) 7th Digit – Options 0 = Straight Cool 1 = 1 KW Heat Strip, Nominal 2nd Digit Q = Chassis Size 6th Digit – Voltage 1 = 115 Volts 5th Digit - Model Series / Year Introduced M=2010 3rd and 4th Digit - Approximate BTU/HR in 1000s (Cooling) Heating BTU/Hr capacity listed in the Specification/Performance Data Section RAC Serial Number Identification Guide Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 Year Manufactured A=1 D=4 G=7 B=2 E=5 H=8 C=3 F=6 J=9 K=0 A A A Y 00001 Production Run Number Product Line X-Start Month Manufactured A=Jan D=Apr G=Jul K=Oct B=Feb E=May H=Aug L=Nov C=Mar F=Jun J=Sept M=Dec 5 PERFORMANCE DATA EVAP. AIR TEMP. DEG. F COOLING PERFORMANCE DATA** Discharge Air Temp. Drop F. * CONDENSER Discharge Temp Suction Temp Super Heat Sub-Cooling TEMPERATURE DEG. F OPERATING PRESSURES Suction Discharge R-410A REF. ELECTRICAL RATINGS Amps Cool Amps Heat Locked Rotor Amps Charge in OZ. 57 23 117 133 60 5 19 157 410 4.5 24.0 * 54 26 120 152 63 12 18 150 410 4.9 25.0 XQ06M10 * XQ08M10 51 29 119 160 63 13 25 138 420 6.3 32.0 * 47 33 131 176 59 12 32 132 490 9.8 57.0 XQ10M10 * EQ08M11 162 60 14 27 133 420 7.0 7.6 32.0 * research49 in new31energy-saving120 technology, performance Due to continuing data and 8th and 9th character are subject to change without notice. Q-Chassis XQ05M10 BREAKER FUSE Voltage 60 Hertz Amps 27.0 115 15 21.0 115 15 25.5 115 15 24.0 115 15 25.5 115 15 *** Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R410A. Energy Cooling Capacity Btu Model Heating Capacity Btu Volts Rated Cooling Amps Cooling Watts Heating Amps Heating Watts Ratio EER COP Estimated Moisture Yearly Operating Removal Pints/HR Cost Room Side Air Circulation CFM Net Weight Sleeve Lbs XStar ® XQ05M10 5500 — 115 4.5 491 — — 11.2 $39 1.0 170 Q 72 XQ06M10 6000 — 115 4.9 500 — — 12.0 † 1.0 175 Q 72 7500 — 115 6.9 701 — — 10.7 $56 1.7 175 Q 71 9500 — 115 9.0 970 — — 9.8 $56 2.5 180 Q 71 4000 115 6.3 701 11.2 1290 10.7 $56 1.9 175 Q 72 * * XQ08M10 * XQ10M10 * XStar ® Electric Heat EQ08M11 * 7500 2.8 R-410A As an ENERGY STAR® partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR ® (H) models meet the ENERGY STAR® All models use environmentally friendly R-410A refrigerant. Estimated yearly operating cost based on a 2007 national average electricity cost of 10.65 cents per kWh. † The estimated yearly operating cost of this model was not available at the time the range was published. Installation Information / Sleeve Dimensions Sleeve Height Width Q 14" 19 ¾ " Depth Shell Depth to Minimum with Front Louvers Extension Into Room* 21 3/8" 8 ½" Minimum Extension Outside* 5 ½" 10 ¾" Thru-the-wall Installation Finished Hole Window Width Minimum** Maximum 22" Height Width 14 ¼" 20" 42" Max. Depth 8 ½” * Minimum extensions when mounted in a window. ** Minimum widths achieved using one side curtain assembly as opposed to both in a standard installation. Circuit Rating/ Breaker (C) Circuit Rating Breaker or T-D Fuse Model Plug Face (NEMA#) XQ05M10 , XQ06M10 , XQ08M10 , XQ10M10 EQ08M11 * * * Power Cord Length (ft.) Wall Outlet Appearance 7 * * 125V - 15A 5 - 15P 6 Front (B) Window Mounting Kits Heat/Cool Models Kit No. EQ08M11 WIKQ * Friedrich heat/cool models include accessories for thru-the-wall installation only. Window mounting requires use of optional accessory kit as listed above. 6 SIDE VIEW ELECTRICAL DATA WARNING ELECTRIC SHOCK HAZARD Turn off electric power before service or installation. All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in personal injury or death. NOTICE FIRE HAZARD Not following the above WARNING could result in fire or electically unsafe conditions which could cause moderate or serious property damage. Read, understand and follow the above warning. Wire Size Use ONLY wiring size recommended for single outlet branch circuit. Fuse/Circuit Breaker Use ONLY the correct HACR type and size fuse/circuit breaker. Read electrical ratings on unit’s rating plate. Proper circuit protection is the responsibiity of the homeowner. Grounding Unit MUST be grounded from branch circuit through service cord to unit, or through separate ground wire provided on permanently connected units. Be sure that branch circuit or general purpose outlet is grounded. Receptacle The field supplied outlet must match plug on service cord and be within reach of service cord. Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above for proper receptacle and fuse type. The consumer - through the AHAM Room Air Conditioner Certification Program - can be certain that the AHAM Certification Seal accurately states the unit’s cooling and heating capacity rating, the amperes and the energy efficiency ratio. *HACR: Heating Air Conditioning and Refrigeration 7 WARNING ELECTRICAL SHOCK HAZARD Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician. Do not use plug adapters. Do not use an extension cord. Do not remove ground prong. Always plug into a grounded 3 prong outlet. Failure to follow these instructions can result in electrical shock, serious injury or death. 8 How to operate the Friedrich room air conditioner To start unit 8 9 8 9 If your air conditioner is installed and plugged into a proper receptacle, it is ready to go. The first time the unit is started, the compressor will delay for three minutes. See Automatic Component Protection on the following page. 1 Touch the Power button once. The unit will automatically be in Cool mode with the temperature set at 75°F (24°C) and the fan speed at F1, the sleep setting. 2 3 4 2 3 4 Figure 5 Figure 3 1 1 X Star PM PM Power Power To set mode of operation Cool Fan Spee d Fan Speed When you rst turn the unit on, it will be in the Cool mode (light on), with constant fan. 2 (XQ models) Mode Mode Cool ® MoneySaver Money Saver ® Fan Only Fan Only Clock Timer Timer On/Off Touch the Mode button once to activate the MoneySaver ® (light on). MoneySaver ® is a feature that cycles the fan with the compressor so that the fan does not run all the time. This saves energy and improves dehumidi cation. Or you may prefer constant fan for more air movement (to return to constant fan, touch the Mode button two more times). 13 13 Set Hour Set Hour 10 11 12 10 11 12 Clock Sta rtTime Start Time Sto p Tim e Stop Time Temp/Hour Temp/Hour 6 6 5 5 7 7 In order to run the fan by itself, do the following: 3 Continuing from MoneySaver ® mode (light on), touch the Mode button once to activate the FAN ONLY feature (light on). To set the hour clock 10 Touch the Set Hour button to see the current setting (clock light comes on). The number that is displayed is the approximate time (hour only). Use the and buttons to change the settings. BE SURE TO SET A.M. AND P.M. ACCORDINGLY. (P.M. is indicated by a red light in the upper left corner of the display). The FAN ONLY setting will circulate air in the room without the compressor coming on. To adjust temperature Use the Mode button to select either the COOL or MoneySaver ® function To set the timer 5 COOLER – Touch the button to lower the room air temperature. You can set the START and STOP times a minimum of one hour apart, and a maximum of twenty-three hours apart. 6 WARMER – Touch the button to raise the room air temperature. 7 Press both the and buttons at the same time to switch the temperature readout from Fahrenheit (°F) to Celsius (°C). 4 Repeat step 7 to switch from °C back to °F. NOTE: Set the HOUR CLOCK before attempting to set timer functions. 11 After setting the time, press the Set Hour button once (Start light comes on). Use the and buttons to select the time that the unit will START. 12 After selecting the START time, press the Set Hour button once more (Stop light comes on). Use the and buttons to select the time that the unit will STOP. After selecting the stopping time, press the Set Hour button once. 13 Press the Timer On/Off button (light turns on) to activate the timer function. To deactivate this function, press the Timer On/Off button once again (light turns off). Once the on and off times have been selected, they will remain in memory and cycle daily until changed. To adjust fan speed 8 Touch the Fan Speed button to see the current setting. Touch it again to change speed. F1 is the lowest setting (SLEEP SETTING / LOW), F2 is MEDIUM, and F3 is HIGH. To activate Smart Fan 9 There is a fourth option, SF, when selecting the fan speed. This is the SMART FAN function. SMART FAN DOES NOT OPERATE IN CONJUCTION WITH THE FAN ONLY MODE. Smart Fan will adjust the fan speed automatically to maintain the desired comfort level. For example, if the outside doors in your home are opened for an extended period of time, or more people enter a room, Smart Fan may adjust to a higher fan speed to compensate for the increased heat load. This keeps you from having to adjust the fan speed on your own. NOTE: If the unit is unplugged or the power is interrupted, the HOUR must be reset or the Timer On/Off will not function when desired. Automatic component protection Your unit is equipped with Automatic Component Protection. To protect the compressor of the unit, there is a three minute start delay if you turn the unit off or if power is interrupted. The fan operation will not be affected. Also, if you switch from Cool mode to Fan Only, and switch back to Cool mode, there is a three minute delay before the compressor comes back on. 9 How to use the remote control (XQ models) To start unit 1 To set the timer POWER - Press the Power button once. The unit will automatically start in the mode and fan speed it was last left on. To set mode of operation NOTE: You can set the START and STOP times a minimum of one hour apart, and a maximum of 23 hours apart. 9 TIMER START - Press Start to view the current start time for cooling. Continue pressing the Start button until you arrive at the start time you desire. The start time for cooling will then be set. 2 COOL - Press the Cool button to automatically switch the operating mode to COOL. 10 3 FAN ONLY - Press the Fan Only button if you want to run the fan only. TIMER STOP - Press the Stop button. Continue pressing the Stop button until you arrive at the stop time you desire. The stop time for cooling will then be set. 11 TIMER ON / OFF - Press the On/Off button to activate (light on) or deactivate (light off) the timer. Once the on and off times have been selected, they will remain in memory and cycle daily until changed. 4 MoneySaver ® - Press the MoneySaver ® button to activate the MoneySaver ® feature. This feature cycles the fan with the compressor so that the fan does not run all the time. NOTE: If the unit is unplugged or the power is interrupted, the Set Hr. function must be reset or the On/Off function will not work. To adjust temperature setting 5 WARMER - Press the setting. Warmer button to raise the temperature 6 COOLER - Press the setting. Cooler button to lower the temperature Temperature Cooler To adjust fan speed 2 7 FAN SPEED - Press the Fan Speed button to see the current setting. Press again to change the fan speed. F1 is the lowest setting (SLEEP / LOW), F2 is MEDIUM, F3 is HIGH, and SF is the SMART FAN setting. To set the hour clock 8 SET HOUR CLOCK - Press Set Hr. once to see the current clock setting. Continue pressing the button until you arrive at the current time (Hour only). Minutes are not shown on the display. Make sure that the A.M. / P.M. setting is correct. How To Operate The EQ08 Function Control Knob The left knob is a six position control that allows you to select heat or cool in either low speed or high speed. Plus you can select fan only if you wish. Thermostat Knob The right hand knob is the thermostat - turn it clockwise for cooler, counter-clockwise for warmer. 10 Warmer 6 3 5 Cool Power Fan Fan Money Only Speed Saver® 4 7 Timer Operation On/Off Start 1 Stop Set Hr. 11 8 9 10 Additional RC1 wireless remote controls can be purchased from your Friedrich dealer. ELECTRONIC CONTROL SEQUENCE OF OPERATION MODE CONTROL The mode control pad(s) allow the selection of the operating modes of the unit. There is a two second delay before the mode activates its appropriate relay. OPERATING SEQUENCE / CHARACTERISTICS AND FEATURES Compressor Operation The run state of the compressor is determined by the difference between the indoor ambient temperature and the set temperature. See specific mode of operation for details. Compressor Time Delay: 180 seconds This feature is initiated every time the compressor is deenergized, either due to: (1) satisfying the temperature set point (2) changing mode to fan only (3) a power interruption or (4) turning the unit off The compressor is also time delayed for 3 minutes when the control is first plugged in or power is restored after failure. When the compressor cycles off as a result of satisfying the “load”, the time delay is typically timed out during the off cycle. Compressor time delay is bypassed by “Test Mode”. Return Air Temperature Sensor The control range is 60°F to 90°F +/- 2.0°F. Frost Protection Sensor Temperature settings: Disable the compressor when sensing 30° +/- 3°F for 2 minutes continuously. Enable compressor @ 55° +/- 5°F. The fan should not be affected by the Frost Protection. It should continue to function normally if freeze protection is called for. COOL MODE FOR XQ MODELS When in the COOL mode, the control will turn on the compressor when the indoor temperature is 1.5°F above the set point and turn off the compressor when the ambient gets below the set point by 1.5°F. The fan will run continuously. MONEY SAVER MODE When in MONEY SAVER mode, the system will be turned on when the indoor temperature gets above the set point by 0.75°F and turns off when the indoor temperature gets below the set point by 0.75°F. The fan will turn on 5 seconds before the compressor and turn off 5 seconds after the compressor stops. If the compressor is delayed the fan will continue to run while the compressor restarts. If the thermostat remains satisfied for more than approximately 9 minutes, the fan will turn on for a period of 90 seconds for air sampling. Operation in MONEY SAVER mode will light both the MONEY SAVER and COOL indicators. FAN ONLY MODE When in the FAN ONLY mode, the compressor will not operate. The fan will run continuously at the user-selected speed (see “Fan Speed Set” below). Smart Fan is not available in FAN ONLY Mode. FAN SPEED SET XQ fan speed is changed by pressing FAN SPEED button and scrolling through F1, F2, F3 and SF (Smart Fan) in the digital display. There will be a 2 second delay before the fan speed changes to prevent unnecessary switching of the relays during fan speed selection. SMART FAN On the XQ model, smart fan is activated by pressing the FAN SPEED button and scrolling through speeds until “SF” appears in the digital display. Using the remote control, Smart Fan is selected by the fourth push of Fan Speed button. Smart fan changes fan speeds based on the temperature differential between the ambient and set temperatures. CHECKING ROOM TEMPERATURE Check the room temperature at the electronic control pad by pressing the “FAN SPEED” button and the “TEMP ” button at the same time on XQ models. The indoor temperature will display for 10 seconds. Indoor temperature can be viewed in all modes, including the TEST mode. The display can be changed back to SET temperature by pressing any key, except the ON/OFF button, or after 10 seconds has elapsed. KEEP ALIVE The electronic control has a memory to retain all functions and status as set up by the user in the event of a power failure. Once power is restored to the unit there is a two second delay before the fan comes on and approximately three minutes delay before the compressor is activated, providing that the mode was set for cooling and the set point temperature has not been met in the room. REBOOT/RESET THE CONTROL BOARD With unit on, press “MODE” and “TEMP/HOUR ” buttons simultaneously for 10 seconds. If the panel will reboot, you will hear the fan come on and the temperature window will read 60°F. If this happens, turn the unit off for about 10 seconds and then turn it back on to finish the reboot cycle. If the panel does not reboot, you possibly need to replace it. 11 FUNCTIONAL COMPONENT DEFINITIONS MECHANICAL COMPONENTS Plenum assembly Diffuser with directional louvers used to direct the conditioned airflow. Blower wheel Attaches to the indoor side of the fan motor shaft and is used for distributing unconditioned, room side air though the heat exchanger and delivering conditioned air into the room. Slinger fan blade Attaches to the outdoor side of the fan motor shaft and is used to move outside air through the condenser coil, while slinging condensate water out of the base pan and onto the condenser coil, thus lowering the temperature and pressures within the coil. ELECTRICAL COMPONENTS Thermostat Used to maintain the specified room side comfort level System switch Used to regulate the operation of the fan motor, the compressor or to turn the unit off. For troubleshooting, refer to the wiring diagrams and schematics in the back of this service manual. Capacitor Reduces line current and steadies the voltage supply, while greatly improving the torque characteristics of the fan motor and compressor motor. Smart Fan Automatically adjusts the fan speed to maintain the desired room temp. MoneySaver® switch When engaged, it sends the power supply to the fan motor through the thermostat, which allows for a cycle-fan operation. Fan Motor Dual-shafted fan motor operates the indoor blower wheel and the condenser fan blade simultaneously. Heating element Electric resistance heater, available in EQ08 model. Heat anticipator Used to provide better thermostat and room air temperature control. HERMETIC COMPONENTS Compressor Motorized device used to compress refrigerant through the sealed system. Capillary tube A cylindrical meter device used to evenly distribute the flow of refrigerant to the heat exchangers (coils.) 12 COMPONENTS TESTING TESTING THE ELECTRONIC CONTROL BOARDS FOR XQ MODELS X Star ERROR CODE LISTINGS E1 SHORT CYCLE SITUATION: Defined as (compressor powered on before the three minute time delay ten times in one hour. Investigate and correct short cycling problem. PM Power Cool Fan Speed Mode Money Saver ® Fan Only E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error “E2” is no longer displayed and unit is functioning. Replace board if “E2” still displays after exiting Error Code Mode. Clock Timer On/Off Set Hour Start Time Stop Time Temp/Hour Activating Test Mode: Activate test mode by pressing at the same time the “MODE” button and the “TEMP ” button on XQ models. LEDs for Hour, Start, and Stop will blink 1 bps while Test Mode is active. Test Mode has duration of 90 minutes. Test Mode can be activated under any conditions, including Off. Test Mode is cancelled by pressing the On/Off button, unplugging the unit, or when the 90 minutes is timed out. All settings revert to the factory default settings of Cool, 75 degrees F, Timer and Set Hour features are nonfunctional. E3 FROST PROBE OPEN: Normal operation is allowed. Ohm frost probe. Replace probe if ohm value not read. If ohm value is present replace board. E4 FROST PROBE SHORT: Normal operation allowed. Replace probe. E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degree F and unit will operate. Ohm indoor probe. Replace probe if ohm value not read. E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degree F and unit will operate. Replace probe. NOTE: All Error Code displays for Frost & Indoor Probe will allow unit to operate. Unit may or will ice up if faulty components not replaced. Test Mode overrides the three-minute lockout, all delays for compressor and fan motor start / speed change, and no delay when switching modes. FROST PROBE SENSOR: disables compressor at 35 degrees F. During Test Mode, the default settings are; Unit ON, Money Saver ON, 60°F, and High fan speed. INDOOR PROBE SENSOR: Control range is 60°F to 90°F +/- 2°F. Activating Error Code Mode: (Submode of Test Mode) Unit must be in Test Mode to enter Error Code Mode Indoor temperature will be displayed by pressing: (XQ units) The Fan Speed button and the “TEMP button. 1. Activate Error Code Mode by pressing the “TIMER ON/ OFF” button on XQ models. LED for the “TIMER ON/OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP/HR ” button will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP/HR ” button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear. ” The indoor temperature will be displayed for 10 seconds. The display will change back to the Set Point temperature by pressing any key button except for the On/Off button. The indoor temperature can be viewed in all modes, including test mode. IMPORTANT: Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ models, press Timer On/Off button. Or unplug unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit. 13 COMPONENTS TESTING (Continued) EQ08 SYSTEM CONTROL SWITCH - TEST “EQ08” SYSTEM CONTROL SWITCH – TEST 4. Turn thermostat knob counterclockwise to its warmest position. 5. Test for continuity - contacts should be open. Turn knob to phase of switch to be tested. There must be continuity as follows: 1. “Fan Only” Position – between terminals “MS” and “H” 2. “Hi Cool” Position – between terminals “L1” and “C” and “MS” and “H” 3. “Low Cool” Position – between terminals “L1” and “C” and “MS” and “LO” 4. “Low Heat” Position – between terminals “L2” and “2” and “MS” and “LO” 5. “Hi Heat” Position – between terminals “L2” and “2” and “MS” and “H” L1 System Control Switch (EQ Models) B1 NOTE: The thermostat must be within the temperature range listed to open and close. To maintain the comfort level desired, a cross ambient type thermostat is used. The thermostat has a range from 60° ±2°F to 92° ±3°F. The thermostat bulb is positioned in front of the evaporator coil to sense the return air temperature. Thermostat malfunction or erratic operation is covered in the troubleshooting section of this manual. TEST: Cooling/Heating Models: Remove wires from thermostat and check continuity between terminal “2” (common) and “3” for cooling. Check between terminals “2” (common) and “1” for heating. Also check that contacts in thermostat open after placing in either position. NOTE: Temperature must be within range listed to check thermostat. Refer to the troubleshooting section in this manual for additional information on thermostat testing. L2 MS H C LO 2 THERMOSTAT (“EQ08” Models) (See Figure 17) This thermostat is single pole-double throw, cross ambient with a range of 60° to 92°F and a differential of ±2°F. Terminal “2” is common. THERMOSTAT ADJUSTMENT No attempt should be made to adjust thermostat. Due to the sensitivity of the internal mechanism and the sophisticated equipment required to check the calibration, it is suggested that the thermostat be replaced rather than calibrated. Thermostat bulb must be straight to insure proper performance. Figure 18 Thermostat Figure 17 Thermostat (EQ Model) WARNING ELECTRIC SHOCK HAZARD Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death. TEST: 1. Remove leads from thermostat. 2. Turn thermostat knob clockwise to its coldest position. 3. Test for continuity between the two terminals. Contacts should be closed. 14 THERMOSTAT BULB LOCATION The position of the bulb is important in order for the thermostat to function properly. The bulb of the thermostat should be located approximately 45° to a maximum of 60° from horizontal. Also, do not allow the thermostat bulb to touch the evaporator coil. (See Figures 17 and 18) Figure 19 Thermostat Bulb Location (EQ Model) Thermostat sensor holder 020 to be positioned between the 4th and 5th and 6th and 7th rows of tubes from the bottom of the coil at dimension shown COMPONENTS TESTING (Continued) FAN MOTOR A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions. (See Figure 23) WARNING ELECTRIC SHOCK HAZARD Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death. BLOWER/FAN MOTOR - TEST 1. Determine that capacitor is serviceable. 2. Disconnect fan motor wires from fan speed switch or system switch. 3. Apply “live” test cord probes on black wire and common terminal of capacitor. Motor should run at high speed. 4. Apply “live” test cord probes on red wire and common terminal of capacitor. Motor should run at low speed. 5. Apply “live” test cord probes on each of the remaining wires from the speed switch or system switch to test intermediate speeds. If the control is in the “MoneySaver” mode and the thermostat calls for cooling, the fan will start - then stop after approximately 2 minutes; then the fan and compressor will start together approximately 2 minutes later. Figure 23 Blower/Fan Motor Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2 watt resistor can be used to discharge capacitors safely. Remove wires from capacitor and place resistor across terminals. When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested. Capacitor Check with Capacitor Analyzer The capacitor analyzer will show whether the capacitor is “open” or “shorted.” It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will automatically discharge the capacitor when the test switch is released. Capacitor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be avoided by proper connection of the running capacitor terminals. From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the “R” terminal to ground through a possible short in the capacitor. However, from the “S” or start terminal, a much higher potential, possibly as high as 400 volts, exists because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when the identified terminal is connected to the “S” or start terminal. The identified terminal should always be connected to the supply line, or “R” terminal, never to the “S” terminal. When connected properly, a shorted or grounded running capacitor will result in a direct short to ground from the “R” terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature. Dual Rated Run Capacitor Hook-up CAPACITORS WARNING ELECTRIC SHOCK HAZARD Turn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handling. Failure to do so may result in personal injury, or death. FIGURE 24 15 COMPONENTS TESTING (Continued) HEATING ELEMENT (See Figure) All electric heat models are equipped with a heating element. The EQ08 has a 1.15 KW element. Figure Heating Element DRAIN PAN VALVE During the cooling mode of operation, condensate which collects in the drain pan is picked up by the condenser fan blade and sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water. During the heating mode of operation, it is necessary that water be removed to prevent it from freezing during cold outside temperatures. This could cause the condenser fan blade to freeze in the accumulated water and prevent it from turning. The heating element contains a fuse link and a heater limit switch. The fuse link is in series with the power supply and will open and interrupt the power when the temperature reaches 199°F or a short circuit occurs in the heating element. Once the fuse link separates, a new fuse link must be installed. NOTE: Always replace with the exact replacement. The heater element has a high limit control. This control is a bimetal thermostat mounted in the top of the heating element. Should the fan motor fail or filter become clogged, the high limit control will open and interrupt power to the heater before reaching an unsafe temperature condition. The control is designed to open at 110°F ±6°F. Test continuity below 110°F and for open above 110°F. TESTING THE HEATING ELEMENT WARNING ELECTRIC SHOCK HAZARD Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death. Testing of the elements can be made with an ohmmeter across the terminals after the connecting wires have been removed. A cold resistance reading of approximately 10.11 ohms for the 1.15 KW heater should be registered. 16 To provide a means of draining this water, a bellows type drain valve is installed over a drain opening in the base pan. This valve is temperature sensitive and will open when the outside temperature reaches 40°F. The valve will close gradually as the temperature rises above 40°F to fully close at 60°F. Figure 26 Bellows Assembly Drain Pan Valve REFRIGERATION SEQUENCE OF OPERATION A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more difficult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic principles (laws) in its operation they are as follows: 1. “Heat always flows from a warmer body to a cooler body.” 2. “Heat must be added to or removed from a substance before a change in state can occur” 3. “Flow is always from a higher pressure area to a lower pressure area.” 4. “The temperature at which a liquid or gas changes state is dependent upon the pressure.” The refrigeration cycle begins at the compressor. Starting the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then “compresses” this refrigerant, raising its pressure and its (heat intensity) temperature. The refrigerant leaves the compressor through the discharge Line as a hot High pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil’s finned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air. The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter. The liquid refrigerant next enters the metering device. The metering device is a capillary tube. The purpose of the metering device is to “meter” (i.e. control or measure) the quantity of refrigerant entering the evaporator coil. In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device. Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as “boiling”. Since the unit’s blower is moving indoor air across the finned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the “cooling” effect. The expansion and absorbing of heat cause the liquid refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to flow across the evaporator coil. When a sufficient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will “condense” (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to flow across the condenser coil. The particular system design determines at exactly what point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil. The RAC design determines at exactly what point (in the condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a Liquid before leaving the condenser coil. The low pressure (suction) created by the compressor causes the refrigerant to leave the evaporator through the suction line as a cool low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated. Suction Line Evaporator Coil Metering Device Refrigerant Strainer Discharge Line Condenser Coil Compressor Refrigerant Drier Liquid Line 17 R-410A SEALED SYSTEM REPAIR CONSIDERATIONS WARNING Refrigeration system under high pressure Do not puncture, heat, expose to flame or incinerate. Only certified refrigeration technicians should service this equipment. R410A systems operate at higher pressures than R22 equipment. Appropriate safe service and handling practicces must be used. Only use gauge sets designed for use with R410A. Do not use standard R22 gauge sets. The following is a list of important considerations when working with R-410A equipment 18 • R-410A pressure is approximately 60% higher than R-22 pressure. • R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture. • R-410A must never be pressurized with a mixture of air, it may become flammable. • Servicing equipment and components must be specifically designed for use with R-410A and dedicated to prevent contamination. • Manifold sets must be equipped with gauges capable of reading 750 psig (high side) and 200 psig (low side), with a 500-psig low-side retard. • Gauge hoses must have a minimum 750-psig service pressure rating • Recovery cylinders must have a minimum service pressure rating of 400 psig, (DOT 4BA400 and DOT BW400 approved cylinders). • POE (Polyol-Ester) lubricants must be used with R-410A equipment. • To prevent moisture absorption and lubricant contamination, do not leave the refrigeration system open to the atmosphere longer than 1 hour. • Weigh-in the refrigerant charge into the high side of the system. • Introduce liquid refrigerant charge into the high side of the system. • For low side pressure charging of R-410A, use a charging adaptor. • Use Friedrich approved R-410A filter dryers only. R-410A SEALED REFRIGERATION SYSTEM REPAIRS IMPORTANT SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER. EQUIPMENT REQUIRED: 1. Voltmeter 9. 2. Ammeter 10. Low Pressure Gauge - (-30 to 200 lbs.) 3. Ohmmeter 11. Vacuum Gauge - (0 - 1000 microns) 4. E.P.A. Approved Refrigerant Recovery System 12. Facilities for flowing nitrogen through refrigeration tubing during all brazing processes. 5. Vacuum Pump (capable of 200 microns or less vacuum.) 6. Acetylene Welder High Pressure Gauge - (0 to 750 lbs.) EQUIPMENT MUST BE CAPABLE OF: 1. Recovering refrigerant to EPA required levels. 7. Electronic Halogen Leak Detector capable of detecting HFC (Hydrofluorocarbon) refrigerants. 8. Accurate refrigerant charge measuring device such as: a. Balance Scales - 1/2 oz. accuracy b. Charging Board - 1/2 oz. accuracy WARNING RISK OF ELECTRIC SHOCK Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service. Failure to do so could result in electric shock, serious injury or death. WARNING HIGH PRESSURE HAZARD Sealed Refrigeration System contains refrigerant and oil under high pressure. Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants. Failure to follow these procedures could result in serious injury or death. Refrigerant Charging NOTE: Because the XStar system is a sealed system, service process tubes will have to be installed. First install a line tap and remove refrigerant from system. Make necessary sealed system repairs and vacuum system. Crimp process tube line and solder end shut. Do not leave a service valve in the sealed system. 2. Evacuation from both the high side and low side of the system simultaneously. 3. Introducing refrigerant charge into high side of the system. 4. Accurately weighing the refrigerant charge introduced into the system. Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or efficiency. Accordingly, the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged. Too much refrigerant (overcharge) in the system is just as bad (if not worse) than not enough refrigerant (undercharge). They both can be the source of certain compressor failures if they remain uncorrected for any period of time. Quite often, other problems (such as low air flow across evaporator, etc.) are misdiagnosed as refrigerant charge problems. The refrigerant circuit diagnosis chart will assist you in properly diagnosing these systems. An overcharged unit will at times return liquid refrigerant (slugging) back to the suction side of the compressor eventually causing a mechanical failure within the compressor. This mechanical failure can manifest itself as valve failure, bearing failure, and/or other mechanical failure. The specific type of failure will be influenced by the amount of liquid being returned, and the length of time the slugging continues. Not enough refrigerant (undercharge) on the other hand, will cause the temperature of the suction gas to increase to the point where it does not provide sufficient cooling for the compressor motor. When this occurs, the motor winding temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector. Continued overheating of the motor windings and/or cycling of the overload will eventually lead to compressor motor or overload failure. 19 Method Of Charging / Repairs The acceptable method for charging the RAC system is the Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate. The weighed in method should always be used whenever a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method, requires the following steps: 1. Install a piercing valve to remove refrigerant from the sealedsystem. (Piercing valve must be removed from the system before recharging.) 2. Recover Refrigerant in accordance with EPA regulations. WARNING BURN HAZARD Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch. Failure to follow these procedures could result in moderate or serious injury. 3. Install a process tube to sealed system. CAUTION FREEZE HAZARD Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant. Failure to follow these procedures could result in minor to moderate injury. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refrigerant with the property quantity of R410-A refrigerant. 7. Start unit, and verify performance. WARNING BURN HAZARD Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch. Failure to follow these procedures could result in moderate or serious injury. 8. Crimp the process tube and solder the end shut. 20 WARNING WARNING ELECTRIC SHOCK HAZARD Turn off electric power before service or installation. HIGH PRESSURE HAZARD Sealed Refrigeration System contains refrigerant and oil under high pressure. Extreme care must be used, if it becomes necessary to work on equipment with power applied. Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants. Failure to do so could result in serious injury or death. Failure to follow these procedures could result in serious injury or death. Undercharged Refrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit. A check of the amperage drawn by the compressor motor should show a lower reading. (Check the Unit Specification.) After the unit has run 10 to 15 minutes, check the gauge pressures. Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures. To check for an undercharged system, turn the unit on, allow the compressor to run long enough to establish working pressures in the system (15 to 20 minutes). During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator; an intermittent hissing and gurgling sound indicates a low refrigerant charge. Intermittent frosting and thawing of the evaporator is another indication of a low charge, however, frosting and thawing can also be caused by insufficient air over the evaporator. Checks for an undercharged system can be made at the compressor. If the compressor seems quieter than normal, it is an indication of a low refrigerant charge. Overcharged Refrigerant Systems Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confirm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated. of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of over charge). Suction pressure should be slightly higher. Whenever an overcharged system is indicated, always make sure that the problem is not caused by air flow problems. Improper air flow over the evaporator coil may indicate some of the same symptoms as an over charged system. An overcharge can cause the compressor to fail, since it would be “slugged” with liquid refrigerant. The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing 21 Restricted Refrigerant System Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions. A partial restriction allows some of the refrigerant to circulate through the system. With a complete restriction there is no circulation of refrigerant in the system. Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges will not equalize at all. With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there. A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds The following conditions are based primarily on a system in the cooling mode. Restricted refrigerant systems display the same symptoms as a “low-charge condition.” When the unit is shut off, the gauges may equalize very slowly. 22 at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor. Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other. COMPRESSOR CHECKS WARNING ELECTRIC SHOCK HAZARD Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied. External Overload The compressor is equipped with an external overload which senses both motor amperage and winding temperature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor. Locked Rotor Voltage (L.R.V.) Test Heat generated within the compressor shell, usually due to recycling of the motor, is slow to dissipate. It may take anywhere from a few minutes to several hours for the overload to reset. Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition. Checking the External Overload Failure to do so could result in serious injury or death. Single Phase Connections Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of the compressor. Restore power to unit. Determine L.R.V. Start the compressor with the volt meter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC, as specified on the rating plate. If less than minimum, check for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc. Amperage (L.R.A.) Test The running amperage of the compressor is the most important of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically. Single Phase Running and L.R.A. Test NOTE: Consult the specification and performance section for running amperage. The L.R.A. can also be found on the rating plate. WARNING ELECTRIC SHOCK HAZARD Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied. Failure to do so could result in serious injury or death. WARNING BURN HAZARD Certain unit components operate at temperatures hot enough to cause burns. Proper safety procedures must be followed, and proper protective clothing must be worn. Failure to follow this warning could result in moderate to serious injury. With power off, remove the leads from compressor terminals. If the compressor is hot, allow the overload to cool before starting check. Using an ohmmeter, test continuity across the terminals of the external overload. If you do not have continuity; this indicates that the overload is open and must be replaced. Select the proper amperage scale and clamp the meter probe around the wire to the “C” terminal of the compressor. Turn on the unit and read the running amperage on the meter. If the compressor does not start, the reading will indicate the locked rotor amperage (L.R.A.). 23 Single Phase Resistance Test Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). 1. Improper air flow over the evaporator. 2. Overcharged refrigerant system causing liquid to be returned to the compressor. 3. Restricted refrigerant system. 4. Lack of lubrication. In a single phase PSC compressor motor, the highest value will be from the start to the run connections (“S” to “R”). The next highest resistance is from the start to the common connections (“S” to “C”). The lowest resistance is from the run to common. (“C” to “R”) Before replacing a compressor, check to be sure it is defective. 5. Liquid refrigerant returning to compressor causing oil to be washed out of bearings. 6. Noncondensables such as air and moisture in the system. Moisture is extremely destructive to a refrigerant system. GROUND TEST Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal. If a reading is obtained the compressor is grounded and must be replaced. 7. Defective capacitors. Touch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from terminals common to run (“C” to “R”). Add values “C” to “S” and “C” to “R” together and check resistance from start to run terminals (“S” to “R”). Resistance “S” to “R” should equal the total of “C” to “S” and “C” to “R.” Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that compressor is not out on internal overload. Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has been operating for sometime, a careful examination must be made to determine why the compressor failed. 24 Many compressor failures are caused by the following conditions: COMPRESSOR REPLACEMENT Recommended procedure for compressor replacement 3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere. 4. Carefully pour a small amount of oil from the suction stub of the defective compressor into a clean container. 5. Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit. 6. If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures. 7. Install the replacement compressor. WARNING RISK OF ELECTRIC SHOCK Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service. Failure to do so could result in electric shock, serious injury or death. 1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing. WARNING WARNING HIGH PRESSURE HAZARD Sealed Refrigeration System contains refrigerant and oil under high pressure. EXPLOSION HAZARD The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc. Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants. Failure to follow proper safety procedures result in serious injury or death. Failure to follow these procedures could result in serious injury or death. 2. Recover all refrigerant from the system though the process tubes. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. Do not use gauge manifold for this purpose if there has been a burnout. You will contaminate your manifold and hoses. Use a Schrader valve adapter and copper tubing for burnout failures. 8. Pressurize with a combination of R410-A and nitrogen and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found. Repeat Step 8 to insure no more leaks are present. 9. WARNING HIGH TEMPERATURES Extreme care, proper judgment and all safety procedures must be followed when testing, troubleshooting, handling or working around unit while in operation with high temperature components. Wear protective safety aids such as: gloves, clothing etc. CAUTION FREEZE HAZARD Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant. Failure to do so could result in serious burn injury. Failure to follow these procedures could result in minor to moderate injury. NOTICE FIRE HAZARD The use of a torch requires extreme care and proper judgment. Follow all safety recommended precautions and protect surrounding areas with fire proof materials. Have a fire extinguisher readily available. Failure to follow this notice could result in moderate to serious property damage. Evacuate the system with a good vacuum pump capable of a final vacuum of 200 microns or less. The system should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections. 10. Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate measuring device, such as a charging cylinder, electronic scales or similar device is necessary. 25 SPECIAL PROCEDURE IN THE CASE OF MOTOR COMPRESSOR BURNOUT WARNING ELECTRIC SHOCK HAZARD Turn off electric power before service or installation. Failure to do so may result in personal injury, or death. WARNING HIGH PRESSURE HAZARD Sealed Refrigeration System contains refrigerant and oil under high pressure. Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants. Failure to follow these procedures could result in serious injury or death. WARNING EXPLOSION HAZARD The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc. Failure to follow proper safety procedures result in serious injury or death. 1. Recover all refrigerant and oil from the system. 2. Remove compressor, capillary tube and filter drier from the system. 3. Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent. Use approved flushing agent to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary. Ensure all acid is neutralized. 4. Reassemble the system, including new drier strainer and capillary tube. 5. Proceed with step 8-10 on previous page. ROTARY COMPRESSOR SPECIAL TROUBLESHOOTING AND SERVICE Basically, troubleshooting and servicing rotary compressors is the same as on the reciprocating compressor with only one main exception: NEVER, under any circumstances, liquid charge a rotary compressor through the LOW side. Doing so would cause permanent damage to the new compressor. 26 ROUTINE MAINTENANCE WARNING ELECTRIC SHOCK HAZARD Turn off electric power before inspections, maintenances, or service. Extreme care must be used, if it becomes necessary to work on equipment with power applied. Failure to do so could result in serious injury or death. WARNING EXCESSIVE WEIGHT HAZARD Use two people to lift or carry the unit, and wear proper protective clothing. Failure to do so may result in personal injury. WARNING CUT/SEVER HAZARD Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury. NOTICE Units are to be inspected and serviced by qualified service personnel only. Use proper protection on surrounding property. Failure to follow this notice could result in moderate or serious property damage. NOTICE AIR FILTER Clean the unit air intake filter at least every 300 to 350 hours of operation. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling. COILS AND BASE PAN The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve. BLOWER WHEEL / HOUSING / CONDENSER FAN / SHROUD Inspect the indoor blower housing, evaporator blade, condenser fan blade and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.). Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them. ELECTRONIC / ELECTRICAL / MECHANICAL Periodically (at least yearly or bi-yearly): inspect all control components: electronic, electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use an electronic tester to measure wet bulb temperatures indoors and outdoors. Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser, to prevent damage to the coil and/or base pan. 27 ROUTINE MAINTENANCE (Continued) NOTICE Do not drill holes in the bottom of the drain pan or the underside of the unit. Not following this notice could result in damage to the unit or condensate water leaking inappropriately which could cause water damage to surrounding property. SLEEVE / DRAIN Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed. FRONT COVER Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis. CLEARANCES Inspect the surrounding area (inside and outside) to ensure that the unit’s clearances have not been compromised or altered. Compressor Condenser Coil Front Cover Discharge Air System Controls Outdoor Grille Evaporator Coil Sleeve Return Air Grille/Filter Blower Wheel Blower Motor 28 Basepan Condenser Fan Blade ROOM AIR CONDITIONER UNIT PERFORMANCE TEST DATA SHEET DATE: _______________ MODEL:_______________ SERIAL:________________ IS THERE A FRIEDRICH SLEEVE INSTALLED? IS THERE A CHASSIS SEAL GASKET INSTALLED? IS MAINTENANCE BEING PERFORMED? If NO is checked use back of sheet for explanation YES ____ ____ ____ NO ____ ____ ____ ELECTRICAL: LINE VOLTAGE (STATIC) START UP VOLTAGE AMPERAGE DRAW AMPERAGE DRAW --------------------------------- VOLTS VOLTS AMPS (COOL) AMPS (HEAT) COMPRESSOR LOCKED ROTOR AMPS RUNNING AMPS LOCKED ROTOR VOLTAGE --------- AMPS --------- AMPS --------- VOLTS INDOOR TEMPERATURES: INDOOR AMBIENT TEMPERATURE RELATIVE HUMIDITY (RH) INDOOR -------- F -------- % COOL DISCHARGE AIR TEMPERATURE (INDOOR) RETURN AIR TEMPERATURE (INDOOR) DIFFERENTIAL ---------- F ---------- F ---------- F HEAT --------- F --------- F --------- F OUTDOOR TEMPERATURE: OUTDOOR AMBIENT TEMPERATURE RH OUTDOOR --------- F --------- % CONDENSER: DISCHARGE AIR TEMPERATURE (OUTDOOR) INTAKE AIR TEMPERATURE (OUTDOOR DIFFERENTIAL --------- F --------- F --------- F ---------- F ---------- F ---------- F APPLICATION USE ------------------------- ROOM (RESIDENTIAL OR COMMERCIAL) This is a general guide. Please consult manual J or M for exact load calculations. 1. If heavily shaded, reduce capacity 10%. 2. If very sunny, add 10%. 3. Add 500 BTU/H per person over 2 people. 4. Add 4,000 BTU/H if area is a kitchen. Due to variations in room design, climate zone and occupancy, larger areas may require the use of multiple units to provide the optimal cooling solution. 29 29 GENERAL TROUBLESHOOTING TIPS Problem Possible Cause The unit is turned to the off position, Unit does not operate. Turn the unit to the on position and raise or lower temperature setting (as appropriate) to call for operation. The LCDI power cord is unplugged. Plug into a properly grounded 3 prong receptacle. See “Electrical Rating Tables” on pg. 6 for the proper receptacle type for your unit. The LCDI power cord has tripped (Reset button has popped out). Press and release RESET (listen for click; Reset button latches and remains in) to resume operation. The circuit breaker has tripped or the supply circuit fuse has blown. Reset the circuit breaker, or replace the fuse as applicable. If the problem continues, contact a licensed electrician. There has been a local power failure. The unit will resume normal operation once power has been restored. Other appliances are being used on the same circuit. The unit requires a dedicated outlet circuit, not shared with other appliances. An extension cord is being used. Do NOT use an extension cord with this or any other air conditioner. The circuit breaker or time-delay fuse is not of the proper rating. Replace with a circuit breaker or time-delay fuse of the proper rating. See “Electrical Rating Tables” on pg. 6 for the proper circuit breaker/fuse rating for your unit. If the problem continues, contact a licensed electrician. The LCDI power cord can trip (Reset button pops out) due to disturbances on your power supply line. Press and release RESET (listen for click; Reset button latches and remains in) to resume normal operation. Unit Trips Circuit Breaker or Blows Fuses. LCDI Power Cord Trips (Reset Button Pops Out). Possible Solution Electrical overload, overheating, or cord pinching can trip (Reset button pops out) the LCDI power cord. NOTE: Once the problem has been determined and corrected, press and release RESET (listen for click; Reset button latches and remains in) to resume normal operation. A damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and must not be repaired. The return/discharge air grille is blocked. Ensure that the return and/or discharge air paths are not blocked by curtains, blinds, furniture, etc. Windows or doors to the outside are open. Ensure that all windows and doors are closed. The temperature is not set at a cool enough/warm enough setting. Adjust the Temperature control to a cooler or warmer setting as necessary. Unit Does Not Cool/Heat remove obstruction. On And Off Too Frequently. 30 The indoor coil or outdoor coil is dirty or obstructed. Clean the coils, (See Routine Maintenance), or remove obstruction. There is excessive heat or moisture (cooking, showers, etc.) in the room. Be sure to use exhaust vent fans while cooking or bathing and, if possible, try not to use heat producing appliances during the hottest part of the day. The temperature of the room you are trying to cool is extremely hot. Allow additional time for the air conditioner to cool off a very hot room. GENERAL TROUBLESHOOTING TIPS (CONTINUED) Problem Possible Cause The outside temperature is below 60° F (16° C). The digital control is set to fan cycling mode. Since the fan does not circulate the room air continuously at this setting, the room air does not mix as well and hot (or cold) spots may result. Using the continuous fan setting is recommended to obtain optimum comfort levels. Unit Does Not Cool/Heat On And Off Too Frequently (continued). Unit Runs Too Much. Possible Solution Do not try to operate your air conditioner in the cooling mode when the outside temperature is below 60° F (16° C). The unit will not cool properly, and the unit may be damaged. cooling capacity to match the heat gain of the room. Check the cooling capacity of your unit to ensure it is properly sized for the room in which it is installed. Room air conditioners are not designed to cool multiple rooms. heating capacity to match the heat loss of the room. Check the heating capacity of your unit. Air conditioners are sized to meet the cooling load, and heater size is then selected to meet the heating load. In extreme northern climates, room air conditioners may not be able to be used as a primary source of heat. This may be due to an excessive heat load in the room. If there are heat producing appliances in use in the room, or if the room is heavily occupied, the unit will need to run longer to remove the additional heat. It may also be due to an improperly sized unit. Be sure to use exhaust vent fans while cooking or bathing and, if possible, try not to use heat producing appliances during the hottest part of the day. This may be normal for higher your new air conditioner may result in the unit running longer than you feel it should. This may be more apparent, if it replaced an compared to older models. You may notice that the discharge air temperature of your new air conditioner may not seem as cold as you may be accustomed to from older units. This does not, however, indicate a reduction in the cooling capacity of the unit. capacity rating (Btu/h) listed on the unit’s rating 31 COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Compressor does not run Possible Cause Low voltage Check voltage at compressor. 115V & 230V units will operate at 10% voltage variance T-stat not set cold enough or inoperative or electronic control board is bad Set t-stat to coldest position. Test t-stat & replace if inoperative Compressor hums but cuts off on overload Hard start compressor. Direct test compressor. If compressor starts, add starting components Open or shorted compressor windings Check for continuity & resistance Open overload Test overload protector & replace if inoperative Open capacitor Test capacitor & replace if inoperative Inoperative system switch, thermistor or electronic board Test for continuity in all positions. Replace if inoperative switch or electronic board. Broken, loose or incorrect wiring Refer to appropriate wiring diagrams to check wiring Problem Fan motor does not run Possible Cause 32 Action Inoperative system switch Test switch & replace if inoperative Broken, loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor & replace if inoperative Fan speed switch open Test switch & replace if inoperative Inoperative fan motor Test fan motor & replace if inoperative (be sure internal overload has had time to reset) Problem Does not cool or only cools slightly Action Possible Cause Action Undersized unit Refer to industry standard sizing chart Thermistor or electronic board is bad, T-stat open or inoperative Set to coldest position. Test t-stat or electronic control board & replace if necessary. Dirty filter Clean as recommended in Owner ’s Manual Dirty or restricted condenser or evaporator coil Use pressure wash or biodegradable cleaning agent to clean Poor air circulation Adjust discharge louvers. Use high fan speed Fresh air or exhaust air door open on applicable models Close doors. Instruct customer on use of this feature Low capacity - undercharge Check for leak & make repair Compressor not pumping properly Check amperage draw against nameplate. If not conclusive, make pressure test COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Unit does not run Possible Cause Fuse blown or circuit tripped Replace fuse, reset breaker. If repeats, check fuse or breaker size. Check for shorts in unit wiring & components Power cord not plugged in Plug it in System switch in “OFF” position Set switch correctly Inoperative system switch or open electronic control board Test for continuity Loose or disconnected wiring at switch, control board or other components Check wiring & connections. Reconnect per wiring diagram Problem Evaporator coil freezes up Problem Possible Cause T-stat does not turn unit off Action Dirty filter Clean as recommended in Owner ’s Manual Restricted airflow Check for dirty or obstructed coil. Use pressure wash or biodegradable cleaning agent to clean Inoperative t-stat or thermistors Test for continuity Short of refrigerant De-ice coil & check for leak Inoperative fan motor Test fan motor & replace if inoperative Partially restricted capillary tube De-ice coil. Check temp. differential (delta T) across coil. Touch test coil return bends for same temp. Test for low running current Possible Cause Action Excessive heat load Unit undersized. Test cooling performance & replace with larger unit if needed Restriction in line Check for partially iced coil & check temperature split across coil Compressor runs continually & does Refrigerant leak not cycle off Problem Action Check for oil at silver soldered connections. Check for partially iced coil. Check split across coil. Check for low running amperage T-stat contacts stuck Check operation of t-stat. Replace if contacts remain closed. T-stat incorrectly wired Refer to appropriate wiring diagram Thermistor shorted Replace thermistor or electronic control board Possible Cause Action T-stat contacts stuck Disconnect power to unit. Remove cover of t-stat & check if contacts are stuck. If so, replace t-stat T-stat set at coldest point Turn to higher temp. setting to see if unit cycles off Incorrect wiring Refer to appropriate wiring diagrams Unit undersized for area to be cooled Refer to industry standard sizing chart Defective thermistor Replace thermistor or electronic control board 33 COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Overload inoperative. Opens too soon Check operation of unit. Replace overload if system operation is satisfactory Compressor restarted before system pressures equalized Allow a minimum of 2 minutes to allow pressures to equalize before attempting to restart. Instruct customer of waiting period Compressor runs Low or Àuctuating voltage for short periods only. Cycles on overload Incorrect wiring Problem T-stat does not turn unit on Problem Noisy operation Problem Water leaks into the room 34 Action Check voltage with unit operating. Check for other appliances on circuit. Air conditioner should be in separate circuit for proper voltage & fused separately Refer to appropriate wiring diagram Shorted or incorrect capacitor Check by substituting a known good capacitor of correct rating or test cap Restricted or low air Àow through condenser coil or evaporator coil Check for proper fan speed or blocked coils Compressor running abnormally hot Check for kinked discharge line or restricted condenser. Check amperage Possible Cause Action Loss of charge in t-stat bulb (EQ08M11) Place jumper across t-stat terminals to check if unit operates. If unit operates, replace t-stat. Loose or broken parts in t-stat Check as above Incorrect wiring Refer to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board Possible Cause Action Poorly installed Refer to Installation Manual for proper installation Fan blade striking chassis Reposition - adjust motor mount Compressor vibrating Check that compressor grommets have not deteriorated. Check that compressor mounting parts are not missing Improperly mounted or loose cabinet parts refrigerant tubes Check assembly & parts for looseness, rubbing & rattling. Correct as needed Possible Cause Action Evaporator drain pan overÀowing Clean obstructed drain trough Condensation forming underneath base pan Evaporator drain pan broken or cracked. Reseal or replace. No chassis gasket installed. Install chassis gasket Poor installation resulting in rain entering the room Check installation instructions. Reseal as required Condensation on discharge grille louvers Dirty evaporator coil. Use pressure wash or biodegradable cleaning agent to clean. Environmental phenomena: point supply louvers upward Chassis gasket not installed Install gasket, per Installation manual Downward slope of unit is too steep inward Refer to installation manual for proper installation COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Water “spitting” into room Problem Excessive moisture Problem T-stat or thermistor short cycles Problem Possible Cause Action Sublimation: When unconditioned saturated, outside air mixes with conditioned air, condensation forms on the cooler surfaces Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve. Also, ensure that fresh air/exhaust vents (on applicable models) are in the closed position & are in tact Downward pitch of installation is too steep towards back of unit Follow installation instructions to ensure that downward pitch of installed unit is no less than 1/4” & no more than 3/8” Restricted coil or dirty filter Clean & advise customer of periodic cleaning & maintenance needs of entire unit Possible Cause Action Insufficient air circulation thru area to be air conditioned Adjust louvers for best possible air circulation Oversized unit Operate in “MoneySaver” position Inadequate vapor barrier in building structure, particularly floors Advise customer Possible Cause Action Defective thermistor Replace thermistor or electronic control board T-stat differential too narrow Replace t-stat Plenum gasket not sealing, allowing discharge air to short cycle t-stat Check gasket. Reposition or replace as needed Restricted coil or dirty filter Clean & advise customer of periodic cleaning & maintenance needs of entire unit Possible Cause Heat anticipator (resistor) wire disconnected at t-stat or system switch Action Refer to appropriate wiring diagram Disconnect plus from outlet. Remove resistor from bracket. Insert plug & depress “COOL” Prolonged off Heat anticipator (resistor) shorted or & “FAN AUTOMATIC” buttons. Place t-stat to cycles (automatic open warmest setting. Feel resistor for temperature. operation) If no heat, replace resistor Problem Outside water leaks Partial loss of charge in t-stat bulb causing a wide differential Replace t-stat Defective thermistor Replace thermistor or electronic control board Possible Cause Action Evaporator drain pan cracked or obstructed Repair, clean or replace as required Water in compressor area Detach shroud from pan & coil. Clean & remove old sealer. Reseal, reinstall & check Obstructed condenser coil Use pressure wash or biodegradable cleaning agent to clean Fan blade/slinger ring improperly positioned Adjust fan blade to 1/2” of condenser coil fin pack 35 HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Room temperature uneven (Heating cycle) Possible Cause Action Heat anticipator (resistor) shorted (on applicable models) Disconnect power to unit. Remove resistor from t-stat bulb block. Plug in unit & allow to operate. Feel resistor for heat. If not heat, replace resistor Wide differential - partial loss of t-stat bulb charge Replace t-stat Refer to appropriate wiring diagram. Resistor is energized during "ON" cycle of compressor or fan. Incorrect wiring Problem Possible Cause Opened doors or windows * NOTE: 36 Close doors or windows. Dirty filter Clean as recommended in Owner's Manual Unit undersized Check heat rise across coil. If unit operates efficiently, check if insulation can be added to attic or walls. If insulation is adequate, recommend additional unit or larger one Heater hi-limit control cycling on & off Check for adequate fan air across heater. Check control for open at 110°F & close at 100°F * Does not heat adequately Action Shorted or opened heater Ohmmeter/continuity check Incorrect wiring Check applicable wiring diagram Heater size on the EQ08M11 is: 1.15 KW. * XQ05M10 ELECTRONIC CONTROL COOL ONLY MODELS: XQ06M10 XQ08M10 * * XQ10M10 * *Last character may vary. 37 ELECTROMECHANICAL CONTROL COOL WITH ELECTRIC HEAT MODEL: EQ08M11 * 38 *Last character may vary. INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE FORM FOR ROOM AIR CONDITIONERS (AHAM PUB. NO. RAC-1) A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations which do not require specific conditions of inside temperature and humidity. B. The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas in the continental United States having other outside design temperatures by applying a correction factor for the particular locality as determined from the map. C. The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as living rooms, offices, etc.) D. The numbers of the following paragraphs refer to the corresponding numbered item on the form: 1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for “Inside Shades.” For windows shaded by outside awnings or by both outside awnings and inside shades (or venetian blinds), use the factor for “Outside Awnings.” “Single Glass” includes all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows, and glass block. Only one number should be entered in the right hand column for Item 1, and this number should represent only the exposure with the largest load. 2. Multiply the total square feet of all windows in the room by the applicable factor. 3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should be considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered “North Exposure.” Do not consider trees and shrubbery as providing permanent shading. An uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.” An insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.” 3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any unconditioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms. 4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application (use one line only.) 5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the ground or over a basement. 6. Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use a minimum of 2 people. 7. Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given. 8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor. NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis. 9. 10. Total the loads estimated for the foregoing 8 items. Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour. E. For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously. F. Intermittent loads such as kitchen and laundry equipment are not included in this form. 4 39 COOLING LOAD ESTIMATE FORM HEAT GAIN FROM 1. 2. 3. 4. WINDOWS: Northeast * East Southeast South Southwest West Northwest North FACTORS DAY QUANTITY Heat gain from the sun. These factors are for single glass only. For glass block, multiply the above factors by 0.5; for double glass or storm windows, multiply the above factors by 0.8. WINDOWS: Heat by conduction (Total of all windows.) Single glass Double glass or glass block WALLS: (Based on linear feet of wall) a. Outside walls North Exposure Other than North exposure b. Inside Walls (between conditioned and unconditioned spaces only.) ROOF OR CEILING: (Use one only) a. Roof, uninsulated b. Roof, 1 inch or more insulation c. Ceiling, occupied space above d. Ceiling, insulated, with attic space above e. Ceiling, uninsulated, with attic space above ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. BTU/Hr. (Quantity x Factor) No (Area Inside Outside Shades* Shades* Awnings* X Factor) 60 Use 20 ____ 25 80 only 25 ____ 40 75 the 20 ____ 30 75 largest 20 ____ 35 110 load. 30 ____ 45 150 Use 45 ____ 65 120 only 35 ____ 50 0 one. 0 ____ 0 _____ _____ 14 7 ____sq. ft. ____sq. ft. Light Construction Heavy Construction 30 60 20 30 ____ ft. ____ ft. ____ ____ ____ ____ ____ ____ ____ ____ _____ _____ ____sq. ft. 30 _____ ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. ____sq. ft. 19 8 3 5 12 _____ _____ _____ _____ _____ 3 _____ 600 _____ 3 _____ 5. Floor: (Disregard if floor is directly on ground or over a basement. ____sq. ft. 6. NUMBER OF PEOPLE ____ 7. LIGHTS AND ELECTRICAL EQUIPMENT IN USE ____watts 8. DOORS AND ARCHES CONTINUOUSLY OPENED TO UNCONDITIONED SPACE: (TOTAL LINEAR FEET OF WIDTH.) ____ft. 300 _____ SUBTOTAL ***** ***** _____ (Factor from Map) = ____ 9. 10. TOTAL COOLING LOAD (BTU per hour to be used for selection of room air conditioner(s).) ____ Total in Item 9 X ____ 5 40 HEAT LOAD FORM The heat load form on the following page may be used by servicing personnel to determine the heat loss of a conditioned space and the ambient winter design temperatures in which the unit will heat the calculated space. The upper half of the form is for computing the heat loss of the space to be conditioned. It is necessary only to insert the proper measurements on the lines provided and multiply by the given factors, then add this result for the total heat loss in BTU/Hr./°F. The BTU/Hr. per °F temperature difference is the 70°F inside winter designed temperature minus the lowest outdoor ambient winter temperature of the area where the unit is installed. This temperature difference is used as the multiplier when calculating the heat loss. The graph shows the following: Left Hand Scale Unit capacity BTU/Hr. or heat loss BTU/Hr. Bottom Scale Outdoor ambient temperature, base point. Heat Pump Model BTU/Hr. capacity heat pump will deliver at outdoor temperatures. Balance Point Maximum BTU/Hr. heat pump will deliver at indicated ambient temperature. Following is an example using the heat load form: A space to be conditioned is part of a house geographically located in an area where the lowest outdoor ambient winter temperature is 40°F. The calculated heat loss is 184 BTU/ Hr./°F. Subtract 40°F (lowest outdoor ambient temperature for the geographical location) from 70°F (inside design temperature of the unit) for a difference of 30°F. Multiply 184 by 30 for a 5500 BTU/Hr. total heat loss for the calculated space. On the graph, plot the base point (70°) and a point on the 40°F line where it intersects with the 5500 BTU/Hr. line on the left scale. Draw a straight line from the base point 70 through the point plotted at 40°F. This is the total heat loss line. Knowing that we have a 5500 BTU/Hr. heat loss, and we expect that our heat pump will maintain a 70°F inside temperature at 40°F outdoor ambient, we plot the selected unit capacity BTU/Hr. of the unit between 35° and 60° on the graph and draw a straight line between these points. Where the total heat loss line and the unit capacity line intersect, read down to the outdoor ambient temperature scale and find that this unit will deliver the required BTU/Hr. capacity to approximately 30°F. 6 41 HEATING LOAD FORM FRIEDRICH ROOM UNIT HEAT PUMPS WALLS: (Linear Feet) 2” Insulation Average WINDOWS & DOORS (Area, sq. ft.) Single Glass: Double Glass: BTU/HR PER °F TEMP. DIFFERENCE Lin. Ft. x 1.6 Lin. Ft. x 2.6 Sq. Ft. x 1.13 Sq. Ft. x 0.61 INFILTRATION - WINDOWS & DOORS: AVG. Loose Lin. Ft. x 1.0 Lin. Ft. x 2.0 CEILING: (Area, Sq. Ft.) Insulated (6”) Insulated (2”) Built-up Roof (2” insulated Built-up Roof (1/2” insulated) No Insulation Sq. Ft. x 0.07 Sq. Ft. x 0.10 Sq. Ft. x 0.10 Sq. Ft. x 0.20 Sq. Ft. x 0.33 FLOOR: (Area, Sq. Ft.) Above Vented Crawl space Insulated (1:) Uninsulated * Slab on Ground 1” Perimeter insulation * Based on Linear Feet of outside wall Sq. Ft. x 0.20 Sq. Ft. x 0.50 Lin. Ft. x 1.70 Lin. Ft. x 1.00 TOTAL HEAT LOSS PER °F BTU/HR/°F Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the unit capacity line represents the winter design heating load. 7 42 Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 1-800-541-6645 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase. SECOND THROUGH FIFTH YEAR SEALED REFRIGERANT SYSTEM: because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within sixty months from the date of the original purchase. APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia, and Canada. This warranty is not applicable to: 1. 2. 3. A Products on which the model and serial numbers have been removed. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes, material shortages beyond the control of FRIEDRICH, or acts of God. OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540. LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY. Performance of Friedrich’s Warranty obligation is limited to one of the following methods: 1. Repair of the unit 2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit. 3. Providing a replacement unit of equal value NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not allow the limitation or exclusion of consequential or incidental damages, so the foregoing exclusions and limitations may not apply to you. OTHER: PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services. All service calls for explaining the operation of this product will be the sole responsibility of the consumer. All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made. (10-08) 43 TECHNICAL SUPPORT CONTACT INFORMATION FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 (210) 546-0500 877-599-5665 x 261 FAX (210) 546-0731 Email: tac@friedrich.com www.friedrich.com Printed in the U.S.A. 44 FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 P 210-546-0500 | F 210-546-0731 www.friedrich.com Printed in the U.S.A. X-Star-ServMan (1-11)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Page Count : 47 Producer : GPL Ghostscript 8.64 Create Date : 2011:02:23 13:21:07-06:00 Modify Date : 2011:02:23 13:21:07-06:00 Title : Xstar_ServMan_02-21-11.indd Creator : Adobe InDesign CS5 (7.0) Author : ArtEXIF Metadata provided by EXIF.tools