Fujimoto Fuji Differential Pressure Transmitter Fkk 4 Users Manual
FKK 4 to the manual eba0b0a1-82dc-472b-b956-d451eac58d11
2015-02-09
: Fujimoto Fujimoto-Fuji-Differential-Pressure-Transmitter-Fkk-4-Users-Manual-552554 fujimoto-fuji-differential-pressure-transmitter-fkk-4-users-manual-552554 fujimoto pdf
Open the PDF directly: View PDF .
Page Count: 74
Instruction Manual
FCX-CII SERIES TRANSMITTERS
Differentiel pressure Transmitter (FKK ...4)
Pressure Transmitter (FKP...4)
Pressure Transmitter with remote seal (FKP...E)
Absolute Pressure Transmitter (FKH...E)
Fuji Electric France S.A.
INF-TN3FCXC2b-E
INTRODUCTION
INTRODUCTION
Thank you very much for your purchase of the Fuji FCX-CII Series Transmitter.
This instruction manual covers the FCX-CII series transmitter and contains information about the
installation, piping, wiring, operation and maintenance of the FCX-CII series (FKK...4 • FKP...4 •
FKP...E).
• First read this instruction manual carefully until an adequate understanding is required, and then
proceed to installation, operation and maintenance of the FCX-CII Series transmitter.
• The specifications of the transmitter will be changed without prior notice for further product
improvement.
• Modification of the transmitter without permission is strictly prohibited. Fuji will not bear any
responsibility for a trouble caused by such a modification.
• This instruction manual should be kept by a person who is actually using the transmitter.
• After reading this manual, keep it at a place easier to access.
• This manual should be delivered to the end user without fail.
• For detail specifications and outline diagrams, refer to the specifications furnished separately.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN513035. The applicable standards used to demonstrate
compliance are :EN 50081-2 :-1993
Conducted and Radiated emissions
EN 50082-2 :-1995
Radiated immunity, ESD and FBT
Manufacturer:
Type:
Date of manufacture:
Product nationality:
Fuji Electric France
Described in nameplate on main frame (see Page v)
Described in nameplate on main frame
France
© Fuji Electric France 2002
Request
Issued in February, 2002
• Transcription of a part or the whole of this manual without permission is prohibited.
• The contents of this manual are subject to change without prior
notice.
i
CAUTION ON SAFETY
First of all, read this “Caution on Safety” to ensure correct operation of the
transmitter.
• The cautionary descriptions listed here contain important information about safety, so they should be
observed without fail. Those safety precautions are classified into ranks “DANGER” and “CAUTION”.
DANGER
Wrong handling may cause a dangerous situation, in which there is a
risk of death or heavy injury.
CAUTION
Wrong handling may invite a dangerous situation, in which there is a
possibility of medium-level trouble or slight injury or only physical
damage is predictable.
On items listed under “
CAUTION ”, they may also lead to serious accidents depending on circumstances, and must be fully observed.
• The signs of prohibition and indication are explained in the following.
PROHIBITION
INDICATION
General items which pertain to prohibition (DO NOT)
General items which pertain to user’s action
Installation and Piping
DANGER
• Non-explosion-proof transmitter must not be used in a place with explosive gases to prevent
serious accidents such as explosion, fire, etc.
CAUTION
• The transmitter is heavy. Be careful when handling it.
• The transmitter should be installed in a place that meets the operating conditions shown in DS
sheet or this instruction manual.
• Install the transmitter according to the instruction manual. Improper installation may lead to the
cause of fall, trouble or incorrect operation.
• When installing, make sure that the transmitter interior is free from cable chips and other foreign
objects to prevent fire, trouble, or incorrect operation.
• When power is ON, do not change the position of the field indicator in an explosion-proof area.
• When power is ON, do not change the position of the transmission unit in an explosion-proof area.
• When power is ON, do not change the angle of the indicator.
• Main valve used for piping should be selected with the maximum pressure of the process taken
into account (piping parts such as main valve, etc. should be furnished by user). If the main valve
and other parts do not meet the rating, it may result in leakage of gas or liquid which could lead to
hazard.
• Pressure pipes to be used must meet the temperature/pressure rating.
ii
Wiring
DANGER
• On explosion-proof type transmitter, its wiring work must be performed according to the required
laws and regulations. Incorrect wiring may cause explosion, fire or other serious accidents.
CAUTION
• Before making wiring work, be sure to turn OFF the main power to prevent electric shocks.
• Use wiring materials of correct rating to prevent fire accidents.
• Connect a power source of correct rating to prevent fire accidents.
• The transmitter should be grounded as specified to prevent electric shocks or incorrect operation.
• After installing the transmitter, firmly close the covers of the transmission unit and terminal box.
If not, rain water enter the transmitter which may result in trouble or incorrect operation.
Adjustment of Smart Type
DANGER
• When using a flame-proof transmitter, do not connect HHC to the transmitter terminals and junction terminals.
Replacement of Maintenance Parts
DANGER
• When removing an explosion-proof transmitter, turn OFF the main power, then disconnect the
piping and wiring. Do not remove it when the power is ON to prevent serious accident such as
explosion, fire, etc.
iii
CAUTION ON USE
Be sure to observe the following Instructions
Storage for a long period
Store the transmitter in a dry room at normal temperature and humidity.
Keep protection caps in place at the conduit connection and process connection.
For installation, select an appropriate place
Site at location with minimal vibration, dust and corrosive gas
At a place allowing an adequate space for checkup
Site at location large enough to allow maintenance and checking.
Mounting angle
Mount to a pipe horizontally or vertically.
Attention to overload
Do not apply a pressure outside the specified range.
Other
Besides the above, be sure to observe the cautions given in this manual.
CONFIRMATION OF YOUR SPECIFICATION
The instrument nameplate as shown below is attached at the transmission unit of this transmitter. Before
use, make sure the contents of the nameplate agree exactly with your specifications.
Tag No.
Series
Type
Range
M.W.P.
Ser.No.
Power Supply
Output
4 ... 20mADC
Fuji Electric Co., Ltd.
Made in Japan
iv
Mfd.
CONTENTS
INTRODUCTION ................................................................................................................................. i
CAUTION ON SAFETY ...................................................................................................................... ii
CAUTION ON USE ............................................................................................................................. iv
CONFIRMATION OF YOUR SPECIFICATION .............................................................................. iv
1
OUTLINE ....................................................................................................................................... 1
2
OPERATING PARTS AND THEIR FUNCTIONS ...................................................................... 2
3
OPERATION AND SHUTDOWN ................................................................................................ 4
3.1 Preparation for operation ............................................................................................................. 4
3.2 Operation ...................................................................................................................................... 6
3.3 Shutdown ...................................................................................................................................... 7
4
ADJUSTMENT OF SMART LINE ............................................................................................... 9
4.1 Adjustment with HHC ................................................................................................................. 9
4.2 Zero adjustment by the external screw ..................................................................................... 29
4.3 Span adjustment by the external screw ..................................................................................... 30
4.4 Local adjustment unit with LCD display .................................................................................. 31
5
MAINTENANCE ......................................................................................................................... 34
5.1 Periodique inspection ................................................................................................................ 34
5.2 Troubleshooting ......................................................................................................................... 35
5.3 Replacement of parts ................................................................................................................. 36
5.4 Adjustment after replacement unit ............................................................................................ 41
6
INSTALLATION AND PIPING ................................................................................................. 42
6.1 Installation .................................................................................................................................. 42
6.2 Piping ......................................................................................................................................... 46
7
WIRING ........................................................................................................................................ 54
7.1 Wiring procedure ....................................................................................................................... 54
7.2 Power voltage and load resistance ............................................................................................ 53
7.3 Grounding .................................................................................................................................. 57
8
SPARE PARTS ............................................................................................................................. 58
A1 BUILT-IN ARRESTER ............................................................................................................... 61
A2 CALIBRATION ........................................................................................................................... 63
A3 PARAMETER SETTING PRIOR TO DELIVERY .................................................................... 65
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION ............................................ 66
v
1
OUTLINE
The FCX-CII series transmitter detects the differential pressure or pressure of various
fluids, converts it into a current signal of 4 to 20 mA DC and transmits it.
All the adjustment functions are incorporated in the transmission unit for making
adjustments easily and exactly.
Transmitter settings (such as range and damping time constant, etc.) can be changed from
an HHC (Hand Held Communicator).
Principle
The operating principle of the FCX-CII series transmitter is shown in the block
diagram below.
The input pressure is changed into an electrostatic capacitance in the detecting unit.
The change proportional to the pressure undergoes conditioning and amplification in
the transmission unit, and is then output as a current of 4 to 20mA DC.
Input
differential
pressure
Capacitance
change
Displacement
Diaphragm
Sensor
Detecting unit
Measuring
circuit
Operational
amplification
circuit
Transmission unit
1
Output
current
2
OPERATING PARTS AND THEIR FUNCTIONS
FCX-CII Series transmitter
Transmission unit
Process connection
Detecting unit
Analog indicator
connector
Transmission unit
Digital indicator
connector
Vent/drain
plug
Conduit
connection
Terminal unit
Indicator
(Digital)
(Analog)
CK+
OUT
DISP
FIX
%
ZERO
abs
0
CK–
Terminal unit
Zero/span
adjustment
screw
%
10
20
40 60 80
0
–
+
Description of FCX-CII Series transmitter
Part name
Description
Detecting unit
Detects pressure, differential pressure or level of fluid.
Transmission unit
Converts the detected signal into an output signal.
Vent/drain plug
Used for gas discharge or draining. (Attention should be paid
under a high pressure.)
Process connection
Connects impulse pipes from the process.
Conduit connection
Connects the output cable.
Zero adjustment screw
Adjusts zero. (For analog type, refer to Section 7.)
Transmission unit
Part name
Description
Analog indicator connector
Used for connecting an analog indicator.
Digital indicator connector
Used for connecting a digital indicator.
Indicator (option)
Analog or digital indicator, available.
Terminals
Symbol
Description
+, -
Connects the output cable.
CK+, CK-
Used for checking the output or connecting an indicator.
An external terminal used for grounding
2
Mode indicating function of digital indicator
OUT
DISP
%
FIX
ZERO
abs
Mode indication
Mode
%
When not indicated
When indicated
% output
Actual scale
External zero adjustment possible
External zero adjustment impossible
DISP
Digital indicator
Digital indicator proportional display
OUT
output
ZERO
FIX
display
Proportional output
Measurement mode
Fixed current mode
Sampling status (Flicker)
abs
–
N
Absolute pressure
Gage pressure
Output value < Zero
Output value
(a part of unit indicator)
3
Zero
3
OPERATION AND SHUTDOWN
3.1 Preparation for operation
Before operating the transmitter, be sure to perform the following checks and procedures. Note
that adjustment is required in a non-hazardous area for zero point check of intrinsically safe
explosionproof and flameproof transmitters, do not open terminal cover and do not use HHC.
Use the transmitter indicator and the external adjustment screw.
Preparation procedure
(1) Check for liquid or gas leakagefrom the process
connection, etc. by applying soapy water or the
like.
(2) Check the signal wiring according to the “Terminal block connection diagram” shown in 4.1
(Page 16).
(3) Vent gas from the transmitter.
Important
When the plant requires chemical cleaning at the start of operation, be sure to
close the valve of the transmitter to prevent entry of cleaning liquid into the
pressure receiving unit.
(4) Perform zero point adjustment.
4
Zero point check
Turn on the power to the transmitter.
Check the output signal of the transmitter by connecting a DC ammeter across CK+ and CK– of
the terminal block.
After ten minutes or longer, adjust the transmitter output current to 4 mA (zero adjustment). (See
below.)
(1) Zero adjustment
Zero point of the transmitter is adjustable by the zero screw on the electronics housing with
the zero adjustment screw.
• If the transmitter is locked (see section
“Operating procedure”, Lock of adjustment
function), it is not possible to adjust with the
external adjustment screw.
Decrease
Increase
• When a digital indicator is attached to the
transmitter, make sure that the LCD lamp
“ZERO” is ON.
(2) Adjustment by HHC
Refer “zero adjustment” explained in section 7.1.
When all the checks and preparatory operations are finished, tighten the cover securely. (Tightening torque 20 N•m {2 kgf•m} <14ft-lb>)
Important
1. After adjustment of the transmitter, it should be kept energized for about 10
seconds to write the adjustment result into memory.
2. Use a blade-edge screwdriver for adjusting the zero/span adjustment screw.
5
3.2 Operation
(1) Operation of pressure transmitter
Open the valve slowly to apply a pressure. When a pressure is applied, the transmitter is set
in the operating status.
Open
(2) Operation of differential pressure transmitter
Set the operating status by manipulating the manifold valve.
Stop valve
on the low
pressure side
Make sure the equalizing valve is open.
Open
Equalizing
valve
Stop valve
on the high
pressure side
Open the stop valve on the high pressure side slowly.
Open
Close
Close the equalizing valve.
6
Open
Finally, open the stop valve on the low pressure side
slowly.
Check of operating status
Use a field indicator, receiving instrument or HHC to check the operating status.
3.3 Shutdown
(1) Shutdown of pressure transmitter
Close the valve slowly to stop applying a pressure. The transmitter is set in the measurement
stop status.
Close
7
(2) Shutdown of differential pressure transmitter
Set the shutdown status by manipulating the manifold valve.
Turn off power supply.
Close the stop valve on the high pressure side (H side)
slowly.
Close
Open
Open the equalizing valve.
Close
Close the stop valve on the low pressure side (L side)
slowly.
Important
Before a long shutdown, discharge the process fluid and drain completely from
the transmitter.
This is to protect the transmitter from freezing, corrosion, etc.
8
4
ADJUSTMENT OF SMART TYPE
To operate the FCX-CII series transmitter, the HHC is used for each adjustment.
4.1 Adjustment with HHC
Startup and usage of the Hand Held Communicator (HHC) are detailed in the instruction manual
for HHC. Please refer to this manual before commencing adjustment.
Important
After adjustment of the transmitter, it should be kept energized for about 10 seconds to write the adjustment results into memory.
4.1.1 Connection of HHC
CK+
CK–
The HHC can be connected to the transmitter, junction terminal or the terminals in the instrument
room.
–
+
Field device
To junction
terminal or
instrument
room
To HHC
Instrument room
Junction terminal Zener barrier
Terminal block
DC power supply
DC16.1 ~ 45V
Load resistor
DANGER
In the case of a flameproof transmitter, never connect the HHC to the terminal block
of the transmitter in hazardous area installations.
9
4.1.2
Outline of HHC operation
The following shows the flow of the key, explained for FXW Version 6.0
(FXW
1- A3).
FXW prior to Version 6.0 are not available of operation of FCX-CII series transmitter.
In this case, the user is requested to contract our office for ROM version up.
Classification
Display symbol
Key symbol
Referential
page
MENU
11
1 TAG No.
INC 1: TAG No
2 Type
INC 2: TYPE
3 Display of serial No.
INC 3: SERIAL No.
4 Industrial value unit
INC 4: UNIT
5 Range limit
INC 5: RANGE LIMIT
6 Range change
(LRV, URV)
INC 6: RANGE
RANG
14
7 Damping adjustment
INC 7: DAMPING
DAMP
15
8 Output mode
INC 8: OUTPUT MODE
LIN
/
16
9 Burnout direction
INC 9: BURNOUT
A Zero/span adjustment
INC A: CALIBRATE
CALB
18
INC B: OUTPUT ADJ
OUT
19
INC C: DATA
DATA
20
Calibration of
output circuit
Indication of
C
measured data
B
D Self-diagnosis
INC D: SELF CHECK
E Printer function
INC E: PRINT
F Lock of adjustment
functions
Indication of digital
G
indicator
Programmable lineariH
zation function
I Rerange (Set LRV/URV
calibration)
INC F: XMTR EXT.SW
MENU
MENU
INC
12
INC
13
UNIT
UNIT
DATA
INC H: LINEARIZE
DATA
DATA
10
INC
INC
INC
INC
INC
INC
20
INC
INC
DATA
17
INC
DATA
DATA
14
INC
LIN
/
INC G: XMTR DISPLAY
INC I: RERANGE
12
INC
INC
INC
INC
INC
21
INC
22
INC
INC
INC
INC
23
INC
26
INC
INC
INC
28
4.1.3 Operating procedure
In case of a flameproof transmitter, never connect the HHC to the terminal block of
transmitter in hazardous area installations.
TAG N°.
0:
PUSH MENU KEY
MENU
1:
TAG No
FICRA-1234 xxxxxxxxx
xxxxxxxxxxxxxxxxxxx
< INC > < CHANGE >
INC
To menu
2 : TYPE
CHNG
1
1-1: TAG CHANGE
FICRA-1234 xxxxxxxxx
xxxxxxxxxxxxxxxxxxx
< ENT > < CL >
ENT
1-1: TAG CHANGE
FICRA-4321 xxxxxxxxx
xxxxxxxxxxxxxxxxxxx
CHNG OK?< ENT/CL >
after setting
ENT
CL
•
2
CL
•
3
•
1-2: TAG WRITE
FICRA-4321 xxxxxxxxx
xxxxxxxxxxxxxxxxxxx
4
•
•
•
11
To set the TAG N°. of each field device, use the procedures shown in
the following diagram. TAG N°.
can be inputted up to 26 characters
of alphanumeric codes.
After PUSH MENU KEY is
displayed, press the
Source Exif Data:
File Type : PDF
File Type Extension : pdf
MIME Type : application/pdf
PDF Version : 1.4
Linearized : Yes
Create Date : 2002:04:23 09:19:50Z
Modify Date : 2002:11:29 08:23:08+01:00