Futaba FDL01TU Wireless Modem with Serial Interface User Manual

Futaba Corporation Wireless Modem with Serial Interface Users Manual

Users Manual

  i WIRELESS DATA COMMUNICATION MODEM  FDL01TU   Wireless Modem with Serial Interface Instruction Manual                      Futaba Corporation Industrial Radio Control
  iiI  Notice This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.  This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.  Any unauthorized changes or modifications to this device not expressly approved by Futaba Corporation could void the user’s authority to operate the device and possibly result in damage to the equipment and/or cause serious or fatal injuries to the operator or nearby personnel.  This device is intended to be installed and used in accordance with the instructions contained in this manual. Failure to comply with these instructions could void the user’s authority to operate the device and possibly result in damage to the equipment and/or cause serious or fatal injuries to the operator or nearby personnel.
  iiiII  Important Safety Information The list of dangers, warnings and cautions in this section contain important information that will help ensure safe operation of the system. Please read carefully and understand all of these items. All installers, operators and maintenance personnel should read and understand this information before installation, use, or maintenance of the FDL01TU system.  The FDL01TU system by itself is not inherently dangerous. HOWEVER, WHEN THE FDL01TU IS CONNECTED TO OTHER EQUIPMENT FOR THE PURPOSE OF CONTROL, SAFETY AND ALL POSSIBLE ASSOCIATED DANGERS MUST ALWAYS BE GIVEN THE UTMOST CONSIDERATION DURING SYSTEM INTEGRATION, DESIGN, INSTALLATION, AND USE.  The FDL01TU system may be used in virtually unlimited applications. Many of these associated systems can, by themselves, pose a mechanical, electrical or other hazard to operators and other persons or equipment. To address all possible applications and associated safety hazards in this manual would be impossible. The warnings below and throughout this manual give information that will allow safe installation and use the modem system applications. If you have questions regarding the safety of your specific application, please contact the appropriate people for help. Your Futaba sales representative, representatives of the equipment being controlled, and the technical support staff at local branch of Futaba Corporation are among those who can provide assistance with your safety concerns.  The following warnings are included in the lists that follow but warrant repetition here:  In installations where the FDL01TU system is used to control motion or operation of potentially dangerous equipment, it is imperative for safety that all operators and installers be thoroughly trained in the normal function of that equipment before attempting to control it remotely with the FDL01TU system.  To help ensure safe operation of the equipment, the FDL01TU system must be connected so that it will operate in a fail-safe way. In other words, the equipment being controlled should stop or return to its safest state in the absence of a control signal or total loss of RF transmission from the FDL01TU system. Our system uses one of the most reliable methods available to transmit data using radio signals. Many factors can affect a radio signal that may block it or interfere enough to disrupt regular transmission. Because of this, equipment motion or dangerous electrical current, for example, that continues during a loss-of-signal condition could be very dangerous.
  iv Four symbols are used in the margin of the following section and throughout the manual to indicate the level of hazard or information listed.  The symbols are defined as follows: Indicates a hazard that will cause severe personal injury, death, or substantial property damage if the warning is ignored. Indicates a hazard that can cause severe personal injury, death, or substantial property damage if the warning is ignored. Indicates a hazard that will or can cause minor personal injury, or property damage if the warning is ignored. Indicates installation, operation, or maintenance information that is important but not hazard-related.  Please read the following safety information carefully. Some of these notices are duplicated throughout the manual, in areas of associated content, for your benefit.  II.I  General Safety Hazards and Notes Improper installation and/or operation of the FDL01TU system can cause serious or fatal injuries to the operator or nearby persons and cause damage to the FDL01TU system, and any equipment it is used to control. Please read and understand this manual completely and the manual of all equipment being controlled before attempting to operate or install this system. Always keep this manual at a location readily accessible to anyone operating the system and related equipment. Ensure that all operators have read and understood this manual, especially all safety and operation procedures contained in it. Please refer to the section in this manual titled How to Obtain Help for the contact that can supply additional manuals or answers to questions not covered in this manual. If this product is passed on to a different user, be sure that this manual accompanies the product. Be certain that the installer of this equipment reads and understands the instruction manual of the equipment that is being connecting to before attempting this installation. The FDL01TU modem should NOT be used in a manner in which failure of the product or loss of the radio signal could cause damage
  v to the equipment being controlled, or to anything in the area in which such equipment is located. All integrated control systems should be designed for “fail-safe” operation so that a temporary or permanent loss of signal will not endanger any person, critical process, or equipment (refer to the beginning of the safety section for further explanation). The system design should ensure that the equipment being controlled will default to its safest state in the event of signal loss. The FDL01TU modem contains no user serviceable parts. If the unit requires service, contact your sales representative or local branch of Futaba Corporation per instructions the section titled How To Obtain Help. Do not disassemble or attempt to repair the FDL01TU yourself. Doing so could void your warranty and may void the user’s authority to operate the device. Contact Futaba before using the FDL01TU modem in safety critical applications such as medical equipment, aircraft, hazardous materials handling, etc. II.II  Installation Safety Hazards and Notes When mounting the FDL01TU modem, use M2 (ISO) screws that project 2 to 3 mm into the modem. Screws that project further into the modem (3.5mm MAX) may permanently damage the internal components and/or cause the FDL01TU modem to malfunction. Use only the proper regulated DC voltage supplied to the FDL01TU modem. Use of any other voltage may permanently damage the modem and/or cause the modem to malfunction and create a shock or fire hazard. Be certain that all AC power outlets used the power adapters have been properly installed, grounded, and fused. An electrical shock hazard may exist if this unit is powered by a faulty power outlet or source. If such a situation is discovered, immediately discontinue use until the power source and outlet have been properly installed, grounded, and fused by an electrician or other authorized person. Be sure to wire the power and serial connections correctly. Incorrect wiring can damage the system, cause it to malfunction and/or create a shock and fire hazard. Ensure that the FDL01TU modem power and the power to the equipment to be controlled is turned off before connecting or disconnecting the cable between them. This will help prevent
  vi accidental damage to the system and unexpected operation and/or injury. Be sure the FDL01TU modem power, the power to the equipment that is being connecting to it, and the DC power source are all turned off before wiring and connecting the power cable. Be sure that the supplied power is within the specified range (3.5 to 7.0 VDC). Voltages outside the specified range may damage the FDL01TU modem. Be sure that the power source has sufficient current capacity. Insufficient current may cause the unit to malfunction. Securely attach the antenna cable, and serial communication connector to the FDL01TU modem and equipment/power source to which it is connected. Failure to do so could cause an unexpected system failure. II.III  Antenna Installation Hazards and Notes Be sure to keep all systems and antennas clear of power lines. Permanent equipment damage and severe shock injury or death can occur if the system contacts power lines. This device has been designed to operate with an antenna having a maximum gain of 2.14 dB.  Antenna having a higher gain is strictly prohibited for use with this device.  The required antenna impedance is 50 ohms. Contact Futaba before connecting any antenna not provided by Futaba specifically for the FDL01TU modem. Attaching any non-authorized antenna may be in violation of FCC regulations. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that permitted for successful communication. When using two antennas with a single FDL01TU modem for diversity reception, mount the antennas as far apart as possible (6 cm minimum). If the antennas are too close, the diversity advantage will not be achieved.
  vii Before each use, verify that the antenna (and antenna cable, if used) is securely attached and in good condition. A loose antenna or cable may severely reduce the operating range of the system. When installing the FDL01TU modem in a mobile unit such as an Automated Guided Vehicle (AGV), Futaba recommends to use the diversity reception feature as a remedy for multipath fading problems. For diversity reception, install the two antennas as far apart as possible in order to gain maximum benefit (6 cm minimum). The FDL01TU operates at frequencies in the 2.4 GHz band. These frequencies are more directional than lower frequencies and are easily reflected. If there are metal structures nearby, the effective range may be shortened or the directional properties may be further narrowed. To help avoid this, mount the antenna as far away as possible from surrounding metallic structures. Multipath problems occur easily at frequencies in the 2.4 GHz band. When multipath problems are present, moving the antenna as little as 10 cm may result in improved communication or, conversely, worsened or complete loss of communication. Futaba recommends that the mounting position of the antenna be determined after testing and verifying optimal communication conditions. Negative multipath effects can also be overcome with antenna diversity. See p.8 DIVERSITY ANTENNA SETUP  and the related register settings for more details regarding antenna diversity function. When installing multiple FDL01TU modem systems that will use different frequency groups in the same area, modem’s antennas of different frequency groups must be mounted at least 6 feet (2 meters) apart. Failure to do so may severely reduce the modem operating range. Please contact Futaba for information about antenna separation when using the FDL01TU and other wireless products in the same area.
  viii II.IV  Environmental Safety Hazards and Notes If the FDL01TU modem has been stored at a temperature beyond the specified operating temperature range for the system, it may not function properly. Allow it to return to normal temperatures before use. Refer to APPENDIX A – TECHNICAL SPECIFICATIONS for the actual operating temperature range. The FDL01TU modem is a precision electronic device with a rugged design that is intended for industrial applications. However, do not install it where it will encounter excessive vibrations. In some cases, isolation mounts may be used to isolate the modem from the equipment’s vibration. Excessive vibration can permanently damage the modem and/or cause it to malfunction. Do not operate the FDL01TU modem in environments where it will be subjected to excessive moisture (such as rain or water spray), dust, oil, or other foreign matter (such as metal particles). Doing so may permanently damage the modem and/or cause it to malfunction. If it does become wet or contaminated, correct the situation, verify proper operation and have any problems corrected before using it to control other equipment. If necessary, the modem can be mounted inside a protective or waterproof enclosure. If the enclosure is metallic, the antenna must be mounted externally or the effective operating range will be severely limited. The FDL01TU is designed for indoor use. When using it outdoors, the modem should be mounted in a waterproof enclosure and the ambient temperature range should be checked to insure that it is within the modem’s specifications. Always use the modem within its specified environmental ranges. II.V  Other Notice Italicized gothic word used in this manual shows functional and technical term especially important for the FDL01TU modem.
  ix Operational Safety Hazards and Notes Before each use of the FDL01TU modem, ensure that the area where the equipment will be operated is clear of people or obstacles that may affect its safe operation. Before each use of the FDL01TU modem, verify that both the equipment being controlled and the modem are in proper operating condition. When rewriting the FDL01TU modem’s memory registers, do not turn the modem’s power off until the modem returns a “P0” response. If the power is interrupted before a P0 response is returned, the memory contents may be lost or corrupted and the modem operation will be unpredictable. If the memory contents are lost or corrupted, they may be restored to original default settings by reinitializing them. (See p.25 Memory REGISTER INITIALIZATION for more details.) Do not attempt to operate remotely controlled equipment outside the communication range of the FDL01TU system. Doing so could cause loss of control of the equipment. Without implementing proper serial communication flow control settings, the baud rate between the modem and its terminal equipment (wire linked) can exceed the wireless link data rate and cause the modem buffer to overflow. This can result in malfunction of the systems being controlled and/or data corruption. Ensure that the appropriate flow control settings are being used for your upper layer application protocol. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
  x III  System Identification For future reference, please take a moment to fill in the information below. This information will help us respond as quickly as possible should your FDL01TU modem ever need repair or replacement.       Model Name and Number:    FDL01TU     Serial Number:       Date of Purchase:       Distributor Name:       Distributor Address:       Distributor Phone Number:
  xi IV  Limited Warranty FUTABA WARRANTS ONLY THAT THE INDUSTRIAL RADIO CONTROL SYSTEM GOODS  OR  PRODUCTS  FURNISHED  HEREWITH  SHALL  BE  FREE  FROM DEFECTS  IN  MATERIAL  AND  WORKMANSHIP  UNDER  NORMAL  CONDITIONS OF USE  AND  SERVICE  FOR  A  PERIOD OF  ONE  (1)  YEAR  FROM THE  DATE  OF SALE TO THE PURCHASER WHO IS THE FIRST BUYER OF THE GOODS FOR USE OR  CONSUMPTION  AND  NOT  FOR  RESALE  OTHER  THAN  AS  A  COMPONENT OF  ANOTHER  PRODUCT  MANUFACTURED  FOR  SALE  BY  SUCH  PURCHASER (“CONSUMER”).  FUTABA’S  LIABILITY,  WHETHER  BASED  ON  BREACH  OF WARRANTY  OR  NEGLIGENCE, SHALL BE LIMITED, AT FUTABA’S ELECTION, TO  REPLACEMENT  OR  REPAIR  OF  ANY  SUCH  NONCONFORMING  GOODS, F.O.B. FUTABA’S U.S.A. PLANT, OR, AT FUTABA’S ELECTION, CREDIT FOR THE NET PURCHASE PRICE OF SUCH GOODS. ALL CLAIMS HEREUNDER MUST BE MADE  IN  WRITING  DURING  THE  WARRANTY  PERIOD,  AND  FUTABA  SHALL HAVE  THE  RIGHT  PRIOR  TO  ANY  RETURN  OF  GOODS  TO  INSPECT  ANY GOODS  CLAIMED  TO  BE  NONCONFORMING,  AND  IN  ANY  EVENT  RESERVES THE RIGHT TO REJECT CLAIMS NOT COVERED BY WARRANTY. THIS LIMITED WARRANTY  CONSTITUTES  FUTABA’S  SOLE  WARRANTY.  FUTABA  MAKES NO  OTHER  WARRANTY  OF  ANY  KIND,  EXPRESS  OR  IMPLIED,  AND EXPRESSLY  DISCLAIMS  ANY  IMPLIED  WARRANTY  OF MERCHANTABILITY  OR  FITNESS  FOR  A  PARTICULAR  PURPOSE. FUTABA’S  WARRANTY  SHALL  NOT  APPLY  IF,  AMONG  OTHER  LIMITATIONS CONTAINED  HEREIN  OR  FURNISHED  WITH  THE  PRODUCT,  BUYER,  OR CONSUMER,  OR  ANY  USER  OF  THE  PRODUCT    (A)  ALTERS  SUCH  PRODUCT, OR (B) REPLACES ANY PART OF SUCH PRODUCT WITH ANY PART OR PARTS NOT  FURNISHED  BY  FUTABA  FOR  THAT  PURPOSE,  OR  IF,  AMONG  SUCH OTHER  LIMITATIONS,  PRODUCT  FAILS  TO  OPERATE  PROPERLY  OR  IS DAMAGED  DUE  TO  ATTACHMENTS  OR  COMPONENTS  THAT  ARE  NOT FURNISHED BY FUTABA FOR USE WITH OR REPAIR OF THE PRODUCT UNLESS SUCH USE IS AUTHORIZED IN WRITING IN ADVANCE BY FUTABA.  THIS LIMITED WARRANTY EXTENDS ONLY  TO THE CONSUMER AND  IS NOT ASSIGNABLE  OR  TRANSFERABLE.  This  limited  warranty  shall  not  apply  to  fuses, lamps, batteries, or  other items  that  are  expendable  by nature, unless  otherwise  expressly provided.  This limited warranty does not cover any defect or damage to any of the goods caused by or attributable  to  force,  accident,  misuse,  abuse,  faulty  installation,  improper  maintenance, improper electrical current, failure to install or operate in accordance with Futaba’s written instructions,  repair  or  alteration  by  unauthorized  persons,  or  leaking  batteries.  THE GOODS  ARE  SENSITIVE  ELECTRONIC  DEVICES  REQUIRING  SPECIAL HANDLING,  AND  THIS  LIMITED  WARRANTY  DOES  NOT  APPLY  TO PRODUCTS  NOT  HANDLED  IN  ACCORDANCE  WITH  INSTRUCTIONS  SET FORTH IN THE MANUAL.  THIS  LIMITED  WARRANTY  DOES  NOT  COVER  INDUSTRIAL  RADIO CONTROL  PRODUCTS  PURCHASED  OR  USED  OUTSIDE  OF  THE  UNITED STATES WITHOUT FUTABA’S PRIOR APPROVAL.
  xii V  Returns Futaba’s authorization must  be obtained prior to  return  of any item for  warranty or other repair  or  replacement  or  credit  and  will  reflect  Futaba’s  warranty  service  procedure. Consumer’s  warranty  rights  are  governed  by  the  terms  of  Futaba’s  Limited  Warranty,  as above  described.  Products  returned  for  warranty  repair  or  replacement  or  credit  must  be carefully and securely packed for return, preferably in the original carton or equivalent. The Consumer must also include in the carton a legible copy of the bill of sale or invoice which shows  the  date  of  sale and  the  original  Buyer’s  and  Consumer’s  names,  and  also  a  letter which gives the Consumer’s return  address and contact telephone number, the model  and serial numbers of the product(s) returned, and a brief explanation of the problem or claimed defect.  Any  returned  products  that  are  replaced  by  Futaba  shall  become  the  property  of Futaba.  If  after  inspection  Futaba  determines  the  defect  is  not  covered  by  its  limited warranty,  Futaba  will  notify  Consumer  of  its  determination  and  will  not  undertake  any repairs  or  product  replacement  until  Consumer  agrees  to  pay  for  all  necessary  parts  and materials,  labor  (to  be  charged  at  Futaba’s  standard  repair  rate  then  in  effect),  and  other expenses including all  shipping  charges and insurance.  Futaba reserves  the  right to retain possession  of  any  product  returned  by  Consumer  because  of  defects  not  covered  by Futaba’s  warranty  until  Futaba  receives  Consumer’s  agreement  as  above  noted  or,  if Consumer wants the product returned without repair or replacement, Consumer reimburses Futaba  for  all  shipping  and  handling  charges  incurred  by  Futaba.  Issuance  of  credit  for returned  items  shall  be  made  at  Futaba’s  unfettered  discretion.  Consumer  will  not  be entitled  to  return  defective  goods  for  cash  refunds.  Consumer  must  inspect  goods immediately and no rejection or revocation of acceptance shall be permitted more than ten (10) days after delivery to, or first use by, Consumer of the goods, whichever occurs first.  VI  Patents – Copyrights – Trademarks – Proprietary Rights If this product was manufactured according to designs or processes specified by Consumer, Consumer shall indemnify and save Futaba, its affiliates, officers, agents, and employees, harmless from any expense, loss, attorneys’ fees, costs, damages, or liability which may be incurred  as  a  result  of  actual  or  alleged  infringement  of  patent,  copyright,  or  trademark rights. Furnishing of these products does not convey a license, implied or otherwise, under any patent, copyright, or trademark right in which Futaba has an interest, nor does it convey rights to trade secrets or any other proprietary information of Futaba. VII  Limitation of Damages and Action    IN NO EVENT SHALL FUTABA BE LIABLE TO CONSUMER, OR ANY OTHER PERSON FOR ANY INCIDENTAL, CONSEQUENTIAL, OR SPECIAL DAMAGES RESULTING  FROM  THE  USE  OF  OR  INABILITY  TO  USE  THIS  PRODUCT, WHETHER  ARISING  FROM BREACH  OF  WARRANTY  OR NEGLIGENCE  OF FUTABA, OR OTHERWISE. Any action hereunder must be commenced within one (1) year  of  accrual  of  cause  of  action  or  be  barred  and  forever  waived.  No  modification  or alteration  of  Futaba’s  Limited  Warranty  or  any  other  provision  of  this  paragraph  or  the above  paragraphs  shall  result  from  Futaba’s  acknowledgment  of  any  purchase  order, shipment  of  goods,  or  other  affirmative  action  by  Futaba  toward  performance  following receipt of any purchase order, shipping order, or other form containing provisions, terms, or conditions in addition to or in conflict or inconsistent with any such provisions.
  xiii  TABLE OF CONTENTS 1111 INTRODUCTION............................................................................................... 1 1.1 Special Features.............................................................................................................2 1.2 How To Obtain Help........................................................................................................3 1.3 Physical Description .......................................................................................................4 2222 SYSTEM INSTALLATION ................................................................................ 5 2.1 Wireless Modem Installation...........................................................................................6 2.2 Communication Cable Connection.................................................................................7 2.3 Antenna Connection .......................................................................................................7 2.4 Other Installation Precautions ........................................................................................9 3333 SYSTEM OPERATION ................................................................................... 11 3.1 Data Transparent Mode................................................................................................12 3.2 Packet Transmission Mode ..........................................................................................13 3.3 Headerless stream Mode .............................................................................................16 3.4 Power Down Mode .......................................................................................................17 3.5 Frequency Grouping.....................................................................................................18 4444 FUNCTION CONTROL METHODS ................................................................ 21 4.1 Interface........................................................................................................................22 4.2 Serial Interface Setting .................................................................................................23 4.3 Terminal Software Setup for Memory Register Control................................................24 4.4 Memory Register Setting..............................................................................................24 4.5 Command Control ........................................................................................................26 5555 MEMORY REGISTER DESCRIPTION ........................................................... 27 5.1 Memory Register Description .......................................................................................28 6666 COMMAND SET DESCRIPTION.................................................................... 43 6.1 Command Set Description............................................................................................44 7777 APPENDIX...................................................................................................... 63 7.1 Conversion Circuit ........................................................................................................64 7.2 Specification of the Connectors....................................................................................65 7.3 Specification..................................................................................................................66 7.4 Dimensions ...................................................................................................................68
  11SECTION 1   INTRODUCTION
  21.1  Special Features The following list highlights some of the special features of the FDL01TU. For more complete system specifications please refer to p.66 SPECIFICATIONS.  • Approved under FCC Part 15.247 rules   -- no special user license required • Operating range greater than 1000 feet, line-of-sight -- configurable as a repeater for extended range of application service area • 2.4 GHz Direct Sequence Spread Spectrum (DSSS) communication system provides unsurpassed immunity to interference and RF noise • Diversity transmitting / receiving function is employed, which is practically invulnerable to multipath fading • Fast switching Time-Division-Duplex (TDD) provides virtual full-duplex communication between terminal equipments at rates up to 230.4 kbps • 76 user selectable frequencies allow up to 26 independent networks to operate simultaneously in the same area • Single fixed frequency communication or multi-access communication (automatic selection of an vacant frequency from a defined group of frequencies) allows the user to select the best frequency use for the application • Supports 1:1, 1:n, and n:m wireless network topology • Serial communication interface allows direct connection to a micro controller chip. By converting its level by the external interface circuit, conformable to RS232C, RS422 and RS485 • Small size allows easy integration with many systems (1.97" x 1.18" x 0.31" / 50 x 30 x 8 mm)                       • Supply voltage range is DC voltage in 3.5 to 7.0 V DC
  31.2  How To Obtain Help Please contact your local sales representative or local branch of Futaba Corporation at the address shown below for help with the following:  • Application information regarding the FDL01TU or other Futaba products • Technical assistance or training • Answers to safety questions and issues • Additional manuals or other documentation • Repair or service • Comments regarding the product or this manual Japan Futaba Corporation Radio Control Equipment Group 1080 Yabutsuka, Chosei, Chiba, 299-4395 JAPAN Tel: +81 (475) 32-6173, Fax: +81(475) 32-6179 Internet: www.futaba.co.jp   Europe PENDING    When requesting repairs, please provide as much detail as possible regarding the failure and its cause or symptoms. Doing so will help our service department find the problem quickly, resulting in a shorter repair time. The FDL01TU modem contains no user serviceable parts. If the unit requires service, contact your sales representative or local branch of Futaba Corporation as per instructed in this section. Do not disassemble or attempt to repair the modem yourself. Doing so could void your warranty and may void the user’s authority to operate the device. CAUTION
  41.3  Physical Description Please review the following section and take a moment to familiarize yourself with the FDL01TU wireless modem.         Figure 1–1:  Upper View              Figure 1–2:  Bottom View  (1)  Communication Connector Used to connect to the DTE(Data Terminal Equipment) with interface cable. Also controlling functions such as hardware reset and RS232C/RS485 selecting pins are available. Signal is CMOS level.   (2)  Antenna Connector A/B Used to connect to antennas for transmit and receive functions.  (3)  LEDs Four bi-color LEDs indicate the states of the FDL01TU modem.  (4)  Mounting Hole Used to install a modem from the front surface. It is easy to install a modem, however, only two holes are available, it should be fixed by guide structure on the other side of the unit to prevent vibration problem.  (5)  Bottom Mounting Hole The four holes are used to install the modem. Please use this holes instead of above explained holes if tightened mounting is required.
  52SECTION 2   SYSTEM INSTALLATION
  62.1  Wireless Modem Installation 2.1.1  Mounting Method 1 A method to mount the modem directly on a surface using the mounting holes at the side of the modem’s print circuit board. When using this method, provide a guide on the opposite side, because two holes are not sufficient to securely mount the modem.            Figure 2–1:  Mounting Method 1 2.1.2  Mounting Method 2 To mount the modem using the holes on a flat horizontal surface, which are 3.5mm deep for M2 screws. When using this method, use M2 screws which project the hole 2 to 3mm deep. The screw tightening torque is below 2.5kg cm.  Mount the modem on a flat plane and be careful that there is no torsion applied. For the position of the mounting holes, see  p.68 DIMENSIONS.  Figure 2–2:  Mounting Method 2  Be careful not to allow water, oil, dust and other foreign particles (especially metal particles) to enter inside, which may damage the unit. Since the FDL01TU modem is a precision electronic device, install it at a place free of excessive shock and vibration to prevent the unit from damage. WARNINGM2 Screw  WARNING
  7The FDL01TU is designed to be used inside the room. In case of using it outdoor, be sure to use it within the extent limited by the environmental specification, and check the ambient temperature and the state of water-proof. 2.2  Communication Cable Connection Use the serial communication cable prepared by Futaba to connect the FDL01TU modem to the external terminal equipment. For the connection of the modem, see p.22 PIN ASSIGNMENT. The signal level of the FDL01TU is CMOS. If the interface of the equipment to be connected is RS232C or RS485, the level conversion circuit is required. For the example of the level conversion circuit, see p.64 CONVERSION CIRCUIT.                 Figure 2–3:  Connection of Communication Cable Ensure that the FDL01TU modem power and the power to the equipment to be controlled is turned off before connecting or disconnecting the cable between them. This will help prevent accidental damage to the system and unexpected operation and/or injury. In addition to this manual, read the operation manual of a PC (Personal Computer) and PLC (Programmable Logic Controller) to be connected.  2.3  Antenna Connection At least one antenna must be connected to Antenna Connector A on each FDL01TU modem in use. In the environment where multipath fading exists with reliable communication requirements, a second antenna can be installed to Antenna Connector B for the diversity receive  function to improve reception performance. 2.3.1  Single Antenna Setup Always use Antenna Connector A when installing a single antenna.  Refer to the figures below for details about the actual mounting and connecting methods. CAUTIONWARNINGWARNING
  8             Figure 2–5:  Connecting the Antenna 2.3.2  Diversity Antenna Setup In certain situations, reception can be improved by using the integrated antenna diversity feature. This is accomplished by using two separate antennas and enabling the diversity function in REG19 (see p.27 MEMORY REGISTER DESCRIPTION).  Refer to the figures below for details about the actual mounting and connecting methods.               Figure 2–6:  Connecting Two Antennas  When using two antennas with a single modem for diversity reception, mount the antennas as far apart as possible (at least 6 cm). If the antennas are too close, the diversity advantage will not be achieved.     CAUTION
  92.4  Other Installation Precautions 2.4.1  Modem Installation Precautions Securely attach the antenna cable, and serial communication connector to the FDL01TU modem and equipment/power source to which it is connected. Failure to not do so could cause an unexpected system failure. The FDL01TU modem is a precision electronic device. Its rugged design is intended for industrial applications. However, do not install it where it will encounter excessive vibrations. In some cases, isolation mounts may be used to isolate the modem from the equipment vibration. Excessive vibration could permanently damage the modem and/or cause it to malfunction. If the FDL01TU modem has been stored at a temperature beyond the specified operating temperature range for the system, it may not function properly. Allow it to return to normal temperatures before use. Refer to p.66 SPECIFICATION for the actual operating temperature range. Do not operate the FDL01TU modem in environments where it will be subjected to excessive moisture (such as rain or water spray), dust, oil or other foreign matter (such as metal particles). Doing so may permanently damage the modem and/or cause it to malfunction. If it does become wet or contaminated, correct the situation, verify proper operation and have any problems corrected before using it to control other equipment. If necessary, the modem can be mounted inside a protective or waterproof enclosure. If the enclosure is metallic, the antenna must be mounted externally or the effective operating range will be severely limited. The FDL01TU is designed for indoor use. When using it outdoors, the modem should be mounted in a waterproof enclosure and the ambient temperature range should be checked to insure that it is within the modem’s specifications. Always use the modem within its specified environmental ranges. 2.4.2  Antenna Installation Precautions Before each use, verify that the antenna (and antenna cable, if used) is securely attached and in good condition. A loose antenna or cable may severely reduce the operating range of the system. WARNINGWARNINGWARNINGWARNINGWARNINGWARNING
  10Avoid mounting the antenna near large metallic objects or inside metal enclosures. Such objects can severely reduce the operating range of the system. When installing the FDL01TU modem in a mobile unit such as an Automated Guided Vehicle (AGV), Futaba recommends using the diversity receive function as a remedy for to multipath fading problems. For diversity reception, install the two antennas as far apart as possible in order to gain maximum benefit (Actual recommendation is 30 cm, 6 cm at least). The FDL01TU operates at frequencies in the 2.4 GHz band. These frequencies are much directional than lower frequencies and are easily reflected. If there are metal structures nearby, the effective range may be shortened or the directional properties may be further narrowed. To help avoid this, mount the antenna as far away as possible from surrounding metallic structures. Multipath problems occur easily at 2.4 GHz frequencies. When multipath problems are present, moving the antenna as little as 10 cm may result in improved communication or, conversely, a further diminished or total loss of communication. Futaba recommends that the mounting position of the antenna be determined after testing and verifying optimal communication conditions. Negative multipath effects can also be overcome with antenna diversity. See p.8 DIVERSITY ANTENNA SETUP  and the related register settings for more details regarding antenna diversity. 2.4.3  Multiple FDL Modems Installation Precautions When installing multiple FDL (series) modem systems that will use different frequency groups in the same area, modem’s antennas of different frequency groups must be mounted at least 6 feet (2 meters) apart. Failure to do so may severely reduce the modem operating range. Please contact Futaba for information about antenna separation when using the FDL01TU and other wireless products in the same area.      WARNINGCAUTIONCAUTIONCAUTION
 113SECTION 3   SYSTEM OPERATION
  123.1  Data Transparent Mode 3.1.1  What Is Data Transparent Mode? In data transparent mode, the FDL01TU modems are continuously connected in a 1:1 configuration. Full-duplex communication is simulated between the two terminals using a method in which each modem rapidly switches between transmitting and receiving (referred to as Time-Division-Duplex (TDD) transmission).  With the exception of FDL01TU modem commands, all data input from the sending terminal are transmitted to the receiving terminal. Using this mode, the user can simply replace a serial cable with a pair of FDL01TU modems and communicate without any special software or hardware requirements. 3.1.2  Time-Division-Duplex Transmission and ARQ Function As noted above, when in data transparent mode, data packets are exchanged between terminals the modems rapidly switching between transmitting and receiving, simulating full-duplex communication.  Data input to the sending FDL01TU modem are assembled together with error detection bits and other control data, and then transmitted to the receiving modem. If an error is detected by the receiving modem, it will continue to request retransmission of the packet from the transmitting modem until it receives a valid packet. This is referred to as the Automatic Retransmission Request (ARQ) function. The ARQ function greatly enhances the reliability of the wireless connection because it ensures that the receiving FDL01TU modem will not pass corrupted data on to its terminal.  Figure 3–1:  Send/Receive Timing Diagram 3.1.3  Connection Method Link is connected and disconnected with the CON and DCN commands. Receiving modems can be shifted among many others by designating station addresses.        Wireless Modem A send receive send receive sendWireless Modem B receive send receive send receivepacket length A packet length Btime (t)
 133.2   Packet Transmission Mode Packet transmission mode operates as half-duplex communication and requires explicit commands to control the modem transmissions. Because this mode allows the addressing of different destination receiver modems by embedding the address in the data packets, it is best suited for 1:n and n:m topology applications.  In packet transmission mode, the FDL01TU modem normally waits in a ready-to-receive state. When a transmission command is issued to the sender modem from its terminal equipment, the modem searches for a clear frequency channel and, when found, transmits the message to the intended destination receiver modem.  Packet transmission mode also allows expansion of the effective wireless communication range by using an additional FDL01TU modem configured as a repeater. 3.2.1  Packet Transmission Mode Protocol In packet transmission mode, after a data packet is transmitted from the sender modem (station) to a destination station, the destination station acknowledges successful communication by returning an acknowledgement (ACK) packet to the sender modem. The sender modem waits for the ACK packet and when it is received, indicates that the transmission was successful. If it does not receive an ACK packet, it will continue to retransmit the data packet until it does receive an ACK packet or until the retransmission count (REG11 or RNO command setting) reaches the preset limit. If the sender modem receives an ACK packet anytime during the retransmission attempts, it returns a “successive completion response” (P0) code to its terminal equipment. If the modem does not receive an ACK packet, it returns a “transmission failed” (N1) code to its terminal equipment.         Sender Modem                                                                  Destination Modem Figure 3–2:  Packet Transmission and ACK response 3.2.2  Broadcast Transmission Protocol Broadcast transmission (sending the same data to multiple modems simultaneously) is possible in packet transmission mode by setting 255 as the destination address (REG02). However, because ACK packet are not returned when executing the broadcast transmission, the sender modem does not receive confirmation of the “successful reception” of the transmitted data from any of the receiver modems.  In broadcast transmission, the sender modem transmit the data packet the number of times equal to the preset retransmission count (REG11 or RNO command setting) plus Data Transmission ACK response
  14one and then it outputs a successive completion response (P0) to its terminal equipment. When the remote receiver modems receive the transmitted data successfully, they output the data to their terminal equipments normally and do not return ACK packet. Once a valid data packet has been received correctly by a receiver modem, rest of data received during any subsequent retransmissions are discarded and not output to its terminal equipment.               Sender Modem                                                                             Remote Modem Figure 3–3:  Broadcast Transmission 3.2.3  Transmit Command and Receive Header Six transmit commands can be used in packet transmission mode . Both text and binary data can be sent directly from modem-to-modem or sent through a third FDL01TU modem configured as a repeater. The receiver modem automatically determines the transmitted data format and communication path from the information in the received packet header. Refer to the table below for a list of the transmit commands and the corresponding header component.  Transmit Command Receive Header  Function TXT  RXT  Text data transmission TBN  RBN  Binary data transmission TXR  RXR  Text data transmission via repeater TBR  RBR  Binary data transmission via repeater TX2  RX2  Text data via two repeaters TB2  RB2  Binary data via two repeaters Table 3–5:  Transmit Commands and Receive Headers Data Transmission Retransmission Retransmission Retransmission ・ ・ ・ End
 15The following list shows each command’s syntax as issued at the sender terminal equipment and the response displayed at the receiver terminal equipment when the packet is received.    1.  Direct Text Data Transmission   transmit: @TXT [destination address]{source address}[message]    receive:  RXT [source address][message] CR/LF   2.  Direct Binary Data Transmission   transmit: @TBN[destination address]{source address}[message length][message] CR/LF   receive:  RBN [source address][message length][message] CR/LF   3.  Text Data Transmission through Repeater   transmit: @TXR [repeater address][destination address]{source address} [message] CR/LF   receive:  RXR [repeater address][source address][message] CR/LF   4.  Binary Data Transmission through Repeater   transmit: @TBR [repeater address][destination address]{source address}      [message length][message] CR/LF   receive:  RBR [repeater address][source address][message length][message] CR/LF  where {source address} is optional, used in RS485 mode set by serial communication cable 12 pin.  The following list defines the parameters and symbols used in the commands above:  @  =  command header  CR/LF  =  carriage return + line feed   destination address  =  address of modem to receive the message (000 to 239)   source address  =  address of modem sent the message (000 to 239)   repeater address  =  address of the repeater modem (000 to 239)   message length  =  number of bytes in message   message  =  information data (255 bytes or less)   In the text data transmission, the message is considered to be terminated when the CR/LF code appears in it. No data after that will be transmitted. When the CR/LF code contains in a message, use the binary data transmission command.           CAUTION
  163.3  Headerless stream Mode   3.3.1  Operation in the headerless stream mode The headerless stream mode is a specific transmission mode to set transmission data without the packet header, employing the protocol of the packet transmission mode. Parameters such as receiver or repeater addresses are set either by the memory register or by the command. A transmission data packet is automatically terminated by the specific character (terminator). Command responses (P1, P0) are not output.  In the headerless stream mode, since the transmission data is no longer to be issued as the transmission command. At the end to end of the wired link, existing upper layer application protocol can be used without awareness of the wireless link protocol.  This mode can communicate with the normal packet transmission mode interactively. This mode cannot be used in the RS485 mode. 3.3.1.1   Format of the headerless stream mode In the headerless stream mode, no response (P1, P0) following the transmission command is output. Instead of outputting the receive header or the CR/LF code, the specific characters (terminator) is output which separates data to a transmission packet at the sender end.   Since the transmission packet contains the sender’s address, data format (text or binary mode) and the repeater address, the headerless stream mode is compatible with the normal packet transmission mode and the interactive communication can be performed between them.  The transmission and receiving formats in the headerless stream mode are as follows.  1.   Packet transmission mode (for the reference below) Sender:  @TXT002HELLO CR/LF  ->  Receiver: RXT001HELLO CR/LF 2.   Headerless stream mode (when terminator is CR/LF) Sender:  @HELLO CR/LF  ->  Receiver:  HELLO CR/LF 3.   When the receiver is in the packet transmission mode (text mode) Sender:  @HELLO CR/LF ->  Receiver:  RXT001HELLO CR/LF 4.   When the receiver is in the packet transmission mode (binary mode) Sender:  @HELLO CR/LF ->  Receiver:  RBN001HELLO CR/LF CR/LF 5.   When sender is in the packet transmission mode  Sender:  @TXT002HELLO CR/LF ->  Receiver:  HELLO  When the receiver is in the packet transmission mode, be careful about the terminator. For details, refer to REG23 of p.27 MEMORY REGISTER DESCRIPTION.
 17The difference between the text mode and the binary mode does not matter in the headerless stream mode. 3.3.1.2   Commands for the headerless packet mode The same command as used in the packet transmission mode can be used, but the following commands which attempted transmission cannot be used.       TXT, TXR, TBN, TBR, RPT, RTY.  3.3.1.3   Repeater in the headerless packet mode The repeater also can be used in the headerless stream mode. The repeater address is set with the memory register or the PAS command. The repeater itself no needs to be in the headerless stream mode. Set REG18:bit 5 whether the repeater is used or not. The address of the repeater is set using REG08 and REG09 or PAS command.     3.4  Power Down Mode The FDL01TU has three power down modes. Select the mode according to the power supply operating conditions such as battery powered application.  (1) Active Mode This mode is not the power down mode but always capable of transmitting and receiving data. The modem is in the active mode when the power is turned on. The current consumption is 110 mA maximum in this mode.  (2) RF Block Power Down Mode This mode shuts down the power supply of the RF circuit block, where only the control (logic) circuit is activating. Since the control circuit is in operation, the setting of memory registers are retained. When the modem returns to the Active mode, it can continue its operation since the register value is retained. Furthermore, functions such as referencing and setting memory registers can be used in this mode.  This mode is invoked by the following commands.   ROF command:    to become the RF block power down mode  RON command:   to return to the Active mode  The current consumption is about 35 mA in this mode.
  183.5  Frequency Grouping 3.5.1  Frequency Allocation The FDL01TU can operate on 76 available frequencies between 2403 MHz and 2480 MHz with 1 MHz separation between each frequency. See the table below for the exact frequency assignments.   Freq.No.  Freq.(MHz)  Freq.No.  Freq.(MHz) 0 2403.328 45 2449.408 1 2404.352 46 2450.432 2 2405.376 47 2451.456 3 2406.400 48 2452.480 4 2407.424 49 2453.504 5 2408.448 50 2454.528 6 2409.472 51 2455.552 7 2410.496 52 2456.576 8 2411.520 53 2457.600 9 2412.544 54 2458.624 10 2413.568 55 2459.648 11 2414.592 56 2460.672 12 2415.616 57 2461.696 13 2416.640 58 2462.720 14 2417.664 59 2463.744 15 2418.688 60 2464.768 16 2419.712 61 2465.792 17 2420.736 62 2466.816 18 2421.760 63 2467.840 19 2422.784 64 2468.864 20 2423.808 65 2469.888 21 2424.832 66 2470.912 22 2425.856 67 2471.936 23 2426.880 68 2472.960 24 2427.904 69 2473.984 25 2428.928 70 2475.008 26 2429.952 71 2476.032 27 2430.976 72 2477.056 28 2432.000 73 2478.080 29 2433.024 74 2479.104 30 2434.048 75 2480.128 31 2435.072    32 2436.096    33 2437.120    34 2438.144    35 2439.168    36 2440.192    37 2441.216    38 2442.240    39 2443.264    40 2444.288    41 2445.312    42 2446.336    43 2447.360    44 2448.384
 193.5.2  Frequency Group Operation The FDL01TU can operate on a fixed frequency or on any frequency in a set of frequency group.  Multiple FDL01TU systems can be use different frequency groups and operate in the same area without mutual interference between the systems. When the RF environment is relatively clean, wireless channel links can be made on a fixed, clear frequency (no interference) by using Grouping Method A. In less than ideal RF environments, it is better to use multiple frequencies method in the frequency group (Grouping Method B through G, multi-Access function). Since the modem searches clear frequency in the group, it overcomes multipath fading and interference problems and establishes wireless communications.  On the down side, wireless link establishment delays will become longer when using the frequency group function (multi-access function) because the additional time is required for searching the channels in the group with transmitting and receiving the packet on the both end of the modem. The average connection delay will increase and the number of systems that can operate independently in the same area will decrease as the number of frequencies per group increases. Select the best grouping method for your application. 3.5.3  Grouping Methods The frequency grouping method and group number are set using memory register REG06.   Method Group Numbers Frequencies per Group A  0  to  75   1 B  0 to 37   2 C  0 to 24   3 D  0 to 18   4 E  0 to 11   6 F  0 to 8   8 G  0 to 5   12 Table 3–7:  Frequency Grouping Methods and Group Numbers
  20
 214SECTION   4   FUNCTION CONTROL METHODS
  22 4.1  Interface 4.1.1  Pin Assignment The figure below shows the pin location of the serial communication connector, following the DCE (Data Communication Equipment) specification.           Figure 4–1:  Serial Communication Connector Location Pin Name  Abbreviation I/O  Function 1  Carrier Detect Out  DCDO  output  carrier detect output 2  Receive Data  RxD  output  received data output  3  Transmit Data  TxD  input  transmit data input  4  Data Terminal Ready  DTR  input  terminal ready 5  Signal Ground  GND  –  signal ground 6  Data Set Ready  DSR  output  modem ready 7  Request To Send  RTS  input  receive stop/resume request 8  Clear To Send  CTS  output  transmit stop/resume request 9  Carrier Detect In  DCDI  input  ring indicator input 10  Power Supply  VCC  –  2.7V to 3.3V DC 11  Modem Shutdown  POWER_ON input  Power On control 12  RS485 Enable  485ENB  in/out  RS485bus Tx Enable at 485mode 13  Load Default Parameter /INIT  input  Load default parameter when low 14  Reserved  Reserved  –  Reserved Table 4–1:  Pin Descriptions   1. The serial communication connector’s pin of the modem is defined as the DCE specification, where transmission indicates input and reception indicates output. 2.  Pin 12 is for tri-state control for RS485 driver (CMOS - RS485 level converter) which will be externally mounted. When the power is turned on or reset, this pin is configured as an input pin to read the operation mode in the interface. When it is pulled down, the operation becomes the RS485 mode, and when it is pulled up (or leave open) the operation becomes the RS232C mode. Since this pin becomes to configure the output pin after reading the operation mode at the initialize state, never connect it directly to VCC or GND.  This pin is internally pulled up with 470 k ohm. 3.  Pin 13 is internally pulled up with 100 k ohm. 4.  The input pin tolerates 5 V input (5 V tolerant specification). When the user’s system is of 5 V, it is possible to interface with a such system. # 1 # 14
 235.  Pin 11 can be used as the hardware reset. Since the input pin is at high impedance, never fail to tie the input level. 6.  It is no problem if Pins 12, 13 and 14 are leaved open. 7.  Since the interface is CMOS structure circuit, it is recommended to take a remedy against ESD problem (e.g. surge absorber; VRD series, made by Ishizuka Denki). 4.2  Serial Interface Setting For connecting the FDL01TU modem with an external terminal equipment, RS232C is appropriate for 1 to 1 topology. And set the RS485 mode to make RS485 multi-dropping topology for multiple equipment connection. Interface configuration can be made with Pin 12 (/RS485ENB) of the serial communication connector. To configure the RS485 mode, pull down Pin 12 with 10k ohm register.  In this case, do NOT connect this pin DIRECTLY to the GND. This is because in RS485 mode, this pin will be as an output pin, after the initialization completes, to control the output buffer of the RS485 driver IC chip. As for the RS232C interface, no connection is required because it is pulled up inside. Since the interface level of the FDL01TU modem is CMOS, the level conversion circuit must be provided outside for connecting it with the RS232C or RS485 interface. For an example of the level conversion circuit, see p.64 CONVERSION CIRCUIT.                     Figure 4–1:  Connection Example to PC Converter PC RS-232C FDL modem
  244.3  Terminal Software Setup for Memory Register Control Communication or terminal software is necessary to set the memory registers. Nearly any PC communication software can be used. Launch the communication software and set the terminal’s communication parameters as shown below. Refer to your specific communication software instructions how to set these parameters.    bit rate:  9600 bps   data length:  8 bits   stop bits:  1 bit   parity bit:  none   flow control:  none   local echo:  yes   terminator:  carriage return + line feed  4.4  Memory Register Setting Memory registers set the operation mode and communication parameters of the modem and retain them in memory. All of the settings of the modem are made by these memory registers. Since the memory register is based on rewritable non volatile memories, these memories can be readily rewritten by external terminal equipment such as PC and their contents will be kept even after the power is turned off. This non volatile memory can be rewritten about 1 million times. 4.4.1  Memory Register Referencing and Setting Memory registers are referenced and set with the REG command. (For more information, refer to REG section at p.43 COMMAND SET DESCRIPTION)  Example procedure: 1.  To view the current value of register 00, enter: @REG00 CR/LF 2.  Modem responds with 00H CR/LF (REG00 is assumed to be 00H in this case and varies in each setting case) 3.  To set register REG00 to 0FH, enter: @REG00:0FH CR/LF 4.  Modem responds with “P0” CR/LF 5.  Enter “@RST CR/LF” or cycle the modem power, to activate new values   @  =  command header (specify following characters are command)  CR/LF  =  Terminator (carriage return + line feed)  When rewriting the modem’s memory registers, do not turn the modem’s power off until the modem returns “P0” response. If the power is interrupted before “P0” is returned, the memory contents may be lost or corrupted and the modem operation will be unpredictable.  CAUTION
 25If the memory contents are lost or corrupted, they can be restored to original default settings by reinitializing them. (See the section below titled p.25 MEMORY REGISTER INITIALIZATION) Input character arrays of commands quickly and sequentially. Too slow input (taking more than 5 seconds in the initial setting) results in command error.  4.4.2  Memory Register Initialization The memory registers can be restored to the factory default values at any time by using one of the following two methods.  1) Memory Register Initialization by hardware: Use either methods stated below, in which the modem attempts to read Pin 13 (/DefParam) of the serial communication connector at the startup and starts initializing the memory registers when it is “L”.  Method 1.  Set “L” level to Pin 13 (/INIT) of the serial communication connector  with the power turned off. When the power is re-supplied, the memory registers are initialized and the modem starts operation in the factory default state. Method 2. Set “L” level to Pin 13 (/INIT) of the serial communication connector while the power turned on. In this state, force “L” to Pin 11 (POWER ON) of the serial communication connector more than 1ms, then return the level to “H”. The modem once becomes the Shutdown mode and returns to Active mode. Since this sequence is the same as the reset, the memory registers are initialized and the modem starts operation in the factory default state. 2) Memory Register Initialization by Command: 1.  With the modem power is on and the communication software running, enter “@INI CR/LF  ”  at the terminal prompt. 2.  The modem responds with “P0” response and immediately begins to operate using the initialized factory default state. While initializing the memory registers, do not turn the modem’s power off. It take about 1 sec. to initialize the memory registers.  CAUTIONCAUTION
  264.5  Command Control Some FDL01TU parameters can be changed by issuing commands from the terminal equipment. Various applications can be supported with the flexibility that command control offers.  Command Entry • When a command is issued to the modem from the terminal equipment, a command header (one byte character) should be used the modem to acknowledge the command from ordinary data. The command header is initially set to “@” (40H) but can be changed to another character by changing the value stored in the memory register REG10. • Commands must use all upper case letters (A to Z). The modem does not recognize lower case letters (a to z) in commands. • A two byte terminator (carriage return (0DH) + line feed (0AH)) is used to terminate a command. “CR/LF” shows the terminator in this manual. PC can send this two byte character with pressing ENTER key once using a communication software. But some setting is necessary in the software. • The modem immediately executes a command once it’s recognized. If the command requires a response, the modem returns the response to the terminal equipment when its internal processing is completed. The following is an example of a command entry and response:    @BCL CR/LF   :command issued from the terminal equipment   P0 CR/LF    : successive completion response is returned
 275SECTION  5   MEMORY REGISTER DESCRIPTION
  28 5.1  Memory Register Description The FDL01TU modem contains 28 memory registers which are used to control and store communication parameters and operation mode settings. After rewriting new register settings, the power must be cycled, a hardware reset asserted, or a software RST command is issued to validate the new settings.  The following table briefly lists each register, register function and default value:  Register  Function  Default Value  Meaning REG00  Local Station Address  000   address 0 REG01  Local Station Group Address  240   address 240 REG02  Destination Address  000   address 0 REG03  Reserved  F0 H  F0H REG04  ID Code 1  00 H  address 0 REG05  ID Code 2  00 H  address 0 REG06  Frequency Group  C00   see text REG07  Packet Interval  05 H  5 ms REG08  Repeater1 Address  A00   not use REG09  Repeater2 Address  A00   not use REG10  Command Header  40 H  character @ REG11  Retransmission Count  32 H  50 count REG12  Roaming Threshold  50 H  -80dBm REG13  Buufer Data Timeout  1E H  30 s REG14  Command Input Timeoutl  32 H  5 s REG15  Command Recognition Interval  00 H  0 s REG16  Terminator 1  0D H  CR REG17  Terminator 2  0A H  LF REG18  Communication Setting 1  8C H  see text REG19  Communication Setting 2  00 H  see text REG20  Serial Interface Setting 1  05 H  see text REG21  Serial Interface Setting 2  09 H  see text REG22  Serial Interface Setting 3  00 H  see text REG23  Serial Interface Setting 4  00 H  see text REG24  Miscellaneous Settings  C0 H  see text REG25  Miscellaneous Settings  40 H  see text REG26  Data Input Timeout  00 H  not use REG27  Reserved  00 H  - Table 5–1:  Memory Registers Suffix ‘H’ of each default value denotes HEX radix expression in the value.
 29REG00:  Local Station Address  [default value: 000] • Sets the local station address. Valid values are 000 to 999. • This value is inserted in the “source address” field in the transmitted packet header. • If the address check function is enabled (REG18) in the receiving modem, the modem can receive the packet which header contains destination address information identical to REG00. REG01:  Local Station Group Address  [default value: 240] • Sets the local station global address of the modem. Valid values are 240 to 254.   • When plural modems are connected by RS485 multi-dropping topology, commands can be issued to multiple modems simultaneously by setting all connected  modems to the same group address. This is the group addressing. • This group addressing allows to handle multiple multi-dropped modems as if they were one modem. REG02:  Destination Address  [default value: 000] • This address is used in the data transpalent mode and headerless stream mode. • Valid values are 000 to A23(1023). REG03:  Reserved  [default value: F0H] • The FDL01TU does not use this register. Keep the default value as it is. REG04:  ID Code 1  [default value: 00H] • Used with ID code 2 (REG05), set the ID code. Valid values are 000 to 255. Together with ID code 2, up to 65535 ID codes can be set. • The ID code identifies the group of the modems works in the same group. The ID code is used to prevent erroneous connection with other systems and for communication security. • Before transmission, radio data packets are scrambled using a pseudo-random data sequence generated with this ID code as the seed. During reception, the original data is restored by de-scrambling it with the pseudo-random data sequence. The modems with different ID codes cannot communicate with each other. REG05:  ID Code 2  [default value: 00H] • Used with ID code 1 (REG04), set the ID code. Valid values are 000 to 255. Together with ID code 1, up to 65535 ID codes can be set. • In case plural modems are used as a single system, always set the same ID code for all modems and repeaters.
  30REG06:  Frequency Group  [default value:C00] • Refer to p.18 FREQUENCY GROUPING in Section 3, for a detailed description of the frequency operation modes.  Method Group Numbers Frequencies per Group A  0  to  75   1 B  0 to 37   2 C  0 to 24   3 D  0 to 18   4 E  0 to 11   6 F  0 to 8   8 G  0 to 5   12 Table 5–2:  Grouping of Frequency REG07:  RS485 Packet Interval  [default value: 05H] • In the packet transmission mode with the RS485 mode is used, sets the interval between response and/or received data which output from the modem to RS485 line.  • Be able to set 0 to 254 ms at increment of 1 ms. 255ms is not allowed. The default value is 5 ms. • Set this interval to a larger value than the receiving interval set by REG14.   • Suitable setting of this interval avoids the data collision possibility of RS485 line.  REG08:  Repeater 1 Address  [default value: A00] • When a repeater is used, set the repeater1 address to pass through. REG09:  Repeater 2 Address  [default value: A00] • When second repeater is used, set the repeater2 address to pass through. REG10:  Command Header  [default value: 40H] • Sets the character that identifies the start of a command. • The default is character “@” (40H). • When this character is input from the terminal equipment after no character is received for the command recognition interval (REG15) or longer, subsequent input character is recognized as a command for the modem.
 31REG11:  Retransmission Count  [default value: 32H] • Sets the maximum number of packet retransmission attempts. Valid values are 000 to 255. • When retransmission exceeds the retransmission count (retransmission count plus one), the modem outputs an error response to the terminal equipment. REG12:  Roaming Threshold  [default value: 50H] • At the time to set the frequency roaming (REG19:bit 2 is 1), set the receiving strength threshold of the radio beacon which starts scanning frequency. • Set the value of the desired radio beacon strength threshold represented in dBm excluding the minus sign, e.g., set to “080” to search the next master station when the radio beacon strength becomes below –80 dBm. REG13:  Buffer Data Timeout  [default value: 1EH] • Valid values are 000 to 255, representing seconds in 1 s increments. REG14:  Command Input Timeout  [default value: 32H] • Sets the character input timeout interval for command input. It is used as the timeout between the command header and the character following it and between each character of the command. • At the timeout, the modem operation transits from command-input-state to data-wait-state. • Valid values are 000 to 255, representing tenths of seconds in 0.1 second increments. (Set an integer value equal to ten times the number of seconds desired.) • A setting of 000 disables this timeout function REG15:  Command Recognition Interval  [default value: 00H] • When a message data contains a command header character (in case of binary data or data in two-byte Chinese characters), data following the command header character will be interpreted as a command, the message does not transmit properly. • Sets the necessary vacant duration time interval to discriminate between ordinary data character and a command header character. Input a command after a longer interval than time interval setting. • Valid values are 0.1 to 25.4 sec., representing tenths of seconds in 0.1 second increments. (Set an integer value equal to ten times the number of seconds desired.) • When set to 000, the command header is recognized at any time, and when set to 255, all command header character are ignored.
  32REG16:  Terminator 1  [default value: 0DH] • Set an arbitrary 1 byte terminator. In case of a 2-byte terminator, set the first byte character of the terminator. REG17:  Terminator 2  [default value: 0AH] • Set another arbitrary 1 byte terminator. In case of a 2-byte terminator, set the last character of the terminator . REG18:  Communication Setting 1  [default value: 8CH] Bits 7 – 6:  Protocol bit 7 bit 6 Setting 0  0  Data transpalent mode 0  1  Reserved 1  0  Packet transmission mode 1  1  Headerless stream mode Table 5–7:  Protocol Bits 5:  Reserved • The FDL01TU does not use this register. Keep the default value as it is.   Bit 4  Transmission format 0  transmit  in the text form (default value) 1  transmit in the binary form Table 7–4  Transmission format • Selects the transmission format. When data are transmitted to the destination station which is set to the normal packet transmission mode, output text format (RXT, RBN) from the receiver modem (destination station) differs depend on this setting. • This setting does not effect in the receiver modem set as headerless stream mode.  Bits 3 – 2  Terminator Setting bit 3  bit 2  setting 0  0  two kinds of arbitrary 1 byte code (REG16, REG17) 0  1  arbitrary 1 byte code (REG16) + a wild card (any character) 1  0  arbitrary 2 byte code (REG16 + REG17) 1  1  carriage return (CR) + line feed (LF) (default value) Table 7–5  Terminator setting
 33• Sets the terminator to identify the breakpoint of a packet. The modem transmits data considering this character as the breakpoint of a packet. • In case of using an arbitrary terminator, set it to REG16 and 17.   Bit 1:  Source address check 0  Inhibit source address checking  (default value) 1  Activate source address checking Table 5–4:  Source Address Check Settings • When the source address checking is active and the source address in the received packet header does not match the destination address setting (REG02), the data is discarded (data cannot be received). Bit 0:  Destination address check 0  Inhibit destination  address checking on receipt (default) 1  Activate destination address checking on receipt Table 5–5:  Destination address check • When the destination address checking is active and the destination address in the received packet header does not match the received modem’s local station address (REG00), the data is discarded (data cannot be received). REG19:  Communication Setting 2  [default value: 00H] Bit 7:  Reserved • The FDL01TU does not use this register. Keep the default value as it is. Bit 6:  Diversity Reception 0  Disable diversity reception (default value) 1  Enable diversity reception Table 5–6:  Diversity Reception Settings • Enable/disable diversity reception. • To enable diversity reception, set this bit to 1. • Enabling diversity reception with only one antenna connected may degrade the reception performance. Bit 5:  Broadcast Transmission Reception 0  Enable broadcast transmission reception (default value) 1  Disable broadcast transmission reception Table 5–7:  Broadcast Reception Settings
  34• Enable/disable reception of broadcast transmission in packet transmission mode (Mode 3 and 5). Bit 4:  Antenna selection 0  Antenna is fixed to A  (default value) 1  Antenna is fixed to B Table 5–8:  Antenna Selection • At the non-diversity reception, decide the antenna terminal. Bit 3:  Extended reception 0  Disable extended reception (default value) 1  Enable extended reception  Table 5–9:  Extended reception • Contention type communication in packet transmission mode (including the headerless stream mode) may cause repetitive retransmission when two modems are in transmission state in identical timing. This results in the decrease of response rate or the transmission failure. • This extend reception function solves such problems as above. The data packet received during carrier sensing are received first by interrupting the on-going transmission operation.  Bit 2:  Receiving frequency change 0  Regularly change frequency within a group while waiting (default value) 1  Fix the frequency to wait while data can be regularly received. Table 5–10:  Receiving frequency change  • Set the changing method of receiving frequency in packet transmission mode. Sets roaming function with combining bit 1. Bit 1:  Beacon transmission 0  No transmission until transmission command is requested (default) 1  Enable regular beacon transmission. Table 5–11:  Beacon Transmission • Enable or disenable beacon transmission in packet transmission mode. • Set roaming function with combining bit 2. Bit 0:  Reserved • The FDL01TU does not use this register. Keep the default value as it is.
 35REG20:  Serial Interface Setting 1  [default value: 05H] Bit 7:  Data Length 0  8 bit data bytes  (default value) 1  7 bit data bytes Table 5–13:  Data Length Settings Bit 6:  Parity Bit 0  No parity bit   (default value) 1  Parity bit Table 5–14:  Parity Settings Bit 5:  Even/Odd Parity 0  Even parity  (default value) 1  Odd parity Table 5–15:  Odd/Even Parity Settings • Invalid when bit 6 is set to 0, without parity. Bit 4:  Stop Bit 0  1 stop bit  (default value) 1  2 stop bits Table 5–16:  Stop Bit Settings Bits 3 – 0:  Baud rate setting Bit 3 Bit 2 Bit 1 Bit 0 Setting 0  0  0  0                    300 bps 0  0  0  1                    600 bps 0  0  1  0                  1200 bps 0  0  1  1                  2400 bps 0  1  0  0                  4800 bps 0  1  0  1                  9600 bps (default) 0  1  1  0                19200 bps 0  1  1  1               38400 bps 1  0  0  0  Reserved 1  0  0  1  Reserved 1  0  1  0  Reserved 1  0  1  1  Reserved 1  1  0  0             57600 bps 1  1  0  1           115200 bps 1  1  1  0           230400 bps 1  1  1  1  Reserved Table 5–17:  Baud Rate
  36REG21:  Serial Interface  Setting 2  [default value: 09H] Bits 7 – 4:  Reserved • The FDL01TU does not use this register. Keep the default value as it is. Bit 4:  Command Header 0  Use REG 10 character 1  Use Break signal Table 5–16:  Command Header  Bit 1:  Flow Control 0  Software flow control (default value) 1  Hardware flow control Table 5–18  Software/Hardware Flow Control Settings • Selects the flow control method. This setting must match the connected terminal equipment’s setting. • Hardware flow control uses the two control lines RTS and CTS. When using with the RS485 interface, be sure to set to 0. • Software flow control uses XON and XOFF codes. Bit 0:  Flow Control 2 0  disable flow control 1  enable flow control  Table 5–31:  Flow Control 2 Settings  • Enable or disable flow control between the terminal and FDL01TU modem connected through the RS-232C serial interface. • This function should normally be enabled, otherwise buffer overflow can occur and data may be lost. REG22:  Serial Interface Setting 3  [default value: 00H] Bit 7:  Enable and Disable Reception 0  Enable reception at the initial state  (default value) 1  Disable reception at the initial state  Table 5–19:  Enable/Disable Reception • The initial state is in reception enable. Depending on an usage of the modem, the initial state of the modem may be better in the reception disable state. In such a case, use this setting.
 37• Issue the REN command to enable reception. Bit 6:  Reserved • The FDL01TU does not use this register. Keep the default value as it is.  Bits 5 – 4:  DCD (Data Carrier Detect) Bit 5 Bit 4  Setting 0  0  Ignore DCD input; DCD output always ON (default value) 0  1  Ignore DCD input; DCD output ON at connection, OFF at disconnection 1  0  Remote modem’s DCD (IN) is transferred to local modem DCD (OUT). (DCD Output = OFF at reset state) 1  1  Remote modem’s DCD (IN) is transferred to local modem DCD (OUT) (DCD Output = ON at reset state) Table 5–20:  DCD Settings Bits 3 – 2:  DTR/DSR Bit 3 Bit 2  Setting 0  0  Ignore DTR input; DSR output always ON (default value) 0  1  Ignore DTR input; DSR output ON at connection, OFF at disconnection 1  0  Remote modem DTR is transferred on local modem CTS (CTS = OFF at reset state) 1  1  Remote DTR is transferred on local modem CTS (CTS = ON at reset state) Table 5–21:  DTR/DSR Control Settings Bits 1 – 0:  Reserved • The FDL01TU does not use this register. Keep the default value as it is. REG23:  Serial Interface Setting 4  [default value: 00H] Bit 7 :  reserved • The FDL01TU does not use this register. Keep the default value as it is. Bit 6 :  Transmission buffer clear 0  Data of the transmission buffer is kept after disconnection  (default value) 1  Transmission buffer is cleared when the link is disconnected.  Table 5–38  Transmission buffer clear • Determine to clear or not to clear data stored in the transmission buffer in the data transparent mode when the link is reconnected. Bit 5 :  reserved • The FDL01TU does not use this register. Keep the default value as it is.
  38 Bit 4 :  CR/LF addition/deletion (1) Setting at the headerless stream mode 0  does not add CR/LF code to the received data (default value) 1  adds CR/LF code to the received data Table 7–6:  Addition of CR/LF code  • In the headerless stream mode, setting is made whether the CR/LF character is added to the received data or not.  • In the communication between the modems set to the headerless packet mode, this setting is invalid because the terminator is originally added to the transmit data.  However, when a packet is received from the modem in the packet transmission mode, there is no addition of the CR/LF terminator. In this case, set this bit to 1. Then the received packet is output with the CR/LF character is added. (2) Setting at the packet transmission mode 0  adds the CR/LF to the received data (default value) 1  does not add the CR/LF to the received data Table 7–7:  Deletion of CR/LF character • In the packet transmission mode, setting is made whether the CR/LF character is added to the received data or not. • At the receiver modem (set to the packet transmission mode), the sender (set to the headerless stream mode) side terminator (CR/LF character as default) plus packet transmission mode terminator (CR/LF) are output. To avoid such redundant outputs, set this bit of the modem in the normal packet transmission mode to 1. Bit 3:  reserved • The FDL01TU does not use this register. Keep the default value as it is. Bit 2:  RS485 collision avoidance regular interval output 0  No C/R code output for collision avoidance (default value) 1  Regularly output C/R code for collision avoidance Table 5–23:  C/R Code Regular Interval Output • Sets whether the collision avoidance function is used or not, together with bit 1. •  When this bit is set to 1, responses or data will be output to RS485 line if there are such responses or data exist in the buffer at the timeout of the RS485 Packet Interval (REG07).  If there are no such responses or data exist in the buffer, the C/R code (0Dh) is compulsorily output. • The effective use of this function helps to shift the output timing of multi-dropped  modems on RS485 line. Eventually it avoids the data collision on the RS485 line.
 39• To use this function, set REG23:bit 1 of all RS485 multi-dropped modems to 1. And set all the RS485 Packet Interval (REG07) to different values more than 1.5 bytes each. Further set this bit of the modem, the RS485 Packet Interval is set to the longest, to 1. Bit 1:  RS485 collision avoidance 0  Invalid collision avoidance function (default value) 1  Use  collision avoidance function Table 5–24:  Collision Avoidance Function • Sets to decide whether to use the collision avoidance function or not, together with bit 2. • When modem tried to output a response or the received data, the modem outputs only if RS485 line is available at the timeout of RS485 Packets Interval (REG07).  When RS485 line is not available at the timeout, the modem waits for a line becomes available and starts re-measurement of its packet interval. • Set to 1 makes it unable to output neither response nor the received data, unless other modem(s) outputs any data to the RS485 line and interval time measuring becomes effect. • Bit 2 is used for the purpose of resolving this problem.  Bit 0:  Global addressing command response 0  No P0 response to global addressing command (default value) 1  Respond P0 response to global addressing command  Table 5–25:  Global addressing command response • Set to decide whether to return “P0” response (including “P1” for the transmit command) to the terminal equipment for the global addressing command (commands for Addresses 240 to 254).  • When the global addressing command is issued to plural modems, which are multi-dropped and have the same global address on RS485 line, there is a possibility causing data collision on the RS485 line. Unless the RS485 Packet Interval is properly set. This is because all modems return the “P0” (or P1) response to the terminal equipment simultaneously on default memory setting. Such potential problem can be avoided by limiting the modem to output the response to the global addressing command is only one.
  40REG24:  Special Mode Settings  [default value: C0H] Bit 7 :  reserved • The FDL01TU does not use this register. Keep the default value as it is.  Bit 6:  Transmission trigger (Headerless stream mode) 0  Need trigger even if data number exceeds 255 bytes(default value) 1  Transmit without trigger when the data number exceeds 255 bytes Table 5–26:  Transmission trigger setting  • Sets the trigger mode of the Headerles stream mode.  Bit 5 – 2:  reserved • The FDL01TU does not use this register. Keep the default value as it is. Bits 1 – 0:  Reception protocol Bit 1 Bit 0  Setting 0  0  Receive with the setting of REG18 bit7 to bit6(default value) 0  1  Receive with the packet transmission mode 1  0  Receive with the headerless stream mode 1  1  Receive with the protokol of the received packet Table 5–21:  Reception protocol REG25:  Special Mode Settings 2  [default value: 40H] Bit 7 – 3:  reserved • The FDL01TU does not use this register. Keep the default value as it is. Bit 2:  Group address settings 0  Normal group address (240 to 254)(default value) 1  Extended group address (1000 to 1023) Table 5–29:  Group address setting Bit 1:  Address response 0  No response the address when the link is connected or disconnected (default value) 1  Response the destination address when the link is connected or disconnected. Table 5–29:  Address response
 41Bit 0:  Route finding 0  According to the memory registers (default value) 1  Trace the received packet. Table 5–29:  Settings of the route  REG26:  Data input timeout  [default value: 00H] • Sets the vacant duration time interval to recognize as the end of the message data input in the headerless stream mode. REG27:  Reserved  [default value: 00H] • The FDL01TU does not use this register. Keep the default value as it is.
  42
 436SECTION 6   COMMAND SET DESCRIPTION
  446.1  Command Set Description This section provides a description of each command available in the FDL command set. The table below lists each command and it applicability in each operation mode.    Command  Function      1  ARG  Reference All Memory Resisters 2  BCL  Clear Transmit and Receive Buffers  3  CON  Connect Wireless Link 4  DAS  Reference and Set the Destination Address 5  DBM  Read Signal Strength 6  DCN  Disconnect Wireless Link 7  FRQ  Reference and Set Frequency Group 8  INI  Initialize All Memory Resisters 9  ODA  Disable Received Data Output 10  OEN  Enable Received Data Output 11  PAS   Reference and Set Repeater Address 12  RDA  Disable Wireless Reception 13  REG  Reference and Set Memory Resisters 14  REN  Enable Wireless Reception 15  RID  Display Received Serial ID 16  RNO  Reference and Set Retransmission Count 17  ROF  RF Circuit Block Power Down 18  RON  RF Circuit Block Power Up 19  RST  Reset 20  SAS  Reference and Set Local Station Address 21  STS  Read Status 22  TBN  Transmit Binary Data 23  TBR  Transmit Binary Data Through Repeater 24  TID  Display Local Station Serial ID 25  TXR  Transmit Text Data Through Repeater 26  TXT  Transmit Text Data 27  VER  Reference Version Information Table 6–1:  Command to Mode Availability  The symbols used in this section have the following meaning:    >  :  Input character from the terminal equipment to the modem   <  :  Output from the modem to the terminal equipment  @  :  Command header  CR/LF  :  Terminator (carriage return + line feed)   [ ]  :  Required input parameter/s   Be sure to input.   ( )  :  Optional input parameter/s    May be omitted   {}  :  485 mode local station address (REG00). Be sure to       input at 485 mode  In the Syntax and Response segments of the following command descriptions the terminator symbol (CR/LF) has been omitted for clarity.
 45ARG  Reference All Memory Registers Syntax   ARG{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to 999). Response   All settings are indicated (REG00 to REG27)   N0:  command error (Except 485 mode) Function   Recalls the contents of all 28 memory registers. Example   >@ARG CR/LF  :  Recall the contents of all the memory registers    <REG00 : 001 CR/LF  :  Consecutive output of register contents   <REG01 : 240 CR/LF  :  Register values output in hexadecimal codes   <REG02 : 002 CR/LF   <REG03 : F0H CR/LF   |   |   <REG26 : 00H CR/LF   <REG27 : 00H CR/LF BCL  Clear Transmit and Receive Buffers Syntax   BCL{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   On headerless stream mode , clears the contents of the transmit and receive buffers of the modem. Example   >@BCL CR/LF  :  clear the buffer contents   <P0 CR/LF  :  command accepted Example   >@BIV025 CR/LF  :  Set the receiving (transmission) interval at 250 ms   <P0 CR/LF  :  command accepted   >@BIV CR/LF  :  Refer the current value   <025 CR/LF  :  025 (25 0ms) returns    Notes Values set by the BIV command will be lost by turning the power on or resetting. Generally, this parameter is no need to modifying. Use with the default value.
  46CON  Connect Wireless Link Syntax   CON(destination address)    destination address  :  000 to 999 Response   P0  :  connection established   P1  :  command received, link established   N0  :  command error   N1  :  connection failed – no response from destination modem   N4  :  connection failed – local modem already connected to a remote modem. Function   Requests a wireless link connection to the remote modem  in data transparent mode.   If this command is input with no destination address parameter, the destination will be the address that was set with the REG02.   If the destination address is input, change the destination address to connect the wireless. Example   >@DAS002 ↵  :  set the destination address to 002   <P0 ↵  :  connection established   >@CON ↵  :  request wireless connection remote station 002   <P1 ↵  :  connecting…   <P0 ↵  :  connection established     (Time-Division-Duplex communication between terminals is established.)    >@DCN ↵  :  request disconnection of the wireless link   <P1 ↵  :  disconnecting…   <P0 ↵  :  connection established   >@CON003 ↵  :  request wireless connection to remote station 003   <P1 ↵  :  connecting…   <P0 ↵  :  connection established   >@CON004 ↵  :  request wireless connection to remote station 004   <N4 ↵  :  local modem already connected to a remote modem Notes   If this command is input to designate the destination address, the destination address set with the DAS command will be changed to set the address designated with this command to the designation address. DAS  Reference and Set Destination Address Syntax   DAS(set destination address)    set destination address  :   the desired destination address (000 to A23)
 47Response   xxx  :  current value (reference)   P0  :  command accepted (setting)   N0  :  command error Function   References or sets the destination address of the modem connection established with in the data transparent mode and headerless stream mode   The current DAS value can be referenced by entering the command with no parameter.   The DAS command is used for temporary modifying destination address. Change the value of REG02 to change the default value. Example   >@DAS002 CR/LF  :  set the destination address to 002   <P0 CR/LF  :  command accepted   >@DAS CR/LF  :  reference the destination address    <002 CR/LF  :  current value output (002) Notes   This command cannot be used in packet transmission mode.   The local station address (REG00) must be set to communicate with the remote modem. Communication cannot be established unless the addresses coincide with each other.   This command is not arrowed to use in 485 mode. DBM  Read Signal Strength Syntax   DBM{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to 999). Response   -xxxdBm  : signal strength   N0  : command error (Except 485 mode) Function   Reads the received signal strength and outputs the value in dBm.   Higher values represent stronger signal strength and better receiving conditions. Example   >@DBM CR/LF  :  read signal strength   <-78dBm CR/LF  :  signal strength is -78dBm. Notes   The range available for measurement is –40 dBm to –100 dBm. Since the signal strength indication has a slight error in its value, use this result for your ‘rule of a thumb’ reference.   This command outputs the strength of last received packet.
  48DCN  Disconnect Wireless Link Syntax   DCN Response   P0  :  connection established   P1  :  command received, link disconnected   N0  :  command error   N1  :  link disconnect failed   N4  :  link is disconnected Function   In data transparent mode, this command requests wireless disconnection from the remote modem. Example   >@CON002 ↵  :  request wireless connection to station 002   <P1 ↵  :  connecting…   <P0 ↵  :  connection established    (Time-Division-Duplex communication between terminals is established.)    >@DCN ↵  :  request disconnection of the wireless link   <P1 ↵  :  disconnecting…   <P0 ↵  :  connection established   >@DCN ↵  :  request disconnection of the wireless link   <N4 ↵  :  link is disconnected  FRQ  Reference and Set Frequency Group Syntax   FRQ(:frequency group){Local Station Address}    frequency group  :  combination of frequency grouping method (A to H) and group number (00 to 75). See p.18 FREQUENCY GROUPING more details.     Local Station Address   :  local station address for 485 mode (000 to A22) .  Response   xxx  :  current value   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   References or sets the frequency grouping method and group number.   The current set value is referenced by omitting the “:frequency group” parameter   This command is for temporary use only. To change the default value, change the settings of REG06.
 49Example   >@FRQ CR/LF  :  reference the current grouping method and frequency number   <F00 CR/LF  :  output current value (grouping method F: group number 00)   >@FRQ:E03 CR/LF  :  set grouping method to E (6 groups) and group number to 3.   <P0 CR/LF  :  command accepted   Method Group Numbers Frequencies per Group A  0  to  75   1 B  0 to 37   2 C  0 to 24   3 D  0 to 18   4 E  0 to 11   6 F  0 to 8   8 G  0 to 5   12 Table 3–7:  Frequency Grouping Methods and Group Numbers Notes   Do not change this setting while the modem is being transmitted.   The maximum number of frequency groups available depends upon the selected grouping method. INI  Initialize All Memory Registers Syntax   INI{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22).  Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   Sets the all contents of the memory registers to the factory default values. Example   >@INI CR/LF  :  initialize all memory registers   <P0 CR/LF  :  command accepted  Notes   Custom settings of all memory registers are lost when this command is executed.
  50  If the group address (REG01) is designated while RS485 multi-drop connection is being made in the RS485 mode, the local station address of all modems will be initialized to 000. Exercise care when issuing this command.   For a list of the factory default values, see the section titled p.27 MEMORY REGISTER    DESCRIPTION. ODA  Disable Received Data Output Syntax   ODA{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function  Disables output of any data received via the wireless link to the terminal equipment.   Data received, while output is disabled, is stored in the receive buffer.   When the modem’s power is turned on (or a reset), the modem is in the state to enable the received data output. Example   >@ODA CR/LF  :  disable the output of received wireless data   <P0 CR/LF  :  command accepted     (Data is not output during this period even if received.)    >@OEN CR/LF  :  enable the output of received wireless data.   <P0 CR/LF  :  command accepted   <RXT002HELLO CR/LF  :  outputs data stored in the receive buffer   <RXT003MAIL CR/LF  :       OEN  Enable Received Data Output Syntax   OEN{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function  Enables output of any data received via the wireless link to the terminal equipment.
 51  This command enables serial data output after it has been disabled with the ODA command.   When the modem’s power is turned on (or a reset), the modem is in the state to enable the received data output. Example   >@ODA CR/LF  :  disable serial output of received wireless data   <P0 CR/LF  :  command accepted     (Data is not output during this period even if received.)    >@OEN CR/LF  :  enable serial output of received wireless data.   <P0 CR/LF  :  command accepted   <RXT002HELLO CR/LF  :  outputs data stored in receive buffer   <RXT003MAIL CR/LF  :  and any new data received     PAS  Reference and Set Repeater Address Syntax   PAS  (:Repeater Address1 :Repeater Address2)        Repeater Address   :  repeater address to pass through Response   xxx : xxx  :  current address (reference)   P0  :  command accepted (setting)   N0  :  command error Function   In the headerless stream mode , references and sets the repeater address to pass through   When no repeater address is set, the current setting can be referenced.   This command is used to temporarily change repeater address. To change the default value, change REG13. Example   >@PAS CR/LF  :  references the current repeater address   <004 : A00 CR/LF  :  current repeater address is 004   <P0 CR/LF  :  command accepted   < @PAS:002:A00 CR/LF  :  sets the repeater address to 002   <P0 CR/LF  :  command accepted Notes   This command is not allowed to be used in 485 mode.
  52RDA  Disable Wireless Reception Syntax   RDA{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function  Disables wireless reception in the packet transmission mode.   The status when the modem is powered ON or reset follows bit 7 of REG22. Example   >@RDA CR/LF  :  disable wireless reception   <P0 CR/LF  :  command accepted    >@REN CR/LF  :  enable wireless reception   <P0 CR/LF  :  command accepted REG  Reference and Set Memory Register Syntax   REG[register number](: value) {;Local Station Address}    register number  :  register number to be set (00 to 27)   value  :  value to be set. Input 2 hexadecimal digits (0 through 9 and A through F) followed by the number radix designator H.     Local Station Address :  local station address for 485 mode (000 to A22 ).  Response   xxx  : current value (reference)   P0  : command accepted (setting)   N0  : command error (Except 485 mode)   N6  : memory register write error Function   References or sets memory registers.   The current register value is referenced by omitting the “value” parameter. Example   >@REG00 CR/LF  :  reference the contents of register 00   <01H CR/LF  :  displays current value   >@REG00 : 023 CR/LF  :  set value of memory register 00 to 023 (decimal)   <P0 CR/LF  :  command accepted Notes   The register can be rewritten sequentially. However, to make its parameter valid after rewriting it, re-supply the power, reset the modem or use RST command.
 53While rewriting the memory register, do not turn off the power until response is output. Otherwise, the memory registers content may be collapsed.  When the response of the memory register write error is output, set the values after initializing the memory register. REN            Reception Enable Syntax   REN{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function  Enables wireless reception in the packet transmission mode.   The status when the modem is powered ON or reset follows bit 7 of REG22.   Use this command to enable wireless reception after reception is disabled with the RDA command. Example   >@RDA CR/LF  :  disable wireless reception   <P0 CR/LF  :  command accepted    >@REN CR/LF  :  enable wireless reception.   <P0 CR/LF  :  command accepted RID  Display Received Serial ID Syntax   RID{Local Station Address}      Local Station Address :  local station address for 485 mode (000 to 999). Response   XXXXXXXXXXXX  :  displays the received serial ID code(12 digits)   N0       :  command error  (Except 485 mode) Function   Outputs the serial ID code in the received packet and displays it.  The serial ID code consists of 12 digits; upper three digits are 0 and the lower 9 digits are the product serial number of the transmitted-end modem. Be noted that the serial ID code of the packet received last is displayed. When packets are received from multiple stations and their data are stored in the receiving buffer, those data may not be correspond to the serial ID code readout with RID command.
  54To use it more securely, it is recommended to readout the local serial ID code with TID command and pad it (either all or a part of it) in the transmitting packet. When no packet is received, “All Zero” is displayed as the result of this command execution. The serial ID code is no relation with ID code setting of REG04 and 05. Example   >@RID CR/LF  :  requests the received remote station’s serial ID code   < XXXXXXXXXXXX CR/LF :outputs the received remote station’s serial ID code  RNO  Reference and Set Retransmission Count Syntax   RNO (:Retransmission count) {; Local Station Address}    Retransmission count  : maximum number of retransmissions (000 to 255)     Local Station Address  : local station address for 485 mode (000 to A22).  Response   xxx  :  current set value   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   This command references or sets the number of retransmissions (retransmission count) to attempt before making decision as transmission failure.   The current value can be referenced by issuing the command with no parameter.  RNO command is used to temporarily change the retransmission count. To change the default value, change the setting of REG11. Example   >@RNO CR/LF  :  reference the retransmission count   <050 CR/LF  :  output the current set value (50 times)   >@RNO010 CR/LF  :  set the retransmission count to 10 times   <P0 CR/LF  :  command accepted ROF  RF Circuit Block Power Down Syntax   ROF{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   Turn off the power of RF circuit block and stops RF operation.
 55This function is used to save the current consumption when no transmit/receive are required.  Example   >@ROF CR/LF  :  turn off RF circuit block   <P0 CR/LF  :  command accepted    >@RON CR/LF  :  turn on RF circuit block   <P0 CR/LF  :  command accepted RON  RF Circuit Block Power Up Syntax   ROF{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  : command accepted   N0  : command error (Except 485 mode) Function   Turn on the power of RF circuit block and activates RF operation.   Use this command to activate RF circuit block after its power down state set by the ROF command.   The status when the modem is powered ON or reset, the RF circuit block is in the operation state.  Example   >@ROF CR/LF  :  turn off RF circuit block   <P0 CR/LF  :  command accepted    >@RON CR/LF  :  turn on RF circuit block   <P0 CR/LF  :  command accepted RST  Reset Syntax   RST{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to A22). Response   P0  :  command accepted   N0  :  command error (Except 485 mode) Function   Resets the modem to restore the power on state.   When any memory register is rewritten with REG command before issuing this command, the value rewritten becomes valid and active. Temporary settings like DAS and FRQ command become invalid and the memory register settings is loaded.
  56Example   >@RST CR/LF  :  reset the modem   <P0 CR/LF  :  command accepted Note When a serial communication parameter in memory register is changed with REG command, the response of “P0” returns according to the changed setting parameter, which may cause communication error. In such a case, set the communication parameter of the terminal equipment in correspondence with the new setting immediately after the issuance of RST command. SAS  Reference and Set Local Station Address Syntax   SAS (:set value){Local Station Address}      set value  :  new local station address (000 to 999)   Local Station Address   :  local station address for 485 mode (000 to 999). Response   xxx  :  current value (reference)   P0  :  connection established (setting)   N0  :  command error Function   References or sets the local station address.   The current value can be referenced by entering this command with no parameter. For setting, input the desired value to set.   The SAS command is for temporary local address and setting. To more permanently change the local station address value, use REG00. Example   >@SAS001 ↵  :  set the station address to 001   <P0 ↵  :  connection established   >@SAS ↵  :  reference the local station address   <001 ↵  :  output the current value (001) STS  Read Status Syntax   STS{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to 999). Response   xxxxxxxx  :  modem’s current status (x = 0 or 1)   N0  :  command error (Except 485 mode) Function Reads the modem status register. (Represented with an 8-bit binary number.)
 57X X X X X X X X Status Bit  Name 1  0 0  Connection  Connected  Disconnected 1  Reception  Disabled  Enabled 2  Output message Disabled  Enabled 3  Receive buffer  Data exist  Data empty 4  Transmit buffer  Data exist  Data empty 5  Reserved  -  - 6  Reserved  -  - 7  Reserved  -  - Figure 6–2:  Modem Status Bit Description Example   >@STS CR/LF  :  read the current status   <00001010 CR/LF  :  Received data exist, Output message enabled,         Reseption disabled ,Disconnected. TBN  Transmit Binary Data Syntax   TBN[destination address][message byte length]{Local Station Address}[message]   Destination address  :  address of the transmission (000 to A23)   Message byte length  :  message length (001 to 255)   Local Station Address     :  local station address for 485 mode (000 to A22).   Message byte    :  arbitrary binary data (255 or less) Response   P0  :  data transmission succeeded   P1  :  command accepted, data being transmitted   N0  :  command error (Except 485 mode)   N1  :  data transmission failed -- no response from destination station   N2  :  data transmission failed -- destination station is in the reception disabled state   N3  :  data transmission failed -- destination station cannot receive because its receive buffer is full Function   Transmits binary data in the packet transmission mode.   Any message length between 1 to 255 bytes is accepted.   The modem counts the number of message characters and transmits the message.   For broadcasting messages to multiple modems, set the destination address to 255. In this case, the modem retransmits the message the number of times of the Retransmission count plus 1, and then it will return “P0”.   In case the global addressing command is issued to plural modems connected by RS485 multi-dropping interface, the transmission stops when any modem outputs “P0”, “N2” or “N3” response to the RS485 line. Example   >TBN002005HELLO CR/LF  :  transmit “HELLO” from station 001 to station 002   <P1 CR/LF  :  data being transmitted   <P0 CR/LF  :  data transmission succeeded.   >@TBN003004MAIL CR/LF  :  retransmit “MAIL” from station 001 to station 003
  58  <P1 CR/LF  :  data being transmitted   <N1 CR/LF  :  transmission failed, no response from destination station Notes   Set the message length to 255 byte or less. The message length exceeding 255 byte will be command error. Message must be terminated with 2 byte (CR/LF) character, others will be command error. In broadcast transmission, the receiving result of the destination station cannot be confirmed at the sender side. TBR  Transmit Binary Data through Repeater Syntax   TBR [repeater address] [destination address] [message byte length]{Local Station Address}[message]  Repeater address    :  repeater address to pass through (000 to 999) Destination address   :  address of destination station (000 to A23)   Message byte length  :  message byte length (001 to 255)   Local Station Address     :  local station address for 485 mode (000 to A22).   Message byte    :  arbitrary binary data (255 or less) Response   P0  :  data transmission succeeded   P1  :  command accepted, data being transmitted   P2  :  data packet reached to repeater   N0  :  command error (Except 485 mode)   N1  :  data transmission failed -- no response from destination station   N2  :  data transmission failed -- destination station is in the reception disabled state   N3  :  data transmission failed -- destination station cannot receive because its receive buffer is full Function   In the packet transmission mode, transmits binary data through repeater. Any message length between 1 to 255 bytes is accepted.   The modem counts the number of message characters and transmits the message.   For broadcasting messages to multiple modems, set the destination address to 255. In this case, the modem retransmits the message the number of times of the Retransmission count plus 1, and then it will return “P0”.   In case the global addressing command is issued to plural modems connected by RS485 multi-dropping interface, the transmission stops when any modem outputs “P0”, “N2” or “N3” response to the RS485 line. Example   >TBR100002005HELLO CR/LF  :  transmit “HELLO” from station 001 to station 002   <P1 CR/LF  :  data being transmitted   <P2 CR/LF  :  data packet reached to repeater   <P0 CR/LF  :  data transmission succeeded   Notes   Set the message length to 255 byte or less. The message length exceeding 255 byte will be command error. Message must be terminated with 2 byte (CR/LF) character, others will be command error. In broadcast transmission, the receiving result of the destination station cannot be confirmed at the sender side.
 59TID  Display Local Station Serial ID Syntax   TID{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to 999). Response   XXXXXXXXXXXX   : displays the local serial ID code (12 digits)   N0  :  command error (Except 485 mode) Function Readout the local serial ID code of the modem and display it. This command corresponds to RID command. The local serial ID code consists of 12 digits; upper three digits are 0 and the lower 9 digits are the product serial number of the modem. Be noted the usage of RID command, the serial ID code of the packet received last is displayed. When packets are received from multiple stations and their data are stored in the receiving buffer, those data may not correspond to the serial ID code readout with the RID command. To use it more securely, it is recommended to readout the local serial ID code with the TID command and pad it (either all or a part of it) in the transmitting packet.   The serial ID code is no relation with ID code setting of REG04 and 05.  Example   >@TID CR/LF  :  requests the modem’s local serial ID code   < XXXXXXXXXXXX CR/LF :outputs the modem’s local serial ID code TXR  Transmit Text Data through Repeater Syntax   TXR  [repeater address] [destination address]{Local Station Address}[message]   repeater address    :  address of repeater to pass through (000 to 999)   destination address  :  address of destination station (000 to A23)   Local Station Address     :  local station address for 485 mode (000 to A22).   message     :  any text data (255 or less) Response   P0  :  data transmission succeeded   P1  :  command accepted, data being transmitted   P2  :  data packet reached to repeater   N0  :  command error (Except 485 mode)   N1  :  data transmission failed -- no response from the destination station   N2  :  data transmission failed -- destination station is in the reception disabled state   N3  :  data transmission failed -- destination station cannot receive because its receive buffer is full. Function   Transmits text data in the packet transmission mode through repeater.   Any message length between 1 to 255 bytes is accepted. The completion of data input is recognized by the terminator.
  60  For broadcasting messages to multiple modems, set the destination address to 255. In this case, the modem retransmits the message the number of times of the Retransmission count plus 1, and then it will return “P0”.   In case the global addressing command is issued to plural modems connected by RS485 multi-dropping interface, the transmission stops when any modem outputs “P0”, “N2” or “N3” response to the RS485 line. Example   >@TXR100002HELLO CR/LF :    transmits HELLO from station 001 to station 002 through repeater 100   <P1 CR/LF  :  data being transmitted   <P2 CR/LF  :  data packet reached to repeater   <P0 CR/LF :  data transmission succeeded Notes   Set the message length to 255 byte or less. The message length exceeding 255 byte will be command error. When the same character as the terminator (CR/LF) is contained in a message, the modem distinguishes it as the end of a command and ignore the subsequent data. In such a case, use TBR command.  In broadcast transmission, the receiving result of the destination station cannot be confirmed at the sender side. TXT  Transmit Text Data Syntax   TXT  [destination address]{Local Station Address}[message]   destination address  :  address of destination station (000 to A23)   Local Station Address     :  local station address for 485 mode (000 to A22).    message     :  any text data (255 or less) Response   P0  :  data transmission succeeded   P1  :  command accepted, data being transmitted   N0  :  command error (Except 485 mode)   N1  :  data transmission failed  - no response from the destination station   N2  :  data transmission failed - destination station is in the reception disabled state   N3  :  data transmission failed – destination station cannot receive because its receive buffer is full. Function   Transmits text data in the packet transmission mode.   Any message length between 1 to 255 bytes is accepted. The completion of data input is recognized by the terminator (CR/LF).   For broadcasting messages to multiple modems, set the destination address to 255. In this case, the modem will retransmit the message the number of times of the Retransmission count plus 1, and then it will return “P0”.   In case the global addressing command is issued to plural modems connected by RS485 multi-dropping interface, the transmission stops when any modem outputs “P0”, “N2” or “N3” response to the RS485 line. Example   >@TXT002HELLO CR/LF :    transmits HELLO from station 001 to station 002   <P1 CR/LF  :  data being transmitted
 61  <P0 CR/LF :  data transmission succeeded   >@TXT003MAIL CR/LF  :  transmits MAIL from station 001 to station 003   <P1 CR/LF  :  data being transmitted   <N1 CR/LF :  transmission failed. no response from destination station  Notes   Set the message length to 255 byte or less. The message length exceeding 255 byte will be command error. When the same character as the terminator (CR/LF) is contained in a message, the modem distinguishes it as the end of a command and ignores the subsequent data.  In such a case, use TBN command.  In broadcast transmission, the receiving result of the destination station cannot be confirmed at the sender side. VER  Reference Version Information Syntax   VER{Local Station Address}      Local Station Address   :  local station address for 485 mode (000 to 999).  Response   Program Version x.xxx  :Hardware system version   N0  :  command error (Except 485 mode) Function   Reads the modem’s hardware system version. Example   >@VER CR/LF  :  read the version information   <Ver 1.000 CR/LF  :  this modem firmware is version 1.000
  62
Futaba Corporation  Rev. 020323-01  7   APPENDIX    7 SECTION
  647.1  Conversion Circuit Examples of the level conversion circuit are shown as a reference, which is just for the confirmation of system operation. This example does not guarantee the operation under users’ actual operation environment. 7.1.1  RS-232C Level Converter Wire the control line when necessary. Tie down unused input pin(s) to GND and leave the 485ENB pin open.    Figure B–1:  RS-232C Level Conversion Circuit 7.1.2  RS422 Level Converter Wire the output terminator (100 ohm) of the RS422 line driver, the input terminator (100 ohm) of the receiver, the input pull-up (1k ohm) and the input pull-down (1k ohm), when necessary. Provide a surge absorber (e.g. Z2012 made by Ishizuka Denshi) when long RS422 line is used or there is much noisy environment, etc.  Figure B–2:  RS422 Level Conversion Circuit
Futaba Corporation  Rev. 020323-01 7.1.3  RS485 Level Converter Wire the terminator of the RS485 bus (100 ohm), the input pull-up (1k ohm) and the input pull-down (1k ohm), when necessary. When long RS485 line is used or there is much noise, provide the surge absorber (e.g. Z2012 made by Ishizuka Denshi) according to the situation.    Figure B–3:  RS485 Level Conversion Circuit  7.2  Specification of the Connectors (1) Serial Communication connector Connector:     MOLEX   53780-1490 (14 pins) Mating Plug:    MOLEX   51146-1400 (2) Antenna connector RF connector:  HIROSE  U.FL-R-SMT  The antenna connector is guaranteed for 30 times of plugging in/out. When plugging out the antenna connector, use the specially prepared tool of E.FL-LP-N, provided by HIROSE (HIROSE Product No. CL331-0441-9).
   667.3  Specification 7.3.1  Radio Characteristics Engineering standard  FCC Part 15.247 (no user license required) RF power output  6mW/MHz max. Modulation  Direct sequence spread spectrum Communication  scheme  Single communication  Frequency band  2403.328 to 2480.128 MHz Frequency channel   76 channels  (26 channels available for simultaneous communication in one area) Channel management  Fixed mode or group mode   Fixed mode: communication by fixing 1 arbitrary frequency from 76 freq.   Group mode: multi-access within a group of plural frequencies Data barer rate  51.9 kbps Oscillation  PLL synthesizer  Antenna diversity  2 branch reception diversity Service area  In an indoor environment: 60m radius, depending on the environment   In an outdoor environment: more than 300m (line-of-sight) RF connector  Hirose U.FL-R-SMT In/out of connector  30 times max. using E.FL-LP-N extractor (for exclusive use) 7.3.2  Communication Control Radio link control  Command control Error checking  CRC-CCITT (16 bit) Error handling  ARQ (Automatic Retransmission Request) Multi-access function  Connect on clearest channel from selected frequency group 7.3.3  Data Terminal Interface Physical interface  Molex 53780-1400 (14 pins)   Mating connector:  51146-1400 Interface specification  Serial communication   Input  CMOS level (5V tolerant with hysteresis)   Output  CMOS level Communication  Full-duplex or half-duplex system Synchronization  Asynchronous Transmit/receive buffer  Approx. 3 k bytes in total Baud rate  300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200 / 230400 bps Flow control  Hardware flow / Software flow Data length  7 or 8 bit Stop bit  1 or 2 bit  Parity  Even, odd, or none 7.3.4  Power Supplying Supply voltage  3.5 to 7.0Vdc Current consumption  110 mA or less in the active mode   35 mA or less in the RF stop mode   1mA or less in the stanby mode  7.3.5  Environmental Operating temperature  -10 to +60 ℃ Storage temperature  -20 to +70 ℃ Operating humidity  90%RH max. (no condensation)  Storage humidity  90%RH max. (no condensation) Vibration resistance  JIS-C-0040 (50m/s2, 10 to 150 Hz, 15 cycles)
Futaba Corporation  Rev. 020323-01 Shock resistance  JIS-C-0041 (500m/s2)   (JIS specification is Japanese Industry Standard) 7.3.6  Miscellaneous Memory register  Rewritable times:  approx. 1 million times Case  Ni plated steel plate Outer dimensions  30 (W)×50(D)×8(H)mm Weight  Aprox. 14g  †  Operating distances depend on the conditions such as obstructions and electrical interference. Under ideal, line-of-sight conditions, reliable operating distances greater than specified may be achieved. Optional, directional antennas can significantly increase the operating range. *  Specifications and appearance are subject to change without prior notice.
   687.4  Dimensions 7.4.1  FDL01TU                           7.4.2  Communication Cable
Futaba Corporation  Rev. 020323-01                    Futaba Corporation Radio Control Equipment Group  1080 Yabutsuka Chosei Chiba, 299-4395 JAPAN Tel: +81 (475) 32-6173,  Fax:  +81(475)  32-6179 Internet: www.futaba.co.jp    In the United States Futaba Corporation of America Industrial Radio Control Department  1605 Penny Lane Schaumburg, IL  60173 Tel: (847) 884-1444, Fax: (847) 884-1635 Internet: www.futaba.com   In the Europe Pending.

Navigation menu