Hardware Manual for the
HE500TIU050
HE500TIU100
IC300TIU101
HE500TIU102
HE500TIU103
HE500TIU110
IC300TIU111
HE500TIU112
HE500TIU113
HE500TIU200
IC300TIU201
HE500TIU202
HE500TIU203
And SmartStack Modules

Operator Station
Hardware Manual

06 April 2000

GFK-1819

PREFACE

06 Apr 2000

PAGE 3
GFK-1819

Warnings, Cautions, and Notes
as Used in this Publication
Warning
Warning notices are used in this publication to emphasize that
hazardous voltages, currents, temperatures or other conditions that
could cause personal injury exist in this equipment or may be
associated with its use.
In situations where inattention could cause either personal injury
or damage to equipment, a Warning notice is used.

Caution
Caution notices are used where equipment might be damaged if care is
not taken.

Note
Notes merely call attention to information that is especially significant to
understanding and operating the equipment.
This document is based on information available at the time of its publication. While
efforts have been made to be accurate, the information contained herein does not
purport to cover all details or variations in hardware or software, nor to provide for
every possible contingency in connection with installation, operation, or maintenance.
Features may be described herein which are not present in all hardware and software
systems. GE Fanuc Automation assumes no obligation of notice to holders of this document with
respect to changes subsequently made.
GE Fanuc Automation makes no representations or warranty, expressed, implied, or
statutory with respect to, and assumes no responsibility for the accuracy, completeness,
sufficiency, or usefulness of the information contained herein. No warranties of
merchantability or fitness for purpose shall apply.
The following are trademarks of GE Fanuc Automation North America, Inc.
Alarm Master
CIMPLICITY
CIMPLICITY 90 – ADS
CIMPLICITY Power TRAC

CIMSTAR
GEnet
Genius
Genius PowerTRAC

Helpmate
Logicmaster
ModelMaster
ProLoop

PROMACRO
Series One
Series Three
Series Five

The following are trademarks of Horner Electric, APG, LLC.
Cscape

SmartStack

CsCAN

Copyright 2000 GE Fanuc Automation North America, Inc.
All Rights Reserved

Series Six
Series 90
VuMaster
Workmaster

PAGE 4
GFK-1819

06 Apr 2000

PREFACE

ABOUT PROGRAMMING EXAMPLES
Any example programs and program segments in this manual or provided on accompanying diskettes are
included solely for illustrative purposes. Due to the many variables and requirements associated with any
particular installation, GE Fanuc cannot assume responsibility or liability for actual use based on the
examples and diagrams. It is the sole responsibility of the system designer utilising the Operator Station
to appropriately design the end system, to appropriately integrate the Operator Station and to make
safety provisions for the end equipment as is usual and customary in industrial applications as defined in
any codes or standards which apply.

NOTE: The programming examples shown in this manual are illustrative
only. Proper machine operation is the sole responsibility of the system
integrator.
DECLARATION OF EMC CONFORMITY
Manufacturer's Name:
Manufacturer's Address:

Horner Ireland Ltd.
Unit 1, Centrepoint, Centre Park Road, Cork, Ireland

Declares that the products

Models: HE500TIU050, HE500TIU100, IC300TIU101, HE500TIU102,
HE500TIU110, IC300TIU111, HE500TIU200, IC300TIU201 and
HE500TIU202.
Conforms to the following EMC standards:
EMC:

EN 55 022, Radiated and Conducted Emissions
EN 50 082-1, RF, EFT/EFB, ESD Immunity

Supplementary Information:
The above conformity only relates to the products in a stand-alone capacity. The products are used as
part of a system and are therefore classified as a component. As a component, the products are
prohibited by EC regulations to carry a CE Mark for EMC conformity. Static discharge tests only apply to
normal operation of the keyboards via the front panel. We would stress that the use of our products
within your system, while helping to ensure compliance of your system to the same directives, do not
necessarily guarantee that compliance will be achieved. We would also like to point out that the
interpretation of the law concerning CE marking and its application to sub-assemblies and components is
open to interpretation.
Date: 31 Mar 1999

PREFACE

06 Apr 2000

PAGE 5
GFK-1819

TABLE OF CONTENTS
ABOUT PROGRAMMING EXAMPLES ....................................................................................................4
DECLARATION OF EMC CONFORMITY.................................................................................................4
CHAPTER 1: INTRODUCTION ................................................................................................................7
1.1
Scope ....................................................................................................................................... 7
1.2
Equipment Needed ................................................................................................................... 9
1.3
Technical Specifications...........................................................................................................11
1.4
Upgrade Revision Software & Firmware ...................................................................................12
1.4.1
Scope ...............................................................................................................................12
1.4.2
Software Upgrade .............................................................................................................12
1.4.3
Firmware Upgrade ............................................................................................................12
CHAPTER 2: TIU050 .............................................................................................................................15
2.1
Scope ......................................................................................................................................15
2.2
TIU050 Button Selection Actions ..............................................................................................15
2.3
TIU050 Contrast Adjustment ....................................................................................................15
2.4
TIU050 Ports............................................................................................................................16
2.4.1
TIU050 Configuration of the RS-485 Port ..........................................................................16
2.5
TIU050 Dimensions..................................................................................................................17
CHAPTER 3: TIU100/101/102/103 .........................................................................................................19
3.1
Scope ......................................................................................................................................19
3.2
TIU10X Button Selection Actions..............................................................................................19
3.3
TIU10X Contrast Adjustment ....................................................................................................19
3.4
TIUX Rear View .......................................................................................................................20
3.5
TIU100 Ports............................................................................................................................20
3.5.1
TIU10X Configuration of the RS-485 Port ..........................................................................21
3.6
TIU10X Dimensions .................................................................................................................22
CHAPTER 4: TIU110/111/112/113 .........................................................................................................23
4.1
Scope ......................................................................................................................................23
4.2
TIU11X Button Selection Actions .............................................................................................23
4.3
TIU11X Contrast Adjustment ....................................................................................................23
4.4
TIU11X Rear View ...................................................................................................................24
4.5
TIU110 Ports............................................................................................................................24
4.5.1
TIU11X Configuration of the RS-485 Port ..........................................................................26
4.6
TIU11X Dimensions .................................................................................................................26
CHAPTER 5: TIU200/201/202/203 .........................................................................................................27
5.1
Scope ......................................................................................................................................27
5.2
TIU20X Button Selection Actions..............................................................................................27
5.3
TIU20X Contrast Adjustment ....................................................................................................28
5.4
TIU20X Rear View ...................................................................................................................28
5.5
TIU20X Ports ...........................................................................................................................28
5.5.1
TIU20X Configuration of the RS-485 Port ..........................................................................30
5.6
TIU20X Dimensions .................................................................................................................30
CHAPTER 6: COMMUNICATIONS ........................................................................................................31
6.1
PC to Operator Station Communications ..................................................................................31
6.2
Automation Equipment (AE) Communications Connections ......................................................31
6.2.1
Recommended Automation Equipment Communication Cables.........................................31
6.3
RS-232 Connection..................................................................................................................31
6.4
RS-422/485 Four-Wire .............................................................................................................32
6.5
RS-485 Two-Wire ....................................................................................................................33
6.6
Current Loop............................................................................................................................34
CHAPTER 7: GETTING STARTED ........................................................................................................35
7.1
Self-Test ..................................................................................................................................35
7.1.1
Contrast Band ...................................................................................................................35

PAGE 6
GFK-1819

06 Apr 2000

PREFACE

7.1.2
Display Test ......................................................................................................................35
7.1.3
Keyboard Test...................................................................................................................35
7.1.4
RAM Test..........................................................................................................................35
7.1.5
Serial Loop-back Tests......................................................................................................35
7.2
Updating the Protocol...............................................................................................................36
7.3
Updating the Operating System................................................................................................36
CHAPTER 8 : NETWORKS....................................................................................................................37
8.1
Scope ......................................................................................................................................37
8.2
Controller Area Network (CAN) Overview .................................................................................37
8.2.1
CAN Features ...................................................................................................................37
8.3
CsCAN Network Overview .......................................................................................................37
8.3.1
CsCAN Network Features .................................................................................................37
8.3.2
CsCAN Network Operation................................................................................................37
8.4
DeviceNet Overview.................................................................................................................38
8.4.1
DeviceNet Features...........................................................................................................38
8.4.2
DeviceNet Protocol ...........................................................................................................39
8.4.3
DeviceNet Operation .........................................................................................................39
8.5
CAN Wiring Rules ....................................................................................................................40
8.6
Profibus ...................................................................................................................................41
8.6.1
Profibus Wiring..................................................................................................................41
CHAPTER 9: SMARTSTACK  .............................................................................................................43
9.1
Scope ......................................................................................................................................43
9.2
Installing and Removing a SmartStack Module.........................................................................43
9.2.1
Installing SmartStack Modules...........................................................................................43
9.2.2
Removing SmartStack Modules.........................................................................................43

CH.1: INTRODUCTION

06 Apr 2000

PAGE 7
GFK-1819

CHAPTER 1: INTRODUCTION
1.1
Scope
The Operator Station (TIU050/10X/11X/20X) is an Operator Station (OS) that provides extensive
monitoring and control in an extremely small package. The Operator Station “OS” product line offers four
distinct categories of products as described in Table 1.1.
Table 1.1 – Operator Station (OS) Product Line
Note: Only IC300 TIU101 / IC300 TIU111 IC300 TIU201 models are available through GE
Fanuc Channels.
Model
Description
TIU050: Text Only
HE500TIU050-001
2 lines x 20 characters.
HE500TIU050-002
2 lines x 20 characters with Real Time Clock.
TIU10x: Text / Semi-Graphics
HE500TIU100-01
8 Lines x 20 Characters plus 128 x 64 pixels.
HE500TIU100-02
8 Lines x 20 Characters plus 128 x 64 pixels with Real Time Clock.
HE500TIU100-03
8 Lines x 20 Characters plus 128 x 64 pixels with Current Loop.
HE500TIU100-04
8 Lines x 20 Characters plus 128 x 64 pixels with Current Loop and Real
Time Clock.
HE500TIU100-05
8 Lines x 20 Characters plus 128 x 64 pixels with Stud Type Metalwork
HE500TIU100-06
8 Lines x 20 Characters plus 128 x 64 pixels with wide temperature
display.
HE500TIU100-07
8 Lines x 20 Characters plus 128 x 64 pixels with Bezel
HE500TIU100-09
8 Lines x 20 Characters plus 128 x 64 pixels with no metal and dill
connectors
IC300TIU101-01
8 Lines x 20 Characters plus 128 x 64 pixels with CsCAN Network.
8 Lines x 20 Characters plus 128 x 64 pixels with CsCAN Network and
IC300TIU101-02
Real Time Clock.
HE500TIU102-01
8 Lines x 20 Characters plus 128 x 64 pixels with a Profibus Network.
8 Lines x 20 Characters plus 128 x 64 pixels with Profibus Network
HE500TIU102-02
and Real Time Clock.
HE500TIU103-01
8 Lines x 20 Characters plus 128 x 64 pixels with DeviceNet
Networks.
HE500TIU103-02
8 Lines x 20 Characters plus 128 x 64 pixels with DeviceNet
Networks and Real Time Clock.
TIU11X: Text / Semi Graphics with Numeric Keypad
HE500TIU110-01
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad.
HE500TIU110-02
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
Real Time Clock.
HE500TIU110-03
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
Current Loop.
HE500TIU110-04
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
Current Loop and Real Time Clock.
HE500TIU110-05
8 Lines x 20 Characters plus 128 x 64 pixels with Stud Type Metalwork.
HE500TIU110-06
8 Lines x 20 Characters plus 128 x 64 pixels with wide temperature
display.
HE500TIU110-07
8 Lines x 20 Characters plus 128 x 64 pixels with Bezel
HE500TIU110-09
8 Lines x 20 Characters plus 128 x 64 pixels with no metal and dill
connectors
IC300TIU111-01
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
CsCAN Network.
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
IC300TIU111-02
CsCAN Network and Real Time Clock.
HE500TIU112-01
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
Profibus Network.
HE500TIU112-02
8 Lines x 20 Characters plus 128 x 64 pixels plus a Numeric keypad with
Profibus Network and Real Time Clock.

PAGE 8
GFK-1819

06 Apr 2000

CH. 1: INTRODUCTION

HE500TIU113-01

8 Lines x 20 Characters plus 128 x 64 pixels with DeviceNet Network.
8 Lines x 20 Characters plus 128 x 64 pixels with DeviceNet Network
HE500TIU113-02
and Real Time Clock.
TIU20X: Text / Full Graphics with Numeric / Function Keypad
HE500TIU200
16 Lines x 40 Characters plus 240 x 128 pixels plus a Numeric keypad /
Function keypad. Optional SmartStack I/O.
IC300TIU201
16 Lines x 40 Characters plus 240 x 128 pixels plus a Numeric keypad /
Function keypad. Optional SmartStack I/O. Can be used with CsCAN
Network.
HE500TIU202
16 Lines x 40 Characters plus 240 x 128 pixels plus a Numeric keypad /
Function keypad. Optional SmartStack I/O. Can be used in a Profibus
Network.
HE500TIU203
16 Lines x 40 Characters plus 240 x 128 pixels plus a Numeric keypad /
Function keypad. Optional SmartStack I/O. Can be used with
DeviceNet Network.

The front panel of the OS has a bright and clear display (LCD with adjustable back lit) and easy-to-use
push buttons. On the back panel are communication ports for connection to automation equipment
(programmable logic controller, drive, weighing equipment or other equipment) and a PC (IBM or
compatible computer). Also located on the back panel or end of the back panel depending on the model,
the OS has clearly displayed features such as power input, PC and PLC port, Tx and Rx LEDs. Also,
depending on the model, a network port is provided for connection to whichever OS network you have
chosen.
The OS supports a variety of protocols. Various protocols can be downloaded through the PC port and
stored in the unit’s flash memory. The operating system can also be downloaded through the PC port.
The OS range supports 3 network options. CsCAN (TIUXX1) and Device (TIUXX3) and Profibus with the
TIUXX2 range.

Software Cbreeze
Programming Port
RS232
Communication Port
232/485
Flash Ram
Memory Upgrade
Words SRam
Memory Upgrade
Total Pages
Characters per Page
Graphics pixels
Data fields/page
No. of Text tables
Text table size Rows
& Columns
Recipe Memory
Recipes
Editable Fonts
Scaling Range
checking
Tending
Graphing
Editable Graphics

HE500TIU050
Included
Standard

HE500TIU10X
Included
Standard

HE500TIU11X
Included
Standard

HE500TIU20X
Included
Standard

1

1

1

1

64 K Words
No
32 K Bytes
No
300
2x20
Text Only
8
249
No

256 K Words
No
128 K Bytes
No
300
8x20
128 x 64
8
249
No

256 K Words
No
128 K Bytes
No
300
8x20
128 x 64
8
249
No

512 K Words
1 Meg
128 K Bytes
512 K Bytes
300
16x40
240 x 128
24
249
256

0
No
No
Standard

64K
Standard
Standard
Standard

64K
Standard
Standard
Standard

64K
Standard
Standard
Standard

No
No
No

Standard
Standard
No

Standard
Standard
No

Standard
Standard
Standard

CH.1: INTRODUCTION

Animated Bitmaps
Alarms and Status
pages
Numeric keys
System keys
Function keys *
LED's
SmartStack option
Battery Back Ram +
Real Time Clock
Comprehensive
Math's Facilities
Day & Time
Scheduling,
Background Task
Internal Registers
Operating
Temperature C°
Storage Temperature
C°
Humidity Non
Condensing Storage
Environmental
NEMA4 / IP65
Y2K Certified CE
Approved
Size -Width ,Height
,Depth mm
Cut-out -- Width ,
Height mm
Screen dimensions
mm
Input Voltage Range
Weight (grams)
NetworkDeviceNet, CsCAN
Data xfer from
Automated device
via network Profibus

06 Apr 2000

PAGE 9
GFK-1819

No
Standard

No
Standard

No
Standard

Standard
Standard

Standard
4
10
No
No
Optional

No
4
No
No
No
Optional

Standard
4
12
No
No
Optional

Standard
4
18
10
Standard
Standard

No

1024 lines

1024 lines

1024 lines

No

Standard

Standard

Standard

No
0 to 50

1024 %R
0 to 50

1024 %R
0 to 50

1024 %R
0 to 50

-10 to 70

-10 to 70

-10 to 70

-10 to 70

10-90%

10-90%

10-90%

10-90%

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

180 X 120 X 60

121 X 105 X 38

172 X 105 X 38

281 X 192 X 58

151 X 89

100 X 85

153 X 85

242 X 158

80 X 17

70 X 38

70 X 38

130 X 75

9-35 Vdc
325
No

9-35 Vdc
370
Optional

9-35 Vdc
450
Optional

9-35 Vdc
1855
Optional

No

Optional

Optional

Optional

* System keys can be programmed to be function keys at specific times in the project. See Function keys in
CBREEZE Software Manual MAN0023
** The TIU100/110 is available with two non-standard features: 20mA current loop communication and a
real-time clock (RTC). Both can be ordered at the time of purchase. The current loop can be re-fit by the
user later. The RTC requires factor re-fit. The TIU050 is only available with the real-time clock option.
*** The TIU20X provides for the display of both text and full graphics and has a Numeric/Function
Keypad. It also allows the use of a wide range of SmartStack I/O options.
1.2
Equipment Needed
1. The current version of CBREEZE software install on a PC running Windows 95, Windows 98 or
Windows NT.
2. TIU050/10X/11X/20X Interface Unit.

PAGE 10
GFK-1819

06 Apr 2000

CH. 1: INTRODUCTION

3. PC to TIU Programming Cable HE693CBL232 or equivalent See Chapter on Communications

CH.1: INTRODUCTION

1.3

06 Apr 2000

PAGE 11
GFK-1819

Technical Specifications
Table 1.2 – Technical Specifications

Parameter
Input voltage (VI)
Typical power consumption
TIU050
TIU10X
TIU11X
TIU20X
Inrush input current
Operating temperature
TIU050
TIU10X
TIU10X-6
TIU11X
TIU11X-6
TIU20XA
TIU20XB or higher

Conditions

130
130
130
350

VI = 24VDC for 4ms

260

(non-condensing)

IP rating

Max.
32

Units
VDC

mA

mA
50
50
60
50
60
45
50

°C

-20

70

°C

10

90

%

350
400
500
1900

g

0
0
-10
0
-10
0
0

320
370
470
1870

Dimensions
TIU050
TIU10X
TIU11X
TIU20X
Cable Lengths
RS-232
RS-485

Typical
24

VI = 24VDC
VI = 24VDC
VI = 24VDC
VI = 24VDC

Storage temperature
Relative Humidity
Weight
TIU050
TIU10X
TIU11X
TIU20X

Min.
10

179 x 111 x 60
121 x 105 x 38
172 x 105 x 38
282 x 194 x 62

mm

†

1

15
1500

m

NEMA 4-12/IP65
EN 55 022, Radiated and Conducted Emissions
EMC Conformance
EN 61000-4-3, Radiated and Conducted RF Immunity
ENV 50144
†
Cables beyond the maximum recommended length may create communication problems. Both ends of
an RS-485 network must be properly terminated at 120Ω and grounded.

PAGE 12
GFK-1819

1.4

06 Apr 2000

CH. 1: INTRODUCTION

Upgrade Revision Software & Firmware

1.4.1 Scope
To avail of any new features that are included in this new release on units that were purchased previous
to this release, both software and firmware require updating by the user. Any new unit will be set-up for
the latest version released.
1.4.2 Software Upgrade
To update the software requires that the user install the new version of software from the installation CD.
You may install the new software over any previous version installed. See section 1.4 Software
Installation Instructions.
To update existing projects simple open the project from the newly installed version of the software. Once
the project is saved to disk the update is complete. For backup reasons we recommend that you save the
new version of your project in a different location or under a different file name.
1.4.3 Firmware Upgrade
The following steps assume that a project or configuration is loaded to the Operator Station and that the
user is running the latest version of software.
a)
b)
c)
d)

Upload the project/configuration from the unit.
If a customised character set is loaded to the unit then upload the character set also.
Choose Automation Device from main menu Configure/Communication Settings.
From File menu choose Update TIU Operating System. (See Updating Operating System for more
details).
e) From File menu choose Update TIU Protocol. If you are updating from firmware version 2.00 or later
then you just have to update to the latest protocol file. However if you are updating from firmware
version 1.24 or earlier you most update to a Upgrade.1xx protocol file first, then update to the latest
firmware revision. See Note. (See updating protocol for further information).
f) Choose Download Character Sets to TIU from File menu.
g) Choose Download Project to TIU from File menu.
Note: When updating the protocol file the screen may go blank after the protocol file is complete.
Continue with the procedure as described and the display will recover.

CH.1: INTRODUCTION

06 Apr 2000

PAGE 13
GFK-1819

PAGE 14
GFK-1819

06 Apr 2000

NOTES

CH. 1: INTRODUCTION

CH.2: TIU050

06 Apr 2000

PAGE 15
GFK-1819

CHAPTER 2: TIU050
2.1
Scope
The TIU050 is a 2 line text only display terminal. The hardware description is detailed in this chapter.
Alphanumeric
Keypad

PAUSE Key

+(7,8

Programmable
Function Keys

UP Key
DOWN Key

1Q Z _

2 AB C

3 DE F

4 GH I

5 JK L

F1

F2

F3

F4

F5

6 MNO

7 PR S

8 TUV

9 WXY

0

F6

F7

F8

F9

F 10

+

-

ENTER Key

Figure 2.1 – Front View of TIU050
2.2
a)
b)
c)
d)
e)
f)
g)

TIU050 Button Selection Actions
PAUSE key selects data for editing OR exits from data editing.
PAUSE & DOWN keys pressed together, enters sub menu pages.
PAUSE & UP keys pressed together, exits sub menus to the parent menu pages.
UP key selects the previous menu page, sub menu page, alarms, and increments data
DOWN key selects the next menu page, sub menu page, alarms and also decrements data.
ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms.
ALPHANUMERIC KEYPAD and FUNCTION KEYS can be used to enter data or can be used to
preform some pre-programmed action.

2.3
TIU050 Contrast Adjustment
On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to
adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit
using the UP or DOWN key and press Enter when done. Do the same for the upper limit.
WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting
where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max
FE).

PAGE 16
GFK-1819

2.4

06 Apr 2000

CH. 2: TIU050

TIU050 Ports
Pin 1

TIU050 8-pin Terminal Block

Pin 8

Figure 2.2 – Automation Equipment Serial Port

2.4.1

TIU050 Configuration of the RS-485 Port

OFF
ON

SW 1
Figure 2.3 – Power Connector
Powered by +24VDC and Ground.

Figure 2.4 – Configuration Bank

The configuration bank (shown in Figure 2.5) sets the parameters of the RS-485 port as described in
Table 2.1.
Table 2.1 – Configuration Bank
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120Ω termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Switch 1

CH.2: TIU050

06 Apr 2000

PAGE 17
GFK-1819

Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON,
a 120Ω resistance is placed across the bus. This is only used if the TIU050/100/110 is the last device at
either end of the bus.
2.5

TIU050 Dimensions

5.95” [151m m]

+ 0 .0 2

+ 0 .5

3.27”-0 .0 0 [83-0 .0 mm]
UP TO 0.04”[1mm] CORNER
RADIUS IS ACCEPTABLE

TIU050 CUTOUT DETAILS
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE

Figure 2.5 – TIU050 Cutout

PAGE 18
GFK-1819

06 Apr 2000

NOTES

CH. 2: TIU050

CH. 3: TIU100/101/102/103

06 Apr 2000

PAGE 19
GFK-1819

CHAPTER 3: TIU100/101/102/103
3.1
Scope
The TIU10X 128 x 64 pixel display, which allows for some graphics and various fonts to be displayed. .
The hardware description is detailed in this chapter.

PAUSE Key

ENTER Key

UP Key

DOWN Key

Figure 3.1 - Front View of TIU100
3.2
a)
b)
c)
d)
e)
f)

TIU10X Button Selection Actions
PAUSE key selects data for editing OR exits from data editing.
PAUSE & DOWN keys pressed together, enters sub menu pages.
PAUSE & UP keys pressed together, exits sub menus to the parent menu pages.
UP key selects the previous menu page, sub menu page, alarms, and increments data
DOWN key selects the next menu page, sub menu page, alarms and also decrements data.
ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms.

3.3
TIU10X Contrast Adjustment
On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to
adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit
using the UP or DOWN key and press Enter when done. Do the same for the upper limit.
WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting
where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max
FE).

PAGE 20
GFK-1819

3.4

06 Apr 2000

CH.3: TIU100/101/102/103

TIUX Rear View
P in 1

P in 1

To P C
R x P in 2
Tx P in 3
0 V P in 5

Figure 3.2 – Rear View of TIU100/101/102
3.5

TIU100 Ports
TIU100 13-pin Terminal Block
Pin 1

Pin 13

CH. 3: TIU100/101/102/103

06 Apr 2000

PAGE 21
GFK-1819

Rx

Rx

Tx

Tx

S erial P o rt
Figure 3.4 – Automation
Equipment Port Receive &
Transmit LEDs
The LED’s flash when the TIU10X
is communicating with the AE.

P C P o rt
Figure 3.5 – PC Port Receive &
Transmit LEDs
The LED’s flash when the PC is
communicating with the TIU10X

Figure 3.3 – Automation Equipment Serial Port
3.5.1 TIU10X Configuration of the RS-485 Port
The configuration bank (shown in Figure 3.8) sets the parameters of the RS-485 port as described in
Table 3.1.
Table 3.1 – Configuration Bank
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120Ω termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Switch 1

Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.

PAGE 22
GFK-1819

06 Apr 2000

CH.3: TIU100/101/102/103

OFF
ON

SW 1
Figure 3.6 – Power Connector
Powered by +24VDC and Ground.

Figure 3.7 – Configuration Bank

Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON,
a 120Ω resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last
device at either end of the bus.
3.6

TIU10X Dimensions

+ 0 .0 2

+ 0 .5

3.94”-0 .0 0 [100-0 .0 mm]

+ 0 .0 2

+ 0 .5

3.27”-0 .0 0 [83-0 .0 mm]

UP TO 0.04”[1mm] CORNER
RADIUS IS ACCEPTABLE

TIU10X CUTOUT DETAILS
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE

Figure 3.8 – TIU10X Cutout

CH. 4: TIU110/111/112/113

06 Apr 2000

PAGE 23
GFK-1819

CHAPTER 4: TIU110/111/112/113
4.1
Scope
The TIU11X 128 x 64 pixel display, which allows for some graphics and various fonts to be displayed.
The hardware description is detailed in this chapter.

Q Z_

ABC

DEF

1

2

3

GHI

JK L

M NO

4

5

6

PRS

TU V

W XY

7

8

9

Numeric Keypad
Programmable
Function Keys

.

D el

+ /-

Figure 4.1 – Front View of TIU110
4.2
a)
b)
c)
d)
e)
f)
g)

TIU11X Button Selection Actions
PAUSE key selects data for editing OR exits from data editing.
PAUSE & DOWN keys pressed together, enters sub menu pages.
PAUSE & UP keys pressed together, exits sub menus to the parent menu pages.
UP key selects the previous menu page, sub menu page, alarms, and increments data
DOWN key selects the next menu page, sub menu page, alarms and also decrements data.
ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms.
ALPHANUMERIC KEYPAD and PROGRAMMABLE KEYS can be used to enter data or can be
used to preform some pre-programmed action.

4.3
TIU11X Contrast Adjustment
On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to
adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit
using the UP or DOWN key and press Enter when done. Do the same for the upper limit.
WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting
where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max
FE).

PAGE 24
GFK-1819

4.4

06 Apr 2000

CH. 4: TIU110/111/112/113

TIU11X Rear View
P in 1

P in 1

To P C
R x P in 2
Tx P in 3
0 V P in 5

Figure 4.2 – Rear View of TIU11X
4.5

TIU110 Ports
TIU110 13-pin Terminal Block
Pin 1

Pin 13

Figure 4.3 – Automation Equipment Serial Port

CH. 4: TIU110/111/112/113

06 Apr 2000

PAGE 25
GFK-1819

Rx

Rx

Tx

Tx

S erial P o rt
Figure 4.4 – Automation
Equipment Port Receive &
Transmit LEDs
The LED’s flash when the TIU110
is communicating with the AE.

P C P o rt
Figure 4.5 – PC Port Receive &
Transmit LEDs
The LED’s flash when the PC is
communicating with the TIU110

OFF
ON

SW 1
Figure 4.6 – Power Connector
Powered by +24VDC and Ground.

Figure 4.7 – Configuration Bank

PAGE 26
GFK-1819

4.5.1

06 Apr 2000

CH. 4: TIU110/111/112/113

TIU11X Configuration of the RS-485 Port

The configuration bank (shown in Figure 4.8) sets the parameters of the RS-485 port as described in
Table 4.1.
Table 4.1 – Configuration Bank
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120Ω termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Switch 1

Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON,
a 120Ω resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last
device at either end of the bus.
4.6

TIU11X Dimensions

5.95” [151m m]

+ 0 .0 2

+ 0 .5

3.27”-0 .0 0 [83-0 .0 mm]
UP TO 0.04”[1mm] CORNER
RADIUS IS ACCEPTABLE

TIU11X CUTOUT DETAILS
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE

Figure 4.8 – TIU11X Cutout

CH. 5: TIU200/201/202/203

06 Apr 2000

PAGE 27
GFK-1819

CHAPTER 5: TIU200/201/202/203
5.1
Scope
The TIU20X is 240 x 128 pixel display which allows for full graphic screen. The hardware description is
cover under the following chapter

QZ

ABC

DEF

1

2

3

GHI

JKL

M NO

4

5

6

PRS

TU V

W XY

7

8

9

.

0

S PA C E

D el

0

+/NEX T

F9

F10

F 11

F12

F13

F14

F15

F16

F17

F18

Figure 5.1 – Front View of TIU20X
5.2
a)
b)
c)
d)
e)
f)
g)
h)

TIU20X Button Selection Actions
PAUSE key selects data for editing OR exits from data editing.
PAUSE & DOWN keys pressed together, enters sub menu pages.
PAUSE & UP keys pressed together, exits sub menus to the parent menu pages.
UP key selects the previous menu page, sub menu page, alarms, and increments data
DOWN key selects the next menu page, sub menu page, alarms and also decrements data.
ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms.
ALPHANUMERIC KEYPAD can be used to enter data
PROGRAMMABLE KEYS can be used to preform some pre-programmed action.

PAGE 28
GFK-1819

06 Apr 2000

CH. 5: TIU200/201/202/203

5.3
TIU20X Contrast Adjustment
On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to
adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit
using the UP or DOWN key and press Enter when done. Do the same for the upper limit.
WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting
where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max
FE).
5.4

TIU20X Rear View

6HULDO 1R
0RGHO 1R

Figure 5.2 – Rear View of TIU20X
5.5

TIU20X Ports
Pin 1

TIU20X 8-pin Terminal Block

Pin 8

Figure 5.3 Automated Equipment Serial Port

CH. 5: TIU200/201/202/203

06 Apr 2000

PAGE 29
GFK-1819

Rx

Rx

Tx

Tx

S erial P o rt
Figure 5.4 – Automation
Equipment Port Receive &
Transmit LEDs
The LED’s flash when the TIU20X
is communicating with the AE.

P C P o rt
Figure 5.5 – PC Port Receive &
Transmit LEDs
The LED’s flash when the PC is
communicating with the TIU20X

OFF
ON

SW 1
Figure 5.7 – Configuration Bank

Figure 5.6 – Power Connector
Powered by +24VDC and Ground.

PAGE 30
GFK-1819

5.5.1

06 Apr 2000

CH. 5: TIU200/201/202/203

TIU20X Configuration of the RS-485 Port

The configuration bank (shown in Figure 2.23) sets the parameters of the RS-485 port as described in
Table 5.1.
Table 5.1 – Configuration Bank
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120Ω termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Switch 1

Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON,
a 120Ω resistance is placed across the bus. This should only be used if the TIU050/10X/11X/20X is the
last device at either end of the bus.
5.6

TIU20X Dimensions

+0.02
µ
-0.00




PP@

+0.02
µ
-0.00

> PP@

+0.5
>
-0.0

83 72 µ &RUQHU >5$',86 ,6 $&&(37$%/(PP@

7,8; &87287 '(7$,/6
72/(5$1&(6 $5(  µ >PP@ 81/(66 67$7(' 27+(5:,6(
Figure 5.8 – TIU20X Cutout

CH. 6: COMMUNICATIONS

06 Apr 2000

PAGE 31
GFK-1819

CHAPTER 6: COMMUNICATIONS
6.1
PC to Operator Station Communications
The serial pin connections for transmit (Tx), receive (Rx) and ground are displayed below.

1

TIU 1X X
2 Tx
3 Rx

PC
2 Rx
3 Tx

5

5 0V

5 0V

Figure 6.1 – PC Programming Serial Port & Connection Detail
6.2
Automation Equipment (AE) Communications Connections
6.2.1 Recommended Automation Equipment Communication Cables
Horner Electric recommends the following cables for automation equipment communication:
Belden No. 8105, 9807 or 9832 – General Purpose
Belden No. 8165 – Heavy Noise Environment
6.3

RS-232 Connection

TIU110/100
(S ection of 13-pin
Term inal B lock)
RS232

R S 232

Tx D 6
0V 7
R xD 8

AE
Rx
0V
Tx

TIU050/101/102/103/111/112/113/20X
(S ection of 8-pin
Term inal B lock)
RS232

R S 232

Tx D 5
0V 6
R xD 7

Figure 6.2 – RS-232 Connection

AE
Rx
0V
Tx

PAGE 32
GFK-1819

6.4

06 Apr 2000

CH. 6: COMMUNICATIONS

RS-422/485 Four-Wire

TIU110/100
(Section o f 13-pin
Terminal Block)
RS422 /48 5
RS232

R S 4 22 /48 5
(4 -w ire )

Tx +
Tx Rx+
RxTx D
0V
RxD

2
3
4
5

Autom ated Equipm ent
RS422/485 Connections
See Note Below

6
7
8
0.1uF Ceramic

TIU050/101/102/103/111/112/113/20X
(Section o f 8-pin
Terminal Block)
RS422 /48 5
RS232

R S 4 22 /48 5
(4 -w ire )

Tx +
Tx Rx+
RxTx D
0V
RxD

1
2
3
4

Autom ated Equipm ent
RS422/485 Connections
See Note Below

5
6
7
0.1uF Ceramic

Figure 6.2 – RS-422/485 Four-Wire
Note: The descriptions used by different manufacturers for RS-422/485 connections vary. Please refer to
the automation equipment manufacturers own manuals for connection details.
Note: Horner produces application notes explaining the connection to each of the different automated
equipment manufactures. These application notes are ongoing, see your installation CD for any released
documentation.

CH. 6: COMMUNICATIONS

6.5

06 Apr 2000

PAGE 33
GFK-1819

RS-485 Two-Wire

TIU110/100
AE
R S422/485
RS232

R S 4 22 /48 5
(2 -w ire )

Tx+
TxRx+
RxTxD
0V
RxD

Tx/R x+
Tx/R x-

2
3
4
5
6
7
8

COM

0.1uF C e ra m ic

TIU050/101/102/103/111/112/113/20X
AE
RS422/485
RS232

R S 4 22 /48 5
(2 -w ire )

Tx+
TxRx+
RxTxD
0V
RxD

1
2
3
4
5
6
7

Tx/R x+
Tx/R x-

COM

0.1uF C e ra m ic

Figure 6.3 – RS-485 Two-Wire

PAGE 34
GFK-1819

6.6

06 Apr 2000

CH. 6: COMMUNICATIONS

Current Loop

The following diagram shows the connection to a device with an active 20mA current loop. The current
loop on the TIU100/110 is passive. Either the PLC must provide the 20mA source or an external current
source must be supplied.

20m A Loop

2 0m A L o op

T+
TR+
R-

9
10
11
12

+

ST

SR

-

Figure 6.4 – Current Loop
Note: Current Loop is not a standard option on the TIU100/110. Current loop must be ordered
specifically or can be re-fit into a standard unit. Contact a Horner Electric dealer for more information.
Note: Current Loop is not an option with the TIU050/101/102/103/111/112/113/20X.

CH. 7: GETTING STARTED

06 Apr 2000

PAGE 35
GFK-1819

CHAPTER 7: GETTING STARTED
7.1
Self-Test
Power up the unit with the UP and ENTER keys pressed at the same time. The unit enters a self-test
mode. The self-test consists of the following four checks:
7.1.1

Contrast Band

This test allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN
key and press Enter when done. Do the same for the upper limit.

WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a
setting where the display may appear blank. It is recommended that the factory setting are used
(Min 8A, Max FE).
7.1.2 Display Test
The display test continuously blinks all pixels on (black) to off. Look for any pixels stuck on or off. Exit
this test by pressing and holding any key for approximately two seconds.
7.1.3

Keyboard Test

As each key is pressed, an indication *** appears above that key. In the case of units with a numeric
keypad, press the key and a message appears indicating the key press. Check for keys indicating
multiple presses or not reporting presses. Exit this test by pressing and holding any key for
approximately two seconds.
7.1.4 RAM Test
Test either segment 0000 or segment 1000 (on the TIU100/110) of the RAM. The segment 1000 test
performs a base 3 repeating test. This test detects shorted address lines and damaged memory bits.
The segment 0000 test performs a Read-Modify-Write test on each byte of RAM, detecting damaged
memory bits. Exit this test by selecting DONE.
7.1.5 Serial Loop-back Tests
Tests the PC port and the Serial Port in each of it’s three modes for serial loop-back. Pre-made plugs are
required to link the pins of a particular port. This takes the following form:

Port Tested
PC (J2)
RS-232 (J3)
RS-422/485 (J3)

Table 7.1 Loop-back Test Plugs
Product
Type of Connector
TIU100/110
Pin male D link connector
TIU100/110
13-pin phoenix connection
TIU100/110
13-pin phoenix connection

Current Loop

TIU100/110

PC

13-pin phoenix connection

Pins to Short
pin 2 to pin 3
pin 6 to pin 8
pin 2 to pin 4 and pin 3
to pin 5.
pin 1 to 9, pin 10 to 11
and pin 12 to 7
pin 2 to pin 3

TIU050/101/102/1 Pin male D link connector
03/112/113/20X
RS-232
TIU050/101/102/1 8-pin phoenix connection
Pin 5 to pin 7
03/112/113/20X
RS-422/485
TIU050/101/102/1 8-pin phoenix connection
Pin 1 to pin 3, Pin 2 to
03/112/113/20X
pin 4
NOTE: current loop in not installed on standard models, as such a standard model will fail the
current loop-back test. Current Loop is not an option on the TIU050/20X.
After starting the test, the OK counter begins to count up. Exit this test by selecting DONE.

PAGE 36
GFK-1819

06 Apr 2000

CH. 7: GETTING STARTED

7.2
Updating the Protocol
When the software is installed the user decides where the main CBREEZE folder resides. During
installation the following folders are created: -

In the protocol directory 3 folders are created, TIU0xx, TIU1xx and TIU2xx. The protocol files for the
different terminal is loaded into these folders. The protocol files for the TIU050 are loaded into Tiu0xx, the
protocol files for the TIU10X are loaded into Tiu10x and the protocol files for the TIU20X are loaded into
Tiu20x.
The name of the protocol file is broken up into three section, the protocol, the main software revsion and
the terminal type that protocol file is for.
Protocol Name

_

Software Revision

.

Terminal Type

Example
snp_R4.1xx
This is the protocol file for release 4 software for the GE FANUC PLC, for the TIU10X
df1_R4.2xx
This is the protocol file for release 4 software for Allen Brabley PLC, for the TIU20X
To Update Protocol File
1. Set Terminal Type
2. Set the required Automation Equipment in Communications Settings
3. Select Update TIU Protocol from the File menu.
4. Select the folder of the terminal you have connected to the PC. The correct file will appear for the
terminal type selected and the Automation Equipment selected. Select that file and click OK.
5. A status bar appears indicating download progress.
6. After the transfer, the TIU050/10X/11X/20X resets itself. The correct PLC type is displayed on the
TIU050/10X/11X/20X.
7. Next, the project loaded runs.
7.3
1.
2.
3.
4.

Updating the Operating System
Select Update Operating System from the File menu.
Choose the updated file with the “BIN” extension. Click OK.
A status bar appears indicating download progress.
During the download process, TIU050/10X/11X/20X displays the message “SYSTEM SHUTDOWN”.

CH. 8: NETWORKS

06 Apr 2000

PAGE 37
GFK-1819

CHAPTER 8 : NETWORKS
8.1
Scope
This chapter gives a brief introduction into the networking hardware available on the Operator Station
range. The part numbers of the various options are available in the Introduction Chapter of this manual.
For information on programming the various network options see GFK-1818, User Manual for the
CBREEZE Software.
8.2
Controller Area Network (CAN) Overview
The controller area network (or CAN bus) is a serial communications bus that was originally developed in
the late 1980’s by a German company (Robert Bosch) for use in the automotive industry. CAN is an ISO
(International Standards Organisation) - defined serial communications bus for real-time applications.
Established in 1947, the International Standards Organisation (ISO) is a multinational body dedicated to
worldwide agreement on international standards. Specifically, CAN is documented in ISO 11898 (for
high-speed applications) and ISO 11519 (for lower-speed applications).
8.2.1 CAN Features
CAN-based open automation technology successfully competes on the market of distributed automation
systems because of the special features of the CAN protocol. The special features are CAN’s producerconsumer-oriented (or peer-to-peer) principle of data transmission and its multi-master capability. The
general design of CAN originally specified a high bit rate, high immunity to electrical interference and an
ability to detect any errors produced. CAN networks have the following general attributes:
•
•
•
•

Automatic error detection
Easily configurable
Cost-effective to design and implement
Capable of operating in harsh environments

8.3
CsCAN Network Overview
The CsCAN Network was first developed in 1993 by Horner Electric. It was developed for use in a project
that Horner Electric completed for the United States Post Office. Horner Electric developed its own
network, because it needed a network that had a specific set of powerful peer-to-peer and host-to-node
capabilities. The CsCAN Network has a “pass-through” feature whereby PC-based programs access
other nodes connected to a network by passing the programming command through the serial port to the
network port. (For a more detailed description, see below.) Horner Electric found that by developing its
own network, it satisfied several important needs. Horner Electric continues CsCAN Network
development to satisfy the requirements of today and the requirements of the future.
8.3.1 CsCAN Network Features
The CsCAN Network is based on CAN, which has many desirable features such as ruggedness, ease of
configuration, etc. With Horner Electric Controllers, data is passed at 125Kbps using a differential pair of
wires plus a ground. It is important to note that the data rate is not limited to 125Kbps. The maximum
data rate is 1Mbps (limited by the speed of light). The CAN implementation in the CsCAN controller
allows up to 64 controllers to be networked with no additional hardware and up to 253 controllers with
three CAN repeaters.
For the programmer, little knowledge of networking procedures is needed. However for troubleshooting
and optimizing, the following information is helpful. Instead of using master/slave or token passing, the
hardware self-arbitrates based on the Network ID. Controllers with lower Network ID numbers are
given a higher priority than controllers with higher Network ID numbers.
8.3.2 CsCAN Network Operation
When a controller needs to send data over the network, it first waits for the network to be idle (currently a
maximum of 900uS). If two controllers start broadcasting information on the network at the same time, the

PAGE 38
GFK-1819

06 Apr 2000

CH. 8: NETWORKS

"self-arbitration" causes the controller with the greater Network ID number to cease broadcasting without
affecting the message-in-progress of the other controller.
In applications with a large number of networked controllers, better results may be achieved by assigning
lower Network IDs to controllers that have more critical network data than other controllers. By assigning
higher Network IDs to controllers that provide numerous network updates, the controllers are prevented
from monopolising the bus time.
Each controller is capable of broadcasting Global Digital Output bits (%QG) and Global Analog Output
bits (%AQG), which are periodically broadcasted to the other controllers on the network. The coil
representations %QG and %AQG may be used in CBREEZE like any other coil or internal register
reference.
All digital global outputs are broadcast to the network each time one of them has a state change. In
addition, if a controller has not transmitted its global data for specific time period, the controller's
programmable network timer may expire, which in turn results in a global data broadcast. Finally, as part
of its power-up initialisation sequence, another controller can explicitly request a controller to broadcast
its global data.
8.4
DeviceNet Overview
DeviceNet is an open network. The specification and the protocol are open. Vendors are not required to
purchase hardware, software or licensing rights to connect devices to a system.
8.4.1 DeviceNet Features
DeviceNet is a low-cost communications link to connect industrial devices. It allows the interchangeability
of simple devices while making interconnectivity of more complex devices possible. DeviceNet is based
on CAN. It is an application layer protocol (ISO layer 7) and is defined in terms of an abstract object
model, which represents the available communication services and the external visible behaviour of a
DeviceNet node.
The DeviceNet Model is application independent. DeviceNet provides the communication services
needed by various types of applications. Many of today's lower level industrial control devices must retain
their low cost/low resource characteristics even when directly connected to a network. DeviceNet takes
this into consideration by defining a specific instance of the DeviceNet Model for communications typically
seen in a Master/Slave application. This is referred to as the Predefined Master/Slave Connection Set.
Some of the features and functionality of the DeviceNet network are described Table 8.1.

Network Size
Network Length

Table 8.1 - DeviceNet Features and Functionality
Up to 64 Nodes
Selectable end-to end network distance varies with speed
Baud Rate

Data Packets
Bus Topology
Bus Addressing
System
Features

Distance

125 Kbps
500m (1,640 feet)
250 Kbps
250m (820 feet)
500 Kbps
100m (328 feet)
0-8 bytes
Linear (trunkline/dropline); power and signal on the same network cable
Peer-to-Peer with Multi-Cast (one-to-many); Multi-Master and Master/Slave
special case; polled or change-of-state (exception-based)
Removal and replacement of devices from the network under power

CH. 8: NETWORKS

06 Apr 2000

PAGE 39
GFK-1819

8.4.2 DeviceNet Protocol
Some of the communication protocol features of DeviceNet consist of the following:
1. A DeviceNet product can behave as a Client, a Server or both.
2. Master/Slave operation.
3. Capable of Peer-to-Peer exchange capability exists in which any DeviceNet product can produce and
consume messages.
4. Capable of supporting 64 node addresses
5. Each node can support an unlimited number of I/O.
8.4.3 DeviceNet Operation
The following restrictions are placed on operations when using an OS that is configured as a
DeviceNet slave.
1. Currently, communication between the PC and the controller is only possible to the device physically
connected to the PCs’ serial port. Project downloads, uploads, monitoring, and configuration cannot
currently take place over a DeviceNet network.
2. The HE200CGM40x gateway card can not currently be used with DeviceNet communications.
Horner Electric is providing a special Gateway device that is based on the OCS hardware. The
Gateway device makes it possible to connect the PC serial port with the DeviceNet network.
3. DeviceNet network nodes are in a range from 0 to 63. The controller is able to observe network
responses (polled connections) from any slave to the DeviceNet Master. The first 16-words of these
observed responses are made available for mapping on the Network Input Assignments page.
These correspond to the available nodes 0 to 63 and registers AQG1 to AQG16. Node 64 is used for
a special case. When data is sent to a controller from a DeviceNet Master (via the polled connection)
this data is mapped to node 64. Relative addressing is limited to -64 to +64.

PAGE 40
GFK-1819

CH. 8: NETWORKS

VC N_L
S H IEL D
C N_H
V+

VC N_L
S H IEL D
C N_H
V+

VC N_L
S H IEL D
C N_H
V+

CAN Wiring Rules
VC N_L
S H IEL D
C N_H
V+

8.5

06 Apr 2000

121Ω

121Ω

+
1 2 -2 5 V D C

BLK
BLU
W HT
RED
S H IE LD

VCN_L
S H IE L D
CN_H
V+
BLK
BLU
12 1 Ω
W HT
RED

BLK
BLU
W HT
RED

VCN_L
S H IE L D
CN_H
V+

VCN_L
S H IE L D
CN_H
V+

S H IE L D
CN_H
V+

BLK
BLU
1 2 1Ω
W HT
RED
S H IE LD

VCN_L

-

S H IE LD

+

1 2 -2 5 V D C

Figure 8.3 – CAN Network Cabling
1. Wire the CAN network in a daisy-chained fashion such that there are exactly two physical end-points
on the network.
2. The two nodes at the physical end-points need to have 121 ohm 1% terminating resistors connected
across the CN_L and CN_H terminals.
3. Use data conductors (CN_L and CN_H) that are 24 AWG shielded twisted pair for “thin cable” and 22
AWG shielded twisted pair for “thick cable”. They must also have 120-ohm characteristic impedance.
In typical industrial environments, use a Belden wire #3084A (“thin”). Use #3082A (“thick”) for
environments where noise is a concern.
4. Use power conductors (V- and V+) that are 18 AWG twisted-pair for “thin cable” and 15 AWG twistedpair for “thick cable”.
5. Connect the V- power conductor to a good earth ground at one place only on the network, preferably
physical endpoints.
6. For a section of cable between two nodes, the cable shield is connected to the cable shield input at
one end of the cable only.
7. A CAN network (without repeaters) is limited to 64 nodes (with 63 cable segments) with a maximum
cable length of 1500 ft.
8. Up to four CAN network segments, which adhere to the above rules, may be connected together
using three CAN repeaters. In this manner, a CAN network may be extended to 253 nodes with a
total cable distance of 6000 ft.

CH. 8: NETWORKS

06 Apr 2000

PAGE 41
GFK-1819

8.6
Profibus
Profibus utilises a Master-Slave type of communication with the TIUXX2 functioning as a slave device.
Decentralised Peripherals (Slave) Baud rates of up to 12 MBd can be obtained through Profibus.
Up to 32 devices 9master or slaves) can be connected in one segment without using repeaters, or up to
64 devices can be connected using repeaters.
Master devices are used to determine the data communication on the bus. One master can service
several slaves. Several Masters can participate on the bus simultaneously, but only one Master can write
outputs to a slave.
The slave devices are peripheral devices. Slaves do not have bus access rights and can only
acknowledge received messages or send messages to the master when requested to do so. Any master
can read data from the slave devices. All connected Slaves have the same priority.
For further information on the Profibus Network, visit their website at www.profibus.com
8.6.1 Profibus Wiring
The TIUXX2 uses a 9 pin D-sub plug connector for its Profibus port. The pin assignment of the plug
connector and the wiring are show below.

Sta tion 1

Sta tion 2

R x d/T xD -P 3

3

V+ 6

6

D G nd 5

5

R x D /T xD -N 8

8

P rotective G rou nd
Figure 8.4 Profibus Port Pinout

PAGE 42
GFK-1819

06 Apr 2000

CH. 8: NETWORKS

R x D / T x D -P 3
V+ 6

DGND 5
R x D /T xD -N 8

R x D / T x D -P 3
V+ 6

DGND 5
R x D /T xD -N 8

R x D / T x D -P 3

V+ 6
DGND 5
R x D /T xD -N 8

Figure 8.5 – Profibus Network Cabling
Its is necessary to terminate both ends of the network. Both terminations must have power to them to
insure proper operation of the network. The following diagram illustrates the correct connection for the
termination resistors.

V P (6 )
L in e t e rm in at io n

3 90 O h m

A -L in e (3 )

2 20 O h m

B -L in e (8 )
3 90 O h m
G N D (5 )
Figure 8.6 – Profibus termination resistors

CH. 9: SMARTSTACK

06 Apr 2000

PAGE 43
GFK-1819

CHAPTER 9: SMARTSTACK 
9.1
Scope
Horner has now added the SmartStack modules from the OCS Range to the TIU20X range. The
SmartStack system is a method of allowing I/O expansion on an HMI. A wide range of modules is
available including Digital and Analogue.
9.2
Installing and Removing a SmartStack Module
The following section describes how to install and remove a SmartStack Module.
Caution: To function properly and avoid possible damage, do not install more than four
Smart Stack Modules per TIU20X.
9.2.1

Installing SmartStack Modules

1. Hook the tabs. Each SmartStack Module has two tabs that fit into slots located on the TIU20X. (The
slots on the TIU20X are located on the back cover.)
2. Press the SmartStack Module into the “locked” position, making sure to align the SmartStack Module
fasteners with the SmartStack receptacles on the TIU20X.
9.2.2

Removing SmartStack Modules

1. Using a Flathead screwdriver, pry up the end of the SmartStack Module (opposite of tabs) and swing
the module out.
2. Lift out the tabs of the module.

Figure 9.1 – Installing a SmartStack Module in an OCS.

PAGE 44
GFK-1819

06 Apr 2000

NOTES

CH. 9: SMARTSTACK



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : Yes
Create Date                     : 2000:06:06 09:28:05
Producer                        : Acrobat Distiller 4.0 for Windows
Modify Date                     : 2000:06:06 09:28:09-05:00
Page Count                      : 43
EXIF Metadata provided by EXIF.tools

Navigation menu